new medical building dr. caesar hearn,...

45
423 West 800 South, Suite A316 Salt Lake City, UT 84101 cell: 801.232.3638 email: [email protected] Project Manual New Medical Building Dr. CAESAR HEARN, DDS Layton, Utah Date: 22 May 2017 Architect’s Project No; 1252.144.1

Upload: duonglien

Post on 22-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

423 West 800 South, Suite A316 Salt Lake City, UT 84101 cell: 801.232.3638 email: [email protected]

Project Manual

New Medical Building Dr. CAESAR HEARN, DDS

Layton, Utah

Date: 22 May 2017

Architect’s Project No; 1252.144.1

Page 2: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TABLE OF CONTENTES TOC - 1

TABLE OF CONTENTS

015000 Temporary Facilities and Controls

033000 Cast-in-Place Concrete

047300 Manufactured Stone

061000 Rough Carpentry

061053 Miscellaneous Rough Carpentry

062000 Finish Carpentry

064100 Architectural Wood Casework

072100 Thermal Insulation

075000 Single Ply Roofing System

076100 Metal Roof Panels

076200 Sheet Metal Flashing and Trim

079200 Joint Sealers

081423 Doors

084113 Aluminum Framed Entrances and Storefront

087100 Door Hardware

088000 Glazing

092900 Gypsum Board

093000 Tiling

095100 Acoustical Ceilings

096500 Resilient Flooring

099000 Painting and Coating

102800 Toilet Accessories

123623 Plastic Countertops

END OF TABLE OF CONTENTS

Page 3: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TEMPORARY FACILITIES AND CONTROLS 015000 - 1

SECTION 015000 - TEMPORARY FACILITIES AND CONTROLS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Use Charges: Installation and removal of and use charges for temporary facilities shall be included in the Contract Sum unless otherwise indicated.

B. Electric Service: Comply with NECA, NEMA, and UL standards and regulations for temporary electric service. Install service to comply with NFPA 70. It is the contractor’s responsibility to locate and connect to usable electrical power.

C. Accessible Temporary Egress: Comply with applicable provisions in ICC A117.1.

PART 2 - PRODUCTS

2.1 TEMPORARY FACILITIES

A. Provide field support facilities as necessary for construction operations. Store combustible materials apart from building.

2.2 EQUIPMENT

A. Fire Extinguishers: Portable, UL rated; with class and extinguishing agent as required by locations and classes of fire exposures.

PART 3 - EXECUTION

3.1 TEMPORARY UTILITY INSTALLATION

A. Sanitary Facilities: Provide temporary toilets, wash facilities, and drinking-water. Comply with regulations and health codes for type, number, location, operation, and maintenance of fixtures and facilities.

B. Provide temporary lighting with local switching that provides adequate illumination for construction operations, observations, inspections, and traffic conditions.

3.2 SUPPORT FACILITIES INSTALLATION

A. Waste Disposal Facilities: Provide waste-collection containers in sizes adequate to handle waste from construction operations. Comply with requirements of authorities having jurisdiction.

Page 4: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TEMPORARY FACILITIES AND CONTROLS 015000 - 2

3.3 OPERATION, TERMINATION, AND REMOVAL

A. Remove each temporary facility when need for its service has ended, when it has been replaced by authorized use of a permanent facility, or no later than Substantial Completion.

END OF SECTION 015000

Page 5: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne 22 May 2017 1252.144.1

SECTION 033000 - CAST-IN-PLACE CONCRETE

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Concrete mix designs and other submittals required by Structural Engineer.

B. All other requirements by Structural Engineer.

PART 2 - PRODUCTS

2.1 PEFORMANCE REQUIREMENTS

A. As required by Structural Documents.

2.2 MATERIALS

A. Reinforcing Bars: As required by Structural Documents.

B. All other requirements by Structural Documents.

PART 3 - EXECUTION

3.1 CONCRETING

A. Construct formwork according to ACI 301.

B. Comply with CRSI's "Manual of Standard Practice" for fabricating, placing, and supporting reinforcement.

C. Protect concrete from physical damage, premature drying, and reduced strength due to hot or cold weather during mixing, placing, and curing.

D. Formed Surface Finish: Smooth-formed finish for concrete exposed to view, coated, or covered by waterproofing or other direct-applied material; rough-formed finish elsewhere.

E. Slab Finishes: Comply with ACI 302.1R for screeding, restraightening, and finishing operations for concrete surfaces. Do not wet concrete surfaces. Provide the following finishes: 1. Troweled finish.

Page 6: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne 22 May 2017 1252.144.1

F. Cure formed surfaces by moisture curing for at least seven days.

G. Begin curing concrete slabs after finishing. Keep concrete continuously moist for at least seven days.

END OF SECTION 033000

Page 7: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

SECTION 047300 - MANUFACTURED STONE MASONRY

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Samples for adhered masonry veneer units

B. Do not use frozen materials or materials mixed or coated with ice or frost. Do not build on

frozen subgrade or setting beds. Comply with cold-weather construction requirements

contained in ACI 530.1/ASCE 6/TMS 602.

C. Comply with hot-weather construction requirements contained in ACI 530.1/ASCE 6/TMS 602.

PART 2 - PRODUCTS

2.1 ADHERED MASONRY VENEER UNITS

A. Adhered Masonry Veneer Units: Units made from wet-cast lightweight concrete and intended

to resemble natural stone.

1. Products: Use products as manufactured by Dutch Quality Stone,

www.dutchqualitystone.com,

Use Arizona Dry Stack.

Or as selected by the Owner

2.2 MORTAR (Jointless/Dry-Stacked)

A. Polymer modified mortar complying with ANSI A118.4.

B. Mortar prepared to comply with ASTM C 270 Type S mortar.

2.3 BONDING AGENT

A. Exterior integral bonding agent meeting ASTM C 932

2.4 WEATHER BARRIER

A. ASTM D 226, Type 1, No. 15 non-perforated asphalt-saturated felt paper, UBC Standard 14-1

kraft waterproof building paper or UBC Standard no. 14-1 Kraft waterproof building paper or

ICC AC-38, Synthetic house wrap.

B. Metal Flashing: Use best flashing recommended by the manufacturer.

2.5 MISCELLANEOUS MATERIALS

A. Weeps: Round polyethylene tubing, 3/8-inch OD, Absorbent rope, 1/4 inch in diameter, 24

inches long or Free-draining polyethylene mesh, full width of head joint and 2 inches high.

B. Expanded Metal Lath: ASTM C 847, 2.5-lb/sq. yd. galvanized, expanded metal lath.

C. Acidic Cleaner: Cleaner designed for removing mortar stains from masonry surfaces; expressly

approved for intended use by cleaner manufacturer and adhered masonry veneer unit producer.

Use product as recommended by manufacturer of stone.

Page 8: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates upon whick work will be installed.

B. Coordinate with responsible entity to perform corrective work.

C. Commencement of work by installer is acceptance of substrate.

3.2 PREPARATION

A. Protection adjacent work from contact with mortar.

Prepare substrate in accordance with manufacturer's installation instructions

3.3 INSTALLATION

A. Install and clean stone in accordance with manufacturer's installation instructions for

Jointless/Dry-Stacked installation.

B. Apply repellent in accordance with repellent manufacturer's application instructions.

3.4 CLEANING

A. In-Progress Cleaning: Clean masonry as work progresses. Remove mortar fins and smears

before tooling joints.

B. Final Cleaning: After mortar is thoroughly cured, remove large mortar particles, scrub, and

rinse adhered masonry veneer.

1. Wet wall surfaces with water before applying cleaner; remove cleaner promptly by

rinsing thoroughly with clear water.

