NCTCOGNorth Central Texas Council of Government
(COG)
![Page 2: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/2.jpg)
What is NCTCOG?
A voluntary association of, by and for local governments, established to assist local
governments in planning for common needs, cooperating for mutual benefit, and coordinating
for sound regional development.
![Page 3: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/3.jpg)
COG was established on January 20, 1966It was intended to help local governments improve
their capability to serve their citizens by defining regional issues, problems and opportunities; by
setting priorities, and devising policies, plans and programs to deal with them.
![Page 4: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/4.jpg)
About NCTCOGServes 16 Counties and 230 member governments which make up the
General Assembly, who annually elect the Executive Board
![Page 5: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/5.jpg)
What is NCTCOG Pamphlet online?
![Page 6: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/6.jpg)
Executive Board7 locally elected officials and one ex-officio non-
voting member of the legislature and is the policy-making body for all activities undertaken by the
Council of Governments.
![Page 7: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/7.jpg)
Organizational Chart
![Page 8: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/8.jpg)
RCCC
Regional Codes Coordinating Committee(RC3)
Resides under the umbrella of the Environment and Development Department
![Page 9: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/9.jpg)
The RCCC researches and provides recommendations on the standardization of municipal construction codes.
28 members serve 2 year termsIt is comprised of building officials, architects, engineers, contractors,
educators, property management professionals, insurance reps, builders and developers.
![Page 10: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/10.jpg)
RCCC PurposeThe primary purpose of the RCCC is to foster municipal government and private industry cooperation in promoting the
standardization of construction codes used within the North Central Texas region.
This includes the adoption of the NCTCOG Recommended Codes and the NCTCOG Regional Amendments. (The COG Amendments)
![Page 11: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/11.jpg)
Linkshttp://www.nctcog.org/ENVIR/SEEDevEx/codes/index.asphttp://www.nctcog.org/ENVIR/committees/rccc/2017RCCCInternetRoster.pdfhttp://www.nctcog.org/ENVIR/committees/rccc/building/index.asp
![Page 12: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/12.jpg)
5 Regional Code Advisory Boards
Building & ResidentialElectrical
Energy & GreenFire
Plumbing & Mechanical
![Page 13: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/13.jpg)
Building & Residential Advisory Board
Provides support and technical advice to NCTCOG’s Regional Codes Coordinating Committee (RCCC) on a wide range of building issues.
The current Chair is Selso Mata, Building Official City of Plano The current Vice-Chair is Jack Thompson, Building Official Town of Westover
Hills
![Page 14: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/14.jpg)
2015 Code Amendments Letter
![Page 15: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/15.jpg)
Current Code Amendments
![Page 16: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/16.jpg)
Typical Amendment Page
![Page 17: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/17.jpg)
Section 1704 Special Inspections
![Page 18: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/18.jpg)
Statement of Required Special Inspections
![Page 19: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/19.jpg)
Approved Agency Documentation
![Page 20: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/20.jpg)
Final Report of Required Special Inspections
![Page 21: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/21.jpg)
![Page 22: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/22.jpg)
The Code AmendmentsJarod Fancher
![Page 23: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/23.jpg)
I will not read the code to you.
![Page 24: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/24.jpg)
Most of what I say is paraphrased.
![Page 25: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/25.jpg)
Read the amendment text to fully understand the associated changes.
![Page 26: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/26.jpg)
Treat this presentation as a discussion.
![Page 27: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/27.jpg)
Ask questions when you think of them.
![Page 28: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/28.jpg)
How to Understand the Amendments Document
![Page 29: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/29.jpg)
Underlined Text is Added InformationStrikethrough Text is Deleted Information
** = No New Changes from Previous Year*** = New Changes from Previous Year
![Page 30: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/30.jpg)
![Page 31: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/31.jpg)
Chapter 1
![Page 32: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/32.jpg)
101.4 Referenced Codes
Clarification
![Page 33: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/33.jpg)
![Page 34: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/34.jpg)
Adds legal language to state that an amendment to the IBC shall also amend
other referenced documents.
