mVAC Medical VacuumThe mVAC Medical Vacuum System shall conform to EN ISO 7396-1/NHS Health Technical Memorandum No. 02-01 (HTM 02-01) or NHS Health Technical Memorandum No. 2022 (HTM 2022) - depending on model selected. The Medical Vacuum System shall ensure the minimum pipeline vacuum level of 450mmHg is maintained at the plant service connection point at the rated volumetric ‘free air’ flow rate with either two pumps in standby (ISO7396-1/HTM02-01) or with one pump on standby (HTM2022). The bacteria filtration system shall be ‘duplexed’ such that each filter can be isolated for replacement of the filter cartridge.
Vacuum PumpsVacuum pumps shall be air-cooled, oil lubricated rotary vane type suitable for both continuous and frequent start/stop operation at nominal inlet vacuum levels of between 578mmHg and 728mmHg. Composite carbon fibre rotor blades shall be fitted to minimise the cost of maintenance. Rotors shall be driven by directly coupled TEFV, IE2 efficiency electric motors. Pump inlets shall include a wire mesh filter and integral non-return valve to prevent oil suck back and pressure increases in the vacuum system. Each vacuum pump shall have an integral separator filter to ensure a virtually oil-free exhaust. Each pump shall be fitted with anti-vibration pads between the pump foot and mounting frame.
Bacteria FiltersThe duplex bacteria filter system shall incorporate high efficiency filter elements. A differential vacuum indicator shall be installed across the filter to indicate blockage. Additional pressure sensors shall be installed at the inlet and outlet of the filter to measure the pressure drop across the filters. Each filter shall be designed and sized to carry the full plant design flow capacity with a pressure drop not exceeding 33mbar (25mmHg). Bacteria Filter elements shall have penetration levels not exceeding 0.005% when tested by the sodium flame method in accordance with BS 3928:1969 and utilising particles in the 0.02 to 2 micron size range. Drain flasks shall be connected to each filter. Drain flasks shall be manufactured from transparent Pyrex® with a polymer coating on the inner and outer surfaces in order to maintain a seal in the event of inadvertent breakage of the Pyrex® flask. All drain flasks shall be suitable for sterilisation and be connected via a manual isolating valve.
Control SystemThe central control system shall provide an intelligent human machine interface incorporating on board flash memory and real-time clock for recording operational parameters in the in built event log. The central control system shall operate at low voltage and include BMS connection for common fault. Visualisation of plant inputs, outputs and status through a web browser, using a simple Ethernet connection shall be available. The central control unit shall incorporate a user friendly 5.7” high-definition colour display with clear pictograms and LED indicators, providing easy access to system operational information.
Cascading of vacuum pumps shall be achieved by measuring the vacuum level at the plant inlet with a pressure transducer. A mechanical back-up facility shall ensure continued operation in the event of a control system malfunction. The control system shall normally employ automatic rotation of the lead pump to maximise pump life and ensure even wear.
mVAC Medical Vacuum System 400v 50Hz & 380v 60Hz– EN ISO 7396-1/HTM 02-01 and HTM2022
SPECIFICATION
mVA
C M
EDIC
AL
VAC
UU
M S
YSTE
M
Optional Control EquipmentAn advanced monitoring system shall be available to give immediate access to valuable information such as system status, trends, historical data and system performance. Data collected from all pumps shall be made available in real-time visualisation pages and shall be accessed through the hospital’s LAN, such that total data security is assured.
The Airconnect™ monitoring system shall also include :-
• Logging and trending for an accurate performance status of your system.
• Desktop event notification to avoid constant status checking.
• E-mail and SMS event notification for additional convenience.
Optional ItemsThere shall be the followings options available for enhanced operation of the vacuum plant system:-
• Synthetic oil for increased pump life.
• Painted hot dipped galvanised vessels.
• Oil level switch and integrated ES-VAC alarm for notification of low oil level in the pumps.
Vacuum Receiver(s)Vacuum receiver(s) shall be supplied with relevant test certificates and have a total volume of at least 100% of the plant output in 1 minute in terms of free air aspired at normal working pressure. Each vacuum receiver shall be hot dip galvanised inside and out.
Pyrex® is a registered trademark of Corning Glass.
CE MarkingThe standard range of BeaconMedæs Medical Vacuum plant systems are ‘CE’ marked under the Medical Devices Directive 93/42/EEC with approval from notified body no. 0088 (Lloyd’s Register Quality Assurance). Under this directive, the specified products are classified as Class IIa Medical Devices.
