modulation and current/voltage control of the grid converter marco liserre [email protected]...
TRANSCRIPT
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Modulation and current/voltage control of the grid converter
Marco Liserre
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Introduction Modulation and ac current control are the core of grid-connected converters
They are responsible of the safe operation of the converter and of the compliance with standards and grid codes
Ac voltage control is a standard solution in WT-system however can be adopted also in PV-system for reinforcing stability or offering ancillary services
Introduction Model of the grid converter Overview of modulation techniques Current control Voltage control
A glance at the lecture content
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
PI-based current control implemented in a synchronous frame is commonly used in three-phase converters
In single-phase converters the PI controller capability to track a sinusoidal reference is limited and Proportional Resonant (PR) can offer better performances
Modulation has an influence on design of the converter (dc voltage value), losses and EMC problems including leakage current
Introduction: modulation and current/voltage control
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
In Europe there is the standard IEC 61727 In US there is the recommendation IEEE 929 the recommendation IEEE 1547 is valid for all distributed resources technologies
with aggregate capacity of 10 MVA or less at the point of common coupling interconnected with electrical power systems at typical primary and/or secondary distribution voltages
All of them impose the following conditions regarding grid current harmonic content
The total THD of the grid current should not be higher than 5%
Introduction: harmonic limits for PV inverters
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
harmonic limit 5th 5-6 % 7th 3-4 % 11th 1.5-3 % 13th 1-2.5 %
In Europe the standard 61400-21 recommends to apply the standard 61000-3-6 valid for polluting loads requiring the current THD smaller than 6-8 % depending on the type of network.
in WT systems asynchronous and synchronous generators directly connected to the grid have no limitations respect to current harmonics
1
Nhi
hi i
II
in case of several WT systems
Introduction: harmonic limits for WT inverters
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Model of the grid converter
AD
dcv
oi R
+-
L eA
B
AD
AT
AT
BD
BD
BT
BT
di
C
CD
CD
CT
CT
n
ac voltage equation
22( ) ( ) ( ) ( )3 a b cp t p t p t p t
converter switching function
d ( ) 1( ) ( ) ( ) ( )
d dci t
Ri t e t p t v tt L
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Use of a synchronous frame
1 1 2 1 22
3 0 3 2 3 2
a
b
c
pp
pp
p
2 2cos cos cos
3 3
2 2sin sin sin
3 3
ad
bq
c
pp
pp
p
1
1
dc
dc
di tRi t e t p t v t
dt Ldi t
Ri t e t p t v tdt L
1
1
dq d d d dc
qd q q q dc
di ti t Ri t e t p t v t
dt Ldi t
i t Ri t e t p t v tdt L
-frame dq-frame
v
v
qv
dv
v
a
c
b
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Overview of modulation techniques
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Characteristic parameters of these strategies are: the ratio between amplitudes of modulating and carrier waves (called modulation index M) the ratio between frequencies of the same signals (called carrier index m)
These techniques differ for the modulating wave chosen with the goal to obtain a lower harmonic distortion, to shape the harmonic spectrum to guarantee a linear relation between fundamental output voltage and modulation index in a wider range
The space vector modulations are developed on the basis of the space vector representation of the converter ac side voltage
Modulation techniques
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
analogic or digital,
natural sampled or regular sampled
symmetric or asymmetric
Modulation techniques
1
2
Ao
d
V
V
4 .1 278
.1 0
00 .1 0
M for 15fm
.3 24
Linear
Over-modulation
Square-waveOptimization both for the
linearity and harmonic content
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
1
ˆAmplitude modulation ratio :
ˆ
Frequency modulation ratio :
control
tri
S
VM
V
fm
f
Output voltage averaged over one switching period:
ˆ;
2control d
Ao Ao control tritri
v VV v v V
V
Sinusoidal PWM (SPWM)
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
the fundamental frequency componentof the output voltage is given by:
11sin( ) 1.0
2d
Ao
Vv M t M
Assuming a sinusoidal control signal:
1ˆ sin( ),control controlv V t
1
ˆ 1.02d
Ao
VV M M
The inverter stays in its “linear range”while . 0,1M
The harmonics in the output voltage appear as sidebands of fS and its multiples
1hf jm k f
The hth harmonic corresponds to the kth sidebandof j times the frequency modulation ratio m.For even values of j only exist harmonics forodd values of k, and viceversa.