![Page 35: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/35.jpg)
When you change the definition of an Atrium from 2 connected stories to 3 in the IBC.
It also changes the definition in the IFC.
![Page 36: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/36.jpg)
![Page 37: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/37.jpg)
101.4.8 ElectricalNew section added to include the
reference codes for electrical work.
![Page 38: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/38.jpg)
The ICC Electric Code was replaced by IBC Appendix K in 2012.
![Page 39: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/39.jpg)
The ICC Electric Code was replaced by IBC Appendix K in 2012.
So they removed it…
![Page 40: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/40.jpg)
Appendix K recognizes NFPA 70 as the code for electrical construction.
![Page 41: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/41.jpg)
NFPA 70 is the National Electric Code
![Page 42: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/42.jpg)
103.1 Creation of
Enforcement Agency
Recommendation
![Page 43: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/43.jpg)
Recommendation for a city to replace “Department of Building Safety” with the formal
name of their department.
![Page 44: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/44.jpg)
104.2.1 Damaged Buildings104.10.1 Flood Hazard Areas
Recommendation
![Page 45: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/45.jpg)
Un-amended, this states that the building official determines if work on
a damaged building is technically reconstructionor just repairs.
![Page 46: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/46.jpg)
Recommends that Cities amend or delete these sections based on actual enforcement and flood
hazard ordinances.
![Page 47: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/47.jpg)
105.2 Work Exempt from Permit
Removes some exceptions.
![Page 48: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/48.jpg)
Single-story tool sheds, storage buildings, play houses and shade-cloth-structures-for-gardens
should not be exempt from permit.
These are often governed by the International Residential Code and local ordinances.
![Page 49: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/49.jpg)
109.7 Re-Inspection Fee
New Section
![Page 50: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/50.jpg)
New section which lists the faults that allow a City to charge a fee
for re-inspecting work.
![Page 51: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/51.jpg)
For fun…
What are the reasons?
![Page 52: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/52.jpg)
The work is not ready for inspection.
![Page 53: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/53.jpg)
The building address or permit card is not posted.
![Page 54: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/54.jpg)
Approved plans are not on site.
![Page 55: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/55.jpg)
Building is locked.
![Page 56: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/56.jpg)
Job is Red Tagged TWICE for the same reason.
![Page 57: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/57.jpg)
A Red Tag is removed from the job site.
![Page 58: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/58.jpg)
Failure to maintain erosion control, trash control or tree protection.
![Page 59: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/59.jpg)
109.8 Work Without a Permit
New section
![Page 60: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/60.jpg)
Allows an investigation fee to be charged for work started or completed without a permit.
The avoided permit fee must also be paid.
![Page 61: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/61.jpg)
110.3.5 Lath & Gypsum Inspections
Removes an exception.
![Page 62: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/62.jpg)
Removes the exception for materials on a non-rated assembly.
All lath and gypsum are inspected.
![Page 63: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/63.jpg)
Chapter 2
![Page 64: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/64.jpg)
202 Definitions
![Page 65: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/65.jpg)
Ambulatory Care Facility
Buildings which provide services on a less-than-24-hour-basis to individuals who are rendered incapable of self-preservation by the
services provided.
The following services shall be included:
![Page 66: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/66.jpg)
DialysisSedation Dentistry
SurgeryColonic
Psychiatric
![Page 67: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/67.jpg)
Assisted Living Facilities
The definition was removed from the 2012 IBC and should be included since the term is still used
within the code book.
![Page 68: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/68.jpg)
Atrium
An opening connecting two three or more stories.
Allowed by legacy codes. Section 1019 permits unenclosed two-story stairs.
![Page 69: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/69.jpg)
Why?
Section 1019 permits unenclosed two-story stairs & two-story spaces
were allowed by legacy codes.
![Page 70: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/70.jpg)
Repair Garage
Definition added to align with the International Fire Code.
![Page 71: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/71.jpg)
Special Inspector
Now includes language to include the Registered Design Professional
as a party to the special inspections process.
