new in stoat 5

Upload: ronywerner

Post on 13-Oct-2015

84 views

Category:

Documents


5 download

TRANSCRIPT

  • 5/22/2018 New in STOAT 5

    1/55

    WRc Ref: UC8616.04March 2013

    New Models in STOAT 5.0

  • 5/22/2018 New in STOAT 5

    2/55

  • 5/22/2018 New in STOAT 5

    3/55

    RESTRICTION: This report has the following limited distribution:

    External: Freely distributable

    WRc plc 2012The contents of this document are subject to copyright and all rights are reserved. No part of this document may bereproduced, stored in a retrieval system or transmitted, in any form or by any means electronic, mechanical,photocopying, recording or otherwise, without the prior written consent of WRc plc.

    This document has been produced by WRc plc.

    Any enquiries relating to this report should be referred to the Project Manager at the following address:

    WRc plc,

    Frankland Road, Blagrove,Swindon, Wiltshire, SN5 8YF

    Telephone: + 44 (0) 1793 865000

    Fax: + 44 (0) 1793 865001Website: www.wrcplc.co.uk

    New Models in STOAT 5.0

    Report No.: UC8616.04

    Date: March 2013

    Authors: J. Dudley, L. Poinel

    Project Manager: L. Poinel

    Project No.: 15504-0

    Client: Enviatec

    Client Manager: Olaf Sterger

  • 5/22/2018 New in STOAT 5

    4/55

  • 5/22/2018 New in STOAT 5

    5/55

    Contents

    1. Overview ................................................................................................................. 12. Pumping .................................................................................................................. 32.1 In-line pumps ........................................................................................................... 32.2 In-tank pumps.......................................................................................................... 73. Aeration ................................................................................................................... 93.1 Surface aeration ...................................................................................................... 93.2 Diffused aeration ................................................................................................... 104. Site Services ......................................................................................................... 134.1 Electricity ............................................................................................................... 134.2 Heat ...................................................................................................................... 155. Fuzzy Logic Control ............................................................................................... 175.1 Inputs .................................................................................................................... 175.2 Rules ..................................................................................................................... 185.3 Configuration ......................................................................................................... 186. Parameter Setter ................................................................................................... 217. Anaerobic Digestion Systems ................................................................................ 237.1 Anaerobic digestionADM1.................................................................................. 247.2 Converters and influents ........................................................................................ 337.3 Gas holder............................................................................................................. 367.4 CHP ...................................................................................................................... 377.5 Gas-fuelled boiler .................................................................................................. 397.6 Heat exchanger model updates ............................................................................. 408. Additional Process Models ..................................................................................... 418.1 Primary sedimentation ........................................................................................... 418.2 Activated sludge with metal adsorption .................................................................. 438.3 Sludge thickener .................................................................................................... 478.4 Instrumentation ...................................................................................................... 479. Additional resources .............................................................................................. 49

  • 5/22/2018 New in STOAT 5

    6/55

    List of Tables

    Table 3.1 Typical blower efficiencies .................................................................... 11Table 6.1 Typical U-values ................................................................................... 32Table 6.2

    Typical heat exchanger fouling data ...................................................... 32

    Table 6.3 Typical heat exchanger fouling data ...................................................... 40Table 7.1 Adsorption rate data ............................................................................. 44Table 7.2 Inhibition effects with nitrifiers ............................................................... 45Table 7.3 Inhibition coefficients for nitrifiers .......................................................... 46Table 7.4 Inhibition effects with heterotrophs ........................................................ 46Table 7.5 Inhibition coefficients for heterotrophs ................................................... 46

    List of Figures

    Figure 2.1 Default pump curves ............................................................................... 4Figure 3.1 Typical blower curves (Source: Gass, 2009) ......................................... 12

  • 5/22/2018 New in STOAT 5

    7/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 1

    1. Overview

    STOAT has had new models added as part of its use in a project studying energy efficiency at

    sewage works and improved process control.

    The new models have been based on:

    a) including major sources of electrical usagepumps and aeration;

    b) minor sources of electrical usage, lumped together as site electrical demand;

    c) fuzzy logic control, adding to the existing support for ladder-logic and PID control; and

    d) anaerobic digestion, updating the anaerobic digestion process to include the new IWA

    ADM1 model, and models for gas storage, heating/electricity generation through CHP,

    and heating through a gas boiler.

    These models are discussed in more detail in the subsequent sections.

    As always when new models are added to STOAT existing databases cannotbe used with

    STOAT. They must be upgraded to the new database structure, using the Database Copy

    utility that is provided with STOAT, shown in the following figure.

    The main user manuals were written for STOAT 4.0 and comprise an installation guide,

    getting started guide, user guide to the process models and a technical reference to the

    mathematical algorithms behind the process models. Updates to these manuals have been

    made in the read me files for STOAT 4.1, 4.2 and 4.3. This read me file, for STOAT 5.0,

    provides additional updates.

  • 5/22/2018 New in STOAT 5

    8/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 2

  • 5/22/2018 New in STOAT 5

    9/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 3

    2. Pumping

    There are two pumping models. One is in-line, where there are stream connections to the

    pump inlet and outlet. This is expected to be the more common pump model, representing

    where a pump is used to transfer flow between process tanks. The second is in-tank, where

    the pump is used to transfer flow within a tank the most common usage is expected to be

    with activated sludge aeration tanks, where MLSS recycles can be represented within the

    aeration tank symbol, rather than needing explicit representation on the flowsheet.

    Name Symbol

    Inline tank

    In-tank pump

    2.1 In-line pumps

    The inline pump has one inlet and one outlet. The flowsheet symbol is

    At the works level all that needs to be specified is a name. Default names are automatically

    generated.

    Data can be specified for operation, sewage calibration and process calibration. Optionally the

    initial condition (average power usage in the last 24 hours) can also be specified.

    2.1.1 Operation

  • 5/22/2018 New in STOAT 5

    10/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 4

    Specify the pump curve. The head is relativeto the maximum head, which is specified later,

    under Process Calibration.The electrical efficiency is that for the pump. The default curve is

    specified at 0, 10, 100% of pump throughput. The curves are given below.

    Figure 2.1 Default pump curves

    2.1.2 Sewage calibration

  • 5/22/2018 New in STOAT 5

    11/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 5

    If a friction factor is to be calculated (specified under Process Calibration) then the nature of

    the liquid needs to be specified. The options for the liquid (rheological model) are:

    Water.

