Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected systems, network matrices have to be formed to analyze them. I There are two matrices. 1. bus admittance matrix Y bus . 2. bus impedance matrix Z bus . I Y bus is mainly used in load flow studies. Whereas Z bus is mainly used in short circuit studies. I These two matrices are related by Z bus = Y -1 bus

Upload: others

Post on 18-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Network Matrices

I Per unit impedance and reactance diagrams are required toanalyze power systems.

I For interconnected systems, network matrices have to beformed to analyze them.

I There are two matrices.

1. bus admittance matrix Ybus .2. bus impedance matrix Zbus .

I Ybus is mainly used in load flow studies. Whereas Zbus ismainly used in short circuit studies.

I These two matrices are related by

Zbus = Y−1bus

Page 2: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Bus Admittance Matrix (Ybus ) :

−+

V

Z

I Y

Figure: Thevenin - Norton Equivalent

I =V

ZY =

1

Z

Page 3: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Let us consider a four bus system.

G1

1 O

4 O3 O

2 O

G2

Page 4: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

It is assumed that the short line model is used.

−+EG1

z10

1O3O 2O

4O

z14

z13

z34

z32

z24

−+EG2

z20

0O

Page 5: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By using Thevenin - Norton equivalent and converting allimpedances to admittances,

I1 y10

1O3O 2O

4O

y14

y13

y34

y32

y24

I1 y20

0O

Page 6: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By applying KCL at node 1O,

I1 = y10V1 + y13(V1 − V3) + y14(V1 − V4)

I1 = (y10 + y13 + y14)V1 − y13V3 − y14V4

At node 2O,

I2 = y20V2 + y23(V2 − V3) + y24(V2 − V4)

I2 = (y20 + y23 + y24)V2 − y23V3 − y24V4

At node 3O,

0 = y13(V3 − V1) + y34(V3 − V4) + y32(V3 − V2)

0 = −y13V1 − y32V2 + (y13 + y32 + y34)V3 − y34V4

At node 4O,

0 = y14(V4 − V1) + y24(V4 − V2) + y34(V4 − V3)

0 = −y14V1 − y24V2 − y34V3 + (y14 + y24 + y34)V4

Page 7: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By arranging the equations in a Matrix form,[I1I200

]=

[(y10 + y13 + y14) 0 −y13 −y14

0 (y20 + y23 + y24) −y23 −y24−y13 −y32 (y13 + y32 + y34) −y34−y14 −y24 −y34 (y14 + y24 + y34)

] [V1V2V3V4

]In general, for a 4 node (bus) system

I1I2I3I4

=

Y11 Y12 Y13 Y14

Y21 Y22 Y23 Y24

Y31 Y32 Y33 Y34

Y41 Y42 Y43 Y44

V1

V2

V3

V4

where

Y11 = (y10 + y13 + y14)

Y12 = Y21 = 0 Y22 = (y20 + y23 + y24)

Y13 = Y31 = −y13 Y23 = Y32 = −y32 Y33 = (y13 + y32 + y34)

Y14 = Y41 = −y14 Y24 = Y42 = −y24 Y34 = Y43 = −y34 Y44 = (y14 + y24 + y34)

Page 8: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Inclusion of Line Charging CapacitorsTransmission lines are modeled using π model.

I1 y10

1O3O 2O

4O

y14

YC142 y13

YC132

y34YC34

2y32

YC322

y24

YC242

I1 y20

0O

Page 9: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By applying KCL at all the nodes and arranging the equations in aMatrix form,

I1I2I3I4

=

Y11 Y12 Y13 Y14

Y21 Y22 Y23 Y24

Y31 Y32 Y33 Y34

Y41 Y42 Y43 Y44

V1

V2

V3

V4

where

Y11 = (y10 + y13 + y14) + (YC13

2+

YC14

2)

Y12 = Y21 = 0 Y22 = (y20 + y23 + y24) + (YC32

2+

YC24

2)

