Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Title Page Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Florida Institute of Technology
F.W. Olin Physical Science Laboratory
The Effects and Benefits of Desiccant Technology on a
Laboratory Application
Amy E. Pastor
Mechanical Option
Senior Thesis – Spring 2005
The Pennsylvania State University
Department of Architectural Engineering
Amy E. Pastor Florida Institute of Technology Mechanical Option 150 W. University Blvd. Melbourne, FL
F.W. Olin Physical Science Laboratory
Project Team Owner: Florida Institute of Technology
Architect: Schwab, Twitty & Hansen Architectural Group Contractor: The Weitz Company, Inc.
Structural Engineers: O’Donnell, Naccarato, Mignogna & Jackson, Inc. MEP Engineers: Tilden, Lobnitz Cooper Engineering for Architecture
Civil/Surveyor Engineers: Baskerville Donovan, Inc.
Architectural Features 3 floors of laboratory and classroom space Observatory Level with pre-engineered domed telescope Total Square Footage: 80000 sq. ft Total Cost: $14 Million
Structural Cast-in place concrete structure One-way concrete slab CMU exterior walls with cement plaster Brick Veneer
Mechanical Equipment in Chiller Building includes: (2) - 1200 GPM, roof-mounted Marley cooling towers (2) - 400 ton, water-cooled chillers (2) Primary chilled water pumps (2) Secondary chilled water pumps (2) Condenser water pumps (1) Gas-fired, hot water boiler at 4500 MBH (2) Hot water pumps (2) Secondary hot water pumps Equipment in Main Laboratory Building includes: (8) Modular Climate Changers (MCC) Air Handling Units manufactured by Trane Total CFM: 97885 CFM Outdoor Air CFM: 67545 CFM
Construction Design-Build Predicted Completion Date: Fall 2004
Electrical Primary: 675 kW, 2500 A, 277/480V, 3Φ, 4W Step-down Transformers: 480∆-120/208Y Emergency System: 400 kW Diesel Generator
www.arche.psu.edu/thesis/2005/aep132
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 2 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Table of Contents
1.0 Executive Summary__________________________________________________ 3
2.0 Introduction _______________________________________________________ 5
2.1 Outline of Booklet ________________________________________________________ 7
2.2 History of Olin Science Lab ________________________________________________ 9
2.3 Building Statistics _______________________________________________________ 10
3.0 Building Analysis___________________________________________________ 13
3.1 ASHRAE Standard 62 – 2004______________________________________________ 13
3.2 ASHRAE Standard 90.1 – Envelope Compliance _______________________________ 13
3.3 ASHRAE Standard 90.1 – Lighting Compliance _______________________________ 15
3.4 Conclusions of Building Analyses __________________________________________ 17
4.0 Mechanical Redesign _______________________________________________ 18
4.1 Introduction of Desiccant Wheels to All the Air Handling Units __________________ 19
4.2 Construction and Structural Issues _________________________________________ 23
4.3 Ductwork Layout and Changes ____________________________________________ 25
4.4 VOC Sensors and Cross Contamination______________________________________ 25
4.5 Conclusions of Mechanical Depth__________________________________________ 28
5.0 Breadth Work – Electrical Redesign____________________________________ 29
6.0 Breadth Work – Acoustics ___________________________________________ 31
7.0 Conclusions _______________________________________________________ 32
8.0 Acknowledgements _________________________________________________ 34
9.0 Appendices _______________________________________________________ 35
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 3 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
1.0 Executive Summary
The F.W. Olin Physical Science Laboratory in Melbourne, Florida is the building that I
chose to perform my senior thesis. Throughout the past year, I have researched and
redesigned the mechanical system of the building and touched upon the redesign and
compliance of the electrical and acoustical portions of the building with their respective
codes.
For my Mechanical Depth, I added eight SEMCO Energy Recovery Packaged Units to the
eight Modular Climate Changer (MCC) air handling units throughout the building.
This proved to have saved an estimated cost of $168,000.00 for the cooling of the
building, which equates to 416.97 tons per year.
Although many professionals do not agree with the installation of Desiccant Wheels in
laboratory applications, I have proven that with special attention to detail, cross
contamination from the exhaust stream poses no threat to the supply air in the
occupied spaces.
As for my breadth topics, I have proven that the addition of the Desiccant Wheel
packages to the electrical panels would allow for 4 of the 6 panel boards supplying
electricity to the air handling units to remain the same. The addition two would have to
be either sized up or made into a dual panel board because of the slight increase in
kVA. For the acoustical portion of my thesis, using the Trane Acoustics Program (TAP),
I have shown that the addition of the Desiccant Packages into the air handling units
would not affect the transmittance of noise through the walls to the classroom spaces to
the point of having to change the insulation levels or STC ratings of the walls.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 4 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Overall, I feel that I have a successfully completed thesis which proves that the
installation of Desiccant Wheels into the Florida Institute of Technology’s Olin Lab
would be beneficial both in energy and cost savings.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 5 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
2.0 Introduction
In compliance with the Pennsylvania State University Department of Architectural
Engineering in the College of Engineering, I have completed a one-year thesis on the
F.W. Olin Physical Science Laboratory in Melbourne, Florida. The following booklet
outlines and completely describes all the research, calculations, CAD drawings,
building models and conclusions that have been drawn and recreated from the past
year of work.
The Florida Institute of Technology is an institution with a strong emphasis on
engineering and the sciences. Along with the Olin Physical Science Laboratory, two
other building have been built in the name of F.W. Olin and funded by the F.W. Olin
Foundation. These two buildings are the F.W Olin Engineering Complex and the F.W.
Olin Life Sciences Building.
A $25 million grant was given to FIT for the completion of both the Physical Science
Laboratory and the Engineering Complex; however a majority of the fund ($14 million)
went to the design effort and construction of the Olin Science Laboratory. This 69,348
square foot facility houses 14 teaching and 21 research laboratories along with faculty
offices and classroom space. The building is also equipped with two large multi-
use/demonstration classrooms.
As a mechanical option, the depth of my thesis work included a redesign of the air
handling units with the addition of desiccant technology. Through initial research, my
hope was that the addition of these wheels would both lower the cooling load on the
cooling coil and lower the cost of energy used by the cooling system in the Olin
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 6 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Laboratory. Stemming from my depth work and related to the installation of new
mechanical equipment, I decided to complete an electrical analysis on the panels that
include the air handlers in the Olin Laboratory. My hope was that lowering the load on
the cooling coils would reduce the amount of electricity needed to run the machine.
Along with an electrical analysis, I performed an acoustical analysis on the mechanical
rooms located in the corners of the three floors of the Lab. With the addition of more
equipment, rechecking the transmittance of noise through the mechanical room walls
was important due to the fact that classrooms spaces could be found on the other side.
These two analyses were my two breadth areas of study.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 7 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
2.1 Outline of Booklet
My thesis booklet was designed to take you step by step in my redesign process of the
Olin Science Laboratory starting with my research on day one. In the Introduction part
of my booklet, I have given an overview of my depth and breadth topics and some
background history on the F.W. Olin Foundation. Following this section, I will continue
to give a brief history of the Olin Foundation and F.W. Olin himself. Upon conclusion
of that, I will include the research of the construction of the Lab with project players,
construction dates, materials used and so forth.
Section Three of my booklet begins the building analyses of the Olin Laboratory with
data proving its compliance with ASHRAE Standards 90.1 and 62-2004. Along with
the ASHRAE Standards, compliance checks with Florida Emissions Codes will also be
proven.
Section Four is my depth analysis of the Olin Science Lab with strict attention to the
addition of desiccant technology. Since Carrier’s Hourly Analysis Program (HAP) has
no way of modeling desiccant wheels in its program, I have put together a detailed
spreadsheet of the calculations as outlined by SEMCO. This allowed me to select the
desiccant wheel that would best suit the needs of each individual air handling unit.
Section Five begins my breadth areas of study, with its main focus on my electrical
redesign. After resizing my coils due to the lowering of the coil load, a redesign of the
amount of electricity needed to run the eight air handlers was completed. Following
the National Electric Code (NEC), full load ampacity (FLA), minimum current ampacity
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 8 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
(MCA) and maximum overcurrent protection (MCOP) was determined so that panel
board resizing could be an option.
Section Six is the second area of my thesis breadth, Acoustics. With the addition of a
new piece of equipment into the mechanical room, an acoustical problem may arise.
Furthermore, the mechanical room spaces are located next to classroom and office
spaces. For this reason, I have performed an acoustical analysis using the Trane
Acoustical Program (TAP). Included in this section will be my findings, along with a
reference to my printouts in the Appendix part of my report.
Finally, Sections Seven, Eight and Nine are my conclusions, acknowledgements and
appendices, respectively. In Section Seven, I have summarized and concluded all of my
findings and redesigns to the Olin Science Lab over the past year. In Section Nine, all of
the resources and calculations that were used and performed can be found.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 9 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
2.2 History of Olin Science Lab
In 1938, Franklin W. Olin established the F. W. Olin Foundation. A man of many
trades, his titles included engineer, entrepreneur, philanthropist and professional
basketball player. More than $300 million has been given to 57 independent colleges
to construct and fully equip 72 buildings on their campuses. This has all taken place in
the past 60 years. Although a dabbler in the sciences, most, but not all of the buildings
Olin has funded, are science and engineering facilities. A few of the grant recipients
include Bucknell, Johns Hopkins, Marquette, Tufts, the University of Southern
California and the Florida Institute of Technology.
The Florida Institute of Technology (FIT) is a small, independent university with strong
engineering and science programs. Located in Melbourne, Florida, the campus houses
three buildings dedicated to and fully funded by the F.W. Olin Foundation. Granting
$25 million to FIT, the Olin Foundation decided to put $14 million of that into the
construction and equipping of the F.W. Olin Physical Science Laboratory.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 10 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
2.3 Building Statistics
The F.W. Olin Physical Science Laboratory is a 69,348 square foot facility that houses
14 learning and 21 research laboratories along with faculty offices and classroom
spaces. The building is also equipped with 2 large multi-use/demonstration
classrooms.
A design-build delivery method was used. Design of this project began in 2002 when
Tilden Lobnitz Cooper (TLC) in Cocoa, Florida was approached to create the
mechanical, electrical and plumbing portion of the building. Along with Schwab
Twitty Hanser (STH), who was the main architect on the job, the two companies
compiled a construction team. Figure 2.1 is a list of the companies and their roll in the
project:
Construction began in June 2003 and was predicted to be completed by Fall 2004. Due
to some construction delays and the untimely hurricanes, the final completion of the
project was pushed back and is still undergoing some final touchups.
The four-story laboratory is a cast-in place concrete structure with CMU exterior walls
with cement plaster. A brick veneer was used for final decorative touches. A one-way
concrete slab was also used for this structure’s base.
Figure 2.1: Primary Project Team & Their Roles
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 11 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
There are some unique aspects to this building. The fourth floor houses a large
observatory deck with several small telescopes. There is also a large domed, one-meter
telescope that was pre-engineered before putting it in place. With room for twelve
additional telescopes, this lab is state of the art.
Of the 35 laboratories that were mentioned above, 25 of them are equipped with fume
hoods. These fume hoods are controlled by Phoenix Valves, each with an individual set
point to control the emissions from the hood to the ambient air.
Adjacent to the Olin Science Lab is the central mechanical building for the space. The
mechanical equipment in the building is consistent of two – 1200 GPM roof-mounted
Marley Cooling Towers, two – 400 ton water-cooled chillers, two – primary chilled
water pumps, two – secondary chilled water pumps, two – condenser water pumps,
two – hot water pumps, two – secondary hot water pumps and finally, one gas-fired,
hot water boiler rated at 4500 MBH.
The electrical power in the building is rated at 675 kW and 2500 A. It is consistently
277/480V, 3 Ф, 4–wire throughout the building, with step-down transformers to
480∆ – 120/208Y. Emergency power would be generated through a 400 kW Diesel
Generator.
In the classroom, lab and office spaces, fluorescent lighting with high power factor
ballasts are used. HID lamps with minimum 90% power factor ballasts can be found in
the mechanical building.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 12 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Finally, the fire protection specified for the Olin Laboratory is quick-response action
upright, horizontal sidewall and pendant sprinkler heads with integral chrome-plated
escutcheon plates. The chilled water piping is designated for 175 psig and has a
Corrosion Resistance Rating (CRR) of 1.0 or greater. A horizontal split-case fire pump
designed to deliver greater than 150% of rated capacity at a pressure not less than 65%
of rated head developed is present.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 13 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
3.0 Building Analysis
As a mechanical option, my first goal was to check the compliance of the F.W. Olin
Physical Science Lab with two very important ASHRAE Standards: 90.1 and 62-2004.
As mentioned in my schedule drawings that were obtained by TLC – Cocoa, the
standards are met and do comply with both. Through work experience at the firm, I
know that their compliance checks are legitimate; however, I decided to recheck the
compliances for my own thesis defense.
ASHRAE Standard 62 – 2004 was designed to check the levels of ventilation supply
needed based on room type, area and occupancy. A Z-critical, or critical space value is
determined and used in these calculations.
ASHRAE Standard 90.1 was designed as a tool for engineers to show requirements for
the construction of a building based on heat transfer materials and lighting. It also
contains guidelines for glass to wall ratios.
3.1 ASHRAE Standard 62 – 2004
In Appendix A, calculations for the Ventilation Rate Procedure can be found. This is the
compliance check for Standard 62–2004 , taken from a Standard 62-2001 Addendum
n. In these excel spreadsheets, you will find that the Olin Physical Science Lab is indeed
compliant with Standard 62–2004.
3.2 ASHRAE Standard 90.1 – Envelope Compliance
The wall structure of the FIT Lab Building is typical throughout the entire laboratory.
This construction consists of face brick, 8” light weight concrete block and gypsum
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 14 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
board. The overall U-value for this type of construction is 0.124 from Normative
Appendix B in Standard 90.1 (Figure 3.1).
In order for the building envelope to comply with Standard 90.1, a few criteria must be
met. Those include, but are not limited to:
Climate shall be determined based on the cooling degree-days base 50oF, CDD50, and heating degree-days base 65oF, HDD65
Mandatory Provisions (e.g. Insulation General and Air Leakage)
Vertical Fenestration does not exceed 50% of the total gross wall area of the building
As mentioned above in the introduction to this section, my overall U-value for building
envelope material is 0.124. The U – value for my fenestration is 1.02 with my windows
being operable. The total amount of glass throughout my building is approximately
14.13% of the total gross wall area. Because of these three reasons, it is safe to say that
Figure 3.1: Normative Appendix B – Standard 90.1
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 15 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
the FIT Lab complies with Standard 90.1 in regards to building envelope. Detailed
spreadsheets can be found in Appendix B at the end of this report.
3.3 ASHRAE Standard 90.1 – Lighting Compliance
As per Standard 90.1 – Table 9.6.1, Lighting Power Densities Using the Space–by–Space
Method (Figure 3.2), selection of a specific building type allows you to determine the
maximum wattage per square foot depending on the spaces in the building. For the FIT
Olin Lab, I chose education facilities.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 16 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Looking at the different spaces for an education facility, the wattage per square foot
ranges from 1.3 – 1.8 W/ft2 for typically occupied spaces. After a detailed calculation
was completed, the results were that the FIT Lab Building does comply with Standard
Figure 3.2: Table 9.6.1 from Standard 90.1 – Lighting Power Densities Using the Space–by–Space Method
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 17 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
90.1. A set of detailed calculations can be found in Appendix C at the end of this
report.
