ModularVariable SpeedAir Handlers

2TEE3F31A1000A 4TEE3F31B1000A2TEE3F37A1000A 4TEE3F37B1000A2TEE3F39A1000A 4TEE3F39A1000A2TEE3F40A1000A 4TEE3F40B1000A2TEE3F48A1000A 4TEE3F48A1000A2TEE3F49A1000A 4TEE3F49B1000A2TEE3F64A1000A 4TEE3F64A1000A2TEE3F65A1000A 4TEE3F65B1000A

PUB. NO. 22-1717-05

2 Pub. No. 22-1717-05© 2008 Trane

Optional Equipment

OPTIONAL EQUIPMENT FOR AIR HANDLERS (Check mark [✓✓✓✓✓] indicates accessories included).Plenum — Pedestal (2/4TEE3F37, 39, 40, 48, 49, 64, 65) ...................................................................................... TAYPLNM100 [ ]Sub-base For Downflow (2/4TEE3F31) .................................................................................................................. TAYBASE101 [ ]Sub-base For Downflow (2/4TEE3F37, 39, 48, 64) ................................................................................................ TAYBASE100 [ ]Sub-base For Downflow (2/4TEE3F40, 49, 65) ...................................................................................................... TAYBASE102 [ ]Evaporator Defrost Control Kit — Cooling Units (Low Ambient Cooling) .................................................................... AY28X079 [ ]Evaporator Defrost Control Kit — Heat Pumps (Low Ambient Cooling) ....................................................................... AY28X084 [ ]Knockout cover plate (2/4TEE3F31, 37, 40, 49, 65) .................................................................................................. BAY99X123 [ ]Humidistat ............................................................................................................................................................... BAYSTAT253 [ ]

Featuresand Benefits

• Ships vertical - converts to horizontalby laying unit on side.

• Six-way convertibility – horizontal (left& right), front & rear access; upflow,downflow

• Electrical, refrigerant, condensate &blower access convertible to eitherside

• Compact 21" depth for easy installation

• Variable speed ECM motor• 3.5, 4, and 5 ton models available in

26” widths or with VorticaTM in 23.5”widths

• Direct drive blower

• Comfort-R™ enhanced dehumidifica-tion cycle

• Soft Start - On cycle fan speed is in-creased gradually to reduce soundand drafts

• Corrosion resistant galvanized metalwith attractive finish

• Expansion valve refrigerant control

• Check valve for heat pump application

• Internally enhanced finned coil tubing

• External brazed refrigerant connec-tions

• Filter rack with standard size filter

• 200/230 volt primary & 24 voltsecondary transformer

• Low voltage terminal board

• Uses 1400 series heaters

• Access to heater circuit breakers

• Polarized plugs for making motor andtransformer electrical connections fromair handler control box to electric heat-ers

• Primary and secondary drain connec-tions

• Easy Air-TiteTM

access to coils

• Built-in indoor fan delay function for in-creased efficiency

• 2/4TEE3F31 airflow selectable for1-1/2 — 3 ton O.D. unit

• 2/4TEE3F37, 39, 40 airflow selectablefor 2 — 3-1/2 ton O.D. unit

• 2/4TEE3F48, 49 airflow selectable for3 — 5 ton O.D. unit

• 2/4TEE3F64, 65 airflow selectable for3 — 5 ton O.D. unit

• Energy-saving continuous fan

• Enhanced cooling/heating control

Pub. No. 22-1717-05 3

Contents

Features and Benefits 2Optional Equipment 2

“Air-Tite™” Features and Benefits 4

General Data 52TEE3F31A1000A 4TEE3F31B1000A 52TEE3F37A1000A 4TEE3F37B1000A 52TEE3F39A1000A 4TEE3F39A1000A 52TEE3F40A1000A 4TEE3F40B1000A 52TEE3F48A1000A 4TEE3F48A1000A 52TEE3F49A1000A 4TEE3F49B1000A 62TEE3F64A1000A 4TEE3F64A1000A 62TEE3F65A1000A 4TEE3F65B1000A 6

Performance Data 7

Electrical Data 20

Field Wiring 21

Convertibility 22

Dimensions 23

Mechanical Specification Options 26

4 Pub. No. 22-1717-05

“Air-Tite™”Features and Benefits

1 New Duct Flange – Allows flush fit for 3/4", 1" or 11/2" ductinsulation.

2 Liner/Flange Seal – Exclusive Duct Flange Thermal Break/Seal and double wall construction to reduce cabinet loss andsweating.

3 1" Foil Faced Insulation – Thicker foil faced insulation forreduced cabinet loss, sweating and lower power bills.

4 Enclosed Control Box – Totally enclosed control box withtransformer inside to improve component life, unit durabilityand reliability.

5 Corrosion Resistant Screws – Exclusive “Weatherguard™”coated screws to maintain the quality appearance of the unitfor the life of the product.

6 Coupling Panel Insulation – Exclusive “No Burn”refrigerant coupling panel with thicker insulation for reducedheat loss.

7 Filter Door Seal – Improved door seal for reduced airinfiltration, heat transfer, and lower power bills.

8 New Filter Door – “Filter” is stamped on the panel, andincludes two captive screws with easy grip knobs.

9 Insulation on Center Bar – Exclusive center bar insulationfor reduced cabinet loss, sweating and lower power bills.

0 Door Gasket – Exclusive formed gasket (similar to a cardoor gasket) to reduce air infiltration and heat transfer andlower power bills.

q Air-Tite™ Circuit Breaker Door – Easy access to breakerswith positive air seal.

The SEER test for system efficiency places the air handler in theambient return air stream (80°F). If your air handler is to be in anunconditioned/severe climatic location you should consider theadvantages of the “Air-Tite™” model air handler.

