new jersey clean energy collaborative · web viewnew jersey clean energy program protocols to...
TRANSCRIPT
New Jersey Board of Public Utilities
New Jersey Clean Energy Program
Protocols to Measure Resource Savings
DRAFT Revisions toFY2016 Protocols
Date: September 1October 1118, 2017
Release Date: May 31, 2016Board Approval Date: June 29, 2016
New Jersey’s Clean Energy Program Protocols
Table of Contents
Introduction............................................................................................................5Purpose.........................................................................................................................................5Types of Protocols........................................................................................................................6Algorithms....................................................................................................................................8Data and Input Values..................................................................................................................9Baseline Estimates........................................................................................................................9Resource Savings in Current and Future Program Years...........................................................10Prospective Application of the Protocols...................................................................................10Resource Savings.......................................................................................................................10
Electric...................................................................................................................................10Natural Gas...........................................................................................................................11Other Resources.....................................................................................................................12
Adjustments to Energy and Resource Savings...........................................................................12Coincidence with Electric System Peak.................................................................................12Interaction of Energy Savings...............................................................................................12
Calculation of the Value of Resource Savings...........................................................................12Transmission and Distribution System Losses...........................................................................13
Electric Loss Factor..............................................................................................................13Gas Loss Factor.....................................................................................................................13
Calculation of Clean Air Impacts...............................................................................................13Measure Lives............................................................................................................................14Protocols Revision History.........................................................................................................14Protocols for Program Measures................................................................................................14
Residential Electric HVAC..................................................................................15Protocols.....................................................................................................................................15
Central Air Conditioner (A/C) & Air Source Heat Pump (ASHP) & Mini-split (AC or HP)...............................................................................................................................................15Ground Source Heat Pumps (GSHP)....................................................................................16Furnace High Efficiency Fan................................................................................................16Heat Pump Hot Water (HPHW)............................................................................................16
Residential Gas HVAC.........................................................................................21Protocols.....................................................................................................................................21
Furnaces................................................................................................................................21Boilers....................................................................................................................................22Combination Boilers..............................................................................................................23Boiler Reset Controls.............................................................................................................25Storage Water Heaters..........................................................................................................26Instantaneous Water Heaters................................................................................................27
Residential Low Income Program.......................................................................29Protocols.....................................................................................................................................29
Efficient Lighting...................................................................................................................29Hot Water Conservation Measures.......................................................................................29Efficient Refrigerators...........................................................................................................34Air Sealing.............................................................................................................................34Furnace/Boiler Replacement.................................................................................................35Duct Sealing and Repair........................................................................................................35Insulation Upgrades..............................................................................................................35Thermostat Replacement.......................................................................................................35Heating and Cooling Equipment Maintenance Repair/Replacement....................................35Other “Custom” Measures....................................................................................................36
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Residential New Construction Program.............................................................40Protocols.....................................................................................................................................40
Single-Family, Multi-Single (townhomes), Low-Rise Multifamily........................................40Multifamily High Rise (MFHR).............................................................................................40
ENERGY STAR Energy Efficient Products......................................................41Protocols.....................................................................................................................................41
ENERGY STAR Appliances...................................................................................................41ENERGY STAR Lighting........................................................................................................46
Appliance Recycling Program.............................................................................55Protocols.....................................................................................................................................55
Refrigerator/Freezer Retirement Program............................................................................55Home Performance with ENERGY STAR Program........................................57Commercial and Industrial Energy Efficient Construction.............................58
Protocols.....................................................................................................................................58C&I Electric Protocols...............................................................................................................58
Performance Lighting............................................................................................................58Prescriptive Lighting.............................................................................................................62Refrigerated Case LED Lights...............................................................................................64Specialty LED Fixtures..........................................................................................................66Lighting Controls...................................................................................................................68Electronically Commutated Motors for Refrigeration..........................................................69Electric HVAC Systems..........................................................................................................71Fuel Use Economizers...........................................................................................................75Dual Enthalpy Economizers..................................................................................................76Occupancy Controlled Thermostats......................................................................................77Electric Chillers.....................................................................................................................79Variable Frequency Drives....................................................................................................81New and Retrofit Kitchen Hoods with Variable Frequency Drives......................................84Energy Efficient Glass Doors on Vertical Open Refrigerated Cases....................................87Aluminum Night Covers.........................................................................................................88Walk-in Cooler/Freezer Evaporator Fan Control.................................................................89Cooler and Freezer Door Heater Control.............................................................................91Electric Defrost Control........................................................................................................92Novelty Cooler Shutoff...........................................................................................................93
Food Service Measures Protocols..............................................................................................95Electric and Gas Combination Oven/Steamer.......................................................................95Electric and Gas Convection Ovens, Gas Conveyor and Rack Ovens, Steamers, Fryers, and Griddles.................................................................................................................................99Insulated Food Holding Cabinets........................................................................................104Commercial Dishwashers....................................................................................................105Commercial Refrigerators and Freezers.............................................................................106Commercial Ice Machines...................................................................................................107
C&I Gas Protocols....................................................................................................................109Gas Chillers.........................................................................................................................109Gas Fired Desiccants..........................................................................................................111Gas Booster Water Heaters.................................................................................................112Tank Style (Storage)............................................................................................................113Water Heaters......................................................................................................................113Instantaneous Gas Water Heaters.......................................................................................116Prescriptive Boilers.............................................................................................................118
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Prescriptive Furnaces..........................................................................................................120Infrared Heaters..................................................................................................................122Electronic.............................................................................................................................123Fuel Use Economizers.........................................................................................................123
Combined Heat & Power Program...................................................................124Protocols...................................................................................................................................124
Distributed Generation........................................................................................................124Energy Savings Impact........................................................................................................124Emission Reductions............................................................................................................125CHP Emissions Reduction Associated with PJM Grid [2].................................................125
Pay for Performance Program..........................................................................127Protocols...................................................................................................................................127
Direct Install Program.......................................................................................130Protocols...................................................................................................................................130
Electric HVAC Systems........................................................................................................130Variable Frequency Drives..................................................................................................131Refrigeration Measures.......................................................................................................131Gas Water Heating Measures..............................................................................................133Gas Space Heating Measures..............................................................................................133Programmable Thermostats................................................................................................134Boiler Reset Controls...........................................................................................................135Dual Enthalpy Economizers................................................................................................137Electronic Fuel-Use Economizers (Boilers, Furnaces, AC)................................................137Demand-Controlled Ventilation Using CO2 Sensors...........................................................137Low Flow Faucet Aerators, Showerheads, and Pre-rinse Spray Valves.............................138Pipe Insulation.....................................................................................................................142Lighting and Lighting Controls...........................................................................................144
C&I Large Energy Users Incentive Program..................................................146Protocols...................................................................................................................................146
C&I Customer-Tailored Energy Efficiency Pilot Program............................146Protocols...................................................................................................................................146
Renewable Energy Program Protocols.............................................................147SREC Registration Program (SRP)..........................................................................................147
Appendix A Measure Lives...............................................................................148
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
New Jersey Clean Energy ProgramProtocols to Measure Resource Savings
IntroductionThese protocols have been developed to measure resource savings, including electric energy capacity, natural gas, and other resource savings, and to measure electric energy and capacity from renewable energy and distributed generation systems. Specific protocols for determination of the resource savings or generation from each program are presented for each eligible measure and technology.
These protocols use measured and customer data as input values in industry-accepted algorithms. The data and input values for the algorithms come from the program application forms or from standard values. The standard input values are based on the recent impact evaluations and best available measured or industry data applicable for the New Jersey programs when impact evaluations are not available.
PurposeThese protocols were developed for the purpose of determining energy and resource savings for technologies and measures supported by New Jersey’s Clean Energy Program. The protocols will be updated from time to time to reflect the addition of new programs, modifications to existing programs, and the results of future program evaluations. The protocols will be used consistently statewide to assess program impacts and calculate energy and resource savings to:
1. Report to the Board on program performance
2. Provide inputs for planning and cost-effectiveness calculations
3. Provide information to regulators and program administrators for determining eligibility for administrative performance incentives (to the extent that such incentives are approved by the BPU)
4. Assess the environmental benefits of program implementation
Resource savings to be measured include electric energy (kWh) and capacity (kW) savings, natural gas savings (therms), and savings of other resources (oil, propane, water, and maintenance), where applicable. In turn, these resource savings will be used to determine avoided environmental emissions. The Protocols are also utilized to support preliminary estimates of the electric energy and capacity from renewable energy and distributed generation systems and the associated environmental benefits. Note, however, that renewable energy protocols are different from those required for REC certification in the state of New Jersey.
The protocols in this document focus on the determination of the per unit savings for the energy efficiency measures, and the per unit generation for the renewable energy or distributed generation measures, included in the current programs approved by the Board. The number of adopted units to which these per unit savings or avoided generation apply are captured in the program tracking and reporting process, supported by market assessments for some programs. The unit count will reflect the direct participation and, through market assessments, the number of units due to market effects in comparison to a
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
baseline level of adoptions. The protocols report gross savings and generation only. Free riders and free drivers are not addressed in these Protocols. Further research in this area is planned.
The outputs of the Protocols are used to support:
Regulatory reporting Cost-effectiveness analysis Program evaluation Performance incentives for the market managers
These Protocols provide the methods to measure per unit savings for program tracking and reporting. An annual evaluation plan prepared by the NJCEP Evaluation ContractorCenter for Energy, Economic and Environmental Policy (CEEEP) outlines the plans for assessing markets including program progress in transforming markets, and to update key assumptions used in the Protocols to assess program energy impacts. Reporting provides formats and definitions to be used to document program expenditures, participation rates, and program impacts, including energy and resource savings. The program tracking systems, that support program evaluation and reporting, will track and record the number of units adopted due to the program, and assist in documenting the resource savings using the per unit savings values in the Protocols. Cost benefit analyses prepared by NJCEP EvaluationContractorsCEEEP and other evaluation contractors assesses the impact of programs, including market effects, and their relationship to costs in a multi-year analysis.
Types of ProtocolsIn general, energy and demand savings will be measured using measured and customer data as input values in algorithms in the protocols, tracking systems, and information from the program application forms, worksheets, and field tools.
The following table summarizes the spectrum of protocols and approaches to be used for measuring energy and resource savings. No one protocol approach will serve all programs and measures.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Summary of Protocols and ApproachesType of Measure
Type of Protocol General Approach Examples
1. Standard prescriptive measures
Standard formula and standard input values
Number of installed units times standard savings/unit
Residential lighting (number of units installed times standard savings/unit)
2. Measures with important variations in one or more input values (e.g., delta watts, efficiency level, capacity, load, etc.)
Standard formula with one or more site-specific input values
Standard formula in the protocols with one or more input values coming from the application form, worksheet, or field tool (e.g., delta watts, efficiency levels, unit capacity, site-specific load)
Some prescriptive lighting measures (delta watts on the application form times standard operating hours in the protocols)Residential Electric HVAC (change in efficiency level times site-specific capacity times standard operating hours)Field screening tools that use site-specific input valuesCustomer On-Site Renewable Energy
3. Custom or site-specific measures, or measures in complex comprehensive jobs
Site-specific analysis
Greater degree of site-specific analysis, either in the number of site-specific input values, or in the use of special engineering algorithms, including building simulation programs
CustomIndustrial processComplex comprehensive jobs (P4P)CHPCustomer-Tailored Pilot
Three or four systems will work together to ensure accurate data on a given measure:
1. The application form that the customer or customer’s agent submits with basic information.
2. Application worksheets and field tools with more detailed site-specific data, input values, and calculations (for some programs).
3. Program tracking systems that compile data and may do some calculations. 4. Protocols that contain algorithms and rely on standard or site-specific input values
based on measured data. Parts or all of the protocols may ultimately be
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
implemented within the tracking system, the application forms and worksheets, and the field tools.
AlgorithmsThe algorithms that have been developed to calculate the energy and or demand savings are driven by a change in efficiency level for the installed measure compared to a baseline level of efficiency. This change in efficiency is reflected in both demand and energy savings for electric measures and energy savings for gas. Following are the basic algorithms.
Electric Demand Savings = kW = kWbaseline - kWenergy efficient measure
Electric Energy Savings = kW X EFLH
Electric Peak Coincident Demand Savings = kW X Coincidence Factor
Gas Energy Savings = Btuh X EFLH
Where:
EFLH = Equivalent Full Load Hours of operation for the installed measure. Total annual energy use (kWh) of an end use over a range of operating conditions divided by the connected full load of the end use in kW.
Btuh = Btuhbaseline input – Btuhenergy efficient measure input
Other resource savings will be calculated as appropriate.
Specific algorithms for each of the program measures may incorporate additional factors to reflect specific conditions associated with a program or measure. This may include factors to account for coincidence of multiple installations, or interaction between different measures.
When building simulation software programs are used to develop savings estimates for several measures in a comprehensive project, as in the Pay for Performance Program, the specific algorithms used are inherent in the software and account for interaction among measures by design. Detailed Simulation Guidelines have been developed for the Pay for Performance Program and are included in the Pay for Performance Program Guidelines. These Guidelines should be followed when building simulation is used to develop savings estimates. As stated in the Guidelines, simulation software must be compliant with ASHRAE 90.1 2004 Section 11 or Appendix G.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Data and Input ValuesThe input values and algorithms in the protocols and on the program application forms are based on the best available and applicable data for the New Jersey programs. The input values for the algorithms come from the program application forms or from standard values based on measured or industry data.
Many input values, including site-specific data, come directly from the program application forms, worksheets, and field tools. Site-specific data on the application forms are used for measures with important variations in one or more input values (e.g., delta watts, efficiency level, capacity, etc.).
Standard input values are based on the best available measured or industry data, including metered data, measured data from prior evaluations (applied prospectively), field data and program results, and standards from industry associations. The standard values for most commercial and industrial measures are based on recent impact evaluations of New Jersey Programs.
For the standard input assumptions for which metered or measured data were not available, the input values (e.g., delta watts, delta efficiency, equipment capacity, operating hours, coincidence factors) were based on the best available industry data or standards. These input values were based on a review of literature from various industry organizations, equipment manufacturers, and suppliers.
For larger, comprehensive projects, as in the Pay for-Performance Program, measurement and verification (M&V) protocols are followed to better estimate site-specific energy use for the pre- and post-retrofit conditions. Guidelines for developing an M&V plan and protocols to follow for conducting M&V are included in the Pay for Performance Program Guidelines, available on the NJ Office of Clean Energy website at www.njcleanenergy.com. These guidelines and protocols should be followed when M&V is conducted to determine energy use for either the pre- or post-retrofit period.
Program evaluation will be used to assess key data and input values to either confirm that current values should continue to be used or update the values going forward.
Baseline EstimatesFor most efficiency programs and measures, the kW, kWh, and gas energy savings values are based on the energy use of standard new products vs. the high efficiency products promoted through the programs. The approach used for the new programs encourages residential and business consumers to purchase and install high efficiency equipment vs. new standard efficiency equipment. The baseline estimates used in the protocols are documented in the baseline studies or other market information. Baselines will be updated to reflect changing codes, practices and market transformation effects.
For the Direct Install and Low Income programs, some kW, kWh, and gas energy savings values are based on high efficiency equipment versus existing equipment, where the programs specifically target early retirement or upgrades that would not otherwise occur. Protocols for the Direct Install Program include degradation tables to calculate the efficiency of the replaced unit.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
The Pay for Performance Program is a comprehensive program that requires participants to implement energy efficiency improvements that will achieve a minimum of 15% reduction in total source energy consumption. Due to the building simulation and measurement and verification (M&V) requirements associated with this Program, the baseline is the existing energy consumption of the facility, as reported through the U.S. EPA’s Portfolio Manager benchmarking software.
Renewable energy and distributed generation program protocols assume that any electric energy or capacity produced by a renewable energy or distributed generation system displaces electric energy and capacity from the PJM grid.
Resource Savings in Current and Future Program YearsThe Protocols support tracking and reporting the following categories of energy and resource savings:
1. Savings or generation from installations that were completed in the program year and prior program years due to the program’s direct participation and documented market effects.
2. Savings or generation from program participant future adoptions due to program commitments.
3. Savings or generation from future adoptions due to market effects.
Prospective Application of the ProtocolsThe protocols will be applied prospectively. The input values are from the program application forms and standard input values (based on measured data including metered data and evaluation results). The protocols will be updated periodically based on evaluation results and available data, and then applied prospectively for future program years.
Resource Savings
Electric
Protocols have been developed to determine the electric energy and coincident peak demand savings.
Annual Electric energy savings are calculated and then allocated separately by season (summer and winter) and time of day (on-peak and off-peak). Summer coincident peak demand savings are calculated using a demand savings protocol for each measure that includes a coincidence factor. Application of this coincidence factor converts the demand savings of the measure, which may not occur at time of system peak, to demand savings that is expected to occur during the Summer On-Peak period. These periods for energy savings and coincident peak demand savings are defined as:
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Energy Savings Coincident Peak Demand Savings
Summer May through September June through AugustWinter October through April N/ANAOn Peak (Monday - Friday)
8:00 a.m. to 8:00 p.m. 12:00 p.m. to 8:00 p.m.
Off Peak M-F 8:00 p.m. to 8:00 a.m.All day weekends and holidays
NA
The time periods for energy savings and coincident peak demand savings were chosen to best fit the seasonal avoided cost patterns for electric energy and capacity that were used for the energy efficiency program cost effectiveness purposes. For energy, the summer period May through September was selected based on the pattern of avoided costs for energy at the PJM level. In order to keep the complexity of the process for calculating energy savings benefits to a reasonable level by using two time periods, the knee periods for spring and fall were split approximately evenly between the summer and winter periods.
For capacity, the summer period June through August was selected to match the highest avoided costs time period for capacity. The experience in PJM and New Jersey has been that nearly all system peak events occur during these three months. Coincidence factors are used to calculate energy efficiency factors on peak demand. Renewable energy and distributed generation systems are assumed to be operating coincident with the PJM system peak. This assumption will be assessed in the impact evaluation.
Natural Gas
Protocols have been developed to determine the natural gas energy savings on a seasonal basis. The seasonal periods are defined as:
Summer – April through SeptemberWinter – October through March
The time periods for gas savings were chosen to best fit the seasonal avoided gas cost pattern that was used for calculating energy efficiency program benefits for cost effectiveness purposes. However, given the changing seasonal cost patterns for gas supply, different time periods may be more appropriate to reflect a current outlook for the seasonal pattern, if any, at the time that the avoided cost benefits are calculated. The seasonal factors used in the following protocols that correspond to the above time periods reflect either base load or heating load usage. In the case of base load, one twelfth of the annual use is allocated to each month. In the case of heating load, the usage is prorated to each month based on the number of normal degree-days in each month. This approach makes it relatively easy to calculate new seasonal factors to best match different avoided cost patterns.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Other ResourcesSome of the energy savings measures also result in environmental benefits and the saving of other resources. Environmental impacts are quantified based on statewide conversion factors supplied by the NJDEP for electric, gas and oil energy savings. Where identifiable and quantifiable these other key resource savings, such as oil, will be estimated. Oil and propane savings are the major resources that have been identified. If other resources are significantly impacted, they will be included in the resource savings estimates.
Post-Implementation ReviewProgram administrators will review application forms and tracking systems for all measures and conduct field inspections on a sample of installations. For some programs and jobs (e.g., custom, large process, large and complex comprehensive design), post-installation review and on-site verification of a sample of application forms and installations will be used to ensure the reliability of site-specific savings estimates.
Adjustments to Energy and Resource SavingsCoincidence with Electric System PeakCoincidence factors are used to reflect the portion of the connected load savings or generation that is coincident with the electric system peak.
Measure Retention and Persistence of SavingsThe combined effect of measure retention and persistence is the ability of installed measures to maintain the initial level of energy savings or generation over the measure life. Measure retention and persistence effects were accounted for in the metered data that were based on C&I installations over an eight-year period. As a result, some protocols incorporate retention and persistence effects in the other input values. For other measures, if the measure is subject to a reduction in savings or generation over time, the reduction in retention or persistence is accounted for using factors in the calculation of resource savings (e.g., in-service rates for residential lighting measures, degradation of photovoltaic systems).
Interaction of Energy Savings
Interaction of energy savings is accounted for in certain programs as appropriate. For all other programs and measures, interaction of energy savings is zero.
For the Residential New Construction program, the interaction of energy savings is accounted for in the home energy rating tool that compares the efficient building to the baseline or reference building and calculates savings.
For the Residential and Commercial and Industrial Efficient Construction program, the energy savings for lighting is increased by an amount specified in the protocol to account for HVAC interaction.
For commercial and industrial custom measures, interaction where relevant is accounted for in the site-specific analysis. In the Pay for Performance Program, interaction is addressed by the building simulation software program.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Calculation of the Value of Resource SavingsThe calculation of the value of the resources saved is not part of the protocols. The protocols are limited to the determination of the per unit resource savings in physical terms.
In order to calculate the value of the energy savings for reporting and other purposes, the energy savings are determined at the customer level and then increased by the amount of the transmission and distribution losses to reflect the energy savings at the system level. The energy savings at the system level are then multiplied by the appropriate avoided costs to calculate the value of the benefits.
System Savings = (Savings at Customer) x (T&D Loss Factor)Value of Resource Savings = (System Savings) x (System Avoided Costs + Environmental Adder) + (Value of Other Resource Savings)
The value of the benefits for a particular measure will also include the value of the water, oil, maintenance and other resource savings where appropriate. Maintenance savings will be estimated in annual dollars levelized over the life of the measure.
Transmission and Distribution System LossesThe protocols calculate the energy savings at the customer level. These savings need to be increased by the amount of transmission and distribution system losses in order to determine the energy savings at the system level. The following loss factors multiplied by the savings calculated from the protocols will result in savings at the supply level.
Electric Loss FactorThe electric loss factor applied to savings at the customer meter is 1.0811,2076 for both energy and demand. The electric system loss factor was developed to be applicable to statewide programs. Therefore, average system losses at the margin based on a 10 year (2001 to 2010) average of the New Jersey state electricity supply and disposition dataset from the U.S. Energy Information Administration (EIA).
Gas Loss Factor
The gas loss factor is 1.0. The gas system does not have losses in the same sense that the electric system does. All of the gas gets from the “city gate” (delivery point to the distribution system) to the point of use except for unaccounted for gas (such as theft), gas lost due to system leakage or loss of gas that is purged when necessary to make system repairs. Since none of these types of “losses” is affected by a decrease in gas use due to energy efficiency at the customer, there are no losses for which to make any adjustment. Therefore, a system loss factor of 1.0 is appropriate for gas energy efficiency savings.
These electric and gas loss factors reflect losses at the margin and are a consensus of the electric and gas utilities.
1 JPC&L, Summary of reconciliation factors January 1, 2017 – December 31, 2017.2 PSE&G Rate Class & Loss Factor Information
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Calculation of Clean Air ImpactsThe amount of air emission reductions resulting from the energy savings are calculated using the energy savings at the system level and multiplying them by factors developed by the New Jersey Department of Environmental Protection (NJDEP).
System average air emissions reduction factors provided by the NJDEP are:
Electric Emissions FactorsEmissionsProduct Jan 2001–June 2002
July 2003–February 2014 March 2014–Present
CO2 1.1 lbs per kWh saved
1,520 lbs per MWh saved
1,111.79 lbs per MWh saved
NOX 6.42 lbs per metric ton of CO2 saved
2.8 lbs per MWh saved
0.95 lbs per MWh saved
SO2 10.26 lbs per metric ton of CO2 saved
6.5 lbs per MWh saved
2.21 lbs per MWh saved
Hg 0.00005 lbs per metric ton of CO2 saved
0.0000356 lbs per MWh saved
2.11 mg per MWh saved
Gas Emissions FactorsEmissionsProduct
Jan 2001–June 2002 July 2003–Present
CO2 NA 11.7 lbs per therm saved
NOX NA 0.0092 lbs per therm saved
All factors are provided by the NJ Department of Environmental Protection and and are on an average system basis. They will be updated as new factors become available.
Measure LivesMeasure lives are provided in Appendix A for informational purposes and for use in other applications such as reporting lifetime savings or in benefit cost studies that span more than one year. The Pay for Performance Program uses the measure lives as included in Appendix A to determine measure-level and project-level cost effectiveness.
Protocols Revision History
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Revision History of Protocols
Date Issued Reviewer CommentsOctober 2017 ERS See ERS Memo, NJCEP Protocols -
Comparative Measure Life Study and Summary of Measure Changes to NJCEP Protocols, September 5, 2017. Updated October 16, 2017.
Protocols for Program MeasuresThe following pages present measure or project-specific protocols. In those instances where measures are applicable to more than one program, the measures apply to all such programs unless otherwise specified.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Residential Electric HVAC
ProtocolsThe measurement plan for residential high efficiency cooling and heating equipment is based on algorithms that determine a central air conditioners or heat pump’s cooling/heating energy use and peak demand. Input data is based both on fixed assumptions and data supplied from the high efficiency equipment rebate application form. The algorithms also include the calculation of additional energy and demand savings due to the required proper sizing of high efficiency units.
The savings will be allocated to summer/winter and on-peak/off-peak time periods based on load shapes from measured data and industry sources. The allocation factors are documented below in the input value table.
The protocols applicable for this program measure the energy savings directly related to the more efficient hardware installation. Estimates of energy savings due to the proper sizing of the equipment are also included.
The following is an explanation of the algorithms used and the nature and source of all required input data.
Algorithms
Central Air Conditioner (A/C) & Air Source Heat Pump (ASHP)Cooling Energy Consumption and Peak Demand Savings – Central A/C & ASHP (High Efficiency Equipment Only)
Energy Impact (kWh) = CAPY/1000 X (1/SEERb – 1/SEERq ) X EFLHc
Peak Demand Impact (kW) = CAPY/1000 X (1/EERb – 1/EERq ) X CF
Heating Energy Savings – ASHP
Energy Impact (kWh) = CAPY/1000 X (1/HSPFb - 1/HSPFq ) X EFLHh
Cooling Energy Savings for Proper Sizing and QIVkWh p = kWh q * ESF
Cooling Demand Savings for Proper Sizing and QIV
kWp = kWq* DSF
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Cooling Energy Consumption and Demand Savings – Central A/C & ASHP (During Existing System Maintenance)
Energy Impact (kWh) = ((CAPY/(1000 X SEERm)) X EFLHc) X MF
Peak Demand Impact (kW) =((CAPY/(1000 X EERm)) X CF) X MF
Cooling Energy Consumption and Demand Savings– Central A/C & ASHP (Duct Sealing)
Energy Impact (kWh) = (CAPY/ (1000 X SEERq)) X EFLHc X DuctSF
Peak Demand Impact (kW) = ((CAPY/ (1000 X EERq)) X CF) X DuctSF
Ground Source Heat Pumps (GSHP)Cooling Energy (kWh) Savings = CAPY/1000 X (1/(EERg,b X GSER) – (1/ (EERg X GSER))) X EFLHc
Heating Energy (kWh) Savings = CAPY/1000 X (1/(COPg,b X GSOP) – (1/ (COPg X GSOP))) X EFLHh
Peak Demand Impact (kW) = CAPY/1000 X (1/EERg,b – (1/ (EERg X GSPK))) X CF
GSHP DesuperheaterEnergy (kWh) Savings = EDSH
Peak Demand Impact (kW) = PDSH
Furnace High Efficiency FanHeating Energy (kWh) Savings = ((CAPYq X EFLHHT)/100,000 BTU/therm)
X FFSHT
Cooling Energy (kWh) Savings = FFSCL
Solar Domestic Hot Water (augmenting electric resistance DHW)
Heating Energy (kWh) Savings = ESavSDHW
Peak Demand Impact (kW) = DSavSDHW x CFSDHW
Heat Pump Hot Water (HPHW)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Heating Energy (kWh) Savings = ESavHPHW
Peak Demand Impact (kW) = DSavHPHW x CFHPHW
Drain Water Heat Recovery (DWHR)
Heating Energy (kWh) Savings = ESavDWHR
Peak Demand Impact (kW) = DSavDWHR x CFDWHR
Definition of Terms
CAPY = The cooling capacity (output) of the central air conditioner or heat pump being installed. This data is obtained from the Application Form based on the model number.
SEERb = The Seasonal Energy Efficiency Ratio of the Baseline Unit.
SEERq = The Seasonal Energy Efficiency Ratio of the qualifying unit being installed. This data is obtained from the Application Form based on the model number.
SEERm = The Seasonal Energy Efficiency Ratio of the Unit receiving maintenance
EERb = The Energy Efficiency Ratio of the Baseline Unit.
EERq = The Energy Efficiency Ratio of the unit being installed. This data is obtained from the Application Form based on the model number.
EERg = The EER of the ground source heat pump being installed. Note that EERs of GSHPs are measured differently than EERs of air source heat pumps (focusing on entering water temperatures rather than ambient air temperatures). The equivalent SEER of a GSHP can be estimated by multiplying EERg by 1.02.
EERg,b = The EER of a baseline ground source heat pump
GSER = The factor to determine the SEER of a GSHP based on its EER.
EFLH = The Equivalent Full Load Hours of operation for the average unit.
ESF = The Energy Savings Factor or the assumed saving due to proper sizing and proper installation.
MF = The Maintenance Factor or assumed savings due to completing recommended maintenance on installed cooling equipment.
DuctSF = The Duct Sealing Factor or the assumed savings due to proper sealing of all cooling ducts
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
CF = The coincidence factor which equates the installed unit’s connected load to its demand at time of system peak.
DSF = The Demand Savings Factor or the assumed peak demand capacity saved due to proper sizing and proper installation.
HSPFb = The Heating Seasonal Performance Factor of the Baseline Unit.
HSPFq = The Heating Seasonal Performance Factor of the unit being installed. This data is obtained from the Application Form.
COPg = Coefficient of Performance of a GSHP
COPg,b = Baseline Coefficient of Performance of a GSHP
GSOP = The factor to determine the HSPF of a GSHP based on its COP.
GSPK = The factor to convert EERg to the equivalent EER of an air conditioner to enable comparisons to the baseline unit.
EDSH = Assumed savings per desuperheater.
PDSH = Assumed peak demand savings per desuperheater.
ESavSDHW = Assumed energy savings per installed solar domestic hot water system with electric resistance heater backup.
DSavSDHW = Assumed demand savings per installed solar domestic hot water system with electric resistance heater backup.
CAPYYq = Output capacity of the qualifying heating unit in BTUs/hour
EFLHHT = The Equivalent Full Load Hours of operation for the average heating unit
FFSHT = Furnace fan savings (heating mode)
FFSCL = Furnace fan savings (cooling mode)
kWhp = Annual kWh due to proper sizing
kWhq = Annual kWh usage post-program
kWp = Annual kW due to proper sizing
kWq = Annual kW usage post-program
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
ESavHPHW = Assumed energy savings per installed heat pump water heater.
DSavHPHW = Assumed demand savings per installed heat pump water heater.
ESavDWHR = Assumed energy savings per installed drain water heat recovery unit in a household with an electric water heater.
DSavDWHR = Assumed demand savings per installed drain water heat recovery unit in a household with an electric water heater.
The 1000 used in the denominator is used to convert watts to kilowatts.
A summary of the input values and their data sources follows:
Residential Electric HVAC
Sources:[1.] a Survey of New Jersey HVAC equipment distributors, CLEAResult, March 2016
b Federal Register, 76 FR 37408, June 27, 2011
[2.] Average EER for SEER 13 units.[3.] VEIC estimate. VEIC estimate. Consistent with analysis of PEPCo and LIPA,
and conservative relative to ARI.[4.] Xenergy, “New Jersey Residential HVAC Baseline Study”, (Xenergy,
Washington, D.C., November 16, 2001). [5.] NEEP, Mid-Atlantic Technical Reference Manual, May 2010.[6.] Xenergy, “New Jersey Residential HVAC Baseline Study”, (Xenergy,
Washington, D.C., November 16, 2001)[7.] Federal Register, Vol. 66, No. 14, Monday, January 22, 2001/Rules and
Regulations, p. 7170-7200. [8.] Engineering calculation, HSPF/COP=3.413
[9.] VEIC Estimate. Extrapolation of manufacturer data.[10.] VEIC estimate, based on PEPCo assumptions.[11.] VEIC estimate, based on PEPCo assumptions.
[12.] Time period allocation factors used in cost-effectiveness analysis.[13.] Northeast Energy Efficiency Partnerships, Inc., “Benefits of HVAC Contractor
Training”, (February 2006): Appendix C Benefits of HVAC Contractor Training: Field Research Results 03-STAC-01
[14.] Minimum Federal Standard for new Central Air Conditioners between 1990 and 2006
[15.] NJ utility analysis of heating customers, annual gas heating usage[16.] Scott Pigg (Energy Center of Wisconsin), “Electricity Use by New Furnaces: A
Wisconsin Field Study”, Technical Report 230-1, October 2003.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[17.] Ibid., p. 34. ARI charts suggest there are about 20% more full load cooling hours in NJ than southern WI. Thus, average cooling savings in NJ are estimated at 95 to 115
[18.] The same EER to SEER ratio used for SEER 13 units applied to SEER 10 units. EERm = (11.3/13) * 10
VEIC estimate. Conservatively assumes less savings than for QIV because of the retrofit context
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1. Energy savings are estimated based on 2008 SRCC OG300 ratings for a typical 2 panel system with solar storage tank in Newark, NJ with electric DHW backup. Demand savings are estimated based on an estimated electric DHW demand of 2.13kW with 20% CF. Load shape and coincidence factors were developed by VEIC from ASHRAE Standard 90.2 Hot Water Draw Profile and NREL Red Book insulation data for Newark, NJ.
[19.] KEMA, NJ Clean Energy Program Energy Impact Evaluation Protocol Review. 2009.
[20.] Table 1. (Page 2) From “Heat Pump Water Heaters Evaluation of Field Installed Performance.” Steven Winter Associates, Inc. (2012). http://www.ma-eeac.org/Docs/8.1_EMV%20Page/2012/2012%20Residential%20Studies/MA%20RR&LI%20-%202011%20HPWH%20Field%20Evaluation%20Report%20FINAL%206_26_2012.pdf
[21.] VEIC Estimate based upon range derived from FEMP Federal Technology Alert: S9508031.3a (http://www1.eere.energy.gov/femp/pdfs/FTA_res_heat_pump.pdf)
[22.] “Electrical Use, Efficiency, and Peak Demand of Electric Resistance, Heat Pump, Desuperheater, and Solar Hot Water Systems”, http://www.fsec.ucf.edu/en/publications/html/FSEC-PF-215-90/
[23.] 30% savings (from Zaloum, C. Lafrance, M. Gusdorf, J. “Drain Water Heat Recovery Characterization and Modeling” Natural Resources Canada. 2007. Savings vary due to a number of factors including make, model, installation-type, and household behaviors.) multiplied by standard electric resistance water heating baseline annual usage of 4,857 kWh cited in source #23 above.
[24.] Demand savings are estimated based on electric DHW demand of 2.13kW and 20% CF as in cited source #21 adjusting for the proportional difference of 30% savings relative to the 70% solar fraction: 0.426*0.3/0.9 = 0.142.
AHRI directory. Baseline values are the least efficient “Geothermal – Water-to –Air Heat Pumps” active in the
directory, downloaded May 18, 2015.
[25.] Combined space and water heating (Combo)[26.] [27.] Participants installing a qualifying boiler or furnace and a qualifying water
heater at the same time earn a special incentive. For savings calculations, there is no special consideration. The heating system savings are calculated according to the appropriate algorithm and the water heating savings are calculated separately according to the system type.
[28.] Residential Electric HVAC
2. Protocols3. The measurement plan for residential high efficiency cooling and heating
equipment is based on algorithms that determine a central air conditioners or heat
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
pump’s cooling/heating energy use and peak demand. Input data is based both on fixed assumptions and data supplied from the high efficiency equipment rebate application form. The algorithms also include the calculation of additional energy and demand savings due to the required proper sizing of high efficiency units.
4. The savings will be allocated to summer/winter and on-peak/off-peak time periods based on load shapes from measured data and industry sources. The allocation factors are documented below in the input value table.
The protocols applicable for this program measure the energy savings directly related to the more efficient hardware installation. Estimates of energy savings due to the proper sizing of the equipment are also included.
5. The following is an explanation of the algorithms used and the nature and source of all required input data.
6. Central Air Conditioner (A/C) & Air Source Heat Pump (ASHP) & Mini-split (AC or HP)
7.8.[29.] Algorithms9. 10. Cooling Energy and Peak Demand Savings:11. 12. Energy Savings (kWh/yr) = Tons * 12 kBtuh/Ton * (1/SEERb – 1/SEERq ) *
EFLHc 13.
14. Peak Demand Savings (kW) = Tons * 12 kBtuh/Ton * (1/EERb – 1/EERq ) * CF 15. 16. Heating Energy Savings (ASHP and Mini-Split):17. 18. Energy Savings (kWh/yr) = Tons * 12 kBtuh/Ton * (1/HSPFb - 1/HSPFq ) *
EFLHh 19. 20. Proper Sizing and Quality Installation Verification (QIV):21. 22. Energy Savings (kWhp/yr) = kWhq * ESF23. 24. Energy Savings (kWp/yr) = kWq* DSF25.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
26.[30.] During Existing System Maintenance:27.28.[31.] Energy Savings (kWh/yr) = (Tons * 12 kBtuh/Ton * SEERm) * EFLHc * MF29. 30. Peak Demand Savings (kW) =(Tons * 12 kBtuh/Ton * EERm) * CF * MF31. 32. Duct Sealing:33. 34. Energy Savings (kWh/yr) = (Tons * 12 kBtuh/Ton * SEERq) * EFLHc * DuctSF35.36.[32.] Peak Demand Savings (kW) = (Tons * 12 kBtuh/Ton * EERq) * CF *
DuctSF
37. Ground Source Heat Pumps (GSHP)38. 39. Algorithms40.41.[33.] Energy Savings (kWh/yr) = Tons * 12 kBtuh/Ton * (1/(EERg,b * GSER) – (1/ (EERg,q * GSER))) * EFLHc 42. 43. Peak Demand Savings (kW) = Tons * 12 kBtuh/Ton * (1/EERg,b – (1/ (EERg,q * GSPK))) * CF 44.
45. Heating Energy Savings (kWh/yr) = Tons * 12 kBtuh/Ton * (1/(COPg,b * GSOP) – (1/ (COPg,q * GSOP))) * EFLHh
46. GSHP Desuperheater [Inactive 2017, Not Reviewed]47.[34.] Energy (kWh) Savings = EDSH
48.49.[35.] Peak Demand Impact (kW) = PDSH 50.
[36.] Furnace High Efficiency Fan51.52.[37.] Algorithms53.54.[38.] Heating Energy Savings (kWh/yr) = (BtuHq /3.412 kWh/Btu) * EFLH * FFSHT
55. 56. Cooling Energy Savings (kWh/yr) = FFSCL
57.
58. Solar Domestic Hot Water (augmenting electric resistance DHW) [Inactive 2017, Not Reviewed]
59. 60. Heating Energy (kWh) Savings = ESavSDHW
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
61. 62. Peak Demand Impact (kW) = DSavSDHW x CFSDHW
63.
64. Heat Pump Hot Water (HPHW)65.66.[39.] Algorithms67.68.[40.] Heating Energy Savings (kWh/yr) = ESavHPHW
69.70.[41.] Peak Demand Savings (kW) = DSavHPHW * CFHPHW
71. Drain Water Heat Recovery (DWHR) [Inactive 2017, Not Reviewed]72.[42.] 73.[43.] Heating Energy (kWh) Savings = ESavDWHR
74.75.[44.] Peak Demand Impact (kW) = DSavDWHR x CFDWHR
76.
[45.] 77.[46.] Definition of Terms78. Tons = The rated cooling capacity of the unit being installed. This data is obtained
from the Application Form based on the model number.79. SEERb = The Seasonal Energy Efficiency Ratio of the Baseline Unit.80. SEERq = The Seasonal Energy Efficiency Ratio of the qualifying unit being
installed. This data is obtained from the Application Form based on the model number.
81. SEERm = The Seasonal Energy Efficiency Ratio of the Unit receiving maintenance
82. EERm = The Energy Efficiency Ratio of the Unit receiving maintenance83. EERb = The Energy Efficiency Ratio of the Baseline Unit.84. EERq = The Energy Efficiency Ratio of the unit being installed. This data is
obtained from the Application Form based on the model number.85. EERg,q = The EER of the ground source heat pump being installed. Note that
EERs of GSHPs are measured differently than EERs of air source heat pumps (focusing on entering water temperatures rather than ambient air temperatures). The equivalent SEER of a GSHP can be estimated by multiplying EERg by 1.02.
86. EERg,b = The EER of a baseline ground source heat pump87. GSER = The factor to determine the SEER of a GSHP based on its EER.
88. EFLH = The Equivalent Full Load Hours of operation for the average unit (cooling or heating)
89. ESF = The Energy Savings Factor or the assumed saving due to proper sizing and proper installation.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
90. MF = The Maintenance Factor or assumed savings due to completing recommended maintenance on installed cooling equipment.
91. DuctSF = The Duct Sealing Factor or the assumed savings due to proper sealing of all cooling ducts
92. CF = The coincidence factor which equates the installed unit’s connected load to its demand at time of system peak.
93. DSF = The Demand Savings Factor or the assumed peak demand capacity saved due to proper sizing and proper installation.
94. HSPFb = The Heating Seasonal Performance Factor of the Baseline Unit.95. HSPFq = The Heating Seasonal Performance Factor of the unit being installed.
This data is obtained from the Application Form.96. COPg,q = Coefficient of Performance of a GSHP97. COPg,b = Baseline Coefficient of Performance of a GSHP
98. GSOP = The factor to determine the HSPF of a GSHP based on its COP.
99. GSPK = The factor to convert EERg to the equivalent EER of an air conditioner to enable comparisons to the baseline unit. 100. EDSH = Assumed savings per desuperheater. 101. PDSH = Assumed peak demand savings per desuperheater. 102. ESavSDHW = Assumed energy savings per installed solar domestic hot water system with electric resistance heater backup. 103. DSavSDHW = Assumed demand savings per installed solar domestic hot water system with electric resistance heater backup.
104. BtuHq = Output capacity of the qualifying heating unit in BTUs/hour105. EFLHHT = The Equivalent Full Load Hours of operation for the average
heating unit106. FFSHT = Furnace fan savings (heating mode)107. FFSCL = Furnace fan savings (cooling mode)108. kWhp = Annual kWh due to proper sizing109. kWhq = Annual kWh usage post-program110. kWp = Annual kW due to proper sizing111. kWq = Annual kW usage post-program
112. ESavHPHW = Assumed energy savings per installed heat pump water heater. 113. DSavHPHW = Assumed demand savings per installed heat pump water heater.114. ESavDWHR = Assumed energy savings per installed drain water heat recovery unit in a household with an electric water heater.115. DSavDWHR = Assumed demand savings per installed drain water heat recovery unit in a household with an electric water heater.
116.[47.] Summary of Inputs 117.
118.[48.] Residential Electric HVAC
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
119. Component
120. Type
121. Value 122. Source
123. Tons 124. Variable
125. Rated Capacity, Tons 126. Rebate Application
127. SEERb 128. Fixed
129. Split Systems (A/C) = 13
130. Split Systems (HP) = 14
131. Single Package (A/C) = 14
132. Single Package (HP) = 14
133. 1
134. SEERq 135. Variable
136.[49.] 137.[50.] Rebate
Application138. SEERm 139. Fix
ed140. 13 141. 1
142. EERb 143. Fixed
144. Baseline = 11.3 145. 2
146. EERq 147. Fixed
148. = (11.3/13) X SEERq
149. 2
150. EERg,q 151. Variable
152. 153. Rebate Application
154. EERg,b 155. Fixed
156. 11.2 157. 13
158. EERm 159. Fixed
160. 8.69 161. 2
162. GSER 163. Fixed
164. 1.02 165. 3
166. EFLHc or h 167. Fixed
168. Cooling = 501 Hours
[51.] Heating = 727 HoursSee Table Below
169. 123
170. ESF 171. Fixed
172. 9.2% 173. 12
174. DSF 175. Fixed
176. 9.2% 177. 12
178. kWhq 179. Variable
180.[52.] 181.[53.] Rebate
Application
3 From NY TRM 2016, for NYC due to proximity to NJ; for single family detached
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
119. Component
120. Type
121. Value 122. Source
182. kWq 183. Variable
184.[54.] 185.[55.] Rebate
Application186. MF 187. Fix
ed188. 10% 189. 11
190. DuctSF 191. Fixed
192. 18% 193. 8
194. CF 195. Fixed
196. 69% 197. 4
198. DSF 199. Fixed
200. 2.9% 201. 5
202. HSPFb 203. Fixed
204. Split Systems (HP) = 8.2
205. Single Package (HP) = 8.0
206. 1
207. HSPFq 208. Variable
209.[56.] 210.[57.] Rebate
Application211. COPg,q 212. Va
riable213. 214. Rebate
Application215. COPg,b 216. Fix
ed217. 2.9 218. 13
219. GSOP 220. Fixed
221. 3.413 222. 6
223. GSPK 224. Fixed
225. 0.8416 226. 3
227. EDSH 228.[58.] Fixed
229.[59.] 1842 kWh [60.] 1114
230.[61.] PDSH 231.[62.] Fixed
232.[63.] 0.34 kW [64.] 1214
233.[65.] ESavSDHW
234.[66.] Fixed
235.[67.] 3100 kWh [68.] 2116
236.[69.] DSavSDHW
237.[70.] Fixed
238.[71.] 0.426 kW [72.] 2116
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
119. Component
120. Type
121. Value 122. Source
239.[73.] CFSDHW 240.[74.] Fixed
241.[75.] 20% [76.] 2116
242.[77.] ESavHPHW
243.[78.] Fixed
244.[79.] 1687 kWh [80.] 2317
245.[81.] DSavHPHW
246.[82.] Fixed
247.[83.] 0.37 kW [84.] 2418
248.[85.] CFHPHW 249.[86.] Fixed
250.[87.] 70% [88.] 2418
251.[89.] ESavDWHR
252.[90.] Fixed
253.[91.] 1457 kWh [92.] 2620, 2317
254.[93.] DSavDWHR
255.[94.] Fixed
256.[95.] 0.142 kW [96.] 2721
257.[97.] CFDWHR
258.[98.] Fixed
259.[99.] 20% [100.] 2721
260.[101.] Cooling – CAC
261. Time Period
Allocation Factors
262. Fixed
263. Summer/On-Peak 64.9%
264. Summer/Off-Peak 35.1%
265. Winter/On-Peak 0%266. Winter/Off-Peak
0%
267. 7
268. Cooling – ASHP
269. Time Period
Allocation Factors
270. Fixed
271. Summer/On-Peak 59.8%
272. Summer/Off-Peak 40.2%
273. Winter/On-Peak 0%274. Winter/Off-Peak
0%
275. 7
276. Cooling – GSHP
277. Time Period
Allocation Factors
278. Fixed
279. Summer/On-Peak 51.7%
280. Summer/Off-Peak 48.3%
281. Winter/On-Peak 0%282. Winter/Off-Peak
0%
283. 7
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
119. Component
120. Type
121. Value 122. Source
284. Heating – ASHP &
GSHP285. Time
Period Allocation
Factors
286. Fixed
287. Summer/On-Peak 0.0%
288. Summer/Off-Peak 0.0%
289. Winter/On-Peak 47.9%
290. Winter/Off-Peak 52.1%
291. 7
292. GSHP Desuperheat
er Time Period
Allocation Factors
293.[102.] Fixed
294.[103.] Summer/On-Peak 4.5%
295.[104.] Summer/Off-Peak 4.2%
296.[105.] Winter/On-Peak 43.7%
297.[106.] Winter/Off-Peak 47.6%
[107.] 1315
298.[108.] SDHW Time Period
Allocation Factors
299.[109.] Fixed
300.[110.] Summer/On-Peak 27.0%
301.[111.] Summer/Off-Peak 15.0%
302.[112.] Winter/On-Peak 42.0%
303.[113.] Winter/Off-Peak 17.0%
[114.] 2116
304.[115.] HPWH Time Period
Allocation Factors
305.[116.] Fixed
306.[117.] Summer/On-Peak 21%
307.[118.] Summer/Off-Peak 22%
308.[119.] Winter/On-Peak 28%
309.[120.] Winter/Off-Peak 29%
[121.] 2519
310.[122.] DWHR Time Period
Allocation Factors
311.[123.] Fixed
312.[124.] Summer/On-Peak 27.0%
313.[125.] Summer/Off-Peak 15.0%
314.[126.] Winter/On-Peak 42.0%
315.[127.] Winter/Off-Peak 17.0%
[128.] 2116
316.[129.] EFLHHT
317. Fixed
318. 727 hoursSee Table Below
319. 123
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
119. Component
120. Type
121. Value 122. Source
320. FFSHT 321. Fixed
322. 0.5 kWh 323. 9
324. FFSCL 325. Fixed
326. 105 kWh 327. 10
328. 329. EFLH Table
330. Single Family
Detached
331. Heating
EFLH
332. Cooling
EFLH
333. Old 334. 867 335. 670
336. Average 337. 786 338. 64
9
339. New 340. 725 341. 630
342. 343. Sources
344. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Chapter II, Subchapter D, Part 430, Subpart C, §430.32. Available at: https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
345. Average EER for SEER 13 units. The same EER to SEER ratio used for SEER 13 units applied to SEER 10 units. EERm = (11.3/13) * 10.
346.[130.] VEIC estimate. Extrapolation of manufacturer data.347.
[131.] NEEP, Mid-Atlantic Technical Reference Manual, V6. May 2016.348. Xenergy, “New Jersey Residential HVAC Baseline Study,” (Xenergy,
Washington, D.C., November 16, 2001) Table E-8.349. Engineering calculation, HSPF/COP=3.413350. Time period allocation factors used in cost-effectiveness analysis.351. “Review of Emerging HVAC Technologies and Practices” 03-STAC-01
Emerging Technologies Report, October 2005, John Proctor, PE, p. 46.352. Scott Pigg (Energy Center of Wisconsin), “Electricity Use by New Furnaces: A
Wisconsin Field Study,” Technical Report 230-1, October 2003.353. Ibid., p. 34. ARI charts suggest there are about 20% more full load cooling hours
in NJ than southern WI. Thus, average cooling savings in NJ are estimated at 95 to 115.
354. VEIC estimate. Conservatively assumes less savings than for QIV because of the retrofit context.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
355. NY_TRM – Version 4.0 April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling. Page 441. Derived from DOE2.2 simulations reflecting four different prototypical residential home types described in Appendix G.KEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf..
356. AHRI directory; baseline values are the least efficient “Geothermal – Water-to –Air Heat Pumps” active in the directory, downloaded May 18, 2015.
357. VEIC estimate, based on PEPCo assumptions.358. Time period allocation factors used in cost-effectiveness analysis.359. Energy savings are estimated based on 2008 SRCC OG300 ratings for a typical 2
panel system with solar storage tank in Newark, NJ with electric DHW backup. Demand savings are estimated based on an estimated electric DHW demand of 2.13kW with 20% CF. Load shape and coincidence factors were developed by VEIC from ASHRAE Standard 90.2 Hot Water Draw Profile and NREL Red Book insulation data for Newark, NJ.
360. Table 1. (Page 2) From “Heat Pump Water Heaters Evaluation of Field Installed Performance.” Steven Winter Associates, Inc. (2012). http://www.ma-eeac.org/Docs/8.1_EMV%20Page/2012/2012%20Residential%20Studies/MA%20RR&LI%20-%202011%20HPWH%20Field%20Evaluation%20Report%20FINAL%206_26_2012.pdf
361. VEIC Estimate based upon range derived from FEMP Federal Technology Alert: S9508031.3a (http://www1.eere.energy.gov/femp/pdfs/FTA_res_heat_pump.pdf)
362. “Electrical Use, Efficiency, and Peak Demand of Electric Resistance, Heat Pump, Desuperheater, and Solar Hot Water Systems”, http://www.fsec.ucf.edu/en/publications/html/FSEC-PF-215-90/
363. 30% savings (from Zaloum, C. Lafrance, M. Gusdorf, J. “Drain Water Heat Recovery Characterization and Modeling” Natural Resources Canada. 2007. Savings vary due to a number of factors including make, model, installation-type, and household behaviors.) multiplied by standard electric resistance water heating baseline annual usage of 4,857 kWh cited in source #23 above.
364. Demand savings are estimated based on electric DHW demand of 2.13kW and 20% CF as in cited source #21 adjusting for the proportional difference of 30% savings relative to the 70% solar fraction: 0.426*0.3/0.9 = 0.142.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Residential Gas HVAC
Protocols[132.] The following sectionstwo algorithms detail savings calculations for gas space
heating and gas water heating equipment in residential applications.. They are to be used to determine gas energy savings between baseline standard units and the high efficiency units promoted in the program. The input values are based on data on typical customers supplied by the gas utilities, an analysis by the Federal Energy Management Program (FEMP), and customer information on the application form, confirmed with manufacturer data. The energy values are in therms.
365.[133.] Furnaces
366. This section provides energy savings algorithms for qualifying gas and oil furnaces installed in residential settings. The input values are based on the specifications of the actual equipment being installed, federal equipment efficiency standards, and the most recent impact evaluation of the residential Warm and Cool Advantage programs (2009).
367. This measure applies to replacement of failed equipment or end of useful life. The baseline unit is a code compliant unit with an efficiency as required by IECC 2015, which is the current residential code adopted by the state of New Jersey.
368.
369. Space Heaters[134.] Algorithms
[135.] FuelGas Savings (MMBtu/yr) = kBtu/hrin * EFLH * ((AFUEq = [(Capyq/AFUEb) – 1) / 1000 kBtu/MMBtu(Capyq/ AFUEq)] * EFLH / 100,000 BTUs/therm 370.[136.] [137.] Low Income Gas Savings = [(Capyq/AFUELI) – (Capyq/ AFUEq)] * EFLH /
100,000 BTUs/therm [138.] [139.] Gas Definition of Variables 371. kBtu/hrin = Input capacity of qualifying unit in kBtu/hour372. EFLHh = The Equivalent Full Load Hours of operation per year for the average unit during the heating season 373. AFUEq = Annual Fuel Utilization Efficiency of the qualifying furnace 374. AFUEb = Annual Fuel Utilization Efficiency of the baseline furnace meeting current federal equipment standards 375.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
376. Summary of Inputs 377. Furnace Assumptions
378.[140.] Component
379.Type
380. Value 381. Source
382. kBtu/hrin 383.Varia
ble
384. 385. Application
386. EFLHh387.Fixed
388. 727 hoursSee Table Below 389. 1 4
390. AFUEq 391.Varia
ble
392. 393. Application
394. AFUEb395.Fixed
396. Weatherized gas: 81%397. Weatherized oil: 78%
398. Mobile home gas: 80%
399. Mobile home oil: 75%400. Non-weatherized gas:
80%401. Non-weatherized oil:
83%
402. 2
403.404.[141.] EFLH Table
405.[142.] Single Family Detached
406.[143.] Heating EFLH
407.[144.] Cooling
EFLH
408.[145.] Old 409.[146.] 867
410.[147.] 670
411.[148.] Average
412.[149.] 786
413.[150.] 649
414.[151.] New
415.[152.] 725
416.[153.] 630
417.[154.] Sources
1. NY_TRM – Version 4.0 April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling. Page 441. Derived from DOE2.2 simulations reflecting four different prototypical residential home types described in Appendix G.KEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf.
4 From NY TRM 2016, for NYC due to proximity to NJ; for single family detached
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Chapter II, Subchapter D, Part 430, Subpart C, §430.32; available at: https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
418. Boilers
419. BoilersThis section provides energy savings algorithms for qualifying boilers installed in residential settings. The input values are based on the specifications of the actual equipment being installed, federal equipment efficiency standards, and the most recent impact evaluation of the residential Warm and Cool Advantage programs (2009).
420. This measure applies to replacement of failed equipment or end of useful life. The baseline unit is a code compliant unit with an efficiency as required by IECC 2015, which is the current residential code adopted by the state of New Jersey.
421.422.[155.] Algorithms423.424.[156.] Fuel Savings (MMBtu/yr) = kBtuin/hr * EFLHh * ((AFUEq/AFUEb)-1) / 1000 kBtu/MMBtu425.426.[157.] Definition of Variables427. kBtuin/hr = Input capacity of qualifying unit428. EFLHh = The Equivalent Full Load Hours of operation for the average unit during the heating season in hours 429. AFUEq = Annual Fuel Utilization Efficiency of the qualifying boiler430. AFUEb = Annual Fuel Utilization Efficiency of the baseline boiler431. 432. Summary of Inputs
433. Space Heating Boiler Assumptions434. Compon
ent435. Type 436. Value 437. Source
438. kBtuin 439. Variable
440. 441. Application
442. EFLHh 443. Fixed
444. 727 hoursSee Table Below
445. 1 5
446. AFUEq 447. Variable
448.[158.] 449.[159.] Application
450. AFUEb451. Fixe
d
452. Gas fired boiler – 82%
453. Oil fired boiler – 84%
454. 2
5 From NY TRM 2016, for NYC due to proximity to NJ; for single family detached
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
455.456.[160.] EFLH Table
457. Single Family
Detached
458. Heating
EFLH
459. Cooling
EFLH
460. Old 461. 867 462. 670
463. Average 464. 786 465. 64
9
466. New 467. 725 468. 630
469.470.[161.] Sources
1. NY_TRM – Version 4.0 April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling. Page 441. Derived from DOE2.2 simulations reflecting four different prototypical residential home types described in Appendix G.KEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf.
2. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Chapter II, Subchapter D, Part 430, Subpart C, §430.32; available at: https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
471. Combination Boilers
472. This section provides energy savings algorithms for qualifying gas combination boilers installed in residential settings. A combination boiler is defined as a boiler that provides domestic hot water and space heating. The input values are based on the specifications of the actual equipment being installed, federal equipment efficiency standards, DOE2.2 simulations completed by the New York State Joint Utilities and regional estimates of average baseline water heating energy usage.
473. This measure assumes the existing boiler system has failed or is at end of useful life and is replaced with a combination boiler. The baseline boiler unit has an efficiency as required by IECC 2015, which is the current residential code adopted by the state of New Jersey. For the water heating component, this measure assumes that the baseline water heater is a storage water heater, and customers replacing existing tankless water heaters are not eligible.
474. Note, that as of June 12, 2017, the Federal Trade Commission has published a final rule updating the EnergyGuide label to reflect recent changes by the Department of Energy to the Code of Federal Regulations regarding the use of
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
uniform energy factor (UEF) rather than the traditional energy factor (EF)6 for consumer and commercial water heaters.
475. 476. Algorithms477.478.[162.] Fuel Savings (MMBtu/yr) = MMBtu/yr Boiler Fuel Savings + MMBtu/yr DHW Fuel Savings479. 480. MMBtu Boiler Fuel Savings/yr = kBtuin/hr * EFLHh * ((AFUEq/AFUEb)-1) / 1,000 kBtu/MMBTU481. 482. MMBtu DHW Fuel Savings/yr = (1 – (UEFb / UEFq)) × Baseline Water Heater Usage 483.484.[163.] Definition of Variables485. kBtuin/hr = Input capacity of qualifying unit in kBtu/hr486. EFLHh = The Equivalent Full Load Hours of operation for the average unit during the heating season 487. AFUEq = Annual fuel utilization efficiency of the qualifying boiler488. AFUEb = Annual fuel utilization efficiency of the baseline boiler489. UEFq = Uniform energy factor of the qualifying energy efficient water heater.490. UEFb = Uniform energy factor of the baseline water heater. In New Jersey the 2015 International Energy Conseration Code (IECC) generally defines the residential energy efficiency code requirements, but the IECC does not include residential service water heating provisions, leaving federal equipment efficiency standards to define baseline. 491. Baseline Water Heater Usage = Annual usage of the baseline water heater492. 493. Summary of Inputs 494.
495. Combination Boiler Assumptions496. Compon
ent497.Type 498. Value 499. Sourc
e
500. kBtuin/hr
501.Varia
ble
502. 503. Application
504. EFLHh505.Fixed
506. 727 hoursSee Table Below 507. 1 7
508. AFUEq 509.Varia
510. 511. Appli
6 The final ruling on this change is available at: https://energy.gov/sites/prod/files/2016/12/f34/WH_Conversion_Final%20Rule.pdf.7 From NY TRM 2016, for NYC due to proximity to NJ; for single family detached
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
496. Component
497.Type 498. Value 499. Sourc
eble cation
512. AFUEb513.Fixed
514. Gas fired boiler – 82%515. Oil fired boiler – 84%
516. 2
517. UEFb518.Fixed
519. Storage Water Heater – 0.657 520. 2
521. UEFq522.Fixed 523. 0.87 524. 3
525. Baseline Water Heater Usage
526.Fixed
527. 23.6 MMBtu/yr528. 529. 4
530.531.[164.] The referenced federal standards for the baseline UEF are dependent on
both draw pattern and tank size. A weighted average baseline UEF was calculated with a medium draw pattern from the referenced federal standards and water heating equipment market data from the Energy Information Association 2009 residential energy consumption survey for NJ8 assuming tank sizes of 30 gallons for small units, 40 gallons for medium units, and 55 gallons for large units.
532. 533. EFLH Table
534. Single Family
Detached
535. Heating
EFLH
536. Cooling
EFLH
537. Old 538. 867 539. 670
540. Average 541. 786 542. 64
9
543. New 544. 725 545. 630
546.547.[165.] Sources
1. NY_TRM – Version 4.0 April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling. Page 441. Derived from DOE2.2 simulations reflecting four different prototypical residential home types described in Appendix G.KEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf.
8 Available at: https://www.eia.gov/consumption/residential/data/2009/hc/hc8.8.xls
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Chapter II, Subchapter D, Part 430, Subpart C, §430.32; available at: https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
3. Minimum UEF for instantaneous (tankless) water heaters from Energy Star https://www.energystar.gov/products/water_heaters/residential_water_heaters_key_product_criteria.
4. US Energy Information Association, 2009 Residential Energy Consumption Survey Data9; available at: https://www.eia.gov/consumption/residential/data/2009/c&e/ce3.2.xlsx
548. Boiler Reset Controls
549.[166.] The following algorithm details savings for installation of boiler reset control on residential boilers. Energy savings are realized through a better control of boiler water temperature. Through the use of software settings, boiler reset controls use outside or return water temperature to control boiler firing and in turn the boiler water temperature.
550.[167.] The input values are based on data supplied by the utilities and customer information on the application form, confirmed with manufacturer data. Unit savings are deemed based on study results.
551. Algorithms
552. Fuel Savings (MMBtu/yr) = (% Savings) * (EFLHh * kBtuin/hr) / 1,000 kBtu/MMBtu553. 554. Definition of Variables 555. % Savings = Estimated percentage reduction in heating load due to boiler reset controlsduct sealing = (CAPavg AFUEavg) * EFLH * (DuctSFh/100,000 BTUs/therm)556.[168.] EFLHh = The Equivalent Full Load Hours of operation for the average unit during the heating season557. kBtuin/hr = Input capacity of boiler
558. Summary of Inputs 559.
560. Boiler Reset Control Assumptions561. Compon
ent562.Type 563. Value 564. Sourc
e565. %
Savings566.Fixed 567. 5% 568. 1
569. EFLHh570.Fixed
571. 727 hoursSee Table Below 572. 2 10
9 Data for 2015 will be available in 2018.10 From NY TRM 2016, for NYC due to proximity to NJ; for single family detached
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
561. Component
562.Type 563. Value 564. Sourc
e
573. kBtuin/hr
574.Varia
ble
575. 576. Application
577. 578. EFLH Table
579. Single Family
Detached
580. Heating
EFLH
581. Cooling
EFLH
582. Old 583. 867 584. 670
585. Average 586. 786 587. 64
9
588. New 589. 725 590. 630
591. 592. Sources
1. GDS Associates, Inc., Natural Gas Energy Efficiency Potential in Massachusetts, 2009, p. 38, Table 6-4, http://ma-eeac.org/wordpress/wp-content/uploads/5_Natural-Gas-EE-Potenial-in-MA.pdf.
2. NY_TRM – Version 4.0 April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling. Page 441. Derived from DOE2.2 simulations reflecting four different prototypical residential home types described in Appendix G.KEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf.
593. Storage Water Heaters594. This section provides energy savings algorithms for qualifying storage hot
water heaters installed in residential settings. This measure assumes that the baseline water heater is a new storage water heater. The input values are based on federal equipment efficiency standards and regional estimates of average baseline water heating energy usage. Note, that as of June 12, 2017, the Federal Trade Commission has published a final rule updating the EnergyGuide label to reflect recent changes by the Department of Energy to the Code of Federal Regulations regarding the use of uniform energy factor (UEF) rather than the traditional energy factor (EF)11 for consumer and commercial water heaters.
595.596.[169.] Algorithms597.
11 The final ruling on this change is available at: https://energy.gov/sites/prod/files/2016/12/f34/WH_Conversion_Final%20Rule.pdf
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
598.[170.] Fuel Savings (MMBtu/yr) = (1 – (UEFb / UEFq)) × Baseline Water Heater Usage
599.600.[171.] Definition of Variables601. UEFq = Uniform energy factor of the qualifying energy efficient water heater.602. UEFb = Uniform energy factor of the baseline water heater. In New Jersey the 2015 International Energy Conseration Code (IECC) generally defines the residential energy efficiency code requirements, but the IECC does not include residential service water heating provisions, leaving federal equipment efficiency standards to define baseline. 603. Baseline Water Heater Usage = Annual usage of the baseline water heater604. 605. Summary of Inputs 606.
607. Storage Water Heater608. C
omponen
t
609.Type
610. Valuea 611. Sources
612. U EFq
613.Variab
le
614. 615. Applicati
on616. U
EFb 617.Variab
le
618. If gas & less than 55 gal: UEFb = 0.6483–(0.0017×V)
619. If gas & more than 55 gal: UEFb = 0.7897–(0.0004×V)
620. 1
621. B aseline
Water
Heater
Usage
622.Fixed
623. 23.6 MMBtu/yr624.
625. 2
626. a V refers to volume of the installed storage water heater tank in gallons627. 628. The referenced federal standards for the baseline UEF are dependent on both
draw pattern and tank size. The baseline UEF formulas shown in the table above are associated with medium draw patterns.
629.
630. Sources
1. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Part 430, Subpart C; available at:
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
2. US Energy Information Association, 2009 Residential Energy Consumption Survey Data12; available at: https://www.eia.gov/consumption/residential/data/2009/c&e/ce3.2.xlsx.
631. Instantaneous Water Heaters632. This section provides energy savings algorithms for qualifying instantaneous
hot water heaters installed in residential settings. This measure assumes that the baseline water heater is either a new storage water heater, or instantaneous water heater. The input values are based on federal equipment efficiency standards and regional estimates of average baseline water heating energy usage. Note, that as of June 12, 2017, the Federal Trade Commission has published a final rule updating the EnergyGuide label to reflect recent changes by the Department of Energy to the Code of Federal Regulations regarding the use of uniform energy factor (UEF) rather than the traditional energy factor (EF)13 for consumer and commercial water heaters.
633. 634. Algorithms 635. 636. Fuel Savings (MMBtu/yr) = (1 – (UEFb / UEFq)) × Baseline Water Heater
Usage 637. 638. Definition of Variables639. UEFq = Uniform energy factor of the qualifying energy efficient water heater.640. UEFb = Uniform energy factor of the baseline water heater. In New Jersey the 2015 International Energy Conseration Code (IECC) generally defines the residential energy efficiency code requirements, but the IECC does not include residential service water heating provisions, leaving federal equipment efficiency standards to define baseline. 641. Baseline Water Heater Usage = Annual usage of the baseline water heater642. 643. Summary of Inputs
644. Instantaneous Water Heaters645.[172.] C
omponent
646.Type
647. Value 648. S ource
649. UEFq
650.Variab
le
651. 652. A pplication
12 Data for 2015 will be available in 2018.13 The final ruling on this change is available at: https://energy.gov/sites/prod/files/2016/12/f34/WH_Conversion_Final%20Rule.pdf
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
645.[172.] C ompone
nt
646.Type
647. Value 648. S ource
653. UEFb
654.Variab
le
655. Storage water heater – 0.657656. Instantaneous water heater –
0.81
657. 1
658. Baseline
Water Heater Usage
659.Fixed
660. 23.6 MMBtu/yr661.
662. 2
663. 664. The referenced federal standards for the baseline UEF are dependent on both
draw pattern and tank size. A weighted average baseline UEF was calculated with a medium draw pattern from the referenced federal standards and water heating equipment market data from the Energy Information Association 2009 residential energy consumption survey for NJ14 assuming tank sizes of 30 gallons for small units, 40 gallons for medium units, and 55 gallons for large units.
665.666.[173.] Sources
1. US Government Publishing Office, June 2017, Electronic Code of Federal Regulations – Title 10, Part 430, Subpart C; available at: https://www.ecfr.gov/cgi-bin/text-idx?SID=2942a69a6328c23266612378a0725e60&mc=true&node=se10.3.430_132&rgn=div8.
2. US Energy Information Association, 2009 Residential Energy Consumption Survey Data15; available at: https://www.eia.gov/consumption/residential/data/2009/c&e/ce3.2.xlsx.667. 668.[174.] Average Heating Use (therms) = (Capavg / AFUEavg) * EFLH / 100,000
BTUs/therm[175.] [176.] EFLH = Average Heating Use * AFUEavg* 100,000 BTUs/therm) / Capavg
[177.] [178.] Oil Savings for a qualifying boiler = OsavBOILER[179.] [180.] Oil Savings = [(Capyq/AFUEb) – (Capyq/ AFUEq)] * EFLH / 100,000
BTUs/therm[181.] [182.] Circulator Pumps Savings (kWh) = Hours * (WattsBase – WattsEE)/1000 [183.]
14 Available at: https://www.eia.gov/consumption/residential/data/2009/hc/hc8.8.xls15 Data for 2015 will be available in 2018.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[184.] Definition of Variables [185.] [186.] Capyq = Output capacity of qualifying unit output in BTUs/hour[187.] [188.] Capyt = Output capacity of the typical heating unit output in Btus/hour[189.] [190.] Capyavg = Output capacity of the average heating unit output in Btus/hour[191.] [192.] EFLH = The Equivalent Full Load Hours of operation for the average unit. [193.] [194.] DuctSFh = The Duct Sealing Factor or the assumed savings due to proper
sealing of all heating ducts[195.] [196.] AFUEavg = Annual Fuel Utilization Efficiency of the average furnace or boiler
[197.] [198.] AFUEq = Annual Fuel Utilization Efficiency of the qualifying baseline furnace or boiler
[199.] [200.] AFUEb = Annual Fuel Utilization Efficiency of the baseline furnace or boiler[201.] [202.] AFUELI = Annual Fuel Utilization Efficiency of the Low Income Program replaced furnace or boiler.
[203.] [204.] Average Heating Usage = The weighted average annual heating usage (therms)
of typical New Jersey heating customers[205.] [206.] WattsBase = Baseline connected kW[207.]
[208.] WattsEE = Efficient connected kW[209.]
[210.] Space Heating[211.] [212.] [213.] Sources:[1.] NJ Residential HVAC Baseline Study[2.] Federal minimum standards as of 2015.[3.] NJ utility analysis of heating customers, annual gas heating usage[4.] Prorated based on 12% of the annual degree days falling in the summer period
and 88% of the annual degree days falling in the winter period.[5.] Northeast Energy Efficiency Partnerships, Inc., “Benefits of HVAC Contractor
Training”, (February 2006): Appendix C Benefits of HVAC Contractor Training: Field Research Results 03-STAC-01
[6.] KEMA, NJ Clean Energy Program Energy Impact Evaluation Protocol Review. 2009.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[7.] Electric resistance heat calculated by determining the overall fuel cycle efficiency by dividing the average PJM heat rate (9,642 BTU per kWh) by the BTUs per kWh (3,413 BTU per kWh), giving a 2.83 BTUin per BTUout.
[8.] Efficiency Vermont Technical Reference Manual[9.] Boiler run hours, based on Efficiency Vermont TRM methodology, where boilers
have EFLH of 810 and the circ pump run hours are 1973. Therefore for NJ with 965 EFLH, the run hours can be estimated as 965 * 1973/810 = 2350
[214.] Water Heaters[215.] Algorithms [216.] [217.] Gas Savings = ((EFq – EFb)/EFq) X Baseline Water Heater Usage
[1.] [218.] Gas Savings (Solar DHW) = GsavSHW
[219.] Gas Savings (Drain Water Heat Recover) = GsavDWHR * Baseline Water Heater Usage
[220.] [221.] Definition of Variables [222.] [223.] EFq = Energy factor of the qualifying energy efficient water heater.[224.] Note: For qualifying units not rated with an Energy Factor, the estimated EFq
shall be used:[225.] Est. EFq = Qout/Qin
[226.] = 41,09416/ (41,094/TE + Volume*SLratio*24hours)[227.] [228.] Where: TE = Thermal (or Recovery) Efficiency of the unit as a
percentage[229.] Volume = Volume of storage water heater, in gallons.
[230.] SLratio = Average ratio of rated standby losses water heater (BTU loss per hour for > 90% TE units less than 130 Gallons = 9.7317
[231.] Gas & Propane Tankless Water Heaters1: EFb = 00.82 – (0.0019 * Gallons of Capacity)
[232.] Gas & Propane Storage or Power Vented Water Heaters1 :[233.] 55 gallons or less: EFb = 0.675 - (0.0015 * Gallons of Capacity) [234.] 56 gallons or more: EFb = 0.8012 - (0.00078 * Gallons of Capacity)[235.] [236.] Baseline Water Heater Usage = Annual usage of the baseline water heater, in
therms.[237.]
16 Based upon the test conditions of the DOE test protocol for residential water heaters, the amount of energy delivered is equal to 64.3 gallons * density of water (8.3lb/gal) * Specific heat of water (1 BTU/lb-F) and the temperature rise of 77degF (135F-58F).
17 Based upon February, 2012 query of ARHI/GAMA database http://cafs.ahrinet.org/gama_cafs/sdpsearch/search.jsp?table=CWH
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[238.] GsavSHW = Gas savings, in therms, for a solar hot water installation augmented by a new gas hot water heater.
[239.] [240.] GsavDWHR = Gas savings, as a percentage, for a drain water heat recovery
installation in a home with a gas hot water heater.[241.]
[242.] Water Heaters[243.]
669.[244.] [245.] Sources:[1.] Federal EPACT Standard Table II.1, revised April 16, 2015[2.] KEMA. NJ Clean Energy Program Energy Impact Evaluation Protocol Review.
2009.[3.] Prorated based on 6 months in the summer period and 6 months in the winter
period.[4.] Savings derived from US DOE estimates for the SEEARP (ENERGY STAR®
Residential Water Heaters: Final Criteria Analysis)[5.] Zaloum, C. Lafrance, M. Gusdorf, J. “Drain Water Heat Recovery
Characterization and Modeling” Natural Resources Canada. 2007. Savings vary due to a number of factors including make, model, installation-type, and household behaviors.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Residential Low Income Program
Protocols670.[246.] The Protocols set out below are applicable to both the Comfort Partners
component of the Low-income Program currently implemented by the State’s electric and gas utilities and the Weatherization Assistance component of the Low-income Program implemented by the New Jersey Department of Community Affairs (DCA).
671.[247.] The savings protocols for the low-income program are based upon estimated per unit installed savings. In some cases, such as lighting and refrigerators, the savings per unit estimate is based on direct observation or monitoring of the existing equipment being replaced. For other measures, for example air sealing and insulation, the protocols calculation is based on an average % savings of pre-treatment consumption.
672.[248.] 673.[249.] Base Load Measures
674.[250.] Efficient Lighting675.[251.] Savings from installation of screw-in CFLs, high performance fixtures,
fluorescent torchieres, LEDs and LED nightlights are based on a straightforward algorithm that calculates the difference between existing and new wattage, and the average daily hours of usage for the lighting unit being replaced.
676.[252.] 677.[253.] Algorithm
678.[254.] Compact Fluorescent Screw In Lamp[255.] Energy SavingsElectricity Impact (kWh/yr) = ((CFLwatts) X (CFLhours X
365))/1000[256.] Peak Demand SavingsImpact (kW) = (CFLwatts) X Light CF
679.[257.] Efficient Fixtures[258.] Energy SavingsElectricity Impact (kWh/yr) = ((Fixtwatts) X (Fixthours X
365))/1000[259.] Peak Demand SavingsImpact (kW) = (Fixtwatts) X Light CF
680.[260.] Efficient Torchieres[261.] Energy SavingsElectricity Impact (kWh/yr) = ((Torchwatts) X (Torchhours X
365))/1000[262.] Peak Demand SavingsImpact (kW) = (Torchwatts) X Light CF
681.[263.] LED Screw In Lamp[264.] Energy SavingsElectricity Impact (kWh/yr) = ((LEDwatts) X (LEDhours X
365))/1000[265.] Peak Demand SavingsImpact (kW) = (LEDwatts) X Light CF
682.[266.] LED Nightlight
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[267.] Energy SavingsElectricity Impact (kWh/yr) = ((LEDNwatts) X (LEDNhours X 365))/1000683.[268.]
[269.] Hot Water Conservation Measures684.[270.] The protocols savings estimates are based on an average package of
domestic hot water measures typically installed by low-income programs.685.[271.] 686.[272.] Low Flow Showerheads
[273.] Savings for low- flow showerhead measures are determined using the total change in flow rate (gallons per minute) from the baseline (existing) showerhead to the efficient showerhead.
687.[274.] Algorithms [275.] Energy SavingsElectricity Impact (kWh/yr) = %Electric DHW *
(GPM_base – GPM_ee) * kWh/∆GPM[276.] Peak Electric Demand SavingsImpact (kW) = Electricity Impact (kWh) *
Demand Factor688.[277.] Natural Gas Impact (therm) = %Gas DHW * (GPM_base – GPM_ee)
* therm/∆GPM
689.[278.] Definition of Variables 690.[279.] %Electric DHW = proportion of water heating supplied by electricity691.[280.] GPM_base = Flow rate of the baseline showerhead (gallons per
minute)692.[281.] GPM_ee = Flow rate of the efficient showerhead (gallons per minute)693.[282.] kWh/∆GPM = Electric energy savings of efficient showerhead per
gallon per minute (GPM)694.[283.] Demand Factor = energy to demand factor695.[284.] %Gas DHW = proportion of water heating supplied by natural gas 696.[285.] therm/∆GPM = natural gas energy savings of efficient showerhead per
gallon per minute (GPM) 697.[286.]
698.[287.] Low Flow Showerheads699.[288.] Compone
nt
700.[289.] Typ
e
701.[290.] Value 702.[291.] Sourc
es
703.[292.] % Electric
DHW
704.[293.] Vari
able
705.[294.] Electric DHW = 100%
706.[295.] Unknown = 13%
707.[296.] 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
699.[288.] Compone
nt
700.[289.] Typ
e
701.[290.] Value 702.[291.] Sourc
es
708.[297.] %Gas
DHW
709.[298.] Vari
able
710.[299.] Natural Gas DHW =
100%711.[300.] Unknown
= 81%
712.[301.] 1
713.[302.] GPM_bas
e
714.[303.] Vari
able
715.[304.] Rebate Application
716.[305.] Unknown = 2.5
717.[306.] 2
718.[307.] GPM_ee
719.[308.] Vari
able
720.[309.] Rebate Application
721.[310.] Unknown = 1.5
722.[311.] 2
723.[312.] kWh/
∆GPM
724.[313.] Fixe
d
725.[314.] SF = 360.1
726.[315.] MF = 336.9
727.[316.] Unknown = 390.1
728.[317.] 3
729.[318.] therm/
∆GPM
730.[319.] Fixe
d
731.[320.] SF = 15.5732.[321.] MF = 16.9733.[322.] Unknown
= 16.8
734.[323.] 3, 4
735.[324.] Demand
Factor
736.[325.] Fixe
d
737.[326.] 0.00008013
738.[327.] 3
739.[328.] 740.[329.] Sources
[1.] Unknown hot water heating fuel assumption taken from 2009 RECS data for New Jersey; see. See Table HC8.8 Water Heating in U.S. Homes in Northeast Region, Divisions, and States.
[2.] Flow rate specification taken from rebate application; default. Default assumption for unknown flow rate taken from Pennsylvania Technical Reference Manual, effective. Effective June 2016, p.pages 120ff; available. Available at http://www.puc.pa.gov/pcdocs/1370278.docx.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1.[3.] Default assumptions from Pennsylvania Technical Reference Manual (ibid). [4.] Illinois Statewide Technical Reference Manual for Energy Efficiency, Version 4.0,
effective. Effective June 1, 2015, pp. pages 657ff; default. Default assumptions for housing demographic characteristics taken from PA TRM.741.[330.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
742.[331.] Low Flow Faucet Aerators
[332.] Savings for low- flow faucet aerator measures are determined using the total change in flow rate (gallons per minute) from the baseline (existing) faucet to the efficient faucet.
743.[333.] [334.] AlgorithmAlgorithms744. Energy SavingsElectricity Impact (kWh/yr) = %Electric DHW * (GPM_base – GPM_ee) * kWh/∆GPM[335.] Peak Electric Demand SavingsImpact (kW) = Electricity Impact (kWh) *
Demand Factor745.[336.] Natural Gas Impact (therm) = %Gas DHW * (GPM_base – GPM_ee) *
therm/∆GPM746.[337.] 747. Definition of Variables
748.[338.] %Electric DHW = proportion of water heating supplied by electricity749.[339.] GPM_base = Flow rate of the baseline faucet (gallons per minute)750.[340.] GPM_ee = Flow rate of the efficient faucet (gallons per minute) 751.[341.] kWh/∆GPM = Electric energy savings of efficient faucet per gallon per
minute (GPM)752.[342.] Demand Factor = energy to demand factor753.[343.] %Gas DHW = proportion of water heating supplied by natural gas754.[344.] therm/∆GPM = natural gas energy savings of efficient faucet per
gallon per minute (GPM) 755.[345.]
756.[346.] Low Flow Faucet Aerators757.[347.] Compone
nt
758.[348.] Typ
e
759.[349.] Value [350.] SourcesSource
760.[351.] % Electric
DHW
761.[352.] Vari
able
762.[353.] Electric DHW = 100%
763.[354.] Unknown = 13%
764.[355.] 1
765.[356.] % Gas
DHW
766.[357.] Vari
able
767.[358.] Natural Gas DHW =
100%768.[359.] Unknown
= 81%
769.[360.] 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
757.[347.] Compone
nt
758.[348.] Typ
e
759.[349.] Value [350.] SourcesSource
770.[361.] GPM_bas
e
771.[362.] Vari
able
772.[363.] Rebate Application
773.[364.] Unknown = 2.2
774.[365.] 2
775.[366.] GPM_ee
776.[367.] Vari
able
777.[368.] Rebate Application
778.[369.] Unknown = 1.5
779.[370.] 2
780.[371.] kWh/
∆GPM
781.[372.] Fixe
d
782.[373.] SF = 60.5783.[374.] MF = 71.0784.[375.] Unknown
= 63.7
785.[376.] 3
786.[377.] therm/
∆GPM
787.[378.] Fixe
d
788.[379.] SF = 4.8789.[380.] MF = 6.5790.[381.] Unknown
= 5.0
791.[382.] 3, 4
792.[383.] Demand
Factor
793.[384.] Fixe
d
794.[385.] 0.00008013
795.[386.] 3
796.[387.] 797.[388.] Sources
[1.] Unknown hot water heating fuel assumption taken from 2009 RECS data for New Jersey; see. See Table HC8.8 Water Heating in U.S. Homes in Northeast Region, Divisions, and States.
[2.] Flow rate specification taken from rebate application; default. Default assumption for unknown flow rate taken from Pennsylvania Technical Reference Manual; effective. Effective June 2016, pp.pages 114ff; available. Available at http://www.puc.pa.gov/pcdocs/1370278.docx.
1.[3.] Default assumptions from Pennsylvania Technical Reference Manual (ibid). [4.] Illinois Statewide Technical Reference Manual for Energy Efficiency, Version 4.0,
effective. Effective June 1, 2015, pp. pages 648ff; default. Default assumptions for housing demographic characteristics taken from PA TRM.798.[389.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
799.[390.] Indirect Hot Water Heaters800.[391.]
801.[392.] Wisconsin’s 2013 Focus on Energy Deemed Savings are as follows.18
802.[393.] 803.[394.] ∆ Therm=Ther mStd−Ther mEff
804.[395.] 805.[396.] Ther mOut=E FStd ×Ther mStdTank
806.[397.] 807.[398.]
Ther mStd=Standb yStd ×8,760 ×1/100,000/ AFU EStd+Ther mOut × 1/AFU Estd
808.[399.] Average hot water use per person were taken from: Lutz, James D., Liu, Xiaomin, McMahan, James E., Dunham, Camilla, Shown, Leslie J., McCure, Quandra T; “Modeling patterns of hot water use in households;” LBL-37805 Rev. Lawrence Berkeley Laboratory, 1996.
809.[400.] 810.[401.]
Ther mEff=Standb y Eff × 8,760× 1/100,000/AFU EEff +Ther mOut × 1/AFU EEff
811.[402.]
812.[403.] Standb yStd=Vo l Std ×( ℉hrStd )×8.33
813.[404.]
814.[405.] Standb yEff =Vo lEff ×( ℉h r Eff )× 8.33
815.[406.] Table IV-13. Definitions and Values for Indirect Hot Water Heaters
[407.] 816.[408.]
Term 817.[409.] Definition 818.[410.] Value
819.[411.] ∆Therm [412.] Gas savingsSavings 820.[413.]
821.[414.] ThermStd
822.[415.] Calculated therms standard tank 823.[416.] 206
824.[417.] ThermEff
825.[418.] Calculated therms replacement tank 826.[419.] 177.52
827.[420.] ThermOut
828.[421.] 829.[422.]
830.[423.] EFStd
831.[424.] Federal standard energy factor 832.[425.] (.67 – (.0019xvolume))=.
58
18The Cadmus Group, Inc. “Final Report Focus on Energy Evaluated Deemed Savings Changes.” Prepared for the Public Service Commission of Wisconsin. November 26, 2013. Pp.Pages 15-16.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
816.[408.] Term 817.[409.] Definition 818.[410.] Value
833.[426.] Ther
mStdT
ank
834.[427.] Therms used by standard tank 835.[428.] 223
836.[429.] Standb
yStd
837.[430.] Standby loss from standard water heater
[431.] 434 BtuBTU/hr*
838.[432.] AFUEStd
839.[433.] Efficiency (AFUE) of standard water heater 840.[434.] 80%
841.[435.] Standb
yEff
842.[436.] Standby loss from efficient water heater
[437.] 397 BtuBTU/hr**
843.[438.] AFUEEff
844.[439.] Efficiency (AFUE) of efficient water heater 845.[440.] 93%
846.[441.] VolStd
847.[442.] Volume of standard water heater (gallons) 848.[443.] 63.50
849.[444.] VolEff
850.[445.] Volume of efficient water heater (gallons) 851.[446.] 51.20
852.[447.] °F/hrStd
853.[448.] Heat lost per hour from standard water heater tank 854.[449.] 0.8
855.[450.] °F/hrEff
856.[451.] Heat lost per hour from efficient water heater tank 857.[452.] 0.93
858.[453.] 859.[454.] Conversion factor: density of water (lbs./gallon) 860.[455.] 8.33
861.[456.] *AHRI Database. **Data model look-ups of AHRI Certifications.862.[457.]
863.[458.] Efficient Refrigerators[459.] The eligibility for refrigerator replacement is determined by comparing
monitored consumption for the existing refrigerator with the rated consumption of the eligible replacement. Estimated savings are directly calculated based on the difference between these two values. Note that in the case where an under-utilized or unneeded refrigerator unit is removed, and no replacement is installed, the Refnew term of the equation will be zero.
864.[460.] 865.[461.] Algorithm
[462.] Energy SavingsElectricity Impact (kWh/yr) = Refold – Refnew
[463.] Peak Demand SavingsImpact (kW) = (Refold – Refnew) *(Ref DF)866.[464.]
867.[465.] Space Conditioning Measures
[466.] When available, gas heat measure savings will be based on heating use. If only total gas use is known, heating use will be estimated as total use less 300 therms.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
868.[467.] Air Sealing[468.] It is assumed that air sealing is the first priority among candidate space
conditioning measures. Expected percentage savings is based on previous experiences with measured savings from similar programs. Note there are no summer coincident electric peak demand savings estimated at this time.
869.[469.] Algorithm [470.] Energy SavingsElectricity Impact (kWh/yr) = ESCpre X 0.05870.[471.] MMBtu savings = (GHpre X 0.05)
871.[472.] Furnace/Boiler Replacement872.[473.] Quantification of savings due to furnace and boiler replacements
implemented under the low-income program will be based on the algorithms presented in the Residential Gas HVAC section of these Protocols.
873.[474.] Duct Sealing and Repair[475.] The second priority for homes with either Central Air Conditioning (CAC) or
some other form of ducted distribution of electric space conditioning (electric furnace, gas furnace or heat pump) is ensuring integrity and effectiveness of the ducted distribution system.
874.[476.] 875.[477.] Algorithm 876.[478.] With CAC
[479.] Energy SavingsElectricity Impact (kWh/yr) = (ECoolpre) X 0.10[480.] Peak Demand SavingsImpact (kW) = (Ecoolpre X 0.10) / EFLH X AC CF877.[481.] MMBtu savings = (GHpre X 0.02)
878.[482.] No CAC [483.] Energy SavingsElectricity Impact (kWh/yr) = (ESCpre.) X 0.02879.[484.] MMBtu savings = (GHpre X 0.02)
[485.] Combined space and water heating (Combo)[486.] [487.] Participants installing a qualifying boiler or furnace and a qualifying water heater
at the same time earn a special incentive. For savings calculations, there is no special consideration. The heating system savings are calculated according to the appropriate algorithm and the water heating savings are calculated separately according to the system type.
[488.] Insulation UpgradesUp-Grades [489.] For savings calculations, it is assumed that any applicable air sealing and duct
sealing/repair have been done, thereby reducing the space conditioning load, before consideration of upgrading insulation. Attic insulation savings are then projected on the basis of the “new” load. Gas savings are somewhat greater, as homes with gas heat generally have less insulation.
880.[490.] 881.[491.] Algorithm
[492.] Energy savingsElectricity Impact (kWh/yr) = (ESCpre) X 0.08
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
882.[493.] MMBtu savings = GHpre X 0.13
883.[494.] Thermostat Replacement884.[495.] Thermostats are eligible for consideration as an electric space conditioning
measure only after the first three priority items. Savings projections are based on a conservative 3% of the “new” load after installation of any of the top three priority measures.
885.[496.] 886.[497.] Algorithm
[498.] Energy SavingsElectricity Impact (kWh/yr) = (ESCpre) X 0.03 887.[499.] MMBtu savings = (GHpre X 0.03)
888.[500.] Heating and Cooling Equipment Maintenance Repair/Replacement889.[501.] Savings projections for heat pump charge and air flow correction. Protocol
savings account for shell measures having been installed that reduce the preexisting load.
890.[502.] 891.[503.] Algorithm
[504.] Energy SavingsElectricity Impact (kWh/yr) = (ESCpre) X 0.17[505.] Peak Demand SavingsImpact (kW) = (Capy/EER X 1000) X HP CF X
DSF
892.[506.] Other “Custom” Measures893.[507.] In addition to the typical measures for which savings algorithms have been
developed, it is assumed that there will be niche opportunities that should be identified and addressed. The savings for these custom measures will be reported based on the individual calculations supplied with the reporting. As necessary the program working group will develop specific guidelines for frequent custom measures for use in reporting and contractor tracking.
894.[508.] 895.[509.] Definition of Terms 896.[510.] CFLwatts = Average watts replaced for a CFL installation.897.[511.] CFLhours = Average daily burn time for CFL replacements.898.[512.] Fixtwatts = Average watts replaced for an efficient fixture installation.899.[513.] Fixthours = Average daily burn time for CFL replacements.900.[514.] Torchwatts = Average watts replaced for a Torchiere replacement.901.[515.] Torchhours = Average daily burn time for a Torchiere replacements.902.[516.] LEDwatts = Average watts replaced for an LED installation.903.[517.] LEDhours = Average daily burn time for LED replacements.904.[518.] LEDNwatts = Average watts replaced for an LED nightlight installation.905.[519.] LEDNhours = Average daily burn time for LED nightlight replacements.906.[520.] Light CF = Summer demand coincidence factor for all lighting measures.
Currently fixed at 5%.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
907.[521.] HWeavg = Average electricity savings from typical electric hot water measure package.
908.[522.] HWgavg = Average natural gas savings from typical electric hot water measure package.
909.[523.] HWwatts = Connected load reduction for typical hot water efficiency measures
910.[524.] HW CF = Summer demand coincidence factor for electric hot water measure package. Currently fixed at 75%.
911.[525.] Refold = Annual energy consumption of existing refrigerator based on on-site monitoring.
912.[526.] Refnew = Rated annual energy consumption of the new refrigerator.913.[527.] Ref DF = kW /kWh of savings. Refrigerator demand savings factor.914.[528.] Ref CF = Summer demand coincidence factor for refrigeration. Currently
100%, diversity accounted for in the Ref DF factor. 915.[529.] ESCpre = Pre-treatment electric space conditioning consumption.
916.[530.] ECoolpre = Pre-treatment electric cooling consumption.917.[531.] EFLH = Equivalent full load hours of operation for the average unit. This
value is currently fixed at 650 hours. 918.[532.] AC CF = Summer demand coincidence factor for air conditioning. Currently
85%.919.[533.] Capy = Capacity of Heat Pump in Btuh920.[534.] EER = Energy Efficiency Ratio of average heat pump receiving charge and air
flow service. Fixed at 9.2921.[535.] HP CF = Summer demand coincidence factor for heat pump. Currently fixed
at 70%.922.[536.] DSF = Demand savings factor for charge and air flow correction. Currently
fixed at 7%.923.[537.] GCpre = Pre-treatment gas consumption.924.[538.] GHpre = Pre-treatment gas space heat consumption (=.GCpre less 300 therms if
only total gas use is known.925.[539.] WS = Water Savings associated with water conservation measures. Currently
fixed at 3,640 gallons per year per home receiving low-flow showerheads, plus 730 gallons saved per year aerator installed.
926.[540.] Residential Low Income927.[541.] Com
ponent928.[542.] Type 929.[543.] Value [544.] Sourc
eSources930.[545.] CFLWatts 931.[546.] Fixed [547.] 42 wattsWatts 932.[548.] 1933.[549.] CFLHours 934.[550.] Fixed 935.[551.] 2.5 hours 936.[552.] 1937.[553.] Fix
tWatts
938.[554.] Fixed [555.] 100–-120 wattsWatts
939.[556.] 1
940.[557.] Fix 941.[558.] Fixed 942.[559.] 3.5 hours 943.[560.] 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
927.[541.] Component
928.[542.] Type 929.[543.] Value [544.] SourceSources
tHours
944.[561.] TorchWatts
945.[562.] Fixed [563.] 245 wattsWatts
946.[564.] 1
947.[565.] TorchHours
948.[566.] Fixed 949.[567.] 3.5 hours 950.[568.] 1
951.[569.] LEDWatts
952.[570.] Fixed [571.] 52 wattsWatts 953.[572.] 14
954.[573.] LEDHours
955.[574.] Fixed 956.[575.] 2.5 hours 957.[576.] 14
958.[577.] LEDNWatts
959.[578.] Fixed [579.] 6.75 wattsWatts
960.[580.] 14
961.[581.] LEDNHours
962.[582.] Fixed 963.[583.] 12 hours 964.[584.] 15
965.[585.] Light CF
966.[586.] Fixed 967.[587.] 5% 968.[588.] 2
969.[589.] Elec. Water
Heating Savings
970.[590.] Fixed 971.[591.] 178 kWh 972.[592.] 3
973.[593.] Gas Water
Heating Savings
974.[594.] Fixed [595.] 1.01 MMBtuMMBTU
975.[596.] 3
976.[597.] WS Water
Savings
977.[598.] Fixed [599.] 3,640 gal/year per home
receiving low- flow shower
heads, plus 1,460 gal/year per
home receiving aerators.
978.[600.] 12
979.[601.] HWwatts 980.[602.] Fixed 981.[603.] 0.022 kW 982.[604.] 4983.[605.] HW
CF984.[606.] Fixed 985.[607.] 75% 986.[608.] 4
987.[609.] Refold 988.[610.] Variable
989.[611.] 990.[612.] Contractor
Tracking991.[613.] Refnew 992.[614.] Varia
ble993.[615.] 994.[616.] Cont
ractor Tracking
and Manufactur
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
927.[541.] Component
928.[542.] Type 929.[543.] Value [544.] SourceSources
er data995.[617.] Ref
DF996.[618.] Fixed 997.[619.] 0.000139
kW/kWh savings998.[620.] 5
999.[621.] RefCF
1000.[622.] Fixed
1001.[623.] 100% 1002.[624.] 6
1003.[625.] ESCpre
1004.[626.] Variable
1005.[627.] 1006.[628.] 7
1007.[629.] Ecoolpre
1008.[630.] Variable
1009.[631.] 1010.[632.] 7
1011.[633.] ELFH
1012.[634.] Fixed
1013.[635.] 650 hours
1014.[636.] 8
1015.[637.] AC CF
1016.[638.] Fixed
1017.[639.] 85% 1018.[640.] 4
1019.[641.] Capy
1020.[642.] Fixed
1021.[643.] 33,000 Btu/hr
1022.[644.] 1
1023.[645.] EER 1024.[646.] Fixed
1025.[647.] 11.3 1026.[648.] 8
1027.[649.] HP CF
1028.[650.] Fixed
1029.[651.] 70% 1030.[652.] 9
1031.[653.] DSF 1032.[654.] Fixed
1033.[655.] 7% 1034.[656.] 10
1035.[657.] GCpre
1036.[658.] Variable
1037.[659.] 1038.[660.] 7
1039.[661.] GHpre
1040.[662.] Variable
1041.[663.] 1042.[664.] 7
1043.[665.] Time Period
Allocation Factors – Electric
1044.[666.]
1045.[667.] Fixed
1046.[668.] Summer/On-Peak 21%
1047.[669.] Summer/Off-Peak 22%
1048.[670.] Winter/On-Peak 28%
1049.[671.] Winter/Off-Peak 29%
1050.[672.] 11
1051.[673.] Time Period
Allocation Factors –
Gas
1052.[674.] Fixed
1053.[675.] Heating:1054.[676.] Summer
12%1055.[677.] Winter
88%1056.[678.] Non-
Heating:1057.[679.] Summer
1059.[681.] 13
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
927.[541.] Component
928.[542.] Type 929.[543.] Value [544.] SourceSources
50%1058.[680.] Winter
50%1060.[682.] 1061.[683.] Sources/Notes :
1. Working group expected averages for product specific measures. 2. Efficiency Vermont, Technical Reference User Manual, 2016 – average for lighting
products. 3. Experience with average hot water measure savings from low income and direct
install programs.4. VEIC estimate.[5.] UI Refrigerator Load Data profile, .16 kW (5 p.m.5pm July) and 1,147 kWh annual
consumption.5.[6.] Diversity accounted for by Ref DF.6.[7.] Billing histories and (for electricity) contractor calculations based on program
procedures for estimating space conditioning and cooling consumption.7.[8.] Average EER for SEER 13 units.8.[9.] Analysis of data from 6 utilities by Proctor Engineering9.[10.] From Neme, Proctor and Nadel, 1999.10.[11.] These allocations may change with actual penetration numbers are available.[12.] VEIC estimate, assuming 1 GPM reduction for 14 5-five minute showers per week
for shower heads, and 4 gallons saved per day for aerators.[13.] Heating: Prorated based on 12% of the annual degree days falling in the summer
period and 88% of the annual degree days falling in the winter period.[684.] Non-Heating: Prorated based on 6 months in the summer period and 6 months in the winter period.
[14.] “NJ Comfort Partners Energy Saving Protocols and Engineering Estimates,”.” Apprise, June 2014; available. Available at http://www.njcleanenergy.com/files/file/Protocol%20and%20Engineering%20Estimate%20Summary.pdft.http://www.njcleanenergy.com/files/file/Protocol%20and%20Engineering%20Estimate%20Summary.pdft
[15.] Pennsylvania Technical Reference Manual,. June 2016, p.. Page 27; available. Available at http://www.puc.pa.gov/pcdocs/1370278.docxt.http://www.puc.pa.gov/pcdocs/1370278.docxt
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Residential New Construction Program
Protocols
Single-Family, Multi-Single and Low-Rise Multifamily Building Shell[685.] Energy savings due to thermal shell and mechanical equipment improvements
in residential new construction and “gut” renovation projects are calculated using outputs from REM/Rate™ modeling software19. All program homes are modeled in REM/Rate to estimate annual energy consumption for heating, cooling, and hot water. Standards for energy efficient new construction in New Jersey are based on national platforms including IECC 2015, EPA ENERGY STAR® Certified New Homes Program, EPA ENERGY STAR Multifamily High-Rise Program (MFHR), and the DOE Zero Energy Ready Home (ZERH) Program
1062. Single-Family, Multi-Single (townhomes), Low-Rise Multifamily1063. The program home is then modeled to a baseline specification using
REM/Rate’s User Defined Reference Home (UDRH) feature. [686.] The RNC program currently specifies three standards for UDRH baseline
reference: IECC 2015 Energy Rating Index (for specification is for homes permitted on
orprior to and IECC 2015 for homes permitted after March 21, 2016) ENERGY STAR Certified Home v3.1 Zero Energy Ready Home &Zero Energy Home + RE
1064. 1065. The difference in modeled annual energy consumption between the program
and UDRH baseline home is the project savings for heating, hot water, cooling, lighting and appliance end uses. Coincident peak demand savings are also derived from REM/Rate modeled outputs.
[687.] algorithms that calculate energy and demand savings are as follows: [688.] [689.] Energy Savings = (Baseline home energy consumption – Program home
energy consumption)[690.]
[691.] table describes the baseline characteristics of Climate Zone 4 and 5 reference homes for single-family, multi-single and low-rise multifamily buildings.
[692.]
19 Accredited Home Energy Rating Systems (HERS) software, http://www.remrate.com/
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[693.] REM/Rate User Defined Reference Homes Definition[694.] Applicable to buildings permitted prior to March 21, 2016 -- Reflects IECC 2009
[695.] N
[696.] Data Point [697.] Climate Zone 4 [698.] Climate Zone 5[699.] (
[700.] Ceiling Insulation [701.] U=0.030 [702.] U=0.030[703.] [704.] Radiant Barrier [705.] None [706.] None[707.] (
[708.] Rim/Band Joist [709.] U=0.082 [710.] U=0.057[711.] ( [712.] Exterior Walls -
Wood [713.] U=0.082 [714.] U=0.057[715.] ( [716.] Exterior Walls -
Steel [717.] U=0.082 [718.] U=.057 [719.] [720.] Foundation Walls [721.] U=0.059 [722.] U=0.059[723.] (
[724.] Doors [725.] U=0.35 [726.] U=0.35[727.] (
[728.] Windows [729.] U=0.35 , SHGC=NR [730.] U=0.35 , SHGC=NR[731.] (
[732.] Glass Doors [733.] U=0.35 , SHGC=NR [734.] U=0.35 , SHGC=NR[735.] (
[736.] Skylights [737.] U=0.60 , SHGC=NR [738.] U=0.60 , SHGC=NR[739.] (
[740.] Floor [741.] U=0.047 [742.] U=.033 [743.] [744.] Unheated Slab on
Grade [745.] R-10, 2 ft [746.] R-10, 2 ft[747.] [748.] Heated Slab on
Grade [749.] R-15, 2 ft [750.] R-15, 2 ft[751.] [752.] Air Infiltration
Rate [753.] 7 ACH50 [754.] 7 ACH50[755.]
[756.] Duct Leakage[757.] 8 cfm25 per 100ft2
CFA[758.] 8 cfm25 per 100ft2
CFA [759.] [760.] Mechanical
Ventilation [761.] None [762.] None[763.] [764.] Lights and
Appliances [765.] Use RESNET Default [766.] Use RESNET
Default
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[693.] REM/Rate User Defined Reference Homes Definition[694.] Applicable to buildings permitted prior to March 21, 2016 -- Reflects IECC 2009
[767.] [768.] Thermostat [769.] Manual [770.] Manual[771.] [772.] Heating Efficiency [773.] [774.] [775.] (
[776.] Furnace [777.] 80% AFUE [778.] 80% AFUE[779.] [780.] Boiler [781.] 80% AFUE [782.] 80% AFUE[783.] [784.] Combo Water
Heater[785.] 76% AFUE
(Recovery Efficiency)[786.] 76% AFUE
(Recovery Efficiency)[787.] [788.] Air Source Heat
Pump [789.] 7.7 HSPF [790.] 7.7 HSPF[791.] [792.] Cooling Efficiency [793.] [794.] [795.] [796.] Central Air
Conditioning & Window AC units
[797.] 13.0 SEER [798.] 13.0 SEER
[799.] [800.] Air Source Heat Pump [801.] 13.0 SEER [802.] 13.0 SEER
[803.] ( [804.] Domestic WH
Efficiency [805.] [806.] [807.] [808.] Electric stand-
alone tank [809.] 0.90 EF [810.] 0.90 EF [811.] [812.] Natural Gas
stand-alone tank [813.] 0.58 EF [814.] 0.58 EF[815.] [816.] Electric
instantaneous [817.] 0.93 EF [818.] 0.93 EF[819.] [820.] Natural Gas
instantaneous [821.] 0.62 EF [822.] 0.62 EF[823.] [824.] Water Heater Tank
Insulation [825.] None [826.] None[827.] [828.] Duct Insulation,
attic supply [829.] R-8 [830.] R-8[831.] [832.] Duct Insulation, all
other [833.] R-6 [834.] R-6[835.] [836.] Active Solar [837.] None [838.] None[839.] [840.] Photovoltaics [841.] None [842.] None
[843.] [844.] [845.] UDRH Table Notes[846.]
[847.] (
[848.] U values represent total wall system U value, including all components (i.e., clear wall, windows, doors).[849.] Type A-1 - Detached one and two family dwellings.[850.] Type A-2 - All other residential buildings, three stories in height or less.
[851.] [852.] All frame floors shall meet this requirement. There is no requirement for floors
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
( over basements and/or unvented crawl spaces when the basement and/or unvented crawl space walls are insulated.
[853.] (
[854.] MEC 95 minimum requirement is 78 AFUE. However, 80 AFUE is adopted for New Jersey based on typical minimum availability and practice.
[855.] (
[856.] Based on the Federal Government standard for calculating EF (50 gallon assumed):
[857.] •Gas-fired Storage-type EF: 0.67 - (0.0019 x Rated Storage Volume in gallons)[858.] •Electric Storage-type EF: 0.97 - (0.00132 x Rated Storage Volume in gallons)[859.] •Instantaneous Gas-fired EF: 0.62 - (0.0019 x Rated Storage Volume in gallons)[860.] •Instantaneous Electric EF: 0.93 - (0.0013 x Rated Storage Volume in gallons)
[861.] [862.] REM/Rate User Defined Reference Homes Definition
[863.] Applicable to buildings permitted on or after March 21, 2016 -- Reflects IECC 2015
[864.] N
[865.] Data Point [866.] Climate Zone 4 [867.] Climate Zone 5[868.] (
[869.] Ceiling Insulation [870.] U= 0.026 [871.] U=0.026[872.] [873.] Radiant Barrier [874.] None [875.] None[876.] (
[877.] Rim/Band Joist [878.] U=0.060 [879.] U=0.060[880.] ( [881.] Exterior Walls -
Wood [882.] U=0.060 [883.] U=0.060[884.] ( [885.] Exterior Walls -
Steel [886.] U=0.060 [887.] U=0.060 [888.] [889.] Foundation Walls [890.] U=0.059 [891.] U=0.050[892.] (
[893.] Doors [894.] U=0.35 [895.] U=0.32[896.] (
[897.] Windows [898.] U=0.35 , SHGC=40 [899.] U=0.32 , SHGC=NR[900.] (
[901.] Glass Doors [902.] U=0.35 , SHGC=40 [903.] U=0.32 , SHGC=NR[904.] (
[905.] Skylights [906.] U=0.55 , SHGC=40 [907.] U=0.55 , SHGC=NR[908.] (
[909.] Floor [910.] U=0.047 [911.] U=.033
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[862.] REM/Rate User Defined Reference Homes Definition[863.] Applicable to buildings permitted on or after March 21, 2016 -- Reflects IECC
2015
[912.] [913.] Unheated Slab on Grade [914.] R-10, 2 ft [915.] R-10, 2 ft
[916.] [917.] Heated Slab on Grade [918.] R-15, 2 ft [919.] R-15, 2 ft
[920.] ( [921.] Air Infiltration
Rate [922.] 7 ACH50 [923.] 7 ACH50[924.]
[925.] Duct Leakage[926.] 4 cfm25 per 100ft2
CFA[927.] 4 cfm25 per 100ft2
CFA [928.] [929.] Mechanical
Ventilation [930.] Exhaust only [931.] Exhaust only[932.] [933.] Lighting [934.] 75% efficient [935.] 75% efficient[936.]
[937.] Appliances [938.] Use RESNET Default [939.] Use RESNET
Default[940.] (
[941.] Thermostat [942.] Manual [943.] Manual[944.] [945.] Heating Efficiency [946.] [947.] [948.] (
[949.] Furnace [950.] 80% AFUE [951.] 80% AFUE[952.] [953.] Boiler [954.] 80% AFUE [955.] 80% AFUE[956.] [957.] Combo Water
Heater[958.] 76% AFUE
(Recovery Efficiency)[959.] 76% AFUE
(Recovery Efficiency)[960.] [961.] Air Source Heat
Pump [962.] 8.2 HSPF [963.] 8.2 HSPF[964.] [965.] Cooling Efficiency [966.] [967.] [968.] [969.] Central Air
Conditioning & Window AC units
[970.] 13.0 SEER [971.] 13.0 SEER
[972.] [973.] Air Source Heat Pump [974.] 14.0 SEER [975.] 14.0 SEER
[976.] ( [977.] Domestic WH
Efficiency [978.] [979.] [980.] [981.] Electric stand-
alone tank [982.] 0.90 EF [983.] 0.90 EF [984.] [985.] Natural Gas
stand-alone tank [986.] 0.60 EF [987.] 0.60 EF[988.] [989.] Electric
instantaneous [990.] 0.93 EF [991.] 0.93 EF[992.] [993.] Natural Gas [994.] 0.82 EF [995.] 0.82 EF
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[862.] REM/Rate User Defined Reference Homes Definition[863.] Applicable to buildings permitted on or after March 21, 2016 -- Reflects IECC
2015instantaneous
[996.] [997.] Water Heater Tank Insulation [998.] None [999.] None
[1000.] [1001.] Duct Insulation, attic [1002.] R-8 [1003.] R-8
[1004.] [1005.] Duct Insulation, all other [1006.] R-6 [1007.] R-6
[1008.] [1009.] Active Solar [1010.] None [1011.] None[1012.] [1013.] Photovoltaics [1014.] None [1015.] None
[1016.] (
[1017.] U values represent total system U value, including all components (i.e., clear wall, windows, doors).
[1018.] Type A-1 - Detached one and two family dwellings.[1019.] Type A-2 - All other residential buildings, three stories in height or less.
[1020.] (
[1021.] All frame floors shall meet this requirement. There is no requirement for floors over basements and/or unvented crawl spaces when the basement and/or unvented crawl space walls are insulated.
[1022.] (
[1023.] Based on New Jersey’s amendment making the IECC 2015 requirement for air leakage testing optional, there is no empirical evidence that baseline new construction is achieving the 3 ACH50 tightness level through a visual inspection of checklist air sealing items.
[1024.] (
[1025.] While the code requires a programmable actual programming is an occupant behavior, both the rated home and reference home are set at fixed temperatures of 68 heating and 78 cooling, so that no savings are counted or lost
[1026.] (
[1027.] MEC 95 minimum requirement is 78 AFUE. However, 80 AFUE is adopted for New Jersey based on typical minimum availability and practice.
[1028.] (
[1029.] Based on the Federal Government standard for calculating EF (50 gallon assumed):
[1030.] •Gas-fired Storage-type EF: 0.675 - (0.0015 x Rated Storage Volume in gallons)
[1031.] •Electric Storage-type EF: 0.97 - (0.00132 x Rated Storage Volume in gallons)[1032.] •Instantaneous Gas-fired EF: 0.82 - (0.0019 x Rated Storage Volume in
gallons)[1033.] •Instantaneous Electric EF: 0.93 - (0.0013 x Rated Storage Volume in gallons
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1034.]
[1035.] Multifamily High Rise (MFHR) ProtocolsMultifamily High Rise (MFHR)
[1036.]
[1037.] Annual energy and summer coincident peak demand savings for MFHR construction projects (4–6 stories) shall be calculated from the Energy StarEPA Project Submittal document, 'As-Built Performance Path CalculatorCalculator' (PPC)20.). The PPC captures outputs from eQuest modeling software. Coincident peak demand is calculated only for the following end uses: space cooling, lighting, and ventilation. Clothes washer data cannot be parsed out of the PPC "Misc Equip' field. RNC coincident factors are applied to the MFHR demand savings.
1066.[1038.] Energy and demand savings are calculated using the following equations:
1067.[1039.] Energy Savings = Average Baseline energy (kWh and/or therms) - Proposed Design energy (kWh and/or therms)
1068.[1040.] Coincident peak demand = (Average Baseline non-coincident peak demand - Proposed Design non-coincident peak demand) * Coincidence Factor
1069.[1041.]
20 https://www.energystar.gov/index.cfm?c=bldrs_lenders_raters.nh_mfhr_guidance
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
ENERGY STAR Energy Efficient Products Program
1070.[1042.] Protocols1071. ENERGY STAR Appliances, ENERGY STAR Lighting, ENERGY STAR Windows,
and ENERGY STAR Audit[1043.] ENERGY STAR Appliances[1044.] Protocols[1045.] The following sections detail savings calculations ENERGY STAR Appliances and
Lighting Products.
1072. ENERGY STAR Appliances
1073. The general form of the equation for the ENERGY STAR Appliance Program measure savings algorithms is:
[1046.] Number of Units *X Savings per Unit
[1047.] To determine resource savings, the per unit estimates in the protocols will be multiplied by the number of appliance units. The number of units will be determined using market assessments and market tracking.
1074.[1048.] ENERGY STAR Refrigerators – CEE Tier 1 [1049.] Electricity SavingsImpact (kWh/yr) = ESavREF1
[1050.] Peak Demand SavingsImpact (kW) = DSavREF1 *x CFREF
1075.
1076.[1051.] ENERGY STAR Refrigerators – CEE Tier 2 [1052.] Electricity SavingsImpact (kWh/yr) = ESavREF2
[1053.] Peak Demand SavingsImpact (kW) = DSavREF2 *x CFREF
1077.
