PROJECT NUMBER:
C:\Users\rob\Documents\213180_MC4_ARCH_v14_rob.rvt
21-3180
MOSAIC CENTRE FORCONSCIOUS COMMUNITYAND COMMERCE
ISSUED FOR REVIEW
2014 APRIL 11th
STRUCTURAL MECHANICAL ELECTRICAL LANDSCAPEARCHITECTURAL
E000 SYMBOL SCHEDULE/LEGENDE100 ELECTRICAL SITE PLANE200 MAIN FLOOR LIGHTING AND FIRE ALARME201 SECOND FLOOR LIGHTING AND FIRE ALARME202 THIRD FLOOR LIGHTING LIGHTING AND FIRE ALARME203 ROOF LIGHTING AND FIRE ALARME204 LIGHTING AND FIRE ALARM DETAILSE300 MAIN FLOOR POWER AND DATAE301 SECOND FLOOR POWER AND DATAE302 THIRD FLOOR POWER AND DATAE303 ROOF POWER AND DATAE304 POWER AND DATA DETAILS
M100 MECHANICAL SITE PLANM200 MECHANICAL FOUNDATION PLANM201 MAIN FLOOR MECHANICAL PLUMBING,
HEATING AND COOLING PLANM202 SECOND FLOOR MECHANICAL PLUMBING,
HEATING AND COOLING PLANM203 THIRD FLOOR MECHANICAL PLUMBING,
HEATING AND COOLING PLANM301 MAIN FLOOR MECHANICAL VENTILATION
AND FIRE PROTECTION PLANM302 SECOND FLOOR MECHANICAL VENTILATION
AND FIRE PROTECTION PLANM303 THIRD FLOOR MECHANICAL VENTILATION
AND FIRE PROTECTION PLANM400 MECHANICAL ROOM DETAILSM401 MECHANICAL WASHROOM DETAILSM500 MECHANICAL SCHEMATICSM501 MECHANICAL SCHEMATICSM600 MECHANICAL SCHEDULES
CIVIL
N/A C001 SITE SERVICING PLAN
(C002 TO BE ISSUED UPON APPROVALS)
CONSTRUCTION VOL. 3
APRIL 11th
N/AN/A
NFHB
NFHB
NFHB
1
C
B
D
E
F
G
23
45
6
7
8
910
1112
13 1415 16
HJ
K
L
150 SANITARY SERVICE. SEE CIVIL SITE
SERVICING DRAWING COO1 FOR
CONTINUATION
FIRE DEPARTMENT CONNECTION BENEATH
OVERHANG BELOW
200 STORM SERVICE. SEE CIVIL
SITE SERVICING DRAWING C001
FOR CONTINUATION
ERV-1RD-1
RD-1
RD-2
RD-2
RD-1
RD-1
RD-1
RD-1
RD-1
RD-1DUAL CORE ENERGY RECOVERY VENTILATOR WITH
SERVICE CLEARANCE ON NORTH SIDE OF UNITTHERMALLY BROKEN ROOF DRAINS. REFER TO
ARCHITECTURAL FOR ROOF INSULATION SLOPE
AND ROOF DRAIN LOCATIONS
150 MUNICIPAL WATER SERVICE. SEE CIVIL SITE
SERVICING DRAWING C001 FOR CONTINUATION
EXISTING SITE FIRE HYDRANT
E/A&O/A
DUAL CORE ENERGY RECOVERY
VENTILATOR WITHIN
PENTHOUSE. REFER TO DWG5&
6/M400 FOR DETAIL
ROOFTOP NON FREEZE HOSE BIBB
12M400
BELOW GRADE 7,000GAL COMPOSITE
RAINWATER STORAGE TANK. COORDINATE
PLACMENT OF MANHOLE WITH LANDSCAPING
RWT-1
2M200
1190 MBH GAS SUPPLY TO BE
STUBBED OUT BELOW GROUND
ON WEST SIDE OF BUILDING
150 STORM SERVICE. SEE CIVIL DRAWINGS
FOR CONTINUATION
150 BUILDING STORM TO RAINWATER TANK
E/A&O/A
THERMALLY BROKEN PATIO ROOF DRAINS. REFER
TO ARCHITECTURAL FOR ROOF INSULATION SLOPE
AND ROOF DRAIN LOCATIONS
NFHB
P
PIPE DROP
PIPE RISE
ISOLATION VALVECHECK VALVE
DIRECTION OF FLOW
THREE WAY VALVE
SOLENOID/CONTROL VALVE
PRESSURE GAUGE
THERMOMETER
Y TYPE STRAINERUNION
PUMP
FLEX CONNECTION
BALANCING VALVE
HEATING WATER SUPPLYHEATING WATER RETURNCHILLED WATER SUPPLYCHILLED WATER RETURN
HWSHWR
CHWSCHWR
HEATING WATER SUPPLYHEATING WATER RETURNHEAT RECLAIM SUPPLYHEAT RECLAIM RETURN
GLSGLRHRSHRR
LIQUID HEAT TRANSFER
SYMBOL DESCRIPTION
PIPE FITTINGS
PIPE BOTTOM TAKE-OFFPIPE TOP TAKE-OFF
PIPE CAP
PIPE CONTINUATION
INSTRUMENT WELLNEEDLE VALVE/GAS COCK
SYMBOL DESCRIPTION
AUTOMATIC AIR VENT
MANUAL AIR VENTMAV
AAV
SUCTION DIFFUSER AND STRAINER
BACKFLOW PREVENTORBFP
REDUCED PRESSURE PRINCIPLEBACKFLOW PREVENTOR
RPPBFP
PIPE GUIDEPIPE ANCHOREXPANSION JOINT
DRAIN HOSE CONNECTIONQUICK CONNECT COUPLE
ROUND DUCT300Ø
RECTANGULAR DUCT300x200
SINGLE LINE DUCT300x200
DUCT DIMENSIONING
AIR DISTRIBUTIONS
ROUND DUCT
SUPPLY AIR
TURNING VANES
BALANCING DAMPER
BACKDRAFT DAMPER
BD
BDD
MOTORISED DAMPER
FIRE DAMPER
M
UPDN
RETURN AIR
EXHAUST AIR
FLEXIBLE DUCT
ACOUSTIC INSULATION
SUPPLY AIRS/ARETURN AIRR/AEXHAUST AIRE/AOUTSIDE AIRO/A
THERMOSTATT
HUMIDISTATH
FREEZE STATFz
CARBON MONOXIDE DETECTIONCO
FIRE WATER LINESPRINKLER LINESPRINKLER HEAD - PENDANT
SP
SPRINKLER
FW
SPRINKLER HEAD - UPRIGHT
SPRINKLER HEAD - SIDEWALL
DRYFLUSH
SANITARY ABOVE SLABBELOW SLAB
STORM ABOVE SLABBELOW SLAB
WEEPING TILE
SANSTSTWT
SANITARY VENTILATIONDOMESTIC COLD WATERDOMESTIC HOT WATERDOMESTIC HOT WATER RECIRC
VDCWDHWDWR
LIQUID HEAT TRANSFER
SAN
RECYCLED RAIN WATERLOW PRESSURE NATURAL GAS
RWNG
PRESSURE RELEIF VALVE
RADIANT PANEL SYMBOL
SIZECAPACITY
TYPE
IN-FLOOR HEATING SYMBOL
SPACINGLOOP LENGTH
LOOP NUMBER
PIPE SIZECAPACITY
PLUMBING FIXTURE TAG
__-__FIXTURENUMBER
FIXTURELETTER
WATER CLOSETWCLAVATORYLAVURINALURSINKSKDRINKING FOUNTAINDFMOP/JANITOR SINKMSSHOWERSH
EXHAUST FANEFFORCED FLOW UNITFFUNIT HEATERUHCABINET UNIT HEATERCUHFAN COILFCPUMPP
PLUMBING FIXTURE TAG
__-__EQUIPMENTNUMBER
EQUIPMENTLETTER
BOILERBHUMIDIFIERHUMHEAT EXCHANGERHERADIANT PANELRPTANKTK
SECTION LETTER
SECTION FLAG
DRAWING TO FIND SECTION
DETAIL NUMBER
DETAIL FLAG
DRAWING TO FIND DETAIL
TYPE ID.
KEYNOTE TAG_
REVISION NUMBER
REVISION NOTE TAG
_
AIR OUTLET TAG
SIZECAPACITY
TYPEQUANTITY @
SUPPLYSRETURNREXHAUSTETRANSFERTLOUVREL
AI
AO
VSD
PRESSURE REDUCING VALVETEST PORT
ANALOGUE INPUT TO BMS
CONTROLS
ANALOGUE OUTPUT FROM BMSDIGITAL INPUT TO BMSDIGITAL OUTPUT FROM BMS
DIDO
TEMPERATURE SENSORT
FREEZESTATFz
AQUASTATAq
SENSORS
VARIABLE SPEED DRIVE
LEGAL ADDRESSPLAN 072 9580BLOCK 1LOT 47
MUNICIPAL ADDRESSSAVARYN DRIVE + 91st STREET,SOUTH EDMONTON
GAS INFORMATION
DESCRIPTION
EQUIPMENT MBH m³/h
LOAD
440 12.4
KITCHEN WATER HEATER 150 4.23
TOTAL 1190 33.6
KITCHEN MAKE-UP AIR
KITCHEN EQUIPMENT 350 9.89
FUTURE 250 7.06
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
MECHANICAL SITE PLAN
M100
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 200M100MECHANICAL SITE VIEW1
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
CO
CO
COCO
CO
CO
CO
CO
CO
CO
1
C
B
D
E
F
G
2 3 4 5 7 9 10 11 12 13
FD FD
V
100 SAN AND 75 STACK VENT FROM SECONDFLOOR WASHROOM AND JANITOR ROOM200 ST
MS
150 S
AN@
1%
100 SAN@1%
100 S
AN@
1%
100 SAN@1%
150 ST@1%
200 ST@1%
100 SAN@1%
GROUND EXCHANGE PIPING FROM BOREFIELD INTO MECHANICAL ROOM BY OTHERS
FD
FD
V
150 ST FROM ROOF DRAINS
FD
75 SAN AND 75 STACK VENT FROMFAN COIL CONDENSATE PIPINGAND THIRD FLOOR JANITOR ROOM
150 ST FROM ROOF DRAINS
150 ST FROM ROOF DRAINS
75 SAN UP TO ELEVATOR PIT DRAIN. ENSUREELECTRIC TRACTION TYPE ELEVATOR
CRU-2 BELOW GRADE SANITARYROUGH IN PROVIDED WITH BASEBUILDING. PROVIDE TIE INS FORFIXTURES AS REQUIRED
100 SAN@1%
100 S
AN@
1%
75 S
AN@
2%
FD FD
75 S
AN@
2%
V
75 S
AN@
2%
FD
75 S
AN@
2% CRU-1 BELOW GRADE SANITARYROUGH IN PROVIDED WITH BASEBUILDING. PROVIDE TIE INS FORFIXTURES AS REQUIRED
URUR
WCWC
WC
LAVLAV
FD FD
FD
100 SAN@1%
75 S
AN@
2%
75 S
AN@
2%
V V V
150 ST@1%
75 SAN FROM GREENWALL TRENCH DRAIN.COORDINATE WITH GREEN WALL INSTALLER
FD
30mm RAINWATER BACK UP SUPPLYDOWN FROM MECHANICAL ROOM
2M200
RWT-1
150 SANITARY SERVICE. SEE CIVIL SITESERVICING DRAWING COO1 FOR CONTINUATION
200 STORM SERVICE. SEE CIVIL SITESERVICING DRAWING C001 FORCONTINUATION
150 MUNICIPAL WATER SERVICE. SEE CIVIL SITESERVICING DRAWING C001 FOR CONTINUATION
150 STORM OVERFLOW. SEE CIVILSITE SERVICING DRAWING C001FOR CONTINUATION
40mm RAINWATER SUCTION SUPPLYUP TO PUMPING SYSTEM
EXTENT OF 50mm RIGID INSULATION
1190 MBH GAS SUPPLY TO BESTUBBED OUT BELOW GROUNDON WEST SIDE OF BUILDING
FD
SHSH
SH
SHSH
V
VFD
200 ST@1%
150 ST@1%
75 S
AN@
2%
INV. 693.32
INV. 692.52
INV. 692.33
INV. 693.02
INV. 692.82
INV. 692.60
INV. 692.02
E
RWT-1
25,000L COMPOSITE RAINWATER STORAGETANK c/w 900mmØ MANHOLE
FACTORY SUPPLIED CONCRETE DEADMAN
150 ST OVERFLOW TIED INTO STORM SEWER
50mm RIGID INSULATION
150 ST SUPPLY TO RAINWATER TANK
30 DCW BACKUP SUPPLY
BACKUP SUPPLY FLOAT SYSTEM
50mm RAINWATER SUCTION PIPE c/wFOOT VALVE
900mm SOLID STEEL LOCKINGMANHOLE COVER
50 SUCTION RW SUPPLY TO PUMPING SYSTEM.COORDINATE FLOW AND PRESSURE REQUIREMENTSWITH IRRIGATION SYSTEM SUPPLIER
COMPACTED GRNULATED BACKFILL200mm COMPACTED GRAVEL BED
1870
NEW 150Ø PVC DOMESTICWATER MAIN
(4) @ 20Ø S.S. RODS c/w NUTS
300Ø MIN. SDR 35 PVC RISERSLEEVE
SAND COVER
GRAVELCONCRETE THRUST BLOCK TOCITY OF EDMONTON STANDARDS
JOINT RESTRAINER (TYPICAL)
JOINT RESTRAINER (TYPICAL)
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
MECHANICALFOUNDATION PLAN
M200
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M200MECHANICAL FOUNDATION PLAN1