Pub. No. 22-1717-05 5

MODEL

RATED VOLTS/PH/HZ.RATINGS 1

INDOOR COIL — TypeRows — F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2

INDOOR FAN — TypeDiameter-Width (In.)No. UsedDrive - No. SpeedsCFM vs. in. w.g. 1No. Motors — H.P.Motor Speed R.P.M.Volts/Ph/HzF.L. Amps - L.R. AmpsFILTERVertical ApplicationsFilter Furnished?Type RecommendedNo.-Size-ThicknessHorizontal ApplicationsFilter Furnished?Recommended SizeREFRIGERANTRef. Line ConnectionsConn. Size — in. GasConn. Size — in. Liq.DIMENSIONSCrated (In.)UncratedWEIGHT

GeneralData

MODEL

RATED VOLTS/PH/HZ.RATINGS 1

INDOOR COIL — TypeRows — F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2

INDOOR FAN — TypeDiameter-Width (In.)No. UsedDrive - No. SpeedsCFM vs. in. w.g. 1No. Motors — H.P.Motor Speed R.P.M.Volts/Ph/HzF.L. Amps - L.R. AmpsFILTERVertical ApplicationsFilter Furnished?Type RecommendedNo.-Size-ThicknessHorizontal ApplicationsFilter Furnished?Recommended SizeREFRIGERANTRef. Line ConnectionsConn. Size — in. GasConn. Size — in. Liq.DIMENSIONSCrated (In.)UncratedWEIGHT

2TEE3F31A1000A4TEE3F31B1000A

200-230/1/60See O.D. Specifications

Plate Fin3 — 14

3.213/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal10 x 8

1Direct - 16

See Fan Performance Table1 — 1/2Variable

200-230/1/604.3

YesLow Velocity

1 - 20 X 20 - 1 in.

N oSee Note 34

R-22 R-410ABrazed Brazed

3/4 3/45/16 5/16

H x W x D44-1/2 x 24 x 23-1/2See Outline Drawing

134 / 118

2TEE3F37A1000A4TEE3F37B1000A

200-230/1/60See O.D. Specifications

Plate Fin3 — 14

3.93/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal10 x 10

1Direct - 16

See Fan Performance Table1 — 1/2Variable

200-230/1/604.3

YesLow Velocity

1 - 20 X 20 - 1 in.

NoSee Note 34

R-22 R-410ABrazed Brazed

7/8 3/43/8 3/8

H x W x D47-7/8 x 26 x 23-1/2See Outline Drawing

142 / 127

2TEE3F39A1000A4TEE3F39A1000A

200-230/1/60See O.D. Specifications

Plate Fin3 — 14

5.043/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal11 x 10

1Direct - 16

See Fan Performance Table1 — 1/2Variable

200-230/1/604.3

YesThrowaway

1 - 20 X 20 - 1 in.

N oSee Note 34

R-22 R-410ABrazed Brazed

7/8 3/43/8 3/8

H x W x D59-1/2 x 26 x 23-1/257-7/8 x 23-1/2 x 21

160 / 150

2TEE3F48A1000A4TEE3F48A1000A

200-230/1/60See O.D. Specifications

Plate Fin3 — 14

6.193/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal11 x 10

1Direct - 16

See Fan Performance Table1 — 3/4Variable

200-230/1/606.8

YesThrowaway

1 - 20 x 20 x 1 in.

N oSee Note 34

R-22 R-410ABrazed Brazed

1-1/8 7/8 3/8 3/8

H x W x D59-1/2 x 26 x 23-1/257-7/8 x 23-1/2 x 21

170/155

1 These Air Handlers are A.R.I. certified withvarious Split System Air Conditioners andHeat Pumps (ARI STANDARD 210/240).Refer to the Split System Outdoor UnitProduct Data Guides for performance data.

2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76)

3 Minimum filter size for horizontalapplications will be based on airflowselection and will be calculated as follows: Low Velocity Filter: Face area (Sq. Ft.) = CFM / 300 High Velocity Filter: Face area (Sq. Ft.) = CFM / 500

4 For customer ease of filter maintenance, it isrecommended that a properly sized, remotefilter and grille be installed for horizontalapplications. Airflow should not exceed theface value of the filter being used. Thefactory installed filter should then beremoved from the unit.

2TEE3F40A1000A4TEE3F40B1000A

200-230/1/60See O.D. Specifications

Plate Fin4 — 14

5.043/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal10 x 10

1Direct - 16

See Fan Performance Table1 — 1/2Variable

200-230/1/604.3

YesLow Velocity

1 - 20 X 25 - 1 in.

N oSee Note 34

R-22 R-410ABrazed Brazed

7/8 3/43/8 3/8

H x W x D54-1/2 x 28-1/2 x 23-1/2

See Outline Drawing174 / 155

6 Pub. No. 22-1717-05

MODEL

RATED VOLTS/PH/HZ.RATINGS 1

INDOOR COIL — TypeRows — F.P.I.Face Area (sq. ft.)Tube Size (in.)Refrigerant ControlDrain Conn. Size (in.) 2

INDOOR FAN — TypeDiameter-Width (In.)No. UsedDrive - No. SpeedsCFM vs. in. w.g. 1No. Motors — H.P.Motor Speed R.P.M.Volts/Ph/HzF.L. Amps - L.R. AmpsFILTERVertical ApplicationsFilter Furnished?Type RecommendedNo.-Size-ThicknessHorizontal ApplicationsFilter Furnished?Recommended SizeREFRIGERANTRef. Line ConnectionsConn. Size — in. GasConn. Size — in. Liq.DIMENSIONSCrated (In.)UncratedWEIGHT

2TEE3F49A1000A4TEE3F49B1000A

200-230/1/60See O.D. Specifications

Plate Fin4 — 14

6.193/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal10 x 10

1Direct - 16

See Fan Performance Table1 — 3/4Variable

200-230/1/606.8

YesThrowaway

1 - 20 x 25 x 1 in.

N oSee Note 34

R-22 R-410ABrazed Brazed

1-1/8 7/8 3/8 3/8

H x W x D60-7/6 x 28-1/2 x 23-1/2

See Outline Drawing188/173

2TEE3F64A1000A4TEE3F64A1000A

200-230/1/60See O.D. Specifications

Plate Fin3 — 14

6.193/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal11 x 10

1Direct - 16

See Fan Performance Table1 — 1

Variable200-230/1/60

7.0

YesLow Velocity

1 - 20 X 22 - 1 in.

