nhp part d technical catalogue
TRANSCRIPT
PART D CATALOGUE
D
Sales 1300 NHP NHP | nhp.com.au
Industrial Electrical and Automation Products, Systems and Solutions
AUTOMATION PRODUCTS
SOFT STARTERS & DRIVES
AUTOMATION PRODUCTS
SAFETY
PLCs
Safety, Interlock, Limit & Trip-Wire Switches
Switch Mode Power Supplies
Industrial Limit & Foot Operated Switches
Visualisation & Reporting Software
Non-contact Safety Switches
Operator Panels & Touch Screens
Safety Controllers
Fieldbus I/O Systems
Emergency stop trip-wire switches
Soft Starters
Variable Speed Drives
01
02
03
2
NHP Electrical Engineering Products
(NHP) specialises in motor control, power
distribution and automation systems.
NHP offers the Australasian market
the complete industrial electrical
and automation solutions package.
As authorised distributors for Rockwell
Automation and their Allen-Bradley®
products in our designated areas of
Australia and throughout all of New
Zealand, NHP is partnered with the leading
global provider of industrial automation
solutions and switchgear components.
An Australian owned company, NHP is
committed to serving the Australasian
industry with quality products and
customer support. This is achieved through
a 1000+ strong team which is distributed
across 25 branches and 24 regional
locations throughout Australia and New
Zealand.
While NHP stock an impressive 45,000+
line items, we are much more than a
component supplier. NHP source the
highest quality products from leading
global suppliers, and customise these into
solutions for the local Australian and New
Zealand markets, providing a complete fit to
purpose systems and solutions service.
At NHP we have a strong customer focus
and we look to provide the right product
and product solutions for our customers’
requirements and applications, all at a
competitive price. We value and care for our
customers and support them by offering
personalised service and assistance to
meet their every need and demand. Our
customers can have 100% confidence in our
ability to support them when, where and
how it is needed.
Put simply, NHP is ‘easy to do business with’.
NHP Electrical Engineering Products
NHP NATIONAL MANUFACTURING AND DISTRIBUTION CENTRE
Please scan the QR code to view our corporate presentation.
Scan the QR code for career opportunities at NHP
SCALE
KNOWLEDGE
AGILITY
PARTNERSHIPS
“Corporate DNA” The NHP Value Proposition
Qu
ick Re
fere
nce
Ind
ex
2
3
1
AUTOMATION PRODUCTS
PLCs
Fieldbus I/O Systems
Operator Panels and Touch Screens
Visualisation and Reporting Software
Switch Mode Power Supplies
SAFETY
Safety, Interlock, Limit and Trip-Wire Switches
Safety Controllers
Industrial Limit Switches
Foot Operated Switches
SOFT STARTERS & DRIVES
Soft Starters
Variable Speed Drives
This catalogue is segregated into sections. The first page of each
section has its own contents page for easier product selection.
Each page has a bold section number for prompt page location.
Each page is identified by both its section number and its page
number eg. 2-8 signifies this is section 2 page 8.
Three indexes in each catalogue make finding products easy;
A product listing is situated at the front of this catalogue.
A complete section contents listing is situated at the front of the
catalogue.
An alphanumeric index is situated at the rear of this catalogue.
All catalogue numbers are bold and shaded.
For pricing refer to the relevant price list, e.g. to find prices for parts
in the Part D Catalogue, refer to the Part D Price List.
Parts that are available on indent only or parts that are assembled
to order will be identified in the relevant price list.
Please make sure you have the most current price list for each
catalogue. Contact your NHP Sales Representative or refer to
www.nhp.com.au to obtain a copy of the most current price list.
Current NHP standard conditions of sale apply to this price list
catalogue.
Exp
lanatio
n o
f Term
s
TYPICAL PAGE LAYOUT
EXPLANATION OF TERMS AND HEADINGS USED WITHIN THIS CATALOGUE
2 - 8
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B2’
Emergency stop trip-wire switch “kits”
Notes: 1) Items included in all of the above kits
1 x Tension spring (As per requirement AS 1755-2000) 1 x 55164, turnbuckle 4 x 55151, thimble 8 x 55152, wire clamps _ x Cable (quantity as above) _ x 55150, wire support (quantity as above) Wire supports are based upon supporting the trip-wire at 2.5 - 3 metre intervals.
TQZS-75...
TQZS-73...
TQZS-71...
TQZS-80
TQZS-70
Series TQ ZS: Trip-wire switchesEmergency stop for conveyor and various other industries
TQZS70...8 metresSlim housing
Price $Cat. No
TQZS70KIT10M 383.88
Trip-wireSwitch
TQZS70... kit
TQZS70101SVD
Items included in kit 1)Trip-wire length
8 metres
1 x TQZSTS150N
8 x TQZSWR5MM (cable)
3 x 55150 (wire support)
TQZS71...5-20 metresSmall housing
TQZS71KIT20M 581.00
TQZS71... kit
TQZS71101 20 metres
1 x TQZSTS250N
20 x 55153P (cable)
5 x 55150 (wire support)
TQZS73...30-50 metresGeneral purpose
TQZS73KIT50M 1006.38
TQZS73... kit
TQZS3101SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
TQZS-75...30-50 metresLarge housing
TQZS75KIT50M 1130.88
TQZS75... kit
TQZS75101SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
TQZS80...10-50 metresWith emergency stop and flag indicator
TQZS80KIT50M 975.25
TQZS80... kit
TQZS80202SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
Section number
Illustrative photographs or diagrams indicative of products available (not necessarily to scale)
Price Schedule(s) listed for products on this page.
Description of product, ratings etc.
Section and page number e.g. section 2, page 8
Additional information, accessories, technical data, notes, etc.
Footnotes, as necessary, are referenced to the bottom of each page. E.g. 2)
Cat. No. of product is always next to the applicable price.
The catalogue numbers are shaded for quick identification.
Page contents
14
Pro
du
ct Listin
g
Product Sub Product Section Page
EEmergency stop
trip-wire switches
Heavy-duty limit switches: 77 HL and 77 TL series 2 19Installation instructions 2 17Spare parts and accessories 2 15Type NTW cast aluminium 2 13
FFieldbus I/O
systems for
industrial
automation
applications
750 Series 1 21750 Series Intrinsically safe system 1 28750 Series PROFIsafe system 1 29750 Series Starter kits 1 34750 Series Vibration monitoring 1 28751 Series AS-i Fieldbus system 1 30753 Series Quick connect 1 35
857 Series JUMPFLEX Transducers 1 26Overview 1 16Programming and diagnostic software 1 31
Fieldbus I/O
systems for long
distance, lighting
and irrigation
control systems
Ordering details 1 42
Overview 1 38
LLimit switches Light duty 6 A: ES/EM 95 series 2 11
Medium duty 10 A: PS21 series 2 11Medium duty 10 A: PS31 series 2 12Medium Duty 6 A:ES/EM 41 series 2 12
Introduction to CA 8 2.2 - 5.5 kW compact contactor system 1 4Mounting rail - to suit DIN style equipment 1 37Safety contactors CAS - AC and DC operated 4 - 500 kW 1 18
MMicro
Programmable
Logic Controllers
Hitachi EH Micro series 1 6
Mitsubishi Alpha 2 series 1 2
Modular
Programmable
Logic Controllers
Hitachi EH-150 series 1 10
Micro and modular PLC accessory selection guide 1 15
NNon-contact
Safety switches
Belt drift switches 2 10
Emergency stop trip-wire switch kits 2 8Emergency stop trip-wire switches 2 9Series BZ16 2 7Series HSSi4 2 7Series RC Si - 56 2 6Series RC Si - M30 2 6
OOperator panels
and touch
screens
Communications cables 1 54Dimensions and cut-outs 1 56Graphics operator panels 1 51Graphics touch screens 1 52Overview 1 49SC 207 1 48Text based operator panels 1 50VTWIN Configuration software 1 55
SSafety Controllers Foot operated switches 2 22
Limit switches - pull-wire (non safety) 2 21Pressure switches 2 23Series MF1: Standstill monitor 2 20Series NSC: Fail safe control unit 2 20Series SRM: Fail safe control unit 2 20
Pro
du
ct Listin
g
Product Sub Product Section Page
Safety interlock
switches
Series AZM 415: Heavy duty Solenoid 2 5Series ES - 13SB: Light duty hinged 2 4Series ES - 95: General purpose 2 2Series ES - 95: General purpose flap/hinge 2 4
Series ES - 95: General purpose rotary cam 2 4Series ST - 14: Light duty 2 2Series ST - 61: Heavy Duty 2 3Series STM 295: Medium duty solenoid 2 5
Soft starters CSX and CSXi - introduction, specifications and ordering details 3 7Electronic soft starters product selection guide 3 2EMX3 - introduction, specifications and ordering details 3 12PCS - introduction, specifications and ordering details 3 4
Switch mode
power suppliesSwitch mode power supplies 1 68
VVariable Speed
Drives
Brake resistor selection by duty cycle 3 37Brake resistors and accessories - ordering details 3 38Input and output choke - ordering details 3 35
Product selection guide 3 23
Rating and selection chart 3 40
Santerno SINUS Nano range - introduction, standard specifications and ordering details 3 24Semiconductor fuses and accessories - ordering details 3 36SINUS Micro range - introduction, standard specifications and ordering details 3 25SINUS Nano and Micro ranges - options 3 26SINUS Penta - multi-pump application and 3 46SINUS Penta - options 3 48
SINUS Penta - range and selection (380 - 415 V) 3 32
SINUS Penta - range and selection (660 - 690 V) 3 44
SINUS Penta - specifications 3 49
SINUS Penta range - introduction, standard specifications and options 3 27
Visualisation
and reporting
software
Ordering details 1 66
Overview - World class 32-bit SCADA/HMI software 1 59
NHP’s Values
To achieve our vision, NHP has six values
which define how we operate
Energy
An energetic “can and will do” attitude and approach. Enthusiasm is infectious and we look to provide this in all aspects of our business and our customers’ business.
Consistency
We provide our customers with what they want, when, where and how they want it, for today, tomorrow and into the future.
Passion for Customers
Without customers we have no business, so we are passionate about everything we do for them. We service our customers’ needs 24 hours a day, 7 days a week, 365 days a year.
Integrity
We do what is right for our customers, our staff, our industry and our community.
Adaptiveness to Change
If we don’t adapt, we wither then die. While we have adhered to the same values and service objectives since day one, we also have adapted to the changing face of our industry and the industrial world, and we look to help our customers prosper as a result.
Commitment to Performance
We aim to provide products and solutions on time, in full, every time. Our customers can expect to receive service above their expectations in everything we do.
Australia and New Zealand Manufacturing and Distribution Centre
NHP prides itself on being able to provide customers with tailored solutions that suit their individual needs. Whilst we have significant stockholdings and expertise at all our locations throughout Australia and New Zealand, the purpose of our National Manufacturing and Distribution Centre in Laverton, Melbourne is to develop these solutions through manufacturing, assembly, servicing and design and engineering.
SIZE
Warehouse 7,000 m2 Manufacturing 5,000 m2
STAFF 270+ Employees
OPERATING HOURS
6.00am - 11.30pm, Monday-Friday
STOCKHOLDING
- 45,000+ line items (20,000 stocked)
- Approximately $70 M
ITEM THROUGHPUT
- Approximately 5,500 per day (6,000 lines throughout Australasia)
FACTS
3.00 pm are despatched the same day.
95 % customer service based on an ‘on time in full, first time’ measurement.
AUSTRALIA AND NEW ZEALAND MANUFACTURING AND DISTRIBUTION CENTRE
Laverton Facility Tour Booklet2011
Scan the QR code to view the Laverton Tour brochure.
Scan the QR code to view our Concept Express video
ONE OF NHP’S ELECTRIC CARS ON DISPLAY AT THE
SUSTAINABILITY CENTRE IN LAVERTON, MELBOURNE
Sustainability Centre
Emerging technology supporting sustainability
A major push towards more sustainable
practices by many in the industrial
electrical industry is now clear for all to
see in today’s environment.
Learning to use energy smarter to
reduce our consumption and increase
one’s bottom line is now a key
consideration in all applications.
A major focus at NHP is to provide
sustainable solutions for our
customers as well as throughout our
own operations. Early in 2010 we
designed and constructed our very
own Sustainability Centre - located at
our existing National Manufacturing
and Distribution Centre in Laverton,
Melbourne.
The Centre utilises cutting edge
technology and houses equipment
which enables us to conduct research
& development, test new products and
look closely at ways we can effectively
introduce and manage sustainable
practices.
The centre is driven by power
generated from Solar Panels and
houses an interactive display allowing
visitors a close-up view of a range of
sustainable energy technologies which
currently include:
A horizontal axis wind generator
Solar photo-voltaic systems
Grid interactive systems
Off-grid hybrid systems
Dual axis solar tracker, and
Energy Management & control
systems
NHP are also proud participants in
the Victorian Government’s electric
vehicle trial. The trial will provide NHP
with valuable insights to assist in future
business planning, as well as help
the wider community understand
the process, timelines and barriers
for transitioning to electric vehicle
technologies in the future.
NHP’s Sustainability Centre and
participation in the electric vehicle
trial highlight our commitment to
encourage sustainable practices across
all facets of the workplace.
Our aim is to remain at the forefront
of the industry, as leaders in providing
alternative energy solutions for
commercial and industrial applications.
NHP also works closely with Melbourne
University, RMIT University and Victoria
University, providing course advice
and industry based supervision of
undergraduate and postgraduate
students.
NHP is proud to educate young
electrical engineers in this growing,
and important industry sector.
Scan the QR code to Book a Live Tour.
Scan the QR code to view a video on our electric car trial.
Scan the QR
To assist customers in finding what they want, we have classified
our extensive product range into the following categories.
Our vast automation product
range can provide a completely
integrated automation solution,
for both the factory and process
automation industries, that can
be delivered with our Integrated
Architecture platform.
Controllers
Relays
Drives
Screens
Communications
Products and Brands
AUTOMATION SYSTEMSMOTOR CONTROL& DRIVES
NHP offers conventional motor
starting and protection products as
well as advanced electronic starting,
controlling and protection products
to suit fractional horsepower motors
through to large frame main drive
systems. NHP also offers customised
motor starters across the entire
range.
POWER DISTRIBUTION & PROTECTION
NHP provides Australasia’s
widest range of low voltage
power distribution and
protection products supplied
as components or as part of a
manufactured solution. Circuit
protection against current
overloads up to 6300A is available
together with a wide range
of surge and arc protection,
switching products and power
supplies.
ERICO
WOHNER
SELCO
ampcom
GHISALBA
MICROELETTRICA
POWER QUALITY
NHP’s Power Quality products
and systems provide solutions
for power factor correction and
harmonic mitigation. To meet
specific customer requirements,
this group of products are
generally customised at our
manufacturing centre in
Laverton, Victoria.
Systems
Regulators
ELECTRONICONBELUK
COSMOTEC
STEGO
IBOCO
ENCLOSURES & CLIMATE CONTROL
NHP has a complete range of mild
steel, stainless and plastic enclosure
options in a variety of IP ratings and
configurations including modular
switchboard systems.
To complement NHP’s enclosure
systems, a wide range of climate
control solutions are also available.
BOCCHIOTTI
ERICO
TERMINATION & WIRING SYSTEMS
NHP has a wide range of screw
and screw-less terminals, terminal
accessories (such a DIN rail and
jumper pins) and cable ducting.
Products and Brands (cont’d)
NHP offers a range of control
relays and timers that can be
used in conjunction with a
conventional automation system
to switch higher loads or in
stand alone applications where
the only basic single function
control is required.
TIMERS &
CONTROL RELAYS
With an extensive range of
audible and visual signalling
devices, NHP provides solutions
for hundreds of applications,
be it general safety warning,
process control, fire or
evacuation.
SIGNALLING DEVICES
GRASSLIN
The automation system relies
on information from the field
to control the process. NHP’s
switching and sensing suite of
products cover all field sensing
requirements including standard
and hazardous area applications.
FIELD SWITCHING & SENSING
Most processes, even if
automated, still require some
manual control and NHP
provides a complete range of
control products and systems for
this purpose.
ELEKTRA
SPOHN + BURKHARDT
TER
OPERATOR
CONTROL DEVICESR
PLUGS & SOCKETS
Divided into two distinct
product ranges, NHP’s plugs
and sockets provide solutions
for a wide range of applications
and are available in a wide
range of amperages and pin
configurations.
sockets
PROCONECT
NHP offer a large variety of
quality safety products that
meet international standards,
with products ranging from
simple emergency stop switches
to safety monitoring relays.
SAFETY PRODUCTS
STEUTE
Products and Brands (cont’d)
NHP provided a world class
range of hazardous area
equipment for explosive
environments including light
fittings, enclosures and terminal
boxes, control stations and
intrinsically safe automation
products.
HAZARDOUS AREA EQUIPMENT
WAGO
STEUTE
Energy Metering is the essential
component to understanding
your energy consumption
and power quality. NHP has
a complete range of energy
meters and power quality
analysers to meet the most
demanding of applications.
METERING
NHP offers a large selection
of products and solutions
tailored towards renewable
energy applications including
Solar and Wind. From high DC
rated protection and switching
devices, solar panel control and
monitoring products through to
a range of inverters and power
factor correction systems.
and Control Boxes
RENEWABLE ENERGY PRODUCTS
NHP has a wide range of services including
technical support, field service and maintenance
contracts, repair services and training.
These services are delivered by NHP qualified
technicians and our supply partners.
SERVICES & TRAININGSERVICES & TRAINING
Products and Brands (cont’d)
WAGO
STEUTE
STEUTE
KATKO
HAZARDOUS AREA EQUIPMENT SAFETY PROCESS CONTROL
2. Application Classes
When servicing important industries
such as the oil and gas, petrochemical
and grain handling there is no room for
complacency. At NHP our aim is to provide
a world class range of hazardous area
equipment for the hazardous market which
includes light fittings, terminal boxes,
control stations and an extensive suite of
automation products. NHP has been in
this field for many years and has acquired
a comprehensive knowledge on explosion
protection products, so wherever explosive
atmospheres are prevalent, NHP can
provide the safest solution.
For any industrial application, the safety
of employees and the general population
is of major importance. NHP has a long
history in the safety industry and can be
a trusted destination for all your safety
application needs. NHP offer a large
variety of quality products that meet all
relevant international standards, with
products ranging from simple emergency
stop switches, to light curtains, safety
monitoring relays all the way up to fully
integrated safety PLC systems. Our product
range extends further into SIL3 rated Safety
Critical Shutdown systems.
and Control Systems
Like the principles which drive the
process industry, NHP is committed to
delivering products of continuous quality
to assist our customers in achieving
process optimisation. Encompassing
a wide range of industries including
oil refining, petrochemicals, water and
sewage treatment, food processing, and
pharmaceuticals, the NHP process control
product portfolio offers complete system
integration.
With first-hand experience and capabilities,
and a solid understanding of the intensive
continuous nature of Process operations,
NHP reduces the risk associated with
continuously achieving the business
value promised by these technologies. In
addition NHP continues to leverage from
International relationships with recognised
process control companies and experts,
giving NHP access to a knowledge base
which has consistently demonstrated its
ability to deliver product quality, service
and application knowledge.
ENERGY MANAGEMENT SUSTAINABILITY
3. Application Solutions
NHP can provide Energy Management
Metering and Software solutions that
monitor and record energy information
so operators can identify consumption
trends and take corrective actions. Real-
time measurements of these electrical
parameters, such as voltage variations or
distortions, may have alarm thresholds
set to warn managers if preset limits are
reached. These real-time measurements
also allow site managers to anticipate
overload conditions that could, for
example, trip a circuit breaker. NHP can
provide a wide range of products to
complement any Energy Management
Solution.
With an increasing focus on the state of
global warming and the requirement to
decrease our carbon footprint, the use
of sustainability is becoming a popular
phenomenon. Our partnerships with
many of the industries best suppliers
from around the world means that NHP
offer a large selection of products and
solutions tailored towards renewable
energy applications including Solar and
Wind. From high DC rated protection and
switching devices, solar panel control and
monitoring products through to a range of
inverters and power factor correction, NHP
has an extensive offering.
and Control Boxes
1
Automation products, PLCs, I/O systems,
operator panels and touch screens, SCADA software
MICRO PROGRAMMABLE LOGIC CONTROLLERSMitsubishi Alpha 2 series ................................................................................................................1 - 2
Hitachi EH Micro series ....................................................................................................................1 - 6
MODULAR PROGRAMMABLE LOGIC CONTROLLERSHitachi EH-150 series......................................................................................................................1 - 10
Micro and modular PLC accessory selection guide ...................................................1 - 15
FIELDBUS I/O SYSTEMS FOR INDUSTRIAL AUTOMATION
APPLICATIONSOverview ................................................................................................................................................1 - 16
750 Series ..............................................................................................................................................1 - 21
857 Series JUMPFLEX Transducers ........................................................................................1 - 26
750 Series Intrinsically safe system ........................................................................................1 - 28
750 Series PROFIsafe system .....................................................................................................1 - 29
750 Series Vibration monitoring .............................................................................................1 - 28
751 Series AS-i Fieldbus system ..............................................................................................1 - 30
Programming and diagnostic software .............................................................................1 - 31
750 Series Starter kits .....................................................................................................................1 - 34
753 Series Quick connect ............................................................................................................1 - 35
FIELDBUS I/O SYSTEMS FOR LONG DISTANCE, LIGHTING AND
IRRIGATION CONTROL SYSTEMSOverview ................................................................................................................................................1 - 38
Ordering details .................................................................................................................................1 - 42
OPERATOR PANELS AND TOUCH SCREENSSC 207 ......................................................................................................................................................1 - 48
Overview ................................................................................................................................................1 - 49
Text based operator panels .......................................................................................................1 - 50
Graphics operator panels ............................................................................................................1 - 51
Graphics touch screens ................................................................................................................1 - 52
Communications cables ..............................................................................................................1 - 54
VTWIN Configuration software ................................................................................................1 - 55
Dimensions and cut-outs ............................................................................................................1 - 56
VISUALISATION AND REPORTING SOFTWARE - ADROIT
Overview - World class 32-bit SCADA/HMI software ................................................1 - 59
Ordering details .................................................................................................................................1 - 66
Switch mode power supplies...................................................................................................1 - 68
2
Safety
SAFETY INTERLOCK SWITCHESSeries ST - 14: Light duty ................................................................................................................2 - 2
Series ES - 95: General purpose ..................................................................................................2 - 2
Series ST - 61: Heavy Duty .............................................................................................................2 - 3
Series ES - 95: General purpose rotary cam ........................................................................2 - 4
Series ES - 13SB: Light duty hinged .........................................................................................2 - 4
Series ES - 95: General purpose flap/hinge .........................................................................2 - 4
Series STM 295: Medium duty solenoid ................................................................................2 - 5
Series AZM 415: Heavy duty Solenoid ...................................................................................2 - 5
NON-CONTACT SAFETY SWITCHESSeries RC Si - M30 ................................................................................................................................2 - 6
Series RC Si - 56 ....................................................................................................................................2 - 6
Series HSSi4 .............................................................................................................................................2 - 7
Series BZ16 ..............................................................................................................................................2 - 7
Emergency stop trip-wire switch kits .....................................................................................2 - 8
Emergency stop trip-wire switches .........................................................................................2 - 9
Belt drift switches .............................................................................................................................2 - 10
LIMIT SWITCHESLight duty 6 A: ES/EM 95 series ...............................................................................................2 - 11
Medium duty 10 A: PS21 series ...............................................................................................2 - 11
Medium duty 10 A: PS31 series ...............................................................................................2 - 12
Medium Duty 6 A:ES/EM 41 series ........................................................................................2 - 12
EMERGENCY STOP TRIP-WIRE SWITCHESType NTW cast aluminium .........................................................................................................2 - 13
Spare parts and accessories .......................................................................................................2 - 15
Installation instructions ................................................................................................................2 - 17
Heavy-duty limit switches: 77 HL and 77 TL series .....................................................2 - 19
SAFETY CONTROLLERSSeries NSC: Fail safe control unit ............................................................................................2 - 20
Series MF1: Standstill monitor ..................................................................................................2 - 20
Series SRM: Fail safe control unit ............................................................................................2 - 20
Limit switches - pull-wire (non safety) ................................................................................2 - 21
Foot operated switches ...............................................................................................................2 - 22
Pressure switches .............................................................................................................................2 - 23
3
Soft starters and drivesElectronic soft starters product selection guide..............................................................3 - 2
S+SPCS - introduction, specifications and ordering details ..............................................3 - 4
AUCOM
CSX and CSXi - introduction, specifications and ordering details .......................3 - 7
EMX3 - introduction, specifications and ordering details ......................................3 - 12
VARIABLE SPEED DRIVESProduct selection guide ...............................................................................................................3 - 23
Santerno SINUS Nano range - introduction, standard specifications and ordering
details .......................................................................................................................................................3 - 24
SINUS Micro range - introduction, standard specifications and ordering details
3 - 25
SINUS Nano and Micro ranges - options ...........................................................................3 - 26
SINUS Penta range - introduction, standard specifications and options .....3 - 27
SINUS Penta - range and selection (380 - 415 V) .........................................................3 - 32
Input and output choke - ordering details ......................................................................3 - 35
Semiconductor fuses and accessories - ordering details .......................................3 - 36
Brake resistor selection by duty cycle .................................................................................3 - 37
Brake resistors and accessories - ordering details .......................................................3 - 38
Rating and selection chart..........................................................................................................3 - 40
SINUS Penta - range and selection (660 - 690 V) .........................................................3 - 44
SINUS Penta - multi-pump application and ....................................................................3 - 46
SINUS Penta - options ...................................................................................................................3 - 48
SINUS Penta - specifications ......................................................................................................3 - 49
Se
ctio
n C
on
ten
ts Listing
1 - 1
Automation products, PLCs, I/O systems, operator panels and touch screens, SCADA software
1
Micro Programmable Logic Controllers Mitsubishi Alpha 2 series 1 - 2Hitachi EH Micro series 1 - 6Modular Programmable Logic Controllers Hitachi EH-150 series 1 - 10Micro and modular PLC accessory selection guide 1 - 15Fieldbus I/O systems for industrial automation applications Overview 1 - 16750 Series 1 - 21857 Series JUMPFLEX Transducers 1 - 26750 Series Intrinsically safe system 1 - 28750 Series PROFIsafe system 1 - 29750 Series Vibration monitoring 1 - 30751 Series AS-i Fieldbus system 1 - 31Programming and diagnostic software 1 - 33750 Series Starter kits 1 - 34753 Series Quick connect 1 - 35Fieldbus I/O systems for long distance, lighting and irrigation control systems Overview 1 - 38Ordering details 1 - 42Operator panels and touch screens SC 207 1 - 48Overview 1 - 49Text based operator panels 1 - 50Graphics operator panels 1 - 51Graphics touch screens 1 - 52Communications cables 1 - 54VTWIN Configuration software 1 - 55Dimensions and cut-outs 1 - 56Visualisation and reporting software - Adroit Overview - World class 32-bit SCADA/HMI software 1 - 59Ordering details 1 - 66Switch mode power supplies 1 - 68
FFFFFFFFIIIIEEEEEEEEELLLLLDDDDDDDDDBBBBBBBUUUUUUUSSSSSSSSSSS STEMSIII///////////OOOOO SSSSYYYYYYYYYYYSSSSSSSSSTTTTTTTTTTTTTTEEEEEEMMMMMSSSSSSSSSSSSS
MMICCRRO PLCSMMICCRRO PLCS MODULAARR PPLLCCS
FFIELLDDBBUSS II//OO SSYYSSTTEEMMSS
OPEERRAATTOORR PPAANNEELLSS AANNDD TOUCHH SSCCRREEEENNSS
SWITCHH SSWW MMOODE POWER SUUPPPPLIES
1 - 2
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Easier programming
The graphical user interface of the AL-PCSWIN-E package makes programming the Alpha series very easy. On the left and right you have graphical representations of the inputs and outputs, with the pre-programmed function blocks between them (timers, counters, real-time clocks etc.). You just use the mouse to ‘draw’ graphical connections (circuits) between the inputs, function blocks and outputs to define the program logic. Using this simple approach you can create programs with up to 200 function blocks (Alpha 2), and each function block can be reused as many times as necessary within the same program. Program simulation
This feature is particularly useful, enabling you to simulate your program without an Alpha controller connected to your PC.The AL-PCSWIN-E simulation module displays a realistic representation of the controller program. You can activate inputs by clicking with the mouse and the status of the function blocks and program execution are then displayed graphically on your screen.Monitoring functions
The AL-PCSWIN-E “Monitor” function enables you to connect an Alpha controller to your computer and monitor actual program execution on your computer screen. In this mode the current status of the I/Os and function blocks are displayed on the screen during program execution.Process visualisation
AL-PCSWIN-E also comes with a simple process visualisation system called ‘System Sketch’. It is displayed in a separate window into which you can copy and configure graphical elements from your program (inputs, outputs, function blocks etc.) or from another Windows application. Once you have set up the System Sketch window you can use it to perform a graphical simulation and monitoring of your program without using the programming interface. Among other things this can make setting up, installing and maintaining your application much simpler.Modem communications
The Alpha is capable of connection to both GSM and land line modems. Through a GSM modem SMS text messages can be sent to multiple mobile phones from the Alpha whenever an event takes place that requires attention. SMS text messages can be sent to the Alpha from mobile phones to remotely control the outputs. Messages sent to the Alpha are accepted only from “known” mobile phone numbers and a return message is sent to confirm that the requested action has occurred.
