Module B3

More on

Three Phase Analysis

Page 2: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

B3.2

Balanced Three Phase Circuits

Page 3: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Terminology:

• phase: the impedance or voltage source

element in the three-phase connection.

• phase current: current through the phase.

• phase voltage: voltage across the phase.

Notation:

Iϕ: phase current magnitude;

Vϕ: phase voltage magnitude;

Za

Zb Zc

Za

Zc

Zb

phase

Wye connected load Delta connected load

This notation will be used to ex-

press phase current phasor mag.

Page 4: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Terminology:

• line: one of the three conductors connecting

source to load.

• line current: current through a line.

• line voltage (or line-to-line voltage): voltage

between 2 of the 3 lines at a common point. Notation:

IL: line current magnitude;

VL: line voltage magnitude;

Za

Zb Zc

Za

Zc

Zb

line

Wye connected load Delta connected load

This notation will be used to

express line current phasor mag.

Page 5: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

WYE Connection (as shown in B3 notes)Lower and upper case subscripts correspond to the particular identified nodes.

They are used in this figure to be very explicit regarding each quantity.

However, it is more common to use only one or the other, as indicated in the

next slide.

aI

Page 6: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

WYE Connection

Same figure, but with more common nomenclature.

aI

aI

bI

bI

cI

cI

bnV

anV

cnV

Page 7: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

AN BN CNI I I I ,

AN BN CNV V V V

VAN

V0

VBN

V120

VCN

V 120

VAB

VAN

VBN

VV

120 3V

30

VBC

VBN

VCN

V 120 V

120 3V

90

VCA

VCN

VAN

V120 V

0 3V

150

WYE Connection

Page 8: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Wye connection:

Line-Line voltages are sqrt(3) times

phase voltages in magnitude

and lead them by 30 degrees in angle.

Y: Line-Line Voltages Lead: Y-LV-Lead

Line currents equal phase currents

Page 9: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

z

z

z

a

b

c

A

B C

IaA

IbB

IcC

IAB

IBC

ICAV

ab

Vbc

Vca

VAB

VBC

VCA

Delta Connection (as shown in B3 notes)

Page 10: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

z

z

z

a

b

c

A

B C

IaA

IbB

IcC

IAB

IBC

ICAV

ab

Vbc

Vca

VAB

VBC

VCA

Delta ConnectionSame figure, but with more common nomenclature.

abV

bcV

caV

aI

bI

cI

abI caI

bcI

Page 11: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

AB BC CAI I I I ,

AB BC CAV V V V

IAB

I0

IBC

I 120

ICA

I 120

0 120 3 30I I I I = I -IaA AB CA

120 0 3 150I I I I = I -IbB BC AB

120 120 3 90I I I I = I -IcC CA BC

Delta Connection

Page 12: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Delta connection:

Line-line voltages equal phase voltages

Line currents are sqrt(3) times

phase currents in magnitude

and lag them by 30 degrees in angle.

Delta: Line Currents Lag: Delta-LC-LAG

Page 13: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

cos3 IVP

cos3L

IL

VP

sin3 IVQ

sin3L

IL

VQ

S P jQ

S P2 Q2 3VLIL

Power relations for three phase circuits

•These formulae can be used

for Wye or Delta

• All quantities are magnitudes

• θ is the angle for which

phase voltage leads

phase current

• Positive Q is for power

flowing into L load

• Negative Q is for power

flowing “into” C load

• VL: line-to-line voltage magnitude

• IL: line current magnitude

• Iϕ: phase current magnitude;

• Vϕ: phase voltage magnitude;

Page 14: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Per-phase analysis of 3 phase circuits

• Convert all delta connections to Y

connections using

3

ZZY

• “Lift out” the a-phase to neutral circuit

• Perform single phase analysis using

phase quantities and per phase powers

• Multiply all powers by 3 to get solution

in terms of three phase powers.

(We can prove this via

application of a Y-Δ

transformation)

Page 15: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Three balanced three-phase loads are connected in

parallel. Load 1 is Y-connected with an impedance

of 150 + j50 ; load 2 is delta-connected with an impedance

of 900 + j600 ; and load 3 is 95.04 kVA at 0.6 pf leading.

The loads are fed from a distribution line with an

impedance of 3 + j24 . The magnitude of the line-to-neutral

voltage at the load end of the line is 4.8 kV.

a) Calculate the total complex power at the sending end

of the line.

b) What percent of the average power at the sending end

of the line is delivered to the load?

Example B3.2

Page 16: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Example B3.2

150+j50900+j600

95.04 kVA

at 0.6 pf

leading

4.8kV

a

b

c

n

4.8kV √3 ∟30°

150+j50

150+j50 900+j600

900+j600

Page 17: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Solution:

First thing to do is to obtain a per-phase circuit.

Load 1: Z1=150+j50

Load 2: Z2=(900+j600)/3=300+j200

Load 3: 95040(0.6 0.8)1 3

19,008 25,344

S j

j

, 4800an load V ∟0°

And we need a voltage.

What voltage do we take from the three-

phase circuit to use in the per-phase circuit?

Page 18: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Per phase equivalent circuit

19,008 25,344

1j

S

1I 2I3I

How do you compute the four currents?

Page 19: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Compute current from source

)(949.143725.45)(7046.118369.43

3

I 2

I 1

28.596.33846.70769.116.98.28

4800

344,25008,19

200300

4800

50150

4800

rmsArmsAj

I

jjj

j

jj

I

Page 20: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Compute losses in the transmission line

VAR 34.224,148)24(2)3725.45(32

3

W04.528,18)3(2)3725.45(32

3

Xeff

Iloss

Q

Reff

Iloss

P

23 28.8 9.6 (150) 414,720 W

12

3 28.8 9.6 (50) 138,240 VAR 1

P j

Q j

Compute power consumed by load 1.

Page 21: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Compute power consumed by load 3:

2311.0769 7.3846 (300) 159,507.02 W

22

311.0769 7.3846 (200) 106,338.02 VAR2

P j

Q j

VAR 032,76)8.0(040,953

W024,57)6.0(040,953

Q

P

Compute power consumed by load 2:

Page 22: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

end) (loadVA 546,168251,6313,

jtotalload

S

Add the powers to the three loads

Add in the losses to get sending end power:

VA 34.770,31604.649779

VA 34.224,14804.528,18546,168251,6313,

j

jjsending

S

We could have also obtained this from

3VI* (see the “check” in the text)

But which “V” to use?

Page 23: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

148.9710004.779,649

251,631delivered % P

Part b of the problem wants the percent

of the power from the sending end

that is actually delivered at the load.

This is a measure of efficiency.

Why is 100% of the power not delivered?

Page 24: Module B3 Three Phase Analysis - Iowa State Universityhome.engineering.iastate.edu/~jdm/ee303/B3.pdfThree balanced three-phase loads are connected in parallel. Load 1 is Y-connected

Wye-connections

Provides for two different voltages; loads may use the

line-to-neutral or line-to-line (e.g., 277/480 for industrial

loads);

Requires less number of turns in a transformer or

generator for the same line-to-line voltage.

Transformers may still operate if one phase is lost

(called an “open delta” connection)

Lower currents in windings and so winding ampacity

may be lower.

Third harmonics caused by nonlinear magnetizing

current in transformer circulates among windings but is

not passed through.

Delta-connections