1 : 50M200RAINWATER STORAGE TANK DETAIL2
NTSM200INCOMING WATER DETAIL3
TRUE NORTH
1. SEE CIVIL DRAWINGS SUBMITTED FOR APPROVALS ONDECEMBER 13, 2013 FOR CONTINUATION OF SITE SERVICES.
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
DN
DN
CO
CO
CO
CO
CO
WM
NFHB
NFHB
NFHB
NFHB
CO
CO
CO
WM
WM
CO
1
C
B
E
G
2 3 4 5 6 7 8 9 10 11 12 13 14
HJ
K
L
1M400
FC-1103
FC-1104
FC-1307
FC-1304
FC-1303FC-1102
FC-1302
FC-1301
2M400
FD-2 FD-2
1M401
WATER METER ANDSPRINKLER TREE BEHINDCHAIN LINK FENCE
FD-2
IN FLOOR HEAT ZONE 1225mm SPACING20m²3000W
IN FLOOR HEAT ZONE 2225mm SPACING(150mm WITHIN ENTRANCE)70m²10500W
IN FLOOR HEAT ZONE 3225mm SPACING(150mm WITHIN ENTRANCE)55m²8250W
IN FLOOR HEAT ZONE 4225mm SPACING25m²3750W
IN FLOOR HEAT ZONE 5225mm SPACING35m²5250W
IN FLOOR HEAT ZONE 6225mm SPACING30m²4500W
NON FREEZE HOSE BIBB EQUALTO ZURN Z-1300 ECOLOTROLWALL HYDRANT (TYPICAL)
1250
1000 W
RP-1
100 DEEP IN FLOOR HEAT MANIFOLD CABINET.IN SLAB PIPING TO BE RUN BELOW CORRIDORAND NOT BELOW NICHE
100 DEEP IN FLOORHEAT MANIFOLDCABINET
VV
UR
WC
LAV
MSMS
FD-2 FD-2
V V V V
VV
V
V
40 DCW40 DHW20 DHWR
50 D
CW20
DHW
15 D
HWR
20 DHWR
?
40 DHW50 DCW
PIPES RISE ON ANGLEBELOW STAIR
PIPES RISE UP INTO BEAM SPACE.PROVIDE AIR VENTS AS REQUIRED
NON FREEZE HOSE BIBB EQUAL TO ZURNZ-1300 ECOLOTROL WALL HYDRANT
RAINWATER STORAGE TANK BACKUPSUPPLY SHUTOFFRAINWATER STORAGE TANK 30mmBACKUP SUPPLY DOWN INTO FOUNDATION
7000GAL BELOW GRADERAINWATER STORAGE TANK
30 DCW
50 DCW STUBOUT FOR TENANT WITHINBEAM SPACE. PROVIDE BMS FLOW METER
50 DCW, 25 DHW AND15 DHWR FOR MAINFLOOR WASHROOM
SECOND FLOOR WASHROOM SANITARYPIPING TIGHT TO U/S OF BEAM
SECOND FLOOR WASHROOM 50DCW, 20 DHW AND 15 DHWR UP
50 DCW STUBOUT FOR TENANT WITHINBEAM SPACE. PROVIDE BMS FLOW METER
FC-1305
FC-1306
BS-31BS-32BS-33
20 DCW, 20 DHW AND 15 DHWR UPTO SECOND AND THIRD FLOORFIXTURES
15 DHW AND 15 DCW TORECYCLE SERVICE SINK
40 PRESSURE RW SUPPLY FROM RAINWATER STORAGE TANK. COORDINATEWITH IRRIGATION PACKAGE SUPPLIER.ENSURE WINTER DRAIN DOWNCAPABILITY
65 TWS65 TWR
65 TWS65 TWR
40 HWR40 HWS
20 H
WR
20 H
WS
VRF BRANCH SELECTORS WITHINBEAM SPACE
IN FLOOR HEAT PIPING BELOW VESTIBULE GRATEPANS TO BE TIGHTENED TO 150mm SPACING
IN FLOOR HEAT PIPING BELOW VESTIBULE GRATEPANS TO BE TIGHTENED TO 150mm SPACING
2M201
3M201
PROVIDE SLEEVE FORFUTURE GAS LINE. FILL WITHSPRAY FOAM INSULATION
GREEN WALL TRENCH DRAIN
HP-1HP-2AHP-2BBS-11BS-12
FD-3
P-5
20 DCW
RAINWATER PUMPING PACKAGE.COORDINATE WITH IRRIGATIONCONTRACTOR FOR EXACT REQUIREMENTS
FD
FDV
1000
800 W
RP-1
2000
1550 W
RP-1
ARCHITECTURAL SERIES ELECTRIC BASEBOARDTO BE OPERATED BY BMS BASED ON SPACETEMPERATURE SENSOR
150 ST
NICHEOF-02
150 ST
WC WC WCWC
WC WCWC
KS KS
LAV
FD
100 S
AN@
1%
LAV LAVLAVV
MS-1
OFFSET 150 ST DOWN INTO FOUNDATION
OFFSET 150 ST DOWN INTO FOUNDATION
OFFSET 150 ST DOWN INTO FOUNDATION
COORDINATE SANITARY WITHDUCTWORK IN THIS AREA
150 ST DOWN
100 S
P
65 D
CW
40 D
HW
30 D
HWR
65 T
WS
65 T
WR
40 H
WR
25 H
WS
40 H
WR
PROVIDE UNI-STRUT SUPPORT SYSTEM FOR PIPING RUNS
PIPING TO RISE UP TIGHT TO U/S OF STAIRS
VESTIBULE FLOOR GRATE150mm SPACED IN FLOOR HEAT PIPES WITHINVESTIBULE. PRIME PIPING WITH GLYCOL BEFORE SLABPOUR. COORDINATE LOCATION WITH STRUCTURAL
IN FLOOR HEAT MANIFOLD CABINET EQUALTO ROTH HK SERIES 100mm DEEPRETURN MANIFOLDSUPPLY MANIFOLD
PEX PIPING SLAB PENETRATION PROTECTOR EQUALTO AXIOM PEXPAL. COORDINATE LOCATION WITHARCHITECTURAL WALL PLACEMENT ON A101
25 HWS AND 25 HWR
15 IN FLOOR PEX PIPING
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
MAIN FLOOR MECHANICALPLUMBING, HEATING AND
COOLING PLAN
M201
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M201MAIN FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1
TRUE NORTH
1 : 20M201VESTIBULE PIPING DETAIL2
1 : 20M201IN FLOOR HEAT CABINET DETAIL3
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
1
C
B
D
E
F
G
2 3 4 5 6 7 8 9 10 11 12 13 15
HJ
K
L
FC-2201
FC-2401
FC-2406
FC-24072
M401
150 ST DOWN
V
RD
RD
RD
RD
FC-2410
OPEN OFFICESSH-07
GAMES ROOMSH-06
LOUNGESH-05
EXIT STAIRSES-10
DINING AREASH-01
BALCONYSH-03
BAR SEATINGSH-02
LANDINGCS-20
BLEACHERSCS-13
SEATINGCS-11
MEETING ROOMBH-22
MEETING ROOMBH-14
CORRIDORBH-04
OFFICEBH-12
OFFICEBH-11
OFFICEBH-10
MEETING ROOMBH-13
SECURITYBH-01
PRINTER RMBH-05
OFFICEBH-06
OFFICEBH-07
OFFICEBH-08
CORRIDORBH-02
CORRIDORBH-03
CORRIDORCS-07
100 S
T@1%
100 S
T@1%
FC-2203
FC-2202
FC-2204
V
MS
FC-2404
FC-2402
FC-2405
MS-1
FC-2409FC-2408
50 DCW, 25 DHW AND 15 DHWRFOR SECOND FLOOR WASHROOM,JANITOR ROOM AND KITCHENETTE
20 DCW AND 20 DHW TO MOP SINK
75 FROM MOPSINK ABOVE
BS-41
BS-43BS-42
VRF BRANCH SELECTORS WITHINJANITOR ROOM CEILING SPACE
150 ST DOWN
KS-1
FD-2
FD
V
KS-1
V
V V VV
V V V
V100 S
T@1%
OFFICEBH-09
LANDINGES-04
EXIT STAIRSES-03
OPEN OFFICESBH-21
OPEN OFFICESBH-20
OPEN OFFICESBH-20
OPEN OFFICESBH-19
OPEN OFFICESBH-18
OPEN OFFICESBH-17
OPEN OFFICESBH-16
OPEN OFFICESBH-15
BS-22BS-21
BS-23BS-24
FC-2403
F2
150ST DOWN
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
1 : 100
LB
LB/DRC
DRC
21-3180
SECOND FLOORMECHANICAL PLUMBING,HEATING AND COOLING
PLAN
M202
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M202SECOND FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
1
C
B
D
E
F
G
2 3 4 5 6 7 8 9 10 11 12 13 15
HJ
K
L
FC-3501 FC-3502
FC-2205
FC-3503
FC-3509FC-3506
FC-3507
FC-3510
RD
RD
RD
RD
RD
RD
OPEN OFFICESOC-06
OPEN OFFICESOC-07
OPEN OFFICESOC-08
OPEN OFFICESOC-09
OPEN OFFICESOC-10
OPEN OFFICESOC-11
OPEN OFFICESOC-12
OPEN OFFICESOC-13
OPEN OFFICESOC-14
OPEN OFFICESOC-16
OPEN OFFICESOC-15
OPEN OFFICESOC-17
??
HOT DESKSOC-18
MEETING ROOMOC-20
MEETING ROOMOC-19
CORRIDOROC-05
CORRIDOROC-04
HALLWAYOC-01
LANDINGCS-23
OCEOC-26
OFFICEOC-25
OFFICEOC-24
OFFICEOC-23
PRINTER ROOMOC-22
OFFICEOC-21 JANITOR
SE-14
100 S
T@1%
100 S
T@1%
100 S
T@1%
MS-1
SEE DWG1/M202 FORSECOND FLOORPLUMBING PLAN
BS-53BS-52BS-51
VRF SYSTEM BRANCH SELECTORSWITHIN JANITOR ROOM CEILING SPACE
V
MAIN SAN VENT UP THROUGH ROOF
20 DCW AND DHW TO MOP SINK
FC-3508
FD-2
STORM PIPING TIGHT TO U/S OF DECK.PROVIDE 25mm INSULATION ON FIRST 3m
100 S
T@1%
100 S
T@1%
150 ST DOWNINTO FOUNDATION
150 ST DOWN INTO FOUNDATION
20 DCW UP TO NON FREEZE HOSE BIBB
150 ST DOWN INTO FOUNDATION
FC-3504
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
1 : 100
LB
LB/DRC
DRC
21-3180
THIRD FLOORMECHANICAL PLUMBING,COOLING AND HEATING
PLAN
M203
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M203THIRD FLOOR MECHANICAL PLUMBING, HEATING AND COOLING PLAN1
All drawings and specifications are instruments of service and property ofthe Consultant and shall not be used without the Consultant's permission.Contractor shall verify all dimensions and details and refer anydiscrepancies to the Consultants before proceeding with the work.
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
T
T
T
T
T
T
FE
FE
FE
FE
T
T
T
C22700 mm AFF.
C22700 mm AFF.
C22700 mm AFF.
C22700 mm AFF.
C22700 mm AFF.
C22700 mm AFF.
?3054 mm AFF.
?? AFF.
?3795 mm AFF.
?? AFF.
1
C
D
E
F
G
2 3 4 5 6 7 8 9 10 11 12 13 14
HJ
K
L
FC-1102
FC-1103
FC-1304
FC-1307
FC-1104
FC-1302FC-1301
FC-1303
FC-1307
250x150150 L/s
E-1
-
600x300
R-1
BALANCE 250Ø TO 300 LPS
7M400
CRU - 3WE-01
ATRIUMCS-02
VESTIBULECS-01
SITE SAFETYSE-04
MECHANICALSE-06
ELECTRICALSE-07
RECYCLINGSE-08
CORRIDORES-01
RECEPTIONWE-03
LOCKER ROOM - WWE-04 LOCKER ROOM - M
WE-12
WCWE-10
WCWE-07 URINALS
WE-11
SHWR-WWE-08
SHWR-MWE-09
CORRIDORSE-01
1M401
2M400
1M400
11M400
BALANCE TO 150Ø S/A 105 LPS
HANG THERMOSTAT/CONTROLLER AND CONTROLWIRING WITH FAN COIL
HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL
HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL
HANG THERMOSTAT/CONTROLLER ANDCONTROL WIRING WITH FAN COIL
BALANCE 250Ø WASHROOM E/A TO 180 LPSBALANCE 300Ø GENERAL E/A TO 300 LPS
CRU FAN COILS C/W OPEN ENDED ACCOUSTICALLYINSULATED S/A AND R/A PLENUMS
BALANCE 250Ø TO 300 LPS
??
