mshda standards of design - som - michigan€¦ · general design parameters for housing financed...

71
MSHDA STANDARDS OF DESIGN January 10, 2017 MSHDA STANDARDS OF DESIGN The Michigan State Housing Development Authority Standards of Design defines the design process and the specific requirements for multifamily housing financed through the Authority. This version of the Standards of Design replaces all previous versions. The following Standards are requirements of the Multifamily Design Review Process for the Michigan State Housing Development Authority. It is the intent of these Standards and the Design Review Process to insure that housing financed through MSHDA’s Multifamily lending programs is the best housing that can be provided. Nothing in this Standard shall be interpreted to waive the requirements under the Michigan Building Codes, The Federal Fair Housing Act, The Uniform Federal Accessibility Standards, The Americans with Disabilities Act or any other applicable law. It is also the intent of the Design Review Process to determine whether specific standards should be modified for an individual development in order to meet that development’s unique site, design, financing or market constraints. The primary changes in this edition is the family and senior requirements have been separated and there are fewer references to items that are already found in the building codes. Maryanne Vukonich, Chief Architect, 517 373-9478, [email protected]

Upload: phungtu

Post on 04-Jun-2018

231 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

January 10, 2017

MSHDA STANDARDS OF DESIGN The Michigan State Housing Development Authority Standards of Design defines the design process and the specific requirements for multifamily housing financed through the Authority. This version of the Standards of Design replaces all previous versions. The following Standards are requirements of the Multifamily Design Review Process for the Michigan State Housing Development Authority. It is the intent of these Standards and the Design Review Process to insure that housing financed through MSHDA’s Multifamily lending programs is the best housing that can be provided. Nothing in this Standard shall be interpreted to waive the requirements under the Michigan Building Codes, The Federal Fair Housing Act, The Uniform Federal Accessibility Standards, The Americans with Disabilities Act or any other applicable law. It is also the intent of the Design Review Process to determine whether specific standards should be modified for an individual development in order to meet that development’s unique site, design, financing or market constraints. The primary changes in this edition is the family and senior requirements have been separated and there are fewer references to items that are already found in the building codes. Maryanne Vukonich, Chief Architect, 517 373-9478, [email protected]

Page 2: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

2 January 10, 2017

TABLE OF CONTENTS 00000 General Design Requirements 6

00010 General Design Parameters 6 00020 Design Development Policies 7

00021 Architectural Design Responsibility 9 00030 Reviewer Listing 10 00040 Accessibility Policy 11 00045 Environmental Design Concerns 12 00050 Field Engineering Submission Requirements 13

00051 Boundary and Topographic Site Survey 13 00052 Soil Boring Reports 14 00053 Soils Investigation - Previously Developed Sites 15

00100 Design Review Process 18 00110 Design Drawing & Specification Requirements 20

00111 General 20 00112 Phase 1 21 00113 Phase 2 22 00114 Phase 3 23 00115 Color and Material Selections 24

00150 Specific Design Standards 25 02000 Site Work 28

02001 Design 28 02280 Termite Control 29 02780 Exterior Lighting 30 02810 Irrigation 31 02860 Tot or Play Lots 32 02900 Plantings 32 02980 Site Signs 32

03000 Concrete 33 03001 Walk Intersections

03030 Concrete Finishing Materials 06000 Wood and Plastics 34

06001 Basic Trim 06010 Lumber 06190 Trusses 06240 Laminates 06600 Plastic Fabrications

i

Page 3: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

3 January 10, 2017

07000 Thermal & Moisture Protection 35 07195 Sheathing

07200 Insulation 07310 Shingles 07500 Membrane Roofing 07650 Flashing 07710 Gutters 07920 Sealants and Caulking

08000 Doors & Windows 36 08100 Metal Doors and Frames 08200 Wood and Plastic Doors 08310 Sliding Glass Doors 08390 Screen and Storm Doors 08500 Windows 37 08630 Vinyl Windows 08710 Finish Hardware

08742 Electric Locksets 38 08780 Cabinet and Drawer Hardware

08810 Glass

09000 Finishes 39 09250 Gypsum Board 09650 Vinyl Flooring 09681 Carpet 40 09682 Carpet Pad 09900 Painting 41

10000 Specialties 42

10550 Mailboxes 10800 Grab Bars 10825 Residential Bath Accessories

11000 Equipment 43

11250 Water Softeners 11452 Residential Appliances 11455 Kitchen and Bath Cabinets 44

12000 Furnishings 45 12505 Blinds 12664 Tables and Accessories

14000 Conveying Systems 45

14200 Elevators

i

Page 4: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

4 January 10, 2017

15000 Mechanical 46 15050 Basic Materials and Methods 15180 Pipe Insulation 47 15250 Water Softeners and Water Conditioning 15460 Plumbing Fixtures and Trim 48 15470 Water Heaters 15500 Fire Protection Systems 49 15600 Heat Generation 15900 Mechanical Controls

16000 Electrical 50

16140 Wiring Devices 16200 Emergency Generator 16500 Lighting 51 16503 Poles, Posts and Standards 16510 Interior Luminaires 16520 Exterior Luminaires 52 16522 Roadway and Parking Luminaires 16720 Alarm and Detection Systems 53 16722 Building Security and Detection Systems 16760 Intercommunications 16770 Broadband Infrastructure 16780 Television Systems

16850 Electric Heating MSHDA Senior Housing Standards of Design 54 00010 General Design Parameters for Senior Housing 55 02000 Site Work 58

02001 Design

08000 Doors & Windows 59 08001 Doors 08200 Wood and Plastic Doors 08710 Finish Hardware

08780 Cabinet and Drawer Hardware

10000 Specialties 60 10001 Package Shelves 10002 Handrails 10800 Grab Bars

11000 Equipment 61

11452 Residential Appliances 11455 Kitchen and Bath Cabinets

15000 Mechanical 62

15900 Mechanical Controls

Page 5: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

5 January 10, 2017

MSHDA Rehab Standards of Design 63 Occupied Housing Developments 64 00052 Investigation of Structures to be Rehabbed 65 00100 Rehab Design Review Process 65 00120 Replacement Criteria 66

i

Page 6: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

6 January 10, 2017

00000 General Design Requirements 00010 General Design Parameters General design parameters for housing financed by MSHDA shall include these

Standards, latest applicable codes e.g. Michigan Building Codes, Energy Codes, NEC, ASHRAE, NFPA, State Elevator Code, applicable ordinances, and Fair Housing Amendments Act. Also the following regulations shall apply: 1. when Federal programs or funding are involved in the development, use

Section 504 of the Rehabilitation Act of 1973 and the Uniform Federal Accessibility Standards (UFAS);

2. when HUD programs are involved and when program guidelines require conformance to MPS, use HUD Minimum Property Standards; and

3. when areas within the development are used for public functions, use the Americans with Disabilities Act (ADA).

Design parameters discussed and agreed to at Pre-Design meetings, including Development Amenities, shall be incorporated into the design and construction documents.

Architects, engineers and developers should note that these Standards are

minimums. Good architectural and engineering practices and manufacturer recommendations shall also be observed. MSHDA Design Review comments may address such good practices.

Page 7: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

7 January 10, 2017

00020 Design Development Policies

A. Architectural Design Responsibility Developers shall employ State of Michigan licensed architects for design and contract administration services. The design architects shall have experience appropriate to the design of housing proposed for the particular development and shall carry Errors and Omissions Insurance. The design architects shall contract with currently licensed landscape architects and engineers as necessary to carry out the design. Exceptions shall be that Civil Engineering site work and Survey work may be contracted directly by the developer, however, the architect will be required to coordinate the Civil Engineering with other design work.

The Owner-Architect Agreement requires the design architect to confirm that the construction documents conform to the MSHDA Standards of Design, The Federal Fair Housing Act and any other standards and procedures as may be in effect. When developments are funded with federal assistance (HOME units) Section 504 of the Rehabilitation Act of 1973 applies, and all service and submissions of the Architect shall also comply with the Minimum Guidelines and Requirements for Accessible Design as contained in 36 CFR Part 1190, et seq, or any subsequent replacement regulations, as well as the HUD Minimum Property Standards, and Manual of Acceptable Practices.

Typically, construction trade or design/build contractors and subcontractors shall not be employed to carry out design work. Where work such as fire suppression design, irrigation design, truss design and commercial kitchen design are carried out by design build contractors, the architect shall be responsible for coordinating and accepting their work.

Page 8: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

8 January 10, 2017

B. Errors and Omissions Insurance

Design and/or supervisory architects shall retain effective professional liability insurance in form, amount, and term satisfactory to the Authority.

All architects must furnish evidence of professional liability insurance satisfactory to the Authority prior to the date of submission of any preliminary drawings and/or specifications to the Authority. The insurance policy must be in full force and effect as of the date of submission, and must be kept in effect for a period of one year after substantial completion.

AMOUNT OF COVERAGE

Design and Supervisory Errors and Omissions insurance in an amount equal to the greater of $1,000,000 or 10% of the construction contract amount depending on the project size with a deductible minimum of $10,000 to maximum of $100,000 Supervisory only Errors and Omissions insurance in an amount of $250,000 for buildings with up to 3 floors and $500,000 for buildings 4 floors or more with a deductible minimum of $5,000 to maximum of $25,000

C. Design and Supervision of Housing in Excess of Three Stories in Height The Authority requires that appropriate experience of a proposed Design

Architect be documented prior to MSHDA approval of the architect’s firm. Experience is particularly critical in the design of housing developments in excess of three (3) stories in height. A registered structural engineer with appropriate experience must prepare related structural drawings. All firms proposed for doing such work shall submit documentation of their background in such design and further shall submit professional résumés documenting relevant experience of their participating architects and engineers for MSHDA review before proceeding with design. In cases where a Design Architect's firm does not have a qualified structural engineer possessing such experience on staff, a licensed independent structural engineering firm must be retained by the Design Architect. During construction, the Authority requires that the approved structural engineer participate in the supervision of such structures.

Page 9: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

9 January 10, 2017

00021 Architectural Design Responsibility The Authority relies heavily on the professional competency of participating

architectural firms and on the Authority's design process as documented in the MSHDA Standards of Design. For this process to work effectively, participants must encourage the free expression of both designing and reviewing architects. The Design Architects should fully express themselves in the design submissions and in their responses to reviews furnished by the Authority and must not submit proposals or certify drawings which they, as professionals, do not agree with or which are not prepared by, or under the direction of, the Design Architects’ firms.

It should be noted that the Authority will not approve multiple professional service

contracts. All architectural, planning, engineering, landscaping and other services, which contribute to the drawings and specifications by which a housing development is built, shall be in the employ of or under the direction of the Design Architect. Exceptions shall be that Civil Engineering site work and Survey work may be contracted directly by the developer, however, the architect will be required to coordinate the Civil Engineering with other design work.

Participation of the Contractor The Authority encourages constructive participation by the Contractor during the

design process inviting the Contractor's regular input to help maintain cost control for the proposed housing development. Recognizing that field experience has given Contractors unique and invaluable insights into cost-saving construction techniques, the Authority seeks the benefit of this experience as it relates to the design process. To facilitate a constructive exchange of ideas, the Authority also forwards review comments to the Sponsor and to the Contractor, as well as to the Design Architect.