    Water, with a multiplier applied to the calculated water head.

    Sewage sludge, using the equations from the WRc report TR185, How to design

    sewage sludge pumping systems. There are models for activated sludge, primary

    sludge and digested sludge. The equations published in TR185 were developed in the

    late 1970s to early 1980s, and with the widespread use of polymer conditioning these

    equations underpredict the head loss. Therefore, with a polymer-conditioned sludge a

    multiplier, > 1, needs to be specified to increase the TR185-calculated headloss.

    Using the TR185 models for rheology, specify the rheological parameters for the yield

    stress, consistency parameter and flow index.

    The TR185 model is based on a Herschel-Bulkley fluid:

    = 0+ Kn

    Where

    Stress, Pa0 Yield stress, Pa. Modelled in TR185 as 0 = a

    b

    K Consistency parameter. Modelled in TR185 as K = a b

    Shear rate, m/s2. Modelled in TR185 as = a

    b

    n

    Flow index. Modelled in TR185 as n = (1 + a b)-1

    Volume fraction of suspended solids

    The headloss is calculated for Herschel-Bulkley fluids using the method presented in R.A.

    Chilton and R. Stainsby, "Pressure Loss Equations for Laminar and Turbulent Non-Newtonian

    Pipe Flow", J. Hydr. Engrg., ASCE 124 (5), pp. 522-529 (1998). The procedure is

    summarised on the Wikipedia page for Herschel-Bulkley fluids,

    http://en.wikipedia.org/wiki/Herschel-Bulkley_fluid. If the volume fraction is less than 0.004

    (suspended solids less than 4,000 mg/l) then the Einstein approximation is used where the

    fluid is treated as a Newtonian fluid, with the viscosity being that of water multiplied by 1 + 2.5

    http://en.wikipedia.org/wiki/Herschel-Bulkley_fluidhttp://en.wikipedia.org/wiki/Herschel-Bulkley_fluidhttp://en.wikipedia.org/wiki/Herschel-Bulkley_fluid
  • 5/22/2018 New in STOAT 5

    12/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 6

    2.1.3 Process calibration

    Process calibration requires specifying the following:

    Maximum pumpflow (essential if using the friction factorcalculation method).

    Maximum head (essential if using the friction factorcalculation method).

  • 5/22/2018 New in STOAT 5

    13/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 7

    Pipe diameter (essential if using the friction factorcalculation method).

    Pipe length (essential if using the friction factorcalculation method).

    Pipe roughness (select a material from the drop down list; if none are suitable then you

    can use user specifiedand specify the roughness directly).

    Calculation method (the default is fixed headloss; more commonly you would specify

    friction factor).

    Static head (usually the difference in water levels between the body of fluid feeding the

    pump and that of the body of fluid to which the pump discharges).

    Headloss (only if using the fixed headlossmethod).

    There is a long list of possible pipe fittings, where the number of the relevant pipe fittings

    present in the pipe run may be specified. If you are using the fixed headlossmethod then this

    is not needed.

    The pipe fittings are used to add additional velocity heads to the overall headloss the

    headloss is calculated as a multiplier on v2/ (2 g), where v is the velocity in the pipe (m/s),

    and g the gravitational acceleration (9.81 m/s2).

    2.2 In-tank pumps

    In-tanks have the same data requirements as inline tanks. The differences are:

    There are no inlet or outlet connections to be made to the pump symbol.

    Under Process Calibrationthere are four new parameters.

    The first is to specify the process in which the pump is assumed to reside.

    The second is to choose if the flow will be specified directly, or will be taken from

    the internal MLSS recycle flow with activated sludge units. There are no checks

    that the containing process is an activated sludge; the results of using Use

    MLSS recycle with a non-activated sludge unit are undefined, as it will pick up

    whatever data is found for that process at the same location as would be found

    for an activated sludge system.

  • 5/22/2018 New in STOAT 5

    14/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 8

    If Specify flow is used then the pumped flowrate is given. Otherwise, if Use

    MLSS recycle is chosen then the stage from which the MLSS recycle is to be

    pumped should be specified. Should you have two MLSS recycles from a single

    stage then only the first MLSS recycle can be used. WRc have never

    encountered such a system in our experience, or in the published literature foractivated sludge systems.

  • 5/22/2018 New in STOAT 5

    15/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 9

    3. Aeration

    There are two models for activated sludge aeration: surface aerators and diffused air

    systems.

    Name Symbol

    Surface aeration

    Diffused aeration

    3.1 Surface aeration

    Surface aeration requires specifying the correlation used to calculate the power

    efficiency, and to list which activated sludge units are using surface aerator in

    which stages, along with the alpha factor. Standard practice with surface aeration

    systems is to specify an alpha factor of 1.0 unless there is evidence that a different value

    should be used.

  • 5/22/2018 New in STOAT 5

    16/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 10

    There are five correlations to model surface aerators performances:

    The standard correlation was taken from data published in the mid-1980s by the

    Simplex aerator provider, Ames Crosta: this correlation is the recommended

    correlation.

    There are four additional correlations, based on work published in India, in Rao, AR, B

    Kumar and AK Patel, 2007, Relative performance of different shaped surface aeration

    tanks, Water Quality Research Journal of Canada, 42(1). These correlations allow for

    the effect of tank shape to be included. Surface aerators are most commonly installed

    in tanks with a square shape.

    3.2 Diffused aeration

    The diffused aeration model estimates the energy required between the blowerand the diffuser, and therefore also requires an estimate of the blower efficiency.

    At present the blower efficiency is specified as a single value, rather than varying

    with the blower duty.

    The data required are:

    The activated sludge unit and stage where the diffused aeration system is located. It is

    possible to have a system that uses a mixture of surface aerated and diffused air

    systems this was a common configuration in the 1990s, where a surface aerator

    would be used in the first one or two aerated pockets, and the diffused aeration used

    for the rest of the aeration tank.

  • 5/22/2018 New in STOAT 5

    17/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 11

    The correlation for estimating the power efficiency. The choices are Khudenko1,

    Empirical2, Membrane mat

    3or Own coefficients.

    Diffuser submergence.

    Diffuser coverage (percentage of floor area).

    Spacing between diffusers (only essential for the Khudenkocorrelation).