Y13 = Y31 = −y13 Y23 = Y32 = −y32

Y14 = Y41 = −y14 Y24 = Y42 = −y24

Y33 = (y13 + y32 + y34) + (YC32

2+

YC13

2+

YC34

2)

Y34 = Y43 = −y34 Y44 = (y14 + y24 + y34) + (YC14

2+

YC24

2+

YC34

2)

Page 10: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

For an n bus system,

Ibus = YbusVbus

whereIbus is a vector of injected currents in to the network (n × 1).Ybus is a bus admittance matrix (n × n).Vbus is a vector of bus voltages (n × 1).

I Ybus is symmetrical. (It will be unsymmetrical when a phaseshifting transformer is used in a system.)

I Ybus can be formed by inspection.

I Ybus is generally sparse (many zeroes).

Two simple rules to form Ybus by inspection:

1. Diagonal Elements:Yii = sum of the admittances directly connected to node iO.

2. Off-diagonal elements:Yij = Yji = negative of the net admittance connectedbetween nodes iO and jO.

Page 11: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Example 1: Consider the reactance network.

−+1∠0◦

1

0.5

1

−+

1∠30◦

0.25 0.25

1 2

3

1. Form Ybus matrix.

2. Find the voltages at each bus.

Page 12: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By Thevenin - Norton transformation,

1 −90◦ 1

0.5

11∠−60◦

0.25 0.25

1 2

3

Page 13: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

1.

Ybus =

(

1

1+

1

0.25+

1

0.5) − 1

0.5− 1

0.25

− 1

0.5(

1

1+

1

0.25+

1

0.5) − 1

0.25

− 1

0.25− 1

0.25(

1

0.25+

1

0.25)

Ybus =

−7 2 42 −7 44 4 −8

Page 14: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

2.

YbusVbus = Ibus−7 2 42 −7 44 4 −8

V1

V2

V3

=

1 −90◦

1∠−60◦

0

By solving this, V1

V2

V3

=

0.9663 13.3◦

0.9664 16.7◦

0.966 15◦

If the size of the matrix is more than 3, we need to use GaussianElimination to solve it.

Page 15: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Node Elimination - Kron ReductionLet us consider a three node network.Y11 Y12 Y13

Y21 Y22 Y23

Y31 Y32 Y33

V1

V2

V3

=

I1I2I3

Suppose there is no injection at node 3O. I3 = 0.Y11 Y12 Y13

Y21 Y22 Y23

Y31 Y32 Y33

V1

V2

V3

=

I1I20

Since there is no injection (neither generation nor load) at 3O, thiscan be eliminated.

Y11V1 + Y12V2 + Y13V3 = I1

Y21V1 + Y22V2 + Y23V3 = I2

Y31V1 + Y32V2 + Y33V3 = 0

Page 16: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

From the last equation,

V3 = − 1

Y33(Y31V1 + Y32V2)

Substituting V3 in the first two equations, we get

(Y11 −Y13Y31

Y33)V1 + (Y12 −

Y13Y32

Y33)V2 = I1

(Y21 −Y23Y31

Y33)V1 + (Y22 −

Y23Y32

Y33)V2 = I2

Arranging the above equations in a matrix form,(Y11 −Y13Y31

Y33) (Y12 −

Y13Y32

Y33)

(Y21 −Y23Y31

Y33) (Y22 −

Y23Y32

Y33)

[V1

V2

]=

[I1I2

]

Page 17: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

The new Ybus is

Ybus(new) =

(Y11 −Y13Y31

Y33) (Y12 −

Y13Y32

Y33)

(Y21 −Y23Y31

Y33) (Y22 −

Y23Y32

Y33)

The size is now reduced by 1.Let us generalize the above procedure. Suppose the node kO is tobe eliminated from n nodes.

Yij(new) = Yij −YikYkj

Ykki , j = 1, 2 · · · n i , j 6= k

The size of the new Ybus matrix is (n − 1)× (n − 1).