3.4 Conclusions of Building Analyses
Appendix A – C, inclusive, are the calculations and compliance check for ASHRAE
Standards 62 – 2004 and 90.1. These calculations acknowledge that the Florida
Institute of Technology’s Olin Science Lab is in compliance with these two very
important ASHRAE Standards.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 18 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
4.0 Mechanical Redesign
As my depth area of research, I have performed a detailed analysis of the existing air
handling units and the existing conditions of the FIT Science Lab. After one semester of
breaking down the building piece by piece (Fall 2004 – AE 481W), I chose to conduct
my thesis research on the addition of desiccant technology.
A desiccant wheel is used to
remove moisture from the air. As
shown in the desiccant diagram
(Figure 4.1), supply air (process
inlet) passes through the desiccant
wheel. On the desiccant wheel is a
special desiccant coating with a rating for the size of the openings in the wheel. The
wheel is to act as a sieve for the moisture. Typical opening sizes range from 3 – 4
angstroms.
After leaving the wheel, the supply air continues to provide air to the space (process
outlet). In the return or exhaust duct, the air returning to the unit or leaving the
building passed through a heat source (reaction inlet to reaction heat source). This
warmed air then passes back through the desiccant wheel, evaporating the moisture off
of the wheel and then continuing to the ambient air if it is exhaust or to the air
handling unit if it is return air (reaction outlet).
At first glance, the state of the FIT Lab and its air system is perfect. Designed by TLC
Engineering for Architecture in Cocoa, Florida, the standards and rules of thumb were
Figure 4.1: Desiccant Wheel Diagram
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 19 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
followed to a tee. However, with the climate of a coastal city in Florida, humidity can
pose as a huge problem to those who inhabit the area. Along with the stickiness you
feel due to humidity comes water vapor which has the ability to produce mold and
mildew on items throughout the building system. Ductwork insulation can grow mold
on it and when the air is passing through to classrooms and laboratories, the air
particles carry those spores with them, causing sick building syndrome.
I have always been interested in Desiccant Technology although it is not typically seen
in normal building applications. It is known that most people do not choose desiccant
wheels for their mechanical system because it is more costly for the equipment and
perhaps in the long run for maintenance. As will be shown through my research of this
depth area, the cost of the air handler and wheel will be lower and the energy savings is
enormous.
Another issue that seems to arise about desiccant wheels in laboratory applications is
the fact that cross contamination could occur and harmful gases can leak through the
exhaust stream back into the supply air stream. This also will be proven false for my
application to the Olin Lab, therefore proving the addition of the wheels to be beneficial
to the Florida Institute of Technology.
4.1 Introduction of Desiccant Wheels to All the Air Handling Units
My first task was to find a desiccant wheel that would be capable to fit into my existing
air handling units. Since I have eight M – Series Trane Air Handling Units, my first
option was to look at their manufacturing catalogs to see if a wheel was available for
purchase or if it was even an option for the Modular Climate Changers (MCC).
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 20 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
After a brief chat with a Trane representative, it was determined that they do not offer
that type of product for their MCC units. He did, however, lead me to SEMCO,
manufacturer of desiccant wheels and the Pinnacle Unit with a wheel built into it.
Due to the fact that the existing units in the FIT Olin Lab are brand new, I decided that I
would not replace the whole unit, but just look for a desiccant wheel with casing to add
into the 8 MCC units. SEMCO offers a packaged
energy recovery system that has a desiccant wheel in
casing with optional heating and cooling coils. The
technical guide on SEMCO’s website,
www.semcoinc.com, provided a detailed, step-by-step
way to calculate the size of the Packaged Energy
Recovery System (Figure 4.2) that I would need for
each of the individual MCC units.
Along with a calculation to size the
desiccant wheel, SEMCO offered a way to
calculate the size of the heating and
cooling coil that you would need to
produce the air temperature to remove the
moisture from the air. This was important
to me because I theorized that adding a
desiccant wheel would lower the load on the
heating and cooling coils and therefore, downsize them. This would produce a huge
savings on first cost and on energy.
Figure 4.2: SEMCO Packaged Energy Recovery System
Figure 4.3: SEMCO EP Series, No Coils
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 21 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Since the Trane Units were already equipped with cooling and reheat coils, I chose to
use the described selection process from SEMCO and apply it to the Trane coils. I then
would double check my answers based on Trane’s selection standards for cooling and
heating coils. Also, since the Trane Units were equipped with coils, I was able to select
the EP Series of the Energy Recovery System because it offered the most flexibility and
lowest cost. Figure 4.3 shows the diagram for the SEMCO EP Series without coils.
After selecting the size of the Energy Recovery System that I would need for each air
handler, the problem arose as to how I was going to insert these into the existing Trane
Units. Compatibility was not a problem; a Trane representative sent me to the SEMCO
site for the desiccant wheels. Since the Modular Climate Changer Units are built–up air
handlers, each section is attached to each other with nuts and bolts. The build–up of
my specific units is as follows:
Fan Mixing Box (FMB) Cartridge Filter (CF) Cooling Coil (CC) Small Access (SAC) Reheat Coil (RHC) Fan (FAN)
Since the desiccant wheel requires both cooling and heating coils for proper moisture
removal, I decided to split the system between the cartridge filter and the cooling coil.
This would allow me to insert the EP Series Energy Recovery System and allow for the
heating and cooling coils to be used.
Figure 4.4a and 4.4b are typical air handling unit as they currently existing in the FIT
Olin Lab. The room shown in 4.4a is the First Floor Mechanical Room on the left side of
the building, Room 134. Figure 4.4b is the second mechanical room on the First Floor,
Room 116.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 22 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
As you can clearly see, the spaces allotted for the mechanical rooms are big enough to
house the existing equipment only. Therefore, upon insertion of the Desiccant System
into the existing Air Handling Units, I came across a space problem. The Energy
Recovery System package did not fit in the room. Even with the downsizing of the
cooling and heating coils, the space cleared up by the removal of a few rows of coils did
not equate to the space I would need for the ER Package. This problem could be
resolved by moving the exterior wall out by several feet. The extension of the wall
would allow for the exterior door to be moved and the Desiccant Wheel and necessary
equipment to be placed in without problem.
Appendix D contains all of my detailed excel spreadsheets for my process of selecting
the desiccant wheels for each of the Trane MCCs. It also contains the charts and graphs
from the SEMCO cutsheets that were actually used in these calculations. As can be seen
in Appendix E, a total of 416.97 tons of cooling can be saved by adding a desiccant
wheel in the form of the SEMCO EP Series Energy Recovery System Unit. As for cost, a
total of $166,787.00 (based on $400/ton of cooling) can be saved on coil load alone.
This reduction will be found in the first cost.
Figure 4.4a: First Floor Mechanical Room 134 Figure 4.4b: First Floor Mechanical Room 116
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 23 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
4.2 Construction and Structural Issues
Since the FIT Olin Lab is currently in construction and almost 100% complete, a
renovation would need to be done for the mechanical rooms. The sizes of the desiccant
wheel packages that are to be inserted into the mechanical rooms range from 16’ – 10”
to 19’ – 3”. This posed as a problem because there was no room in the existing space to
put in these units. Along with the lost space from the insertion of the units comes the
addition of several thousand pounds. For this reason, I would need to look at the
structural system of the building and the first cost associated with a renovation. I had
not chosen to do structural or construction management as breadth options; however,
since these issues needed to be addressed, I have touched upon them briefly in this
section.
The first floor mechanical rooms are on the back corners of the building, Room 134 on
the back left of the building and Room 116 on the back right of the building. The
extension of the second mechanical room wall, Room 116 (Figure 4.4b), would pose no
issue because there is enough space on the exterior of the building for the exterior wall
to be moved. This concurrently would then allow the mechanical room above it on the
second and third floors (Rooms 214 and 319) to be extended too. The length of the
desiccant wheel packages that need to be inserted can be found in Figure 4.5 below. As
you can see, the longest unit of the three stacked mechanical rooms would be 19’ – 3”.
Therefore, for safety purposes and for margins of error, I would ask that the exterior
wall for Mechanical Rooms 116, 214 and 319 be extended 20’ – 6”.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 24 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
For Mechanical Room 249, which lies in the middle of the very back of the FIT Olin
Lab, an extension of the exterior wall would need to be completed by approximately
18’ – 6”.
My real problem lies in the mechanical rooms that are on the bottom left corner of the
FIT Lab. As you can see from the site plan in Figure 4.6, the Chiller Building that
supplies the chilled water to the air
handling units in the Lab Building
lies only 16’ away from that exterior
wall. Mechanical Room 134 holds
AHU 1–1 and AHU 1–2. The
minimum amount of space that the
exterior wall would need to move
out would be 18’ – 0”. This could not
happen because of the Chiller Building. Since the first floor mechanical room could not
be moved, the two other mechanical rooms stacked above it, Rooms 230 and 344,
would not be able to provide the necessary room. Another alternative setup would need
to be devised so that the desiccant systems can fit on that half of the building.
Figure 4.5: Length of Desiccant Packaged Units
Figure 4.6: Site Plan Showing Mechanical Room in relation to Chiller Building
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 25 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
The only costs associated with the extension of a wall would be the first cost of
materials, demolition, removal of materials from the site and labor. Since these are only
first costs, the payback associated with these compared to the amount of energy cost
savings predicted as above ($166,787.00) would be minimal.
4.3 Ductwork Layout and Changes
Due to the fact that I have not changed the sizes of any of the laboratory or classroom
spaces, the amount of supply air that is provided by the air handling units would not
change. My fan size and the amount of air supplied by it would not be affected by the
addition of a desiccant wheel.
Because I would be breaking apart the existing unit and adding the ER System into it,
some transition ductwork would be necessary for connection of the two pieces of
equipment. The amount of ductwork needed was very minimal and would not have an
adverse affect on the cost of the building’s mechanical system.
4.4 VOC Sensors and Cross Contamination
As with any laboratory, issues will arise with the amount of chemical fumes that are
being released by the building and the equipment inside of it. 25 of the 35 laboratory
spaces are equipped with fume hoods. These fume hoods, used for chemical and
physical science lab tests, are controlled by Phoenix Valves that modulate the amount of
exhaust needed based on position of the fume hood’s sash. When a sash is in use, a
scientist typically has the sash in the fully opened or 80% open position. The control
valve will read this positioning. The valve then varies the amount of exhaust needed.
As a room becomes unoccupied, it is hoped that the scientists would fully close the sash
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 26 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
or close it to a 20% open position. The process of closing or partially closing the fume
hoods makes for a huge energy savings on the FIT Olin Lab and helps to keep the
exhaust gases from leaking back into the space.
With the addition of a desiccant system, the exhaust or return air line must be used so
that a reheating process can occur and the moisture collected on the wheel by the
supply air can be evaporated. If the exhaust line is contaminated with chemical fumes,
this can cause a potential cross contamination problem. Cross contamination is the
leaking of harmful chemical gases into the supply air stream that is used to condition
occupied spaces.
There are many pieces of literature regarding the issues of cross contamination and
desiccant systems with the use of exhaust from a laboratory space. However, all the
literature does not choose one side or the other. It is all dependent on the application
and the specific building type. A cross contamination issue will only occur if the
equipment installed is put in improperly.
For this reason, I have paid close attention to how my desiccant system was set up.
Using many resources, including the expertise of one particular engineer at Hammel,
Green and Abrahamson (HGA), I learned that there are three or four ways for cross
contamination to occur, each of which must be individually addressed.
The first way for cross contamination to occur is for exhaust air to leak into the supply
air by way of the seals in the wheel. The leakage problem, which occurs at the
perimeter of the wheel as it rotates, can be solved by controlling the relative air
pressures such that the air leaks in the opposite way you are concerned. For example,
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 27 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
in this application, I would cause the supply air to leak into the exhaust air by making
the pressure greater on the exhaust side.
Another way for cross contamination to occur is for chemicals to stick to the wheel on
the exhaust side and get thrown off into the supply air side as it rotates around. This
will not happen because of the purge section where the air blows backwards across the
wheel as it transitions between the dirty and clean side. Most of the harmful particles
will get purged off. SEMCO guarantees that no more than 0.0005% will be stuck on
the wheel.
One other way for cross contamination to occur is for the bad chemicals to get
absorbed into the desiccant and then release on the other side. Most of the chemicals
used in laboratories have a large chemical structure and are not an issue; they will stay
in the exhaust stream and not get stuck in the desiccant. I have solved this problem by
choosing a wheel that has a desiccant coating with only 3–angstrom sized openings.
The chemicals physically do not fit in these size openings.
There are times when other chemicals with smaller structures will be used and these
structures will fit into the 3–angstrom sized openings. Although the list of chemicals is
much smaller, radon and ammonia are included on it. These will pass through very
easily. However, if you look at the system as a whole, with all the exhaust streams
coming together, with the chemical needing to pass through a fume hood and with all
the ductwork that the chemical will actually be going through, the exhaust air stream is
very safe. SEMCO can guarantee only 0.005% crossover. The system can be tested
every five years to make sure it is still within that range.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 28 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Finally, regarding corrosion, it was found that the dilution level of laboratory exhaust is
so great that the exhaust air stream is relatively harmless.
4.5 Conclusions of Mechanical Depth
My final conclusions for my mechanical depth work is that the addition of a desiccant
wheel into the 8 existing Modular Climate Changers is a cost–saving and energy saving
decision. 416.97 tons of cooling, or $166,787.00, will be saved on this addition. With
space being an issue, renovations would need to be conducted as well as structural
studies for the additional weight added to the building.
Secondly, there will not need to be any ductwork sizing or layout changes because all of
the work was done in the mechanical room. The size or usage of the rooms throughout
the FIT Lab has not changed, therefore, not changing their air flow requirements. The
slight alteration that I have made to the units requires a minimal amount of ductwork
and would not be a huge factor in the overall cost.
Lastly, the addition of a desiccant wheel to a laboratory application and the continuing
debate on cross contamination is resolved by taking a few simple steps. The selection of
my wheel was based on size of the desiccant coating, i.e. the size of the opening on the
wheel. A change in relative air pressure to cause the supply air to leak into the exhaust
stream and not vice versa will prevent leakage into the supply air stream. The purge
section of the wheel prevents the dirty side of the desiccant wheel to become “clean”
before rotating to the supply air side.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 29 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
5.0 Breadth Work – Electrical Redesign
As one of the breadth portions of my Senior Thesis, I have chosen to perform an
electrical redesign of the panel boards supplying power to my 8 air handling units.
With the addition of new equipment and the downsizing of the cooling and heating
coils in the existing air handlers, I wanted to make sure that the panel boards complied
with the National Electric Code (NEC).
My first step was to find out what portion of the electrical load for the 8 air handling
units was contributed by the coils. With this information, I would be able to neglect
that part of the load and add in the new load for the smaller coils. Appendix F is the
existing 6 panel boards that contain all eight air handlers. For reference now, I have
included the load information for each of the air handlers in Figure 5.1 below.
The only electrical pieces of equipment in my air handlers are the heating and cooling
coils and the fan. It was suggested that an assumption of 35% of the total electrical load
found on the panel boards would be dedicated to the coils.
The next step taken was to calculate the electrical load from the new cooling and
heating coils due to the insertion of a Desiccant Wheel. Referring back to Appendix D,
which is the Desiccant Wheel Selection spreadsheets, the new coil sizes can be found.