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 2
Typical Layout
HTM02-01 50 Hz
Model L (ength) W (idth) H (eight) LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 250 T - 50 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
mVAC 330 T - 50 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
mVAC 500 T - 50 Hz 2400 980 1650 3700 1980 500 800 54 54 n/a
mVAC 300 T - 60 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
mVAC 400 T - 60 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 660 Q - 50 Hz 1910 980 2100 660 3210 3740 500 800 54 54 54 outl. unit - 54 inl. vessel
mVAC 1000 Q - 50 Hz 1910 980 2100 660 3210 3740 500 800 54 54 54 outl. unit - 54 inl. vessel
mVAC 2560 Q - 50 Hz 2600 1200 2400 1060 3900 4360 500 800 76 54 76 outl. unit - 54 inl. vessel
mVAC 3300 Q - 50 Hz 2600 1200 2500 1230 3900 4530 500 800 76 54 76 outl. unit - 76 inl. vessel
mVAC 3840 P - 50 Hz 4100 1250 2500 1230 5990 4580 500 800 76 54 76 outl. unit - 76 inl. vessel
mVAC 620 T - 60 Hz 1910 980 2100 660 3210 3740 500 800 54 54 54 outl. unit - 54 inl. Vessel
mVAC 800 Q - 60 Hz 1910 980 2100 660 3210 3740 500 800 54 54 54 outl. unit - 54 inl. Vessel
mVAC 1200 Q - 60 Hz 1910 980 2500 860 3210 3940 500 800 54 54 54 outl. unit - 54 inl. Vessel
mVAC 1500 T - 60 Hz 2200 1100 2500 860 3500 4060 500 800 54 54 54 outl. unit - 54 inl. Vessel
mVAC 3000 Q - 60 Hz 2600 1200 2500 1230 3900 4530 500 800 86 54 76 outl. unit - 76 inl. Vessel
mVAC 3900 Q - 60 Hz 2600 1200 2500 1230 3900 4530 500 800 86 54 76 outl. unit - 76 inl. Vessel
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 3
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 1280 T - 50 Hz 2200 1100 2100 660 4280 3860 500 800 76 54 54 outl. unit - 54 inl. Vessel
mVAC 4950 P - 50 Hz 4100 1250 2500 1230 5990 4580 500 800 108 54 108 outl. unit - 76 inl. Vessel
mVAC 6000 H - 50 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. Vessel
mVAC 4500 P - 60 Hz 4100 1250 2400 1060 5480 4410 500 800 86 108 108 outl. unit - 76 inl. Vessel
mVAC 5850 P - 60 Hz 4100 1250 2500 1230 5990 4580 500 800 86 108 108 outl. unit - 76 inl. Vessel
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 6600 H - 50 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. Vessel
mVAC 7800 H - 60 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. Vessel
Note!
mVAC-6600-H includes 4 x vessels
Drawing shows other models not used in this range and are for illustration purposes only.
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 4
HTM2022 50 Hz
Model L (ength) W (idth) H (eight) LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 250 D - 50 Hz 2040 980 1650 3340 1980 500 800 54 54 n/a
mVAC 300 D - 60 Hz 2040 980 1650 3340 1980 500 800 54 54 n/a
Model L (ength) W (idth) H (eight) LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 500 T - 50 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
mVAC 660 T - 50 Hz 2400 980 1900 3700 1980 500 800 54 54 n/a
mVAC 1000 T - 50 Hz 2400 980 1900 3700 1980 500 800 54 54 n/a
mVAC 500 T - 60 Hz 2300 980 1650 3600 1980 500 800 54 54 n/a
mVAC 800 T - 60 Hz 2400 980 1900 3700 1980 500 800 54 54 n/a
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 1500 Q - 50 Hz 1830 980 2400 1060 3130 3840 500 800 54 54 54 outl. unit - 54 inl. vessel
mVAC 1200 T - 60 Hz 1910 980 2400 1060 3210 3840 500 800 54 54 54 outl. unit - 54 inl. vessel
mVAC 1860 Q - 60 Hz 2200 1200 2500 1230 3500 4230 500 800 76 54 76 outl. unit - 76 inl. vessel
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 5
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 2560 T - 50 Hz 2600 1200 2400 1060 3900 4360 500 800 76 54 76 outl. unit - 54 inl. vessel
mVAC 3840 Q - 50 Hz 2600 1200 2500 1230 3900 4530 500 800 76 54 76 outl. unit - 76 inl. vessel
mVAC 3000 T - 60 Hz 2600 1200 2500 1230 3900 4530 500 800 76 54 76 outl. unit - 76 inl. vessel
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 4950 Q - 50 Hz 3400 1250 2500 1230 5990 4580 500 800 76 108 108 outl. unit - 76 inl. vessel
mVAC 6000 P - 50 Hz 4100 1250 2500 1230 5990 4580 500 800 76 108 108 outl. unit - 76 inl. vessel
mVAC 4500 Q - 60 Hz 3400 1250 2400 1060 5480 4410 500 800 76 108 108 outl. unit - 76 inl. vessel
mVAC 5850 Q - 60 Hz 3400 1250 2500 1230 5990 4580 500 800 76 108 108 outl. unit - 76 inl. vessel
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 6
Note!