1 15
13 17 31293327
3525454743 494139 51
Sinusoidal PWM (SPWM)
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Bipolar and unipolar modulations
2dcV +
-
+
-2dcV
2C
1C
dcV
+
-
v t+ -
P
P
dcV
+
-
v t+ -
P
P
P
P
00 1
0cos2
sin2
14)(
mm
nn
cndc tntmnmMqJ
q
Vtv
10120 122cos1cos
2
18cos2)(
m ncn
dcdc tntmnmMmJ
m
VtMVtv
bipolar
unipolar
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
0 10 20 30 40-1.5
-1
-0.5
0
0.5
1
1.5
t [ms]
v ref, v
tri
vref
vtri
0 10 20 30 40-100
-50
0
50
100
v Ao [V
]
t [ms]
0 10 20 30 40-100
-50
0
50
100
v Bo [V
]
t [ms]
0 10 20 30 40-150
-100
-50
0
50
100
150
v AB [V
]
t [ms]
0 5 10 15 20 25 30 35 40 45 50 55 600
0.20.40.60.8
1
v Ao/V
d
h
0 10 20 30 40-1.5
-1
-0.5
0
0.5
1
1.5
t [ms]
v ref, v
tri
vref
vtri
0 10 20 30 40-100
-50
0
50
100
v Ao [V
]
t [ms]
0 10 20 30 40-100
-50
0
50
100
v Bo [V
]
t [ms]
0 10 20 30 40-150
-100
-50
0
50
100
150
v AB [V
]
t [ms]
0 5 10 15 20 25 30 35 40 45 50 55 600
0.20.40.60.8
1
v AB/V
d
h
Bipolar and unipolar modulations
Due to the unipolar PWM the odd carrier and associated sideband harmonics are completely cancelled leaving only odd sideband harmonics (2n-1) terms and even (2m) carrier groups
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Three-phase modulation techniques
0 10 20 30 40-1.5
-1
-0.5
0
0.5
1
1.5
t [ms]
v ref, v
tri
vref
vtri
0 10 20 30 40-100
-50
0
50
100
v Ao [V
]
t [ms]
0 10 20 30 40-100
-50
0
50
100
v An [V
]
t [ms]
0 10 20 30 40-100
-50
0
50
100
v on [V
]
t [ms]
0 10 20 30 40-150
-100
-50
0
50
100
150
v AB [V
]
t [ms]
0 10 20 30 40-150
-100
-50
0
50
100
150
E [V
]
t [ms]
0 10 20 30 40-20
-10
0
10
20
i o [A]
t [ms]
0 10 20 30 40-20
-10
0
10
20
i d [A]
t [ms]
The basic three-phase modulation is obtained applying a bipolar modulation to each of the three legs of the converter. The modulating signals have to be 120 deg displaced. The phase-to-phase voltages are three levels PWM signals that do not contain triple harmonics. If the carrier frequency is chosen as multiple of three, the harmonics at the carrier frequency and at its multiples are absent.
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Extending the linear range (m=1,1)
SPWM
SVM
64
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Three-phase continuous modulation techniques
0 /2 2/3 2
vdc
/2
0
-vdc
/2
0 /2 2/3 2
vdc
/2
0
-vdc
/2
0 /2 2/3 2
vdc
/2
0
-vdc
/2
onv
DCRv
ACRv
onv
DCRv
ACRv
onv
DCRv
ACRvTHIPWM1/6 THIPWM1/4 SVPWM
Maximum linear range Minimum current harmonics Maximum linear range and almost optimal current harmonics
Triple harmonic injection 1/6 Triple harmonic injection 1/4 Space vector - Triangular 1/4
Continuous modulations
sinusoidal PWM with Third Harmonic Injected –THIPWM. If the third harmonic has amplitude 25 % of the fundamental the minimum current harmonic content is achieved; if the third harmonic is 17 % of the fundamental the maximal linear range is obtained;
suboptimum modulation (subopt). A triangular signal is added to the modulating signal. In case the amplitude of the triangular signal is 25 % of the fundamental the modulation corresponds to the Space Vector Modulation (SVPWM) with symmetrical placement of zero vectors in sampling time.