Page 10: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

10 January 10, 2017

00030 Reviewer Listing

Architecture Review Consultants The Design Forum, Inc. 560 Fifth St. NW, Suite 201 Grand Rapids, MI 49504 (616) 454-1398 FAX: (616) 454-0944 Contact: Neale Bauman Byce & Associates, Inc. 487 Portage Street, P.O. Box 50866 Kalamazoo, MI 49005-0866 (269) 381-6170 FAX: (269) 381-6176 Contact: Michael Flynn

Stephen Auger & Associates

Architects, Inc. 214 Broadway, Suite 110 Lake Orion, MI 48362 Contact: Steve Auger Site Review Consultants Beckett and Raeder, Inc. 535 West William Suite #101 Ann Arbor, MI 48103 (734) 663-2622 FAX: (734) 663-6759 Contact: John Beckett O'Boyle, Cowell, Blalock & Associates, Inc. 521 South Riverview Drive Kalamazoo, MI 49004 (269) 381-3357 FAX: (269) 381-2944 Contact: Ken Peregon VIRIDIS Design Group 313 North Burdick Street Kalamazoo, MI 49007 (269) 978-5143 FAX: (866) 683-5060 Contact: Woody Isaacs

Engineering Review Consultants

Byce & Associates, Inc. 487 Portage Street, P.O. Box 50866 Kalamazoo, MI 49005-0866 (269) 381-6170 FAX: (269) 381-6176 Contact: Jim Escamilla

GeoTech, Inc. 4900 Cascade Rd., SE Grand Rapids (616) 949-3340

Page 11: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

11 January 10, 2017

00040 Accessibility Policy

New construction (structures containing 3 units or more): A percentage of the units as required by State Law, but no less than 1% of the total units, shall be fully accessible. If the development is primarily town homes, accessible units shall be ranch units. For ease in exiting in emergencies, accessible units shall be located on the ground floor (at grade) if possible. Rehabilitation: Accessible units shall be provided as required by State Law. Federal Funding: Where Federal funds such as HOME funds or housing vouchers are used in financing a development, the design must comply with all applicable Federal regulations, which means compliance with the Uniform Federal Accessibility Standards. Under UFAS, the required number of units designed for physical accessibility is 5% of the total number of units plus an additional 2% of the units be made accessible for persons with hearing and vision impairments. (Refer to HUD 24 CFR Part 8) (Refer also to 00010.)

Page 12: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

12 January 10, 2017

00045 Environmental Design Concerns Mitigation Design and construction documents shall incorporate work necessary to mitigate

environmental concerns identified by MSHDA and the Owner's consultants unless these concerns are addressed prior to construction start and are outside the limits of the construction documents. Mitigation methods shall be in conformance with a plan prepared in conformance with applicable State and Federal regulations and accepted by MSHDA.

Hazardous Material Notification In all developments involving demolition or rehabilitation, specifications shall be

written to include the following: "In carrying out the work of this contract, should the contractor encounter asbestos

or other toxic materials the contractor shall: 1. Notify all parties to this contract; 2. Notify applicable State and Local authorities; and (if the cleanup is to be carried

out under the direction of the contractor) 3. Make application for permits necessary for removal (or other methods of

mitigating the potential harmful effects) of such materials; and 4. Upon receipt of required permits mitigate potential harmful effects of such

materials in accordance with permits and applicable codes and laws." If the contractor is not to be responsible for mitigation, the sponsor/developer/owner shall carry out mitigation in accordance with the requirements as stated above.

Page 13: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

13 January 10, 2017

00050 Field Engineering Submission Requirements 00051 Boundary and Topographic Site Survey The purpose of these specifications is to designate and describe the minimum

requirements for a boundary and topographic site survey for use in the design and construction of MSHDA housing developments.

A. General In general, the surveyor shall perform all field work necessary to accurately

determine property lines and existing physical conditions of the site, set monument markers, establish bench marks and ascertain and record on a topographical map and boundary survey drawing the information and data as required and hereinafter specified. The surveyor shall obtain such information and data from public and other records, including a review of underlying documents to current (within 30 days) title work, as may be required to complete the work. All data and information required by these specifications shall be shown on the survey drawing or designated as nonexistent. Boundary and topographical work shall be signed and sealed by a licensed professional surveyor.

Compass direction shall be shown by an accurately positioned North Arrow

designated as (A) magnetic north or (B) true north. The legal description shall appear on the face of the survey map. Said

description shall conform entirely to the survey. Whatever form is utilized, the precise legal description shall be preceded by identification of the appropriate street address if one is available. Acceptable forms of legal description are the metes and bounds description or the lot and block description. Any contiguous plot shall be described by a single perimeter description of the entire property. Division into parcels shall be avoided unless such is requested to serve a special purpose. If the property is described as being on a filed map, the survey map should contain a legend relating the plot to the map on which it is shown.

Two bench marks referenced to an established datum shall be marked on a

permanent object adjacent to the site and clearly located and described on the survey drawing.

Boundary lines of the site shall be shown in bearings and distances. The survey drawing shall be prepared at a scale of not less than one inch equal

to 50 feet. All corners of the site and other boundary line intersections not previously

marked by a monument shall be marked. Where existing structures preclude setting monuments at the intersection of property lines, a brass pin should be set in the property line extended, tagged and so noted, along with the distance from the true corner. At least one corner of the property shall be designated by course and distance from a readily discernible reference marker. Location and description of each marker shall be shown on the survey drawing.

The total area within boundary lines shall be designated on the drawing in

square feet and in acreage, as well as the area of the property of each ownership within the boundary lines.

Page 14: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

14 January 10, 2017

B. Easements, Encroachments, Improvements Indicate any and all servient and beneficial easements and any and all

easements appurtenant to the property indicating the identity by Liber and Page, if any, the origin (e.g. Deed from A to B), if applicable, and nature. It is also desirable to describe an easement appurtenant to a fee parcel by using a separate parcel description.

Accurately and clearly indicate the location, dimensions and nature of (A) all

encroachments upon the property; (B) all encroachments upon adjoining property, streets or alleys by any buildings, structures or other improvements upon the property; and (C) all party walls between, with or adjoining the property and other property.

Indicate position, size and material of any and all improvements on the

property, including buildings, retaining walls, architectural walls, areaways, driveways, paving, etc. Indicate existence and location of off-site structures within 10 feet of the property lines.

Indicate the location of any and all adjacent building lines. Note names of

adjoining property owners. C. Trees

Indicate location, species and size of trees over six inches in trunk diameter, measured at breast height.

D. Roads and Right of Ways

The following data shall be indicated on survey drawing for all streets, alleys, roads, highways and rights-of-way adjacent to the site: Distance from property lines and dimensions; Type and condition of material; Type of curb and gutter; Elevations of sidewalk along edge nearest site at 50-foot intervals at

corners and points of slope change; Elevations of top of curbs and flow-line of gutters at 50-foot intervals at

corners and points of slope change; Description of proposed sidewalk curb and gutter improvements,

contemplated date of installation and proposed locations and elevations. E. Utilities

The following data pertaining to utilities adjacent to the site shall be shown and noted on the survey drawing: Location, type and capacity of available electric service, including lines,

poles and manholes; Location of water mains, hydrants and manholes, indicating size of water

mains; Location and size of gas mains, including type, pressure and source of gas

supply;

Page 15: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

15 January 10, 2017

Location, size, direction of flow, rate of fall and type of material of sanitary, storm or combined sewer mains. Indicate public or private and if use is exclusively for sanitary wastes or storm water drainage. Indicate elevations of flow-line, "in" and "out" inverts and location of manholes.

If a utility is not available at the site, it shall be noted if service is available in the community and where.

List the company or governmental body of jurisdiction for all utilities. F. Topography

Elevations of the site shall be taken on a grid suitable to the topography and size of the site. Contour lines shall be drawn at intervals that accurately reflect the existing topography of the site. Contour lines shall be at one-foot intervals. Elevations shall be marked on contour lines at regular intervals and shall be based on USGS datum.

G. Miscellaneous Information

Note other information pertaining to site conditions, e.g. abandoned underground foundations, ditches, culverts, mine shafts, tunnels, wells, sanitary drain fields, excavations, etc. Also indicate locations of any and all waterways, wetlands and established floodplains and floodways.

In addition to other contractual services, the surveyor shall obtain and/or verify requisite information and data from public records, including names, locations, dimensions and elevations of streets, curbs, gutters, sidewalks, established building lines, easements, utilities, proposed improvements, condemnations, etc., necessary for, and incidental to, a completed site survey, preparation of the drawing thereof and the certification by the surveyor that the data represented therein is true and correct.

H. Coordination with Legal Survey

The survey shall also meet the requirements of MSHDA's Legal document 026.

The drawing shall also have the imprint of the surveyor's registration seal or, in lieu thereof, a certification as to his state registration or license. The "Surveyor's Certificate" (Legal document 025) is required to be executed, sealed and submitted to MSHDA as a prerequisite to Initial Closing. Legal forms may be obtained from MSHDA's Legal Affairs Division.

The surveyor shall cooperate with the Title Company, Abstractor or Attorneys selected by the Sponsor to furnish title information in connection with the site in order that the numbering of certificates or opinions of title will correspond with the maps furnished by the surveyor. The surveyor shall review the Title Insurance Commitment/Policy for the particular parcel of property to insure the survey and the Title Insurance Commitment/Policy describe the same parcel of property. The survey must disclose all easements, rights-of-way and encroachments set forth in the Title Insurance Commitment/Policy by Liber and Page Number.

Page 16: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

16 January 10, 2017

00052 Soil Boring Reports

The soil survey is to be performed under the direction of a civil or geotechnical engineer registered in the State of Michigan. The entire site is to be inspected to note variations in types of soils and ground water conditions. Locations for borings are to reflect varying site conditions. Special attention is to be given to boring locations in low or marshy areas, areas where there is a history or evidence of fill or where rock may be expected. Soil borings are to be made with a drilling rig, taking samples as often as the character of the soil changes, and describing it in accordance with acceptable engineering standards. Samples are to be submitted to a soil specialist for analysis. The engineer is to indicate the location of borings on a boundary survey and log the borings on the site plan or on a separate document. The logs are to use an exaggerated vertical scale to indicate, with acceptable key names and symbols, the nature of soil composition at each stratum to a depth of 15 to 20 feet. For sites anticipating high-rise buildings, borings are to be concentrated in the area of the anticipated building location. At least one of these borings shall be drilled to a depth of 100 feet or to hardpan. Borings are to be performed after buildings have been located on the site plan. There shall be one boring per building for low-rise structures and one boring per wing for mid-rise structures with a minimum of three to four borings for this building type. Borings shall also be carried out in parking areas and roadways. The engineer shall indicate bearing capacities of soils at various levels with a recommendation for the footing / foundation type for proposed structures and shall provide a recommendation for pavement design of roads and parking. The engineer shall note and make recommendations on ground water conditions and remedies as needed.

Page 17: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

17 January 10, 2017

00053 Soils Investigation for Previously Developed Sites

Where proposed developments are to be located on previously developed sites, a soils investigation plan shall be submitted to the Authority and receive Authority agreement prior to Authority Feasibility. The intent of the plan is to determine the extent of underground debris that needs to be removed in order to construct the proposed development’s buildings, parking, and utilities. The plan shall be based on the location of previous structures using a review of historical Sanborn Insurance maps, similar historical information, historical aerial photographs, previous environmental investigations, and the proposed location of future buildings, parking and utilities. The plan shall call for test pit trenches, using a backhoe, to be dug across the width of all areas of previous structures. The extent of the test pit trenches shall be explicitly delineated in the plan. The extent shall be suitable to determine the amount and cost of debris removal and replacement of excavated materials. The test pits shall be a minimum of 18” wide and to the depth of virgin soil. Prior to undertaking the soil investigation, and only after plan approval, the development team shall notify the Authority’s Construction staff as to the time and place of the investigation to allow Authority staff to observe the soil investigation. A complete soils report of the investigation, prepared by a qualified professional soils engineer, shall be submitted to the Authority. This soils investigation shall not remove the development team from the responsibility to carry out soil borings necessary to adequately determine the bearing capacity of the soil and recommend an adequate structural design for buildings, parking and utilities. After the soils investigation and subsequent report, the developer, contractor and architect shall estimate the costs necessary to remove the underground debris and provide a “buildable” site. The costs shall be submitted to the Authority as a separate line item on the Authority’s Trade Payment Breakdown (TPB) form. This line item shall also include costs necessary to cover all environmental remediation of the site. The Authority shall review the soils removal costs and the environmental remediation costs as part of the TPB approval process for Feasibility. The “soft costs” portion of the Pro Forma for the development, as included in the Feasibility and Commitment action by the Authority’s Board, shall include a contingency for the removal of underground debris, environmental remediation and site restoration to a “buildable” condition, in an amount equal to or exceeding 1.5% of the construction contract amount.