FC-1306
BS-33
BS-31BS-32
CRU FAN COILS C/W OPEN ENDED ACCOUSTICALLY INSULATEDS/A AND R/A PLENUMS. CRU-2 FAN COILS BELOW FIRE RATING
2M301
BALANCE TO 130 LPS
-
650x250
R-2-
300x250
S-2
300Ø T/A-
300x250
S-2
400x15060 L/s
E-23@
EF-3
?
EF-2
? 250x250 T/A. PROVIDE ACCOUSTIC INSULATION AS SHOWN
F D
F D
F D
10 L/s
S-3
380x380
700x300 INSULATED EXHAUST PLENUM
150x15035 L/s
E-18@
250Ø E/A
250Ø E/A
200Ø E/A
250Ø
E/A
350Ø
E/A
2@ 250x250 E/A CONNECTION TO PLENUMSERVER ROOM HEAT REJECTION INLINE FAN
ELECTRICAL ROOM HEAT REJECTION CEILING TYPE FAN
BALANCE 250Ø E/A TO 190 LPS
BALANCE 200Ø S/A TO 210 LPSFC-1305
100 SP
SPRINKLER TREE LOCATIONFIRE DEPARTMENT CONNECTION
5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET
TO ZONE VALVES
FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.
EXHAUST PLENUM AT HIGH LEVEL. SEEARCHITECTURAL ELEVATION VIEWS FOR DETAIL
LOWER
UPPER
SPF-1
STAIRWELLPRESSURISATION FAN
-
1200x200
L-1
SPF-2 STAIRWELL PRESSURISATION FAN
-
1200x200
L-1
HP-2BHP-2AHP-1
BS-11BS-12
VRF ZONE THERMOSTAT/CONTROLLER c/w COVER PLATETO ALLOW LIMITED SET POINT ADJUSTMENT ANDOCCUPANCY OVERRIDE ONLY (TYPICAL)
BMS TEMPERATURE SENSORLOCATION FOR IFH ZONE2
100 SP FROM FIRE DEPARTMENTCONNECTION. SLOPE BACK TOSPRINKLER TREE
BMS TEMPERATURE SENSOR LOCATIONFOR IFH ZONE 3ATRIUM VRF FAN COILS TO OPERATEDURING OCCUPIED HOURS BASEDON RETURN AIR TEMPERATURE
CRU - 2OF-03
-
700x1100
L-1
EF-1
MECHANICAL ROOM CEILING TYPE FAN
CRU-1RT-01
150x15030 L/s
E-1
F D
250Ø
E/A
CORRIDORES-08
F D F DF D
FIRE DAMPERS AT FLOORPENETRATIONS
COORDINATE DUCTWORK WITHSANITARY PIPING IN THIS AREA
300Ø
E/A
S/A 2-POSITION CONTROL DAMPERS
E/A 2-POSITION CONTROL DAMPERS
FC-1101
CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE
-
650x250
R-2
E/A 2-POSITION CONTROL DAMPERS
650x250130 L/s
R-2
300Ø S/A INTO SPACE. ALIGN TOPOF DUCT WITH U/S OF BEAM
D E
SERVERRACKS
WAR
M IS
LE
COOL
ISLE
HEAT REJECTION EXHAUST GRILLE IN T-BAR CEILING
250Ø E/A DUCTWORK BACK TO EXHAUST FAN WITHINELECTRICAL ROOM
250Ø E/A
HEAT RECLAIM VRF UNIT HUNG AT U/S T-BAR CEILING.UNIT TO BE PLACED AS SHOWN WITH RETURN OVERWARM ISLE AND SUPPLY DIRECTED TO COOL ISLE.UNIT TO OPERATE CONTINUOUSLY 24/7 BASED UPONRETURN AIR TEMPERATURE
TRANSFER AIR DUCT
-
250x250
E-1
-
250x150
S-2 DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
MAIN FLOOR MECHANICALVENTILATION AND FIRE
PROTECTION PLAN
M301
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M301MAIN FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1
1 : 50M301SERVER ROOM COOLING DETAIL2
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
Sco
Sco
S co
T
T
T
T
T
TT
T
T
FE
FE
FE
FET
T
T
T
?3000 mm AFF.
?3000 mm AFF.
?3000 mm AFF.
?3000 mm AFF.
?3000 mm AFF.
?? AFF.
?? AFF.
C22700 mm AFF.
?? AFF.
C22700 mm AFF.
?10081 mm AFF.
C22700 mm AFF.
1
C
B
D
E
F
G
2 3 4 5 6
6
7 8
8
9 10 11 12 13 15
H
H
J
K
L
FC-2201
FC-2406
FC-2407
FC-2401
250Ø
S/A
250Ø S/A
300Ø S/A
250Ø
S/A
250Ø S/A
250Ø
S/A
250Ø S/A250Ø S/A
200Ø S/A 200Ø S/A
FC-2409
200Ø S/A
200Ø S/A
FC-2410
300Ø S/A
300Ø S/A
9M400
OPEN OFFICESSH-07
GAMES ROOMSH-06
LOUNGESH-05
EXIT STAIRSES-10
DINING AREASH-01
BALCONYSH-03
BAR SEATINGSH-02
LANDINGCS-20
BLEACHERSCS-13
SEATINGCS-11
MEETING ROOMBH-22
MEETING ROOMBH-14
CORRIDORBH-04
OFFICEBH-12
OFFICEBH-11
OFFICEBH-10
MEETING ROOMBH-13
SECURITYBH-01
PRINTER RMBH-05
OFFICEBH-06
OFFICEBH-07
OFFICEBH-08
CORRIDORBH-02
CORRIDORBH-03
CORRIDORCS-07
300Ø S/A
250Ø
S/A
FC-2403
10M400
FC-2203
BALANCE TO 140 LPS
CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE
350x350 S/A DROP FROM ERV-1INTO FIRE RATED BULKHEAD
750x350 R/A UP TO ERV-1. SEEDWG12/M400 FOR DUCTING DETAIL
BALANCE TO 265 LPS
DECK MOUNTED DUCTLESS FAN COIL UNIT350 S/A DUCT TIGHT TO U/S OF DECK.DROP 300 S/A DUCTS BELOW BEAM
200 CUBICAL R/A DUCT C/W150x150 R/A GRILLES
BS-41
FC-2404
FC-2402
FC-2405
FC-2408
BS-42BS-43
OPEN OFFICE SPACE FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM300Ø DROPS BELOW GLULAM BEAM
300Ø S/A
BALANCE TO60 LPS
LOUNGE FAN COIL C/W ACCOUSTICALLYINSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM
BALANCE TO30 LPS
BALANCE 150Ø TO 50 LPSBALANCE 150Ø TO 65 LPS
BALANCE 100Ø TO 35 LPSBALANCE 100Ø TO 30 LPS
DEMAND VENTILATION DISPLACEMENT DIFFUSERON WALL @ 600 AFF. CONTROL DAMPER TOREGULATE CO2 TO 800PPM
DEMAND VENTILATION DISPLACEMENT DIFFUSER ONWALL @ 600 AFF. CONTROL DAMPER TO REGULATECO2 TO 800PPM
BALANCE 100ØTO 30 LPS
BALANCE TO 30 LPS WITH CONTROL VALVEFULLY OPEN
2M302
FC-2204
FC-2204 R/A GRILLE @ 4000 AFF
FC-2202
CEILING SPACE ENCLOSED FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE SIDEWALL ACCESS FOR SERVICE
2M401
300x20080 L/s
E-3
-
650x250
R-2
500x25090 L/s
R-2
F D
F D
F D
F D
150x15040 L/s
E-1
F D
150x15040 L/s
R-13@
FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.
350x150200 L/s
S-2
VRF ZONE THERMOSTAT/CONTROLLER c/w COVER PLATETO ALLOW LIMITED SET POINT ADJUSTMENT ANDOCCUPANCY OVERRIDE ONLY (TYPICAL)
VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT
VRF ZONE THERMOSTAT/CONTROLLERc/w COVER PLATE TO ALLOW LIMITED SETPOINT ADJUSTMENT AND OCCUPANCYOVERRIDE ONLY (TYPICAL)
VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT
55 L/s
S-3
380x380
25 L/s
S-3
380x380
55 L/s
S-3
380x380
PRINTER ROOM FAN COIL UNIT TO RUNCONTINUOUSLY DURING OCCUPIED HOURSTO MAINTAIN RETURN AIR TEMPERATURE
OPEN OFFICESBH-21
OPEN OFFICESBH-20
OPEN OFFICESBH-19
OPEN OFFICESBH-18
OPEN OFFICESBH-17
OPEN OFFICESBH-16
OPEN OFFICESBH-15
250x10050 L/s
S-16@
250x10045 L/s
S-17@
250x10060 L/s
S-15@
250x10045 L/s
S-14@
250x10070 L/s
S-16@
250x10060 L/s
S-17@
250x10055 L/s
S-16@
350Ø
S/A
30 L/s
S-3
380x380
150Ø
S/A
150Ø
S/A
250Ø S/A
150x15030 L/s
E-1
F D
ERV-1 FLOW GRID BELOW 150 S/A DUCT
150Ø
S/A
5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET
150Ø S/A
350x350 S/A
200Ø S/A
150x15035 L/s
E-1200x20070 L/s
E-14@
250Ø E/A
250Ø E/A
S/A 2-POSITION CONTROL DAMPERS
S/A 2-POSITION CONTROL DAMPER
9
150x150 DEMAND VENTILATIONCONTROL DAMPER
360x360 DISPLACEMENT DIFFUSERWITH FACTORY PLENUM
300x65 FRESH AIR DUCT IN WALL
WALL MOUNTED HEAT/COOL AIRCONDITIONER
55 L/s
S-3
380x380DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
SECOND FLOORMECHANICAL
VENTILATION AND FIREPROTECTION PLAN
M302
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M302SECOND FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1
1 : 50M302MEETING ROOM VENTILATION DETAIL2
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
FE
FET
T
T
T
T
T
T S co
S coT
?? AFF.
C23000 mm AFF.
C23000 mm AFF.
C23000 mm AFF.
1
C
B
D
E
F
G
2 3 4 5 6 7 8 9 10 11 12 13 15
H
H
J
K
L
FC-3509
FC-3503
FC-3501 FC-3502
FC-2205 FC-3505
FC-3506
FC-3507
250Ø S/A
300Ø S/A 300Ø S/A
250Ø
S/A
250Ø
S/A
300Ø S/A
8M400
OPEN OFFICESOC-06
OPEN OFFICESOC-07
OPEN OFFICESOC-08
OPEN OFFICESOC-09
OPEN OFFICESOC-10
OPEN OFFICESOC-11
OPEN OFFICESOC-12
OPEN OFFICESOC-13
OPEN OFFICESOC-14
OPEN OFFICESOC-16
OPEN OFFICESOC-15
OPEN OFFICESOC-17
HOT DESKSOC-18
MEETING ROOMOC-20
MEETING ROOMOC-19
CORRIDOROC-05
CORRIDOROC-04
HALLWAYOC-01
LANDINGCS-23
OCEOC-26
OFFICEOC-25
OFFICEOC-24
OFFICEOC-23
PRINTER ROOMOC-22
OFFICEOC-21
JANITORSE-14
2M303
200Ø S/A
FC-3510
BS-51
400Ø
S/A
300Ø S/A
350Ø
S/A
TIGHT TO U/S PENTHOUSE ROOF DECKTIGHT TO U/S PENTHOUSE FLOOR DECK
DEMAND VENTILATION DISPLACEMENT DIFFUSERSON WALL @ 600 AFF. CONTROL DAMPERS TOREGULATE CO2 TO 800PPM
OPEN OFFICE SPACE FAN COILS C/WACCOUSTICALLY INSULATED R/A AND S/A PLENUMS.PROVIDE R/A OPENING IN U/S OF PLENUM
PROVIDE DUCTED RETURNTO EAST FAN COIL
BALANCE 200Ø TO 135 LPS
BALANCETO 40 LPS
BALANCETO 110 LPS
BALANCE TO 70 LPS
BS-52BS-53
FC-3508
FC-3504
SEE DWG1/M302 FORSECOND FLOORVENTILATIONPLAN
-
900x250
R-2
150x10030 L/s
S-2
150x15020 L/s
E-1
150x15050 L/s
E-1
300x200100 L/s
E-1
F D F D
FULL SPRINKLER LAYOUT ANDHYDRAULIC DESIGN AS PERNFPA 13 TO BE PROVIDED BYPROUDLINE FIRE PROTECTION.
