PROJECT NUMBER: C:\Users\rob\Documents\213180_MC4_ARCH_v14_rob.rvt 21-3180 MOSAIC CENTRE FOR CONSCIOUS COMMUNITY AND COMMERCE ISSUED FOR REVIEW 2014 APRIL 11th STRUCTURAL MECHANICAL ELECTRICAL LANDSCAPE ARCHITECTURAL E000 SYMBOL SCHEDULE/LEGEND E100 ELECTRICAL SITE PLAN E200 MAIN FLOOR LIGHTING AND FIRE ALARM E201 SECOND FLOOR LIGHTING AND FIRE ALARM E202 THIRD FLOOR LIGHTING LIGHTING AND FIRE ALARM E203 ROOF LIGHTING AND FIRE ALARM E204 LIGHTING AND FIRE ALARM DETAILS E300 MAIN FLOOR POWER AND DATA E301 SECOND FLOOR POWER AND DATA E302 THIRD FLOOR POWER AND DATA E303 ROOF POWER AND DATA E304 POWER AND DATA DETAILS M100 MECHANICAL SITE PLAN M200 MECHANICAL FOUNDATION PLAN M201 MAIN FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN M202 SECOND FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN M203 THIRD FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN M301 MAIN FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN M302 SECOND FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN M303 THIRD FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN M400 MECHANICAL ROOM DETAILS M401 MECHANICAL WASHROOM DETAILS M500 MECHANICAL SCHEMATICS M501 MECHANICAL SCHEMATICS M600 MECHANICAL SCHEDULES CIVIL N/A C001 SITE SERVICING PLAN (C002 TO BE ISSUED UPON APPROVALS) CONSTRUCTION VOL. 3 APRIL 11th N/A N/A

Upload: others

Post on 20-Nov-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

PROJECT NUMBER:

C:\Users\rob\Documents\213180_MC4_ARCH_v14_rob.rvt

21-3180

MOSAIC CENTRE FORCONSCIOUS COMMUNITYAND COMMERCE

ISSUED FOR REVIEW

2014 APRIL 11th

STRUCTURAL MECHANICAL ELECTRICAL LANDSCAPEARCHITECTURAL

E000 SYMBOL SCHEDULE/LEGENDE100 ELECTRICAL SITE PLANE200 MAIN FLOOR LIGHTING AND FIRE ALARME201 SECOND FLOOR LIGHTING AND FIRE ALARME202 THIRD FLOOR LIGHTING LIGHTING AND FIRE ALARME203 ROOF LIGHTING AND FIRE ALARME204 LIGHTING AND FIRE ALARM DETAILSE300 MAIN FLOOR POWER AND DATAE301 SECOND FLOOR POWER AND DATAE302 THIRD FLOOR POWER AND DATAE303 ROOF POWER AND DATAE304 POWER AND DATA DETAILS

M100 MECHANICAL SITE PLANM200 MECHANICAL FOUNDATION PLANM201 MAIN FLOOR MECHANICAL PLUMBING,

HEATING AND COOLING PLANM202 SECOND FLOOR MECHANICAL PLUMBING,

HEATING AND COOLING PLANM203 THIRD FLOOR MECHANICAL PLUMBING,

HEATING AND COOLING PLANM301 MAIN FLOOR MECHANICAL VENTILATION

AND FIRE PROTECTION PLANM302 SECOND FLOOR MECHANICAL VENTILATION

AND FIRE PROTECTION PLANM303 THIRD FLOOR MECHANICAL VENTILATION

AND FIRE PROTECTION PLANM400 MECHANICAL ROOM DETAILSM401 MECHANICAL WASHROOM DETAILSM500 MECHANICAL SCHEMATICSM501 MECHANICAL SCHEMATICSM600 MECHANICAL SCHEDULES

CIVIL

N/A C001 SITE SERVICING PLAN

(C002 TO BE ISSUED UPON APPROVALS)

CONSTRUCTION VOL. 3

APRIL 11th

N/AN/A

NFHB

NFHB

NFHB

1

C

B

D

E

F

G

23

45

6

7

8

910

1112

13 1415 16

HJ

K

L

150 SANITARY SERVICE. SEE CIVIL SITE

SERVICING DRAWING COO1 FOR

CONTINUATION

FIRE DEPARTMENT CONNECTION BENEATH

OVERHANG BELOW

200 STORM SERVICE. SEE CIVIL

SITE SERVICING DRAWING C001

FOR CONTINUATION

ERV-1RD-1

RD-1

RD-2

RD-2

RD-1

RD-1

RD-1

RD-1

RD-1

RD-1DUAL CORE ENERGY RECOVERY VENTILATOR WITH

SERVICE CLEARANCE ON NORTH SIDE OF UNITTHERMALLY BROKEN ROOF DRAINS. REFER TO

ARCHITECTURAL FOR ROOF INSULATION SLOPE

AND ROOF DRAIN LOCATIONS

150 MUNICIPAL WATER SERVICE. SEE CIVIL SITE

SERVICING DRAWING C001 FOR CONTINUATION

EXISTING SITE FIRE HYDRANT

E/A&O/A

DUAL CORE ENERGY RECOVERY

VENTILATOR WITHIN

PENTHOUSE. REFER TO DWG5&

6/M400 FOR DETAIL

ROOFTOP NON FREEZE HOSE BIBB

12M400

BELOW GRADE 7,000GAL COMPOSITE

RAINWATER STORAGE TANK. COORDINATE

PLACMENT OF MANHOLE WITH LANDSCAPING

RWT-1

2M200

1190 MBH GAS SUPPLY TO BE

STUBBED OUT BELOW GROUND

ON WEST SIDE OF BUILDING

150 STORM SERVICE. SEE CIVIL DRAWINGS

FOR CONTINUATION

150 BUILDING STORM TO RAINWATER TANK

E/A&O/A

THERMALLY BROKEN PATIO ROOF DRAINS. REFER

TO ARCHITECTURAL FOR ROOF INSULATION SLOPE

AND ROOF DRAIN LOCATIONS

NFHB

P

PIPE DROP

PIPE RISE

ISOLATION VALVECHECK VALVE

DIRECTION OF FLOW

THREE WAY VALVE

SOLENOID/CONTROL VALVE

PRESSURE GAUGE

THERMOMETER

Y TYPE STRAINERUNION

PUMP

FLEX CONNECTION

BALANCING VALVE

HEATING WATER SUPPLYHEATING WATER RETURNCHILLED WATER SUPPLYCHILLED WATER RETURN

HWSHWR

CHWSCHWR

HEATING WATER SUPPLYHEATING WATER RETURNHEAT RECLAIM SUPPLYHEAT RECLAIM RETURN

GLSGLRHRSHRR

LIQUID HEAT TRANSFER

SYMBOL DESCRIPTION

PIPE FITTINGS

PIPE BOTTOM TAKE-OFFPIPE TOP TAKE-OFF

PIPE CAP

PIPE CONTINUATION

INSTRUMENT WELLNEEDLE VALVE/GAS COCK

SYMBOL DESCRIPTION

AUTOMATIC AIR VENT

MANUAL AIR VENTMAV

AAV

SUCTION DIFFUSER AND STRAINER

BACKFLOW PREVENTORBFP

REDUCED PRESSURE PRINCIPLEBACKFLOW PREVENTOR

RPPBFP

PIPE GUIDEPIPE ANCHOREXPANSION JOINT

DRAIN HOSE CONNECTIONQUICK CONNECT COUPLE

ROUND DUCT300Ø

RECTANGULAR DUCT300x200

SINGLE LINE DUCT300x200

DUCT DIMENSIONING

AIR DISTRIBUTIONS

ROUND DUCT

SUPPLY AIR

TURNING VANES

BALANCING DAMPER

BACKDRAFT DAMPER

BD

BDD

MOTORISED DAMPER

FIRE DAMPER

M

UPDN

RETURN AIR

EXHAUST AIR

FLEXIBLE DUCT

ACOUSTIC INSULATION

SUPPLY AIRS/ARETURN AIRR/AEXHAUST AIRE/AOUTSIDE AIRO/A

THERMOSTATT

HUMIDISTATH

FREEZE STATFz

CARBON MONOXIDE DETECTIONCO

FIRE WATER LINESPRINKLER LINESPRINKLER HEAD - PENDANT

SP

SPRINKLER

FW

SPRINKLER HEAD - UPRIGHT

SPRINKLER HEAD - SIDEWALL

DRYFLUSH

SANITARY ABOVE SLABBELOW SLAB

STORM ABOVE SLABBELOW SLAB

WEEPING TILE

SANSTSTWT

SANITARY VENTILATIONDOMESTIC COLD WATERDOMESTIC HOT WATERDOMESTIC HOT WATER RECIRC

VDCWDHWDWR

LIQUID HEAT TRANSFER

SAN

RECYCLED RAIN WATERLOW PRESSURE NATURAL GAS

RWNG

PRESSURE RELEIF VALVE

RADIANT PANEL SYMBOL

SIZECAPACITY

TYPE

IN-FLOOR HEATING SYMBOL

SPACINGLOOP LENGTH

LOOP NUMBER

PIPE SIZECAPACITY

PLUMBING FIXTURE TAG

__-__FIXTURENUMBER

FIXTURELETTER

WATER CLOSETWCLAVATORYLAVURINALURSINKSKDRINKING FOUNTAINDFMOP/JANITOR SINKMSSHOWERSH

EXHAUST FANEFFORCED FLOW UNITFFUNIT HEATERUHCABINET UNIT HEATERCUHFAN COILFCPUMPP

PLUMBING FIXTURE TAG

__-__EQUIPMENTNUMBER

EQUIPMENTLETTER

BOILERBHUMIDIFIERHUMHEAT EXCHANGERHERADIANT PANELRPTANKTK

SECTION LETTER

SECTION FLAG

DRAWING TO FIND SECTION

DETAIL NUMBER

DETAIL FLAG

DRAWING TO FIND DETAIL

TYPE ID.

KEYNOTE TAG_

REVISION NUMBER

REVISION NOTE TAG

_

AIR OUTLET TAG

SIZECAPACITY

TYPEQUANTITY @

SUPPLYSRETURNREXHAUSTETRANSFERTLOUVREL

AI

AO

VSD

PRESSURE REDUCING VALVETEST PORT

ANALOGUE INPUT TO BMS

CONTROLS

ANALOGUE OUTPUT FROM BMSDIGITAL INPUT TO BMSDIGITAL OUTPUT FROM BMS

DIDO

TEMPERATURE SENSORT

FREEZESTATFz

AQUASTATAq

SENSORS

VARIABLE SPEED DRIVE

LEGAL ADDRESSPLAN 072 9580BLOCK 1LOT 47

MUNICIPAL ADDRESSSAVARYN DRIVE + 91st STREET,SOUTH EDMONTON

GAS INFORMATION

DESCRIPTION

EQUIPMENT MBH m³/h

LOAD

440 12.4

KITCHEN WATER HEATER 150 4.23

TOTAL 1190 33.6

KITCHEN MAKE-UP AIR

KITCHEN EQUIPMENT 350 9.89

FUTURE 250 7.06

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

MECHANICAL SITE PLAN

M100

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 200M100MECHANICAL SITE VIEW1