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
0 /2 2/3 2
vdc
/2
0
-vdc
/2
0 /2 2/3 2
vdc
/2
0
-vdc
/2
onv
ACRv DPWM0=-/6
DCRv
onv
ACRv
DPWM1=0DCRv
0 /2 2/3 2
vdc
/2
0
-vdc
/2
onv
ACRv
DPWM2=/6DCRv
The discontinuous modulations formed by unmodulated 60 deg segments in order to decrease the switching losses
symmetrical flat top modulation, also called DPWM1;
asymmetrical shifted right flat top modulation, also called DPWM2;
asymmetrical shifted left flat top modulation, also called DPWM0.
Three-phase discontinuous modulation techniques
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Multilevel converters and modulation techniques
alternative phase opposition (APOD) where carriers in adjacent bands are phase shifted by 180 deg;
phase opposition disposition (POD), where the carriers above the reference zero point are out of phase with those below zero by 180 deg;
phase disposition (PD), where all the carriers are in phase across all bands.
Wind turbine systems: high power -> 5 MW Alstom converter
Photovoltaic systems: many dc-links for a transformerless solution
0V 0V0V
2dcV
2dcV
A B CDifferent possibilities:
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
ab
cd
dcV
i L
e
Cascaded inverter
v
dcV
1 1012
0
2122cos1cos2
14
cos)(
m n
N
iicn
dc
dc
mtntmnmMmJm
V
tMNVtv
( 1)i
i
N
, 1, 2,3...m kN k
Multilevel converters and modulation techniques
•carrier shifting
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Carrier shifting
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-1
0
1
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-1
0
1
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-100
0
100
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-100
0
100
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-200
0
200
h
0 10 20 30 40 50 600
0.5
1
h
A [
pu]
v ab [
V]
v cd [
V]
v ad [
V]
v ref,
Vtr
iv re
f, V
tri
t [s]
t [s]
t [s]
t [s]
t [s]
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
PD Modulation for NPC
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-1
0
1
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-101
t [s]
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-101
t [s]
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-2000
200
t [s]
0 10 20 30 40 50 600
0.5
1
h
A [p
u]V
an [V
]V
ref, V
tri
Vre
f, Vtr
iV
bn [V
]V
ab [V
]
0.02 0.025 0.03 0.035 0.04 0.045 0.05 0.055 0.06
-1
0
1
Best WTHD !
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Current Control
PWM current control methods
ON/OFF controllers Separated PWM
hysteresis Delta optimized
linear non-linear
fuzzypassivity
PI predictive resonant
dead-beatfeedforward
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Typically PI controllers are used for the current loop in grid inverters Technical optimum design (damping 0.707 overshoot 5%)
-
+- ++
gv
v gidG ( s ) fG ( s )PIG ( s )
i
+-
e
-1 -0.5 0 0.5 1
-1
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
10-1
100
101
102
103
104
-20
-15
-10
-5
0
Ma
gn
itud
e (
Db
)
100
101
102
103
104
-400
-300
-200
-100
0
Frequency (Hz)
Ph
ase
(D
eg
ree
)
( ) IPI P
KG s K
s
sTsG
sd 5.11
1)(
( ) 1( )
( )f
i sG s
v s R Ls
PI current control
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Shortcomings of PI controller
When the current controlled inverter is connected to the grid, the phase error results in
a power factor decrement and the limited disturbance rejection capability leads to the
need of grid feed-forward compensation. However the imperfect compensation action of the feed-forward control due to the
background distortion results in high harmonic distortion of the current and
consequently non-compliance with international power quality standards.
