modern rules for an old practice - vaisala · 2017-08-23 · 10/15/2013 1 modern rules for an old...
TRANSCRIPT
10/15/2013
1
Modern Rules for an Old Practice:
Sensor Placement for GMP Temperature Mapping
Paul DanielSenior Regulatory Compliance ExpertVaisala, Inc
Page 2 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�Review Mapping Regulations.
�Discuss 5 Rules for Sensor Placement.
�Review Current Guidance on Sensor Placement.
Goals
10/15/2013
2
Page 3 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Page 4 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� Health Canada
– GUI-0069 – Guidelines for Temperature Control of Drug Products during Storage and Transportation
� ISPE
– Good Practice Guide: Cold Chain Management
Recent History
10/15/2013
3
Page 5 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� PDA
– Technical Report 58 – Risk Management for Temperature Controlled Distribution
� CDSCO (India)
– Draft Guidelines on Good Distribution Practice for Biological Products
Recent History
Page 6 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� CFDA (China)
– Good Supply Practices for Pharmaceutical Products
� EMA (Europe)
– (2013/C 68/01) Good Distribution Practice of Medicinal Products for Human Use
� USP 36
– Chapter <1079> Good Storage and Distribution Practices for Drug Products
Recent History
10/15/2013
4
Page 7 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�The regulations don’t tell us how to map, or even to map.
�Regulatory Summary
1. Determine if environmental parameters affect product quality.
2. Do stability testing to determine appropriate storage specifications.
3. Ensure that storage spaces are controlled to meet specifications.
�Mapping and monitoring is industry GMP response to #3.
�Therefore, regulations aren’t very helpful for sensor placement!
Regulations and Mapping
Page 8 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�Tradition and Precedence
� What has been done at your facility before?
�Equipment
� What equipment do you already have?
�Science
� What makes sense based on scientific principles?
� Guidance
Resources for Sensor Placement
10/15/2013
5
Page 9 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT
SIDE
Page 10 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
5 Rules
Map the Extremes.
Map in 3 Dimensions.
For Large Spaces, Map Storage Only.
Identify and Address Variables
If it’s worth mapping, its worth monitoring.
10/15/2013
6
Page 11 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 1: Map the Extremes.
�Geometric
� Place sensors at each end of the storage area.
�Conditions
� Apply validation principle of worst cases.
Page 12 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Parts of a Cube
Corner – 3 planes
Edge – 2 planes
Side – 1 plane
Space – 0 planes
10/15/2013
7
Page 13 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Parts of a Cube
Corner – 3 planes
Space – 0 planes
Rule 1: Map the Extremes
Page 14 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Corollary 1A: If ≤ 2m3, use 9 + 1.
TOP
FRONT
SIDE
10/15/2013
8
Page 15 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
9 spots = worst case?
�Air Flow:
� Corners have least air circulation.
� Center has most air circulation.
�Heat Exchange:
� Corners have the most exposure (3 planes)
� Center has the least exposure (0 planes)
Page 16 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
How many? Where? < 20m3
TOP
FRONT SIDE
10/15/2013
9
Page 17 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
How many? Where? < 20m3
TOP
FRONT
SIDE
Page 18 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
How many? Where? < 20m3
TOP
FRONT
SIDE
10/15/2013
10
Page 19 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
How many? Where? < 20m3
TOP
FRONT
SIDE
Page 20 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
How many? Where? < 20m3TOP
FRONT
SIDE
10/15/2013
11
Page 21 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Corollary 1B: If ≤ 20m3, use 15 +1.
TOP
FRONT
SIDE
Page 22 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� ISPE Good Practice Guide: Cold Chain Management (2011)
Guidance describes 9 +1 and 15 +1
10/15/2013
12
Page 23 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 2: Map in 3 Dimensions.
3 planes.
Left to right.
Page 24 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 2: Map in 3 Dimensions.
3 planes.
Top to bottom.
10/15/2013
13
Page 25 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 2: Map in 3 Dimensions.
3 planes.
Front to back.
Page 26 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Corollary 2A: If ≥ 20m3, use Stacks of 3.
High
Middle
Low
10/15/2013
14
Page 27 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
Page 28 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
10/15/2013
15
Page 29 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
Page 30 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
10/15/2013
16
Page 31 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
Page 32 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Corollary 2A: If ≥ 20m3, use Stacks of 3.
High
Middle
Low
10/15/2013
17
Page 33 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Corollary 2B: Remove sensors if possible.
�Remove “extra” sensors.
� 15 +1 diagram.
� With “Stacks of 3, in 3-D”, it would have 27 sensors.
Page 34 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
10/15/2013
18
Page 35 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Stacks of 3, in 3 dimensions.
Page 36 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
“Completing a three-dimensional temperature profile shouldbe achieved by measuring points at not less than three
dimensional planes in each direction/axis—top-to-bottom, left-to-right, front-to-back…”
USP 36 Chapter <1079> Good Storage and Distribution
Practices for Drug Products (2013)
More published support....
10/15/2013
19
Page 37 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 3: If ≥ 20m3, map storage only.
�As the space gets larger, it is not necessary to map hallways and access areas.
�Map only the shelves and areas
where product is actually stored.
�Requires controls to prevent storage in wrong areas.
� SOPs
� Training
� Signs
Page 38 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
“Completing a three-dimensional temperature profile shouldbe achieved by measuring points at not less than three
dimensional planes in each direction/axis—top-to-bottom, left-to-right, front-to-back, where product will be present.”
USP 36 Chapter <1079> Good Storage and Distribution
Practices for Drug Products (2013)
More published support....
10/15/2013
20
Page 39 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�Rule 1 – Map the Extremes
� Corollary 1A – If ≤ 2m3, use 9+1.