3M303
4M303
2@ DUCTLESS ATRIUM VRF FAN COIL UNITS TIGHT TO U/SOF ROOF DECK. ATRIUM UNITS TO OPERATECONTINUOUSLY DURING OCCUPIED HOURS BASED ONRETURN AIR TEMPERATURE (TYPICAL)
BMS TEMPERATURE SENSOR ATBOTTOM OF OPERABLE WINDOW LINE
BMS TEMPERATURE SENSOR ATBOTTOM OF OPERABLE WINDOW LINE
PRINTER ROOM WALL MOUNT FAN COIL TO RUNCONTINUOUSLY DURING OCCUPIED HOURS TOMAINTAIN RETURN AIR TEMPERATURE
VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)BMS CARBON DIOXIDE SENSOR WITH READOUT
250x10055 L/s
S-110@
250x10055 L/s
S-16@
250x10050 L/s
S-18@
200x10030 L/s
S-15@
VRF ZONE THERMOSTAT/CONTROLLER c/w COVERPLATE TO ALLOW LIMITED SET POINT ADJUSTMENTAND OCCUPANCY OVERRIDE ONLY (TYPICAL)
F D
200Ø E/A
5# ABC FIRE EXTINGUISHER c/w RECESSEDPAINTED CHARCOAL (PT-1) CABINET
F D
300Ø PERIMETERSPIRAL S/A DUCT
SPIRAL DUCT 2-HALFBAND HANGER
THREADED READY RODSUPPORT HANGER
GLUELAM STRUCTURALBEAM
FC-3504
300Ø S/A
150Ø S/A-
900x250
R-2
FC-3504ACOUSTICALLY INSULATED RETURNAIR PLENUM100Ø FRESH AIR SUPPLY INTOPLENUMFILTER SECTION
CANVAS CONNECTION ONSUPPLY AND RETURN PLENUMS
VRF FAN COIL UNIT TIGHT TO U/SOF DECKCONDENSATE TO BE PIPED TOCLOSEST SANITARY
RL AND RF TO BE RUN IN TANDEMWITH FRESH AIR AND CONDENSATE300 S/A DUCT FROM BOTTOM OFPLENUM TO AVOID BEAM ATGRIDLINE 12
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
THIRD FLOORMECHANICAL
VENTILATION AND FIREPROTECTION PLAN
M303
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 100M303THIRD FLOOR MECHANICAL VENTILATION AND FIRE PROTECTION PLAN1
1 : 20M303PERIMETER SPIRAL DUCT HANGING DETAIL2
TRUE NORTH
1 : 50M303FC-3504 CONNECTION DETAIL3
1 : 50M303FC-3504 CONNECTION DETAIL4
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
B
11 12
4M400
3M400
GEO EXCHANGE MANIFOLDAND PIPING TO GEOEXCHANGE FIELD BY OTHERS
GEO EXCHANGE PUMPS c/wFACTORY VSD
TEMPERED GLYCOL FILL TANK
TEMPERED GLYCOLEXPANSION TANK
RECYCLING AREA IN FLOORHEAT MANIFOLD CABINETWATER SOURCE VRF HEATPUMPS
ACTIVE SLAB GLYCOLEXPANSION TANK
ACTIVE SLAB GLYCOL FILLTANK
ACTIVE SLAB GLYCOL FILLTANK
ACTIVE SLAB BUFFER TANK
ACTIVE SLAB WATER TOWATER HEAT PUMP
BUFFER TANK CIRCULATOR
HYBRID ELECTRIC DOMESTICWATER HEATER
ELECTRIC BASEBOARDRADIATION SET TO 10°C
TEMPERED GLYCOLPUMPS C/W FACTORY VSD
HP-3HP-4AHP-4B
ET-1
GFT-1
P-2B
P-2A
P-1BP-1A
FD-3
FD-3
DWH-1
HP-6P-4
BT-1
P-3
GFT-2ET-2
DWRP-1
LOCATION FOR GREENWALLIRRIGARTION EQUIPMENT.COORDINATE WITHGREENWALL EQUIPMENTMANUFACTURER
1000
800 W
RP-1
BMS CONTROLS CABINET
B
11 12
4M400
3M400
TEMPERED GLYCOL RETURNWITHIN BEAM SPACE
TEMPERED GLYCOL SUPPLYWITHIN BEAM SPACE
HP-5A HP-5B
150
150
40 DCW40 DHW20 DHWR65 TWS65 TWR40 HWR40 HWS
20 D
CW20
DHW
EF-2
250x250 E/A
FD
B
P-2BP-2A
GFT-1 ET-1
150
EF-2
P-1AP-1B
HP-5B
HP-3HP-4A
BMS CABINET
TW PUMPSGEO EXCHANGE PIPING
ELECTRIC BASEBOARD1000
800 W
RP-1
GEO EXCHANGE PUMPS
GLYCOL FILL TANKTW EXPANSION TANK
STACKED HEAT PUMPSFIRE EXTINGUISHER
MECHANICAL ROOMEXHAUST FAN
B
BT-1
HP-6
DWH-1
150
P-4
P-3
HP-5A
HP-4B
HP-5A
ET-2
GFT-2 FD-3
TW SUPPLY HEADERSTACKED HEAT PUMPSACTIVE SLAB PUMP
ACTIVE SLAB BUFFER TANK
W TO W HEAT PUMPBUFFER TANK PUMP
HYBRID ELECTRIC WATER HEATER
76 S
AN
40 HWS40 HWR65 TWR65 TWS
20 DHWR40 DHW40 DCW
D
E
10 11
6M400
ERV-2
DUAL CORE ENERGY RECOVERY VENTILATOR
700x300 INSULATED INTAKE/EXHAUST PLENUM AND LOUVRE
400x400 S/A DUCT. PROVIDE TURNING VANES ON MITRED ELBOWS350Ø S/A DUCT DOWN SHAFT BELOW. PROVIDEFIRE DAMPER AT FLOOR PENETRATION
-
700x300
L-1
-
700x300
L-1
M
M
MOTORISED DAMPERS INTERLOCKED WITHERV UNIT
10
ERV-2
350Ø
S/A
700x300980 L/s
L-1
DUAL CORE ENERGYRECOVERY VENTILATOR
300x400 E/A PLENUM
350Ø GENERAL E/A
700x300 LOUVRE
450x300
700x300 PLENUMAND LOUVRE
350Ø MEDIUM PRESSUREFRESH AIR SUPPLY
300Ø WASHROOM E/A
FD
FD
ERV-2 FLOW GRID
D
E
10
75 SAN
150 ST
200Ø
S/A
250Ø
E/A
350Ø
E/A
75 SAN
75 SAN
15 DHWR
20 DHW
20 DCW
50 D
CW
D
E
10
200Ø E/A
100 S
T250Ø
S/A
450x300 E/A
150Ø
E/A
150Ø
E/A
350Ø S/A
20 D
HW
20 D
CW
100 S
T
350Ø E/A 400Ø E/A
FD
FD
FD
FD
FIRE CAULK AT ALL PIPE FIRESEPARATION PENETRATIONS
OUT OF STREAM FIREDAMPERS AT ALL DUCT FIRESEPARATION PENETRATIONS
20 DCW UP TO ROOFTOP NON-FREEZE HOSE BIBB
D
E
10
150Ø E/A
20 DCW
20 DHW
15 DHWR
350Ø E/A 350Ø E/A
250Ø S/A
250Ø
S/A
200Ø E/A
150 ST
75 SAN VENT
75 SAN
FIRE CAULK AT ALL PIPE FIRESEPARATION PENETRATIONSOUT OF STREAM FIREDAMPERS AT ALL DUCT FIRESEPARATION PENETRATIONS
FD
FD
FD
E
4
350Ø GENERAL EXHAUST OPEN TO SHAFT.FIRE DAMPER AT FLOOR PENETRATION
350x350 FROM 350Ø WASHROOM EXHAUST.FIRE DAMPER AT FLOOR PENETRATION 350X350 S/A INTO SHAFT TRANSITIONS TO
350Ø S/A DOWN. FIRE DAMPER AT FLOORPENETRATION
2@ 100 ST INTO 150 ST DOWN INTOFOUNDATION
FD
FD
FD
350x350 GENERAL EXHAUST OPEN TO SHAFT
E
4
350Ø GENERAL EXHAUST INTO SHAFT. FIREDAMPER AT FLOOR PENETRATION
350Ø WASHROOM EXHAUST INTO SHAFT.FIRE DAMPER AT FLOOR PENETRATION
350Ø S/A DOWN FROM SHAFT. FIRE DAMPERAT FLOOR PENETRATION150 ST DOWN FROM ROOF DRAINS. OFFSETAND DROP INTO FOUNDATION
FD
FD
FD
34
ERV-1
ACOUSTICALLY INSULATED 750x350 E/A RISE TOUNIT. PROVIDE CANVAS CONNECTION AS SHOWN350Ø GENERAL E/A OPEN TO SHAFT350Ø WASHROOM E/A FROM SHAFT
350x350 ACOUSTICALLY INSULATED S/A DROP INTO FRR BULKHEAD ABOVEEXIT. SIZES DENOTE FREE AREA. PROVIDE CANVAS CONNECTION AS SHOWN
350x350 S/A. PROVIDE TURNING VANES ON MITRED ELBOWS
CHANGEOVERSECTION
EXHAUST FANSECTION
HE CORESECTION
EXHAUSTPLENUM
PERFORATED FACE WASHROOM EXHAUST GRILLE
DUAL CORE ENERGY RECOVERY VENTILATORSUPPLY FANSECTION
HE CORESECTION
200x20070 L/s
E-12@
250Ø E/A
350Ø
E/A
350Ø
S/A
200x
200 E
/A
200x
200 E
/A
350x750 E/A
350x350 S/A INTO SHAFT. TRANSITION TO 350Ø. PROVIDETURNING VANES ON MITRED ELBOWS
GENERAL EXHAUST SHAFT SEALED TO U/S OF DECK
WASHROOM EXHAUST 2-POSITIONCONTROL DAMPER
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
As indicated
LB
LB/DRC
DRC
21-3180
MECHANICAL ROOMDETAILS
M400
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 50M201EAST MECHANICAL ROOM LOWER DETAIL1
1 : 50M201EAST MECHANICAL ROOM UPPER DETAIL2
1 : 50M400EAST MECHANICAL ROOM EAST SECTION VIEW3
1 : 50M400EAST MECHANICAL ROOM WEST SECTION VIEW4
1 : 50M400PENTHOUSE MECHANICAL ROOM PLAN5
1 : 50M400ERV-2 DUCTING DETAIL6
1 : 20M301EAST MECHANICAL CHASE DETAIL - MAIN FLOOR7
1 : 20M303EAST MECHANICAL CHASE DETAIL - THIR FLOOR8
1 : 20M302EAST MECHANICAL CHASE DETAIL - SECOND FLOOR9
1 : 20M302WEST MECHANICAL CHASE DETAIL - SECOND FLOOR10
1 : 20M301WEST MECHANICAL CHASE DETAIL - MAIN FLOOR11
1 : 50M100ERV-1 DUCTING DETAIL12
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
CO
C
4 5
-
600x300
R-1
-
650x250
R-2
WC-1
SH-1SH-1
WC-1 WC-1
UR-1
UR-1
LAV-1
LAV-1
LAV-1
LAV-1
3@LAV
V
50 D
CW40
DHW
30 D
HWR
65 T
WS
65 T
WR
100 SP65 DCW40 DHW30 DHWR65 TWS65 TWR40 HWR25 HWS40 HWR
FD-1FD-1
150x15035 L/s
E-18@
300Ø
E/A
250Ø E/A 200Ø E/A
150Ø
E/A
150Ø
E/A
350Ø T/A
-
300x250
S-2
-
300x250
S-2
VV
VV
100 SAN@1%
SH-1
SH-1
E
3 4
500x25090 L/s
R-2
350x150200 L/s
S-2
-
650x250
R-2
LAV-1
BS-23BS-24
BS-22
BS-21
MS-1
FC-2202
FC-2204
250Ø E/A
100 S
T10
0 ST
350Ø
S/A
350Ø
S/A
150Ø
E/A
200Ø S/A
200Ø R/A WC-1
WC-1
V V V
V V V
LAV-1 LAV-1
LAV-1 LAV-1 LAV-1
FD-2
FD-1
FD-1
UR-1UR-1
350x350 S/A
200Ø S/A
200x20070 L/s
E-14@
250Ø E/A
5@
3@
V V
RD
RD
KS-1 KS-1
150Ø S/A
350x350 S/A750x350 E/A
CONCEALED FLUSH VALVE
VENT CLEANOUT CONCEALEDBEHIND FLUSH VALVE PLATE
SANITARY CLEANOUT BEHINDROUND STAINLESS STEEL
CLEANOUT COVER ON CENTRELINE OF URINAL
TIE VENTS IN MAIN SAN VENTTHROUGH ROOF
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
1 : 50
LB
LB/DRC
DRC
21-3180
MECHANICAL WASHROOMDETAILS
M401
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
1 : 50M201NORTH MAIN FLOOR WASHROOM DETAIL1
1 : 50M202SECOND FLOOR WASHROOM DETAIL2
1 : 50URINAL SANITARY PIPING DETAIL3
TRUE NORTH
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
HP-2A
P
HP-2B
HP-1
H HP1 RTAIT
H HP2 RTAIT
HP-4A HP-4B
H HP4 RTAIT
HP-3
TH HP3 RTAI
HP-5A HP-5B
H HP5 RTAIT
PARALLEL TEMPEREDWATER PUMPS WITH
INTEGRAL SPEEDCONTROL2@ 5.2L/s
P-1B
PP
P-1A
200 T
WS
200 T
WR
P
P-2B
PP
P-2A
VSD
VSD
H P2A SH P2A C
DIDO
H P2A VAO
GEO EXCHANGE TRANSFERPUMPS WITH BMSCONTROLLED INTEGRAL VFD2@ 3.0L/s