    Use alpha correlationto use a correlation between MLSS and the alpha factor4.

    Use longitudinal variation to use an empirical correlation between location and the

    average alpha factor5.

    Alpha factora value must be specified.

    Model parameters if Own coefficients was chosen. The model is KLa = (a0 Floor

    coveragea1

    + a2)

    QGa3

    , where Floor coverage is in percent, and the gas flow, QG, is in

    m3/d.

    Some typical data6for blower efficiencies are presented in Table 3.1 andFigure 3.1

    Table 3.1 Typical blower efficiencies

    Blower typeNominal blower

    efficiency, %

    Nominal turndown,

    % of rated flow

    Positive displacement with 60 to 45 50

    1 B.M. Khudenko and E. Shpirt, 1986 ,Hydrodynamic parameters of diffused air systems. Water Research, 20(7),

    905-915.2 Envirosim correlation.

    http://www.envirosim.com/products/bw32/techref/correlationformasstransfercoefficient.php3 Jolly, M., Green, S., Wallis-Lage, C. and Buchanan, A. (2010), Energy saving in activated sludge plants by the

    use of more efficient fine bubble diffusers. Water and Environment Journal, 24: 5864. doi: 10.1111/j.1747-

    6593.2009.00164.x.4 Gunder, B, 2001, The Membrane Coupled-Activated Sludge Process in Municipal Wastewater Treatment,

    Technomic Publishing, Lancaster, USA.5 Assumption: alpha factor increases linearly with distance, and close to 0.9 by the end. The alpha-factor from

    the correlation is an average value. The alpha factor is then calculated from the linear model V = 0.5: alpha =

    calculated from correlation; V = 1.0: alpha = 0.9.6 Gass, JV, 2009, Scoping the Energy Savings Opportunities in Municipal Wastewater Treatment, presentation at

    Consortium for Energy Efficiency, July 2009. Available online at: http://www.cee1.org/cee/mtg/09-

    09mtg/files/WWWGass.pdf.

  • 5/22/2018 New in STOAT 5

    18/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 12

    Blower typeNominal blower

    efficiency, %

    Nominal turndown,

    % of rated flow

    VFD

    Multi-stage centrifugal 76 to 50 60

    Single-stage integrally geared

    centrifugal80 to 72 45

    High speed turbo gearless

    centrifugal80 to 72 50

    Figure 3.1 Typical blower curves (Source: Gass, 2009)

  • 5/22/2018 New in STOAT 5

    19/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 13

    4. Site Services

    Site services are used to represent the sum of minor electricity requirements and space

    heating requirements. The site electricity process is also used to calculate the site electricity

    costs.

    Name Symbol

    Site electricity

    Site heat

    4.1 Electricity

    There should be only one electricity demand process on a flowsheet.

    Data is provided in two places. Major power users are specified under Process

    Calibration, and minor users under Operation.

    Process Calibration provides a simple list of pumps and aerators already included in the

    works model, and all that is required is to select those required. Usually all would be selected.

    Operation then adds the total electricity demand from minor users. This can be specified

    varying with time.

    Electricity charges are specified from the menu item Utilities.

  • 5/22/2018 New in STOAT 5

    20/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 14

    This brings up the data entry form.

    Here you can specify the currency unit (STOAT should pick up your local currency unit, but

    this can be over-ridden if required).

    The electricity charges are based on an amalgamation of several UK electricity-providing

    companies, to ensure that most options are covered. The charges are typically based on:

    An availability charge, based on the contracted power, which is then charged on the

    contracted power demand, whether used or not. STOAT currently ignores this element

    of the cost.

    An excess demand charge, should the site require more than the contracted demand.

    The default contracted demand is 0 kW, so the contracted demand mustbe changed to

    reflect the values used at the site under investigation.

    Demand-based charges:

    A price for usage during peak winter daytime hours (for which the months and

    time where the charge is in operation should be specified; the defaults are

  • 5/22/2018 New in STOAT 5

    21/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 15

    December February, 16:00 19:00. The possibility of having a summer peak

    demand is also available.

    A price for usage during winter, for weekends, day and night. The winter months

    need not be exactly the same as the peak winter months. The defaults areNovemberMarch. Night is defined as 00:0007:00.

    Fossil fuel and climate change charges.

    If electricity is generated on site and sent back to the grid then there is a feed-in-

    tariff available to generate income for the site.

    4.2 Heat

    The heat demand unit is intended to reflect the requirement for low-grade space

    heating. The model has one inlet and one outlet, for the hot water generated by

    either a gas boiler or CHP unit. As many heat demand processes as are

    required can be used on the flowsheet. The space heat demand is specified as

    it varies with time. The required temperature is also specified this is only used if the

    temperature of the heating fluid is low, as the heating fluid is required to always be at least

    5C hotter than the space heat demand.

  • 5/22/2018 New in STOAT 5

    22/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 16

  • 5/22/2018 New in STOAT 5

    23/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 17

    5. Fuzzy Logic Control

    The fuzzy logic controller allows specification of control systems using either a

    triangular or rectangular fuzzy classification. The rectangular classification will

    behave in a similar manner to a ladder logic controller. Data are specified under

    four categories: inputs, outputs, control rulesand configuration.The fuzzy logic controller was

    based on the work of Tong et al.(1979)7, Stahtaki and King (2007)

    8, Beck et al.(1978)

    9, and

    Tomiello et al.(1999)10

    5.1 Inputs

    Up to 20 inputs may be specified. Each input needs to specify the minimum and maximum

    value. The inputs are regarded as belonging in one of five categories: Very Small (VS), Small

    (S), Average (A), Large (L) or Very Large (VL). With a triangular distribution you need to

    specify the triangular boundaries, upper and lower, denoted by 1 (lower) and 2 (upper). For

    the VS and VL categories you need specify only one boundary, as the other boundary is given

    by the values specified by the minimum and maximum values.

    5.1.1 Outputs

    Up to 20 outputs may also be specified. For each output the minimum and maximum

    permitted value must be specified. There are five control changes defined, for which values

    must be specified for four. The five values are Large Decrease (LD), Small Decrease (SD),

    No change (N), Small Increase (SI) and Large Increase (LI). The values for the changes LD,

    SD, SI and LI must be specified.