Figure 5.1: Electrical Load from Air Handling Units
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 30 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
With this information, I was able to determine the new electrical load that would be on
the panel board due to the coils themselves.
Figure 5.1 is a summary of the calculations done so far for my electrical breadth.
Included in the figure is the information for the total electrical load currently on the
panel, the coil electrical load, the new electrical load from the downsized coils and the
new total load from the air handling units.
Appendix G concludes my Electrical Breadth with the newly sized panels as they would
be in the FIT Olin Lab. Figure 5.2 is a summary of the panel boards with proof that they
are compliant with the NEC or a suggestion to make them compliant. Issues arose with
the two panel boards that contained two air handling units (OSB1 and OSB2).
Resolving this issue would be as easy as using two panel boards conjoined to supply the
need load to the units.
Figure 5.2: Panel Board Summary
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 31 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
6.0 Breadth Work – Acoustics
When designing a mechanical room, special attention must be paid to the design of the
walls and their transmittance. When a critical space is located on the other side of a
mechanical room, such as a classroom or lecture hall, the noise level that is produced
by the machine and how much of that can be heard from the adjoining spaces is very
important. Since I will be introducing a new piece of equipment into an existing
mechanical room, an acoustical analysis was done to see that the transmittance through
the wall is still below the necessary level.
Using the Trane Acoustics Program (TAP), I have performed this analysis. I feel that
this is a very accurate analysis due to the fact that one of the options for air handling
units was specifically the Modular Climate Changer. This, along with the acoustical
data for the air handlers from a Trane representative, proved to complete the necessary
parts of the critical acoustics path used to determine the transmittance level.
In Appendix H at the end of this report, a full set of Sound Transmittance Class (STC)
and Room Criteria (RC) curves can be found. These curves, along with the data printed
out for each newly redesigned mechanical room, show that the transmittance level
through the walls does not exceed the necessary levels for a classroom. This is mainly
due to the fact that the added Desiccant Wheel Package does not have any critically
loud pieces of equipment. Another main reason is that the existing units were designed
specifically to a lower decibel level for each octave band. The engineers at TLC already
took into account that the mechanical rooms would be next to a teaching space.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 32 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
7.0 Conclusions
With my thesis finished and all of my calculations compiled, I was able to step back and
look as this project as a whole. I was extremely pleased with myself, with the faculty in
the Architectural Engineering Department and with the courses offered by the
Architectural Engineering Department. It is unusual to have such a successful program
and it was all thanks to the faculty and the students, past, present and future, that make
up the AE Department.
With the strength of mechanical department and its faculty, I was able to go through
five years of intense courses teaching me every aspect of the mechanical building
systems. With the uniqueness of the architectural engineering department at Penn
State, I was able to understand and complete redesigns and analyses on my building
from other options besides mechanical. Finally, with my own strengths and the
strengths of the other AE students, I was able to complete a full year thesis because of
the uniqueness and strengths of this program.
My final conclusions for the F.W. Olin Science Lab are that the addition of Desiccant
Wheels into each of the air handling units would be a cost and energy savings option.
416.97 tons of cooling are saved from the air handlers because of the addition of a
desiccant wheel and almost $168,000.00 was saved by this reduction in tonnage. With
careful installation and precise steps, the insertion of the Desiccant System proves to be
safe against cross contamination from the harmful chemical gases removed by the
exhaust stream. Pressurizing one side of the wheel to have the air leak from the supply
side to the exhaust side, including a purge section in the system and sizing the desiccant
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 33 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
coating for 3–angstroms will satisfy the requirements to keep the supply air to the
occupied spaces clean.
The electrical panel boards containing the air handling units were redesigned to
include the Desiccant Wheel Systems. Four of the six existing panel boards were
capable of holding the newly installed systems. The remaining two will need to be
resized or changed to a dual panel board.
The acoustical properties of the Energy Recovery Systems are so slight that the
transmittance of sound from the mechanical rooms to the classroom spaces adjacent to
the mechanical rooms does not increase enough to redesign the walls and their
insulation values. This was mainly due to the careful attention to detail by the
engineers at TLC – Cocoa. Their initial design of the air handling units took the
adjoining classroom and lecture hall spaces into account. The existing air handlers
were sized and options were selected so that the equipment would be extremely quiet.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Pastor 34 Thesis Advisor – Dr. Jim Freihaut April 8, 2005
8.0 Acknowledgements
Thesis Sponsor AE Students TLC Engineering for Architecture Jess Baker Pat Hopple Luke Klock Thesis Advisor Katie McGimpsey Dr. James Freihaut Friends Thesis Professors Maureen Casey Dr. M. Kevin Parfitt Krista Greer Jonathan Dougherty Julie Martinet Katie McKeever Mandy Ott Mechanical Professors Lauren Scott Dr. William Bahnfleth Meshall Thomas Dr. Moses Ling Nicole Tilley Dr. Stanley Mumma Jess Wolford Dr. Jelena Srebric Chief Dr. DeFrank Professionals GRG, Inc. Greg Romancyzk, E.I.T. Family Kathy Pastor, Mom HGA Engineering Matthew Pastor, Brother Kermit Olson, P.E. Debbye Sweeney, Aunt Robert Sweeney, Uncle TLC Engineering for Architecture Stasia Wyszinski, Aunt
James McTavish, P.E. Phyllis Leonard, Aunt Jim Wamsley, P.E. Bob Sweeney, Cousin
Paul Sweeney, Cousin Trane Representative Texas von Weiner, Family Puppy
Todd Moore, P.E., LEED – AP Champ, Texas’s Brother
In Loving Memory, Scruffy (June 10, 1989 – January 20, 2005) Beloved Pet, Friend and Companion
To my family, I want to thank you for supporting me throughout this past year and most importantly, all my life. I would not have been where I am today were it not for your constant urging and words of wisdom, advice and encouragement. My future is bright because of the person you have all shaped me to be. To my friends, I want to thank you for your support throughout college, for keeping me sane this past year, for making me take much needed breaks and for always being there through thick and thin. I love you all and the times we’ve had. Penn State would never have been the same without you.
“I live for the times I’ll never remember with the friends I’ll never forget.”
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
9.0 Appendices
Appendix A: Standard 62 – 2004 Calculations (Ventilation Rate Procedure)
Appendix B: Standard 90.1 – Glass Area and Envelope Compliance
Appendix C: Standard 90.1 – Lighting Density Compliance
Appendix D: Selection of Desiccant Wheel Calculations
Appendix E: Energy and Cost Savings for Desiccant Wheel Selection
Appendix F: Existing Panel Boards
Appendix G: New Panel Boards with Desiccant Wheel (Electrical Redesign)
Appendix H: Acoustical Calculations and Graphs (Acoustical Analysis)
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix A: Standard 62 – 2004 Calculations
(Ventilation Rate Procedure)
Zones served by system Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12Space type (select from pull-down list) Science labScience labOffice spacScience labLecture ClaCorridors Lecture ClaOffice spacOffice spacLobbies Reception Office space
Az Floor area of zone, ft2 1211 1071 120 185 1188 656 770 500 198 1736 354 198Pz Zone population, largest # of people expected to occupy
zone20 20 3 6 32 0 20 6 3 34 6 3
Rp Area outdoor air rate from Table 6.1, cfm/ft2 10 10 5 10 7.5 0 7.5 5 5 5 5 5Ra People outdoor air rate from Table 6.1, cfm/person 0.18 0.18 0.06 0.18 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06Pz*Rp 200 200 15 60 240 0 150 30 15 170 30 15Az*Ra 217.98 192.78 7.2 33.3 71.28 39.36 46.2 30 11.88 104.16 21.24 11.88
Voz Outdoor airflow to the zone corrected for zone air distribution effectiveness, (Pz*Rp + Az*Ra)/Ez, cfm
417.98 392.78 22.2 93.3 311.28 39.36 196.2 60 26.88 274.16 51.24 26.88
Vpz Primary airflow to zone from air handler (intake plus recirculated air, but not local recirculation such as at mixing boxes), cfm. In VAV systems, use the design
1550 1420 320 400 1600 535 1000 310 280 1700 300 280
Vdz Supply/discharge to zone including primary air Vpz and locally recirculated air, cfm. In VAV systems, use the design value.
1550 1420 320 400 1600 535 1000 310 280 1700 300 280
Vdzm Minimum supply/discharge to zone used to calculate Ev, cfm. In CAV systems, Vdzm = Vdz. In VAV systems, Vdzm is the minimum expected value of Vdz.
465 425 100 120 480 160 300 90 85 510 90 85
Zd Outdoor air fraction required in air discharged to zone,= Voz/Vdzm
0.90 0.92 0.22 0.78 0.65 0.25 0.65 0.67 0.32 0.54 0.57 0.32
Ep Primary air fraction to zone, = Vpz/Vdz (=1 for single duct and single zone systems)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Er Fraction of secondary recirc to zone representative of system average, only applies if Ep<1. For plenum return =0. For duct return with local secondary recirc =1.
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Ez Zone air distribution effectiveness, Table 6.2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fa Fraction of supply air to zone from sources outside zone, = Ep + (1-Ep)*Er
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fb Fraction of supply air to zone from full mixed primary air, = Ep = Vpz/Vdz
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fc Fraction of outdoor air to zone from sources outside zone, = 1 - (1-Ez) * (1-Er) * (1-Ep)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SYSTEM LEVELPs System population, maximum simultaneous # of
occupants of space served by system110
D Occupant diversity, ratio of system peak occupancy to sum of space peak occupancies, = Ps/ΣPz
0.72
Vou Uncorrected outdoor air intake, = D*ΣRp*Pz +ΣRa*Az, cfm 1596Vps Total system primary flow to all zones, Σ Vpz, cfm 9695
Xs Mixing ratio at primary air handler of uncorrected outdoor air intake to system primary flow, = Vou/Vps
0.16
SYSTEM EFFICIENCYEvs Zone ventilation efficiency, (Fa +Xs*Fb - Z*Fc)/Fa 0.27 0.24 0.94 0.39 0.52 0.92 0.51 0.50 0.85 0.63 0.60 0.85Ev System ventilation efficiency, min(Evs) 0.24
Percent outdoor air intakeVot Minimum outdoor air intake, Vou/Ev, cfm 6638 68% = Vot/Vps
ZONE LEVEL: AHU 1-1
Note: In VAV systems, Vps is equal to the fan airflow, and the formula in cell c40 needs to be replaced by this value.
Zones served by system Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17Space type (select from pull-down list) Science la Science la Science la Science la Office spacOffice spacScience la Science la Office spacConferenceOffice spacOffice spacAuditorium Auditorium Office spacOffice spacOffice space
Az Floor area of zone, ft2 630 780 872 730 525 450 750 680 855 900 490 500 1866 1866 215 132 150Pz Zone population, largest # of people expected to occupy
zone10 14 16 10 5 5 14 13 10 14 3 3 35 35 1 1 1
Rp Area outdoor air rate from Table 6.1, cfm/ft2 10 10 10 10 5 5 10 10 5 5 5 5 5 5 5 5 5Ra People outdoor air rate from Table 6.1, cfm/person 0.18 0.18 0.18 0.18 0.06 0.06 0.18 0.18 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06Pz*Rp 100 140 160 100 25 25 140 130 50 70 15 15 175 175 5 5 5Az*Ra 113.4 140.4 156.96 131.4 31.5 27 135 122.4 51.3 54 29.4 30 111.96 111.96 12.9 7.92 9
Voz Outdoor airflow to the zone corrected for zone air distribution effectiveness, (Pz*Rp + Az*Ra)/Ez, cfm
213.4 280.4 316.96 231.4 56.5 52 275 252.4 101.3 124 44.4 45 286.96 286.96 17.9 12.92 14
Vpz Primary airflow to zone from air handler (intake plus recirculated air, but not local recirculation such as at mixing boxes), cfm. In VAV systems, use the design
750 1000 1470 840 720 720 1150 1000 510 2400 510 350 1500 1500 820 550 300
Vdz Supply/discharge to zone including primary air Vpz and locally recirculated air, cfm. In VAV systems, use the design value.
750 1000 1470 840 720 720 1150 1000 510 2400 510 350 1500 1500 820 550 300
Vdzm Minimum supply/discharge to zone used to calculate Ev, cfm. In CAV systems, Vdzm = Vdz. In VAV systems, Vdzm is the minimum expected value of Vdz.
225 300 440 250 220 220 345 300 150 720 150 105 525 525 330 220 85
Zd Outdoor air fraction required in air discharged to zone,= Voz/Vdzm
0.95 0.93 0.72 0.93 0.26 0.24 0.80 0.84 0.68 0.17 0.30 0.43 0.55 0.55 0.05 0.06 0.16
Ep Primary air fraction to zone, = Vpz/Vdz (=1 for single duct and single zone systems)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Er Fraction of secondary recirc to zone representative of system average, only applies if Ep<1. For plenum return =0. For duct return with local secondary recirc =1.
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Ez Zone air distribution effectiveness, Table 6.2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fa Fraction of supply air to zone from sources outside zone, = Ep + (1-Ep)*Er
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fb Fraction of supply air to zone from full mixed primary air, = Ep = Vpz/Vdz
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fc Fraction of outdoor air to zone from sources outside zone, = 1 - (1-Ez) * (1-Er) * (1-Ep)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SYSTEM LEVELPs System population, maximum simultaneous # of
occupants of space served by system100
D Occupant diversity, ratio of system peak occupancy to sum of space peak occupancies, = Ps/ΣPz
0.53
Vou Uncorrected outdoor air intake, = D*ΣRp*Pz +ΣRa*Az, 1979Vps Total system primary flow to all zones, Σ Vpz, cfm 16270
Xs Mixing ratio at primary air handler of uncorrected outdoor air intake to system primary flow, = Vou/Vps
0.12
SYSTEM EFFICIENCYEvs Zone ventilation efficiency, (Fa +Xs*Fb - Z*Fc)/Fa 0.17 0.19 0.40 0.20 0.86 0.89 0.32 0.28 0.45 0.95 0.83 0.69 0.58 0.58 1.07 1.06 0.96Ev System ventilation efficiency, min(Evs) 0.17
Percent outdoor air intakeVot Minimum outdoor air intake, Vou/Ev, cfm 11427 70% = Vot/Vps
ZONE LEVEL: AHU 2-1
Note: In VAV systems, Vps is equal to the fan airflow, and the formula in cell c40 needs to be replaced by this value.
Zones served by system Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 Zone 17 Zone 18Space type (select from pull-down list) Science la Office spacScience la Science la Office spacOffice spacOffice spacOffice spacScience la Office spacScience la Office spacScience la Reception Office spacOffice spacLobbies Office space
Az Floor area of zone, ft2 685 240 850 1110 300 240 530 576 486 487 961 408 140 486 635 530 590 120Pz Zone population, largest # of people expected to occupy
zone6 3 22 14 3 3 6 12 10 3 30 2 6 6 12 3 15 1
Rp Area outdoor air rate from Table 6.1, cfm/ft2 10 5 10 10 5 5 5 5 10 5 10 5 10 5 5 5 5 5Ra People outdoor air rate from Table 6.1, cfm/person 0.18 0.06 0.18 0.18 0.06 0.06 0.06 0.06 0.18 0.06 0.18 0.06 0.18 0.06 0.06 0.06 0.06 0.06Pz*Rp 60 15 220 140 15 15 30 60 100 15 300 10 60 30 60 15 75 5Az*Ra 123.3 14.4 153 199.8 18 14.4 31.8 34.56 87.48 29.22 172.98 24.48 25.2 29.16 38.1 31.8 35.4 7.2
Voz Outdoor airflow to the zone corrected for zone air distribution effectiveness, (Pz*Rp + Az*Ra)/Ez, cfm
183.3 29.4 373 339.8 33 29.4 61.8 94.56 187.48 44.22 472.98 34.48 85.2 59.16 98.1 46.8 110.4 12.2
Vpz Primary airflow to zone from air handler (intake plus recirculated air, but not local recirculation such as at mixing boxes), cfm. In VAV systems, use the design
700 440 1510 1300 440 400 410 610 740 780 1880 600 350 400 450 450 610 100
Vdz Supply/discharge to zone including primary air Vpz and locally recirculated air, cfm. In VAV systems, use the design value.