H P2B SH P2B C
DIDO
H P2B VAO
H GE STAIT
GEO EXCHANGEMANIFOLD ANDPIPING BY OTHERS
TO ACTIVE SLABLOOPS
H AS ST
H AS RT
P-4
AI
AI T
T
T
P
HP-6
P
P
P-3
P
T H TW STAI
TT TW RTAI
H HP6 RTAI
BT-1
T
WEST MECHANICALCLOSET
FD
POTFEEDER
MAV
100mm INLET/OUTLETAIR SEPARATOR
EXPANSION TANKAND GLYCOL FILLTANK
HEAT PUMPCONTROLLER
AIRPURGER
BMS MAPPEDPOINTS
GFT-2 ET-2
GFT-1 ET-1
VSDH P3 SH P3 C
DIDO
H P3 VAI
FD
POTFEEDER
MAV
TH OATAI
COMBINED PUMP ANDDIFFERENTIALPRESSURE CONTROL1.0L/s
WATER TO WATERHEAT PUMP
VRF WATERSOURCE HEATPUMPS
VRF WATERSOURCE HEATPUMPS
VRF SYSTEMCONTROLLER
BMS MAPPEDPOINTS
FINE MESH STRAINERON SUPPLY
FINE MESH STRAINERON SUPPLY OF ALL
VRF HEAT PUMPS
VSD
VSD
H P1A SH P1A C
DIDO
H P1A VH P1B SH P1B C
DIDO
H P1B V
H GFT1 LADI
75 TWS
75 TWR
65 65
75
AI
AI
2-POSITION CONTROL VALVESINTERLOCKED WITH ALL VRF
HEAT PUMPS
2-POSITION CONTROL VALVESINTERLOCKED WITH ALL VRF HEAT PUMPS
P
P
PP
P
65 TWS65 TWR
P
P P
5050
40 40
4040
40 40
50
4040
65
65
BUFFER TANKCIRCULATION PUMP
2.3L/s
50
20% PROPYLENE GLYCOL BYVOLUME. COORDINATE GLYCOLPERCENTAGE AND MANUFACTURERWITH GEO FIELD CONTRACTOR
40% PROPYLENEGLYCOL BYVOLUME IFH LOOP
SUPPLY HEADER
RETURN HEADERPROVIDE 20mm HOSE BIBB C/WTHREADED HOSE CONNECTION
15mm PEX LOOPS IN FLOOR
MANIFOLD CONTAINMENT CABINET
SLAB TEMPERATURESENSOR
T
HWS
HWR
MAV
P
PNCSPACE TEMPERATURE
SENSOR
T
H IFH1 SLTAI
H IFH1 RTAI
H IFH1 CVAO
3-WAY MODULATING CONTROL VALVE IN LIEU OF2-WAY VALVE ON STORAGE ROOM IFH LOOP ONLY
2-WAY MODULATING CONTROL VALVETO CONTROL SLAB TEMPERATURE
E/A
E/A
O/A
S/A
E/AO/A
E/A
ERV-1
H ERV1 SH ERV1 C
DIDO
H ERV1 FCDO
H ERV1 RTAIT
H ERV1 RHAIH
T
HH ERV1 STAIH ERV1 SHAI
F H ERV1 AFAI
ERV-1 FLOW GRID
MERV-13 FILTRATION
S/A
Dm
E/A
Dm
H ERV1 RVDO
S/A
DmH ERV1 OVDO
LOUNGE/GAMES S/A OFFICE/LUNCH S/A
S/A
Dm
S/A
Dm
RESTAURANT S/A OFFICE/LUNCH S/A
2ND FLRWASHROOM E/A
E/A
Dm
E/A
Dm
WELLNESS E/A RESTERAUNTGENERAL E/A
E/A
Dm
RESTAURANTWASHROOM E/A
OFFICE SPACE/RESTAURANTVENTILATION CONTROL
2-POSITIONCONTROL DAMPERS
H ERV1 SVAI
VSD
VSD
H ERV1 COAICO
H ERV1 RFAI2
REF
RETURN AIR TEMPERATURE,HUMIDITY, CARBON DIOXIDE,AND REFRIGERANT SENORS
ELECTRIC TEMPERING COIL
E/A
S/A
E/A
H ERV2 SH ERV2 C
DIDO
H ERV2 FCDO
E/A
O/A
E/A
O/A
ERV-2
H ERV2 STAIT
H ERV2 RTAIT
H ERV2 RHAIH
H ERV2 SHAIH
MERV-13 FILTRATION
S/A
H ERV2 AFAI
ERV-2 FLOW GRID
F
RETURN AIR TEMPERATURE,HUMIDITY, CARBON DIOXIDE,AND REFRIGERANT SENORS
H ERV2 COAICO
H ERV2 RFAI2
REF
ELECTRIC TEMPERING COIL
BFP
WM
NC
PROVIDE APPROVED BACKFLOW PREVENTIONDEVICE AND STRAINER ON 65mm WATER SERVICE
WATER METER c/w VOLUMEMONITORING TIED TO BMS
65 DCW TO BUILDING
PRESSURE REDUCING VALVE IF REQUIRED BYLOCAL CODES
P WM VAI
WM
P CR1WM VAI
WM
P CR2WM VAI50 CRU2 DOMESTIC WATER VOLUME METER50 CRU1 DOMESTIC WATER VOLUME METER30 RAINWATER MAKE UP DOMESTIC WATER VOLUME METER
WM
P RMUWM VAI
DWH-1
FD
20 DHWR FROM BUILDING
40 DHW TO BUILDING
40 DCW FROM WATER METER
DWRP-1
40
T
P DWRP SP DWRP E
DIDO
20
P DHWR TAIP DWH1 TAI
BUILDING THERMOSTATIC MIXING VALVESET TO 50°C
P HWM VAIW
M
DOMESTIC HOT WATER VOLUME METER
20 GREEN WALL SUPPLY20
NC
GREENWALL THERMOSTATIC MIXING VALVESET TO 18°C. CONSULT GREENWALLSUPPLIER FOR REQUIREMENTS
40NC
BFP
APPROVED BACKFLOWPREVENTION AS REQUIRED P GWM VAI
WM
HEAT TRAP
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
1 : 50
LB
LB/DRC
DRC
21-3180
MECHANICALSCHEMATICS
M500
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
NTSM500TEMPERED WATER AND ACTIVE SLAB WATER SCHEMATIC2
NTSM500ACTIVE SLAB HEADER DETAIL3
NTSM500ERV-1 ENERGY RECOVERY UNIT CONTROLS SCHEMATIC4
NTSM500ERV-2 ENERGY RECOVERY UNIT CONTROLS SCHEMATIC5
NTSM500WATER METER SCHEMATIC1
NTSM500DOMESTIC WATER HEATING SCHEMATIC6
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
HP-1RWEYQ84PTJU -HR
31.8Strainer
*
1.20l/s
31.8
12.7
Inlet
Outlet
Drain
3.0m [3]
KHRP25A33T9.5x22.2x19.1
BS-11BSVQ36PVJU
0.3m6.4x12.7x9.5 *
FC-1101FXMQ18PVJU
11.3m [8]6.4x12.7 *
0.4m
KHRP26A33T9.5x22.2x19.1
BS-12BSVQ60PVJU
0.3m9.5x15.9x12.7
FC-1103FXMQ48PVJU
5.0m [7]9.5x15.9
1.0m
KHRP26A22T9.5x15.9
FC-1104FXMQ24PVJU
1.0m [3]9.5x15.9
FC-1102FXAQ07PVJU
7.0m [4]6.4x12.7
HP-2RWEYQ144PTJU -HR
RWEYQ72PTJU -HR RWEYQ72PTJU -HR
9.5x19.1x15.9 9.5x19.1x15.9
BHFP26MA56U
31.8Strainer
*
2.02l/s
31.8
12.7
31.8Strainer
*
1.01l/s
31.8
12.7
Inlet
Outlet
Drain
18.0m [6]
KHRP25M72TU12.7x28.6x22.2 *
BS-21BSVQ36PVJU
0.3m6.4x12.7x9.5 *
FC-2201FXHQ12MVJU
23.3m [7]6.4x12.7 *
0.3m
KHRP25A33T9.5x22.2x19.1
BS-22BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-2202FXMQ30PVJU
2.8m [5]9.5x15.9
0.3m
KHRP25A33T9.5x22.2x19.1
BS-23BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-2203FXMQ24PVJU
13.0m [8]9.5x15.9
BS-24BSVQ60PVJU
0.3m9.5x15.9x12.7
1.5m
KHRP26A22T9.5x15.9
FC-2204FXMQ30PVJU
1.0m [3]9.5x15.9
FC-2205FXHQ24MVJU
16.9m [6]9.5x15.9
HP-3RWEYQ84PTJU -HR
31.8Strainer
*
1.20l/s
31.8
12.7
Inlet
Outlet
Drain
6.9m [4]
KHRP25A33T9.5x22.2x19.1
BS-31BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-1306FXMQ24PVJU
4.0m [6]9.5x15.9
0.4m
KHRP25A33T9.5x22.2x19.1
BS-32BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-1304FXMQ24PVJU
15.0m [7]9.5x15.9
0.4m
KHRP26A22T9.5x15.9x12.7
BS-33BSVQ36PVJU
0.3m6.4x12.7x9.5 *
FC-1307FXHQ12MVJU
26.0m [7]6.4x12.7 *
5.0m [3]
KHRP26A22T9.5x15.9
FC-1305FXMQ07PVJU
1.0m [2]6.4x12.7
3.9m
KHRP26A22T9.5x15.9
FC-1301FXHQ12MVJU
3.0m [3]6.4x12.7
2.3m
KHRP26A22T6.4x12.7
FC-1302FXHQ12MVJU
1.0m [2]6.4x12.7
FC-1303FXAQ07PVJU
4.0m [3]6.4x12.7
HP-4RWEYQ144PTJU -HR
RWEYQ72PTJU -HR RWEYQ72PTJU -HR
9.5x19.1x15.9 9.5x19.1x15.9
BHFP26MA56U
31.8Strainer
*
2.02l/s
31.8
12.7
31.8Strainer
*
1.01l/s
31.8
12.7
Inlet
Outlet
Drain
23.0m [9]
KHRP25M72TU12.7x28.6x22.2 *
BS-41BSVQ36PVJU
0.3m9.5x15.9x12.7
1.0m
KHRP26A22T9.5x15.9
FC-2401FXAQ07PVJU
11.3m [6]6.4x12.7
FC-2402FXMQ18PVJU
13.5m [8]6.4x12.7
0.3m
KHRP25A33T9.5x22.2x19.1
BS-42BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-2405FXMQ24PVJU
14.5m [8]9.5x15.9
0.3m
KHRP26A22T9.5x15.9x12.7
BS-43BSVQ36PVJU
0.3m9.5x15.9x12.7
1.0m [1]
KHRP26A22T9.5x15.9
FC-2410FXAQ07PVJU
7.0m [7]6.4x12.7
FC-2408FXMQ18PVJU
5.0m [7]6.4x12.7
0.3m
KHRP26A22T9.5x15.9
FC-2404FXMQ07PVJU
5.5m [5]6.4x12.7
0.3m
KHRP26A22T9.5x15.9
FC-2403FXAQ07PVJU
4.0m [4]6.4x12.7
0.3m
KHRP26A22T6.4x12.7
FC-2406FXAQ07PVJU
2.5m [4]6.4x12.7
0.3m
KHRP26A22T6.4x12.7
FC-2407FXAQ07PVJU
2.5m [4]6.4x12.7
FC-2409FXMQ07PVJU
10.0m [6]6.4x12.7
HP-5RWEYQ144PTJU -HR
RWEYQ72PTJU -HR RWEYQ72PTJU -HR
9.5x19.1x15.9 9.5x19.1x15.9
BHFP26MA56U
31.8Strainer
*
2.40l/s
31.8
12.7
31.8Strainer
*
1.20l/s
31.8
12.7
Inlet
Outlet
Drain
23.1m [10]
KHRP25M72TU12.7x28.6x22.2
BS-51BSVQ60PVJU
0.3m9.5x15.9x12.7
4.0m [2]
KHRP26A22T9.5x15.9
FC-3503FXMQ36PVJU
2.0m [2]9.5x15.9
20.0m [5]
KHRP26A22T9.5x15.9
FC-3501FXHQ12MVJU
2.5m [2]6.4x12.7
FC-3502FXHQ12MVJU
2.5m [2]6.4x12.7
0.3m
KHRP25A33T9.5x22.2x19.1
BS-52BSVQ36PVJU
0.3m9.5x15.9x12.7
FC-3504FXMQ24PVJU
7.6m [3]9.5x15.9
0.3m
KHRP26A33T9.5x22.2x19.1
BS-53BSVQ60PVJU
0.3m9.5x15.9x12.7
7.0m [6]
KHRP26A22T9.5x15.9
FC-3509FXMQ30PVJU
7.0m [6]9.5x15.9
FC-3505FXHQ24MVJU
19.0m [8]9.5x15.9
6.0m [3]
KHRP26A22T9.5x15.9
FC-3506FXAQ07PVJU
8.0m [3]6.4x12.7
0.3m
KHRP26A22T6.4x12.7
FC-3507FXAQ07PVJU
8.0m [3]6.4x12.7
6.0m [3]
KHRP26A22T6.4x12.7
FC-3508FXMQ07PVJU
0.5m [3]6.4x12.7
FC-3510FXAQ07PVJU
4.0m [4]6.4x12.7
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
1 : 35
LB
LB/DRC
DRC
21-3180
MECHANICALSCHEMATICS
M501
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
NTSM501MAIN FLOOR WEST (HP-1) VRF SCHEMATIC1
NTSM501SECOND FLOOR WEST (HP-2) VRF SCHEMATIC2
NTSM501MAIN FLOOR EAST (HP-3) VRF SCHEMATIC3
NTSM501SECOND FLOOR EAST (HP-4) VRF SCHEMATIC4
NTSM501THIRD FLOOR EAST (HP-5) VRF SCHEMATIC5
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
T: 780.440.2806 W: www.clarkeng.ca
9409 98 AvenueEdmonton AB T6C 2C8
CLARK ENGINEERING INC.PERMIT #7440
All drawings and specifications are instruments of service andproperty of the Consultant and shall not be used without theConsultant's permission. Contractor shall verify all dimensionsand details and refer any discrepancies to the Consultantsbefore proceeding with the work.