![Page 72: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/72.jpg)
A qualified person employed or retained by an approved agency
who shall prove to the satisfaction of the registered design professional in responsible charge
and approved by the Building Official as having the competence necessary to inspect a particular type of
construction requiring special inspection.
![Page 73: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/73.jpg)
![Page 74: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/74.jpg)
High-Rise Building
Option A: Maintains the original definition with the 75-foot threshold.
Option B: The 75-foot threshold is reduced to 55-feet for jurisdictions who lack certain fire fighting capabilities; therefore, requiring larger sprinkler
threshold requirements.
![Page 75: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/75.jpg)
Question
Does anyone know how the sprinkler thresholds are affected by being a “high-rise building” ?
![Page 76: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/76.jpg)
Chapter 3
![Page 77: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/77.jpg)
303.1.3 Assembly Occupancy Associated
with E Occupancies
Clarification
![Page 78: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/78.jpg)
An assembly room associated with an Education building is not considered a separate occupancy.
![Page 79: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/79.jpg)
An assembly room associated with an Education building is not considered a separate occupancy.
Except when applying the assembly requirements of Chapters 10 & 11.
![Page 80: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/80.jpg)
Clarifications Only:
Cafeterias & Auditoriums must comply with means of egress & accessibility.
![Page 81: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/81.jpg)
304.1 Business Group B
Adds to the uses list.
![Page 82: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/82.jpg)
![Page 83: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/83.jpg)
Fire Stations
Police Stations with 5 or less detention facilities
![Page 84: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/84.jpg)
307.1.1 Uses Other than Group HUses with hazardous materials that are not
classified under Group H.
![Page 85: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/85.jpg)
Clarifies Exception 4: Dry Cleaners.
New text calls attention to IFC Chapter 21, Dry Cleaning Plant provisions.
![Page 86: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/86.jpg)
Chapter 4
![Page 87: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/87.jpg)
403.1 High-Rise Buildings
Clarification to an exemption.
![Page 88: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/88.jpg)
ONLY open air portions of a high-rise stadium are exempt from the high-rise requirements.
![Page 89: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/89.jpg)
403.3 Automatic Sprinkler System
Removes an Exception
![Page 90: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/90.jpg)
Removes the exception for telecommunication buildings to
be un-sprinkled.
![Page 91: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/91.jpg)
403.3.2 Water Supply to Fire Pumps
Modification
![Page 92: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/92.jpg)
Buildings above a certain height are required to connect to two separate water mains.
The amendment changes this threshold from 420 feet to only 120 feet.
![Page 93: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/93.jpg)
404.5 Smoke Control
Removes Exception
![Page 94: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/94.jpg)
Deletes the exception which excludes two-story atriums from requiring
smoke control.
This is consistent with the amended definition for an atrium.
![Page 95: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/95.jpg)
406.3.5.1 Carport Separation
Adds text.
![Page 96: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/96.jpg)
A fire separation is not required between carports and R-3 buildings.
COG recommends including R-2 apartment buildings, so long as they are at least
10 feet from the adjacent building.
![Page 97: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/97.jpg)
Chapter 5
![Page 98: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/98.jpg)
506.3.2.1 Open space Limits
Clarification
![Page 99: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/99.jpg)
Explains that an accessible area must be a street, fire lane, or 10 foot pathway meeting fire
department access requirements.
![Page 100: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/100.jpg)
Chapter 7
![Page 101: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/101.jpg)
712.1.9 Two-Story Openings
Modification
![Page 102: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/102.jpg)
Two-story openings will be allowed to open onto corridors in R occupancies, but not allowed in H
occupancies.
This is consistent with the amended definition for an atrium.
![Page 103: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/103.jpg)
Chapter 9
![Page 104: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/104.jpg)
901.6.1.1 Standpipe Testing
New Section
![Page 105: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/105.jpg)
Building owners must maintain and test standpipe systems per NFPA 25.
![Page 106: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/106.jpg)
903.1.1 Alternative Protectionfor Automatic Sprinkler Systems
Modification
![Page 107: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/107.jpg)
Alternate extinguishing methods cannot replace sprinkling, but can only be provided in addition to
a sprinkling.