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

CO

CO

COCO

CO

CO

CO

CO

CO

CO

1

C

B

D

E

F

G

2 3 4 5 7 9 10 11 12 13

FD FD

V

100 SAN AND 75 STACK VENT FROM SECONDFLOOR WASHROOM AND JANITOR ROOM200 ST

MS

150 S

AN@

1%

100 SAN@1%

100 S

AN@

1%

100 SAN@1%

150 ST@1%

200 ST@1%

100 SAN@1%

GROUND EXCHANGE PIPING FROM BOREFIELD INTO MECHANICAL ROOM BY OTHERS

FD

FD

V

150 ST FROM ROOF DRAINS

FD

75 SAN AND 75 STACK VENT FROMFAN COIL CONDENSATE PIPINGAND THIRD FLOOR JANITOR ROOM

150 ST FROM ROOF DRAINS

150 ST FROM ROOF DRAINS

75 SAN UP TO ELEVATOR PIT DRAIN. ENSUREELECTRIC TRACTION TYPE ELEVATOR

CRU-2 BELOW GRADE SANITARYROUGH IN PROVIDED WITH BASEBUILDING. PROVIDE TIE INS FORFIXTURES AS REQUIRED

100 SAN@1%

100 S

AN@

1%

75 S

AN@

2%

FD FD

75 S

AN@

2%

V

75 S

AN@

2%

FD

75 S

AN@

2% CRU-1 BELOW GRADE SANITARYROUGH IN PROVIDED WITH BASEBUILDING. PROVIDE TIE INS FORFIXTURES AS REQUIRED

URUR

WCWC

WC

LAVLAV

FD FD

FD

100 SAN@1%

75 S

AN@

2%

75 S

AN@

2%

V V V

150 ST@1%

75 SAN FROM GREENWALL TRENCH DRAIN.COORDINATE WITH GREEN WALL INSTALLER

FD

30mm RAINWATER BACK UP SUPPLYDOWN FROM MECHANICAL ROOM

2M200

RWT-1

150 SANITARY SERVICE. SEE CIVIL SITESERVICING DRAWING COO1 FOR CONTINUATION

200 STORM SERVICE. SEE CIVIL SITESERVICING DRAWING C001 FORCONTINUATION

150 MUNICIPAL WATER SERVICE. SEE CIVIL SITESERVICING DRAWING C001 FOR CONTINUATION

150 STORM OVERFLOW. SEE CIVILSITE SERVICING DRAWING C001FOR CONTINUATION

40mm RAINWATER SUCTION SUPPLYUP TO PUMPING SYSTEM

EXTENT OF 50mm RIGID INSULATION

1190 MBH GAS SUPPLY TO BESTUBBED OUT BELOW GROUNDON WEST SIDE OF BUILDING

FD

SHSH

SH

SHSH

V

VFD

200 ST@1%

150 ST@1%

75 S

AN@

2%

INV. 693.32

INV. 692.52

INV. 692.33

INV. 693.02

INV. 692.82

INV. 692.60

INV. 692.02

E

RWT-1

25,000L COMPOSITE RAINWATER STORAGETANK c/w 900mmØ MANHOLE

FACTORY SUPPLIED CONCRETE DEADMAN

150 ST OVERFLOW TIED INTO STORM SEWER

50mm RIGID INSULATION

150 ST SUPPLY TO RAINWATER TANK

30 DCW BACKUP SUPPLY

BACKUP SUPPLY FLOAT SYSTEM

50mm RAINWATER SUCTION PIPE c/wFOOT VALVE

900mm SOLID STEEL LOCKINGMANHOLE COVER

50 SUCTION RW SUPPLY TO PUMPING SYSTEM.COORDINATE FLOW AND PRESSURE REQUIREMENTSWITH IRRIGATION SYSTEM SUPPLIER

COMPACTED GRNULATED BACKFILL200mm COMPACTED GRAVEL BED

1870

NEW 150Ø PVC DOMESTICWATER MAIN

(4) @ 20Ø S.S. RODS c/w NUTS

300Ø MIN. SDR 35 PVC RISERSLEEVE

SAND COVER

GRAVELCONCRETE THRUST BLOCK TOCITY OF EDMONTON STANDARDS

JOINT RESTRAINER (TYPICAL)

JOINT RESTRAINER (TYPICAL)

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

MECHANICALFOUNDATION PLAN

M200

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M200MECHANICAL FOUNDATION PLAN1

1 : 50M200RAINWATER STORAGE TANK DETAIL2

NTSM200INCOMING WATER DETAIL3

TRUE NORTH

1. SEE CIVIL DRAWINGS SUBMITTED FOR APPROVALS ONDECEMBER 13, 2013 FOR CONTINUATION OF SITE SERVICES.

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

DN

DN

CO

CO

CO

CO

CO

WM

NFHB

NFHB

NFHB

NFHB

CO

CO

CO

WM

WM

CO

1

C

B

E

G

2 3 4 5 6 7 8 9 10 11 12 13 14

HJ

K

L

1M400

FC-1103

FC-1104

FC-1307

FC-1304

FC-1303FC-1102

FC-1302

FC-1301

2M400

FD-2 FD-2

1M401

WATER METER ANDSPRINKLER TREE BEHINDCHAIN LINK FENCE

FD-2

IN FLOOR HEAT ZONE 1225mm SPACING20m²3000W

IN FLOOR HEAT ZONE 2225mm SPACING(150mm WITHIN ENTRANCE)70m²10500W

IN FLOOR HEAT ZONE 3225mm SPACING(150mm WITHIN ENTRANCE)55m²8250W

IN FLOOR HEAT ZONE 4225mm SPACING25m²3750W

IN FLOOR HEAT ZONE 5225mm SPACING35m²5250W

IN FLOOR HEAT ZONE 6225mm SPACING30m²4500W

NON FREEZE HOSE BIBB EQUALTO ZURN Z-1300 ECOLOTROLWALL HYDRANT (TYPICAL)

1250

1000 W

RP-1

100 DEEP IN FLOOR HEAT MANIFOLD CABINET.IN SLAB PIPING TO BE RUN BELOW CORRIDORAND NOT BELOW NICHE

100 DEEP IN FLOORHEAT MANIFOLDCABINET

VV

UR

WC

LAV

MSMS

FD-2 FD-2

V V V V

VV

V

V

40 DCW40 DHW20 DHWR

50 D

CW20

DHW

15 D

HWR

20 DHWR

?

40 DHW50 DCW

PIPES RISE ON ANGLEBELOW STAIR

PIPES RISE UP INTO BEAM SPACE.PROVIDE AIR VENTS AS REQUIRED

NON FREEZE HOSE BIBB EQUAL TO ZURNZ-1300 ECOLOTROL WALL HYDRANT

RAINWATER STORAGE TANK BACKUPSUPPLY SHUTOFFRAINWATER STORAGE TANK 30mmBACKUP SUPPLY DOWN INTO FOUNDATION

7000GAL BELOW GRADERAINWATER STORAGE TANK

30 DCW

50 DCW STUBOUT FOR TENANT WITHINBEAM SPACE. PROVIDE BMS FLOW METER

50 DCW, 25 DHW AND15 DHWR FOR MAINFLOOR WASHROOM

SECOND FLOOR WASHROOM SANITARYPIPING TIGHT TO U/S OF BEAM

SECOND FLOOR WASHROOM 50DCW, 20 DHW AND 15 DHWR UP

50 DCW STUBOUT FOR TENANT WITHINBEAM SPACE. PROVIDE BMS FLOW METER

FC-1305

FC-1306

BS-31BS-32BS-33

20 DCW, 20 DHW AND 15 DHWR UPTO SECOND AND THIRD FLOORFIXTURES

15 DHW AND 15 DCW TORECYCLE SERVICE SINK

40 PRESSURE RW SUPPLY FROM RAINWATER STORAGE TANK. COORDINATEWITH IRRIGATION PACKAGE SUPPLIER.ENSURE WINTER DRAIN DOWNCAPABILITY

65 TWS65 TWR

65 TWS65 TWR

40 HWR40 HWS

20 H

WR

20 H

WS

VRF BRANCH SELECTORS WITHINBEAM SPACE

IN FLOOR HEAT PIPING BELOW VESTIBULE GRATEPANS TO BE TIGHTENED TO 150mm SPACING

IN FLOOR HEAT PIPING BELOW VESTIBULE GRATEPANS TO BE TIGHTENED TO 150mm SPACING

2M201

3M201

PROVIDE SLEEVE FORFUTURE GAS LINE. FILL WITHSPRAY FOAM INSULATION

GREEN WALL TRENCH DRAIN

HP-1HP-2AHP-2BBS-11BS-12

FD-3

P-5

20 DCW

RAINWATER PUMPING PACKAGE.COORDINATE WITH IRRIGATIONCONTRACTOR FOR EXACT REQUIREMENTS

FD

FDV

1000

800 W

RP-1

2000

1550 W

RP-1

ARCHITECTURAL SERIES ELECTRIC BASEBOARDTO BE OPERATED BY BMS BASED ON SPACETEMPERATURE SENSOR

150 ST

NICHEOF-02

150 ST

WC WC WCWC

WC WCWC

KS KS

LAV

FD

100 S

AN@

1%

LAV LAVLAVV

MS-1

OFFSET 150 ST DOWN INTO FOUNDATION

OFFSET 150 ST DOWN INTO FOUNDATION

OFFSET 150 ST DOWN INTO FOUNDATION

COORDINATE SANITARY WITHDUCTWORK IN THIS AREA

150 ST DOWN

100 S

P

65 D

CW

40 D

HW

30 D

HWR

65 T

WS

65 T

WR

40 H

WR

25 H

WS

40 H

WR

PROVIDE UNI-STRUT SUPPORT SYSTEM FOR PIPING RUNS

PIPING TO RISE UP TIGHT TO U/S OF STAIRS

VESTIBULE FLOOR GRATE150mm SPACED IN FLOOR HEAT PIPES WITHINVESTIBULE. PRIME PIPING WITH GLYCOL BEFORE SLABPOUR. COORDINATE LOCATION WITH STRUCTURAL

IN FLOOR HEAT MANIFOLD CABINET EQUALTO ROTH HK SERIES 100mm DEEPRETURN MANIFOLDSUPPLY MANIFOLD

PEX PIPING SLAB PENETRATION PROTECTOR EQUALTO AXIOM PEXPAL. COORDINATE LOCATION WITHARCHITECTURAL WALL PLACEMENT ON A101

25 HWS AND 25 HWR

15 IN FLOOR PEX PIPING

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

MAIN FLOOR MECHANICALPLUMBING, HEATING AND

COOLING PLAN

M201

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M201MAIN FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1

TRUE NORTH

1 : 20M201VESTIBULE PIPING DETAIL2

1 : 20M201IN FLOOR HEAT CABINET DETAIL3

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

1

C

B

D

E

F

G

2 3 4 5 6 7 8 9 10 11 12 13 15

HJ

K

L

FC-2201

FC-2401

FC-2406

FC-24072

M401

150 ST DOWN

V

RD

RD

RD

RD

FC-2410

OPEN OFFICESSH-07

GAMES ROOMSH-06

LOUNGESH-05

EXIT STAIRSES-10

DINING AREASH-01

BALCONYSH-03

BAR SEATINGSH-02

LANDINGCS-20

BLEACHERSCS-13

SEATINGCS-11

MEETING ROOMBH-22

MEETING ROOMBH-14

CORRIDORBH-04

OFFICEBH-12

OFFICEBH-11

OFFICEBH-10

MEETING ROOMBH-13

SECURITYBH-01

PRINTER RMBH-05

OFFICEBH-06

OFFICEBH-07

OFFICEBH-08

CORRIDORBH-02

CORRIDORBH-03

CORRIDORCS-07

100 S

T@1%

100 S

T@1%

FC-2203

FC-2202

FC-2204

V

MS

FC-2404

FC-2402

FC-2405

MS-1

FC-2409FC-2408

50 DCW, 25 DHW AND 15 DHWRFOR SECOND FLOOR WASHROOM,JANITOR ROOM AND KITCHENETTE

20 DCW AND 20 DHW TO MOP SINK

75 FROM MOPSINK ABOVE

BS-41

BS-43BS-42

VRF BRANCH SELECTORS WITHINJANITOR ROOM CEILING SPACE

150 ST DOWN

KS-1

FD-2

FD

V

KS-1

V

V V VV

V V V

V100 S

T@1%

OFFICEBH-09

LANDINGES-04

EXIT STAIRSES-03

OPEN OFFICESBH-21

OPEN OFFICESBH-20

OPEN OFFICESBH-20

OPEN OFFICESBH-19

OPEN OFFICESBH-18

OPEN OFFICESBH-17

OPEN OFFICESBH-16

OPEN OFFICESBH-15

BS-22BS-21

BS-23BS-24

FC-2403

F2

150ST DOWN

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

1 : 100

LB

LB/DRC

DRC

21-3180

SECOND FLOORMECHANICAL PLUMBING,HEATING AND COOLING

PLAN

M202

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M202SECOND FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

1

C

B

D

E

F

G

2 3 4 5 6 7 8 9 10 11 12 13 15

HJ

K

L

FC-3501 FC-3502

FC-2205

FC-3503

FC-3509FC-3506

FC-3507

FC-3510

RD

RD

RD

RD

RD

RD

OPEN OFFICESOC-06

OPEN OFFICESOC-07

OPEN OFFICESOC-08

OPEN OFFICESOC-09

OPEN OFFICESOC-10

OPEN OFFICESOC-11

OPEN OFFICESOC-12

OPEN OFFICESOC-13

OPEN OFFICESOC-14

OPEN OFFICESOC-16

OPEN OFFICESOC-15

OPEN OFFICESOC-17

??

HOT DESKSOC-18

MEETING ROOMOC-20

MEETING ROOMOC-19

CORRIDOROC-05

CORRIDOROC-04

HALLWAYOC-01

LANDINGCS-23

OCEOC-26

OFFICEOC-25

OFFICEOC-24

OFFICEOC-23

PRINTER ROOMOC-22

OFFICEOC-21 JANITOR

SE-14

100 S

T@1%

100 S

T@1%

100 S

T@1%

MS-1

SEE DWG1/M202 FORSECOND FLOORPLUMBING PLAN

BS-53BS-52BS-51

VRF SYSTEM BRANCH SELECTORSWITHIN JANITOR ROOM CEILING SPACE

V

MAIN SAN VENT UP THROUGH ROOF

20 DCW AND DHW TO MOP SINK

FC-3508

FD-2

STORM PIPING TIGHT TO U/S OF DECK.PROVIDE 25mm INSULATION ON FIRST 3m

100 S

T@1%

100 S

T@1%

150 ST DOWNINTO FOUNDATION

150 ST DOWN INTO FOUNDATION

20 DCW UP TO NON FREEZE HOSE BIBB

150 ST DOWN INTO FOUNDATION

FC-3504

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

1 : 100

LB

LB/DRC

DRC

21-3180

THIRD FLOORMECHANICAL PLUMBING,COOLING AND HEATING

PLAN

M203

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M203THIRD FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1

All drawings and specifications are instruments of service and property ofthe Consultant and shall not be used without the Consultant's permission.Contractor shall verify all dimensions and details and refer anydiscrepancies to the Consultants before proceeding with the work.