END OF SECTION 047300

Page 9: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

SECTION 061000 - ROUGH CARPENTRY

PART 1 - PRODUCTS

1.1 WOOD PRODUCTS, GENERAL

A. Lumber: Provide dressed lumber, S4S, marked with grade stamp of inspection agency.

1.2 TREATED MATERIALS

A. Provide preservative-treated materials for items indicated on Drawings, and the following:

1. Wood sills plates, blocking and similar concealed members in contact with masonry or

concrete.

1.3 FRAMING

A. Dimension Lumber: See Structural Notes.

1.4 MISCELLANEOUS PRODUCTS

A. Fasteners: See requirements of Structural drawings.

B. Metal Framing Anchors: Structural capacity, type, and size indicated.

PART 2 - EXECUTION

2.1 INSTALLATION

A. Set rough carpentry to required levels and lines, with members plumb, true to line, cut, and

fitted. Locate nailers, blocking, and similar supports to comply with requirements for attaching

other construction.

B. Framing Standard: Comply with AF&PA's WCD 1, "Details for Conventional Wood Frame

Construction," unless otherwise indicated.

C. Do not splice structural members between supports unless otherwise indicated.

D. Securely attach rough carpentry to substrates, complying with the following:

1. CABO NER-272 for power-driven fasteners.

2. Published requirements of metal framing anchor manufacturer.

END OF SECTION 061000

Page 10: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ARCHITECTURAL WOOD CASEWORK 064100 - 1

SECTION 064100 - ARCHITECTURAL WOOD CASEWORK

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Fabricator Qualifications: Certified participant in AWI's Quality Certification Program

B. Installer Qualifications: Fabricator of products.

PART 2 - PRODUCTS

2.1 ARCHITECTURAL CABINETS

A. Quality Standard: AWI, AWMAC, and WI's "Architectural Woodwork Standards."

B. Plastic-Laminate Cabinets: Custom grade.

1. Type of Construction: Face frame.

2. Cabinet and Door and Drawer Front Interface Style: Flush overlay.

3. Drawer Sides and Backs: Solid hardwood.

4. Drawer Bottoms: Hardwood plywood.

2.2 MATERIALS

A. Wood Moisture Content: 4 to 9 percent.

B. Medium-Density Fiberboard: ANSI A208.2, Grade 130.

C. Particleboard: ANSI A208.1.

D. Veneer-Faced Panel Products Hardwood Plywood.

E. High-Pressure Decorative Laminate: NEMA LD 3.

1. Manufacturers:

a. Abet Laminati, Inc.

b. Formica Corporation.

c. Lamin-Art, Inc.

d. Panolam Industries International, Inc.

e. Wilsonart International; Div. of Premark International, Inc.

Page 11: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ARCHITECTURAL WOOD CASEWORK 064100 - 2

2.3 CABINET HARDWARE AND ACCESSORY MATERIALS

A. Frameless Concealed Hinges European Type: BHMA A156.9, B01602, self-closing.

B. Wire Pulls: Back mounted, solid metal, 4 inches long, 5/16 inch in diameter 2-1/2 inches deep.

C. Catches: Magnetic catches, BHMA A156.9, B03141

D. Drawer Slides: BHMA A156.9, B05091. Roller type.

E. Exposed Hardware Finishes: Comply with BHMA A156.18 for BHMA code number indicated.

1. Finish: As selected by Owner.

2.4 FABRICATION

A. Complete fabrication to maximum extent possible before shipment to Project site. Disassemble

components only as necessary for shipment and installation. Where necessary for fitting at site,

provide ample allowance for scribing, trimming, and fitting.

2.5 FABRICATION

A. Complete fabrication to maximum extent possible before shipment to Project site. Disassemble

components only as necessary for shipment and installation. Where necessary for fitting at site,

provide ample allowance for scribing, trimming, and fitting.

2.6 INSTALLATION

A. Before installation, condition cabinets to average prevailing humidity conditions in installation

areas.

B. Install cabinets to comply with referenced quality standard for grade specified.

C. Install cabinets level, plumb, true, and straight. Shim as required with concealed shims. Install

level and plumb (including tops) to a tolerance of 1/8 inch in 96 inches (3 mm in 2400 mm).

D. Scribe and cut cabinets to fit adjoining work, refinish cut surfaces, and repair damaged finish at

cuts.

E. Anchor cabinets to anchors or blocking built in or directly attached to substrates. Fasten with

countersunk concealed fasteners and blind nailing. Use fine finishing nails[ or finishing screws]

for exposed nailing, countersunk and filled flush.

F. Cabinets: Install so doors and drawers are accurately aligned. Adjust hardware to center doors

and drawers in openings and to provide unencumbered operation.

1. Fasten wall cabinets through back, near top and bottom, at ends.

Page 12: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ARCHITECTURAL WOOD CASEWORK 064100 - 3

END OF SECTION 064100

Page 13: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

THERMAL INSULATION 072100 - 1

SECTION 072100 - THERMAL INSULATION

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data[ and ICC-ES evaluation reports for foam-plastic insulation].

B. Surface-Burning Characteristics: According to ASTM E 84 by a qualified testing agency.

Identify products with appropriate markings of applicable testing agency.

PART 2 - PRODUCTS

2.1 INSULATION PRODUCTS

A. Extruded-Polystyrene Board Insulation: ASTM C 578, with flame-spread and smoke-

developed indexes of 75 and 450, respectively.

1. Manufacturers:[ One of the following:]

a. DiversiFoam Products.

b. Dow Chemical Company (The).

c. Owens Corning.

d. Pactiv Building Products.

e. Or as approved by the owner.

B. Glass-Fiber-Blanket Insulation: ASTM C 665, with flame-spread and smoke-developed

indexes of 25 and 450, respectively.

1. Manufacturers:[ One of the following:]

a. CertainTeed Corporation.

b. Guardian Building Products, Inc.

c. Johns Manville.

d. Knauf Insulation.

e. Owens Corning.

f. As approved by the Owner.

Page 14: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

THERMAL INSULATION 072100 - 2

C. Cellulosic-Fiber Loose-Fill Insulation: ASTM C 739; chemically treated for flame-resistance,

processing, and handling characteristics.

D. Glass-Fiber Loose-Fill Insulation: ASTM C 764, application, with flame-spread and smoke-

developed indexes of 25 and 450, respectively.

2.2 ACCESSORIES

A. Sheet Radiant Barrier: ASTM C 1313, foil on one side, flame-spread and smoke-developed

indexes of 75 and 450, respectively, and water-vapor transmission of 1 perm, maximum.

1. Products:[ One of the following:]

a. Fi-Foil Company; Radiant Shield.

b. Innovative Energy, Inc.; R+Heatshield [Commercial Solid] [Perforated].

c. Innovative Insulation, Inc.; Super R [Premium] [Plus].

d. TVM Building Products; Reflective [House Wrap] [Vapor Barrier].

e. As approved by the Owner.

B. Vapor Retarder: Polyethylene.

1. Products:[ One of the following:]

a. Raven Industries Inc.; DURA-SKRIM 6WW.

b. Reef Industries, Inc.; Griffolyn T-65.

c. As approved by the owner.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install insulation in areas and in thicknesses indicated or required to produce R-values indicated.

Cut and fit tightly around obstructions and fill voids with insulation.

B. Maintain 3-inch (76-mm) clearance of insulation around recessed lighting fixtures not rated for

or protected from contact with insulation.

C. Install eave ventilation troughs between roof framing members in insulated attic spaces at

vented eaves.

D. Except for loose-fill insulation and insulation that is friction fitted in stud cavities, bond units to

substrate with adhesive or use mechanical anchorage to provide permanent placement and

support of units.