Page 18: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Example 2 : Let us consider the example 1.

Ybus =

−7 2 42 −7 44 4 −8

Let us eliminate the node 3O.

Y11(new) = Y11 −Y13Y31

Y33= −7− −16

−8= −5

Y12(new) = 2− −16

−8= 4

Y21(new) = Y12(new) = 4

Y22(new) = −7− −16

−8= −5

Ybus(new) =

[−5 44 −5

]

Page 19: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Triangular Factorization

I In practical applications, the nodal admittance equations aresolved for wide range of operating conditions.

I In most of these studies, the network parameters and theconfiguration remain the same. There will be changes only inthe injections.

I In this situation, Ybus remains fixed.

I This makes us think of factorizing Ybus into two triangularmatrices. This reduces the time required in solving theequations considerably.

I = YV = LUV

where

Y = LU

L and U are the lower triangular and upper triangular matrix.

Page 20: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Once the triangular factorization is done, V is found as follows:

I = LV′

V′ = UV

I Since L and U are triangular matrices, it is easy to solve theabove equations.

I Solve for V′ from the first set of equations.

I Then solve for V from the second set of equations.

Page 21: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

ConsiderAx = b

A can be written asA = LU

To find triangular factors, apply row eliminations techniques on A.Example:

A =

2 1 31 5 43 4 7

2 1 3

1 5 43 4 7

I R2 = R2 − 1

2 × R1 2 1 30 9

252

3 4 7

Page 22: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

I R3 = R3 − 32 × R1 2 1 3

0 92

52

0 52

52

I R3 = R3 − 5

9 × R2 2 1 30 9

252

0 0 109

U =

2 1 30 9

252

0 0 109

Page 23: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

I L is a unit lower triangular matrix.

I It can be formed by recording the multipliers used in theelementary row operations. The multiplier lij is the numberthat multiplies the pivot row i when it is subtracted from therow j and produces a zero in the i , j position.

L =

1 0 012 1 032

59 1

L and U are called triangular factors and unique for a given A.

Page 24: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

A can be written as

A = LU

where L =

1 0 0l21 1 0l31 l32 0

and U =

u11 u12 u13

0 u22 u23

0 0 u33

.

If A is symmetric,

A = AT

U can be written as follows:

U =

u11 0 00 u22 00 0 u33

︸ ︷︷ ︸

D

1 u12u11

u13u11

0 1 u23u22

0 0 1

︸ ︷︷ ︸

LT

where D is a diagonal matrix and contains the diagonal elements ofU.

Page 25: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Therefore,

A = LDLT

Let us use the same example:

A =

2 1 31 5 43 4 7

A =

1 0 012 1 032

59 1

︸ ︷︷ ︸

L

2 1 30 9

252

0 0 109

︸ ︷︷ ︸

U

=

1 0 012 1 032

59 1

︸ ︷︷ ︸

L

2 0 00 9

2 00 0 10

9

︸ ︷︷ ︸

D

1 12

32

0 1 59

0 0 1

︸ ︷︷ ︸

LT

I When a matrix is symmetric, L can be formed from U.

I Ybus is almost always symmetric.

Page 26: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Bus Impedance Matrix Zbus :

Zbus = Y−1bus

I If Ybus is symmetric, Zbus must also be symmetric.

I Unlike Ybus , Zbus is a full matrix.

I Zbus is used in fault calculations.

For a network of 3 nodes,

Zbus =

Z11 Z12 Z13

Z21 Z22 Z23

Z31 Z32 Z33

I The diagonal elements are called the driving point impedances

of the buses.

I The off-diagonal elements are called the transfer impedancesof the buses.