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

T

T

T

T

T

T

FE

FE

FE

FE

T

T

T

C22700 mm AFF.

C22700 mm AFF.

C22700 mm AFF.

C22700 mm AFF.

C22700 mm AFF.

C22700 mm AFF.

?3054 mm AFF.

?? AFF.

?3795 mm AFF.

?? AFF.

1

C

D

E

F

G

2 3 4 5 6 7 8 9 10 11 12 13 14

HJ

K

L

FC-1102

FC-1103

FC-1304

FC-1307

FC-1104

FC-1302FC-1301

FC-1303

FC-1307

250x150150 L/s

E-1

-

600x300

R-1

BALANCE 250Ø TO 300 LPS

7M400

CRU - 3WE-01

ATRIUMCS-02

VESTIBULECS-01

SITE SAFETYSE-04

MECHANICALSE-06

ELECTRICALSE-07

RECYCLINGSE-08

CORRIDORES-01

RECEPTIONWE-03

LOCKER ROOM - WWE-04 LOCKER ROOM - M

WE-12

WCWE-10

WCWE-07 URINALS

WE-11

SHWR-WWE-08

SHWR-MWE-09

CORRIDORSE-01

1M401

2M400

1M400

11M400

BALANCE TO 150Ø S/A 105 LPS

HANG THERMOSTAT/CONTROLLER AND CONTROLWIRING WITH FAN COIL

HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL

HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL

HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL

BALANCE 250Ø WASHROOM E/A TO 180 LPSBALANCE 300Ø GENERAL E/A TO 300 LPS

CRU FAN COILS C/W OPEN ENDED ACCOUSTICALLYINSULATED S/A AND R/A PLENUMS

BALANCE 250Ø TO 300 LPS

??

FC-1306

BS-33

BS-31BS-32

CRU FAN COILS C/W OPEN ENDED ACCOUSTICALLY INSULATEDS/A AND R/A PLENUMS. CRU-2 FAN COILS BELOW FIRE RATING

2M301

BALANCE TO 130 LPS

-

650x250

R-2-

300x250

S-2

300Ø T/A-

300x250

S-2

400x15060 L/s

E-23@

EF-3

?

EF-2

? 250x250 T/A. PROVIDE ACCOUSTIC INSULATION AS SHOWN

F D

F D

F D

10 L/s

S-3

380x380

700x300 INSULATED EXHAUST PLENUM

150x15035 L/s

E-18@

250Ø E/A

250Ø E/A

200Ø E/A

250Ø

E/A

350Ø

E/A

2@ 250x250 E/A CONNECTION TO PLENUMSERVER ROOM HEAT REJECTION INLINE FAN

ELECTRICAL ROOM HEAT REJECTION CEILING TYPE FAN

BALANCE 250Ø E/A TO 190 LPS

BALANCE 200Ø S/A TO 210 LPSFC-1305

100 SP

SPRINKLER TREE LOCATIONFIRE DEPARTMENT CONNECTION

5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET

TO ZONE VALVES

FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.

EXHAUST PLENUM AT HIGH LEVEL. SEEARCHITECTURAL ELEVATION VIEWS FOR DETAIL

LOWER

UPPER

SPF-1

STAIRWELLPRESSURISATION FAN

-

1200x200

L-1

SPF-2 STAIRWELL PRESSURISATION FAN

-

1200x200

L-1

HP-2BHP-2AHP-1

BS-11BS-12

VRF ZONE THERMOSTAT/CONTROLLER c/w COVER PLATETO ALLOW LIMITED SET POINT ADJUSTMENT ANDOCCUPANCY OVERRIDE ONLY (TYPICAL)

BMS TEMPERATURE SENSORLOCATION FOR IFH ZONE2

100 SP FROM FIRE DEPARTMENTCONNECTION. SLOPE BACK TOSPRINKLER TREE

BMS TEMPERATURE SENSOR LOCATIONFOR IFH ZONE 3ATRIUM VRF FAN COILS TO OPERATEDURING OCCUPIED HOURS BASEDON RETURN AIR TEMPERATURE

CRU - 2OF-03

-

700x1100

L-1

EF-1

MECHANICAL ROOM CEILING TYPE FAN

CRU-1RT-01

150x15030 L/s

E-1

F D

250Ø

E/A

CORRIDORES-08

F D F DF D

FIRE DAMPERS AT FLOORPENETRATIONS

COORDINATE DUCTWORK WITHSANITARY PIPING IN THIS AREA

300Ø

E/A

S/A 2-POSITION CONTROL DAMPERS

E/A 2-POSITION CONTROL DAMPERS

FC-1101

CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE

-

650x250

R-2

E/A 2-POSITION CONTROL DAMPERS

650x250130 L/s

R-2

300Ø S/A INTO SPACE. ALIGN TOPOF DUCT WITH U/S OF BEAM

D E

SERVERRACKS

WAR

M IS

LE

COOL

ISLE

HEAT REJECTION EXHAUST GRILLE IN T-BAR CEILING

250Ø E/A DUCTWORK BACK TO EXHAUST FAN WITHINELECTRICAL ROOM

250Ø E/A

HEAT RECLAIM VRF UNIT HUNG AT U/S T-BAR CEILING.UNIT TO BE PLACED AS SHOWN WITH RETURN OVERWARM ISLE AND SUPPLY DIRECTED TO COOL ISLE.UNIT TO OPERATE CONTINUOUSLY 24/7 BASED UPONRETURN AIR TEMPERATURE

TRANSFER AIR DUCT

-

250x250

E-1

-

250x150

S-2 DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

MAIN FLOOR MECHANICALVENTILATION AND FIRE

PROTECTION PLAN

M301

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M301MAIN FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1

1 : 50M301SERVER ROOM COOLING DETAIL2

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

Sco

Sco

S co

T

T

T

T

T

TT

T

T

FE

FE

FE

FET

T

T

T

?3000 mm AFF.

?3000 mm AFF.

?3000 mm AFF.

?3000 mm AFF.

?3000 mm AFF.

?? AFF.

?? AFF.

C22700 mm AFF.

?? AFF.

C22700 mm AFF.

?10081 mm AFF.

C22700 mm AFF.

1

C

B

D

E

F

G

2 3 4 5 6

6

7 8

8

9 10 11 12 13 15

H

H

J

K

L

FC-2201

FC-2406

FC-2407

FC-2401

250Ø

S/A

250Ø S/A

300Ø S/A

250Ø

S/A

250Ø S/A

250Ø

S/A

250Ø S/A250Ø S/A

200Ø S/A 200Ø S/A

FC-2409

200Ø S/A

200Ø S/A

FC-2410

300Ø S/A

300Ø S/A

9M400

OPEN OFFICESSH-07

GAMES ROOMSH-06

LOUNGESH-05

EXIT STAIRSES-10

DINING AREASH-01

BALCONYSH-03

BAR SEATINGSH-02

LANDINGCS-20

BLEACHERSCS-13

SEATINGCS-11

MEETING ROOMBH-22

MEETING ROOMBH-14

CORRIDORBH-04

OFFICEBH-12

OFFICEBH-11

OFFICEBH-10

MEETING ROOMBH-13

SECURITYBH-01

PRINTER RMBH-05

OFFICEBH-06

OFFICEBH-07

OFFICEBH-08

CORRIDORBH-02

CORRIDORBH-03

CORRIDORCS-07

300Ø S/A

250Ø

S/A

FC-2403

10M400

FC-2203

BALANCE TO 140 LPS

CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE

350x350 S/A DROP FROM ERV-1INTO FIRE RATED BULKHEAD

750x350 R/A UP TO ERV-1. SEEDWG12/M400 FOR DUCTING DETAIL

BALANCE TO 265 LPS

DECK MOUNTED DUCTLESS FAN COIL UNIT350 S/A DUCT TIGHT TO U/S OF DECK.DROP 300 S/A DUCTS BELOW BEAM

200 CUBICAL R/A DUCT C/W150x150 R/A GRILLES

BS-41

FC-2404

FC-2402

FC-2405

FC-2408

BS-42BS-43

OPEN OFFICE SPACE FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM300Ø DROPS BELOW GLULAM BEAM

300Ø S/A

BALANCE TO60 LPS

LOUNGE FAN COIL C/W ACCOUSTICALLYINSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM

BALANCE TO30 LPS

BALANCE 150Ø TO 50 LPSBALANCE 150Ø TO 65 LPS

BALANCE 100Ø TO 35 LPSBALANCE 100Ø TO 30 LPS

DEMAND VENTILATION DISPLACEMENT DIFFUSERON WALL @ 600 AFF. CONTROL DAMPER TOREGULATE CO2 TO 800PPM

DEMAND VENTILATION DISPLACEMENT DIFFUSER ONWALL @ 600 AFF. CONTROL DAMPER TO REGULATECO2 TO 800PPM

BALANCE 100ØTO 30 LPS

BALANCE TO 30 LPS WITH CONTROL VALVEFULLY OPEN

2M302

FC-2204

FC-2204 R/A GRILLE @ 4000 AFF

FC-2202

CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE

2M401

300x20080 L/s

E-3

-

650x250

R-2

500x25090 L/s

R-2

F D

F D

F D

F D

150x15040 L/s

E-1

F D

150x15040 L/s

R-13@

FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.

350x150200 L/s

S-2

VRF ZONE THERMOSTAT/CONTROLLER c/w COVER PLATETO ALLOW LIMITED SET POINT ADJUSTMENT ANDOCCUPANCY OVERRIDE ONLY (TYPICAL)

VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT

VRF ZONE THERMOSTAT/CONTROLLERc/w COVER PLATE TO ALLOW LIMITED SETPOINT ADJUSTMENT AND OCCUPANCYOVERRIDE ONLY (TYPICAL)

VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT

55 L/s

S-3

380x380

25 L/s

S-3

380x380

55 L/s

S-3

380x380

PRINTER ROOM FAN COIL UNIT TO RUNCONTINUOUSLY DURING OCCUPIED HOURSTO MAINTAIN RETURN AIR TEMPERATURE

OPEN OFFICESBH-21

OPEN OFFICESBH-20

OPEN OFFICESBH-19

OPEN OFFICESBH-18

OPEN OFFICESBH-17

OPEN OFFICESBH-16

OPEN OFFICESBH-15

250x10050 L/s

S-16@

250x10045 L/s

S-17@

250x10060 L/s

S-15@

250x10045 L/s

S-14@

250x10070 L/s

S-16@

250x10060 L/s

S-17@

250x10055 L/s

S-16@

350Ø

S/A

30 L/s

S-3

380x380

150Ø

S/A

150Ø

S/A

250Ø S/A

150x15030 L/s

E-1

F D

ERV-1 FLOW GRID BELOW 150 S/A DUCT

150Ø

S/A

5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET

150Ø S/A

350x350 S/A

200Ø S/A

150x15035 L/s

E-1200x20070 L/s

E-14@

250Ø E/A

250Ø E/A

S/A 2-POSITION CONTROL DAMPERS

S/A 2-POSITION CONTROL DAMPER

9

150x150 DEMAND VENTILATIONCONTROL DAMPER

360x360 DISPLACEMENT DIFFUSERWITH FACTORY PLENUM

300x65 FRESH AIR DUCT IN WALL

WALL MOUNTED HEAT/COOL AIRCONDITIONER

55 L/s

S-3

380x380DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

SECOND FLOORMECHANICAL

VENTILATION AND FIREPROTECTION PLAN

M302

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M302SECOND FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1

1 : 50M302MEETING ROOM VENTILATION DETAIL2

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

FE

FET

T

T

T

T

T

T S co

S coT

?? AFF.

C23000 mm AFF.

C23000 mm AFF.

C23000 mm AFF.