mVAC-6600-P and mVAC 8000-H include 4 x vessels
Drawing shows other models not used in this range and are for illustration purposes only.
Model L (ength) W (idth) H (eight) Ø D LMA WMA F G I (nlet) Ø E (xhaust) Ø V (essel con.) Ø
mVAC 6600 P - 50 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. vessel
mVAC 8000 H - 50 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. vessel
mVAC 7800 P - 60 Hz 4100 1250 2500 1230 7220 4580 500 800 108 54 108 outl. unit - 76 inl. vessel
mVAC 9200 H - 60 Hz 4100 1250 2500 1230 7720 4580 500 800 108 54 108 outl. unit - 76 inl. vessel
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 7
Model Number
mVA
C-2
50-T
H
mVA
C-3
30-T
H
mVA
C-5
00-T
H
mVA
C-6
60-Q
mVA
C-1
000-
Q
mVA
C-1
280-
T
mVA
C-2
560-
Q
mVA
C-3
300-
Q
mVA
C-3
840-
P
mVA
C-4
950-
P
mVA
C-6
000-
H
mVA
C-6
600-
H
Plant Output (litres/minute) 250 330 500 660 1000 1280 2560 3300 3840 4950 6000 6600
System Flow (m3/h - l/m) 4066552
86579
1315105
1750 159
2650203
3380406
6765 524
8730609
10150 786
13100 952
158651047
17450
Number of pumps 3 3 3 4 4 3 4 4 5 5 6 6
Number of receivers 1(H) 1(H) 1(H) 2 2 3 2 2 2 3 3 4
Total receiver volume (litres) 500 500 500 1000 1000 1500 3000 4000 4000 6000 6000 8000
Receiver connection(s) (mm) n/a n/a n/a 54 54 54 54 76 76 76 76 76
Inlet/service connection (mm) 54 54 54 54 54 54 76 76 76 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 69 70 69 70 72 72 75 72 75 75 75
Weight (kg) 650 690 750 960 1040 1475 2215 2335 2660 3190 3390 3820
Motor rating (kW) 1.1 1.5 2.2 1.5 2.2 5.5 5.5 7.5 5.5 7.5 7.5 7.5
Motor cable size (mm2/Amps) 1.5 (13)1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
2.5 (17)
1.5 (13)
2.5 (17)
2.5 (17)
2.5 (17)
Motor rated supply per pump (A) 10 10 10 10 10 20 20 20 20 20 20 20
FLC per pump (A) 2.8 3.6 5.1 3.6 5.1 12 12 14.9 12 14.9 14.9 14.9
Starting current (A) 14 18 26 18 26 60 60 75 60 75 75 75
Central control supply - single phase (mm2/Amps)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.2 0.1 0.2 0.3 0.3 0.4 0.3 0.4 0.4 0.4
Installation ProposalPart Number
9820
636
5 00
8152
130
6 00
9820
636
5 00
8152
1 30
6 02
9820
636
5 00
8152
130
6 04
9820
636
8 00
8152
130
6 06
9820
636
8 00
8152
130
6 08
9820
636
9 00
8152
130
6 10
9820
636
8 00
8152
130
6 12
9820
636
8 00
8152
130
6 14
9820
636
8 00
8152
130
6 16
9820
636
9 00
8152
130
6 18
9820
636
9 00
8152
130
6 20
9820
637
0 00
8152
130
6 22
• Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with two pumps on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with two pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.