700 440 1510 1300 440 400 410 610 740 780 1880 600 350 400 450 450 610 100
Vdzm Minimum supply/discharge to zone used to calculate Ev, cfm. In CAV systems, Vdzm = Vdz. In VAV systems, Vdzm is the minimum expected value of Vdz.
210 130 450 390 130 120 120 180 220 230 560 180 105 120 180 180 245 40
Zd Outdoor air fraction required in air discharged to zone,= Voz/Vdzm
0.87 0.23 0.83 0.87 0.25 0.25 0.52 0.53 0.85 0.19 0.84 0.19 0.81 0.49 0.55 0.26 0.45 0.31
Ep Primary air fraction to zone, = Vpz/Vdz (=1 for single duct and single zone systems)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Er Fraction of secondary recirc to zone representative of system average, only applies if Ep<1. For plenum return =0. For duct return with local secondary recirc =1.
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Ez Zone air distribution effectiveness, Table 6.2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fa Fraction of supply air to zone from sources outside zone, = Ep + (1-Ep)*Er
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fb Fraction of supply air to zone from full mixed primary air, = Ep = Vpz/Vdz
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Fc Fraction of outdoor air to zone from sources outside zone, = 1 - (1-Ez) * (1-Er) * (1-Ep)
1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
SYSTEM LEVELPs System population, maximum simultaneous # of
occupants of space served by system60
D Occupant diversity, ratio of system peak occupancy to sum of space peak occupancies, = Ps/ΣPz
0.38
Vou Uncorrected outdoor air intake, = D*ΣRp*Pz +ΣRa*Az, 1538Vps Total system primary flow to all zones, Σ Vpz, cfm 12130
Xs Mixing ratio at primary air handler of uncorrected outdoor air intake to system primary flow, = Vou/Vps
0.13
SYSTEM EFFICIENCYEvs Zone ventilation efficiency, (Fa +Xs*Fb - Z*Fc)/Fa 0.25 0.90 0.30 0.26 0.87 0.88 0.61 0.60 0.27 0.93 0.28 0.94 0.32 0.63 0.58 0.87 0.68 0.82Ev System ventilation efficiency, min(Evs) 0.25
Percent outdoor air intakeVot Minimum outdoor air intake, Vou/Ev, cfm 6057 50% = Vot/Vps
ZONE LEVEL: AHU 3-1
Note: In VAV systems, Vps is equal to the fan airflow, and the formula in cell c40 needs to be replaced by this value.
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix B: Standard 90.1 – Glass Area and
Envelope Compliance
HDD65 490 Width 3.33 ft Width of Building 125.00 ftCDD50 8448 Height 7.58 ft Length of Building 160.00 ft Assembly Maximum Insulation Min. R-Value
Number of Windows 18 Height of Building 10 ftTotal Area of 1st Fl. Windows 455.00 sq. ft Total Wall Area of 1st Floor 5700.00 sq. ft Insulation Entirely above Deck U-0.063 R-15.0 ci
Fenestration Area 2980.56 sq. ft Metal Building U-0.065 R-19.0Total Wall Area 21100.00 sq. ft Attic and Other U-0.034 R-30.0
Width 3.33 ft Width of Building 125.00 ftHeight 4.67 ft Length of Building 160.00 ft Mass U-0.580 NR
<50% of Wall Area Number of Windows 32 Height of Building 10 ft Metal Building U-0.113 R-13.0Total Area of 2nd Fl. Windows 497.78 sq. ft Total Wall Area of 2nd Floor 5700.00 sq. ft Steel Framed U-0.124 R-13.0
Wood Framed and Other U-0.089 R-13.0
Width 3.33 ft Width of Building 125.00 ft Below Grade Wall C-1.140 NRHeight 4.67 ft Length of Building 160.00 ftNumber of Windows 72 Height of Building 10 ft Mass U-0.322 NRTotal Area of 3rd Fl. Windows 1120.00 sq. ft Total Wall Area of 3rd Floor 5700.00 sq. ft Steel Joist U-0.350 NR
Wood Framed and Other U-0.282 NR
Width of Windows 3.17 ft Width of Building 125.00 ft Unheated F-0.730 NRHeight of Windows 8.33 ft Length of Building 75.00 ft Heated F-1.020 R-7.5 for 12 in.Number of Windows 2 Height of Building 10 ftWidth of Glass Doors 15.83 ft Total Wall Area of 4th Floor 4000.00 sq. ft Swinging U-0.700Height of Glass Doors 8.33 ft Non-Swinging U-1.450Number of Entrances 1 TOTAL WALL AREA 21100.00 sq. ftTotal Area of Entrance Glass 184.72 sq. ft
Width of Middle Window 6.33 ft 0 - 10.0% Ufixed-1.22 SHGCall-0.40Height of Middle Window 22.83 ft Uoper-1.27 SHGCnorth-0.61Number of Middle Windows 2 10.1 - 20.0% Ufixed-1.22 SHGCall-0.25Width of Side Windows 19.00 ft Uoper-1.27 SHGCnorth-0.61Height of Side Windows 22.83 ft 20.1 - 30.0% Ufixed-1.22 SHGCall-0.25Number of Side Windows 1 Uoper-1.27 SHGCnorth-0.61Total Area of Atrium Glass 723.06 sq. ft 30.1 - 40.0% Ufixed-1.22 SHGCall-0.25
Uoper-1.27 SHGCnorth-0.61TOTAL AREA OF GLASS 2980.56 sq. ft 40.1 - 50.0% Ufixed-1.22 SHGCall-0.19
Uoper-1.27 SHGCnorth-0.47
0 - 2.0% Uall-1.98 SHGCall-0.362.1 - 5.0% Uall-1.98 SHGCall-0.19
0 - 2.0% Uall-1.90 SHGCall-0.392.1 - 5.0% Uall-1.90 SHGCall-0.34
0 - 2.0% Uall-1.36 SHGCall-0.362.1 - 5.0% Uall-1.36 SHGCall-0.19
Third Floor Windows
Entrance Windows and Glass Doors
Atrium Windows - Middle and Sides
Percentage of Gross Wall Area
Wall Area of Third Floor
Wall Area of Fourth Floor
Climate in Florida
* Use Table B-3 in Normative App. B
14.13%
YES
First Floor Windows
Second Floor Windows
Wall Area for First Floor
Wall Area for Second Floor
Skylight with Curb, All, % of Roof
Table B-3: Building Envelope Requirements (HDD65: 0 - 900, CDD50: 7201 - 9000)NonresidentialOpaque Elements
Skylight with Curb, Glass, % of Roof
Fenestration
Vertical Glazing, % of Wall
Skylight with Curb, Plastic, % of Roof
Assembly Max. U (Fixed/Operable)
Assembly Max. SHGC (All Orientations/North-Oriented)
Slab-on-Grade Floors
Opaque Doors
Roofs
Walls, Above Grade
Wall, Below Grade
Floors
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix C: Standard 90.1 – Lighting Density
Compliance
Lobby 0.63 201 1.16 301 1.1102 0.46 202 1.59 307 0.65103 0.73 203 0.81 310 0.71107 0.62 204 0.81 311 0.6109 1.17 205 0.94 312 0.36110 1.03 206 0.91 314 0.71112 0.5 209 0.65 315 0.69115 1.01 210 0.69 316 0.66117 1.64 211 0.94 320 0.85118 0.51 212 0.67 321 0.58119 1.2 216 0.6 325 0.58120 0.8 217 0.65 326 0.85126 0.51 218 0.66 327 0.58127 0.6 219 0.6 330 0.82129 0.49 220 0.66 331 1.09131 0.86 221 0.6 332 1.16133 1.38 222 0.62 333 0.61
135 & 132 2.04 223 0.59 334 1.09138 0.8 225 0.66 335 0.82139 0.52 226 1.03 336 0.82
140 & 144 0.71 227 0.69 337 0.82145 0.73 228 0.83 338 0.53146 0.45 229 0.58 339 0.59
232 0.79 340 0.82233 0.79 341 0.56234 0.79 342 0.8235 0.79 343 0.8236 0.8 346 0.79237 0.8 347 0.79240 0.75 348 0.79241 0.84 349 0.79242 0.61 350 0.79243 0.57 351 0.79248 1.2 353 0.76
354 0.74355 0.6356 0.76358 1.24
Second Floor Lighting Densities (W/ft2) Third Floor Lighting Densities (W/ft2)First Floor Lighting Densities (W/ft2)
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix D: Selection of Desiccant Wheel
Calculations
Supply Air 9695 CFM OA Opening 0.06 in. wg EA Opening 0.13 in. wgOutdoor Air 2550 CFM SA Opening 0.06 in. wg RA Opening 0.13 in. wg RPM BHP RPM BHP RPM BHPReturn Air 7145 CFM Filter 0.28 in. wg Enthalpy Wheel 0.51 in. wg 11000 2398 10.09 2487 12.04
Enthalpy Wheel 0.51 in. wg Casing 0.3 in. wg 11135 2420.95 10.33 2476.51 11.57 2509.14 12.30Unit Size (from Table 1) EP-18 Cooling Coil 0.36 in. wg Total 1.07 in. wg 11500 2483 10.97 2569 13Choose Model EP Heating Coil 0.06 in. wg
Casing 0.3 in. wgInternal Static Pressure SA Side 1.63 in. wg Total 1.63 in. wg RA Fan Horse Power (5 HP) 7.6 ampsInternal Static Pressure RA Side 1.07 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 3.63 in. wg Control Power 6.25 amps 8500 1757 3.5 1877 4.96Total Static Pressure RA Side (+ 0.5") 1.57 in. wg OADBT 93 F Total FLA 18.55 amps 8585 1772.13 3.58 1840.05 4.42 1891.28 5.05
Eff. SA 66.30% 9000 1846 3.97 1961 5.51Purge/Seal Air Volume - Added to SA & RA Sides (Table 4) 1440 CFM RADBT 75 F
FLA 18.55 ampsTotal SA Fan Flow 11135 CFM 25% of largest motor amps 1.9 amps 85.00%Total RA Fan Flow 8585 CFM OAgr 0.0182 gr Total MCA 20.45 amps 1.25 72.00%
Eff. SA 66.30% 1.36 66.30%Rotations Per Minute 2476.51 RPM RAgr 0.0093 gr 1.4 64.00%Brake Horse Power 11.57 BHP FLA 18.55 ampsActual HP: BHP x 1.1 (for safety factor) 12.7266788 HP 75% of largest motor amps 5.7 ampsMinimum HP 15 HP OAh 42.62 BTU/lb Total MCOP 24.25 amps
Eff. SA (%) 66.30%Rotations Per Minute 1840.05 RPM RAh 28.14 BTU/lbBrake Horse Power 4.42 BHPActual HP: BHP x 1.1 (for safety factor) 4.8618372 HPMinimum HP 5 HP
Base Efficiency based on RA CFM (Table 1) 85.00%
SA/RA Ratio 1.36SA Efficiency (Table 2) 66.30%
SA (DBT) 81.07 FSA (grains) 86.10 grSA (h) 33.02 BTU/lb
Finned Height 78 in.Finned Width 54 in.Feet Per Minute 342 fpmModel Number 5WS1008BWater Pressure Drop 8.1 ft.Gallons Per Minute 174 gpmLeaving Air Temp DB 51.4 FLeaving Air Temp WB 51.3 FConnection Size 2.5 in.
Finned Height 78 in.Finned Width 54 in.Feet Per Minute 342 fpmModel Number 5MH0702BWater Pressure Drop 2.4 ft.Gallons Per Minute 72 gpmLeaving Air Temp DB 74.8 FLeaving Air Temp WB 74.8 FConnection Size 2 in.
Full Load Amps 18.55 ampsMinimum Circuit Ampacity (MCA) 20.45 ampsMaximum Overcurrent Protection (MOCP) 24.25 amps
Internal Static Pressure RA Side RPM & BHP Calculation from Charts - Interpolation for SA Side
1 1.57 2
3 3.63 4
RPM & BHP Calculation from Charts - Interpolation for RA SideFull Load Amps (FLA)
Unit Sizing Information
Static Pressure
General Air Flow Data: AHU 1-1 Internal Static Pressure SA Side
Base Efficiency
Supply Air Efficiency
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
Fan Data Tables - SA Fan: SIZE 9, 5XX (Max. HP = 20 HP)
Purge Section
Total Fan Flow
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coils
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coils
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - RA Fan: SIZE 9, 5XX (Max. HP = 20 HP)
Supply Air Base Efficiency Calculations
Supply Air 7100 CFM OA Opening 0.04 in. wg EA Opening 0.09 in. wgOutdoor Air 7100 CFM SA Opening 0.04 in. wg Enthalpy Wheel 0.41 in. wg RPM BHP RPM BHP RPM BHPExhaust Air 5325 CFM Filter 0.19 in. wg Casing 0.3 in. wg 8450 2620 7.53 2722 9.04
Enthalpy Wheel 0.41 in. wg Total 0.8 in. wg 8540 2641.34 7.68 2666.65 8.06 2742.57 9.20Unit Size (from Table 1) EP-18 Cooling Coil 0.23 in. wg 8800 2703 8.12 2802 9.67Choose Model EP Heating Coil 0.04 in. wg
Casing 0.3 in. wg EA Fan Horse Power (5 HP) 7.6 ampsInternal Static Pressure SA Side 1.25 in. wg Total 1.25 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 ampsInternal Static Pressure RA Side 0.8 in. wg Control Power 6.25 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 3.25 in. wg Total FLA 18.55 amps 6700 1956 2.73 2092 3.89Total Static Pressure EA Side (+ 0.5") 1.3 in. wg OADBT 93 F 6765 1972.34 2.79 2012.86 3.14 2107.41 3.96
Eff. SA 67.56% 7050 2044 3.06 2175 4.27Purge/Seal Air Volume - Added to SA & RA Sides (Table 4) 1440 CFM RADBT 75 F FLA 18.55 amps
25% of largest motor amps 1.9 ampsTotal SA Fan Flow 8540 CFM Total MCA 20.45 amps 85.00%Total EA Fan Flow 6765 CFM OAgr 0.0182 gr 1.25 72.00%
Eff. SA 67.56% 1.33 67.56%Rotations Per Minute 2666.65 RPM RAgr 0.0093 gr FLA 18.55 amps 1.4 64.00%Brake Horse Power 8.06 BHP 75% of largest motor amps 5.7 ampsActual HP: BHP x 1.1 (for safety factor) 8.8679643 HP Total MCOP 24.25 ampsMinimum HP 10 HP OAh 42.62 BTU/lb
Eff. SA (%) 67.56%Rotations Per Minute 2012.86 RPM RAh 28.14 BTU/lbBrake Horse Power 3.14 BHPActual HP: BHP x 1.1 (for safety factor) 3.4562786 HPMinimum HP 5 HP
Base Efficiency based on EA CFM (Table 1) 85.00%
SA/EA Ratio 1.33SA Efficiency (Table 2) 67.56%
SA (DBT) 80.84 FSA (grains) 85.31 grSA (h) 32.84 BTU/lb
Finned Height 78 in.Finned Width 54 in.Feet Per Minute 274 fpmModel Number 5WS1008BWater Pressure Drop 5.4 ft.Gallons Per Minute 139 gpmLeaving Air Temp DB 50.4 FLeaving Air Temp WB 50.3 FConnection Size 2.5 in.