Page 15: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

THERMAL INSULATION 072100 - 3

E. Place loose-fill insulation to comply with ASTM C 1015.

1. Comply with the CIMA's Special Report #3, "Standard Practice for Installing Cellulose

Insulation."

F. Spray-Applied Insulation: Apply insulation according to manufacturer's written instructions.

Do not apply insulation until installation of pipes, ducts, conduits, wiring, and electrical outlets

in walls is completed and items not indicated to receive insulation are masked. After insulation

is applied, make flush with face of studs.

G. Install sheet radiant barriers according to ASTM C 1158.

H. Extend vapor retarder to extremities of areas to be protected from vapor transmission. Secure in

place with adhesives or other anchorage. Locate seams at framing members, overlap, and seal

with tape. Seal joints caused by pipes, conduits, electrical boxes, and similar items with tape.

END OF SECTION 072100

Page 16: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

SINGLE PLY ROOFING SYSTEM

07500 - 1

SECTION 07500 – SINGLE PLY ROOFING SYSTEM

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Warranties: Manufacturer's standard form or customized, without monetary limitation, signed

by roofing manufacturer agreeing to repair leaks due to defects in materials or workmanship for

period of 15 years.

PART 2 - PRODUCTS

2.1 ROOFING SYSTEM

A. Sarnafast System as manufactured by Sika Sarnafil.

B. Thickness: 60 mils

C. Rigid insulation: as recommended by Sika Sarnafil to achieve R = 30.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install as recommended by Sika Sarnafil for system.

B. Install sheet flashings and preformed flashing accessories and adhere to substrates as

recommended by Sika Sarnafil for system.

C. Clean-up after installation.

END OF SECTION 07500

Page 17: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

METAL ROOF PANELS 076100 - 1

SECTION 076100 - METAL ROOFING PANELS

PART 1 - GENERAL

1.2 SUMMARY

A. This Section includes

1. Factory formed metal roof panels: Standing-seam, hidden fastener, non-insulated

1.4 PERFORMANCE REQUIREMENTS

A. Wind-Uplift Resistance: Capable of producing sheet metal roofing assemblies that comply with UL

580 for Class 90 wind-uplift resistance.

1.5 SUBMITTALS

A. Product Data: Include construction details, material descriptions, dimensions of individual

components and profiles, and finishes for each type of metal roof panel and accessory, including each

type of underlayment product indicated:

D. Samples: For exposed finish.

1.6 QUALITY ASSURANCE

A. Installer Qualifications: Installer of sheet metal roofing for a minimum of 10 years.

A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions

permit assembly of metal roof panels to be performed according to manufacturers' written instructions

and warranty requirements.

1.10 WARRANTY

A. Special Warranty on Finishes: Manufacturer's standard form in which manufacturer agrees to repair

finish or replace sheet metal roofing that shows evidence of deterioration of factory-applied finishes

within specified warranty period.

1. Fluoropolymer Finish Warranty Period: 30 years from date of Substantial Completion.

B. Special Installer's Warranty: Specified form in which Roofing Installer agrees to repair or replace

components of custom-fabricated sheet metal roofing that fail in materials or workmanship within 5 years

from date of Substantial Completion.

PART 2 - PRODUCTS

A. General: Provide factory-formed metal roof panels designed to be field assembled by lapping and

interconnecting raised side edges of adjacent panels with joint type indicated and mechanically attaching

panels to supports using concealed clips in side laps. Include clips, cleats, pressure plates, and accessories

required for weathertight installation. Unless more stringent requirements are indicated, comply with

ASTM E 1514.

B. Vertical-Rib, Snap-Joint, Standing-Seam Metal Roof Panels. Formed with vertical ribs at panel edges

and flat pan between ribs; designed for sequential installation by mechanically attaching panels to

supports using concealed clips located under one side of panels and engaging opposite edge of adjacent

panels, and snapping panels together.

1. Basis-of-Design Product: ATAS International, Inc.; PC™ Snap On System; PCP120 or a comparable

product

2. Manufacturer:

a. ATAS International, Inc.

3. Material: 24 gauge metallic coated Steel

a. Texture: Smooth

b. Pan Coverage: 12-5/8"

c. Seam Height: 1"

Page 18: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

METAL ROOF PANELS 076100 - 2

d. KYNAR 5000® PDVF or HYLAR 5000® Finish

e. Standard color to be chosen later

2.3 UNDERLAYMENT

A. Self-Adhering, High-Temperature Sheet: 45 mil homogeneous rubberized asphalt waterproofing

compound, glass fiber reinforced designed specifically for use under sheet metal roofing. Basis for

design ATAS ATA-Shield as supplied by ATAS International, Inc. Thermal Stability: Resistant to 240

deg F; ASTM D 1970. Low Temperature Flexibility: Passes after testing at minus 20 deg F; ASTM D

1970.

2.4 MISCELLANEOUS MATERIAL

A. Fasteners: Self-tapping screws, self-locking rivets and bolts, and other suitable fasteners designed to

withstand design loads. Manufacturer shall provide or authorize all fasteners utilized with the sheet metal

roofing system.

1. Exposed Fasteners: Heads matching color of sheet metal roofing by means of plastic caps or factory-

applied coating.

2. Fasteners for Flashing and Trim: Blind fasteners or screws spaced to resist wind uplift loads.

B. Sealing Tape: Pressure-sensitive, 100 percent solid polyisobutylene compound sealing tape with

release-paper backing. Provide permanently elastic, non-sag, non-toxic, non-staining tape.

C. Elastomeric Joint Sealant: ASTM C 920, of base polymer, type, grade, class, and use classifications

required to produce joints in sheet metal roofing that will remain weathertight.

D. Expansion-Joint Sealant: For hooked-type expansion joints, which must be free to move, provide

non-setting, non-hardening, non-migrating, heavy-bodied polyisobutylene sealant.

E. Bituminous Coating: Cold-applied asphalt mastic, SSPC-Paint 12, compounded for 15 mil dry film

thickness per coat.

2.5 ACCESSORIES

A. Sheet Metal Roofing Accessories: Provide components required for a complete sheet metal roofing

assembly including trim, copings, fasciae, corner units, ridge closures, clips, flashings, sealants, gaskets,

fillers, closure strips, and similar items. Match material and finish of sheet metal roofing, unless

otherwise indicated. All trim and flashing components shall be supplied in a minimum of 12'-0” lengths

and shall conform to manufacturer's standard part dimensions and details.

1. 24 ga. Steel clips designed to withstand negative-load requirements.

2. Closures: Closed-cell, expanded, cellular, rubber or cross linked, polyolefin-foam or closed-cell

laminated polyethylene; minimum 1-inch thick, flexible closure strips; cut or premolded to match sheet

metal roofing profile. Provide closure strips where indicated or necessary to ensure weathertight

construction.

3. Sealants as recommended by manufacturer.

4. Fasteners as recommended by manufacturer.

B. Flashing and Trim: Formed from matching materials as sheet metal roof panel in gauges noted.

Provide flashing and trim in heavier gauge materials as required to seal against weather and to provide

finished appearance. Locations include, but are not limited to, eaves, rakes, corners, bases, framed

openings, ridges, fasciae, and fillers. Finish flashing and trim with same finish system as adjacent sheet

metal roofing.

C. Snow Guards: Prefabricated, non-corrosive units designed for compatibility with metal roof panels.

2.6 EQUIPMENT

A. Manufacturer must maintain quality control and maintenance procedures of all equipment.

Verification of quality control procedures must be validated by a 3rd party entity.

1. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products

that may be incorporated into the Work include, but are not limited to, the following:

Page 19: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

METAL ROOF PANELS 076100 - 3

2. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

a. ATAS International, Inc.

2.7 FABRICATION

A. General: Fabricate sheet metal roofing and components to comply with details shown, manufacturers

installation details and recommendations in SMACNA's "Architectural Sheet Metal Manual" and NRCA

Waterproofing Manual that apply to the design, dimensions (pan width and seam height), geometry, metal

thickness, and other characteristics of installation indicated. Fabricate sheet metal roofing and accessories

at the manufacturer’s location to the greatest extent possible.

B. General: Fabricate sheet metal roofing panels to comply with details shown and sheet metal roofing

manufacturer's written instructions.

C. Fabricate sheet metal roofing to allow for expansion in running work sufficient to prevent leakage,

damage, and deterioration of the Work. Form exposed sheet metal work to fit substrates without

excessive oil canning, buckling, and tool marks, true to line and levels indicated, and with exposed edges

folded back to form hems.

1. Fold and cleat eaves as required by manufacturer to insure weathertightness and wind uplift

resistance.

2. Form and fabricate sheets, seams, strips, cleats, valleys, ridges, edge treatments, integral flashings,

and other components of metal roofing to profiles, patterns, and drainage arrangements shown and as

required for leak proof construction and wind uplift resistance.

D. Metal Protection: Where dissimilar metals will contact each other, protect against galvanic action by

painting contact surfaces with bituminous coating, by applying rubberized-asphalt underlayment to each

contact surface, or by other permanent separation as recommended by manufacturers of dissimilar metals

or by fabricator.

E. Sheet Metal Accessories: Custom fabricate flashings and trim to comply with recommendations in

SMACNA's "Architectural Sheet Metal Manual" that apply to design, dimensions, metal, and other

characteristics of item indicated. Obtain field measurements for accurate fit before manufacturer

fabrication.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements

for installation tolerances, metal roof panel supports, and other conditions affecting performance of work.

1. Examine primary and secondary roof framing to verify that rafters, purlins, angles, channels, and

other structural panel support members and anchorages have been installed within alignment tolerances

required by metal roof panel manufacturer.

2. Examine solid roof sheathing to verify that sheathing joints are supported by framing or blocking and

that installation is within flatness tolerances required by metal roof panel manufacturer.

3. For the record, prepare written report for the General Contractor, endorsed by Installer, listing

conditions detrimental to performance of work.

B. Examine roughing-in for components and systems penetrating metal roof panels to verify actual

locations of penetrations relative to seam locations of metal roof panels before metal roof panel

installation.

C. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Lay out and examine substrate before installation of sheet metal roofing. Space fasteners as required

to resist design uplift, but not more than 24 inches o.c.

B. Install flashings and other sheet metal to comply with requirements specified in Division 7 Section

"Sheet Metal Flashing and Trim

3.3 UNDERLAYMENT INSTALLATION

Page 20: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

METAL ROOF PANELS 076100 - 4

A. Self-Adhering Sheet Underlayment; ATA-SHIELD™: Install self-adhering sheet underlayment,

wrinkle free, on roof sheathing under sheet metal roofing. Comply with temperature restrictions of

underlayment manufacturer for installation; use primer rather than nails for installing underlayment at low

temperatures. Apply at locations noted on Drawings in shingle fashion to shed water, with end laps of not

less than 6 inches staggered 24 inches between courses. Overlap side edges not less than 3.5 inches.

Extend underlayment a minimum of 1.5 inches of fascia board. Roll laps with roller. Cover underlayment

within 14 days.

3.4 INSTALLATION, GENERAL

A. General: Anchor sheet metal roofing and other components of the Work securely in place, with

provisions for thermal and structural movement. Install fasteners, protective coatings, separators,

sealants, and other miscellaneous items as required for a complete roofing system and as recommended

by fabricator for sheet metal roofing.

1. Field cutting of sheet metal roofing by torch is not permitted.

2. Rigidly fasten ridge end of sheet metal roofing and allow for positive panel attachment as per

manufacturer’s recommendations. All flashing details shall accommodate thermal movement.

3. Provide metal closures at peaks, ridge, gable and hip caps.

4. Flash and seal sheet metal roofing with weather closures at eaves, rakes, and at perimeter of all

openings. Fasten with self-tapping screws.

5. Locate roofing splices over, but not attached to, structural supports. Stagger roofing splices and end

laps to avoid a four-panel lap splice condition.

6. Lap metal flashing over sheet metal roofing to allow moisture to run over and off the material.

B. Fasteners: Use fasteners of size and length as required for compatibility with substrate.

C. Metal Protection: Where dissimilar metals will contact each other or corrosive substrates, protect

against galvanic action by painting contact surfaces with bituminous coating, by applying rubberized-

asphalt underlayment to each contact surface, or by other permanent separation as recommended by

fabricator of sheet metal roofing or manufacturers of dissimilar metals.

1. Separate sheet metal roofing from bituminous coating where roofing will contact wood, ferrous metal,

or cementitious construction. Interlock and overlap shingles and stagger end joints from shingles above

and below according to shingle manufacturer's written instructions.

D. Conceal fasteners and expansion provisions where possible in exposed work and locate to minimize

possibility of leakage. Cover and seal fasteners and anchors as required for a tight installation.

3.5 ACCESSORY INSTALLATION

A. General: Install accessories with positive anchorage to building and weathertight mounting and

provide for thermal expansion. Coordinate installation with flashings and other components.

1. Install components required for a complete sheet metal roofing assembly including trim, copings,

ridge closures, seam covers, flashings, sealants, gaskets, fillers, closure strips, and similar items.

2. Comply with performance requirements, manufacturer's written installation instructions, and

SMACNA's "Architectural Sheet Metal Manual" and NRCA Waterproofing Manual. Provide concealed

fasteners where possible, and set units true to line and level as indicated. Install work with laps, joints,

and seams that will be permanently watertight and weather resistant.

B. Coordinate with installation of:

1. Cold Formed Metal Framing, as noted in Section 5

2. Rough Carpentry, as noted in Section 6

3. Sheet Metal Flashing and Trim, as noted in Section 7

C. Pipe Flashing: Form flashing around pipe penetration and metal roof panels. Fasten and seal to metal

roof panels as recommended by manufacturer.

3.6 CLEANING AND PROTECTION

Page 21: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

METAL ROOF PANELS 076100 - 5

A. Remove temporary protective coverings and strippable films, if any, as sheet metal roofing is

installed. On completion of sheet metal roofing installation, clean finished surfaces, including removing

unused fasteners, metal filings, pop rivet stems, and pieces of flashing. Maintain in a clean condition

during construction.

END OF SECTION 076100

Page 22: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

SHEET METAL FLASHING AND TRIM 076200 - 1

SECTION 076200 - SHEET METAL FLASHING AND TRIM

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Comply with SMACNA's "Architectural Sheet Metal Manual." Conform to dimensions and

profiles shown unless more stringent requirements are indicated.

B. Coordinate installation of sheet metal flashing and trim with interfacing and adjoining

construction to provide a leakproof, secure, and noncorrosive installation.

PART 2 - PRODUCTS

2.1 SHEET METAL

A. Metallic-Coated Steel Sheet: Galvanized structural-steel sheet, ASTM A 653/A 653M, G90

(Z275), or aluminum-zinc alloy-coated structural-steel sheet, ASTM A 792/A 792M,

Class AZ50 coating designation, Grade 40 0.028-inch

2.2 ACCESSORIES

A. Self-Adhering Sheet Underlayment, High Temperature: Butyl or SBS-modified asphalt; slip-

resisting-polyethylene surfaced; with release paper backing; cold applied. Stable after testing at

240 deg F and passes after testing at minus 20 deg F ; ASTM D 1970.