NoSee Note 34

R-22 R-410ABrazed Brazed

1-1/8 7/8 3/8 3/8

H x W x D59-1/2 x 26 x 23-1/257-7/8 x 23-1/2 x 21

170 / 155

2TEE3F65A1000A4TEE3F65B1000A

200-230/1/60See O.D. Specifications

Plate Fin4 — 14

7.333/8 - Copper

TXV - NonBleed3/4 NPT

Centrifugal10 x 10

1Direct - 16

See Fan Performance Table1 — 1

Variable200-230/1/60

7.0

YesLow Velocity

1 - 20 X 25 - 1 in.

NoSee Note 34

R-22 R-410ABrazed Brazed

1-1/8 7/8 3/8 3/8

H x W x D65-78 x 28-1/2 x 23-1/2

See Outline Drawing218 / 196

1 These Air Handlers are A.R.I. certified with various Split System Air Conditioners and Heat Pumps(ARI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for perfor-mance data.

2 3/4" Male Plastic Pipe (Ref.: ASTM 1785-76)

3 Minimum filter size for horizontal applications will be based on airflow selection and will be calcu-lated as follows:

Low Velocity Filter: Face area (Sq. Ft.) = CFM / 300

High Velocity Filter: Face area (Sq. Ft.) = CFM / 5004 For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and

grille be installed for horizontal applications. Airflow should not exceed the face value of the filterbeing used. The factory installed filter should then be removed from the unit.

Pub. No. 22-1717-05 7

PerformanceData

2/4TEE3F31 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2TEE3F31A, 4TEE3F31B WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.2 0.3 0.5 0.7 0.9

1.5

Low350

CFM/tonON ON OFF ON

CFMWatts

56575

56085

55098

525135

495175

450200

Normal400

CFM/tonON ON OFF OFF

CFMWatts

64090

640110

640130

615155

570180

545200

High450

CFM/tonON ON ON OFF

CFMWatts

710110

710130

700140

685175

665190

630220

2

Low350

CFM/tonOFF ON OFF ON

CFMWatts

745120

740135

730150

710190

690215

665245

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

835145

840165

845190

840230

820265

795295

High450

CFM/tonOFF ON ON OFF

CFMWatts

940195

940220

940245

930285

915320

900350

2.5

Low350

CFM/tonON OFF OFF ON

CFMWatts

885170

890200

890230

890270

880300

860345

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1020235

1020255

1020275

1015320

1010370

995425

High450

CFM/tonON OFF ON OFF

CFMWatts

1130300

1130335

1130365

1130420

1125475

1115505

3.0

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1060270

1060300

1060320

1055360

1045405

1030460

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1220365

1220400

1220435

1220485

1200530

1030550

High450

CFM/tonOFF OFF ON OFF

CFMWatts

1370510

1370545

1370575

1295615

1200600

1030530

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

2TEE3F31A / 4TEE3F31B Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 700

Med -Lo OFF ON 1000

Med-Hi** ON OFF 1125

High OFF OFF 1350

8 Pub. No. 22-1717-05

PerformanceData

2/4TEE3F37 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2TEE3F37A, 4TEE3F37B WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2

Low350

CFM/tonON ON OFF ON

CFMWatts

70090

700115

700155

700190

660220

Normal400

CFM/tonON ON OFF OFF

CFMWatts

800110

800140

800180

770230

750260

High450

CFM/tonON ON ON OFF

CFMWatts

900130

900165

900220

900265

900310

2.5

Low350

CFM/tonOFF ON OFF ON

CFMWatts

880130

880165

880215

880265

880305

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1000165

1000215

1000270

1000315

880325

High450

CFM/tonOFF ON ON OFF

CFMWatts

1125225

1125285

1125330

1100380

900340

3

Low350

CFM/tonON OFF OFF ON

CFMWatts

1040170

1040230

1040280

1040330

1000325

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1160240

1160300

1160350

1100385

870335

High450

CFM/tonON OFF ON OFF

CFMWatts

1300325

1300365

1260425

1140410

950330

3.5

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1225295

1225330

1200385

1070390

890340

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1350365

1350420

1280455

1140415

940365

High450

CFM/tonOFF OFF ON OFF

CFMWatts

1400405

1400475

1300460

1150430

940375

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

2TEE3F37A / 4TEE3F37B Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 600

Med -Lo OFF ON 900

Med-Hi** ON OFF 1100

High OFF OFF 1400

Pub. No. 22-1717-05 9

2/4TEE3F39 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2/4TEE39A1 WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

2 tons

Low350

CFM/tonON ON OFF ON

CFMWatts

76269

739107

723153

679191

636231

Normal400

CFM/tonON ON OFF OFF

CFMWatts

84084

840126

832176

787228

742265

High450

CFM/tonON ON ON OFF

CFMWatts

935105

931151

921202

904255

869317

2.5 tons

Low350

CFM/tonOFF ON OFF ON

CFMWatts

90399

910145

897194

873249

839301

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1029129

1029178

1031236

1013294

986353

High450

CFM/tonOFF ON ON OFF

CFMWatts

1139165

1164226

1167288

1150350

1131409

3 tons

Low350

CFM/tonON OFF OFF ON

CFMWatts

1062137

1074195

1083256

1072316

1046375

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1224201

1248265

1237318

1208383

1196441

High450

CFM/tonON OFF ON OFF

CFMWatts

1380270

1377333

1363398

1355474

1368561

3.5 tons

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1243201

1260270

1248336

1222394

1216459

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1421293

1413357

1416434

1419519

1375577

High450

CFM/tonOFF OFF ON OFF

CFMWatts

1596409

1592493

1533536

1446546

1373579

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 600

Med -Lo OFF ON 900

Med-Hi** ON OFF 1100

High OFF OFF 1400

10 Pub. No. 22-1717-05

PerformanceData

2/4TEE3F40 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2TEE3F40A, 4TEE3F40B WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.2 0.3 0.5 0.7 0.9