Page 27: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Let us compare the elements of Zbus with Ybus .I1I2I3

=

Y11 Y12 Y13

Y21 Y22 Y23

Y31 Y32 Y33

V1

V2

V3

I1 −+ V2

I2

I3

1 2

3

Page 28: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

The self admittance Y22 can be found as follows:

Y22 =I2V2

∣∣∣∣V1=V3=0

The mutual admittance Y12 can be found as follows:

Y12 =I1V2

∣∣∣∣V1=V3=0

Page 29: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Let us find the elements of Zbus .V1

V2

V3

=

Z11 Z12 Z13

Z21 Z22 Z23

Z31 Z32 Z33

I1I2I3

+

V1

+

V2I2

I2

+

V3

1 2

3

Page 30: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

The driving point impedance Z22 is determined as follows:

Z22 =V2

I2

∣∣∣∣I1=I3=0

Z22 6=1

Y22

The transfer impedance Z12 is found as follows:

Z12 =V1

I2

∣∣∣∣I1=I3=0

Z12 6=1

Y12

I Z22 is the Thevenin Impedance at node 2O.

I Similarly, all the diagonal elements of Zbus are the Theveninimpedance at the respective buses.

Page 31: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Modification of an Existing Zbus :

I An existing Zbus is modified whenever a new bus or line isadded to the network.

I If we know how to modify an existing Zbus , we can build itdirectly.

There are normally four cases

1. Adding a new bus to the reference bus through an impedance

2. Adding a new bus to an existing bus through an impedance

3. Adding an impedance between an existing bus and thereference bus

4. Adding an impedance between two existing buses

Let us assume that there are n buses in the existing network.V1...Vn

=

Z11 · · · Z1n...

. . ....

Zn1 · · · Znn

I1...In

Page 32: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

1. Adding a new bus to the reference bus through an impedance

0O

pO

Zb

Ip

Original Network

A new bus p is added to the network through an impedanceZb.

V1...Vn

Vp

=

Z11 · · · Z1n 0

.... . .

......

Zn1 · · · Znn 00 · · · 0 Zb

︸ ︷︷ ︸

Zbus(new)

I1...InIp

Page 33: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

2. Adding a new bus to an existing bus through an impedance.

0O

kOIk Ik + Ip

pO

Zb Ip

Original Network

A new bus p is added to an existing bus k through animpedance Zb.Since Ip is flowing into the network, the voltage at all thenode will increase.The voltage at the node kO will be

Vk =Zk1I1 + · · ·+ Zkk(Ik + Ip) + · · ·+ ZknIn

=Zk1I1 + · · ·+ Zkk Ik + · · ·+ ZknIn + Zkk Ip

Page 34: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

The voltage at the node pO will be

Vp = Vk +IpZb = Zk1I1+· · ·+Zkk Ik +· · ·+ZknIn+(Zkk +Zb)Ip

V1...Vn

Vp

=

Z11 · · · Z1n Z1k

.... . .

......

Zn1 · · · Znn Znk

Zk1 · · · Zkn Zkk + Zb

︸ ︷︷ ︸

Zbus(new)

I1...InIp

3. Adding an impedance between an existing bus and thereference busI Add a new bus p temporarily to an existing bus k through an

impedance Zb.I The modified Zbus will be (n + 1)× (n + 1).I Short-circuit the node p to the reference bus by letting Vp

equal to zero.I Eliminate the node p using the Kron-reduction.

Page 35: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

4. Adding an impedance between two existing buses

0O

kOIk Ik − Ib

jO

Ij

Ij + Ib

Zb

Ib

Original Network

The voltage of the bus 1O will be

V1 = Z11I1 + · · ·+ Z1j(Ij + Ib) + Z1k(Ik − Ib) + · · ·+ Z1nIn

= Z11I1 + · · ·+ Z1j Ij + Z1k Ik + · · ·+ Z1nIn + (Z1j − Z1k)Ib

Similarly, at buses jO and kO

Vj = Zj1I1 + · · ·+ Zjj Ij + Zjk Ik + · · ·+ ZjnIn + (Zjj − Zjk)Ib

Page 36: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Vk = Zk1I1 + · · ·+ Zkj Ij + Zkk Ik + · · ·+ ZknIn + (Zkj − Zkk)Ib

Since Ib is unknown,

Vk − Vj = IbZb

0 = (Zj1−Zk1)I1+· · ·+(Zjj−Zkj)Ij+(Zjk−Zkk)Ik+· · ·+(Zjn−Zkn)In

+ (Zjj + Zkk − 2Zjk + Zb)Ib

V1

...Vn

0

=

Z11 · · · Z1n (Z1j − Z1k )...

