EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 645 9888 [email protected] [email protected] [email protected] The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes. MTL4504 SWITCH/ PROXIMITY DETECTOR INTERFACE 1-channel with LFD and phase reversal The MTL4504 enables a safe–area load to be controlled, through a relay, by a proximity detector or switch located in a hazardous area. Line faults are signalled through a separate relay and indicated on the top of the module. MTBF information for the LFD relay is available from MTL to allow the failure rate for the LFD relay to be calculated when used in the critical path with the output relay for safety critical applications. Switches are provided to select phase reversal and to enable the line fault detection. SPECIFICATION See also common specification Number of channels One Location of switch Zone 0, IIC, T6 hazardous area Div.1, Group A, hazardous location Location of proximity detector Zone 0, IIC, T4–6 hazardous area, if suitably certified Div.1, Group A, hazardous location Hazardous–area inputs Inputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR) Voltage applied to sensor 7 to 9V dc from 1k±10% Input/output characteristics Normal phase Outputs closed if input > 2.1mA (< 2kin input circuit) Outputs open if input < 1.2mA (> 10kin input circuit) Hysteresis: 200µA (650) nominal Line fault detection (LFD) (when selected) User-selectable via switches on the side of the unit. Line faults are indicated by an LED. Line fault relay is de-energised and channel output relay de-energised if input line-fault detected Open-circuit alarm on if I in < 50µA Open-circuit alarm off if I in > 250µA Short-circuit alarm on if R in < 100Short-circuit alarm off if R in > 360Note: Resistors must be fitted when using the LFD facility with a contact input 500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch Safe-area output Channel: Single pole relay with changeover contacts LFD: Single pole relay with changeover contacts Note: reactive loads must be adequately suppressed Relay characteristics Response time: 10ms maximum Contact rating: 10W, 0.5A, 35V dc * Signal plug HAZ1-3 is required for access to this function LED indicators Green: power indication Yellow: channel status, on when output energised Red: LFD indication, on when line fault detected Maximum current consumption 25mA at 24V dc Power dissipation within unit 0.6W at 24V Safety description U o =10.5V I o =14mA P o =37mW U m = 253V rms or dc SIL 2 IEC 61508:2010 SIL capable These models have been assessed for use in IEC 61508 functional safety applications. See data on MTL web site and refer to the safety manual. MTL4504 22kΩ 680Ω + Output LFD Switch-type sensors require resistors if LFD is selected Vs– Vs+ 20 to 35V dc To earth-leakage detector * To earth-leakage detector * 6 5 4 3 2 1 LFD 9 8 7 12 11 10 13 14 EPS4504 Rev3 200913 Hazardous area Safe area FSM FUNCTIONAL SAFETY MANAGEMENT IEC 61508:2010

Upload: ihab

Post on 15-Jan-2016

224 views

Category:

Documents


0 download

DESCRIPTION

Safety barrier for ESD system and IS

TRANSCRIPT

Page 1: Mtl 4504

EUROPE (EMEA): +44 (0)1582 723633 THE AMERICAS: +1 800 835 7075 ASIA-PACIFIC: +65 6 645 9888

[email protected] [email protected] [email protected]

The given data is only intended as a product description and should not be regarded as a legal warranty of properties or guarantee. In the interest of further technical developments, we reserve the right to make design changes.

MTL4504SWITcH/ ProXIMITYDeTecTor InTerFace1-channel with LFD and phase reversal

The MTL4504 enables a safe–area load to be controlled, through a relay, by a proximity detector or switch located in a hazardous area. Line faults are signalled through a separate relay and indicated on the top of the module. MTBF information for the LFD relay is available from MTL to allow the failure rate for the LFD relay to be calculated when used in the critical path with the output relay for safety critical applications. Switches are provided to select phase reversal and to enable the line fault detection.

SPECIFICATIONSee also common specification

number of channelsOne

Location of switchZone 0, IIC, T6 hazardous areaDiv.1, Group A, hazardous location

Location of proximity detectorZone 0, IIC, T4–6 hazardous area, if suitably certifiedDiv.1, Group A, hazardous location

Hazardous–area inputsInputs conforming to BS EN60947–5–6:2001 standards for proximity detectors (NAMUR)

Voltage applied to sensor7 to 9V dc from 1kΩ ±10%

Input/output characteristicsNormal phase Outputs closed if input > 2.1mA (< 2kΩ in input circuit) Outputs open if input < 1.2mA (> 10kΩ in input circuit)Hysteresis: 200µA (650Ω) nominal

Line fault detection (LFD) (when selected)User-selectable via switches on the side of the unit. Line faults are indicated by an LED. Line fault relay is de-energised and channel output relay de-energised if input line-fault detectedOpen-circuit alarm on if Iin < 50µAOpen-circuit alarm off if Iin > 250µAShort-circuit alarm on if Rin < 100ΩShort-circuit alarm off if Rin > 360ΩNote: Resistors must be fitted when using the LFD facility with a contact input

500Ω to 1kΩ in series with switch 20kΩ to 25kΩ in parallel with switch

Safe-area output Channel: Single pole relay with changeover contactsLFD: Single pole relay with changeover contacts

Note: reactive loads must be adequately suppressed

relay characteristicsResponse time: 10ms maximumContact rating: 10W, 0.5A, 35V dc

* Signal plug HAZ1-3 is required for access to this function

LeD indicatorsGreen: power indicationYellow: channel status, on when output energisedRed: LFD indication, on when line fault detected

Maximum current consumption 25mA at 24V dc

Power dissipation within unit0.6W at 24V

Safety descriptionUo=10.5V Io=14mA Po=37mW Um = 253V rms or dc

SIL2

IEC 61508:2010

SIL capableThese models have been assessed for use in IEC 61508 functional safety applications. See data on MTL web site and refer to the safety manual.

MTL4504

22kΩ

680Ω

+

Output

LFD

Switch-type sensorsrequire resistorsif LFD is selected

Vs–Vs+

20 to 35V dc

To earth-leakage detector *

To earth-leakage detector *

654

321

LFD

987

121110

13 14

EPS4504 Rev3 200913

Hazardous area Safe area

FSM FUNCTIONAL SAFETY

MANAGEMENT

IEC 61508:2010