2

Low350

CFM/tonON ON OFF ON

CFMWatts

74590

725105

700120

620150

595185

555225

Normal400

CFM/tonON ON OFF OFF

CFMWatts

825105

810120

790140

750190

710215

675250

High450

CFM/tonON ON ON OFF

CFMWatts

910135

910150

910166

875205

845275

770305

2.5

Low350

CFM/tonOFF ON OFF ON

CFMWatts

870125

865140

855160

820205

805255

750280

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1000165

1000185

1000205

980245

940290

890340

High450

CFM/tonOFF ON ON OFF

CFMWatts

1130210

1125235

1115255

1100305

1080350

1055400

3

Low350

CFM/tonON OFF OFF ON

CFMWatts

1075185

1070200

1060220

1025275

985315

945365

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1200235

1200260

1195290

1185355

1170440

1145475

High450

CFM/tonON OFF ON OFF

CFMWatts

1350300

1365345

1375380

1375440

1350495

1320550

3.5

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1215245

1215270

1210300

1205355

1190405

1160460

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1400345

1400395

1400435

1400485

1400530

1400575

High450

CFM/tonOFF OFF ON OFF

CFMWatts

1415355

1425390

1430435

1425495

1405545

1365595

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

2TEE3F40A / 4TEE3F31B Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 600

Med -Lo OFF ON 900

Med-Hi** ON OFF 1100

High OFF OFF 1400

Pub. No. 22-1717-05 11

2/4TEE3F48 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2/4TEE48A1 WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3 tons

Low350

CFM/tonON ON OFF ON

CFMWatts

1096162

1117219

1129278

1139339

1146405

Normal400

CFM/tonON ON OFF OFF

CFMWatts

1253224

1291297

1311366

1320437

1316496

High450

CFM/tonON ON ON OFF

CFMWatts

1435312

1465394

1471463

1447516

1487611

3.5 tons

Low350

CFM/tonOFF ON OFF ON

CFMWatts

1277233

1313308

1332381

1345447

1325513

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1482342

1512423

1517496

1500559

1533648

High450

CFM/tonOFF ON ON OFF

CFMWatts

1661462

1671541

1690632

1694713

1623727

4 tons

Low350

CFM/tonON OFF OFF ON

CFMWatts

1478336

1506421

1510495

1493552

1519645

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1678470

1691554

1711647

1719728

1642744

High450

CFM/tonON OFF ON OFF

CFMWatts

1870653

1907770

1896838

1798828

1739812

5 tons

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1628444

1641525

1660612

1673696

1641748

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1884652

1915775

1896846

1796821

1724830

High450

CFM/tonOFF OFF ON OFF

CFMWatts

1878653

1911775

1897845

1799822

1718823

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values

Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 800

Med -Lo OFF ON 1100

Med-Hi** ON OFF 1400

High OFF OFF 1700

12 Pub. No. 22-1717-05

PerformanceData

2/4TEE3F49 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2TEE3F49A, 4TEE3F49B WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 .02 0.3 0.5 0.7 0.9

3

Low350

CFM/tonON ON OFF ON

CFMWatts

1050168

1045192

1040217

1025265

1005313

1000362

Normal400

CFM/tonON ON OFF OFF

CFMWatts

1190215

1195245

1200274

1200333

1185392

1175451

High450

CFM/tonON ON ON OFF

CFMWatts

1355295

1360326

1370358

1365421

1345484

1325547

3.5

Low350

CFM/tonOFF ON OFF ON

CFMWatts

1200234

1205264

1215294

1210354

1205413

1185473

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1405326

1405366

1405402

1395462

1390505

1290532

High450

CFM/tonOFF ON ON OFF

CFMWatts

1580429

1570458

1560496

1555573

1550608

1390547

4

Low350

CFM/tonON OFF OFF ON

CFMWatts

1405326

1405366

1405402

1395462

1390505

1290532

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1600444

1595475

1585515

1590593

1555623

1390547

High450

CFM/tonON OFF ON OFF

CFMWatts

1775635

1780679

1785701

1740697

1600656

1450611

5

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1565427

1560458

1550497

1545577

1540609

1380539

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

1800652

1800693

1800714

1740703

1600651

1450621

High450

CFM/tonOFF OFF ON OFF

CFMWatts

2020808

1975801

1930790

1795760

1665715

1530658

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

2TEE3F49A / 4TEE3F49B Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 800

Med -Lo OFF ON 1100

Med-Hi** ON OFF 1400

High OFF OFF 1700

Pub. No. 22-1717-05 13

2/4TEE3F64 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2/4TEE64A1 WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.3 0.5 0.7 0.9

3 tons

Low350

CFM/tonON ON OFF ON

CFMWatts

1192191

1222256

1226315

1213370

1185420

Normal400

CFM/tonON ON OFF OFF

CFMWatts

1380269

1382329

1388396

1402472

1381531

High450

CFM/tonON ON ON OFF

CFMWatts

1532348

1564433

1580513

1583590

1591679

3.5 tons

Low350

CFM/tonOFF ON OFF ON

CFMWatts

1389272

1385332

1396400

1409473

1387532

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1605394

1630482

1643564

1636633

1636712

High450

CFM/tonOFF ON ON OFF

CFMWatts

1831563

1846651

1845731

1793769

1619692

4 tons

Low350

CFM/tonON OFF OFF ON

CFMWatts

1588385

1624477

1632555

1626626

1627701

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1862591

1879685

1869754

1783762

1622698

High450

CFM/tonON OFF ON OFF

CFMWatts

2081811

2052863

1956845

1827806

1699764

5 tons

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

2002729

2005816

1948841

1806787

1718786

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

2225978

2116945

2010913

1904879

1765841

High450

CFM/tonOFF OFF ON OFF

CFMWatts

22811061

21801025

2074985

1956941

1838901

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values

Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 900

Med -Lo OFF ON 1200

Med-Hi ON OFF 1500

High OFF OFF 1800

14 Pub. No. 22-1717-05

PerformanceData

4TEE3F65 AIRFLOW PERFORMANCE TABLE

AIRFLOW PERFORMANCE2TEE3F65A, 4TEE3F65B WITH WET COIL, FILTER, NO HEATER

OUTDOORUNIT SIZE

(TONS)