Data Tables
HTM02-01 50 Hz
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 8
Model Number
mVA
C-2
50-T
N
V
mVA
C-3
30-T
N
V
mVA
C-5
00-T
N
V
mVA
C-6
60-Q
N
V
mVA
C-1
000-
Q
NV
mVA
C-1
280-
T N
V
mVA
C-2
560-
Q
NV
mVA
C-3
300-
Q
NV
mVA
C-3
840-
P N
V
mVA
C-4
950-
P N
V
mVA
C-6
000-
H
NV
mVA
C-6
600-
H
NV
Plant Output (litres/minute) 250 330 500 660 1000 1280 2560 3300 3840 4950 6000 6600
System Flow (m3/h - l/m) 40 66552
86579
1315105
1750 159
2650203
3380406
6765 524
8730609
10150 786
13100 952
158651047
17450
Number of pumps 3 3 3 4 4 3 4 4 5 5 6 6
Number of receivers n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Total receiver volume (litres) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Receiver connection(s) (mm) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Inlet/service connection (mm) 54 54 54 54 54 54 76 76 76 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 69 70 69 70 72 72 75 72 75 75 75
Motor rating (kW) 1.1 1.5 2.2 1.5 2.2 5.5 5.5 7.5 5.5 7.5 7.5 7.5
Motor cable size (mm2/Amps) 1.5 (13)1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
2.5 (17)
1.5 (13)
2.5 (17)
2.5 (17)
2.5 (17)
Motor rated supply per pump (A) 10 10 10 10 10 20 20 20 20 20 20 20
FLC per pump (A) 2.8 3.6 5.1 3.6 5.1 12 12 14.9 12 14.9 14.9 14.9
Starting current (A) 14 18 26 18 26 60 60 75 60 75 75 75
Central control supply - single phase (mm2/Amps)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.2 0.1 0.2 0.3 0.3 0.4 0.3 0.4 0.4 0.4
Installation ProposalPart Number
-81
52 1
306
48
-81
521
306
49
-81
52 1
306
50
-81
52 1
306
51
-81
52 1
306
52
-81
52 1
306
53
-81
52 1
306
54
-81
52 1
306
55
-81
52 1
306
56
-81
52 1
306
57
-81
52 1
306
58
-81
52 1
306
59 • Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with two pumps on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with two pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.
HTM02-01 50 Hz - No Vessels
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 9
HTM2022 50 Hz
Model Number
mVA
C-2
50-D
H
mVA
C-5
00-T
H
mVA
C-6
60-T
H
mVA
C-1
000-
TH
mVA
C-1
500-
Q
mVA
C-2
560-
T
mVA
C-3
840-
Q
mVA
C-4
950-
Q
mVA
C--
6000
-P
mVA
C-6
600-
P
mVA
C-8
000-
H
Plant Output (litres/minute) 250 500 660 1000 1500 2560 3840 4950 6000 6600 8000
System Flow (m3/h - l/m) 4066579
1315105
1750159
2650238
3965406
6765609
10150 786
13100 952
158651047
174501270
21165
Number of pumps 2 3 3 3 4 3 4 4 5 5 6
Number of receivers 1(H) 1(H) 1(H) 1(H) 1 2 2 3 3 4 4
Total receiver volume (litres) 500 500 1000 1000 1500 3000 4000 6000 6000 8000 8000
Receiver connection(s) (mm) n/a n/a n/a n/a 54 54 76 76 76 76 76
Inlet/service connection (mm) 54 54 54 54 54 54 76 108 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 67 69 70 70 72 72 75 75 75 75
Weight (kg) 540 650 800 860 1120 2105 2560 3090 3340 3770 4080
Motor rating (kW) 1.1 1.1 1.5 2.2 2.2 5.5 5.5 7.5 7.5 7.5 7.5
Motor cable size (mm2/Amps) 1.5 (13)1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
2.5 (17)
2.5 (17)
2.5 (17)
2.5 (17)
Motor rated supply per pump (A) 10 10 10 10 10 20 20 20 20 20 20
FLC per pump (A) 2.8 3.6 5.1 3.6 5.1 12 12 14.9 14.9 14.9 14.9
Starting current (A) 14 18 26 18 26 60 60 75 75 75 75
Central control supply - single phase (mm2/Amps) 1.5(5)1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4 0.4 0.4
Installation ProposalPart Number
9820
636
4 00
8152
130
6 82
9820
636
5 00
8152
130
6 84
9820
636
5 00
8152
130
6 86
9820
636
5 00
8152
130
6 88
9820
636
7 00
8152
130
6 90
9820
636
8 00
8152
130
6 92
9820
636
8 00
8152
130
6 94
9820
636
9 00
8152
130
6 96
9820
636
9 00
8152
130
6 98
9820
637
0 00
8152
130
7 00
9820
637
0 00
8152
130
7 02
• Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with one pump on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with one pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 10
Model Number
mVA
C-2
50-D
N
V
mVA
C-5
00-T
N
V
mVA
C-6
60-T
N
V
mVA