B. Slip Sheet: Building paper, 3-lb/100 sq. ft. minimum, rosin sized.

C. Fasteners: Wood screws, annular-threaded nails, self-tapping screws, self-locking rivets and

bolts, and other suitable fasteners.

1. Exposed Fasteners: Heads matching color of sheet metal roofing using plastic caps or

factory-applied coating.

2. Spikes and Ferrules: Same material as gutter; with spike with ferrule matching internal

gutter width.

3. Fasteners for Copper: Copper, hardware bronze, or Series 300 stainless steel.

4. Fasteners for Aluminum Sheet: Aluminum or Series 300 stainless steel.

5. Fasteners for Stainless-Steel Sheet: Series 300 stainless steel.

6. Fasteners for Zinc-Tin Alloy-Coated Stainless-Steel Sheet: Series 300 stainless steel.

7. Fasteners for Metallic-Coated Steel Sheet: Hot-dip galvanized steel or Series 300

stainless steel.

D. Solder for Zinc-Tin Alloy-Coated Stainless Steel: ASTM B 32, 100 percent tin.

E. Butyl Sealant: ASTM C 1311, solvent-release butyl rubber sealant.

Page 23: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

SHEET METAL FLASHING AND TRIM 076200 - 2

F. Bituminous Coating: Cold-applied asphalt emulsion complying with ASTM D 1187.

2.3 FABRICATION

A. Fabricate sheet metal flashing and trim to comply with recommendations in SMACNA's

"Architectural Sheet Metal Manual" that apply to the design, dimensions, metal, and other

characteristics of the item indicated.

B. Expansion Provisions: Where lapped expansion provisions cannot be used, form expansion

joints of intermeshing hooked flanges, not less than 1 inch deep, filled with butyl sealant

concealed within joints.

C. Fabrication Tolerances: Fabricate sheet metal flashing and trim that is capable of installation to

tolerances specified in MCA's "Guide Specification for Residential Metal Roofing."

D. <Insert list of items required, identify sheet metal from which each is to be fabricated, and

reference appropriate SMACNA plate number, if not detailed on Drawings>.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with SMACNA's "Architectural Sheet Metal Manual." Allow for thermal expansion;

set true to line and level. Install Work with laps, joints, and seams permanently watertight and

weatherproof; conceal fasteners where possible.

B. Sealed Joints: Form nonexpansion, but movable, joints in metal to accommodate elastomeric

sealant to comply with SMACNA standards.

C. Fabricate nonmoving seams in sheet metal with flat-lock seams.[ For aluminum, form seams

and seal with epoxy seam sealer. Rivet joints for additional strength.]

D. Separate dissimilar metals with a bituminous coating or polymer-modified, bituminous sheet

underlayment.

END OF SECTION 076200

Page 24: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

JOINT SEALANTS 079200 - 1

SECTION 079200 - JOINT SEALANTS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data and color Samples.

PART 2 - PRODUCTS

2.1 JOINT SEALANTS

A. Low-Emitting Materials: Sealants shall comply with the following limits for VOC content:

1. Architectural Sealants: 250 g/L.

B. Low-Emitting Materials:

1. Interior sealants shall comply with the testing and product requirements of the California

Department of Health Services' "Standard Practice for the Testing of Volatile Organic

Emissions from Various Sources Using Small-Scale Environmental Chambers."

C. Compatibility: Provide joint sealants, joint fillers, and other related materials that are

compatible with one another and with joint substrates under service and application conditions.

2.2 MISCELLANEOUS MATERIALS

A. Provide sealant backings of material that are nonstaining; are compatible with joint substrates,

sealants, primers, and other joint fillers; and are approved for applications indicated by sealant

manufacturer based on field experience and laboratory testing.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with ASTM C 1193.

B. Install sealant backings to support sealants during application and to produce cross-sectional

shapes and depths of installed sealants that allow optimum sealant movement capability.

C. Install bond-breaker tape behind sealants where sealant backings are not used between sealants

and backs of joints.

END OF SECTION 079200

Page 25: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

DOORS 081423 - 1

SECTION 081423 - DOORS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data.

PART 2 - PRODUCTS

2.1 DOORS

A. Doors as selected by the owner and contractor.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with WDMA's "How to Store, Handle, Finish, Install, and Maintain Wood Doors."

1. Install fire-rated doors to comply with NFPA 80.

END OF SECTION 081423

Page 26: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 1

SECTION 084113 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data, Shop Drawings, and color Samples.

1. For entrance doors, include hardware schedule.

PART 2 - PRODUCTS

2.1 ALUMINUM-FRAMED STOREFRONTS

A. Manufacturers:[ One of the following:]

B. Basis-of-Design Product: or a comparable product of one of the following:

1. Arcadia, Inc.

2. Arch Aluminum & Glass Co., Inc.

3. CMI Architectural

4. Commercial Architectural Products, Inc.

5. EFCO Corporation.

6. Kawneer North America; an Alcoa company.

7. Leed Himmel Industries, Inc.

8. Pittco Architectural Metals, Inc.

9. TRACO.

10. Tubelite.

11. United States Aluminum.

12. Vistawall Architectural Products; The Vistawall Group; a Bluescope Steel company.

13. YKK AP America Inc.

C. Accessible Entrances: Comply with ICC A117.1.

D. Performance Requirements:

Page 27: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 2

1. Limit deflection of framing members normal to wall plane to 1/175 of clear span.

2. Limit deflection of framing members parallel to glazing plane to L/360 of clear span or

1/8 inch, whichever is smaller.

3. Air Infiltration: Limited to 0.06 cfm/sq. ft. of system surface area when tested according

to ASTM E 283 at a static-air-pressure difference of 1.57 lbf/sq. ft. (75 Pa.

4. Water Penetration: Systems do not evidence water leakage when tested according to

ASTM E 331 at minimum differential pressure of 20 percent of positive wind-load design

pressure, but not less than 6.24 lbf/sq. ft.

5. Thermal Conductance: Average U-factor of not more than 0.57 Btu/sq. ft. x h x deg F.

E. Aluminum: Alloy and temper recommended by manufacturer for type of use and finish

indicated; ASTM B 209 sheet; ASTM B 221extrusions.

F. Glazing: As specified in Section 088000 "Glazing."

G. Framing Members: Manufacturer's standard extruded-aluminum framing members of thickness

required and reinforced as required to support imposed loads.

H. Doors: 1-3/4-inch- thick glazed doors with minimum 0.125-inch-thick, extruded-aluminum

tubular rail and stile members. Mechanically fasten corners with reinforcing brackets that are

deeply penetrated and fillet welded or that incorporate concealed tie rods. Provide snap-on

extruded-aluminum glazing stops, and preformed gaskets.

1. Door Design: Narrow stile; 2-1/8-inch nominal width.

2. Accessible Doors: Smooth surfaced for width of door in area within 10 inches (255 mm)

above floor or ground plane.

3. Exterior Doors: Provide compression weather stripping at fixed stops. At other

locations, provide sliding weather stripping retained in adjustable strip mortised into door

edge.

I. Fasteners and Accessories: Compatible with adjacent materials, corrosion resistant,

nonstaining, and nonbleeding. Use concealed fasteners except for application of door hardware.

J. Fabrication: Fabricate framing in profiles indicated for flush glazing (without projecting stops).

Provide subframes and reinforcing of types indicated or, if not indicated, as required for a

complete system. Factory assemble components to greatest extent possible. Disassemble

components only as necessary for shipment and installation.