1078.[1054.] ENERGY STAR Clothes Washers – CEE Tier 1 [1055.] Electricity SavingsImpact (kWh/yr) = ESavCW1 [1056.] Peak Demand SavingsImpact (kW) = DSavCW1 *x CFCW
[1057.] Gas SavingsImpact (Therms/yr) = EGSavCW1
[1058.] Water SavingsImpact (gallons/yr) = WSavCW1
1079.
1080.[1059.] ENERGY STAR Clothes Washers – CEE Tier 2 [1060.] Electricity SavingsImpact (kWh/yr) = ESavCW2 [1061.] Peak Demand SavingsImpact (kW) = DSavCW2 *x CFCW
[1062.] Gas SavingsImpact (Therms/yr) = EGSavCW2
[1063.] Water SavingsImpact (gallons/yr) = WSavCW2
1081.
1082.[1064.] ENERGY STAR Set Top Boxes [Inactive 2017, Not Reviewed] 1083.[1065.] Electricity Impact (kWh) = ESavSTB
1084.[1066.] Demand Impact (kW) = DSavSTB x CFSTB
1085.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1086.[1067.] Advanced Power Strip – Tier 1 1087.[1068.] Electricity Impact (kWh) = ESavAPS
1088.[1069.] Demand Impact (kW) = DSavAPS x CFAPS
1089.
1090.[1070.] Advanced Power Strip – Tier 2 1091.[1071.] Electricity Impact (kWh) = ESavAPS2
1092.[1072.] Demand Impact (kW) = DSavAPS2 x CFAPS
1093.
1094.[1073.] ENERGY STAR Electric Clothes Dryers – Tier 1 [1074.] Electricity SavingsImpact (kWh/yr) = ESavCDE1
[1075.] Peak Demand SavingsImpact (kW) = DSavCDE1 *x CFCD
1095.[1076.]
1096.[1077.] ENERGY STAR Gas Clothes Dryers – Tier 1 [1078.] Electricity SavingsImpact (kWh/yr) = ESavCDG1
[1079.] Peak Demand SavingsImpact (kW) = DSavCDG1 *x CFCD
[1080.] Gas SavingsImpact (Therms/yr) = GSavCDG1
1097.[1081.] [1082.] ENERGY STAR 2014 Emerging Technology Award Electric Clothes Dryers – Tier
2[1083.] Electricity SavingsImpact (kWh/yr) = ESavCDE2
[1084.] Peak Demand SavingsImpact (kW) = DSavCDE2 x CFCD
1098.[1085.]
[1086.] ENERGY STAR 2014 Emerging Technology Award Gas Clothes Dryers – Tier 2 [1087.] Energy SavingsElectricity Impact (kWh/yr) = ESavCDG2
[1088.] Peak Demand SavingsImpact (kW) = DSavCDG2 x CFCD
[1089.] Gas SavingsImpact (Therms/yr) = GSavCDG2) = GSavCDG1
1099.[1090.] 1100. ENERGY STAR Room AC – Tier 1 [Inactive 2017, Not Reviewed] 1101.[1091.] Electricity Impact (kWh) = ESavRAC1
1102.[1092.] Demand Impact (kW) = DSavRAC1 1103.[1093.] 1104.[1094.] ENERGY STAR Room AC – Tier 2 [Inactive 2017, Not Reviewed] 1105.[1095.] Electricity Impact (kWh) = ESavRAC2
1106.[1096.] Demand Impact (kW) = DSavRAC2 1107.1108.[1097.] ENERGY STAR Room Air Purifier [Inactive 2017, Not Reviewed] 1109.[1098.] Electricity Impact (kWh) = ESavRAPDemand Savings (kW) 1110.[1099.] 1111.[1100.] Where ESavRAP is based on the CADR in table below
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1112.[1101.] Room Air Purifier Deemed kWh Table
1113.[1102.] Clean Air
Delivery Rate
(CADR)
1114.[1103.] CADR
used in
calculation
1115.[1104.] Baseline
Unit Energ
y Consumption (kWh/year)
1116.[1105.] ENERGY STAR Unit
Energy Consump
tion (kWh/yea
r)
1117.[1106.] ESavRAP
1118.[1107.] CADR 51-
100
1119.[1108.] 75
1120.[1109.] 441
1121.[1110.] 148
1122.[1111.] 293
1123.[1112.] CADR 101-
150
1124.[1113.] 125
1125.[1114.] 733
1126.[1115.] 245
1127.[1116.] 488
1128.[1117.] CADR 151-
200
1129.[1118.] 175
1130.[1119.] 1025
1131.[1120.] 342
1132.[1121.] 683
1133.[1122.] CADR 201-
250
1134.[1123.] 225
1135.[1124.] 1317
1136.[1125.] 440
1137.[1126.] 877
1138.[1127.] CADR Over
250
1139.[1128.] 275
1140.[1129.] 1609
1141.[1130.] 537
1142.[1131.] 1072
1143.[1132.] 1144.[1133.] = DSavRAC2 is based on the CADR in the table below1145.[1134.]
1146.[1135.] Room Air Purifier Deemed kW Table
1147.[1136.] Clean Air Delivery Rate
1148.[1137.] DSavRAC2
1149.[1138.] CADR 51-100
1150.[1139.] 0.034
1151.[1140.] CADR 101-150
1152.[1141.] 0.056
1153.[1142.] CADR 151-200
1154.[1143.] 0.078
1155.[1144.] CADR 201-250
1156.[1145.] 0.101
1157.[1146.] CADR Over 250
1158.[1147.] 0.123
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1159.[1148.] ENERGY STAR Freezer [Inactive 2017, Not Reviewed] 1160.[1149.] Electricity Impact (kWh) = ESavFRZ
1161.[1150.] Demand Impact (kW) = DSavFRZ based on table below1162.1163.[1151.] ENERGY STAR Soundbar [Inactive 2017, Not Reviewed] 1164.[1152.] Electricity Impact (kWh) = ESavSDB
1165.[1153.] Demand Impact (kW) = DSavSDB 1166.[1154.] [1155.] Definition of Variables Terms 1167.[1156.] [1157.] ESavREF1 = Electricity savings per purchased ENERGY STAR refrigerator – CEE Tier
1.1168.[1158.] DSavREF1 = Summer demand savings per purchased ENERGY STAR refrigerator –
CEE Tier 1.1169.[1159.] ESavREF2 = Electricity savings per purchased ENERGY STAR refrigerator – CEE
Tier 2.1170.[1160.] DSavREF2 = Summer demand savings per purchased ENERGY STAR refrigerator –
CEE Tier 2.1171.[1161.] ESavCW1 = Electricity savings per purchased ENERGY STAR clothes washer.1172.[1162.] DSavCW1 = Summer demand savings per purchased ENERGY STAR clothes
washer.1173.[1163.] GSavCW1 = Gas savings per purchased clothes washer ENERGY STAR clothes
washer.1174.[1164.] WSavCW1 = Water savings per purchased clothes washer ENERGY STAR clothes
washer.[1165.] ESavCW2 = Electricity savings per purchased CEE Tier 2 ENERGY STAR clothes
washer.[1166.] DSavCW2 = Summer demand savings per purchased CEE Tier 2 ENERGY STAR clothes
washer.[1167.] GSavCW2 = Gas savings per purchased CEE Tier 2 ENERGY STAR clothes washer[1168.] WSavCW2 = Water savings per purchased CEE Tier 2 ENERGY STAR clothes washer.1175.[1169.] ESavSTB = Electricity savings per purchased ENERGY STAR set top box.1176. DSavSTB = Summer demand savings per purchased ENERGY STAR set top box.1177. ESavAPS1 = Electricity savings per purchased advanced power strip.1178.[1170.] DSavAPS1 = Summer demand savings per purchased advanced power strip.1179.[1171.] ESavAPS2 = Electricity savings per purchased Tier 2 advanced power strip.1180.[1172.] DSavAPS2 = Summer demand savings per purchased Tier 2 advanced power
strip.1181.[1173.] ESavCDE1 = Electricity savings per purchased ENERGY STAR electric clothes
dryer.1182.[1174.] DSavCDE1 = Summer demand savings per purchased ENERGY STAR electric
clothes dryer.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1183.[1175.] ESavCDG1 = Electricity savings per purchased ENERGY STAR gas clothes dryer.[1176.] DSavCDG1 = Summersummer demand savings per purchased ENERGY STAR gas clothes
dryer.1184.[1177.] GSavCDG1 = Gas savings per purchased ENERGY STAR gas clothes dryer.[1178.] ESavCDE2 = Electricity savings per purchased Tier 2 ENERGY STAR electric clothes
dryer meeting the ENERGY STAR 2014 Emerging Technology Award criteria.[1179.] DSavCDE2 = Demand savings per purchased Tier 2 ENERGY STAR electric clothes
dryer. meeting the ENERGY STAR 2014 Emerging Technology Award criteria.[1180.] ESavCDG2 = Electricity savings per purchased Tier 2 ENERGY STAR gas clothes dryer
meeting the ENERGY STAR 2014 Emerging Technology Award criteria.[1181.] DSavCDG2 = Demand savings per purchased gas Tier 2clothes dryer meeting the
ENERGY STAR gas clothes dryer2014 Emerging Technology Award criteria.[1182.] GSavCDG2 = Gas savings per purchased Tier 2 ENERGY STAR gas clothes dryer,
meeting the ENERGY STAR 2014 Emerging Technology Award criteria.1185.[1183.] ESavRAC1 = Electricity savings per purchased ENERGY STAR room air
conditioner.1186.[1184.] DSav RAC1 = Summer demand savings per purchased ENERGY STAR room air
conditioner.1187.[1185.] ESavRAC1 = Electricity savings per purchased Tier 2 room air conditioner.1188.[1186.] DSav RAC2 = Summer demand savings per purchased Tier 2 room air conditioner.1189.[1187.] ESavRAC1 = Electricity savings per purchased ENERGY STAR room air purifier.1190.[1188.] DSav RAP = Summer demand savings per purchased ENERGY STAR room air
purifier.1191.[1189.] ESavFRZ = Electricity savings per purchased ENERGY STAR freezer.1192.[1190.] DSav FRZ = Summer demand savings per purchased ENERGY STAR freezer.1193.[1191.] ESavSDB = Electricity savings per purchased ENERGY STAR soundbar.1194.[1192.] DSavSDB = Summer demand savings per purchased ENERGY STAR soundbar1195.[1193.] TAF = Temperature Adjustment Factor1196.[1194.] LSAF = Load Shape Adjustment Factor1197.[1195.] CFREF, CFCW, , CFDH, CFRAC, , CFSTB, , , , CFAPS, CFCD = Summer demand
coincidence factor. 1198.[1196.] 1199. Summary of Inputs
1200. ENERGY STAR Appliances1201.[1197.] Comp
onent1202.[1198.]
Type1203.[1199.] Value 1204.[1200.]
Sources1205.[1201.] ESa
vREF1
1206.[1202.] Fixed
1207.[1203.] 59 kWh 1208.[1204.] 5
1209.[1205.] DSavREF1
1210.[1206.] Fixed
1211.[1207.] 0.007 kW 1212.[1208.] 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1201.[1197.] Component
1202.[1198.] Type
1203.[1199.] Value 1204.[1200.] Sources
1213.[1209.] ESavREF2
1214.[1210.] Fixed
1215.[1211.] 89 kWh 1216.[1212.] 5
1217.[1213.] DSavREF2
1218.[1214.] Fixed
1219.[1215.] 0.01 kW 1220.[1216.] 5
1221.[1217.] REF Time Period Allocation
Factors
1222.[1218.] Fixed
1223.[1219.] Summer/On-Peak 20.9%
1224.[1220.] Summer/Off-Peak 21.7%
1225.[1221.] Winter/On-Peak 28.0%
1226.[1222.] Winter/Off-Peak 29.4%
1227.[1223.] 1
1228.[1224.] ESavCW1
1229.[1225.] Fixed
1230.[1226.] 55 kWh 1231.[1227.] 2
1232.[1228.] GsavCW1
1233.[1229.] Fixed
1234.[1230.] 4.8 therms
1235.[1231.] 2
1236.[1232.] DSavCW1
1237.[1233.] Fixed
1238.[1234.] 0.005 kW 1239.[1235.] 2
1240.[1236.] WSavCW1
1241.[1237.] Fixed
1242.[1238.] 2175 gallons
1243.[1239.] 2
1244.[1240.] ESavCW2
1245.[1241.] Fixed
1246.[1242.] 61 kWh 1247.[1243.] 2
1248.[1244.] GsavCW2
1249.[1245.] Fixed
1250.[1246.] 9.00 therms
1251.[1247.] 2
1252.[1248.] DSavCW2
1253.[1249.] Fixed
1254.[1250.] 0.006 kW 1255.[1251.] 2
1256.[1252.] WSavCW2
1257.[1253.] Fixed
1258.[1254.] 2966 gallons
1259.[1255.] 2
1260.[1256.] CW, CD Electricity Time Period Allocation
Factors
1261.[1257.] Fixed
1262.[1258.] Summer/On-Peak 24.5%
1263.[1259.] Summer/Off-Peak 12.8%
1264.[1260.] Winter/On-Peak 41.7%
1265.[1261.] Winter/Off-Peak 21.0%
1266.[1262.] 1
1267.[1263.] CW, CD Gas Time
Period Allocation Factors
1268.[1264.] Fixed
1269.[1265.] Summer 50%
1270.[1266.] Winter 50%
1271.[1267.] 3
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1201.[1197.] Component
1202.[1198.] Type
1203.[1199.] Value 1204.[1200.] Sources
1272.[1268.] CFREF,
CFCW, CFSTB,
CFAPS, CFCD
1273.[1269.] Fixed
[1270.] 1.01.0, 1.0, 1.0, 1.0, 1.0, 1.0
1274.[1271.] 4
1275.[1272.] CFAC 1276.[1273.] Fixed
1277.[1274.] 0.31 1278.[1275.] 14
1279.[1276.] ESavSTB
1280.[1277.] Fixed
1281.[1278.] 44 kWh [1279.] 67
1282.[1280.] DSavSTB
1283.[1281.] Fixed
1284.[1282.] 0.005 kW [1283.] 67
1285.[1284.] ESavAPS1
1286.[1285.] Fixed
1287.[1286.] 102.8 kWh
1288.[1287.] 8
1289.[1288.] DSavAPS1
1290.[1289.] Fixed
1291.[1290.] 0.012 kW 1292.[1291.] 8
1293.[1292.] ESavAPS2
1294.[1293.] Fixed
1295.[1294.] 346 kWh 1296.[1295.] 9
1297.[1296.] DSavAPS2
1298.[1297.] Fixed
1299.[1298.] 0.039 kW 1300.[1299.] 9
1301.[1300.] APS, STB Time
Period Allocation
Factors
1302.[1301.] Fixed
1303.[1302.] Summer/On-Peak 16%
1304.[1303.] Summer/Off-Peak 17%
1305.[1304.] Winter/On-Peak 32%
1306.[1305.] Winter/Off-Peak 35%
1307.[1306.] 10
1308.[1307.] ESavCDE1
1309.[1308.] Fixed
1310.[1309.] 186 kWh 1311.[1310.] 12
1312.[1311.] DSavCDE1
1313.[1312.] Fixed
1314.[1313.] 0.016 kW 1315.[1314.] 12
1316.[1315.] ESavCDG1
1317.[1316.] Fixed
1318.[1317.] 9 kWh 1319.[1318.] 12
1320.[1319.] DSavCDG1
1321.[1320.] Fixed
1322.[1321.] 0.001 kW 1323.[1322.] 12
1324.[1323.] GSavCDG1
1325.[1324.] Fixed
1326.[1325.] 5.8 therms
1327.[1326.] 12
1328.[1327.] ESavCDE2
1329.[1328.] Fixed
1330.[1329.] 388 kWh 1331.[1330.] 12,13
1332.[1331.] DSavCDE2
1333.[1332.] Fixed
1334.[1333.] 0.029 kW 1335.[1334.] 12,13
1336.[1335.] ESavCDG2
1337.[1336.] Fixed
1338.[1337.] 42.94 kWh
1339.[1338.] 14
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1201.[1197.] Component
1202.[1198.] Type
1203.[1199.] Value 1204.[1200.] Sources
1340.[1339.] DSavCDG2
1341.[1340.] Fixed
1342.[1341.] 0.003 kW 1343.[1342.] 14
1344.[1343.] GSavCDG2
1345.[1344.] Fixed
1346.[1345.] 7.69 therms
1347.[1346.] 14
1348.[1347.] ESavRAC1
1349.[1348.] Fixed
1350.[1349.] 9 kWh 1351.[1350.] 14
1352.[1351.] DSavRAC1
1353.[1352.] Fixed
1354.[1353.] 0.008 1355.[1354.] 14
1356.[1355.] ESavRAC2
1357.[1356.] Fixed
1358.[1357.] 19.3 kWh 1359.[1358.] 14
1360.[1359.] DSavRAC2
1361.[1360.] Fixed
1362.[1361.] 0.018 1363.[1362.] 14
1364.[1363.] ESavRAP
1365.[1364.] Variable
1366.[1365.] Dependent on CARD
1367.[1366.]
1368.[1367.] DSavRAP
1369.[1368.] Variable
1370.[1369.] Dependent on CADR
1371.[1370.]
1372.[1371.] ESavFRZ
1373.[1372.] Fixed
1374.[1373.] 41.2 kWh 1375.[1374.] 14
1376.[1375.] DSavFRZ
1377.[1376.] Fixed
1378.[1377.] 0.0067 kW
1379.[1378.] 14
1380.[1379.] ESavSDB
1381.[1380.] Fixed
1382.[1381.] 44 kWh [1382.] 1514
1383. DSavSDB 1384. Fixed 1385. 0.0005 kW [1386.] 1514
1386.[1387.] TAF 1387.[1388.] Fixed
1388.[1389.] 1.23 1389.[1390.] 14
1390.[1391.] LSAF 1391.[1392.] Fixed
1392.[1393.] 1.15 1393.[1394.] 14
1394.[1395.] [1396.] Sources :
[1.] Time period allocation factors used in cost-effectiveness analysis. From residential appliance load shapes.
[2.] Clothes washer energy and water savings estimates are based on clothes washers that exceed the federal standard with a shipment weighted average measured integrated modified energy factor (IMEF) of 1.66 and integrated water factor (IWF) of 5.92 versus that of ENERGY STAR models with IMEF of 2.26 and of 3.93 and CEE Tier 2 models at IMEF of 2.74 and WF of 3.21. See Mid-Atlantic Technical Reference Manual Version 5.0 April 2015 p.page 209 available at http://www.neep.org/mid-atlantic-technical-reference-manual-v5. This assumes 87% of participants have gas water heating and 56% have gas drying (the balance being electric) based on 2009 RECS data for New Jersey. Demand savings are calculated based on 317 annual cycles from 2009 RECS data for New Jersey. See 2009 RECS Table HC8.8 Water Heating in U.S. Homes in Northeast
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Region, Divisions, and States and Table HC3.8 Home Appliances in Homes in Northeast Region, Divisions, and States.
1.[3.] Prorated based on 6 months in the summer period and 6 months in the winter period. 2.[4.] The coincidence of average appliance demand to summer system peak equals 1 for
demand impacts for all appliances reflecting embedded coincidence in the DSav factor.[5.] ENERGY STAR and CEE Tier 2 refrigerator savings are based on refrigerators that
exceed the federal standard with a shipment weighted average 2014 measured energy use of 592 kWh versus 533 kWh and 503 kWh respectively for eligible ENERGY STAR and CEE Tier 2 models. Demand savings estimated based on a flat 8760 hours of use during the year. Energy Star Ref: https://data.energystar.gov/Active-Specifications/ENERGY-STAR-Certified-Residential-Refrigerators/p5st-her9 CEE Tier 2 Ref: http://library.cee1.org/content/qualifying-product-lists-residential-refrigerators.http://library.cee1.org/content/qualifying-product-lists-residential-refrigerators
[6.] Energy savings represent the difference between the weighted average eligible ENERGY STAR V4.1 models (132 kWh) and minimum requirements of the 2012 voluntary agreement established by the cable industry and tied to ENERGY STAR V3.0 (88 kWh). Demand savings estimated based on a flat 8760 hours of use during the year. On average, demand savings are the same for both Active and Standby states and is based on 8760 hours usage.
3.[7.] Set top box lifetimes: National Resource Defense Counsel, Cable and Satellite Set-Top Boxes Opportunities for Energy Savings, 2005. http://www.nrdc.org/air/energy/energyeff/stb.pdf
[8.] 2010 NYSERDA Measure Characterization for Advanced Power Strips; study. Study based on review of:
a. Smart Strip Electrical Savings and Usability, Power Smart Engineering, October 27, 2008.
[b.] Final Field Research Report, Ecos Consulting, October 31, 2006; prepared. Prepared for California Energy Commission’s PIER Program.
[c.] Developing and Testing Low Power Mode Measurement Methods, Lawrence Berkeley National Laboratory (LBNL), September 2004; prepared. Prepared for California Energy1395.[1397.] Commission’s Public Interest Energy Research (PIER) Program.
[d.] 2005 Intrusive Residential Standby Survey Report, Energy Efficient Strategies, March, 2006.
[9.] Energy savings estimates are based on a California Plug Load Research Center report, “Tier 2 Advanced Power Strip Evaluation for Energy Saving Incentive.” Demand savings estimated based on a flat 8760 hours of use during the year. Savings for Tier 2 APS are temporarily included pending additional support.
4.[10.] 2011 Efficiency Vermont Load shape for Advanced Power Strips.[11.] Advanced Power Strip Measure Life: David Rogers, Power Smart Engineering, October
2008: "Smart Strip electrical savings and usability,” p 22", p22. [1398.] Clothes dryer energy and demand savings are based on NEEP, Mid-Atlantic
Technical Reference Manual, V6, May 2016.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
5. Version 5.0 April 2015 page 237 available at http://www.neep.org/mid-atlantic-technical-reference-manual-v5. Demand savings are calculated based on 297 annual cycles from 2009 RECS data for New Jersey (See RECS 2009 Table HC3.8 Home Appliances in Homes in Northeast Region, Divisions, and States) and an average 10.4 lb load based on paired ENERGY STAR washers. Available at http://www.neep.org/mid-atlantic-technical-reference-manual-v5.
6.[12.] Savings for clothes dryers meeting the 2014 Emerging Technology Award criteria assume an average of measured performance and a 50% usage of both normal and most efficient dryer settings for eligible models.
7. Clothes dryer energy and demand savings are based on NEEP, Mid-Atlantic Technical Reference Manual, V6, May 2016.1396.
[13.] Mid-Atlantic TRM V5[14.] Mid-Atlantic TRM V6 Draft[1399.]
[1400.] Residential ENERGY STAR Lighting[1401.] Savings from the installation of screw-in ENERGY STAR CFLs, ENERGY STAR
LED lamps, ENERGY STAR fluorescent torchieres, ENERGY STAR specialty LED fixtures, ENERGY STAR fixtures are based on a straightforward algorithm that calculates the difference between existing and new wattage, and the average daily hours of usage for the lighting unit being replaced.
[1402.] The coincidence factor (CF) discounts the peak demand savings to reflect the kW reduction realized during the summer on-peak demand period. This is based on typical operating schedules for the geographical area covered by the program.
[1403.] HVAC interactive factors are applied to capture the additional savings or penalty associated with the impact of lighting measures on the building’s HVAC system. A reduction in lighting load will result in additional cooling savings during the summer period, and a gas heating penalty during the winter period.
[1404.] Protocols[1405.] [1406.] Savings from installation of screw-in ENERGY STAR CFLs, ENERGY STAR
fluorescent torchieres, ENERGY STAR indoor fixtures and ENERGY STAR outdoor fixtures are based on a straightforward algorithm that calculates the difference between existing and new wattage, and the average daily hours of usage for the lighting unit being replaced. An “in-service” rate is used to reflect the fact that not all lighting products purchased are actually installed.
[1407.] [1408.] The general form of the equation for the ENERGY STAR or other high efficiency
lighting energy savings algorithm is:[1409.] [1410.] Number of Units X Savings per Unit
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1411.] [1412.] Per unit savings estimates are derived primarily from a 2004 Nexus Market Research
report evaluating similar retail lighting programs in New England (MA, RI and VT). Per unit savings will decrease for CFLs in operation after 2012 due to the effects of federal minimum efficiency standards for incandescent lighting. Because CFLs typically have rated lifespans of 6-8000 hours (5-7 years) and incandescent light bulbs are rated at 1000 hours (1 year), after 2013 there will be less of a difference between CFLs in service and the incandescents that they would have been replacing.
[1413.] [1414.] National lighting efficiency standards are being increased according to the Energy
Independence and Security Act of 2007 (EISA).21 EISA pertains to the efficiency of newly manufactured bulbs, not existing stock. Existing Protocol baselines and measure lifetimes will remain until the impact of the standard can be fully measured and quantified. The future EISA wattage standards are:
[1415.] [1416.] EISA Phase 1 Standard for General Service Bulbs[1417.]
Rated Lumen Ranges Maximum Rate Wattage
Minimum Rate Lifetime Effective Date
Efficacy Ranges (lumens per
watt) 1490-2600 (~90W –
150W) 72 1000 hrs 1/1/2012 21 – 36
1050-1489 (~75W – 90W) 53 1000 hrs 1/1/2013 20 – 28 750-1049 (~60W – 75W) 43 1000 hrs 1/1/2014 17 – 24 310-749 (~30W – 60W) 29 1000 hrs 1/1/2014 11 – 26
[1418.] [1419.] [1420.] ENERGY STAR CFL Standard and Specialty Bulbs [1421.]
[1422.] Standard CFL Wattage Equivalency 1
[1423.] [1424.] Specialty CFL Wattage Equivalency 1
[1425.] [1426.] Energy Savings (kWh) = (CFLwatts[CFLbase – CFLee]/1000) X CFLhours X 365 X CFLISR
[1427.] [1428.] Demand Savings (kW) = ([CFLbase – CFLee]CFLwatts/1000) X CF X CFLISR [1429.]
[1430.] ENERGY STAR LED Recessed Downlights & Integral Lamps /Fixtures [1431.]
[1432.] LED Fixture Wattage Equivalency
[1433.]
21 EISA information available at http://www1.eere.energy.gov/femp/regulations/eisa.html
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1434.] Energy Savings (kWh) = (([LEDbase – LEDee] / 1000) X LEDHours X 365 X LEDISR
[1435.] [1436.] Demand Savings (kW) = ([LEDbase – LEDee] /1000) X CF X LEDISR
[1437.] [1438.] Definition of Terms[1439.] [1440.] CFLbase = Based on lumens of the CFL bulb[1441.] [1442.] CFLee = Actual wattage of CFL purchased/installed[1443.] [1444.] CFLhours = Average hours of use per day per CFL[1445.] [1446.] CFBulb = Summer demand coincidence factor for CFLs and LEDs[1447.] [1448.] CFLISR = In-service rate per CFL[1449.] [1450.] [1451.] CFFixtures = Summer demand coincidence factor for CFL fixtures. [1452.] [1453.] LEDbase = Based on lumens of the LED[1454.] [1455.] LEDee = Actual wattage of LED purchased/installed[1456.] [1457.] LEDhours = Average hours of use per day per LED recessed downlight or integral
lamp[1458.] [1459.] LEDISR = In-service rate per LED recessed downlight or integral lamp[1460.] [1461.] LEDFbase = Based on lumens of the LED Fixture[1462.] [1463.] LEDFee = Actual wattage of LED Fixture purchased/installed[1464.] [1465.] LEDFhours = Average hours of use per day per LED Fixture recessed downlight or
integral lamp[1466.] [1467.] LEDFISR = In-service rate per LED Fixture recessed downlight or integral lamp[1468.] [1469.]
[1470.] ENERGY STAR Lighting[1471.] Compon
ent[1472.] Type [1473.] Value [1474.] S
ources
[1475.] CFLbase [1476.] Variable [1477.] Based on lumens
[1478.] 8
[1479.] CFLee [1480.] Variable [1481.] Actual bulb wattage
[1482.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1471.] Component
[1472.] Type [1473.] Value [1474.] Sources
[1483.] CFLhours [1484.] Fixed [1485.] 2.8 [1486.] 6[1487.] CFLISR [1488.] Fixed [1489.] 83.4% [1490.] 5[1491.] CFBulb [1492.] Fixed [1493.] 9.9 % [1494.] 4[1495.] LEDwatts [1496.] Variable [1497.] Based on
lumens[1498.] 8
[1499.] LEDee [1500.] Variable [1501.] Actual bulb wattage
[1502.]
[1503.] LEDhours [1504.] Fixed [1505.] 2.8 [1506.] 6[1507.] LEDISR [1508.] Fixed [1509.] 100% [1510.] 7[1511.] CFLED [1512.] Fixed [1513.] 8.2% [1514.] [1515.] LEDFwatts [1516.] Variable [1517.] Based on
lumens[1518.] 8
[1519.] LEDFee [1520.] Variable [1521.] Actual fixture wattage
[1522.]
[1523.] LEDFhours
[1524.] Fixed [1525.] 2.8 [1526.] 6
[1527.] LEDFISR [1528.] Fixed [1529.] 100% [1530.] 7[1531.] CFLEDF [1532.] Fized [1533.] 8.2% [1534.]
[1535.] [15.] SourcesNEEP, Mid-Atlantic Technical Reference Manual, V6, May 2016.1397.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1536.] Nexus Market Research, “Impact Evaluation of the Massachusetts, Rhode Island and Vermont 2003 Residential Lighting Programs”, Final Report, October 1, 2004, p. 43 (Table 4-9) The delta watts are reduced by 22.2% in the same proportion to individual CFLs (48.5W to 32.9W) following full enactment of EISA requirements.
[1537.] US Department of Energy, Energy Star Calculator.
[1538.] Nexus Market Research, “Impact Evaluation of the Massachusetts, Rhode Island and Vermont 2003 Residential Lighting Programs”, Final Report, October 1, 2004. p. 42 (Table 4-7). These values reflect both actual installations and the % of units planned to be installed within a year from the logged sample. The logged % is used because the adjusted values (i.e. to account for differences between logging and telephone survey samples) were not available for both installs and planned installs. However, this seems appropriate because the % actual installed in the logged sample from this table is essentially identical to the % after adjusting for differences between the logged group and the telephone sample (p. 100, Table 9-3).
[1539.] RLW Analytics, “Development of Common Demand Impacts for Energy Efficiency Measures/Programs for the ISO Forward Capacity Market (FCM)”, prepared for the New England State Program Working Group (SPWG), March 25, 2007, p. IV.
[1540.] The average wattage (18.4W) of the standard CFL established in the 2009 “NJCEP Residential CFL Impact Evaluation and Protocol Review”, September 28, 2008, p.3-8 (Table 3-6) is adjusted by a post-EISA multiplier (1.79) of the 2014 Mid-Atlantic Technical Reference Manual V4.0 for calculating the new delta watts after the incandescent bulb wattage is reduced (from 100W to 72W in 2012, 75W to 53W in 2013 and 60W to 43W and 40W to 29W in 2014).
[1541.] RLW Analytics, New England Residential Lighting Markdown Impact Evaluation, January 20, 2009.
[1542.] For determining demand savings the baseline was adopted from 2009 KEMA evaluation and represents the replacement of a 65W BR30 downlight and high efficiency is the average of ENERGY STAR qualified downlights (11/10/2009) with lighting output exceeding 475 lumens. Due to the high incremental cost and limited market availability of products, the higher ISR reflects the assumption that every LED downlight purchased is directed towards immediate use.
[1543.] Mid-Atlantic TRM V5
[1544.]
[1545.] Home Energy Reporting System
[1546.] Protocols[1547.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1548.] The purpose of the program is to provide information and tools that residential customers can use to make decisions about what actions to take to improve energy efficiency in their homes. The information is mailed in reports separately from a utility’s regular bill to create a neighbor-to-neighbor comparison where homes of similar size are compared to each other, as well as targeting energy saving tips to individuals. The quantity and timing of mailed reports will vary by utility and fuel type.
[1549.]
[1550.] Home Energy Reporting System[1551.] Gas Savings (Therms) = GSavHERS
[1552.] Residential ENERGY STAR Lighting1398.1399.[1553.] Savings from the installation of screw-in ENERGY STAR CFLs, ENERGY
STAR LED lamps, ENERGY STAR fluorescent torchieres, ENERGY STAR specialty LED fixtures, ENERGY STAR fixtures are based on a straightforward algorithm that calculates the difference between existing and new wattage, and the average daily hours of usage for the lighting unit being replaced.
1400. The coincidence factor (CF) discounts the peak demand savings to reflect the kW reduction realized during the summer on-peak demand period. This is based on typical operating schedules for the geographical area covered by the program.
1401. HVAC interactive factors are applied to capture the additional savings or penalty associated with the impact of lighting measures on the building’s HVAC system. A reduction in lighting load will result in additional cooling savings during the summer period, and a gas heating penalty during the winter period.
1402. [1554.] Algorithms1403.
1404.[1555.] ❑❑
()❑()❑❑❑
()❑❑
1405.
1406. ( )❑()❑❑❑
()❑❑
1407.
1408. (❑❑ ) ()❑()❑❑❑
()❑❑
1409.1410.[1556.] Definition of Variables1411. Wattsb = Wattage of baseline connected fixture or lamp1412. Wattsq = Wattage of qualifying connected fixture or lamp1413. Qtyb= Quantity of baseline fixtures or lamps
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1414. Qtyq = Quantity of energy-efficient fixtures or lamps1415. Hrs = Annual lighting operating hours1416. CF = Coincidence factor1417. HVACe = HVAC interaction factor for annual energy savings1418. HVACd = HVAC interaction factor for peak demand reduction1419. HVACg = HVAC interaction factor for annual gas fuel consumption
1420. Summary of Inputs
1421. Residential ENERGY STAR Lighting1422. Compon
ent1423.[1557.]
Type1424.[1558.] Value [1559.] S
ourcesSource
1426.[1561.] Wattsb
1427. V ariab
le1428. See Tables below 1429. 1
1431. Wattsq
1432. V ariab
le
1433. Actual Lamp/Fixture Wattage
1434. A pplication
1436. Qtyb 1437. V ariab
le
1438. Actual Lamp/Fixture Quantity
1439. A pplication
1441. Qtyq 1442. V ariab
le
1443. Actual Lamp/Fixture Quantity
1444. A pplication
1446. Hrs1447. V
ariable
1448. Interior: 1,205 hrs22 1449. Exterior: 2,007 hrs23
1450. 2
1452. C FGsavHERS
[1562.] Fixed [1563.] 0.0813.1 therms [1564.] 3
24 11454.[1566.] H 1455. V 1456. See Tables below 1457. 4
22 From EVT TRM 2015: “The hours of use for this measure are based on the assumption that these will be installed in the highest use locations due to their high cost. Residential hours of use are based on average daily hours of use of 3.3, from Table 3-5, p. 43, value for Living Space for Upstate New York, from NMR Group, Inc., Northeast Residential Lighting Hours-of-Use Study, prepared for CT Energy Efficiency Board, Cape Light Compact, Massachusetts Energy Efficiency Advisory Council, National Grid MA, National Grid RI, NYSERDA, Northeast Utilities, May 5, 2014.” 23 From EVT TRM 2015 : “Based on average daily hours of use of 5.5 for exterior lighting, from Table 3-1, p. 34 for Upstate New York from NMR Group, Inc., Northeast Residential Lighting Hours-of-Use Study, prepared for CT Energy Efficiency Board, Cape Light Compact, Massachusetts Energy Efficiency Advisory Council, National Grid MA, National Grid RI, NYSERDA, Northeast Utilities, May 5, 2014.”
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1422. Component
1423.[1557.] Type
1424.[1558.] Value [1559.] SourcesSource
VACeariab
le25
1458. HVACd
1459. V ariab
le1460. See Tables below 1461. 4
2
1462. HVACg
1463. V ariab
le1464. See Tables below 1465. 4
2
1466.1467.[1567.] HVAC Interactive Factors
1468.
HVACe HVACd HVACg HVACe HVACd HVACg HVACe HVACd HVACg HVACe HVACd HVACg HVACe HVACd HVACgSingle Family Residential
0.077 0.085 -0.023 -0.105 0.111 0.000 -0.579 0.085 0.000 -0.403 0.000 0.000 0.000 0.000 -0.023
Multi-Family Low Rise
0.055 0.136 -0.016 -0.064 0.163 0.000 -0.260 0.136 0.000 -0.320 0.000 0.000 -0.005 0.000 -0.016
Building Type AC with gas heat Heat Pump AC with electric heat Electric heat only Gas heat only
1469.
HVACe HVACd HVACg HVACe HVACd HVACgMulti-Family High Rise
0.101 0.194 0.021 0.000 0.000 0.024
Building Type Fan coil with chiller and hot water boiler
Steam heat only
1470. Standard CFL Lamp Wattage Equivalency1471. Min
imum Lumens
1472. Maximum
Lumens 1473. Wattsb
1474. Sources: [1568.] The
average natural
gas4000
1475. 6000 1476. 300
1477. 3001
1478. 3999 1479. 200
1480. 2550
1481. 3000 1482. 150
24 From NY TRM 2016, for NYC due to proximity to NJ. From the NY TRM: “The coincidence factors were derived from an examination of studies throughout New England that calculated coincident factors based on the definition of system peak period at the time, as specified by the New England Power Pool and later, ISO-New England.”25 From NY TRM 2016, for NYC due to proximity to NJ; for single family residential and multi-family low rise
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1483. 2000
1484. 2549 1485. 125
1486. 1600
1487. 1999 1488. 72
1489. 1100
1490. 1599 1491. 53
1492. 800 1493. 1099 1494. 431495. 450 1496. 799 1497. 291498. 250 1499. 449 1500. 25
1501. CFL Lamp Wattage Equivalency
1502. Bulb Type
1503. Lower
Lumen Range
1504. U pper Lume
n Rang
e1505. W
attsb
1506. 3-Way
1507. 250 1508. 449
1509. 2 5
1511.[1570.] 450
1512. 799
1513. 4 0
1515.[1572.] 800
1516. 1099
1517. 6 0
1519.[1574.] 1100
1520. 1599
1521. 7 5
1523.[1576.] 1600
1524. 1999
1525. 1 00
1527.[1578.] 2000
1528. 2549
1529. 1 25
1531.[1580.] 2550
1532. 2999
1533. 1 50
1534. Globe1535. (medium and intermediate bases less
than 750 lumens)
1536. 90 1537. 179
1538. 1 0
1540.[1582.] 180
1541. 249
1542. 1 5
1544.[1584.] 250
1545. 349
1546. 2 5
1548.[1586.] 350
1549. 749
1550. 4 0
1551. Decorative1552. (Shapes B, BA, C,
CA, DC, F, G, medium and intermediate bases
1553. 70 1554. 89 1555. 1 0
1557.[1588.] 90
1558. 149
1559. 1 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1502. Bulb Type
1503. Lower
Lumen Range
1504. U pper Lume
n Rang
e1505. W
attsb
less than 750 lumens)
1561.[1590.] 150
1562. 299
1563. 2 5
1565.[1592.] 300
1566. 749
1567. 4 0
1568. Globe1569. (candelabra bases less
than 1050 lumens)
1570. 90 1571. 179
1572. 1 0
1574.[1594.] 180
1575. 249
1576. 1 5
1578.[1596.] 250
1579. 349
1580. 2 5
1582.[1598.] 350
1583. 499
1584. 4 0
1586.[1600.] 500
1587. 1049
1588. 6 0
1589. Decorative1590. (Shapes B, BA, C,
CA, DC, F, G, candelabra bases less than 1050
lumens)
1591. 70 1592. 89 1593. 1 0
1595.[1602.] 90
1596. 149
1597. 1 5
1599.[1604.] 150
1600. 299
1601. 2 5
1603.[1606.] 300
1604. 499
1605. 4 0
1607.[1608.] 500
1608. 1049
1609. 6 0
1610. Reflector with medium screw bases w/ diameter
<=2.25"
1611. 400 1612. 449
1613. 4 0
1615.[1610.] 450
1616. 499
1617. 4 5
1619.[1612.] 500
1620. 649
1621. 5 0
1623.[1614.] 650
1624. 1199
1625. 6 5
1626. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
screw bases w/ diameter >2.5" (*see exceptions
1627. 640 1628. 739
1629. 4 0
1631.[1616.] 740
1632. 849
1633. 4 5
1635.[1618.] 1636. 11 1637. 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1502. Bulb Type
1503. Lower
Lumen Range
1504. U pper Lume
n Rang
e1505. W
attsb
below)
850 79 01639.[1620.]
11801640. 14
191641. 6
51643.[1622.]
14201644. 17
891645. 7
51647.[1624.]
17901648. 20
491649. 9
01651.[1626.]
20501652. 25
791653. 1
001655.[1628.]
25801656. 34
291657. 1
201659.[1630.]
34301660. 42
701661. 1
50
1662. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
screw bases w/ diameter > 2.26'' and ≤ 2.5" (*see
exceptions below)
1663. 540 1664. 629
1665. 4 0
1667. 630 1668. 719
1669. 4 5
1671.[1632.] 720
1672. 999
1673. 5 0
1675.[1634.] 1000
1676. 1199
1677. 6 5
1679.[1636.] 1200
1680. 1519
1681. 7 5
1683.[1638.] 1520
1684. 1729
1685. 9 0
1687.[1640.] 1730
1688. 2189
1689. 1 00
1691.[1642.] 2190
1692. 2899
1693. 1 20
1695.[1644.] 2900
1696. 3850
1697. 1 50
1698. *ER30, BR30, BR40, or ER40
1699. 400 1700. 449
1701. 4 0
1703.[1646.] 450
1704. 499
1705. 4 5
1707. 500 1708. >6 1709. 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1502. Bulb Type
1503. Lower
Lumen Range
1504. U pper Lume
n Rang
e1505. W
attsb
49 01710. *BR30, BR40, or
ER401711. 650 1712. 14
191713. 6
5
1714. *R20
1715. 400 1716. 449
1717. 4 0
1719.[1649.] 450
1720. 719
1721. 4 5
1722. *All reflector lamps1723. below lumen ranges
specified above
1724. 200 1725. 299
1726. 2 0
1728. 300 1729. >399
1730. 3 0
1731. 1732. LED Downlight Fixture Wattage Equivalency
1733. Bulb Type
1734. Lower
Lumen Range
1735. U pper Lume
n Rang
e1736. W
attsb
1737. Reflector with medium screw bases w/ diameter
<=2.25"
1738. 400 1739. 449
1740. 4 0
1742. 450 1743. 499
1744. 4 5
1746. 500 1747. 649
1748. 5 0
1750. 650 1751. 1199
1752. 6 5
1753. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
screw bases w/ diameter >2.5" (*see exceptions
below)
1754. 640 1755. 739
1756. 4 0
1758. 740 1759. 849
1760. 4 5
1762. 850 1763. 1179
1764. 5 0
1766. 1180
1767. 1419
1768. 6 5
1770. 1420
1771. 1789
1772. 7 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1733. Bulb Type
1734. Lower
Lumen Range
1735. U pper Lume
n Rang
e1736. W
attsb
1774. 1790
1775. 2049
1776. 9 0
1778. 2050
1779. 2579
1780. 1 00
1782. 2580
1783. 3429
1784. 1 20
1786. 3430
1787. 4270
1788. 1 50
1789. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
screw bases w/ diameter > 2.26'' and ≤ 2.5" (*see
exceptions below)
1790. 540 1791. 629
1792. 4 0
1794. 630 1795. 719
1796. 4 5
1798. 720 1799. 999
1800. 5 0
1802. 1000
1803. 1199
1804. 6 5
1806. 1200
1807. 1519
1808. 7 5
1810. 1520
1811. 1729
1812. 9 0
1814. 1730
1815. 2189
1816. 1 00
1818. 2190
1819. 2899
1820. 1 20
1822. 2900
1823. 3850
1824. 1 50
1825. *ER30, BR30, BR40, or ER40
1826. 400 1827. 449
1828. 4 0
1830.[1652.] 450
1831. 499
1832. 4 5
1834. 500 1835. >649
1836. 5 0
1837. *BR30, BR40, or ER40
1838. 650 1839. 1419
1840. 6 5
1841. *R201842. 400 1843. 44
91844. 4
01846.[1655.] 4 1847. 71 1848. 4
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1733. Bulb Type
1734. Lower
Lumen Range
1735. U pper Lume
n Rang
e1736. W
attsb
50 9 5
1849. *All reflector lamps1850. below lumen ranges
specified above
1851. 200 1852. 299
1853. 2 0
1855. 300 1856. >399
1857. 3 0
1858. LED Lamp Wattage Equivalency 1859. Bulb Type 1860. Lo
wer Lumen Range
1861. U pper Lume
n Rang
e
1862. W attsb
1863. Standard
1864. 2501865. 44
91866. 2
51868.[1658.]
4501869. 79
91870. 2
91872.[1660.]
8001873. 10
991874. 4
31876.[1662.]
11001877. 15
991878. 5
31880.[1664.]
16001881. 19
991882. 7
21884.[1666.]
20001885. 25
491886. 1
251888.[1668.]
25501889. 30
001890. 1
501892.[1670.]
30011893. 39
991894. 2
001896.[1672.]
40001897. 60
001898. 3
00
1899. 3-Way
1900. 250 1901. 449
1902. 2 5
1904.[1674.] 450
1905. 799
1906. 4 0
1908.[1676.] 800
1909. 1099
1910. 6 0
1912.[1678.] 1913. 15 1914. 7
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1859. Bulb Type 1860. Lower
Lumen Range
1861. U pper Lume
n Rang
e
1862. W attsb
1100 99 51916.[1680.]
16001917. 19
991918. 1
001920.[1682.]
20001921. 25
491922. 1
251924.[1684.]
25501925. 29
991926. 1
50
1927. Globe1928. (medium and intermediate bases less
than 750 lumens)
1929. 90 1930. 179
1931. 1 0
1933.[1686.] 180
1934. 249
1935. 1 5
1937.[1688.] 250
1938. 349
1939. 2 5
1941.[1690.] 350
1942. 749
1943. 4 0
1944. Decorative1945. (Shapes B, BA, C,
CA, DC, F, G, medium and intermediate bases less than 750 lumens)
1946. 70 1947. 89 1948. 1 0
1950.[1692.] 90
1951. 149
1952. 1 5
1954.[1694.] 150
1955. 299
1956. 2 5
1958.[1696.] 300
1959. 749
1960. 4 0
1961. Globe1962. (candelabra bases less
than 1050 lumens)
1963. 90 1964. 179
1965. 1 0
1967. 180 1968. 249
1969. 1 5
1971. 250 1972. 349
1973. 2 5
1975. 350 1976. 499
1977. 4 0
1979. 500 1980. 1049
1981. 6 0
1982. Decorative1983. (Shapes B, BA, C,
CA, DC, F, G, candelabra
1984. 70 1985. 89 1986. 1 0
1988. 90 1989. 14 1990. 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1859. Bulb Type 1860. Lower
Lumen Range
1861. U pper Lume
n Rang
e
1862. W attsb
bases less than 1050 lumens)
9 51992. 150 1993. 29
91994. 2
51996. 300 1997. 49
91998. 4
02000. 500 2001. 10
492002. 6
0
2003. Reflector with medium screw bases w/ diameter
<=2.25"
2004. 400 2005. 449
2006. 4 0
2008.[1698.] 450
2009. 499
2010. 4 5
2012.[1700.] 500
2013. 649
2014. 5 0
2016.[1702.] 650
2017. 1199
2018. 6 5
2019. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
screw bases w/ diameter >2.5" (*see exceptions
below)
2020. 640 2021. 739
2022. 4 0
2024.[1704.] 740
2025. 849
2026. 4 5
2028.[1706.] 850
2029. 1179
2030. 5 0
2032.[1708.] 1180
2033. 1419
2034. 6 5
2036.[1710.] 1420
2037. 1789
2038. 7 5
2040.[1712.] 1790
2041. 2049
2042. 9 0
2044.[1714.] 2050
2045. 2579
2046. 1 00
2048.[1716.] 2580
2049. 3429
2050. 1 20
2052.[1718.] 3430
2053. 4270
2054. 1 50
2055. R, PAR, ER, BR, BPAR or similar bulb shapes with medium
2056. 540 2057. 629
2058. 4 0
2060. 630 2061. 71 2062. 4
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1859. Bulb Type 1860. Lower
Lumen Range
1861. U pper Lume
n Rang
e
1862. W attsb
screw bases w/ diameter > 2.26'' and ≤ 2.5" (*see
exceptions below)
9 52064.[1720.]
7202065. 99
92066. 5
02068.[1722.]
10002069. 11
992070. 6
52072.[1724.]
12002073. 15
192074. 7
52076.[1726.]
15202077. 17
292078. 9
02080.[1728.]
17302081. 21
892082. 1
002084.[1730.]
21902085. 28
992086. 1
202088.[1732.]
29002089. 38
502090. 1
50
2091. *ER30, BR30, BR40, or ER40
2092. 400 2093. 449
2094. 4 0
2096.[1734.] 450
2097. 499
2098. 4 5
2100. 500 2101. >649
2102. 5 0
2103. *BR30, BR40, or ER40
2104. 650 2105. 1419
2106. 6 5
2107. *R20
2108. 400 2109. 449
2110. 4 0
2112.[1737.] 450
2113. 719
2114. 4 5
2115. *All reflector lamps2116. below lumen ranges
specified above
2117. 200 2118. 299
2119. 2 0
2121. 300 2122. >399
2123. 3 0
2124. 2125. Specialty LED Fixtures
2126. Some LED products do not allow for a fixture-to-fixture comparison due to unique form factors, such as LED rope lights, sign lighting, and cove lighting.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2127. In these instances, a similar savings and demand algorithm may be used, however with a different metric other than fixture quantity entered. For example, a comparison of watts per linear foot between LED and incandescent technologies would result in accurate energy savings calculations.
2128.2129.[1739.] Algorithms2130.2131.[1740.] ❑❑()()❑❑
2132. 2133. ❑❑() (❑❑ )
2134.2135.[1741.] where:2136. 2137. 2138. () –
2139. ()()
2140. The remaining variables are unchanged from those presented above.
2141. 2142. similar program offered to Puget Sound Energy customers. ( Sources
1. NEEP, Mid-Atlantic Technical Reference Manual, V6. May 2016., p. 21, pp. 30–31, 38–39, 46–47, 51–52, and 59–60. From the NEEP Mid-Atlantic TRM: “Base wattage is based upon the post first phase of EISA wattage and wattage bins consistent with ENERGY STAR, v1.1.”
2. Efficiency Vermont, Technical Reference User Manual, 2016, p. 265. The hours of use for this measure are based on the assumption: Evidence from Two Large Field Experiments that these will be installed in the highest use locations due to their high cost.Peer Comparison Feedback Can Reduce Residential hours of use are based on average daily hours of use of 3.3, from Table 3-5, page 43, value for Living Space for Upstate New York, from NMR Group, Inc., Northeast Residential Lighting Hours-of-Use Study, prepared for CT Energy Efficiency Board, Cape Light Compact, Massachusetts Energy Efficiency Advisory Council, National Grid MA, National Grid RI, NYSERDA, Northeast Utilities, May 5, 2014. Usage, Ayres, 2009)
3.[1.] NY, Standard Approach for Estimating Energy Savings, V4, April 2016, p.133. From the NY TRM: “From NY TRM 2016, for NYC due to proximity to NJ. From the NY TRM: “The coincidence factors were derived from an examination of studies throughout New England that calculated coincident factors based on the definition of system peak period at the time, as specified by the New England Power Pool and later, ISO-New England.”
4. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Appendix D – HVAC Interactive Effects Multipliers, p. 344 and 345. 2143. Coincidence factor: p. 133 2144.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2145. Appliance Recycling Program
2146. Protocols2147. The following sections detail savings calculations ENERGY STAR
Refrigerator/Freezer retirement program.
[1742.] Refrigerator/Freezer Retirement Program
[1743.] Protocols
[1744.] The general form of the equation for the Refrigerator/Freezer Retirement Program savings algorithm is:
[1745.] Number of Units *X Savings per Unit
[1746.] To determine resource savings, the per unit estimates in the protocols will be multiplied by the number of appliance units.
2148.[1747.] [1748.] Unit savings are the product of average fridge/freezer consumption (gross annual savings), and a net to gross ratio that adjusts for both free ridership and the portion of retired units that are replaced with more efficient new units.[1749.] [1750.]
2149.[1751.] Algorithm [1752.] Energy SavingsElectricity Impact (kWh/yr) = ESavRetFridge, ESavRAC, ESavDEH
[1753.] Peak Demand SavingsImpact (kW) = DSavRetFridge *x CFRetFridge
2150.[1754.] 2151.[1755.] Definition of Terms 2152.[1756.] ESavRetFridge = Gross annual energy savings per unit retired refrigerator2153.[1757.] ESavRetFreezer = Gross annual energy savings per unit retired freezer2154.[1758.] DSavRetFridge = Summer demand savings per retired refrigerator2155.[1759.] DSavRetFreezer = Summer demand savings per retired freezer2156.[1760.] CFRetFridge = Summer demand coincidence factor.
2157.[1761.] 2158.[1762.] Summary of Inputs
2159. Refrigerator/Freezer Recycling[1763.]
2160.[1764.] Component
2161.[1765.] Type
2162.[1766.] Value [1767.] SourcesSource
2163.[1768.] ESavRetFridge
2164.[1769.] Fixed
2165.[1770.] 761 kWh
2166.[1771.] 1
2167.[1772.] ESavRetFreezer
2168.[1773.] Fixed
2169.[1774.] 639 kWh
2170.[1775.] 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2160.[1764.] Component
2161.[1765.] Type
2162.[1766.] Value [1767.] SourcesSource
2171.[1776.] ESavRAC
2172.[1777.] Fixed
2173.[1778.] 166 kWh
[1779.] 1 4
2174.[1780.] ESavDEH
2175.[1781.] Fixed
2176.[1782.] 169 kWh
[1783.] 3 5
2177.[1784.] DSavRetFridge
2178.[1785.] Fixed
2179.[1786.] 0.114 kW
[1787.] 2 3
2180.[1788.] DSavRetFreezer
2181.[1789.] Fixed
2182.[1790.] 0.114 kW
[1791.] 2 3
2183.[1792.] DSavRAC
2184.[1793.] Fixed
2185.[1794.] 0.16 kW
[1795.] 1 4
2186.[1796.] DSavDEH
2187.[1797.] Fixed
2188.[1798.] 0.114 [1799.] 3 5
2189.[1800.] CFRetFridge
2190.[1801.] Fixed
2191.[1802.] 1 [1803.] 1 4
2192.[1804.] [1805.] Sources :
[1.] NEEP, Northeast Energy Efficiency Partnerships, “Mid-Atlantic Technical Reference Manual, V6. May 2016.”, Version 4.0, June, 2014, p. 96. Savings incorporate regression analysis results of EmPower Maryland evaluation of the 2013 Appliance Recycling Program.
[2.] Northeast Energy Efficiency Partnerships, “Mid-Atlantic Technical Reference Manual”, Version 4.0, June, 2014, p. 98.
[3.] Coincidence factor already embedded in summer peak demand reduction estimates[4.] Mid-Atlantic TRM V5[5.] Rhode Island TRM 2016 Program Year –-
https://www9.nationalgridus.com/non_html/eer/ri/PY2016%20RI%20TRM.pdf (p.pg 20).)
2193.[1806.] 2194.[1807.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2195.[1808.] Home Performance with ENERGY STAR Program2196.[1809.] In order to implement Home Performance with Energy Star, there are various
standards a program implementer must adhere to in order to deliver the program. The program implementer must use software that meets a national standard for savings calculations from whole-house approaches such as home performance. The difference in modeled annual energy consumption between the program and existing home is the project savings for heating, hot water, cooling, lighting and appliance end uses.
2197. The software the program implementer uses must adhere to at least one of the following standards:
A software tool whose performance has passed testing according to the National Renewable Energy Laboratory’s HERS BESTEST software energy simulation testing protocol.26
Software approved by the US Department of Energy’s Weatherization Assistance Program.27
RESNET approved rating software.28
2198.[1810.] There are numerous software packages that comply with these standards. Some examples of the software packages are REM/Rate, Real Home Analyzer, EnergyGauge, TREAT, and HomeCheck.
2199.[1811.]
26 Information about BESTEST-EX can be found at http://www.nrel.gov/buildings/bestest-_ex.htmlhttp://www.nrel.gov/buildings/bestest_ex.html.27 A listing of the approved software available at http://www.waptac.org/data/files/Website_Docs/technical_tools/EnergyAuditMatrixTable2.pdfhttp://www.waptac.org/data/files/Website_Docs/technical_tools/EnergyAuditMatrixTable2.pdf..28 A listing of the approved software available at http://resnet.us .
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Commercial and Industrial Energy Efficient Construction
[1812.] C&I Electric Protocols
[1813.] Baselines and Code Changes[1814.]
[1815.] In general, efficiency baselines are designed to reflect current market practices - typically, the higher of applicable codes or the minimum efficiency of available new equipment - and are updated periodically to reflect upgrades in code or information from evaluation results. There are exceptions to this approach, as in the Direct Install program (see below).
[1816.] Baseline data reflect ASHRAE 90.1-2007 for existing building retrofit and ASHRAE 90.1-2013 for new construction, replacement of failed equipment, end of useful life, and entire facility rehabilitation. unless otherwise noted for applications designated “2011”.
[1817.] Building Shell
[1818.]