Full-featured calendar and clockThe Alpha family has a calendar and clock function with automatic summer/winter time switching. Each Alpha2 controller program can process up to 1,200 clock/calendar-activated on/off switching commands.
Mitsubishi programmable logic controllerAlpha 2 series
OUT4OUT2 OUT3OUT1
AL2-10MR-D
OK
ESC
+
-
1 2 3 4 5 6DC INPUT
-+ (B)(A)
POWER24V DC
RELAY OUTPUT
8290
71.2
2- 4.2 Ø
RELAYOUTPUT
(B) 1 2 3 4 5 6 7 8DC INPUT
+
24V DC
OUT1 OUT2 OUT3 OUT4
OK
ESC
+
-
80M1 LISTEDIND. CONT.EQ.
MADE IN JAPANMITSUBISHI ELECTRIC CORPORATION L U
CU
SR
AL2-14MR-D
POWER
- (A)
OUT5 OUT6
124.6
90
112.6
82
2- 4.2 ØDimensions (mm)
14/24 I/O
10 I/O
All models are 52 mm deep.
Features
Compact and robust 100 V AC - 240 V AC or 24 V DC power supply 1500 bytes EEPROM memory standard Built-in Real Time Clock as standard Sourcing or sinking type DC inputs (on 24 V DC models only) 0-10 V analogue signal inputs (on 24 V DC models only) High current outputs On-device programming through keypad and LCD screen Windows based programming software, Visual Logic Easy access PC programming port
The simple, user friendly Mitsubishi series has been designed for use around your home, office, factory...anywhere that requires flexible programmable control. Every Alpha allows your to analyse inputs and set outputs according to your program. The Alpha displays that status of your inputs and outputs on a LCD screen for quick verification.
1 - 3
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Mitsubishi programmable logic controllerAlpha 2 series
The ALPHA 2 family - Defining a new class of performance
The new Alpha 2 family from Mitsubishi Electric defines a new class of performance for automation applications. With its outstanding capabilities the Alpha 2 family is set to dominate the class it has created.
The Alpha 2 will exceed your expectations in any task you set it and can process up to 200 function blocks in a single program, and every function (timers, counters, analogue signal processing, calendar, clock etc.) can be used as many times as you need in all your programs.
Designed to suit all applications
Public facilities - Airports, train stations, hospitals, road guidance
Building automation - Lighting, HVAC, shutters/gates, security
Commerce - Parking, stores, gas station, hotels golf courses
Home automation - ON/OFF of electrical products, life support for aged, security
Testing facilities - Testing and measuring equipment Exhibition stage effects - lighting, movement control Agriculture - Farms, green house, animal house,
temperature watering, feeding control Hobby - Model making, gardening, weekend carpenter Education - Educational materials in schools Factory Automation - Automation equipment, facility
retrofit, controls
1 - 4
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Accessories
Description Cat. No. Price $
Programming/Comms cable, PLC to PC, or PLC to L/line Modem (9 pin D)
USB to Serial converter (RS 232)
Alpha DVD which includes AL-PCSWINE programming software, manuals, sample code, laboratory notes and quick start guides
Transducer, PT100 RTD, 2 channel, 3-wire, -50 °C to +200 °C range
Transducer, Thermocouple, 2 channel, K-Type, -50 °C to +450 °C range
Memory Module, EEPROM to copy and transfer user memory
GSM Modem with antenna, 12 - 24 V DC
NEXTG Modem with antenna, 12 - 24 V DC
Modem cable, PLC to Modem, (9 pin D)
External Power supply 24 V DC, 3.5 A power supply
External Power supply 24 V DC, 5 A power supply
Mitsubishi programmable logic controllerAlpha 2 series
AL-210-MRA
AL-210-MRD
AL-214-MRA
AL-214-MRD
AL-224-MRA
AL-224-MRD
Base units
I/O counts
100 - 240 V AC
24 V DC
100 - 240 V AC
24 V DC
100 - 240 V AC
24 V DC
Cat. No. Price $Power Supply
6
8
15
100 - 240 V AC
6
8
15
24 V DC
(sink/souce)
10
14
24
4
4
6
6
9
9
Relays
6 1)
8 2)
8 2)
0-10 V DC
Digital Inputs Digital
Output
Analogue
Output
AL-232-CAB
USB-COM 3)
AL-DVD
AL2-2PT-ADP 4)
AL2-2TC-ADP 4)
AL2-EEPROM-2 5)
ALPHAGSMMODEM6)7)
ALPHANXGMODEM6)7)
AL2-GSM-CAB 6)
XCSL85C
XCSP120C
The ALPHA family delivers unbeatable features and performance:
• Operational in ambient conditions -25 °C to +55 °C
• Alarm messages and process data can be displayed
• Programming and variable adjustments can be made through the buttons and screen
• Capable of being used as an AS-I bus slave
• DC expansion input module can be used as a 1 KHz high speed counter
• DNV, CE, UL and cUL Certifications
• Graphical windows based software
Starter kits
Description Cat. No. Price $
AL2-14MRA + AL-232-CAB + USB-COM + AL-DVD
AL2-14MRD + AL-232-CAB + USB-COM + AL-DVD
AL2-24MRA + AL-232-CAB + USB-COM + AL-DVD
AL2-24MRD + AL-232-CAB + USB-COM + AL-DVD
AL2-14AC-KIT
AL2-14DC-KIT
AL2-24AC-KIT
AL2-24DC-KIT
Notes: 1) Inputs can either be digital or analogue. 2) The first 8 inputs can either be digital or analogue. 3) Required for programming when no serial port is available on the personal computer. 4) Temperature element is not included. Customer to supply. 5) Cannot be used with old Alpha series PLCs. 6) Not compatible with 10 I/O models. 7) Requires an AL2-GSM-CAB, a DC power supply and a customer supplied SIM card.
+ USB-COM + AL-DVD AL
Price Schedule ‘B3’
1 - 5
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Cat. No. Price $
4 Digital Input, 100-240 V AC
4 Digital Input, 24 V DC, NPN or PNP
4 Digital Output, Relay, 2 A
4 Digital Output, Transistor PNP only2 Analogue Output, 0-10 V DC, or 4-20 mA, Accuracy of +/- 1% full scale, resolution of 2.5 mV, or 8 mA, Load of 5K-1m, or up to 500 Ω
Mitsubishi programmable logic controllerAlpha 2 series
AL2-4EX-A2
AL2-4EX
AL2-4EYR
AL2-4EYT
AL2-2DA
Description Cat. No. Price $
4.5” STF 3 CLR high resolution 24 V DC + GT Designer3 software
HMI Programmable Cable
USB to serial converter (RS-232)
GT1030HBD2 1)
GT01-C30R2-6P 2)
USB-COM
Visualisation with Graphical Operating Terminal (GOT)
has never been easier
Price Schedule ‘B3’
Notes: 1) Additional GOT HMI are available. Please contact NHP. 2) Cable suitable for GT1020 and GT1030 HMI.
1 - 6
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Micro programmable logic
controllersEH Micro series
Base model options - 10/14/20/23/28/40/64 I/O
Expandable to 320 I/O with 4 x 64 I/O expansion units
Digital input options - 24 V DC, both PNP and NPN (universal)
Digital output options - relay, or 24 V DC NPN, PNP or SSR
Analogue resolution - 12 bit
Analogue in options - 0-20 mA/4-20 mA/0-10 V/-10 V to +10 V
Analogue output options - 0-20 mA, 4-20 mA, 0-10 V
Power supply options 100-240 V AC, or 24 V DC
CPU - 32-bit RISC, 10 microseconds/instruction
User Memory - 16 K steps 20/40/64 I/O, 3 K steps other
Data Memory - 32 K words 20/40/64 I/O, 4 K words other
Memory - Flash for User Memory, Battery for Data Memory
Self diagnosis - LED indication memory, prog, battery low
Programmable in Ladder, or IL - 101 instruction types
High speed counter - 1 phase, 100 kHz, 20/40/64 I/O bases
High speed counter - 2 phase, 60 kHz, 20/40/64 I/O bases
High speed counter - 1&2 phase, 10 kHz, 14/23/28 I/O base
PWM - 2 kHz total for 10/14/23/28 Transistor output models
24 V DC for ext. use, 14/20/23/28/40/64 I/O base models
Filtering delay - Adjustable 0 to 20 milliseconds - stop chatter
Removable terminals for easy installation and removal
Protective hinged terminal covers
Conformity to global standards - CE, UL, c-UL and C-Tick
RS 232 port, with selectable speed 4800 to 38400 bps.
RS 422/485 port for 23/28 base, optional 20/40/64 I/O base
Real time clock - 20/23/28/40/64 I/O base models
LED indication of digital input and output status
Relay contact life - 20 mill. mech, 200,000 elec @ 1.5 A
Program Run/Stop switch 14/20/23/28/40/64 I/O base models
RTD modules - Pt100, 2&3 wire, -100 to +600°C range
External pots to adjust internal variables 14/23/28 I/O
Pulse Train - 65 kHz, 20/40/64 I/O transistor output models
Pulse Train - 5 kHz total, 16 bits for 10/14/23/28 models
PWM - 65 kHz, 20/40/64 I/O transistor output models
Refer catalogue SI-E108U
Features
The EH-Micro series provides an economical, compact and yet powerful solution for your programmable logic control requirements. The base units of the EH-Micro series can either be used as a stand alone PLC, or most have the ability to connect to a much larger network. The base units can manage as few as 10 I/O, or as many as 320 I/O using the maximum of four expansion units. The range of features of the EH-Micro is extensive and the programming software is free for some of the smaller base units. (See below). Up to 32 individual EH-Micro base units can be networked to an Hitachi EH-150 PLC, or to a PC, or an IPC. The new EH-Micro web controller models, (Just like the EH-150 series) have the ability to act as a gateway from the Hitachi PLC ranges, through a LAN to a host PC, or IPC.
Free software - ACTWIN can be downloaded from the NHP website. This version of the ACTWIN software allows full programming capabilities for the 10, 14 and 28 I/O base units only. It will permit all other base units to be programmed, but with the following limitations.
• Program size max. 3 K steps • Ladder programming only • Analogue functions are not available • No expansion units are permitted
To download the software go to: http://www.nhp.com.au/orc Register yourself with NHP and you will be presented with the member homepage. Go to – Product Info and Tools> Automation and Communication> PLC> ACTWIN Download the zip file, extract the contents to a folder, run “install.exe” and follow the instructions. Select the “Hitachi EH-Nano” driver option during the program installation. If you have any difficulty with this process then contact the Automation and Process department – 03 9420 4501
The programming software required for the 23 I/O EH-Micro base units and for all base units using any of the expansion units must be either ACTWINH, or the more economical ACTWINM1. ACTWINH can be also used for the larger Hitachi PLC series, while ACTWINM1 is only for the EH-Micro series. All three versions of the software are nearly identical and so there is no need to learn to how to use a new software package when moving to another Hitachi PLC Hardware series. All three versions of the software use ladder logic and are compliant with IEC61131-3.
1 - 7
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Micro programmable logic
controllersEH Micro series – Ordering details
Price Schedule ‘B3’
Refer catalogue SI-E108U
10 I/O
14 I/O
20 I/O
23 I/O
28 I/O
40 I/O
64 I/O
Approvals
6 DI, 24 V DC / 4 DO, 24 V DC PNP Transistor / 24 V DC power supply
6 DI, 24 V DC / 4 DO, 24 V DC NPN Transistor / 24 V DC power supply
6 DI, 24 V DC / 4 DO, Relay, 2 ampere / 24 V DC power supply
8 DI, 24 V DC / 6 DO, 24 V DC PNP Transistor / 24 V DC power supply
8 DI, 24 V DC / 6 DO, 24 V DC NPN Transistor / 24 V DC power supply
8 DI, 24 V DC / 6 DO, 24 V DC PNP Transistor, Short Circuit Protected /
24 V DC power supply
8 DI, 24 V DC / 6 DO, Relay, 2 ampere / 24 V DC power supply
8 DI, 24 V DC / 6 DO, Relay, 2 ampere / 110-240 V AC power supply
8 DI, 110 V AC ONLY / 6 DO, 110-240 V AC SSR, 0.5 ampere /
110-240 V AC power supply
12 DI, 24 V DC / 8 DO, 24 V DC NPN Transistor / 24 V DC power supply
12 DI, 24 V DC / 8 DO, 24 V DC PNP Transistor, Short Circuit Protected /
24 V DC power supply
12 DI, 24 V DC / 8 DO, Relay, 2 ampere / 24 V DC power supply
12 DI, 24 V DC / 8 DO, Relay, 2 ampere / 110-240 V AC power supply
13 DI, 24 V DC, 2 AI, 0-10 V DC, or 0-20 mA / 9 DO, Relay, 2 ampere, 1 DO,
24 V DC PNP Transistor, 1 AO, 0-10 V DC, or 0-20 mA / 24 V DC power supply
13 DI, 24 V DC, 2 AI, 0-10 V DC, or 0-20 mA / 9 DO, Relay, 2 ampere, 1 DO, 24
V DC PNP Transistor, 1 AO, 0-10 V DC, or 0-20 mA / 110-240 V AC power supply
16 DI, 24 V DC / 12 DO, 24 V DC PNP Transistor / 24 V DC power supply
16 DI, 24 V DC / 12 DO, 24 V DC NPN Transistor / 24 V DC power supply
16 DI, 24 V DC / 12 DO, 24 V DC PNP Transistor, short circuit protection /
24 V DC power supply
16 DI, 24 V DC / 11 DO, Relay, 2 ampere, 1 DO 24 V DC PNP Transistor /
24 V DC PS
16 DI, 24 V DC / 11 DO, Relay, 2 ampere, 1 DO 24 V DC PNP Transistor / AC PS
16 DI, 24 V DC / 12 DO, Relay, 2 ampere / 24 V DC power supply
16 DI, 24 V DC / 12 DO, Relay, 2 ampere / 110-240 V AC power supply
16 DI, 110 V AC ONLY / 12 DO, 110-240 V AC SSR, 0.5 ampere /
110-240 V AC power supply
24 DI, 24 V DC / 16 DO, 24 V DC PNP Transistor, short circuit protection /
24 V DC power supply
24 DI, 24 V DC / 16 DO, 24 V DC NPN Transistor / 24 V DC power supply
24 DI, 24 V DC / 16 DO, Relay, 2 ampere / 24 V DC power supply
24 DI, 24 V DC / 16 DO, Relay, 2 ampere / 110-240 V AC power supply
40 DI, 24 V DC / 24 DO, 24 V DC PNP Transistor, short circuit protection /
24 V DC power supply
40 DI, 24 V DC / 24 DO, 24 V DC NPN Transistor / 24 V DC power supply
40 DI, 24 V DC / 24 DO, Relay, 2 ampere / 24 V DC power supply
40 DI, 24 V DC / 24 DO, Relay, 2 ampere / 110-240 V AC power supply
EH-D10DTP
EH-D10DTN
EH-D10DR
EH-D14DTP
EH-D14DTN
EH-D14DTPS
EH-D14DR
EH-A14DR
EH-A14AS
EH-D20DTN
EH-D20DTPS
EH-D20DR
EH-A20DR
EH-D23DRP
EH-A23DRP
EH-D28DTP
EH-D28DTN
EH-D28DTPS
EH-D28DRP
EH-A28DRP
EH-D28DR
EH-A28DR
EH-A28AS
EH-D40DTPS
EH-D40DTN
EH-D40DR
EH-A40DR
EH-D64DTPS
EH-D64DT
EH-D64DR
EH-A64DR
Base Units
Description Cat. No. Price $
1 - 8
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B3’
Micro programmable logic controllersEH Micro series – Ordering details
Refer catalogue SI-E108U
Expansion Units - Digital
Description Cat. No. Price $
8 DI, 24 V DC / 24 V DC power supply
8 DO, 2 ampere / 24 V DC power supply
8 DO, 24 V DC PNP Transistor, Short Circuit Protected / 24 V DC power supply
8 DO, 24 V DC NPN Transistor / 24 V DC power supply
4 DI, 24 V DC / 4 DO, Relay, 2 ampere / 24 V DC power supply
4 DI, 24 V DC / 4 DO, 24 V DC PNP Transistor, Short Circuit Protected / 24 V DC power supply
4 DI, 24 V DC / 4 DO, 24 V DC NPN Transistor / 24 V DC power supply
8 DI / 6 DO, 24 V DC PNP Transistor / 24 V DC power supply
8 DI / 6 DO, 24 V DC PNP Transistor, Short Circuit Protected / 24 V DC power supply
8 DI / 6 DO, 24 V DC NPN Transistor / 24 V DC power supply
8 DI, DC / 6 DO, Relay, 2 ampere / 24 V DC power supply
8 DI, DC / 6 DO, Relay, 2 ampere / 110-240 V AC power supply
16 DI, 24 V DC / 24 V DC power supply
16 DO, Relay, 2 ampere / 24 V DC power supply
16 DO, 24 V DC PNP Transistor, Short Circuit Protected / 24 V DC power supply
16 DO, 24 V DC NPN Transistor / 24 V DC power supply
16 DI / 12 DO, 24 V DC PNP Transistor / 24 V DC power supply
16 DI / 12 DO, 24 V DC PNP Transistor, Short Circuit Protected / 24 V DC power supply
16 DI / 12 DO, 24 V DC NPN Transistor / 24 V DC power supply
16 DI / 12 DO, Relay, 2 ampere / 24 V DC power supply
16 DI / 12 DO, Relay, 2 ampere / 110-240 V AC power supply
40 DI, 24 V DC / 24 DO, 24 V DC NPN Transistor / 24 V DC power supply
40 DI, 24 V DC / 24 DO, 24 V DC NPN Transistor / 24 V DC power supply
40 DI, 24 V DC / 24 DO, relay 2 ampere / 24 V DC power supply
40 DI, 24 v DC / 24 DO, relay 2 ampere / 100 - 240 V AC power supply
Expansion Units - Analogue
4 AI, 0-10 V DC or -10 to +10 V DC or 0-20 mA or 4-20 mA / 2 AO, 0-10 V DC or 0-20 mA or 4-20 mA / 110-240 V AC power supply
4 AI, 0-10 V DC or -10 to +10 V DC or 0-20 mA or 4-20 mA / 2 AO, 0-10 V DC or 0-20 mA or 4-20 mA / 24 V DC power supply
4 RTD, PT100, 2 or 3 wire / 24 V DC power supply
4 RTD, PT100, 2 or 3 wire / 110-240 V AC power supply
4 RTD, PT100, 2 or 3 wire / 2 AO, 0-10 V DC or 0-20 mA or 4-20 mA / 24 V DC power supply
4 RTD, PT100, 2 or 3 wire / 2 AO, 0-10 V DC or 0-20 mA or 4-20 mA / 110-240 V AC power supply
2 AI, 0-10 V DC with RS232C port for 20, 40 and 64 I/O base units
2 AI, 0-10 V DC with RS485 port for 20, 40 and 64 I/O base units
Expansion Cables
Expansion cable, 100 cm long (included for free with all types of expansion modules)
Expansion cable, 500 cm long (vertical arrangement)
Expansion cable, 1000 cm long (remote arrangement)
EH-D8ED
EH-D8ER
EH-D8ETPS
EH-D8ETN
EH-D8EDR
EH-D8EDTPS
EH-D8EDTN
EH-D14EDTP
EH-D14EDTPS
EH-D14EDTN
EH-D14EDR
EH-A14EDR
EH-D16ED
EH-D16ER
EH-D16ETPS
EH-D16ETN
EH-D28EDTP
EH-D28EDTPS
EH-D28EDTN
EH-D28EDR
EH-A28EDR
EH-D64EDT
EH-D64EDTPS
EH-D64EDR
EH-A64EDR
EH-D6EAN
EH-A6EAN
EH-D4ERTD
EH-A4ERTD
EH-D6ERTD
EH-A6ERTD
EH-OB232
EH-OB485
EH-MCB01
EH-MCB05
EH-MCB10
Approvals
1 - 9
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Accessories
Description Cat. No. Price $
RS232C port with 2 AI, 0-10 V DC for 20, 40 and 64 I/O base units - Plug on module
RS485 port with 2 AI, 0-10 V DC for 20, 40 and 64 I/O base units - Plug on module
Memory unit for backup of a user program - Plug on module
USB to serial converter (RS232C) - Plug on Module
USB to serial converter (RS232) Plug in Cable
Battery Standard for 23 or 28 I/O base units
Battery Long for 23 or 28 I/O base units
Battery Long for 20, 23, 28, 40 and 64 I/O base units
External Power supply 24 V DC, 3.5 Ampere power supply
External Power supply 24 V DC, 5 Ampere power supply
Programming Software
Description Cat. No. Price $
Programming software for EH Micro base units, 10, 14, and 28 I/O
Programming software for EH Micro
Programming software for EH Micro/EH150/H200/H250/H252
Programming cable, PLC to PC, (9 pin D), 200 cm
ACTWINCD 1)
ACTWINM1 1)
ACTWINH 1)
CBL-1509
Refer catalogue SI-E108U
Price Schedule ‘B3’
Micro programmable logic
controllersEH Micro series – Ordering details
EH-OB232
EH-OB485
EH-OBMEM
EH-OBUSB
USB-COM
EH-MBAT
EH-MBATLC
EH-MBATL
XCSP85C
XCSP120C
EH-OBUSB
EH-OB232
Notes: 1) Read about software on page 1 - 6.