APRIL 11TH, 2014
P:\2013\122 - MIA\04 - Mosaic\Model\13.122.04_MC4_MECH_v14.rvt
0
LB
LB/DRC
DRC
21-3180
MECHANICAL SCHEDULES
M600
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
DIFFUSER/GRILLE SCHEDULE
UNIT NO. MAKE MODEL DESCRIPTION COUNT REMARKSE-1 PRICE 10/F/A/B12 PERFORATED FACE RETURN GRILLE 24E-2 PRICE SDGER/A/B12 SPIRAL DUCT MOUNTED RETURN GRILLE 3 SPIRAL DUCT MOUNTED, ALUMINUM CONSTRUCTION RETURN GRILLE C/W COUNTERSUNK SCREW HOLES, AND WHITE
POWDER COATE-3 PRICE 530/F/L/A/B12 LOUVRED FACE RETURN GRILLE 1L-1 PRICE ZE445 6R-1 PRICE 10/F/A/B12 PERFORATED FACE RETURN GRILLE 4R-2 PRICE 530/F/L/A/B12 LOUVRED FACE RETURN GRILLE 6S-1 PRICE SDGE/DD/VCS3/A/B12 SPIRAL DUCT MOUNTED SUPPLY GRILLE 76 SPIRAL DUCT MOUNTED, ALUMINUM CONSTRUCTION GRILLE C/W OPPOSED BLADE DAMPER, COUNTERSUNK SCREW HOLES,
AND WHITE POWDER COATS-2 PRICE 520/F/L/A/B12 LOUVRED FACE SUPPLY GRILLE 7S-3 PRICE DF1W/PC12 FLUSH MOUNT DISPLACEMENT DIFFUSER AND SUPPLY PLENUM 7 FIELD PAINT TO MATCH. COORDINATE WITH ARCHITECT
VRF BRANCH SELECTOR UNIT SCHEDULE
UNIT NO. MAKE MODEL NUMBER BRANCHESMAX. BRANCH CAPACITY ELECTRICAL LOCATION
REMARKSMBH kW ELECTRICAL REMARKS VOLTS NO NAMEBS-11 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 RT-01 CRU - 1BS-12 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 RT-01 CRU - 1BS-21 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-09 HALLWAYBS-22 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-09 HALLWAYBS-23 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SH-10-1 WASHROOM-1BS-24 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SH-10-1 WASHROOM-1BS-31 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-32 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-33 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 OF-03 CRU - 2BS-41 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-42 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-43 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-11 JANITORBS-51 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITORBS-52 DAIKIN AC BSVQ36PVJU 1 36 11 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITORBS-53 DAIKIN AC BSVQ60PVJU 1 60 18 MCA - 0.1A MOCP - 15A 208/1/60 SE-14 JANITOR
VRF HEAT PUMP SCHEDULE
UNIT NO. MAKE MODELFLOW PIPE LOSS HEATING COOLING ELECTRICAL LOCATION
REMARKSGPM L/s ft kPa MBH kW MBH kW REQUIREMENTS VOLTS NO NAMEHP-1 DAIKIN AC VRV-WIII 7-TON 19.0 1.2 7.5 22 90 26 80 23 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-2A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-2B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 RT-01 CRU - 1HP-3 DAIKIN AC VRV-WIII 7-TON 19.0 1.2 7.5 22 90 26 80 23 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-4A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-4B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-5A DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICALHP-5B DAIKIN AC VRV-WIII 6-TON 16.0 1.0 6.4 19 77 23 69 20 MCA - 22.4 MOCP - 40 208/3/60 SE-06 MECHANICAL
VRF TERMINAL UNIT SCHEDULE
UNIT NO. MAKE MODELAIRFLOW HEATING COOLING ELECTRICAL LOCATION
REMARKSCFM L/s MBH kW MBH kW VOLTS ELECTRICAL REMARKS NO NAMEFC-1101 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A BALANCE FRESH AIR TO 300 L/SFC-1102 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A WE-03-2 RECEPTION-2 AIR TRANSFER FROM ATRIUMFC-1103 DAIKIN AC FXMQ48PVJU 1377 650 54 16 48 14 208/1/60 MCA - 3.4A MOCP - 15A RT-01 CRU - 1 BALANCE FRESH AIR TO 300 L/SFC-1104 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A RT-01 CRU - 1 BALANCE FRESH AIR TO 105 L/SFC-1301 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SE-10 SERVER NO FRESH AIRFC-1302 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SE-10 SERVER NO FRESH AIRFC-1303 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A OF-02 NICHE BALANCE FRESH AIR GRILLE TO 10 L/SFC-1304 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1305 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1306 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OF-03 CRU - 2 BALANCE CRU-2 FRESH AIR TO 210 L/SFC-1307 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-02 ATRIUM BALANCE ATRIUM FRESH AIR TO 200 L/SFC-2201 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A SH-06-1 GAMES ROOM-1 BALANCE FRESH AIR GRILLE TO 30 L/SFC-2202 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A SH-09 HALLWAY BALANCE FRESH AIR TO 140 L/SFC-2203 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A SH-05-1 LOUNGE-1 BALANCE FRESH AIR TO 60 L/SFC-2204 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A SH-10-1 WASHROOM-1 BALANCE FRESH AIR TO 265 L/SFC-2205 DAIKIN AC FXHQ24MVJU 710 335 27 8 24 7 230/1/60 MCA - 1A MOCP - 15A 53 Space BALANCE ATRIUM FRESH AIR TO 200 L/SFC-2401 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-14 MEETING ROOM (14 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-2402 DAIKIN AC FXMQ18PVJU 630 295 20 6 18 5 208/1/60 MCA - 1.6A MOCP - 15A BH-10 OFFICE BALANCE FRESH AIR TO 50 L/SFC-2403 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-13 MEETING ROOM (6 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-2404 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A BH-12 OFFICE BALANCE FRESH AIR TO 30 L/SFC-2405 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A BH-10 OFFICE BALANCE FRESH AIR TO 65 L/SFC-2406 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space GENERAL EXHAUST TO DRAW AIR FROM ATRIUMFC-2407 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-05 PRINTER ROOM PRINTER ROOM EXHAUSTEDFC-2408 DAIKIN AC FXMQ18PVJU 630 295 20 6 18 5 208/1/60 MCA - 1.6A MOCP - 15A BH-09 OFFICE BALANCE FRESH AIR TO 35 L/SFC-2409 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A BH-09 OFFICE BALANCE FRESH AIR TO 30 L/SFC-2410 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A BH-22 MEETING ROOM (14 PERSON) DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3501 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-18-2 HOT DESKS-2 BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3502 DAIKIN AC FXHQ12MVJU 410 195 14 4 12 4 208/1/60 MCA - 0.8A MOCP - 15A CS-18-2 HOT DESKS-2 BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3503 DAIKIN AC FXMQ36PVJU 1130 535 40 12 36 11 208/1/60 MCA - 2.9A MOCP - 15A OC-21 OFFICE BALANCE FRESH AIR TO 135L/SFC-3504 DAIKIN AC FXMQ24PVJU 680 320 27 8 24 7 208/1/60 MCA - 1.8A MOCP - 15A OC-22 PRINTER ROOM BALANCE FRESH AIR TO 70 L/SFC-3505 DAIKIN AC FXHQ24MVJU 710 335 27 8 24 7 230/1/60 MCA - 1A MOCP - 15A BALANCE ATRIUM FRESH AIR TO 200 L/SFC-3506 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3507 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A 53 Space DEMAND FRESH AIR VENTILATION DISPLACEMENT DIFFUSERFC-3508 DAIKIN AC FXMQ07PVJU 381 180 9 2 8 2 208/1/60 MCA - 0.6A MOCP - 15A OC-24 OFFICE BALANCE FRESH AIR TO 40 L/SFC-3509 DAIKIN AC FXMQ30PVJU 880 415 34 10 30 9 208/1/60 MCA - 2.3A MOCP - 15A OC-23 OFFICE BALANCE FRESH AIR TO 110 L/SFC-3510 DAIKIN AC FXAQ07PVJU 260 125 9 2 8 2 208/1/60 MCA - 0.4A MOCP - 15A OC-22 PRINTER ROOM PRINTER ROOM EXHAUSTED
ENERGY RECOVERY VENTILATION UNIT SCHEDULE
UNIT NO MAKE MODELAIRFLOW DUCT LOSS ELECTRICAL
LOCATION REMARKSCFM L/s in wg Pa HP VOLTAGEERV-1 TEMPEFF RG 5400 2970 1400 3.0 750 6.0 208/3/60 HIGH EFFICIENY DUAL CORE ENERGY RECOVERY VENTILATOR c/w SINGLE POINT POWER
CONNECTION, ELECTRIC REHEAT, MERV 13 FILTERSERV-2 TEMPEFF RGSP 2700 2120 1000 3.0 750 7.0 208/3/60 HIGH EFFICIENY DUAL CORE ENERGY RECOVERY VENTILATOR c/w SINGLE POINT POWER
CONNECTION, ELECTRIC REHEAT, MERV 13 FILTERS
PUMP SCHEDULE
UNIT NO. MAKE MODELFLOW HEAD ELECTRICAL
SERVICELOCATION
REMARKSGPM L/s Ft H2O kPa POWER RPM V/Ph/Hz NO NAMEDWRP-1 TACO 006B 4 0.3 7.0 21 25 W 120/1/60 DOMESTIC HOT WATER RECIRC PUMP SE-06 MECHANICALP-1A TACO SKV2007 83 5.2 40.0 120 1500 W 1800 208/3/60 TEMPERED WATER CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET
COMMUNICATION INTERFACE. PROVIDE UPRIGHT MOUNTING PLATE FOR VFDP-1B TACO SKV2007 83 5.2 40.0 120 1500 W 1800 208/3/60 TEMPERED WATER CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET
COMMUNICATION INTERFACE. PROVIDE UPRIGHT MOUNTING PLATE FOR VFDP-2A TACO 1919 47 3.0 45.0 135 1250 W 1800 208/3/60 GEO FIELD CIRCULATION SE-06 MECHANICAL BMS CONTROLLED PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET
COMMUNICATION INTERFACEP-2B TACO 1919 47 3.0 45.0 135 1250 W 1800 208/3/60 GEO FIELD CIRCULATION SE-06 MECHANICAL BMS CONTROLLED PARALLEL PUMP OPERATION. PROVIDE FACTORY BACNET
COMMUNICATION INTERFACEP-3 TACO 1911 16 1.0 20.0 60 375 W 3600 120/1/60 ACTIVE SLAB CIRCULATION SE-06 MECHANICAL PROPORTIONAL PRESSURE PUMP OPERATION. PROVIDE FACTORY BACNET
COMMUNICATION INTERFACEP-4 TACO 1915 36 2.3 29.0 87 500 W 3600 120/1/60 ACTIVE SLAB BUFFER TANK
CIRCULATIONSE-06 MECHANICAL
P-5 MYERS PQP10 25 1.6 90.0 269 751 W 208/1/60 RAINWATER PRESSURE PUMP RT-01 CRU - 1 c/w PRESSURE PUMPING PACKAGE AND STAND ALONE CONTROLS. COORDINATE WITHIRRIGATION CONTRACTOR FOR EXACT REQUIREMENTS
TANK SCHEDULE
UNIT NO. MAKE MODEL SERVICEVOLUME PRESSURE DIMENSIONS LOCATION