1

C

B

D

E

F

G

2 3 4 5 6 7 8 9 10 11 12 13 15

H

H

J

K

L

FC-3509

FC-3503

FC-3501 FC-3502

FC-2205 FC-3505

FC-3506

FC-3507

250Ø S/A

300Ø S/A 300Ø S/A

250Ø

S/A

250Ø

S/A

300Ø S/A

8M400

OPEN OFFICESOC-06

OPEN OFFICESOC-07

OPEN OFFICESOC-08

OPEN OFFICESOC-09

OPEN OFFICESOC-10

OPEN OFFICESOC-11

OPEN OFFICESOC-12

OPEN OFFICESOC-13

OPEN OFFICESOC-14

OPEN OFFICESOC-16

OPEN OFFICESOC-15

OPEN OFFICESOC-17

HOT DESKSOC-18

MEETING ROOMOC-20

MEETING ROOMOC-19

CORRIDOROC-05

CORRIDOROC-04

HALLWAYOC-01

LANDINGCS-23

OCEOC-26

OFFICEOC-25

OFFICEOC-24

OFFICEOC-23

PRINTER ROOMOC-22

OFFICEOC-21

JANITORSE-14

2M303

200Ø S/A

FC-3510

BS-51

400Ø

S/A

300Ø S/A

350Ø

S/A

TIGHT TO U/S PENTHOUSE ROOF DECKTIGHT TO U/S PENTHOUSE FLOOR DECK

DEMAND VENTILATION DISPLACEMENT DIFFUSERSON WALL @ 600 AFF. CONTROL DAMPERS TOREGULATE CO2 TO 800PPM

OPEN OFFICE SPACE FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM

PROVIDE DUCTED RETURNTO EAST FAN COIL

BALANCE 200Ø TO 135 LPS

BALANCETO 40 LPS

BALANCETO 110 LPS

BALANCE TO 70 LPS

BS-52BS-53

FC-3508

FC-3504

SEE DWG1/M302 FORSECOND FLOORVENTILATIONPLAN

-

900x250

R-2

150x10030 L/s

S-2

150x15020 L/s

E-1

150x15050 L/s

E-1

300x200100 L/s

E-1

F D F D

FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.

3M303

4M303

2@ DUCTLESS ATRIUM VRF FAN COIL UNITS TIGHT TO U/SOF ROOF DECK. ATRIUM UNITS TO OPERATECONTINUOUSLY DURING OCCUPIED HOURS BASED ONRETURN AIR TEMPERATURE (TYPICAL)

BMS TEMPERATURE SENSOR ATBOTTOM OF OPERABLE WINDOW LINE

BMS TEMPERATURE SENSOR ATBOTTOM OF OPERABLE WINDOW LINE

PRINTER ROOM WALL MOUNT FAN COIL TO RUNCONTINUOUSLY DURING OCCUPIED HOURS TOMAINTAIN RETURN AIR TEMPERATURE

VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT

250x10055 L/s

S-110@

250x10055 L/s

S-16@

250x10050 L/s

S-18@

200x10030 L/s

S-15@

VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)

F D

200Ø E/A

5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET

F D

300Ø PERIMETERSPIRAL S/A DUCT

SPIRAL DUCT 2-HALFBAND HANGER

THREADED READY RODSUPPORT HANGER

GLUELAM STRUCTURALBEAM

FC-3504

300Ø S/A

150Ø S/A-

900x250

R-2

FC-3504ACOUSTICALLY INSULATED RETURNAIR PLENUM100Ø FRESH AIR SUPPLY INTOPLENUMFILTER SECTION

CANVAS CONNECTION ONSUPPLY AND RETURN PLENUMS

VRF FAN COIL UNIT TIGHT TO U/SOF DECKCONDENSATE TO BE PIPED TOCLOSEST SANITARY

RL AND RF TO BE RUN IN TANDEMWITH FRESH AIR AND CONDENSATE300 S/A DUCT FROM BOTTOM OFPLENUM TO AVOID BEAM ATGRIDLINE 12

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

THIRD FLOORMECHANICAL

VENTILATION AND FIREPROTECTION PLAN

M303

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 100M303THIRD FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1

1 : 20M303PERIMETER SPIRAL DUCT HANGING DETAIL2

TRUE NORTH

1 : 50M303FC-3504 CONNECTION DETAIL3

1 : 50M303FC-3504 CONNECTION DETAIL4

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

B

11 12

4M400

3M400

GEO EXCHANGE MANIFOLDAND PIPING TO GEOEXCHANGE FIELD BY OTHERS

GEO EXCHANGE PUMPS c/wFACTORY VSD

TEMPERED GLYCOL FILL TANK

TEMPERED GLYCOLEXPANSION TANK

RECYCLING AREA IN FLOORHEAT MANIFOLD CABINETWATER SOURCE VRF HEATPUMPS

ACTIVE SLAB GLYCOLEXPANSION TANK

ACTIVE SLAB GLYCOL FILLTANK

ACTIVE SLAB GLYCOL FILLTANK

ACTIVE SLAB BUFFER TANK

ACTIVE SLAB WATER TOWATER HEAT PUMP

BUFFER TANK CIRCULATOR

HYBRID ELECTRIC DOMESTICWATER HEATER

ELECTRIC BASEBOARDRADIATION SET TO 10°C

TEMPERED GLYCOLPUMPS C/W FACTORY VSD

HP-3HP-4AHP-4B

ET-1

GFT-1

P-2B

P-2A

P-1BP-1A

FD-3

FD-3

DWH-1

HP-6P-4

BT-1

P-3

GFT-2ET-2

DWRP-1

LOCATION FOR GREENWALLIRRIGARTION EQUIPMENT.COORDINATE WITHGREENWALL EQUIPMENTMANUFACTURER

1000

800 W

RP-1

BMS CONTROLS CABINET

B

11 12

4M400

3M400

TEMPERED GLYCOL RETURNWITHIN BEAM SPACE

TEMPERED GLYCOL SUPPLYWITHIN BEAM SPACE

HP-5A HP-5B

150

150

40 DCW40 DHW20 DHWR65 TWS65 TWR40 HWR40 HWS

20 D

CW20

DHW

EF-2

250x250 E/A

FD

B

P-2BP-2A

GFT-1 ET-1

150

EF-2

P-1AP-1B

HP-5B

HP-3HP-4A

BMS CABINET

TW PUMPSGEO EXCHANGE PIPING

ELECTRIC BASEBOARD1000

800 W

RP-1

GEO EXCHANGE PUMPS

GLYCOL FILL TANKTW EXPANSION TANK

STACKED HEAT PUMPSFIRE EXTINGUISHER

MECHANICAL ROOMEXHAUST FAN

B

BT-1

HP-6

DWH-1

150

P-4

P-3

HP-5A

HP-4B

HP-5A

ET-2

GFT-2 FD-3

TW SUPPLY HEADERSTACKED HEAT PUMPSACTIVE SLAB PUMP

ACTIVE SLAB BUFFER TANK

W TO W HEAT PUMPBUFFER TANK PUMP

HYBRID ELECTRIC WATER HEATER

76 S

AN

40 HWS40 HWR65 TWR65 TWS

20 DHWR40 DHW40 DCW

D

E

10 11

6M400

ERV-2

DUAL CORE ENERGY RECOVERY VENTILATOR

700x300 INSULATED INTAKE/EXHAUST PLENUM AND LOUVRE

400x400 S/A DUCT. PROVIDE TURNING VANES ON MITRED ELBOWS350Ø S/A DUCT DOWN SHAFT BELOW. PROVIDEFIRE DAMPER AT FLOOR PENETRATION

-

700x300

L-1

-

700x300

L-1

M

M

MOTORISED DAMPERS INTERLOCKED WITHERV UNIT

10

ERV-2

350Ø

S/A

700x300980 L/s

L-1

DUAL CORE ENERGYRECOVERY VENTILATOR

300x400 E/A PLENUM

350Ø GENERAL E/A

700x300 LOUVRE

450x300

700x300 PLENUMAND LOUVRE

350Ø MEDIUM PRESSUREFRESH AIR SUPPLY

300Ø WASHROOM E/A

FD

FD

ERV-2 FLOW GRID

D

E

10

75 SAN

150 ST

200Ø

S/A

250Ø

E/A

350Ø

E/A

75 SAN

75 SAN

15 DHWR

20 DHW

20 DCW

50 D

CW

D

E

10

200Ø E/A

100 S

T250Ø

S/A

450x300 E/A

150Ø

E/A

150Ø

E/A

350Ø S/A

20 D

HW

20 D

CW

100 S

T

350Ø E/A 400Ø E/A

FD

FD

FD

FD

FIRE CAULK AT ALL PIPE FIRESEPARATION PENETRATIONS

OUT OF STREAM FIREDAMPERS AT ALL DUCT FIRESEPARATION PENETRATIONS

20 DCW UP TO ROOFTOP NON-FREEZE HOSE BIBB

D

E

10

150Ø E/A

20 DCW

20 DHW

15 DHWR

350Ø E/A 350Ø E/A

250Ø S/A

250Ø

S/A

200Ø E/A

150 ST

75 SAN VENT

75 SAN

FIRE CAULK AT ALL PIPE FIRESEPARATION PENETRATIONSOUT OF STREAM FIREDAMPERS AT ALL DUCT FIRESEPARATION PENETRATIONS

FD

FD

FD

E

4

350Ø GENERAL EXHAUST OPEN TO SHAFT.FIRE DAMPER AT FLOOR PENETRATION

350x350 FROM 350Ø WASHROOM EXHAUST.FIRE DAMPER AT FLOOR PENETRATION 350X350 S/A INTO SHAFT TRANSITIONS TO

350Ø S/A DOWN. FIRE DAMPER AT FLOORPENETRATION

2@ 100 ST INTO 150 ST DOWN INTOFOUNDATION

FD

FD

FD

350x350 GENERAL EXHAUST OPEN TO SHAFT

E

4

350Ø GENERAL EXHAUST INTO SHAFT. FIREDAMPER AT FLOOR PENETRATION

350Ø WASHROOM EXHAUST INTO SHAFT.FIRE DAMPER AT FLOOR PENETRATION

350Ø S/A DOWN FROM SHAFT. FIRE DAMPERAT FLOOR PENETRATION150 ST DOWN FROM ROOF DRAINS. OFFSETAND DROP INTO FOUNDATION

FD

FD

FD

34

ERV-1

ACOUSTICALLY INSULATED 750x350 E/A RISE TOUNIT. PROVIDE CANVAS CONNECTION AS SHOWN350Ø GENERAL E/A OPEN TO SHAFT350Ø WASHROOM E/A FROM SHAFT

350x350 ACOUSTICALLY INSULATED S/A DROP INTO FRR BULKHEAD ABOVEEXIT. SIZES DENOTE FREE AREA. PROVIDE CANVAS CONNECTION AS SHOWN

350x350 S/A. PROVIDE TURNING VANES ON MITRED ELBOWS

CHANGEOVERSECTION

EXHAUST FANSECTION

HE CORESECTION

EXHAUSTPLENUM

PERFORATED FACE WASHROOM EXHAUST GRILLE

DUAL CORE ENERGY RECOVERY VENTILATORSUPPLY FANSECTION

HE CORESECTION

200x20070 L/s

E-12@

250Ø E/A

350Ø

E/A

350Ø

S/A

200x

200 E

/A

200x

200 E

/A

350x750 E/A

350x350 S/A INTO SHAFT. TRANSITION TO 350Ø. PROVIDETURNING VANES ON MITRED ELBOWS

GENERAL EXHAUST SHAFT SEALED TO U/S OF DECK

WASHROOM EXHAUST 2-POSITIONCONTROL DAMPER

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

As indicated

LB

LB/DRC

DRC

21-3180

MECHANICAL ROOMDETAILS

M400

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 50M201EAST MECHANICAL ROOM LOWER DETAIL1