[1819.] Building shell measures identified in an approved Local Government Energy Audit (or equivalent) are eligible for incentives through the Custom and Pay for Performance program. Savings for these measures will vary from project to project based on factors such as building size, existing levels of insulation and infiltration levels. As a result, energy savings for these installed building shell measures will be taken from what is provided in the approved Audit and/or energyAuditenergy analysis provided with the application submission.
[1820.] Performance Lighting
[1821.] C&I Electric Protocols2200.[1822.] The following measures are outlined in this section: Performance Lighting,
Prescriptive Lighting, Refrigerated Case LED Lights, Lighting Controls, ECMs for Refrigeration, Electric HVAC Systems, Fuel Use Economizers, Dual Enthalpy Economizers, Occupancy Controlled Thermostats, Electric Chillers, VFDs, and Commercial Refrigeration.
2201. Performance Lighting
2202. For new construction and entire facility rehabilitation projects, savings are calculated by comparing the lighting power density of fixtures being installed to the baseline lighting power density, or “lighting power allowance,”power densities from the building code. For the state of New Jersey, the applicable building code is ASHRAE 90.1 2013.
[1823.] Lighting equipment includes fluorescent fixtures, ballasts, compact fluorescent fixtures, LED fixtures , and metal halide lamps. The measurement of energy savings is based on algorithms with measurement of key variables (i.e., Coincidence Factor and lamps, and high-intensity discharge fixtures such as metal halide and high pressure
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
sodium luminaires. Operating Hours) through end-use metering data accumulated from a large sample of participating facilities from 1995 through 1999.
2203.[1824.] 2204.[1825.] Algorithms 2205.[1826.]
2206.[1827.] ❑❑()()❑❑
2207. 2208. ()()❑❑
2209. 2210. (❑❑❑❑ )2211.
2212. Fuel Savings( MMBtuyr )= (Watts∗Qty )b – (Watts∗Qty )q
1,000 WattskW
∗( Hrs )∗(HVAC ¿¿ g)¿
2213. Demand Savings = kW X CF X (1+IF) [1828.] [1829.] Energy Savings = kW X EFLH X (1+IF) [1830.] [1831.] kW = (LPDbase – LPDinst) X SF[1832.] 2214.[1833.] Definition of Variables [1834.] kW = Change in connected load from baseline to efficient lighting. level. [1835.] LPDb LPDbase = Baseline lighting power density in Watt per square foot of space
floor area, based on ASHRAE 90.1 Table 9.6.1 (Space-by-Space Method) [1836.] LPDq LPDinst = Lighting power density of qualifiedinstalled fixtures, equal to the sum of
installed fixture wattage divided by floor area of the space where the fixtures are installed. Wattage of installed fixtures is based on table at http://www.sce.com/NR/rdonlyres/FC51087D-2848-42DF-A52A-BDBA1A09BF8D/0/SCE_B_StandardFixtureWatts010108.pdf.
2215.[1837.] [1838.] SF = Space= space floor area, in square feetSquare Foot
[1839.] CF = Coincidence factor2216. Hrs = Annual operating hours2217. HVACd = HVAC Interactive Factor for peak demand savings2218. HVACe = HVAC Interactive Factor for annual energy savings
2219. HVACg = HVACEFLH = Equivalent Full Load Hours[1840.]
[1841.] IF = Interactive Factor for annual energy savings2220.[1842.]
2221. Summary of Inputs 2222.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2223.[1843.] Lighting Verification Performance Lighting2224.[1844.] Compon
ent
2225.[1845.] Typ
e
2226.[1846.] Value 2227.[1847.] Source
2228.[1848.] kW
[1849.] Fixe
dVariable
[1850.] See NGrid Fixture WattageCalifornia SPC Table:
2229.[1851.] 2230.[1852.] https://
www1.nationalgridus.com/files/AddedPDF/POA/
RILightingRetrofit1.pdf2231.
2232.http://www.sce.com/NR/ rdonlyres/FC51087D-2848-42DF-A52A-BDBA1A09BF8D/0/SCE_B_StandardFixtureWatts010108.pdf
[1853.] [1854.] And Formula Above.
2233.[1855.] 12234.[1856.]
2235. Baseline LPD from
ASHRAE 90.1-2013 Table
9.6.12236.[1857.]
Fixture counts and typesInstalled LPD, space type, and floor area from customer application.[1858.]
[1859.] 2237.[1860.]
SF2238.Vari
able
2239. From Customer Application
2240. Application
2241. CF
2242.[1861.] Fixe
d
[1862.] See Lighting Table by
Building Type
[1863.]
[1864.] 3 2
[1865.] H rsIF
2243.[1866.] Fixe
d
2244.[1867.] See Lighting Table by Building Type
[1868.] 35[1869.]
[1870.] H VACd
EFLH
2245.[1871.] Fixe
d
[1872.] See Lighting Table by Building Type
[1873.] 2 3, 5
[1874.]
2246.[1875.] HVACe
2247.Fixe
d
2248. See Lighting Table by Building Type
2249. 2
2250. H VACg
2251.Fixe
d
2252. - 0.000175 2253. 4
2254.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2255.[1876.] Yearly [1877.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1878.] [1879.] Lighting Hours of Operation by Building Type [5]
2256.[1880.] Building Type [1881.] Yearly Hours of OperationEFLH
[1882.] Education – Primary School
[1883.] 2257.[1884.] 2258.[1885.]
[1886.] EducationEducation – Secondary School 2259.[1887.] 2,456
[1888.] Education – Community College
[1889.] 2260.[1890.] 2261.[1891.]
[1892.] Education – University
[1893.] 2262.[1894.] 2263.[1895.]
[1896.] GroceryGrocery 2264.[1897.] 6,019[1898.] Medical – Hospital [1899.] 2265.[1900.] 2266.[1901.] [1902.] LodgingMedical –
Clinic [1903.] 4,808007[1904.] Lodging Hotel (Guest
Rooms)[1905.] 2267.[1906.] 2268.[1907.]
[1908.] Lodging Motel [1909.] 2269.[1910.] 2270.[1911.] [1912.] Manufacturin
gManufacturing – Light Industrial 2271.[1913.] 4,781
2272.[1914.] Health 2273. 4,0072274. MunicipalOffice-
Large [1915.] 3,116642[1916.] OfficeOffice-Small 2275.[1917.] 3,642[1918.] OtherRestaurant –
Sit-Down [1919.] 4,268089[1920.] Restaurant – Fast-
Food[1921.] 2276.[1922.] 2277.[1923.]
2278.[1924.] Public assembly 2279. 3,035Retail – 3-Story Large
2280.[1925.] Religious 2281. 2,6482282. RestaurantRetail –
Single-Story Large [1926.] 4,089103[1927.] RetailRetail – Small 2283.[1928.] 4,103[1929.] ServiceStorage
Conditioned [1930.] 3,5214,290[1931.] University/
collegeStorage Heated or Unconditioned [1932.] 4,2903,416
2284. WarehouseWarehouse 2285.[1933.] 4,009
[1934.] Average = Miscellaneous [1935.] 4,268 [1936.] 0.72 [1937.] 0.13
[1938.] 2286. Coincidence Factors by Building Type [3]
2287. Building Type 2288.C
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2289. Education2290.0
2291. Exterior2292.0
2293. Grocery2294.0
2295. Health2296.0
2297. Industrial/Manufacturing – 1
Shift
2298.0
2299. Industrial/Manufacturing – 2
Shift
2300.0
2301. Industrial/Manufacturing – 3
Shift
2302.0
2303. Institutional/Public Service
2304.0
2305. Lodging2306.0
2307. Miscellaneous/Other
2308.0
2309. Multi-Family Common Areas
2310.0
2311. Office2312.0
2313. Parking Garage2314.0
2315. Restaurant2316.0
2317. Retail 2318.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
0
2319. Street Lighting2320.0
2321. Warehouse2322.0
2323. 2324.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2325. HVAC Interactive Effects [2]
2326. Building Type
2327. Demand Waste
Heat Factor
(HVACd)
2328. Annual Energy Waste Heat Factor by Cooling/Heating
Type (HVACe)
2330.AC
(Utility)
2331.AC
(PJM)
2332.AC/
NonElec
2333.AC/
ElecRes
2334.He
at Pump
2335.No
AC/ ElecRes
2336. Office 2337.0.35
2338.0.3
2
2339.0.10
2340.-
0.15
2341.-
0.06
2342.-
0.25
2343. Retail 2344.0.27
2345.0.2
6
2346.0.06
2347.-
0.17
2348.-
0.05
2349.-
0.23
2350. Education 2351.0.44
2352.0.4
4
2353.0.10
2354.-
0.19
2355.-
0.04
2356.-
0.29
2357. Warehouse 2358.0.22
2359.0.2
4
2360.0.02
2361.-
0.25
2362.-
0.11
2363.-
0.27
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2364. Other29 2365.0.34
2366.0.3
2
2367.0.08
2368.-
0.18
2369.-
0.07
2370.-
0.26
2371.2372.
2373. Sources
1. Device Codes and Rated Lighting System Wattage Table Retrofit Program, National Grid, January 13, 2015. https://www1.nationalgridus.com/files/AddedPDF/POA/RILightingRetrofit1.pdf
2. Average HVAC interactive effects by building type derived from the NEEP Mid-Atlantic TRM 2016, NEEP, Mid-Atlantic Technical Reference Manual, V6. May 2016, pp. 506-507. From NEEP TRM: “EmPOWER Maryland DRAFT Final Impact Evaluation Report Evaluation Year 4 (June 1, 2012 – May 31, 2013) Commercial & Industrial Prescriptive & Small Business Programs, Navigant, March 31, 2014. Values for Washington, D.C. and Delaware assume values from Maryland, Pepco and Maryland, DPL, respectively.2374. Pennsylvania PUC, Technical Reference Manual, June 2016, pp. 229–230.
*Note: Figures in italics are derived from NEEP Report – July 2011 (source #5)[1939.] [1940.] Sources :[1.] California Standard Performance Contracting Program[2.] RLW Analytics, Coincident Factor Study, Residential and Commercial & Industrial
Lighting Measures, 2007.[3.] Quantum Consulting, Inc., for Pacific Gas & Electric Company , Evaluation of Pacific
Gas & Electric Company’s 1997 Commercial Energy Efficiency Incentives Program: Lighting Technologies”, March 1, 1999
[4.] KEMA. New Jersey’s Clean Energy Program Energy Impact Evaluation and Protocol Review. 2009.
[5.] Sources for these values include the following: a) The Mid-Atlantic TRM – Northeast Energy Efficiency Partnerships, Mid-Atlantic
Technical Reference Manual, Version 2.0, submitted by Vermont Energy Investment Corporation, July, 2011.
b) Development of Interior Lighting Hours of Use and Coincidence Factor Values for EmPOWER Maryland Commercial Lighting Program Evaluations, Itron, 2010.
c) California Public Utility Commission. Database for Energy Efficiency Resources, 2008d) Small Commercial Contract Group Direct Impact Evaluation Report prepared by Itron for
the California Public Utilities Commission Energy Division, February 9, 2010
29 Per the NEEP Mid-Atlantic TRM: “The ‘Other’ building type should be used when the building type is known but not explicitly listed above. A description of the actual building type should be recorded in the project documentation.”
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
e) State of Ohio Energy Efficiency Technical Reference Manual, Vermont Energy Investment Corporation, August 6, 2010.
f) UI and CL&P Program Savings Documentation for 2013 Program Year, United Illuminating Company, September 2012.
g) CL&P and UI 2008 program documentation (referenced above) cites an estimated 4,368 hours, only 68 hours greater than dusk to down operating hours. ESNA RP-20-98; Lighting for Parking Facilities acknowledges "Garages usually require supplemental daytime luminance in above-ground facilities, and full day and night lighting for underground facilities." Emphasis added. The adopted assumption of 6,552 increases the CL&P and UI value by 50% (suggest data logging to document greater hours i.e., 8760 hours per year).
h) Pennsylvania Statewide Act 129 2014 Commercial & Residential Lighting Metering Study. Prepared for Pennsylvania Public Utilities Commission. January 13, 2015. http://www.puc.pa.gov/pcdocs/1340978.pdf
3. Massachusetts TRM, 2016-2018 Program Years, October 2015. Original source: DNV KEMA (2013). Impact Evaluation of 2010 Prescriptive Lighting Installations. Prepared for Massachusetts Energy Efficiency Program Administrators and Massachusetts Energy Efficiency Advisory Council.
4. Northeast Energy Efficiency Partnerships & KEMA, for NEEP. C&I Lighting Load Shape Project FINAL Report - Prepared for the Regional Evaluation, Measurement and Verification Forum.. July 19, 2011.
[1941.] http://www.neep.org/sites/default/files/products/ NEEP_CI_Lighting_LS_FINAL_Report_ver_5_7-19-11.pdf[1942.]
[1943.] [1944.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1945.] Prescriptive Lighting
[1946.] This is a fixture replacement program for existing commercial customers targeted for facilities performing efficiency upgrades to their lighting systems.
[1947.]
[1948.] The baseline for linear and U-bend fluorescent measures is standard T8 fixtures with electronic ballasts or actual existing HID fixtures.
[1949.]
[1950.] The baseline for LED fixtures is the actual fixture being replaced.
[1951.]
[1952.] The baseline for induction lighting is an equivalent pulse start metal halide fixture (6).
[1953.]
[1954.] The baseline for LED refrigerator Case Lighting is that the fixture replaced was 2.63 times the wattage of the replacement LED (7).
[1955.]
[1956.] New fixtures and technologies available after publication will be periodically updated. Baselines will be established based on the guidelines noted below.
2375.[1957.] 2376.[1958.] [1959.] Algorithms 2377.[1960.] [1961.] Demand Savings = (kW) X (CF) X (1+ IF)[1962.] [1963.] Energy Savings = (kW) X (1 + IF) X (EFLH)[1964.]
[1965.] KW = (Number of fixtures installed X baseline wattage for new fixture) – (number of replaced fixtures X wattage from table)
[1966.] [1967.] *For refrigerated case LED fixtures, the following protocols will be applied to
account for the lighting and refrigeration energy savings associated with this measure.*[1968.] [1969.] Algorithms [1970.]
2378.[1971.] ❑❑❑❑
2379. 2380. ❑❑
2381. 2382. () –
2383. ()()2384.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2385. (❑❑ ) ()❑()❑❑❑
()❑❑
2386. Demand Savings = (kW) X (CF) X (1+ IF) X (1 + (0.28 X Eff))[1972.] [1973.] Energy Savings = (kW) X (1 + IF) X EFLH X (1 + (0.28 X Eff))[1974.] 2387.[1975.] Definition of Variables [1976.] kW = Change in connected load from baseline to efficient lighting level. [1977.] CF = Coincidence factorFactor2388.[1978.] Hrs = Annual hours of operation2389. HVACd = HVAC interactive factor for peak demand savings2390. HVACe = HVAC interactive factor for annual energy savings2391. HVACg = HVAC interactive factor for annual fuel savings
2392. Summary of InputsEFLH = Equivalent Full Load Hours[1979.] [1980.] IF = Interactive Factor
[1981.] [1982.] 0.28 = Conversion from kW to tons (Refrigeration)[1983.] [1984.] Eff = Efficiency of typical refrigeration system in kW/ton[1985.]
[1986.] Prescriptive Lighting for Commercial Customers2393.[1987.]
[1988.] Component
2394.[1989.] Type
2395.[1990.] Value 2396.[1991.] Source
2397.[1992.] kW
2398. FVariable
2399. See NGrid Fixture Wattage Table
2400. 2401. https://
www1.nationalgridus.com/files/AddedPDF/POA/
RILightingRetrofit1.pdf2402.
2403. 1
2404. C FkW
2405.[1993.] Fixed
[1994.] See Lighting Wattage Table by Building in Performance Lighting Section Abovederived from California SPC Table at:
[1995.] [1996.] (http://www.sce.com/NR/
rdonlyres/FC51087D-2848-42DF-A52A-BDBA1A09BF8D/0/
[1998.] 3 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[1988.] Component
2394.[1989.] Type
2395.[1990.] Value 2396.[1991.] Source
SCE_B_StandardFixtureWatts010108.pdf)
[1997.] [1999.] H
rsCF2406.[2000.]
Fixed2407.[2001.] See Lighting Table by
Building in Performance Lighting Section Above
[2002.] 3 [2003.] 2
5[2004.] H
VACd
EFLH
2408.[2005.] Fixed
2409.[2006.] See Lighting Table by Building Type in Performance
Lighting Section Above
2410.[2007.] [2008.] 3
, 4[2009.] H
VACe
IF
2411.[2010.] Fixed
2412.[2011.] See Lighting Table by Building Type in Performance
Lighting Section Above
[2012.] 2 3
[2013.] [2014.] H
VACg
Eff
2413.[2015.] Fixed
[2016.] 1.6See Table Below 2414. 4 5
2415.[2017.]
2416.[2018.] Interactive Factor (HVACg) for Annual Fuel Savings2417.Proj
ect Type
2418.Fuel
Type
2419. Impact (MMBtu/∆kWh)
2420.Larg
e Retrofit
2421.C&I
Gas Heat
2422. - 0.00023
2423.Larg
e Ret
2424.Oil
2425. - 0.00046
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
rofit
2426.Sma
ll Retrofit
2427.Gas
Heat
2428. - 0.001075
2429.Sma
ll Retrofit
2430.Oil
Heat
2431. - 0.000120
2432. Refrigerated Case LED Lights
2433. This measure includes the installation of LED lamps in commercial display refrigerators, coolers
2434. or freezers. The display lighting in a typical cooler or freezer add to the load on that unit by
2435. increasing power consumption of the unit when the lamp is on, and by adding heat to the inside
2436. of the unit that must be overcome through additional cooling.
2437. Replacing fluorescent lamps with low heat generating LEDs reduces the energy consumption associated with the lighting components and reduces the amount of waste heat generated from the lamps that must be overcome by the unit’s compressor cycles.
[1.] For induction Lighting, used the lowest PSMH that would produce a 30% reduction in wattage to the induction fixture, which is the minimum requirement for incentives replacing HID with induction lighting. Assume 5% increase for input wattage vs nominal wattage.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2.] Based on assuming LED is 62% more efficient than replacement as per RPI study: http://www.lrc.rpi.edu/programs/solidstate/pdf/SPIE4776-13_Raghavan.pdf
[2019.] 2438.[2020.] Algorithms2439.
2440.[2021.] ❑❑ (❑❑❑❑ )❑❑
2441. 2442. (❑❑❑❑ ) (❑❑)
2443. 2444. ❑❑ (❑❑❑❑ )❑❑
2445.2446.[2022.] Definition of Variables2447. Units = Number of LED linear lamps or fixtures installed2448. kWb = Baseline fixture wattage2449. kWq = Qualified LED fixture wattage2450. Lighting kWhbase = Total energy usage of lighting fixtures being replaced2451. Lighting kWhee= Total energy usage of new LED lighting fixtures are being
installed2452. Compfactor = Compressor factor for cooler or freezer, depending on location of
install2453. Compeff = Compressor efficiency for cooler or freezer; the efficiency
factors in portion of saved energy eliminated via the compressor2454. CF = Coincidence factor
2455. 2456. Summary of Inputs
2457. Refrigerated Case Assumptions2458. C
omponen
t
2459.Typ
e
2460.Valu
e
2461. Methodology 2462. Source
2463. L ighting kWhbase
2464.Vari
able
2465.Vari
able
2466. Total lighting operating hours per year × wattage of baseline lighting; use 2 × LED watts as
default
2467. Applicati
on
2468. L ighting kWhee
2469.Vari
able
2470.Vari
able
2471. Total lighting operating hours per year × wattage of LED
lighting.
2472. Applicati
on
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2458. C omponen
t
2459.Typ
e
2460.Valu
e
2461. Methodology 2462. Source
2473. H rs
2474.Fixe
d
2475.6,20
5
2476. 2477. 2
2478. O Compeff – cooler
2479.Fixe
d
2480.0.41
2481. V alue is calculated by multiplying 0.51 (compressor efficiency for cooler) by 0.80
(portion of saved energy eliminated via the compressor).See
also PA TRM, p.258. Values adopted from Hall, N. et al, New
York Standard Approach for Estimating Energy Savings from Energy Efficiency Measures in
Commercial and Industrial Programs, TecMarket Works,
September 1, 2009. http://www3.dps.ny.gov/W/PSCWeb.nsf/0/06f2fee55575bd8a852576
e4006f9af7/$FILE/TechManualNYRevised10-15-
10.pdf
2482. 1
2483. O Compeff
– freez
er
2484.Fixe
d
2485.0.52
2486. Value is calculated by multiplying 0.65 (compressor efficiency for cooler) × 0.80
(portion of saved energy eliminated via the compressor).
2487. 1
2488. C ompf
actor –cooler
2489.Fixe
d
2490.0.40
2491. Based on EER value of 1.8 kW/ton × 0.285 ton/kW × 0.8 (20% of case lighting load not
converted into case cooling load) = 0.40
2492. 1
2493. C ompf
actor –freez
er
2494.Fixe
d
2495.0.51
2496. Based on EER value of 2.3 kW/ton × 0.285 ton/kW × 0.8 (20% of case lighting load not
converted into case cooling load) = 0.51
2497. 1
2498. C F
2499.Fixe
d
2500.0.92
2501. 2502. 2
2503.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2504. Typical applications of LED case lighting are shown below (1): 2505.
2506. Measure description
2507. Baseline 2508. M easure
watts
2509.Baseli
ne watts
2510.Fixtur
e savings
2511. 5 foot LED case light
2512. 5 ft T8 lamp with
normal light output
2513. 3 8
2514.76
2515.38
2516. 6 foot LED case light
2517. 6 ft T12lamp with
high light output
2518. 4 6
2519.112
2520.66
2521. 2522. Sources 2523. 1. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, pages 223-222. Pennsylvania PUC, Technical Reference Manual, June 2016, page 258. From PA TRM:
“Methodology adapted from Kuiken et al, “State of Wisconsin Public Service Commission of Wisconsin Focus on Energy Evaluation Business Programs: Deemed Savings Parameter Development”, KEMA, November 13, 2009, assuming summer coincident peak period is defined as June through August on weekdays between 3:00 p.m. and 6:00 p.m., unless otherwise noted. https://focusonenergy.com/sites/default/files/bpdeemedsavingsmanuav10_evaluationreport.pdf”
2524. Specialty LED Fixtures
2525. Some LED fixtures do not adhere to the Prescriptive Lighting algorithm due to unique form factors that do not lend to a fixture-to-fixture comparison, such as LED rope lights, cove lighting, and so on.
2526. In these instances, a similar algorithm may be used, with a different metric other than fixture quantity entered. For example, a comparison of watts per linear foot between LED and incandescent technologies would result in accurate energy savings calculations.
2527.2528.[2023.] Algorithms2529.
2530.[2024.] ❑❑❑❑
2531. 2532. ❑❑
2533.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2534. () –( linear feet of installed LED cove light i ng ) × ( wattageof new LED cove lighting per foot )2535. 2536. Definition of Variables
2537. The remaining variables are unchanged from those presented in the Prescriptive Lighting section:
2538. 2539. Summary of Inputs 2540.
2541. Specialty Lighting for Commercial Customers2542. C
omponent
2543. T ype
2544. Value 2545. Source
2546. kW
2547. V ariab
le
2548. See algorithm above 2549. Application
2550. C F
2551. F ixed
2552. See Lighting Table by Building in Performance Lighting Section Above
2553. 2
2554. H rs
2555. F ixed
2556. See Lighting Table by Building in Performance Lighting Section Above
2557. 2
2558. H VACd
2559. F ixed
2560. See Lighting Table by Building Type in
Performance Lighting Section Above
2561. 1
2562. H VACe
2563. F ixed
2564. See Lighting Table by Building Type in
Performance Lighting Section Above
2565. 1
2566.2567.[2025.] Sources
1. NEEP, Mid-Atlantic Technical Reference Manual, V6. May 2016, pp 504-507.2. Pennsylvania PUC, Technical Reference Manual, June 2016, page 258. From PA TRM:
“Methodology adapted from Kuiken et al, “State of Wisconsin Public Service Commission of Wisconsin Focus on Energy Evaluation Business Programs: Deemed Savings Parameter Development”, KEMA, November 13, 2009, assuming summer coincident peak period is defined as June through August on weekdays between 3:00 p.m. and 6:00 p.m., unless otherwise noted. https://focusonenergy.com/sites/default/files/bpdeemedsavingsmanuav10_evaluationreport.pdf”2568.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2569. Lighting Controls
[2026.] Lighting controls include occupancy sensors, daylight dimmer systems, and occupancy controlled hi-low controls for fluorescent, LED and HID fixtures. The measurement of energy savings is based on algorithms with key variables (i.e., coincidence factor, equivalent full load hours) provided through existing end-use metering of a sample of facilities or from other utility programs with experience with these measures (i.e., % of annual lighting energy saved by lighting control). For lighting controls, the baseline is a manual switch, based on the findings of the New Jersey Commercial Energy Efficient Construction Baseline Study.
2570.[2027.] 2571.[2028.] Algorithms 2572.[2029.] 2573.[2030.] ❑❑ = kW c × SVG× Hrs ׿❑❑
2574. 2575. = kW c × SVG× CF ׿❑❑
2576. Demand Savings = kWc X SVG X CF X (1+ IF)[2031.] [2032.] Energy Savings = kWc X SVG X EFLH X (1+IF)[2033.] 2577.[2034.] Definition of Variables [2035.] SVG = % of annual lighting energy saved by lighting control; refer to table by
control type2578.[2036.] kWc = kW lighting load connected to control[2037.] ❑❑ IF = Interactive Factor – This applies to C&I interior lighting only. This
represents the secondary demand in reduced HVAC consumption resulting from decreased indoor lighting wattage.
2579. ❑❑ = Interactive Factor – This applies to C&I interior lighting only. This represents the secondaryand energy savings in reduced HVAC consumption resulting from decreased indoor lighting wattage. This value will be fixed at 5%.
2580.[2038.] CF = Coincidence factor2581. Hrs = Annual hours of operation prior to installation of controls2582. 2583.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2584. Summary of Inputs 2585. CF = Coincidence Factor – This value represents the percentage of the total load
which is on during electric system’s peak window.[2039.] [2040.] EFLH = Equivalent full load hours.[2041.]
2586.[2042.] Lighting Controls2587.[2043.]
[2044.] Component
2588.[2045.] Type
2589.[2046.] Value 2590.[2047.] Source
2591.[2048.] kWc
2592.[2049.] Variable
2593.[2050.] Load connected to control
2594.[2051.] Application
2595.[2052.] SVG
2596.[2053.] Fixed
[2054.] Occupancy Sensor, Controlled Hi-Low
Fluorescent Control, LED and controlled HID = 2430%[2055.] Daylight Dimmer
System=2850%
[2056.] 2 See sources below
2597.[2057.] CF
2598.[2058.] Fixed
2599.[2059.] See Lighting Table by Building in Performance
Lighting Section Above
2600.[2060.] 2601.[2061.] 1
[2062.] H rsEFL
H
2602.[2063.] Fixed
2603.[2064.] See Lighting Table by Building in Performance
Lighting Section Above
2604.[2065.] [2066.] 1, 2, 3
[2067.] H VACd
IF
2605.[2068.] Fixed
2606.[2069.] See HVAC Interactive Effects Table
Lighting Table by Building Type in Performance
Lighting Section Above
[2070.] 1 2
2607.[2071.] HVACe
2608. F ixed
2609. See HVAC Interactive Effects Table by Building
Type in Performance Lighting Table Above
2610. 1
2611.2612.[2072.] [2073.] Sources :
1. NEEP, Mid-Atlantic Technical Reference Manual, V6. May 2016, pp 505-507. Sources per NEEP TRM: “2. EmPOWER Maryland DRAFT Final Impact Evaluation Report Evaluation Year 4 (June
1, 2012 – May 31, 2013) RLW Analytics, Coincident Factor Study, Residential and Commercial & Industrial Prescriptive & Small Business Programs, Navigant,Lighting Measures, 2007.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[a.] Quantum Consulting, Inc., for Pacific Gas & Electric Company , Evaluation of Pacific Gas & Electric Company’s 1997 Commercial Energy Efficiency Incentives Program: Lighting Technologies”, March 31, 20141, 1999
[b.] KEMA for NEEP. C&I Lighting Load Shape Project FINAL Report, KEMA. July 19, 2011
[2074.] http://www.neep.org/sites/default/files/products/ NEEP_CI_Lighting_LS_FINAL_Report_ver_5_7-19-11.pdf
[2075.] [2076.] [2077.] For premium efficiency motors 1-200 HP. [2078.] [2079.] Algorithms [2080.] [2081.] From application form calculate kW where:
[2082.] [2083.] kW = 0.746 * HP * IFVFD * (1/ηbase – 1/ηprem)[2084.]
[2085.] Demand Savings = (kW) X CF[2086.]
[2087.] Energy Savings = (kW)*HRS * LF[2088.] [2089.] Definition of Variables [2090.]
[2091.] kW = kW Savings at full load[2092.] [2093.] HP = Rated horsepower of qualifying motor, from nameplate/manufacturer specs.[2094.] [2095.] LF = Load Factor, percent of full load at typical operating condition[2096.] [2097.] IFVFD = VFD Interaction Factor, 1.0 without VFD, 0.9 with VFD[2098.] [2099.] ηbase = Efficiency of the baseline motor[2100.] [2101.] ηprem = Efficiency of the energy-efficient motor
[2102.] [c.] HRSEmPOWER Maryland DRAFT Final Impact Evaluation Report Evaluation
Year 4 (June 1, 2012 – May 31, 2013) Commercial & Industrial Prescriptive & Small Business Programs, Navigant, March 31, 2014. Values for Washington, D.C. and Delaware assume values from Maryland, Pepco and Maryland, DPL, respectively.”
3. A Meta-Analysis of Energy Savings from Lighting Controls in Commercial Buildings, Lawrence Berkeley National Laboratory, September 2011.
2613. = Annual operating hours[2103.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2104.] CF = Coincidence Factor[2105.] Motors
[2106.] Component
[2107.] Type [2108.] Value [2109.] Source
[2110.] HP [2111.] Variable [2112.] Nameplate/Manufacturer Spec. Sheet
[2113.] Application
[2114.] LF [2115.] Fixed [2116.] 0.75 [2117.] 1[2118.] hpbase [2119.] Fixed [2120.] ASHRAE
90.1-2013 Baseline Efficiency Table
[2121.] ASHRAE
[2122.] hpprem [2123.] Variable [2124.] Nameplate/Manufacturer Spec. Sheet
[2125.] Application
[2126.] IFVFD [2127.] Fixed [2128.] 1.0 or 0.9 [2129.] 3[2130.] Efficien
cy - ηee
[2131.] Variable [2132.] Nameplate/Manufacturer Spec. Sheet
[2133.] Application
[2134.] CF [2135.] Fixed [2136.] 0.74 [2137.] 1[2138.] HRS[2139.]
[2140.] Fixed [2141.] Annual Operating Hours Table
[2142.] 1
[2143.] [2144.] Baseline Motor Efficiency Table[2145.]
ODP TEFC ODP TEFC ODP TEFC1 0.8 0.8 0.825 0.825 na 0.755
1.5 0.84 0.855 0.84 0.84 0.825 0.8252 0.855 0.865 0.84 0.84 0.84 0.843 0.865 0.875 0.865 0.875 0.84 0.8555 0.875 0.875 0.875 0.875 0.855 0.875
7.5 0.885 0.895 0.885 0.895 0.875 0.88510 0.9002 0.895 0.895 0.895 0.885 0.89515 0.902 0.902 0.91 0.91 0.895 0.90220 0.91 0.902 0.91 0.91 0.902 0.90225 0.917 0.917 0.917 0.924 0.91 0.9130 0.924 0.917 0.924 0.924 0.91 0.9140 0.93 0.93 0.93 0.93 0.917 0.91750 0.93 0.93 0.93 0.93 0.924 0.92460 0.936 0.936 0.936 0.936 0.93 0.9375 0.936 0.936 0.941 0.941 0.93 0.93100 0.941 0.941 0.941 0.945 0.93 0.936125 0.941 0.941 0.945 0.945 0.936 0.945150 0.945 0.95 0.95 0.95 0.936 0.945200 0.945 0.95 0.95 0.95 0.945 0.95
Motor Horsepower
1200 RPM (6 pole) 1800 RPM (4 pole) 3600 RPM (2 pole)
[2146.] *Note: For the Direct Install Program, different baseline efficiency values are used. [2147.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2148.] NEMA ASHRAE 90.1-2013 Motor Efficiency Table – General Purpose Subtype I
[2149.]
ODP TEFC ODP TEFC ODP TEFC1 0.825 0.825 0.855 0.855 0.77 0.77
1.5 0.865 0.875 0.865 0.865 0.84 0.842 0.875 0.885 0.865 0.865 0.855 0.8553 0.885 0.895 0.895 0.895 0.855 0.8655 0.895 0.895 0.895 0.895 0.865 0.885
7.5 0.902 0.91 0.91 0.917 0.885 0.89510 0.917 0.91 0.917 0.917 0.895 0.90215 0.917 0.917 0.93 0.924 0.902 0.9120 0.924 0.917 0.93 0.93 0.91 0.9125 0.93 0.93 0.936 0.936 0.917 0.91730 0.936 0.93 0.941 0.936 0.917 0.91740 0.941 0.941 0.941 0.941 0.924 0.92450 0.941 0.941 0.945 0.945 0.93 0.9360 0.945 0.945 0.95 0.95 0.936 0.93675 0.945 0.945 0.95 0.954 0.936 0.936100 0.95 0.95 0.954 0.954 0.936 0.941100 0.95 0.95 0.954 0.954 0.941 0.95150 0.954 0.958 0.958 0.958 0.941 0.95200 0.954 0.958 0.958 0.962 0.95 0.954
Motor Horsepower
1200 RPM (6 pole) 1800 RPM (4 pole) 3600 RPM (2 pole)
[2150.] [2151.] Annual Operating Hours Table
[2152.]
Motor Horsepower
Operating Hours, HRS
1 to 5 HP 2,7456 to 20 HP 3,39121 to 50 HP 4,067
51 to 100 HP 5,329101 to 200 HP 5,200
[2153.]
[2154.] Electronically Commutated Motors for Refrigeration
[2155.] [2156.] This measure is applicable to existing walk-in, multi-deck and free standing coolers
and freezers with shaded pole or permanent split capacitor (PSC) motors. These fractional horsepower motors are significantly more efficient than mechanically commutated, brushed motors, particularly at low speeds or partial load. By employing variable-speed technology, EC motors are able to optimize fan speeds for changing load requirements. Because these motors are brushless and utilize DC power, losses due to friction and phase shifting are eliminated. Calculations of savings for this measure take into account both the increased efficiency of the motor as well as the reduction in refrigeration load due to motor heat loss.
2614.[2157.] 2615.[2158.] EC Motor Retrofits in Walk-in Coolers and Freezers
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2616.[2159.] 2617.[2160.] Algorithms 2618.[2161.] 2619.[2162.] ∆kW = ((AmpsEF * VoltsEF * (PhaseEF) 1/2)/1000) * PFEF * LR65%2620.[2163.] 2621.[2164.] Gross kWh Savings = kWh SavingsEF + kWh SavingsRH
2622.[2165.] 2623.[2166.] kWh SavingsEF = ((AmpsEF * VoltsEF * (PhaseEF) 1/2)/1000) * PFEF * Operating Hours * LR65%2624.[2167.] 2625.[2168.] kWh SavingsRH = kWh SavingsEF * 0.28 * 1.62626.[2169.]
2627.[2170.] PLEASE NOTE: 2628.[2171.] “((AmpsEF * VoltsEF * (PhaseEF) 1/2)/1000) * PFEF” is equivalent to “HP *
0.746”2629.[2172.] 2630.[2173.] Definition of Variables 2631.[2174.] ∆kW = Demand Savings due to EC Motor Retrofit2632.[2175.] kWh SavingsEF = Savings due to Evaporator Fan Motors being replaced2633.[2176.] kWh SavingsRH = Savings due to reduced heat from Evaporator Fans2634.[2177.] AmpsEF = Nameplate Amps of Evaporator Fan2635.[2178.] VoltsEF = Nameplate Volts of Evaporator Fan2636.[2179.] PhaseEF = Phase of Evaporator Fan2637.[2180.] PFEF = Evaporator Fan Power Factor2638.[2181.] Operating Hours = Annual operating hours if Evaporator Fan Control2639.[2182.] LR = Percent reduction of load by replacing motors2640.[2183.] 0.28 = Conversion from kW to tons (Refrigeration)2641.[2184.] 1.6 = Efficiency of typical refrigeration system in kW/ton2642.[2185.] 2643.[2186.] Case Motor Replacement2644.[2187.] 2645.[2188.] Algorithms 2646.[2189.] 2647.[2190.] Gross kWh Savings = kWh SavingsCM + kWh SavingsRH
2648.[2191.] 2649.[2192.] kWh SavingsCM = kW * ER * RT8, 5002650.[2193.] 2651.[2194.] kWh SavingsRH = kWh SavingsEF * 0.28 * Eff2652.[2195.] 2653.[2196.] Definition of Variables 2654.[2197.] kWh SavingsCM = Savings due to Case Motors being replaced2655.[2198.] kWh SavingsRH = Savings due to reduced heat from Case Motors2656.[2199.] kW = Metered load of Case Motors
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2657.[2200.] ER = Energy reduction if a motor is being replaced2658.[2201.] RT = Average runtime of Case Motors2659.[2202.] 0.28 = Conversion from kW to tons (Refrigeration)2660.[2203.] Eff = Efficiency of typical refrigeration system in kW/ton2661.[2204.] 2662.[2205.] Summary of Inputs 2663.
2664.[2206.] ECM Fraction HP Motors[2207.]
2665.[2208.] Component
2666.[2209.] Type
2667.[2210.] Value 2668.[2211.] Source
2669.[2212.] AmpsEF
2670.[2213.] Variable
2671.[2214.] Nameplate/
Manufacturer Spec. Sheet
2672.[2215.] Application
2673.[2216.] VoltsEF
2674.[2217.] Variable
2675.[2218.] Nameplate/
Manufacturer Spec. Sheet
2676.[2219.] Application
2677.[2220.] PhaseEF
2678.[2221.] Variable
2679.[2222.] Nameplate/
Manufacturer Spec. Sheet
2680.[2223.] Application
2681.[2224.] PFEF
2682.[2225.] Fixed
2683.[2226.] 0.55 2684.[2227.] 1
2685.[2228.] Operating Hours
2686.[2229.] Fixed
2687.[2230.] Not Installed = 8,760
2688.[2231.] Installed = 5,600
2689.[2232.]
2690.[2233.] LR 2691.[2234.] Fixed
2692.[2235.] 65% 2693.[2236.] 2
2694.[2237.] ER 2695.[2238.] Fixed
2696.[2239.] Shaded Pole Motor
Replaced = 53%2697.[2240.] PSC
Motor Replaced = 29%
2698.[2241.] 3
2699.[2242.] RT 2700.[2243.] Fixed
2701.[2244.] 8500 2702.[2245.]
2703.[2246.] Eff 2704.[2247.] Fixed
2705.[2248.] 1.6 2706.[2249.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2707.[2250.] [2251.] [2252.] Sources:[2253.]
[1.] Select Energy Services, Inc., Cooler Control Measure Impact Spreadsheet User’s Manual, 2004.
1.[2.] This value is an estimate by NRM based on several pre- and post- meter readings of installations. This is supported by RLW report for National Grid, “Small Business Services, Custom Measure Impact Evaluation,” March 23, 2007.
2.[3.] Based on numerous pre- and post- meterings conducted by NRM.
2708.[2254.] Electric HVAC Systems
[2255.] This measure provides energy and demand savings algorithms for C&/I ElectricEfficient HVAC systems. The type of systems included in this measure are:program for Room AC, Central AC, and air cooled DX is based on algorithms. (Includes split systems, single package systems, air to air cooled heat pumps, packaged terminal systems (PTAC and PTHP),, single package vertical systems (SPVAC and SPVHP),, central DX AC systems, water source heat pumps, ground water source heat pumps, and/or ground source heat pumps.)
2709. This measure applies to new construction, replacement of failed equipment, or end of useful life. The baseline unit is a code compliant unit with an efficiency as required by ASHRAE Std. 90.1 – 2013, which is the current code adopted by the state of New Jersey.
2710.2711.[2256.] Algorithms 2712.[2257.] 2713.[2258.] Air Conditioning Algorithms:2714.[2259.] [2260.] EnergyDemand Savings (kWh/yr) = N * Tons * 12 kBtuh/Ton *= (BtuH/1000) X
(1/EERb-1/EERq) * EFLHcX CF 2715.[2261.] [2262.] Peak DemandEnergy Savings (kW) = N * Tons * 12 kBtuh/Ton *= (BtuH/1000) X
(1/EERb-1/EERq) * CFX EFLH 2716.[2263.] 2717.[2264.] Heat Pump Algorithms:2718.[2265.]
[2266.] Cooling Energy Savings (kWh/yr) = N * Tons * 12 kBtuh/Ton *-Cooling = (BtuHc/1000) X (1/EERb-1/EERq) *X EFLHc
2719.[2267.] [2268.] Heating Energy Savings (Btu/yr) = N * Tons * 12 kBtuh/Ton *-Heating = BtuHh/1000
X ((1/ (COPb *X 3.412))-(1/ (COPq *X 3.412)) *))) X EFLHh
2720.[2269.] 2721.[2270.] Where c is for cooling and h is for heating.
2722.[2271.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2723.[2272.] Definition of Variables 2724.[2273.] N = Number of units 2725. Tons BtuH = Rated cCooling capacity of unitin Btu/Hour. T – This value comes from ARI/AHRI or AHAM rating or manufacturer data.[2274.] EERb = Energy Efficiency Ratio of the baseline unit. This data is found in the HVAC and Heat Pumps table below. For units < 65,000 BtuH (5.4 tons),, SEER should be used in place of EER. [2275.] COPb = Coefficient of Performance of the baseline unit. This data is found in the HVAC and Heat Pumps table below. For units < 65,000 BtuH (5.4 tons),, SEER and HSPF/3.412 should be used in place of COP X 3.412 for cooling and heating savings, respectively. 2726.[2276.] EERq = Energy Efficiency Ratio of the high efficiency unit. This value comes from the ARI/AHRI or AHAM directories or manufacturer data. For units < 65,000 (5.4 tons) BtuH, SEER should be used in place of EER. [2277.] COPq = Coefficient of Performance of the high efficiency unit. This value comes from the ARI/AHRI or AHAM directories or manufacturer data. For units < 65,000 BtuH (5.4 tons),,, SEER and HSPF/3.412 should be used in place of COP X 3.412 .for cooling and heating savings, respectively. [2278.] CF = Coincidence Factor – This value represents the percentage of the total load which is on during electric system’s Peak Window. This value iswill be based on existing measured usage and determined as the average number of operating hours during the peak window period.[2279.] EFLHc or h EFLH = Equivalent Full Load Hours – This represents a measure of energy use by season during the on-peak and off- peak periods. This value will be determined by existing measured data of kWh during the period divided by kW at design conditions.2727.[2280.] 2728. Summary of Inputs 2729.
2730.[2281.] HVAC and Heat Pumps2731.[2282.] [2283.] C
omponen
t
2732.[2284.] Typ
e
2733.[2285.] Value 2734.[2286.] Source
[2287.] T onsBtuH
2735.[2288.] Vari
able
[2289.] ARI/AHRI or AHAM or Manufacturer DataRated Capacity,
Tons
2736.[2290.] Application
2737.[2291.] EERb
2738.[2292.] Vari
a
2739.[2293.] See Table below [2294.] 1 Collaborati
ve
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2283.] Componen
t
2732.[2284.] Typ
e
2733.[2285.] Value 2734.[2286.] Source
ble
agreement and C/I baseline
study2740.[2295.]
EERq
2741.[2296.] Vari
able
2742.[2297.] ARI/AHRI or AHAM Values
2743.[2298.] Application
2744.[2299.] CF
2745.[2300.] Fixe
d
[2301.] 5067% [2302.] 2 Engineering estimate
2746.[2303.] EFLH(
c or h)
2747.Vari
ableFixed
[2304.] See Table belowHVAC 1,495 [2305.] HP cooling 381
[2306.] HP heating 800
[2307.] 3 301, JCP&L metered data31
2748.[2308.]
30 From NY TRM 2016, for NYC due to proximity to NJ; for small commercial and large commercial buildings31 Results reflect metered use from 1995 – 1999.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2309.] HVAC Baseline Efficiencies Table – New Construction/EUL/RoFExisting Buildings
2749.[2310.] [2311.] Equipment Type [2312.] Baseline = ASHRAE Std.
90.1 – 2013- 20072750.[2313.] Unitary HVAC/Split Systems and
Single Package, Air Cooled[2314.] · <=5.4 tons, split:
2751.[2315.] <=5.4 tons, single2752. · >5.4 to 11.25 tons[2316.] · >11.25 to 20 tons[2317.] > .> 21 to 63 tons2753.[2318.] >63 Tons
2754.[2319.] 2755.
2756.[2320.] 13 SEER2757.[2321.] 14 SEER
2758. 11.0 EER, 12.7 IEER2759.[2322.] 10.8 EER, 12.2 IEER[2323.] 9.8 EER, 11.4 IEER9.5 IPLV[2324.] 9.5 EER, 11.0 IEER9.2 IPLV
[2325.] Air-Air Cooled Heat Pump Systems, Split
System and Single Package[2326.] · <=5.4 tons, split:
2760.[2327.] <=5.4 tons, single2761. · >5.4 to 11.25 tons[2328.] · >11.25 to 20 tons
[2329.] >=.>= 21
2762.[2330.] 2763.[2331.]
[2332.] 1413 SEER, 8.27.7 HSPF2764.[2333.] 14 SEER, 8.0 HSPF2765. 10.8 EER, 11.0 IEER, 3.3
heating COP[2334.] 10.4 EER, 11.4 IEER3.2 heating
COP[2335.] 9.3 EER, 9.0 IPLV, 3.2 heating
COP2766. 9.3 EER, 10.4 IEER, 3.2
heating COP2767.[2336.] Water Source
Heat Pumps (water to air, water loop)
[2337.] All Capacities[2338.] <=1.4 tons
2768.[2339.] >1.4 to 5.4 tons2769.[2340.] >5.4 to 11.25 tons
2770.[2341.] 2771.[2342.]
2772. 12.0 EER[2343.] 11.2 EER, 4.32 heating COP
[2344.] 1312.0 EER, 4.32 heating COP[2345.] 1312.0 EER, 4.32 heating COP
2773.[2346.] Ground Water Source Heat Pumps
[2347.] Open and Closed Loop All Capacities<=11.25 tons
2774.[2348.] 18.0[2349.] 16.2 EER, 3.76 heating COP
2775.[2350.] Ground Source Heat Pumps (brine to air,
ground loop)2776.[2351.] <=11.25 tons
2777.[2352.] 14.1[2353.] 13.4 EER, 3.21 heating COP
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2311.] Equipment Type [2312.] Baseline = ASHRAE Std. 90.1 – 2013- 2007
[2354.] Package Terminal Air Conditioners32 a
2778.[2355.]
2779.[2356.] 14.[2357.] 12.5 - (0 – (0.300.213 *
Cap/1,000), EER2780.[2358.]
[2359.] Package Terminal Heat Pumps a
2781.[2360.] [2361.]
[2362.]
2782.[2363.] 14.[2364.] 12.3 - (0 – (0.300.213 *
Cap/1,000), EER[2365.] 3.72 – (0.052026 * Cap/1,000),
heating COP2783.[2366.]
2784.[2367.] Single Package Vertical Air Conditioners[2368.] · <=5.4 tons
[2369.] · >5.4 to 11.25 tons[2370.] · >11.25 to 20 tons
2785.[2371.] [2372.] 109.0 EER
[2373.] 10.08.9 EER[2374.] 10.08.6 EER
2786.[2375.] Single Package Vertical Heat Pumps
[2376.] · <=5.4 tons[2377.] · >5.4 to 11.25 tons[2378.] · >11.25 to 20 tons
2787.[2379.] 2788.[2380.]
2789. 109.0 EER, 3.0 heating COP[2381.] 10.08.9 EER, 3.0 heating COP
[2382.] 10.08.6 EER, 3.02.9 heating COP
2790.[2383.] 2791.[2384.]
2792.[2385.] EFLH
32 Cap means the rated cooling capacity of the product in Btu/h.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2386.] HVAC Baseline Table – New Construction
[2387.] FacilityEquipment
Type
[2388.] Heating
EFLHBaseline
= ASHRAE Std. 90.1 -
2013
2793.[2389.] Cooling
EFLH
[2390.] Unitary HVAC/Split Systems and Single Package,
Air Cooled[2391.] ·
<=Assembly5.4 tons, split
[2392.] · <=5.4 tons, single
[2393.] · >5.4 to 11.25 tons
[2394.] · >11.25 to 20 tons
[2395.] .> 21 to 63 tons
[2396.] >63 Tons
2794.[2397.] 6 03[2398.]
[2399.] 13 SEER
[2400.] 14 SEER
[2401.] 11.0 EER, 12.7
IEER[2402.] 10.8
EER, 12.2 IEER
[2403.] 9.8 EER, 11.4
IEER[2404.] 9.5
EER, 11.0 IEER
2795.[2405.] 669
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2387.] FacilityEquipment
Type
[2388.] Heating
EFLHBaseline
= ASHRAE Std. 90.1 -
2013
2793.[2389.] Cooling
EFLH
[2406.] Air Cooled
Heat Pump Systems,
Split System and
Single Package
[2407.] · <=Auto repair5.4 tons, split
[2408.] · <=5.4 tons, single
[2409.] · >5.4 to 11.25 tons
[2410.] · >11.25 to 20 tons
[2411.] .>= 21
2796.[2412.] 1 910
[2413.] [2414.] 14
SEER, 8.2 HSPF
[2415.] 14 SEER, 8.0
HSPF[2416.] 10.8
EER, 11.0 IEER, 3.3
heating COP
[2417.] 10.4 EER, 11.4 IEER, 3.2
heating COP
[2418.] 9.3 EER, 10.4 IEER, 3.2
heating COP
2797.[2419.] 426
2798. DormitoryWater Source Heat Pumps (water to air, water loop)
[2420.] <=1.4 tons[2421.] >1.4 to
5.4 tons[2422.] >5.4 to
11.25 tons
2799.[2423.] 4 65
[2424.] [2425.] 12.2
EER, 4.3 heating COP
[2426.] 13.0 EER, 4.3 heating COP
[2427.] 13.0 EER, 4.3 heating COP
2800.[2428.] 800
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2387.] FacilityEquipment
Type
[2388.] Heating
EFLHBaseline
= ASHRAE Std. 90.1 -
2013
2793.[2389.] Cooling
EFLH
2801. HospitalGround Water Source Heat Pumps
[2429.] <=11.25 tons
2802.[2430.] 3 366
[2431.] 18.0 EER, 3.7 heating COP
2803.[2432.] 1424
2804. Light industrialGround Source Heat Pumps (brine to air, ground loop)
[2433.] <=11.25 tons
2805.[2434.] 7 14
[2435.] [2436.] 14.1
EER, 3.2 heating COP
2806.[2437.] 549
2807. Lodging – HotelPackage Terminal Air Conditioners a
[2438.]
2808.[2439.] 1 077
[2440.] 14.0 - (0.300 *
Cap/1,000), EER
[2441.]
2809.[2442.] 2918
2810. Lodging – MotelPackage Terminal Heat Pumps a [2443.]
2811.[2444.] 6 19
[2445.] 14.0 - (0.300 *
Cap/1,000), EER
[2446.] 3.7 – (0.052 *
Cap/1,000), heating COP
[2447.]
2812.[2448.] 1233
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2387.] FacilityEquipment
Type
[2388.] Heating
EFLHBaseline
= ASHRAE Std. 90.1 -
2013
2793.[2389.] Cooling
EFLH
2813. Office – largeSingle Package Vertical Air Conditioners
[2449.] · <=5.4 tons
[2450.] · >5.4 to 11.25 tons
[2451.] · >11.25 to 20 tons
2814.[2452.] 2 034
[2453.] 10.0 EER
[2454.] 10.0 EER
[2455.] 10.0 EER
2815.[2456.] 720
2816. Office – smallSingle Package Vertical Heat Pumps
[2457.] · <=5.4 tons
[2458.] · >5.4 to 11.25 tons
[2459.] · >11.25 to 20 tons
2817.[2460.] 4 31
[2461.] 10.0 EER, 3.0 heating COP
[2462.] 10.0 EER, 3.0 heating COP
[2463.] 10.0 EER, 3.0 heating COP
2818.[2464.] 955
2819. Other 2820. 681 2821. 736
2822. Religious worship 2823. 722 2824. 27
92825. Restaur
ant – fast food
2826. 813 2827. 645
2828. Restaurant – full service
2829. 821 2830. 574
2831. Retail – big box 2832. 191 2833. 12
792834. Retail –
Grocery 2835. 191 2836. 1279
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2387.] FacilityEquipment
Type
[2388.] Heating
EFLHBaseline
= ASHRAE Std. 90.1 -
2013
2793.[2389.] Cooling
EFLH
2837. Retail – large 2838. 545 2839. 88
22840. Retail –
large 2841. 2101 2842. 1068
2843. School –
Community college
2844. 1431 2845. 846
2846. School –
postsecondary
2847. 1191 2848. 1208
2849. School – primary 2850. 840 2851. 39
42852. School
– secondary
2853. 901 2854. 466
2855. Warehouse 2856. 452 2857. 40
02858. a – Cap means the rated cooling capacity of the product in BtuH. If the unit’s capacity
is less than 7,000 BtuH, use 7,000 BtuH in the calculation. If the unit’s capacity is greater than 15,000
[2465.] BtuH, use 15,000 BtuH in the calculation[2466.] [2467.] [2468.] Sources :
2859.[2469.] ASHRAE Standards 90.[1.] EFLH of 1-2013, Energy Standard,495 hours for Buildings Except Low Rise Residential
Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
1. Unitary HVAC is represented in the “C&I Unitary HVAC Load Shape Project Final Report. August 2011, v.1.1, p. 12,”, Table O-5. The CF reported here is a center point for NJ chosen between the CF for urban NY and for the 0-2, Mid-Atlantic region in the PJM peak periods. Available at: . This report was published August 2, 2011 and was performed by KEMA for NEEP.2860.[2470.] http://www.neep.org/sites/default/files/resources/ NEEP_HVAC_Load_Shape_Report_Final_August2_0.pdf.
2. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, Appendix G – Equivalent Full-Load Hours (EFLH) for Heating and Cooling, pp. 443‒444. Derived from DOE2.2 simulations reflecting a range of building types and climate zones.
2861. Fuel Use Economizers2862.[2471.] Algorithms 2863.[2472.] 2864. EnergyElectric Savings (kWh/yr) = (AEU * 0.13) 2865.[2473.]
[2474.] 2866.[2475.] Definition of Variables 2867.[2476.] AEU = Annual Electric Usage for an uncontrolled AC or refrigeration unit (kWh) = (Input power in kW) * (annual run time)2868.[2477.] 0.13 = Approximate energy savings factor related to installation of fuel use
economizers
[2478.] Sources :
[1.] Approximate energy savings factor of 0.13 based on average % savings for test sites represented in Table 2 (p.page 3) of NYSERDA Study: A Technology Demonstration and Validation Project for Intellidyne Energy Saving Controls; Intellidyne LLC & Brookhaven National Laboratories; 2006; available at: http://www.cleargreenpartners.com/attachments/File/NYSERDA_Report.pdf. (http://www.cleargreenpartners.com/attachments/File/NYSERDA_Report.pdf)
2869.[2479.] Dual Enthalpy Economizers2870.[2480.] The following algorithm details savings for dual enthalpy economizers. They
are to be used to determine electric energy savings between baseline standard units and the high efficiency units promoted in the program. The baseline condition is assumed to be a rooftop unit with fixed outside air (no economizer). The high efficiency units are equipped with sensors that monitor the enthalpy of outside air and return air and modulate the outside air damper to optimize energy performance.
2871. The input values are based on data provided on the application form and stipulated savings values derived from DOE 2.2 simulations of a series of prototypical small commercial buildings.
2872. 2873. Algorithms 2874.[2481.] 2875.[2482.] Electric energy savings (kWh/yr) = N * Tons * (ΔkWh/ton)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2876. 2877. Peak Energy Savings (kWh) = OTF * *SF * *Cap/Eff[2483.] [2484.] Demand Savings (kW) = 033 kWSavings/Operating Hours2878.[2485.] 2879.[2486.] Definition of Variables 2880.[2487.] N = Number of units2881. Tons OTF = Operational Testing Factor [2488.] [2489.] SF = Approximate savings factor based on regional temperature bin data (assume
4576 for equipment under 5.4 tons where a fixed damper is assumed for the baseline and 3318 for larger equipment where a dry bulb economizer is assumed for the baseline). (Units for savings factor are in kWh x rated EER per ton of cooling or kWh*EER/Ton)
[2490.] [2491.] Cap = Rated cCapacity of theconnected cooling system retrofitted with anload (tons) [2492.] [2493.] Eff = Cooling equipment energy efficiency ratio (EER) [2494.] [2495.] Operating Hours = 4,438 = Approximate number of economizer operating hours 2882.[2496.] ΔkWh/ton = Stipulated per building type electricity energy savings per ton of cooling system retrofitted with an economizer2883. 2884. Summary of Inputs 2885.
2886.[2497.] Dual Enthalpy Economizers2887.[2498.]
[2499.] Component
2888.[2500.] Type
2889.[2501.] Value 2890.[2502.] Source
[2503.] OTF [2504.] Fixe
d
[2505.] 1.0 when operational testing is performed, 0.8
otherwise
[2506.]