14-point type, 8/16-point expansion unit 20/40-point type
64-point type23/28-point type
10-point type
70 80 80 90 80 90
80 9080 90
6575 47 85
95140150
76 8.4185195
140150
4.8 4.
8
4.8
Dimensions (mm)
76 8.4
10 I/O base
23/28 I/O bases 64 I/O base, 64 I/O expansions
Elevation 10 I/O 14 I/O base, 8/16 expansions
Elevation 14/20/23/28/40/64 I/O
20/40 I/O bases
Approvals
1 - 10
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Modular programmable logic controllersEH-150 series
Refer catalogue SI-E103Y
Flexible networking possibilitiesApprovals
Quality Control
Programming
Terminal
Adroit
SCADA
Ethernet IEEE802.3
Optical Link Coaxial Link
Web Controller EH-150 EH-150
H252EH-150 RS-422 up to 32 units connectable
EH-Micro 20/23/28/40/64 I/O
EH-150 EH-150 H252 H-302~H-4010H-302~H-4010
ESA HMI Third PartyDeviceNet™ Slaves
EH-150DeviceNet™ Slave
Third PartyProfibus® Slaves
EH-150Profibus® Slave
1 - 11
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
CPUs
Description Cat. No. Price $
Up to 512 I/O, Up to an 8 slot rack, No expansion racks possible, 4 K flash, 2 Ports @ 19.2 kbpsUp to 1,024 I/O, Up to an 8 slot rack, Up to 1 expansion rack of up to 8 slots, 8 K Flash, 2 Ports @ 38.4 kbps, Real Time Clock, Modem ControlUp to 1,024 I/O, Up to an 8 slot rack, Up to 1 expansion rack of up to 8 slots, 16 K Flash, 2 Ports @ 38.4 kbps, Real Time Clock, Modem Control, Additional Control FunctionsUp to 2,112 I/O, Up to an 11 slot rack, Up to 2 expansion racks of up to 11 slots, 16 K Flash, 2 Ports @ 38.4 kbps, Real Time Clock, Modem Control, Additional Control FunctionsUp to 3,520 I/O, Up to an 11 slot rack, Up to 4 expansion racks of up to 11 slots, 48 K Flash, 2 Ports @ 38.4 kbps, Real Time Clock, Modem Control, Additional Control FunctionsBase Rack Power Supply Modules
Input from 85 to 264 V AC / Output, 3.8 ampere @ 5 V DC and 0.4 ampere @ 24 V DCInput 21.6 to 26.4 V DC / Output, 3.8 ampere @ 5 V DCBase Racks
Space for Power supply and CPU and 3 slots for I/O modulesSpace for Power supply and CPU and 5 slots for I/O modulesSpace for Power supply and CPU and 8 slots for I/O modulesSpace for Power supply and CPU and 11 slots for I/O modules, Requires EH-CPU516 and aboveMemory Modules
Stores up to 48 K steps of user program for EH-CPU316 and aboveStores up to 16 K steps of user program and stores 384 K words of memory data for EH-CPU316 and above I/O Controller
Required for each expansion rack if not using Profibus, or Devicenet slavesLinking cable between racks and the EH-IOCH I/O controller, 1 meter longCommunication Modules
Devicenet master, 256 word input, 256 word output. Requires EH-CPU316 and above. Up to 2 masters can be installed per CPU in LINK mode and 4 in REMOTE mode. Up to 63 slaves can be controlled by each masterDevicenet slave (check compatibility of I/O)Profibus master, 256 word input, 256 word output. Requires EH-CPU316 and above. Up to 2 masters can be installed per CPU. Up to 124 slaves can be controlled by each master Profibus slave (check compatibility of I/O)Ethernet, IEEE802.3 standard, 10 BASE-T, TCP or UDP. Requires EH-CPU316, or aboveSerial communications, Modbus RTU, Modbus ASCII, RS232C port and RS232C/422/485 port. Requires EH-CPU516 and aboveCPU Link Modules – Requires EH-CPU 316 and above
Coaxial Link, 1.0 Mbps, Up to 500 meters between stations. Up to 64 stationsOptical Link, 1.0 Mbps, Up to 1,000 meters between stations. Up to 64 stations
Price Schedule ‘A4’
Refer catalogue SI-E103Y
EH-I0CD
EH-CPU104
IntroductionThe EH-150 series of PLCs incorporates the most advanced technologies in its compact body, such as a 32 bit RISC chip microcomputer for high speed arithmetic operations and a large flash memory. A big range of modular hardware options allows systems to be tailored to the requirements of each application, while spending a minimum on capital outlay and permitting future upgrades and expansions. The EH-150 series can easily network with other PLCs in the Hitachi range and it supports several common fieldbus systems, such as Ethernet, Profibus, Modbus and DeviceNet™ allowing communication with third party devices.
Modular programmable logic controllersEH-150 series
Ordering details – EH-150 series
EH-CPU548
EH-RMD
Approvals
EH-CPU104
EH-CPU208
EH-CPU316
EH-CPU516
EH-CPU548
EH-PSA
EH-PSD
EH-BS3
EH-BS5
EH-BS8
EH-BS11
EH-MEMP
EH-MEMD
EH-IOCH
EH-CB10
EH-RMD
EH-IOCD
EH-RMP
EH-IOCP
EH-ETH2
EH-SIO
EH-LINK
EH-OLINK
1 - 12
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
DC Input Modules
Description Cat. No. Price $
16 DI, 24 V DC, Removable screw terminal block
32 DI, 24 V DC, Plug connector
64 DI, 24 V DC, Plug connector
8 DI, 24 V DC, Removable screw terminal block
16 DI, 24 V DC, 16 millisecond filter, Removable screw terminal block
32 DI, 24 V DC, 16 millisecond filter, Plug connector
32 DI, 24 V DC, Euro cage clamp connector
32 DI, 24 V DC, 16 millisecond filter, Euro cage clamp connector
High Density Input Interface Board and Cable
32 Input terminal interface board
Cable for 32/64-point Input modules (Connectors at both ends)
AC Input Module
16 DI, 100 to 120 V AC, Removable screw terminal block
16 DI, 200 to 240 V AC, Removable screw terminal block
DC Output Module
16 DO, 12 to 24 V DC, PNP Transistor, Removable screw terminal block
32 DO, 12 to 24 V DC, PNP Transistor, Plug connector
64 DO, 12 to 24 V DC, PNP Transistor, Plug connector
16 DO, 12 to 24 V DC, NPN Transistor, Removable screw terminal block
32 DO, 12 to 24 V DC, NPN Transistor, Plug connector
64 DO, 12 to 24 V DC, NPN Transistor, Plug connector
8 DO, 12 to 24 V DC, NPN Transistor, Removable screw terminal block
8 DO, 12 to 24 V DC, PNP Transistor, Removable screw terminal block
16 DO, 12 to 24 V DC, PNP Transistor with Short Circuit Protection, Removable screw terminal block
32 DO, 12 to 24 V DC, NPN Transistor, Euro cage clamp connector
32 DO, 12 to 24 V DC, PNP Transistor, Euro cage clamp connector
High Density Output Interface Board and Cable
16 Output relay interface board
Cable for 32 and 64-point Output modules (Connectors at both ends)(PNP Only)
Cable for 32 and 64-point Output modules (Connectors at both ends)(NPN Only)
Plug in relay for EHRLY16
AC Output Module
16 DO, 100/240 V AC, Triac, Removable screw connector
4 DO, 100/240 V AC, Triac, Removable screw connectorRelay Output Module
16 DO, Relay, 2 ampere, Removable screw terminals
8 DO, Relay, 2 ampere, Isolated commons, Removable screw terminals
12 DO, Relay, 2 ampere, Removable screw terminals High Function Module
2 High Speed Counter Inputs, 32 bit, Up to 100 KHz, 1, or 2 phase, 2-point open collector output, Plug connector
Cable for EH-CU counter module. 30 to 34 socket.Interface board for EH-CBLCU counter cable. Cage clamp connectors 34 pin/point2 High Speed Counter Inputs, 32 bit, Up to 100 KHz, 1, or 2 phase, 2-point open collector output, Euro cage clamp connector
EH-XD16
EH-XD32 1)
EH-XD64 1)
EH-XD8
EH-XDL16
EH-XDL32 1)
EH-XD32E
EH-XDL32E
EHTRM32
EHCBLIN32
EH-XA16
EH-XAH16
EH-YTP16
EH-YTP32 2)
EH-YTP64 2)
EH-YT16
EH-YT32 2)
EH-YT64 2)
EH-YT8
EH-YTP8
EH-YTP16S
EH-YT32E
EH-YTP32E
EHRLY16
EHCBLOUT32PNP
EHCBLOUT32NPN
40.51-24 VDC
EH-YS16
EH-YS4
EH-YR16
EH-YR8B
EH-YR12
EH-CU
EH-CBLCU
289-506
EH-CUE
Price Schedule ‘A4’
Refer catalogue SI-E103Y
Modular programmable logic controllersEH-150 series (Cont’d)Ordering details
Notes: 1) Requires 1 (2) High density input interface board(s) and 1 (2) cable(s) for 32 (64) input module. 2) Requires 2 (4) High density output interface boards and 1 (2) cable(s) and 32 (64) relays for 32 (64) output module.
EH-YR16
EH-XD32
EH-XD64
EH-XD16
Approvals
1 - 13
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Modular programmable logic controllersEH-150 series (Cont’d)
Price Schedule ‘A4’
Refer catalogue SI-E103Y
Ordering details
Number of I/O modules
L1
L2
11
447
462.5
Base
Dimensions (mm)
EH-BS11
8
357
372.5
EH-BS8
5
267
282.5
EH-BS5
3
207
222.5
EH-BS3
Notes: 1) XCSF85C and XCSF120C power supplies are on Price Schedule ‘A2’.
EH-TC8
EH-YTP64
EH-POS
EH-CU
Approvals
Analogue Input Module
Description Cat. No. Price $
8 AI, 0-10 V DC, 12 bit resolution, Removable screw terminals
8 AI, -10 to +10 V DC, 12 bit resolution, Removable screw terminals
8 AI, 4-20 mA, 12 bit resolution, Removable screw terminals
4 AI, PT100, or PT1000 RTD, 15 bit signed resolution, Removable screw terminals
8 AI, Thermocouple types K,E,J,T,B,R,S,N selectable, 15 bit resolution
4 AI, 4-20 mA and 4 AI, 0-10 V DC, 12 bit resolution, Removable screw terminals
8 AI, 0-22 mA, 12 bit resolution, Removable screw terminals
8 AI, 0-22 mA, 4-22 mA, 0-10 V DC, selectable, 14 bit resolution, Removable screw terminals
Analogue Output Module
4 AO, 0-10 V DC, 12 bit resolution, Removable screw terminals
4 AI, -10 to +10 V DC, 12 bit resolution, Removable screw terminals
4 AO, 4-20 mA, 12 bit resolution, Removable screw terminals
2 AO, 4-20 mA and 2 AO, 0-10 V DC, 12 bit resolution, Removable screw terminals
2 AI, -10 to +10 V DC, 12 bit resolution, Removable screw terminals
8 AO, 0-22 mA, 4-22 mA, 0-10 V DC, selectable, 14 bit resolution, Removable screw terminals
Programming Items
Programming Software, (IEC 61131-3 compliant), site license
PC-PLC programming cable, 2 meters long, 9 pin female to RJ45
USB to serial converter, for when your laptop doesn't have a serial port
SYCON Profibus configuration software
Miscellaneous
Lithium Battery to backup data memory during power outage
Cover for unused slots in racks
DC power supplies
External Power supply 24 V DC, 3.5 Ampere power supply
External Power supply 24 V DC, 5 Ampere power supply
Positional control modules
Single axis, Plug connector
Four axis, Plug connector
EH-AX8V
EH-AX8H
EH-AX8I
EH-PT4
EH-TC8
EH-AX44
EH-AX8IO
EH-AXH8M
EH-AY4V
EH-AY4H
EH-AY4I
EH-AY22
EH-AY2H
EH-AYH8M
ACTWINH
CBL-1509
USB-COM
SYCON
LIBAT-H
EH-DUM
XCSP85C 1)
XCSP120C 1)
EH-POS
EH-POS4
IEC 61131-3 PROGRAMMING SOFTWARE
AUTOMATION SYSTEMS
FREEDevelopmentSoftware
ActWin licensed packagesActWin-M1
ActWin-H
For licensing, please contact your nearest
NHP representative.
Minimum system requirements
64 MB RAM, 25 MB free HDD space,
CD-ROM drive and Windows® 95/98 XP
or NT4.0/2000
1 - 15
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Micro and modular PLC accessory
selection guideEH-150 /
EH MICRO
ACTWINH
CBL-1509
EH150
-PGMCHH
-PGMGPH
EH150
- PGCB02H
+ RS05
N/A
EH Micro
-EHMCB10
-EHMCB05
-EHMCB01
EH150
-EHCB10
EHCBLOUT32
EHCBLIN32
–
EH 150-LIBATH
EH Micro-EHMBAT
PLC type
Software
PC to PLC
cables
Programmers
Programmer to
PLC cables
Programmer to
PC cables
Base/main to
expansion rack
cables
Interface board
cables
EHRLY16
EHTRM32
HTRMBRD32
Batteries
EC / EM series
ACT-MINI
EM3 - CBLEM3
EC - CBLEC
PGMJ
PGMJR2
CNPG15
CBL-PGMJR
EM series
-CNM01
-CNM06
-CNM10
-CNMS10
N/A
N/A
Mitsubishi
Alpha 2
AL-PCSWIN-E
AL-232CAB
Via front panel
N/A
N/A
N/A
N/A
N/A
H200/250/252
H Board
ACTWINH
CBL-90H
PGMCHH
PGMGPH
PGCB-02H
N/A
CNM-01
CNM-06
CNM-10
CNM-S10
CBLHOUT32
–
CBM-02
LIBAT-H
H300/700/2000
302/702/1002/2002,
ACTWINH
CBL-90H
PGMCHH
PGMGPH
PGCB-02H
N/A
1st rack (W/CPU)
CBL-05H
CBL-10H
Rack to rack
(Expansions)
CBE-05H
CBE-10H
N/A
LIBAT-H
Cable guide
EC SERIES
(Discontinued)
Mitsubishi Alpha 2
Mitsubishi Alpha
(Discontinued)
H200/250/252
SERIES
(Discontinued)
EM SERIES
(Discontinued)
PGMJ-R2
(Discontinued)CABLE ONBOARD PROGRAMMER
EH MICRO SERIES
EH-150
SERIES
EHCBLOUT32
EHCBLIN32
CBLHOUT32
CBM-02
EHRLY16
EHTRM32
EHRLY16
HTRMBRD32
EM 3 SERIES
(Discontinued)
CBL-1509
AL-232CAB CBL-1509
AL-232CAB CBL-90H
CBL-EM3
CBL-EC
CNPG-15
CBL-PGMJR
1 - 16
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Optimum design of a Fieldbus node
The following requirements must be met in order to design an economic fieldbus node:
best possible modularity – 1, 2, 4 or 8 channel for standard I/Os – single channel for special functions
combination of digital and analogue I/Os including various voltage, power and instrumentation signal requirements within a node
sensors and actuators may be wired independently of the fieldbus fast coupling to the chosen fieldbus quick and clear marking facility easy handling with few additional accessories fast and easy wiring with high operational reliability RS 232/RS 485 communication modules, user configurable and easy to use
WAGO I/O-SystemFieldbus independent BUS terminal block
Quick adaption to standard fieldbus systems
Using the WAGO I/O-SYSTEM it is now possible: To proceed with external wiring of the I/O modules without knowledge of the fieldbus system to
be used simple snap-fit mounting of the respective fieldbus coupler to the wired modules when fieldbus system
is known This gives inventory reduction and greater availability of modules for many different fieldbus systems,by adaption of all modules with a single bus coupler chosen for that system.
Refer catalogue WFC2
DeviceNet
Profibus
Ethernet
Modbus
A huge
range of
fieldbus
connection
options
areavailable
1 - 17
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
WAGO I/O-SystemFieldbus independent BUS terminal block
Combination of different functionsOver 350 module types in the range
The combination of digital and analogue I/Os with different potentials, powers and measuring signals allows the realisation of user specific fieldbus nodes.
Wide choice of Fieldbus couplers with integrated supply terminal block for external 24 V DC
Digital inputs 1)Digital outputs 2) Analogue
inputs 3)
Analogue
outputs 4)
Special functions
Notes: 1) Supply terminal block for external 230 V AC. 2) Supply terminal block for external 24 V DC (electrical isolation). 3) Supply terminal block for external modification of reference potential. 4) Supply terminal block for external 5 V DC.
ProfibusInterbus CAN OpenDeviceNetModbusLONEthernet
Refer catalogue WFC2
Each node of the WAGO® I/O System can easily be assembled to match your existing fieldbus and I/O needs, or adapted to meet your changing requirements. One, two, four and eight channel I/O modules allow you to purchase the minimum amount of I/O that you need for your application. Nodes can each accommodate up to 64 multi-channel modules. The range of modules includes over 350 types to suit your diverse I/O needs. There are digital I/O, analogueI/O, and 16 specialty modules in the range with new modules being frequently developed. The specialty modules include counters, encoder inputs, RS 232 and RS 485 serial comms, AS-i, DALI/DSI, MP-bus, SSI and TTY 20 mA loop.
Flexibility Approvals
1 - 18
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
WAGO I/O-System – 750 SeriesThe BUS terminal block
The universal basic module
Assembly Power jumper contacts on the field side
Slim design modules for assembly onto
DIN rail...
...secure connection with dovetails
Quick exchange of a bus
terminal block
...within the assembly – without tools Safe, automatic connection by gold-plated, self-cleaning, slide contacts.
Safe, automatic connection by tinned, self-cleaning slide contact, ground (earth) makes first
and breaks last
W x H 1) x D (mm) 12 x 64 x 100
Note: 1) From upper edge of carrier rail.
H
W
D
Exchange within the assembly
Data contacts
1 - 19
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
WAGO I/O-System – 750 SeriesThe BUS terminal block
The universal basic module
Marking of clamping units by coloured
miniature WSB markers
Yellow - digital inputs
Red - digital outputs
Green - analogue inputs
Blue - analogue outputs
Clear - supply and special
function terminal block
Different functions marked by transparent
coloured group marker carriers
Group marking carrier (can be withdrawn and
replaced) with large area for self marking
Vibration proof, fast and maintenance-free
wiring of 0.08 mm2-2.5 mm2/AWG 28-14
Function at locked position 1:
Power output to I/O group is off
Function at locked position 2: Easy fuse replacement via hinged cover
Diagnosis and status indication by LED for
safe start-up and system control
Signal tracing with wired conductors
Colour coded for identification/handling
Moulded marking of clamping units
CAGE-CLAMP connection Status indication Testing
Fuse holder
Refer catalogue WFC2
1 - 20
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
WAGO I/O-SystemFieldbus independent BUS terminal block
Automation in industry
Complex production equipment such as that used in automated manufacturing industries use large numbers of sensors and actuators.Use of a fieldbus system and distributed control can considerably reduce costs.Fieldbus nodes (the fieldbus connection + I/O points) are of special importance in this context. If these are properly designed much of the cost can be minimised.
Typical node featuring optional Quick Connect I/O modules
A WAGO I/O node may be physically divided into several parts and the Data bus extended for up to 5 metres using Extension modules and standard RJ45 connectors and cables. A free software tool and a 750-920 programming cable is also required.