C-1
000-
T N
V
mVA
C-1
500-
Q
NV
mVA
C-2
560-
T N
V
mVA
C-3
840-
Q
NV
mVA
C-4
950-
Q
NV
mVA
C--
6000
-P
NV
mVA
C-6
600-
P N
V
mVA
C-8
000-
H
NV
Plant Output (litres/minute) 250 500 660 1000 1500 2560 3840 4950 6000 6600 8000
System Flow (m3/h - l/m) 4066579
1315105
1750159
2650238
3965406
6765609
10150 786
13100 952
158651047
174501270
21165
Number of pumps 2 3 3 3 4 3 4 4 5 5 6
Number of receivers n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Total receiver volume (litres) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Receiver connection(s) (mm) n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Inlet/service connection (mm) 54 54 54 54 54 54 76 108 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 69 69 70 70 72 72 75 75 75 75
Motor rating (kW) 1.1 1.5 1.5 2.2 2.2 5.5 5.5 7.5 7.5 7.5 7.5
Motor cable size (mm2/Amps) 1.5 (13)1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
2.5 (17)
2.5 (17)
2.5 (17)
2.5 (17)
Motor rated supply per pump (A) 10 10 10 10 10 20 20 20 20 20 20
FLC per pump (A) 2.8 2.8 5.1 3.6 5.1 12 12 14.9 14.9 14.9 14.9
Starting current (A) 14 14 26 18 26 60 60 75 75 75 75
Central control supply - single phase (mm2/Amps) 1.5(5)1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.1 0.2 0.2 0.3 0.3 0.4 0.4 0.4 0.4
Installation ProposalPart Number
-81
52 1
307
26
-81
52 1
307
27
-81
52 1
307
28
-81
52 1
307
29
-81
52 1
307
30
-81
52 1
307
31
-81
52 1
307
32
-81
52 1
307
33
-81
52 1
307
34
-81
52 1
307
35
-81
52 1
307
36• Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with one pump on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with one pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.
HTM2022 50 Hz - No Vessels
-
BeaconMedæs ● Telford Crescent, Staveley, Derbyshire S43 3PF ● Tel: +44 (0) 1246 474 242 ● Fax: +44 (0) 1246 472 982 Company Reg No. 2957933 (English) ● Company VAT Reg No. 598612590 ● www.beaconmedaes.com ● [email protected]
Constructionline Reg No. 75463 ● CHAS accredited contractor ● SAFEcontractor Reg No. N00184450
200516116/05/14
Issue 7
Page 11
HTM02-01 60 Hz
Model Number
mVA
C-3
00-T
H
mVA
C-4
00-T
H
mVA
C-6
20-T
mVA
C-8
00-Q
mVA
C-1
200-
Q
mVA
C-1
500-
T
mVA
C-3
000-
Q
mVA
C-3
900-
Q
mVA
C-4
500-
P
mVA
C-5
850-
P
mVA
C-7
800-
H
Plant Output (litres/minute) 300 400 620 800 1200 1500 3000 3900 4500 5850 7800
System Flow (m3/h - l/m) 4880063
105098
1630127
2115190
3165 238
3965476
7930619
10315 714
11900928
15465 1238
20630
Number of pumps 3 3 3 4 4 3 4 4 5 5 6
Number of receivers 1(H) 1(H) 2 2 2 2 2 2 3 3 4
Total receiver volume (litres) 500 500 1000 1000 2000 2000 3000 4000 4500 6000 8000
Receiver connection(s) (mm) n/a n/a 54 54 54 54 54 76 54 76 76
Inlet/service connection (mm) 54 54 54 54 54 54 76 76 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 75 72 75 72 74 74 77 74 77 77
Weight (kg) 650 690 1050 960 1260 1545 2380 2560 3185 3340 4080
Motor rating (kW) 1.7 2.4 3.4 2.4 3.4 9.2 9.2 10 9.2 10 10
Motor cable size (mm2/Amps)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
4(23)
4(23)
4(23)
4(23)
4(23)
4(23)
Motor rated supply per pump (A) 10 10 25 10 25 25 25 25 25 25 25
FLC per pump (A) 4 5.7 7.4 5.7 7.4 18.5 18.5 20.8 18.5 20.8 20.8
Starting current (A) 20 29 37 29 37 93 93 104 93 104 104
Central control supply - single phase(mm2/Amps)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.2 0.1 0.2 0.3 0.3 0.4 0.3 0.4 0.4
Installation ProposalPart Number
9820
636
5 00
8152
130
6 60
9820
636
5 00
8152
130
6 62
9820
636
8 00
8152
130
6 64
9820
636
8 00
8152
130
6 66
9820
636
8 00
8152
130
6 68
9820
636
8 00
8152
130
6 70
9820
636
8 00
8152
130
6 72
9820
636
8 00
8152
130
6 74
9820
636
9 00
8152
130
6 76
9820
636
9 00
8152
130
6 78
9820
637
0 00
8152
1 30
6 80
• Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with two pumps on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with two pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.