Page 18: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

18 January 10, 2017

00100 Design Review Process

The Design Review Process includes the following stages: Initial Staff Review Site Analysis / Site Concept Design Development / Feasibility Construction Documents / Commitment

A. Initial Staff Review

The process starts when an application is received. The Housing Development Officer (HDO) sends a memo to MSHDA staff with information about the development team, the development type, size and location. The Chief Architect and Chief Construction Manager will visit the site.

B. Site Analysis / Site Concept

The Site Analysis and Site Concept Review meeting is a response to the preparation and submission of a Site Analysis and a Site Concept in accordance with MSHDA's Submission Requirements. (Refer to 00112.) This submission is prepared by the Developer's Design Team and submitted to MSHDA and to MSHDA's Site and Architectural Review Consultants ten working days prior to the scheduled Review Meeting. The MSHDA Site and Architectural Review Consultants will prepare and distribute a written review prior to the meeting. The Developer's Design Team shall prepare a written response for discussion at the meeting. The purpose of the Site Analysis / Site Concept meeting is to: explain the MSHDA Design Review Process discuss the site analysis agree on a conceptual plan for the development discuss applicable requirements discuss specific programmatic parameters agree on program amenities and to set forth a specific schedule

The Site Analysis / Site Concept meeting is a meeting of members of the Development Team, Authority staff from Development, Design, Market Analysis, Management and other areas as affected, and the Authority Site Review Consultant. . Site Concept Review meeting shall precede site plan approval by the local municipality.

The soils report shall be submitted to the Chief Construction Manager prior to Feasibility.

Page 19: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

19 January 10, 2017

C. Design Development / Feasibility

The Review of Design Development or Feasibility Drawings is the next stage of the Design Review Process. A complete Feasibility Submission, in accordance with the submission Requirements in the MSHDA Standards of Design, is made directly to MSHDA and MSHDA's Site and Architecture Design and Engineering Review Consultants. Allow ten (10) working days after documents are received for the Consultants to complete their review. After the documents have been corrected to meet the Review Consultants comments submit the documents to the MSHDA and the Review Consultants. After ten (10) working days for the Consultants to complete their review, a Feasibility Design Review Meeting is held. The participants at the meeting shall be members of the Development Team, Authority staff from Development, Design, Market Analysis, Management and other areas as affected, and the Authority Site and Architecture Design Review Consultants. The MSHDA Site, Architecture Design, and Engineering Review Consultants will prepare and distribute written reviews prior to the meeting. The Developer's Design Team shall prepare a written response. The purpose of this step is to definitively set forth and agree upon a design solution consistent with the Site Analysis and Site Concept, the Authority's Standards, the construction budget available to the development and, appropriate to, the needs of the anticipated future residents. The Development Team shall identify desired variances from the MSHDA Standards of Design. In requesting a variance the Development Team shall provide, for MSHDA's consideration, the reasons for requesting a waiver.

D. Construction Documents / Commitment

The Review of Construction Documents or Commitment Drawings is the next stage of the Design Review Process. A complete Commitment Submission is made directly to MSHDA. Allow ten (10) working days for the staff to complete their review. The purpose of this step is to complete construction documents consistent with the Design Development or Feasibility drawings, the Authority's Standards, the construction budget available to the development and, appropriate to, the needs of the anticipated future residents. The Development Team shall identify desired variances from the MSHDA Standards of Design. In requesting a variance the Development Team shall provide, for MSHDA's consideration, the reasons for requesting a waiver.

Page 20: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

20 January 10, 2017

00110 Design Drawing and Specification Submission Requirements 00111 General

It is necessary that the programming, planning, design and construction of housing developments be based on a logical, step-by-step process that proceeds from the general to the specific, from the overall to the detailed. Such a process will also provide MSHDA with a rational sequence for the review of applications for financial assistance. Therefore, the development process will be divided into three phases: Phase 1: Concept Plan Phase 2: Design Development / Feasibility Phase 3: Construction Documents / Commitment

The intent, content and requirements of each phase are outlined herein. Adherence to these requirements will insure expeditious process of applications and minimize the need for modifications. Each submission is to include the following basic information: A. All sheets should have: Number; graphic and lettered scale; north arrow; sheet title. B. Title Sheet

Development location, including location map; Sponsor; Architect; Landscape Architect, Site Planner, Surveyor, Engineer (if applicable); special consultants; revision dates; MSHDA number; and index of contents.

C. Development Data Summary, (on Title Sheet) including: (detailed area

calculations are not required at Site Concept Phase) Total number of family units; area per unit type (net and gross); breakdown of

the number of each type of unit (breakdown is to include barrier free units). Total number of senior units; area per unit type (net and gross); breakdown of

the number of each type of unit (breakdown is to include barrier free units). Total number of family parking spaces (covered and uncovered). Total number of senior parking spaces (covered and uncovered). Total area of the site in acres. Gross area tabulation, e.g. senior building, senior commons, family building,

family commons, commercial building.

Page 21: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

21 January 10, 2017

00112 PHASE 1: Concept Plan

The intent is to prepare a concept appropriate to the site. The concept plan shall indicate general building masses, circulation (vehicular and pedestrian), parking, open spaces, special facilities, and site features portraying the overall intent, spatial form and system of development. It shall be prepared on a site topography base map with contours at no greater than 2' intervals and at a scale no smaller than 1"= 50'. Structures: Indicate location, arrangement and general groupings. Locate any recreation or service structures. Circulation: Indicate roadways, parking areas and services. Indicate the general walkway system and the connection to common facilities. Utilities: Indicate major trunk lines and connection points to existing utilities. Show easements. Recreation: Indicate open spaces and facilities. Indicate parking and service for common facilities. Parking: Location Grading: General character Snow storage areas Mounds and berms On-site storm water detention / retention Indicate any special problems Planting: Consider existing vegetation in concept development General planting concept

Page 22: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

22 January 10, 2017

00113 PHASE 2: Design Development/Feasibility

Submit one copy to MSHDA and to each Design Review Consultant (Site, Architectural, and Engineering). Provide a Development Data Summary (refer to Title Sheet specifications). A. Site Plan The design shall be developed from the concept plan. The Design Development Plan shall refine the arrangement and functional groupings of units to a more exact scale to create a meaningful sequence of usable spaces. Specific relationship of unit arrangement, of the structure to the site, site grading, circulation, lighting, paving, screening, setbacks, parking, play areas and recreation areas shall be presented. This plan should be produced at a scale of 1"= 50' or larger and include: Structures: Location, shape, size, arrangements and groupings. Circulation and Parking: Indicate location and materials of vehicular and pedestrian routes. Indicate parking/dwelling unit relationship, location and number of spaces. Soils: Depth and analysis of topsoil Locate soil borings and present data (may be separate report). Utilities: Indicate general major utility layout, easements and connections. Irrigation source. Recreation: Location and type of facilities. Grading: Resolve special and typical relationships General character, existing and proposed contours at 1' intervals, section, etc. Berms and mounds Storm water management; Detention and Retention areas Snow storage areas Planting: Indicate character Indicate screening concepts, relationship to units and open space, etc., with

sections or sketches Lighting: Location and Character (catalog illustration), height, wattage and photometric. Alta Survey: (reference to 00050 Field Engineering Submission Requirements, 00051 Boundary

and Topographic Site Survey).

Page 23: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

23 January 10, 2017

B. Residential and Community Buildings

Definitive designs for typical dwelling units, residential buildings and community building(s) shall be developed and submitted to MSHDA. These designs shall be based on careful study of the development program and concept plan. Dwelling Unit Schedule: Total number of units. Number and percent of total of each unit type. "Net Area" and "Gross Area" of each unit type. Dwelling Unit Design Development: Floor plans and sections (with dimensions), as required, at 1/4"=1'-0" scale for

each unit type (including door swings, doors and window locations). Room area, dimensions and designation of each room and space (including

storage). Demonstration of the "furnishability" of each unit type. Plans and elevations of typical residential buildings (groups of town houses) at

1/8"= 1'-0" scale. Indicate basic construction technique and exterior materials. Key residential

building plans to site plan. Outline specification. Community Facilities: Floor plans, sections and elevations (with dimensions) at 1/4”= 1'-0" scale of

community building(s). Indicate room areas. Gross area of community building(s). Outline specification. Nonresidential Facilities: Plans and elevations of commercial and other nonresidential facilities included

in development as appropriate. Additional Information: Such information as is necessary to fully illustrate development conditions

00114 PHASE 3: Construction Contract Documents/Commitment Submit one copy of the construction documents to MSHDA, including a digital copy.

Page 24: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

24 January 10, 2017

00115 Color and Material Selections:

Exterior and interior material selections shall be submitted and approved prior to initial closing. Upon receipt of a satisfactory submission, the Design Chief Architect shall issue a letter of approval. All approved submissions shall be retained by MSHDA and transmitted to MSHDA's Construction Specialist for field verification. Where a change in a specific item is desired after approval has been received, the Architect shall submit the request for change. Approval shall be given prior to placing an order for the new item. A. Submission Format Exterior and interior material selections shall be submitted on neutral color

boards, e.g. illustration boards. The boards are to be clearly labeled indicating where selections are intended to be used clarifying and distinguishing between selections for units and community spaces.

Selections shall be accompanied by written specifications regarding material name and identifying number, color and manufacturer. Where graphic location of materials warrants an explanation or numerous floor plan changes have occurred since Feasibility submissions floor plans necessary to indicate material locations shall also be submitted.

B. Exterior Material Selections: Samples of actual materials to be used in exterior construction are to be

submitted. Aluminum products may be represented by flat stock; paints or stains may be represented by "color chips" of paper. All visible surfaces are to be represented, including but not limited to, as follow:

Brick, siding, roofing, trim, gutters, downspouts, frames, doors and graphics. C. Interior Material Selections: Samples of actual finishes and materials to be used are to be submitted.

Surfaces, fixtures, etc., are to be represented, including but not limited to, as follows:

Carpet, vinyl products, ceramic tiles, quarry tiles, base trim, counter tops, wall coverings, paints, ceiling finishes, cabinets, all door finishes, appliances, draperies, and blinds.

Page 25: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

25 January 10, 2017

00150 Specific Design Standards

These Design Standards are guidelines to features and facilities which the Authority has found essential for sound affordable housing. In exceptional cases, departures from the Standards may be considered through the Design Review Process by which they may be accepted, rejected, or result in modified design, depending on the circumstances. In the case of measurable or numeric Standards, Standards given as minimum may be exceeded and maximums should not be exceeded.

A. General Building Arrangement Dwelling units shall not be located in basement spaces or where the finish

floor of the habitable area is entirely below grade.

Efficiency units are not an acceptable dwelling unit for MSHDA funding.

Units of three-bedroom or larger size shall have their entry at grade level. Their habitable spaces may be placed on a second floor level, but not at third floor level or above. Adequate sound insulation must be provided between units on separate floor levels.

Site plans shall not concentrate three and four bedroom units into one area.

Concentrating units in such a manner has an adverse impact on parking and site maintenance.

In all buildings that are designed to include a multiple number of dwelling

units, an enclosed access shall be provided to any of those units that are located above grade. This access may be individual stair enclosures or common stair enclosures.

All units shall have broadband internet available in the living or dining room.

The installation must result in broadband infrastructure that meets the Federal Communications Commission’s (FCC’s) requisite broadband speeds.

Units with three or more bedrooms shall have a clothes washer and dryer

hook-ups in the unit

B. Common Space Developments require community spaces for activities, office space (including

work areas) for rent up and continued leasing, maintenance spaces and storage space for flammable items. Proposed furnishings for Community Buildings shall be appropriate for the spaces to be furnished and for the intended resident.