Finned Height 78 in.Finned Width 54 in.Feet Per Minute 274 fpmModel Number 5MH0702BWater Pressure Drop 1.6 ft.Gallons Per Minute 58 gpmLeaving Air Temp DB 81 FLeaving Air Temp WB 81 FConnection Size 2 in.
Full Load Amps 18.55 ampsMinimum Circuit Ampacity (MCA) 20.45 ampsMaximum Overcurrent Protection (MOCP) 24.25 amps
Supply Air Base Efficiency Calculations
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
RPM & BHP Calculation from Charts - Interpolation for EA Side1 1.3 2
Fan Data Tables - EA Fan: SIZE 5X (Max. HP = 10 HP)
Purge Section
Total Fan Flow
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coils
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coils
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
General Air Flow Data: AHU 1-2 Internal Static Pressure SA Side Internal Static Pressure EA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 5X (Max. HP = 10 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
RPM & BHP Calculation from Charts - Interpolation for SA Side3 3.25 4
Supply Air 11060 CFM OA Opening 0.05 in. wg EA Opening 0.16 in. wgOutdoor Air 11060 CFM SA Opening 0.05 in. wg Enthalpy Wheel 0.42 in. wg RPM BHP RPM BHP RPM BHPExhaust Air 8295 CFM Filter 0.27 in. wg Casing 0.3 in. wg 12600 1978 10.68 2064 12.67
Enthalpy Wheel 0.42 in. wg Total 0.88 in. wg 12795 2000.75 10.98 2039.71 11.95 2085.45 13.09Unit Size (from Table 1) EP-24 Cooling Coil 0.32 in. wg 13200 2048 11.59 2130 13.95Choose Model EP Heating Coil 0.05 in. wg
Casing 0.3 in. wg EA Fan Horse Power (10 HP) 14 ampsInternal Static Pressure SA Side 1.46 in. wg Total 1.46 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 ampsInternal Static Pressure RA Side 0.88 in. wg Control Power 6.25 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 3.46 in. wg Total FLA 24.95 amps 9600 1420 3.48 1536 5.16Total Static Pressure EA Side (+ 0.5") 1.38 in. wg OADBT 93 F 10030 1472.32 3.82 1515.31 4.48 1585.45 5.57
Eff. SA 67.06% 10200 1493 3.95 1605 5.73Purge/Seal Air Volume - Added to SA & EA Sides (Table 4) 1735 CFM RADBT 75 F FLA 24.95 amps
25% of largest motor amps 3.5 ampsTotal SA Fan Flow 12795 CFM Total MCA 28.45 amps 83.00% 84.00% 85.00%Total EA Fan Flow 10030 CFM OAgr 0.0182 gr 1.25 71.00% 72.00%
Eff. SA 67.06% 1.33 66.56% 67.06% 67.56%Rotations Per Minute 2039.71 RPM RAgr 0.0093 gr FLA 24.95 amps 1.4 63.00% 64.00%Brake Horse Power 11.95 BHP 75% of largest motor amps 10.5 ampsActual HP: BHP x 1.1 (for safety factor) 13.141112 HP Total MCOP 35.45 ampsMinimum HP 15 HP OAh 42.62 BTU/lb
Eff. SA (%) 67.06%Rotations Per Minute 1515.31 RPM RAh 28.14 BTU/lbBrake Horse Power 4.48 BHPActual HP: BHP x 1.1 (for safety factor) 4.9307133 HPMinimum HP 10 HP
Base Efficiency based on RA CFM (Table 1) 84.00%
SA/RA Ratio 1.33SA Efficiency (Table 2) 67.06%
SA (DBT) 80.93 FSA (grains) 85.62 grSA (h) 32.91 BTU/lb
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5WS1008BWater Pressure Drop 10.7 ft.Gallons Per Minute 244 gpmLeaving Air Temp DB 52.4 FLeaving Air Temp WB 52.2 FConnection Size 3 in.
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5MH0702BWater Pressure Drop 3.8 ft.Gallons Per Minute 101 gpmLeaving Air Temp DB 69.6 FLeaving Air Temp WB 69.6 FConnection Size 2 in.
Full Load Amps 24.95 ampsMinimum Circuit Ampacity (MCA) 28.45 ampsMaximum Overcurrent Protection (MOCP) 35.45 amps
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - EA Fan: SIZE 13, 9X, 5XX (Max. HP = 20 HP)
Purge Section
Total Fan Flow
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity Chilled Water Coil
Heating Coil Sizing Data - Increased Capacity Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
General Air Flow Data: AHU 1-3 Internal Static Pressure SA Side Internal Static Pressure EA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 13, 9X, 5XX (Max. HP = 20 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
RPM & BHP Calculation from Charts - Interpolation for SA Side3 3.46 4
Supply Air Base Efficiency Calculations
RPM & BHP Calculation from Charts - Interpolation forEA Side1 1.38 2
Supply Air 16270 CFM OA Opening 0.06 in. wg EA Opening 0.11 in. wgOutdoor Air 2850 CFM SA Opening 0.06 in. wg RA Opening 0.11 in. wg RPM BHP RPM BHP RPM BHPReturn Air 13420 CFM Filter 0.3 in. wg Enthalpy Wheel 0.47 in. wg 18000 1324 13.47 1405 16.98
Enthalpy Wheel 0.47 in. wg Casing 0.3 in. wg 18567 1349.52 14.07 1400.19 16.36 1429.95 17.71Unit Size (from Table 1) EP-35 Cooling Coil 0.38 in. wg Total 0.99 in. wg 19000 1369 14.53 1449 18.27Choose Model EP Heating Coil 0.06 in. wg
Casing 0.3 in. wgInternal Static Pressure SA Side 1.63 in. wg Total 1.63 in. wg RA Fan Horse Power (10 HP) 14 ampsInternal Static Pressure RA Side 0.99 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 3.63 in. wg Control Power 6.25 amps 15000 987 4.83 1095 7.56Total Static Pressure RA Side (+ 0.5") 1.49 in. wg OADBT 93 F Total FLA 24.95 amps 15717 1023.57 5.30 1074.73 6.68 1127.98 8.12
Eff. SA 72.60% 16000 1038 5.48 1141 8.34Purge/Seal Air Volume - Added to SA & RA Sides (Table 4) 2297 CFM RADBT 75 F
FLA 24.95 ampsTotal SA Fan Flow 18567 CFM 25% of largest motor amps 3.5 amps 83.00%Total RA Fan Flow 15717 CFM OAgr 0.0182 gr Total MCA 28.45 amps 1.1 77.00%
Eff. SA 72.60% 1.21 72.60%Rotations Per Minute 1400.19 RPM RAgr 0.0093 gr 1.25 71.00%Brake Horse Power 16.36 BHP FLA 24.95 ampsActual HP: BHP x 1.1 (for safety factor) 18.000926 HP 75% of largest motor amps 10.5 ampsMinimum HP 20 HP OAh 42.62 BTU/lb Total MCOP 35.45 amps
Eff. SA (%) 72.60%Rotations Per Minute 1074.73 RPM RAh 28.14 BTU/lbBrake Horse Power 6.68 BHPActual HP: BHP x 1.1 (for safety factor) 7.3473652 HPMinimum HP 10 HP
Base Efficiency based on RA CFM (Table 1) 83.00%
SA/RA Ratio 1.21SA Efficiency (Table 2) 72.60%
SA (DBT) 79.93 FSA (grains) 82.17 grSA (h) 32.11 BTU/lb
Finned Height 111 in.Finned Width 66 in.Feet Per Minute 442 fpmModel Number 5WS1008BWater Pressure Drop 10 ft.Gallons Per Minute 392 gpmLeaving Air Temp DB 53.4 FLeaving Air Temp WB 53.2 FConnection Size 2.5 in.
Finned Height 111 in.Finned Width 66 in.Feet Per Minute 442 fpmModel Number 5MH0702BWater Pressure Drop 8.9 ft.Gallons Per Minute 162 gpmLeaving Air Temp DB 68.4 FLeaving Air Temp WB 68.4 FConnection Size 2 in.
Full Load Amps 24.95 ampsMinimum Circuit Ampacity (MCA) 28.45 ampsMaximum Overcurrent Protection (MOCP) 35.45 amps
4RPM & BHP Calculation from Charts - Interpolation for SA Side
RPM & BHP Calculation from Charts - Interpolation for RA Side1 1.49 2
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - RA Fan: SIZE 24, 18X, 13XX (Max. HP = 50 HP)
Purge Section
Total Fan Flow
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
Base Efficiency
Cooling Coil Sizing Data- Increased Capacity EP Chilled Water Coil
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 24, 18X, 13XX (Max. HP = 50 HP)
Unit Sizing Information
Static Pressure
Supply Air Base Efficiency Calculations
General Air Flow Data: AHU 2-1 Internal Static Pressure SA Side Internal Static Pressure RA Side
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
3 3.63
Supply Air 13730 CFM OA Opening 0.08 in. wg EA Opening 0.24 in. wgOutdoor Air 13730 CFM SA Opening 0.08 in. wg Enthalpy Wheel 0.55 in. wg RPM BHP RPM BHP RPM BHPExhaust Air 10298 CFM Filter 0.41 in. wg Casing 0.3 in. wg 15000 1635 14.42 1720 17.43
Enthalpy Wheel 0.55 in. wg Total 1.09 in. wg 15465 1664.64 15.05 1667.97 15.18 1747.90 18.12Unit Size (from Table 1) EP-24 Cooling Coil 0.53 in. wg 15800 1686 15.51 1768 18.62Choose Model EP Heating Coil 0.09 in. wg
Casing 0.3 in. wg EA Fan Horse Power (10 HP) 14 ampsInternal Static Pressure SA Side 2.04 in. wg Total 2.04 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 ampsInternal Static Pressure RA Side 1.09 in. wg Control Power 6.25 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 4.04 in. wg Total FLA 24.95 amps 11800 1111 3.79 1233 5.94Total Static Pressure EA Side (+ 0.5") 1.59 in. wg OADBT 93 F 12033 1128.18 3.94 1199.13 5.23 1248.44 6.12
Eff. SA 64.56% 12600 1170 4.32 1286 6.57Purge/Seal Air Volume - Added to SA & EA Sides (Table 4) 1735 CFM RADBT 75 F FLA 24.95 amps
25% of largest motor amps 3.5 ampsTotal SA Fan Flow 15465 CFM Total MCA 28.45 amps 81.00%Total EA Fan Flow 12033 CFM OAgr 0.0182 gr 1.25 69.00%
Eff. SA 64.56% 1.33 64.56%Rotations Per Minute 1667.97 RPM RAgr 0.0093 gr FLA 24.95 amps 1.4 61.00%Brake Horse Power 15.18 BHP 75% of largest motor amps 10.5 ampsActual HP: BHP x 1.1 (for safety factor) 16.693916 HP Total MCOP 35.45 ampsMinimum HP 20 HP OAh 42.62 BTU/lb
Eff. SA (%) 64.56%Rotations Per Minute 1199.13 RPM RAh 28.14 BTU/lbBrake Horse Power 5.23 BHPActual HP: BHP x 1.1 (for safety factor) 5.7530509 HPMinimum HP 10 HP
Base Efficiency based on EA CFM (Table 1) 81.00%
SA/EA Ratio 1.33SA Efficiency (Table 2) 64.56%
SA (DBT) 81.38 FSA (grains) 87.18 grSA (h) 33.27 BTU/lb
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5WS1008BWater Pressure Drop 10.7 ft.Gallons Per Minute 244 gpmLeaving Air Temp DB 52.4 FLeaving Air Temp WB 52.2 FConnection Size 3 in.
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5MH0702BWater Pressure Drop 3.8 ft.Gallons Per Minute 101 gpmLeaving Air Temp DB 69.6 FLeaving Air Temp WB 69.6 FConnection Size 2 in.
Full Load Amps 24.95 ampsMinimum Circuit Ampacity (MCA) 28.45 ampsMaximum Overcurrent Protection (MOCP) 35.45 amps
General Air Flow Data: AHU 2-2 Internal Static Pressure SA Side Internal Static Pressure EA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 18, 13X, 9XX (Max. HP = 30 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coil
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - EA Fan: SIZE 18, 13X, 9XX (Max. HP = 30 HP)
Purge Section
Total Fan Flow
RPM & BHP Calculation from Charts - Interpolation for SA Side4 4.04 5
Supply Air Base Efficiency Calculations
RPM & BHP Calculation from Charts - Interpolation for EA Side1 1.59 2
Supply Air 12130 CFM OA Opening 0.08 in. wg EA Opening 0.24 in. wgOutdoor Air 2355 CFM SA Opening 0.08 in. wg RA Opening 0.24 in. wg RPM BHP RPM BHP RPM BHPReturn Air 9775 CFM Filter 0.41 in. wg Enthalpy Wheel 0.55 in. wg 13800 2198 15.02 2276 17.55
Enthalpy Wheel 0.55 in. wg Casing 0.3 in. wg 13865 2205.48 15.14 2208.58 15.24 2283.15 17.68Unit Size (from Table 1) EP-24 Cooling Coil 0.53 in. wg Total 1.33 in. wg 14400 2267 16.15 2342 18.76Choose Model EP Heating Coil 0.09 in. wg
Casing 0.3 in. wgInternal Static Pressure SA Side 2.04 in. wg Total 2.04 in. wg RA Fan Horse Power (10 HP) 14 ampsInternal Static Pressure RA Side 1.33 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 4.04 in. wg Control Power 6.25 amps 11400 1643 5.04 1745 6.99Total Static Pressure RA Side (+ 0.5") 1.83 in. wg OADBT 93 F Total FLA 24.95 amps 11510 1656.75 5.15 1740.95 6.79 1758.20 7.12
Eff. SA 71.36% 12000 1718 5.65 1817 7.7Purge/Seal Air Volume - Added to SA & RA Sides (Table 4) 1735 CFM RADBT 75 F
FLA 24.95 ampsTotal SA Fan Flow 13865 CFM 25% of largest motor amps 3.5 amps 81.00%Total RA Fan Flow 11510 CFM OAgr 0.0182 gr Total MCA 28.45 amps 1.1 77.00%
Eff. SA 71.36% 1.24 71.36%Rotations Per Minute 2208.58 RPM RAgr 0.0093 gr 1.25 71.00%Brake Horse Power 15.24 BHP FLA 24.95 ampsActual HP: BHP x 1.1 (for safety factor) 16.76836 HP 75% of largest motor amps 10.5 ampsMinimum HP 20 HP OAh 42.62 BTU/lb Total MCOP 35.45 amps
Eff. SA (%) 71.36%Rotations Per Minute 1740.95 RPM RAh 28.14 BTU/lbBrake Horse Power 6.79 BHPActual HP: BHP x 1.1 (for safety factor) 7.464105 HPMinimum HP 10 HP
Base Efficiency based on RA CFM (Table 1) 81.00%
SA/RA Ratio 1.24SA Efficiency (Table 2) 71.36%
SA (DBT) 80.15 FSA (grains) 82.94 grSA (h) 32.29 BTU/lb
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5WS1008BWater Pressure Drop 10.7 ft.Gallons Per Minute 244 gpmLeaving Air Temp DB 52.4 FLeaving Air Temp WB 52.2 FConnection Size 3 in.