0 0.002 0.004 0.006 0.008 0.01 0.012 0.014 0.016 0.018 0.02-0.2
0
0.2
0.4
0.6
0.8
1
error (scaled)
reference
actual
time [s]
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04
-1.5
-1
-0.5
0
0.5
1
error
actual
reference
0.019 0.0192 0.0194 0.0196 0.0198 0.02 0.0202 0.0204 0.0206 0.0208 0.021
-0.25
-0.2
-0.15
-0.1
-0.05
0
0.05
0.1
0.15
0.2
0.023 0.0235 0.024 0.0245 0.025 0.0255 0.026 0.0265 0.027 0.0275
0.8
0.82
0.84
0.86
0.88
0.9
0.92
0.94
0.96
0.98
1
time [s]
steady-state magnitude and
phase error
limited disturbance
rejection capability
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
The current control can be performed on the
grid current or on the converter current
The voltage used for the dq-frame orientation could be measured after a dominant reactance
d
q
)(te
)(ti
qi di
0( )
0
ip
PI dqi
p
KK
sD sK
Ks
Use of a PI controller in a rotating frame
d
q
) ‘( te
)(te ) ‘( te
d
q
dt
diLtet'e g
g
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Use of a PI controller in a rotating frame
ip
KK
s
1
3
ga a gb b gc c
gab a gbc b gca c
P v i v i v i
Q v i v i v i
dcv
dcV
P
Q
i
v
P
Q+-
+-
+ -
di
qi
Q controller
P controller
dcV controller
PQ controller
+ -
PLLgv
gv
gv
fgV
je
gdv
gqv
*v
abc
je
i
i
di
qi
+-
di
di
gdv
+-
qi Current
controller
Currentcontroller
gqv
je
v
v
ip
KK
s
ip
KK
s
ip
KK
s
ip
KK
s
L
L
i αβ
abc
αβ
αβ
abc
• active and reactive
power control can be
achieved
• vdc control can be
achieved too
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Use of a PI controllers in a rotating frame in single-phase systems
ip
KK
s
dcv
dci
Qgdv
Qx
+ -
qi
dcV controller
PLLgv
gv
gv
fgV
je
gdv
gqv
ije
i
i
di
qi
+-
di
di
gdv
+-
qi Current
controller
Currentcontroller
gqv
je
v
v
MPPT
P
dcV
gqv
di
L
L
ip
KK
s
ip
KK
s
2je
2je
v
an independent Q control is
achieved
A phase delay block create the
virtual quadrature component that
allows to emulate a two-phase
system
the v component of the
command voltage is ignored for
the calculation of the duty-cycle
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Use of a PI controllers in two rotating frames
++
di
++
qi
PI
PI
i
i
v
v
++
di
++
qi
PI
PI
i
i
v
v
je je
je je
Under unbalanced conditions in order
to compensate the harmonics
generated by the inverse sequence
present in the grid voltage both the
positive- and negative-sequence
reference frames are required
Obviously using this approach,
double computational effort must be
devoted
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Dead-beat controller
The dead-beat controller belongs to the family of the predictive controllers
They are based on a common principle: to foresee the evolution of the controlled
quantity (the current) and on the basis of this prediction: to choose the state of the converter (ON-OFF predictive) or the average voltage produced by the converter (predictive with pulse width
modulator)
The starting point is to calculate its derivative to predict the effect of the control
action
The controller is developed on the basis of the model of the filter and of the grid,
which is used to predict the system dynamic behavior: the controller is inherently
sensitive to model and parameter mismatches
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Dead-beat controller
*i
i
sTONt
k 1k 2k
ONt
sT
The information on the model is used to decide the switching state of the
converter with the aim to minimize the possible commutations (ON-OFF
predictive) or the average voltage that the converter has to produce in order to null
it.
In case it is imposed that the error at the
end of the next sampling period is zero
the controller is defined as “dead-beat”. It
can be demonstrated that it is the fastest
current controller allowing nulling the
error after two sampling periods.
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Dead-beat controller
450 460 470 480 490 500 510 520 530 540 550-0.2
0
0.2
0.4
0.6
0.8
1
samples
450 460 470 480 490 500 510 520 530 540 550-0.2
0
0.2
0.4
0.6
0.8
1
samples
resp
on
se
resp
on
se
reference
actual
reference
actual
)1()1()1()(1
)1()1( kekekib
aki
bkvkv
)()1()(1
)1( kekekib
kvkv neglecting R !