[2507.] SF [2508.] [2509.] 4576 for equipment under 5.4 tons, 3318
otherwise
[2510.] 1
[2511.] N Cap 2891.[2512.] Variable
2892.[2513.] 2893.[2514.] Application
2894. Cooling tonsTonsEff
2895.[2515.] Variable
[2516.] TonsRated Capacity, Tons
2896.[2517.] Application
[2518.] ΔkWh/ 2897.[2519.] F [2520.] 4,438See 2898. 1 34 2
33 Economizer savings occur when outdoor air enthalpy is relatively low, and these conditions mostly exist outside of defined system peak demand periods, therefore, the seasonal peak demand savings for this measure are assumed to be negligible. 34 From NY TRM 2016, for NYC due to proximity to NJ for small commercial and large ommercial buildings
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2499.] Component
2888.[2500.] Type
2889.[2501.] Value 2890.[2502.] Source
tonOperating Hours
ixed Table Below
2899.[2521.] [2522.] Sources:[1.] DOE-2 Simulation Modeling
[2523.] ClimateQuest Economizer Savings per Ton of Cooling SystemCalculator2900.[2524.] Building Type 2901. Savings
(ΔkWh/ton)2902. Assembly 2903. 27
2904. Big Box Retail 2905. 1522906. Fast Food Restaurant 2907. 39
2908. Full Service Restaurant
2909. 31
2910. Light Industrial 2911. 252912. Primary School 2913. 42
2914. Small Office 2915. 1862916. Small Retail 2917. 95
2918. Religious 2919. 6 2920. Warehouse 2921. 2
2922. Other 2923. 612924. [2525.] 2925.[2526.] Sources1. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Appendix J –
Commercial HVAC Unit Savings. P.455.
2926.[2527.] Occupancy Controlled Thermostats
2927. The program has received a large amount of custom electric applications for the installation of Occupancy Controlled Thermostats in hotels, motels, and, most recently, university dormitories. Due to the number of applications, consistent incentive amounts ($75 per thermostat) and predictable savings of the technology TRC recommends that a prescriptive application be created for this technology.
2928. Standard practice today is thermostats which are manually controlled by occupants to regulate temperature within a facility. An occupancy controlled thermostat is a thermostat paired with a sensor and/or door detector to identify movement and determine if a room is occupied or unoccupied. If occupancy is sensed by the sensor, the thermostat goes into an occupied mode (i.e., programmed setpoint). If a pre-programmed time frame elapses (i.e., 30 minutes) and no occupancy is sensed during that time, the thermostat goes into an unoccupied mode (e.g., setback setpoint or off) until occupancy is sensed again. This type of thermostat is often used in hotels to conserve energy.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2929. The occupancy controlled thermostat reduces the consumption of electricity and/or gas by requiring less heating and/or cooling when a room or a facility is vacant or unoccupied.
2930.2931.[2528.] Algorithms2932.2933.[2529.] Cooling Energy Savings (kWh) = (((Tc * (H+5) + Sc * (168 - (H+5)))/168) Tc) * (Pc * Caphp * 12 * EFLHc/EERhp)2934.2935.[2530.] Heating Energy Savings (kWh) = (((Th * (H+5) + Sh * (168 - (H+5)))/168)-Th) *
(Ph * Caphp * 12 * EFLHh/EERhp)2936. Heating Energy Savings (Therms) = (Th - (Th * (H+5) + Sh * (168 - (H+5)))/168) * (Ph * Caph * EFLHh/AFUEh/100,000)2937.2938.[2531.] Definition of Variables2939. T h = Heating Season Facility Temp. (°F) 2940. T c = Cooling Season Facility Temp. (°F) 2941. S h = Heating Season Setback Temp. (°F) 2942. S c = Cooling Season Setup Temp. (°F) 2943. H = Weekly Occupied Hours2944. Caphp = Connected load capacity of heat pump/AC (Tons) – Provided on
Application.2945. Caph = Connected heating load capacity (Btu/hr) – Provided on Application.2946. EFLHc = Equivalent full load cooling hours 2947. EFLHh = Equivalent full load heating hours 2948. P h = Heating season percent savings per degree setback 2949. P c = Cooling season percent savings per degree setup 2950. AFUEh = Heating equipment efficiency – Provided on Application.2951. EERhp = Heat pump/AC equipment efficiency – Provided on Application2952. 12 = Conversion factor from Tons to kBtu/hr to acquire consumption in kWh.2953. 168 = Hours per week.2954. 5 = Assumed weekly hours for setback/setup adjustment period (based on 1 setback/setup per day, 5 days per week).2955. 2956. Summary of Inputs 2957.
2958. Occupancy Controlled Thermostats2959. Comp
onent2960.Typ
e
2961. Value 2962. Source
2963. T h 2964. 2965. 2966. Applicati
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2959. Component
2960.Typ
e
2961. Value 2962. Source
Variable
on
2967. T c 2968.Vari
able
2969. 2970. Application
2971. S h 2972.Fixe
d
2973. T h-5° 2974.
2975. S c 2976.Fixe
d
2977. T c+5° 2978.
2979. H 2980.Vari
able
2981. 2982. Application; Default
of 56 hrs/week
2983. Caphp 2984.Vari
able
2985. 2986. Application
2987. Caph 2988.Vari
able
2989. 2990. Application
2991. EFLHc 2992.Fixe
d
2993. 381 2994. 1
2995. EFLHh 2996.Fixe
d
2997. 900 2998. PSE&G
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2959. Component
2960.Typ
e
2961. Value 2962. Source
2999. P h 3000.Fixe
d
3001. 3% 3002. 2
3003. P c 3004.Fixe
d
3005. 6% 3006. 2
3007. AFUEh 3008.Vari
able
3009. 3010. Application
3011. EERhp 3012.Vari
able
3013. 3014. Application
3015. Sources
1. JCP&L metered data from 1995–1999 .2. ENERGY STAR Products website.
3016. Electric Chillers
3017.[2532.] The measurement of energy and demand savings for C&I chillers is based on algorithms with key variables.
3018. This measure applies to new construction, replacement (i.e., kW/ton, Coincidence Factor, Equivalent Full Load Hours) measured through existing end-use metering of failed equipment, or enda sample of useful life. The baseline unit is a code compliant unit with an efficiency as required by ASHRAE Std. 90.1 – 2013, which is the current code adopted by the state of New Jerseyfacilities.
3019.[2533.] 3020.[2534.] Algorithms 3021.[2535.] 3022.[2536.] For IPLV:3023.[2537.] Energy Savings (kWh/yr) = N * Tons * EFLH * (IPLVb – IPLVq)
3024. 3025. Peak Demand Savings (kW) = N *= Tons *X PDC *X (IPLVb – IPLVq)
[2538.] Energy Savings = Tons X EFLH X (IPLVb – IPLVq)[2539.] 3026.[2540.] For FLV:
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3027.[2541.] Energy Savings (kWh/yr) = N * Tons * EFLH * (FLVb – FLVq)3028.
3029. Peak Demand Savings (kW) = N *= Tons *X PDC *X (FLVb – FLVq)3030.[2542.] [2543.] Energy Savings = Tons X EFLH X (FLVb – FLVq)[2544.] [2545.]
[2546.] Definition of Variables 3031.[2547.] N = Number of units3032. Tons = Rated capacity of cooling equipment. cooling capacity[2548.] EFLH = Equivalent Full Load Hours – This represents a measure of energychiller use by season determined by measured kWh during the on-peak and off peak periodsperiod divided by kW at design conditions from JCP&L measurement data.
3033.[2549.] PDC = Peak Duty Cycle: fraction of time the compressor runs during peak hours
3034.[2550.] IPLVb = Integrated Part Load Value of baseline equipment, kW/Ton. The efficiency of the chiller under partial-load conditions.3035.[2551.] IPLVq = Integrated Part Load Value of qualifying equipment, kW/Ton. The efficiency of the chiller under partial-load conditions.3036.[2552.] FLVb = Full Load Value of baseline equipment, kW/Ton. The efficiency of the chiller under full-load conditions.3037.[2553.] FLVq = Full Load Value of qualifying equipment, kW/Ton. The efficiency of the chiller under full-load conditions.3038.[2554.] 3039.[2555.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3040.[2556.] Summary of Inputs 3041. Electric Chiller Assumptions
3042. Electric
Chillers Compone
nt3043.[2557.] T
ype3044.[2558.] S
ituation3045.[2559.] Value
3046.[2560.] Source
3047.[2561.] Tons
[2562.] VariableRated
Capacity, Tons
3048.[2563.] All
3049.[2564.] Varies
3050.[2565.] From
Application
3051.[2566.] I PLVb
(kW/ton)
3052. Variable
3053. See table
below
3054. V arie
s
3055. 1
3056. IPLVq
(kW/ton)3057.[2567.] V
ariable3058.[2568.] A
ll3059.[2569.] Varies
3060.[2570.] From
Application (per AHRI Std.
550/590)3061.[2571.] F
LVb
(kW/ton)
3062. Variable
3063. See table
below
3064. V arie
s
3065. 1
3066. FLVq
(kW/ton)3067. Variabl
e3068. All 3069. V
aries
3070. From Applicatio
n (per AHRI Std.
550/590)3071. PDC 3072.[2572.] F
ixed3073.[2573.] A
ll3074.[2574.]
67%3075.[2575.] E
ngineering
Estimate3076.[2576.] E
FLH[2577.] Fixe
dVariable3077.[2578.] A
ll[2579.] S
ee Tabl
e Below1,360
[2580.] 2 35California DEER
35 From NY TRM 2016, for NYC due to proximity to NJ; for small commercial and large commercial buildings
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3078.[2581.] [2582.] Electric Chillers – Existing Buildings
[2583.] [2584.] [2585.] ASHRAE 90.1 2007 a
[2586.] Type
[2587.] Capacity
[2588.] F
[2589.] IP
[2590.] Full
Load
kW/ton
[2591.] IPL
V
kW/ton
[2592.] Air Cooled [2593.] tons
< 150
[2594.] 2
[2595.] 3.0
[2596.] 1.25
6
[2597.] 1.15
3
[2598.] [2599.] tons > 150
[2600.] 2
[2601.] 3.0
[2602.] 1.25
6
[2603.] 1.15
3
[2604.] Water
Cooled[2605.] Pos
itive[2606.] Dis
placement
[2607.] (rotary
screw[2608.] and
scroll)
[2609.] tons < 75
[2610.] 4
[2611.] 5.2
[2612.] 0.79
0
[2613.] 0.67
6[2615.] 75 <
tons < 150
[2616.] 4
[2617.] 5.2
[2618.] 0.79
0
[2619.] 0.67
6[2621.] 150 <
tons < 300
[2622.] 4
[2623.] 5.6
[2624.] 0.71
8
[2625.] 0.62
8[2627.] 300 <
tons < 600
[2628.] 5
[2629.] 6.1
[2630.] 0.63
9
[2631.] 0.57
2
[2633.] tons > 600
[2634.] 5
[2635.] 6.1
[2636.] 0.63
9
[2637.] 0.57
2
[2638.] Water
Cooled[2639.] Ce
ntrifugal
[2640.] tons < 150
[2641.] 5
[2642.] 5.2
[2643.] 0.70
3
[2644.] 0.67
0[2646.] 150 <
tons < 300
[2647.] 5
[2648.] 5.9
[2649.] 0.63
4
[2650.] 0.59
6[2652.] 300 <
tons < 400
[2653.] 6
[2654.] 6.4
[2655.] 0.57
6
[2656.] 0.54
9
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2658.] 400 < tons < 600
[2659.] 6
[2660.] 6.4
[2661.] 0.57
6
[2662.] 0.54
9
[2664.] tons > 600
[2665.] 6
[2666.] 6.4
[2667.] 0.57
6
[2668.] 0.54
9[2669.]
[2670.] a - The 90.1 2007 efficiencies were used in the 90.1 2013 capacity categories for consistency between tables. The 2007 water cooled reciprocating category was removed and the 90.1 2007 water cooled screw and scroll efficiencies were used in the appropriate 90.1 2013 water cooled positive displacement capacity categories (the water cooled reciprocating category was removed from ASHRAE 90.1 in 2010).
[2671.] Electric Chillers – New Construction3079.[2672.] 3080.[2673.] 3081.[2674.] ASHRAE 90.1 20133082.[2675.] 3083.[2676.] 3084.[2677.] effective 1/1/2015 a
3085.[2678.] 3086.[2679.] 3087.[2680.] P
ath A3088.[2681.] P
ath B
3089.[2682.] Type3090.[2683.] Ca
pacity
3091.[2684.] Full
Load
kW/ton
3092.[2685.] IPL
V
kW/ton
3093.[2686.] Full
Load
kW/ton
3094.[2687.] IPL
V
kW/ton
3095.[2688.] Air Cooled
3096.[2689.] 3097.[2690.] 10.1
3098.[2691.] 13.
73099.[2692.] 9.7
3100.[2693.] 15.8
3102.[2695.] tons < 150
3103.[2696.] 1.18
8
3104.[2697.] 0.8
76
3105.[2698.] 1.23
7
3106.[2699.] 0.75
9
3108.[2701.] 3109.[2702.] 10.1
3110.[2703.] 14.
03111.[2704.] 9.7
3112.[2705.] 16.1
3114.[2707.] tons > 150
3115.[2708.] 1.18
8
3116.[2709.] 0.8
57
3117.[2710.] 1.23
7
3118.[2711.] 0.74
5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3119.[2712.] Water Cooled Positive
3120.[2713.] Displacement
3121.[2714.] (rotary screw
3122.[2715.] and scroll)
3123.[2716.] tons < 75
3124.[2717.] 0.75
0
3125.[2718.] 0.6
00
3126.[2719.] 0.78
0
3127.[2720.] 0.50
0
3129.[2722.] 75 < tons < 150
3130.[2723.] 0.72
0
3131.[2724.] 0.5
60
3132.[2725.] 0.75
0
3133.[2726.] 0.49
0
3135.[2728.] 150 < tons < 300
3136.[2729.] 0.66
0
3137.[2730.] 0.5
40
3138.[2731.] 0.68
0
3139.[2732.] 0.44
0
3141.[2734.] 300 < tons < 600
3142.[2735.] 0.61
0
3143.[2736.] 0.5
20
3144.[2737.] 0.62
5
3145.[2738.] 0.41
0
3147.[2740.] tons > 600
3148.[2741.] 0.56
0
3149.[2742.] 0.5
00
3150.[2743.] 0.58
5
3151.[2744.] 0.38
0
3152.[2745.] Water Cooled
3153.[2746.] Centrifugal
3154.[2747.] tons < 150
3155.[2748.] 0.61
0
3156.[2749.] 0.5
50
3157.[2750.] 0.69
5
3158.[2751.] 0.44
0
3160.[2753.] 150 < tons < 300
3161.[2754.] 0.61
0
3162.[2755.] 0.5
50
3163.[2756.] 0.63
5
3164.[2757.] 0.40
0
3166.[2759.] 300 < tons < 400
3167.[2760.] 0.56
0
3168.[2761.] 0.5
20
3169.[2762.] 0.59
5
3170.[2763.] 0.39
0
3172.[2765.] 400 < tons < 600
3173.[2766.] 0.56
0
3174.[2767.] 0.5
00
3175.[2768.] 0.58
5
3176.[2769.] 0.38
0
3178.[2771.] tons > 600
3179.[2772.] 0.56
0
3180.[2773.] 0.5
00
3181.[2774.] 0.58
5
3182.[2775.] 0.38
0
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3183.[2776.] a – Values in italics are EERs.3184.[2777.]
3185.[2778.] EFLH Table
3186. Facility Type
3187. Cooling
EFLH3188. Assembly 3189. 669
3190. Auto repair 3191. 4263192. Dormitory 3193. 800
3194. Hospital 3195. 1424
3196. Light industrial 3197. 549
3198. Lodging – Hotel
3199. 2918
3200. Lodging – Motel
3201. 1233
3202. Office – large 3203. 720
3204. Office – small 3205. 955
3206. Other 3207. 7363208. Religious
worship 3209. 279
3210. Restaurant – fast food 3211. 645
3212. Restaurant – full service 3213. 574
3214. Retail – big box
3215. 1279
3216. Retail – Grocery
3217. 1279
3218. Retail – large 3219. 882
3220. Retail – large
3221. 1068
3222. School – Community
college3223. 846
3224. School – postsecondary
3225. 1208
3226. School – primary 3227. 394
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3186. Facility Type
3187. Cooling
EFLH3228. School –
secondary 3229. 466
3230. Warehouse 3231. 4003232.3233.[2779.] Sources
1. ASHRAE Standards 90.1-2013. Energy Standard for Buildings Except Low Rise Residential Buildings. https://www.ashrae.org/standards-research--technology/standards--guidelines.
2. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling; pp. 443–444. Derived from DOE2.2 simulations reflecting a range of building types and climate zones.
3234. Variable Frequency Drives[2780.] This section provides algorithms and assumptions for reportingThe measurement of energy and demand savings for C/I Variable Frequency Drive (VFD) installationsfor VFD applications is are for constant and variable air volume system HVAC systems including: supply air fans, return air fans, chilled water and condenser water pumps, hot water circulation pumps, water source heat pump circulation pumps, cooling tower fans, and kitchen hood fans, boiler feed water pumps., and boiler draft fans only. VFD applications for other end usesthan this use should follow the custom path.3235.[2781.]
3236.[2782.] Algorithms 3237.[2783.] [2784.] Energy Savings (kWh/year) = N * ) = 0.746 * *HP * *HRS * (ESF/ηmotor)
3238.[2785.] [2786.] Peak Demand Savings (kW) = N * 0.746 * *HP * (DSF/ηmotor)
3239.[2787.] 3240.[2788.] Definitions of Variables 3241.[2789.] N = Number of motors controlled by VFD(s) per application
3242. HP = Nameplate= nameplate motor horsepower or manufacturer specificationspec. sheet per application[2790.] ηmotor = Motor efficiency at the peak load. Motor efficiency varies with load. At low loads relative to the rated hp (usually below 50%) efficiency often drops dramatically.[2791.] [2792.] ESF = Energy Savings Factor (kWh/year per HP) . The energy savings factor is calculated by determining the ratio of the power requirement for baseline and VFD control at peak conditions.3243.[2793.] DSF = Demand Savings Factor (kW per HP) 3244.
3245. Summary . The demand savings factor is calculated by determining the ratio of Inputs the power requirement for baseline and VFD control at peak conditions
3246.[2794.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2795.] HRS = annual operating hours[2796.]
3247.[2797.] Variable Frequency Drives3248.[2798.]
[2799.] Component
3249.[2800.] Type
3250.[2801.] Value 3251.[2802.] Source
3252.[2803.] Motor HP
3253.[2804.] Variable
3254.[2805.] Nameplate/
Manufacturer Spec. Sheet
3255.[2806.] Application
[2807.] ηmotor [2808.] Variable [2809.] Nameplate/Manufacturer Spec. Sheet
[2810.] Application
[2811.] ESF 3256.[2812.] Variable
3257.[2813.] See Table Below
[2814.] 1, 2, 3
Connecticut Light
and Power
3258.[2815.] DSF
3259.[2816.] Variable
3260.[2817.] See Table Below
[2818.] 1, 2, 3
Connecticut Light
and Power
[2819.] HRS [2820.] Variable [2821.] >2,000 [2822.] Application
[2823.] [2824.] VFD Savings Factors
[2825.]
ComponentEnergy Savings
Factor, ESFDemand Savings
Factor, DSFAirfoil/Backward Inclined Fans 0.475 0.448
Forward Curved Fans 0.240 0.216Chilled Water Pumps 0.580 0.201Cooling Tower Fans 0.580 0.000
[2826.]
[2827.] Air Compressors with Variable Frequency Drives[2828.] [2829.] The measurement of energy and demand savings for variable frequency drive (VFD)
air compressors.[2830.] [2831.] Algorithms [2832.] 3261.[2833.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3262. The ESF for the supply and return fans and circulating pumps are derived from a 2014 NEEP-funded study of 400 VFD installations in eight northeast states. The derived values are based on actual logged input power data and reflect average operating hours, load factors, and motor efficiencies for the sample. Savings factors representing cooling tower fans and boiler feed water pumps are not reflected in the NEEP report. Values representing these applications are taken from April 2016 New York TRM, Appendix K, and represent average values derived from DOE2.2 simulation of various building types and climate zones, supplemented with results from an earlier analysis of actual program data completed by NSTAR in 2010.
3263. The DSF are derived from the same sources. The NEEP values reflect the actual average impact for the category occurring in the PJM defined peak demand period. The NY values are based on a similar but not identically defined peak period. In all cases the values are expressed in kW/HP rating of the controlled motor and reflect average load factors during the peak period and motor efficiencies for the sample.
3264.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3265. VFD Savings Factors3266. Energy Savings (kWh) = HRS * (*(Maximum kW/HP Savings) * )*Motor HP[2834.] [2835.] Demand Savings (kW) = PDC * (*(Maximum kW/HP Savings) * )*Motor HP[2836.] [2837.] Maximum kW/HP Savings = Percent Energy Savings * (0.746 / EFFb)[2838.]
[2839.] Definitions of Variables [2840.] [2841.] HRS = Annual compressor runtime (hours) from application.[2842.] [2843.] PDC = Peak Duty Cycle: fraction of time the compressor runs during peak hours[2844.] [2845.] EEFb = Efficiency of the industry standard compressor at average load [2846.] [2847.] 0.746 = kW to HP conversion factor
[2848.] [2849.] Air Compressors with VFDs
[2850.] [2851.] Component [2852.] Type [2853.] Value [2854.] Source
[2855.] Motor H
PApplication
3267. ESF (kWh/Year-HP)Variable
[2856.] DSF (kW/HP
)Nameplate
[2857.] SourceApplicatio
n[2859.] Supply Air
FanMaximum kW/HP Savings
[2860.] 2,033Fixed [2861.] 0.286274 [2862.] Calculated1
[2864.] Return Air FanPDC
[2865.] 1,788Fixed [2866.] 0.297865 3270.[2867.] 1
3272.[2869.] CHW or CW Pump
3273. 1,633 3274. 0.185 3275. 1
3276. HHW Pump
3277. 1,548 3278. 0.096 3279. 1
3280. WSHP PumpHRS
[2870.] 2,562Fixed [2871.] 0.2344957
[2872.] 1 2
[2874.] CT FanPercent
Energy Savings
[2875.] 290Fixed [2876.] - 0.02522%
3282.[2877.] 2, 3
[2879.] Boiler Feedwater PumpEEFb
[2880.] 1,588Fixed [2881.] 0.49860 3284.[2882.] 2, 3
3286.[2884.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[2885.] Sources :
[1.] Cadmus, NEEP – Aspen Systems Corporation, Prescriptive Variable Speed Drive Loadshape Project, August 2014; available at: http://www.neep.org/variable-speed-drive-loadshape-study-final-report.
3. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, Appendix K – VFD Savings Factors, derived from DOE2.2 simulations reflecting a range of building types and climate zones.
4. Chan, Tumin Formulation of Prescriptive Incentive for VFD, and Motors and VFD Impact Tables, NSTAR 2010.
3287. Program Support for IndustrialVariable Speed Air Compressors, June 20, 2005.3288.[2886.] This measure applies to the installation of variable speed air compressors in
retrofit installations where they replace fixed speed compressor with either inlet vane modulation, load no load, or variable displacement flow control. The measure also applies to “lost opportunity” installations including new construction, the expansion of existing facilites, or replacement of existing equipment at end of life. In all cases the baseline is assumed to be a fixed speed compressor with one of the flow control methods described above.
1. The measure applies to variable speed air compressor up to 75 HP. For larger installations, the implementation cost and energy savings varies significantly between installations and the deemed savings factors provided here are not applicable. Custom protocols should be applied to derive savings and incentive levels for installations larger than 75 HP. Xenergy, Assessment of the Market for Compressed Air Efficiency Systems. 2001.
[1.] ACEEE, Modeling and Simulation of Air Compressor Energy Use. 2005.[2887.]
3289.[2888.] Algorithms3290.3291.[2889.] Energy Savings (kWh) = HRS * SF * Motor HP
3292. Peak Demand Savings (kW) = Motor HP * CF
3293.[2890.] Definition of Variables3294. HRS = Annual compressor run time from application, (hours/year).
3295. 0.746 = kW to HP conversion factorSF = Deemed Savings factor from savings factor table, kW/nameplate HP.
3296. Motor HP = Nameplate motor HP for variable speed air compressor, HP.
3297. CF = Coincidence factor applicable to commercial compressed air installations
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3298. Summary of Inputs 3299.
3300. Air Compressors with VFDs3301. Comp
onent3302. Ty
pe3303. Value 3304. Source
3305. Motor HP
3306. Variable
3307. Nameplate 3308. Application
3309. SF 3310. Fixed
3311. 0.186 3312. 1
3313. HRS 3314. Variable
3315. 6,978 hours/year (default)
3316. Application, default value from source 1
3317. CF 3318. Fixed
3319. 1.05 3320. 1
3321.3322.[2891.] Sources
1. Impact Evaluation of 2014 RI Prescriptive Compressed Air Installations, National Grid, Prepared by KEMA, July 15, 2016.
3323. New and Retrofit Kitchen Hoods with Variable Frequency Drives 3324.[2892.] [2893.] Kitchen Hoods with Variable Frequency Control utilize optical and temperature
sensors at the hood inlet to monitor cooking activity. Kitchen hood exhaust fans are throttled in response to real time ventilation requirements. Energy savings result from fan power reduction during part load operation as well as a decrease in heating and cooling requirement of make-up air.
3325.[2894.] 3326.[2895.] Algorithms 3327.[2896.] [2897.] Electric Fan Savings (kWh) = NQ * (HP * *LF * 0.746/FEFF) * RH * PR3328.[2898.] 3329.[2899.] Heating Savings (MMBtu) = SF * CFM/SF * OF * FR * HDD * 24 * 1.08 / (HEFF * 1,000,000)3330.[2900.] 3331.[2901.] Cooling Savings (kWh) = SF * CFM/SF * OF * FR * CDD * 24 * 1.08 / (CEFF
* 3,412)3332.[2902.] 3333.[2903.] Definition of Variables [2904.] N = NumberQ=Quantity of Kitchen Hood Fan Motors3334.[2905.] HP = Kitchen Hood Fan Motor HP3335.[2906.] LF = Existing Motor Loading Factor3336.[2907.] 0.746 = Conversion from HP to kW3337.[2908.] FEFF = Efficiency of Kitchen Hood Fan Motors (%)3338.[2909.] RH = Kitchen Hood Fan Run Hours
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3339.[2910.] PR = Fan Motor Power Reduction resultant from VFD/Control Installation3340.[2911.] SF = Kitchen Square Footage3341.[2912.] CFM/SF = Code required ventilation rate per square foot for Commercial
Kitchen spaces3342.[2913.] OF = Ventilation rate oversize factor (compared to code requirement)3343.[2914.] FR = Flow Reduction resultant from VFD/Control Installation3344.[2915.] HDDmod = Modified Heating Degree Days based on location and facility type3345.[2916.] CDDmod = Modified Cooling Degree Days based on location and facility type3346.[2917.] 24 = Hours per Day3347.[2918.] 1.08 = Sensible heat factor for air ((Btu/hr) / (CFM * Deg F))3348.[2919.] HEFF = Efficiency of Heating System (AFUE %)3349.[2920.] CEFF = Efficiency of Cooling System (COP)3350.[2921.] 3,412 = Conversion factor from Btu to kWh (3,412 Btu = 1 kWh)3351.[2922.] 1,000,000 = Btu/MMBtu3352.[2923.] 3353.[2924.] Summary of Inputs 3354.
3355. Kitchen Hoods with VFDs[2925.]
3356.[2926.] Compon
ent
3357.[2927.] Type
3358.[2928.] Value
3359.[2929.] Source
[2930.] N Q
3360.[2931.] Variable
3361.[2932.] Quantity
3362.[2933.] Application
3363.[2934.] HP
3364.[2935.] Variable
3365.[2936.] Nameplate
3366.[2937.] Application
3367.[2938.] LF
3368.[2939.] Fixed
3369.[2940.] 0.9
3370.[2941.] Melink Analysis Sample1
3371.[2942.] FEFF
3372.[2943.] Variable
[2944.] Based on Motor
HP
3373.[2945.] NEMA Premium Efficiency, TEFC 1800 RPM
3374.[2946.] RH
3375.[2947.] Variable
3376.[2948.] Based on Facility Type
3377.[2949.] Facility Specific Value Table
3378.[2950.] PR
3379.[2951.] Variable
3380.[2952.] Based on Facility Type
3381.[2953.] Facility Specific Value Table
3382.[2954.] SF
3383.[2955.] Variable
3384.[2956.] Kitchen
Square
3385.[2957.] Application
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Footage3386.[2958.]
CFM / SF
3387.[2959.] Fixed
3388.[2960.] 0.7
3389.[2961.] ASHRAE 62.1 2013 Table 6.5
3390.[2962.] OF
3391.[2963.] Fixed
3392.[2964.] 1.4
3393.[2965.] Estimated Typical Kitchen Design2
3394.[2966.] FR
3395.[2967.] Variable
3396.[2968.] Based on Facility Type
3397.[2969.] Facility Specific Value Table
3398.[2970.] HDDmod
3399.[2971.] Variable
3400.[2972.] 3401.[2973.] Heating Degree Day Table
3402.[2974.] CDDmod
3403.[2975.] Variable
3404.[2976.] 3405.[2977.] Cooling Degree Day Table
3406.[2978.] HEFF
3407.[2979.] Fixed
3408.[2980.] 0.8
3409.[2981.] 8.1F3Estimated Heating System Efficiency3
3410.[2982.] CEFF
3411.[2983.] Fixed
3412.[2984.] 3.00
3413.[2985.] Estimated Cooling System Efficiency4
3414.[2986.] 3415.[2987.] Facility-Specific Values Table5
3416.[2988.]
Facility Type Run Hours Power Reduction (PR) Flow Reduction (FR)Campus 5250 0.568 0.295Lodging 8736 0.618 0.330
Restaurant 5824 0.552 0.295Supermarket 5824 0.597 0.320
Other 5250 0.584 0.310
3417.[2989.] Modified Heating Degree Days Table6
3418.[2990.]
Building TypeHeating Energy
Density (kBtu/sf)
Degree Day Adjustment
Factor
Atlantic City (HDD)
Newark(HDD)
Philadelphia(HDD)
Monticello(HDD)
Education 29.5 0.55 2792 2783 2655 3886Food Sales 35.6 0.66 3369 3359 3204 4689
Food Service 39.0 0.73 3691 3680 3510 5137Health Care 53.6 1.00 5073 5057 4824 7060
Lodging 15.0 0.28 1420 1415 1350 1976Retail 29.3 0.55 2773 2764 2637 3859Office 28.1 0.52 2660 2651 2529 3701
Public Assembly 33.8 0.63 3199 3189 3042 4452Public Order/Safety 24.1 0.45 2281 2274 2169 3174Religious Worship 29.1 0.54 2754 2745 2619 3833
Service 47.8 0.89 4524 4510 4302 6296Warehouse/Storage 20.2 0.38 1912 1906 1818 2661
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3419.[2991.] Modified Cooling Degree Days Table7
3420.[2992.]
Building TypeDegree Day Adjustment
Factor
Atlantic City (CDD)
Newark (CDD)
Philadelphia (CDD)
Monticello (CDD)
Education 0.55 824 893 806 625Food Sales 0.66 989 1071 967 750
Food Service 0.73 1094 1185 1069 830Health Care 1.00 1499 1623 1465 1137
Lodging 0.28 420 454 410 318Retail 0.55 824 893 806 625Office 0.52 779 844 762 591
Public Assembly 0.63 944 1022 923 716Public Order/Safety 0.45 675 730 659 512Religious Worship 0.54 809 876 791 614
Service 0.89 1334 1444 1304 1012Warehouse/Storage 0.38 570 617 557 432
3421.[2993.] [2994.] Sources :
[1.] To assist with development of this protocol, Melink Corporation provided several sample analyses performed on typical facilities utilizing Intelli-Hood control systems. The analysis performed is used nationwide by Melink to develop energy savings and financial reports related to installation of these systems for interested building owners. Melink’s analysis is mirrored in this protocol and includes several of the assumed values utilized here, including an average 0.9 load factor on hood fan motors, as well as operating hours for typical campus, lodging, restaurant and supermarket facility types.
[2.] Oversize factor of 1.4 is a best estimate based on past experience, assessments conducted at facilities with commercial food service equipment and approximations based on Melink sample analyses, which lead to average commercial kitchen ventilation rate of 1 CFM/SF (0.7 * 1.4). While exact ventilation rate is dependent on installed equipment and other factors, this figure is meant to represent average ventilation across potential retrofit and new installation projects.
[3.] A typical heating system efficiency of 80% AFUE is assumed based on estimates of average facility size, heating system age, and past and present code requirements, as well as assumptions indicated in Melink sample analyses. This figure is meant to represent average heating system efficiency across potential retrofit and new installation projects.
[4.] A typical cooling system efficiency of 3.00 COP (10.24 EER, 1.17 kW/Ton) is assumed based on estimates of average facility size, cooling system age, and past and present code requirements, as well as assumptions indicated in Melink sample analyses. This figure is meant to represent average cooling system efficiency across potential retrofit and new installation projects.
[5.] Facility Specific Values table constructed based on consolidation of Melink sample analysis data. Facility run hours were averaged across all like sample analyses. Fan power and flow reductions were calculated utilizing fan power profiles included in each sample analysis.
[6.] KEMA, June 2009, New Jersey’s Clean Energy Program Smartstart Program Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
%20Report%20-%20Final%20June%2011%202009.pdf.KEMA, Smartstart Program Protocol Review. 2009.
2.[7.] Modified Cooling Degree Days table utilizes Degree Day Adjustment factors from Heating Degree Days table and cooling degree days for each of the four representative cities as indicated by degreedays.net.3422.[2995.] [2996.] Commercial Refrigeration Measures[2997.] [2998.] For Aluminum Night Curtains, Door Heater Controls, Electric Defrost Controls,
Evaporator Fan Controls, and Novelty Cooler Shutoff, see applicable protocols for the commercial Direct Install program.
[2999.]
[3000.] For Energy Efficient Glass Doors on Verticalfor Open Refrigerated Cases:
3423.[3001.] This measure applies to retrofitting vertical, open, refrigerated display cases with high efficiency glass doors that have either no anti-sweat heaters (“zero energy doors”), or very low energy anti- sweat heaters. The deemed savings factors are derived from the results of a controlled test designed to measure the impact of this measure. The results of the test were presented at the 2010 International Refrigeration and Air Conditioning conference.
3424.3425.[3002.] Algorithms 3426.[3003.] [3004.] Demand Savings: ΔkW = (HG × EF × CL) / (EER × 1000)[3005.] [3006.] Annual Energy Savings (kWh/yr):: ΔkWh = ESF × CLΔkW × Usage3427.[3007.] 3428.[3008.] Peak Demand Savings (kW): ΔkW = ΔkWh / Hours3429. 3430. Heating Energy Savings: ΔTherms = HSF x CL3431. 3432. Definition Definitions of Variables 3433.[3009.] Δ kWh = Gross customer annual kWh savings for the measure 3434. ΔkW = Gross= gross customer connected load kW savings for the measure
(kW)3435.[3010.] ESF = Stipulated annual electric savings per linear foot of case3436. HSF = Stipulated annual heating savings factor per linear foot of case 3437. HG = Loss of cold air or heat gain for refrigerated cases with no cover (Btu/hr-ft
opening)[3011.] [3012.] EF = Efficiency Factor, fraction of heat gain prevented by case door[3013.] [3014.] CL = = Case Length, open length of the refrigerated case in feet (from
application)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3438.[3015.] Hours = Hours per year that case is in operation, use 8,760 unless otherwise indicated.
3439. 3440. Summary of Inputs
3441. EER = Compressor efficiency (Btu/hr-watt)
[3016.]
[3017.] 1000 = Conversion from watts to kW (W/kW).
[3018.]
[3019.] ΔkWh = gross customer annual kWh savings for the measure (kWh)
[3020.]
[3021.] Usage = hours per year[3022.] Commercial Refrigeration
3442.[3023.] [3024.] Compo
nent3443.[3025.] Type
3444.[3026.] Value 3445.[3027.] Source
[3028.] ESFHG 3446.[3029.] Fixed
3447.[3030.] 3448. 395 kWh/year-foot760
[3031.] 1,2,3,4,5 PG&E study by ENCON
Mechanical & Nuclear
Engineering, 1992
[3032.] HSFEF 3449.[3033.] Fixed
[3034.] 0.8510.5 Therms/year-foot 3450. 1,2,3,4,5PG&E study by ENCON
Mechanical & Nuclear
Engineering, 1992
3451.[3035.] CL
3452.[3036.] Variab
le
3453.[3037.] 3454.[3038.] Rebate
Application or Manufacturer
Data[3039.] EER [3040.] Fixed [3041.] 9.0 [3042.] Average based
on custom applications for the NJCEP C&I Program in 2010
[3043.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3024.] Component
3443.[3025.] Type
3444.[3026.] Value 3445.[3027.] Source
[3044.] UHoursUsage
3455.[3045.] Fixed
3456.[3046.] 8,760/year unless otherwise specified
3457. 3 Continuous
Operation365 days/year, 24
hours/day3458.[3047.]
3459.[3048.] Sources
1. Energy Use of Doored and Open Vertical Refrigerated Display , Brian Fricke and Bryan Becker, University of Missouri – Kansas City, 2010; presented at the 2010 International Refrigeration and Air Conditioning Conference, School of Mechanical Engineering, Purdue University, Paper #1154; available at: http://docs.lib.purdue.edu/cgi/viewcontent.cgi?article=2153&context=iracc http://docs.lib.purdue.edu/iracc/1154
2. Refrigeration COP of 2.2 used in derivation of savings factors – Kuiken et al, Focus on Energy Evaluation, Business Program: Deemed Savings Manual V 1.0, KEMA, March 22, 2010.
3. HVAC COP of 3.2 used in derivation of savings factors – ASHRAE Standards 90.1-2007 and 2013, Energy Standard for Buildings Except Low Rise Residential Buildings. https://www.ashrae.org/standards-research--technology/standards--guidelines, Table 6.8.1A.
4.[8.] Gas boiler efficiency of 80% used in derivation of savings factors – ASHRAE Standards 90.1-2007 and 2013, Energy Standard for Buildings Except Low Rise Residential Buildings. https://www.ashrae.org/standards-research--technology/standards--guidelines, Table 6.8.1F.
5. DOE Typical Meteorological Year (TMY3) data for Trenton, Newark, and Atlantic City.
3460. Aluminum Night Covers
3461. Commercial Refrigerators and Freezers[3049.] [3050.] This measure is applicable to replacement of existing open-type refrigerated display
cases where considerable heat is lost through an opening that is directly exposed to ambient air. commercial grade refrigeratorsThese retractable aluminum woven fabric covers provide a barrier between the contents of the case and the outside environment. They are employed during non-business hours to significantly reduce heat loss from these cases when contents need not be visible.
3462. Savings approximations are based on the report, “Effects of the Low Emissivity Shields on performance and Power use of a refrigerated display case,” by Southern California Edison, August 8, 1997. Southern California Edison (SCE) conducted this test at its state-of-the-art Refrigeration Technology and Test Center (RTTC), located in Irwindale, CA. The RTTC’s sophisticated instrumentation and data acquisition system provided detailed tracking of the refrigeration system’s critical temperature and pressure points during the test period. These readings were then utilized to quantify various heat transfer and power related parameters within the refrigeration cycle. The results of SCE’s test focused on three typical scenarios found mostly in supermarkets: low, medium and high temperature cases.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3463. 3464. Algorithms 3465. 3466. kWh Savings = W * H * F3467. 3468. Definition of Variables 3469. W = Width of protected opening in ft.3470. H = Hours per year covers are in place3471. F = Savings factor based on case temperature:3472. Low temperature (-35F to -5F) F = 0.1 kW/ft3473. Medium temperature (0F to 30F) F = 0.06 kW/ft3474. High temperature (35F to 55F) F = 0.04 kW/ft
3475. Walk-in Cooler/Freezer Evaporator Fan Control
3476. This measure is applicable to existing walk-in coolers and freezers that have evaporator fans which run continuously. with energy efficient glass and solid door units complying with ANSI/ASHRAE Standard 72-2005, Method of Testing Commercial Refrigerators and Freezers. The measure adds a control system feature to automatically shut off evaporator fans when the cooler’s thermostat is not calling for cooling. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein. These savings take into account evaporator fan shut off and associated savings as a result of less heat being introduced into the walk-in, as well as the savings from the compressor, which is now being controlled through electronic temperature control.
3477.[3051.] Several case studies have been performed that verify the accuracy of these savings. The algorithms below are based on field-tested approximations of energy savings realized through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system. [1]
3478.3479.[3052.] Algorithms 3480.[3053.] 3481.[3054.] Gross kWh Savings = kWh SavingsEF + kWh SavingsRH + kWh SavingsEC
3482.3483.[3055.] kWh SavingsEF = ((AmpsEF * VoltsEF * (PhaseEF)1/2 )/1000) * 0.55 * 8,760 *
35.52%3484.3485.[3056.] kWh SavingsRH = kWh SavingsEF * 0.28 * 1.63486.3487.[3057.] kWh SavingsEC = (((AmpsCP * VoltsCP * (PhaseCP)1/2 )/1000) * 0.85 * ((35% * WH) + (55% * NWH)) * 5%) + (((AmpsEF * VoltsEF * (PhaseEF)1/2 )/1000) * 0.55 * 8,760 * 35.52% * 5%)3488.3489.[3058.] Gross kW Savings = ((AmpsEF * VoltsEF * (PhaseEF)1/2 )/1000) * 0.55 * D3490.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3491.[3059.] Definition of Variables3492. kWh SavingsEF = Savings due to Evaporator Fan being off3493. kWh SavingsRH = Savings due to reduced heat from Evaporator Fans3494. kWh SavingsEC = Savings due to the electronic controls on compressor and evaporator3495. AmpsEF = Nameplate Amps of Evaporator Fan3496. VoltsEF = Nameplate Volts of Evaporator Fan3497. PhaseEF = Phase of Evaporator Fan3498. 0.55 = Evaporator Fan Motor power factor3499. 8,760 = Annual Operating Hours3500. 35.52% = Percent of time Evaporator Fan is turned off. [2]3501. 0.28 = Conversion from kW to tons (Refrigeration)3502. 1.6 = Efficiency of typical refrigeration system in kW/ton [3]3503. AmpsCP = Nameplate Amps of Compressor3504. VoltsCP = Nameplate Volts of Compressor3505. PhaseCP = Phase of Compressor3506. 0.85 = Compressor power factor.3507. 35% = Compressor duty cycle during winter months (estimated)3508. WH = Compressor hours during winter months (2,195)3509. 55% = Compressor duty cycle during non-winter months (estimated)3510. NWH = Compressor hours during non-winter months (6,565)3511. 5% = Reduced run time of Compressor and Evaporator due to
electronic controls [4]3512. D = 0.228 or Diversity Factor [5]3513.
3514.[3060.] Sources
1. Several case studies related to NRM’s Cooltrol system can be found at: http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html.
2. This value is an estimate by NRM based on hundreds of downloads of hours of use data from the electronic controller. It is an ‘average’ savings number and has been validated through several Third Party Impact Evaluation Studies including study performed by HEC, “Analysis of Walk-in Cooler Air Economizers,” p. 22, Table 9, October 10, 2000 for National Grid.
3. Select Energy Services, Inc. Cooler Control Measure Impact Spreadsheet User’s Manual. 2004.Savings (kWh) = D * (Eb – Eq)
4.[9.] This percentage has been collaborated by several utility sponsored 3rd Party studies including study conducted by Select Energy Services for NSTAR, March 9, 2004.
5. Based on the report “Savings from Walk-In Cooler Air Economizers and Evaporator Fan Controls,” HEC, June 28, 1996.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3515. Cooler and Freezer Door Heater Control
3516. This measure is applicable to existing walk-in coolers and freezers that have continuously operating electric heaters on the doors to prevent condensation formation. This measure adds a control system feature to shut off the door heaters when the humidity level is low enough such that condensation will not occur if the heaters are off.
[3061.] This is performed by measuring the ambient humidity and temperature of the store, calculating the dewpoint, and using PWM (pulse width modulation) to control the anti-sweat heaters based on specific algorithms for freezer doors. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
3517. Several case studies have been performed that verify the accuracy of these savings. The algorithms below are based on field-tested approximations of energy savings realized through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system. [1]
3518.3519.[3062.] Low Temperature (Freezer) Door Heater Control3520. 3521. Algorithms 3522. 3523. kWh Savings = (kWDH * 8,760) – ((40% * kWDH * 4,000) + (65% * kWDH * 4,760))3524. 3525. kW Savings = kWDH * 46% * 75%3526. 3527. Definition of Variables
3528. kWDH = Total demand (kW) of the freezer door heaters, based on nameplate volts and amps.3529. 8,760 = Annual run hours of Freezer Door Heater before controls.3530. 40% = Percent of total run power of door heaters with controls providing maximum reduction [2]3531. 4,000 = Number of hours door heaters run at 40% power.3532. 65% = Percent of total run power of door heaters with controls providing minimum reduction [3]3533. 4,760 = Number of hours door heaters run at 65% power.3534. 46% = Freezer Door Heater off time [3]3535. 75% = Adjustment factor to account for diversity and coincidence at peak demand
[2]3536.3537.[3063.] Medium Temperature (Cooler) Door Heater Control3538.3539.[3064.] Algorithms3540.3541.[3065.] Energy Savings (kWh/yr) = (kWDH * 8,760) – (60% * kWDH * 3,760)3542.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3543. Peak Demand Savings (kW) = kWDH * 74% * 75%kWh Savings/ (D * H)3544.[3066.] 3545.[3067.] Definition of Variables [3068.] D = Operating Days per Year (assume 365)[3069.] H = Daily Operating Hours (assume 24)[3070.] Eb = Daily kWh Consumption of Baseline Equipment (from Table 1 below)[3071.] Eq = Daily kWh Consumption of Qualifying Equipment (from Application)[3072.]
[3073.]
Proposed Equipment Type kWh Consumption (V = Unit Volume in ft 3)Glass Door Freezer 0.75V + 4.1Glass Door Refrigerator 0.12V + 3.34Solid Door Freezer 0.4V + 1.38Solid Door Refrigerator 0.1V + 2.04
Table 1: Baseline Equipment Daily kWh Consumption
[3074.] [3075.] kWDH = Total demand (kW) of the cooler door heaters, based on nameplate volts and amps.3546. 8,760 = Annual run hours of Cooler Door Heater before controls.3547. 60% = Percent of total run power of door heaters with controls providing minimum reduction.2 3548. 3,760 = Number of hours door heaters run at 60% power.3549. 74% = Cooler Door Heater off time [3]3550. 75% = Adjustment factor to account for diversity and coincidence at peak demand
[2]3551. 3552. Sources : [3076.] Savings algorithm, baseline values, assumed values and lifetimes developed from
information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
[3077.] [1.] Several case studies related to NRM’s Cooltrol system can be found at:
http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html
1. Estimated by NRM based on their experience of monitoring the equipment at various sites.2. This value is an estimate by National Resource Management based on hundreds of
downloads of hours of use data from Door Heater controllers. This supported by 3rd Party Analysis conducted by Select Energy for NSTAR, “Cooler Control Measure Impact Spreadsheet Users’ Manual,” P.5, March 9, 2004.
3553. Electric Defrost Control
3554. This measure is applicable to existing evaporator fans with a traditional electric defrost mechanism. This control system overrides defrost of evaporator fans when
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
unnecessary, reducing annual energy consumption. The estimates for savings take into account savings from reduced defrosts as well as the reduction in heat gain from the defrost process.
3555. Independent Testing was performed by Intertek Testing Service on a Walk-in Freezer that was retrofitted with Smart Electric Defrost capability. A baseline of 28 electric defrosts per week were established as the baseline for a two week period without the Smart Electric Defrost capability. With Smart Electric Defrost capability an average skip rate of 43.64% was observed for the following two week period.
3556.3557.[3078.] Algorithms3558.3559.[3079.] Gross kWh Savings = kWh SavingsDefrost + kWh SavingsRH
3560.3561.[3080.] kWh SavingsDefrost = KWDefrost * 0.667 * 4 * 365 * 35%3562.3563.[3081.] kWh SavingsRH = kWh SavingsDefrost * 0.28 * 1.63564.3565.[3082.] Definition of Variables3566. kWh SavingsDefrost = Savings due to reduction of defrosts3567. kWh SavingsRH = Savings due to reduction in refrigeration load3568. KWDefrost = Nameplate Load of Electric Defrost3569. 0.667 = Average Length of Electric Defrost in hours3570. 4 = Average Number of Electric Defrosts per day3571. 365 = Number of Days in Year3572. 35% = Average Number of Defrosts that will be eliminated in year3573. 0.28 = Conversion from kW to tons (Refrigeration)3574. 1.6 = Efficiency of typical refrigeration system in kW/ton [1]3575.[3083.] 3576.[3084.] Sources
1. Select Energy Services, Inc. Cooler Control Measure Impact Spreadsheet User’s Manual. 2004.
3577. Novelty Cooler Shutoff
3578. This measure is applicable to existing reach-in novelty coolers which run continuously. The measure adds a control system feature to automatically shut off novelty coolers based on pre-set store operating hours. Based on programmed hours, the control mechanism shuts off the cooler at end of business, and begins operation on reduced cycles. Regular operation begins the following day an hour before start of business. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
3579. Several case studies have been performed that verify the accuracy of these savings. The algorithms below are based on field-tested approximations of energy savings realized
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system. [1]
3580. Algorithms3581.3582.[3085.] kWh Savings = (((AmpsNC * VoltsNC * (PhaseNC)1/2 )/1000) * 0.85) * ((0.45 * ((CH – 1) * 91)) + (0.5 * ((CH – 1) * 274)))3583.3584.[3086.] Definition of Variables
3585. AmpsNC = Nameplate Amps of Novelty Cooler3586. VoltsNC = Nameplate Volts of Novelty Cooler3587. PhaseNC = Phase of Novelty Cooler3588. 0.85 = Novelty Cooler power factor [2]3589. 0.45 = Duty cycle during winter month nights [3]3590. CH = Closed Store hours3591. 91 = Number of days in winter months3592. 0.5 = Duty cycle during non-winter month nights [3]3593. 274 = Number of days in non-winter months
3594. Sources
1. Several case studies related to NRM’s Cooltrol system can be found at: http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html.
2. Estimated by NRM based on their experience of monitoring the equipment at various sites.3. Duty Cycles are consistent with third-party study done by Select Energy for NSTAR “Cooler
Control Measure Impact Spreadsheet Users Manual,” p. 5, March 9, 2004.3595.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3596. Food Service Measures Protocols3597.[3087.] Energy efficient electric or natural gas cooking equipment of the following listed types utilized in commercial food service applications which have performance rated in accordance with the listed ASTM standards:
Electric and gas combination oven/steamer – ASTM F2861
Gas convection ovens – ASTM F1496
Gas conveyor ovens – ASTM F1817
Gas rack ovens – ASTM F2093
Electric and gas small vat fryers – ASTM F1361
Electric and gas large vat fryers – ASTM F2144
Electric and gas steamers – ASTM F1484
Electric and gas griddles – ASTM F1275
Hot food holding cabinets –CEE Tier II
Commercial dishwashers – ENERGY STARRefrigerators, Freezers – ENERGY STAR
Ice Machines – ARI Standard 810
3598. Electric and Gas Combination Oven/Steamer3599.[3088.] The measurement of energy savings for this measure is based on algorithms
with key variables provided by manufacturer data or prescribed herein.3600. 3601. Algorithms 3602. 3603. Energy Savings (kWh/yr or Therms/yr) = D*(Ep + Eic + Eis + Ecc + Ecs)3604. 3605. Peak Demand Savings (kW) = kWh Savings/(D*H)3606.3607.[3089.] Preheat Savings† : Ep = P*(PEb – PEq)3608.3609.[3090.] Convection Mode Idle Savings† : Eic = (Icb – Icq)*((H – (P*Pt)) – (Icb/PCcb – Icq/PCcq)*Lbs)*(1 – St)3610.3611.[3091.] Steam Mode Idle Savings† : Eis = (Isb – Isq)*((H – (P*Pt)) – (Isb/PCsb –
Isq/PCsq)*Lbs)*St
3612.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3613.[3092.] Convection Mode Cooking Savings: Ecc = Lbs*(1-St)*Heatc*(1/Effcb – 1/Effcq)/C
3614.3615.[3093.] Steam Mode Cooking Savings: Ecs = Lbs*St*Heats*(1/Effsb – 1/Effsq)/C3616.3617.[3094.] † – For gas equipment, convert these intermediate values to therms by dividing the result by 100,000 Btu/therm3618.3619.[3095.] Definition of Variables 3620. (See tables of values below for more information) 3621. C = Conversion Factor from Btu to kWh or Therms3622. D = Operating Days per Year3623. Effcb = Baseline Equipment Convection Mode Cooking Efficiency3624. Effcq = Qualifying Equipment Convection Mode Cooking Efficiency3625. Effsb = Baseline Equipment Steam Mode Cooking Efficiency3626. Effsq = Qualifying Equipment Steam Mode Cooking Efficiency3627. H = Daily Operating Hours3628. Heatc = Convection Mode Heat to Food3629. Heats = Steam Mode Heat to Food3630. Icb = Baseline Equipment Convection Mode Idle Energy Rate3631. Icq = Qualifying Equipment Convection Mode Idle Energy Rate3632. Isb = Baseline Equipment Steam Mode Idle Energy Rate3633. Isq = Qualifying Equipment Steam Mode Idle Energy Rate3634. Lbs = Total Daily Food Production3635. P = Number of Preheats per Day3636. PCcb = Baseline Equipment Convection Mode Production Capacity3637. PCcq = Qualifying Equipment Convection Mode Production Capacity3638. PCsb = Baseline Equipment Steam Mode Production Capacity3639. PCsq = Qualifying Equipment Steam Mode Production Capacity3640. PEb = Baseline Equipment Preheat Energy3641. PEq = Qualifying Equipment Preheat Energy3642. Pt = Preheat Duration3643. St = Percentage of Time in Steam Mode3644.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3645. Summary of Inputs
3646.
<15 Pans 15-28 Pans >28 Pans <15 Pans 15-28 Pans >28 PansD - Operating Days per Year Table 3 Table 3 Table 3 Table 3 Table 3 Table 3P - Number of Preheats per Day 1 1 1 1 1 1PEb & PEq - Preheat Energy (kWh) 3.00 3.75 5.63 1.50 2.00 3.00Icb & Icq - Convection Mode Idle Energy Rate (kW) 3.00 3.75 5.25 Application Application ApplicationH - Operating Hours per Day Table 3 Table 3 Table 3 Table 3 Table 3 Table 3Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25 0.25 0.25PCcb & PCcq - Convection Mode Prod. Capacity (lbs/hr) 80 100 275 100 125 325Lbs - Total Daily Food Production (lbs) 200 250 400 200 250 400St - Percentage of Time in Steam Mode 50% 50% 50% 50% 50% 50%Isb & Isq - Steam Mode Idle Energy Rate (kW) 10.0 12.5 18.0 Application Application ApplicationPCsb & PCsq - Steam Mode Prod. Capacity (lbs/hr) 100 150 350 120 200 400Heatc - Convection Heat to Food (Btu/lb) 250 250 250 250 250 250Effcb & Effcq - Convection Mode Cooking Efficiency 65% 65% 65% Application Application ApplicationC - Btu/kWh 3,412 3,412 3,412 3,412 3,412 3,412Heats - Steam Heat to Food (Btu/lb) 105 105 105 105 105 105Effsb & Effsq - Steam Mode Cooking Efficiency 40% 40% 40% Application Application Application
Baseline QualifyingTable 1: Electric Combination Oven/Steamers
Variable
3647. 3648.
<15 Pans 15-28 Pans >28 Pans <15 Pans 15-28 Pans >28 PansD - Operating Days per Year Table 3 Table 3 Table 3 Table 3 Table 3 Table 3P - Number of Preheats per Day 1 1 1 1 1 1PEb & PEq - Preheat Energy (Btu) 18,000 22,000 32,000 13,000 16,000 24,000Icb & Icq - Convection Mode Idle Energy Rate (Btu/h) 15,000 20,000 30,000 Application Application ApplicationH - Operating Hours per Day Table 3 Table 3 Table 3 Table 3 Table 3 Table 3Pt - Preheat Duration (h) 0.25 0.25 0.25 0.25 0.25 0.25PCcb & PCcq - Convection Mode Prod. Capacity (lbs/h) 80 100 275 100 125 325Lbs - Total Daily Food Production (lbs) 200 250 400 200 250 400St - Percentage of Time in Steam Mode 50% 50% 50% 50% 50% 50%Isb & Isq - Steam Mode Idle Energy Rate (kW) 45,000 60,000 80,000 Application Application ApplicationPCsb & PCsq - Steam Mode Prod. Capacity (lbs/h) 100 150 350 120 200 400Heatc - Convection Heat to Food (Btu/lb) 250 250 250 250 250 250Effcb & Effcq - Convection Mode Cooking Efficiency 35% 35% 35% Application Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000 100,000 100,000Heats - Steam Heat to Food (Btu/lb) 105 105 105 105 105 105Effsb & Effsq - Steam Mode Cooking Efficiency 20% 20% 20% Application Application Application
Baseline QualifyingTable 2: Gas Combination Oven/Steamers
Variable
3649. 3650. 3651.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3652.