    7 Tong, RM, MB Beck and A Latten, 1979, Fuzzy control of the activated sludge wastewater treatment process ,

    International Institute for Applied Systems Analysis report PP-79-7.8 Stathaki, A and RE King, 2007, An intelligent decision support system for wastewater treatment plant

    management, International Journal of Engineering Simulation 8(1).9 Beck, MB, A Latten and RM Tong, 1978, Modelling and operational control of the activated sludge process in

    wastewater treatment, International Institute for Applied Systems Analysis report PP-78-10.10

    Tomiello, M, E Perrin, M Roubens and M Crine, 1999, Fuzzy control of an activated sludge process, Second

    European Congress of Chemical Engineering (ECCE 2).

  • 5/22/2018 New in STOAT 5

    24/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 18

    If control changes are specified as absolute values then the changes are specified as the

    change that should be made directly to the output variable. However, if the change to be

    made is relativethen the changes are specified aspercentage changes.

    5.2 Rules

    Each output can be associated with up to four rules, to indicate that the relevant output

    change (LD, SD, SI or LI) should be made. The associated values for the inputs (VS, S, A, L,

    VL) should be specified, where there is a sixth possible value for each input, Ignore (I). When

    you look at the results the change for each output will be given as LD, etc., and also as NF

    (rule Not Firedi.e. no change made to the output value).

    5.3 Configuration

    There are three configuration parameters:

    The first is the sampling interval. Too small a sampling interval will slow down the

    simulation and may result in many small changes to the output. Too large a sampling

    value will result in poor control. Typical sampling periods for process control are 10

    minutes1 hour; the default is 15 minutes.

  • 5/22/2018 New in STOAT 5

    25/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 19

    The second configuration parameter is whether the fuzzy values should be interpreted

    as a rectangular system (where fuzzy values cannot overlap), or triangular. The

    rectangular approach will behave in a similar manner to a ladder logic controller; but the

    ladder logic control assigns the output a fixed value; the fuzzy controller allows relative

    changes to the output value, rather than fixed values. The default is the triangularapproach, which allows for an input value to be present in two categories (for example,

    low and medium), with different probabilities for belonging in each category.

    The final configuration parameter is whether the changes that are made should be

    absolute or relative.

  • 5/22/2018 New in STOAT 5

    26/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 20

  • 5/22/2018 New in STOAT 5

    27/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 21

    6. Parameter Setter

    The parameter setter allows changes with time for parameters that are

    normally kept constant, such as the sewage and process calibration

    parameters.

    Up to ten inputs may be specified using the Connectivity menu. As usual, the entry form

    requires specifying the name of the process, the stage (if the parameter does not depend

    upon the stage then this must be specified, but will not be used) and finally the parameter that

    will be changed.

    Then, under the Operation menu, the values that will be used for a given time must be

    specified. Up to 4,320 values may be specified (sufficient for changing values every two hours

    for 360 days).

  • 5/22/2018 New in STOAT 5

    28/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 22

  • 5/22/2018 New in STOAT 5

    29/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 23

    7. Anaerobic Digestion Systems

    STOAT has always had anaerobic digestion models, but these have mostly been based on

    BOD. There has been one COD model, that of Droste. The IWA has published a large

    consensus model for anaerobic digestion, the Anaerobic Digestion Model Number 1 (ADM1),

    which is now seen as the preferred model for anaerobic digestion. This model has been

    implemented in STOAT v5.0, but as a different process symbol to the standard anaerobic

    digestion models.

    The standard anaerobic digestion models (the BOD-based models first orderand Mosey, and

    the COD model Droste) looked at the sludge stream, and provided no means of using the

    digester gas, other than as reported production values in the digester. In addition they had no

    link between the digester temperature and the heating requirements for the digester. The newmodel has provided a new digester symbol to allow for a gas outlet from the digester, and for

    a heating water inlet and outlet. The new model is referred to in the process toolbox as

    Anaerobic Digester, while the older models have their symbol labelled as Mesophilic

    Anaerobic Digester.

    Name Symbol

    Anaerobic digestion ADM1

    Digester gas monitoring

    Gas holder

    Gas holder flow splitter

    ASM1 to ADM1 conversion

    ADM1 to ASM1 conversion

    Food waste to ASM1conversion

    CHP engine

  • 5/22/2018 New in STOAT 5

    30/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 24

    Name Symbol

    Gas boiler

    Heat exchanger

    7.1 Anaerobic digestion ADM1

    The anaerobic digester has two inlets and three outlets. The inlets are feed sudge

    (the upper inlet on the left) and heating fluid (the lower inlet on the left; the heating

    fluid may be water, if internal heating is used, or sludge, if external heating is

    used). The outlets are digester gas (on the top), digested sludge (the upper outleft

    on the right) and heating fluid (the lower outlet on the left).

    The IWA modelling community has released three reference implementaions, described as

    ODE, DAE1 and DAE2. All three are available in STOAT, with DAE2 recommended for most

    uses. The ODE model treats organic acid dissassociation (for example, acetic acid,

    CH3COOH CH3COO- + H

    =) and hydrogen exchange between the gas and air as being

    time-varying. DAE1 treats the acid dissassociation equations as being sufficiently fast that

    they can be taken as being at equilibrium, while DAE2 assumes that both the acid

    dissassociation and the hydgrogen mass transfer are at equilibrium. The difference in model

    predictions between the three is usually negligible, with ODE being the most accurate and

    DAE2 the fastest to run. ODE requires the use of a stiffsolver, and WRc recommend the use

    of either RK-Chebychev or ROCK2 as the solvers; with a large flowsheet the use of ODE as

    the anaerboic digester model can result in the simulation taking hours to model hours, and a

    switch to DAE2 is advised. ODE usually runs at an acceptable speed when it is used as an

    anaerobic digester model separate from the associated sewage works.

    The total tank volumesludge plus gasshould be specified under Names and dimensions.

    The total volume is only used if, under Process calibration, you specify that the digester has a

    fixed, rather than floating roof.

    There is a large amount of calibration data that can be specified for the ADM1 model,

    available under Sewage calibrationand Process calibration.There is little guidance from the

  • 5/22/2018 New in STOAT 5

    31/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 25

    IWA ADM1 report on how to calibrate the model, and most users appear to leave the model

    parameters at the default values. The parameters are given in the following screen captures.