-
BeaconMedæsTelford Crescent,Staveley, DerbyshireS43 3PF, EnglandTel: +44 (0) 1246 474 242Fax: +44 (0) 1246 472 982www.beaconmedaes.comE-mail: [email protected] 0088
200516116/05/14
Issue 7
In an effort to continuously improve our products, the right is reserved to change the specification of the items described herein at any time. Please contact us for further information and up to date specifications.
Page 12
HTM2022 60 Hz
Model Number
mVA
C-3
00-D
H
mVA
C-5
00-T
H
mVA
C-8
00-T
H
mVA
C-1
200-
T
mVA
C-1
860-
Q
mVA
C-3
000-
T
mVA
C-4
500-
Q
mVA
C-5
850-
Q
mVA
C-7
800-
P
mVA
C-9
200-
H
Plant Output (litres/minute) 300 500 800 1200 1860 3000 4500 5850 7800 9200
System Flow (m3/h - l/m) 4880079
1315127
2115190
3165 295
4915476
7930714
11900928
15465 1238
20630 1460
24330
Number of pumps 2 3 3 3 4 3 4 4 5 6
Number of receivers 1(H) 1(H) 1(H) 1 1 2 3 3 4 5
Total receiver volume (litres) 500 500 1000 1500 2000 3000 4500 6000 8000 10000
Receiver connection(s) (mm) n/a n/a n/a 54 76 54 54 76 76 76
Inlet/service connection (mm) 54 54 54 54 54 76 76 108 108 108
Exhaust connection (mm, per pump) 54 54 54 54 54 54 54 54 54 54
Maximum exhaust back pressure (mbar) 60 60 60 60 60 60 60 60 60 60
Noise level/pump (dB[A]) 67 67 75 72 72 74 74 77 77 77
Weight (kg) 540 650 800 980 1480 2565 2935 3090 3880 4510
Motor rating (kW) 1.7 1.7 2.4 3.4 3.4 9.2 9.2 10 10 10
Motor cable size (mm2/Amps) 1.5 (13)1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
4 (23)
4 (23)
4 (23)
4 (23)
4 (23)
Motor rated supply per pump (A) 10 10 10 25 25 25 25 25 25 25
FLC per pump (A) 4 4 5.7 7.4 7.4 18.5 18.5 20.8 20.8 20.8
Starting current (A) 20 20 29 37 37 93 93 104 104 114
Central control supply - single phase (mm2/Amps) 1.5(5)1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
1.5(5)
Maximum Inlet Temperature (0C) 40 40 40 40 40 40 40 40 40 40
Cooling air flow per pump (m3/s) 0.1 0.1 0.2 0.2 0.3 0.3 0.3 0.4 0.4 0.4
Installation ProposalPart Number
9820
636
4 00
8152
130
7 37
9820
636
5 00
8152
130
7 39
9820
636
5 00
8152
130
7 41
9820
636
7 00
8152
130
7 43
9820
636
7 00
8152
130
7 45
9820
636
8 00
8152
130
7 47
9820
636
9 00
8152
130
7 49
9820
636
9 00
8152
130
7 51
9820
637
0 00
8152
130
7 53
9820
637
0 00
8152
130
7 55
• Plant Output in terms of free air aspired at a vacuum of 450 mmHg at the inlet connection with one pump on standby and with a tolerance of ±10%.• System Flow at atmospheric pressure at the inlet connection with one pump on standby and with a tolerance of ±10%.• Plant dimensions include the required space around the plant for maintenance access.• Mean sound level measured at a distance of 1m as measured to ISO 2151 / DIN 45635.• Electrical details are provided for guidance only and are referenced at 400C ambient temperature. Site conditions may impose a larger cable size. For exact cable sizing, and fuse / MCB ratings, consult a qualified electrical engineer.• Plant weight includes packaging for shipping purposes.