1. Door Framing: Reinforce to support imposed loads. Factory assemble door and frame

units and factory install hardware to greatest extent possible. Reinforce door and frame

units for hardware indicated. Cut, drill, and tap for factory-installed hardware before

finishing components.

K. Aluminum Finish: [Class II, clear anodic finish; complying with AAMA 611] [Class I, clear

anodic finish; complying with AAMA 611] [Class II, color anodic finish; complying with

AAMA 611] [Class I, color anodic finish; complying with AAMA 611] [Baked-enamel or

powder-coat finish complying with AAMA 2603] [Fluoropolymer two-coat coating system

complying with AAMA 2604] [Fluoropolymer three-coat coating system complying with

AAMA 2605].

Page 28: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS 084113 - 3

PART 3 - EXECUTION

3.1 INSTALLATION

A. Isolate metal surfaces in contact with incompatible materials, including wood, by painting

contact surfaces with bituminous coating or primer, or by applying sealant or tape

recommended by manufacturer.

B. Install components to drain water passing joints, condensation occurring within framing

members, and moisture migrating within the system to exterior.

C. Set continuous sill members and flashing in full sealant bed as specified in Section 079200

"Joint Sealants" to produce weathertight installation.

D. Install framing components true in alignment with established lines and grades to the following

tolerances:

1. Variation from Plane: Limit to 1/8 inch in 12 feet ; 1/4 inch over total length.

2. Alignment: For surfaces abutting in line, limit offset to 1/16 inch. For surfaces meeting

at corners, limit offset to 1/32 inch.

3. Diagonal Measurements: Limit difference between diagonal measurements to.

E. Install doors without warp or rack. Adjust doors and hardware to provide tight fit at contact

points and smooth operation.

END OF SECTION 084113

Page 29: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

DOOR HARDWARE 087100 - 1

SECTION 087100 - DOOR HARDWARE

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Hardware schedule and keying schedule.

PART 2 - PRODUCTS

2.1 HARDWARE

A. Door hardware shall be as selected by the owner.

B. Key as directed by the owner.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Mount hardware in locations required to comply with governing regulations and according to

SDI A250.8 and DHI WDHS.3.

B. Deliver keys to Owner.

3.2 HARDWARE SCHEDULE

A. See Hardware Schedule on drawings.

END OF SECTION 087100

Page 30: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

GLAZING 088000 - 1

SECTION 088000 - GLAZING

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Glazing Publications: Comply with published recommendations of glass product manufacturers

and organizations below, unless more stringent requirements are indicated.

1. GANA Publications: GANA's "Glazing Manual."

2. IGMA Publication for Insulating Glass: SIGMA TM-3000, "North American Glazing

Guidelines for Sealed Insulating Glass Units for Commercial and Residential Use."

PART 2 - PRODUCTS

2.1 GLASS, GENERAL

A. Safety Glass: Category II materials complying with testing requirements in 16 CFR 1201.

Provide safety glazing labeling where safety glass is indicated.

2.2 GLASS PRODUCTS

A. Float Glass: ASTM C 1036, Type I, Quality-Q3.

B. Heat-Treated Float Glass: ASTM C 1048; Type I; Quality-Q3.

C. Insulating-Glass Units: Factory-assembled units consisting of sealed lites of glass separated by

a dehydrated interspace, qualified according to ASTM E 2190

2.3 GLAZING SEALANTS

A. Glazing Sealant: Neutral-curing silicone glazing sealant complying with ASTM C 920, Type S,

Grade NS, Class 25, Use NT.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with combined recommendations of manufacturers of glass, sealants, gaskets, and other

glazing materials, unless more stringent requirements are contained in GANA's "Glazing

Manual."

B. Set glass lites in each series with uniform pattern, draw, bow, and similar characteristics.

Page 31: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

GLAZING 088000 - 2

C. Remove nonpermanent labels, and clean surfaces immediately after installation.

END OF SECTION 088000

Page 32: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

GYPSUM BOARD 092900 - 1

SECTION 092900 - GYPSUM BOARD

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Fire-Resistance-Rated Assemblies: Provide materials and construction identical to those tested

in assemblies per ASTM E 119 by an independent testing and inspecting agency acceptable to

authorities having jurisdiction.

2.2 PANEL PRODUCTS

A. Provide in maximum lengths available to minimize end-to-end butt joints.

B. Interior Gypsum Board: ASTM C 1396/C 1396M, in thickness indicated, with manufacturer's

standard edges. Regular type unless otherwise indicated and Type X where indicated.

1. Manufacturers:

a. American Gypsum.

b. CertainTeed Corp.

c. Georgia-Pacific Gypsum LLC.

d. Lafarge North America Inc.

e. National Gypsum Company.

f. PABCO Gypsum.

g. Temple-Inland.

h. USG Corporation.

i.

C. Water-Resistant Gypsum Backing Board: ASTM C 1396/C 1396M, in thickness indicated.

2.3 ACCESSORIES

A. Trim Accessories: ASTM C 1047, formed from galvanized or aluminum-coated steel sheet,

rolled zinc, plastic, or paper-faced galvanized-steel sheet. For exterior trim, use accessories

formed from hot-dip galvanized-steel sheet, plastic, or rolled zinc.

1. Provide square cornerbead at outside corners unless otherwise indicated.

2. Provide LC-bead (J-bead) at exposed panel edges.

B. Joint-Treatment Materials: ASTM C 475/C 475M.

Page 33: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

GYPSUM BOARD 092900 - 2

C. Sound-Attenuation Blankets: ASTM C 665, Type I (unfaced).

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install gypsum board to comply with ASTM C 840.

1. Isolate gypsum board assemblies from abutting structural and masonry work. Provide

edge trim and acoustical sealant.

2. Single-Layer Fastening Methods: Fasten gypsum panels to supports with screws.

B. Install cementitious backer units to comply with ANSI A108.11.

C. Finishing Gypsum Board: ASTM C 840.

1. At concealed areas, unless a higher level of finish is required for fire-resistance-rated

assemblies, provide Level 1 finish: Embed tape at joints.

2. At substrates for tile, provide Level 2 finish: Embed tape and apply separate first coat of

joint compound to tape, fasteners, and trim flanges.

3. Unless otherwise indicated, provide Level 4 finish: Embed tape and apply separate first,

fill, and finish coats of joint compound to tape, fasteners, and trim flanges.

END OF SECTION 092900

Page 34: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TILING 093000 - 1

SECTION 093000 – TILING

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data and Samples.

B. Obtain tile of each type and color or finish from same production run for each contiguous area

PART 2 - PRODUCTS

2.1 CERAMIC TILE

A. Ceramic tile that complies with Standard grade requirements in ANSI A137.1, "Specifications

for Ceramic Tile."

1. Manufacturers: One of the following:

a. American Olean; Division of Dal-Tile International Inc.

b. Crossville, Inc.

c. Daltile; Division of Dal-Tile International Inc.

d. Deutsche Steinzeug America, Inc.

e. Interceramic.

f. Lone Star Ceramics Company.

g. Grupo Porcelanite.

h. Portobello America, Inc.

i. Seneca Tiles, Inc.

2. Module Size: See Finish Schedule.

3. Color and Pattern: As selected.

4. Grout Color: As selected

5. Trim Units:

a. Base: Coved.

b. Wainscot Cap for Portland Cement Mortar Installations: Bead.

c. External Corners for Portland Cement Mortar Installations: Bead (bullnose)..

d. Internal Corners: Field-butted square corners. For coved base and cap, use angle

pieces designed to fit with stretcher shapes.