    7.1.1 Sewage calibration

    The standard ADM1 model has kinetic parameters that are independent of temperaturethe

    digester is assumed to be controlled at a constant tempearture, and the kinetic parameters

    (mainly growth rates) will be specified as appropriate for that temperature. The ADM1 report

    provides three sets of values, all based on typical sewage sludge: low rate mesophilic single-

    stage digestion (the most common form of anaerobic digestion); high-rate mespophilic single-

    stage digestion; and thermophilic single-stage digestion. WRc have chosen the STOAT model

    defaults based on the low-rate mesophilic parameters. WRc have made on main change in

    the handling of parameters: many of the kinetic parameters have been given a temperature

    dependency, as the STOAT implementation allows for variable temperature (unlike the

    reference implementations described above). A further difference between STOAT and thereference implementations is that the STOAT version allows for varying volume, as some

    digesters have sludge removed before raw sludge is added, to ensure that there is no short-

    circuiting and contaminantion of the treated sludge.

    The standard temperature variation model is:

    (kinetic parameter) = A1exp(-B1(T30))A2exp(-B2(T30)),

    Where T is the temperature in Celsius, and A1, B1, A2and B2are the model parameters. The

    default parameter values were chosen to meet the following constraints: to be the same as in

    the IWA ADM1 report at 35C; to have a maximum at 45C, as this is commonly quoted as

    the mesophilic optimal temperature; to be zero at 55C, as mesophilic activity falls off rapidly

    with increasing temperature above the optimal value, and thermophilc bacteria take over as

    the preferred bacterial population; and to be around 10% of the maximum value at 10C,

    reflecting the fall-off in activity with low temperatures.

    For calibrating the model WRc would suggest that the main effort is given to the parameters

    on the first page of the calibration data, for the composition of the composites (seen as

    complex material which wil be broken down into fats (lipids), carbohydrates and proteins). As

    experience is acquired with the use of this model WRc will provide updates on model usage,

    parameter values, and calibration.

  • 5/22/2018 New in STOAT 5

    32/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 26

  • 5/22/2018 New in STOAT 5

    33/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 27

  • 5/22/2018 New in STOAT 5

    34/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 28

  • 5/22/2018 New in STOAT 5

    35/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 29

    7.1.2 Process calibration

    Process calibration specifies parameters relating to the digester construction and operation.

    The volume specified under the Name and dimensions submenu defines the maximum

    volume of the digester, including gas head space.Under Process Calibrationyou can specify

    the sludge volume; the minimum sludge volume if the operating mode is chosen to be draw &

    fill, rather than overflow; and the pump flowrate and operating schedule when using draw &

  • 5/22/2018 New in STOAT 5

    36/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 30

    fill. Note that draw & fill can be set to have an intermittent fill; if the raw sludge sent to the

    digester has a continuous flow then, during the non-fill periods, that sludge will go nowhere,

    and will disappear from the mass balance. You will need to ensure that there are appropriate

    balancing tanks or flow splitters so that sludge is only sent to the digester during a fill period.

    Gas leaving the digester is assumed to pass through a control valve. The reference

    implementation of the ADM1 assumed that the valve had flow varying linearly with the

    pressure difference between the digester and the downstream process. In practice most

    valves have a flow that varies approximately with the square root of the pressure difference,

    unless chocked flow conditions are reached. (Choked flow occurs when the upstream

    pressure is twice the downstream pressureunlikely with most anaerobic digesters.)

    The gas space can be modelled as either a fixed roof (in which case the gas headspace is the

    difference between the total digester volume and the sludge volume), or a floating head (in

    which case the gas head space is constant, and specified here the volume specified underNames and dimensionsis then ignored).

    The mass transfer rate of gases from the sludge to the gas space can be calculated using

    either the same value for all gases (the approach used in the IWA reference implementation)

    or varying with the inverse of the square root of the diffusivity (which is the case with most

    mass transfer models).

    The digester temperature can be specified as either fixed or variable; if variable, the heat

    exchange can be either internal (in which case the heating circuit inlet and outlet are assumed

    to be water, and to be used with an internal heat exchanger, for which the transfer area and

    U-value must be specified), or external (in which case the heating circuit inlet and outlet are

    assumed to be sludge taken from, and returned to, the digester).

    If a varying digester temperature is specified then the heat loss from the digester must be

    specified, through the wall and roof areas and U-values. Many older digesters were part-

    buried in the earth, and so there is provision to specify the wall surface areas above and

    below the ground levelabove, the external temperature is that of the air; below, that of the

    ground. Air and ground temperatures are specified under the main menu item Ambient,

    described below.

    If an internal heat exchanger is used it is possible to specify at what rate it will foul, what the

    fully-fouled heat transfer coefficient (U-value) will be, and when it is cleaned.

  • 5/22/2018 New in STOAT 5

    37/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 31

  • 5/22/2018 New in STOAT 5

    38/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 32

    Table 7.1 Typical U-values

    MaterialU-value, W/m

    2 C

    Escritt11

    EPA12

    Fixed steel cover, plate 4.7 5.2

    Fixed concrete cover, 9 thick 2.2 3.3

    Floating cover, Downes-type, with wood composition roof 1.4 1.9

    Concrete wall, 12 thick, exposed to air 3.2 4.9

    Concrete wall, 12 thick, plus 1 air space and 4 brick facing 0.8 1.5

    Concrete wall or floor, 12 thick, exposed to 10 wet earth 0.62

    Concrete wall or floor, 12 thick, exposed to 10 dry earth 0.36 0.35

    Table 7.2 Typical heat exchanger fouling data13

    Description Fouling rate Biofilm thickness Fouling coefficient

    Biofouling @ 300C 0.0125 150m 4 000 W/m

    2K

    Biofouling @ 350C 0.0317 250m 2 400 W/m

    2K

    The overall fouled heat transfer coefficient is calculated from the equation

    1/Ufouled= 1/Uclean+ 1/Ufouling material

    7.1.3 Ambient conditions

    Ambient conditions specify the minimum and maximum air and ground temperatures and the

    relative humidity. An annual profile can be specified the defaults are suitable for the

    Northern UK.

    11 Escritt, LB, 1971, Sewers and sewage works, George Allen and Unwin.

    12 EPA, 1979, Process design manualsludge treatment and disposal.

    13 Bott, TR, 1990, Fouling notebook, Institution of Chemical Engineers, Rugby, UK, ISBN 0852952597. There is

    no direct data suitable for sewage sludge or sewage treatment; WRc have used the graphs presented in the

    book to assess likely fouling rates and reductions in U-value.