Extended WAGO I/O node example Internal Data Bus Extension Coupler Modules
1 - 21
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Profibus DP/V1, 12 MBaudDeviceNet, 125-500 KbaudEthernet TCP/IP 10 Mbit/sEthernet TCP/IP 10/100 Mbit/sModbus RS 485, 150-19200 baudProfibus DP, 12 MBaud (economy)DeviceNet, 125-500 Kbaud (economy)Programmable Fieldbus controller - Stocked
Profibus DP/V1, 12 MBaudProfiNet TCP/IP, 100 Mbit/sEthernet TCP/IP 10 Mbit/sEthernet TCP/IP 10/100 Mbit/sEthernet TCP/IP 10/100 Mbit/s, with RS232 serial portFieldbus couplers / Economy fieldbus couplers (smaller process image) - Indent 1)
Profibus DP, 1.5 MBaud, fibre opticProfiNet TCP/IP, 100 Mbit/sProfiNet TCP/IP, 100 Mbit/s, 2 portEthernet, Powerlink, 10/100 Mbit/s, V2, ARP, HTTP, DNS,SNTP, FTPModbus RS 232, 150-19200 baudModbus RS 485, 1.2-115.2 KbaudModbus RS 232, 1.2-115.2 KbaudCANopen, 10 Kbaud - 1 Mbaud, MCSCANopen, 10 Kbaud - 1 Mbaud, D-SubLON, FTTPeer to Peer, FTTInterbus, 500 KBaudInterbus, fibre opticCAL, 10 Kbaud - 1 MbaudFirewire, 100 MBaud, 200 MBaud, 400 MBaudCC-Link, 156 KBaud, 10 MbaudII/O-Lightbus, 2.5 MBaudII/O-Lightbus, 2.5 MBaud, digital signals onlySDSSercoss IIIInterbus, 500 KBaud (economy)Interbus, 2 MBaud (economy)CANopen, 10 Kbaud - 1 Mbaud, MCS (economy)CANopen, 10 Kbaud - 1 Mbaud, D-Sub (economy)Programmable Fieldbus controller - Indent 1)
DeviceNet, 125-500 KbaudEthernet TCP/IP 10/100 Mbit/s, 2 portEthernet TCP/IP 10/100 Mbit/s, 2 port, integrated switchLON, FTTModbus RS 485, 150-19200 baudModbus RS 232, 150-19200 baudModbus RS 485, 1.2-115.2 KbaudModbus RS 232, 1.2-115.2 KbaudInterbus, 500 KBaudCANopen, 10 Kbaud - 1 Mbaud, MCSCANopen, 10 Kbaud - 1 Mbaud, D-SubBACnet/IPKNXnet/IPLinux, 32-bit ARM CPU, 44 MHz, 16 MB RAM, 2.5 MB for JFFS2, BSP with 2.6 kernel, CGI
750-333
750-306
750-342
750-341
750-312
750-343
750-346
750-833
750-840
750-842
750-841
750-873
750-331
750-340
750-370750-350
750-314
750-315
750-316
750-337
750-338
750-319
750-319/004-000
750-304
750-334
750-305
750-339
750-310
750-300
750-320
750-313
750-351
750-344
750-345
750-347
750-348
750-806
750-871
750-881
750-819
750-812
750-814
750-815
750-816
750-804
750-837
750-838
750-830
750-849
750-860
Fieldbus couplers / Economy fieldbus couplers (smaller process image) - Stocked
750-343
Eco-Coupler
750-306
DeviceNet
750-333
Profibus
WAGO I/O System – 750 Series
750-833
Programmable
Price Schedule ‘A4’
Notes: 1) WAGO indent items have a typical delivery time of 2-3 weeks. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
Description Cat. No. Price $
1 - 22
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Notes: 1) WAGO indent items have a typical delivery time of 2-3 weeks. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
Refer catalogue WFC2
Price Schedule ‘A4’
750-400
750-430
750-424
750-530
750-523
WAGO I/O System – 750 Series
4 DI, DC 5 V, 0.2 ms, 2 to 3 connection, PNP2 DI, DC 24 V, 3.0 ms, 2 to 4 connection, PNP2 DI, DC 24 V, 0.2 ms, 2 to 4 connection, PNP4 DI, DC 24 V, 3.0 ms, 2 to 3 connection, PNP4 DI, DC 24 V, 3.0 ms, 2 connection, PNP4 DI, DC 24 V, 0.2 ms, 2 to 3 connection, PNP4 DI, DC 24 V, 3.0 ms, 2 to 3 connection, NPN8 DI, DC 24 V, 3.0 ms, 1 connection, PNP8 DI, DC 24 V, 0.2 ms, 1 connection, PNP4 DI, AC/DC 24 V, 2 connection2 DO, DC 24 V, 0.5 A, short-cct-protected, PNP2 DO, DC 24 V, 2.0 A, short-cct-protected, PNP4 DO, DC 24 V, 0.5 A, short-cct-protected, PNP4 DO, DC 24 V, 0.5 A, 2 connection, short-cct-protected, PNP8 DO, DC 24 V, 0.5 A, NPN8 DO, DC 24 V, 0.5 A, short-cct-protected, PNP2 DO, AC 125 V, AC 0.5 A, DC 30 V, DC 1 A, isol o/pts, 2 C/O2 DO, AC 230 V, 1 A, isolated outputs, 2 c/o contacts2 DO, AC 230 V, DC 30 V, AC/DC 2 A, non-float, 2 make cntcts2 DO, AC 230 V, DC 30 V, AC/DC 2 A, isol o/pts, 2 make cntctsDigital Input modules / Digital Output modules - Indent 1)
2 DI, DC 24 V, 3.0 ms, Prox-Sw, 2 to 4 connection, PNP2 DI, DC 24 V, 0.2 ms, Prox-Sw, 2 to 4 connection, PNP2 DI, DC 24 V, 3.0 ms, 2 to 3 connection, PNP, with diagnostics2 DI, DC 24 V, 3.0 ms, PNP, with diagnostics4 DI, DC 24 V, 0.2 ms, 2 connection, PNP4 DI, DC 24 V, 2 to 3 connection, PNP, pulse extension 10 ms4 DI, DC 24 V, 0.2 ms, 2 to 3 connection, NPN8 DI, DC 24 V, 3.0 ms, 1 connection, NPN8 DI, DC 24 V, 0.2 ms, 1 connection, NPN4 DI, AC/DC 24 V, 2 to 3 connection with power contacts4 DI, AC/DC 24 V, 2 connection2 DI, DC 48 V, 3.0 ms, 2 to 4 connection, PNP2 DI, DC 110 V, configurable high-side or NPN2 DI, AC 120 V, 2 to 4 connection2 DI, AC 230 V, 2 to 4 connection2 DI, NAMUR, Proximity switch acc. to DIN EN 502272 DI, DC 24 V, Intruder detection4 DO, DC 5 V, 20 mA, short-cct-protected, PNP2 DO, DC 24 V, 0.5 A, with diagnostics, short-cct-protected, PNP2 DO, DC 24 V, 2.0 A, with diagnostics, short-cct-protected, PNP4 DO, DC 24 V, 0.5 A, TYPE N, short-cct-protected, NPN4 DO, DC 24 V, 0.5 A, with diagnostics, PNP8 DO, DC 24 V, 0.5 A, with diagnostics, PNP2 DO, Solid State Relay, AC/DC 230 V, 300 mA2 DO, Solid State Relay, AC/DC 230 V, 500 mA, 3 A (< 30 s)1 DO, AC 230 V, AC 16 A, isol output, 1 make cntct, bistable
750-414
750-400
750-401
750-402
750-432
750-403
750-408
750-430
750-431
750-415
750-501
750-502
750-504
750-531
750-536
750-530
750-514
750-517
750-512
750-513
750-410
750-411
750-418
750-421
750-433
750-422
750-409
750-436
750-437
750-423
750-428
750-412
750-427
750-406
750-405
750-425
750-424
750-519
750-506
750-508
750-516
750-532
750-537
750-509
750-522
750-523
Digital Input modules / Digital Output modules - StockedDescription Cat. No. Price $
1 - 23
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A4’
Refer catalogue WFC2
WAGO I/O System – 750 Series
750-452
750-457
750-491
750-557
Notes: 1) WAGO indent items have a typical delivery time of 2-3 weeks. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
750-493
Analogue Input / Analogue Output modules - Stocked
4-channel, 0 - 20 mA, single ended, 12 Bit2-channel, 0 - 20 mA, differential inputs, 14 Bit2-channel, 4 - 20 mA, differential inputs, 12 Bit4-channel, 4 - 20 mA, single ended, 12 Bit2-channel, 4 - 20 mA, single ended, 15 Bit2-channel, 4 - 20 mA, single ended, 12 Bit2-channel, 4 - 20 mA, isolated differential inputs, 12 Bit4-channel, DC 0 - 10 V, single ended, 12 Bit4-channel, DC ± 10 V, single ended, 12 Bit2-channel, DC ± 10 V, Diff. measurement input, 14 Bit2-channel, DC0 - 30 V, Diff. measurement input, 14 Bit2-channel, input module for RTDs, PT100 / RTD, 16 Bit4-channel, 0 - 20 mA, 12 Bit2-channel, 4 - 20 mA, 12 Bit4-channel, 4 - 20 mA, 12 Bit2-channel, DC 0 - 10 V, 12 Bit4-channel, DC 0 - 10 V, 12 Bit4-channel, DC ± 10 V, 12 BitAnalogue Input / Analogue Output modules - Indent 1)
2-channel, 4-20 mA, HART, 4 variables per channel, FDT tool routing to DTM, 12 bit3-phase power measurement, to 500 V AC, 1 A, 0.5 % error, 16 bit3-phase power measurement, to 500 V AC, 5 A, 0.5 % error, 16 bit2-channel, 0 - 20 mA, differential inputs, 12 Bit2-channel, 0 - 20 mA, single ended, 12 Bit2-channel, 0 - 20 mA, single ended, 15 Bit2-channel, 4 - 20 mA, single ended, short circuit protected, 12 Bit2-channel, 0 - 1 A AC/DC, differential inputs, 16 Bit4-channel, DC 0 - 10 V, single ended, 12 Bit2-channel, DC 0 - 10 V, single ended, 12 Bit2-channel, AC/DC 0 - 10 V, differential inputs, 16 Bit2-channel, DC 0 - 10 V, single ended, 16 Bit2-channel, DC ± 10 V, differential inputs, 12 Bit2-channel, DC ± 10 V, single ended, 14 Bit4-channel, input module for RTDs, PT100 / RTD, 16 Bit2-channel, thermocouple, K Type, -100 °C to +1370 °C, 16 Bit2-channel, thermocouple, S Type, 0 °C to +1700 °C, 16 Bit2-channel, thermocouple, T Type, -100 °C to +400 °C, 16 Bit2-channel, thermocouple, +/- 120 mV, 16 Bit2-channel, thermocouple, J Type, -100 °C to +1200 °C, 16 Bit2-channel, thermocouple, E Type, -100 °C to +1000 °C, 16 Bit2-channel, thermocouple, L Type, -25 °C to +900 °C, 16 Bit2-channel, thermocouple, Configurable Temp range with I/O Check1-channel input module for resistor bridge (Strain gauge), 16 Bit, 250 msec conversion1-channel input module for resistor bridge (Strain gauge), 16 Bit, 65 msec conversion2-channel, 0 - 20 mA, 12 Bit2-channel, DC 0 - 10 V, 100 mA, 24 V, 8 Bit2-channel, DC ± 10 V, 12 Bit
750-453
750-480
750-454
750-455
750-474
750-466
750-492
750-468
750-457
750-479
750-483
750-461
750-553
750-554
750-555
750-550
750-559
750-557
750-482
750-493
750-493/000-001
750-452
750-465
750-472
750-473
750-475
750-459
750-467
750-477
750-478
750-456
750-476
750-460
750-469/00000
750-469/000001
750-469/000002
750-469/000003
750-469/000006
750-469/000008
750-469/000012
750-469/003000
750-491
750-491/000-001
750-552
750-560
750-556
Description Cat. No. Price $
1 - 24
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
Price Schedule ‘A4’
WAGO I/O System – 750 Series
750-404
Vibration Module
750-645
Vibration Sensor
750-925
Notes: 1) WAGO indent items have a typical delivery time of 2-3 weeks. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
2-channel, Vibration velocity/Shock pulse, Bearing condition monitoringUp/Down Counter, DC 24 V, 100 kHz2-channel Up/Down Counter, DC 24 V / 16 Bit / 500 HzSerial Interface RS 232 C – ConfigurableSerial Interface RS 485 – ConfigurableModule Bus Extension, End ModuleModule Bus Extension, Coupler ModuleDC 24 V, passiveDC 24 V, max. 6.3 A, without diagnostics, with fuse-holderDC 24 V, max. 6.3 A, with diagnostics, with fuse-holderFilter Module, System and field side pwr supply filter with surge protField Side Connection Module, DC 0 VField Side Connection Module, DC 24 VSeparation ModuleEnd Module, to loop the internal busSpecialty / System modules - Indent 1)
Bluetooth, 2.4 GHz ISM band, Class 1 (100 metres), Master/SlaveExternal antenna for Bluetooth module 750-644, magnetic standBluetooth, serial port adaptor for linking coupler/controller to laptop PC, Class 2Tandem Piezo vibration sensor for Vibration module 750-645Real Time Clock, 32 channel integrated time switch2-channel Pulse Width Module, DC 24 V, short-cct-prot, PNPSSI Transmitter InterfaceIncremental Encoder Interface, TTL level squarewaveIncremental Encoder Interface, RS 422, cam outputsIncremental Encoder Interface, DC 24 VDigital Impulse InterfaceTTY-Serial Interface, 20 mA Current LoopData Exchange ModuleDALI/DSI Master ModuleAS-interface Master ModuleRF-Receiver EnOceanMP-Bus (Multi Point-Bus) Master ModuleStepper Controller, RS422, 24 V DC, 20 mA interfaces, 30 mA outputStepper Controller, 24 V DC, 2-phase, 2 x 1.5 A outputsDC Drive controller, 24 V DC, 5 A output, incremental encoder interface, end stop inputsBus Power Supply, DC 24 VSupply Module, 24 V DC input, selectable 5,8,10,12,15 V DC outputs, 0.5 A, 1 A @ 5 V DCAC 120 V, max. 6.3 A, without diagnostics, with fuse-holderAC/DC 230 V, without diagnostics, passiveAC 230 V, max. 6.3 A, without diagnostics, with fuse-holderAC 230 V, max. 6.3 A, with diagnostics, with fuse-holderFilter Module, Field side power supply filter with o/voltage protField Side Connection Module, AC/DC 0 ...230 VSeparation Module with Power ContactsBinary Spacer Module
Specialty / System modules - Stocked
750-645
750-404
750-638
750-650/003000
750-653/003000
750-627
750-628
750-602
750-601
750-610
750-626
750-604
750-603
750-616
750-600
750-644
758-912
750-921
750-925
750-640
750-511
750-630750-631/000-004
750-637
750-634
750-635
750-651
750-654
750-641
750-655
750-642
750-643
750-670
750-671
750-636
750-613
750-623
750-615
750-612
750-609
750-611
750-624
750-614
750-621
750-622
Description Cat. No. Price $
1 - 25
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
Price Schedule ‘A4’
AccessoriesDescription Cat. No. Price $
PROFIBUS, Bus connector with D-SUB male connector, 9 pole
PROFIBUS, Bus connector with D-SUB male and female, 9 pole
INTERBUS (IN), Bus connector with D-SUB female, 9 pole
INTERBUS (OUT), Bus connector with D-SUB male, 9 pole
CANopen, Bus connector with D-SUB female connect, 9 pole
CC-Link, Bus connector with D-SUB male connecter, 9 pole
Multi-Port Device Taps, 2 trunk Cable (in/output), 4 drop cables
Multi-Port Device Taps, 2 trunk Cable (in/output), 2 drop cables
Multi-Port Device Taps, 2 trunk Cable (in/output), 1 & 2 drop cables
Programming/configuration cable from laptop/PC to Controller/D-ConnectorBluetooth, serial port adaptor for linking coupler/controller to laptop PC, Class 2 Programming/configuration cable from laptop/PC to Controller, USB-connectorPower Supply for AS-Interface, Input 90 to 264 V AC, Output 30.5 V DC, 3.0 APower Supply, Input 90 to 264 V AC, Output 1.0 A V DC, Cage Clamp connectorsPower Supply, Input 90 to 264 V AC, Output 2.5 A V DC, Cage Clamp connectors
Extended Temperature Range from -20° to +60 °C
Ethernet Controller, 100 Mbit/s, EXTModbus Controller RS-485, 150-19, 200 Bd EXTModbus Controller RS-485, 1.2-115.2 KBd EXTProfibus coupler, DP/V1, 12 MBd, EXTProfibus controller, DP/V1, 12 MBd, EXTCANopen coupler, EXT2 Digital Input, 24 V DC, 3.0 msec, EXT4 Digital Input, 24 V DC, 3.0 msec, EXT8 Digital Input, 24 V DC, 3.0 msec, EXT4 Digital Output, 24 V DC, 0.5 A, EXT8 Digital Output, 24 V DC, 0.5 A, EXT2 Analogue Input, 4-20 mA, Single Ended, EXT4 Analogue Input, 4-20 mA, Single Ended, EXT4 Analogue Input, 4-20 mA, Differential, EXTSupply module, 24 V DC, EXTSerial Interface, RS-485, 9600/n/8/1/5 Byte Cont., EXTSerial Interface, RS-485, Configurable, EXT
750-960
750-970
750-961
750-962
750-963
750-965
810-900/000-001
810-901/000-001
810-902/000-001
750-920
750-921
750-923
787-692
787-602
787-612
750-841/025-000
750-812/025-000
750-815/025-000
750-333/025-000
750-833/025-000
750-337/025-000
750-400/025-000
750-402/025-000
750-430/025-000
750-504/025-000
750-530/025-000
750-466/025-000
750-455/025-000
750-454/025-000
750-602/025-000
750-653/025-018
750-653/025-000
WAGO I/O System – 750 Series 1)
Notes: 1) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
750-960
750-970
288-824
810-901/000-001
810-902/000-001
750-921
1 - 26
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
WAGO I/O System – 857 Series
JUMPFLEX Transducers
Refer catalogue WFC2
Multi-Talented With High ProfileA complete product line is available, bringing each signal into
shape.
The perfect match of housing and electronics is the key to a highly successful device. This goal has been achieved by WAGO with the new family of transducers and relay modules Series 857.
Features:
“True” 6.0 mm/0.236” width Extended range of temperatures from -25 °C to +70 °C “Safe isolation” with 2.5 kV test voltage Configuration via DIP switch CAGE CLAMP® S connection – fast – reliable – maintenance free
solid
AWG 28 … 12 (0.08 mm2 … 2.5 mm2)
ferruled
AWG 22 … 14 (0.25 mm2 … 1.5 mm2)
fine-stranded
AWG 22 … 12 (0.34 mm2 … 2.5 mm2)
Vibration Proof - Fast - Maintenance FreeCAGE CLAMP® S connection for all types of wires.
For Extreme ApplicationsExtended range of temperatures from -25 °C to +70 °C allows for wide application areas.
1 - 27
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Specifications Cat. No. Price $
Isolation Amplifier Input: 0(4) - 20 mA, 0(1) - 5 V, 0(2) - 10 V
(Configuration via DIP Switch) Output: 0(4) - 20 mA, 0(1) - 5 V, 0(2) - 10 V
Isolation Current Amplifier Input: 0(4) - 20 mA
(Fixed Settings) Output: 0(4) - 20 mA
Isolation Voltage Amplifier Input: 0(2) - 10 V
(Fixed Settings) Output: 0(2) - 10 V
Power Supply Transducers
Repeater Power Supply Input: 0(4) - 20 mA
(Configuration via DIP Switch) Output: 0(4) - 20 mA, 0(1) - 5 V, 0(2) - 10 V
Repeater Power Supply, HART Input: 4 - 20 mA
(Fixed Settings) Output: 4 - 20 mA
Signal Splitter Input: 0(4) - 20 mA, 0(1) - 5 V, 0(2) - 10 V
(Configuration via DIP Switch) Output: 2 x 0(4) - 20 mA
Isolator Transducers
Passive Isolator, 1 Channel Input: 0(4) - 20 mA
(Fixed Settings) Output: 0(4) – 20 mA
Passive Isolator, 2 Channels Input: 0(4) - 20 mA
(Fixed Settings) Output: 0(4) - 20 mA
Temperature Transducers
Transducer for RTDs Input: Pt 100, Pt 200, Pt 500, Pt 1000
(Configuration via DIP Switch) Output: 0(4) - 20 mA, 0(2) - 10 mA,
0(2) - 10 V, 0(1) - 5 V
Transducer for RTDs Input: Pt 100, Pt 200, Pt 500, Pt 1000
(Configuration via DIP Switch Output: 0(4) - 20 mA, 0(2) - 10 mA,
or Software) 1) 0(2) - 10 V, 0(1) - 5 V
Transducer for Thermocouples Input: Type J: -150 °C ... +1200 °C /
(Configuration via DIP Switch) Type K: -150 °C ... +1350 °C
Output: 0(4) - 20 mA, 0(2) - 10 mA,
0(2) - 10 V, 0(1) - 5 V
Transducer for Thermocouples Input: Type J: -150 °C ... +1200 °C /
(Configuration via DIP Switch Type K: -150 °C ... +1350 °C
or Software) 1) Output: 0(4) - 20 mA, 0(2) - 10 mA,
0(2) - 10 V, 0(1) - 5 V
Programming/configuration cable from laptop/PC to Controller, D-Connector
Bluetooth, serial port adaptor for linking coupler/controller to laptop PC, Class 2
Programming/configuration cable from laptop/PC to Controller, USB-connector
WAGO I/O System – 857 Series 2)
JUMPFLEX Transducers
Refer catalogue WFC2
Price Schedule ‘A4’
Highest SafetyAll devices provide “safe isolation” with 2.5 kV test voltage to EN 61140.
Flexibility at its FinestConfiguration via DIP switch.
Temperature transducers can also be configured via software.
Isolation Amplifier,
Configurable
Temperature
Transducer
for RTDs
Amplifier Transducers
857-400
857-412
857-411
857-420
857-421
857-423
857-451
857-452
857-800
857-801
857-810
857-811
750-920
750-921
750-923
Notes: 1) WAGO I/O Check Software (P/N 759-302 refer page 1 - 27) and WAGO Programming cable. 2) Please check availability.
1 - 28
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A4’
Description Cat. No. Price $
EExi 1 channel digital input
EExi 2 channel digital input
EExi 2 channel digital output
EExi 1 channel analogue input 4-20 mA
EExi 1 channel analogue input RTD
EExi 1 channel analogue output 0-20 mA
EExi power supply 24 Volt fused
750-435
750-438
750-535
750-485
750-481
750-585
750-625
WAGO I/O-System – 750 Series Intrinsically Safe System for applications in Hazardous Areas
EExi Modules 1)
Notes: 1) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
WAGO-I/O-SYSTEM 750 - Now IECex approved, test certificates available
Today’s development shows that many chemical and petrochemical companies have production plants, production and process automation machines in operation, which use gas-air or dust-air mixtures which can be explosive. For this reason, the electrical components used in such plants and systems must not pose a risk of explosion resulting in injury to persons or damage to property.
The WAGO-I/O-SYSTEM 750 is designed for use in both hazardous and non-hazardous environments.
Using fieldbus technology in hazardous environments can be very time consuming and cost intensive and is only made possible in a limited way. When used in hazardous areas of Zone 2, the WAGO-I/O-SYSTEM 750 offers a safe, easy an economical connection to the sensors and actuators of Zones 0 and 1.
The EExi I/O modules were specially developed for this purpose. They build up an intrinsically safe section, which can be integrated into a standard fieldbus node, offering all the advantages of state-of-the-art fieldbus technology (e.g. fieldbus independency, flexibility, modularity, programmability, reliability, cost effectiveness).
750-485
Now IECex approved, test certificates available
1 - 29
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Cat. No. Price $
Input - [8 Digital Inputs (Cat 2)] or [4 Digital Inputs (Cat 4)]
Output - [(4 DO + 4 DI) - (Cat 2)] or [(2 DI + 2 DO) - (Cat 4)]
Power Switch - [1 DO (Cat 3)] or [1 DI + 1 DO] - (Cat 4)
Input - [4 Digital Inputs (Cat 2)] or [2 Digital Inputs (Cat 4)]
Input - [8 Digital Inputs (Cat 2)] or [4 Digital Inputs (Cat 4)]
Output -[(4 DO + 4 DI) (Cat 2)] or [(2 DI + 2 DO (Cat 4)]
WAGO I/O-System – 750 Series PROFIsafeThe WAGO-I/O-System 750 integrates modules with SAFETY
functionality into the fieldbus node in accordance with industry
standards.
Price Schedule ‘A4’
Notes: 1) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
Refer catalogue WFC2
750-660
750-665
750-666
753-661
753-662
753-667
PROFIsafe modules 1)
The advantages
The same input module allows the connection of emergency switches, protection door switches, two-handed control devices, mode selectors, as well as other hardware based safe sensors.
All inputs of a module are monitored for cross short circuits which makes it possible to combine all sensors in one single cable.
Status, configuration and diagnostics are available in every module.
An output module can operate outputs with stop category 0 or 1. The outputs are also monitored for cross short circuits.
The power switch module offers the possibility to switch off various 24 V output modules (up to safety category 3) that shall be combined in one safety area.
All safety modules are connected to the master station via the PROFIsafe protocol. The master station takes care of initialisation, setting parameters and assignments.
This allows their use in safety applications up to category 4 in accordance with EN 954-1 or SIL 3 according to base standard IEC 61508 and AK 6-(DIN V 19250).
750-660
750-665
750-666
1 - 30
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A4’
WAGO I/O-System – 750 Series
Vibration monitoringVibration monitoring and analysis is a well established and commonly used method of predictive maintenance. Motors, pumps, gear boxes, fans and many other types of rotating components of mechanical systems can fail unexpectedly and result in major production losses and expensive repairs. Many of these failures can be predicted by measuring the normal vibration levels of rotating components and watching for increases. Vibration monitoring and analysis equipment traditionally has been expensive and often separate to, or awkwardly integrated into factory control and maintenance systems. WAGO has developed a vibration monitoring system that overcomes many of the problems with existing vibration systems. The WAGO system consists of a vibration sensor that constantly measures both the mean value of the vibration severity and the “shock pulse” value. Two such sensors can be monitored by the new WAGO vibration module 750-645. The new module is fully compatible with all of the other modules in the WAGO remote I/O 750/753 series and with all WAGO standard couplers and WAGO controllers. This allows the vibration monitoring information to be transmitted back to a central control system along any of the popular fieldbus types. Limits can be set for the measured values of vibration and if these limits are exceeded then alarms can be raised and further investigation can be conducted, or if higher limits are exceeded the module can trigger a slow down, or a shut down of the equipment to protect it from damage. The module employs coloured LEDs to locally display the status of the module and to show if the alarm, or shut down limits have been exceeded. The new WAGO Vibration system thus provides another reason to choose WAGO I/O for all of your future remote I/O needs.
Ordering detailsDescription Cat. No. Price $
2-channel, Vibration velocity/Shock pulse, Bearing condition monitoring
Tandem Piezo vibration sensor for Vibration module 750-645
750-645
750-925
1 - 31
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Cat. No. Price $
Master Module
AS-interface Master Module, Specification 2.1 Compliant, Controls up to 62 AS-
interface Slaves, Gateway to other Fieldbus Systems, Compatible with “Safety at
Work”, Supports Analogue Data Transmission, Cyclic and Acyclic Communications,
Supports Extended Diagnostics, Configurable with WAGO-IO-CHECK
IP 67 I/O Modules
4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP), Standard Addressing
4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP), A/B Extended Addressing
4 Digital Outputs, 24 V DC/2A, Standard Addressing
4 Digital Outputs, 24 V DC/2A, 4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP),
Standard Addressing
3 Digital Outputs, 24 V DC/2A, 4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP),
A/B Extended Addressing
IP 20 I/O Modules
4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP), Standard Addressing
4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP), A/B Extended Addressing
4 Digital Outputs, 24 V DC/2A, Standard Addressing
4 Digital Outputs, 24 V DC/2A, 4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP),
Standard Addressing
3 Digital Outputs, 24 V DC/2A, 4 Digital Inputs, 24 V DC, 2 or 3 Wire Sensors (PNP),
A/B Extended Addressing
Power Supply
Input Voltage 100-240 V AC at 50 - 60 Hz or 140 - 300 V DC, Output Voltage
30.5 V DC at 3A, Overload ProtectionWAGO-I/O-CHECK
Configuration, start-up, and diagnostic software tool
WAGO I/O-System – 750 Series
AS-i Fieldbus System
Notes: 1) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
751-5701
IP 20 Casing
751-4001
IP 67 Casing
Price Schedule ‘A4’
For As-i safe components refer to NHP
750-655
751-3001
751-3002
751-4001
751-5201
751-5202
751-3501
751-3502
751-4501
751-5701
751-5702
787-692
759-302
AS-i Master and Slave Modules 1)
Ordering details
AS-i bus - up to 100 metres, or 300 metres with two repeaters
0800 NHP NHP nhp-nz.com1300 NHP NHP nhp.com.au
As an integrated group that spans across six key
business areas, the unique and complete NHP
package rests on a strong team of staff that pride
itself on a shared set of core company values.