Community space is not required for developments of less than 50 units,

however the development team must satisfactorily provide for office and maintenance operations.

Page 26: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

26 January 10, 2017

C. Dwelling Unit Design The adequacy of the design of dwelling units shall, for the greatest part, be

measured by the dwelling units "furnishability" and the inclusion of several key components. “Furnishability” shall be shown to accommodate the following:

1. Living Room: Minimum dimension of 11'-6". Sofa Two chairs Television on a table Table

2. Foyer including a 2' x 3' minimum coat closet

3. General Storage (near the exterior door) Where no basement is provided:

One-bedroom: 15 sq. ft. minimum Two-bedroom: 18 sq. ft. minimum Three-bedroom: 22 sq. ft. minimum

4. Dining area: Table to accommodate four (accommodate six in three-bedroom units)

5. Kitchen: (minimum of 48" between counters) Double bowl sink, with garbage disposal and 18" minimum counters

each side Task light over sink (Refer also to 16510.3) Dishwasher shall be required Range/oven: 30" in width with counter on one side of 18" minimum Exhaust hood with task light (Refer also to 16510.3) “Frost Free” Refrigerator/freezer with 15" minimum counter on latch side Natural light shall be provided; borrowed light using pass-throughs and

open areas over cabinets is acceptable. Cabinets at a pass-through shall allow a vertical opening of 24"

minimum. Appliance and cabinet doors and drawers shall not conflict. Counter top work surface shall be a minimum of six lineal feet with

cabinets above and below (with drawers). Space and an electrical outlet for a counter top microwave oven shall be

provided. (Refer also to 11452.3 and 16010) Provide a cabinet above the refrigerator. A pantry is desirable, especially in barrier free designed units.

6. Master bedroom: (least dimension 9’-0”) Queen bed Dresser Two nightstands Closet with minimum six lineal feet of hanging rod

7. Secondary bedroom: (least dimension 9'-0"; 90 sq. ft. minimum) Two twin beds

Page 27: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

27 January 10, 2017

Dresser Closet with minimum four lineal feet of hanging rod

8. Linen closet near bedrooms with minimum two lineal feet and five shelves

9. Bathroom In all dwelling units visitors shall have access to a water closet and lavatory

without having to circulate through a bedroom. Water Closet Bathtub and/or shower Lavatory with vanity (vanity top in barrier free designed units) Mirror Medicine cabinet or base cabinet with drawers Toilet paper holder Two Towel bars Grab bars, as required (Refer also to 10800 and 15460.)

10. Outdoor space For families units, provide a patio or balcony at 80 sq. ft. minimum; 8'-0"

least dimension. Patios shall be concrete

D. Acoustical Rating

Listed Acoustical or Sound ratings for wall and floor/ceiling assemblies shall be as

follows:

STC 50 between living units and public corridors, stairs or lobbies STC 55 between living units and noisy public spaces, e.g. elevators,

mechanical rooms, etc.

Page 28: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

28 January 10, 2017

02000 Site Work Site design shall take advantage of positive site features and characteristics and

shall address and mitigate negative site features. Site analysis and design concept shall be developed to respond to these features. None conforming sites are subject to waivers.

02001 Design 02001.11 Parking Lots Designs shall not contain dead end parking lots. 02001.12 Collector Roads Designs shall have no parking along collector roads. 02001.13 Parking Ratios Parking shall be provided in the following ratio: 2 spaces per unit or greater. 02001.16 Drive Widths

Collector drives shall be a minimum of 22'-0" in width. Drives within parking areas shall be a minimum of 20'-0".

02001.17 Parking Spaces

Parking spaces within developments shall be a minimum of 9' in width. 02001.18 Curbing

All drives, parking areas and parking islands shall be curbed. Curbing shall be concrete. Curb profiles shall accommodate snow plowing in identified areas. The Authority recommends main drives and collector roads be crowned with

drainage along curbs. 02001.19 Catch Basins

Catch basins shall not be located under carports. Drainage shall be away from carports and not towards or through carports. Catch Basins shall have concrete collars.

Page 29: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

29 January 10, 2017

02001.2 Design of Walkways

There shall be an internal system of walkways. BF ramps shall be provided at curb crossings. Walks shall be concrete. (Refer also to 03000.2.) Asphalt "walking trails" may be provided.

02001.3 Widths

Walkways along parking spaces where cars may overhang the walk shall be 6'-0" wide or as required by ADA, FHA, or local ordinance, whichever the greater.

02001.4 Patios Dwelling units at grade shall have concrete patios with a minimum area of 80 sq.ft.

(Refer also to 00150 C) 02001.5 Lawn areas Grades at lawns shall slope a minimum of 2%, swales at a minimum of 2%, and berms

at a maximum of a 1 on 3 "mowable" slopes.

02001.6 Maintenance Strips A maintenance strip, not less than 18” in width, to protect siding from mowing

operations, shall be provided along all non-masonry building facades. Stone mulch is not acceptable in family developments. This maintenance strip shall extend beyond the roofline where gutters and downspouts are not provided.

02280 Termite Control Termite control shall be provided in locales that have had previous evidence of

termites as determined by the design architect. Toxicants shall be applied by a contractor licensed by the manufacturer to soil beneath concrete slabs on grade and along inside and outside the perimeter of foundation walls.

Page 30: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

30 January 10, 2017

02780 Exterior Lighting (refer also to 16520) 02780.1 Light Poles Building mounted lighting for purposes of lighting parking lots and walks, to or from

parking, shall not be used but rather pole-mounted lights shall be used for such purposes. Pole bases shall be located 3’-0” back of curb where cars are parked along the curb. (Refer also to 16503).

02780.2 Lamps Combination photocells or timers shall control exterior lighting. Cut-off lamp

fixtures and internal reflectors or other means shall be used to minimize light trespass beyond the property or into adjacent windows.

02780.3 Lighting Levels Exterior lighting levels for parking and walkways shall be a minimum of ½ foot

candle. Lighting shall be even, and "hot" spots are to be avoided. Switched light fixtures under the control of residents may not be used in the foot-candle calculation. All designs should consider the character and location of the development.

02780.4 Carport Lighting Lighting shall be provided beneath carports at the same ½ foot candle lighting level

required for parking.

Page 31: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

31 January 10, 2017

02810 Irrigation 02810.1 Design Parameters

Total run-time shall not exceed ten hours per day based on an application rate of .2" of precipitation per day.

The irrigation plan must conform to the landscape plan, as well as other site features.

Appropriate equipment and design principles shall be practiced regarding terrain, planting materials, exposure and obstructions. Zone for sun and shade if practical.

Separately zone sprinklers with differing precipitation rates, particularly sprays and rotaries. Where it is not practical to separately zone full and part circle rotaries, use matched precipitation rate sprinklers or increase the nozzle size of the full circle sprinklers to more nearly match the precipitation rate of the part circle sprinklers.

A maximum 20 percent pressure differential in the mainline will be allowed. For example, if pressure in the mainline at the water source is 55 psi, pressure at the furthest point on the mainline shall be 44 psi or greater (55 psi less 20 percent or 11 psi).

Velocities in the mainline pipe are to be 5 feet per second or less. Velocities in the lateral pipe are to be 6 feet per second or less. Over-spray on public roads, parking areas or buildings is prohibited. Over-spray across walks is acceptable with MSHDA approval. Booster pumps shall be approved by the local municipality.

02810.2 Material Specifications

A maximum of two brands of equipment will be allowed for all irrigation equipment, including sprinklers, automatic valves, quick coupling valves and control timers.

Wire is to be minimum #14 AWG, UF UL, approved. Mainline pipe is to be PVC, minimum pressure rating of 160 psi. All pipe downstream from the valves is to be polyethylene, medium density, minimum pressure rating of 80 psi. Install quick coupling valves on three elbow swing joints. Install sprinklers on one or two elbow swing joints. Controls shall not be located within residential units. Control timers located outdoors are to be in a weather- resistant locking metal enclosure. Simple mechanical or "hybrid" type controller is preferred. A "hybrid" controller

contains solid-state circuitry with mechanical controls.

Page 32: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

32 January 10, 2017

02860 Tot or Play Lots

Tot and/or play lots shall be provided. Play equipment shall be installed per manufacturer’s recommendations for

safety and configuration. In addition to the play equipment, provide a bench and a shade tree.

02900 Plantings Select native species where practical. Plant Sizes

Shade trees shall have a minimum caliper of 2 ½”. Flowering trees shall have a minimum caliper of 1 ½". Evergreen trees shall have a minimum height of 5'-0", with an average height of all evergreen plants of 6'-0". Mulch all tree saucers with a minimum of 3” of finely processed shredded bark mulch. Mass plantings of evergreen seedlings should be considered for use in screening objectionable views. Tree stakes shall be within mulch saucers.

Locations Plants shall be planted so that at maturity they remain at least 12 inches from all buildings. When planted beneath windows, they shall not exceed the height of the window sill at maturity.

02980 Site Signs

A lighted development sign containing Fair Housing and Equal Opportunity logos shall be provided (refer also to 16520.)

A construction project sign shall be erected on site per the Preconstruction Manual.

Page 33: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

33 January 10, 2017

03000 Concrete 03001 Walk Intersections Walk intersections shall have a radius or angle configuration that protects the lawn

from "cutting the corner". MSHDA prefers a “haunch” design where the straight leg(s) of the haunch is no less than 12” and the 45 degree diagonal leg of the haunch is no less than 17” (12” x 1.414). The bottom of the haunch connects with the straight run of the intersecting walk.

03030 Concrete Finishing Materials Sealing All exposed concrete floors in common areas shall be sealed using an epoxy

stabilized chlorinated rubber or an acrylic polymer (refer also to 09001.2).

Page 34: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

34 January 10, 2017

06000 Wood and Plastics 06001 Base Trim

All rooms with floor coverings shall have base trim. 06010 Lumber

Balconies Wood framing at balconies, decks and patio fences shall be pressure treated

lumber. Deck boards and trim shall be treated lumber, cedar or composite materials are

an acceptable alternative. Fence

All wood fence materials shall be treated, cedar or composite materials are an acceptable alternative above grade.

Exterior Trim

Exterior Trim shall be treated, composite or cedar. Trim may be other wood species if back-primed and stained.

06190 Trusses

Energy heels are required. Where no gutters are provided, roof overhangs shall be no less than 24”. (Refer also to 07710)

06240 Laminates

Stools (Sills) Window Stools with plastic laminate shall be sealed with plastic laminate on all

sides. Cultured marble stools are preferred. Painted wood stools are not acceptable. Counter tops Counter tops shall not have sharp exposed corners. Corners protruding in excess of 1-1/2” shall be rounded or have a 45 degree corner.

06600 Plastic Fabrications

Casings and trim Polystyrene molded door casing and baseboard shall not be used (refer also to 08200 and 09650.)

Page 35: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

35 January 10, 2017

07000 Thermal & Moisture Protection 07195 Sheathing

Sheathing shall be a nailable wood product. All joints shall occur over wood structural members on walls.

07200 Insulation

No plumbing should occur in an exterior wall. If plumbing in the exterior wall cannot be avoided, a furred out and insulated space for the plumbing shall be provided.

07200.4 Crawl Space

Crawl Spaces shall be mechanically conditioned spaces. 07310 Shingles

Shingles shall have a minimum 25 year warranty. All old roofing is to be removed. New shingles, flashings, underlayments, and accessories to be installed

following National Roofing Contractors Association (NRCA) guidelines and manuals.

Three-tab shingles are not allowed.

07500 Membrane Roofing

Membrane roofing shall have a minimum 10 year warranty on labor and materials.

07650 Flashing

All roof systems to include industry best practices as they relate to flashings and roof penetrations. Kickout flashing shall be located where a roof and exterior wall intersect, where the wall continues past the lower roof-edge and gutter, and where gutters terminate at the side of a chimney.