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 3: Operating Days/Hours by Building Type
3653.3654.[3096.] Sources
3655. Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission. Values for Tables 1 and 2 from PG&E Work Paper PGECOFST100, “Commercial Combination Ovens/Steam –Electric and Gas,” Revision 6, 2016.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3656. Electric and Gas Convection Ovens, Gas Conveyor and Rack Ovens, Steamers, Fryers, and Griddles
3657.[3097.] The measurement of energy savings for these measures are based on algorithms with key variables provided by manufacturer data or prescribed herein.
3658. 3659. Algorithms 3660. 3661. Energy Savings (kWh/yr or Therms/yr) = D * (Ep + Ei + Ec)3662. 3663. Peak Demand Savings (kW) = kWh Savings / (D * H)3664.3665.[3098.] Preheat Savings† : Ep = P * (PEb – PEq)3666.3667.[3099.] Idle Savings† : Ei = (Ib – Iq) * ((H – (P*Pt)) – (Ib/PCb – Iq/PCq) * Lbs)3668.3669.[3100.] Cooking Savings: Ec = Lbs * Heat * (1/Effb – 1/Effq) / C3670. 3671. † – For gas equipment, convert these intermediate values to therms by dividing the result by 100,000 Btu/therm3672. 3673. Definition of Variables 3674. (See tables of values below for more information) 3675. D = Operating Days per Year3676. P = Number of Preheats per Day3677. PEb = Baseline Equipment Preheat Energy3678. PEq = Qualifying Equipment Preheat Energy3679. I b = Baseline Equipment Idle Energy Rate3680. I q = Qualifying Equipment Idle Energy Rate3681. H = Daily Operating Hours3682. P t = Preheat Duration3683. PCb = Baseline Equipment Production Capacity3684. PCq = Qualifying Equipment Production Capacity3685. Lbs = Total Daily Food Production3686. Heat = Heat to Food3687. Effb = Baseline Equipment Convection Mode Cooking Efficiency3688. Effq = Qualifying Equipment Convection Mode Cooking Efficiency3689. C = Conversion Factor from Btu to kWh or Therms3690.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3691. Summary of Inputs
3692.
Full Size Half Size Full Size Half SizeD - Operating Days per Year Table 11 Table 11 Table 11 Table 11P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (kWh) 1.50 1.00 1.00 0.90Ib & Iq - Idle Energy Rate (kW) 2.00 1.50 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 70 45 82 53Lbs - Total Daily Food Production (lbs) 100 100 100 100Heat - Heat to Food (Btu/lb) 250 250 250 250Effb & Effq - Heavy Load Cooking Efficiency 65% 65% Application ApplicationC - Btu/kWh 3,412 3,412 3,412 3,412
Table 1: Electric Convection Ovens
VariableBaseline Qualifying
3693. Source: PGECOFST101 R6, “Commercial Convection Oven – Electric and Gas,” 2016.
3694.
3695.
Full Size Half Size Full Size Half SizeD - Operating Days per Year Table 11 Table 11 Table 11 Table 11P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (Btu) 19,000 13,000 11,000 7,500Ib & Iq - Idle Energy Rate (Btu/h) 18,000 12,000 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 70 45 83 55Lbs - Total Daily Food Production (lbs) 100 100 100 100Heat - Heat to Food (Btu/lb) 250 250 250 250Effb & Effq - Heavy Load Cooking Efficiency 30% 30% Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000
Table 2: Gas Convection Ovens
VariableBaseline Qualifying
3696. Source: PGECOFST101 R6, “Commercial Convection Oven – Electric and Gas,” 2016.
3697.
3698.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 35,000 18,000Ib & Iq - Idle Energy Rate (Btu/hr) 70,000 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 114 167Lbs - Total Daily Food Production (lbs) 190 190Heat - Heat to Food (Btu/lb) 250 250Effb & Effq - Heavy Load Cooking Efficiency 20% ApplicationC - Btu/Therm 100,000 100,000
Table 3: Gas Conveyor Ovens
3699. Source: PGECOFST117 R5, “Commercial Conveyor Oven– Gas,” 2014.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3700.
3701.
Double Rack Single Rack Double Rack Single RackD - Operating Days per Year Table 11 Table 11 Table 5 Table 5P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (Btu) 100,000 50,000 85,000 44,000Ib & Iq - Idle Energy Rate (Btu/h) 65,000 43,000 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 5 Table 5Pt - Preheat Duration (hrs) 0.33 0.33 0.33 0.33PCb & PCq - Production Capacity (lbs/hr) 250 130 280 140Lbs - Total Daily Food Production (lbs) 1200 600 1200 600Heat - Heat to Food (Btu/lb) 235 235 235 235Effb & Effq - Heavy Load Cooking Efficiency 30% 30% Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000
Table 4: Gas Rack Ovens
VariableBaseline Qualifying
3702. Source: PGECOFST109, “Commercial Rack Oven– Gas,” 2016.3703.
3704.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 1.50 1.50Ib & Iq - Idle Energy Rate (kW) 0.167 x No. of Pans ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 11.7 x No. of Pans 14.7 x No. of PansLbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 105 105Effb & Effq - Heavy Load Cooking Efficiency 26% ApplicationC - Btu/kWh 3,412 3,412
Table 5: Electric Steamers
3705. Source: PGECOFST104 R6, “Commercial Steam Cooker – Electric and Gas,” 2016.3706.
3707.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 20,000 9,000Ib & Iq - Idle Energy Rate (Btu/h) 2,500 x No. of Pans ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 23.3 x No. of Pans 20.8 x No. of PansLbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 105 105Effb & Effq - Heavy Load Cooking Efficiency 15% ApplicationC - Btu/Therm 100,000 100,000
Table 6: Gas Steamers
3708. Source: PGECOFST104 R6, “Commercial Steam Cooker – Electric and Gas,” 2016.3709. 3710.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3711.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 2.40 1.90Ib & Iq - Idle Energy Rate (kW) 1.2 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 71 71Lbs - Total Daily Food Production (lbs) 150 150Heat - Heat to Food (Btu/lb) 570 570Effb & Effq - Heavy Load Cooking Efficiency 75% ApplicationC - Btu/kWh 3,412 3,412
Table 7: Electric Fryers
3712. Source: PGECOFST102 R6, “Commercial Fryer – Electric and Gas,” 2016.3713.
3714.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 18,500 16,000Ib & Iq - Idle Energy Rate (Btu/h) 17,000 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 75 75Lbs - Total Daily Food Production (lbs) 150 150Heat - Heat to Food (Btu/lb) 570 570Effb & Effq - Heavy Load Cooking Efficiency 35% ApplicationC - Btu/Therm 100,000 100,000
Table 8: Gas Fryers
3715. Source: PGECOFST102 R6, “Commercial Fryer – Electric and Gas,” 2016.3716.
3717.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 1.3 x Griddle Width (ft) 0.7 x Griddle Width (ft)Ib & Iq - Idle Energy Rate (kW) 0.8 x Griddle Width (ft) ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 11.7 x Griddle Width (ft) 13.3 x Griddle Width (ft)Lbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 475 475Effb & Effq - Heavy Load Cooking Efficiency 60% ApplicationC - Btu/kWh 3,412 3,412
Table 9: Electric Griddles
3718. Source: PGECOFST103 R7, “Commercial Griddle – Electric and Gas,” 2016.3719.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3720.
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 7,000 x Griddle Width (ft) 5,000 x Griddle Width (ft)Ib & Iq - Idle Energy Rate (Btu/h) 7,000 x Griddle Width (ft) ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 8.3 x Griddle Width (ft) 15 x Griddle Width (ft)Lbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 475 475Effb & Effq - Heavy Load Cooking Efficiency 30% ApplicationC - Btu/Therm 100,000 100,000
Table 10: Gas Griddles
3721. Source: PGECOFST103 R7, “Commercial Griddle – Electric and Gas,” 2016.3722.
3723.
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 11: Operating Days/Hours by Building Type
3724. 3725. Sources
3726. Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission. Baseline efficiency and idle load rate values developed based on Fishnick Food Service Technology Center LEED suggested baselines and prescriptive measures, 2011.
3727.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3728. Insulated Food Holding Cabinets3729.[3101.] The measurement of energy savings for this measure is based on algorithms
with key variables provided by manufacturer data or prescribed herein.3730. 3731. Algorithms 3732. 3733. Energy Savings (kWh/yr) = D * H * (Ib – Iq)3734. 3735. Peak Demand Savings (kW) = Ib – Iq
3736.3737.[3102.] Definition of Variables 3738. (See tables of values below for more information) 3739. D = Operating Days per Year3740. H = Daily Operating Hours3741. I b = Baseline Equipment Idle Energy Rate3742. I q = Qualifying Equipment Idle Energy Rate3743.
3744. Summary of Inputs
3745.
Full Size 3/4 Size 1/2 Size Full Size 3/4 Size 1/2 SizeD - Operating Days per Year Table 2 Table 2 Table 2 Table 2 Table 2 Table 2Ib & Iq - Idle Energy Rate (kW) 1.00 0.69 0.38 Application Application ApplicationH - Operating Hours per Day Table 2 Table 2 Table 2 Table 2 Table 2 Table 2
Table 1: Insulated Food Holding Cabinets
VariableBaseline Qualifying
3746. Source: PGECOFST105 R5, “Insulated Holding Cabinet – Electric,” 2016.3747.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3748.
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 2: Operating Days/Hours by Building Type
3749.
3750. Sources
3751. Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
3752. Commercial Dishwashers3753. This measure is applicable to replacement of existing dishwashers with energy
efficient under counter, door type, single-rack and multi-rack conveyor machines testing in accordance with NSF/ANSI 3-2007, ASTM F1696, and ASTM F1920 standards. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
3754.3755.[3103.] Algorithms 3756. 3757. Energy Savings (kWh/yr or Therms/yr) = EBuild + EBoost + EIdle
3758. 3759. Peak Demand Savings (kW) = kWh Savings/87603760.3761.[3104.] Note: Depending on water heating system configuration (e.g. gas building
water heater with electric booster water heater), annual energy savings may be reported in both therms and kWh.
3762.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3763.[3105.] Definition of Variables3764. E Build = Annual Building Water Heater Energy Savings, in kWh or Therms (from tables below)3765. E Boost = Annual Booster Water Heater Energy Savings, in kWh or Therms (from tables below)3766. E Idle = Annual Dishwasher Idle Energy Savings, in kWh (from tables below)3767. 8760 = Hours per Year3768. 3769. Summary of Inputs 3770.
3771.
Dishwasher Type
Electric Building Water Heater Savings (kWh)
Gas Building Water Heater
Savings (Therms)
Electric Booster Water Heater Savings (kWh)
Gas Booster Water Heater
Savings (Therms)
Idle Energy Savings (kWh)
Under Counter
1,213 56.2 0 0.0 0
Door Type 12,135 562.1 0 0.0 0Single Tank Conveyor
11,384 527.3 0 0.0 0
Multi Tank Conveyor
17,465 809.0 0 0.0 0
Table 1: Low Temperature Dishwasher Savings
3772.
3773.
Dishwasher Type
Electric Building Water Heater Savings (kWh)
Gas Building Water Heater
Savings (Therms)
Electric Booster Water Heater Savings (kWh)
Gas Booster Water Heater
Savings (Therms)
Idle Energy Savings (kWh)
Under Counter
4,754 220.2 2,717 110.1 0
Door Type 8,875 411.1 5,071 205.5 198Single Tank Conveyor
11,126 515.3 6,358 257.7 1,752
Multi Tank Conveyor
21,734 1,006.7 12,419 503.3 0
Table 2: High Temperature Dishwasher Savings
3774. 3775. Sources
3776. Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission and from the Savings Calculator for ENERGY STAR Qualified Commercial Kitchen Equipment.
3777. Commercial Refrigerators and Freezers3778. This measure is applicable to replacement of existing commercial grade refrigerators
and freezers with energy efficient glass and solid door units complying with ANSI/ASHRAE Standard 72-2005, Method of Testing Commercial Refrigerators
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
and Freezers. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
3779.3780.[3106.] Algorithms3781.3782.[3107.] Energy Savings (kWh/yr) = D * (Eb – Eq)3783. 3784. Peak Demand Savings (kW) = kWh Savings/ (D * H)3785. 3786. Definition of Variables 3787. D = Operating Days per Year (assume 365)3788. H = Daily Operating Hours (assume 24)3789. E b = Daily kWh Consumption of Baseline Equipment (from Table 1 below)3790. E q = Daily kWh Consumption of Qualifying Equipment (from Application)3791.
3792. Summary of Inputs
3793.
Proposed Equipment Type kWh Consumption (V = Unit Volume in ft 3)Glass Door Freezer 0.75V + 4.1Glass Door Refrigerator 0.12V + 3.34Solid Door Freezer 0.4V + 1.38Solid Door Refrigerator 0.1V + 2.04
Table 1: Baseline Equipment Daily kWh Consumption
3794. 3795. Sources
3796. Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
3797. Commercial Ice Machines[3108.] This measure is applicable to replacement of existing ice makers with energy
efficient, air-cooled ice machines tested in accordance with ARI Standard 810. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
3798.[3109.] 3799.[3110.] Algorithms 3800.[3111.] [3112.] Annual Energy Savings (kWh) = D * DC * (IHR/100) * (Eb – Eq)3801.[3113.] 3802.[3114.] Peak Demand Savings (kW) = kWh Savings / (D * 24 * DC)3803.[3115.] 3804.[3116.] Definition of Variables 3805.[3117.] D = Operating Days per Year (assume 365)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3806.[3118.] DC = Duty Cycle, defined as Ice Harvest Rate/Actual Daily Ice Production (assume 75%)
3807.[3119.] IHR = Proposed Equipment Ice Harvest Rate in lbs/day (from Application)3808.[3120.] Eb = kWh Consumption of Baseline Equipment in kWh/100 lbs (from
Table 1 below)3809.[3121.] Eq = kWh Consumption of Qualifying Equipment in kWh/100 lbs (from
Application)3810.[3122.] 24 = Hours per Day3811.[3123.]
3812.[3124.] Summary of Inputs
3813.
Ice Harvest Rate (lbs/day) Baseline Energy Consumption (kWh/100 lbs)0-100 18.0
101-200 16.0201-300 11.0301-400 8.5401-500 7.6501-1000 6.9
1001-1500 6.41501 6.1
Table 1: Baseline Energy Consumption
3814.[3125.] [3126.] Sources :
3815.[3127.] Savings algorithm, baseline values, assumed values and lifetimes developed from information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
3816.[3128.]
[3129.] Commercial Dishwashers
[3130.] This measure is applicable to replacement of existing dishwashers with energy efficient under counter, door type, single-rack and multi-rack conveyor machines testing in accordance with NSF/ANSI 3-2007, ASTM F1696, and ASTM F1920 standards. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
[3131.] [3132.] Algorithms [3133.] [3134.] Annual Energy Savings (kWh or Therms) = EBuild + EBoost + EIdle
[3135.] [3136.] Demand Savings (kW) = kWh Savings/8760[3137.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3138.] Note : Depending on water heating system configuration (e.g. gas building water heater with electric booster water heater), annual energy savings may be reported in both therms and kWh.
[3139.] [3140.] Definition of Variables [3141.] [3142.] EBuild = Annual Building Water Heater Energy Savings, in kWh or Therms (from
tables below)[3143.] EBoost = Annual Booster Water Heater Energy Savings, in kWh or Therms (from
tables below)[3144.] EIdle = Annual Dishwasher Idle Energy Savings, in kWh (from tables below)[3145.] 8760 = Hours per Year[3146.]
[3147.]
Dishwasher Type
Electric Building Water Heater Savings (kWh)
Gas Building Water Heater
Savings (Therms)
Electric Booster Water Heater Savings (kWh)
Gas Booster Water Heater
Savings (Therms)
Idle Energy Savings (kWh)
Under Counter
1,213 56.2 0 0.0 0
Door Type 12,135 562.1 0 0.0 0Single Tank Conveyor
11,384 527.3 0 0.0 0
Multi Tank Conveyor
17,465 809.0 0 0.0 0
Table 1: Low Temperature Dishwasher Savings
[3148.]
[3149.]
Dishwasher Type
Electric Building Water Heater Savings (kWh)
Gas Building Water Heater
Savings (Therms)
Electric Booster Water Heater Savings (kWh)
Gas Booster Water Heater
Savings (Therms)
Idle Energy Savings (kWh)
Under Counter
4,754 220.2 2,717 110.1 0
Door Type 8,875 411.1 5,071 205.5 198Single Tank Conveyor
11,126 515.3 6,358 257.7 1,752
Multi Tank Conveyor
21,734 1,006.7 12,419 503.3 0
Table 2: High Temperature Dishwasher Savings
[3150.] [3151.] Sources:[3152.] Savings algorithm, baseline values, assumed values and lifetimes developed from
information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission and from the Savings Calculator for ENERGY STAR Qualified Commercial Kitchen Equipment.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3153.] C&I Construction Gas Protocols[3154.] For measures installed as part of the Direct Install program, different baselines will
be utilized to estimate savings as defined further in the Direct Install section of these Protocols.
[3155.] [3156.] The following The following measures are outlined in this section: Gas Chillers, Gas
Fired Dessicants, Water Heating Equipment, Space Heating Equipment, and Fuel Use Economizers.
3817. fuel conversions will be used to calculate energy savings for propane and oil equipment for all eligible C&I programs including C&I Construction, Direct Install, and Pay for Performance.
[3157.] [3158.] 1 therm of gas = 1.087 gal of propane = 0.721 gal of #2 oil[3159.] [3160.] 1 therm = 100,000 Btu[3161.] 1 gal of propane = 92,000 Btu[3162.] 1 gal of #2 oil = 138,700 Btu[3163.]
[3164.] Gas Chillers
[3165.] The measurement of energy savings for C&I gas fired chillers and chiller heaters is based on algorithms with key variables captured on the application form or from manufacturer’s(i.e., Equivalent Full Load Hours, Vacuum Boiler Efficiency, Input Rating, Coincidence Factor) provided by manufacturer data sheets and collaborative/utility studies.or measured through existing end-use metering
[3166.] For certain fixed components, studies and surveys developed by the utilities in the State or based on a review of manufacturer’s data, other utilities, regulatory commissions or consultants’ reports will be used to update the values for future filings. a sample of facilities.
3818.3819.[3167.] Algorithms 3820.[3168.] [3169.] Winter Gas Savings (MMBtu/yr) = (VBEq – BEb)/VBEq *X IR *X EFLH 3821.[3170.] [3171.] Electric Demand Savings = Tons X (kW/Tonb – kW/Tongc) X CF [3172.] [3173.] Electric Energy Savings (kWh/yr) = Tons *X (kW/Tonb – kW/Tongc) *X EFLH 3822.[3174.] [3175.] Summer Gas Usage (MMBtu/yr) = MMBtu Output Capacity / COP *X EFLH 3823.[3176.] [3177.] Net Energy Savings (kWh/yr) == Electric Energy Savings + Winter Gas Savings –
Summer Gas Usage
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3824.[3178.] 3825. Peak Demand Savings (kW) = Tons * (kW/Tonb – kW/Tongc) * CF 3826.3827.[3179.] Definition of Terms 3828.[3180.] VBEq = Vacuum Boiler Efficiency3829.[3181.] BEb = Efficiency of the baseline gas boiler[3182.] IR = Input Rating = MMBtuTherms/hour [3183.] Tons = The rated capacity of the chiller (in tons) at site design conditions accepted
by the program.3830.[3184.] kW/Tonb = The baseline efficiency for electric chillers, as shown in the Gas Chiller Verification Summary table below.3831.[3185.] kW/Tongc = Parasitic electrical requirement for gas chiller.3832.[3186.] COP = Efficiency of the gas chiller3833.[3187.] MMBtu Output Capacity = Cooling Capacity of gas chiller in MMBtu.[3188.] CF = Coincidence Factor. This value represents the percentage of the total load that is on during electric system peak.[3189.] EFLH = Equivalent Full Load Hours. This represents a measure of chiller use by
season.3834.[3190.] 3835.[3191.] Summary of Inputs
3836. Gas Chillers[3192.]
3837.[3193.] Component
3838.[3194.] Type
3839.[3195.] Value 3840.[3196.] Source
3841.[3197.] VBEq
3842.[3198.] Variable
3843.[3199.] 3844.[3200.] Rebate
Application or
Manufacturer Data
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3837.[3193.] Component
3838.[3194.] Type
3839.[3195.] Value 3840.[3196.] Source
3845.[3201.] BEb
3846.[3202.] Fixed
3847.[3203.] 75%80% Et
3848.[3204.] ASHRAE
90.1-2013 Table 6.8.1
– 63849.[3205.]
3850.[3206.] Assumes a
baseline hot water boiler with rated input >300 MBh and ≤
2,500 MBh.
3851.[3207.] IR 3852.[3208.] Variable
3853.[3209.] 3854.[3210.] Rebate
Application or
Manufacturer Data
3855.[3211.] Tons
3856.[3212.] Variable
3857.[3213.] 3858.[3214.] Rebate
Application3859.[3215.] M
MBtu 3860.[3216.] V
ariable3861.[3217.] 3862.[3218.] R
ebate Application
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3837.[3193.] Component
3838.[3194.] Type
3839.[3195.] Value 3840.[3196.] Source
3863.[3219.] kW/Tonb
3864.[3220.] Fixed
3865.[3221.] <100 tones
3866.[3222.] 1.25 kW/ton
3867.[3223.] 3868.[3224.] 100 to
< 150 tons3869.[3225.] 0.703
kW/ton3870.[3226.]
3871.[3227.] 150 to <300 tons:
3872.[3228.] 0.634 kW/Ton
3873.[3229.] 3874.[3230.] 300
tons or more:3875.[3231.] 0.577
kW/ton3876.[3232.]
3877.[3233.] Collaborative agreement
and C/I baseline
study3878.[3234.]
3879.[3235.] Assumes new
electric chiller
baseline using air
cooled unit for chillers less than 100 tons;
water cooled for
chillers greater than
100 tons3880.[3236.] kW/
Tongc
3881.[3237.] Variable
3882.[3238.] 3883.[3239.] Manufacturer
Data3884.[3240.] C
OP3885.[3241.] V
ariable3886.[3242.] 3887.[3243.] M
anufacturer Data
3888.[3244.] CF 3889.[3245.] Fixed
3890.[3246.] 67% 3891.[3247.] Engineering estimate
3892.[3248.] EFLH
[3249.] VariableFixed
[3250.] See table below1,360
[3251.] 1 JCP&L
Measured data36
3893.[3252.] 3894.[3253.]
36 Results reflect metered use from 1995 – 1999.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3254.] Variable data will be captured on the application form or from manufacturer’s data sheets and collaborative/utility studies.
[3255.] [3256.] For certain fixed components, studies and surveys developed by the utilities in
the State or based on a reviewEFLH Table
3895. Facility Type3896. Coo
ling EFLH
3897. Assembly 3898. 6693899. Auto repair 3900. 4263901. Dormitory 3902. 800
3903. Hospital 3904. 1424
3905. Light industrial 3906. 5493907. Lodging –
Hotel3908. 291
83909. Lodging –
Motel3910. 123
33911. Office – large 3912. 7203913. Office – small 3914. 955
3915. Other 3916. 7363917. Religious
worship 3918. 279
3919. Restaurant – fast food 3920. 645
3921. Restaurant – full service 3922. 574
3923. Retail – big box
3924. 1279
3925. Retail – grocery
3926. 1279
3927. Retail – large 3928. 882
3929. Retail – large 3930. 1068
3931. School – community college 3932. 846
3933. School – postsecondary
3934. 1208
3935. School – primary 3936. 394
3937. School – secondary 3938. 466
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3895. Facility Type3896. Coo
ling EFLH
3939. Warehouse 3940. 4003941. 3942. Sources 1. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Appendix G –
Equivalent Full-Load Hours (EFLH), For Heating and Cooling, pp. 443–444. Derived from DOE2.2 simulations reflecting a range of building types and climate zones
3943. of manufacturer’s data, other utilities, regulatory commissions or consultants’ reports will be used to update the values for future filings.
[3257.] Gas Fired Desiccants
[3258.] Gas Fired Dessicants
3944.[3259.] Gas-fired desiccant systems employ a desiccant wheel (a rotating disk filled with a dry desiccant such as silica gel, titanium gel, or dry lithium chloride) which adsorbs outside air moisture, reducing the air’s latent heat content. This air is then conditioned by the building’s cooling system, before being delivered to the occupied space. By reducing the relative humidity of the air, the operating temperature of the building can be increased, as comfort levels are maintained at higher temperatures when air moisture content is decreased. Electric savings are realized from a reduction in the required cooling load as a result of decreased humidity.
3945.[3260.] In order to maintain the usefulness of the desiccant (to keep it dry) hot air must be passed through the desiccant that has been used to remove moisture from the outside air. To supply this hot air, a gas-fired heater is employed to heat “regeneration” air, which picks up moisture from the saturated desiccant and exhausts it to the outside. As a result, in addition to electric benefits, these systems will also incur a natural gas penalty.
3946.[3261.] Electric savings and natural gas consumption will vary significantly from system to system depending on regional temperature and humidity, facility type, occupancy, site processes, desiccant system design parameters, ventilation requirements and cooling load and system specifications. Due to the multitude of site and equipment specific factors, along with the relative infrequency of these systems, gas-fired desiccant systems will be treated on a case-by-case basis.
3947.[3262.] Gas Booster Water Heaters3948.[3263.] C&I gas booster water heaters are substitutes for electric water heaters. The
measurement of energy savings is based on engineering algorithms with key variables (i.e., Input Rating Coincidence Factor, Equivalent Full Load Hours) provided by manufacturer data or measured through existing end-use metering of a sample of facilities.
3949.[3264.] 3950.[3265.] Algorithms [3266.] Demand Savings (kW) = IR X EFF/3,412 X CF
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3267.] [3268.] Energy Savings (kWh/yr) = IR *X EFF/3,412 *X EFLH 3951.[3269.] 3952. Peak Demand Savings (kW) = IR * EFF/3,412 * CF3953.[3270.] Gas Usage Increase (MMBtu/yr) = IR *X EFLH3954.[3271.] 3955.[3272.] Net Energy Savings (kWh/yr) = Electric Energy Savings – Gas Usage
Increase/3,412[3273.] (Calculated in MMBtu)[3274.] 3956.[3275.] Definition of Variables [3276.] IR = Input Rating in MMBtu/hrBtuh3957.[3277.] EFF = Efficiency3958.[3278.] CF = Coincidence Factor 3959.[3279.] EFLH = Equivalent Full Load Hours
3960.[3280.] The 3412 used in the denominator is used to convert Btus to kWh.
3961.[3281.] 3962.[3282.] Summary of Inputs
3963. Gas Booster Water Heaters[3283.]
3964.[3284.] Component
3965.[3285.] Type
3966.[3286.] Value
3967.[3287.] Source
3968.[3288.] IR 3969.[3289.] Variable
3970.[3290.] 3971.[3291.] Application Form or
Manufacturer Data
3972.[3292.] CF 3973.[3293.] Fixed
3974.[3294.] 30%
3975.[3295.] Summit Blue NJ Market Assessment
3976.[3296.] EFLH
3977.[3297.] Fixed
3978.[3298.] 1,000
3979.[3299.] PSE&G
3980.[3300.] EF 3981.[3301.] Variable
3982.[3302.] 3983.[3303.] Application Form or
Manufacturer Data
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3984.[3304.] Tank Style (Storage)
[3305.] Water Heaters
[3306.] This prescriptive measure is intended for storagetargets solely the use of smaller-scale domestic water heaters installed(50 gallons or less per unit) in all commercial facilities. Larger gas water heaters are treated under the custom measure path. The measurement of energy savings for C&I gas water heaters is based on algorithms are based on installed equipment specifications and data from the Commercial Building Energy Consumption Survey (CBECS).
3985. Baseline efficiencies are set by current and previous equipment performance standards. In New Jersey ASHRAE 90.1 defines the commercial energy code requirements. For new buildings, ASHRAE 90.1-2013 standards apply, and for existing buildings, ASHRAE 90.1-2007 standards are assumed.
3986. Note, that for storage tank water heaters with a rated input capacity greater than 75 kBtu/hr, equipment standards are defined in terms of thermal efficiency. Equipment below this input capacity is rated in terms of energy key variables (i.e., energy factor. Energy factor is determined on a 24 hour basis and includes standby or storage loss effects, while thermal efficiency does not. Therefore, if the equipment is large enough to be rated in terms of thermal efficiency, a percent standby loss factor must be included in the calculation as shown in the algorithms) provided by manufacturer data.
3987.[3307.] 3988.[3308.] Algorithms 3989.[3309.] [3310.] FuelGas Savings (MMBtu/yr) = ((1 – (EFFb / = ((EFFq) + %SL37) * – EFFb)/EFFq) X Energy Use Density * X (Area / 1000 kBtu/MMBtu) 3990.[3311.] 3991.[3312.] where,3992. 3993. %SL = (SLb – SLq) / kBtu/hrq
3994. 3995. 3996. Definition of Variables [3313.] EFFq = Efficiency of the qualifying storageenergy efficient water heater.3997.[3314.] EFFbc = Efficiency of the baseline water heater, commercial grade. 3998. UEFb EFFb = Efficiency of the baseline water heater, residential grade.. 3999.[3315.] Energy Use Density = Annual baseline water heater energy use per square foot of commercial space served (MMBtu/sq.ft./yr)4000. Area = Square feet of building area served by the water heater4001.[3316.] %SL = Percent standby loss savings of qualifying storage water heater over
baseline4002. SLb or q = Standby losses in kBtu/hr of the baseline and qualifying storage water heater respectively. The baseline standby losses is calculated assuming the baseline storage water
37 Standby losses only apply if the storage water heater is rated for more than 75 kBtu/hr
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
heater has the same input capacity rating as the qualifying unit’s input capacity using ASHRAE equipment performance standards. The qualifying unit’s standby losses are available on the AHRI certificate provided with the application.4003. kBtu/hrq = Rated input capacity of the qualifying storage water heater4004. 4005. Summary of Inputs 4006.
4007. Water Heater AssumptionsHeaters4008.[3317.]
[3318.] Component
4009.[3319.] Typ
e
4010.[3320.] Value 4011.[3321.] Source
4013.[3323.] EFFq
4014.[3324.] Vari
able
4015.[3325.] 4016.[3326.] Application
4018.[3328.] EFFb
[3329.] Vari
ableFixed
[3330.] See Table Below <50 gal or <75,000 BtuH: EF
[3331.] >50 gal or >75,000 BtuH: TE
[3332.] EF = Energy Factor[3333.] TE = Thermal
Efficiency
[3334.] 1, 2From ASHRAE 90.1
2007
4019.[3335.] U EFb
4020.Vari
able
4021. See baseline values in residential storage water
heater measure
4022. 1, 2
4023. Energy Use Density
4024.[3336.] Vari
able
4025.[3337.] See Table Below [3338.] 3 1
[3340.] AreaFluid
Capacity
4027.[3341.] Vari
ab
4028.[3342.] 4029.[3343.] Application
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3318.] Component
4009.[3319.] Typ
e
4010.[3320.] Value 4011.[3321.] Source
le
4031.[3345.] kBtu/hrq
4032.Vari
able
4033. 4034. Application
4035. SLb 4036.Vari
able
4037. See Table Below 4038. 1 & Application
4039. SLq 4040.Vari
able
4041. 4042. Application
4043.[3346.] Efficiency of Baseline Water Heaters – Existing Buildings
4044.[3347.] ASHRAE 90.1-2007 and 2013a
4045.[3348.] Equipm
ent Typ
e
4046.[3349.] Size
Category (Input
)
[3350.] Existing Building
Baseline Efficiency (ASHRAE 90.1-
2007)Subcategory or Rating Condition
[3351.] New Building Baseline Efficiency
(ASHRAE 90.1-2013)Performance
Requireda
4047.[3352.] Gas
Storage Water
Heaters
[3353.] ≤ 75 kBtu/hr,000
BtuH
[3354.] EF = 0.62 – 0.0019 × V≥20 gal
[3355.] EF = 0.6762 – 0.0005 × V0019V EF
4048.[3356.] Gas
Stor
[3357.] > 75 kBt
4049.[3358.] TE = 0.804050. SL = (kBtu/hrq /
0.8 + 110 × √V) /
4051.[3359.] TE = 0.804052. SL = (kBtu/hrq /
0.799 + 16.6 ×% Et
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
age Water
Heaters
u/hr,000
BtuH
1000<4,000 (BtuH)/gal
(Q/800 + 110 √V) / 1000
SL, BtuH
[3360.] Gas Instantaneous Water Heaters
[3361.] >50,000 BtuH and<200,000
BtuH
[3362.] ≥4,000 (
BtuH)/gal
and <2 gal
[3363.] 0.62 – 0.0019V EF
[3364.]
[3365.] Gas Instantaneous Water Heaters
[3366.] ≥200,000 BtuHb
[3367.] ≥4,000 (
BtuH)/gal
and <10 gal
[3368.] 80% Et
[3369.]
[3370.] Gas Instantaneous Water Heaters
[3371.] ≥200,000 BtuH
[3372.] ≥4,000 (
BtuH)/gal
and ≥10 gal
[3373.] 80% Et (Q/800 + 110 √V)SL, BtuH
[3374.]
4053.[3375.] [3376.] a – EF is energy- Energy factor, TE is (EF) and thermal efficiency (Et) are minimum
requirements, while standby loss (SL) is maximum BtuH based on a 70°F temperature difference between stored water and ambient requirements. In the EF equation, V is the rated volume in gallons. In the SL equation, V is the rated volume of the installed storage water heater,in gallons and kBtu/hrqQ is the ratednameplate input of the proposed storagerate in BtuH.
[3377.] [3378.] b - Instantaneous water heaterheaters with input rates below 200,000 BtuH must comply
with these requirements if the water heater is designed to heat water to temperatures of 180°F or higher.
4054.[3379.] 4055.[3380.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4056.[3381.] Energy Use Density Look-up Table4057. Water Heaters – New Construction
[3382.] ASHRAE 90.1-2013 (most current requirement as of February 2016)
[3383.] BuildingEqui
pment Type
[3384.] Energy Use Density (kBtu/SF/yr
)Size Category (Input)
4058.[3385.]
[3386.] EducationGas
Storage Water
Heaters
[3387.] 7.00.67 –
0.0005V EF
4059.[3388.]
[3389.] Food sales Gas
Storage Water
Heaters
[3390.] 4.4<4,000
(BtuH)/gal
4060.[3391.]
4061.[3392.] Food
service 4062. 39.2
4063.
4064. Health care 4065. 23.7
4066.
4067. Inpatient 4068. 34.3
4069.
4070. Outpatient 4071. 3.9
4072.
4073. Lodging 4074. 26.5
4075.
4076. Retail (other than mall) 4077. 2.5
4078.
4079. Enclosed>50,000 BtuH and strip
malls <200,000
BtuH
[3393.] 14.1≥4,000
(BtuH)/galand <2 gal
4080.[3394.]
4081.[3395.] Office 4082. 4.8
4083.
4084. Pub 4085. 2.1 4086.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
lic assembly
4087. Public order ≥4,000
(BtuH)/galand safety
<10 gal[3396.] 21.
480% Et
4088.[3397.]
4089.[3398.] Religious worship 4090. 0.9
4091.
4092. Service 4093. 15
4094.
4095. Warehouse ≥4,000
(BtuH)/galand storage
≥10 gal
[3399.] 2.980% Et (Q/799 + 16.6 √V)SL, BtuH
4096.[3400.]
4097.[3401.] Other 4098. 2.3
4099.
4100.[3402.] 4101.[3403.]
4102. Example: If a water heater of 150 kBtu/hr input capacity and 100 gallons storage capacity is installed in an existing building, the baseline standby losses would be calculated as SL = (150 kBtu/hr / 0.8 + 110 × √100) / 1000 = 1.29 kBtu/hr. If the proposed equipment’s standby losses were rated for 1.0 kBtu/hr, the percent standby loss savings would be %SL = (1.29 – 1.0) / 100 = 0.0019.
4103. In the above example, if the unit was rated for 96% thermal efficiency, and installed in an office building space of 10,000 ft2 , the annual energy savings would be ((1 – 0.8/0.96) + 0.0019) × 4.8 × 10000 / 1000 = 8.1 MMBtus/yr
4104. 4105. a - Energy factor (EF) and thermal efficiency (Et) are minimum requirements, while
standby loss (SL) is maximum BtuH based on a 70°F temperature difference between stored water and ambient requirements. In the EF equation, V is the rated volume in gallons. In the SL equation, V is the rated volume in gallons and Q is the nameplate input rate in BtuH.
[3404.] [3405.] b - Instantaneous water heaters with input rates below 200,000 BtuH must comply
with these requirements if the water heater is designed to heat water to temperatures of 180°F or higher.
[3406.] [3407.] Energy Use Density Lookup Table
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3408.]
Building Type Energy Use Density(kBtu/SF/yr)
Education 5.2Food Sales 3.2
Food Service 40.0Health Care 28.9- Inpatient 39.4
- Outpatient 3.5Lodging 29.2
Retail (Other Than Mall) 1.0Office 1.6
Public Assembly 0.9Public Order and Safety 15.1
Religious Worship 0.9Service 0.9
Warehouse and Storage 0.7Other 1.7
[3409.] [3410.] Sources :
1. ASHRAE Standards 90.1-2007, Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
2. ASHRAE Standards 90.1-2013, Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
3. Energy Information Administration, Commercial Building Energy Consumption Survey Data, 2012; available at: https://www.eia.gov/consumption/commercial/data/2012/c&e/cfm/e7.cfm.. 2003.
4106.[3411.] Instantaneous Gas Water Heaters
4107. This prescriptive measure is intended for instantaneous water heaters installed in commercial facilities. The savings algorithms are based on installed equipment specifications and data from the Commercial Building Energy Consumption Survey (CBECS).
4108. Baseline efficiencies are set by current and previous equipment performance standards. In New Jersey ASHRAE 90.1 defines the commercial energy code requirements. For new buildings, ASHRAE 90.1-2013 standards apply, and for existing buildings, ASHRAE 90.1-2007 standards are assumed.
4109. If the qualifying instantaneous water heater is greater than 200 kBtu/hr and replacing a storage water heater, use a baseline storage water heater efficiency greater than 75 kBtu/hr. Similarly, if the qualifying instantaneous water heater is less than 200 kBtu/hr, and replacing a storage water heater, use an efficiency for equipment less than 75 kBtu/hr.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4110. Note, that for storage tank water heaters rated above 75 kBtu/hr, and instantaneous water heaters above 200 kBtu/hr, equipment standards are defined in terms of thermal efficiency. Equipment below these levels is rated in terms of energy factor. Energy factor is determined on a 24 hour basis and includes standby or storage loss effects, while thermal efficiency does not. Therefore, if the equipment is large enough to be rated in terms of thermal efficiency, a percent standby loss factor must be included in the calculation as shown in the algorithms.
4111. 4112. Algorithms 4113. 4114. Fuel Savings (MMBtu/yr) = ((1 – (EFFb / EFFq) + %SL38) * Energy Use Density *
Area4115. 4116. Where,4117. 4118. %SL = 0.775 × (kBtu/hrqualifying input)-0.778 4119. 4120. Definition of Variables 4121. EFFq = Efficiency of the qualifying instantaneous water heater.4122. EFFb = Efficiency of the baseline water heater, commercial grade. 4123. UEFb = Efficiency of the baseline water heater, residential grade. 4124. %SL = Percent standby losses of the baseline water heater fuel usage. This was calculated from standby loss and input capacity data for commercial water heaters exported from the AHRI database. 4125. Energy Use Density = Annual baseline water heater energy use per square foot of commercial space served (MMBtu/sq.ft./yr)4126. Area = Square feet of building area served by the water heater
4127. Summary of Inputs 4128.
4129. Water Heater Assumptions4130. Com
ponent4131.Type
4132. Value 4133. Source
4134. EFFq 4135.Varia
ble
4136. 4137. Application
4138. EFFb 4139.Varia
ble
4140. See Table Below 4141. If storage water heater
< 75 kBtu/Hhr or instantaneous water heater
< 200 kBtu/hr: EF4142. Otherwise TE.
4145. 1, 2
38 Standby losses only apply if the baseline water heater is a storage water heater rated for more than 75 kBtu/hr
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4130. Component
4131.Type
4132. Value 4133. Source
4143. EF = Energy Factor4144. TE = Thermal
Efficiency4146. UEFb 4147.
Variable
4148. See baseline values in residential instantaneous
water heater measure
4149.
4150. Energy Use
Density
4151.Varia
ble
4152. See Table Below 4153. 3
4154. Area 4155.Varia
ble
4156. 4157. Application
4158. 4159. Efficiency of Baseline Water Heaters
4160. ASHRAE 90.1-2007 and 2013a
4161. Equipment Type
4162. Size
Category
(Input)
4163.Existing Building
Baseline Efficiency
(ASHRAE 90.1-2007)
4164. New Building Baseline
Efficiency (ASHRAE 90.1-2013)
4165. Gas Storage Water Heater
s39
4166. ≤ 75
kBtu/hr
4167. EF = 0.54 4168. EF = 0.65
4169. Gas Storage Water
Heaters
4170. > 75
kBtu/hr
4171. TE = 0.80 4172. TE = 0.80
4173. Gas Instantaneous Water Heater
s40
4174. < 200
kBtu/hr
4175. EF = 0.62 4176. EF = 0.62
39 Note, for qualifying instantaneous water heaters less than 200kBtu/hr, the storage water heater tank size is assumed to be 40 gallons.40 For instantaneous water heaters rated for less than 200 kBtu/hr, the tank size is assumed to be 1 gallon.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4177. Gas Instantaneous Water
Heaters
4178. ≥ 200
kBtu/hr
4179. TE = 0.80 4180. TE = 0.80
4181. a – EF means energy factor and TE means thermal efficiency4182.
4183. Energy Use Density Look-up Table
4184. Building Type
4185. Energy Use Density (kBtu/SF/yr)
4186. Education 4187. 7.04188. Food sales 4189. 4.4
4190. Food service 4191. 39.24192. Health care 4193. 23.7
4194. Inpatient 4195. 34.34196. Outpatient 4197. 3.94198. Lodging 4199. 26.5
4200. Retail (other than mall) 4201. 2.5
4202. Enclosed and strip malls 4203. 14.1
4204. Office 4205. 4.84206. Public
assembly 4207. 2.14208. Public order
and safety 4209. 21.44210. Religious
worship 4211. 0.94212. Service 4213. 15
4214. Warehouse and storage 4215. 2.9
4216. Other 4217. 2.34218. 4219. Sources
1. ASHRAE Standards 90.1-2007, Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
2. ASHRAE Standards 90.1-2013, Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3. Energy Information Administration, Commercial Building Energy Consumption Survey Data, 2012; available at: https://www.eia.gov/consumption/commercial/data/2012/c&e/cfm/e7.cfm.
4220.[3412.] Prescriptive Boilers4221.[3413.]
[3414.] This prescriptive measure targets the use of smaller-scale boilers (less than or equal to 4000 MBH) and furnaces (no size limitation) in all commercial facilities. Larger sized boilers are treated under the custom measure path. The measurement of energy savings for C&I gas, oil, and propane fired furnaces and boilers is based on algorithms with key variables (i.e. Annual Fuel Utilization Efficiency, capacity of the furnace, EFLH) provided by manufacturer data or utility data. Savings are calculated for four zones throughout the state by heating degree days and for twelve different building types.
4222.[3415.] This measure applies to new construction, replacement of failed equipment, or end of useful life. The baseline unit is a code compliant unit with an efficiency as required by ASHRAE Std. 90.1 – 2013, which is the current code adopted by the state of New Jersey.
4223. Algorithms
4224.[3416.] ()❑❑
❑❑❑
❑ [(❑❑
❑❑)]
[3417.] ( )❑❑
❑❑❑❑[(❑❑
❑❑)]
[3418.] [3419.] Definition of Variables [3420.] 4225.[3421.] Definition of Variables4226. OF = Oversize factor of standard boiler (OF=0.8)4227.[3422.] HDDmod = HDD by zone and building type4228.[3423.] ∆T = design temperature difference[3424.] [3425.] HCfuel = Conversion from Btu to Therms of gas (100,000 Btu/Therm)[3426.] kBtuin/hr =IRB = Boiler Baseline Input capacity of qualifying unit Rating (BtuH)[3427.] EffbEffB = Boiler Baseline Efficiency[3428.] EffqEffQ = Boiler Proposed Efficiency4229.[3429.] 1000 = Conversion from kBtu to MMBtu4230. 4231. Summary of Inputs 4232.
4233. Prescriptive Boilers4234.[3430.] Co
mponent4235.[3431.] Ty
pe4236.[3432.] Va
lue4237.[3433.] So
urce4238.[3434.] OF 4239.[3435.] Fix 4240.[3436.] 0.8 4241.[3437.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
ed[3438.] kBtuin/
hrIRB
4242.[3439.] Variable
4243.[3440.] 4244.[3441.] Application
[3442.] HCfuel [3443.] Fixed [3444.] 100,000 Btu/Therm
[3445.]
[3446.] EffbEffB 4245.[3447.] Variable
4246.[3448.] See Table Below
4247.[3449.] 2
[3450.] EffqEffQ 4248.[3451.] Variable
4249.[3452.] 4250.[3453.] Application
4251.[3454.] ∆T 4252.[3455.] Variable
4253.[3456.] See Table Below
4254.[3457.] 1
4255.[3458.] HDDmod
4256.[3459.] Fixed
4257.[3460.] See Table Below
4258.[3461.] 1
4259.[3462.] 4260.[3463.] Adjusted Heating Degree Days by Building Type
[3464.]
Building TypeHeating Energy
Density (kBtu/sf)
Degree Day Adjustment
Factor
Atlantic City (HDD)
Newark(HDD)
Philadelphia(HDD)
Monticello(HDD)
Education 29.5 0.55 2792 2783 2655 3886Food Sales 35.6 0.66 3369 3359 3204 4689
Food Service 39.0 0.73 3691 3680 3510 5137Health Care 53.6 1.00 5073 5057 4824 7060
Lodging 15.0 0.28 1420 1415 1350 1976Retail 29.3 0.55 2773 2764 2637 3859Office 28.1 0.52 2660 2651 2529 3701
Public Assembly 33.8 0.63 3199 3189 3042 4452Public Order/Safety 24.1 0.45 2281 2274 2169 3174Religious Worship 29.1 0.54 2754 2745 2619 3833
Service 47.8 0.89 4524 4510 4302 6296Warehouse/Storage 20.2 0.38 1912 1906 1818 2661
4261.[3465.] 4262.[3466.] Heating Degree Days and Outdoor Design Temperature by Zone
4263.[3467.]
Weather Station HDD Outdoor Design Temperature (F)
Atlantic City 5073 13Newark 5057 14
Philadelphia, PA 4824 15Monticello, NY 7060 8
4264.[3468.] 4265.[3469.] Baseline Boiler Efficiencies (Effb)
4266.[3470.] Boiler Type 4267.[3471.] Size Catego
ry
[3473.] Existin
g Buildi
[3474.] New Constructio
nStandard
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3472.] (kBtuM
Bh input)
ngsStandard
90.1-2007
90.1-2013
4268.[3475.] Hot Water – Gas fired
4269.[3476.] < 300
4270. > 300
[3477.] 80%
AFUE
4272.[3478.] 82% AFUE
4273. 80% Et4274. 82% Ec4275.[3479.] Hot Water –
Oil fired4276. <
3004277. >
300
4279. 84%
AFUE4280. 8
[3480.] 80% Et
[3481.] Steam – Gas firedHot Water
[3482.] < 300>
[3483.] 80%
[3484.] 82% Ec[3485.] SteamSteam – Gas
fired, all except natural 4282. > <
300 4283. 79
% [3486.] 80%
AFUE4284.[3487.] Steam – Gas
fired, all except natural [3488.] >
300 [3489.] 75
% Et[3490.] 79%
EcEt[3491.] Steam – Gas fired,, all except natural draft
4285.[3492.] > 300 and
[3493.] 80% Ec
[3494.] 7779% Et4286.[3495.] Steam – Gas
fired, natural draft[3496.] >
300 [3497.] 75
% Et[3498.] 77%
EcEt[3499.] Steam – Oil fired, natural draft
4287.[3500.] < 300
4288. > 300
4290. 82%
AFUE4291. 81
[3501.] 77% Et
4293.[3502.] [3503.] Sources :
[1.] KEMA, Smartstart Program Protocol Review. 2009.[2.] ASHRAE 90.1 2007
[3504.] [3.] Infrared HeatersKEMA, June 2009, New Jersey’s Clean Energy Program Residential HVAC
Impact Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/SmartStart%20Protocol%20Review%20-%20Final%20July%2010%202009.pdf.
1. ASHRAE Standards 90.1-2013. Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
4294. Prescriptive, Furnaces and Direct Install Boilers4295.[3505.]
[3506.] The methodology outlined below shall be adopted for estimating savings for installation of qualifying furnaces. and infrared heaters as well as Direct Install boilers in order to accommodate resizing.
4296.[3507.] This measure applies to new construction, replacement of failed equipment, or end of useful life. The baseline unit is a code compliant unit with an efficiency as required by ASHRAE Std. 90.1 – 2013, which is the current code adopted by the state of New Jersey.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4297. Algorithms
4298.[3508.] ()❑❑
❑❑❑
❑ [(❑❑
❑❑)]
[3509.] [❑❑ (❑❑❑❑ ) (❑❑❑❑)❑❑❑❑❑❑
][3510.] 4299.[3511.] 4300.[3512.] Definition of Variables [3513.] OF = Oversize factor of standard furnace/boiler/heater (OF=0.8)4301.[3514.] [3515.] CAPYB.out = Total output capacity of the baseline furnace/boiler/heater(s) in Btu/hour[3516.] [3517.] EffAFUEQ = Efficiency of qualifying furnace/boiler/heater(s) (AFUE %)[3518.] [3519.] CAPYQ.out = Total output capacity of the qualifying furnace/boiler/heater(s) in
Btu/hour[3520.] [3521.] EffB = Efficiency of baseline furnace/boiler/heater(s) (AFUE %)[3522.] [3523.] ICF = Infrared Compensation Factor (ICF = 0.8 for IR Heaters, 1.0 for
Furnaces/Boilers)2
[3524.] HDDmod = HDD by zone and building type[3525.] ∆T24 = Hours/Day[3526.] [3527.] ΔT = design temperature difference4302.[3528.] kBtuin/hr = Input capacity of qualifying unit 4303. Effb = Furnace Baseline Efficiency4304. Effq = Furnace Proposed Efficiency4305. 1000HCfuel = Conversion from kBtu to MMBtu4306. Btu to Therms of gas (100,000 Btu/Therm)4307.[3529.] Summary of Inputs 4308.[3530.]
4309. PrescriptiveIR Heaters, Furnaces and Boilers[3531.]
4310.[3532.] Component
4311.[3533.] Type
4312.[3534.] Value
4313.[3535.] Source
4314.[3536.] OF 4315.[3537.] Fixed
4316.[3538.] 0.8 4317.[3539.]
[3540.] HCfuel [3541.] Fixed [3542.] 100,000 Btu/Therm
[3543.]
[3544.] Effq 4318.[3545.] Va 4319.[3546.] 4320.[3547.] Ap
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
riable plication 4321.[3548.] Ef
fb
4322.[3549.] Fixed
[3550.] See Table BelowFurnaces: 78%
[3551.] Boilers: 80%a
[3552.] Infrared: 78% [3553.]
[3554.] 2 EPACT
Standard for furnaces and
boilers
4323.[3555.] CAPYB/Q, Out
4324.[3556.] Variable
4325.[3557.] 4326.[3558.] Application
4327.[3559.] ∆T 4328.[3560.] Variable
4329.[3561.] See Table Below
4330.[3562.] 1
4331.[3563.] HDDmod
4332.[3564.] Fixed
4333.[3565.] See Table Below
4334.[3566.] 14335.[3567.]
4336.[3568.] [3569.] a – 80% efficiency used for Direct Install protocols only. SmartStart gas boiler
efficiencies referenced in Boiler Baseline Efficiency table.[3570.] [3571.] Sources:
[3572.] 1. KEMA, Smartstart Program Protocol Review. 2009.[3573.] 2. http://www.spaceray.com/1_space-ray_faqs.php
[3574.] 4337.[3575.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3576.] Adjusted Heating Degree Days by Building Type4338.[3577.]
Building TypeHeating Energy
Density (kBtu/sf)
Degree Day Adjustment
Factor
Atlantic City (HDD)
Newark(HDD)
Philadelphia(HDD)
Monticello(HDD)
Education 29.5 0.55 2792 2783 2655 3886Food Sales 35.6 0.66 3369 3359 3204 4689
Food Service 39.0 0.73 3691 3680 3510 5137Health Care 53.6 1.00 5073 5057 4824 7060
Lodging 15.0 0.28 1420 1415 1350 1976Retail 29.3 0.55 2773 2764 2637 3859Office 28.1 0.52 2660 2651 2529 3701
Public Assembly 33.8 0.63 3199 3189 3042 4452Public Order/Safety 24.1 0.45 2281 2274 2169 3174Religious Worship 29.1 0.54 2754 2745 2619 3833
Service 47.8 0.89 4524 4510 4302 6296Warehouse/Storage 20.2 0.38 1912 1906 1818 2661
4339.[3578.] 4340.[3579.] Heating Degree Days and Outdoor Design Temperature by Zone
4341.[3580.]
Weather Station HDD Outdoor Design Temperature (F)
Atlantic City 5073 13Newark 5057 14
Philadelphia, PA 4824 15Monticello, NY 7060 8
4342.[3581.] 4343. Baseline Furnace Efficiencies (Effb)
4344. Furnace Type
4345. Size Category
4346. (kBtu input)
4347. Standard 90.1-2013
4348. Gas Fired 4349. < 2254350. ≥ 225
4351. 78% AFUE
4353. Oil Fired 4354. < 2254355. ≥ 225
4356. 78% AFUE
4358. [3582.] Baseline Boiler Efficiencies (Effb)
[3583.] [3584.] [3585.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3586.] Sources : 1. KEMA, June 2013, New Jersey’s Clean Energy Program Residential HVAC Impact
Evaluation and Protocol Review; available at: http://www.njcleanenergy.com/files/file/Library/HVAC%20Evaluation%20Report%20-%20Final%20June%2011%202009.pdf.
2. ASHRAE Standards 90.1-2013, Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
1. KEMA, Smartstart Program Protocol Review. 2009.[3587.] http://www.spaceray.com/1_space-ray_faqs.php
4359.[3588.] Infrared Heaters4360. This measures outlines the deemed savings for the installation of a gas-fired low
intensity infrared heating system in place of unit heater, furnace, or other standard efficiency equipment. The deemed savings are based on a Massachusetts Impact Evaluation Study[1].
4361. 4362. Summary of Assumptions 4363.
4364. Variable 4365. Value 4366. Source4367. Deemed
Savings4368. 12.0
MBtu/yr4369. 1
4370. 4371. Sources
1. KEMA, Impact Evaluation of 2011 Prescriptive Gas Measures; prepared for Massachusetts Energy Efficiency Program Administrators and Massachusetts Energy Efficiency Advisory Council, 2013, pp. 1–5.
4372.
4373. Electronic
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3589.] Fuel Use Economizers4374.[3590.] [3591.] Algorithms [3592.] [3593.] Fuel Savings (MMBtu) = (AFU * 0.13)[3594.] [3595.] AFU = Annual Fuel Usage for an uncontrolled (gas, oil, propane) HVAC unit
(MMBtu or gallons) = (Input power in MMBtu or gallons) * (annual run time)[3596.] 0.13 = Approximate energy savings factor related to installation of fuel use
economizers1.[3597.] [3598.] SourcesThe following algorithms detail savings for the installation of electronic fuel
use economizers on commercial boilers and furnace systems. :
[3599.] Approximate energy savings factor of 0.13 based on average % savings for test sites represented in Table 2 (page 3) of NYSERDA Study: A Technology Demonstration and Validation Project for Intellidyne Energy Saving Controls; Intellidyne LLC & Brookhaven National Laboratories; 2006 (http://www.cleargreenpartners.com/attachments/File/NYSERDA_Report.pdf)These devices are microprocessor-based fuel-saving controls for commercial HVAC. They optimize energy consumption by adjusting burner or compressor run patterns to match the system’s load. They can be used to control gas or oil consumption for any type of boiler or forced air furnace system. Here, the baseline system is a boiler or furnace that does not have fuel economizers installed.
4375. The input values are based on customer billing data supplied by the utilities and customer information on the application form, confirmed with manufacturer data.
4376. The savings are based on research performed by ERS for the Massachusetts Technical Assessment Committee (MTAC) for one of the systems available in the marketplace. The research was based on data collected through a combination of third party technical reviews and impact evaluation M&V data, both billing analysis and field measurements. ERS observed that the savings vary between 1% and 10%. In general, it was observed that the installations with the oversized boilers (estimated as sites with lower average firing rates) are most likely to yield the highest savings. The actual savings will vary somewhat from project to project, it is reasonable to assume that program-wide energy savings across all approved fuel-use economizers measures will likely be close to the weighted average of 4% of the baseline use.
4377.[3600.] 4378.[3601.] Algorithms
4379. 4380. Fuel Savings (MMBtu) = (AFU * SF)4381. 4382. Definition of Variables
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4383. Distributed Energy Resource (DER)AFU = Annual Fuel Usage for an uncontrolled (gas, oil, propane) HVAC unit (MMBtu or gallons)4384. SF = Savings factor, based on data collected through a combination of third party technical reviews and impact evaluation M&V data, both billing analysis and field measurements.4385. 4386. Summary of Inputs 4387.