Make NHP part of your business.
Think Quality Service. Think NHP.
THINK QUALITY SERVICE. THINK NHP.NHP is shaped by a team of over 850 quality staff dedicated to providing ‘what you want, when, where and how you want it’.
1 - 33
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
Price Schedule ‘A4’
WAGO I/O-SystemProgramming and diagnostic software
I/O PROWAGO-I/O-PRO 32 is a programming and visualisation tool, allowing users to develop SPS applications for the Programmable Fieldbus Controller from the WAGO-I/O-SYSTEMS 750. WAGO-I/O-PRO conforms to IEC 61131-3. This standard defines the requirements fulfilled by a programming system as well as five programming languages for PLCs. The languages IL, LD, FBD, ST and FC are supported. For every automation task, the appropriate language can be chosen.The software meets the increasing requirements of control program development, for example re-usability or modularisation.
Powerful translation of the programming languages Automatic declaration of variables Librarian / library maintenance
Furthermore, integrated test and diagnostic functions facilitate and speed up PLC working processes.
Online status indication in the program code Offline simulation Integrated visual display of internal and external markers Storage and graphic display of project variables
I/O CHECKWAGO-I/O-CHECK is a WindowsTM application for the check of inputs and outputs and the display of nodes of the WAGO-I/O-SYSTEM 750. The software is easy to handle and it is not necessary to connect the node to a fieldbus system.The software reads out the node configuration and displays it as a graphic on the screen. This graphic can be printed out along with a configuration list, together being a complete documentation.With WAGO-I/O-CHECK it is possible to display and to determine the process data of the bus modules. The field wiring including all sensors and actuators, can thus be checked before startup.The communication between WAGO-I/O-CHECK and the node is made via the communication cable (included with the delivery) which is connected to the coupler and to a serial interface of the PC.
Note: 1) Includes: manual (electronic), communications cable and installation disks. 2) The software choice depends on the hardware and firmware that is being used. Ask your NHP automation specialist for advice. WAGO indent items have a typical delivery time of 2-3 weeks.
Accessory/Spare
759-332
759-333
Description Cat. No.
WAGO I/O PRO 1) 2)
WAGO I/O PRO CAA 1) 2)
Price $
759-302WAGO I/O CHECK 1)
Description Cat. No. Price $
750-920
750-921
750-923
Programming/configuration cable from laptop/PC to Coupler/controller, D-connector
Bluetooth, serial port adaptor for linking coupler/ controller to laptop PC, Class 2
Programming/configuration cable from laptop/PC to Controller, USB-connector
Description Cat. No. Price $
1 - 34
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A4’
WAGO I/O-System – 750 Series Starter Kits 1)
Refer catalogue WFC2
ETHERNET StarterKit 1 Item No. 750-841 KITContent:
Type Description Item No.
Fieldbus controller ETHERNET TCP/IP 10/100 MBit/s 750-841+ basic components
ETHERNET StarterKit 2 Item No. 750-842 KITContent:
Type Description Item No.
Fieldbus controller ETHERNET TCP/IP 10 MBit/s 750-842+ basic components
Basic components
Type Description Item No.
Digital input module 2 DI 24 V DC 3.0 ms 750-400Digital output module 2 DO 24 V DC 0.5 A 750-501End module 750-600Power supply unit 24 V DC 1.3 A 787-602Software WAGO DLL MODBUS/TCP 759-312Programming software WAGO-I/O-PRO CAA 759-911CD-ROM Tools & Docs Documentation 0888- 0412/0001-010Programming cable 750-920
PROFIBUS StarterKit Item No. 750-833 KITContent:
Type Description Item No.
Fieldbus controller PROFIBUS DP/ V1 12 MBd 750-833Input module 2 DI 24 V DC 3.0 ms 750-400Input module 4 DI 24 V DC 3.0 ms 750-402Output module 8 DO 24 V DC 0.5 A 750-530Input module 2 AI 0 -10 V 750-478Output module 4 AO 0-10 V 750-559End module 750-600Power supply unit 24 V DC 1,3 A 787-602DEMO Programming software WAGO-I/O-PRO CAACD-ROM Documentation/GSD file 0888-0412/0001-0101
AS-Interface Expansion Kit Item No. 750-655 KIT 1)Content:
Type Description Item No.
Specialty module AS-Interface master (M3) V.2.1 750-655Power supply unit AS-Interface 30.1 V/3A 787-692AS-Interface slave IP 67 4 IN/3 OUT 24 V/2 A 751-5202AS-Interface slave IP 20 4 IN/3 OUT 24 V/2 A 751-5702Software WAGO-I/O-CHECK 759-302Bus cable 1 meter AS-Interface, yellow 2x1.5Bus cable 1 meter control cable, OB 500 2x1.0CD-ROM Documentation 0888-0412/0001-0101
IP 67 IP 20
AS-interface power
supply unit AS-interface master
Note: 1) AS interface expansion kit requires a WAGO controller and an end module. WAGO indent items have a typical delivery t ime of 2-3 weeks.
Description Cat. No. Price $
Ethernet Starter Kit 1
Ethernet Starter Kit 2
Profibus Starter Kit
ASinterface Starter Kit
750-841KIT
750-842KIT
750-833KIT
750-655KIT
1 - 35
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
WAGO I/O-System – 753 SeriesQuick connect modules
Quick release by lever
Quick connect Secure cable locationMiniature marking
Coding Elements
Signal tracing with wired conductorsDiagnosis and status shown by LED
Removeable terminalsEasy insert
Quick release by lever Quick release by lever
Quick release by screwdriver Easy module removal
Colour coded modules
Easy module removal
1 - 36
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue WFC2
WAGO I/O-System – 753 SeriesQuick connect modules 1)2)
Notes: 1) Same size as the 750 series. 2) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
753-400
BxH 1) xT (mm) 12x65x100
Digital Input modules
Description Cat. No. Price $
2 DI, DC 24 V, 3.0 ms, 2 to 4 connection, PNP
2 DI, DC 24 V, 0.2 ms, 2 to 4 connection, PNP
2 DI, DC 24 V, 3.0 ms, Prox-Sw, 2 to 4 connection, PNP
2 DI, DC 24 V, 0.2 ms, Prox-Sw, 2 to 4 connection, PNP
2 DI, DC 24 V, 3.0 ms, 2 to 3 connection, PNP, with diagnostics
2 DI, DC 24 V, 3.0 ms, PNP, with diagnostics
4 DI, DC 24 V, 3.0 ms, 2 to 3 connection, PNP
4 DI, DC 24 V, 3.0 ms, 2 connection, PNP
4 DI, DC 24 V, 0.2 ms, 2 to 3 connection, PNP
4 DI, DC 24 V, 0.2 ms, 2 connection, PNP
4 DI, DC 24 V, 2 to 3 connection, PNP, pulse extension 10 ms
4 DI, DC 24 V, 3.0 ms, 2 to 3 connection, NPN
4 DI, DC 24 V, 0.2 ms, 2 to 3 connection, NPN
8 DI, DC 24 V, 3.0 ms, 1 connection, PNP
8 DI, DC 24 V, 0.2 ms, 1 connection, PNP
4 DI, AC/DC 24 V, 2 connection
4 DI, AC/DC 24 V, 2 to 3 connection with power contacts
4 DI, AC/DC 42 V, 2 connection
2 DI, DC 48 V, 3.0 ms, 2 to 4 connection, PNP
2 DI, DC 110 V, configurable high-side or NPN
2 DI, AC 120 V, 2 to 4 connection, PNP
2 DI, AC 230 V, 2 to 4 connection, PNP
2 DI, NAMUR, Proximity switch acc. to DIN EN 50227
2 DI, DC 24 V, Intruder detection
8 DI, DC 5 to 12 V, 0,2 ms, PNP
4 DI, AC 90 to 230 V
Digital Output modules
2 DO, DC 24 V, 0.5 A, short-cct-protected, PNP
2 DO, DC 24 V, 2.0 A, short-cct-protected, PNP
2 DO, DC 24 V, 0.5 A, with diagnostics, short-cct-protected, PNP
2 DO, DC 24 V, 2.0 A, with diagnostics, short-cct-protected, PNP
4 DO, DC 24 V, 0.5 A, short-cct-protected, PNP
4 DO, DC 24 V, 0.5 A, 2 connection, short-cct-protected, PNP
4 DO, DC 24 V, 0.5 A, TYPE N, short-cct-protected, NPN
8 DO, DC 24 V, 0.5 A, short-cct-protected, PNP
2 DO, Solid State Relay, AC/DC 230 V, 300 mA
2 DO, AC 125 V, AC 0.5 A, DC 30 V, DC 1 A, isol o/pts, 2 c/o
2 DO, AC 230 V, 1 A, isolated outputs, 2 c/o contacts
2 DO, AC 230 V, DC 30 V, AC/DC 2 A, non-float, 2 make cntcts
2 DO, AC 230 V, DC 30 V, AC/DC 2 A, isol o/pts, 2 make cntcts
8 DO, DC 12 V, 1.0 A
4 DO, AC 230 V, 0.25 A
753-400
753-401
753-410
753-411
753-418
753-421
753-402
753-432
753-403
753-433
753-422
753-408
753-409
753-430
753-431
753-415
753-423
753-428
753-412
753-427
753-406
753-405
753-425
753-424
753-434
753-440
753-501
753-502
753-506
753-507
753-504
753-531
753-516
753-530
753-509
753-514
753-517
753-512
753-513
753-534
753-540
Price Schedule ‘A4’
1 - 37
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Cat. No. Price $
2-channel, 0 - 20 mA, Diff.
4-channel, 0 - 20 mA, single ended
2-channel, 0 - 20 mA, single ended
2-channel, 0 - 20 mA, single ended, 16 Bit
2-channel, 0 - 20 mA, Differential inputs
2-channel, 4 - 20 mA, Diff.
4-channel, 4 - 20 mA, single ended
2-channel, 4 - 20 mA, single ended, 16 Bit
2-channel, 4 - 20 mA, single ended
2-channel, 4 - 20 mA, Isolated differential inputs
2-channel, 0 - 1 A AC/DC, Diff.
4-channel, DC 0 - 10 V, single ended
2-channel, DC 0 - 10 V, single ended
2-channel, DC 4 - 20 mA, single ended
2-channel, AC/DC 0 - 10 V, Diff.
2-channel, DC 0 - 10 V, single ended
2-channel, DC ± 10 V, Diff.
4-channel, DC ± 10 V, single ended
2-channel, DC ± 10 V, Diff. measurement input
2-channel, DC ± 10 V, single ended
2-channel, DC 0 - 30 V, Diff. measurement input
2-channel, input module for RTDs, PT100 / RTD
2-channel, t/cpls, open-cct, K type
2-channel, 4-20 mA, HART, up to 4 variables per channel, 12 bit
Analogue Output modules
2-channel, 0 - 20 mA
2-channel, 4 - 20 mA
2-channel, DC 0 - 10 V
4-channel, DC 0 - 10 V
2-channel, DC ± 10 V
4-channel, DC ± 10 V
Speciality modules
Up/Down counter, DC 24 V, 100 kHz
2-channel Up/Down counter, DC 24 V / 16 Bit / 500 Hz
Digital impulse interface
Serial interface RS 232 C
Serial interface RS 485
KNX/TP1, KNX/EIB
System modules
Field Side connection module, DC 0 V
Field Side connection module, DC 24 V
Field Side connection module, AC/DC 0 ...230 V
Connector (required for all 753 Series modules)
Accessories
Coding element Series 753
Refer catalogue WFC2
Price Schedule ‘A4’
753-400
BxH 1)xT (mm) 12x65x100
WAGO I/O-System – 753 SeriesQuick connect modules 2)
Notes: 1) Same size as the 750 series. 2) Please check availability. The WAGO I/O range is frequently increased, and extensive technical literature is available. Contact NHP.
Analogue Input modules
753-452
753-453
753-465
753-472
753-480
753-454
753-455
753-474
753-466
753-492
753-475
753-459
753-467
753-466
753-477
753-478
753-456
753-457
753-479
753-476
753-483
753-461
753-469
753-482
753-552
753-554
753-550
753-559
753-556
753-557
753-404
753-638
753-635
753-650
753-653
753-646
753-604
753-603
753-614
753-110
753-150
1 - 38
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
I/O Systems - Dupline® field and installation
bus system
Refer catalogue CDFB-C
Fieldbus Installationbus
®
Dupline is a field- and installation-bus that offers unique solutions for a wide range of applications in building automation, water distribution, energy management, railway systems and many other areas. The system is capable of transmitting multiple digital and analogue signals over several kms, via an ordinary 2-wire cable. Its modular design and simple operating principle enable even novices to implement its use in new or existing applications. Solutions are engineered by combining products from the wide range of Dupline® modules, including digital and analogue I/O modules, PLC and PC interfaces, HMIs and Modems. All modules in an installation connect to the same 2-wire cable which is used to exchange data between modules and between a central controller and modules.
Dupline© is typically used as a remote I/O system, creating a link between field devices, such as sensors, contactors, valves, pushbuttons etc. and a central Monitoring Controller, which may be a PLC, PC or the Dupline® Controller. Dupline® can also be used as a simple wire replacement system where signals are transmitted peer-to-peer without involving a controller or other intelligent unit. The Dupline® signals can be transmitted not only on copper wire, but also on fibre optic cable, via radio modem, on leased telephone lines or via GSM Modem. Dupline® has proven its performance in more than 100,000 installations worldwide since 1986. And even though the latest ASIC technology is used today, the new Dupline® modules are still compatible with those installed 17 years ago.
Parallel wiring of traditional automation systems is often costly and complicated. Each sensor and actuator needs its own wiring, which makes the initial installation cost high. Expansion is also a problem, and even ongoing maintenance costs are high. Therefore, serial bus technology has become an increasingly important part of the concepts of electrical installations for buildings, industrial processes and public services. There are numerous advantages in using a bus system, which replaces a bundle of parallel wires with a single 2-wire cable. Easy and fast installation reduces labor cost significantly, and the possibility of expanding the system using the existing cabling makes it easy to adapt to changing needs. Bus systems also provide cost-effective access to a larger number of signals. This supports the increasing demand for automation systems to collect and use more and more data to optimise cost and performance.
Traditional Installation
Dupline Installation
What is Dupline® ?
Example:Dupline® used as wire replacement system (peer-to-peer)
2 wire cable Dupline (up to 10 km)
I/O Modules
• Digital
• Analogue
I/O Modules
• Digital
• Analogue
Channel Generator
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
1 - 39
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
I/O Systems - Dupline® field and
installation bus system
Refer catalogue CDFB-C
Fieldbus Installationbus
®
Many criteria have to be considered when selecting a fieldbus system. These include transmission distance capabilities, easy operation, noise immunity, topology and response-time. And cost-effectiveness, of course, is always a factor. Therefore, it is important to define the key application requirements in order to optimise the bus system for the specific task. The strength of the Dupline® system lies in a unique set of features that enable elegant, flexible and cost effective solutions for a wide range of applications.Most of these features originate from the effective time-division multiplex technology used. The efficiency of the protocol allows a low carrier frequency of 1 kHz, providing long transmission distance and superior noise immunity. Hence, Dupline® is capable of transmitting multiple digital and analogue signals over distances up to 10 Km, via a non-shielded, non-twisted 2-wire cable, without using repeaters. These unique Dupline® features provide considerable cost savings in many installations, especially when existing ordinary cables are available for use. Another important Dupline® characteristic is easy handling in all project phases. It does not take an engineering degree to work with Dupline®. No PC is required, since the coding of addresses and testing is carried out by means of simple handheld devices. There is no need for special cables and terminations, and there are no cable
routing restrictions as with many other Fieldbuses. It is so simple and easy to implement, that many customers do their own installation, troubleshooting and maintenance, thus eliminating the need for costly service and installation contracts.Dupline® is system independent and open for interfacing with basically any kind of controller.Serial interfaces with Modbus and dedicated PLC protocols, together with gateways for Profibus-DP and DeviceNet™, enable easy and flexible interfacing to PLCs, PCs and dedicated controllers.
Dupline® features at a glance
Up to 10 km transmission distance without repeaters
Easy handling
Extremely noise immune
Unrestricted topology
Flexible
No special cable requirements
Existing cable can be used
Bus-powered devices available
Flexible interfacing to PLCs and PCs
Transmission via GSM modem, radio modem or fibre optics possible
Proven performance in more than 150,000 installations
Cost-effective
Example:Dupline® used as Remote I/O for PLC
RS 485 / RS 232
Modbus Profibus-DP
DeviceNet
Dupline® # 1
I/O Modules
• Digital
• Analogue
• Counters
Dupline® # 2
I/O Modules
• Digital
• Analogue
• Counters
Interface
Interface
Why use Dupline® ?
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
1 - 40
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
G50101106
Bus-Powered
single input module
INPUT MODULES
DISPL
AY MODULE
S
G34296470
Analogue inputs
G88104401
Self-powered
light switch
input module
G4420740
Counter module
G34205501
Digital inputs
GAP1605
Handheld
coding unit
ADDRESSCONFIGURATION
VT565W
Touch screen 1)
VT50
Text Display 1)
G54606606
LED status
indicator
G82452574
Temp. display
I/O Systems - Dupline® field and installation
bus system
Refer catalogue CDFB-C
Product categories
The wide range of Dupline® products for industrial applications and building automation can be divided into different categories depending on the function they perform on the network.By combining products from the various categories, complete solutions can be engineered for a multitude of different applications.
Central units
Being the heart of the system, the Dupline® Central Unit produces the carrier signal allowing all the other modules on the network to communicate with each other. There is always one, and only one, central unit in a Dupline® network. Some central units have built-in control and/or interfacing functions.
Digital and Analogue input modules
These modules are used to collect the digital and analogue signals in the field for transmission via Dupline®. They connect to contacts, voltages and analogue signal sources with DIN-norm outputs like 4-20 mA. A Counter module for counting pulses from energy meters is also available.
Digital and Analogue output modules
These modules are used to output signals transmitted on Dupline® to field devices. The digital types are available with relay or transistor outputs and the analogue types have DIN-norm outputs like 4-20 mA. They typically connect to contactors, lamps, instruments, drives etc.
Sensors
Dupline® sensors are self-powered devices that detect or measure physical states directly. The digital types can detect presence of people, magnet proximity, metal proximity or water leakage, while the analogue types measure temperature or light intensity.
Interface products
In many applications, the Dupline® signals need to be controlled and monitored from a central PLC or PC. To accommodate easy and flexible interfacing there are a number of products available for interfacing via serial ports (RS 232 or RS 485) or via standard Fieldbus connections (Profibus-DP and DeviceNet™).
Modems and converters
Sometimes it is necessary to convert the Dupline® signal for transmission on media other than copper wire. Via modems and converters Dupline® can be transmitted on telephone cables, wireless via radio modems, on optical fibre or via GSM modem. The transmission distance on copper wire can be extended by using the Dupline repeater.
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
1 - 41
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Optional Direct Interface to
PLCs and PCs via
• Modbus (RS 232, RS 485)
• Dedicated PLC protocols
• Profibus-DP
• DeviceNet
OUTPUT M
ODULESG88301143
Bus-powered
single relay
output
G34404443
Digital
inputs/outputs
G34485324
Light dimmer
G34396470
Analogue outputs
G38000015
Central unit and interface G34305545
Digital outputs
G34930000
Optical converter
G34910040
Private line modem
MODEMS ANDCONVERTERS
TEST UNIT
D38920000
Repeater
GTU8
Handheld
Bus-powered
test unit
I/O Systems - Dupline® field and
installation bus system
Refer catalogue CDFB-C
Display and HMIs
The products in this category are used to perform the interface between the users and the Dupline® network. The status of digital and analogue signals can be read out on Text Displays, Panel Meters, Touchscreens or LED indicators and control of signals is also possible.
Coding and Testing tools
No PC or other advanced tool is required for address coding of Dupline® modules or for testing an installation. Instead, these tasks are performed by means of two simple handheld devices that are intuitive in use.
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
Notes: 1) GTI50 adaptor required.
1 - 42
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A7’
I/O Systems - Dupline® field and installation
bus system – Components
Refer catalogue CDFB-C
Channel Generators
G3490
G3800
G3496
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
24 V AC P.S.
115 V AC P.S.
230 V AC P.S.
15-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
115-230 V AC P.S.
10-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
20-30 V DC P.S.
Standard Channel Generator, up to 128 channels -
selectable
Ch.G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 x RS 232 ports
Ch.G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 x RS 232 ports, with internal GSM modem. (Antenna &
SIM card required)
Ch.G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 x RS 232 ports, with 1 RS 485 port
Ch.G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 x RS 232 ports, with internal GSM modem & 1 RS 485
port. (Antenna & SIM card required)
Ch. G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 RS 232 ports, 1 RS 485 port, Data Logging
Ch. G. Controller, 4 DI 6-30 V DC, 4 DO PNP <35 V DC,
2 RS 232 ports, 1 RS 485 port, Data Logging, GSM modem,
(Antenna and sim card required)
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Optolink PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for LG PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for G.E.-Fanuc PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Mitsubishi FX PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Omron PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Modbus
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Allen-Bradley PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Schneider PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Koyo PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Matsushita PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Siemens PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for Toshiba PLCs
Ch.G., Plug and Play RS 232/RS 485 interface, inbuilt
protocols for IDEC PLCs
Description Cat. No. Price $
G34900000024
G34900000115
G34900000230
G34900000824
G38000015230
G38000015800
G38001015230
G38001015800
G38000016230
G38000016800
G38001016230
G38001016800
G38000036230
G38000036800
G38001036230
G38001036800
G34960000700
G34960001700
G34960002700
G34960003700
G34960004700
G34960005700
G34960006700
G34960007700
G34960008700
G34960009700
G34960010700
G34960011700
G34960012700
1 - 43
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
G3891
G3890
G3420
G5010 1106
G4420 7401
G8910 2217
I/O Systems - Dupline® field and
installation bus system – Components
Refer catalogue CDFB-C
Price Schedule ‘A7’
G6110 1145G8910 1101 G8810 4401 G8910 1127 G8910 2116
G8810 1102
G2110 4401
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
Description Cat. No. Price $
Ch. G. Profibus DP slave gateway, 12 Mbaud, 128 I/O, 115-230 V AC P.S.
PNO certified
Ch. G. Profibus DP slave gateway, 12 Mbaud, 128 I/O, 115-230 V AC P.S.
PNO certified, analogue output multiplex
Ch. G. DeviceNet slave gateway, 500 kBaud, 128 I/O 115-230 V AC P.S.
Ch. G. Lonworks gateway, 78 kbps, 128 I/O 115-230 V AC P.S.
Ch. G. Modbus TCP slave gateway, 10/100 Mbit, 128 I/O 115-230 V AC P.S.
Profibus DP slave gateway, 12 Mbaud, 128 I/O, PNO certified 115-230 V AC P.S.
Ch.G., 112 Analink signals, Real time Clock, 1 DO NPN < 35 115-230 V AC P.S.
V DC, Liquid Crystal Display, Printer port, Modbus port 20-30 V DC P.S.
Digital Inputs8 DI, Optoisolated, Contact or NPN 24 V AC P.S.
115 V AC P.S.
230 V AC P.S.
10-30 V AC P.S.
8 DI, Optoisolated, 6-265 V DC/V AC 24 V AC P.S.
115 V AC P.S.
230 V AC P.S.
10-30 V AC P.S.
8 DI, Volt-free Contacts Dupline P.S.
1 DI, Contact, Powered through the network Dupline P.S.
2 DI, Volt-free Contacts Dupline P.S.
4 DI, Counter <14 kHz, non-volatile memory 230 V AC P.S.
15-30 V DC P.S.
1 DI, Inductive proximity switch, M18, cable Dupline P.S.
1 DI, Inductive proximity switch, M18, plug Dupline P.S.
1 DI, Magnetic proximity switch, 11 mm housing Dupline P.S.
1 DI, Magnetic proximity switch, M14 thread Dupline P.S.
4 DI, Universal switch interface Dupline P.S.
Passive Infra-red movement detector Dupline P.S.