2.2 STONE THRESHOLDS

A. Stone Threshold Type

1. Stone Type: Marble, complying with ASTM C 503,

2. Color: As selected.

3. Finish: Polished

Fabricate thresholds to be not more than 1/2 inch above adjoining finished floor surfaces, with

transition edges beveled on a slope of no greater than 1:2.

2.3 INSTALLATION MATERIALS

A. Cementitious Backer Units: ANSI A118.9 or ASTM C 1325, 1/2 inch (12.7 mm) thick.

1. Products: One of the following:

a. C-Cure; C-Cure Board 990.

b. Custom Building Products; Wonderboard.

c. FinPan, Inc.; Util-A-Crete Concrete Backer Board.

d. USG Corporation; DUROCK Cement Board.

Page 35: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TILING 093000 - 2

B. Waterproofing Membranes for Thin-Set Installations: ANSI A118.10, fabric-faced chlorinated

polyethylene, PVC, or polyethylene sheet product

C. Setting and Grouting Materials: Comply with material standards in ANSI's "Specifications for

the Installation of Ceramic Tile" that apply to materials and methods indicated.

1. Thin-Set Mortar Type: Latex-portland cement.

2. Grout Type: Polymer modified

a. Manufacturers: One of the following:

1) Boiardi Products; a QEP company.

2) Bonsal American; an Oldcastle company.

3) Bostik, Inc.

4) C-Cure.

5) Custom Building Products.

6) Jamo Inc.

7) Laticrete International, Inc.

8) MAPEI Corporation.

9) Southern Grouts & Mortars, Inc.

10) Summitville Tiles, Inc.

11) TEC; a subsidiary of H. B. Fuller Company.

D. Stone Floor Sealer: Colorless, slip and stain resistant, not affecting color or physical properties

of stone surfaces.

1. Manufacturers: One of the following:

a. Bostik, Inc.

b. Custom Building Products.

c. Hillyard, Inc.

d. HMK Stone Care System.

e. Summitville Tiles, Inc.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Comply with TCA's "Handbook for Ceramic Tile Installation" for TCA installation methods

specified in tile installation schedules. Comply with parts of ANSI A108 Series "Specifications

for Installation of Ceramic Tile" that are referenced in TCA installation methods, specified in

tile installation schedules, and apply to types of setting and grouting materials used.

1. For installations indicated below, follow procedures in ANSI's "Specifications for the

Installation of Ceramic Tile" for providing 95 percent mortar coverage.

a. Tile floors in wet areas.

b. Tile floors composed of tiles 8 by 8 inches or larger.

B. Perform cutting and drilling of tile without marring visible surfaces. Carefully grind cut edges

of tile abutting trim, finish, or built-in items for straight aligned joints. Fit tile closely to

electrical outlets, piping, fixtures, and other penetrations so plates, collars, or covers overlap

tile.

C. Lay tile in grid pattern unless otherwise indicated. Align joints where adjoining tiles on floor,

base, walls, and trim are the same size.

D. Install cementitious backer units and treat joints according to ANSI A108.11.

E. Where indicated, prepare substrates to receive waterproofing by applying a reinforced mortar

bed that complies with ANSI A108.1A and is sloped 1/4 inch per foot (1:50) toward drains.

F. Install waterproofing to comply with ANSI A108.13.

G. Do not install tile over waterproofing until waterproofing has cured and been tested to

determine that it is watertight.

H. Install stone thresholds in same type of setting bed as adjacent floor unless otherwise indicated.

Page 36: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TILING 093000 - 3

I. Apply sealer to cleaned stone tile flooring according to sealer manufacturer's written

instructions.

J. Interior Floor Tile Installation Method(s):

1. Over Concrete Subfloors: TCA F113 thin-set mortar

K. Interior Wall Tile Installation Method(s):

1. Over Concrete and Masonry: TCA W202 (thin-set mortar)

Page 37: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ACOUSTICAL CEILINGS 095100 - 1

SECTION 095100 - ACOUSTICAL CEILINGS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data and Samples.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Seismic Standard: Acoustical ceiling shall withstand the effects of earthquake motions

determined according to ASCE/SEI 7.

2.2 ACOUSTICAL PANELS

A. Manufacturers:[ One of the following:]

B. Basis-of-Design Product: As below or a comparable product of one of the following:

1. Armstrong World Industries, Inc. Armstrong Second Look 2’x2’ panels

C. Color: White.

D. Edge Detail: Reveal sized to fit exposed flange of suspension system

E. Modular Size: 24 by 24 inches.

2.3 CEILING SUSPENSION SYSTEM <Insert drawing designation, if any; e.g., CSS-1>

A. Ceiling Suspension System: .

1. Manufacturers: One of the following:

a. Armstrong World Industries, Inc.

b. CertainTeed Corp.

c. Chicago Metallic Corporation.

d. USG Interiors, Inc.; Subsidiary of USG Corporation.

2. Face Design: Flat, flush.

3. Face Finish: Painted white.

Page 38: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

ACOUSTICAL CEILINGS 095100 - 2

B. Wire Hangers, Braces, and Ties: Zinc-coated carbon-steel wire; ASTM A 641/A 641M, Class 1

zinc coating, soft temper.

C. Access: Identify upward access tile with manufacturer's standard unobtrusive markers for each

access unit.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install acoustical ceilings to comply with ASTM C 636/C 636M and seismic design

requirements indicated, according to manufacturer's written instructions and CISCA's "Ceiling

Systems Handbook."

B. Install acoustical panels with undamaged edges and fit accurately into suspension system

runners and edge moldings. Scribe and cut panels at borders and penetrations to provide a neat,

precise fit.

END OF SECTION 095100

Page 39: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

RESILIENT FLOORING 096500 - 1

SECTION 096500 - RESILIENT FLOORING

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data and Samples.

PART 2 - PRODUCTS

2.1 RESILIANT FLOORING

A. See Finish Schedule.

2.2 RESILIANT BASE

A. Manufacturers: One of the following:

1. Allstate Rubber Corp.; Stoler Industries.

2. Armstrong World Industries, Inc.

3. Burke Mercer Flooring Products; Division of Burke Industries, Inc.

4. Endura Rubber Flooring; Division of Burke Industries, Inc.

5. Estrie Products International; American Biltrite (Canada) Ltd.

6. Flexco, Inc.

7. Johnsonite.

8. Mondo Rubber International, Inc.

9. Musson, R. C. Rubber Co.

10. Nora Rubber Flooring; Freudenberg Building Systems, Inc.

11. PRF USA, Inc.

12. Roppe Corporation, USA.

13. VPI, LLC; Floor Products Division.

B. Color and Pattern: As selected by the owner.

Page 40: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

RESILIENT FLOORING 096500 - 2

C. ASTM F 1861, Rubber base

D. Style: Cove base with toe.

E. Minimum Thickness: 0.125 inch.

F. Height: 4 inches in dry areas 6 inches in wet areas.

G. Finish: As selected.

2.3 INSTALLATION ACCESSORIES

A. Trowelable Leveling and Patching Compounds: Latex-modified, portland cement- or blended

hydraulic cement-based formulation provided or approved by flooring manufacturer for

applications indicated.

B. Adhesives: Water-resistant type recommended by manufacturer to suit floor covering and

substrate conditions indicated.

1. Low-Emitting Materials: Adhesives shall have a VOC content of [50] [60] g/L or less.

2. Low-Emitting Materials: Adhesives shall comply with Green Seal's GS-36 and with the

testing and product requirements of the California Department of Health Services'

"Standard Practice for the Testing of Volatile Organic Emissions from Various Sources

Using Small-Scale Environmental Chambers."