Alternate methods are not as reliable as sprinkling. This also align with local practices.
![Page 108: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/108.jpg)
903.2 Where Required
Sprinkler Exclusions
![Page 109: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/109.jpg)
Elevator machine rooms, hoist ways, and elevator pits shall not be sprinkled.
Shunt trips are not allowed.
![Page 110: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/110.jpg)
Storage must not be allowed within an elevator machine room, and signage must be posted on
the entry door stating that storage is not allowed in the machine room.
![Page 111: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/111.jpg)
Telecommunication rooms are not excluded from automatic fire suppression.
![Page 112: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/112.jpg)
903.2.9.3 Self-Storage Facility
New Section
![Page 113: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/113.jpg)
All self-service storage facilities shall be sprinkled.
![Page 114: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/114.jpg)
903..3.1.1.1 Exempt Locationsfor NFPA 13 Sprinkler Systems
Added Language
![Page 115: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/115.jpg)
When approved by the fire code official, certain spaces may be excluded…
![Page 116: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/116.jpg)
903.3.1.2.3 Attics & Attached Garages
New Section
![Page 117: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/117.jpg)
Sprinkler protection is required in attics of buildings over one-story and in all car garages
attached to a building.
![Page 118: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/118.jpg)
903.3.1.3 NFPA 13D
Modification
![Page 119: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/119.jpg)
Adds that a 13D system may be installed in residential occupancies or in accordance with
state law.
This allows the plumbing section of the IRC to be used in lieu of the 13D system in the IBC.
![Page 120: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/120.jpg)
903.3.1.4 Freeze Protection
New Section
![Page 121: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/121.jpg)
Requires freeze protection in vented attics with dry or anti-freeze systems.
Only allows heat trace & insulation in specific circumstances approved
by the building official.
![Page 122: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/122.jpg)
903.3.5 Water Supplies
Added text.
![Page 123: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/123.jpg)
Water-based fire protection systems must be designed with a 10 psi safety factor.
![Page 124: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/124.jpg)
903.4 Sprinkler SystemSupervision & Alarms
Added text.
![Page 125: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/125.jpg)
Additional water-flow detectors shall be installed which will detect water flow to prevent significant
water loss.
![Page 126: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/126.jpg)
903.4.2 Alarms
Added text.
![Page 127: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/127.jpg)
An alarm device is required on the exterior of the building with a waterproof
horn & strobe, and must be located as closely as practical to each fire department
connection (FDC).
![Page 128: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/128.jpg)
905.2 Standpipe Installation
Added text.
![Page 129: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/129.jpg)
Dry standpipes must have a minimum 10psi, maximum 40 psi
air pressure high/low alarm.
![Page 130: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/130.jpg)
905.3.9 Buildings Exceeding 10,000 SF
New Section
![Page 131: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/131.jpg)
Class I wet standpipes shall be provided in buildings with more than 10,000 SF per story or
200 feet of travel distance to the nearest point of fire department access.
![Page 132: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/132.jpg)
905.4 Location of Hose Connections
Added requirements.
![Page 133: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/133.jpg)
All standpipes to roofs with a slope less than 4:12 shall be provided with
a two-way hose connection.
![Page 134: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/134.jpg)
Standpipe connections shall be placed at all required exits and at 200-foot
intervals along major corridors or as approved by the code official.
![Page 135: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/135.jpg)
905.9 Valve Supervision
Added requirements.
![Page 136: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/136.jpg)
Reinforces previous amendment:
Additional water-flow detectors shall be installed which will detect water flow to prevent significant
water loss.
![Page 137: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/137.jpg)
907.1.4 Design Standardsfor Fire Alarms
New Section
![Page 138: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/138.jpg)
All new fire alarms shall be addressable.
Alarms systems with more than 20 smoke detectors shall have
“analog initiating devices”.
![Page 139: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/139.jpg)
Addressable Device
A component of a fire alarm system that has a specific identification and location.
These devices allow the user to check the individual status of a device and control many
other functions.