1 : 50M201EAST MECHANICAL ROOM UPPER DETAIL2

1 : 50M400EAST MECHANICAL ROOM EAST SECTION VIEW3

1 : 50M400EAST MECHANICAL ROOM WEST SECTION VIEW4

1 : 50M400PENTHOUSE MECHANICAL ROOM PLAN5

1 : 50M400ERV-2 DUCTING DETAIL6

1 : 20M301EAST MECHANICAL CHASE DETAIL - MAIN FLOOR7

1 : 20M303EAST MECHANICAL CHASE DETAIL - THIR FLOOR8

1 : 20M302EAST MECHANICAL CHASE DETAIL - SECOND FLOOR9

1 : 20M302WEST MECHANICAL CHASE DETAIL - SECOND FLOOR10

1 : 20M301WEST MECHANICAL CHASE DETAIL - MAIN FLOOR11

1 : 50M100ERV-1 DUCTING DETAIL12

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

CO

C

4 5

-

600x300

R-1

-

650x250

R-2

WC-1

SH-1SH-1

WC-1 WC-1

UR-1

UR-1

LAV-1

LAV-1

LAV-1

LAV-1

3@LAV

V

50 D

CW40

DHW

30 D

HWR

65 T

WS

65 T

WR

100 SP65 DCW40 DHW30 DHWR65 TWS65 TWR40 HWR25 HWS40 HWR

FD-1FD-1

150x15035 L/s

E-18@

300Ø

E/A

250Ø E/A 200Ø E/A

150Ø

E/A

150Ø

E/A

350Ø T/A

-

300x250

S-2

-

300x250

S-2

VV

VV

100 SAN@1%

SH-1

SH-1

E

3 4

500x25090 L/s

R-2

350x150200 L/s

S-2

-

650x250

R-2

LAV-1

BS-23BS-24

BS-22

BS-21

MS-1

FC-2202

FC-2204

250Ø E/A

100 S

T10

0 ST

350Ø

S/A

350Ø

S/A

150Ø

E/A

200Ø S/A

200Ø R/A WC-1

WC-1

V V V

V V V

LAV-1 LAV-1

LAV-1 LAV-1 LAV-1

FD-2

FD-1

FD-1

UR-1UR-1

350x350 S/A

200Ø S/A

200x20070 L/s

E-14@

250Ø E/A

5@

3@

V V

RD

RD

KS-1 KS-1

150Ø S/A

350x350 S/A750x350 E/A

CONCEALED FLUSH VALVE

VENT CLEANOUT CONCEALEDBEHIND FLUSH VALVE PLATE

SANITARY CLEANOUT BEHINDROUND STAINLESS STEEL

CLEANOUT COVER ON CENTRELINE OF URINAL

TIE VENTS IN MAIN SAN VENTTHROUGH ROOF

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

1 : 50

LB

LB/DRC

DRC

21-3180

MECHANICAL WASHROOMDETAILS

M401

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

1 : 50M201NORTH MAIN FLOOR WASHROOM DETAIL1

1 : 50M202SECOND FLOOR WASHROOM DETAIL2

1 : 50URINAL SANITARY PIPING DETAIL3

TRUE NORTH

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

HP-2A

P

HP-2B

HP-1

H HP1 RTAIT

H HP2 RTAIT

HP-4A HP-4B

H HP4 RTAIT

HP-3

TH HP3 RTAI

HP-5A HP-5B

H HP5 RTAIT

PARALLEL TEMPEREDWATER PUMPS WITH

INTEGRAL SPEEDCONTROL2@ 5.2L/s

P-1B

PP

P-1A

200 T

WS

200 T

WR

P

P-2B

PP

P-2A

VSD

VSD

H P2A SH P2A C

DIDO

H P2A VAO

GEO EXCHANGE TRANSFERPUMPS WITH BMSCONTROLLED INTEGRAL VFD2@ 3.0L/s

H P2B SH P2B C

DIDO

H P2B VAO

H GE STAIT

GEO EXCHANGEMANIFOLD ANDPIPING BY OTHERS

TO ACTIVE SLABLOOPS

H AS ST

H AS RT

P-4

AI

AI T

T

T

P

HP-6

P

P

P-3

P

T H TW STAI

TT TW RTAI

H HP6 RTAI

BT-1

T

WEST MECHANICALCLOSET

FD

POTFEEDER

MAV

100mm INLET/OUTLETAIR SEPARATOR

EXPANSION TANKAND GLYCOL FILLTANK

HEAT PUMPCONTROLLER

AIRPURGER

BMS MAPPEDPOINTS

GFT-2 ET-2

GFT-1 ET-1

VSDH P3 SH P3 C

DIDO

H P3 VAI

FD

POTFEEDER

MAV

TH OATAI

COMBINED PUMP ANDDIFFERENTIALPRESSURE CONTROL1.0L/s

WATER TO WATERHEAT PUMP

VRF WATERSOURCE HEATPUMPS

VRF WATERSOURCE HEATPUMPS

VRF SYSTEMCONTROLLER

BMS MAPPEDPOINTS

FINE MESH STRAINERON SUPPLY

FINE MESH STRAINERON SUPPLY OF ALL

VRF HEAT PUMPS

VSD

VSD

H P1A SH P1A C

DIDO

H P1A VH P1B SH P1B C

DIDO

H P1B V

H GFT1 LADI

75 TWS

75 TWR

65 65

75

AI

AI

2-POSITION CONTROL VALVESINTERLOCKED WITH ALL VRF

HEAT PUMPS

2-POSITION CONTROL VALVESINTERLOCKED WITH ALL VRF HEAT PUMPS

P

P

PP

P

65 TWS65 TWR

P

P P

5050

40 40

4040

40 40

50

4040

65

65

BUFFER TANKCIRCULATION PUMP

2.3L/s

50

20% PROPYLENE GLYCOL BYVOLUME. COORDINATE GLYCOLPERCENTAGE AND MANUFACTURERWITH GEO FIELD CONTRACTOR

40% PROPYLENEGLYCOL BYVOLUME IFH LOOP

SUPPLY HEADER

RETURN HEADERPROVIDE 20mm HOSE BIBB C/WTHREADED HOSE CONNECTION

15mm PEX LOOPS IN FLOOR

MANIFOLD CONTAINMENT CABINET

SLAB TEMPERATURESENSOR

T

HWS

HWR

MAV

P

PNCSPACE TEMPERATURE

SENSOR

T

H IFH1 SLTAI

H IFH1 RTAI

H IFH1 CVAO

3-WAY MODULATING CONTROL VALVE IN LIEU OF2-WAY VALVE ON STORAGE ROOM IFH LOOP ONLY

2-WAY MODULATING CONTROL VALVETO CONTROL SLAB TEMPERATURE

E/A

E/A

O/A

S/A

E/AO/A

E/A

ERV-1

H ERV1 SH ERV1 C

DIDO

H ERV1 FCDO

H ERV1 RTAIT

H ERV1 RHAIH

T

HH ERV1 STAIH ERV1 SHAI

F H ERV1 AFAI

ERV-1 FLOW GRID

MERV-13 FILTRATION

S/A

Dm

E/A

Dm

H ERV1 RVDO

S/A

DmH ERV1 OVDO

LOUNGE/GAMES S/A OFFICE/LUNCH S/A

S/A

Dm

S/A

Dm

RESTAURANT S/A OFFICE/LUNCH S/A

2ND FLRWASHROOM E/A

E/A

Dm

E/A

Dm

WELLNESS E/A RESTERAUNTGENERAL E/A

E/A

Dm

RESTAURANTWASHROOM E/A

OFFICE SPACE/RESTAURANTVENTILATION CONTROL

2-POSITIONCONTROL DAMPERS

H ERV1 SVAI

VSD

VSD

H ERV1 COAICO

H ERV1 RFAI2

REF

RETURN AIR TEMPERATURE,HUMIDITY, CARBON DIOXIDE,AND REFRIGERANT SENORS

ELECTRIC TEMPERING COIL

E/A

S/A

E/A

H ERV2 SH ERV2 C

DIDO

H ERV2 FCDO

E/A

O/A

E/A

O/A

ERV-2

H ERV2 STAIT

H ERV2 RTAIT

H ERV2 RHAIH

H ERV2 SHAIH

MERV-13 FILTRATION

S/A

H ERV2 AFAI

ERV-2 FLOW GRID

F

RETURN AIR TEMPERATURE,HUMIDITY, CARBON DIOXIDE,AND REFRIGERANT SENORS

H ERV2 COAICO

H ERV2 RFAI2

REF

ELECTRIC TEMPERING COIL

BFP

WM

NC

PROVIDE APPROVED BACKFLOW PREVENTIONDEVICE AND STRAINER ON 65mm WATER SERVICE

WATER METER c/w VOLUMEMONITORING TIED TO BMS

65 DCW TO BUILDING

PRESSURE REDUCING VALVE IF REQUIRED BYLOCAL CODES

P WM VAI

WM

P CR1WM VAI

WM

P CR2WM VAI50 CRU2 DOMESTIC WATER VOLUME METER50 CRU1 DOMESTIC WATER VOLUME METER30 RAINWATER MAKE UP DOMESTIC WATER VOLUME METER

WM

P RMUWM VAI

DWH-1

FD

20 DHWR FROM BUILDING

40 DHW TO BUILDING

40 DCW FROM WATER METER

DWRP-1

40

T

P DWRP SP DWRP E

DIDO

20

P DHWR TAIP DWH1 TAI

BUILDING THERMOSTATIC MIXING VALVESET TO 50°C

P HWM VAIW

M

DOMESTIC HOT WATER VOLUME METER

20 GREEN WALL SUPPLY20

NC

GREENWALL THERMOSTATIC MIXING VALVESET TO 18°C. CONSULT GREENWALLSUPPLIER FOR REQUIREMENTS

40NC

BFP

APPROVED BACKFLOWPREVENTION AS REQUIRED P GWM VAI

WM

HEAT TRAP

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

1 : 50

LB

LB/DRC

DRC

21-3180

MECHANICALSCHEMATICS

M500

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

NTSM500TEMPERED WATER AND ACTIVE SLAB WATER SCHEMATIC2

NTSM500ACTIVE SLAB HEADER DETAIL3

NTSM500ERV-1 ENERGY RECOVERY UNIT CONTROLS SCHEMATIC4

NTSM500ERV-2 ENERGY RECOVERY UNIT CONTROLS SCHEMATIC5

NTSM500WATER METER SCHEMATIC1

NTSM500DOMESTIC WATER HEATING SCHEMATIC6

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

HP-1RWEYQ84PTJU -HR

31.8Strainer

*

1.20l/s

31.8

12.7

Inlet

Outlet

Drain

3.0m [3]

KHRP25A33T9.5x22.2x19.1

BS-11BSVQ36PVJU

0.3m6.4x12.7x9.5 *

FC-1101FXMQ18PVJU

11.3m [8]6.4x12.7 *

0.4m

KHRP26A33T9.5x22.2x19.1

BS-12BSVQ60PVJU

0.3m9.5x15.9x12.7

FC-1103FXMQ48PVJU

5.0m [7]9.5x15.9

1.0m

KHRP26A22T9.5x15.9

FC-1104FXMQ24PVJU

1.0m [3]9.5x15.9

FC-1102FXAQ07PVJU

7.0m [4]6.4x12.7

HP-2RWEYQ144PTJU -HR

RWEYQ72PTJU -HR RWEYQ72PTJU -HR

9.5x19.1x15.9 9.5x19.1x15.9

BHFP26MA56U

31.8Strainer

*

2.02l/s

31.8

12.7

31.8Strainer

*

1.01l/s

31.8

12.7

Inlet

Outlet

Drain

18.0m [6]

KHRP25M72TU12.7x28.6x22.2 *

BS-21BSVQ36PVJU

0.3m6.4x12.7x9.5 *

FC-2201FXHQ12MVJU

23.3m [7]6.4x12.7 *

0.3m

KHRP25A33T9.5x22.2x19.1

BS-22BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-2202FXMQ30PVJU

2.8m [5]9.5x15.9

0.3m

KHRP25A33T9.5x22.2x19.1

BS-23BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-2203FXMQ24PVJU

13.0m [8]9.5x15.9

BS-24BSVQ60PVJU

0.3m9.5x15.9x12.7

1.5m

KHRP26A22T9.5x15.9

FC-2204FXMQ30PVJU

1.0m [3]9.5x15.9

FC-2205FXHQ24MVJU

16.9m [6]9.5x15.9

HP-3RWEYQ84PTJU -HR

31.8Strainer

*

1.20l/s

31.8

12.7

Inlet

Outlet

Drain

6.9m [4]

KHRP25A33T9.5x22.2x19.1

BS-31BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-1306FXMQ24PVJU

4.0m [6]9.5x15.9

0.4m

KHRP25A33T9.5x22.2x19.1

BS-32BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-1304FXMQ24PVJU

15.0m [7]9.5x15.9

0.4m

KHRP26A22T9.5x15.9x12.7

BS-33BSVQ36PVJU

0.3m6.4x12.7x9.5 *

FC-1307FXHQ12MVJU

26.0m [7]6.4x12.7 *

5.0m [3]

KHRP26A22T9.5x15.9

FC-1305FXMQ07PVJU

1.0m [2]6.4x12.7

3.9m

KHRP26A22T9.5x15.9

FC-1301FXHQ12MVJU

3.0m [3]6.4x12.7

2.3m

KHRP26A22T6.4x12.7

FC-1302FXHQ12MVJU

1.0m [2]6.4x12.7

FC-1303FXAQ07PVJU

4.0m [3]6.4x12.7

HP-4RWEYQ144PTJU -HR

RWEYQ72PTJU -HR RWEYQ72PTJU -HR

9.5x19.1x15.9 9.5x19.1x15.9

BHFP26MA56U

31.8Strainer

*

2.02l/s

31.8

12.7

31.8Strainer

*

1.01l/s

31.8

12.7

Inlet

Outlet

Drain

23.0m [9]

KHRP25M72TU12.7x28.6x22.2 *

BS-41BSVQ36PVJU

0.3m9.5x15.9x12.7

1.0m

KHRP26A22T9.5x15.9

FC-2401FXAQ07PVJU

11.3m [6]6.4x12.7

FC-2402FXMQ18PVJU

13.5m [8]6.4x12.7

0.3m

KHRP25A33T9.5x22.2x19.1

BS-42BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-2405FXMQ24PVJU

14.5m [8]9.5x15.9

0.3m

KHRP26A22T9.5x15.9x12.7

BS-43BSVQ36PVJU

0.3m9.5x15.9x12.7

1.0m [1]