C. Heat-Welding Bead: Solid-strand product of floor covering manufacturer.

D. Chemical-Bonding Compound: Manufacturer's product for chemically bonding seams.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Prepare concrete substrates according to ASTM F 710. Verify that substrates are dry and free

of curing compounds, sealers, and hardeners.

B. Install wall base in maximum lengths possible. Apply to walls, columns, pilasters, casework,

and other permanent fixtures in rooms or areas where base is required.

END OF SECTION 096500

Page 41: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

PAINTING AND COATING 099000 - 1

SECTION 099000 - PAINTING AND COATING

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals:

1. Product Data.

2. Samples.

PART 2 - PRODUCTS

2.1 PAINT

A. Manufacturers

1. Behr Process Corporation.

2. Benjamin Moore & Co.

3. Benjamin Moore & Co. (Canada).

4. Columbia Paint & Coatings.

5. Dunn-Edwards Corporation.

6. Duron, Inc.

7. Kelly-Moore Paints.

8. Kwal Paint.

9. Pratt & Lambert.

10. Or brand selected by the owner

B. MPI Standards: Provide materials that comply with MPI standards indicated and listed in its

"MPI Approved Products List."

C. Material Compatibility: Provide materials that are compatible with one another and with

substrates.

1. For each coat in a paint system, provide products recommended in writing by

manufacturers of topcoat for use in paint system and on substrate indicated.

D. Colors: As selected.

PART 3 - EXECUTION

3.1 PREPARATION

A. Comply with recommendations in MPI's "MPI Architectural Painting Specification Manual"

applicable to substrates indicated.

B. Remove hardware, lighting fixtures, and similar items that are not to be painted. Mask items

that cannot be removed. Reinstall items in each area after painting is complete.

Page 42: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

PAINTING AND COATING 099000 - 2

C. Clean and prepare surfaces in an area before beginning painting in that area. Schedule painting

so cleaning operations will not damage newly painted surfaces.

3.2 APPLICATION

A. Comply with recommendations in MPI's "MPI Architectural Painting Specification Manual"

applicable to substrates indicated.

B. Paint exposed surfaces unless otherwise indicated.

1. Paint surfaces behind movable equipment and furniture same as similar exposed surfaces.

2. Paint surfaces behind permanently fixed equipment or furniture with prime coat only.

3. Do not paint prefinished items, items with an integral finish, operating parts, and labels

unless otherwise indicated.

C. Apply paints according to manufacturer's written instructions.

D. Apply paints to produce surface films without cloudiness, spotting, holidays, laps, brush marks,

roller tracking, runs, sags, ropiness, or other surface imperfections. Cut in sharp lines and color

breaks.

1. If undercoats or other conditions show through topcoat, apply additional coats until cured

film has a uniform paint finish, color, and appearance.

E. Apply stains and transparent finishes to produce surface films without color irregularity,

cloudiness, holidays, lap marks, brush marks, runs, ropiness, or other imperfections. Use

multiple coats to produce a smooth surface film of even luster.

3.3 INTERIOR PAINT APPLICATION SCHEDULE

A. Steel:

1. High-Gloss, Quick-Dry Enamel: Two coats over quick-drying alkyd metal primer:

MPI INT 5.1A.

B. Including trim and doors.

1. Gloss Latex: Two coats over latex primer:

C. Gypsum Board:

1. Satin Latex: Two coats over latex primer/sealer: MPI INT 9.2A.

2. Flat Latex: Two coats over latex primer/sealer: MPI INT9.2A.

3.4 INTERIOR STAIN AND CLEAR FINISH APPLICATION SCHEDULE

A. Wood:

1. Wood Trims: Gloss Oil-Modified Polyurethane Varnish. Two coats over stain: MPI INT

6.1J.

END OF SECTION 099000

Page 43: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017 1252.144.1

TOILET ACCESSORIES 102800 - 1

SECTION 102800 – TOILET ACCESSORIES

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Product Data.

PART 2 - PRODUCTS

2.1 TOILET AND BATH ACCESSORIES

A. Paper Towel Dispenser: American Specializes Paper Towel Dispenser Stainless steel folded

towel dispenser ASI 0210

B. Toilet Tissue Dispenser: American Specialties, Stainless steel, recessed ASI 7402-HBSM.

C. Liquid-Soap Dispenser: American Specialties, Stainless steel, model ASI 0332.

D. Grab Bar: American Specialties, Stainless steel

E. Mirror Unit: American Specialties, Stainless steel, size per drawings, ” model ASI 6020.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Install accessories using fasteners appropriate to substrate indicated and recommended by unit

manufacturer. Install units level, plumb, and firmly anchored in locations and at heights

indicated.

1. Install grab bars to withstand a downward load of at least 250 lbf , when tested according

to method in ASTM F 446.

B. Adjust accessories for unencumbered, smooth operation and verify that mechanisms function

properly. Replace damaged or defective items. Remove temporary labels and protective

coatings.

END OF SECTION 102800

Page 44: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017

1252.144.1

PLASTIC COUNTERTOPS 123623 - 1

SECTION 123623 - PLASTIC COUNTERTOPS

PART 1 - GENERAL

1.1 SECTION REQUIREMENTS

A. Submittals: Shop Drawings, Samples showing the full range of colors, textures, and patterns

available for each type of finish and AWI Quality Certification Program certificates

B. Fabricator Qualifications: Certified participant in AWI's Quality Certification Program Licensee

of WI's Certified Compliance Program.

C. Installer Qualifications: Fabricator of products.

D. Environmental Limitations: Do not deliver or install countertops until building is enclosed, wet

work is completed, and HVAC system is operating.

PART 2 - PRODUCT

2.1 PLASTIC-LAMINATE COUNTERTOPS

A. Quality Standard: AWI, AWMAC, and WI's "Architectural Woodwork Standards."

B. Plastic-Laminate Countertops: Custom grade.

1. Laminate Grade: HGS for flat countertops, HGP for post-formed countertops.

2. Grain Direction: Parallel to cabinet fronts.

3. Edge Treatment: Same as laminate cladding on horizontal surfaces.

2.2 MATERIALS

A. Medium-Density Fiberboard: ANSI A208.2, Grade 130.

B. Softwood Plywood: DOC PS 1.

C. High-Pressure Decorative Laminate: NEMA LD 3.

D. Grommets for Cable Passage through Countertops: 1-1/4-inch OD, molded-plastic grommets

and matching plastic caps with slot for wire passage.

1. Product: by Doug Mockett & Company, Inc.

2.3 FABRICATION

A. Complete fabrication to maximum extent possible before shipment to Project site. Disassemble

components only as necessary for shipment and installation. Where necessary for fitting at site,

provide ample allowance for scribing, trimming, and fitting.

Page 45: New Medical Building Dr. CAESAR HEARN, DDSidiutah.com/wp-content/uploads/2017/06/Hearne-Project...New Medical Building Dr. CAESAR HEARN, DDS Layton ... and reduced strength due

Dr. Caesar Hearne, DDS 22 May 2017

1252.144.1

PLASTIC COUNTERTOPS 123623 - 2

PART 3 - EXECUTION

3.1 INSTALLATION

A. Before installation, condition countertops to average prevailing humidity conditions in

installation areas.

B. Install countertops to comply with referenced quality standard for grade specified.

C. Install countertops level, plumb, true, and straight. Shim as required with concealed shims.

Install level and plumb to a tolerance of 1/8 inch in 96 inches.

D. Scribe and cut countertops to fit adjoining work, refinish cut surfaces, and repair damaged finish

at cuts.

E. Anchor countertops securely to base units. Seal space between backsplash and wall.

F. Provide 4” splash.

END OF SECTION 123623