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Dead-beat controller: limits
0.04 0.045 0.05 0.055 0.06-60
-50
-40
-30
-20
-10
0
10
20
time [s]
curr
ent
[A]
0.04 0.045 0.05 0.055 0.06-60
-50
-40
-30
-20
-10
0
10
20
time [s]
curr
ent
[A]
Pole-Zero Map
Real Axis
Imag
inar
y A
xis
-1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8 1
-1
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
0.8
1
0.90.80.70.60.50.40.30.20.1
/T
0.9/T
0.8/T
0.7/T
0.6/T0.5/T
0.4/T
0.3/T
0.2/T
0.1/T
/T
0.9/T
0.8/T
0.7/T
0.6/T0.5/T
0.4/T
0.3/T
0.2/T
0.1/T
0.04 0.045 0.05 0.055 0.06-60
-50
-40
-30
-20
-10
0
10
20
time [s]
curr
ent
[A]
due to PWM !
due to parameter error !
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Resonant control Resonant control is based on the use of Generalized Integrator (GI)
A double integrator achieves infinite gain at a certain frequency, called resonance frequency, and almost no attenuation outside this frequency
The GI will lead to zero stationary error and improved and selective disturbance rejection as compared with PI controller
101
102
103
-180
-90
0
90
180
Phase (
deg)
Bode Diagram
Frequency (Hz)
-200
-100
0
100
200
Magnitude (
dB
)
2 2
s
s
2 2
s
s GI
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Resonant control
101
102
103
0
200
400
600
800
Mag
nitu
de (
dB)
Frequency (Hz)
101
102
103
-100
-50
0
50
100
Pha
se (
deg)
Frequency (Hz)
101
102
103
0
20
40
60
80
Mag
nitu
de (
dB)
Frequency (Hz)
101
102
103
-100
-50
0
50
100
Pha
se (
deg)
Frequency (Hz)
22 2
2)(
ss
sKsG
c
ciAC
22
2)(
s
sKsG i
ACs
KsG i
DC )(
)(1)(
c
iDC s
KsG
)()()( jsGjsGsG DCDCAC The resonant controller can be obtained via a frequency shift
Bode plots of ideal and non-ideal PR with KP = 1, Ki = 20, = 314 rad/s c = 10 rad/s
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
-200
-100
0
100
200
300
400
Magnitude (
dB
)
101
102
103
-180
-90
0
90
180
Phase (
deg)
Bode Diagram
Frequency (Hz)
-100
0
100
200
300
400
Magnitude (
dB
)
Bode Diagram
Frequency (Hz)
101
102
103
-180
-90
0
90
180P
hase (
deg)
2 2P I
sk k
s
PM
The stability of the system should be taken into consideration
The phase margin (PM) decreases as the resonant frequency approach to the crossover frequency
2 2
1P I
sk k
R Lss
Resonant control
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Tuning of resonant control The gain Kp is founded by ensuring the desired bandwidth
The integral constant Ki acts to eliminate the steady-state phase error
A higher Ki will "catch" the reference faster but with higher overshoot
Another aspect is that Ki determines the bandwidth centered at the resonance frequency, in this case the grid frequency, where the attenuation is positive. Usually, the grid frequency is stiff and is only allowed to vary in a narrow range, typically ± 1%.