REMARKSGal. L MAX RELIEF HEIGHT WIDTH/DIA NO NAMEBT-1 LOCHINVAR SBT080 ACTIVE SLAB BUFFER TANK 80 303 1770 mm 610 mm SE-06 MECHANICAL STAINLESS STEEL INSULATED BUFFER TANKET-1 AMTROL AX-40V TW EXPANSION TANK 22 82 125 psi 150 psi 750 mm 410 mm SE-06 MECHANICAL UPRIGHT DIAPHRAGM EXPANSION TANK c/w SIGHT GLASSET-2 AMTROL AX-20V 11 41 125 psi 150 psi 670 mm 300 mm SE-06 MECHANICAL UPRIGHT DIAPHRAGM EXPANSION TANK c/w SIGHT GLASSGFT-1 AXIOM SF-100 GLS FILL 20 75 1240 mm 610 mm SE-06 MECHANICAL AUTOMATIC GLYCOL FILL TANK c/w FACTORY LOW LEVEL ALARM TIED INTO BMSGFT-2 AXIOM MF200 GLS FILL 6 23 410 mm 300 mm SE-06 MECHANICAL AUTOMATIC GLYCOL FILL TANK c/w FACTORY LOW LEVEL ALARM TIED INTO BMSRWT-1 ZCL COMPOSITES Z86SW RAINWATER STORAGE 7000 26498 6000 mm 2500 mm COMPOSITE STORAGE TANK c/w 900Ø MAN HOLE, 100mm INLET, 100mm
OVERFLOW
FAN SCHEDULE
UNIT NO. MAKE MODELAIR FLOW DUCT LOSS MOTOR LOCATION
REMARKSCFM L/s in wg Pa RPM W V/Ph/Hz NO NAMEEF-1 GREENHECK SP-A410 410 190 0.1 25 1000 120 120/1/60 SE-07 ELECTRICAL ELECTRICAL ROOM HEAT REJECTION FANEF-2 GREENHECK SP-A410 410 190 0.1 25 1000 120 120/1/60 SE-06 MECHANICAL MECHANICAL ROOM HEAT AND REFRIGERANT REJECTION FANEF-3 GREENHECK CSP-A390 390 190 0.2 60 1350 140 120/1/60 SE-07 ELECTRICAL SERVER ROOM HEAT REJECTION FANSPF-1 GREENHECK CSP-A410 405 190 0.1 35 1200 120 120/1/60 ES-08 CORRIDOR STAIRWELL PRESSURISATION FAN TIED INTO FIRE ALARM PANELSPF-2 GREENHECK CSP-A410 405 190 0.2 60 1200 120 120/1/60 ES-01 CORRIDOR STAIRWELL PRESSURISATION FAN TIED INTO FIRE ALARM PANEL
DOMESTIC WATER HEATER SCHEDULE
UNIT NO. MAKE MODEL VOLUME
FIRST HOURRATING MAX. HEAT ELECTRICAL LOCATION
REMARKSGPH L/H MBH kW REMARKS VOLTS NO NAMEDWH-1 AO SMITH PHPT-80 300 L 84.0 5.3 15 4.5 4500W MAX. 208/1/60 SE-06 MECHANICAL HYBRID ELECTRIC WATER HEATER. 2000W HEAT PUMP, 4500W TRADITIONAL ELECTRIC
PLUMBING FIXTURE SCHEDULE
FIXTURE TYPE DESCRIPTION COUNTFD-1 FLOOR DRAIN - WASHROOM Drain: 3 inch dura-coated cast iron floor drain with invertible membrane clamp and adjustable collar with “Type B” polished nickel bronze strainer. Zurn model ZN-415-B 6FD-2 FLOOR DRAIN - SERVICE AREA Drain: 3 inch dura-coated cast iron floor drain with invertible membrane clamp and adjustable collar with “Type B” polished nickel bronze strainer. Zurn model ZN-415-B 10FD-3 FLOOR DRAIN - SERVICE AREA c/w FUNNEL Drain: 3 inch dura-coated cast iron body with bottom outlet, and adjustable collar c/w “Type BF” polished nickel bronze open throat oval funnel grate. Zurn model ZN-415-BF 3KS-1 SINK - KITCHEN DOUBLE Basin: 775x450, 18 gauge stainless steel counter mounted, double equal basin. Franke Model D6410PCB-1
Trim: Polished Chrome finish, counter mounted, 6.8LPM single lever faucet, aerator, no side spray. Kohler Model Purist K7507.2
LAV-1 STANDARD LAVATORY Basin: 550mm x 560mm, vitreous china, self-rimming, 3/4 counter, concealed front overflow. American Standard Mezzo Series Model 996001Trim: 2LPM, 10 second run time, polished chrome finish, aerator, single supply, thermal mixing, laminar flow, hydropower charging sensor faucet. Toto Model Helix TEL5LC.
10
MS-1 600x600 MOP SINK Basin: Square, molded stone, plain curbs, 610mm x 610mm x 254mm deep (24” x 24” x 10”). Stainless steel drain with strainer, 76mm (3”) outlet. Fiat Model MSB2424. OrEquivalent.Trim: Chicago model 897-369XK wall mounted two handle faucet, 203mm (8”) centre-set, solid brass exposed body construction, ceramic 1/4 turn cartridge, unrestricted hoseend outlet, atmospheric vacuum breaker, metal red and blue index buttons, 60mm (2-3/4”) long lever handles with vandal-resistant screw, adjustable wall brace. Include stainlesssteel back splash panel. Or Equivalent.
4
RD-1 STANDARD ROOF DRAIN Drain: 300mm thermally broken roof drain. Dura-coated cast iron body with combination membrane flashing clamp/gravel guard and poly dome. Zurn model Z-121. 8RD-2 PATIO DRAIN Drain: Patio area drain, Thermally broken, dura-coated cast iron body with 75mm bottom outlet and combination invertible membrane clamp, vertically adjustable nickel-bronze
head with clamp collar. Zurn model2
SH-1 SHOWER TRIM Surround: Built in place shower surround. Refer to architectural drawings for detailing.Trim: American Standard Moments shower head and trim Model T506/R120S pressure balancing mixing valve, brass body, integral hot limit stop, screwdriver stops. Brass wallescutcheon, 6.6 L (1.75 US Gal) flow per minute adjustable 3 function showerhead. American Standard hand shower Model 1662.604 5.7 LPM (1.5 GPM) maximum flow rate, spraypattern adjust. Watts shower drain Model FD-100-A 2" (51mm) outlet, epoxy coated cast iron, anchor flange, adjustable round nickel bronze strainer, reverisble clamping collar.
5
UR-1 URINAL W/ CONCEALED FLUSH VALVE Urinal: Vitreous china, 0.5L low consumption washout, wall hung urinal with flushing rim, integral trap, stainless steel strainer, 20mm back spud. American Standard Washbrook SeriesModel 6515005.Carrier: J.R. Smith Model 0637 off the floor supportFlush Valve: Concealed, sensor actuated, single flush, hydropower charging flushometer with 20mm back spud connection, angle stop and vacuum breaker. Toto ModelTEU2UN11.
4
WC-1 FLUSH VALVE TOILET Bowl: High Mount 1.1 US gallon (4 liter) flush elongated washdown bowl with open flushing rim. Back spud connection. 54mm trapway as standard. American Standard MaderaSeries Model 3451.001.020Flush Valve: Concealed, battery powered, self regenerating, sensor actuated flushometer with 40mm back spud connection. Toto Model TET2GNSeat: Solid white plastic elongated open front seat, hinge with built-in check and stainless steel posts. Centoco Model AM1500STSCCSS.001.
11
ROOF
PENTHOUSE MECH. ROOM
- WEST EXTERIOR
WATER TO WATER HEAT PUMP SCHEDULE
UNIT NO. MAKE MODELSOURCE FLOW SOURCE LOSS LOAD FLOW LOAD LOSS HEATING COOLING ELECTRICAL LOCATION
REMARKSGPM L/s ft kPa GPM L/s ft kPa MBH kW MBH kW REQUIREMENTS VOLTS NO NAMEHP-6 WATERFURNACE NDW180R SE-06 MECHANICAL c/w BACNET INTERFACE45 2.8 6.9 21 36 2.3 7.1 21 125 36 165 48 MCA: 58.5A MOCP: 80A 208/3/60
RADIANT PANEL SCHEDULE
UNIT NO. MAKE MODEL W/m VOLTS REMARKSRP-1 OULETTE ODBA ARCHITECTURAL SERIES 787 W OPERATED BY BMS. PROVIDE SPACE TEMPERATURE SENSOR208/1/60
NO. Y/M/D DESCRIPTION0 2014/04/11 ISSUED FOR
CONSTRUCTION
E
K
M
M
B
M
M
S
S
V
s
CM
F
G
ISO
MM
F
T
FS
EOL
ASD
BD
DD
M
S
BATT
T
FLUORESCENT STRIP LUMINAIRE
LUMINAIRES
POWER
FIRE ALARM
DATA
NOTES / ABBREVIATIONS
PUBLIC ADDRESS
PANEL BOARD DESIGNATIONPNL - M 6 E A
INDIVIDUAL PANEL DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600VFLOOR LEVEL SERVICEDCDP = CENTRAL DISTRIBUTION PANELBOARDPNL = BRANCH CIRCUIT PANELBOARD
TRANSFORMER DESIGNATION
TX - 1 E A
TRANSFORMER DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)FLOOR LEVEL SERVICEDTRANSFORMER
MOTOR CONTROL CENTER DESIGNATIONMCC - 1
INDIVIDUAL DESIGNATION NUMBERMOTOR CONTROL CENTER
LOW VOLTAGE RELAY CABINET DESIGNATION
LVRC M - 6 E AINDIVIDUAL DESIGNATION NUMBEREMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600VFLOOR LEVEL SERVICEDLOW VOLTAGE RELAY CABINET
CIRCUIT DESIGNATION2 E A 15
PANELBOARD CIRCUIT POSITION NUMBERPANELBOARD DESIGNATIONEMERGENCY (BLANK FOR NORMAL POWER)VOLTAGE2=120/208V6=347/600V
MOTOR FEEDER DESIGNATIONMCC #STACK #CELL #
EQUIPMENT DESIGNATION
ABCXXX
CEILING SUSPENDED FLUORESCENTLUMINAIRE
SURFACE MOUNTED OR RECESSEDPOT LUMINAIRE
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
20 AMP RECEPTACLE
FOURPLEX RECEPTACLE
CONTROL MODULE
SPRINKLER FLOW VALVE
SPRINKLER GATE VALVE
HEAT DETECTOR
CATV
DATA
ISOLATION MODULE
MONITORING MODULE
PULL STATION
TAMPER SWITCH
SMOKE DETECTOR
HORN STROBE
SECURITYCARD READER
ELECTRIC STRIKE
KEYPAD
MAGNETIC LOCK
MOTION DETECTOR
PUSHBUTTON
BUZZER
ELECTROMAGNETIC DOOR LOCK
SPEAKER
MICROPHONE OUTLET
SPEAKER VOLUME CONTROL
SPEAKER HORN
CAT6 NAMING CONVENTION
3 V W 1 1 - 48
RACK #LOCATION SERVICED(ie. WEST)VOICEFLOOR LEVEL SERVICED
PATCH #PORT #
SITEDUPLEX REC
SINGLE POLE LUMINAIRE
SURFACE / RECESSED LUMINAIRE
WALL MOUNT DEVICE
CEILING MOUNT DEVICE
FLOOR MOUNT DEVICE
1050 Aff. (SYMBOL ABOVE POWER DEVICE) BLANK OFF DEVICE
WEATHERPROOF DEVICE
EXPLOSION PROOF DEVICE
GROUND FAULT PROTECTED DEVICE
EXISTING DEVICE TO REMAIN
RELOCATE EXISTING DEVICE
REMOVE EXISTING DEVICE
BO
WP
EXP
GF
ER
RL
R
RE-USE EXISTING DEVICERU
•
INDICATES DEVICE MOUNTED BELOWMILLWORK COORDINATE EXACT MOUNTINGHEIGHT WITH ARCH. DETAIL
*
MAIN DISTRIBUTION PANELMDP
SUB DISTRIBUTION PANELSDP
WIRE GUARDWG
LOW VOLATGELV
LOW VOLTAGE RELAY PANELLVRP
SURGE SUPPRESSION DEVICESP
MAGNETIC PROTECTION DEVICEMG
HANDS. OFF. AUTO.HOA
TRANSIENT VOLTAGE SURGE SUPPRESSION(LOW VOLTAGE)TVSS
TRANSFORMERT#
MOTOR CONTROL CENTERMCC
DRAWING KEYNOTER
MOTOR PROTECTION DEVICEMP
INDICATES DEVICE MOUNTED ABOVEMILLWORK COORDINATE EXACT MOUNTINGHEIGHT WITH ARCH. DETAIL
SURFACE MOUNTED FLUORESCENTLUMINAIRE
CEILING SUSPENDED POT LUMINAIRE
NURSE CALL
WALL MOTION WITH SWITCH BYPASS
LV SWITCH
208V SPECIALTY RECEPTACLE
CAR PARK PEDESTAL
END OF LINE RESISTOR
AIR SAMPLING DEVICE
BEAM DETECTOR
DISCONNECT
DUCT DETECTOR
NOTES / ABBREVIATIONS
BOLLARD
EQUIPMENT MOUNTING HEIGHT
POWER GENERAL NOTES
COMMUNICATION GENERAL NOTES
LIGHTING GENERAL NOTES
NOTES / ABBREVIATIONS
FIRE ALARM GENERAL NOTES
MOTION DETECTOR LINE VOLTAGE
MOTION DETECTOR LOW VOLTAGE
STROBE
EMERGENCY SIGN
EMERGENCY BATTERY PACK
EMERGENCY REMOTE HEAD
THERMOSTAT
DRAWING KEYNOTE#
LINE VOLTAGE DIMMERd
PROJECT GENERAL NOTES
SECURITY GENERAL NOTES
1. ALL LIGHTING WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING LIGHTING WIRING SHALL BE PAINTED YELLOW AND SHALL NOT CONTAIN WIRING THAT ISNOT PART OF THE LIGHTING SYSTEM.