. . ....

...Zn1 · · · Znn (Znj − Znk )

(Zj1 − Zk1) · · · (Zjn − Zjk ) Zbb

I1

...InIb

where Zbb = Zjj + Zkk − 2Zjk + Zb = Zth, jk + Zb.I Eliminate the last row and last column using the

Kron-reduction.

Page 37: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Example 3:

1

0.5

1

0O

0.25 0.25

1 2

3

Page 38: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

1. Let us add 1 from the reference bus to the bus 1O.

1

1O

0O

Zbus =

[0 00 1

]=[1]

Page 39: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

2. Let us add 1 from the reference bus to the bus 2O.

1

1O

0O

2O

1

Zbus =

[1 00 1

]

Page 40: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

3. Let us add 0.5 between 1O and 2O.

1

1O

0O

2O

1

0.5

Ztempbus =

1 0 10 1 −11 −1 2.5

On eliminating the last row and last columns using theKron-reduction,

Zbus =

1−1× 12.5

0− 1×−12.5

0− 1×−12.5

1− −1×−12.5

=

[0.6 0.40.4 0.6

]

Page 41: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

4. Let us add 0.25 between 1O and a new bus 3O.

1

1O

0O

2O

13O

0.5

0.25

Zbus =

0.6 0.4 0.60.4 0.6 0.40.6 0.4 0.85

Page 42: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

5. Let us add 0.25 between 2O and 3O.

1

1O

0O

2O

13O

0.5

0.25 0.25

Ztempbus =

0.6 0.4 0.6 −0.20.4 0.6 0.4 0.20.6 0.4 0.85 −0.45−0.2 0.2 −0.45 0.9

Page 43: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

On eliminating the last row and last column using theKron-reduction,

Zbus =

0.6−

−0.2×−0.20.9

0.4−−0.2× 0.2

0.90.6−

−0.2×−0.45

0.9

0.4−−0.2× 0.2

0.90.6−

0.2× 0.2

0.90.4−

−0.2×−0.45

0.9

0.6−−0.2×−0.45

0.90.4−

0.2×−0.45

0.90.85−

−0.45×−0.45

0.9

Zbus =

0.5556 0.4444 0.50.4444 0.5556 0.50.5 0.5 0.6250

This can also be formed by inverting Ybus matrix of thenetwork.

Ybus =

−7 2 42 −7 44 4 −8

Zbus = Y−1

bus

Page 44: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Calculation of Zbus elements from Ybus : If all the elements of Zbusare not needed, the required elements can be calculated from Ybus .

YbusZbus = I

YbusZ(m)bus =

0...

1m...0

where Z

(m)bus is the mth column of Zbus . If the triangular factors are

available,

LUZ(m)bus =

0...

1m...0

The elements in the column vector Z

(m)bus can be found by forward

elimination and back substitution.

Page 45: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Thevenin’s Theorem and Zbus :Let us consider an n node network.

V0 = Zbus I0

where V0 denotes the voltages of buses due to the bus currents I0.When the bus currents are changed from their initial values to newvalues (I0 + ∆I),

V = Zbus(I0 + ∆I) = Zbus I0︸ ︷︷ ︸V0

+ Zbus∆I︸ ︷︷ ︸∆V

Let us assume that there is change in the current injection only atbus kO.

∆V1...

∆Vk...

∆Vn

=

Z11 · · · Z1k · · · Z1n

.... . .

.... . .

...Zk1 · · · Zkk · · · Zkn

.... . .