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05-6
-4
-2
0
2
4
650Hz response
Time (sec)
Am
plit
ud
e
2 2( )c P I
o
sG s K K
s
0 0.005 0.01 0.015 0.02 0.025 0.03 0.035 0.04 0.045 0.05-6
-4
-2
0
2
4
650Hz response
Time (sec)A
mp
litu
de
2 2( )c P I
o
sG s K K
s
Ki = 100 Ki = 500
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Discretization of generalized integrators
2 2
2
1
1
y s u s v sy s s su s s
v s y ss
2
y u
v
GI integrator decomposed in two simple integrators
1 1 1
21
( )k k s k k
k k s k
y y T u v
v v T y
*2 2
( ) Ii p
K su s s K
s
Forward integrator for direct path and backward for feedback path
The inverter voltage reference
1 1 1
*,
21
1
1
1
k k s I k s k
i k p k k
k k s k
k k
k k
k k
y y T K T v
u K y
v v T y
y y
v v
Difference equationsi i
*
i i
i i u i*
y u
v
k p
k I
2
a w
G f ( s )
Control diagram of PR implementation
max max
max max
,
,
y y y yaw
y y y y
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
2 20
2 20
0
( )
0
ip
PRi
p
K sK
sD s
K sK
s
Use of P+resonant controller in stationary frame
3
2
SVM
PLL
3
2
u
ix*
iy*
idd*
i*
iiy
ix
ux*
uy*
iy*
ix*
Kp
Kp
-
+
+
+
+
+
+
+
-
6
ej
2 2
Ki s
s
2 2
Ki s
s
ixd*
)(te
)(ti
The voltage used for reference generation could be measured after a dominant reactance
The current control can be performed on the grid current or on the converter current
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
PI vs PR for single-phase grid inverter current control
The current loop of PV inverter with PR controller
The current loop of PV inverter with PI controller
( ) IPI P
KG s K
s
2 2( )c P I
o
sG s K K
s
No grid voltage feed-forward is required
GIs tuned to the low harmonics can be used for selective harmonic compensation by cascading the fundamental component GI
2 2
2 2
( ) 1( )
( )
LCif
i fi res
s zi sG s
u s L s s
.
1
1)(
sd sT
sG
Plant
Inverter
PRPI
fgLC CL
z12
i
LCigres L
zLL 22
-
+-v i
dG ( s ) fG ( s )P RESG ( s )
i
+-
e
-
+- ++
gv
v gidG ( s ) fG ( s )PIG ( s )
i
+-
e
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
In the hypothesis
H11(s)=H22(s)=
H12(s)=H21(s)=0
s
KK i
p H11(s)
H12(s)
H21(s)
H22(s)
+
+
+
+
Vd(s)
Vq(s)
Ed(s)
Eq(s)
)()()(
)()()(
22
11
tethtv
tethtv
dd
From PI in a rotating-frame to P+res for each phase
20
220
20
20
20
20
20
20
220
20
20
20
20
20
20
2
).,(
)(2
3
2)(2
3
2
)(2
3
2)(2
3
2
)(2
3
2)(2
3
2
3
2)(
s
sKK
s
KsKK
s
KsKKs
KsKK
s
sKK
s
KsKKs
KsKK
s
KsKK
s
sKK
sG
ip
iipiip
iipip
iip
iipiipip
cbac
s
KK
s
KK
Gi
p
ip
qdc
0
0),(
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
)(
)(
10
01
)(
)(
0
01
)(
)(
tv
tv
ti
ti
R
R
Lti
ti
dt
d
c
a
c
a
c
a
z
z z
va
vb vc
)(
)(
)(
211
112
3
1
)(
)(
0
01
)(
)(
tv
tv
tv
ti
ti
R
R
Lti
ti
dt
d
c
b
a
c
a
c
a
0)()()( tvtvtv cba
20
220
20
20
20
20
20
20
220
20
20
20
20
20
20
2
).,(
)(2
3
2)(2
3
2
)(2
3
2)(2
3
2
)(2
3
2)(2
3
2
3
2)(
s
sKK
s
KsKK
s
KsKKs
KsKK
s
sKK
s
KsKKs
KsKK
s
KsKK
s
sKK
sG
ip
iipiip
iipip
iip
iipiipip
cbac
20
2
20
2
20
2
).,(1
00
00
00
)(
s
sKK
s
sKK
s
sKK
sG
ip
ip
ip
cbac
Linear controllers : from PI in a rotating-frame to P+res for each phase
each current is determined only by its voltage !
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Linear controllers : results (ideal grid conditions)
current error
current error
harmonic spectrum
harmonic spectrum
PI controller in a rotating frame
P+resonant controller for each phase
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Linear controllers: results (equivalence of PI in dq and P+res in )
PI controller in a rotating frame
P+resonant in stationary frame
triggering LCL-filter resonance
triggering LCL-filter resonance
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Ac voltage control When it is needed to control the ac voltage because the system should operate
in stand-alone mode, in a microgrid, or there are requirements on the voltage quality a multiloop control can be adopted
The ac capacitor voltage is controlled though the ac converter current.
The current controlled converter operates as a
current source to charge/discharge the
capacitor.