KHRP26A22T9.5x15.9

FC-2410FXAQ07PVJU

7.0m [7]6.4x12.7

FC-2408FXMQ18PVJU

5.0m [7]6.4x12.7

0.3m

KHRP26A22T9.5x15.9

FC-2404FXMQ07PVJU

5.5m [5]6.4x12.7

0.3m

KHRP26A22T9.5x15.9

FC-2403FXAQ07PVJU

4.0m [4]6.4x12.7

0.3m

KHRP26A22T6.4x12.7

FC-2406FXAQ07PVJU

2.5m [4]6.4x12.7

0.3m

KHRP26A22T6.4x12.7

FC-2407FXAQ07PVJU

2.5m [4]6.4x12.7

FC-2409FXMQ07PVJU

10.0m [6]6.4x12.7

HP-5RWEYQ144PTJU -HR

RWEYQ72PTJU -HR RWEYQ72PTJU -HR

9.5x19.1x15.9 9.5x19.1x15.9

BHFP26MA56U

31.8Strainer

*

2.40l/s

31.8

12.7

31.8Strainer

*

1.20l/s

31.8

12.7

Inlet

Outlet

Drain

23.1m [10]

KHRP25M72TU12.7x28.6x22.2

BS-51BSVQ60PVJU

0.3m9.5x15.9x12.7

4.0m [2]

KHRP26A22T9.5x15.9

FC-3503FXMQ36PVJU

2.0m [2]9.5x15.9

20.0m [5]

KHRP26A22T9.5x15.9

FC-3501FXHQ12MVJU

2.5m [2]6.4x12.7

FC-3502FXHQ12MVJU

2.5m [2]6.4x12.7

0.3m

KHRP25A33T9.5x22.2x19.1

BS-52BSVQ36PVJU

0.3m9.5x15.9x12.7

FC-3504FXMQ24PVJU

7.6m [3]9.5x15.9

0.3m

KHRP26A33T9.5x22.2x19.1

BS-53BSVQ60PVJU

0.3m9.5x15.9x12.7

7.0m [6]

KHRP26A22T9.5x15.9

FC-3509FXMQ30PVJU

7.0m [6]9.5x15.9

FC-3505FXHQ24MVJU

19.0m [8]9.5x15.9

6.0m [3]

KHRP26A22T9.5x15.9

FC-3506FXAQ07PVJU

8.0m [3]6.4x12.7

0.3m

KHRP26A22T6.4x12.7

FC-3507FXAQ07PVJU

8.0m [3]6.4x12.7

6.0m [3]

KHRP26A22T6.4x12.7

FC-3508FXMQ07PVJU

0.5m [3]6.4x12.7

FC-3510FXAQ07PVJU

4.0m [4]6.4x12.7

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

1 : 35

LB

LB/DRC

DRC

21-3180

MECHANICALSCHEMATICS

M501

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

NTSM501MAIN FLOOR WEST (HP-1) VRF SCHEMATIC1

NTSM501SECOND FLOOR WEST (HP-2) VRF SCHEMATIC2

NTSM501MAIN FLOOR EAST (HP-3) VRF SCHEMATIC3

NTSM501SECOND FLOOR EAST (HP-4) VRF SCHEMATIC4

NTSM501THIRD FLOOR EAST (HP-5) VRF SCHEMATIC5

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

T: 780.440.2806 W: www.clarkeng.ca

9409 98 AvenueEdmonton AB T6C 2C8

CLARK ENGINEERING INC.PERMIT #7440

All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.

APRIL 11TH, 2014

P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt

0

LB

LB/DRC

DRC

21-3180

MECHANICAL SCHEDULES

M600

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

DIFFUSER/GRILLE SCHEDULE

UNIT NO. MAKE MODEL DESCRIPTION COUNT REMARKSE-1 PRICE 10/F/A/B12 PERFORATED FACE RETURN GRILLE 24E-2 PRICE SDGER/A/B12 SPIRAL DUCT MOUNTED RETURN GRILLE 3 SPIRAL DUCT MOUNTED, ALUMINUM CONSTRUCTION RETURN GRILLE C/W COUNTERSUNK SCREW HOLES, AND WHITE

POWDER COATE-3 PRICE 530/F/L/A/B12 LOUVRED FACE RETURN GRILLE 1L-1 PRICE ZE445 6R-1 PRICE 10/F/A/B12 PERFORATED FACE RETURN GRILLE 4R-2 PRICE 530/F/L/A/B12 LOUVRED FACE RETURN GRILLE 6S-1 PRICE SDGE/DD/VCS3/A/B12 SPIRAL DUCT MOUNTED SUPPLY GRILLE 76 SPIRAL DUCT MOUNTED, ALUMINUM CONSTRUCTION GRILLE C/W OPPOSED BLADE DAMPER, COUNTERSUNK SCREW HOLES,

AND WHITE POWDER COATS-2 PRICE 520/F/L/A/B12 LOUVRED FACE SUPPLY GRILLE 7S-3 PRICE DF1W/PC12 FLUSH MOUNT DISPLACEMENT DIFFUSER AND SUPPLY PLENUM 7 FIELD PAINT TO MATCH. COORDINATE WITH ARCHITECT

VRF BRANCH SELECTOR UNIT SCHEDULE

UNIT NO. MAKE MODEL NUMBER BRANCHESMAX. BRANCH CAPACITY ELECTRICAL LOCATION

REMARKSMBH kW ELECTRICAL REMARKS VOLTS NO NAMEBS-11 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 RT-01 CRU - 1BS-12 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 RT-01 CRU - 1BS-21 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-09 HALLWAYBS-22 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-09 HALLWAYBS-23 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-10-1 WASHROOM-1BS-24 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SH-10-1 WASHROOM-1BS-31 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-32 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-33 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-41 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-42 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-43 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-51 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITORBS-52 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITORBS-53 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITOR

VRF HEAT PUMP SCHEDULE

UNIT NO. MAKE MODELFLOW PIPE LOSS HEATING COOLING ELECTRICAL LOCATION

REMARKSGPM L/s ft kPa MBH kW MBH kW REQUIREMENTS VOLTS NO NAMEHP-1 DAIKIN AC VRV-WIII 7-TON 19.0 1.2 7.5 22 90 26 80 23 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-2A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-2B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-3 DAIKIN AC VRV-WIII 7-TON 19.0 1.2 7.5 22 90 26 80 23 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-4A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-4B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-5A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-5B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICAL

VRF TERMINAL UNIT SCHEDULE

UNIT NO. MAKE MODELAIRFLOW HEATING COOLING ELECTRICAL LOCATION

REMARKSCFM L/s MBH kW MBH kW VOLTS ELECTRICAL REMARKS NO NAMEFC-1101 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A BALANCE FRESH AIR TO 300 L/SFC-1102 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A WE-03-2 RECEPTION-2 AIR TRANSFER FROM ATRIUMFC-1103 DAIKIN AC FXMQ48PVJU 1377 650 54 16 48 14 208/1/60 MCA - 3.4A MOCP - 15A RT-01 CRU - 1 BALANCE FRESH AIR TO 300 L/SFC-1104 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A RT-01 CRU - 1 BALANCE FRESH AIR TO 105 L/SFC-1301 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SE-10 SERVER NO FRESH AIRFC-1302 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SE-10 SERVER NO FRESH AIRFC-1303 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A OF-02 NICHE BALANCE FRESH AIR GRILLE TO 10 L/SFC-1304 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1305 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1306 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1307 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-02 ATRIUM BALANCE ATRIUM FRESH AIR TO 200 L/SFC-2201 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SH-06-1 GAMES ROOM-1 BALANCE FRESH AIR GRILLE TO 30 L/SFC-2202 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A SH-09 HALLWAY BALANCE FRESH AIR TO 140 L/SFC-2203 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A SH-05-1 LOUNGE-1 BALANCE FRESH AIR TO 60 L/SFC-2204 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A SH-10-1 WASHROOM-1 BALANCE FRESH AIR TO 265 L/SFC-2205 DAIKIN AC FXHQ24MVJU 710 335 27 8 24 7 230/1/60 MCA - 1A MOCP - 15A 53 Space BALANCE ATRIUM FRESH AIR TO 200 L/SFC-2401 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-14 MEETING ROOM (14 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-2402 DAIKIN AC FXMQ18PVJU 630 295 20 6 18 5 208/1/60 MCA - 1.6A MOCP - 15A BH-10 OFFICE BALANCE FRESH AIR TO 50 L/SFC-2403 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-13 MEETING ROOM (6 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-2404 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A BH-12 OFFICE BALANCE FRESH AIR TO 30 L/SFC-2405 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A BH-10 OFFICE BALANCE FRESH AIR TO 65 L/SFC-2406 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space GENERAL EXHAUST TO DRAW AIR FROM ATRIUMFC-2407 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-05 PRINTER ROOM PRINTER ROOM EXHAUSTEDFC-2408 DAIKIN AC FXMQ18PVJU 630 295 20 6 18 5 208/1/60 MCA - 1.6A MOCP - 15A BH-09 OFFICE BALANCE FRESH AIR TO 35 L/SFC-2409 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A BH-09 OFFICE BALANCE FRESH AIR TO 30 L/SFC-2410 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-22 MEETING ROOM (14 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3501 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-18-2 HOT DESKS-2 BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3502 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-18-2 HOT DESKS-2 BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3503 DAIKIN AC FXMQ36PVJU 1130 535 40 12 36 11 208/1/60 MCA - 2.9A MOCP - 15A OC-21 OFFICE BALANCE FRESH AIR TO 135L/SFC-3504 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OC-22 PRINTER ROOM BALANCE FRESH AIR TO 70 L/SFC-3505 DAIKIN AC FXHQ24MVJU 710 335 27 8 24 7 230/1/60 MCA - 1A MOCP - 15A BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3506 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3507 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3508 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A OC-24 OFFICE BALANCE FRESH AIR TO 40 L/SFC-3509 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A OC-23 OFFICE BALANCE FRESH AIR TO 110 L/SFC-3510 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A OC-22 PRINTER ROOM PRINTER ROOM EXHAUSTED

ENERGY RECOVERY VENTILATION UNIT SCHEDULE

UNIT NO MAKE MODELAIRFLOW DUCT LOSS ELECTRICAL

LOCATION REMARKSCFM L/s in wg Pa HP VOLTAGEERV-1 TEMPEFF RG 5400 2970 1400 3.0 750 6.0 208/3/60 HIGH EFFICIENY DUAL CORE ENERGY RECOVERY VENTILATOR c/w SINGLE POINT POWER

CONNECTION, ELECTRIC REHEAT, MERV 13 FILTERSERV-2 TEMPEFF RGSP 2700 2120 1000 3.0 750 7.0 208/3/60 HIGH EFFICIENY DUAL CORE ENERGY RECOVERY VENTILATOR c/w SINGLE POINT POWER

CONNECTION, ELECTRIC REHEAT, MERV 13 FILTERS

PUMP SCHEDULE

UNIT NO. MAKE MODELFLOW HEAD ELECTRICAL

SERVICELOCATION

REMARKSGPM L/s Ft H2O kPa POWER RPM V/Ph/Hz NO NAMEDWRP-1 TACO 006B 4 0.3 7.0 21 25 W 120/1/60 DOMESTIC HOT WATER RECIRC PUMP SE-06 MECHANICALP-1A TACO SKV2007 83 5.2 40.0 120 1500 W 1800 208/3/60 TEMPERED WATER CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET

COMMUNICATION INTERFACE. PROVIDE UPRIGHT MOUNTING PLATE FOR VFDP-1B TACO SKV2007 83 5.2 40.0 120 1500 W 1800 208/3/60 TEMPERED WATER CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET

COMMUNICATION INTERFACE. PROVIDE UPRIGHT MOUNTING PLATE FOR VFDP-2A TACO 1919 47 3.0 45.0 135 1250 W 1800 208/3/60 GEO FIELD CIRCULATION SE-06 MECHANICAL BMS CONTROLLED PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET

COMMUNICATION INTERFACEP-2B TACO 1919 47 3.0 45.0 135 1250 W 1800 208/3/60 GEO FIELD CIRCULATION SE-06 MECHANICAL BMS CONTROLLED PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET

COMMUNICATION INTERFACEP-3 TACO 1911 16 1.0 20.0 60 375 W 3600 120/1/60 ACTIVE SLAB CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PUMP OPERATION. PROVIDE FACTORY BACNET

COMMUNICATION INTERFACEP-4 TACO 1915 36 2.3 29.0 87 500 W 3600 120/1/60 ACTIVE SLAB BUFFER TANK

CIRCULATIONSE-06 MECHANICAL

P-5 MYERS PQP10 25 1.6 90.0 269 751 W 208/1/60 RAINWATER PRESSURE PUMP RT-01 CRU - 1 c/w PRESSURE PUMPING PACKAGE AND STAND ALONE CONTROLS. COORDINATE WITHIRRIGATION CONTRACTOR FOR EXACT REQUIREMENTS

