nhl trailer fs (4)
TRANSCRIPT
History of the “Big Rig” Events
NHL “Big Rig” . . .NHL “Big Rig” . . . The Cal l to DutyThe Cal l to Duty
Dan Craig NHL Facility Operations Manager
Event Teams Weather
2009 Winter Classic Wrigley Field, Chicago
vs 00 C
Overcast
2010 Winter Classic Fenway Park, Boston
vs 10 C
Overcast
2011 Winter Classic Heinz Field, Pittsburgh
vs 100 C
Overcast
2011 Alumni Game Heinz Field, Pittsburgh
vs 100 C
Overcast
2011 Heritage Classic McMahon Stadium, Calgary
vs -150 C
Partly Cloudy
2012 Winter Classic Citizens Bank Park Philadelphia
vs 30 C
Mostly Cloudy
2014 Winter Classic Michigan Stadium, Ann Arbor
vs -110 C
Light Snow
2014 Stadium Series Dodger Stadium, Los Angeles
vs 250 C
Overcast
2014 Stadium Series Yankee Stadium, New York
vs -80 C Clear
2014 Stadium Series Yankee Stadium, New York
vs -60 C Clear
2014 Stadium Series Soldier Field, Chicago
vs -50 C
Overcast
2014 Heritage Classic BC Place, Vancouver
vs Indoor
2015 Winter Classic Nationals Park, Washington
vs 70 C
Mostly Cloudy
2015 Stadium Series Levi’s Stadium, Santa Clara
vs 200 C
Partly Cloudy
2016 Winter Classic Gillette Stadium, Foxborough
vs 50 C
Overcast
2016 Stadium Series TCF Bank Stadium, Minneapolis
vs 20 C
Overcast
2016 Stadium Series Coors Field, Denver
vs 210 C
Mostly Cloudy
“My experience with CIMCO started when I worked
at the Rexall Place in Edmonton. I have been in the
business for a number of years and have not seen
another company as experienced and professional
as CIMCO. They provide the best refrigeration
mechanics in the world. Being in the NHL spotlight I
cannot afford to cut any corners when it comes to
maintaining our plants.”
“Big Rig” Specifications“Big Rig” Specifications
Refrigerant:
R717 (Ammonia)
Two Compressors for a total of 310TR:
RXF 85 compressor
140TR (10°F Evaporating temperature and 95°F condensing
temperature)
235HP motor
Quantum LX Microprocessor
RXF-101 Compressor
170TR (10°F Evaporating temperature and 95°F condensing
temperature)
263 HP motor
Quantum LX Microprocessor
Evaporative condenser Model: Evapco LRC-379
Capacity 4760 MBH
40HP fan motor
Alfa Laval Plate and Frame heat exchanger:
Model T20-BWFS
13340 lb/hr ammonia flowrate
857300 Lb/hr glycol flowrate
Glycol supply temperature 15°F
Complete with 42” surge drum
Pumps (2)
Armstrong base mounted end suction pumps
1400gpm
40HP each
Trailer
53’ step deck trailer
Manufacturer Di-Mond Trailers in Burlington.
65,000 Lbs Gross Weight, with equipment
Electrical
460V/3ph/60hz power from Generator typically
591 HP total
1055 FLA
www.cimcorefrigeration.com