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5MH0702BWater Pressure Drop 3.8 ft.Gallons Per Minute 101 gpmLeaving Air Temp DB 69.6 FLeaving Air Temp WB 69.6 FConnection Size 2 in.
Full Load Amps 24.95 ampsMinimum Circuit Ampacity (MCA) 28.45 ampsMaximum Overcurrent Protection (MOCP) 35.45 amps
General Air Flow Data: AHU 3-1 Internal Static Pressure SA Side Internal Static Pressure RA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 13, 9X, 13XXX (Max. HP = 20 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coil
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - RA Fan: SIZE 13, 9X, 13XXX (Max. HP = 20 HP)
Purge Section
Total Fan Flow
4 4.04 5RPM & BHP Calculation from Charts - Interpolation for SA Side
Supply Air Base Efficiency Calculations
RPM & BHP Calculation from Charts - Interpolation for RA Side1 1.83 2
Supply Air 16700 CFM OA Opening 0.06 in. wg EA Opening 0.11 in. wgOutdoor Air 16700 CFM SA Opening 0.06 in. wg Enthalpy Wheel 0.47 in. wg RPM BHP RPM BHP RPM BHPExhaust Air 12525 CFM Filter 0.3 in. wg Casing 0.3 in. wg 18000 1324 13.47 1405 16.98
Enthalpy Wheel 0.47 in. wg Total 0.88 in. wg 18997 1368.87 14.53 1419.27 16.88 1448.87 18.27Unit Size (from Table 1) EP-35 Cooling Coil 0.38 in. wg 19000 1369 14.53 1449 18.27Choose Model EP Heating Coil 0.06 in. wg
Casing 0.3 in. wg EA Fan Horse Power (10 HP) 14 ampsInternal Static Pressure SA Side 1.63 in. wg Total 1.63 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 ampsInternal Static Pressure EA Side 0.88 in. wg Control Power 6.25 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 3.63 in. wg Total FLA 24.95 amps 14000 936 4.83 1095 7.56Total Static Pressure EA Side (+ 0.5") 1.38 in. wg OADBT 93 F 14822 1019.84 5.36 1062.77 6.44 1132.81 8.20
Eff. SA 66.56% 15000 1038 5.48 1141 8.34Purge/Seal Air Volume - Added to SA & EA Sides (Table 4) 2297 CFM RADBT 75 F FLA 24.95 amps
25% of largest motor amps 3.5 ampsTotal SA Fan Flow 18997 CFM Total MCA 28.45 amps 83.00%Total EA Fan Flow 14822 CFM OAgr 0.0182 gr 1.25 71.00%
Eff. SA 66.56% 1.33 66.56%Rotations Per Minute 1419.27 RPM RAgr 0.0093 gr FLA 24.95 amps 1.4 63.00%Brake Horse Power 16.88 BHP 75% of largest motor amps 10.5 ampsActual HP: BHP x 1.1 (for safety factor) 18.570844 HP Total MCOP 35.45 ampsMinimum HP 20 HP OAh 42.62 BTU/lb
Eff. SA (%) 66.56%Rotations Per Minute 1062.77 RPM RAh 28.14 BTU/lbBrake Horse Power 6.44 BHPActual HP: BHP x 1.1 (for safety factor) 7.0865375 HPMinimum HP 10 HP
Base Efficiency based on EA CFM (Table 1) 83.00%
SA/EA Ratio 1.33SA Efficiency (Table 2) 66.56%
SA (DBT) 81.02 FSA (grains) 85.94 grSA (h) 32.98 BTU/lb
Finned Height 111 in.Finned Width 66 in.Feet Per Minute 354 fpmModel Number 5WS1008BWater Pressure Drop 6.6 ft.Gallons Per Minute 313 gpmLeaving Air Temp DB 52.2 FLeaving Air Temp WB 52.1 FConnection Size 2.5 in.
Finned Height 111 in.Finned Width 66 in.Feet Per Minute 354 fpmModel Number 5MH0702BWater Pressure Drop 5.8 ft.Gallons Per Minute 130 gpmLeaving Air Temp DB 74.5 FLeaving Air Temp WB 74.5 FConnection Size 2 in.
Full Load Amps 24.95 ampsMinimum Circuit Ampacity (MCA) 28.45 ampsMaximum Overcurrent Protection (MOCP) 35.45 amps
General Air Flow Data: AHU 3-2 Internal Static Pressure SA Side Internal Static Pressure EA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 24, 18X, 13XX (Max. HP = 50 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coil
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
Fan Data Tables - EA Fan: SIZE 24, 18X, 13XX (Max. HP = 50 HP)
Purge Section
Total Fan Flow
RPM & BHP Calculation from Charts - Interpolation for SA Side3 3.63 4
Supply Air Base Efficiency Calculations
RPM & BHP Calculation from Charts - Interpolation for EA Side1 1.38 2
Supply Air 11200 CFM OA Opening 0.08 in. wg EA Opening 0.24 in. wgOutdoor Air 11200 CFM SA Opening 0.08 in. wg Enthalpy Wheel 0.55 in. wg RPM BHP RPM BHP RPM BHPExhaust Air 8400 CFM Filter 0.41 in. wg Casing 0.3 in. wg 12600 1492 11.56 1589 14.21
Enthalpy Wheel 0.55 in. wg Total 1.09 in. wg 12935 1511.26 11.94 1515.08 12.05 1606.59 14.65Unit Size (from Table 1) EP-24 Cooling Coil 0.53 in. wg 13400 1538 12.47 1631 15.25Choose Model EP Heating Coil 0.09 in. wg
Casing 0.3 in. wg EA Fan Horse Power (5 HP) 7.6 ampsInternal Static Pressure SA Side 2.04 in. wg Total 2.04 in. wg Wheel VFD (Yaskawa Model CIMR - V7AM20P4) 4.7 ampsInternal Static Pressure EA Side 1.09 in. wg Control Power 6.25 amps RPM BHP RPM BHP RPM BHPTotal Static Pressure SA Side (+ 2") 4.04 in. wg Total FLA 18.55 amps 9400 942 2.53 1083 4.36Total Static Pressure EA Side (+ 0.5") 1.59 in. wg OADBT 93 F 10135 992.53 2.87 1071.93 4.01 1127.10 4.80
Eff. SA 67.06% 10200 997 2.9 1131 4.84Purge/Seal Air Volume - Added to SA & EA Sides (Table 4) 1735 CFM RADBT 75 F FLA 18.55 amps
25% of largest motor amps 1.9 ampsTotal SA Fan Flow 12935 CFM Total MCA 20.45 amps 83.00% 84.00% 85.00%Total EA Fan Flow 10135 CFM OAgr 0.0182 gr 1.25 71.00% 72.00%
Eff. SA 67.06% 1.33 66.56% 67.06% 67.56%Rotations Per Minute 1515.08 RPM RAgr 0.0093 gr FLA 18.55 amps 1.4 63.00% 64.00%Brake Horse Power 12.05 BHP 75% of largest motor amps 5.7 ampsActual HP: BHP x 1.1 (for safety factor) 13.254164 HP Total MCOP 24.25 ampsMinimum HP 15 HP OAh 42.62 BTU/lb
Eff. SA (%) 67.06%Rotations Per Minute 1071.93 RPM RAh 28.14 BTU/lbBrake Horse Power 4.01 BHPActual HP: BHP x 1.1 (for safety factor) 4.4101908 HPMinimum HP 5 HP
Base Efficiency based on EA CFM (Table 1) 84.00%
SA/EA Ratio 1.33SA Efficiency (Table 2) 67.06%
SA (DBT) 80.93 FSA (grains) 85.62 grSA (h) 32.91 BTU/lb
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5WS1008BWater Pressure Drop 10.7 ft.Gallons Per Minute 244 gpmLeaving Air Temp DB 52.4 FLeaving Air Temp WB 52.2 FConnection Size 3 in.
Finned Height 90 in.Finned Width 54 in.Feet Per Minute 415 fpmModel Number 5MH0702BWater Pressure Drop 3.8 ft.Gallons Per Minute 101 gpmLeaving Air Temp DB 69.6 FLeaving Air Temp WB 69.6 FConnection Size 2 in.
Full Load Amps 18.55 ampsMinimum Circuit Ampacity (MCA) 20.45 ampsMaximum Overcurrent Protection (MOCP) 24.25 amps
Supply Air Base Efficiency Calculations
Full Load Amps (FLA)
Minimum Current Ampacity (MCA)
Maximum Overcurrent Protection (MCOP)
RPM & BHP Calculation from Charts - Interpolation for EA Side1 1.59 2
Fan Data Tables - RA Fan: SIZE 18, 13X, 9XX (Max. HP = 30 HP)
Purge Section
Total Fan Flow
Base Efficiency
Cooling Coil Sizing Data - Increased Capacity EP Chilled Water Coil
Heating Coil Sizing Data - Increased Capacity EP Hot Water Coil
Electrical Sizing Data
Equation 1 from SEMCO Technical Paper
General Air Flow Data: AHU 3-3 Internal Static Pressure SA Side Internal Static Pressure EA Side
Supply Air Efficiency
Fan Data Tables - SA Fan: SIZE 18, 13X, 9XX (Max. HP = 30 HP)
Unit Sizing Information
Static Pressure
SA (DBT) = OADBT - [Eff SA*(OADBT - RADBT)]
SA (h) = OAh - [Eff SA*(OAh - RAh)]
SA (gr) = OAgr - [Eff SA*(OAgr - RAgr)]
RPM & BHP Calculation from Charts - Interpolation for SA Side4 4.04 5
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Charts and Graphs from SEMCO Cutsheets
8 • Packaged Energy Recovery Systems Technical Guide
RA @ 6000 cfmEA opening .15 in.wg.RA opening .15 in.wg.Damper .08 in.wg.RA filter .49 in.wg.Wheel .67 in.wg.Casing .30 in.wg.ISP 1.84 in.wg.
SA @ 7000 cfmOA opening .11 in.wg.SA opening .11 in.wg.Damper .11 in.wg.OA filter .42 in.wg.Wheel .82 in.wg.CHW coil .61 in.wg.HW Coil .10 in.wg.Casing .30 in.wg.ISP 2.58 in.wg.
Determine fan total static pressure (TSP) by adding the ISP to therequired external static pressure.
ex. SA side TSP is 2.58" + 1" = 3.58" RA side TSP is 1.84" + .5" = 2.34"
Select unit size from Table 1 based on the larger supply air (SA) orreturn air (RA) cfm required. Then select the smallest unit which meetsthe required task, since it will provide the most cost-effective selection.
ex. If 7000 cfm SA at 1-inch external static pressure and 6000 cfm RA at.5-inch external static pressure is required, then select size 9 based on7000 cfm.
EP Detailed Selection Procedure
Select unit configuration(EP, EPH, EPC, EPCH or EPHC) basedon project requirements (see page 6 and 7 for guidance).
ex. Select EPHC if a year-round controlled SA condition is desired.
Use Table 4 (page 24) to determine the internal static pressures(ISP) for both the SA and RA sides of the unit.
ex. In an indoor unit, the ISP for the SA side of the EPCH-9 at 7000 cfmis 2.54 inches. The ISP for the RA side of the EP-9 at 6000 cfm is 1.81inches.
TTTTTable 1. able 1. able 1. able 1. able 1. System Capacities andBase Effectiveness
ledoM yticapaCesaB%-evitceffE
ssen
3-PE000,2woL005,2diM000,3hgiH
875747
5-PE000,3woL000,4diM005,4hgiH
187767
9-PE005,4woL000,6diM000,8hgiH
288757
31-PE000,6woL000,8diM000,01hgiH
480877
81-PE000,8woL000,01diM000,51hgiH
582867
42-PE000,11woL000,41diM000,81hgiH
481877
82-PE000,51woL000,81diM000,32hgiH
289767
53-PE000,81woL000,22diM000,72hgiH
380877
34-PE000,62woL000,03diM000,04hgiH
088757
2
1
3
Use Table 4 again to determine purge/seal air volume to be addedto each designed airflow to determine total fan airflow.
ex. EP-9 purge/seal volume is 906 cfm.
Total SA fan flow = 7906 cfmTotal RA fan flow = 6906 cfm
5
4
Packaged Energy Recovery Systems Technical Guide • 9
Determine motor horsepower based on the unit’s basic fan size,total fan airflow and TSP from the fan data table on pages 26-31.The minimum motor horsepower is the fan brake horsepower plus10 percent to allow for drive loss and safety factors. An optionalextended range fan (shown as size X or XX) is offered for most modelsizes. This fan offers horsepower savings depending on exactperformance required. However, an increase in unit size is possible.
ex. Using a size 9 fan, the SA fan brake horsepower is 6.9 based on 7900cfm at 3.58 in.wg. static pressure. This would require a minimum 10 hpmotor. The RA fan brake horsepower is 4.0 based on 6900 cfm at 2.34in.wg. static pressure. This would require a minimum of 5.0 hp motor.
Find the base wheel effectiveness percentage from Table 1 based onthe model selected and the smaller SA or RA cfm.
ex. Base effectiveness for EP-9 based on 6000 cfm is 78 percent.
Determine summer and winter SA conditions, based on designtemperatures and SA efficiency by using Equation 1 from Figure 1.(See page 6 for EP configuration.)
TTTTTable 2. able 2. able 2. able 2. able 2. Supply Air Efficiency Chart Figure 1:
Equation 1:XSA
= XOA - ESA(XOA - XRA)
Equation 2:XEA = XRA + ESA(XOA - XRA)
X = dry bulb temperature (°F) or moisture content (gr/lb) orenthalpy (BTU/lb).
Notes:For SA efficiency use SA cfm/RA cfm.For RA efficiency use RA cfm/SA cfm.
ex. The following design condition example and a 70 percent SA efficiencyare determined below:
Equation 1 for summer dry bulb:SA(DB TEMP) = 95° - .70 (95°-75°) = 81°F
Equation 1 for summer humidity:SA(GRAINS) = 117 gr - .70 (117gr - 63 gr) = 79 gr
Example 1Example 1Example 1Example 1Example 1
Determine SA efficiency from Table 2 and their cfm ratio.
ex. SA efficiency would be approximately 70 percent interpolating fromTable 2 for a base wheel effectiveness of 78 percent and a SA/RA ratio of7000 cfm/6000 cfm = 1.17.
noitidnoC.pmeT
yrDbluB
.pmeTteWbluB
.sbAytidimuH
bl/rg
remmuSAO
°59 °87 711
remmuSAR
°57 °9.16 36
remmuSAS
°18 °7.26 97
retniWAO
°0 °1- 4
retniWAR
°07 °4.15 72
retniWAS
°94 °2.93 02
maertsriAwolFoitaR
%nissenevitceffEesaB
57 77 97 18 38 58
07.0 18 38 68 88 09 29
08.0 97 18 38 58 78 09
09.0 77 97 18 38 58 78
00.1 57 77 97 18 38 58
01.1 96 17 37 57 77 87
52.1 36 56 76 96 17 27
04.1 75 85 06 16 36 46
6
7
8
9
10 • Packaged Energy Recovery Systems Technical Guide
ex. For the EPCH-9, use a 10-hp SA fan, a 7.5-hp RA fan, a variablespeed wheel and 240 volt/3 phase/60-cycle power.