2 DI, Water level sensor Dupline P.S.
2 DI, Smoke detector Dupline P.S.
1 DI, 90-265 V AC, for external PIR sensor Dupline P.S.
4 DI, Contact/NPN, Alarm inputs Dupline P.S.
8 DI, Contacts, or NPN, designed for elevator control 10-30 V DC P.S.
8 DI, Voltage, or PNP, designed for elevator control 10-30 V DC P.S.
Channel Generators/Gateways
G38910020230
G38910021230
G38910050230
G38910051230
G38910052230
G38910120230
G38900014230
G38900014800
G34205501024
G34205501115
G34205501230
G34205501800
G34205502024
G34205502115
G34205502230
G34205502800
G34105501
G50101106
G50102206
G44207401230
G44207401724
G61101145
G61101145-1
G89101101
G89101101-G
G88104401
G89101127
G89102116
G89102217
G88101102
G21104401700
G21205501700
G21205502700
1 - 44
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A4’
I/O Systems - Dupline® field and installation
bus system – Components
Refer catalogue CDFB-C
Digital Outputs
G3430 / G3830
G3430 5545
G3430 4249
G8830 1143
G4248 4134
G3448 5234
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
Description Cat. No. Price $
1 DO, 5 A, SPDT 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 10-30 V DC P.S.2 DO, 5 A, SPDT 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 15-30 V DC P.S.4 DO, 5 A, SPST 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 15-30 V DC P.S.4 DO, Relay 16 A, SPST 24 V AC P.S. 115 V AC P.S. 230 V AC P.S.8 DO, 5 A, SPST 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 15-30 V DC P.S.8 DO, 0.7 A, NPN 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 10-30 V DC P.S.8 DO, 0.7 A, PNP 24 V AC P.S. 115 V AC P.S. 230 V AC P.S. 10-30 V DC P.S.8 DO, 16 A/250 V AC, SPST 24 V AC P.S. 115 V AC P.S. 230 V AC P.S.4 DO, 5 A/250 V AC, with interlocking relay 24 V AC P.S.for control of two roller blind motors 115 V AC P.S. 230 V AC P.S. 15-30 V DC P.S.1 DO, 13 A/250 V AC, SPST Dupline P.S.8 DO, 0.1 A, PNP, designed for elevator control 10-30 V DC P.S.8 DO, 0.1 A, PNP, designed for elevator control 10-30 V DC P.S.
Dimmer modules1 Channel, 20-600 Watt, 230 V AC, 6 scenarios/ Dupline P.S., orchoices, -ve, or +ve phase angle dimming 18-30 V DC P.S.1 Channel, 500 Watt, 230 V AC, 4 scenarios/ 230 V AC P.S.choices, -ve, or +ve phase angle dimming 2 Channel, 230 Watt, 230 V AC, 4 scenarios/choices 230 V AC P.S.2 Channel, 1-10 V for adjustable ballasts4 Lighting scenarios per channel
G34301149024
G34301149115
G34301149230
G34301149800
G34302249024
G34302249115
G34302249230
G34302249824
G34304443024
G34304443115
G34304443230
G34304443824
G34304445024
G34304445115
G34304445230
G38305543024
G38305543115
G38305543230
G38305543824
G34305511024
G34305511115
G34305511230
G34305511800
G34305521024
G34305521115
G34305521230
G34305521800
G34305545024
G34305545115
G34305545230
G34304249024
G34304249115
G34304249230
G34304249824
G88301143
G21305521700
G21305511700
G42484134724
G34485134230
G34485234230
G34485238230
1 - 45
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue CDFB-C
Price Schedule ‘A7’
Fieldbus Installationbus
®
I/O Systems - Dupline® field and
installation bus system – Components
Irrigation control with Dupline®
By running the power, valve control signals and pulses from flow meters on a single two-wire cable, Dupline reduces the wiring and cable cost significantly and makes expansion easy. Any type of irrigation controller, whether it is a PLC, PC or dedicated controller, can use Dupline as a remote I/O system.In order to achieve sufficient voltage level to switch the 3-wire latching valves in the field, a Booster module converts the Dupline voltage level to 28 V DC. Each valve is connected to an I/O-module with two outputs for opening and closing the valve, and with 2 inputs that can be used for transmission of pulses from flow meters. The module is available in a housing that allows underground installation, and in a DIN-rail mount housing. Each time the valve is fired, a built-in capacitor slowly charges up and after 10s it stores enough energy for the next valve operation. The wiring topology is unrestricted with no limitation in number and length of branches. One Hi-Line network can handle up to 64 valves over distances up to 7 km, and several networks can be linked together.
Digital Mixed I/O
G3440 4443
GH3440 4412
GH6440 4412
G8210
G8510
G8110
Up to 7 Kilometres!
PLC (optional) Channel
generator Valve module
Hi-Line
converter
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Description Cat. No. Price $
2 DI, 2 DO, Combined I/O module, 2 x 6-265 V AC/DC 24 V AC P.S.optoisolated inputs and 2 SPST relay outputs 115 V AC P.S. 230 V AC P.S. 15-30 V DC P.S.2 outputs for control of 3 wire 12 V DC latching valve Highline P.S.and 2 contact inputs GH348500002 outputs for control of 3 wire 12 V DC latching valve Highline P.S.and 2 contact inputs GH348500004 DI light switch with 4 DO LED indicators, grey Dupline P.S.4 DI light switch with 4 DO LED indicators, grey Dupline P.S.4 DI light switch with 4 DO LED indicators, white Dupline P.S.1 light switch with 1 LED indicator Dupline P.S.2 light switches with 2 LED indicators Dupline P.S.3 light switches with 3 LED indicators Dupline P.S.4 wireless light switches, 4 LED indicators, OPUS, white CR2023 Battery4 wireless light switches, 4 LED indicators, FUGA, white CR2023 Battery4 DI, Volt-free Contact, 4 DO, 1.5 mA, PNP, for light switches Dupline P.S.2 DI, Volt-free Contact, 2 DO, 200 mA, PNP, for elevators 10-30 V DC P.S.2 DI, Volt-free Contact, 2 DO, 200 mA, NPN, for elevators 10-30 V DC P.S.4 DI, Volt-free Contact, 4 DO, 200 mA, PNP, for elevators 10-30 V DC P.S.4 DI, Volt-free Contact, 4 DO, 200 mA, NPN, for elevators 10-30 V DC P.S.Room temperature controller, LC display, OPUS, white Dupline P.S.Room temperature controller, LC display, FUGA, white Dupline P.S.
G34404443024
G34404443115
G34404443230
G34404443824
GH34404412
GH64404412
G81104406
G81104407
G82104406
G85101101
G85102201
G85103301
G82864406703
G81864407703
G88405521
G21404422700
G21404421700
G21405520700
G21405510700
G82452574
G81452574
1 - 46
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Description Cat. No. Price $
4 AI, isolated, 0 - 20 mA, 4-20 mA, 0-10 V DC, 24 V AC P.S.
configurable, Analink, Multiplexed BCD, 8-bit selectable 115 V AC P.S.
230 V AC P.S.
10-30 V DC P.S.
1 AI, 4-20 mA, Analink 8-bit protocol Dupline P.S.
1 AI, PT100 RTD, 3-wire input, -50 °C to +40 °C Dupline P.S.
1 AI, PT100 RTD, 3-wire input, +30 °C to +120 °C Dupline P.S.
1 AI, PT100 RTD, 3-wire input, -10 °C to +100 °C Dupline P.S.
1 AI, Built in PT1000, +10 °C to +35 °C Dupline P.S.2 AI, built in Temperature and Humidity sensors, Dupline P.S.0 °C to 50 °C, 5 to 95 % RH
1 AI, Light intensity sensor, 0.1 to 100,000 lux Dupline P.S.
1 AI, Temperature sensor, indoor, -30 °C to +60 °C Dupline P.S.
1 AI, Temperature sensor, IP 67, -30 °C to +60 °C Dupline P.S.
1 AO, 0-10 V DC, 8 bit resolution 230 V AC P.S.
4 AO, isolated, 0-20 mA, 4 - 20 mA, 0-10 V DC, 24 V AC P.S.
configurable, Analink, Multiplexed BCD, 8-bit selectable 115 V AC P.S.
230 V AC P.S.
10-30 V DC P.S.
Thermostat, with built-in temp. sensor, -20 °C to +70 °C Dupline P.S.
ConvertersLandline modem, Digital 8-bit analogue, 24 V AC P.S.
non-multiplexed 3 1/2 digit BCD 115 V AC P.S.
230 V AC P.S.
Optical to Electrical, converting optical to Dupline 230 V AC P.S.
Electrical to Optical, converting Dupline to optical 230 V AC P.S.
Dupline to Highline converter, 28 V DC irrigation 20-30 V DC
Dupline to signal repeater for signals beyond 10 km 24 V AC P.S.
Dupline to signal repeater for signals beyond 10 km 115 V AC P.S.
Dupline to signal repeater for signals beyond 10 km 230 V AC P.S.
Dupline to Wireless signals @ 868MHz, up to 100 meters 230 V AC P.S.
Interface between ESA Text and Touch screens and Powered by
Dupline channel generators with Modbus RS 485 ports RS 485 port
Interface between Carlo Gavazzi EM4 and WM22 energy Dupline P.S.
meters and Dupline
Optolink interface, Reads up to 63 Dupline systems 24 V AC P.S.
networked through optolinks (G34910000). 115 V AC P.S.
Operates with G34910090. 230 V AC P.S.
Optolink interface, Links a PC, or a PLC that has an 24 V AC P.S.
RS 232 serial port with a fibre optic Lan-ring. 115 V AC P.S.
Operates with G34910000 230 V AC P.S.
Ethernet to RS 232 converter, 1 port, 10/100, TCP/IP 12 - 48 V DC
Ethernet to RS 232 converter, 2 port, 10/100, TCP/IP 12 - 48 V DC
Price Schedule ‘A7’
Refer catalogue CDFB-C
Fieldbus Installationbus
®
G3210 1111
I/O Systems - Dupline® field and
installation bus system – Components
Analogue modules
G3429 6470
G3210 1161
G4311 1120
G8611 1010
G8911 1010
G3439 6470
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
G34910040024
G34910040115
G34910040230
G34920000230
G34930000230
GH34850000724
D38920000024
D38920000115
D38920000230
G34860058230
GTI50
G63910240
G34910000024
G34910000115
G34910000230
G34910090024
G34910090115
G34910090230
ETHCONV2
ETHCONV3
G34296470024
G34296470115
G34296470230
G34296470800
G32101161
G32101111
G32101112
G32101113
G81112211
G81113315
G43111120
G86111010
G89111010
G32385138230
G34396470024
G34396470115
G34396470230
G34396470800
G81103394
1 - 47
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
I/O Systems - Dupline® field and
installation bus system – Components
Refer catalogue CDFB-C
Price Schedule ‘A7’
Displays / HMI
GTU8
D6369 6475
G5460 6606
G4185 5530DUPDATACC
GAP1605
NOT APPROVED FOR SIL3 SAFETY APPLICATIONS
Fieldbus Installationbus
®
ADAPT1605DT01
G4085 5562
Description Cat. No. Price $
LED, 4 x 7 segment BCD digits for display of 8-bit analogue 24 V AC P.S.values, with 4 digital outputs 230 V AC P.S.16 channel LED status indicator, panel mounting 24 V AC P.S. 115 V AC P.S. 230 V AC P.S.Note: Many types of ESA text and touch screens are compatible with Dupline using the Dupline GTI50 interface.
Remote controls
Infra-red remote control hand-held transmitter for 9 Volt batterycontrol of lighting, dimming, roller blinds etc... Must be paired with G4185 5531 Infra-Red remote receiver, wall mounted. Dupline P.S.Must be paired with G4085 5562
Programming / testing
Coding device for assigning addresses to Dupline I/O 9 V DC batterymodules and sensorsTest unit for monitoring and control of Dupline channels. 9 V DC batteryNot to be used for Hi-Line installions. Test unit for monitoring and control of Hi-Line channels. 9 V DC batteryNot to be used for Dupline installations. Coding adaptor between GAP1605 and Dupline modules without a standard connection. Includes an M12 plug for modules like G89111010. Accessories
Power supply, Boosts power to some Dupline modules 15 - 30 V DC P.S. through a third wire DC-bus. Up to 4 ampere @ 25 °CGSM antenna, 900 MHz for G3800xxxx Ch. generators Synchronizer for analogue modules, max of 112 signals Dupline P.S.Cable termination unit for standard Dupline Cable termination unit for Hi-line
Software
Software, DDE and ActiveX drivers for G3800 series channel generators and interfaces. Copies and pastes dynamic Dupline links into Excel spreadsheets.Software, Dupline-Online One License for data logging, visualization and alarm handling for G3800xx36 series channel generatorsSoftware, ADD-License to Dupline-Online for data logging, visualization and alarm handling for G3800xx36 series channel generators
D63696475024
D63696475230
G54606606024
G54606606115
G54606606230
G40855562
G41855531
GAP1605
GTU8
GHTU8
ADAPT1605
G34850000
ANT1
D32124000
DT01
DT02
DUPDATACC
DUPSERVSW
DUPSERVADD
1 - 48
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Operator panels and touch screens
SC207
Allen-Bradley (ETH), MicroLogix, DF1 Delta DVP Hitachi Mitsubishi A-Fx-Fx2 Modbus RTU Master and Slave Modbus TCP Master and Slave (ETH)
Omron Host Link, CJ1-CS1-CP1, CS1-CJ1 (ETH) Panasonic FP-Sigma series (RS 232),
FP series (ETH) Schneider Twido-Zelio-Unitelway, Premium
(ETH) Siemens S5, S7-200 PPI, S7 300/400 (ETH),
7” Wide 65.536 colors tft 800 X 480 resolution White LED backlighting RS232/RS485 (Integrated MPI) Ethernet USB host and sevice SD/MMC Slot
Features
SC207 Drivers available
Display SC207
Technology 7” LCD Graphic TFT 65.536 colours
Touch screen Analogue
Backlighting White LED
Minimum lamp life at 25° C
50,000 hours
Resolution 800 x 480 pixel
Terminal
Processor Intel PXA 270
CPU Clock 520 MHz
RAM 64 MB
Flash 32 MB
Interfaces
Serial port SP1 (RS232/485/MPI)
USB Host port 1 x v 1.1
USB Device port 1 x v 1.1
Card Bus Slot Secure Digital/MMC
Network Ethernet 10/100 Mbit - RJ45
Dimensions
External (W x H x D) (mm)
202 x 142 x 40
Bore holes (W x H) (mm)
194 x 134
Technical specifications
Chassis Plastic ABS
Power supply 18...32 Vcc
Power consumption ~ 8 W (24 V DC)
Hardware clock Supercapacitor 72h
Working temperature 0...+50 °C
Storage/transport temperature
-20...+60 °C
Humidity 85% (non-condensing)
Weight ~ 1,6 Kg
Protection level IP 65 front
Certification CE
Description Cat. No.
7" widescreen 65k colours TFT, Port: SP1, Ethernet, USB:Host device, SD/MMC slot
SC207A0101
1 - 49
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Operator panels and touch screens
- System Overview
Dual serial ports allow simultaneous communications to different front-end devices, while pipelining expands the functionality of the panel into a gateway by providing bi-directional data transfer between disparate devices. Alarms, reports and mimic pages can be sent directly to a parallel printer by panels fitted with an on-board centronics port.
Fast and easy configuration Extensive product range Large displays - up to 12.1” IP 65 protection lever (front)
Serial and network communications
ESANet
ESANet is a high-speed network that allows both the text and graphical panels to communicate and share data with each other. Up to 32 ESA panels can be configured in a client server archi tecture. Server panels connect to I/O devices such as a PLC, while clients use variables and memory areas exported by the server. Using one of the standard serial ports on each panel, units can be linked together to provide remote monitoring and control from all areas of the factory or process.
Communication drivers
The VT range of panels will directly communicate with an extensive range of I/O devices including PLCs and drives. Standard interfaces include: ABB, Allen Bradley, Crouzet, GE-Fanuc, Hitachi, Idec, Izumi, Keyence, Klockner Moeller, LG, Matsushita / NAIS, NHP Microlink, Mitsubishi, Modicon, Omron, SAIA, Siemens, Sprecher + Schuh, Telemecanique, Toshiba.
PC (programming)
MSP
ASP
CONTROL NETWORK
ESANET (32 UNITS – Available on all the panels)
LPT
PC (programming)
Drives
ASP RS 232/RS 485
LPT
VT 170 W / VT 190 W / VT 300 W
VT 310 W / VT 320 W / VT 330 W
VT 555 W / VT 565 W / VT 575 W
VT 585 W / VT 595 W
PLCs
MSP RS 232
RS 422/485/TTY
Printer
(not VT 170 W)
1 - 50
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer publications VT50, VT170
Notes: 1) Multi serial port (25 pin). 2) Auxiliary serial port (15 pin). 3) XCSF85C power supplies are on Price Schedule ‘A2’. 4) NETT price only.
Operator panels and touch screensText based operator panels
The ESA range of text and graphic operator panels comprises three groups of models – text panels, graphical touch panels and graphical touch screens. Each model, with its own array of features, is targeted towards specific applications and user requirements.
Flexible serial and network connectivity
One software package for all models
Robust die-cast construction
Full range of interface drivers
Fast and easy configuration
Extensive product range
Large displays - up to 12.1”
IP 65 protection level (front)
Text operator panelsThe compact range of text only displays is ideal for machine control in small to medium sized applications. With bright LCD back-lit displays available in either a 2 x 20 character or 4 x 20 character configuration and an optional printer port, these text displays offer extreme flexibility at a cost price.
Thanks to the availability of a large number of serial protocols, these terminals can be connected to PLCs, variable speed drives, thermoregulators and other serial devices.
Text operator panels (dimensions in mm)
Ordering details
RVT5009
VTBUTTONCELL
PCNET
VT5ESABUS
VTPROFI/DP
XCSP85C
VTWINLITE
Accessories
Mounting brackets and screws, rubber gasket, phoenix connector
(VT 050, VT 060)
Lithium 3 V battery back-up recipe and clock
External gateway to connect a PC (SCADA, MS Excel, MS Access,
Internet Explorer, etc.) to any PLC or ESA operator panel
RS 485 module to connect the terminal in an ESANET Network
(to use the VT 170 WA / VT 190 WA in a server configuration)
External module PROFIBUS / DP
External 24 V DC 3.5 A Power supply 3)
Programme CD software and cable 4)
VT 170WA
VT 190W A
VT050
VT060
VT150W
VT150W DP
VT160W
VT160W DP
VT170W A
VT190W A
VT190W AP
Cat. No.Description
Text, LCD, 2 x 20, Dim. 166 x 86 x 41, MSP 1)
Text, LCD, 4 x 20, Dim. 166 x 86 x 41, MSP 1)
Text, LCD, 4 x 20, Dim. 148 x 188 x 41, MSP 1)
Text, LCD, 4 x 20, Dim. 148 x 188 x 41, MSP 1), PROFIBUS DP
Text, LCD, 4 x 20, Dim. 296 x 188 x 42, MSP 1)
Text, LCD, 4 x 20, Dim. 296 x 188 x 42, MSP 1), PROFIBUS DP
Text, LCD, 4 x 20, Dim. 126 x 196 x 60, MSP 1), ASP 2)
Text, LCD, 4 x 40, Dim. 252 x 196 x 60, MSP 1), ASP 2)
Text, LCD, 4 x 40, Dim. 252 x 196 x 60, MSP 1), ASP 2), LPT
Price $
VT 050
Price Schedule ‘A4’
1 - 51
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer publications VT32-F Operator panels and touch screens
Graphics operator panels
This range of graphic based touch panels is ideal for replacing pushbuttons, indicating lights, analogue meters and much more. Starting at the compact 5” display the units are available in colour or monochrome, STN or TFT graphics. Dual serial ports, optional printer port, trending, recipe management and lifelike graphics make these units ideal for any size applications.Easy to configure and simple to use. Thanks to the availability of a large number of serial protocols, these terminals can be connected to PLCs, variable speed drives, thermoregulators and other serial devices.
Ordering details Graphic operator panels (dimensions in mm)
VT 310W A
VT 320W A
VT 330W APM
VTBUTTONCELL
PCNET
VTPROFI/DP
XCSP85C
VTWINLITE
Accessories
Lithium 3 V battery back-up recipe and clock
External gateway to connect a PC (SCADA, MS Excel, MS Access,
Internet Explorer, etc.) to any PLC or ESA operator panel
External module PROFIBUS / DP
External 24 V DC, 3.5 A Power supply 3)
Programme CD software and cable 4)
Cat. No. Price $
Price Schedule ‘A4’
Notes: 1) Multi serial port (25 pin). 2) Auxiliary serial port (15 pin). 3) XCSF85C power supplies are on Price Schedule ‘A2’. 4) NETT price only.
VT300W A
VT300W AP
VT310W A
VT310W AP
VT320W A
VT320W AP
VT330W APM
VT330W APT
Cat. No.
Graphic, Monochrome STN, Res 240 x 64,
Dim. 252 x 196 x 60, MSP 1), ASP 2)
Graphic, Monochrome STN, Res 240 x 64,
Dim. 252 x 196 x 60, MSP 1), ASP 2), LPT
Graphic 5.5” screen, Monochrome STN, Res 240 x 128,
Dim. 252 x 196 x 60, MSP 1), ASP 2)
Graphic 5.5” screen, Monochrome STN, Res 240 x 128,
Dim. 252 x 196 x 60, MSP 1), ASP 2), LPT
Graphic 5.7” screen, Colour STN, Res 320 x 240,
Dim. 305 x 196 x 60, MSP 1), ASP 2)
Graphic 5.7” screen, Colour STN, Res 320 x 240,
Dim 305 x 196 x 60, MSP 1), ASP 2), LPT
Graphic 10.4” screen, Monochrome STN, Res 640 x 480,
Dim 435 x 260 x 74, MSP 1), ASP 2), LPT
Graphic 10.4” screen, Colour TFT, Res 640 x 480,
Dim 435 x 260 x 74, MSP 1), ASP 2), LPT
Description Price $
1 - 52
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
VT 555W
This range of graphic based touch screens is ideal for replacing pushbuttons, indicating lights, analogue meters and much more. With a large display of up to 10.4”, the units are available in colour or monochrome, STN or TFT graphics. Dual serial ports, optional printer port, trending, recipe management and lifelike graphics make these units ideal for any size applications.Easy to configure and simple to use. Thanks to the availability of a large number of serial protocols, these terminals can be connected to PLCs, variable speed drives, thermoregulators and other serial devices.
Ordering details Graphic touch screens (dimensions in mm)
VT 505W
VT 155W
VT 505H
Operator panels and touch screensGraphics touch screens
VT 525W
VT 515W
Price Schedule ‘A4’
Refer publications VT155-F, VT525-F,
VT555-F
Notes: 1) Multi Serial Port (25 pin). 2) Auxiliary Serial Port (8 pin). 3) Auxiliary Serial Port (15 pin).
VT 185W
Graphic 4" screen, 4 Tones of grey LCD, Res 240 x 128, Dim 166 x 100 x 40, MSP 1), ASP-8 2), Project: 640 KB - Recipes: 16 KBGraphic 4" screen, 4 Tones of grey LCD, Res 240 x 128, Dim 166 x 100 x 40, ASP-8 2), Project: 640 KB - Recipes: 16 KB, Profibus DPGraphic 4" screen, 4 Tones of grey LCD, Res 240 x 128, Dim 166 x 100 x 40, ASP-8 2), Project: 640 KB - Recipes: 16 KB, Ethernet 10/100Graphic 3.6" screen, 16 Colour TFT, Res 320 x 240, Dim 166 x 100 x 40, MSP 1), ASP-8 2), Project: 960 KB - Recipes: 32 KBGraphic 3.6" screen, 16 Colour TFT, Res 320 x 240, Dim 166 x 100 x 40, ASP-8 2), Project: 960 KB - Recipes: 32 KB, Ethernet 10/100Graphic 5.5" screen, Monochrome STN, Res 240 x 128, Dim 210 x 158 x 54, MSP 1), ASP 3), 512 KB - Recipes: 128 KB, Ethernet 10/100Graphic 5.5" screen, Monochrome STN, Res 240 x 128, Dim 210 x 158 x 54, MSP 1), ASP 3), LPT, 512 KB - Recipes: 128 KBGraphic 5.5" screen, Monochrome STN, Res 240 x 128, Dim 210 x 158 x 54, MSP 1), LPT, 512 KB - Recipes: 128 KB, Profibus DPGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, MSP 1), Project: 640 KB - Recipes: 16 KBGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, MSP 1), Project: 640 KB - Recipes: 16 KB, Profibus DPGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, ASP-8 2), Project: 640 KB - Recipes: 16 KB, Ethernet 10/100Hand held Graphic 5.7" screen, 4 level blue STN, Res 320 x 240, 10 function keys, 2 push buttons, optional MSP 1) if VTHCB adaptor fitted, Project: 640 KB - Recipes: 16 KBGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, MSP 1), Project: 640 KB - Recipes: 16 KB, 8 KB Memory Alarms, capacitor back-upGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, MSP 1), Project: 640 KB - Recipes: 16 KB, 8 KB Memory Alarms, Capacitor back-up, Profibus DPGraphic 5.7" screen, 4 level blue STN, Res 320 x 240, Dim 210 x 158 x 54, ASP-8 2), Project: 640 KB - Recipes: 16 KB, 8 KB Memory Alarms, Capacitor back-up, Ethernet 10/100Graphic 5.7" screen, 16 Colour STN, Res 320 x 240, Dim 210 x 158 x 54, MSP 1), ASP-8 2), Project: 960 KB - Recipes: 32 KBGraphic 5.7" screen, 16 Colour STN, Res 320 x 240, Dim 210 x 158 x 54, ASP-8 2), Project: 960 KB - Recipes: 32 KB, Profibus DPGraphic 5.7" screen, 16 Colour STN, Res 320 x 240, Dim 210 x 158 x 54, ASP-8 2), Project: 960 KB - Recipes: 32 KB, Ethernet 10/100Hand held Graphic 5.7" screen, 16 Colour STN, Res 320 x 240, 10 function keys, 2 push buttons, optional MSP 1) and ASP-8 2) if VTHCB fitted, Project: 960 KB - Recipes: 32 KB
VT155W
VT155W 000DP
VT155W 000ET
VT185W
VT185W 000ET
VT555W A
VT555W AP
VT555W AP0DP
VT505W
VT505W DP
VT505W 000ET
VT505H
VT515W
VT515W 000DP
VT515W 000ET
VT525W
VT525W 000DP
VT525W 000ET
VT525H
Cat. No.Description Price $
1 - 53
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer publications VT575-F, VT595-F,
VT 560W
VT 565W
VT 575W
VT 580W
VT 585W
VT 595W
Ordering details Graphic touch screens (dimensions in mm)
Operator panels and touch screens
Graphics touch screens
VT560W A
VT560W A0M
VT565W A
VT565W AP
VT565W A0M
VT565W APM
VT580W APT
VT580W 0PTDP
VT580W 0PTET
VT585W BPT
VT585W BPTDP
VT585W BPTET
VT595W APT
VT595W 0PTDP
VT595W 0PTET
Cat. No.