07650.1 Stepped Roofs

Stepped sloped roofs shall be flashed with appropriate metal flashing and ice and water shield or equal two feet vertically where the sloped roof meets the vertical wall.

07710 Gutters

Gutters and downspouts and, where necessary, rain diverters shall be used on all developments. (Refer also to 06190).

07920 Sealants and Caulking

Caulk all exterior joints of dissimilar materials.

Page 36: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

36 January 10, 2017

08000 Doors & Windows

Bi-fold doors shall not be used.

08001.1 Sliding glass doors

In areas where the crime of breaking and entering is prevalent, pass doors in lieu of sliding doors shall be used as access to ground level patios.

Particular attention during design shall address FHA requirements for thresholds and for 32” actual clear width for egress.

Sliding glass doors shall be forced entry resistant meeting AAMA/NWWDA 101/I.S.2-97 or current equivalent standard.

08100 Metal Doors and Frames

Exterior unit entry doors shall have foam filled cores and be no less than 1-3/4" thick.

Jambs at the strike area shall be reinforced with an equivalent of a plywood plate 3/8” x 3-1/2” x 6” nailed to the back of the jamb.

Doorjambs shall be reinforced with 2" x 4" horizontal bracing at latch height. In-swinging exterior and unit entry doors shall have rabbeted jambs.

08200 Wood and Plastic Doors

Doorframes or casing shall not be polystyrene. (Refer also to 06600 and 09650) Where allowed by code, doors may be undercut a maximum of 1” to provide return air from bedrooms and bathrooms.

08390 Screens and Storm Doors

Sliding screen doorframes may not be rolled form frames.

Page 37: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

37 January 10, 2017

08500 Windows Security and operation

Windows within eight feet of grade, or otherwise accessible without the use of a ladder, shall be forced entry resistant meeting AAMA/NWWDA 101/I.S.2-97 or current equivalent standard. Windows shall have a breakaway effort of less than 30 pounds for single hung windows and 20 pounds for sliders. Windows shall have an operating effort of 18 pounds for single hung and 12 pounds for sliders.

08630 Vinyl Windows Vinyl windows shall be certified as meeting or exceeding ANSI/AAMA 101-93 (or

subsequent revisions) and shall have fully welded construction. 08710 Finish Hardware 08710.1 Peephole/viewer

All unit entry doors shall have peepholes and all barrier free units shall have a second peephole at 45 inches above the finish floor. Peepholes shall be fitted with a fisheye viewer.

08710.2 Locksets

The dead bolt shall have a 1" throw. The dead latch shall have a 1/2" throw. Unit entry hardware shall not have parts made of plastic. Bathrooms and master bedrooms shall have door locks. Interior doors may not be locked against egress or panic release operation. Exterior doors from common spaces, stairs, maintenance areas etc. shall have adjustable self-closing devices, self-locking dead latches and trigger bolt protection.

08710.4 Hinge Pins

Out-swinging exterior doors shall have non-removable hinge pins or shall have security type hinges that prevent unauthorized door removal.

08710.5 Alarms

Exterior doors in buildings designed for multiple dwelling units for residents in areas where security from trespass is anticipated as a substantial problem shall have door ajar alarms wired to a central control panel. Such security areas shall include large metropolitan areas as determined by MSHDA’s Marketing staff. (Refer also to 16010.1.)

08742 Electric Locksets

Main entrance doors to buildings designed for access to multiple dwelling units for residents shall have electric door release. (Refer also to 16010.1.)

Page 38: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

38 January 10, 2017

08780 Cabinet and Drawer Hardware

In dwelling units designed for barrier free units, cabinets and drawers shall have easily graspable pulls

08810 Glass

Doors at laundry rooms shall have integral glazing or glazing immediately adjacent to provide visibility.

Page 39: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

39 January 10, 2017

09000 Finishes 09001 Design 09001.1 Floor covering

Floor covering must be provided over all substrates of plywood, "gypcrete" or lightweight concrete.

09001.2 Concrete floors

All exposed concrete floors in common areas shall be sealed using an epoxy stabilized chlorinated rubber or an acrylic polymer. (Refer also to 03030.)

09250 Gypsum Board

Dwelling units shall have drywall ceilings. Painted concrete ceilings are acceptable where the concrete is part of the structural system. (Refer also to 09900.1.) Ceilings and walls in kitchens and baths shall have a smooth washable surface.

09650 Vinyl Flooring

Resilient flooring or vinyl tile shall be used in kitchens, baths and laundry areas (except in basements). (Refer also to 09681.) Vinyl plank, vinyl tile, and resilient tile shall not be used over wood substrate. The minimum wear layer in units is .012” and .020” in public spaces. Wall Base Wall base trim shall be used in all habitable spaces. Base trim shall not be polystyrene. (Refer also to 06600 and 08200.)

Page 40: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

40 January 10, 2017

09681 Carpet

Carpeting shall be the usual floor finish material in all rooms except kitchens, bathrooms and laundries. (Refer also to 09650.) All carpeting shall meet the requirements of HUD Use of Materials Bulletin UM44D. Carpet shall be used in accordance with the type and class required per the Bulletin. Per UM44D, all carpeting shall be stamped and labeled as meeting the requirements of the Bulletin. An exception to the requirement of stamping and labeling may be granted for common area carpeting i.e. carpeting in lobbies, lounges, community rooms, libraries etc., (not corridors at residential entries). Carpeting in these areas may be certified by the manufacturer as having met or exceeded the performance standards of UM44D and need not be stamped and labeled, if such carpeting exceeds the pile weight and density required by UM44d by 25% or greater. This exception is intended to allow the use of higher quality "feature" carpeting in limited quantities, without adding the cost of laboratory authorized stamping and labeling. Such exceptions must receive written approval from MSHDA prior to the contractor or sponsor or owner ordering the carpet. MSHDA prefers all carpeting within dwelling units to be nylon, however polypropylene or a blend of nylon and polypropylene is acceptable. The minimum critical radiant flux limits for carpeting in corridors and is 0.45 watts/cm2. This limit shall be reduced to 0.22 watts/cm2 where the building has fire sprinkler protection. The limit for carpeting in corridors and exitways shall be 0.22 watts/cm2. Carpeting shall meet applicable requirements of UM44D.

09682 Carpet Pad

All carpet pad must meet the requirements of UM72. Carpet pad is required under carpeting except in barrier free units.

Page 41: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

41 January 10, 2017

09900 Painting 09900.1 Interior

All paint over interior drywall shall meet or exceed the limit of 400 strokes on the "scrubability" testing standards established in the most recent version of ASTM #D-2486 and be low VOC.

Kitchens and baths shall be painted with a washable semi-gloss paint. Satin sheen or egg shell finish paint may be used if a satin or egg shell finish is used throughout the residential unit.

Dwelling units shall have painted drywall ceilings. Painted concrete ceilings are acceptable where the concrete is part of the structural system. (Refer also to 09250.)

9900.3 Exterior

Exterior wood shall have at least 2 coats of stain. Vents penetrating roofs, with the exception of stainless steel vents, shall be

painted with appropriate paint to match the roof shingles. Exterior composite materials shall be installed, painted and caulked following

manufacturer recommendations.

Page 42: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

42 January 10, 2017

10000 Specialties 10550 Mailboxes

Verify postal requirements with local USPS post master. Comply with accessibility codes.

10800 Grab Bars

Tub and/or shower enclosures with integral grab bars substantially complying with the aforementioned grab bar requirements may be used with approval, prior to initial closing, by the MSHDA Chief Architect.

10825 Residential Bath Accessories

Medicine Cabinets Recessed medicine cabinets are preferred and may be substituted with a drawer

base cabinets, subject to approval. They shall not be located on an exterior or rated walls.

Page 43: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

43 January 10, 2017

11000 Equipment 11250 Water Softeners

Any domestic water supply with hardness in excess of 200 milligrams/liter of Calcium Carbonate shall be treated by water softening the domestic hot water. This determination will be made by MSHDA’s Chief Architect and will be based upon water quality data provided by the Drinking Water and Radiological Protection Division of the Michigan Department of Environmental Quality. Domestic hot water only shall be treated. Where it is economically infeasible to treat only the hot water the domestic cold water may also be treated.

11452 Residential Appliances

All dwelling unit appliances including range/oven, refrigerator, dishwasher, washers and dryers, shall be by a single group manufacturer. Refrigerators shall be placed so that the door will be able to swing 180 degrees to allow removal of all drawers and accessibility.

11452.1 Refrigerators

All refrigerators shall be frost-free (no-frost) refrigerator/freezers with two separate compartment doors.

11452.2 Range/Ovens

All ranges and ovens shall be four (4) burner electric appliances with a minimum width of 30 inches. Gas range/ovens may be used where they have automatic ignition and automatic pilot shutoff.

Ranges in units designed as barrier free shall have front controls with indicator lights.

Range/ovens in units designed as barrier free, shall be self-cleaning. Ranges shall have grease shields.

11452.3 Microwave ovens

An electrical outlet shall be conveniently placed for a counter top microwave oven.

11452.4 Exhaust Hoods

A task light is required. (Refer also to 15010.3 and 16510.) Firestops are required at all range hoods.

11452.5 Garbage Disposal Units

Garbage disposal units shall be provided. (Refer also to 15010.3.) 11452.7 Washers and Dryers

If washers and dryers are provided within dwelling units, side-by-side washers and dryers are preferred. Stacked washers and dryers may be used if they are full size units.

Page 44: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

44 January 10, 2017

11455 Kitchen and Bath Cabinets

All cabinets shall comply with the design and construction of the Kitchen Cabinet Manufacturers Association and shall be certified as such. All cabinets shall have hardwood stiles and rails. All cabinets except sink bases shall have backs. All bathrooms shall have vanities. In bathrooms designed to be barrier free, in order to provide "roll under access" a reduced vanity size may be used or a lavatory set in a counter top may be used. Wall hung lavatories may not be used. (Refer also to 15460.) In the primary bath, if the vanity is longer than 39", drawers shall be provided on one side of the vanity.

Page 45: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

45 January 10, 2017

12000 Furnishings 12505 Blinds

Blinds shall be provided at all windows and door wall openings. Blinds must be integral in swing doors.

12664 Tables and Accessories

Laundry Rooms In common laundry rooms, a table and a hanging rack meeting ADA requirements shall be provided.

14000 Conveying Systems 14200 Elevators

Hooks and removable pads shall be provided in elevators that will be used for move-ins.

Page 46: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

46 January 10, 2017

15000 Mechanical 15010 Design

Energy load data for heating, cooling and electrical energy loads comprised of summary loads of each type of dwelling shall be included as part of the Commitment Submission. (Refer also to 00114)

15010.2 Heating and Cooling

All dwelling units shall have individual mechanically ventilated HVAC units. Through wall or window mounted air conditioning is not acceptable in new construction. Where unit entries are located at grade for units that have living areas above grade i.e. individual entry stacked units, a supply air duct run shall be provided at the grade level entry foyer. At a minimum, this duct shall be provided in the ceiling of this foyer. Electrical heat maybe used when ductwork is not feasible. Electrical heating shall not be used except as specifically approved by MSHDA. Allowable in the foyer of multi-unit building. (Refer also to 16850.) All common corridors in developments shall be air-conditioned and provide positive air pressure. Corridor make-up air shall maintain corridor temperature at 76 degrees F in the summer and 70 degrees F in the winter. (Refer also to 15600.1) Common laundries, craft rooms and trash and trash compactor rooms shall all be designed to have negative pressure.

15010.3 Appliances

Garbage disposal units shall be provided in all dwelling unit kitchens and common space kitchens. (Refer also to 11452.5) Exhaust hoods over ranges/ovens shall include a task light. (Refer also to 11452.4 and 16510.)

15050 Basic Materials and Methods 15050.2 Valves

Hot and cold water shut off valves for each living unit shall be provided. Valves shall be installed at all service connections and in all branch lines and risers.