From Electrical Data Table:
Full Load Ampacity10-hp SA fan 28.0 amps5-hp RA fan 15.2 ampsWheel VFD 4.4 ampsControl power 0.8 ampsTotal FLA’s 48.4 amps
Minimum Circuit AmpacityFLA from above 48.4 amps25% of largest motor 7.0 ampsTotal MCA 55.4 amps
Maximum Overcurrent Protection(MOCP)FLA from above 48.4 amps75% of largest motor 14.0 ampsMOCP* 62.4 amps
*Select the next larger sized time delay fuse.
Estimate unit SA conditions using the cooling coil table (page33) and the heating coil tables (page 35).
Select unit voltage and determine power requirements from theElectrical Data Table on page 38.
Determine the need for variable speed option on the wheel.
ex. If the 7000 cfm EP unit supplies preconditioned outdoor air directly toan air-conditioned space, the unit's full capacity will be required in thecooling season. On cool days, the unit may have the capacity to provideSA conditions above the desired setpoint design, such as 65°F, with a desired55°F SA setpoint. To provide better control of the unit’s SA conditions,the variable speed option should be selected. This option can also be usedto provide frost protection for the wheel. (See also the SEMCO EnergyRecovery Wheel Technical Guide for a complete discussion of wheelperformance and controls.)
10
11
12
16 • Packaged Energy Recovery Systems Technical Guide
Unit Weights and Dimensions
EP
EPD
Notes :No tes :No tes :No tes :No tes :1. Electric heating coil will add 12” to unit length.2. 12” wider EA side available for increased capacity.3. 24” wider EA side available for increased capacity.4. Add 12” to width for X and XX size EA fan.
5. Add 18” to unit length for X and XX size SA or EA fan.6. Right handed units shown. For left hand unit, mirror downcenterline.
FOR ALL EP MODELSFOR ALL EP MODELSFOR ALL EP MODELSFOR ALL EP MODELSFOR ALL EP MODELS
W L 1L 2L H thgieW1#doM
thgieW2#doM
ledoM ).ni( ).ni( ).ni( ).ni( ).ni( )sbl( )sbl( setoN3-PE 68 361 - - 84 059,4 - 55-PE 68 761 - - 06 057,5 - 59-PE 89 171 - - 27 053,7 - 4,231-PE 89 281 - - 68 004,9 - 4,281-PE 221 091 - - 89 051,21 - 4,242-PE 221 402 - - 011 052,41 - 4,282-PE 641 512 911 69 221 001,01 057,7 4,253-PE 641 132 921 201 431 007,11 056,8 4,234-PE 281 542 731 801 641 001,51 005,01 3
ledoMW L 1L 2L 3L 4L H thgieW
1#doMthgieW2#doM
thgieW3#doM
thgieW4#doM setoN
).ni( ).ni( ).ni( ).ni( ).ni( ).ni( ).ni( )sbl( )sbl( )sbl( )sbl(3-DPE 68 362 - - - - 84 001,7 - - - 5,15-DPE 68 762 - - - - 06 003,8 - - - 5,19-DPE 89 172 - - - - 27 054,01 - - - 4,131-DPE 89 592 - - -- - 68 007,31 - - - 4,181-DPE 221 803 801 002 - - 89 051,7 000,01 - - 4,142-DPE 221 123 511 602 - - 011 054,8 054,11 - - 4,182-DPE 641 433 911 - 311 201 221 001,01 - 008,7 057,7 4,153-DPE 641 053 921 - 311 801 431 007,11 - 005,8 056,8 4,134-DPE 281 463 731 - 311 311 641 001,51 - 051,01 005,01 1
L1 L2
L
W
L1 L2
L
+ -
L3 L4
W
24 • Packaged Energy Recovery Systems Technical Guide
Component Pressure Drop Tables
TTTTTable 4: Single Wheel Unit Pressure Dropsable 4: Single Wheel Unit Pressure Dropsable 4: Single Wheel Unit Pressure Dropsable 4: Single Wheel Unit Pressure Dropsable 4: Single Wheel Unit Pressure Drops
Notes:1. Filter pressure drops based on 2 inches thick, 30% efficient Class II filters.2. Cooling coil pressure drops based on 6 row, 10 fins per inch single-circuited coil.3. Heating coil pressure drops based on 1 row, 6 fins per inch.4. Purge volumes based on 4 inches POA-PRA for wheel.5. Casing losses include fan inlet losses.
eziS 3-PE 5-PE 9-PE 31-PE 81-PEMFC 0002 0052 0003 0003 0004 0054 0054 0006 0008 0006 0008 00001 0008 00001
egrupleehw.htnE 315 345 315 596 596 596 609 609 609 8611 8611 8611 0441 0441mfcnaF 3152 3103 3153 5963 5964 5915 6045 6096 6098 8617 8619 86111 0449 04411
)dooh/w(gninepoAO 20.0 40.0 50.0 20.0 30.0 30.0 10.0 20.0 30.0 10.0 20.0 03.0 10.0 10.0)dooh/w(gninepoAE 40.0 50.0 70.0 80.0 21.0 51.0 70.0 21.0 02.0 80.0 21.0 81.0 70.0 11.0
gninepoAEroAR 01.0 41.0 91.0 90.0 51.0 91.0 90.0 51.0 42.0 90.0 51.0 22.0 90.0 31.0gninepoAOroAS 60.0 01.0 41.0 60.0 11.0 41.0 50.0 80.0 41.0 50.0 80.0 31.0 40.0 60.0
repmaD 70.0 01.0 41.0 50.0 80.0 90.0 50.0 80.0 31.0 60.0 90.0 41.0 40.0 70.0retlifAO 62.0 83.0 15.0 52.0 14.0 05.0 91.0 23.0 35.0 42.0 93.0 85.0 91.0 82.0retlifAR 71.0 62.0 73.0 71.0 03.0 73.0 72.0 94.0 78.0 03.0 25.0 28.0 22.0 43.0leehw.htnE 96.0 29.0 81.1 25.0 47.0 68.0 84.0 76.0 79.0 24.0 75.0 57.0 14.0 15.0liocgnilooC 62.0 04.0 85.0 13.0 65.0 07.0 52.0 44.0 97.0 03.0 35.0 28.0 32.0 63.0liocgnitaeH 40.0 70.0 90.0 50.0 90.0 11.0 40.0 70.0 31.0 50.0 90.0 31.0 40.0 60.0sessolgnisaC 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0erusserpcitats.tnIerusserpcitats.txEerusserpcitatslatoT
eziS 81-PE 42-PE 82-PE 53-PE 34-PEMFC 00051 00011 00041 00081 00051 00581 00032 00081 00522 00072 00062 00003 00004
egrupleehw.htnE 0441 5371 5371 5371 1691 1691 1691 7922 7922 7922 2662 2662 2662mfcnaF 04461 53721 53751 53791 16961 16402 16942 79202 79742 79292 26682 26623 26624
)dooh/w(gninepoAO 30.0 02.0 20.0 40.0 10.0 20.0 30.0 20.0 20.0 30.0 20.0 20.0 40.0)dooh/w(gninepoAE 22.0 90.0 41.0 12.0 01.0 51.0 22.0 11.0 61.0 32.0 11.0 41.0 32.0
gninepoAEroAR 62.0 61.0 42.0 83.0 11.0 71.0 52.0 11.0 71.0 42.0 21.0 51.0 62.0gninepoAOroAS 41.0 50.0 80.0 31.0 60.0 90.0 51.0 60.0 01.0 41.0 60.0 80.0 41.0
repmaD 41.0 60.0 90.0 31.0 70.0 01.0 41.0 60.0 01.0 31.0 90.0 11.0 91.0retlifAO 95.0 72.0 14.0 56.0 62.0 83.0 75.0 03.0 54.0 36.0 82.0 73.0 26.0retlifAR 67.0 13.0 5.0 48.0 03.0 54.0 96.0 43.0 45.0 77.0 14.0 55.0 89.0leehw.htnE 38.0 24.0 55.0 47.0 94.0 26.0 18.0 74.0 06.0 57.0 65.0 76.0 89.0liocgnilooC 08.0 23.0 35.0 78.0 33.0 15.0 87.0 83.0 06.0 68.0 53.0 74.0 38.0liocgnitaeH 31.0 50.0 90.0 41.0 50.0 80.0 31.0 60.0 01.0 41.0 60.0 80.0 31.0sessolgnisaC 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0 03.0erusserpcitats.tnIerusserpcitats.txEerusserpcitatslatoT
Packaged Energy Recovery Systems Technical Guide • 33
Increased Capacity EPC, EPCH, EPHC Chilled Water Coils
Increased Capacity EPC, EPCH, EPHC DX Coils
Design basis: Entering air temperature: 95°Fdb/78°Fwb; entering water temperature: 45°F; water temperature rise:11°±2°F. Dx coil suction temperature: 45°F; refrigerant: R-22. *(2) 2-5/8 & (1) 2-1/8
Design basis: Entering air temperature: 95°Fdb/78°Fwb; entering water temperature: 45°F; water temperature rise: 11°±2°F.
slioCretaWdellihCdradnatS
ledoMyticapaC)mfc(
denniFthgieH
denniFhtdiW
yticoleVecaF)mpf( ledoM
erusserPretaW.tf,porD MPG
.pmeTriAgnivaeLbw/bdF°
noitcennoCTPMeziS
3-PEwoLdeMhgiH
000200520003
ni33 ni03192463634
B8080HW51.97.318.81
534425
8.15/9.159.25/1.359.35/3.45
"5.1
5-PEwoLdeMhgiH
000300040054
ni54 ni03023724084
B8001HW56.9617.91
250787
7.05/8.052.25/3.258.25/35
"2
9-PEwoLdeMhgiH
005400060008
ni45 ni24682183805
B8001LW51.62.0171
87501931
3.05/4.056.15/7.152.35/4.35
"2
31-PEwoLdeMhgiH
0006000800001
ni66 ni24213614915
B8001LW577.114.71
501931471
7.05/8.051.25/2.253.35/5.35
"5.2
81-PEwoLdeMhgiH
00080000100051
ni87 ni45472243315
B8001SW54.51.89.61
931471162
3.05/4.053.15/4.154.35/6.35
"5.2
42-PEwoLdeMhgiH
000110004100081
ni09 ni45623514335
B8001SW59.67.019.61
291442413
1.15/2.152.25/4.256.35/8.35
"3
82-PEwoLdeMhgiH
000510058100032
ni99 ni66133804705
B8001MW53.58.77.11
162223104
7.15/8.157.25/9.259.35/1.45
"5.2
53-PEwoLdeMhgiH
000810052200072
ni111 ni66453244135
B8001MW56.6011.41
313293074
1.25/2.252.35/4.351.45/4.45
"5.2
34-PEwoLdeMhgiH
000620000300004
ni321 ni09833093025
B6001TW54.65.88.41
354325796
5.65/9.653.75/7.757.85/4.95
"3
slioCretaWdellihCdradnatS
ledoMyticapaC)mfc(
denniFthgieH
denniFhtdiW
yticoleVecaF)mpf( ledoM
.pmeTriAgnivaeLbw/bdF°
-cennoCeniLnoitcuSTPMeziSnoit
-cennoCeniLdiuqiLTPMeziSnoit
3-PEwoLdeMhgiH
000200520003
ni33 ni03192463634
B8001NE55.15/5.152.25/2.253.45/3.45
8/5-1)1(8/1-2)1(8/1-2)1(
8/3-1)1(8/3-1)1(8/3-1)1(
5-PEwoLdeMhgiH
000300040054
ni54 ni03023724084
B8001NE51.25/1.252.45/2.45
55/55
8/1-2)1(8/1-2)1(8/5-2)1(
8/3-1)1(8/3-1)1(8/3-1)1(
9-PEwoLdeMhgiH
005400060008
ni45 ni24682183805
B8001NE53.15/3.154.35/4.353.65/3.65
8/1-2)2(8/1-2)2(8/1-2)2(
8/3-1)2(8/3-1)2(8/3-1)2(
31-PEwoLdeMhgiH
0006000800001
ni66 ni24213614915
B8001NE51.25/1.253.45/3.455.65/5.65
8/1-2)2(8/1-2)2(8/5-2)2(
8/3-1)2(8/3-1)2(8/3-1)2(
81-PEwoLdeMhgiH
00080000100051
ni87 ni45472243315
B8001NE56.15/6.159.25/9.258.55/8.55
8/1-2)2(8/5-2)2(8/5-2)2(
8/5-1)2(8/5-1)2(8/5-1)2(
42-PEwoLdeMhgiH
000110004100081
ni09 ni45623514335
B8001NE53.25/3.251.45/1.4565/1.65
8/5-2)2(8/5-2)2(8/1-2)2(
8/5-1)2(8/5-1)2(8/5-1)2(
82-PEwoLdeMhgiH
000510058100032
ni99 ni66133804705
B8001NE51.25/1.255.35/5.354.55/4.55
8/5-2)3(8/5-2)3(8/5-2)3(
8/5-1)3(8/5-1)3(8/5-1)3(
53-PEwoLdeMhgiH
000810052200072
ni111 ni66453244135
B8001NE55.25/5.252.45/2.458.55/8.55
8/5-2)3(8/5-2)3(8/5-2)3(
8/5-1)3(8/5-1)3(8/5-1)3(
34-PEwoLdeMhgiH
000620000300004
ni321 ni09833093025
B8001NE56.25/6.257.35/7.355.65/5.65
*8/5-2)3(8/5-2)3(
8/5-1)3(8/5-1)3(8/5-1)3(
Packaged Energy Recovery Systems Technical Guide • 35
Standard EPH, EPCH, EPHC Hot Water Coils
Increased Capacity EPH, EPCH, EPHC Hot Water Coils
Design Basis: Entering air temperature: 30°Fwb; entering water temperature: 180°F; leaving water temperature: 160±3°F.