Graphic 5.7" screen, 16 Colours STN, Res 320 x 240, Dim 210 x 158 x 61,
MSP 1), ASP 2), Project: 1 MB - Recipes: 128 KB, Battery back-up
Graphic 5.7" screen, 8 tones of blue STN, Res 320 x 240, Dim 210 x 158 x 61,
MSP 1), ASP 2), Project: 1 MB - Recipes: 128 KB, Battery back-up
Graphic 5.7" screen, Colour STN, Res 320 x 240,
Dim 210 x 158 x 54, MSP 1), ASP 2)
Graphic 5.7" screen, Colour STN, Res 320 x 240,
Dim 210 x 158 x 54, MSP 1), ASP 2), LPT,
Graphic 5.7" screen, Monochrome STN, Res 320 x 240,
Dim 210 x 158 x 54, MSP 1), ASP 2)
Graphic 5.7" screen, Monochrome STN, Res 320 x 240,
Dim 210 x 158 x 54, MSP 1), ASP 2), LPT,
Graphic 8.4" screen, 256 Colours TFT, Res 800 x 600, Dim 246 x 189 x 38,
MSP 1), ASP 2), LPT, Project: 7 MB - Recipes: 192 KB
Graphic 8.4" screen, 256 Colours TFT, Res 800 x 600, Dim 246 x 189 x 38,
MSP 1), LPT, Project: 7 MB - Recipes: 192 KB, Profibus DP
Graphic 8.4" screen, 256 Colours TFT, Res 800 x 600, Dim 246 x 189 x 38,
MSP 1), LPT, Project: 7 MB - Recipes: 192 KB, Ethernet 10/100
Graphic 10.4" screen, Colour TFT, Res 640 x 480, Dim 336 x 256 x 44,
MSP 1), ASP 2), LPT, Project: 7 MB - Recipes: 128 KB
Graphic 10.4" screen, Colour TFT, Res 640 x 480, Dim 336 x 256 x 44,
MSP 1), LPT, Project: 7 MB - Recipes: 128 KB, Profibus DP
Graphic 10.4" screen, Colour TFT, Res 640 x 480, Dim 336 x 256 x 44,
MSP 1), LPT, Project: 7 MB - Recipes: 128 KB, Ethernet 10/100
Graphic 12.1" screen, 256 Colour TFT, Res 800 x 600, Dim 336 x 256 x 44,
MSP 1), ASP 2), LPT, Project: 7 MB - Recipes: 128 KB
Graphic 12.1" screen, 256 Colour TFT, Res 800 x 600, Dim 336 x 256 x 44,
MSP 1), LPT, Project: 7 MB - Recipes: 128 KB, Profibus DP
Graphic 12.1" screen, 256 Colour TFT, Res 800 x 600, Dim 336 x 256 x 44,
MSP 1), LPT, Project: 7 MB - Recipes: 128 KB, Ethernet 10/100
Description Price $
Price Schedule ‘A4’
Notes: 1) Multi Serial Port (25 pin). 2) Auxiliary Serial Port (15 pin).
1 - 54
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Accessories
VTBUTTONCELL
PROTFILM6
PROTFILM10
PROTFILM12
PCNET
VTPROFI/DP
XCSP85C
VTWINLITE
Lithium 3 V battery back-up recipe and clock
Transparent adhesive protection film for 6” touch screen
(VT505W, VT525W, VT555W, VT565W) 5 sheets included
Transparent adhesive protection film for 10” touch screen
(VT585W) 5 sheets included
Transparent adhesive protection film for 12” touch screen (VT595W)
5 sheets included
External gateway to connect a PC (SCADA, MS Excel, MS Access,
Internet Explorer, etc.) to any PLC or ESA operator panel
External module PROFIBUS / DP
External 24 V DC 3.5 A Power supply 2)
Programme CD software and cable 3)
Notes: 1) All cables are 2 m in length. 2) XCSF85C power supplies are on Price Schedule ‘A2’. 3) NETT price only.
Operator panels and touch screensCommunication cables
Price Schedule ‘A4’
Download cable from PC to ESA displays
ESA MINI DIN download adaptor
Communications cable between the 9 pin ASP port
(VT 170 / VT 190 ) and the Hitachi H Board,
H 200 / H 250 / H 252 B / H 252 C PLCs
(Can also be used to program the above PLCs)
Communications cable between the 25 pin MSP port (all ESA panels)
and the Hitachi H Board, H 200 / H 250 / H 252 B / H 252 C PLCs
Communications cable between the 9 pin ASP (VT 170 / VT 190 )
and the Hitachi EH-150 PLC
(Can also be used to program the EH-150 PLC)
Communications cable between the 25 pin MSP port (all ESA panels)
and the Hitachi EH-150 PLC
VTCBLXFR 1)
VTCBLADP 1)
CBL90H 1)
VTCBL2515 1)
CBL1509 1)
VTCBL2545 1)
Description Cat. No. Price $
1 - 55
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Operator panels and touch screens
VTWIN Configuration software
One software package for the entire rangeAll graphic and text based panels are configured with one package - VTWIN. VTWIN is the Microsoft Windows® based software for configuring your operator panel. The software supports Windows 95, Windows 98, Windows NT 4.0, Windows 2000 and Windows XP. It is intuitive, easy to use and includes a graphics editor for developing professional looking screens with a minimum of fuss. The software comes packaged with all available communication drivers and a cable for communication between a PC and the panel. On-line help and the ability to import bitmap images make configuration quick and easy, saving both time and money.
Use the same software development environment to configure all of the operator units, whether it is the low-end text based panels or the high-end graphics based touch panels. Application programs previously created for one particular model can be re-used for any model in the range. This means you only need to learn one software package and importantly, you only need to purchase one software package.
VTWIN features Rapid application development – a wide variety of pre-configured picture elements can be inserted
into a page – multi-language labels and texts, dynamic text fields, lines, rectangles, ellipses, arcs, bar graphs, touch buttons, bitmap images, information messages, alarms, etc
Graphic image formats – directly import graphic images from a wide selection of standard formats e.g. BMP, JPG, GIF, DXF, PSD, TIFF, WMF and many more
3-D Graphics – create life-like 3-D graphic pictures with image compression, stretching, dithering and support for 256 colours
Alarm thresholds – specify alarm thresholds on objects making it possible to dynamically change colours based on the related process variable
Advanced graphics functions – represent analogue values using analogue indicators, selector knobs, potentiometers and sliders
With the WYSIWYG graphics editor you know exactly
how your text and graphics will appear on the VT
terminal before you download the project.
To gain access to PLC data simply assign a variable
name and the required PLC register.
1 - 56
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Operator panels and touch screensDimensions and cut-outs (mm)
Text and Graphic panels
305
196
560
291275
120
28
28
176186
8 137.5 137.5
ø 4.5
VT 320W
13927
86
166
95
41
77
157
VT 50/ VT 60 VT 190W
435
260
5
74
418.3403
240 130249
4.5
49 49
ø 5
7.6
152.5 152.5
55
55
VT 330W
VT 170W
252
196
5
60
242232
29
120178
29
116116
5
186
4.5
1 - 57
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Operator panels and touch screensDimensions and cut-outs (mm)
VT 505W/VT 555W/VT 565W
VT 155W / VT 185
VT 595W
VT 575W / VT 580
VT 585W
Touch Operator panels
AC-ADROIT-SCADA HMI
WORLD CLASS SCADA / HMI SOFTWARE
0800 NHP NHP nhp-nz.com1300 NHP NHP nhp.com.au
AUTOMATION SYSTEMS
PLCs Smart UI (web enabled)
Classic UI
RTUs
DatabasesMES
OPC Client
API
OPC Server
Databases
Web ServicesWeb Services
1 - 59
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting softwareWorld class 32 bit
SCADA / HMI software
Open automation technology
Adroit is a technologically advanced 32 bit SCADA (Supervisory Control and Data Acquisition) system designed for process control, manufacturing systems and open automation applications Developed specifically for Windows 2000, XP, and 2003 Server, Adroit has a flexible object-oriented client server architecture that supports from a standalone implementation to an installation spanning multiple sites.
Adroit Client Adroit Client
Ethernet/ICP/IP
Control Network
Active Cluster
Hot Stand-By
Adroit
SCADA
Server
Adroit
SCADA
ServerAdroit
SCADA
Server
Modem
Internet
Remote
Adroit Client
Distributed multi-client multi-server configuration in a large network system with several servers and several clients, each running on separate Windows 32 bit operating system.
Programmable logic controllers (PLCs), databases, remote terminal units (RTUs), OPC servers
• On-line configuration• No separate development system• Mimic replay• Template mimics and trends
• Scalable open server architecture• Integrated Visual Basic scripting• Wide area network support• SQL database connectivity
Microsoft®
Technologies
Outstanding features
Alarm ManagementSMS Handling SystemSystem Auditing
Plant VCR - replay historical data using mimics Database connectivity - connect to any third-party ODBC
and OLE DB database Active clusters - Adroit’s elegant answer to Hot stand-by
and Server redundancy Web client - view plant data from anywhere in the world Visual basic and java scripting - built-in
scripts require no proprietary code OPC client and server 150 + native drivers
1 - 60
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting softwareWorld class 32 bit
SCADA / HMI software
Server Redundancy with Active clusters
Very few commercial off-the-shelf SCADA HMI products offer genuine hot-standby redundancy, whereby a computer running the real-time, tag database, can suffer catastrophic hardware or software failure without causing loss of data or operator control and monitoring capability. Now with the release of Adroit with its Active Clustering technology this most demanding of all requirements is now achievable.
The above diagram shows 5 Adroit workstations, 2 Adroit servers, and some PLCs connected in a typical client-server, hot-standby configuration. To achieve 100 % redundancy and bumpless switch-over of workstations from a failed server to a standby server, both servers need to be running exactly the same tag database. Server I/O options allow for replicated scanning in and/or out, when in standby mode. Alternatively, if the PLC or other front-end device does not support more than one port, or, as is often the case, PLC communications bandwidth is the critical system bottleneck, then automatic shadowing of plant I/O will occur.
Open Interfaces and Drivers
Adroit has a comprehensive range of drivers for all major controllers and networks including:
More than 150 drivers available…visit www.nhp.com.au/p_automation_communication.asp for complete driver list.
OPC Client and Server
DNP3
Hitachi
Siemens
Allen Bradley
Modbus
Omron
Mitsubishi
Texas Instruments
ABB
Toshiba
Microlink
Opto 22
Samsung
Yokogawa
Applicom
Moore
Eagle
Lonworks
Gem 80
Motorola
Square D
Klockner Moeller
1 - 61
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting softwareWorld class 32 bit
SCADA / HMI software
DB connectivity
OLE DB has been brought into Adroit to give tight, bi-directional data transfer of both real-time and historical data between Adroit and third-party databases. These databases may exist locally or remotely on a LAN/WAN. Data transfer will execute on data change and/or at configurable time intervals. The nice thing about the Adroit DB connectivity is that Adroit will act as a database client. Third-party gateway software applications are no longer needed.The dbAccess agent also support ODBC allowing values to be written to or read from any ODBC source including CSV files.Both OLE DB and ODBC allow values to be appended, deleted, updated or retrieved.
Scripting
Scripting is essentially user-coded routines that will run concurrently with the Adroit software. With these routines the user has the facility to manipulate agent data, manage User interface (UI) operations, control third-party data interfacing (via COM and OLE), automate complex tasks, perform mathematical operations and manage the look and feel of the Adroit application.Adroit scripting is developed in the following area: Script agent: greater control of agent server data through powerful mathematical and conditional scripting. Scripts execute at set time intervals or on change of data.Scripts are edited with an editor and debugger having colour syntax highlighting, script tips (VBA style syntax assistance) and a dialogue editor. A Microsoft™ script engine has been incorporated into Adroit thereby allowing integrators and end users to develop script in VB or Java. In addition to selecting which subroutine within the script is executed, separate initialisation and clean up subroutines can also be optionally configured.
Plant VCR
Plant VCR is essentially a more graphical alternative to historical trends. One may wish to traverse through the historical values of tags using existing pictures to diagnose and analyse plant conditions as they happened. Plant VCR can be thought of as a third mode for pictures, namely, editing, viewing (real time) and viewing (historical). The historical picture can be played backwards or forwards VCR style using the tag’s historical values at a configured speed, or one ‘freezed frame’ at a time in either direction. There is no configuration required to enable the operation of plant VCR for any existing or new picture in Adroit. However, all the tags in the picture that require historical playback need to be data logged.
1 - 62
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting softwareWorld class 32 bit
SCADA / HMI software
This key feature provides an open platform through which third-party applications communicate with Adroit.The OLE automation function together with the command set available in the automation interface allows for powerful data retrieval and manipulation that can easily be used for process monitoring, control, reporting, QA control and data archiving. In fact the scope of the automation interface is such that the complete configuration of an Adroit agent database is possible via an external package;– thereby bypassing the built-in agent configurator,
– allowing for rapid, rules-based tag generating.
Open systems connectivity
In days gone by, plant mimics were built using archaic bitmap techniques. Users came to accept the inherent restrictions imposed by these methods. There was no other choice.
A few years ago Adroit changed it all.
Since then users have been creating concise process graphics with the on-line vector-based drawing tools available in Adroit - mimics that automatically size to the display resolution to give crisp, clear images. Images that do not pixelate when sized, images made so life-like with 3D shading that it becomes difficult to distinguish the mimic from a photo.
That’s the power of Adroit.
Graphics
Efficient data logging and recall where disk space is optimised is old hat to Adroit (in Adroit the exception-based logging function only logs a value if it changes by more than a user-set amount – if a value does not change it is not logged. This leads to an efficient utilisation of disk space but not to “holes” in the log files, as Adroit has the built-in intelligence to recreate a complete set of time-based records at any time).Adroit has however taken its already highly efficient functions of data logging and data recall to yet another level of optimisation and flexibility, with increased data throughput and programme responsiveness when logging to huge databases. And now you can also log to named files, log on demand at any time, establish multiple logging rates per tag and have greater integrity with the log file systems.
With Adroit’s OLE DB connectivity you can now log directly
to any third-party database (SQL, MS ACCESS, ORACLE, ETC.)
Logging
1 - 63
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting softwareWorld class 32 bit
SCADA / HMI software
So you want to see how the temperature has changed over the last year, but still want to maintain realtime trending? With its built-in capability of trending up to eight variables per trend window, and letting the operator scroll from realtime to historical and back to realtime using the keyboard or mouse, Adroit offers a complete trending package. That’s the trend in Adroit – always way ahead of the rest.Adroit’s multi-colour trends dynamically change colour based on the alarm condition of the trend variable, while bookmarks allow you to insert notes into your trend.
Trending
Recipes provide an easy way to download process parameters to front-end devices, to automate routine tasks, and for constructing process simulations. In Adroit, recipes are made up of two components: a Master recipe and one or more associated control recipes. The Master recipe contains the ingredients to be used and the sequence that they will be downloaded, while the control recipe specifies the quantities the ingredients take on.Although essentially sequential in nature, Adroit recipes have the built-in capability to react to unexpected process deviations by executing process-related conditional branching instructions.A very high degree of process safety can therefore be achieved when using Adroit recipes.
Recipes
Alarms are events that need to be brought to the attention of the operator for action. Unfortunately most SCADA applications are over-alarmed where everything is alarmed in case it is needed.The result: a flood of meaningless alarms that the operator eventually starts ignoring.Can this happen with Adroit? No! Because Adroit provides a structure for configuring alarms that immediately allows for intelligent alarming practices. For example, groups of alarms can be disabled automatically by an internal or external event, alarms can be dynamically routed to various peripheral devices (mobile phones, pagers etc.) depending on process conditions, alarms can be globally acknowledged, and more.And above all, hierarchical alarm management scenarios are easy to setup and manage.That’s the power of Adroit.
Alarming
1 - 64
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Visualisation and reporting software World class 32 bit
SCADA / HMI software
Alarm Management
Alarm Management is an important aspect of process control required to counteract inefficient alarming.Alarm management allows you to create an alarming system that alerts the operator to the most relevant alarm for the current incident. In this case fewer alarms are more effective as the human mind can only focus on a few things at a time.The Alarm Management agent logs all incidents and their details, including their time of occurrence, their time of acknowledgement and the time at which they were cleared to a database. This repository of incidents then allows you to:
Generate statistics from the data produced by the alarming system. This allows you to have efficient and meaningful incident reviews to identify and remove nuisance alarms by analysing the counts, frequencies, durations and acknowledgement times of alarms.
Measure KPIs to improve your alarming configuration.
SMS Handling System
The Command agent can send and receive SMS messages by using a device of the GSM_SMS protocol driver. It uses the GSM_SMS driver, which sole function is the sending and receiving of SMS messages to and from GSM modems. The Command agent provides the following functionality:
Ability to both send and receive SMS messages of up to the full 160 character SMS message limit;
Send SMS messages to a single recipient, manually, programmatically or automatically to remotely monitor the status of important process values;
Monitoring of the sent SMS messages for auditing purposes. Sending a message to a different mobile number if no response is
received within a specified period; Receive SMS messages from one or more mobile phones, and if
necessary, perform commands to remotely supervise and control your process and configure Adroit (acknowledging alarms or fetching or setting process values etc.);
Ability to configure pseudonyms and macros to simplify the process of specifying commands by providing shorter aliases for the names of commonly referenced tags.
Built-in Auditing
Agent Server Auditing allows logging of the Agent Server’s sessions and selected activities performed during these sessions to an OLE DB database. In addition, by using the Audit Agent you can log the changes of values that are important to the running of your process, such as set point values and/or alarm limits.Generally, you will audit the Agent Server to provide a means of recourse in the event of a problem occurring to your process. Examining the audit logs you can determine any of the following user actions:
When the Agent Server was stopped and started; What agents have been added or removed from your Adroit installation; What Adroit documents have been saved; Which audited tags (as specified in the Audit agent) have changed in
value; Who the logged on user was, when these audited events occurred.
1 - 65
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Adroit is a modular system that is made up of 1 or more Servers and remote clients if required. The following steps will help guide you through the process of selecting the components required for an Adroit SCADA system
Step 1 – Select the Adroit SCADA Server
Select the Adroit SCADA Server Option you require. This is based on the number of external variables (Scan Points) you need to read or write to an external device. Internal variables 1) are not counted as part of the licence.
Step 2 (Optional) - Adroit SCADA Active Cluster (Redundant) Server if required
If your application requires the additional security of a backup server which will retain all of your data and enable you to continue to monitor and control your plant in the event of a failure of the server, then select an Adroit SCADA Active Cluster Server. The Active Cluster Server must match the Primary Server in terms of the number of Scan Points. Example: If you have selected a 750 Scan Point Primary Server, you must select the 750 Scan Point Active Cluster Server.
Step 3 (Optional) – Adroit SCADA Remote Clients if required
Both the Adroit SCADA Server and Adroit SCADA Active Cluster Server include a User Interface which means that they can both be used as an operation station. If, however, you require additional User Interfaces that are either located in a remote location from the Servers or would like to reduce the load on the servers by running them as dedicated servers, then select the Adroit SCADA Remote Client licence that matches your Server. Example: If you have selected a 150 Scan Point Adroit SCADA Server, then you must select 1 or more Adroit SCADA Remote Clients for 150 Scan Point Server.
UpgradesIf you already have an Adroit SCADA system and would like to upgrade to the latest version of Adroit or increase the size or your system, please contact NHP as the cost of the upgrade depends both on the version you are upgrading from and the system configuration, in terms of the number of scan points, the number of clients and whether your system has a redundant server pair (active cluster).
Adroit Technology AgreementAn alternative method of keeping your system up-to-date is via the Adroit Technology agreement. The agreement lasts for 12 months and entitles you to any new versions of Adroit that are released within the 12 months following the agreement start date. As for upgrades, please contact NHP if you wish to purchase a technology agreement. Please note that the Adroit Technology agreement provides a more cost effective method of keeping your Adroit SCADA software up-to-date with a built-in discount over standard upgrades.
Visualisation and reporting softwareAdroit SCADA
Ordering instructions
Note: 1) Internal Variables are variables which do not read or write data to or from an external device or software package.
Adroit Primary
Server
Adroit Active
Cluster Server
Adroit Primary
Server
Adroit ClientAdroit Client Adroit Client
Adroit Primary
Server
Adroit Active
Cluster Server
1 - 66
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
All prices are NETT
Visualisation and reporting softwareAdroit SCADA
SCADA Software
Ordering details
Notes: 1) 1 Scan Point = 1 PLC Variable. Internal variables are free. 2) Requires Adroit SCADA server Licence of equivalent number of Scan Points.
Adroit SCADA Server Options (Step 1)
Description Cat. No. Price $
30 Scan Point 1) Server and User Interface
75 Scan Point 1) Server and User Interface
150 Scan Point 1) Server and User Interface
300 Scan Point 1) Server and User Interface
750 Scan Point 1) Server and User Interface
1500 Scan Point 1) Server and User Interface
2500 Scan Point 1) Server and User Interface
5000 Scan Point 1) Server and User Interface
25000 Scan Point 1) Server and User Interface
Unlimited Scan Point 1) Server and User Interface
Adroit SCADA Active Cluster (Redundant) Server Options (Step 2 – optional)
30 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
75 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
150 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
300 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
750 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
1500 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
2500 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
5000 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
25000 Scan Point 1) Active Cluster 2) (Redundant) Server & User Interface
Unlimited Scan Point 1) Active Cluster 2) (Redundant) Server &
User Interface
Adroit SCADA Remote Client Options (Step 3 – optional)
Remote Client (User Interface) for 30 Scan Point 1) Server
Remote Client (User Interface) for 75 Scan Point 1) Server
Remote Client (User Interface) for 150 Scan Point 1) Server
Remote Client (User Interface) for 300 Scan Point 1) Server
Remote Client (User Interface) for 750 Scan Point 1) Server
Remote Client (User Interface) for 1500 Scan Point 1) Server
Remote Client (User Interface) for 2500 Scan Point 1) Server
Remote Client (User Interface) for 5000 Scan Point 1) Server
Remote Client (User Interface) for 25000 Scan Point 1) Server
Remote Client (User Interface) for Unlimited Scan Point 1) Server
ADROIT30SI
ADROIT75SI
ADROIT150SI
ADROIT300SI
ADROIT750SI
ADROIT1500SI
ADROIT2500SI
ADROIT5000SI
ADROIT25000SI
ADROITULSI
ADROIT30SI-A
ADROIT75SI-A
ADROIT150SI-A
ADROIT300SI-A
ADROIT750SI-A
ADROIT1500SI-A
ADROIT2500SI-A
ADROIT5000SI-A
ADROIT25000SI-A
ADROITULSI-A
ADROIT30RC
ADROIT75RC
ADROIT150RC
ADROIT300RC
ADROIT750RC
ADROIT1500RC
ADROIT2500RC
ADROIT5000RC
ADROIT25000RC
ADROITULRC
Adroit ServerAdroit Server
Adroit Active Cluster
(Redundant) Server
Adroit Server
Adroit Stand-alone
Server
Adroit Server
Adroit Remote Clients
Adroit ClientAdroit Client
1 - 67
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
All prices are NETT
Visualisation and reporting softwareAdroit SCADA
SCADA Software
Ordering details
Adroit Upgrades and Maintenance Agreements
Description
Adroit Upgrade
The cost to upgrade from a previous version of Adroit depends both on the version number you are upgrading from and the system configuration in terms of the number of scan points, the number of clients and whether your system has a redundant server pair (cluster).Please contact NHP for a quote on Adroit Upgrades.