15050.7 Wall, Floor and Ceiling Plates

In finished spaces and within sink and vanity bases, furnish a chromium plated sectional escutcheon on each pipe or hanger rod penetrating the wall, floor or ceiling. Plates shall fit snugly.

Page 47: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

47 January 10, 2017

15050.8 Plastic Drain Pipe

Cellular foam core PVC shall not be used for wet pipes. 15180 Pipe Insulation

Insulation shall be continuous over pipes, valves and fittings, etc.

No plumbing should occur in an exterior wall. If plumbing in the exterior wall cannot be avoided, a furred out and insulated space for the plumbing shall be provided.

15250 Water Softeners and Water Conditioning

Any domestic water supply with hardness in excess of 200 milligrams/liter of Calcium Carbonate shall be treated by water softening domestic hot water. This determination will be made by MSHDA Design and Technical Resource staff and will be based upon water quality data provided by the Drinking Water and Radiological Protection Division of the Michigan Department of Environmental Quality. Domestic hot water only shall be treated. Where it is economically infeasible to treat only the hot water the domestic cold water may be treated.

Page 48: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

48 January 10, 2017

15460 Plumbing Fixtures and Trim

Kitchen sinks shall be double bowl and shall be stainless steel. (Refer also to 00150 C.) Sinks shall have a single lever control. A garbage disposal shall be provided. Lavatories shall not be fiberglass material. Wall hung lavatories shall not be used in any units. (Refer also to 11452 and 11455.) In common areas where wall hung lavatories are used; use wall chairs to support the lavatories. All bathtub bottoms shall have a non-slip finish. All bathroom water controls shall be single lever controls. All exposed fittings, trimmings, faucets, traps and exposed connections shall be chromium plate brass. Faucets shall be heavy brass, compression type with renewable seats and discs or cartridge style. Provide a stop or shut-off valve in the water connection(s) to each water heater, water closet, group of fixtures and main riser. Common laundry areas shall have a floor drain. Roll in showers shall have a floor drain outside of the shower.

15470 Water Heaters 15470.1 Residential Water Heaters

All dwelling units shall have individual water heaters. Water heaters shall be gas-fired. Where permitted shutoff valves for inlet and outlet lines shall be provided for ease of replacement.

15470.2 Commercial Water Heaters

Water heaters shall be gas-fired. All common water heaters shall be of the continuous recirculation design. All copper fin-tube domestic water heaters with storage tanks shall have solid state electronic controls to circulate water through the boiler based upon a drop in water temperature in the storage tank.

Page 49: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

49 January 10, 2017

15500 Fire Protection Systems

If building(s) are equipped with a fire protection system, then unit smoke detectors shall activate if the fire protection system flow alarm activates.

All fire sprinkler heads within residential space shall be white in color and recessed into ceilings and walls.

Firestops are required at all range hoods. Wet system piping shall not be in the attic or unconditioned spaces. Backflow preventers are required for wet pipe systems. Nitrogen gas is preferred over compressed air in dry pipe fire protection systems.

15600 Heat Generation 15600.1 Boilers and Chillers

Gas fired boilers and chillers shall be used where heating systems are not provided for each dwelling unit. Boiler systems shall have two or more boilers and shall be furnished with a control panel designed to reset the supply water temperature based on the outdoor temperature. The Control panel shall step fire the boilers in sequential order. A heat exchanger is to be provided so that each unit may have cool air. Systems shall be designed to evenly and adequately distribute conditioned air throughout the living unit. (Refer also to 15010.2) All heating systems shall be designed so that each living unit has at least one thermostat to control space temperature.

15900 Mechanical Controls 15900.1 Thermostats

In all heating/cooling systems, unit thermostats shall be placed on an interior wall, at 48" above the finish floor, away from the direct flow of forced air and drafts. Thermostats in common areas shall have automatic setback controls.

Page 50: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

50 January 10, 2017

16000 Electrical 16010 Design

Electrical service shall be designed so that all dwelling units can be metered separately. Large multipurpose rooms shall be wired so that one half the fixtures may be shutoff and a uniformly reduced lighting level is achieved with the balance of the lighting wired in a similar manner. An electrical outlet shall be conveniently placed for a counter top microwave oven, unless a built-in microwave is being provided. (Refer also to 11452.3.)

16010.1 Doors

Main entrance doors to buildings designed for access to multiple dwelling units for residents shall have electric door release. (Refer also to 16010.1.)

16140 Wiring Devices

Switches A dwelling unit's bath exhaust fan shall be switched separately from the lights. Bathroom lights shall be the first switch adjacent to the door latch; the second switch shall be for the bathroom exhaust fan. (Refer also to 11452.6)

16200 Emergency Generator

An emergency generator shall be provided buildings with elevators. Additionally any building that is required to have a fire pump for the fire protection system, unless a diesel fire pump is provided, shall have an emergency generator. Emergency Generators shall provide automatically transferred power for the full operation of all loads essential for the safety of human life as defined in N.E.C. and Life Safety Code 101. In addition, the system shall include but not be limited to: lighting in areas of refuge, emergency elevator (with cab size capable of handling a stretcher horizontally), and emergency call systems. Where capacity exists in a generator sized for the above equipment, recirculation pumps on boilers and make up air supply shall be powered off that generator. The emergency generator shall be provided with a fuel supply that will operate such a generator for a minimum of 24 hours. No underground storage tanks shall be used.

Page 51: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

51 January 10, 2017

16500 Lighting 16500.1 Lighting Levels

Average illumination levels at the task surface shall be: 50 fc offices 15 fc corridors, lobby, stairs 30 fc kitchen counter top, sink and range surfaces 15 fc toilet rooms and bathrooms at vanity top 10 fc bathrooms at bathtub 10 fc store rooms, mechanical rooms, electrical rooms, etc.

Egress emergency lighting shall be maintained at a 1 foot-candle level inside the building and to a point 20 feet outside the building exits.

16500.2 Night lights

A night light, or outlet for a night light, shall be provided near the bedroom/bathroom area in all units.

16503 Poles, Posts, and Standards

Building mounted lighting for purposes of lighting parking lots and walks to or from parking shall not be used. Pole mounted lights of an appropriate height shall be used for such purposes. Aluminum poles are preferred. Lighting shall be provided beneath carports at the same ½-foot candle lighting level required for parking. (Refer also to 02780)

16510 Interior Luminaires 16510.1 Corridor Lighting

Wiring systems shall be designed to allow shutdown of half the corridor lighting at night. This does not apply to garden apartment buildings with common corridors. Corridor lighting shall be a minimum of 15 foot-candles.

16510.2 Bedroom Lighting Each bedrooms shall have a ceiling mounted light fixture. 16510.3 Kitchen Lighting

Each kitchen shall have a task light above the sink and a ceiling mounted general kitchen light. Additionally the range hood shall have a task light. (Refer also to 00150 C.)

Page 52: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

52 January 10, 2017

16510.4 Fixture Types

Bare bulb porcelain fixtures shall not be used except in basements and mechanical closets. Exit lights shall be LED type fixtures.

16520 Exterior Luminaires

Exterior lighting shall be controlled by photocells. Luminaires shall be designed to reduce light spillage into unwanted areas. Mercury vapor lighting is not acceptable. Site development signs shall be illuminated (refer also to 02780 and 02980.)

16520.1 Balcony and Patio Lighting

Balconies and patios shall have a switched light. 16522 Roadway and Parking Luminaires

Exterior lighting levels for parking and walk areas shall be a minimum of 1/2 foot-candle. Provide a maximum to minimum foot-candle ratio of 10 within the limits of the parking area and walks to buildings.

Page 53: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

53 January 10, 2017

16720 Alarm and Detection Systems 16720.1 Smoke Detectors

All dwelling unit smoke detectors shall have a photoelectric type close to the kitchen, ionized detectors may be used elsewhere.

If building(s) are equipped with a fire protection system, then unit smoke detectors shall activate if the fire protection system flow alarm activates.

The operation of this system shall be discussed during the design stage with the local fire department to determine how the system shall operate. The operation of the system shall comply with the fire department regulations, however the capabilities of the system, as required herein, shall not be diminished.

16722 Building Security and Detection Systems

Intrusion alarms shall be installed within residential units, which are at grade or otherwise accessible to intrusion, in areas where criminal trespass is a substantial problem as determined by MSHDA marketing staff.

16760 Intercommunications

All buildings that are designed to include a multiple number of dwelling units accessible through a common entry shall have a two-way intercom between the main entry and the individual units. Intercom communications shall not result in costs to the resident. In areas where added security is necessary, as determined by MSHDA and the development’s management company, door releases at common entries shall be at the door and not remotely operated.

16770 Broadband Infrastructure

A broadband infrastructure that meets the Federal Communications Commission’s (FCC’s) requisite broadband speeds must be installed. Broadband speeds must be 25 megabits per second (mbps) download and 3 mbps upload to meet the FCC’s broadband requirements.

16780 Television Systems

A central TV antenna system shall be provided unless three major networks and public television can be received at the site without cost to the resident or basic cable is to be provided at no cost to the residents.

All units shall be wired for cable television. Television antenna and cable outlets shall be provided on at least two walls of

the living room and one location in the master bedroom. All antenna and cable wiring shall be concealed within walls.

16850 Electric Heating

Electrical heating shall not be used except as specifically approved by MSHDA (refer also to 15010.2.)

Page 54: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

54 January 10, 2017

MSHDA Senior Housing Standards 00010 General Design Parameters for Senior Housing 55 02000 Site Work 58

02001 Design

08000 Doors & Windows 59 08001 Doors 08200 Wood and Plastic Doors 08710 Finish Hardware

08780 Cabinet and Drawer Hardware

10000 Specialties 60 10001 Package Shelves 10002 Handrails 10800 Grab Bars

11000 Equipment 61

11452 Residential Appliances 11455 Kitchen and Bath Cabinets

15000 Mechanical 61

15900 Mechanical Controls 16000 Electrical 62

i

Page 55: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

55 January 10, 2017

00010 General Design Parameters for Senior Housing

1. Elevators Buildings having two or more stories shall be equipped with at least one elevator

and of sufficient size (approximately 5' x 7') so as to facilitate move-ins/outs and emergencies (refer also to 14001.).

Buildings with 100 or more dwelling units or of three or more stories shall be

equipped with at least two elevators. One such elevator shall be located and of sufficient size (approximately 5' x 7') so as to facilitate move-ins/outs and emergencies (refer also to 14001.)

2. Accessible Units Accessible units shall not be arranged all in one wing of a building. Such units shall

be located on the floor at grade for ease of exiting in an emergency, but shall be located throughout that floor.

3. Congregate Housing At a minimum, congregate housing shall include facilities and services for common

dining, housekeeping and personal health services. 4. Common Spaces Management, mail pick-up and primary vertical circulation functions shall be

grouped at the primary entrance and lounge. All common facilities shall be accessible without passing directly through the

lounge. If provided, medical and social services, central dining facilities and similar common facilities (including trash removal) shall be grouped in close proximity to the main circulation elements but in such a way that it is not necessary for a resident to pass through the lobby or the lounge to reach them.

The design shall provide easy “way finding” cues to distinguish location within a

building. These cues can include: clear organization in the design of space and circulation, plants, lighting, features, color (carpet, walls, features), furnishings, and consistent signs.

Provide glass panels adjacent to or in doors to common area rooms, allowing

residents to see into a room before attempting to open the door. Proposed furnishings for Common spaces shall be appropriate for the spaces to be

furnished and for the intended resident. (Refer also to 02870 and 12600.)

Page 56: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

56 January 10, 2017

5. Circulation Common corridors shall be a minimum of five (5) feet wide. For reasons of

eliminating visual and physical corridor length, the maximum length of a corridor shall be 150’. For the purpose of this measurement, a corridor shall be defined as ending at any intersection with another corridor resulting in a visual terminus or where common space provides a significant visual break or offset. The maximum length of travel from a unit to an elevator shall be 150’. The maximum length of travel from the farthest unit to common dining and/or office facilities shall be minimized through building arrangement. No ramps shall be used in corridors.