![Page 140: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/140.jpg)
Analog Initiating Device
Indicates different degrees of conditions, as compared to a conventional device
that only indicates a on or off condition.
![Page 141: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/141.jpg)
907.2.1 Group A
Modification
![Page 142: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/142.jpg)
Adds the requirement of a manual fire alarm when there are more than 100 occupants above
or below the the level of exit discharge.
![Page 143: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/143.jpg)
Activation of the fire alarm shall illuminate the means of egress and stop other conflicting sounds
or visual distractions.
![Page 144: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/144.jpg)
907.2.3 Group E
Modification
![Page 145: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/145.jpg)
All day care facilities shall be equipped with a smoke detection system.
![Page 146: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/146.jpg)
907.2.13 High-Rise Buildings
Modification
![Page 147: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/147.jpg)
The exception for stadiums is amended to align with the previous amendment.
Only open-air portions of a high-rise stadium do not require smoke detection.
![Page 148: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/148.jpg)
907.4.2.7 Fire Alarm Box Type
New Section
![Page 149: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/149.jpg)
Manual alarms shall be double-action.
![Page 150: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/150.jpg)
907.6.1.1 Wiring Installation
New Section
![Page 151: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/151.jpg)
Alarm systems shall be designed so that the failure of one device
does not affect the other devices.
![Page 152: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/152.jpg)
907.6.3 Initiating Device ID
Exceptions Removed
![Page 153: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/153.jpg)
The fire alarms system shall identify each specific device, as well as
its location and status.
![Page 154: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/154.jpg)
909.22 Pressurization Alternative
New Section
![Page 155: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/155.jpg)
Enforces language from the Fire Code for the pressurization of egress stairs and ramps and
proper ventilation.
![Page 156: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/156.jpg)
910.2 Smoke & Heat Removal
Modification
![Page 157: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/157.jpg)
Automatic smoke & heat removal is prohibited from areas with an (ESFR) Early Suppression Fast
Response sprinkler system.
Only manual systems can be required.
![Page 158: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/158.jpg)
910.2.3 Group H
New Section
![Page 159: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/159.jpg)
H-2 & H-3 buildings of more than 15,000 SF will require smoke & heat removal,
unless the building and its contents are non-combustible.
![Page 160: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/160.jpg)
This allows for specific instances where it is best for a chemical to burn out
rather than to be extinguished.
![Page 161: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/161.jpg)
910.3.4 Vent Operation
New Section
![Page 162: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/162.jpg)
Smoke & heat vents shall be capable of activating both automatically and manually, controlled by
the fire alarm system or by a heat sensor.
![Page 163: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/163.jpg)
910.4.3.1 Make-Up Air
Modification
![Page 164: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/164.jpg)
Make-up air openings for smoke & heat removal shall be automatic.
This decreases the time for first responders to begin fighting a fire and saving lives.
![Page 165: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/165.jpg)
910.4.4 Activation
Modification
![Page 166: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/166.jpg)
The mechanical smoke removal system shall be activated by manual controls only automatically
by the automatic sprinkler system…
only early response systems will be manual.
![Page 167: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/167.jpg)
912.2.3 Hydrant Distance
New Section
![Page 168: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/168.jpg)
Hydrants must not be farther than 100’ from the FDC as the hose lays on the ground.
![Page 169: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/169.jpg)
913.2.1 Fire Pump Room Protection
Modification
![Page 170: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/170.jpg)
When located on the ground floor at an exterior wall, pump rooms shall have a man door for fire
department access, regardless of any interior access doors.
A knox-box is also required at this exterior door.
![Page 171: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/171.jpg)
Chapter 10
![Page 172: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/172.jpg)
1006.2.2.6 Electrical Rooms
Clarification
![Page 173: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/173.jpg)
Instructs the reader to refer to the Electrical Code for exit door requirements.
![Page 174: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/174.jpg)
1009.1 Required Accessible Egress
New Exception
![Page 175: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/175.jpg)
Buildings regulated under State Law and in conformance with State Law are exempt from the
IBC for accessible egress requirements.