TANK SCHEDULE

UNIT NO. MAKE MODEL SERVICEVOLUME PRESSURE DIMENSIONS LOCATION

REMARKSGal. L MAX RELIEF HEIGHT WIDTH/DIA NO NAMEBT-1 LOCHINVAR SBT080 ACTIVE SLAB BUFFER TANK 80 303 1770 mm 610 mm SE-06 MECHANICAL STAINLESS STEEL INSULATED BUFFER TANKET-1 AMTROL AX-40V TW EXPANSION TANK 22 82 125 psi 150 psi 750 mm 410 mm SE-06 MECHANICAL UPRIGHT DIAPHRAGM EXPANSION TANK c/w SIGHT GLASSET-2 AMTROL AX-20V 11 41 125 psi 150 psi 670 mm 300 mm SE-06 MECHANICAL UPRIGHT DIAPHRAGM EXPANSION TANK c/w SIGHT GLASSGFT-1 AXIOM SF-100 GLS FILL 20 75 1240 mm 610 mm SE-06 MECHANICAL AUTOMATIC GLYCOL FILL TANK c/w FACTORY LOW LEVEL ALARM TIED INTO BMSGFT-2 AXIOM MF200 GLS FILL 6 23 410 mm 300 mm SE-06 MECHANICAL AUTOMATIC GLYCOL FILL TANK c/w FACTORY LOW LEVEL ALARM TIED INTO BMSRWT-1 ZCL COMPOSITES Z86SW RAINWATER STORAGE 7000 26498 6000 mm 2500 mm COMPOSITE STORAGE TANK c/w 900Ø MAN HOLE, 100mm INLET, 100mm

OVERFLOW

FAN SCHEDULE

UNIT NO. MAKE MODELAIR FLOW DUCT LOSS MOTOR LOCATION

REMARKSCFM L/s in wg Pa RPM W V/Ph/Hz NO NAMEEF-1 GREENHECK SP-A410 410 190 0.1 25 1000 120 120/1/60 SE-07 ELECTRICAL ELECTRICAL ROOM HEAT REJECTION FANEF-2 GREENHECK SP-A410 410 190 0.1 25 1000 120 120/1/60 SE-06 MECHANICAL MECHANICAL ROOM HEAT AND REFRIGERANT REJECTION FANEF-3 GREENHECK CSP-A390 390 190 0.2 60 1350 140 120/1/60 SE-07 ELECTRICAL SERVER ROOM HEAT REJECTION FANSPF-1 GREENHECK CSP-A410 405 190 0.1 35 1200 120 120/1/60 ES-08 CORRIDOR STAIRWELL PRESSURISATION FAN TIED INTO FIRE ALARM PANELSPF-2 GREENHECK CSP-A410 405 190 0.2 60 1200 120 120/1/60 ES-01 CORRIDOR STAIRWELL PRESSURISATION FAN TIED INTO FIRE ALARM PANEL

DOMESTIC WATER HEATER SCHEDULE

UNIT NO. MAKE MODEL VOLUME

FIRST HOURRATING MAX. HEAT ELECTRICAL LOCATION

REMARKSGPH L/H MBH kW REMARKS VOLTS NO NAMEDWH-1 AO SMITH PHPT-80 300 L 84.0 5.3 15 4.5 4500W MAX. 208/1/60 SE-06 MECHANICAL HYBRID ELECTRIC WATER HEATER. 2000W HEAT PUMP, 4500W TRADITIONAL ELECTRIC

PLUMBING FIXTURE SCHEDULE

FIXTURE TYPE DESCRIPTION COUNTFD-1 FLOOR DRAIN - WASHROOM Drain: 3 inch dura-coated cast iron floor drain with invertible membrane clamp and adjustable collar with “Type B” polished nickel bronze strainer. Zurn model ZN-415-B 6FD-2 FLOOR DRAIN - SERVICE AREA Drain: 3 inch dura-coated cast iron floor drain with invertible membrane clamp and adjustable collar with “Type B” polished nickel bronze strainer. Zurn model ZN-415-B 10FD-3 FLOOR DRAIN - SERVICE AREA c/w FUNNEL Drain: 3 inch dura-coated cast iron body with bottom outlet, and adjustable collar c/w “Type BF” polished nickel bronze open throat oval funnel grate. Zurn model ZN-415-BF 3KS-1 SINK - KITCHEN DOUBLE Basin: 775x450, 18 gauge stainless steel counter mounted, double equal basin. Franke Model D6410PCB-1

Trim: Polished Chrome finish, counter mounted, 6.8LPM single lever faucet, aerator, no side spray. Kohler Model Purist K7507.2

LAV-1 STANDARD LAVATORY Basin: 550mm x 560mm, vitreous china, self-rimming, 3/4 counter, concealed front overflow. American Standard Mezzo Series Model 996001Trim: 2LPM, 10 second run time, polished chrome finish, aerator, single supply, thermal mixing, laminar flow, hydropower charging sensor faucet. Toto Model Helix TEL5LC.

10

MS-1 600x600 MOP SINK Basin: Square, molded stone, plain curbs, 610mm x 610mm x 254mm deep (24” x 24” x 10”). Stainless steel drain with strainer, 76mm (3”) outlet. Fiat Model MSB2424. OrEquivalent.Trim: Chicago model 897-369XK wall mounted two handle faucet, 203mm (8”) centre-set, solid brass exposed body construction, ceramic 1/4 turn cartridge, unrestricted hoseend outlet, atmospheric vacuum breaker, metal red and blue index buttons, 60mm (2-3/4”) long lever handles with vandal-resistant screw, adjustable wall brace. Include stainlesssteel back splash panel. Or Equivalent.

4

RD-1 STANDARD ROOF DRAIN Drain: 300mm thermally broken roof drain. Dura-coated cast iron body with combination membrane flashing clamp/gravel guard and poly dome. Zurn model Z-121. 8RD-2 PATIO DRAIN Drain: Patio area drain, Thermally broken, dura-coated cast iron body with 75mm bottom outlet and combination invertible membrane clamp, vertically adjustable nickel-bronze

head with clamp collar. Zurn model2

SH-1 SHOWER TRIM Surround: Built in place shower surround. Refer to architectural drawings for detailing.Trim: American Standard Moments shower head and trim Model T506/R120S pressure balancing mixing valve, brass body, integral hot limit stop, screwdriver stops. Brass wallescutcheon, 6.6 L (1.75 US Gal) flow per minute adjustable 3 function showerhead. American Standard hand shower Model 1662.604 5.7 LPM (1.5 GPM) maximum flow rate, spraypattern adjust. Watts shower drain Model FD-100-A 2" (51mm) outlet, epoxy coated cast iron, anchor flange, adjustable round nickel bronze strainer, reverisble clamping collar.

5

UR-1 URINAL W/ CONCEALED FLUSH VALVE Urinal: Vitreous china, 0.5L low consumption washout, wall hung urinal with flushing rim, integral trap, stainless steel strainer, 20mm back spud. American Standard Washbrook SeriesModel 6515005.Carrier: J.R. Smith Model 0637 off the floor supportFlush Valve: Concealed, sensor actuated, single flush, hydropower charging flushometer with 20mm back spud connection, angle stop and vacuum breaker. Toto ModelTEU2UN11.

4

WC-1 FLUSH VALVE TOILET Bowl: High Mount 1.1 US gallon (4 liter) flush elongated washdown bowl with open flushing rim. Back spud connection. 54mm trapway as standard. American Standard MaderaSeries Model 3451.001.020Flush Valve: Concealed, battery powered, self regenerating, sensor actuated flushometer with 40mm back spud connection. Toto Model TET2GNSeat: Solid white plastic elongated open front seat, hinge with built-in check and stainless steel posts. Centoco Model AM1500STSCCSS.001.

11

ROOF

PENTHOUSE MECH. ROOM

- WEST EXTERIOR

WATER TO WATER HEAT PUMP SCHEDULE

UNIT NO. MAKE MODELSOURCE FLOW SOURCE LOSS LOAD FLOW LOAD LOSS HEATING COOLING ELECTRICAL LOCATION

REMARKSGPM L/s ft kPa GPM L/s ft kPa MBH kW MBH kW REQUIREMENTS VOLTS NO NAMEHP-6 WATERFURNACE NDW180R SE-06 MECHANICAL c/w BACNET INTERFACE45 2.8 6.9 21 36 2.3 7.1 21 125 36 165 48 MCA: 58.5A MOCP: 80A 208/3/60

RADIANT PANEL SCHEDULE

UNIT NO. MAKE MODEL W/m VOLTS REMARKSRP-1 OULETTE ODBA ARCHITECTURAL SERIES 787 W OPERATED BY BMS. PROVIDE SPACE TEMPERATURE SENSOR208/1/60

NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR

CONSTRUCTION

E

K

M

M

B

M

M

S

S

V

s

CM

F

G

ISO

MM

F

T

FS

EOL

ASD

BD

DD

M

S

BATT

T

FLUORESCENT STRIP LUMINAIRE

LUMINAIRES

POWER

FIRE ALARM

DATA

NOTES / ABBREVIATIONS

PUBLIC ADDRESS

PANEL BOARD DESIGNATIONPNL - M 6 E A

INDIVIDUAL PANEL DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600VFLOOR LEVEL SERVICEDCDP = CENTRAL DISTRIBUTION PANELBOARDPNL = BRANCH CIRCUIT PANELBOARD

TRANSFORMER DESIGNATION

TX - 1 E A

TRANSFORMER DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)FLOOR LEVEL SERVICEDTRANSFORMER

MOTOR CONTROL CENTER DESIGNATIONMCC - 1

INDIVIDUAL DESIGNATION NUMBERMOTOR CONTROL CENTER

LOW VOLTAGE RELAY CABINET DESIGNATION

LVRC M - 6 E AINDIVIDUAL DESIGNATION NUMBEREMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600VFLOOR LEVEL SERVICEDLOW VOLTAGE RELAY CABINET

CIRCUIT DESIGNATION2 E A 15

PANELBOARD CIRCUIT POSITION NUMBERPANELBOARD DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600V

MOTOR FEEDER DESIGNATIONMCC #STACK #CELL #

EQUIPMENT DESIGNATION

ABCXXX

CEILING SUSPENDED FLUORESCENTLUMINAIRE

SURFACE MOUNTED OR RECESSEDPOT LUMINAIRE

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

20 AMP RECEPTACLE

FOURPLEX RECEPTACLE

CONTROL MODULE

SPRINKLER FLOW VALVE

SPRINKLER GATE VALVE

HEAT DETECTOR

CATV

DATA

ISOLATION MODULE

MONITORING MODULE

PULL STATION

TAMPER SWITCH

SMOKE DETECTOR

HORN STROBE

SECURITYCARD READER

ELECTRIC STRIKE

KEYPAD

MAGNETIC LOCK

MOTION DETECTOR

PUSHBUTTON

BUZZER

ELECTROMAGNETIC DOOR LOCK

SPEAKER

MICROPHONE OUTLET

SPEAKER VOLUME CONTROL

SPEAKER HORN

CAT6 NAMING CONVENTION

3 V W 1 1 - 48

RACK #LOCATION SERVICED(ie. WEST)VOICEFLOOR LEVEL SERVICED

PATCH #PORT #

SITEDUPLEX REC

SINGLE POLE LUMINAIRE

SURFACE / RECESSED LUMINAIRE

WALL MOUNT DEVICE

CEILING MOUNT DEVICE

FLOOR MOUNT DEVICE

1050 Aff. (SYMBOL ABOVE POWER DEVICE) BLANK OFF DEVICE

WEATHERPROOF DEVICE

EXPLOSION PROOF DEVICE

GROUND FAULT PROTECTED DEVICE

EXISTING DEVICE TO REMAIN

RELOCATE EXISTING DEVICE

REMOVE EXISTING DEVICE

BO

WP

EXP

GF

ER

RL

R

RE-USE EXISTING DEVICERU

INDICATES DEVICE MOUNTED BELOWMILLWORK COORDINATE EXACT MOUNTINGHEIGHT WITH ARCH. DETAIL

*

MAIN DISTRIBUTION PANELMDP

SUB DISTRIBUTION PANELSDP

WIRE GUARDWG

LOW VOLATGELV

LOW VOLTAGE RELAY PANELLVRP

SURGE SUPPRESSION DEVICESP

MAGNETIC PROTECTION DEVICEMG

HANDS. OFF. AUTO.HOA

TRANSIENT VOLTAGE SURGE SUPPRESSION(LOW VOLTAGE)TVSS

TRANSFORMERT#

MOTOR CONTROL CENTERMCC

DRAWING KEYNOTER

MOTOR PROTECTION DEVICEMP

INDICATES DEVICE MOUNTED ABOVEMILLWORK COORDINATE EXACT MOUNTINGHEIGHT WITH ARCH. DETAIL

SURFACE MOUNTED FLUORESCENTLUMINAIRE

CEILING SUSPENDED POT LUMINAIRE

NURSE CALL

WALL MOTION WITH SWITCH BYPASS

LV SWITCH

208V SPECIALTY RECEPTACLE

CAR PARK PEDESTAL

END OF LINE RESISTOR

AIR SAMPLING DEVICE

BEAM DETECTOR

DISCONNECT

DUCT DETECTOR

NOTES / ABBREVIATIONS

BOLLARD

EQUIPMENT MOUNTING HEIGHT

POWER GENERAL NOTES

COMMUNICATION GENERAL NOTES

LIGHTING GENERAL NOTES

NOTES / ABBREVIATIONS

FIRE ALARM GENERAL NOTES

MOTION DETECTOR LINE VOLTAGE

MOTION DETECTOR LOW VOLTAGE

STROBE

EMERGENCY SIGN

EMERGENCY BATTERY PACK

EMERGENCY REMOTE HEAD

THERMOSTAT

DRAWING KEYNOTE#

LINE VOLTAGE DIMMERd

PROJECT GENERAL NOTES

SECURITY GENERAL NOTES

1. ALL LIGHTING WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING LIGHTING WIRING SHALL BE PAINTED YELLOW AND SHALL NOT CONTAIN WIRING THAT ISNOT PART OF THE LIGHTING SYSTEM.