6. Community rooms All community rooms shall be provided with a kitchen that shall minimally have a

double bowl sink, garbage disposal, a range/oven, a refrigerator, and a barrier free workspace.

7. Crafts rooms All crafts rooms shall be provided with a sink with gooseneck faucet and plaster

trap. All craft rooms shall have negative air pressure. 8. Maintenance Space Common maintenance space shall be provided for storage and as a work area.

Maintenance buildings or in large buildings, maintenance spaces shall be provided at all developments. Buildings or spaces shall be heated and insulated, a toilet for staff shall be provided. The maintenance space shall be approximately 400 square feet. Provision shall be made for the storage of flammable materials. Workbenches and storage shelves shall be provided within the maintenance space.

9. Common Laundry Common laundry rooms shall be provided with a table for folding laundry and a

rod for hanging clothes. If feasible, common laundry rooms shall have a window to the exterior. Common laundry rooms shall have a floor drain. Common laundry rooms shall have a seating area within, immediately adjacent

to, or in line of sight of the laundry room. All laundry rooms shall have negative air pressure.

10. Trash Compactor and Trash Chute The trash compactor room shall be designed so that the trash gondola can be

easily wheeled in and out of the space without sharp turns. A hose bib shall be provided within the trash compactor area for ease in washing

down the area. A wash down sprayer shall be provided for within the trash chute. The residents shall not have to carry trash through the main lobby in order to dispose of their trash. A remote trash room shall be provided as needed.

All trash rooms shall have negative air pressure.

Page 57: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

57 January 10, 2017

11. Package Shelves Where dwelling unit entries are accessed from common corridors, entry package shelves shall be placed immediately outside each dwelling unit entry with a minimum dimension of twelve (12) inches. (Refer also to 06240 and 10001)

12. General Storage In buildings with multiple units for senior residents, storage may be located in cubicles located in common area storage rooms.

Page 58: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

58 January 10, 2017

02000 Site Work 2001.13 Parking Ratios

Parking for developments for senior residents shall be provided in the following ratio: 1.0 space per unit or greater.

Parking for developments providing congregate services and marketed as “congregate” developments may be provided at 0.8 space per unit or greater.

02001.17 Parking Spaces

Parking spaces shall be a minimum of 10' in width X 20' in length. 02001.3 Patios

Dwelling units at grade shall have patios with a minimum area of 45 sq. ft. Patios shall be concrete. (Refer also to 00150 C)

02001.6 Maintenance Strips

A maintenance strip, not less than 18” in width, to protect siding from mowing operations, shall be provided along all non-masonry building facades.

02870 Seating

In housing for senior residents, exterior seating and common area seating shall have backs and arms.

Page 59: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

59 January 10, 2017

08000 Doors & Windows

08001 Sliding Glass Doors

Pass doors, in lieu of sliding glass doors, to patios and balconies are required in housing for senior residents.

Particular attention during design shall address FHA requirements for thresholds and for 32” actual clear width for egress.

08001 Bathroom Doors

Bathroom doors in dwelling units shall swing outward. (Refer also to 00150 C) 08710 Locksets

All unit entries shall have door locks with simultaneous retraction of the dead bolt and dead latch from the inside and a single key operation from the exterior.

The dead bolt shall have a 1" throw. The dead latch shall have a 1/2" throw.

08710.3 Lever handles

Door handles shall be the lever type.

08780 Cabinet and Drawer Hardware

Cabinets and drawers shall have easily graspable pulls. (Refer also to 11455.)

Page 60: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

60 January 10, 2017

10000 Specialties 10001 Package Shelves

Package shelves at unit entries shall be provided Package shelves shall provide a minimum area of one square foot. Ninety-degree corners shall have a radius. A package shelf shall be provided at the elevator(s) on the first floor.

10002 Handrails

Handrails shall be provided on both sides of all corridors for residents. 10800 Grab Bars

Grab bar on an adjacent wall to the water closet One vertical grab bar 18 inches minimum in length shall be mounted with the

bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall.

Grab bars shall be provided at all bathtubs. One 24" long, 1" minimum in diameter, grab bar shall be placed at 45 degrees,

centered on the side opposite the accessible side, and with the lowest point of the bar 12” above the tub rim. The highest end of the diagonal bar shall be at the control end of the bathtub.

One 24" long, 1" minimum in diameter, grab bar shall be placed vertically at the control end of the bathtub at the outside edge with the top of the bar 4'-6" above the floor.

Grab bars shall be provided at all showers. One 24" long, 1" minimum in diameter, grab bar shall be placed at 45 degrees,

centered on the side opposite the accessible side, and with the lowest point of the bar 29” above the shower floor. The highest end of the diagonal bar shall be at the control end of the shower.

An identical bar shall be placed vertically at the control end of the shower at the outside edge with the top of the bar 4'-6" above the floor.

Tub and/or shower enclosures with integral grab bars substantially complying with the aforementioned grab bar requirements may be used with approval, prior to initial closing, by the MSHDA Chief Architect. It is preferred to have water closets located adjacent to a wall 48” in length (perpendicular to the plumbing wall) to facilitate the future addition of a grab bar. (Refer also to 15460.)

Page 61: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

61 January 10, 2017

11000 Equipment 11452.2 Range/Ovens

Ranges shall have front controls with indicator lights. 11455 Kitchen and Bath Cabinets

Kitchen and bath cabinets shall have easily grasped door and drawer pulls.

(Refer also to 08780.) Cabinets in units designed for senior residents may have frames of composite

wood materials provided the design, materials and installation insures the screw holding capacity of the frame is equal to or exceeds that of oak. All cabinets except sink bases shall have backs.

15000 Mechanical 15900.1 Thermostats

Thermostat shall have large easy to read settings.

16200 Emergency Generator

An emergency generator shall be provided in all senior buildings exceeding two

stories. Emergency Generators shall provide automatically transferred power for the full

operation of all loads essential for the safety of human life as defined in N.E.C. and Life Safety Code 101. In addition, the system shall include but not be limited to:

lighting in areas of refuge, emergency elevator (with cab size capable of handling a stretcher horizontally), and emergency call systems.

Where capacity exists in a generator sized for the above equipment, recirculation pumps on boilers and make up air supply shall be powered off that generator.

The emergency generator shall be provided with a fuel supply that will operate such a generator for a minimum of 24 hours. No underground storage tanks shall be used.

Page 62: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

62 January 10, 2017

16000 Electrical 16720.2 Emergency Call

An emergency call system shall be installed in all buildings designed for senior residents. The emergency call system shall be a “fully addressable” system which shall include: pull cord stations in the bathroom and bedrooms with "furnishability" dictating

station placement (note especially conflicts with towel bars); optionally a light, and only a light (not to include a bell or alarm) over the unit

entry; an annunciator panel located in the manager's office or reception area on which

a light displays and a sound is emitted to indicate the dwelling unit in which the emergency call was pulled; and

optionally a remote annunciator panel located in the manager's unit. To be “fully addressable” the display at the office annunciator panel(s) shall differentiate between the smoke detector alarm signal and the emergency call signal and shall be able to identify from which dwelling unit the call originated. The system must require a manual reset at the annunciator panel. The system shall have the capability to send the same identifying information to a remote location off-site to a monitoring agent, a pager, etc. The operation of this system shall be discussed during the design stage with the local emergency medical service provider to determine how the system shall operate. The operation of the system may comply with the service provider regulations; however the capabilities of the system shall not be diminished.

Page 63: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

63 January 10, 2017

Rehab Standards of Design

The Michigan State Housing Development Authority (MSHDA) Rehab Standards of Design defines the design process and the specific requirements for occupied multifamily housing financed through the Authority. General Policy Statement for Rehab Developments MSHDA will undertake rehab projects when they provide the best development alternative, meet MSHDA targeted objectives, and provide a reasonable risk with a reasonable prediction that the property will be successful. Successful outcomes are measured in terms of providing a continuing marketable development, a stable resident population, a well maintained structure, and repayment of the loan throughout the term of the loan. Occupied Housing Developments 64 00052 Investigation of Structures to be Rehabbed 65 00100 Rehab Design Review Process 65 00120 Replacement Criteria 66

Page 64: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

64 January 10, 2017

Occupied Housing Developments A. An analysis by MSHDA staff shall be made to determine if the proposal will meet the

overall objectives set forth in the General Policy Statement on the previous page. B. Location and site selection shall be important underwriting considerations of acceptance

for processing. 1) Locations shall provide appropriate parking that meets MSHDA standards. 2) Locations shall provide reasonable security. 3) Locations shall provide appropriate outdoor spaces for the development’s

residents. 4) Locations shall provide nearby amenities for the targeted resident population and

meet MSHDA’s Site Selection Criteria. C. The design of the existing building shall be an important consideration of the acceptance

for processing. 1) All units shall have central air conditioning. 2) Private balconies or patios shall be provided for each unit. 3) Rehab proposals shall provide units and common spaces that are marketable,

provide living conditions comparable to new construction, and provide a development that is cost effective to operate and maintain.

4) Living units shall have acceptable views. 5) Living units located below slab on grade conditions are not desirable. 6) Elevators in family developments are not desirable. However, elevators are

required in senior developments with more than one story. 7) Walk-up buildings with three or more stories are not acceptable. 8) In family developments, common corridors shall serve no more than five units. 9) Exterior elevations that consist primarily of concrete block that are painted or

coated with epoxy coatings are not acceptable. 10) Flat roofs on low-rise structures are not desirable. 11) Living units shall be furnishable as defined in the Standards of Design. 12) Parking shall be secure, well lit, and adjacent to the building.

D. If commercial space is to be located within the structure, an analysis of the marketability and financial impact of the proposed commercial space shall be prepared by the development team. Uses inappropriate for, or incompatible with, the target population shall not be allowed.

E. Where the development proposal involves the rehab of an existing occupied development, a Rehab Capital Needs Assessment (CNA) shall be required. The CNA shall include the owners proposed Scope of Work.

F. The proposed design and costing shall address all CNA identified needs through the proposed construction or replacement reserves.

G. Where the development proposal includes the reuse of internal building components, the reuse shall be done in accordance with MSHDA’s Replacement Criteria (00120).

H. All replacement materials shall be equal to materials and methods of construction as required in the MSHDA Standards of Design for new construction. Green building materials and practices shall also be considered when they can assist in the development meeting the General Policy Statement.

I. Financing shall provide a construction contingency equal to no less than 5% of the construction contract. Site, scope, environmental concerns and other factors may justify a higher contingency as determined by appropriate MSHDA staff.

Page 65: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

65 January 10, 2017

00052 Investigation of Structures to be Rehabbed The Sponsor/Owner shall obtain and submit a report from a licensed structural engineer regarding structural capacities and conditions of the building(s). The Sponsor/Owner shall also obtain and submit a report from a licensed architect or a licensed engineer in association with a contractor licensed to do repair work on the mechanical and electrical system(s) to be preserved. Any and all basement areas must be inspected. Any settling, cracks, water infiltration, heaving, and rotted wood must be noted and repaired as part of the rehab. Past repairs must also be noted. 00100 Rehab Design Review Process A. Site Visit At the site visit the Owner will have a preliminary CNA that incorporates the proposed Scope of Work. This visit is for MSHDA staff and its representative to determine the overall condition of the property. We look at the general neighborhood, grounds, structures, common areas, mechanical and electrical rooms, and typical apartments. B. Final Scope of Work is determined and final CNA is ordered. The Development team and MSHDA staff meet to discuss the preliminary CNA line by line in order to determine the final scope of work and replacement reserves. The participants at the meeting shall be members of the Development Team including the architect, contractor, and management agent and Authority staff from Development, Design, Market Analysis, Asset Management, the Authority Site and Architecture Design Review Consultants and other areas as needed. The purpose of this step is to definitively set forth and agree upon a Scope of Work consistent with the CNA, the Authority's Rehab Standards, and the construction budget available to the development and appropriate to the needs of the anticipated future residents. The Development Team shall identify desired variances from the MSHDA Standards of Design. In requesting a variance, the Development Team shall provide for MSHDA's consideration, the reasons for requesting a waiver and the proposed alternative to meeting the Standards of Design objectives. Meeting notes are prepared by the Housing Development Officer. Following acceptance of the notes, a Final CNA is ordered and the Design Team can start work on the construction documents. C. Construction Documents / Commitment The Review of Construction Documents is the next stage of the Design Review Process. A complete submission is made directly to MSHDA and MSHDA's Site, Architecture, and Engineering Review Consultants. After ten working days for the Consultants to complete their review, a Commitment Design Review Meeting is held. The MSHDA Design Review Consultants will prepare and distribute written reviews prior to the meeting. The Developer's Design Team shall prepare a written response. The purpose of this step is to complete construction documents consistent with the Scope of Work, the Authority's Rehab Standards, the construction budget available to the development and appropriate to the needs of the anticipated future residents. Other meetings may occur at the request of the developer, architect, or MSDHA.