SpeedSettings

AIRFLOWSETTING

DIP SWITCH SETTING AirflowPower

EXTERNAL STATIC PRESSURE

SW 1 SW 2 SW 3 SW 4 0.1 0.2 0.3 0.5 0.7 0.9

3.0

Low350

CFM/tonON ON OFF ON

CFMWatts

1030135

1030160

1030185

1015235

1000285

975325

Normal400

CFM/tonON ON OFF OFF

CFMWatts

1170195

1170225

1170255

1170315

1170375

1170435

High450

CFM/tonON ON ON OFF

CFMWatts

1320255

1325295

1340330

1370405

1375480

1365545

3.5

Low350

CFM/tonOFF ON OFF ON

CFMWatts

1195210

1195240

1195320

1195340

1195385

1195440

Normal400

CFM/tonOFF ON OFF OFF

CFMWatts

1380290

1405345

1425390

1440450

1440515

1425580

High450

CFM/tonOFF ON ON OFF

CFMWatts

1620420

1620455

1630495

1645565

1625636

1590695

4.0

Low350

CFM/tonON OFF OFF ON

CFMWatts

1365265

1385315

1405365

1430450

1450505

1440575

Normal400

CFM/tonON OFF OFF OFF

CFMWatts

1630435

1640470

1650505

1650575

1640640

1620700

High450

CFM/tonON OFF ON OFF

CFMWatts

1860570

1860620

1860680

1860785

1850825

1710830

5.0

Low350

CFM/tonOFF OFF OFF ON

CFMWatts

1830530

1810565

1810605

1830730

1795790

1740805

Normal**

400CFM/ton

OFF OFF OFF OFFCFMWatts

2080800

2075855

2065895

2010925

1890905

1750870

High450

CFM/tonOFF OFF ON OFF

CFMWatts

22751015

22251005

2170995

2035955

1880900

1750840

NOTES: 1. ** Factory Setting 2. At continuous fan setting: Airflow values are approximately 50% of the listed values.

2TEE3F65A / 4TEE3F65B Airflow Performance with Auxiliary Heat

Airflow SettingsDip Switch Settings

Nominal AirflowSee Following Tables for

heater application:-Pressure Drop for

Electric Heaters-Minimum Heating

Airflow Heater Matrix(on unit nameplates)

Switch 7 Switch 8

Low ON ON 900

Med -Lo OFF ON 1200

Med-Hi** ON OFF 1500

High OFF OFF 1800

Pub. No. 22-1717-05 15

PerformanceData

2/4TEE3F31 WIRING DATA(Indoor Blower Motor Powered from Heater Circuit 1)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 5 15 - - - 5 15

BAYHTR1405 +++ 1/1 4.80 16400 20 30 30 3.60 12300 17.3 27 30

BAYHTR1408 +++ 1/1 7.68 26200 32 45 45 5.76 19700 27.7 40 40

BAYHTR1410 +++ 1/1 9.60 32800 40 55 60 7.20 24600 34.6 49 50

BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40

BAYHTR1415 BRK 2/1 15.36 52400 40/24 55*/30 60*/30 11.53 39300 34.6/20.8 49*/26 50*/30

BAYHTR3415 000 1/3 15.36 52400 38.2 52 60 11.53 39300 33.1 46 50

BAYHTR1419 BRK 2/1 19.2 65500 32/48 45*/60 45*/60 14.42 49200 27.7/41.6 40*/52 40*/60

NOTES:* Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps)+++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnectIMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEE3F37 WIRING DATA(Indoor Blower Motor Powered from Heater Circuit 1)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 5 15 - - - 5 15

BAYHTR1405 +++ 1/1 4.80 16400 20 30 30 3.60 12300 17.3 27 30

BAYHTR1408 +++ 1/1 7.68 26200 32 45 45 5.76 19700 27.7 40 40

BAYHTR1410 +++ 1/1 9.60 32800 40 55 60 7.20 24600 34.6 49 50

BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40

BAYHTR1415 BRK 2/1 15.36 52400 40/24 55*/30 60*/30 11.53 39300 34.6/20.8 49*/26 50*/30

BAYHTR3415 000 1/3 15.36 52400 38.2 52 60 11.53 39300 33.1 46 50

BAYHTR1419 BRK 2/1 19.2 65500 32/48 45*/60 45*/60 14.42 49200 27.7/41.6 40*/52 40*/60

NOTES:* Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps)+++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnectIMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEE39A1000A WIRING DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 5 15 - - - 5 15 BAYHTR1405 +++ 1/1 4.80 16400 20 30 30 3.60 12300 17.3 27 30 BAYHTR1408 +++ 1/1 7.68 26200 32 45 45 5.76 19700 27.7 40 40 BAYHTR1410 +++ 1/1 9.60 32800 40 55 60 7.20 24600 34.6 49 50 BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40 BAYHTR1415 BRK 2/1 15.36 52400 40/24 55*/30 60*/30 11.52 39300 34.6/20.8 49*/26 50*/30 BAYHTR3415 000 1/3 15.36 52400 38.2 52 60 11.52 39300 33.1 46 50

BAYHTR1419 BRK 2/1 19.20 65500 32/48 45*/60 45*/60 14.42 49200 27.7/41.6 40*/52 40*/60

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

Notes:1. See Product Data or

Air Handler Name-plate for approvedcombinations of AirHandlers and Heat-ers.

2. Heater model num-ber may have addi-tional suffix digits.

16 Pub. No. 22-1717-05

PerformanceData

Notes:1. See Product Data or

Air Handler Name-plate for approvedcombinations of AirHandlers and Heat-ers.