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Ac voltage control The repetitive controller ensures precise tracking of the selected harmonics and
it provides the reference of the PI current controller. Controlling the voltage Vc’ the PV shunt converter is improved with the function of voltage dips mitigation. In presence of a voltage dip the grid current Ig is forced by the controller to have a sinusoidal waveform which is phase shifted by almost 90° with respect to the corresponding grid voltage.
PV converter
Iload
Ic’
E Ig
PIRepetitive
control
Ic’
Vref+
- -
+
Iref
Vc’
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Conclusions
The PR uses Generalized Integrators (GI) that are double integrators achieving very high gain in a narrow frequency band centered on the resonant frequency and almost null outside.
This makes the PR controller to act as a notch filter at the resonance frequency and thus it can track a sinusoidal reference without having to increase the switching frequency or adopting a high gain, as it is the case for the classical PI controller.
PI adopted in a rotating frame achieves similar results, it is equivalent to the use of three PR’s one for each phase
Also single phase use of PI in a dq frame is feasible
Dead-beat controller can compensate current error in two samples but it is affected by PWM limits and parameters mismatches
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Bibliography1. D. G. Holmes and T. Lipo, Pulse Width Modulation for Power Converters, Principles and Practice. New York: IEEE Press, 2003.
2. M. Kazmierkowski, R. Krishnan, and F. Blaabjerg, Control in Power Electronics – Selected Problems. Academic Press, 2002.
3. X. Yuan, W. Merk, H. Stemmler, and J. Allmeling, “Stationary-frame generalized integrators for current control of active power filters with zero steady-state error for current harmonics of concern under unbalanced and distorted operating conditions,” IEEE Trans. on Industry Applications, vol. 38, no. 2, pp. 523–532, 2002.
4. D. Zmood and D. G. Holmes, “Stationary frame current regulation of PWM inverters with zero steady-state error,” IEEE Trans. on Power Electronics, vol. 18, no. 3, pp. 814–822, 2003.
5. M. Bojrup, P. Karlsson, M. Alaküla, L. Gertmar, ”A Multiple Rotating Integrator Controller for Active Filters”, Proc. of EPE 1999, CD-ROM.
6. R. Teodorescu, F. Blaabjerg, M. Liserre and A. Poh Chiang Loh, “Proportional-Resonant Controllers and Filters for Grid-Connected Voltage-Source Converters” IEE Proceedings on Electric Power Applications.
7. A. Timbus, M. Liserre, R. Teodorescu, P. Rodriguez, F. Blaabjerg, Evaluation of Current Controllers for Distributed Power Generation Systems, IEEE Transactions on Power Electronics, March 2009, vol. 24, no. 3, pp. 654-664.
8. R. A. Mastromauro, M. Liserre, A. Dell'Aquila, “Study of the Effects of Inductor Nonlinear Behavior on the Performance of Current Controllers for Single-Phase PV Grid Converters”, IEEE Transactions on Industrial Electronics, May 2008, vol. 55, no 5, pp. 2043 – 2052.
9. IEEE Std 1547-2003 "IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems", 2003.
10. IEEE Std 1547.1-2005 "IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distribut ed Resources with Electric Power Systems", 2005.
11. IEC Standard 61727, “Characteristic of the utility interface for photovoltaic (PV) systems,”, 2002.
12. IEC Standard 61400-21 “Wind turbine generator systems Part 21: measurements and assessment of power quality characteristics of grid connected wind turbines”, 2002.
13. IEC Standard 61000-4-7, “Electromagnetic Compatibility, General Guide on Harmonics and Interharmonics Measurements and Instrumentation”, 1997.
14. IEC Standard 61000-3-6, “Electromagnetic Compatibility, Assessment of Emission Limits for Distorting Loads in MV and HV Power Systems”, 1996.
Marco Liserre [email protected]
Modulation and current/voltage control of the grid converter
Acknowledgment
Part of the material is or was included in the present and/or past editions of the
“Industrial/Ph.D. Course in Power Electronics for Renewable Energy Systems – in theory and practice”
Speakers: R. Teodorescu, P. Rodriguez, M. Liserre, J. M. Guerrero,
Place: Aalborg University, Denmark
The course is held twice (May and November) every year