Page 66: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

66 January 10, 2017

D. Contingency Wish-List The Development team submits a contingency wish-list to MSDHA for approval prior to the start of construction.

Page 67: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

67 January 10, 2017

00120 Replacement Criteria The following criteria are to be used in MSHDA financed rehab where interior building components are to be reused. The evaluation of building components, using these criteria, shall be done by the assigned MSHDA staff person in cooperation with the supervising architect, owner, and contractor. Components not covered in this listing shall be evaluated using the listed criteria for similar components. Replacement components shall meet the Standards for new construction. A. General

1) Painting: Repaint all painted surfaces and paint all repaired surfaces to match existing and/ or adjacent. Lead based paint shall be abated in conformance with applicable law.

2) Drywall: Must be clean, smooth, and match existing drywall as new.

3) Floor Covering: Unless existing is as new, all sheet vinyl is to be replaced. Reuse

carpet only if it has no stains, no worn areas and each room within a unit matches. Ceramic tile bathroom floors must have no chips or cracks and be clean. If a ceramic floor is not acceptable, it may be replaced or it may be overlaid with new sheet vinyl after reparation of existing flooring so as to be a smooth, clean surface not subject to telegraphing the joints.

4) Closet Shelving: Wood shelving must be smooth, tight fitting, with no delaminating, and

be properly anchored. Wire shelving is acceptable.

5) Blinds: Unless existing is as new, new blinds shall be provided. Existing blinds shall comply with MSHDA Standards of Design.

6) Appliances, Motors and Other Equipment: Life cycle costing should be considered. The

projected life of existing appliances, motors and other existing equipment should be equal to or exceed five (5) years. If the projected life is less than five years, replacement is required.

B. Kitchens

1) Kitchen Appliances: Reuse only if they function properly, have good overall appearance, and only minor scratches.

2) Kitchen Counter Tops: No bad chips, burns, stains, cracks, or deformities; must match

within same kitchen and be adequately anchored. Counters shall be plastic laminate or better. Painted or epoxy coatings are not acceptable.

3) Kitchen Cabinets: Must function properly and provide equal or greater capacity as

original; new and existing in same kitchen must match; hardware must match; no deep gouges or broken pieces or parts. In developments for seniors, cabinets must have easily graspable hardware pulls.

4) Kitchen Sinks: No cracks or chips (unless chip can be satisfactorily re-glazed); must

function properly and be adequately anchored; small light stains are acceptable. Disposal must function properly and not leak.

Page 68: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

68 January 10, 2017

C. Bathrooms 1) Bath Vanity, Vanity Top, Lavatory (sink) and Medicine Cabinet: Remove any wall-hung

sink and replace with new vanity and lavatory (sink). Existing vanities, sinks, tops, legs, and medicine cabinets must meet criteria for kitchen tops, cabinets and sinks above.

2) Bathtub, Showers, Water Closets, Wall Surround (Ceramic Wall Tile or Fiberglass):

Bathtubs and shower bases shall have no cracks or chips (unless chip can be satisfactorily re-glazed); must function properly and be adequately anchored; small light stains are acceptable. Fixtures must function properly. Ceramic wall tile and fiberglass surrounds must have no chips or cracks and be clean with no bad stains or deformities and tiles must match within same bathroom and be adequately anchored.

D. Doors and Door Hardware

1) Unit Interior Doors: Repairs will be allowed on minor cracks and punctures only; otherwise, new doors will be installed. Repaired doors must function properly, be smooth and tight fitting with no delaminating. All door finishes within unit must match. Repaint all painted doors. Previously unpainted (stained) doors may be painted to match doors within units. New bathroom doors shall swing out in senior apartments.

2) Unit Entry Door: All entry doors are to be new with new door hardware that is non-

locking against egress.

3) Door Hardware: All unit entry door hardware is to be new and shall meet MSHDA criteria for entry door hardware. Interior hardware must function properly and have clean appearance.

Senior residents require interconnecting hardware on unit entry door.

E. Windows 1) Interior Trim: All window finishes within a unit must match. Repaint all painted window

trim. Previously unpainted (stained) trim may be painted to match all window trim within units. At all window units, seal perimeter.

2) Window Glazing and Sash: All windows and sash shall be thermal break with insulating

glass and a low-E coating. All window units are to be free of paint and have functional locks. Replace all torn screens, broken glass, and insulating glass that has spoiled thermal seals.

F. Plumbing

Plumbing: Must function properly. See fixtures in Bathrooms and Kitchens above. G. Mechanical

Heating, Air Conditioning Units and Covers: Must function properly and have clean and neat appearance with no large dents or visible damage. Paint covers to match adjacent walls.

Page 69: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

69 January 10, 2017

H. Electrical Electrical wiring: Replace all aluminum wiring smaller than #4 or used for branch

service other than to a range. Electrical Fixtures, Outlets, Switches, Exhaust Fans, etc.: Must function properly and

have clean appearance with no chips, cracks, or paint. Electrical Receptacles and Switch Cover Plates: Replace all cover plates.

Smoke Detectors: Must function properly and have clean appearance. Replacement

smoke detectors shall preferably be hard-wired.

Smoke Detectors shall be replaced at 10 years.

END OF STANDARDS

Page 70: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

70 January 10, 2017

INDEX

Acoustical rating ...................................... 27 Alarm ........................................................ 53 Alarms ...................................................... 37 Appliances ............................. 26, 43, 46, 54 Architectural design responsibility ......... 7, 9 Balcony .............................................. 27, 52 Barrier Free .............................................. 11 Bathroom ......................... 27, 48, 50, 51, 62 Bathtub ........................................ 48, 51, 60 Blinds ....................................................... 45 Boilers and chillers .................................. 49 Building arrangement .............................. 25 Cabinets ................................. 26, 44, 54, 61 Carpet ................................................ 24, 40 Carport lighting ........................................ 30 Circulation .................................... 21, 22, 56 Civil engineering .................................... 7, 9 Collector roads ........................................ 28 Commitment ........ 15, 17, 18, 19, 20, 23, 46 Common areas .................................. 41, 55 Common facilities .............................. 21, 55 Common laundry ..................................... 56 Common spaces ................................ 41, 55 Community rooms ................................... 56 Community space .................................... 25 Concrete ............................................ 33, 39 Congregate .............................................. 55 Construction documents .............. 18, 19, 20 Contractor ...................................................9 Cooling ............................................... 46, 49 Corridors .................... 27, 40, 46, 51, 56, 57 Crafts rooms ............................................ 56 Design architects ................................... 7, 9 Design development .... 7, 18, 19, 20, 22, 23 Development data ............................. 20, 22 Development team ............................ 18, 19 Dining ....................................................... 26 Doors ..................................... 36, 38, 50, 54 Dryers ...................................................... 43 Ductwork .................................................. 46 Dwelling unit ...................................... 23, 26 Efficiency units ......................................... 25 Electrical .................... 26, 43, 46, 50, 51, 53 Elevator ............................ 50, 55, 56, 60, 61 Emergency call ........................................ 62 Emergency generator ........................ 50, 61 Energy load .............................................. 46 Environmental .............................. 12, 43, 47 Errors and omissions insurance ............ 7, 8

Exhaust hoods ................................... 43, 46 Faucets .................................................... 48 Feasibility ................... 17, 18, 19, 20, 22, 24 Federal Fair Housing Act ........................... 7 Field engineering ............................... 13, 22 Floor drain .......................................... 48, 56 Furnishability ................................ 23, 26, 62 Garbage disposal ............................... 43, 46 Generator ........................................... 50, 61 Glass ........................................................ 38 Grab bars ........................................... 42, 54 Gutters ..................................................... 35 Gypsum board ......................................... 39 Handrails .................................................. 54 Hanging rack ............................................ 45 Hazardous material.................................. 12 Heating ......................................... 46, 49, 53 Housing vouchers .................................... 11 HUD ........................................... 6, 7, 11, 40 HVAC ....................................................... 46 Insulation ............................................ 35, 47 Irrigation ............................................. 22, 31 Kitchen ............................. 26, 44, 48, 51, 54 Laundry ............................ 38, 39, 45, 48, 56 Laundry rooms ............................. 38, 45, 56 Lawn ......................................................... 29 Legal description ...................................... 13 Lighting .................................. 22, 30, 51, 52 Linen closet .............................................. 27 Living room .............................................. 26 Mailboxes ................................................. 42 Maintenance space.................................. 56 Maintenance strips ................................... 29 Material selections ................................... 24 Mechanical ................................... 46, 49, 54 Medicine cabinets .................................... 42 Microwave ................................................ 43 Mitigation .................................................. 12 Moisture ................................................... 35 One-bedroom ........................................... 26 Ovens ....................................................... 43 Owner-architect agreement ....................... 7 Package shelves ................................ 54, 57 Painting .................................................... 41 Parking lots .............................................. 28 Parking ratios ........................................... 28 Parking spaces ........................................ 28 Patios ........................................... 27, 29, 52 Pipe .......................................................... 47

Page 71: mshda Standards Of Design - Som - Michigan€¦ · General design parameters for housing financed by MSHDA shall include these Standards, latest applicable codes e.g. Michigan Building

MSHDA STANDARDS OF DESIGN

71 January 10, 2017

Plantings .................................................. 32 Plumbing .................................................. 48 Range ................................................ 26, 43 Refrigerators ............................................ 43 Rehabilitation ................................... 6, 7, 11 Resilient flooring ...................................... 39 Review consultants...................... 10, 18, 19 Seating ..................................................... 58 Section 504 ............................................ 6, 7 Security .............................................. 37, 53 Senior............................... 20, 37, 57, 61, 62 Sheathing ................................................. 35 Shut off valves ......................................... 46 Signs ........................................................ 32 Sinks ........................................................ 48 Site analysis....................................... 18, 19 Site plan ................................................... 22 Site work ...................................... 28, 54, 55 Smoke detectors ...................................... 53 Soil boring ................................................ 16 Sound ratings .......................................... 27 Storage .............................................. 26, 57 Structural engineer .....................................8

Substrate .................................................. 39 Survey ................................. 7, 9, 13, 15, 22 Task light ................................ 26, 43, 46, 51 Thermal .................................................... 35 Thermostats ....................................... 49, 61 Three-bedroom ........................................ 26 Title sheet .......................................... 20, 22 Tot or play lots ......................................... 32 Trash compactor ...................................... 56 Two-bedroom ........................................... 26 UFAS .................................................... 6, 11 Valves ...................................................... 46 Vinyl tile .................................................... 39 Walkways ................................................. 29 Wall base ................................................. 39 Wall hung ........................................... 44, 48 Washers ................................................... 43 Water ...................................... 27, 43, 47, 48 Water softeners ................................. 43, 47 Way finding .............................................. 55 Windows ...................................... 36, 37, 54 Wood ............................................ 34, 36, 54