2. Heater model numbermay have additionalsuffix digits.

2/4TEE3F49 WIRING DATA CHECK DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 9 15 - - - 9 15

BAYHTR1405 +++ 1/1 4.80 16400 20 34 40 3.60 12300 17.3 30 30

BAYHTR1408 +++ 1/1 7.68 26200 32 49 50 5.76 19700 27.7 43 45

BAYHTR1410 +++ 1/1 9.60 32800 40 59 60 7.20 24600 34.6 52 60BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40BAYHTR1415 BRK 2/1 15.36 52400 40/24 59*/30 60*/30 11.53 39300 34.6/20.8 52*/26 60*/30BAYHTR3415 000 1/3 15.36 52400 38.2 55 60 11.53 39300 33.1 49 50

BAYHTR1419 BRK 2/1 19.2 65500 32/48 49*/60 50*/60 14.42 49200 27.7/41.6 43*/52 45*/60

BAYHTR1425 BRK 3/1 24.96 85200 44/40/20 55/59*/25 60/60*/25 18.73 63900 38.1/34.6/17.3 48/50*/22 50/60*/25

NOTES:* Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps)+++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnectIMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEE3F40 WIRING DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 5 15 - - - 5 15

BAYHTR1405 +++ 1/1 4.80 16400 20 30 30 3.60 12300 17.3 27 30

BAYHTR1408 +++ 1/1 7.68 26200 32 45 45 5.76 19700 27.7 40 40

BAYHTR1410 +++ 1/1 9.60 32800 40 55 60 7.20 24600 34.6 49 50 BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40 BAYHTR1415 BRK 2/1 15.36 52400 40/24 55*/30 60*/30 11.52 39300 34.6/20.8 49*/26 50*/30 BAYHTR3415 000 1/3 15.36 52400 38.2 52 60 11.52 39300 33.1 46 50

BAYHTR1419 BRK 2/1 19.2 65500 32/48 45*/60 45*/60 14.42 49200 27.7/41.6 40*/52 40*/60

BAYHTR1425 BRK 3/1 24.96 85200 44/40/20 55/55*/25 60/60*/25 18.73 63900 38.1/34.6/17.3 48/49*/22 50*/50/25 NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

2/4TEE3F48A1000A WIRING DATA CHECK DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heeter - - - - 9 15 - - - 9 15

BAYHTR1405 +++ 1/1 4.80 16400 20 34 35 3.60 12300 17.3 30 30

BAYHTR1408 +++ 1/1 7.68 26200 32 49 50 5.76 19700 27.7 43 45

BAYHTR1410 +++ 1/1 9.60 32800 40 59 60 7.20 24600 34.6 52 60 BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40 BAYHTR1415 BRK 2/1 15.36 52400 40/24 59*/30 60*/30 11.53 39300 34.6/20.8 52*/26 60*/30 BAYHTR3415 000 1/3 15.36 52400 38.2 55 60 11.53 39300 33.1 49 50

BAYHTR1419 BRK 2/1 19.20 65500 32/48 49*/60 50*/60 14.42 49200 27.7/41.6 43*/52 45*/60

BAYHTR1425 BRK 3/1 24.96 85200 44/40/20 55/59*/25 60/60*/25 18.73 63900 38.1/34.6/17.3 48/52*/22 50/60*/25

NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

Pub. No. 22-1717-05 17

AIR HANDLER ELECTRIC HEATER PRESSURE DROP

2/4TEE3F65 WIRING DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 9 15 - - - 9 15

BAYHTR1405 +++ 1/1 4.80 16400 20 34 35 3.60 12300 17.3 30 30

BAYHTR1408 +++ 1/1 7.68 26200 32 49 50 5.77 19700 27.7 43 45

BAYHTR1410 +++ 1/1 9.60 32800 40 59 60 7.20 24600 34.7 52 60BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40BAYHTR1415 BRK 2/1 15.36 52400 44/20 59*/30 60*/30 11.53 39300 38.2/17.3 52*/26 60*/30BAYHTR3415 000 1/3 15.36 52400 38.2 55 60 11.53 39300 33 49 50

BAYHTR1419 BRK 2/1 19.2 65500 32/48 49*/60 50*/60 14.42 49200 27.7/41.6 43*/52 45*/60

BAYHTR1425 BRK 3/1 24.96 85200 44/40/20 55/59*/25 60/60*/25 18.73 63900 38.1/34.6/17.3 48/50*/22 50/60*/25

NOTES:* Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps)+++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnectIMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

HEATER RACKSHEATER

MODEL NO.NO. OFRACKS

BAYHTR1405 1

BAYHTR1408 2

BAYHTR1/3410 2

BAYHTR1/3415 3

BAYHTR1419 4

BAYHTR1425 5

NUMBER OF RACKS NUMBER OF RACKS

AIRFLOWCFM

1 2 3 4 5 AIRFLOWCFM

1 2 3 4 5

AIR PRESSURE DROPINCHES W.G.

AIR PRESSURE DROPINCHES W.G.

600 0.01 0.02 0.02 1400 0.07 0.08 0.10 0.11 0.13

700 0.01 0.02 0.02 1500 0.08 0.09 0.11 0.13 0.15

800 0.02 0.03 0.03 0.04 1600 0.09 0.10 0.12 0.15 0.17

900 0.03 0.03 0.04 0.05 1700 0.10 0.11 0.14 0.17 0.19

1000 0.04 0.04 0.05 0.06 1800 0.11 0.13 0.16 0.19 0.21

1100 0.04 0.05 0.06 0.07 0.08 1900 0.13 0.15 0.18 0.21 0.23

1200 0.05 0.06 0.07 0.08 0.09 2000 0.14 0.17 0.20 0.23 0.26

1300 0.06 0.07 0.08 0.09 0.11

2/4TEE3F64A1000A WIRING DATA(Indoor Blower Motor Powered from Heater Circuit *)

HeaterModel No.