� Corollary 1B – If ≤ 20m3, use 15+1
Rule Summary (so far…)
Page 40 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�Rule 1 – Map the Extremes
� Corollary 1A – If ≤ 2m3, use 9+1.
� Corollary 1B – If ≤ 20m3, use 15+1
�Rule 2 - Map in 3 Dimensions
� Corollary 2A – If ≤ 20m3, use Stacks of 3
� Corollary 2B – Remove Sensors if Possible
Rule Summary (so far…)
10/15/2013
21
Page 41 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�Rule 1 – Map the Extremes
� Corollary 1A – If ≤ 2m3, use 9+1.
� Corollary 1B – If ≤ 20m3, use 15+1
�Rule 2 - Map in 3 Dimensions
� Corollary 2A – If ≤ 20m3, use Stacks of 3
� Corollary 2B – Remove Sensors if Possible
�Rule 3 - If ≥ 20m3, map storage only.
Rule Summary (so far…)
Page 42 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� “…additional points may be needed depending on airflow sources/characteristics, shelving (storage locations), external
temperature sources, and previous experience with similar units and their thermal behavior.”
– ISPE Good Practice Guide: Cold Chain Management (2011)
It’s just guidance. It’s a place to start.
10/15/2013
22
Page 43 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
�The following factors should be considered during temperature mapping of storage locations:
� Size of the space
� HVAC Locations
� Sun-facing walls
� Low ceilings or roofs
� Geography
� Airflow
� Outside temperature variability
� Weekly workflow variation
� Equipment movement
� Storage patterns of product
� Equipment capabilities
� SOPs.
More from USP 36 Chapter <1079>...
Page 44 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 4: Identify Variables
�Volume
�Temperature ∆
�Height
�Exterior Walls
�Construction Materials
�Doors and Windows
�Lighting
�Gradients
�HVAC Vents and Returns
�Air Circulation
�Control Sensors
�Energy Sources
�Racks and Shelving
�Traffic Patterns
�Human Factors
10/15/2013
23
Page 45 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Volume
Page 46 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Temperature ∆
10/15/2013
24
Page 47 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Height
Page 48 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Exterior Walls
10/15/2013
25
Page 49 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Construction Materials
Page 50 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Doors and Windows
10/15/2013
26
Page 51 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Lighting
Page 52 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Gradients
10/15/2013
27
Page 53 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
HVAC Vents and Returns
Page 54 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Air Circulation
10/15/2013
28
Page 55 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Control Sensors
Page 56 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Energy Sources
10/15/2013
29
Page 57 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Racks, Shelves, and Product
Page 58 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Traffic Patterns
10/15/2013
30
Page 59 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Human Factors
Page 60 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 4: Identify Variables
�Place sensors near representative variables!
�Adjust ideal “grid” to intersect
variables.
10/15/2013
31
Page 61 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
Page 62 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
10/15/2013
32
Page 63 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
Page 64 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
10/15/2013
33
Page 65 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
Page 66 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (X)
Distance Between Points
10/15/2013
34
Page 67 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (X)
Distance Between Points
Page 68 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (1/2X)
Distance Between Points
10/15/2013
35
Page 69 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (1/2X)
Distance Between Points
Page 70 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (1/4X)
Distance Between Points
10/15/2013
36
Page 71 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (1/8X)
Distance Between Points
Page 72 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Tem
pera
ture
Distance (1/16X)
Distance Between Points
10/15/2013
37
Page 73 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
TOP
FRONT (South Wall)
SIDE
Page 74 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Rule 5: If it is worth mapping…It is worth monitoring.
�Find the hot and cold spots and monitor them.
�Select the right monitoring solution.
�Validate the monitoring system.
10/15/2013
38
Page 75 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
“Temperature monitoring… documents the temperatures during the qualification and operation. It allows conclusions on
whether the product is stored and shipped within the approved temperature range. Therefore, an appropriate temperature
monitoring strategy should be selected and qualified.”
PDA Technical Report No. 58: Risk Management for Temperature Controlled Distribution (2012)
Monitoring....
Page 76 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� Rule 1 – Map the Extremes
� Corollary 1A – If ≤ 2m3, use 9+1.
� Corollary 1B – If ≤ 20m3, use 15+1
� Rule 2 - Map in 3 Dimensions
� Corollary 2A – If ≤ 20m3, use Stacks of 3
� Corollary 2B – Remove Sensors if Possible
� Rule 3 - If ≥ 20m3, map storage only.
� Rule 4 – Identify Variables
� Rule 5 – If it is worth Mapping, it is worth Monitoring
Rule Summary
10/15/2013
39
Page 77 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� Its always best to measure air temperature.
� Worst case scenario provides best challenge.
“It is normal practice to use air temperature as the reference source for the stored [product]…” and is ‘the worst case representation of the stored product temperatures.”
-ISPE Good Practice Guide: Cold Chain Management (2011)
What about product temperature?
Page 78 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� The same concepts apply, but concerned with sources of moisture.
� Use the same number of sensors unless you have an expert who understands humidity theory.
“Where relative humidity is a critical factor, then humidity sensors could be located in the same locations – or fewer locations used with the impact of the temperature considered for other locations – as absolute humidity will be very similar throughout the space.”
-ISPE Good Practice Guide: Cold Chain Management (2011)
What about mapping humidity?
10/15/2013
40
Page 79 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
� Reviewed Mapping Regulations.
� Explored 5 Rules for Sensor Placement for Mapping Storage Areas.
� Reviewed Mapping Guidance.
Summary
Page 80 / 2013 / Sensor Placement for Validation Mapping – GxP Webinar / ©Vaisala
Paul DanielSenior Regulatory Compliance InstructorVaisala, Inc.
Email: [email protected]
Thanks for Attending!