Design Basis: Entering air temperature: 0°F; entering water temperature: 180°F; leaving water temperature: 160±3°F.
slioCretaWdellihCdradnatS
ledoMyticapaC)mfc(
denniFthgieH
denniFhtdiW
yticoleVecaF)mpf( ledoM
erusserPretaW.tf,porD MPG
.pmeTriAgnivaeLbw/bdF°
noitcennoCTPMeziS
3-PEwoLdeMhgiH
000205220052
ni33 ni03192723463
B1060HM52.02.03.0
8901
7.663.5646
"5.1
5-PEwoLdeMhgiH
000300040054
ni54 ni03023724084
B1060HM51.02.03.0
216171
6.561.2606
"2
9-PEwoLdeMhgiH
005400060008
ni45 ni24682183805
B1060HM53.05.09.0
713213
4.865616
"5.1
31-PEwoLdeMhgiH
0006000800001
ni66 ni24213614915
B1060HM54.07.01.1
321393
4.764616
"5.1
81-PEwoLdeMhgiH
00080000100051
ni87 ni45472243315
B1060HM56.012.2
139385
1.07765.16
"5.1
42-PEwoLdeMhgiH
000110004100081
ni09 ni45623514335
B1060HM55.08.03.1
344507
862.4616
"2
82-PEwoLdeMhgiH
000510058100032
ni99 ni66133804705
B1060HM53.19.19.2
852798
864.561.23
"5.1
53-PEwoLdeMhgiH
000810052200072
ni111 ni66453244135
B1060HM56.15.26.3
0778501
1.769.365.16
"5.1
34-PEwoLdeMhgiH
000620000300004
ni321 ni09833093025
B1060HM51.31.43.7
101611551
4.863.663.26
"5.1
slioCretaWdellihCdradnatS
ledoMyticapaC)mfc(
denniFthgieH
denniFhtdiW
yticoleVecaF)mpf( ledoM
erusserPretaW.tf,porD MPG
.pmeTriAgnivaeLbw/bdF°
noitcennoCTPMeziS
3-PEwoLdeMhgiH
000205220052
ni33 ni03192723463
B2070HM57.09.02.1
416181
6.676.3717
"5.1
5-PEwoLdeMhgiH
000300040054
ni54 ni03023724084
B2070HM56.013.1
229223
3.471.7646
"2
9-PEwoLdeMhgiH
005400060008
ni45 ni24682183805
B2070HM53.13.21.4
233485
7.871.1746
"5.1
31-PEwoLdeMhgiH
0006000800001
ni66 ni24213614915
B2070HM58.12.39.4
348527
4.67961.36
"5.1
81-PEwoLdeMhgiH
00080000100051
ni87 ni45472243315
B2070HM56.14.22.5
8527801
188.471.46
"2
42-PEwoLdeMhgiH
000110004100081
ni09 ni45623514335
B2070HM54.28.36
97101031
1.676.9636
"2
82-PEwoLdeMhgiH
000510058100032
ni99 ni66133804705
B2070HM55.53.87.21
801431661
3.676.078.46
"5.1
53-PEwoLdeMhgiH
000810052200072
ni111 ni66453244135
B2070HM58.59.87.21
031261591
5.474.8646
"2
34-PEwoLdeMhgiH
000620000300004
ni321 ni09833093025
B2080SM56.25.32.6
881612982
6.086.677.86
"5.2
Packaged Energy Recovery Systems Technical Guide • 39
Electrical Data
Note 1: To determine Minimum Circuit Ampacity, add the FLA’s for each fan motor, the FLA ofthe constant speed wheel motor or the Variable Frequency Drive. Then add the CPT amps and25 percent of the largest motor FLA.
Note 2: Fuse Recommendations: Size fuses at the unit FLA and 75% of the largest motor FLA,then select the next larger size Dual-Element, Time-Delay Fuses (LOW-PEAK©, FUSETRON©or equivalent). If the fuses don’t hold, consult N.E.C. for suitability of larger sized fuses.
Note 3: Use a 3KVA transformer for units with 120 volt lights. Otherwise use the 180 VAtransformer.
PH
spmAdaoLlluFesahP3 muminiMycneiciffEsrotoM.dtS
muminiMycneiciffE
hgiHsrotoM.ffEV802 V042 V084
6/1 6.0 6.0 3.0 - -
4/1 0.1 0.1 5.0 - -
2/1 4.2 2.2 1.1 - -
4/3 5.3 2.3 6.1 37 -
1 6.4 2.4 1.2 6.67 5.28
2/1-1 6.6 0.6 0.3 08 48
2 5.7 8.6 4.3 9.97 48
3 6.01 6.9 8.4 1.38 5.68
5 7.61 2.51 6.7 4.38 5.78
2/1-7 2.42 22 11 6.68 5.88
01 8.03 82 41 2.88 5.98
51 2.64 24 12 3.98 2.09
02 4.95 45 72 4.09 19
52 8.47 86 43 5.09 4.29
03 0.88 08 04 3.98 39
04 411 401 25 09 39
05 - 031 56 2.19 1.49
06 - - 77 29 6.39
57 - - 69 4.29 1.49
001 - - 421 5.29 1.49
PH )DFV(evirDycneuqerFelbairaVØ3 #ledoMawaksaY
2/1 9.3 9.3 - 4P02MA7V-RMIC
2/1 - - 6.1 2P04MA7V-RMIC
1 4.6 4.6 - 7P02MA7V-RMIC
1 - - 7.4 7P04MA7V-RMIC
)TPC(remrofsnarTrewoPlortnoC
AV051 7.0 6.0 4.0
AV005 4.2 0.2 0.1
AVK3 4.41 0.31 52.6
48 • Packaged Energy Recovery Systems Technical Guide
EP
Eq
uip
me
nt
Su
mm
ary
No
tes
:N
ote
s:
No
tes
:N
ote
s:
No
tes
:1.
Max
imum
airf
low
lim
itatio
ns v
ary.
Con
sult
SE
MC
O b
efor
e la
ying
out
uni
t with
vel
ociti
es g
reat
er th
an 5
25 fp
m o
n 2”
filte
rs, 5
25 fp
m o
n co
olin
g co
ils, a
nd 1
100
fpm
on
whe
els.
2. F
or o
ptio
nal w
ide
RA
sid
e, R
A s
ide
com
pone
nts
will
be
the
sam
e as
the
SA
sid
e co
mpo
nent
s.3.
Sin
gle
whe
el p
urge
vol
ume
base
d on
4”
PO
A-P
RA.
eziSledoM
35
931
8142
8253
34
htdiW
52.6852.68
52.8952.89
52.22152.221
52.64152.641
52.281
thgieH
52.0552.26
52.4752.68
52.8952.011
52.22152.431
52.641
egnaRMFC
riAylppuS
1
000,3-000,2005,4-000,3
000,8-005,4000,01-000,6
000,51-000,8000,81-000,11
000,32-000,51000,72-000,81
000,04-000,62egnaR
MFCriA
nruteR1
)dradnats(ezis
naF141
FPA181
FPA122
FPA152
FPA182
FPA123
FPA153
FPA193
FPA144
FPA
)Xnoitpo(
ezisnaF
-102
FPA152
FPA182
FPA123
FPA153
FPA193
FPA144
FPA194
FPA
)XXnoitpo(
ezisnaF
-122
FPA182
FPA123
FPA153
FPA193
FPA144
FPA194
FPA-
)leehw
elgnis(e
mulovegruP
3315
596609
86110441
53711691
79222662
thgiehniflatotlioclooc/tae
Hni
33ni
54ni
45ni
66ni
87ni
09ni
99ni
111ni
321
htgnelniflatotliocl ooc/tae
Hni
03ni
03ni
24ni
24ni
45ni
45ni
66ni
66ni
09
)thgieh(slioc
dekcatsforeb
muN
ni33
)1(ni
54)1(
ni72
)2(ni
33)2(
n93
)2(ni
54)2(
ni33
)3(ni
63)2(
ni24
)2(
--
--
--
-ni
93)1(
ni93
)1(
retlifylppuS
42x42)1(
42x42)2(
42x02)6(
42x42)6(
42x02)3(
42x02)21(
42x42)21(
42x42)51(
42x42)02(
42x21)2(
42x21)2(
--
02x02)9(
-42x21
)3(-
42x21)4(
retlifnruteR
42x42)1(
42x42)2(
42x42)2(
42x42)3(
42x42)6(
42x42)8(
42x02)6(
42x02)51(
42x42)51(
42x21)2(
42x21)2(
42x21)3(
42x21)3(
42x21)2(
-02x02
)9(-
42x21)3(
)sehcni(ezis
rooD13x31
34x3165x31
66x9166x91
66x9166x91
66x9166x91
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix E: Energy and Cost Savings for Desiccant
Wheel Selection
Label Air Flow, cfm Efficiency, %AHU #-# Rated Supply Air h(oa) h(ra) delta h cfm to lb/hr BTU/hr to tons Wheel Efficiency Q(cc,no) Q(cc, yes) Cooling Coil Load Savings Q(cc,no) Q(cc, yes) Cooling Coil Load SavingsAHU 1-1 9695 32.95 21.03 11.92 4.5 12000 66.30% 43.34 14.60 28.73 520.04 175.25 344.79AHU 1-2 7100 41.58 20.47 21.11 4.5 12000 67.56% 56.21 18.23 37.97 674.46 218.80 455.67AHU 1-3 11060 41.58 21.55 20.03 4.5 12000 67.06% 83.07 27.36 55.71 996.89 328.38 668.52AHU 2-1 16270 32.95 22.14 10.81 4.5 12000 72.60% 65.95 18.07 47.88 791.45 216.86 574.60AHU 2-2 13730 41.58 21.55 20.03 4.5 12000 64.56% 103.13 36.55 66.58 1237.55 438.59 798.96AHU 3-1 12130 32.95 21.55 11.4 4.5 12000 71.36% 51.86 14.85 37.00 622.27 178.22 444.05AHU 3-2 16700 41.58 21.49 20.09 4.5 12000 66.56% 125.81 42.07 83.74 1509.76 504.86 1004.90AHU 3-3 11200 42.62 21.55 21.07 4.5 12000 67.06% 88.49 29.15 59.34 1061.93 349.80 712.13
Label Air Flow, cfm Load, tons Load, MBHAHU #-# Rated Supply Air h(oa) h(ra) delta h cfm to lb/hr BTU/hr to tons Q(cc,no) Q(cc,no)AHU 1-1 9695 34.61 21.96 12.65 4.5 12000 45.99 551.89AHU 1-2 7100 41.58 21.96 19.62 4.5 12000 52.24 626.86AHU 1-3 11060 41.58 21.96 19.62 4.5 12000 81.37 976.49AHU 2-1 16270 31.86 21.96 9.9 4.5 12000 60.40 724.83AHU 2-2 13730 41.58 21.96 19.62 4.5 12000 101.02 1212.22AHU 3-1 12130 32.1 21.96 10.14 4.5 12000 46.12 553.49AHU 3-2 16700 41.58 21.96 19.62 4.5 12000 122.87 1474.44AHU 3-3 11200 41.58 21.96 19.62 4.5 12000 82.40 988.85
Label Cost, $ Total Savings, tonsAHU #-# $/ton Q(cc,no) Q(cc, yes) Q(cc, savings) Q(cc,no) Q(cc, yes) SavingsAHU 1-1 $400.00 43.34 14.60 28.73 $17,334.66 $5,841.78 $11,492.88AHU 1-2 $400.00 56.21 18.23 37.97 $22,482.15 $7,293.21 $15,188.94AHU 1-3 $400.00 83.07 27.36 55.71 $33,229.77 $10,945.89 $22,283.88AHU 2-1 $400.00 65.95 18.07 47.88 $26,381.81 $7,228.61 $19,153.19AHU 2-2 $400.00 103.13 36.55 66.58 $41,251.79 $14,619.63 $26,632.15AHU 3-1 $400.00 51.86 14.85 37.00 $20,742.30 $5,940.59 $14,801.71AHU 3-2 $400.00 125.81 42.07 83.74 $50,325.45 $16,828.83 $33,496.62AHU 3-3 $400.00 88.49 29.15 59.34 $35,397.60 $11,659.97 $23,737.63
617.86 200.90 416.97 $247,145.52 $80,358.52 $166,787.00TOTALS
CALCULATED COOLING COIL LOAD
ACTUAL COOLING COIL LOADEnthalpy, BTU/lb
Enthalpy, BTU/lb Load, tons Load, MBH
Load, tons
Conversion Factors
Conversion Factors
COST INFORMATIONCost, $
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix F: Existing Panel Boards
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix G: New Panel Boards with Desiccant
Wheel (Electrical Redesign)
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
Appendix H: Acoustical Calculations and Graphs
(Acoustical Analysis)
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-1: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 22 25 27 252017 23 AHU 1-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU11.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU11.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU11.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-1: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 22 25 27 252017 23 AHU 1-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU11.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU11.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU11.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-2: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 22 25 27 252017 23 AHU 1-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU12.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU12.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU12.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-2: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 22 25 27 252017 23 AHU 1-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU12.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU12.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU12.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-3: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 24 27 28 242119 25 AHU 1-3 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU13.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU13.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU13.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 1-3: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 24 27 28 242119 25 AHU 1-3 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU13.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU13.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU13.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 2-1: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 26 30 31 272422 27 AHU 2-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU21.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU21.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU21.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 2-1: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 26 30 31 272422 27 AHU 2-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU21.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU21.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU21.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 2-2: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 26 30 31 272422 27 AHU 2-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU22.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU22.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU22.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 2-2: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 26 30 31 272422 27 AHU 2-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU22.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU22.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU22.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-1: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 24 28 29 252220 25 AHU 3-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU31.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU31.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU31.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-1: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 24 28 29 252220 25 AHU 3-1 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU31.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU31.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU31.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-2: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 31 34 35 302725 32 AHU 3-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU32.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU32.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU32.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-2: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 31 34 35 302725 32 AHU 3-2 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU32.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU32.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU32.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-3: Main Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 30 33 33 292724 27 AHU 3-3 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -3 -1 -1 -1-5-8 -1
52 49 42 35 2656 55NC 45 RC 42(N) 49 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU33.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1:
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU33.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 45
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU33.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 42(N)
Reference Line
Maximum Permitted Deviation
Amy E. Pastor Florida Institute of Technology Mechanical Option F.W. Olin Physical Science Laboratory
Olin Science Laboratory Appendix Thesis Advisor – Dr. Jim Freihaut April 8, 2005
AHU 3-3: Branch Duct Ratings and Curves
FIT Olin Physical Science LabMelbourne, FloridaFlorida Institute of Technology502075
Climate Changer 30 33 33 292724 27 AHU 3-3 Straight Duct(RU2) -1 0 0 0-1-2 0 Wall or Floor -4 -5 -5 -502 -5 Trans Loss Val -35 -37 -41 -46-34-32 -49 Rec Rm Corr -6 -7 -8 -8-7-7 -8 Junction (T,atten.) -4 -4 -4 -4-4-4 -4SubSum 5555555 55 50 43 366064 27 Regenerated sound from junction.SubSum 27364350556064 Straight Duct(RU2) -11 -2 -2 -2-16-24 -2
44 48 41 34 2540 44NC 44 RC 41(N) 47 dBARATINGS
Amy E. Pastor 04/04/05P:\THESIS\AHU33.PDT 1
THE TRANE ACOUSTICS PROGRAM
Project Name:Location:
Building Owner:Project Number:
Comments:
Octave Band DataLINE ELEMENT 250125 1k 2k 4k50063 COMMENTS
SUM
Run Date:Program User:Page Number:File Name:
Path Table View -- Path1 Branch1 :
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU33.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
NC = 44
Trane Acoustics Program Project Name: FIT Olin Physical Science Lab Location: Melbourne, Florida Building Owner: Florida Institute of Technology Program User: Amy E. Pastor File Name: P:\THESIS\AHU33.PDT Run Date: 04/04/05Project Number: 502075
Path View Graph--Path1
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LEV
EL,dB
re 20 MIC
63 125 250 500 1K 2K 4K
90
80
70
60
50
40
30
20
10
OCTAVE BAND CENTER FREQUENCY, HZ
RC-50
RC-45
RC-40
RC-35
RC-30
RC-25
Decibel (dB) Levels
RC = 41(N)
Reference Line
Maximum Permitted Deviation