![Page 176: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/176.jpg)
1010.1.9.4 Bolt Locks
Modification
![Page 177: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/177.jpg)
Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, S, or M occupancy, the inactive leaf may receive bolt
locks.
![Page 178: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/178.jpg)
Where a pair of doors serves a Group B, F, S, A or M occupancy, the inactive leaf may receive bolt
locks.
As long as it is not needed to meet egress requirements, the building is sprinkled, and the the leaf is free from latches or panic hardware.
![Page 179: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/179.jpg)
Question
For funzies…
![Page 180: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/180.jpg)
If the code explicitly allows something…it is allowed.
![Page 181: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/181.jpg)
If the code explicitly prohibits something…it is not allowed.
![Page 182: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/182.jpg)
What if it’s not explicit ?
![Page 183: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/183.jpg)
1015.8 Window OpeningsR2 & R3 Occupancies
Red Pill / Blue Pill
![Page 184: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/184.jpg)
Option AUnchanged: IF a window sill is
less than 36” AFF and 6’ above the ground, it must have fall protection.
![Page 185: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/185.jpg)
Option BOperable windows where the sill is
55’ or more above the ground, fall protection is required.
![Page 186: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/186.jpg)
1020.1 Construction
New Exception
![Page 187: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/187.jpg)
Corridor walls in a single-tenant office building are not required to be rated as long as the space is
sprinkled, has a fire alarm, and has smoke detectors tied to that
fire alarm.
This aligns with previous City of Dallas amendments.
![Page 188: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/188.jpg)
1029.1.1.1
Section Removed
![Page 189: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/189.jpg)
Grandstands and bleachers shall be separated (1HR) from spaces below, unless that space is a
ticket booth or restroom.
![Page 190: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/190.jpg)
Reason: Unenforceable.
![Page 191: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/191.jpg)
Chapter 11
![Page 192: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/192.jpg)
1101.1 Scope
New Exception
![Page 193: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/193.jpg)
This is the only time that I am giving you the codeword for word.
![Page 194: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/194.jpg)
ExceptionComponents of projects regulated by and registered with
Architectural Barriers Division of Texas Department of Licensing and Regulation shall be deemed to be in compliance
with the requirements of this chapter.
![Page 195: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/195.jpg)
If TDLR covers it…
and there is an EAB number on the drawings…
You can ignore Chapter 11.
![Page 196: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/196.jpg)
TDLR does not cover “apartment units”.
Those are considered private.
![Page 197: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/197.jpg)
Apartments & condos must still comply with Chapter 11.
![Page 198: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/198.jpg)
Apartments & condos must still comply with Chapter 11.
Right ?
![Page 199: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/199.jpg)
Chapter 12
![Page 200: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/200.jpg)
1203.1 General. Ventilation
Modification
![Page 201: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/201.jpg)
Unamended: Buildings must be vented if the air change per hour is less than 5 changes.
Amended: Buildings must be vented if the air change per hour is 5 changes or less.
![Page 202: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/202.jpg)
Chapter 15
![Page 203: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/203.jpg)
1505.1 Minimum Roof Classification
Modification
![Page 204: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/204.jpg)
The exception for R-3 & U occupancies to have unclassified materials is revised to exclude R-3.
Only Group U of less than 120 SF is excluded for unclassified combustible materials. Larger than that, must have non-combustible materials if they are to remain unclassified.
![Page 205: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/205.jpg)
Deletes an exception for cedar and redwood shakes. These shall not be used for any commercial roof.
![Page 206: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/206.jpg)
1505.7 Special Purpose Roofs
Removed
![Page 207: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/207.jpg)
Special Purpose Roof = Wood Shingle / Shake Roof
![Page 208: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/208.jpg)
Like we just said…you can’t do it.
![Page 209: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/209.jpg)
NO wooden roofs.
![Page 210: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/210.jpg)
1510.1 General. Roof Structures
Clarified
![Page 211: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/211.jpg)
Replacement Shingles or Shakes shall be in compliance with 1505.1.