2. CIRCUITS ARE INDICATED BESIDE ELECTRICAL EQUIPMENT. FOR EXAMPLE: "2A-1" INDICATES CIRCUIT 1 ON PANEL 2A. ELECTRICAL OUTLETS LABELED "GFI" ARE TO BEGROUND FAULT INTERRUPT TYPE OUTLETS.

3. MOUNTING HEIGHTS DIFFERING FROM THE TYPICAL HEIGHTS LISTED IN THE SPECIFICATION ARE INDICATED AS "+xxxx", WHERE xxxx IS THE HEIGHT ABOVE FINISHED FLOOR INmm.

4.CONTRACTOR IS RESPONSABLE FOR THE INSTALLATION OF A FULLY FUNCTIONAL LIGHTING SYSTEM. DRAWINGS IDENTIFY INTENT OF SYSTEMAND IT'S DEVICES.

1. ALL FIRE ALARM WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING FIRE ALARM WIRING SHALL BE PAINTED RED AND SHALL NOT CONTAIN WIRING THAT IS NOT PART OFTHE FIRE ALARM SYSTEM.

2. THE FIRE ALARM SYSTEM IS ADDRESSABLE WITH CLASS A WIRING. OUTGOING PATH AND RETURN PATH MUST BE IN SEPARATE CONDUIT. PROVIDE ISOLATION MODULES AS INDICATED ONDWGS.

3. ALL DOOR SECURITY WIRING AND CONDUIT IS TO BE PROVIDED UNDER THIS CONTRACT.

4. CONFIRM ANY AND ALL CHANGES TO FIRE ALARM DESIGN WITH THE ELECTRICAL CONSULTANT PRIOR TO INSTALLATION, LOCATIONS ARE TO BE DOCUMENTED AND PROVIDED WITHIN THE ASBUILT UPON COMPLETION OF CONSTRUCTION.

5. ISOLATION MODULES ON ARE TO BE INSTLLED ON BOTH SIDES OF FIRE SEPERATIONS AND AS INDICATED IN DRAWINGS.

6. FIRE ALARM SYSTEM TO BE PROGRAMMED AND PRE-VERIFIED PRIOR TO REQUEST FOR VERIFICATION/INSPECTION WITH ELECTRICAL CONSULTANT.

7. PROVIDE FIRE STOPPING (TO MATCH RATING OF FIREWALL) WHERE ELECTRICAL CONDUIT PENETRATES THROUGH A FIRE SEPARATION. REFER TO ARCHITECTURAL DRAWINGS FOR FIRESEPARATION LOCATIONS.

8. ALL CONDUIT TO BE INSTALLED FOR DEVICES ON EXPOSED CONCRETE IS TO BE INSTALLED IN CONCRETE. ONLY EXCEPTION ARE ELECTRICAL ROOMS, MECHANICAL ROOMS ANDCOMMUNICATION ROOMS. ATTENTION SHOULD BE MADE TO PROTECT INTERIOR OF JUNCTION BOXES FROM CONCRETE.

1. PROVIDE ALL ELECTRICAL CONNECTIONS TO DEVICES REQUIREING POWER WITHIN MILLWORK.

2. REFER TO MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR FOR ALL CONNECTIONS TO MECHANICAL EQUIPMENT.

3. ALL RECEPTACLE WITHIN 1m OF WATER SUPPLIES ARE TO BE PROTECTED WITH GFCI RECEPTACLES.

4. REFER TO ARCHITECTURAL DRAWINGS FOR ALL POWER LOCATED WITHIN AND AROUND MILLWORK PRIOR TO ROUGH-IN.

5. REFER TO MECHANICAL DRAWINGS M301,302,303 FOR FAN COIL LOCATIONS. A 20AMP CIRCUIT IS TO FEED A MAXIMUM OF 5-FC UNITS.

6. ALL TRANSFORMERS ARE TO BE K-RATED TO MITIGATE HARMICS.

7. ALL PNLs AND DISTRIBUTION CENTERS ARE TO HAVE 20% SPARE CAPACITY.

8. PROVIDE POWER TO ALL WINDOW OPERATORS.

9. CONDUCTOR AND DISTRIBUTION PANELS ARE OVERSIZED AS INDICATED TO HANDLE FUTURE UPS AND GENERATOR SIZE INCREASES AS WELL ASIMPROVING VOLTAGE DROP LOSSES. CABLE SIZES TO BE AS INDICATED UNLESS LARGER SIZE IS REQUIRED TO MEET CEC REQUIREMENTS.

10. ALL DISCONNECT SWITCHES ARE TO BE HEAVY DUTY, LOCKABLE IN 'OFF' POSITION.

18. ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL ALL STARTERS UNLESS OTHERWISE NOTED. (VFD'S ARE SUPPLIED BY MECHANICAL)

19. ELECTRICAL CONTRACTOR TO INSTALL ALL PILOT DEVICES UNLESS OTHERWISE NOTED ON MECHANICAL DRAWINGS.

20. WHERE EMT IS USED IN ABOVE GRADE SLABS, 90 DEGREE BONDS STUBBED OUT OF SLAB ARE TO BE IN EMT.

21. ELECTRICAL CONTRACTOR IS TO PROVIDE CONDUIT FOR ALL MECHANICAL CONTROLS WIREING INCLUDING TERMOSTATS, AND BMS CONTROLWIRING. COORDINATE WITH CONTROLS AND MECHANICAL CONTRACTOR ON SITE.

1. ALL COMMUNICATION WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING COMMUNICATION WIRING SHALL BE PAINTED BLUE AND SHALLNOT CONTAIN WIRING THAT IS NOT PART OF THE COMMUNICATION SYSTEM.

2. ALL COMMUNICATION CABLE TO BE CAT 6.

3. EACH LOW VOLTAGE SYSTEMS WITHIN THE BUILDING TO HAVE DIFFERENT COLOUR TO DISTIGUISH SYSTEM WITHIN COMMUNICATION ROOM..

4. ALL MECHANICAL EQUIPMENT TO BE CONNECTED BY COMMUNICATION CABLE.REFER TO MECHANICA DRAWINGS AND COORDINATE WITH MECHANICALCONTRACTOR.

5.REFER TO MECHANICAL DRAWINGS FOR LOCATION OF THEMOSTATS. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT FROM FAN COIL UNITS TOTHERMOSTAT LOCATIONS.

6. OWNER TO SUPPLY COMMUNICATION RACK PRIOR TO ELECTRICAL CONTRACTOR INSTALLING PATCH PANELS AND TESTING COMMUNICATION CABLING.

7. ELECTRICAL CONTRACTOR TO CONFIRM RACK POWER REQUIREMENTS PRIOR TO COMM ROOM ROUGH-IN.

NOTE: ALIGN ALL EQUIPMENT VERTICALLY AND HORIZONTALLY

FLOOR

FINISHED FLOORCONSOLIDATIONZONE BOX

RECESSFLOORBOX

DISCONNECT

STARTER

FOR

FIN

ISH

ED C

EILI

NG

HE

IGH

T

REF

ER T

O A

RC

HIT

ECTU

RAL

DR

AWIN

GS

2000

2100

1800

1400

300

FAHORN

EMERGENCYLIGHTINGUNIT

DOOR ENTRYPUSHBUTTON

SWITCH

PULLSTATION

EOLA

RECEPTACLEMECH. ROOM

RECEPTACLE

1500

TV TEL.INTER-COM

1. ALL CONDUIT FOR MAIN BUILDING SERVICE SPACE IS NOT TO ENTER TENANT SPACES..

2. ALL SWITCHES AND ELECTRICAL EQUIPMENT TO BE LABELED WITH LAMACOID LABELS UNLESS IT IS PART OF THE LIGHTING SYSTEM.

3. ALL FLOOR AND WALL PENETRATION REQUIRED TO BE MADE FOR THE ELECTRICAL INSTALLATION REQUIRES FIRE STOPPING, WHERE REQUIRED BY CODE.

4. CONDUIT IS TO BE RUN PARALLEL TO BUILDING LINES UNLESS OTHERWISE INDICATED. RIGID CONDUIT TO BE INSTALLED AS INDICATED IN DRAWINGS AND FOR ALL EXPOSEDAREAS AND UNDER ACCESS FLOOR.

5. PROVIDE ALL ELECTRICAL CONNECTIONS TO DEVICES REQUIREING POWER WITHIN MILLWORK.

6. MAXIMUM VOLTAGE DROP TO BE 3%.

7. ALL CONDUCTORS ARE TO BE COPPER UNLESS OTHERWISE NOTED.

8. JUNCTION BOXES ON EXTERIOR WALL TO HAVE 35mm OF SEMI-RIGID THERMAL INSULATION.

9. ALL CONDUIT IS TO BE LOCATED IN THE CONTRETE TOPPING ON THE SECOND AND THIRD FLOORS. NO CONDUIT IS TO BE INSTALLED SURFACE MOUNTED TO THE WOOD DECK.NO EXPESED CONDUIT ON CEILINGS OR WALLS EXCEPT IN SERVICE SPACES.

10. REFER TO ARCHITECTURAL EXTERIOR ELEVATION FOR LOCATION OF LIGHT FIXTURES, EXIT SIGNS, FIRE ALARM DEVICES AND OUTLETS. REFER TO A401-A408.

11. PROVIDE 100mm HOUSEKEEPING PADS BELOW ALL ELECTRICAL EQUIPMENT FLOOR MOUNTED IN SERVICE SPACES.

1. ALL CARD ACCESS WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING CARD ACCESS WIRING SHALL BE PAINTED PURPLE AND SHALL NOT CONTAIN WIRING THAT IS NOTPART OF THE CARD ACCESS SYSTEM.

2. CONTRACTOR TO PROVIDE CONDUIT AS REQUIRED BY THE DOOR HARDWARE AND SECURITY CONTRACTORS.

3. CONFIRM WITH LOCATION OF BARRIER FREE PUSH BUTTONS WITH DOOR HARDWARE CONTRACTOR PRIOR TO ROUGH-IN.

4. ELECTRICAL DRAWINGS IDENTIFY DOOR AND APPROXIMATE LOCATION OF THE CARD READERS AND SECURITY DEVICES. EXACT LOCATION OF DEVICES AND WIRING REQUIREMENTS ARE TOBE PROVIDED BY THE ARCHITECT AND DOOR HARDWARE CONTRACTOR.

5. ALL SECURITY AND CARD ACCESS EQUIPMENT AND CONTROLLES ARE TO BE LOCATED ON THE SECURED SIDE OF THE DOOR.HEAD END EQUIPMENT IS TO BE LOCATED WITHIN THEBUILDINGS COMMUNICATION ROOM.

This drawing is a copyright and the exclusive property of ManascIsaac Architects Ltd., and shall not be reproduced, nor distributed,nor used in any way without their written permission. Thearchitectural design and all other information shown on thisdrawing shall not be copied, nor loaned out, nor recreated withoutwritten consent by Manasc Isaac Architects Ltd.

DRAWING SCALE

PROJECT #

REVISION

NOTES

PERMITS AND SEALS

PROJECT NAME

CLIENT

SUBCONSULTANT

ARCHITECT

DRAWN BY

DESIGNED BY

CHECKED BY

DRAWING TITLE

DRAWING NUMBER REVISION

ISSUED FOR CONSTRUCTION2014/04/14

NTS

DP

MM

MM

21-3180

SYMBOL SCHEDULE /LEGEND

E000

MOSAIC CENTRE FORCONSCIOUS COMMUNITY

AND COMMERCE

NO. Y/M/D DESCRIPTION