Electro-technical Symbols & Usage
2
CNS/GSS/2008/M2
2
Electro-technical Symbols
3
CNS/GSS/2008/M2
3
Electro-technical Symbols
4
CNS/GSS/2008/M2
4
Electro-technical Symbols Code Name of Function Definition
25 Synchro-Check Check before paralleling two parts of power system
26 Thermostat Protection against Overloads
27 Under-Voltage Protection of Voltage under sags
32P Directional active over power Protection against active over power transfer
32Q Directional reactive over power Protection against reactive over power transfer
37 Phase undercurrent 3-phase protection against undercurrent
46 Negative sequence/ unbalance Protection against unbalanced phase current
47 Negative sequence over voltage Negative sequence voltage protection
48-51LRExcessive starting time & locked rotor
Protection of motors against starting with overloads or reduced voltage, & for loads that can block
49 Thermal overload Protection against overloads
49T RTDs Protection against overheating of M/C windings
50 Instantaneous phase overcurrent 3-phase protection against short-circuits
50BF Breaker FailureChecking & protection if the CB fails to trip after a tripping order
50N/50G Instantaneous earth fault Protection against earth faults
5
CNS/GSS/2008/M2
5
Electro-technical Symbols Code Name of Function Definition
50V Inst. Voltage-restrained phase Over current3-Ph Protection against S/Cs with Voltage dependent threshold
51 Delayed Phase Over current3-Ph Protection against Overloads & short circuits
51N/51G Delayed earth fault Protection against earth faults
51V Delayed Voltage restrained phase O/C3-Ph protection against short circuits with voltage dependent threshold
59 Over voltage Protection against excessive voltage
59N Neutral voltage displacement Insulation fault protection
64REF Restricted earth fault differentialEarth fault protection for star connected 3-Ph wdgs with earthed neutral
64G 100% generator stator earth faultDetection of stator wdg insulation earth faults
81H/81L Over/Under frequencyProtection against abnormally High/Low frequency
87B Busbar differential3-Ph protection against busbar internal faults
87G Generator differential3-Ph protection against internal faults in AC generators
87M/87T Motor/Trafo. differential3-Ph protection against internal faults in Motors/Trafos.