4388. Electronic Fuel Use Economizer Assumptions4389. Compon
ent4390. Type 4391. Value 4392. Source
4393. AFU 4394. Variable 4395. 4396. Application
4397. SF 4398. Fixed 4399. 0.04 4400. 1 4401. 4402. Sources
1. IntelliCon Boiler Controls and Savings Potential,” presentation delivered to MTAC by ERS on April 6, 2015.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
Combined Heat & Power Program4403.[3602.]
4404.[3603.] Protocols[3604.] The measurement of energy and demand savings for Combined Heat and Power
(CHP)/fuel cell systems is based primarily on the characteristics of the individual systems subject to the general principles set out below. The majority of the inputs used to estimate energy and demand impacts of CHP/fuel cell systems will be drawn from individual project applications.
[3605.] [3606.] CHP/fuel cell systems typically use fossil fuels to generate electricity that displaces
electric generation from other sources. Therefore, the electricity generated from a CHP/fuel cell system should not be reported as either electric energy savings or renewable energy generation. Alternatively, electric generation and capacity from CHP/fuel cell systems should be reported as Distributed Generation (DG) separate from energy savings and renewable energy generation. However, any waste heat recaptured and utilized should be reported as energy savings as, discussed below.
[3607.] Distributed Generation[3608.] Electric Generation (MWh) = Estimated annual and lifetime electric generation in
MWh provided on the project application, as adjusted during the project review and approval process.
[3609.] [3610.] Electric Demand (kW) = Electric capacity of the CHP/fuel cell system in kW
provided on the project application, as adjusted during the project review and approval process.
[3611.] Energy Savings[3612.] Gas Energy Savings: Gas savings should be reported on a consistent basis by all
applicants as the reduction in fuel related to the recapture of thermal energy (e.g., reduction in boiler gas associated with the recapture of waste heat from the CHP engine or turbine, or a fuel cell with heat recovery.)
[3613.] [3614.] Electric Energy Savings: Electric energy savings should be reported only in cases
where the recapture of thermal energy from the CHP system is used to drive an absorption chiller that would displace electricity previously consumed for cooling.
[3615.] Emission Reductions[3616.] For many CHP/fuel cell applications there can be substantial emission benefits due to
the superior emission rates of many new CHP engines and turbines as compared to the average emission rate of electric generation units on the margin of the grid. However,
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
CHP engines and turbines produce emissions, which should be offset against the displaced emissions from the electricity that would have been generated by the grid.41
[3617.] [3618.] The New Jersey Department of Environmental Protection (DEP) has provided the
BPU with emission factors that are used to calculate the emission savings from energy efficiency and renewable energy projects. These factors should be used to calculate the base emission factors which the CHP system emission factors would be compared to. The emissions from the CHP system would be subtracted from the base emissions to determine the net emission changes as follows:
[3619.] [3620.] Emissions Factors Associated with PJM Grid
[3621.] [3622.] CO2 – 1015 lbs per MWh[3623.] NOX – 0.95 lbs per MWh[3624.] SO2 – 2.21 lbs per MWh
[3625.] [3626.] CHP Emissions Reduction (ER) Formulas
[3627.] (Assuming that the useful thermal output will displace natural gas)[3628.]
[3629.] CO2e ER (lbs) = [1015 * Electrical Output (MWh) + Useful Thermal Output (MMBtu) * CO2 EFNG] – [CHP CO2 EFf * Fuel Consumption (MMBtu)]
[3630.] [3631.] NOx ER (lbs) = [0.95 * Electrical Output (MWh) + Useful Thermal Output (MMBtu) *
NOx EFNG] – [CHP NOX EFf * Fuel Consumption (MMBtu)][3632.]
[3633.] SO2 ER (lbs) = [2.21 * Electrical Output (MWh) + Useful Thermal Output (MMBtu) * SO2 EFNG] – [CHP SO2 EFf * Fuel Consumption (MMBtu)]
[3634.] [3635.] Note: [3636.] [1.] EFNG values associated with boiler fuel displacement:
[3637.] CO2 EFNG = 115 lb/MMBtu[3638.] NOX EFNG = 0.12 lbs/MMBtu[3639.] SO2 EFNG = .0006 lb/MMBtu
[3640.] [2.] CHP EFf (lb/MWh) - Emission factor of fuel type used in the CHP system, which will
vary with different projects based on the types of prime movers and emission control devices used.
[3641.] [3642.] NJDEP Regulatory Limits for CHP Systems
[3643.] [3644.] NOX: 0.047 lb/MMBtu[3645.] SO2: 0.0006 lb/MMBtu[3646.] CO: 0.157 lb/MMBtu
41 Summit Blue, Draft Energy Efficiency Market Assessment of New Jersey Clean Energy Program, Book III, Page 196, May 26, 2006
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3647.] VOC: 0.047 lb/MMBtu[3648.] TSP: 0.01 lb/MMBtu[3649.] PM-10: 0.038 lb/MMBtu[3650.] Emission reductions from any CHP system energy savings, as discussed above,
would be treated the same as any other energy savings reported.[3651.]
[3652.] Sustainable Biomass
[3653.] Estimated annual energy generation and peak impacts for sustainable biomass systems will be determined on a case-by-case basis based on the information provided by project applicants and inspection data for verification of as- installed conditions. The measurement of energy and demand savings for Combined Heat and Power (CHP) systems is based primarily on the characteristics of the individual systems subject to the general principles set out below. The majority of the inputs used to estimate energy and demand impacts of CHP systems will be drawn from individual project applications. Eligible systems include: powered by non-renewable or renewable fuel sources, gas internal combustion engine, gas combustion turbine, microturbine, and fuel cells with heat recovery.
4405. The NJ Protocol is to follow the National Renewable Energy Laboratory’s Combined Heat and Power, The Uniform Methods Project: Methods for Determining Energy-Efficiency Savings for Specific Measures [1]. The product should be all of the below outputs, as applicable:
a. Annual energy input to the generator, HHV basis (MMBtu/yr)b. Annual electricity generated, net of all parasitic loads (kWh/yr)c. Annual fossil fuel energy savings from heat recovery (MMBtu/yr)d. Annual electric energy savings from heat recovery, including absorption chiller
sourced savings if chiller installation is included as part of the system installation (kWh/yr)
e. Annual overall CHP fuel conversion efficiency, HHV basis (%)f. Annual electric conversion efficiency, net of parasitics, HHV basis (%)
4406. CHP systems typically use fossil fuels to generate electricity that displaces electric generation from other sources. Therefore, the electricity generated from a CHP system should not be reported as either electric energy savings or renewable energy generation. Alternatively, electric generation and capacity from CHP systems should be reported as Distributed Generation (DG) separate from energy savings and renewable energy generation. However, any waste heat recaptured and utilized should be reported as energy savings as discussed below.
4407. Distributed Generation
4408. Net Electricity Generation (MWh) = Estimated electric generation provided on the project application, as adjusted during the project review and approval process.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4409. Peak Electric Demand (kW) = Electric demand reduction delivered by the CHP system provided on the project application, as adjusted during the project review and approval process.
4410. Total Fuel Consumption or Fuel Consumed by Prime Mover (MMBtu @HHV) = Total heating value of used by CHP system provided on the project application, as adjusted during the project review and approval process.
4411. Energy Savings Impact
4412. Gas Energy Savings or Fuel Offset (MMBtu @HHV): Gas savings should be reported on a consistent basis by all applicants as the reduction in fuel related to the recapture of thermal energy (e.g., reduction in boiler gas associated with the recapture of waste heat from the CHP engine or turbine, or a fuel cell with heat recovery.)
4413. Electric Energy Savings or Offset Chiller Electricity Use (MWh): Electric energy savings should be reported only in cases where the recapture of thermal energy from the CHP system is used to drive an absorption chiller that would displace electricity previously consumed for cooling.
4414. Emission Reductions
4415. For many CHP applications there can be substantial emission benefits due to the superior emission rates of many new CHP engines and turbines as compared to the average emission rate of electric generation units on the margin of the grid. However, CHP engines and turbines produce emissions, which should be offset against the displaced emissions from the electricity that would have been generated by the grid.
4416.[3654.] The New Jersey Department of Environmental Protection (NJDEP) has provided the BPU with emission factors that are used to calculate the emission savings from energy efficiency and renewable energy projects. These factors should be used to calculate the base emission factors which the CHP system emission factors would be compared to. The emissions from the CHP system would be subtracted from the base emissions to determine the net emission changes as follows:
4417. CHP Emissions Reduction Associated with PJM Grid [2]4418. (Assuming that the useful thermal output will displace natural gas)4419.4420.[3655.] Algorithms 4421.4422.[3656.] CO2 ER (lbs) = [CO2emission * Net Electricity Generation (MWh) + Gas Energy
Savings (MMBtu) * CO2 EFNG] – [CHP CO2 EFf * Total Fuel Consumption (MMBtu)]
4423. 4424. NOx ER (lbs) = [NOxemission * Net Electricity Generation (MWh) + Gas
Energy Savings (MMBtu) * NOx EFNG] – [CHP NOX EFf * Total Fuel Consumption (MMBtu)]
4425.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4426. SO2 ER (lbs) = [SO2emission * Net Electricity Generation (MWh) + Gas Energy Savings (MMBtu) * SO2 EFNG] – [CHP SO2 EFf * Total Fuel Consumption (MMBtu)]
4427. 4428. Definition of Variables 4429. CO2emission = 992 lbs per MWh4430. NOXemission = 0.75 lbs per MWh4431. SO2emission = 1.32 lbs per MWh
4432. EFNG values associated with boiler fuel displacement [3]:4433. CO2 EFNG = 118 lb/MMBtu4434. NOX EFNG = 0.12 lbs/MMBtu (average for all boilers)4435. SO2 EFNG = 0.0006 lb/MMBtu
4436.4437.[3657.] CHP EFf (lb/MMBtu) = Emission factor of fuel type used in the CHP system, which will vary with different projects based on the types of prime movers and emission control devices used.
4438. Emission reductions from any CHP system energy savings, as discussed above, would be treated the same as any other energy savings reported.
4439. Sources 1. Simons, George, Stephan Barsun, and Charles Kurnik. 2016. Chapter 23: Combined Heat
and Power, The Uniform Methods Project: Methods for Determining Energy-Efficiency Savings for Specific Measures. Golden, CO; National Renewable Energy Laboratory. NREL/ SR-7A40-67307. http://www.nrel.gov/docs/fy17osti/67307.pdf.
2. PJM report; “2012–2016 CO2, SO2 and NOX Emission Rates,” March 2017. PJM system average values for the year 2016 are used.
3. US EPA AP-42: AP-42, Compilation of Air Pollutant Emission Factors, 5th Edition, Chapter 1.4 Natural Gas Combustion https://www3.epa.gov/ttnchie1/ap42/ch01/final/c01s04.pdf.4440.
4441. Sustainable Biomass Biopower4442. Estimated annual energy generation and peak impacts for sustainable biomass
systems will be determined on a case-by-case basis based on the information provided by project applicants and inspection data for verification of as-installed conditions.
4443. 4444.4445.[3658.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4446.[3659.] Pay for Performance Program
Protocols[3660.] The Pay for Performance Program is a comprehensive program targeted at existing
commercial and industrial (C&I) buildings that have an average annual peak demand of 200 kW or greater; as well as select multifamily buildings with annual peak demand of 100 kW or greater. Participants in the Pay for Performance Program are required to identify and implement energy efficiency improvements that will achieve a minimum savings target. of 15% reduction in total source energy consumption.
4447.[3661.] Energy Savings Requirements4448.[3662.] For Existing Buildings, projects
[3663.] Projects are required to identify and implement comprehensive energy efficiency improvements that will achieve a minimum of 15% reduction in total source energy consumption as measured from existing energy use. For New Consturction, including major rehabilitation, projects are required to identify and implement comprehensive energy efficiency measures that achieve a minimum 5% energy cost savings (for commercial and industrialexisting buildings,) and 15% for multifamily, energy cost savings from the current state energy code (for new construction). Further, no more than 50% of the total savings may be derived from lighting measures, Savings may not come from a single measure and no more than 50% of the total savings may be derived from lighting measures. Lighting savings up to 70% of total projected savings can be considered but the minimum savings required will increase proportionately as
demonstrated in the table below.
Lighting SavingsMinimum Source
Energy Target
51% 16%52% 17%53% 18%54% 19%55% 20%56% 21%57% 22%58% 23%59% 24%60% 25%61% 26%62% 27%63% 28%64% 29%65% 30%66% 31%67% 32%68% 33%69% 34%70% 35%
4449.[3664.] Existing Buildings projects must include multiple measures, where lighting measures do not exceed 50% of total savings (exceptions apply, see program guidelines). New Construction projects
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3665.] The must have at least one measure addressing each envelope, heating, cooling, and lighting systems. Buildings that are not heated (e.g. refrigerated warehouse) or not cooled (e.g. warehouse) will not be required to have a measure addressing the missing building system.
4450. In both program components, the total package of measures must have at least a 10%, internal rate of return (IRR), and at least 50% of the savings must come from investor-owned electricity and/or natural gas. If 50% of the savings does not meet this criteria, then the project must save a minimum of 100,000 kWh or 2,000 therms from investor-owned utility accounts.
[3666.] For Existing Buildings, anAn exception to the 15% savings requirement is availablewill be limited to sectors such as manufacturing, pharmaceutical, chemical, refinery, packaging, food/beverage, data center, transportation, mining/mineral, paper/pulp, biotechnology, etc, as well as hospitals. The manufacturing and/or processing loads use should be equal to or greater than approximately 50% of the total metered energy use. Instead of the 15% savings requirement, the project must deliver a minimum energy savings of 100,000 kWh, 350 MMBTU or 4% of total facility consumption. , whichever is greater. Exceptions must be pre-approved by Market Manager and currently only apply to existing buildings component of program
4451.[3667.] [3668.] New Construction and Gut Rehabilitation [3669.] Projects are required to identify and implement energy efficiency improvements that
will achieve a minimum of 5% energy cost savings for C&I buildings, and 15% for multifamily, as measured from ASHRAE 90.1-2013 baseline. Equivalent performance targets for ASHRAE Building Energy Quotient (bEQ) As-Designed and ASHRAE 90.1-2013 with Addendum BM are provided in the program guidelines (see Baseline Conditions below).
[3670.] [3671.] Each project must have at least one measure addressing each envelope, heating,
cooling, and lighting systems. Buildings that are not heated (e.g. refrigerated warehouse) or not cooled (e.g. warehouse) will not be required to have a measure addressing the missing building system.
[3672.] Software Requirements[3673.] In order for a project to qualify for incentives under the Pay for Performance
Program, the Partner must create a whole-building energy simulation to demonstrate energy savings from recommended energy efficiency measures, as described in detail in the Simulation Guidelines section of the Pay for Performance Program Guidelines. The primary source for developing the Simulation Guidelines is ASHRAE Guideline 14. Simulation software must be compliant with ASHRAE 90.1 Section 11 or Appendix G. Examples of allowed tools include eQUEST, HAP, EnergyPlus, Trane Trace, DOE 2.1. Approval for use in LEED and Federal Tax Deductions for Commercial Buildings program may serve as the proxy to demonstrate compliance with the requirement.
4452.[3674.] Baseline Conditions 4453.[3675.] Existing Buildings
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4454.[3676.] Baseline from which energy savings are measured will be based off the most recent 12 months of energy use from all sources. Site energy use is converted to source energy use following EPA’s site-to-source conversion factors42.
4455.[3677.] 4456.[3678.] New Construction 4457.[3679.] Project may establish building baseline in one of two ways: Path 1 –- Under this path, the Partner will develop a single energy model representing the
proposed project design using prescribed modeling assumptions that follow ASHRAE Building Energy Quotient (bEQ) As-Designed 43 simulation requirements.
Path 2 –- Under this option the Partner will develop a baseline building using ASHRAE 90.1-2013 Appendix G modified by Addendum BM44. (for existing buildings) or current state energy code, such as ASHRAE 90.1 2007 (for new construction).
[3680.]
4458.[3681.] Measure Savings4459.[3682.] Measures must be modeled to demonstrate proposed energy/energy cost savings
according to Pay for Performance program guidelines, including meeting or exceeding Minimum Performance Standards, or current state or local energy code, whichever is more stringent. Minimum Performance Standards generally align with C&I SmartStart Program equipment requirements.
4460.[3683.] 4461.[3684.] Existing Buildings 4462.[3685.] Measures must be modeled within the approved simulation software and
modeled incrementally to ensure interactive savings are taken into account. 4463.[3686.] 4464.[3687.] New Construction 4465.[3688.] Measures must be modeled based on the baseline path chosen: Path 1 –- Modeled within the same proposed design energy model, but as parametric runs
or alternatives downgraded to code compliant parameters. Path 2 – Modeled as interactive improvements to the ASHRAE 90.1-2013 Appendix G
baseline (with Addendum BM accepted). 4466.[3689.] In the event that a software tool cannot adequately model a particular measure
or component, or in cases where Program Manager permits savings calculations outside of the model, projects are required to use stipulated savings calculations as outlined in the Program Guidelines or within these Protocols as applicable. If stipulated savings do not exist within these documents, the Program Maanger will work with the applicant to establish acceptable industry calculations.
4467.
42 https://portfoliomanager.energystar.gov/pdf/reference/Source%20Energy.pdf 43 http://buildingenergyquotient.org/asdesigned.html44 Addendum BM sets a common baseline building approach that will remain the same for ASHRAE 90.1-2013 and all future iterations of ASHRAE 90.1, and is roughly equivalent to ASHRAE 90.1-2004. To comply with ASHRAE 90.1-2013, a proposed building has to have energy cost savings of 11-40% from the Addendum BM baseline, depending on the building type and climate zone.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4468.[3690.] Measurement & Verification 4469.[3691.] Existing Buildings 4470.[3692.] The Program metering requirements are based on the 2010 International
Performance Measurement and Verifications Protocol (“IPMVP”) and the 2008 Federal Energy Management
4471.[3693.] Program (“FEMP”) M&V Guidelines, Version 3.0. All projects must follow Option D, Calibrated Simulation, as defined by the IPMVP. Calibrated simulation involves the use of computer software to predict building energy consumption and savings from energy-efficiency measures. Options A and B, as defined by the IPMVP, may be used as guidelines for data collection to help create a more accurate model. Additionally, for the existing buildings component, Option C is used to measure actual savings using twelve months of post-retrofit utility data.
4472.[3694.] 4473.[3695.] New Construction 4474.[3696.] Projects are required to commission all energy efficiency measures. Further,
projects are required to complete a benchmark through EPA’s ENERGY STAR Portfolio Manager to demonstrate operational performance based on the building’s first year of operation. Building types not eligible ofor ENERGY STAR Score may demonstrate compliance through ASHRAE Building Energy Quotient (bEQ) In-Operation.
4475.[3697.] Energy Savings Reporting[3698.] Committed energy savings are reported upon approval of the Energy Reduction Plan
and are based on modeling results of recommended measures as described above. Installed energy savings are reported upon installation of recommended measures and are based on modeling results. Unless significant changes to the scope of work occurred during construction, installed savings will be equal to committed savings. Verified savings are reported at the end of the performance period (for Existing Buildings) and are based on twelve (12) months of post-retrofit utility bills compared to pre-retrofit utility bills used during Energy Reduction Plan development. For New Construction, verified savings are not currently reportedreportedor at the end of the Commissioning process (for new construction) and may vary from committed/installed savings. Note that only installed savings are reported on New Jersey’s Clean Energy Quarterly Financial and Energy Savings Reports.
4476.[3699.] 4477.[3700.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4478.[3701.] Direct Install Program
4479.[3702.] Protocols[3703.] This section identifies the protocols for all measures proposed under the Direct Install
Program. Several of the This section includes protocols for measures usethat are not included in other sections of the Protocols. In addition, for several of the where Direct Install Protocols uses algorithms and inputs identical tofrom the “Commercial and Industrial Energy Efficient Construction section of the Protocols, and as such, the user is directed to that ” section for the specific protocol. Other measures may have similar algorithms and inputs, but identifyof the Protocols, different equipment baselines will be used to reflect the Direct Install includes early replacement program where retirement. Baseline equipment is replaced as a direct result of the program. For those measures, the applicable baseline tables are included in efficiency shown in this section, but the user is directed to the C&I section is an estimate of the Protocols for algorithms and other inputs. existing equipment efficiency rather than currently available standard efficiency.
4480.[3704.] Electric HVAC Systems
[3705.] Replacement of existing electric HVAC equipment with high efficiency units is a proposed measure under the C&I Energy Efficienct Direct Install Program. (See C&I Construction Electric HVAC Systems Protocols.). The Direct Install savings protocol will be the same as previously stated in this document with the exception of the assumption for baseline efficiency.
4481. Efficiency baselines are designed to reflect current market practices, which in this case reflect ASHRAE 90.1-2007. For the Direct Install program, the following values will be used for the variable identified as SEERb EERb COPb IPLVb and HSPFb
4482. 4483.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4484. HVAC Baseline Table –EERb. These age-based efficiencies are used in estimating savings associated with the Direct Install Program because as an early
replacement program, equipment is replaced as a direct result of the program. 4485.[3706.] [3707.] Default Values for Mechanical System Efficiencies – Age-Based
[3708.] Equipment TypeSystem
[3709.] Baseline = ASHRAE Std.
90.1-2007Units
4486.[3710.]
[3711.] Unitary HVAC / Split Systems
[3712.] 8.03
[3713.] <= 5.4 tons
[3714.] SEER
[3715.] 7.80
[3716.] 10.00 [3717.]
4487.[3718.] Unitary HVAC/Split Systems and Single Package, Air Cooled4488. · <=5.4 tons4489. · >5.4 to- 11.25 tons4490. · >11.25 to 20 tons
4491.[3719.]
4492. 13 SEER4493. 11 EER
4494. 10.8 EER
4495.[3720.]
[3721.] 11.25 - 20 tons
[3722.] EER
[3723.] 9.45
[3724.] 8.31 [3725.]
[3726.] Air-Air Heat Pump Systems
[3727.] 9.10
[3728.] <= 5.4 tons
[3729.] SEER
[3730.] [3731.] 10.00 [3732.]
4496.[3733.] Air-Air Cooled Heat Pump Systems, Split System and Single Package4497. · <=5.4 tons4498. · >5.4 to- 11.25 tons4499. · >11.25 to 20 tons
4500.[3734.]
4501.
4502. 13 SEER, 7.7 HSPF
4503. 10.8 EER, 3.3 heating COP
4504. 10.4 EER, 3.2 heating COP
4505.[3735.]
[3736.] Packaged Terminal Systems
[3737.] 8.03
[3738.] [3739.] [3740.] [3741.] [3742.] [3743.] [3744.] [3745.] [3746.] [3747.] [3748.] [3749.] [3750.] [3751.] [3752.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3708.] Equipment TypeSystem
[3709.] Baseline = ASHRAE Std.
90.1-2007Units
4486.[3710.]
4506.[3753.] Water Source Heat Pumps
4507.
Capacities
4508.[3754.] 4509. 12.0 EER
4510.[3755.]
[3756.] All Capacities
[3757.] E
[3758.] 9
[3759.] 10.00 [3760.]
[3761.] Source: Based on the 2006 Mortgage Industry National Home Energy Ratings Systems Standards, Table 303.7.1(3) Default Values for Mechanical System Efficiencies (Age-based), RESNET.
[3762.] [3763.] NOTE – The age-based efficiencies in the above table have been interpolated from
RESNET standards and current baseline figures utilized in NJ C&I Energy Efficiency Rebate programs. With no equivalent resource available specific to small commercial equipment, these combined resources reflect the closest approximation to typical efficiencies of mechanical equipment present in Direct Install project facilities. The Direct Install program is targeted towards small commercial customers. As such, eligible equipment must not exceed a maximum capacity determined to be commonplace in the small C&I sector. In most cases, these capacity ranges correlate well with equipment certified by AHRI under the designation “Residential”.
4511.[3764.] Motors [Inactive 2017, Not Reviewed]4512.[3765.] Replacement of existing motors with high efficiency units is a proposed
measure under the Direct Install Program. (See C&I Construction Motors Protocols). The savings protocol will be the same as previously stated in this document with the exception of the assumption for baseline efficiency. For the Direct Install program, the following values will be used for the variable identified as base. These efficiencies are used in estimating savings associated with the Direct Install Program because as an early replacement program, equipment is replaced as a direct result of the program.
4513.[3766.] 4514.[3767.] Motor4515.[3768.] HP
4516.[3769.] Baseline
Efficiency
4517.[3770.] 1
4518.[3771.] 0.75
4519.[3772.] 1.5
4520.[3773.] 0.775
4521.[3774.] 2
4522.[3775.] 0.80
4523.[3776.] 3
4524.[3777.] 0.825
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4525.[3778.] 5
4526.[3779.] 0.84
4527.[3780.] 7.5
4528.[3781.] 0.845
4529.[3782.] 10
4530.[3783.] 0.85
4531.[3784.] >10
4532.[3785.] Use EPAct
Baseline Motor Efficiency Table on pg. 72
4533.[3786.] Source: Opportunities for Energy Savings in the Residential and Commercial Sectors with High-Efficiency Electric Motors, US DOE, 1999, Figure 4-4, page 4-5.
4534.[3787.]
4535.[3788.] Variable Frequency Drives[3789.] Installation of variable frequency motor drive systems is a proposed measure under
Commercial and Industrial Energy Efficientthe Direct Install Program. (See C&I Construction. Motors Protocols). Because there is no baseline assumption included in the protocols for this measure, the savings protocol will be exactly the same as previously stated in this document.
4536.[3790.]
[3791.] Refrigeration Measures4537.[3792.] Installation of the following refrigeration measures are proposed under the
Commercial and Industrial Energy Efficient Construction Program. Because there is no baseline assumption included in the protocols for these measures, the savings protocol will be exactly the same as previously stated in this document.
4538. Walk-in Cooler/Freezer Evaporator Fan Control 4539.[3793.] [3794.] This measure is applicable to existing walk-in coolers and freezers that have
evaporator fans which run continuously. The measure adds a control system feature to automatically shut off evaporator fans when the cooler’s thermostat is not calling for cooling. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein. These savings take into account evaporator fan shut off and associated savings as a result of less heat being introduced into the walk-in, as well as the savings from the compressor, which is now being controlled through electronic temperature control.
[3795.] [3796.] Several case studies have been performed that verify the accuracy of these savings.
The algorithms below are based on field-tested approximations of energy savings realized
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system. 1
[3797.] [3798.] Algorithms [3799.] [3800.] Gross kWh Savings = kWh SavingsEF + kWh SavingsRH + kWh SavingsEC
[3801.] [3802.] kWh SavingsEF = ((AmpsEF * VoltsEF * (PhaseEF)1/2)/1000) * 0.55 * 8,760 * 35.52%[3803.] [3804.] kWh SavingsRH = kWh SavingsEF * 0.28 * 1.6[3805.] [3806.] kWh SavingsEC = (((AmpsCP * VoltsCP * (PhaseCP)1/2)/1000) * 0.85 * ((35% * WH) + (55% * NWH)) * 5%) + (((AmpsEF * VoltsEF * (PhaseEF)1/2)/1000) * 0.55 * 8,760 * 35.52% * 5%)[3807.] [3808.] Gross kW Savings = ((AmpsEF * VoltsEF * (PhaseEF)1/2)/1000) * 0.55 * D[3809.] [3810.] Definition of Variables [3811.]
[3812.] kWh SavingsEF = Savings due to Evaporator Fan being off[3813.] kWh SavingsRH = Savings due to reduced heat from Evaporator Fans[3814.] kWh SavingsEC = Savings due to the electronic controls on compressor and evaporator[3815.] AmpsEF = Nameplate Amps of Evaporator Fan[3816.] VoltsEF = Nameplate Volts of Evaporator Fan[3817.] PhaseEF = Phase of Evaporator Fan[3818.] 0.55 = Evaporator Fan Motor power factor.[3819.] 8,760 = Annual Operating Hours[3820.] 35.52% = Percent of time Evaporator Fan is turned off. 2
[3821.] 0.28 = Conversion from kW to tons (Refrigeration).[3822.] 1.6 = Efficiency of typical refrigeration system in kW/ton.3
[3823.] AmpsCP = Nameplate Amps of Compressor[3824.] VoltsCP = Nameplate Volts of Compressor[3825.] PhaseCP = Phase of Compressor[3826.] 0.85 = Compressor power factor.[3827.] 35% = Compressor duty cycle during winter months (estimated)[3828.] WH = Compressor hours during winter months (2,195)[3829.] 55% = Compressor duty cycle during non-winter months (estimated)[3830.] NWH = Compressor hours during non-winter months (6,565)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3831.] 5% = Reduced run time of Compressor and Evaporator due to electronic controls.4
[3832.] D = 0.228 or Diversity Factor5
[3833.] [3834.] Sources :[3835.]
[(1)] Several case studies related to NRM’s Cooltrol system can be found at: http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html
[(2)] This value is an estimate by NRM based on hundreds of downloads of hours of use data from the electronic controller. It is an ‘average’ savings number and has been validated through several 3rd Party Impact Evaluation Studies including study performed by HEC, “Analysis of Walk-in Cooler Air Economizers”, Page 22, Table 9, October 10, 2000 for National Grid.
[(3)] Select Energy Services, Inc. Cooler Control Measure Impact Spreadsheet User’s Manual. 2004.
[(4)] This percentage has been collaborated by several utility sponsored 3rd Party studies including study conducted by Select Energy Services for NSTAR, March 9, 2004.
[(5)] Based on the report “Savings from Walk-In Cooler Air Economizers and Evaporator Fan Controls”, HEC, June 28, 1996.[3836.]
[3837.] Cooler and Freezer Door Heater Control 4540.[3838.] [3839.] This measure is applicable to existing walk-in coolers and freezers that have
continuously operating electric heaters on the doors to prevent condensation formation. This measure adds a control system feature to shut off the door heaters when the humidity level is low enough such that condensation will not occur if the heaters are off. This is performed by measuring the ambient humidity and temperature of the store, calculating the dewpoint, and using PWM (pulse width modulation) to control the anti-sweat heaters based on specific algorithms for freezer doors. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
[3840.] [3841.] Several case studies have been performed that verify the accuracy of these savings. The
algorithms below are based on field-tested approximations of energy savings realized through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system.1
[3842.] [3843.] Low Temperature (Freezer) Door Heater Electric Defrost Control 4541.[3844.] [3845.] Algorithms [3846.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3847.] kWh Savings = (kWDH * 8,760) – ((40% * kWDH * 4,000) + (65% * kWDH * 4,760))[3848.] [3849.] kW Savings = kWDH * 46% * 75%[3850.] [3851.] Definition of Variables [3852.]
[3853.] kWDH = Total demand (kW) of the freezer door heaters, based on nameplate volts and amps.[3854.] 8,760 = Annual run hours of Freezer Door Heater before controls.[3855.] 40% = Percent of total run power of door heaters with controls providing maximum reduction.2
[3856.] 4,000 = Number of hours door heaters run at 40% power.[3857.] 65% = Percent of total run power of door heaters with controls providing minimum reduction.2
[3858.] 4,760 = Number of hours door heaters run at 65% power.[3859.] 46% = Freezer Door Heater off time.3
[3860.] 75% = Adjustment factor to account for diversity and coincidence at peak demand time.2
[3861.] [3862.] Medium Temperature (Cooler) Door Heater Control[3863.] [3864.] Algorithms [3865.] [3866.] kWh Savings = (kWDH * 8,760) – (60% * kWDH * 3,760)[3867.] [3868.] kW Savings = kWDH * 74% * 75%[3869.] [3870.] Definition of Variables [3871.]
[3872.] kWDH = Total demand (kW) of the cooler door heaters, based on nameplate volts and amps.[3873.] 8,760 = Annual run hours of Cooler Door Heater before controls.[3874.] 60% = Percent of total run power of door heaters with controls providing minimum reduction.2
[3875.] 3,760 = Number of hours door heaters run at 60% power.[3876.] 74% = Cooler Door Heater off time.3
[3877.] 75% = Adjustment factor to account for diversity and coincidence at peak demand time.2
[3878.] [3879.] Sources:
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3880.] [2.] Several case studies related to NRM’s Cooltrol system can be found at:
http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html
[3.] Estimated by NRM based on their experience of monitoring the equipment at various sites.[(1)] This value is an estimate by National Resource Management based on hundreds of
downloads of hours of use data from Door Heater controllers. This supported by 3rd Party Analysis conducted by Select Energy for NSTAR, “Cooler Control Measure Impact Spreadsheet Users’ Manual”, Page 5, March 9, 2004.[3881.]
[3882.] Aluminum Night Covers 4542.[3883.] [3884.] This measure is applicable to existing open-type refrigerated display cases where
considerable heat is lost through an opening that is directly exposed to ambient air. These retractable aluminum woven fabric covers provide a barrier between the contents of the case and the outside environment. They are employed during non-business hours to significantly reduce heat loss from these cases when contents need not be visible.
[3885.] [3886.] Savings approximations are based on the report, “Effects of the Low Emissivity
Shields on performance and Power use of a refrigerated display case”, by Southern California Edison, August 8, 1997. Southern California Edison (SCE) conducted this test at its state-of-the-art Refrigeration Technology and Test Center (RTTC), located in Irwindale, CA. The RTTC’s sophisticated instrumentation and data acquisition system provided detailed tracking of the refrigeration system’s critical temperature and pressure points during the test period. These readings were then utilized to quantify various heat transfer and power related parameters within the refrigeration cycle. The results of SCE’s test focused on three typical scenarios found mostly in supermarkets: low, medium and high temperature cases.[3887.]
[3888.] Algorithms [3889.]
[3890.] kWh Savings = W * H * F[3891.]
[3892.] Definition of Variables [3893.] [3894.] W = Width of protected opening in ft.[3895.] H = Hours per year covers are in place[3896.] F = Savings factor based on case temperature:
[3897.] Low temperature (-35F to -5F) F = 0.1 kW/ft[3898.] Medium temperature (0F to 30F) F = 0.06 kW/ft[3899.] High temperature (35F to 55F) F = 0.04 kW/ft
[3900.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3901.] Electric Defrost Control[3902.] [3903.] This measure is applicable to existing evaporator fans with a traditional electric
defrost mechanism. This control system overrides defrost of evaporator fans when unnecessary, reducing annual energy consumption. The estimates for savings take into account savings from reduced defrosts as well as the reduction in heat gain from the defrost process.
[3904.] [3905.] Independent Testing was performed by Intertek Testing Service on a Walk-in Freezer
that was retrofitted with Smart Electric Defrost capability. A baseline of 28 electric defrosts per week were established as the baseline for a two week period without the Smart Electric Defrost capability. With Smart Electric Defrost capability an average skip rate of 43.64% was observed for the following two week period.
[3906.] 4543.[3907.] [3908.] Algorithms [3909.] [3910.] Gross kWh Savings = kWh SavingsDefrost + kWh SavingsRH
[3911.] [3912.] kWh SavingsDefrost = KWDefrost * 0.667 * 4 * 365 * 35%[3913.] [3914.] kWh SavingsRH = kWh SavingsDefrost * 0.28 * 1.6[3915.] [3916.] Definition of Variables [3917.] [3918.] kWh SavingsDefrost = Savings due to reduction of defrosts[3919.] kWh SavingsRH = Savings due to reduction in refrigeration load[3920.] KWDefrost = Nameplate Load of Electric Defrost[3921.] 0.667 = Average Length of Electric Defrost in hours[3922.] 4 = Average Number of Electric Defrosts per day[3923.] 365 = Number of Days in Year[3924.] 35% = Average Number of Defrosts that will be eliminated in year[3925.] 0.28 = Conversion from kW to tons (Refrigeration)[3926.] 1.6 = Efficiency of typical refrigeration system in kW/ton1
[3927.] [3928.] Sources:
[(1)] Select Energy Services, Inc. Cooler Control Measure Impact Spreadsheet User’s Manual. 2004.[3929.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3930.] LED Lighting for Coolers and Freezers[3931.] This measure is applicable to existing walk-in and reach-in coolers and freezers with
non-LED lighting. LED lighting is not only more efficient, but also provides higher quality lighting for cooler and freezer displays as they are more suited for cold environments. In addition, LEDs have a longer operating life than fluorescents in cooler and freezer applications, which results in reduced life cycle costs. The estimated savings for this measure take into account both reduced wattage of replacement lighting and reduced refrigeration load from lighting heat loss.
[3932.] [3933.] Algorithms [3934.] [3935.] kWh Savings = (((WattsB - WattsLED)/1000) * H) * (1 + (0.28 * 1.6))[3936.] [3937.] kW Savings = ((WattsB - WattsLED)/1000) * (1 + (0.28 * 1.6))[3938.] [3939.] Definition of Variables [3940.] [3941.] WattsB = Baseline Lighting Wattage[3942.] WattsLED = LED Lighting Wattage[3943.] 1000 = Conversion from W to kW[3944.] H = Lighting Operating Hours[3945.] 0.28 = Conversion from kW to tons (Refrigeration)[3946.] 1.6 = Efficiency of typical refrigeration system in kW/ton45
[3947.] Novelty Cooler Shutoff 4544.[3948.] Energy Efficient Glass Doors on Open Refrigerated Cases 4545. ECM on Evaporator Fans 4546. Refrigerated Vending Machine Control 4547. Refrigerated Case LED Lighting (Prescriptive Lighting)
4548. Vending Machine Controls4549. This measures outlines the deemed savings for the installation of a gas-fired low
intensity infrared heating system in place of unit heater, furnace, or other standard efficiency equipment4550.
4551.[3949.] Algorithms4552.4553.[3950.] Electric Savings (kWh/yr) = kWv * Hrs * SF4554. 4555. Peak Demand Savings (kW) = kWv * SF4556.
45 Select Energy Services, Inc. Cooler Control Measure Impact Spreadsheet User’s Manual. 2004.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4557.[3951.] Definition of Variables4558. This measure is applicable to existing reach-in novelty coolers which run
continuously. The measure adds a control system feature to automatically shut off novelty coolers based on pre-set store operating hours. Based on programmed hours, the control mechanism shuts off the cooler at end of business, and begins operation on reduced cycles. Regular operation begins the following day an hour before start of business. The measurement of energy savings for this measure is based on algorithms with key variables provided by manufacturer data or prescribed herein.
[3952.] [3953.] Several case studies have been performed that verify the accuracy of these savings.
The algorithms below are based on field-tested approximations of energy savings realized through installation of National Resource Management Inc. (NRM)’s Cooltrol® energy management system. 1
[3954.] [3955.] Algorithms [3956.] [3957.] kWh Savings = (((AmpsNC * VoltsNC * (PhaseNC)1/2)/1000) * 0.85) * ((0.45 * ((CH – 1) * 91)) + (0.5 * ((CH – 1) * 274)))[3958.] [3959.] Definition of Variables [3960.]
4559.[3961.] kWv = Connected kW of equipment4560. Hrs = Operating hours of equipment4561. SF = Percent savings factor of equipment
4562. Summary of Assumptions 4563.
4564.Varia
ble
4565. Type 4566. Value
4567. S ourc
e
4568.kWv
4569. Refrigerated beverage vending machine
4570. Non-refrigerated snack vending machine
4571. Glass front refrigerated coolers
4572. 0.4 kW
4573. 0.085 kW
4574. 0.46 kW
4575. 1
4576.Hrs
4577. Hours of operating of vending machine
4578. Variable,
default 8,760 hours
4579. A pplication
4580.SF
4581. Refrigerated beverage vending machine
4582. Non-refrigerated snack
4584. 46%4585. 46%4586. 30%
4587. 1
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
vending machine4583. Glass front refrigerated coolers
4588. 4589. AmpsNC = Nameplate Amps of Novelty Cooler[3962.] VoltsNC = Nameplate Volts of Novelty Cooler[3963.] PhaseNC = Phase of Novelty Cooler[3964.] 0.85 = Novelty Cooler power factor2
[3965.] 0.45 = Duty cycle during winter month nights3
[3966.] CH = Closed Store hours[3967.] 91 = Number of days in winter months[3968.] 0.5 = Duty cycle during non-winter month nights3
[3969.] 274 = Number of days in non-winter months[3970.] [3971.] Sources :
4590.[3972.]
[(1)] Several case studies related to NRM’s Cooltrol system can be found at: http://www.nrminc.com/national_resource_management_case_studies_cooltrol_cooler_control_systems.html
[2.] Estimated by NRM based on their experience of monitoring the equipment at various sites.[1.] Massachusetts Technical Reference Manual, October 2015.
(1) Duty Cycles are consistent with 3rd Party study done by Select Energy for NSTAR“Cooler Control Measure Impact Spreadsheet Users’ Manual”, page 5, March 9, 2004.[3973.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3974.] Gas Space and Water Heating Measures4591.[3975.] Replacement of existing gas, oil, and propane water heaters with high
efficiency units is a proposed measure under the C&I Energy Efficienct Construction GasHVAC Systems Protocols. The Direct Install savings protocol will be the same as previously stated in this document with the baselines designed to reflect current market practices, which in this case reflect ASHRAE 90.1-2007. These tables are included in the C&I Protocol.
4592. Gas Space Heating Measures
[3976.] Gas Furnaces and Boilers
[3977.] Replacement of existing gas, oil, andor propane furnaces and boilers with high efficiency units is a proposed measure under the C&I Energy Efficienct Direct Install Program. (See C&I Construction GasHVAC SystemsGas Protocols.). The Direct Install savings protocol will be the same as previously stated in this document with the exception of the assumption for baseline efficiency.
4593. Efficiency baselines are designed to reflect current market practices, which in this case reflect ASHRAE 90.1-2007. For the Direct Install program, the following values will be used for the variable identified as Effb.AFUEb. These age-based efficiencies are used in estimating savings associated with the Direct Install Program because as an early replacement program, equipment is replaced as a direct result of the program.
4594.[3978.] 4595.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4596. Baseline Boiler Efficiencies (Effb)[3979.] Default Values for Mechanical System Efficiencies – Age-Based
[3980.] Boiler TypeSystem
4597.[3981.] Size Categor
y4598. (kBt
u input)Units
[3982.] Standard 90.1-200
7Pre-1992
[3983.] Hot Water – Gas firedor
Propane
4599.[3984.] < 300
4600. >
4602. 80% AFUE
4603. 75% 4605. Hot Water
– Oil fired4606. <
3004607. >
4609. 80% AFUE
4610. 78% 4612. Steam –
Gas firedor 4613.[3985.]
< 3004614. 75%
AFUE4615.[3986.] Steam, all except
4616. > 300 and
4617. 75% Et4618. Steam,
natural draft4619. >
300 and 4620. 75%
Et4621. Steam – Oil firedFurnace or
Boiler
4622.[3987.] < 300
4623. >
4625. 80% AFUE
4626. 78% 4628.[3988.] Source: 2006 Mortgage Industry National Home Energy Ratings Systems Standards, Table 303.7.1(3) Default Values for Mechanical System Efficiencies (Age-based), RESNET.
4629.[3989.] 4630.[3990.] NOTE – The age-based efficiencies in the above table have been interpolated
from RESNET standards and current baseline figures utilized in NJ C&I Energy Efficiency Rebate programs. With no equivalent resource available specific to small commercial equipment, these combined resources reflect the closest approximation to typical efficiencies of mechanical equipment present in Direct Install project facilities. The Direct Install program is targeted towards small commercial customers. As such, eligible equipment must not exceed a maximum capacity determined to be commonplace in the small C&I sector. In most cases, these capacity ranges correlate well with equipment certified by AHRI under the designation “Residential”.
4631.[3991.] Small Commercial Boilers [Inactive 2017, Not Reviewed]4632.[3992.] This section will apply only for boilers that are closed loop and for space
heating. 4633.[3993.] 4634.[3994.] For Boilers that are under 5000 MBtuH use the calculator from the Federal
Energy Management Program at: http://www1.eere.energy.gov/femp/technologies/eep_boilers_calc.html
4635.[3995.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[3996.] Gas, Oil, and Propane FurnacesInfrared Heating
[3997.] Replacement of existing atmospherically vented heating with gas, oil, and or propane infrared heating is an available measure under the Direct Install Program. (See C&I Construction Gas Protocols).
[3998.] Gas Water Heating[3999.]
[4000.] Replacement of existing gas furnaces and boilers with gas high efficiency units is a proposed measure under the Direct Install Program. (See C&I Energy Efficienct Construction Gas HVAC Systems Protocols.). The Direct Install savings protocol will be the same as previously stated in this document with the exception of the assumption for baseline efficiency.
4636. Efficiency baselines are designed to reflect current market practices, which in this case reflect ASHRAE 90.1-2007. For the Direct Install program, the following values will be used for the variable identified as Effb.EFFb. These age-based efficiencies are used in estimating savings associated with the Direct Install Program because as an early replacement program, equipment is replaced as a direct result of the program.
4637.[4001.] [4002.] Baseline FurnaceDefault Values for Water Heating System Efficiencies (Effb)–
Age-Based
[4003.] FurnaceWater
Heater Type
4638.[4004.] Size Categ
ory4639. (k
Btu input)Units
[4005.] Standard 90.1-200
7Pre-1992
4640.[4006.] Gas Fired
4641. < 225
4643.[4007.] 78% AFUE4645.[4008.] Oil
Fired4646. <
2254648.[4009.] 78% AFUE[4010.] Ele
ctric[4011.] EF
[4012.] 0.87
[4013.] 0.88
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4014.] Source: 2006 Mortgage Industry National Home Energy Ratings Systems Standards, Table 303.7.1(3) Default Values for Mechanical System Efficiencies (Age-based), RESNET.
[4015.]
[4016.] NOTE – The age-based efficiencies in the above table have been interpolated from RESNET standards and current baseline figures utilized in NJ C&I Energy Efficiency Rebate programs. With no equivalent resource available specific to small commercial equipment, these combined resources reflect the closest approximation to typical efficiencies of mechanical equipment present in Direct Install project facilities. The Direct Install program is targeted towards small commercial customers. As such, eligible equipment must not exceed a maximum capacity determined to be commonplace in the small C&I sector. In most cases, these capacity ranges correlate well with equipment certified by AHRI under the designation “Residential”.
[4017.]
[4018.] Food Service Measures
[4019.]
[4020.] Energy efficient electric or natural gas cooking equipment of the following listed types utilized in commercial food service applications which have performance rated in accordance with the listed ASTM standards:
[4021.] Infrared Heating4650. Replacement of existing atmospherically vented heating with infrared heating is is a
proposed measure under Commercial and Industrial Energy Efficient Construction. Because this is a deemed savings measure the protocol will be exactly the same as previously stated in this document.
4651. Programmable Thermostats
4652. This measure provides savings algorithms for programmable thermostats installed through the direct install program in commercial buildings. The baseline for this measure is manual thermostats that require occupant adjustment to change the space temperature. Non-communicating programmable thermostats achieve energy savings over manual thermostats by automatically setting temperatures back in the winter, or up in the summer, per a factory default schedule, or a user modified schedule. Setback/set up schedules achieve heating fuel savings in the winter, and cooling electric savings in the summer.
4653. The savings factors for this measure come from the Michigan Energy Measures Database (MEMD), which shows deemed cooling and heating savings per 1,000 square feet of building space. The MEMD savings values for programmable thermostats were determined through measurement and verification of installed thermostats in a variety of commercial building types. For this measure, values for the Detroit airport locale are used
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
because the ambient temperatures are closest to those for the New Jersey locale, and results are averaged across HVAC equipment types.
4654. There are no peak demand savings for this measure, and motel and auto repair space types are excluded from this measure. Electric combination and convection ovens – ASTM 1639-F
Gas combination and convection ovens – ASTM 1639-F
Gas conveyor and rack ovens – ASTM 1817-F
Electric and gas small vat fryers – ASTM 1361-F
Electric and gas large vat fryers – ASTM 2144-F
Electric and gas steamers – ASTM 1484-F
Electric and gas griddles – ASTM 1275-F
Hot food holding cabinets – ATM F2140-11
[4022.] [4023.] Electric and Gas Combination Oven/Steamer[4024.] [4025.] The measurement of energy savings for this measure is based on algorithms with key
variables provided by manufacturer data or prescribed herein.[4026.] 4655.[4027.] Algorithms 4656.[4028.] 4657.[4029.] Fuel Savings (MMBtu/yr) = SQFT1000 * SFheat
4658. 4659. Annual Energy Savings (kWh/yr) = SQFT1000 * SFcool or Therms) = D*(Ep + Eic + Eis +
Ecc + Ecs)4660.[4030.] [4031.] Demand Savings (kW) = kWh Savings/(D*H)[4032.] [4033.] Preheat Savings†: Ep = P*(PEb – PEq)[4034.] [4035.] Convection Mode Idle Savings†: Eic = (Icb – Icq)*((H – (P*Pt)) – (Icb/PCcb – Icq/PCcq)*Lbs)*(1 – St)[4036.] [4037.] Steam Mode Idle Savings†: Eis = (Isb – Isq)*((H – (P*Pt)) – (Isb/PCsb – Isq/PCsq)*Lbs)*St
[4038.] [4039.] Convection Mode Cooking Savings: Ecc = Lbs*(1-St)*Heatc*(1/Effcb – 1/Effcq)/C[4040.] [4041.] Steam Mode Cooking Savings: Ecs = Lbs*St*Heats*(1/Effsb – 1/Effsq)/C[4042.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4043.] † - For gas equipment, convert these intermediate values to therms by dividing the result by 100,000 Btu/therm
[4044.] [4045.] Definition of Variables (See tables of values below for more information) [4046.] SQFT1000D = Operating Days per Year[4047.] P = Number of thousandsPreheats per Day[4048.] PEb = Baseline Equipment Preheat Energy[4049.] PEq = Qualifying Equipment Preheat Energy[4050.] Icb = Baseline Equipment Convection Mode Idle Energy Rate[4051.] Icq = Qualifying Equipment Convection Mode Idle Energy Rate[4052.] H = Daily Operating Hours[4053.] Pt = Preheat Duration[4054.] PCcb = Baseline Equipment Convection Mode Production Capacity[4055.] PCcq = Qualifying Equipment Convection Mode Production Capacity[4056.] Lbs = Total Daily Food Production[4057.] St = Percentage of Time in Steam Mode[4058.] Isb = Baseline Equipment Steam Mode Idle Energy Rate[4059.] Isq = Qualifying Equipment Steam Mode Idle Energy Rate[4060.] PCsb = Baseline Equipment Steam Mode Production Capacity[4061.] PCsq = Qualifying Equipment Steam Mode Production Capacity[4062.] Heatc = Convection Mode Heat to Food[4063.] Effcb = Baseline Equipment Convection Mode Cooking Efficiency[4064.] Effcq = Qualifying Equipment Convection Mode Cooking Efficiency[4065.] C = Conversion Factor from Btu to kWh or Therms[4066.] Heats = Steam Mode Heat to Food[4067.] Effsb = Baseline Equipment Steam Mode Cooking Efficiency[4068.] Effsq = Qualifying Equipment Steam Mode Cooking Efficiency[4069.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4070.]
<15 Pans 15-28 Pans >28 Pans <15 Pans 15-28 Pans >28 PansD - Operating Days per Year Table 3 Table 3 Table 3 Table 3 Table 3 Table 3P - Number of Preheats per Day 1 1 1 1 1 1PEb & PEq - Preheat Energy (kWh) 3.00 3.75 5.63 1.50 2.00 3.00Icb & Icq - Convection Mode Idle Energy Rate (kW) 3.00 3.75 5.25 Application Application ApplicationH - Operating Hours per Day Table 3 Table 3 Table 3 Table 3 Table 3 Table 3Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25 0.25 0.25PCcb & PCcq - Convection Mode Prod. Capacity (lbs/hr) 80 100 275 100 125 325Lbs - Total Daily Food Production (lbs) 200 250 400 200 250 400St - Percentage of Time in Steam Mode 50% 50% 50% 50% 50% 50%Isb & Isq - Steam Mode Idle Energy Rate (kW) 10.0 12.5 18.0 Application Application ApplicationPCsb & PCsq - Steam Mode Prod. Capacity (lbs/hr) 100 150 350 120 200 400Heatc - Convection Heat to Food (Btu/lb) 250 250 250 250 250 250Effcb & Effcq - Convection Mode Cooking Efficiency 65% 65% 65% Application Application ApplicationC - Btu/kWh 3,412 3,412 3,412 3,412 3,412 3,412Heats - Steam Heat to Food (Btu/lb) 105 105 105 105 105 105Effsb & Effsq - Steam Mode Cooking Efficiency 40% 40% 40% Application Application Application
Baseline QualifyingTable 1: Electric Combination Oven/Steamers
Variable
[4071.] [4072.]
<15 Pans 15-28 Pans >28 Pans <15 Pans 15-28 Pans >28 PansD - Operating Days per Year Table 3 Table 3 Table 3 Table 3 Table 3 Table 3P - Number of Preheats per Day 1 1 1 1 1 1PEb & PEq - Preheat Energy (Btu) 18,000 22,000 32,000 13,000 16,000 24,000Icb & Icq - Convection Mode Idle Energy Rate (Btu/h) 15,000 20,000 30,000 Application Application ApplicationH - Operating Hours per Day Table 3 Table 3 Table 3 Table 3 Table 3 Table 3Pt - Preheat Duration (h) 0.25 0.25 0.25 0.25 0.25 0.25PCcb & PCcq - Convection Mode Prod. Capacity (lbs/h) 80 100 275 100 125 325Lbs - Total Daily Food Production (lbs) 200 250 400 200 250 400St - Percentage of Time in Steam Mode 50% 50% 50% 50% 50% 50%Isb & Isq - Steam Mode Idle Energy Rate (kW) 45,000 60,000 80,000 Application Application ApplicationPCsb & PCsq - Steam Mode Prod. Capacity (lbs/h) 100 150 350 120 200 400Heatc - Convection Heat to Food (Btu/lb) 250 250 250 250 250 250Effcb & Effcq - Convection Mode Cooking Efficiency 35% 35% 35% Application Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000 100,000 100,000Heats - Steam Heat to Food (Btu/lb) 105 105 105 105 105 105Effsb & Effsq - Steam Mode Cooking Efficiency 20% 20% 20% Application Application Application
Baseline QualifyingTable 2: Gas Combination Oven/Steamers
Variable
[4073.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4074.]
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 3: Operating Days/Hours by Building Type
[4075.] [4076.] Sources:[4077.] Savings algorithm, baseline values, assumed values and lifetimes developed from
information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspicessquare feet of building space46the California Public Utility Commission.
46 For example, a 5,000 ft2 building would have a SQFT1000 value of 5
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4078.] Electric and Gas Convection Ovens, Gas Conveyor and Rack Ovens, Steamers, Fryers, and Griddles
[4079.] [4080.] The measurement of energy savings for these measures are based on algorithms with
key variables provided by manufacturer data or prescribed herein.[4081.] [4082.] Algorithms [4083.] 4661.[4084.] SFheat = Heating savings factor (MMBtu per 1,000 ft2 of building space)4662. SFcool = Cooling savings factorAnnual Energy Savings (kWh or Therms) = D * (Ep +
Ei + Ec)[4085.] [4086.] Demand Savings (kW) = kWh Savings / (D * H)[4087.] [4088.] Preheat Savings†: Ep = P * (PEb – PEq)[4089.] [4090.] Idle Savings†: Ei = (Ib – Iq) * ((H – (P*Pt)) – (Ib/PCb – Iq/PCq) * Lbs)[4091.] [4092.] Cooking Savings: Ec = Lbs * Heat * (1/Effb – per 1/Effq) / C[4093.] [4094.] † - For gas equipment, convert these intermediate values to therms by dividing the
result by 100,000 Btu/therm[4095.] [4096.] Definition,000 ft2 of building spaceVariables (See tables of values below for more
information)4663.[4097.] [4098.] SummaryD = Operating Days per Year[4099.] P = Number of Inputs Preheats per Day [4100.] PEb = Baseline Equipment Preheat Energy[4101.] PEq = Qualifying Equipment Preheat Energy[4102.] Ib = Baseline Equipment Idle Energy Rate[4103.] Iq = Qualifying Equipment Idle Energy Rate[4104.] H = Daily Operating Hours[4105.] Pt = Preheat Duration[4106.] PCb = Baseline Equipment Production Capacity[4107.] PCq = Qualifying Equipment Production Capacity[4108.] Lbs = Total Daily Food Production[4109.] Heat = Heat to Food[4110.] Effb = Baseline Equipment Convection Mode Cooking Efficiency[4111.] Effq = Qualifying Equipment Convection Mode Cooking Efficiency[4112.] C = Conversion Factor from Btu to kWh or Therms[4113.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4114.]
Full Size Half Size Full Size Half SizeD - Operating Days per Year Table 11 Table 11 Table 11 Table 11P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (kWh) 1.50 1.00 1.00 0.90Ib & Iq - Idle Energy Rate (kW) 2.00 1.50 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 70 45 82 53Lbs - Total Daily Food Production (lbs) 100 100 100 100Heat - Heat to Food (Btu/lb) 250 250 250 250Effb & Effq - Heavy Load Cooking Efficiency 65% 65% Application ApplicationC - Btu/kWh 3,412 3,412 3,412 3,412
Table 1: Electric Convection Ovens
VariableBaseline Qualifying
[4115.]
[4116.]
Full Size Half Size Full Size Half SizeD - Operating Days per Year Table 11 Table 11 Table 11 Table 11P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (Btu) 19,000 13,000 11,000 7,500Ib & Iq - Idle Energy Rate (Btu/h) 18,000 12,000 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 70 45 83 55Lbs - Total Daily Food Production (lbs) 100 100 100 100Heat - Heat to Food (Btu/lb) 250 250 250 250Effb & Effq - Heavy Load Cooking Efficiency 30% 30% Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000
Table 2: Gas Convection Ovens
VariableBaseline Qualifying
[4117.]