  • 5/22/2018 New in STOAT 5

    39/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 33

    7.1.4 Monitoring gas quality

    A moving average can be calculated for the gas quality. There is only one

    calibration parameterthe averaging period.

    7.2 Converters and influents

    The ADM1 model uses a set of determinands that are different to those commonly used in

    modelling sewage treatment. Because of this there is a need to convert between the ADM1

    determinands and those used by activated sludge models. At present the published literature

    has focused on converting between the IWA ASM1 and the ADM1, and therefore this is

    supported in STOAT. As the research literature offers additional conversions, between ADM1

    and ASM2d and ASM3, STOAT will be extended to include these alternates. As there is much

    similarity between ASM1, ASM2 and ASM3 the use of ASM1 is seen as an acceptable

    starting point the main loss of information is phosphorus, as this is ignored by the ADM1,

    and therefore return liquors from the ADM1 will always be treated as having zero phosphate.

    7.2.1 Influents

    Influents are reached in the usual way, by right-clicking over the influent icon and selecting

    Generate profile.

  • 5/22/2018 New in STOAT 5

    40/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 34

    7.2.2 ADM1 influent

    This is available from the influent models, and allows specifying the influent directly using the

    ADM1 determinands.

    7.2.3 Food waste influent

    This is also available from the influent models, and allows specifying the influent using

    determinands that are convenient when given food waste compositions (particulate COD,

    soluble COD, VFAs as COD, ammonia, total inorganic carbon, and cations). This influent

    must be used with the food waste converter to subsequently convert the determinands into

    the ADM1 equivalents for use by the digester model.

    7.2.4 Food waste converter

    The food waste converter is based on work published by Zaher14. The procedure

    makes use of two steps. The first maps the food waste parameters (mainly

    specified as COD) into an intermediate set of parameters suitable for defining

    sewage sludge.

    These parameters are, in their turn, mapped onto the ADM1 determinands. As can be seen

    many of the parameters have a one-to-one relationship between the food waste and the

    ADM1; those that do not generally can be calculated from the assumed stoichiometry ofproteins, lipids and carbohydrates. The default stocihiometry is that commonly quoted for

    these mateials, so that the model should be useable for most food wastes the main

    characterisiation will be that of the particulate COD into proteins, carbohydrates, lipids, and

    organic inerts as part of the first stage of the conversion process.

    14 U Zaher, P. Buffiere, J-P Steyer and S. Chen, 2009, A Procedure to Estimate Proximate Analysis of

    Mixed Organic Wastes, Water Environment Research 81(4) 407415.

  • 5/22/2018 New in STOAT 5

    41/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 35

    7.2.5 ASM1 to ADM1

    The ASM1 to ADM1 converter is used to convert between STOAT COD-based

    sewage streams and the ADM1 determinands. The defaults are those

    recommended by the IWA benchmarking taskforce looking at modelling sewage

    treatment plants. As an extension to the reference version provided by the IWA benchmarking

    group WRc has added phosphorusthe standard (IWA) model ignores phosphorus.

    7.2.6 ADM1 to ASM1

    The ADM1 to ASM1 converter is used to convert between ADM1 determinands

    and STOAT COD-based sewage streams. The defaults are those recommended

    by the IWA benchmarking taskforce looking at modelling sewage treatment plants.

  • 5/22/2018 New in STOAT 5

    42/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 36

    As an extension to the reference version provided by the IWA benchmarking group WRc has

    added phosphorusthe standard (IWA) model ignores phosphorus.

    7.3 Gas holder

    The gas holder has one inletfrom the digester gasand three outlets. These are,

    starting from the top, excess gas lost to the atmosphere (usually this will be sent to

    a flare stack there is no explicit model for a flare stack in STOAT, but the flows

    through this outlet will represent what has been sent to the flare); gas taken from

    the gas holder for benefiial use either to power a boiler or a CHP system; and condensate

    water, which should normally be a value close to zero. Unlike most models in STOAT the gas

    outflow is set by the downstream process the gas flow is set by the demands from the gas

    boiler or CHP engine, rather than by any operating conditions set at the gas holder.

    The flowrate of gas diverted to the flare can be specified; it is also possible to flare gas before

    the gas holder reaches its maximum value. The default values of zero will result in gas being

    flared only when the digester is at maximum volume and the flow of gas in exceeds that of

    gas out. A non-zero value will result in gas being always sent to the flare stack.

  • 5/22/2018 New in STOAT 5

    43/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 37

    7.3.1 Using CHP and a gas boiler

    The standard flow splitters in STOAT set the outlet flow based on the inlet flow.

    However, with the gas holder, the outlet flow is set by the downstream process

    the gas demand from a boiler or CHP engine. If both a CHP engine and a boiler are

    required then a special flow splitter is required, where the outlet is specified by the

    downstream process, and the inlet flow is calculated as the sum of the two outlets.

    7.4 CHP

    The CHP engine has two inlets: for digester gas (upper left) and heating water

    (lower left); and two outlets: for the combustion gas exhaust (lower right) and the

    heated water (upper right).

    The operational settings specify the required electricity demand and the cooling water

    flowrate. The CHP engine is always operated to meet the required electrciity demand, if

    possible.

    The process calibration data specifies the maximum electrical output, and the maximum

    electrical and thermal efficiency. The relative efficiency, as a function of the load, is specified

    as the last set of data in the process calibration menu. The default electrical relative efficiency

    profile was taken from US EPA reports on CHP systems; WRc were unable to locate any

    equivalent data for thermal efficiency, so assumed that the thermal efficiency would be

    constant with load.

    As well as specifying the electrical demand it is possible to specify that there is an additional

    demand that will be taken from the site electricity demand model.

  • 5/22/2018 New in STOAT 5

    44/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 38

    The air:fuel ratio is used to calculate the air consumption, which is added to the mass flow of

    the exhaust combustion gas.

  • 5/22/2018 New in STOAT 5

    45/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 39

    7.5 Gas-fuelled boiler

    The gas boiler has two inlets: digester gas (top left) and heating water (bottom

    left); and two outlets: combustion gas (top right) and heated water (bottom right).

    There is one operational parameter: the flowrate of the heating water.