2. CIRCUITS ARE INDICATED BESIDE ELECTRICAL EQUIPMENT. FOR EXAMPLE: "2A-1" INDICATES CIRCUIT 1 ON PANEL 2A. ELECTRICAL OUTLETS LABELED "GFI" ARE TO BEGROUND FAULT INTERRUPT TYPE OUTLETS.
3. MOUNTING HEIGHTS DIFFERING FROM THE TYPICAL HEIGHTS LISTED IN THE SPECIFICATION ARE INDICATED AS "+xxxx", WHERE xxxx IS THE HEIGHT ABOVE FINISHED FLOOR INmm.
4.CONTRACTOR IS RESPONSABLE FOR THE INSTALLATION OF A FULLY FUNCTIONAL LIGHTING SYSTEM. DRAWINGS IDENTIFY INTENT OF SYSTEMAND IT'S DEVICES.
1. ALL FIRE ALARM WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING FIRE ALARM WIRING SHALL BE PAINTED RED AND SHALL NOT CONTAIN WIRING THAT IS NOT PART OFTHE FIRE ALARM SYSTEM.
2. THE FIRE ALARM SYSTEM IS ADDRESSABLE WITH CLASS A WIRING. OUTGOING PATH AND RETURN PATH MUST BE IN SEPARATE CONDUIT. PROVIDE ISOLATION MODULES AS INDICATED ONDWGS.
3. ALL DOOR SECURITY WIRING AND CONDUIT IS TO BE PROVIDED UNDER THIS CONTRACT.
4. CONFIRM ANY AND ALL CHANGES TO FIRE ALARM DESIGN WITH THE ELECTRICAL CONSULTANT PRIOR TO INSTALLATION, LOCATIONS ARE TO BE DOCUMENTED AND PROVIDED WITHIN THE ASBUILT UPON COMPLETION OF CONSTRUCTION.
5. ISOLATION MODULES ON ARE TO BE INSTLLED ON BOTH SIDES OF FIRE SEPERATIONS AND AS INDICATED IN DRAWINGS.
6. FIRE ALARM SYSTEM TO BE PROGRAMMED AND PRE-VERIFIED PRIOR TO REQUEST FOR VERIFICATION/INSPECTION WITH ELECTRICAL CONSULTANT.
7. PROVIDE FIRE STOPPING (TO MATCH RATING OF FIREWALL) WHERE ELECTRICAL CONDUIT PENETRATES THROUGH A FIRE SEPARATION. REFER TO ARCHITECTURAL DRAWINGS FOR FIRESEPARATION LOCATIONS.
8. ALL CONDUIT TO BE INSTALLED FOR DEVICES ON EXPOSED CONCRETE IS TO BE INSTALLED IN CONCRETE. ONLY EXCEPTION ARE ELECTRICAL ROOMS, MECHANICAL ROOMS ANDCOMMUNICATION ROOMS. ATTENTION SHOULD BE MADE TO PROTECT INTERIOR OF JUNCTION BOXES FROM CONCRETE.
1. PROVIDE ALL ELECTRICAL CONNECTIONS TO DEVICES REQUIREING POWER WITHIN MILLWORK.
2. REFER TO MECHANICAL DRAWINGS AND COORDINATE WITH MECHANICAL CONTRACTOR FOR ALL CONNECTIONS TO MECHANICAL EQUIPMENT.
3. ALL RECEPTACLE WITHIN 1m OF WATER SUPPLIES ARE TO BE PROTECTED WITH GFCI RECEPTACLES.
4. REFER TO ARCHITECTURAL DRAWINGS FOR ALL POWER LOCATED WITHIN AND AROUND MILLWORK PRIOR TO ROUGH-IN.
5. REFER TO MECHANICAL DRAWINGS M301,302,303 FOR FAN COIL LOCATIONS. A 20AMP CIRCUIT IS TO FEED A MAXIMUM OF 5-FC UNITS.
6. ALL TRANSFORMERS ARE TO BE K-RATED TO MITIGATE HARMICS.
7. ALL PNLs AND DISTRIBUTION CENTERS ARE TO HAVE 20% SPARE CAPACITY.
8. PROVIDE POWER TO ALL WINDOW OPERATORS.
9. CONDUCTOR AND DISTRIBUTION PANELS ARE OVERSIZED AS INDICATED TO HANDLE FUTURE UPS AND GENERATOR SIZE INCREASES AS WELL ASIMPROVING VOLTAGE DROP LOSSES. CABLE SIZES TO BE AS INDICATED UNLESS LARGER SIZE IS REQUIRED TO MEET CEC REQUIREMENTS.
10. ALL DISCONNECT SWITCHES ARE TO BE HEAVY DUTY, LOCKABLE IN 'OFF' POSITION.
18. ELECTRICAL CONTRACTOR TO SUPPLY AND INSTALL ALL STARTERS UNLESS OTHERWISE NOTED. (VFD'S ARE SUPPLIED BY MECHANICAL)
19. ELECTRICAL CONTRACTOR TO INSTALL ALL PILOT DEVICES UNLESS OTHERWISE NOTED ON MECHANICAL DRAWINGS.
20. WHERE EMT IS USED IN ABOVE GRADE SLABS, 90 DEGREE BONDS STUBBED OUT OF SLAB ARE TO BE IN EMT.
21. ELECTRICAL CONTRACTOR IS TO PROVIDE CONDUIT FOR ALL MECHANICAL CONTROLS WIREING INCLUDING TERMOSTATS, AND BMS CONTROLWIRING. COORDINATE WITH CONTROLS AND MECHANICAL CONTRACTOR ON SITE.
1. ALL COMMUNICATION WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING COMMUNICATION WIRING SHALL BE PAINTED BLUE AND SHALLNOT CONTAIN WIRING THAT IS NOT PART OF THE COMMUNICATION SYSTEM.
2. ALL COMMUNICATION CABLE TO BE CAT 6.
3. EACH LOW VOLTAGE SYSTEMS WITHIN THE BUILDING TO HAVE DIFFERENT COLOUR TO DISTIGUISH SYSTEM WITHIN COMMUNICATION ROOM..
4. ALL MECHANICAL EQUIPMENT TO BE CONNECTED BY COMMUNICATION CABLE.REFER TO MECHANICA DRAWINGS AND COORDINATE WITH MECHANICALCONTRACTOR.
5.REFER TO MECHANICAL DRAWINGS FOR LOCATION OF THEMOSTATS. ELECTRICAL CONTRACTOR TO PROVIDE CONDUIT FROM FAN COIL UNITS TOTHERMOSTAT LOCATIONS.
6. OWNER TO SUPPLY COMMUNICATION RACK PRIOR TO ELECTRICAL CONTRACTOR INSTALLING PATCH PANELS AND TESTING COMMUNICATION CABLING.
7. ELECTRICAL CONTRACTOR TO CONFIRM RACK POWER REQUIREMENTS PRIOR TO COMM ROOM ROUGH-IN.
NOTE: ALIGN ALL EQUIPMENT VERTICALLY AND HORIZONTALLY
FLOOR
FINISHED FLOORCONSOLIDATIONZONE BOX
RECESSFLOORBOX
DISCONNECT
STARTER
FOR
FIN
ISH
ED C
EILI
NG
HE
IGH
T
REF
ER T
O A
RC
HIT
ECTU
RAL
DR
AWIN
GS
2000
2100
1800
1400
300
FAHORN
EMERGENCYLIGHTINGUNIT
DOOR ENTRYPUSHBUTTON
SWITCH
PULLSTATION
EOLA
RECEPTACLEMECH. ROOM
RECEPTACLE
1500
TV TEL.INTER-COM
1. ALL CONDUIT FOR MAIN BUILDING SERVICE SPACE IS NOT TO ENTER TENANT SPACES..
2. ALL SWITCHES AND ELECTRICAL EQUIPMENT TO BE LABELED WITH LAMACOID LABELS UNLESS IT IS PART OF THE LIGHTING SYSTEM.
3. ALL FLOOR AND WALL PENETRATION REQUIRED TO BE MADE FOR THE ELECTRICAL INSTALLATION REQUIRES FIRE STOPPING, WHERE REQUIRED BY CODE.
4. CONDUIT IS TO BE RUN PARALLEL TO BUILDING LINES UNLESS OTHERWISE INDICATED. RIGID CONDUIT TO BE INSTALLED AS INDICATED IN DRAWINGS AND FOR ALL EXPOSEDAREAS AND UNDER ACCESS FLOOR.
5. PROVIDE ALL ELECTRICAL CONNECTIONS TO DEVICES REQUIREING POWER WITHIN MILLWORK.
6. MAXIMUM VOLTAGE DROP TO BE 3%.
7. ALL CONDUCTORS ARE TO BE COPPER UNLESS OTHERWISE NOTED.
8. JUNCTION BOXES ON EXTERIOR WALL TO HAVE 35mm OF SEMI-RIGID THERMAL INSULATION.
9. ALL CONDUIT IS TO BE LOCATED IN THE CONTRETE TOPPING ON THE SECOND AND THIRD FLOORS. NO CONDUIT IS TO BE INSTALLED SURFACE MOUNTED TO THE WOOD DECK.NO EXPESED CONDUIT ON CEILINGS OR WALLS EXCEPT IN SERVICE SPACES.
10. REFER TO ARCHITECTURAL EXTERIOR ELEVATION FOR LOCATION OF LIGHT FIXTURES, EXIT SIGNS, FIRE ALARM DEVICES AND OUTLETS. REFER TO A401-A408.
11. PROVIDE 100mm HOUSEKEEPING PADS BELOW ALL ELECTRICAL EQUIPMENT FLOOR MOUNTED IN SERVICE SPACES.
1. ALL CARD ACCESS WIRING IS TO BE WITHIN EMT CONDUIT. JUNCTION BOXES CONTAINING CARD ACCESS WIRING SHALL BE PAINTED PURPLE AND SHALL NOT CONTAIN WIRING THAT IS NOTPART OF THE CARD ACCESS SYSTEM.
2. CONTRACTOR TO PROVIDE CONDUIT AS REQUIRED BY THE DOOR HARDWARE AND SECURITY CONTRACTORS.
3. CONFIRM WITH LOCATION OF BARRIER FREE PUSH BUTTONS WITH DOOR HARDWARE CONTRACTOR PRIOR TO ROUGH-IN.
4. ELECTRICAL DRAWINGS IDENTIFY DOOR AND APPROXIMATE LOCATION OF THE CARD READERS AND SECURITY DEVICES. EXACT LOCATION OF DEVICES AND WIRING REQUIREMENTS ARE TOBE PROVIDED BY THE ARCHITECT AND DOOR HARDWARE CONTRACTOR.
5. ALL SECURITY AND CARD ACCESS EQUIPMENT AND CONTROLLES ARE TO BE LOCATED ON THE SECURED SIDE OF THE DOOR.HEAD END EQUIPMENT IS TO BE LOCATED WITHIN THEBUILDINGS COMMUNICATION ROOM.
This drawing is a copyright and the exclusive property of ManascIsaac Architects Ltd., and shall not be reproduced, nor distributed,nor used in any way without their written permission. Thearchitectural design and all other information shown on thisdrawing shall not be copied, nor loaned out, nor recreated withoutwritten consent by Manasc Isaac Architects Ltd.
DRAWING SCALE
PROJECT #
REVISION
NOTES
PERMITS AND SEALS
PROJECT NAME
CLIENT
SUBCONSULTANT
ARCHITECT
DRAWN BY
DESIGNED BY
CHECKED BY
DRAWING TITLE
DRAWING NUMBER REVISION
ISSUED FOR CONSTRUCTION2014/04/14
NTS
DP
MM
MM
21-3180
SYMBOL SCHEDULE /LEGEND
E000
MOSAIC CENTRE FORCONSCIOUS COMMUNITY
AND COMMERCE
NO. Y/M/D DESCRIPTION