[4118.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 35,000 18,000Ib & Iq - Idle Energy Rate (Btu/hr) 70,000 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 114 167Lbs - Total Daily Food Production (lbs) 190 190Heat - Heat to Food (Btu/lb) 250 250Effb & Effq - Heavy Load Cooking Efficiency 20% ApplicationC - Btu/Therm 100,000 100,000
Table 3: Gas Conveyor Ovens
[4119.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4120.]
Double Rack Single Rack Double Rack Single RackD - Operating Days per Year Table 11 Table 11 Table 5 Table 5P - Number of Preheats per Day 1 1 1 1PEb & PEq - Preheat Energy (Btu) 100,000 50,000 85,000 44,000Ib & Iq - Idle Energy Rate (Btu/h) 65,000 43,000 Application ApplicationH - Operating Hours per Day Table 11 Table 11 Table 5 Table 5Pt - Preheat Duration (hrs) 0.33 0.33 0.33 0.33PCb & PCq - Production Capacity (lbs/hr) 250 130 280 140Lbs - Total Daily Food Production (lbs) 1200 600 1200 600Heat - Heat to Food (Btu/lb) 235 235 235 235Effb & Effq - Heavy Load Cooking Efficiency 30% 30% Application ApplicationC - Btu/Therm 100,000 100,000 100,000 100,000
Table 4: Gas Rack Ovens
VariableBaseline Qualifying
[4121.]
[4122.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 1.50 1.50Ib & Iq - Idle Energy Rate (kW) 0.167 x No. of Pans ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 11.7 x No. of Pans 14.7 x No. of PansLbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 105 105Effb & Effq - Heavy Load Cooking Efficiency 26% ApplicationC - Btu/kWh 3,412 3,412
Table 5: Electric Steamers
[4123.]
[4124.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 20,000 9,000Ib & Iq - Idle Energy Rate (Btu/h) 2,500 x No. of Pans ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 23.3 x No. of Pans 20.8 x No. of PansLbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 105 105Effb & Effq - Heavy Load Cooking Efficiency 15% ApplicationC - Btu/Therm 100,000 100,000
Table 6: Gas Steamers
[4125.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4126.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 2.40 1.90Ib & Iq - Idle Energy Rate (kW) 1.2 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 71 71Lbs - Total Daily Food Production (lbs) 150 150Heat - Heat to Food (Btu/lb) 570 570Effb & Effq - Heavy Load Cooking Efficiency 75% ApplicationC - Btu/kWh 3,412 3,412
Table 7: Electric Fryers
[4127.]
[4128.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 18,500 16,000Ib & Iq - Idle Energy Rate (Btu/h) 17,000 ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 75 75Lbs - Total Daily Food Production (lbs) 150 150Heat - Heat to Food (Btu/lb) 570 570Effb & Effq - Heavy Load Cooking Efficiency 35% ApplicationC - Btu/Therm 100,000 100,000
Table 8: Gas Fryers
[4129.]
[4130.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (kWh) 1.3 x Griddle Width (ft) 0.7 x Griddle Width (ft)Ib & Iq - Idle Energy Rate (kW) 0.8 x Griddle Width (ft) ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 11.7 x Griddle Width (ft) 13.3 x Griddle Width (ft)Lbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 475 475Effb & Effq - Heavy Load Cooking Efficiency 60% ApplicationC - Btu/kWh 3,412 3,412
Table 9: Electric Griddles
[4131.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4132.]
Variable Baseline QualifyingD - Operating Days per Year Table 11 Table 11P - Number of Preheats per Day 1 1PEb & PEq - Preheat Energy (Btu) 7,000 x Griddle Width (ft) 5,000 x Griddle Width (ft)Ib & Iq - Idle Energy Rate (Btu/h) 7,000 x Griddle Width (ft) ApplicationH - Operating Hours per Day Table 11 Table 11Pt - Preheat Duration (hrs) 0.25 0.25PCb & PCq - Production Capacity (lbs/hr) 8.3 x Griddle Width (ft) 15 x Griddle Width (ft)Lbs - Total Daily Food Production (lbs) 100 100Heat - Heat to Food (Btu/lb) 475 475Effb & Effq - Heavy Load Cooking Efficiency 30% ApplicationC - Btu/Therm 100,000 100,000
Table 10: Gas Griddles
[4133.]
[4134.]
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 11: Operating Days/Hours by Building Type
[4135.] [4136.] Sources:[4137.] Savings algorithm, baseline values, assumed values and lifetimes developed from
information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
[4138.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4139.] Insulated Food Holding Cabinets[4140.] [4141.] The measurement of energy savings for this measure is based on algorithms with key
variables provided by manufacturer data or prescribed herein.[4142.] [4143.] Algorithms [4144.] [4145.] Annual Energy Savings (kWh) = D * H * (Ib – Iq)[4146.] [4147.] Demand Savings (kW) = Ib – Iq
[4148.] [4149.] Definition of Variables (See tables of values below for more information) [4150.] [4151.] D = Operating Days per Year[4152.] H = Daily Operating Hours[4153.] Ib = Baseline Equipment Idle Energy Rate[4154.] Iq = Qualifying Equipment Idle Energy Rate[4155.] [4156.]
Full Size 3/4 Size 1/2 Size Full Size 3/4 Size 1/2 SizeD - Operating Days per Year Table 2 Table 2 Table 2 Table 2 Table 2 Table 2Ib & Iq - Idle Energy Rate (kW) 1.00 0.69 0.38 Application Application ApplicationH - Operating Hours per Day Table 2 Table 2 Table 2 Table 2 Table 2 Table 2
Table 1: Insulated Food Holding Cabinets
VariableBaseline Qualifying
[4157.]
[4158.]
Building Type Days/Year Hours/DayEducation - Primary School 180 8Education - Secondary School 210 11Education - Community College 237 16Education - University 192 16Grocery 364 16Medical - Hospital 364 24Medical - Clinic 351 12Lodging Hotel (Guest Rooms) 229 5Lodging Motel 364 24Manufacturing - Light Industrial 330 13Office - Large 234 12Office - Small 234 12Restaurant - Sit-Down 364 12Restaurant - Fast-Food 364 17Retail - 3-Story Large 355 12Retail - Single-Story Large 364 12Retail - Small 364 11Storage Conditioned 330 13Storage Heated or Unconditioned 330 13Warehouse 325 12Average = Miscellaneous 303 14
Table 2: Operating Days/Hours by Building Type
[4159.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4664.[4160.] [4161.] Sources:[4162.] Savings algorithm, baseline values, assumed values and lifetimes developed from
information on the Food Service Technology Center program’s website, www.fishnick.com, by Fisher-Nickel, Inc. and funded by California utility customers and administered by Pacific Gas and Electric Company under the auspices of the California Public Utility Commission.
[1.]
[4163.] Occupancy Controlled Thermostats[4164.] [4165.] The program has received a large amount of custom electric applications for the
installation of Occupancy Controlled Thermostats in hotels, motels, and, most recently, university dormitories. Due to the number of applications, consistent incentive amounts ($75 per thermostat) and predictable savings of the technology TRC recommends that a prescriptive application be created for this technology.
[4166.] [4167.] Standard practice today is thermostats which are manually controlled by occupants to
regulate temperature within a facility. An occupancy controlled thermostat is a thermostat paired with a sensor and/or door detector to identify movement and determine if a room is occupied or unoccupied. If occupancy is sensed by the sensor, the thermostat goes into an occupied mode (i.e. programmed setpoint). If a pre-programmed time frame elapses (i.e. 30 minutes) and no occupancy is sensed during that time, the thermostat goes into an unoccupied mode (e.g., setback setpoint or off) until occupancy is sensed again. This type of thermostat is often used in hotels to conserve energy.
[4168.] [4169.] The occupancy controlled thermostat reduces the consumption of electricity and/or
gas by requiring less heating and/or cooling when a room or a facility is vacant or unoccupied.
4665.[4170.] [4171.] Algorithms [4172.] [4173.] Cooling Energy Savings (kWh) = (((Tc * (H+5) + Sc * (168 - (H+5)))/168) Tc) * (Pc * Caphp * 12 * EFLHc/EERhp)[4174.] [4175.] Heating Energy Savings (kWh) = (((Th * (H+5) + Sh * (168 - (H+5)))/168)-Th) * (Ph * Caphp * 12 * EFLHh/EERhp)[4176.] [4177.] Heating Energy Savings (Therms) = (Th - (Th * (H+5) + Sh * (168 - (H+5)))/168) * (Ph * Caph * EFLHh/AFUEh/100,000)[4178.] [4179.] Definition of Variables
[4180.] [4181.] Th = Heating Season Facility Temp. (°F) [4182.] Tc = Cooling Season Facility Temp. (°F) [4183.] Sh = Heating Season Setback Temp. (°F)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4184.] Sc = Cooling Season Setup Temp. (°F) [4185.] H = Weekly Occupied Hours[4186.] Caphp = Connected load capacity of heat pump/AC (Tons) – Provided on Application.[4187.] Caph = Connected heating load capacity (Btu/hr) – Provided on Application.[4188.] EFLHc = Equivalent full load cooling hours [4189.] EFLHh = Equivalent full load heating hours [4190.] Ph = Heating season percent savings per degree setback [4191.] Pc = Cooling season percent savings per degree setup [4192.] AFUEh = Heating equipment efficiency – Provided on Application.[4193.] EERhp = Heat pump/AC equipment efficiency – Provided on Application[4194.] 12 = Conversion factor from Tons to kBtu/hr to acquire consumption in kWh.[4195.] 168 = Hours per week.[4196.] 5 = Assumed weekly hours for setback/setup adjustment period (based on 1
setback/setup per day, 5 days per week).[4197.] [4198.] Occupancy Controlled Thermostats
4666. Programmable Thermostat Assumptions4667. [4199.]
[4200.] Component
4668.[4201.] Type
4669.[4202.] Value 4670.[4203.] Source
[4204.] SQFT1000Th
4671.[4205.] Variable
4672.[4206.] Customer specified
4673.[4207.] Application
[4208.] Tc [4209.] Vari
able
[4210.] [4211.] Application
[4212.] Sh [4213.] Fixe
d
[4214.] Th-5° [4215.]
[4216.] Sc [4217.] Fixe
d
[4218.] Tc+5° [4219.]
[4220.] H [4221.] Vari
able
[4222.] [4223.] Application; Default of 56 hrs/week
[4224.] Caphp [4225.] Vari
abl
[4226.] [4227.] Application
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4200.] Component
4668.[4201.] Type
4669.[4202.] Value 4670.[4203.] Source
e[4228.] Caph [4229.]
Variable
[4230.] [4231.] Application
[4232.] SFheatEFLHc 4674.[4233.] Fixed
[4234.] 1.68 MMBtu / 1,000 ft2 381
4675.[4235.] 1
[4236.] SFcoolEFLHh4676.[4237.]
Fixed[4238.] 74.7 kWh /
1,000 ft2 900[4239.] 1
PSE&G[4240.] Ph [4241.]
Fixed
[4242.] 3% [4243.] 2
[4244.] Pc [4245.] Fixe
d
[4246.] 6% [4247.] 2
[4248.] AFUEh
[4249.] Vari
able
[4250.] [4251.] Application
[4252.] EERhp [4253.] Vari
able
[4254.] [4255.] Application
[4256.] [4257.] Sources : [1.] JCP&L metered data from 1995-1999[1.] ENERGY STAR Products websiteMichigan Public Service Commission. 2017 Michigan
Energy Measures Database (MEMD) with Weather Sensitive Weighting Tool. Available for download at: http://www.michigan.gov/mpsc/0,4639,7-159-52495_55129---,00.html
4677. Boiler Reset Controls
4678. The following algorithm detail savings for installation of boiler reset control on commercial boilers. Energy savings are realized through a better control on boiler water temperature. Through the use of software settings, boiler reset controls use outside or return water temperature to control boiler firing and in turn the boiler water temperature.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4679. The input values are based on data supplied by the utilities and customer information on the application form, confirmed with manufacturer data. Unit savings are deemed based on study results.
4680. Algorithms
4681. Fuel Savings (MMBtu/yr) = (% Savings) * (EFLHh * kBtuin/hr) / 1,000 kBtu/MMBtu4682. 4683. Definition of Variables 4684. % Savings = Estimated percentage reduction in heating load due to boiler reset controls
(5%)4685. EFLHh = The Equivalent Full Load Hours of operation for the average unit during the heating season4686. kBtuin/hr = Input capacity of boiler
4687. 4688. Summary of Inputs 4689.
4690. Boiler Reset Control Assumptions4691. Compon
ent4692.Type 4693. Value 4694. Sourc
e4695. %
Savings4696.Fixed 4697. 5% 4698. 1
4699. EFLHh
4700.Varia
ble
4701. See Table 1 4702. 2 47
4703. kBtuin/hr
4704.Varia
ble
4705. 4706. Application
4707. 4708. Small Commercial EFLHh
4709. Building 4710. EFLHh
4711. Assembly 4712. 6034713. Auto Repair 4714. 19104715. Fast Food
Restaurant4716. 813
4717. Full Service Restaurant
4718. 821
4719. Light Industrial
4720. 714
4721. Motel 4722. 6194723. Primary 4724. 840
47 From NY TRM 2016, for NYC due to proximity to NJ; for small commercial and large commercial buildings
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4709. Building 4710. EFLHh
School4725. Religious
Worship4726. 722
4727. Small Office
4728. 431
4729. Small Retail 4730. 5454731. Warehouse 4732. 452
4733. Other 4734. 6814735. 4736. Sources
1. GDS Associates, Inc. Natural Gas Energy Efficiency Potential in Massachusetts, 2009, p. 38 Table 6-4.
2. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, Appendix G – Equivalent Full-Load Hours (EFLH), For Heating and Cooling, p. 444. Derived from DOE2.2 simulations reflecting a range of building types and climate zones.3. [4258.]
[4259.] Dual Enthalpy Economizers4737.[4260.] Installation of Dual Enthalpy Economizers is a proposed measure under the
Commercial and Industrial Energy Efficient Construction. Because there is no baseline assumption included in the protocols for this measure, the savings protocol will be exactly the same as previously stated in this document.
[4261.] Dual enthalpy economizers are used to control a ventilation system’s outside air intake in order to reduce a facility’s total cooling load. An economizer monitors the outside air to ensure that its temperature (sensible heat) and humidity (latent heat) are low enough to utilize outside air to provide cooling in place of the cooling system’s compressor. This reduces the demand on the cooling system, lowering its usage hours, saving energy.
[4262.]
[4263.] The measurement of energy savings associated with dual enthalpy economizers is based on algorithms with key variables provided through DOE-2 simulation modeling and ClimateQuest’s economizer savings calculator. Savings are calculated per ton of connected cooling load. The baseline conditions are fixed damper for equipment under 5.4 tons and dry bulb economizer otherwise.
[4264.] [4265.] Algorithms [4266.] [4267.] Energy Savings (kWh) = OTF * SF * Cap / Eff[4268.] [4269.] Demand Savings (kW) = Savings/Operating Hours[4270.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4271.] Definition of Variables [4272.]
[4273.] OTF = Operational Testing Factor [4274.] [4275.] SF = Approximate savings factor based on regional temperature bin data (assume
4576 for equipment under 5.4 tons where a fixed damper is assumed for the baseline and 3318 for larger equipment where a dry bulb economizer is assumed for the baseline). (Units for savings factor are in kWh x rated EER per ton of cooling or kWh*EER/Ton)
[4276.] [4277.] Cap = Capacity of connected cooling load (tons) [4278.] [4279.] Eff = Cooling equipment energy efficiency ratio (EER) [4280.] [4281.] Operating Hours = 4,438 = Approximate number of economizer operating hours
[4282.] [4283.] Duel Enthalpy Economizers
[4284.] 4738.[4285.] [4286.] Sources:[2.] DOE-2 Simulation Modeling[3.] ClimateQuest Economizer Savings Calculator
[4287.]
[4288.] Electronic Fuel-Use Economizers (Boilers, Furnaces, AC)[4289.] These devices are microprocessor-based fuel-saving controls for commercial HVAC.
They optimize energy consumption by adjusting burner or compressor run patterns to match the system’s load. They can be used to control gas or oil consumption for any type of boiler or forced air furnace system. There are also fuel use economizers available that control the electric consumption for commercial air conditioning and refrigeration units by optimizing compressor cycles to maximize energy efficiency.1
[4290.] [4291.] A recent study of Fuel-use economizer controls by the New York State Energy
Research and Development Authority (NYSERDA) in conjunction with Brookhaven National Laboratories (BNL) found that the typical energy savings for these devices generally varies between 10.08% and 19.15%, when used under normal operating conditions and normalized for typical annual degree-days in the New York metro area.2 The NYSERDA study tested at each of the different models of fuel-use economizers manufactured by Intellidyne, LLC, (under the brand name IntelliCon). Operational data was recorded for various commercial heating, cooling, and refrigeration systems (of different sizes and fuel types) with and without the IntelliCon fuel-use economizers added. The average energy savings across all system and fuel types and operational conditions was found to be 13%. Another study of IntelliCon fuel-use economizers by Consolidated Edison, Inc. (ConEd) found a similar range of savings for the devices when the devices were studied as a control option for commercial refrigeration units at supermarkets in New York City and the surrounding area.3
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4292.] [4293.] Test results in both studies showed a very good payback for the devices across all
applications studied. However, no discernable pattern was evident to determine which installations are most likely to yield the highest savings. Though actual savings will vary somewhat from project to project, it is reasonable to assume that program-wide energy savings across all approved fuel-use economizers measures will likely be close to the average savings found in the NYSERDA study. Annual energy savings for each approved fuel-use economizer installation (for any IntelliCon brand or equivalent devices) can be estimated as simply 13% of the expected annual energy usage for the HVAC (or refrigeration) system without the device.
[4294.] [4295.] Algorithms [4296.] [4297.] Installation of variable Fuel Use Economizers is a proposed measure under the
Commercial and Industrial Energy Efficient Construction. Because there is no baseline assumption included in the protocols for this measure, the savings protocol will be exactly the same as previously stated in this document.Electric
4739. Demand-Controlled Ventilation Using CO2 Sensors4740. Maintaining acceptable air quality requires standard ventilation systems designers to
determine ventilation rates based on maximum estimated occupancy levels and published CFM/occupant requirements. During low occupancy periods, this approach results in higher ventilation rates than are required to maintain acceptable levels of air quality. This excess ventilation air must be conditioned and therefore results in wasted energy.
4741. Building occupants exhale CO2, and the CO2 concentration in the air increases in proportion to the number of occupants. The CO2 concentration provides a good indicator of overall air quality. Demand control ventilation (DCV) systems monitor indoor air CO2 concentrations and use this data to automatically modulate dampers and regulate the amount of outdoor air that is supplied for ventilation. DCV is most suited for facilities where occupancy levels are known to fluctuate considerably.
4742. The magnitude of energy savings associated with DCV is a function of the type of facility, hours of operation, occupancy schedule, ambient air conditions, space temperature set points, and the heating and cooling system efficiencies. Typical values representing this factors were used to derive deemed savings factors per CFM of the design ventilation rate for various space types. These deemed savings factors are utilized in the following algorithms to predict site specific savings.
4743. Algorithms 4744. 4745. Energy Savings (kWh/yr) = CESF x CFM) = (AEU * 0.13)
4746.[4298.] Peak Demand[4299.] Fuel Savings (kW) = CDSF x CFM
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4747. Savings Factor (MMBtu) = HSF X CFM(AFU * 0.13)[4300.]
4748.[4301.] Definition of Variables [4302.] AEU = Annual Electric Usage for an uncontrolled AC or refrigeration unit
(kWh) [4303.]
[4304.] AFU = Annual Fuel Usage for an uncontrolled (gas, oil, propane) HVAC unit (MMBtu or gallons)
[4305.] [4306.] SourcesCESF = Cooling:[4307.]
[4308.] (1) Some examples of the different types of fuel-use economizer controls available on the market can be found at: http://www.intellidynellc.com/02_prods.htm
[4309.] [4310.] (2) NYSERDA (2007) “A Technology Demonstration and Validation Project for Intellidyne
Energy Saving Controls”.[4311.]
[4312.] (3) ConEd Solutions (2000) “Report on Intellidyne Unit Installation at Six Key Food Supermarkets”.
[4313.] Low Flow Devices[4314.] Low flow showerheads, faucet aerators and pre-rinse spray valves save water heating
energy by reducing the total flow rate from water sources.[4315.]
[4316.] The measurement of energy savings associated with low flow devices is based on algorithms with key variables provided through Fisher-Nickel’s Life Cycle cost calculators.
[4317.] [4318.] Algorithms [4319.] [4320.] Savings Factor (kWh/CFM) = N x (60 x H x D x (Fbase – Feff) x 8.33 x DT x (1/Eff)/
C4749.[4321.] [4322.] Definition of Variables [4323.] [4324.] 60 = Conversion from hours to minutes[4325.] [4326.] N = Number of fixtures[4327.] [4328.] H = Hours per day of device usage [4329.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4330.] D = Days per year of CDSF = Cooling Demand Savings Factor (kW/CFM)4750. HSF = Heating Savings Factor (MMBtu/CFM) 4751. CFMfacility operation [4331.] [4332.] Fbase = Baseline Design Ventilation Rate of Controlled Space (CFMdevice flow rate
(gal/m)
4752.[4333.] [4334.] Feff = Low flow device flow rate (gal/m) [4335.] [4336.] 8.33 = Heat content of water (Btu/gal/°F )[4337.] [4338.] DT = Difference in temperature (°F) between cold intake and output [4339.] [4340.] Eff = Percent efficiency of water heating equipment [4341.] 4753.[4342.] Summary of Inputs 4754. 4755. C = Conversion factor from Btu to Therms or kWh (100,000 for gas water heating
(Therms), 3,413 for electric water heating (kWh))[4343.]
[4344.] Low Flow Devices[4345.]
[4346.] Demand Controlled Ventilation Using CO2
SensorsComponentCompo
nent
4756.[4347.] Typ
e
4757.[4348.] Value 4758.[4349.] Source
[4350.] N [4351.] Vari
able
[4352.] [4353.] Application
[4354.] CESFH 4759.[4355.] Fixe
d
[4356.] 0.0484 MMBtu/CFMSee Table 23 for pre-rinse spray valves
4760.[4357.] 1
[4358.] CDSFH 4761.[4359.] Fixe
d
[4360.] 20 minutes for showerheads
[4361.] 30 minutes for aerators
[4362.] 1 2
[4363.] D [4364.] Vari
a
[4365.] [4366.] Applicat ion
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4346.] Demand Controlled Ventilation Using CO2
SensorsComponentCompo
nent
4756.[4347.] Typ
e
4757.[4348.] Value 4758.[4349.] Source
ble
[4367.] Fbase [4368.] Vari
able
[4369.] [4370.] Applicat ion
[4371.] Feff [4372.] Vari
able
[4373.] Max of 1.0 gpm for lavatory aerators, 2.2 for kitchen aerators and 2.0
gpm for showerheads per EPA’s Water Sense Label
[4374.] Applicat ion
[4375.] HSFDT 4762.[4376.] Fixe
d
[4377.] 50°F for showerheads and faucet aerators, 70°F for pre-rinse spray valves
4763.[4378.] 1
[4379.] CFMEff 4764.[4380.] Vari
able
[4381.] default of 80% for gas water heaters and 95% for
electric water heaters
4765.[4382.] Application
4766.[4383.] 4767.[4384.] Savings for Demand-Controlled Ventilation Using CO2 Sensors
4768. Component
4769. CESF
4770. CDSF
4771. HSF
4772. Assembly 4773. 2.720 4774. 0.0014
4775. 0.074
4776. Auditorium – Community
Center4777. 1.500 4778. 0.001
54779. 0.04
3
4780. Gymnasium 4781. 2.558 4782. 0.001
34783. 0.06
94784. Office
Building 4785. 2.544 4786. 0.0013
4787. 0.068
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4768. Component
4769. CESF
4770. CDSF
4771. HSF
4788. Elementary School 4789. 1.079 4790. 0.001
34791. 0.02
94792. High
School 4793. 2.529 4794. 0.0015
4795. 0.072
4796. Shopping Center 4797. 1.934 4798. 0.001
24799. 0.05
0
4800. Other 4801. 2.544 4802. 0.0013
4803. 0.068
4804. 4805. Sources :
1. ERS spreadsheet derivation of deemed savings values for demand control ventilation. DCV Deemed savings Analysis. Based on DOE-2 default space occupancy profiles and initially developed for NYSERDA in 2010, revised to reflect typical New Jersey weather data.
4806. Low Flow Faucet Aerators, Showerheads, and Pre-rinse Spray Valves
4807. The following algorithm details savings for low-flow showerheads and faucet aerators. These devices save water heating energy by reducing the total flow rate from hot water sources.
4808. The measurement of energy savings associated with these low-flow devices is based on algorithms with key variables obtained from analysis by the Federal Energy Management Program (FEMP), published data from the Environmental Protection Agency water conservations studies, and customer information provided on the application form. The energy values are in Btu for natural gas fired water heaters or kWh for electric water heaters.
4809. Low Flow Faucet Aerators and Showerheads
1. Fisher-Nickel Life Cycle cost calculator [1.] FEMP Cost Calculator located at
http://www1.eere.energy.gov/femp/technologies/eep_faucets_showerheads_calc.html[4385.] Algorithm
4810. Btu or KWh Fuel Savings/yr = N x H x D x (Fb – Fq) x (8.33 x DT / EFF )/ C4811. 4812. Definition of Variables 4813. N = Number of fixtures4814. H = Hours per day of device usage 4815. D = Days per year of device usage 4816. F b = Baseline device flow rate (gal/m) 4817. F q = Low flow device flow rate (gal/m) 4818. 8.33 = Heat content of water (Btu/gal/°F)4819. DT = Difference in temperature (°F) between cold intake and output
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4820. EFF = Efficiency of water heating equipment 4821. C = Conversion factor from Btu to therms or kWh = (100,000 for gas water heating (Therms), 3,413 for electric water heating (kWh)
4822. Summary of Inputs
4823. Low Flow Faucet Aerators and Showerheads
4824. Component 4825. Type 4826. Value
4827. S ourc
e
4828. N 4829. Variable 4830.4831. A
pplication
4832. H 4833. Fixed
4834. Aerators4835. 30 minutes
4836. 1 4839. Shower heads
4840. 20 minutes
4842. D 4843. Fixed
4844. Aerators4845. 260 days
4846. 1 4849. Shower heads
4850. 365 days
4852. F b 4853. Fixed
4854. Aerators4855. 2.2 gpm
4856.4859. Showerhead
4860. 2.5 gpm
4862. F q 4863. Fixed
4864. Aerators4865. <=1.5 gpm (kitchen)4866. <=0.5 gpm (public
restroom)4867. <=1.5 gpm (private
restroom)
4868. 2 ,3,4
4871. Showerheads4872. <=2 gpm
4873. 4
4874. DT 4875. Fixed
4876. Aerators4877. 25°F
4878. 5
4881. Showerheads4882. 50°F
4883. 6
4884. EFF 4885. Fixed4886. 97% electric
4887. 80% natural gas4888. 7
,8
4889. Sources
1. FEMP Cost Calculator; located at: https://energy.gov/eere/femp/energy-cost-calculator-faucets-and-showerheads-0#output.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
2. EPA WaterSense requirements for faucet aerators; available at: https://www.epa.gov/watersense/bathroom-faucets.
3. Department of Energy, Best Management Practice #7, Faucets and Showerheads; available at: https://energy.gov/eere/femp/best-management-practice-7-faucets-and-showerheads
4. EPA WaterSense requirements for showerheads; available at: https://www.epa.gov/watersense/showerheads.
5. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Calculated using Tfaucet and Tmain for Faucet – Low-flow aerator measure. Values for both Tfaucet and Tmain found on p. 177, Table 1 and p. 178, Table 2 respectively.
6. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Calculated using Tsh
and Tmain for Showerhead – Low-flow measure. Values for both Tsh and Tmain found on p. 181, Table 1 and p. 181, Table 2, respectively.
7. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, p. 177, Table 1.8. ASHRAE Standards 90.1-2007. Energy Standard for Buildings Except Low Rise Residential
Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.4890.
[4386.] Demand Control Ventilation Using CO2 Sensors[4387.] Demand control ventilation (DCV) monitors indoor air CO2 content as a result of
occupancy production levels and uses this data to regulate the amount of outdoor air that is permitted for ventilation. In order to ensure adequate air quality, standard ventilation systems permit outside air based on estimated occupancy levels in CFM/occupant. However, during low occupancy hours, the space may become over ventilated due to decreased CO2 levels. This air must be conditioned and, therefore, unnecessary ventilation results in wasted energy. DCV reduces unnecessary outdoor air intake by regulating ventilation based on actual CO2 levels, saving energy. DCV is most suited for facilities where occupancy levels are known to fluctuate considerably.
[4388.]
[4389.] The measurement of energy savings associated with DCV is based on hours of operation, occupancy schedule, return air enthalpy, return air dry bulb temperature, system air flow, outside air reduction, cooling system efficiency, and other factors. As a conservative simplification of complex algorithms, DCV is assumed to save 5% of total facility HVAC load in appropriate building types based on FEMP DCV documentation.
[4390.] [4391.]
[4392.] Algorithms [4393.] 4891.[4394.] Low Flow Pre-rinse Spray Valves4892.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4893. Algorithm 4894. 4895. Btu or KWh Fuel Savings/yr = N x H x D x (Fb – Fq) x (8.33 x DT / EFF) / C 4896. Electric Savings (kWh) = 0.05 * HVACE
[4395.] [4396.] Gas Savings (4897.[4397.] Definition of Variables4898. 60 = Conversion from hours to minutes4899. N = Number of fixtures4900. H = Hours per year of device usage 4901. D = Days per year of device usage4902. F b = Baseline device flow rate (gal/m) 4903. F q = Low flow device flow rate (gal/m) 4904. 8.33 = Heat content of water (Btu/gal/°F)4905. DT = Difference in temperature (°F) between cold intake and output 4906. Eff = Percent efficiency of water heating equipment 4907. C = Conversion factor from Btu to Therms) = 0.05 * HVACG
[4398.] [4399.] Definition of Variables or kWh = (100,000 for gas water heating (Therms), 3,413 for [4400.] [4401.] HVACE = Total electric water heatingHVAC consumption (kWh))) 4908.[4402.] [4403.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4909.[4404.] Summary of Inputs 4910.
4911. Low Flow Pre-Rinse Spray Valves4912. HVACG = Total gas HVAC consumption (Therms)
[4405.] [4406.] Demand Control Ventilation Using CO2 Sensors
[4407.] [4408.] Comp
onent4913.[4409.] T
ype 4914.[4410.] Value 4915.[4411.] Source
[4412.] N HVACE
4916.[4413.] Variable 4917.[4414.]
4918.[4415.] Applica
tion4919.[4416.] H 4920. Fixed 4921. 1.06 hours 4922. 1
4923. D 4924. Fixed 4925. 344 days 4926. 1 4927. F b 4928. Fixed 4929. 1.6 gpm 4930. 2
4931. F qHVACG
4932.[4417.] Variable 4933.[4418.] <=1.28 gpm
[4419.] Application3
4934. DT 4935. Fixed 4936. 75°F 4937. 4
4938. Eff 4939. Variable
4940. 97% electric4941. 80% natural gas
4942. 5 , 6
4943. 4944. 4945. Sources
1. EPA WaterSense Specification for Commercial Pre-Rinse Spray Valves Supporting Statement, September 19, 2013, Appendix A, Page 7.
2. EPA Energy Policy Act of 2005, p. 40, Title I, Subtitle C. 3. EPA WaterSense Specification for Commercial Pre-Rinse Spray Valves, available at:
https://www.epa.gov/watersense/pre-rinse-spray-valves.4. NY, Standard Approach for Estimating Energy Savings, V4, April 2016. Calculated using
Theater and Tmain for Low-flow Pre-rinse spray valve measure. Values for both Tsh and Tmain
found on p. 184, Table 1 and p. 184, Table 2, respectively.5. NY, Standard Approach for Estimating Energy Savings, V4, April, p. 177, Table 1.6. ASHRAE Standards 90.1-2007, Energy Standard for Buildings Except Low Rise Residential
Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
4946. Pipe Insulation
4947.[4420.] This measure applies to insulation installed on previously bare hot water distribution piping located in unconditioned spaces. Deemed savings factors were derived using the North American Insulation Manufacturers Association, 3E Plus Version 4.1 heat loss calculation tool. The savings factors represent average values for copper or steel
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
pipe with mineral fiber or polyolefin tube pipe insulation. Savings are a function of pipe size and insulation thickness. A table of savings factors for nominal pipe size ranging from ½ inch to 4 inches, with insulation ranging from ½ inch to 2 inches thick is provided.
4948. The savings factors are based on a fluid temperature of 180°F, and an ambient temperature of 50°F, resulting in a temperature differential of 130° F . If the actual temperature differential varies significantly from this value, the reported savings should be scaled proportionally.
4949. The default value for annual operating hours represents the average annual hours when space heating is required. For non-space heating applications, the value should be adjusted to reflect the annual hours when the hot fluid is circulated.
4950. Un-insulated hot water carrying pipes lose considerable heat to outside air due to high thermal conductivity. In order to reduce this heat loss, pipes can be covered with a layer of fiberglass insulation, which will reduce source heating demand, resulting in significant energy savings.
[4421.]
[4422.] The measurement of energy savings associated with pipe insulation is based on the length of the supply pipe, pipe diameter, relative thermal conductivity of bare and insulated piping and the temperature difference between supplied water and outside air temperature as indicated in the EPRI report referenced below. The baseline case is un-insulated copper pipe and the default proposed case is 0.5” of fiberglass insulation.
[4423.] Algorithms 4951.[4424.] 4952.[4425.] Fossil Fuel Source:4953. 4954. Fuel Savings (MMBtu/yr) = SF x L x Oper Hrs / EFF
4955. Electric Source:
4956. Energy Savings (kWh/yr) = SF x L x Oper Hrs / EFF) = (L * (HLCbase - HLCee) / C) * ΔT * 8,760
[4426.]
4957.[4427.] Definition of Variables 4958.[4428.] SF = Savings factor derived from #E Plus Version 4.1 tool, Btu/hr-ft see table
below4959. L = Length of pipe from water heating source to hot water application, (ft) 4960.[4429.] Operating Hours = hours per year fluid flows in pipe, hours 4961. EFF = Efficiency of equipment providing heat to the fluid4962. [4430.] HLCbase = Pipe heat loss coefficient by pipe diameter (baseline) (BtuH -°F-ft) [4431.] [4432.] HLCee = Pipe heat loss coefficient by pipe diameter (proposed) (BtuH -°F-ft)
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4433.] C = Conversion factor from Btu to kWh = or Therms (3,413 for electric water heating (kWh (Electric Water Heating), 100,000 for Therms (Gas Water Heating)
4963.[4434.] Summary of Inputs 4964. 4965. ΔT = Average temperature difference between supplied water and outside air
temperature (°F)[4435.] [4436.] 8,760 = Hours per year
[4437.] Pipe Insulation4966.[4438.]
[4439.] Component
4967.[4440.] Typ
e
4968.[4441.] Value 4969.[4442.] Source
[4443.] SFL [4444.] Vari
ableFixed
4970. See Table Below [4445.] Application1
4971. L HLCbase
[4446.] Vari
ableFixed
[4447.] See Table Below 4972.[4448.] Application
4973. Oper HrsHLCee
4974.[4449.] Fixe
d
[4450.] See Table Below4,282 hrs/year (default value reflects average heating
season hours)
4975. 2
4976. EFFΔT
[4451.] Fixe
dVar
4977.[4452.] 97% electric4978. 80% natural gas
Default is 65°F
[4453.] 3, 4EPRI Study
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4439.] Component
4967.[4440.] Typ
e
4968.[4441.] Value 4969.[4442.] Source
iable
4979.[4454.]
4980.[4455.] Deemed Savings Values
4981.
Nominal Pipe Size,
Inches0.5"
Insulation1.0"
Insulation1.5"
Insulation2.0"
Insulation0.50 47 53 56 57 0.75 58 64 68 70 1.00 72 82 85 87 1.25 89 100 107 108 1.50 100 115 120 125 2.00 128 143 148 153 2.50 153 171 182 185 3.00 195 221 230 236 3.50 224 241 248 253 4.00 232 263 274 281
Savings, Btu/hr-ft
4982. Pipe Heat Loss Coefficient Table
[4456.] [4457.] [4458.] Sources :
1. North American Insulation Manufacturers Association, 3E Plus, Version 4.1, heat loss calculation tool, August 2012.
2. NOAA, Typical Meteorological Year (TMY3) weather data – Newark, Trenton, and Atlantic City averaged.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
3. ASHRAE Standards 90.1-2007. Energy Standard for Buildings Except Low Rise Residential Buildings; available at: https://www.ashrae.org/standards-research--technology/standards--guidelines.
4. NY, Standard Approach for Estimating Energy Savings, V4, April 2016, p. 177, Table 1. Derived from DOE2.2 simulations reflecting a range of building types and climate zones.4983. Engineering Methods for Estimating the Impacts of Demand-Side Management
Programs, Volume 2, EPRI, 1993[4459.] [4460.]
[4461.] Lighting and Lighting Controls
4984.[4462.] For lighting and lighting control projects performed by Direct Install programs, use the C&I prescriptive lighting tables for the lighting types identified within those tables. For any fixtures not listed on the table, go to the source table for that fixture. If the fixture is not on the source table, then use manufacture cut sheets for replacement kW to calculate the savings.
4985. Eligible measures include:
4986. 4987. Prescriptive Lighting 4988. T84989. T54990. CFL Screw-In4991. LED Screw-In4992. LED Linear Tubes4993. LED Hard-Wired Fixtures4994. 4995. Lighting Controls 4996. Occupancy Sensors4997. High-Bay Occupancy Sensors4998. Photocell with Dimmable Ballast
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
4999.[4463.] C&I Large Energy Users Incentive Program [4464.] The purpose of the program is to foster self-investment in energy-efficiency, and
combined heat and power projects while providing necessary financial support to large commercial and industrial utility customers in New Jersey.
Protocols[4465.] Please refer to the Pay for Performance Existing Buildings protocols to calculate
demand and energy savings for the Large Energy Users Program. If a project addresses a specific end-use technology, protocols for that technology should be used.
5000.[4466.] C&I Customer-Tailored Energy Efficiency Pilot Program
[4467.] The purpose of the program is to better serve the needs of specific commercial and industrial customers whose usage is too large for them to qualify for the Direct Install program, but too low for the Large Energy Users Program.
Protocols[4468.] Please refer to the Pay for Performance Existing Buildings protocols to calculate
demand and energy savings for comprehensive projects in the Customer Tailored Pilotthe Large Energy Users Program. If a project addresses a specific end-use technology, protocols for that technology should be used.
5001.[4469.] 5002.[4470.]
5003.[4471.] 5004.[4472.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
5005.[4473.] Renewable Energy Program Protocols
5006.[4474.] SREC Registration Program (SRP)5007.[4475.] The energy and demand impacts for customer sited solar PV generation systems
participating in the program are based on fixed assumptions which are applied to the total project system capacity. The annual electricity generation is derived by multiplying the estimated annual production factor of 1,200 kWh per kW by the total system capacity (kW) to yield the estimated annual output (kWh).48 The combined values for all projects participating in a specified period are then summed up and converted to MWh for reporting purposes.
5008.[4476.]
[4477.] Renewable Non-SRP
[4478.] Renewable Electric Storage [4479.] [4480.] The impact of Renewable Electric Storage, if any on net renewable energy generation
will be analyzed over the coming year based upon quarterly performance reporting that is required of participants in this program.
48 Estimated annual production factor is based on combined average calculation of the PV Watts estimated annual output for the Newark and Atlantic City weather stations.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4481.] Appendix A Measure Lives
5009.[4482.] 5010.[4483.] NEW JERSEY STATEWIDE ENERGY-EFFICIENCY
PROGRAMS5011.[4484.] Measure Lives Used in Cost-Effectiveness
Screening[4485.] Updated October 2017April 2012
5012.[4486.] If actual measure lives are available through nameplate information or other manufacturing specifications with proper documentation, those measure lives should be utilized to calculate lifetime savings. In the absence of the actual measure life, Protocol measure lives listed below should be utilized49.
5013.[4487.] 5014.[4488.] Measure 5015.[4489.] Measure Life
5016.[4490.] Residential Sector5017.[4491.] Lighting End Use 5018.[4492.] 5019.[4493.] CFL 5020.[4494.] 75021.[4495.] LED 5022.[4496.] 165023.[4497.] HVAC End Use 5024.[4498.] 5025.[4499.] Central Air Conditioner (CAC) 5026.[4500.] 155027.[4501.] CAC QIV 5028.[4502.] 155029.[4503.] Air Source Heat Pump (ASHP) 5030.[4504.] 155031.[4505.] Mini-Split (AC or HP) 5032.[4506.] 175033.[4507.] Ground Source Heat Pumps (GSHP) 5034.[4508.] 205035.[4509.] Furnace High Efficiency Fan 5036.[4510.] 185037.[4511.] Heat Pump Hot Water (HPHW) 5038.[4512.] 115039.[4513.] Furnaces 5040.[4514.] 185041.[4515.] Boilers 5042.[4516.] 205043.[4517.] Combination Boilers 5044.[4518.] 195045.[4519.] Boiler Reset Controls 5046.[4520.] 165047.[4521.] Heating and Cooling Equipment Maintenance
Repair/Replacement 5048.[4522.] 75049.[4523.] Thermostat Replacement 5050.[4524.] 55051.[4525.] Hot Water End-Use 5052.[4526.] 5053.[4527.] Storage Water Heaters 5054.[4528.] 135055.[4529.] Instantaneous Water Heaters 5056.[4530.] 205057.[4531.] Building Shell End-Use 5058.[4532.] 5059.[4533.] Air Sealing 5060.[4534.] 155061.[4535.] Duct Sealing and Repair 5062.[4536.] 155063.[4537.] Insulation Upgrades 5064.[4538.] 20
5065.[4539.]
49 ERS Memo, Comparative Measure Life Study and Summary of Measure Changes to NJCEP Protocols, September 5, 2017. Updated October 16911, 2017.
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
5066.[4540.] Appliances/Electronics End-Use 5067.[4541.] 5068.[4542.] ES Refrigerator 5069.[4543.] 125070.[4544.] ES Freezer 5071.[4545.] 115072.[4546.] ES Dishwasher 5073.[4547.] 105074.[4548.] ES Clothes washer 5075.[4549.] 115076.[4550.] ES RAC 5077.[4551.] 105078.[4552.] ES Air Purifier 5079.[4553.] 95080.[4554.] ES Set Top Box 5081.[4555.] 45082.[4556.] ES Sound Bar 5083.[4557.] 105084.[4558.] Advanced Power Strips 5085.[4559.] 45086.[4560.] ES Clothes Dryer 5087.[4561.] 125088.[4562.] Refrigerator/Freezer Retirement 5089.[4563.] 8
5090.[4564.] Commercial Sector5091.[4565.] Lighting End Use 5092.[4566.] 5093.[4567.] Performance Lighting 5094.[4568.] 155095.[4569.] Prescriptive Lighting 5096.[4570.] 155097.[4571.] Refrigerated Case LED Lights 5098.[4572.] 95099.[4573.] Specialty LED Fixtures (Signage) 5100.[4574.] 155101.[4575.] Lighting Controls 5102.[4576.] 95103.[4577.] HVAC End Use 5104.[4578.] 5105.[4579.] Electronically Commutated Motors for
Refrigeration 5106.[4580.] 155107.[4581.] Electric HVAC Systems 5108.[4582.] 155109.[4583.] Fuel Use Economizers 5110.[4584.] 155111.[4585.] Dual Enthalpy Economizers 5112.[4586.] 105113.[4587.] Occupancy Controlled Thermostats 5114.[4588.] 135115.[4589.] Electric Chillers 5116.[4590.] 225117.[4591.] Gas Chillers 5118.[4592.] 255119.[4593.] Gas Fired Desiccants 5120.[4594.] NA5121.[4595.] Prescriptive Boilers 5122.[4596.] 225123.[4597.] Prescriptive Furnaces 5124.[4598.] 205125.[4599.] Commercial Small Motors (1-10 HP) 5126.[4600.] 205127.[4601.] Commercial Small Motors (11-75 HP) 5128.[4602.] 205129.[4603.] Commercial Small Motors (76-200 HP) 5130.[4604.] 205131.[4605.] Small Commercial Gas Boiler 5132.[4606.] 205133.[4607.] Infrared Heaters 5134.[4608.] 175135.[4609.] Electronic Fuel Use Economizers 5136.[4610.] 155137.[4611.] Programmable Thermostats 5138.[4612.] 125139.[4613.] Demand-Controlled Ventilation Using CO2
Sensors 5140.[4614.] 105141.[4615.] Boiler Reset Controls 5142.[4616.] 165143.[4617.] VFDs End Use 5144.[4618.] 5145.[4619.] Variable Frequency Drives 5146.[4620.] 155147.[4621.] New and Retrofit Kitchen Hoods with Variable
Frequency Drives 5148.[4622.] 155149.[4623.] Refrigeration End Use 5150.[4624.] 5151.[4625.] Energy Efficient Glass Doors on Vertical Open
Refrigerated Cases 5152.[4626.] 125153.[4627.] Aluminum Night Covers 5154.[4628.] 65155.[4629.] Walk-in Cooler/Freezer Evaporator Fan Control 5156.[4630.] 13
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
5157.[4631.] Cooler and Freezer Door Heater Control 5158.[4632.] 125159.[4633.] Electric Defrost Control 5160.[4634.] 105161.[4635.] Novelty Cooler Shutoff 5162.[4636.] 85163.[4637.] Vending Machine Controls 5164.[4638.] 55165.[4639.] Food Service Equipment End-Use 5166.[4640.] 5167.[4641.] Electric and Gas Combination Oven/Steamer 5168.[4642.] 125169.[4643.] Electric and Gas Convection Ovens, Gas
Conveyor and Rack Ovens, Steamers, Fryers, and Griddles
5170.[4644.] 12
5171.[4645.] Insulated Food Holding Cabinets 5172.[4646.] 125173.[4647.] Commercial Dishwashers 5174.[4648.] 155175.[4649.] Commercial Refrigerators and Freezers 5176.[4650.] 125177.[4651.] Commercial Ice Machines 5178.[4652.] 95179.[4653.] Hot Water End-Use 5180.[4654.] 5181.[4655.] Gas Booster Water Heaters 5182.[4656.] NA5183.[4657.] Tank Style (Storage) Water Heaters 5184.[4658.] 145185.[4659.] Instantaneous Gas Water Heaters 5186.[4660.] 205187.[4661.] Low Flow Faucet Aerators and Showerheads 5188.[4662.] 95189.[4663.] Low Flow Pre-rinse Spray Valves 5190.[4664.] 55191.[4665.] Pipe Insulation 5192.[4666.] 135193.[4667.] Combined Heat & Power Program 5194.[4668.] 5195.[4669.] Fuel Cell 5196.[4670.] 55197.[4671.] Combustion Gas Turbine 5198.[4672.] 175199.[4673.] IC Small <= 200 KW* 5200.[4674.] 175201.[4675.] IC Large > 200 KW* 5202.[4676.] 205203.[4677.] Micro Turbine 5204.[4678.] 155205.[4679.] Steam Turbine 5206.[4680.] 25
5207.[4681.] *Size of individual prime-mover, not the overall system. For example, a project with three 75kW internal combustion engines should be assigned a 17-year measure life for small systems.5208.[4682.]
[4683.] PROGRAM/Measure
[4684.] Measure Life
[4685.] Residential Programs [4686.] [4687.] Energy Star Appliances [4688.]
[4689.] ES Refrigerator post 2001 [4690.] 12
[4691.] ES Refrigerator 2001 [4692.] 12
[4693.] ES Freezer [4694.] 11
[4695.] ES Dishwasher [4696.] 10
[4697.] ES Clothes washer [4698.] 11
[4699.] ES Dehumidifier [4700.] 11
[4701.] ES RAC [4702.] 10
[4703.] ES Air Purifier [4704.] 9
[4705.] ES Set Top Box [4706.] 4
[4707.] ES Sound Bar [4708.] 10
[4709.] Advanced Power Strips [4710.] 4
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4711.] ES Clothes Dryer [4712.] 12
[4713.] Energy Star Lighting [4714.]
[4715.] CFL [4716.] 5
[4717.] LED [4718.] 15
[4719.] Energy Star Windows [4720.] 20
[4721.] WIN-heat pump [4722.] 20
[4723.] WIN-gas heat/CAC [4724.] 20
[4725.] WIN-gas No CAC [4726.] 20
[4727.] WIN-oil heat/CAC [4728.] 20
[4729.] WIN-oil No CAC [4730.] 20
[4731.] Win-elec No AC [4732.] 20
[4733.] Win-elec AC [4734.] 20
[4735.] Refrigerator/Freezer Retirement [4736.]
[4737.] Refrigerator/Freezer retirement [4738.] 8
[4739.] Residential New Construction [4740.]
[4741.] SF gas w/CAC [4742.] 20
[4743.] SF gas w/o CAC [4744.] 20
[4745.] SF oil w/CAC [4746.] 20
[4747.] SF all electric [4748.] 20
[4749.] TH gas w/CAC [4750.] 20
[4751.] TH gas w/o CAC [4752.] 20
[4753.] TH oil w/CAC [4754.] 20
[4755.] TH all electric [4756.] 20
[4757.] MF gas w/AC [4758.] 20
[4759.] MF gas w/o AC [4760.] 20
[4761.] MF oil w/CAC [4762.] 20
[4763.] MF all electric [4764.] 20
[4765.] ES Clothes washer [4766.] 20
[4767.] Recessed Can Fluor Fixture [4768.] 20
[4769.] Fixtures Other [4770.] 20
[4771.] Efficient Ventilation Fans w/Timer [4772.] 10
5209.[4773.] 5210.[4774.]
[4775.] PROGRAM/Measure
[4776.] Measure Life
[4777.] Residential Programs [4778.] [4779.] Residential Electric HVAC [4780.]
[4781.] CAC 13 [4782.] 15
[4783.] CAC 14 [4784.] 15
[4785.] ASHP 13 [4786.] 15
[4787.] ASHP 14 [4788.] 15
[4789.] CAC proper sizing/install [4790.] 15
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4791.] CAC QIV [4792.] 15
[4793.] CAC Maintenance [4794.] 7
[4795.] CAC duct sealing [4796.] 15
[4797.] ASHP proper sizing/install [4798.] 15
[4799.] E-Star T-stat (CAC) [4800.] 15
[4801.] E-star T-stat (HP) [4802.] 15
[4803.] GSHP [4804.] 30
[4805.] CAC 15 [4806.] 15
[4807.] ASHP 15 [4808.] 15
[4809.] Residential Gas HVAC [4810.]
[4811.] High Efficiency Furnace [4812.] 20
[4813.] High Efficiency Boiler [4814.] 20
[4815.] High Efficiency Gas DHW [4816.] 10
[4817.] E-Star T-stat [4818.] 15
[4819.] Boiler Reset Controls [4820.] 7
[4821.] Low-Income Program [4822.]
[4823.] Air sealing electric heat [4824.] 30
[4825.] Duct Leak Fossil Heat & CAC [4826.] 15
[4827.] typical fossil fuel heat [4828.] 17
[4829.] typical electric DHW pkg [4830.] 10
[4831.] typical fossil fuel DHW pkg [4832.] 10
[4833.] screw-in CFLs [4834.] 6.4
[4835.] high-performance fixtures [4836.] 20
[4837.] fluorescent torchieres [4838.] 10
[4839.] TF 14 [4840.] 20
[4841.] TF 16 [4842.] 20
[4843.] TF 18 [4844.] 20
[4845.] SS 20 [4846.] 20
[4847.] TF 21 [4848.] 20
[4849.] SS 22 [4850.] 20
[4851.] TF 25 [4852.] 20
[4853.] audit fees [4854.] 20
[4855.] Attic Insulation- ESH [4856.] 30
[4857.] Duct Leak - ESH [4858.] 15
[4859.] T-Stat- ESH [4860.] 5
[4861.] HP charge air flow [4862.] 8
[4863.] electric arrears reduction [4864.] 1
[4865.] gas arrears reduction [4866.] 1
[4867.] Home Performance with ENERGY STAR [4868.]
[4869.] Blue Line Innovations – PowerCost MonitorTM [4870.] 5
[4871.]
[4872.] PROGRAM/Measure[4873.] M
easur
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
e Life[4874.] Non-Residential Programs [4875.] [4876.] C&I Construction [4877.]
[4878.] Commercial Lighting — New [4879.] 15
[4880.] Commercial Lighting — Remodel/Replacement [4881.] 15
[4882.] Commercial Lighting Controls — Remodel/Replacement [4883.] 18
[4884.] Commercial Custom — New [4885.] 18
[4886.] Commercial Chiller Optimization [4887.] 18
[4888.] Commercial Unitary HVAC — New - Tier 1 [4889.] 15
[4890.] Commercial Unitary HVAC — Replacement - Tier 1 [4891.] 15
[4892.] Commercial Unitary HVAC — New - Tier 2 [4893.] 15
[4894.] Commercial Unitary HVAC — Replacement Tier 2 [4895.] 15
[4896.] Commercial Chillers — New [4897.] 25
[4898.] Commercial Chillers — Replacement [4899.] 25
[4900.] Commercial Small Motors (1-10 HP) — New or Replacement [4901.] 20[4902.] Commercial Medium Motors (11-75 HP) — New or
Replacement [4903.] 20[4904.] Commercial Large Motors (76-200 HP) — New or
Replacement [4905.] 20
[4906.] Commercial VSDs — New [4907.] 15
[4908.] Commercial VSDs — Retrofit [4909.] 15
[4910.] Commercial Air Handlers Units [4911.] 20
[4912.] Commercial Heat Exchangers [4913.] 24
[4914.] Commercial Burner Replacement [4915.] 20
[4916.] Commercial Boilers [4917.] 25
[4918.] Commercial Controls (electric/electronic) [4919.] 15
[4920.] Commercial Controls (Pneumatic) [4921.] 10
[4922.] Commercial Comprehensive New Construction Design [4923.] 18
[4924.] Commercial Custom — Replacement [4925.] 18
[4926.] Industrial Lighting — New [4927.] 15
[4928.] Industrial Lighting — Remodel/Replacement [4929.] 15
[4930.] Industrial Unitary HVAC — New - Tier 1 [4931.] 15
[4932.] Industrial Unitary HVAC — Replacement - Tier 1 [4933.] 15
[4934.] Industrial Unitary HVAC — New - Tier 2 [4935.] 15
[4936.] Industrial Unitary HVAC — Replacement Tier 2 [4937.] 15
[4938.] Industrial Chillers — New [4939.] 25
[4940.] Industrial Chillers — Replacement [4941.] 25
[4942.] Industrial Small Motors (1-10 HP) — New or Replacement [4943.] 20[4944.] Industrial Medium Motors (11-75 HP) — New or
Replacement [4945.] 20
[4946.] Industrial Large Motors (76-200 HP) — New or Replacement [4947.] 20
[4948.] Industrial VSDs — New [4949.] 15
[4950.] Industrial VSDs — Retrofit [4951.] 15
[4952.] Industrial Custom — Non-Process [4953.] 18
[4954.] Industrial Custom — Process [4955.] 10
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings
[4956.] Industrial Air Handler Units [4957.] 20
[4958.] Industrial Heat Exchangers [4959.] 20
[4960.] Industrial Burner Replacements [4961.] 20
[4962.] Small Commercial Gas Furnace — New or Replacement [4963.] 20
[4964.] Infrared Heating [4965.] 17
[4966.] Small Commercial Gas Boiler — New or Replacement [4967.] 20
[4968.] Small Commercial Gas DHW — New or Replacement [4969.] 10
[4970.] C&I Gas Absorption Chiller — New or Replacement [4971.] 25[4972.] C&I Gas Custom — New or Replacement (Engine Driven
Chiller) [4973.] 25[4974.] C&I Gas Custom — New or Replacement (Gas Efficiency
Measures) [4975.] 18
[4976.]
[4977.] PROGRAM/Measure
[4978.] Measure Life
[4979.] Non-Residential Programs [4980.] [4981.] Building O&M [4982.]
[4983.] O&M savings [4984.] 3
[4985.] Compressed Air [4986.]
[4987.] Compressed Air (GWh participant) [4988.] 8
[4989.] Refrigeration [4990.]
[4991.] Evaporator Fan Control [4992.] 10
[4993.] Cooler and Freezer Door Heater Control [4994.] 10
[4995.] Polyethylene Strip Curtains [4996.] 4
[4997.] Food Service [4998.]
[4999.] Fryers [5000.] 12
[5001.] Steamers [5002.] 10
[5003.] Griddles [5004.] 12
[5005.] Ovens [5006.] 12
[5007.]
[5008.] PROGRAM/Measure
[5009.] Measure Life
[5010.] Solar Panels [5011.] 25[5012.] CHP System ≤1 MW [5013.] 15[5014.] CHP System >1 MW [5015.] 20[5016.] Fuel Cells [5017.] 20
[5018.] [5019.] * For custom applications, projects will be evaluated upon industry/manufacturer
data but not to exceed value in above table unless authorized by the Market Manager. Reported savings will be calculated per measure life indicated in this table.
5211.[5020.]
New Jersey’s Clean Energy Program Page Protocols to Measure Resource Savings