    Process calibration data requires specifying the maximum boiler ouput and the boiler

    efficiency. The digester gas is calculated by specifying that the boiler operating mode is one

    of the following: constant output (constant at the maximum value); constant outlet

    temperature; a constant water temperature rise; or a constant rise relative to another stream

    typically the outlet from a heat exchanger.

  • 5/22/2018 New in STOAT 5

    46/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 40

    7.6 Heat exchanger model updates

    The heat exchanger models (co- and counter-currrent)have been updated to

    include time-varying fouling of the heat exchanger.

    Table 7.3 Typical heat exchanger fouling data15

    Description Fouling rate Biofilm thickness Fouling coefficient

    Biofouling @ 300C 0.0125 150m 4 000 W/m

    2K

    Biofouling @ 350C 0.0317 250m 2 400 W/m

    2K

    The overall fouled heat transfer coefficient is calculated from the equation:

    1/Ufouled= 1/Uclean+ 1/Ufouling material

    15 Bott, TR, 1990, Fouling notebook, Institution of Chemical Engineers, Rugby, UK, ISBN 0852952597. There is

    no direct data suitable for sewage sludge or sewage treatment; WRc have used the graphs presented in the

    book to assess likely fouling rates and reductions in U-value.

  • 5/22/2018 New in STOAT 5

    47/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 41

    8. Additional Process Models

    8.1 Primary sedimentation

    There is an IWA benchmarking group focused on modelling complete sewage treatment

    plants. This working group has currently developed two benchmark systems, called BSM1

    (Benchmark System 1) and BSM2. BSM2 added a simple primary tank model based on the

    work of Otterpohl and Freund16

    . STOAT provides two implementations of this model. The

    standard Otterpohl model calculates the hydraulic retention time as the differential equation d

    /dt = (Q ) / 3 and the relationship HRT = V / (0.001 + ). The alternate model uses the

    preferred WRc calculation, d HRT/dt = 1 Q HRT / V. Performance of the primary tank is

    based upon an empirical correlation developed by Otterpohl and Freund from data collected

    at German sewage treatment plants.

    There are two extensions to standard models. When industrial determinands are being

    modelled there is a model which will allow metals in the influent to be adsorbed to the solids

    and settle. There is also an extension to the standard primary tank model (PSED3) to allow

    for chemical phosphorus removal to take place within the tank.

    16R. Otterpohl and M. Freund, 1992, Dynamic models for clarifier of activated sludge plants with dry and wetweather flows. Water Science and Technology. 26, pp. 1391-1400.

  • 5/22/2018 New in STOAT 5

    48/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 42

    8.1.1 Otterpohl model

    Sewage calibration is just the settleable fraction of the particulate BOD.

    Under operational data, instead of specifying the primary sludge solids content, the

    percentage of flow removed as sludge is specified.

    8.1.2 Industrial with metal adsorption

    Adsorption and desorption rates are calculated from an empirical correlation based on the

    octanol-water coefficient. This coefficient is specified under the main menu bar, under

    Edit/Component properties.The default components are all organic compounds.

    8.1.3 PSED3 with chemical phosphorus removal

    The sewage calibration parameters have been enhanced with the ASM2 model parametersfor chemical phosphorus reactions.

  • 5/22/2018 New in STOAT 5

    49/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 43

    8.2 Activated sludge with metal adsorption

    8.2.1 Adsorption

    Adsorption was modelled using the following model (Huang et al., 2000)17

    :

    TKpHK

    TKpHK

    CKCCKdt

    dC

    D

    A

    DA

    76.343log0632.00892.00635.1log

    2.1848

    log1285.021.02775.7log

    11010

    11010

    ***

    where

    KA Adsorption rate, mol-1min

    -1

    KD Desorption rate, min-1

    Maximum metal uptake, mg metal/g biomass

    C* Adsorbed metal, mg metal/g biomass

    C Bulk liquid metal concentration, mol/

    NOTE: if C is measured in mg/ then the value for KAshould be divided by 103

    MW, where MW is the molar weight

    pH pH; log10[H+]

    K1 First hydrolysis constant, [M2+

    ] + [H2O] [MOH+] + [H

    +]

    17 Huang, CP, HE Allen, J Wang, LR Takiyama, H Poesponegro, I Poesponegro, D Pirestani, SP Myoda and D

    Crumety, 2000, Chemical Characteristics and Solids Uptake of Heavy Metals in Wastewater Treatment, Water

    Environment Research Foundation report D93013/93-CTS-1ISBN 1-893664-07-04, WERF, Alexandria,

    Virginia, USA

  • 5/22/2018 New in STOAT 5

    50/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 44

    The fundamental equation, the dC*/dt equation, underlies the Langmuir adsorption model,

    which has been found to be the best predictor of the adsorption properties of activated sludge

    systems (Hussein et al., 200418

    ; Ahalya et al,.200319

    ; Tilaki and Alli, 200320

    ; Nelson et al.,

    198121

    ).

    A spreadsheet provided with the Huang et al.report includes the following data.

    Table 8.1 Adsorption rate data

    Metal

    , mg/g

    log10K1Primary sludge

    22

    Secondary

    sludge23

    Cadmium 269.76 191.08 3.9

    Cobalt 141.432 100.181 4.3

    Nickel 140.904 99.807 4.1

    Zinc 156.912 111.146 5

    This correlation is used to partition the four metals between the soluble phase (where the

    metal cannot be removed) and the adsorbed phase (where the metal is removed by

    sedimentation, and subsequent removal of the settled sludge).

    8.2.2 Inhibition effects

    Nitrification inhibition data was taken principally from Richardson (1985)24

    , and is summarised

    in the following table.