Numberof

Circuits/Phase

240 VOLT 208 VOLT

CapacityHeater

Amps perCircuit

240

MinimumCircuit

Ampacity240

MaximumOverloadProtection

240

Capacity HeaterAmps per

Circuit

MinimumCircuit

Ampacity

MaximumOverloadProtection

KW BTUH KW BTUH

No Heater - - - - 9 15 - - - 9 15 BAYHTR1405 +++ 1/1 4.80 16400 20 34 35 3.60 12300 17.3 30 30 BAYHTR1408 +++ 1/1 7.68 26200 32 49 50 5.77 19700 27.7 43 45 BAYHTR1410 +++ 1/1 9.60 32800 40 59 60 7.20 24600 34.6 52 60 BAYHTR3410 000 1/3 9.60 32800 34.6 43 45 7.20 24600 30 37 40 BAYHTR1415 BRK 2/1 15.36 52400 40/24 59*/30 60*/30 11.53 39300 34.6/20.8 52*/26 60*/30 BAYHTR3415 000 1/3 15.36 52400 38.2 55 60 11.53 39300 33.1 49 50 BAYHTR1419 BRK 2/1 19.2 65500 32/48 49*/60 50*/60 14.42 49200 27.7/41.6 43*/52 45*/60 BAYHTR1425 BRK 3/1 24.96 85200 44/40/20 55/59*/25 60/60*/25 18.73 63900 38.1/34.6/17.3 48/52*/22 50/60*/25 NOTES: * Circuit 1/Circuit 2 (Minimum Circuit Ampacity for Circuit 1 includes Blower Motor Amps) +++ = 000, BRK, PDC 000 = pigtails, BRK = contains circuit breakers, PDC = contains pull disconnect IMPORTANT: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local Electrical Codes.

Notes:1. See Product Data or

Air Handler Name-plate for approvedcombinations of AirHandlers and Heat-ers.

2. Heater model num-ber may have addi-tional suffix digits.

18 Pub. No. 22-1717-05

PerformanceData

2/4TEE3F MINIMUM HEATING AIRFLOW CFM HEATER MATRIX

MINIMUM AIRFLOWWITH AUXILIARY HEAT

HEATER MODEL NUMBER BAYHTR----

14054.80kw

14087.68kw

14103410

9.60kw

14153415

15.36kw

141919.20kw

142524.96kwMODEL

NUMBERAPPLICATION

NUMBER OF HEATER RACKS 1 2 2 3 4 5

2/4TEE3F31

A/C or Elec.Furnace

700 700 700 700 1000 N/A

Heat Pump 1000 1000 1000 1125 1350 N/A

2/4TEE3F37

A/C or Elec.Furnace

600 600 600 1000 1000 N/A

Heat Pump 700 900 900 1300 1350 N/A

2/4TEE3F39

A/C or Elec.Furnace

900 900 900 900 900 N/A

Heat Pump 900 900 900 1400** 1400** N/A

2/4TEE3F40

A/C or Elec.Furnace

600 600 600 1100 1100 1100

Heat Pump 1100 1100 1100 1400 1400 1400

2/4TEE3F48

A/C or Elec.Furnace

800 800 800 800^ 800^ 800^^

Heat Pump 800 800 800 800^ 800^ 800^^

2/4TEE3F49

A/C or Elec.Furnace

700 700 700 1400 1400 1400

Heat Pump 1400 1400 1400 1600 1600 1600

2/4TEE3F64

A/C or Elec.Furnace

900 900 900 900@ 900 900

Heat Pump 900 900 900 900@ 900 900

2/4TEE3F65

A/C or Elec.Furnace

900 900 900 1200 1200 1200

Heat Pump 1500* 1500* 1500* 1800 1800 1800

*For upflow position only, minimum setting is 1200 ** For horizontal right and downflow only, minimun setting is 1100CFM ^ 208V approved for upflow and horizontal right only ^^ Not qualified for downflow @ Not approved for horizontal left

Pub. No. 22-1717-05 19

AIR HANDLER SUBBASE

FLOOR OPENING - SIZE

MODEL NO. A B TAYBASE100 23-3/4 14-13/16

TAYBASE101 21-3/4 14-13/16

TAYBASE102 26-3/4 14-13/16

20 Pub. No. 22-1717-05

ElectricalData

WIRING DIAGRAM FOR VARIABLE SPEED AIR HANDLERS

Pub. No. 22-1717-05 21

FieldWiring

From Dwg. 21D800255 Rev. 0

From Dwg. 21D800254 Rev. 0

2/4TEE3F AIR HANDLERS WITH SINGLE SPEED COOLING

2/4TEE3F AIR HANDLERS WITH SINGLE SPEED HEAT PUMP

NOTES:1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.

2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE.

3. LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM.

4. USE COPPER CONDUCTORS ONLY.

5. POLARIZED PLUG SECTION PM-A IS ATTACHED TO HEATER CONTROL BOX. SECTION I-PF IS FACTORY WIRED INTO AIR HANDLER.

6. TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF SECOND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEATING ELEMENTS. IF SECOND (BH) CONTACTOR IS NOT USED, THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE.

7. CONNECTIONS TO "R", "BK", "O", AND "Y" MUST BE MADE AS SHOWN FOR PROPER OPERATION OF BLOWER WITH HUMIDISTAT IN COOLING.

D800254

NOTES:1. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES.

2. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE.

3. LOW VOLTAGE WIRING TO BE NO. 18 A.W.G. MINIMUM.

4. USE COPPER CONDUCTORS ONLY.

5. POLARIZED PLUG SECTION PM-A IS ATTACHED TO HEATER CONTROL BOX. SECTION I-PF IS FACTORY WIRED INTO AIR HANDLER.

6. TERMINAL W2 WILL HAVE INTERNAL CONNECTIONS ONLY IF SECOND CONTACTOR IS USED BY THE HEATER FOR CONTROLLING POWER TO ELECTRIC HEATING ELEMENTS. IF SECOND (BH) CONTACTOR IS NOT USED, THEN FIELD CONNECTIONS TO W2 CAN BE OMITTED AS APPROPRIATE.