![Page 212: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/212.jpg)
Meaning: You can’t use them unless it is a tiny carport.
![Page 213: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/213.jpg)
Like mini-cooper tiny…
![Page 214: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/214.jpg)
9 x 18 = 162
![Page 215: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/215.jpg)
9 x 18 = 162
162 > 120
![Page 216: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/216.jpg)
![Page 217: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/217.jpg)
No wooden shakes.
![Page 218: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/218.jpg)
Chapter 17
![Page 219: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/219.jpg)
1704.2 Special Inspections
Modified
![Page 220: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/220.jpg)
Special Inspections must be obtained by the Registered Design Profession in Responsible Charge,
the owner, or the owner’s agent.
![Page 221: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/221.jpg)
The special inspector must NOT be employed by the contractor.
![Page 222: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/222.jpg)
Chapter 29
![Page 223: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/223.jpg)
2901.1 Scope. Plumbing
Clarified
![Page 224: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/224.jpg)
IF this chapter conflicts with any part of Chapter 4 in the Plumbing Code, the Building Official chooses.
![Page 225: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/225.jpg)
2902.1 Minimum # of Fixtures
Clarified
![Page 226: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/226.jpg)
Except for Group E, the number of fixtures may be reduced for special occupancy needs.
Submit reasons in writing to the Building Official for approval.
![Page 227: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/227.jpg)
2902.1 Footnote ‘f’
Added note
![Page 228: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/228.jpg)
Drinking fountains are not required for Group M with 100 people or less; Group B with 25 people or less; or
any dining & drinking establishments.
![Page 229: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/229.jpg)
2902.1.3 Additional Fixtures
New Section
![Page 230: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/230.jpg)
Hand washing sinks and service sinks shall be provided at all food preparation areas.
![Page 231: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/231.jpg)
Chapter 30
![Page 232: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/232.jpg)
3002.1 Hoistway Enclosure Protection
Clarification
![Page 233: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/233.jpg)
Elevator enclosures within atriums are not required to be rated.
![Page 234: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/234.jpg)
Elevator enclosures within parking garages are not required to be rated if they ONLY serve the
parking garage structure.
![Page 235: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/235.jpg)
3005.4 Machine Rooms
Clarification
![Page 236: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/236.jpg)
Reworded to allow for remote closets where the cables from the closet to the hoist way
are not required to be rated.
![Page 237: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/237.jpg)
3005.7 Fire Protection in Machine Rooms
Modification
![Page 238: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/238.jpg)
Prohibits any fire suppression system that would require a shunt trip.
Shunt trips are not allowed.
![Page 239: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/239.jpg)
3005.8 No Storage Sign
New Section
![Page 240: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/240.jpg)
Reinforces that a machine room requires signage stating that storage is not allowed within the
elevator machine room.
![Page 241: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/241.jpg)
![Page 242: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/242.jpg)
3006.2 Hoistway Opening Protection
Options
![Page 243: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/243.jpg)
Option A: Rated doors are required if the hoist way is more than 75 feet in height measured from
the ground level to the top floor.
Option B: …55 feet…
![Page 244: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/244.jpg)
Chapter 31
![Page 245: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/245.jpg)
Ready for the LAST one!!
![Page 246: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/246.jpg)
3109.1 General. Pools & Spas
Clarification
![Page 247: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/247.jpg)
Swimming pools shall comply with the requirements of this code as well as applicable
state laws.
![Page 248: NCTCOG - AIA Dallas...Buildings which provide services on a ... 403.1 High-Rise Buildings Clarification to an exemption. ... exempt from the high-rise requirements. 403.3 Automatic](https://reader033.vdocument.in/reader033/viewer/2022053017/5f1c7250bd64a669d1093c29/html5/thumbnails/248.jpg)
NCTCOGNorth Central Texas Council of Government
(COG)
The preceding information was taken from the NCTCOG website:North Central Texas Council of Governments | 616 Six Flags Drive P.O. Box 5888 Arlington, TX
76005-5888 Main Operator: (817) 640-3300 | Fax: (817) 640-7806