    18 Hussein, H, SF Ibrahamin, K Kandeel and H Moawad, 2004, Biosorption of heavy metals from wastewater

    using Pseudomonas sp., Electronic Journal of Biotechnology. Available at:

    www.ejbiotechnology.info/content/vol7/issue1/full/2,accessed 10 July 2006.19

    Ahalya, N, TV Ramachandra and RD Kanamadi, 2003, Biosorption of heavy metals, Research Journal of

    Chemistry and Environment 7(4) 7179.20

    Tilaki, D and R Ali, 2003, Study on removal of cadmium from water environment by adsorption on GAC, BAC

    and biofilter, Diffuse Pollution Conference, Dublin.21

    Nelson, PO, AK Chung and MC Hudson, 1981, Factors affecting the fate of heavy metals in the activated

    sludge process, Journal of the Water Pollution Control Federation, 53(8) 13231333.22

    Correlated as 0.0024 MW g/g.23

    Correlated as 0.0017 MW g/g/.24

    Richardson, M, 1985, Nitrification inhibition in the treatment of sewage, The Royal Society of Chemistry,

    London, ISBN 0-85186-596-8.

    http://www.ejbiotechnology.info/content/vol7/issue1/full/2http://www.ejbiotechnology.info/content/vol7/issue1/full/2
  • 5/22/2018 New in STOAT 5

    51/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 45

    Table 8.2 Inhibition effects with nitrifiers

    Metal Degree Concentration

    Cadmium

    Threshold 10 mg/l

    42% reduction 14.3 mg/g VSS

    Cobalt

    Threshold No data

    50%25

    1 mg/l

    78% 10 mg/l

    Nickel

    Threshold 1 mg/l

    100% 5 mg/l

    88% 12 mg/g VSS

    Zinc Threshold 10 mg/l

    25% 11 mg/ g VSS

    Assuming a simple inhibition model26

    :

    C

    I

    CKC/1

    10

    where KI Inhibition coefficient

    C Inhibitor concentration, mg/

    X Biomass concentration, mg/

    growth rate

    C=0 growth rate with no inhibitor

    25 MLSS concentrations were 360 mg/ for the 1 ppm test and 148 mg/l for the 10 ppm test. Data not for

    nitrification, but used here as a bestestimate.

    Constable, SWC, AF Rozich, R DeHaas and RJ Colvin, 1992, Respirometric investigation of activated sludge

    bioinhibition by cobalt/manganese catalyst, 46th Purdue Industrial Waste Conference Proceedings, Lewis

    Publishers, Chelsea, Michigan, USA.26

    This form of inhibition model has been used previously in the IWA Activated Sludge Models 1, 2 and 3. Henze,

    M, W Gujer, T Mino and M van Loosdrecht, 2000, Activated sludge models ASM1, ASM2, ASM2d and ASM3,

    IWA Publishing, London. ISBN 1-900222-24-8.

  • 5/22/2018 New in STOAT 5

    52/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 46

    The estimates of KIfrom the above data are presented in the table below:

    Table 8.3 Inhibition coefficients for nitrifiers

    Metal KI

    Cadmium 0.02

    Cobalt 0.019

    Nickel 0.0016

    Zinc 0.033

    For heterotrophs the effect of heavy metals is commonly regarded as much less than for

    nitrifiers, and typically is regarded as no significant inhibition (Sujarittnonta and Sherrard,

    1981)27

    However, other studies have found different results.

    Knoetze et al

    28

    .has the following data for a biological phosphorus removal plant (similar to theReading sewage treatment works).

    Table 8.4 Inhibition effects with heterotrophs

    Metal Threshold for general activated sludge,

    mg/l29

    Cadmium 15

    Cobalt No data

    Nickel 15

    Zinc 10

    Knoetze et al.provide data for inhibition. The inhibition coefficients are given in the following

    table:

    Table 8.5 Inhibition coefficients for heterotrophs

    Metal KI

    Cadmium 0.0675

    Cobalt 0.019

    Nickel 0.0675

    Zinc 0.045

    27 Sujarittnonta, S and JH Sherrard, 1981, Activated sludge nickel toxicity studies, Journal of the Water Pollution

    Control Federation 53(8) 13141322.28

    Knoetze, C, TR Davies and SG Wiechers, 1980, Chemical inhibition of biological nutrient removal processes,

    Water SA 6(4) 171180.29

    MLSS c. 2000 mg/. Threshold taken as being a 5% reduction in activity.

  • 5/22/2018 New in STOAT 5

    53/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 47

    8.3 Sludge thickener

    The thickener has one inlet, the feed, and two outlets supernatant and

    thickened sludge.

    The model is based on a simple steady-state mass balance, and had no dynamic behaviour.

    This model was defined as a required model by the IWA benchmarking group. Calibration is

    to specify the thickened sludge concentration and the capture of solids.

    8.4 Instrumentation

    As part of the IWA benchmarking project new controllers have been specified. These

    are a standard sensor, but with the addition of noise, and a sensor in which there is a

    delay between taking the sample and the result being available. The IWA models

    also require a version in which the noise is taken from a data file, to ensure

    repeatable results between simulations, but this has not been implemented in STOAT.

    8.4.1 Noisy probe

    The noisy probe requires specifying the noise parameters, which can be white noise (absolute

    values the noise is independent of the magnitude of the signal), and also noise where the

    noise is proportional to the magnitude of the signal.

  • 5/22/2018 New in STOAT 5

    54/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 48

    8.4.2 Delay sampler

    The delay sampler requires specifying the time delay between the signal being taken and

    being made available, and the noise parameters, which can be white noise (absolute values

    the noise is independent of the magnitude of the signal), and also noise where the noise is

    proportional to the magnitude of the signal.

  • 5/22/2018 New in STOAT 5

    55/55

    Enviatec

    WRc Ref: UC8616.04/15504-0March 2013

    WRc plc 2012 49

    9. Additional resources

    Our German partner, EnviaTec, has a variety of STOAT flowsheets that may be downloaded

    at http://www.enviatec.de/de/de_downloads.htm . The webpage is in German, but may be

    accessed through

    www.microsofttranslator.com/bv.aspx?from=de&to=en&a=www.enviatec.de/de/de_downloads

    to provide an English translation.

    The available flowsheets are

    Pre-denitrification

    Cascade denitrif ication

    Simultaneous denitrification

    Intermittent denitrification

    Alternating denitrification

    Post-denitrification

    SBR system (sequencing batch reactor)

    There are also additional resources on using STOAT, including some in English as well as

    German.

    http://www.enviatec.de/de/de_downloads.htmhttp://www.enviatec.de/de/de_downloads.htmhttp://www.microsofttranslator.com/bv.aspx?from=de&to=en&a=/www.enviatec.de/de/de_downloads.htmhttp://www.microsofttranslator.com/bv.aspx?from=de&to=en&a=/www.enviatec.de/de/de_downloads.htmhttp://www.microsofttranslator.com/bv.aspx?from=de&to=en&a=/www.enviatec.de/de/de_downloads.htmhttp://www.enviatec.de/de/de_downloads.htm