7. IF ODT IS NOT USED, THEN CONNECT APPROPIATE JUMPER FROM W1 TO W2 ON LVTB.

8. IF OPTIONAL HUMIDISTAT IS USED, REMOVE JUMPER (R-BK) AND INSTALL HUMIDISTAT BETWEEN "R" AND "BK".

9. CONNECT IN THIS MANNER IF O. D. UNIT HAS "F" CONNECTION.

10. CONNECT W3 TO W2 ONLY IF USING HEATER WITH 3 HEATER STAGES.

D800255

22 Pub. No. 22-1717-05

2/4TEE3F31 Through 65Convertibility

SIX (6) WAY CONVERTIBILITY

Primary Condensate

Horizontal Drain pan

Refrigerant Connections

Coil Supports

Airflow

One Unit - 4 Applications(Conversions 1-4)

Airflow

Vertical Upflow (as shipped)

One-step Conversion Stand unit on end

Horizontal LeftRotate Coil

Airflow

Vertical Downflow One-step Conversion

from Horizontal left

AirflowAirflow

Airflow

Airflow

Airflow

Easy Conversion to Opposite side Access(Conversions 5 & 6)

1 Unit is shipped asHorizontal right

2 Pull coil out androtate the coil 180˚

Slide coil back in onsupports and roll unit180˚ (so primarycondensate is down)

3

Note connections and access are nowon back side of unit

4

Horizontal Right(as shipped)

6 CONVERSION APPLICATIONS1. Horizontal Right - (Front Access)2. Vertical Upflow3. Horizontal Left - (Front Access)4. Vertical Downflow5. Horizontal Right - (Rear Access)6. Horizontal Left - (Rear Access)

Pub. No. 22-1717-05 23

Dimensions

2/4TEE3F AIR HANDLER DIMENSIONAL DATA

From Dwg. B802150 Rev 1

Model No. H W

2/4TEE3F31 43.00 21.50

2/4TEE3F37 45.00 23.50

2/4TEE3F39 57.90 23.50

2/4TEE3F40 51.75 26.00

2/4TEE3F48 57.90 23.50

2/4TEE3F49 57.90 26.00

2/4TEE3F62 62.75 26.00

2/4TEE3F64 57.90 23.50

2/4TEE3F65 62.75 26.00

* FOR TWO PIECE CABINET ONLY.

2/4TEE3F39, 2/4TEE3F48,2/4TEE3F64 and 2/4TEE3F65are two piece cabinets

24 Pub. No. 22-1717-05

MO

DE

LN

O.

AB

CD

EF

GH

LF

LOW

CO

NT

RO

LG

AS

LIN

EB

RA

ZE

LIQ

LIN

EB

RA

ZE

2TE

E3F

31A

4TE

E3F

31B

4321

.519

.515

.57

3.65

5.77

3.62

1.89

N/A

TX

V /

NB

3/4

5/16

2TE

E3F

37A

4523

.521

.517

.57

4.65

6.77

7/8

3/8

2TE

E3F

40A

51.7

5

2624

18.3

3

5.90

8.02

3.21

1.48

2TE

E3F

49A

57.9

027

.12

1-1/

82T

EE

3F65

A62

.75

36.0

0

4TE

E3F

37B

4523

.521

.517

.57

4.65

6.77

3.62

1.89

N/A

3/4

4TE

E3F

40B

51.7

5

2624

18.3

3

5.90

8.02

3.21

1.48

4TE

E3F

49B

57.9

027

.12

1-1/

84T

EE

3F65

B62

.75

36.0

0

FIG

. 1F

IG. 2

MO

DE

L N

O.

JK

JK

2TE

E3F

31A

, 4T

EE

3F31

B

12.0

2

19.2

2

11.0

2

18.2

2

2TE

E3F

37A

, 4T

EE

3F37

B21

.22

20.2

2

2TE

E3F

40A

, 2T

EE

3F49

A.

2TE

E3F

65A

, 4T

EE

3F40

B,

4TE

E3F

49B

, 4T

EE

3F65

B23

.72

22.7

2

OU

TLIN

E D

RA

WIN

G F

OR

2/4

TEE

3F31

, 37,

40,

49,

65

Pub. No. 22-1717-05 25

MO

DE

LN

O.

AB

CD

EF

GH

LF

LOW

CO

NT

RO

LG

AS

LIN

EB

RA

ZE

LIQ

LIN

EB

RA

ZE

2TE

E3F

39

57.9

23.5

21.5

17.5

74.

656.

773.

621.

8931

.15

TX

V /

NB

7/8

3/8

2TE

E3F

481-

1/8

2TE

E3F

64

4TE

E3F

393/

4

4TE

E3F

487/

84T

EE

3F64

OU

TLIN

E D

RA

WIN

G F

OR

2/4

TEE

3F39

, 48,

64A

1000

A

Trane6200 Troup HighwayTyler, TX 75707www.trane.com

05/08

The manufacturer has a policy of continuous product and product data improvement and it reserves the rightto change design and specifications without notice.

MechanicalSpecification Options

Features and General InformationThese blower coil units are completely factoryassembled including coil, condensate drainpan, fan, motor, filters and controls in an insu-lated casing that can be applied in horizontalor vertical configuration. The “Air-Tite™”model has 4.2 “R” value insulation and addi-tional sealing systems. The 2/4TEE3F line ofair handlers provides exclusive compact sizecombined with 6-way convertibility in sizes upto 5 ton.

The 3.5, 4, and 5 ton TEE3F models areavailable in 26" widths or with VorticaTM

in 23.5" widths.

The unit ships in the vertical upflow configura-tion and converts to right-hand horizontalconfiguration just by laying the unit on its side.No tools required. Simple coil rotation pro-vides downflow and horizontal left applica-tions.

CasingThese models have a rugged galvanizedsheet metal and steel frame construction.The casing is painted with an enamel finish.The casing is insulated and provides knock-outs for electrical power and control wiring.

Refrigerant CircuitsThe 2/4TEE3F units have a single refrigerantcircuit. The refrigerant circuit is controlled bya factory installed non-bleed thermalexpansion valve (TXV).

CoilAluminum fin surface is mechanically bondedto 3/8-inch OD copper tubing. Coils are fac-tory pressure and leak tested.

FanThe blower housing is forward curved, dy-namically balanced with a variable speed di-rect drive fan motor. The fan motor is perma-nently lubricated.

ControlsLow voltage terminal board, fan contactor,and plug-in module for accessory electricheat control is included. 2/4TEE3F modelsalso have a check valve.

FiltersThe 2/4TEE3F31 through 2/4TEE3F65 havestandard size filters.

Electric HeatersHeaters for the 2/4TEE3F air handlers areavailable in a wide range of capacities andvoltages with various staging options, andplug-in control wiring. Heaters fit inside the in-ternal compartment.