.... . .

...Zn1 · · · Znk · · · Znn

0...

∆Ik...0

Page 46: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

0O

∆V33O

∆V22O

∆V11O

Original Network

nO ∆Vn

kO∆Vk

∆Ik

∆V1

...∆Vk

...∆Vn

=

Z1k

...Zkk

...Znk

∆Ik

Vk = V 0k + Zkk∆Ik

Page 47: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

0O

Original Network

kO

−+V 0

k

Zkk

∆Ik

The Thevenin impedance at bus kO is

Zth = Zkk

Page 48: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

In a similar manner, we can determine the Thevenin impedancebetween any two buses jO and kO of the network.Let us assume that there are current injections from jO and kO.

∆V1...

∆Vj

∆Vk...

∆Vn

=

Z11 · · · Z1j Z1k · · · Z1n...

. . ....

.... . .

...Zj1 · · · Zjj Zjk · · · Zjn

Zk1 · · · Zkj Zkk · · · Zkn...

. . ....

.... . .

...Zn1 · · · Znj Znk · · · Znn

0...

∆Ij∆Ik

...0

The bus voltages at jO and kO are

Vj = V 0j + ∆Vj = V 0

j + Zjj∆Ij + Zjk∆Ik

Vk = V 0k + ∆Vk = V 0

k + Zkj∆Ij + Zkk∆Ik

Page 49: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

By adding and subtracting Zjk∆Ij in the first equation and Zkj∆Ikin the second equation,

Vj = V 0j + (Zjj − Zjk)∆Ij + Zjk(∆Ij + ∆Ik)

Vk = V 0k + Zkj(∆Ij + ∆Ik) + (Zkk − Zkj)∆Ik

The above equations can be represented as follows:

Page 50: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Zth,jk =V 0k − V 0

j

Isc

Since Isc = ∆Ij = −∆Ik and Vj − Vk = 0,

0 = V 0j − V 0

k + (Zjj − Zjk)Isc − (Zkk − Zkj)(−Isc)

V 0k − V 0

j = (Zjj + Zkk − 2Zkj)Isc

Zth,jk = Zjj + Zkk − 2Zkj

The branch current Ib is given by

Ib =Vk − Vj

Zb=

V 0k − V 0

j

Zth,jk + Zb

Page 51: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Example 4: Consider the reactance network.

−+1∠0◦

1

0.5

1

−+

1∠30◦

0.25 0.25

1 2

3

1. Find the voltages at each bus.

2. Find the voltage at each bus after connecting a capacitorhaving a reactance of 5 p.u. between 3O and 0O.

Page 52: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

1.V0bus = Zbus I0busV 0

1

V 02

V 03

=

0.5556 0.4444 0.50.4444 0.5556 0.50.5 0.5 0.6250

1 −90◦

1 −60◦

0

V 0

1

V 02

V 03

=

0.9663 13.3◦

0.9664 16.7◦

0.966 15◦

2. To find change in voltage at each bus due to a capacitor:

0O

Original Network

3O

−+V 0

3

Z33

−5Ic

Page 53: Network Matrices - iitp.ac.insiva/2020/ee381/Network_Matrices.pdf · Network Matrices I Per unit impedance and reactance diagrams are required to analyze power systems. I For interconnected

Ic =V 0

3

Z33 − Xc=

0.966 15◦

0.6250− 5= 0.22 105◦∆V1

∆V2

∆V3

Z11 Z12 Z13

Z21 Z22 Z23

Z31 Z32 Z33

00−Ic

∆V1

∆V2

∆V3

=

0.50.5

0.6250

(−0.22 105◦) =

0.11 15◦

0.11 15◦

0.1375 15◦

V1

V2

V3

=

V 01

V 02

V 03

+

∆V1

∆V2

∆V3

=

1.0765 13.5◦

1.0767 16.5◦

1.104 15◦

This example shows how adding a capacitor at a bus causes a risein bus voltages.