Adroit Technology Agreement
The Technology Agreement is a 12 month contract which entitles you to all Adroit upgrades and premium support for the period of the contract. The cost of the Technology Agreement depends both on the version number you have and the system configuration in terms of the number of scan points, the number of clients and whether your system has a redundant server pair (cluster).Please contact NHP for pricing on Adroit Technology Agreements.
Notes: 1 Scan Point = 1 PLC Variable. Internal variables are free. Other variants including redundant servers (Clusters) available. Please contact NHP for more information.
Price $
Price $
Training
Adroit configuration Level I - 2 day course. This course is targeted at new Adroit users, configurators, technicians and engineers. The course sets the foundation for the next level course and provides delegates with the tools to implement and configure small projects. All commonly used features are covered in appropriate detail. The pre-requisite for attending this course is an understanding of SCADA and an operational knowledge of Microsoft Windows 95/98. Operational experience of Microsoft Windows 2000 / XP is an advantage.
Adroit configuration Level II - 2 day course. This course is targeted at Adroit users, configurators, technicians and engineers who have successfully implemented at least one project. The concepts and principals presented in the Level I course are covered in depth, while additional features are introduced and explained. The pre-requisite for attending this course is the Level I configuration course as well as project experience.
Contact NHP for further information.
1 - 68
1
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘E9’
Switch mode power supplies
Features
5 year warrantyQuick mounting and connecting, innovative DIN railHigh efficiency
Low power lossElectronic protection from short circuit, overload and over-voltageVoltage limitingAdjustable output
Notes: 1) Wide range single-phase input 2) Double range single-phase input 3) Two-phase input 4) Three-phase input 5) With Oring diode for redundant parallel
6) With failure contact (power good) 7) With adjustable output 8) UL508C approved
XCSD15B 1)8)
XCSD30C 1)8)
XCSD50B 1)7)8)
XCSD70C 1)8)
XCSL85C 1)8)
XCSF85CP 1)5)6)8)
XCSF120B1)6)7)8)
XCSL120C 1)8)
XCSF120CP1)5)6)8)
XCSF120D 1)6)8)
XCSF240B 2)6)7)8)
XCSL240C 2)8)
XCSF240CP2)5)6)8)
XCSF240D 2)6)8)
XCSF500C 2)6)8)
Single phase switching power supplies
15
30
50
85
120
240
500
Cat No. Price $
Output power (W)
Output voltage
12 V DC
24 V DC
12...15 V DC
24 V DC
24 V DC
12...15 V DC
24 V DC
48 V DC
12...15 V DC
24 V DC
48 V DC
24 V DC
Output current (A)
Inrush current Model type
CSD Series
CSD Series
CSD Series
CSD Series
CSL Series
CSF Series
CSF Series
CSL Series
CSF Series
CSF Series
CSF Series
CSL Series
CSF Series
CSF Series
CSF Series
1.2
1.2
3.5
3
3.5
7
5
2.5
16
10
5
20
<5 A
<13 A
<15 A
<15 A
<20 A
<20 A
<35 A
<25 A
XCSBC
XCSBD
AccessoriesCat No. Price $Description
PS Batt charger module
PS redundant conn module
CSD series
CSF Series
CSL series
CSG Series
XCSB150C 3)8)
XCSB150D 3)8)
XCSG240C 4)6)8)
XCSG500C 4)6)8)
XCSG720C 4)6)8)
XCSG42 4)8)
XCSG2400C 4)8)
Three phase switching power supplies
150
240
500
720
1008
2400
Cat No. Price $
Output power (W)
Output voltage
24 V DC
48 V DC
24 V DC
24 V DC
24 V DC
24 V DC
24 V DC
Output current (A)
Inrush current Model type
CSG Series
CSG Series
CSG Series
CSG Series
CSG Series
CSG Series
CSG Series
<50 A
<50 A
<35 A
<30 A
<20 A
<130 A
6
3
10
20
30
40
100
XCSA120BC
XCSA120CB
XCSA120DC
Cat No. Price $
Input voltage V (DC)
12
24
48
Output voltage V (DC)
24
12...15
24
Output current (A)
5
7
5
Inrush current
<60 A / <2ms
<100 A / <2ms
<120 A / <2ms120
Output power (W)
DC/DC Insulated converters
2 - 1
Safety2
Safety interlock switches
Series ST - 14: Light duty 2 - 2Series ES - 95: General purpose 2 - 2Series ST - 61: Heavy Duty 2 - 3Series ES - 95: General purpose rotary cam 2 - 4Series ES - 13SB: Light duty hinged 2 - 4Series ES - 95: General purpose flap/hinge 2 - 4Series STM 295: Medium duty solenoid 2 - 5Series AZM 415: Heavy duty Solenoid 2 - 5Non-contact Safety switches
Series RC Si - M30 2 - 6Series RC Si - 56 2 - 6Series HSSi4 2 - 7Series BZ16 2 - 7Emergency stop trip-wire switch kits 2 - 8Emergency stop trip-wire switches 2 - 9Belt drift switches 2 - 10Limit switches
Light duty 6 A: ES/EM 95 series 2 - 11Medium duty 10 A: PS21 series 2 - 11Medium duty 10 A: PS31 series 2 - 12Medium Duty 6 A:ES/EM 41 series 2 - 12Emergency stop trip-wire switches
Type NTW cast aluminium 2 - 13 to 2 - 18Spare parts and accessories 2 - 15 to 2 - 16Installation instructions 2 - 17 to 2 - 18Heavy-duty limit switches: 77 HL and 77 TL series 2 - 19Safety Controllers
Series NSC: Fail safe control unit 2 - 20Series MF1: Standstill monitor 2 - 20Series SRM: Fail safe control unit 2 - 20Limit switches - pull-wire (non safety) 2 - 21Foot operated switches 2 - 22Pressure switches 2 - 23
SAFETY INTEREEEEEEEERRRRRRRRRRRRRRRRRLLLLLOOOOOOCCCCCCCKKKKKK WITCHESSSSSSSSSSSSWWWWWWWWWWWWWWWWWWWW
FOOT OPERATED SWITCHES
NON-CONTACT SAFETY SSS SWITCHESS
LIMMIT LLLLLLLLLIIIIIIIIIMMMMMMMMMIIIIIIIIIITTTTTTTTTTTT SWITCCHHEESS
PRESSURRE SWITCHESEEMERGENCY STTOPP TTRRIIPP-WIRE SWITCHESS
EEMMEERRGGEENNCCYY STTOOPP TTRRIIPP-WWIIRREE SSWWITCHH KKITTSS
2 - 2
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule 'B2'
Safety interlock switches
Series ST -14: Safety interlock switchLight Duty - safety guard interlock IP 67
Series ES-95: Safety interlock switchGeneral purpose - safety interlock switch - machine guards IP 67
ST14 B1
ST14 B5
ST14 B3
Accessories - actuators
Actuator Straight for ST14
Actuator Right angle for ST14
Actuator Spring loaded for ST14
Price $
Switch Cat. No.
95AZB1
95AZB5
Accessories - actuators
Actuator Straight for ES95
Actuator Right angle for ES95
Price $
Switch Cat. No.
ST14
11
15
53
16 7,58
ø4
.2
Rmin.140
Rmin.1000
11
8
3538
16 1530
ø4.2
Rmin.140
Rmin.1000
ST 14 B1 ST 14 B5 ST 14 B3
ES95AZ
95AZB1 95AZB5
Dimensions in mm
Dimensions in mm
1 N/O + 1 N/C
2 N/C
1 N/O + 1 N/C Ex-version
Contacts
ST14-10/1S
ST14-20
EEXST-14-10/1S 5M
Price $
Switch Cat. No.Actuator Action Type
Retaining
Retaining
Retaining
BAC19
BAC19
BAC19
Fencing Adaptor
1 N/O + 1 N/C
2 N/C
Contacts
ES95AZ101S
ES95AZ20
Price $Switch Cat. No.Actuator Action Type
Retaining
RetainingBAC20
BAC20
Fencing Adaptor
2 - 3
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Safety interlock switches
Price Schedule 'B2'
Series ST-61: Safety interlock switchHeavy Duty - safety interlock switch - machine guards IP 65
ST61 B1
ST61 B5
Accessories - actuators
Actuator Straight for ST61
Actuator Right angle for ST61
Price $Switch Cat. No.
ST6110 1S
Dimensions in mm
ST61 B1
ST61 B5
1 N/O + 1 N/C
2 N/C
Contacts
ST6110/1S
ST6120
Price $Switch Cat. No.Actuator Action Type
Retaining
Retaining
BAC21
BAC21
Fencing Adaptor
2 - 4
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Safety interlock switches
Price Schedule 'B2'
Series ES-13: Rotary cam interlock switchLight duty safety switch - guards, doors, covers, etc.
1 N/O + 1 N/C
Contacts
ES13SB101S
Price $
Switch Cat. No.IP Rating
IP 67 Thermoplastic
Material
Series ES-95: Rotary cam interlock switchGeneral purpose safety switch - guards, doors, covers, etc.
1 N/O + 1 N/C
2 N/C
Contacts
ES95SB101S
ES95SB20
Price $
Switch Cat. No.IP Rating
IP 67
IP 67
Thermoplastic
Thermoplastic
Material
ES95T5C101S
ES13SB101S
ES95SB101S
Series ES-95: Flap/hinge safety switchGeneral purpose safety switch - machine guards
1 N/O + 1 N/C
Contacts
ES95T5C101S
Price $
Switch Cat. No.IP Rating
IP 67 Thermoplastic
Material
2 - 5
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule 'B2'
Safety interlock switches
Series AZM 415: Heavy duty solenoid safety interlock switch Removable guards, doors, covers, etc. IP 67
AZM415 B1
AZM415 B2
AZM415 B3
Accessories - actuators
Actuator Straight for AZM415
Actuator Adjustable X axis for AZM 415
Actuator Adjustable Y axis for AZM 415
Price $
Switch Cat. No.
Series STM: 295 Medium duty solenoid safety interlock switchRemovable guards, doors, covers, etc. IP 67
STM295 B1
STM295 B5
Accessories - actuators
Actuator Straight for STM295
Actuator Right angle for STM295
Price $
Switch Cat. No.
STM295202SR
AZM415202SR3D
STM295 B1 STM295 B5
Dimensions in mm
Dimensions in mm
AZM415 B1 AZM415 B2 AZM415 B3
2 N/O + 2 N/C
2 N/0 + 2 N/C
Contacts
STM295202SR
STM295202SA
Price $
Switch Cat. No.Solenoid Action
Power unlock
Power lock
24 V DC
24 V DC
Solenoid Voltage
BAC22
BAC22
Fencing Adaptor
2 N/O + 2 N/C
2 N/0 + 2 N/C
Contacts
AZM415202SR3D
AZM415202SA3D
Price $
Switch Cat. No.Solenoid Action
Power unlock
Power lock
24 V DC
24 V DC
Solenoid Voltage
BAC23
BAC23
Fencing Adaptor
2 - 6
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule 'B2'
Non-contact safety switches
Series RC Si-56: Magnetic coded safety switches - IP 67RC Si Recommended to be used with SRM 21 RT2 relay
Series RC Si-M30: Magnetic coded safety switches - IP 67RC Si Recommended to be used with SRM 21 RT2 relay
1 N/O + 1 N/C
2 N/C
Contacts
RCSIM30101S5M
RCSIM30205M
Price $Cat. No.Description
Magnetic cylinder M30
Magnetic cylinder M30
MC56
Accessories - actuators
Coded magnet
Price $Cat. No.
MC30
Accessories - actuators
Coded magnet
Price $Cat. No.
RCSI56101S5M
RCSIM30101S5M
Dimensions in mm
MC56-3
Dimensions in mm
MC30
1 N/O + 1 N/C
2 N/C
Contacts
RCSI56101S5M
RCSI56205M
Price $Cat. No.Description
Magnetic switch rectangle
Magnetic switch rectangle
BAC24
BAC24
Fencing Adaptor
2 - 7
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Non-contact safety switches
Series HSSi 4 : Hall sensor - IP 67General duty guard door monitor
Price $Cat. No.
HSSI4101S
HSSI420
Descriptions Contacts
Hall sensor
Hall sensor
1 N/O + 1 N/C
2 N/C
Price $Cat. No.
MC4
Accessories - actuators
Actuator
RCSIM30101S5M
HSSI4101S
BZ16 11
BZ16 B1
Series BZ16 : Induction/Hall sensor - IP 67General duty guard door monitor
Price $Cat. No.
BZ1611V
BZ1611D
BZ1611U
BZ1602V
BZ1602D
BZ1602U
Face actuation Contacts
Front
Top
Bottom
Front
Top
Bottom
1 N/O + 1 N/C
1 N/O + 1 N/C
1 N/O + 1 N/C
2 N/C
2 N/C
2 N/C
Price $Cat. No.
BZ16B1
Accessories - actuators
Actuator
Actuation face
Price Schedule 'B2'
2 - 8
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B2’
Emergency stop trip-wire switch “kits”
Notes: 1) Items included in all of the above kits
1 x Tension spring (As per requirement AS 1755-2000) 1 x 55164, turnbuckle 4 x 55151, thimble 8 x 55152, wire clamps _ x Cable (quantity as above) _ x 55150, wire support (quantity as above) Wire supports are based upon supporting the trip-wire at 2.5 - 3 metre intervals.
TQZS-75...
TQZS-73...
TQZS-71...
TQZS-80
TQZS-70
Series TQ ZS: Trip-wire switchesEmergency stop for conveyor and various other industries
TQZS70...8 metresSlim housing
Price $Cat. No
TQZS70KIT10M
Trip-wireSwitch
TQZS70... kit
TQZS70101SVD
Items included in kit 1)Trip-wire length
8 metres
1 x TQZSTS150N
8 x TQZSWR5MM (cable)
3 x 55150 (wire support)
TQZS71...5-20 metresSmall housing
TQZS71KIT20M
TQZS71... kit
TQZS71101 20 metres
1 x TQZSTS250N
20 x 55153P (cable)
5 x 55150 (wire support)
TQZS73...30-50 metresGeneral purpose
TQZS73KIT50M
TQZS73... kit
TQZS3101SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
TQZS-75...30-50 metresLarge housing
TQZS75KIT50M
TQZS75... kit
TQZS75101SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
TQZS80...10-50 metresWith emergency stop and flag indicator
TQZS80KIT50M
TQZS80... kit
TQZS80202SWVD 50 metres
1 x TQZSTS250N (spring)
50 x 55153P (cable)
10 x 55150 (wire support)
2 - 9
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Emergency stop trip-wire switches
Price Schedule ‘B2’
Price $Cat. No.
TQ441 01/01 YUR 137 1)
TQ441 01/01 YUR 157 2)
TQ441 01/01 YUR 1)
Trip-wirelength (metres) Contact arrangement Description
5-25 m
0-5 m
5-25 m
(1 N/C + 1 N/C)
(1 N/C + 1 N/C)
(1 N/C + 1 N/C)
Cast Iron Body
35 N Type
Cast Aluminium
Series TQ441/T3Z : Trip-wire switchEmergency stop for conveyor and various other industries
Series TQZS : Trip-wire switchesEmergency stop for conveyor and various other industries
Price $Cat. No.
55153P
TQZSTS250N
TQZSTS150N
55150
55152
55151
55164
S900
Description
Steel wire red PVC covered 7 mm Ø (per metre)
Tension spring heavy duty
Tension spring light duty
Wire support bracket
Wire clamp / shackle
Thimble
Turnbuckle
Tensioning device (for 5 mm Ø wire)
Trip-wire switch accessories
55153P
Wire rope
Trip-wire switch
TQ441-01/01YUR137
55152
Wire clamp
55150
Wire support
Notes: 1) Use in combination with TQZSTS250N tension spring and 55153P 7 mm wire rope. 2) Use in combination with TQZSTS150N tension spring and TQZSWR5MM 5 mm wire rope.
Price $Cat. No.
TQZS-70 10/1S VD 2)
TQZS-71 10/1SWVD 1)
TQZS-71 20 WVD 1)
EEXZS-71 10/1S WVD 1)
TQZS-73 10/1SWVD 1)
TQZ-73 20 WVD 1)
EEXZS-73 10/1S WVD 1)
TQZS-75 10/1S WVD 1)
TQZS-75 20/2S WVD 1)
TQZS-80 20/2S WVD 1)
Trip-wirelength (metres) Contact arrangement Description
0-8 m
5-20 m
5-20 m
5-20 m
30-50 m
30-50 m
30-50 m
30-50 m
30-50 m
10-50 m
(1 N/O + 1 N/C)
(1 N/O + 1 N/C)
(2 N/C)
(1 N/O + 1 N/C)
(1 N/O + 1 N/C)
(2 N/C)
(1 N/O + 1 N/C)
(1 N/O + 1 N/C)
(2 N/O + 2 N/C)
(2 N/O + 2 N/C)
Ex version
Ex version
2 - 10
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Belt drift switches
Series ES 61 SR: Belt drift switchLight duty
Series ZS 73 SR: Belt drift switchGeneral duty
Series ZS 75 SR: Belt drift switchGeneral duty
Price Schedule ‘B2’
ES61SR101S
ZS73SR101S
ZS90SR202S
Price $Cat. No.IP Rating
ES61SR101SIP 65 Aluminium
Material
1 N/O + 1 N/C
Contacts
Price $Cat. No.Description
ZS73SR101SIP 65 Aluminium
Material
1 N/O + 1 N/C
Contacts
Price $Cat. No.IP Rating
ZS75SR101S
ZS75SR202S
IP 65
IP 65Aluminium
Aluminium
Material
1 N/O + 1 N/C
2 N/O + 2 N/C
Contacts
Series ZS 90 SR: Belt drift switchHeavy duty
Price $Cat. No.IP Rating
ZS90SR10S10SIP 67 Duroplast
Material
2 N/O + 2 N/C
ContactsZS75SR101S
2 - 11
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Limit switches
Price Schedule 'B2'
Light Duty 6A (Ithe) IP 67 ES/EM 95 series 1)1 N/O & 1 N/C
Medium Duty 10A (Ithe) IP 66 PS 21 L series 1)1 N/O & 1 N/C
Notes: 1) Versions with 2 N/0 or 2 N/C contacts available on indent.
ES95W101S
ES95D101S
ES95DS101S
PS21LMS11PR00
PS21LMS11POM00
Dimensions in mm
Dimensions in mmØ10/0.39”
37/1
.46”
107/
4.21
”
16/0.63”
PS21L
ES95
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Price $Cat. No.
ES95W1O1S
EM95W1O1S
ES95R1O1S
EM95R1O1S
ES954K1O1S
EM954K1O1S
ES95D1O1S
EM95D1O1S
ES95DS1O1S
EM95DS1O1S
ES95DD1O1S
EM95DD1O1S
ES95TL1O1S
EM95TL1O1S
ES95TK1O1S
EM95TK1O1S
Actuator Action
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Body Material
W
4K
R
D
DS
DD
TL
TK
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Price $Cat. No.
PS21LM11P0M00
PS21LMS11P0M00
PS21LMT11PRM00
PS21LMS11PRM00
PS21LMT11RTM00
PS21LMS11RTM00
PS21LMT11R1M00
PS21LMS11R1M00
Actuator Action
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Body Material
PO
PR
RT
R1
2 - 12
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B2’
Limit switches
Medium duty 10A (Ithe) IP 65 PS 31 L series 1)1 N/O & 1 N/C
Heavy duty 6A (Ithe) IP 65 ES/EM 41 series 2)1 N/O & 1 N/C
Notes: 1) Versions with 2 N/O or 2 N/C contacts available on indent, except Steute snap action models. 2) Versions with 2 N/C contacts available on indent.
Ø12/0.47”
20/0
.79”
44/1
.73”
30°
50/1
.97”
120/
4.72
”
16/0.63”10/0.39”
5/0.20”
Ø10/0.39”
37/1
.46”
107/
4.21
”
16/0.63”
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Plastic
Price $Cat. No.
PS31LMT11P0T00
PS31LMS11P0T00
PS31LMT11PRT00
PS31LMS11PRT00
PS31LMT11RVT00
PS31LMS11RVT00
PS31LMT11RTT00
PS31LMS11RTT00
PS31LMT11R1T00
PS31LMS11R1T00
Actuator Action
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Body Material
PO
RV
PR
RT
R1
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Metal
Price $Cat. No.
ES41
EM411O1S
ES41R1O1S
EM41R1O1S
ES41D1O1S
EM41D1O1S
ES41DS1O1S
EM41DS1O1S
EM41TL1O1S
Actuator Action
Slow
Snap
Slow
Snap
Slow
Snap
Slow
Snap
Snap
Body Material
W
D
R
DS
TL
PS31LMT11RT00
ES41R101S
ES41DS101S
ES41TL101S
PS31LMS11RT00Dimensions in mm
Dimensions in mm
ES41
2 - 13
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Emergency stop trip-wire switch Type NTW Cast aluminium type
Protection class IP 65 and IP 67
Features
Rugged construction - cast aluminium housing Non-ferrous components throughout All operating shafts & springs are stainless steel Hoseproof - dustproof IP 65 & IP 67 enclosure Complies with AS 1755-2000/AS 1939-1990 Standard unit supplied with 2 N/O + 2 N/C silver wiping action contacts. Flag indicator & padlocking facility supplied as standard
(Padlocking is for prevention of manual reset only) Single or double sided operation Fail-safe mechanism including removal or breakage of either wire Cannot break the N/C circuit without latching open Switch must be manually reset Ex Version complies with AS/NZS 61241
Trip-wire switch with
flag indicator, pilot
light, lamp and lens
55.4.01 NBB
Padlocking feature
Optional window for
external adjustment
IP 65/67 protection
UV resistant
neoprene seals
Manual reset
Pilot light/indicator
Refer Publication
55-NTW, C-100
2 - 14
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
1380.00
1580.00
1390.00
1800.00
Price Schedule ‘B2’
Emergency stop trip-wire switch Type NTW
Standard switch with 2 N/O
+ 2 N/C contact blocks
Standard switch with glass
window and 2 N/O + 2 N/C
contact block
Standard switch with pilot
light and 2 N/O + 2 N/C
contact block 4)
Standard switch with amber
strobe indication and 2 N/O
+ 2 N/C contact block 6)
Description Price $
Trip-wire switchsingle-sided leftCat. No. 1) 2) 3) Price $
55.4.00NBB
55.4.00GWNBB
55.4.01NBB
55.4.01STRANBB
55.4.00RHNBB
55.4.00RHGWNBB
55.4.01RHNBB
–
55.4.00LHNBB
55.4.00LHGWNBB
55.4.01LHNBB
–
1400.00
1610.00
1480.00
Notes: 1) Installation information, lanyard rope and accessories, refer pages 6 - 15 to 6 - 18.
2) Also available with gold plated contacts at extra cost – insert ‘G’ at the end of Cat. No. Contact NHP for additional price.
3) Suitable for use with conveyor control and monitoring communications systems. Contact the NHP Automation team to discuss your requirements.
4) Supplied with red and amber lenses, lamp must be ordered separately. 5) Supplied with red lens, lamp must be ordered separately. 6) Supplied with Allen-Bradley 45 mm strobe light 855PSB30ME522.
Trip wire switch with
glass window
55.4.00 GWNBB
NTW Trip-wire switches, standard range
IP 65/IP 67 padlockable trip-wire switches Single-sided or double-sided operation Supplied with silver wiping action contact blocks
(gold available on request).
Ordering details
55.4.00LH NBB
55.4.01 NBB
Price $
Trip-wire switchdouble-sidedCat. No. 1) 2) 3)
Standard switch with 2 N/O
+ 2 N/C contact block
Description Price $
Switch withGlass window
Cat. No. 1) 2) Price $
Switch with lid mounted pilot light
Cat. No. 1) 2) 5)
EX55400NBB 1710.00 EX55401NBBEX55400GWNBB 1970.00
Price $Standard switch Cat. No. 1) 2)
Explosion proof (Ex) trip-wire switch
Special trip-wire switch for hazardous environments such as grain handling. Supplied with 2 N/O + 2 N/C contact blocks. Complies with AS/NZS 61241.
Ex 55.4.00 NBB
Trip-wire switchsingle-sided rightCat. No. 1) 2) 3)
Dimensions (in mm)
2 - 15
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price $
StandardSilver contactCat. No.
Price Schedule ‘B2’
Price $StandardCat. No.
Emergency stop trip-wire switch Type NTW
Spare contact blocks/Lamp block
NBAFP
NBBFP
-
VFBC
55.00
109.00
106.00
NBAG
NBBG
554LVKIT
-
1 N/O + 1 N/C contacts
2 N/O + 2 N/C contacts
3 N/O + 3 N/C low voltage micro contact set
and bracket
Lamp block for 55.4.01 (suit SES lamp)
Spare lamps SES style for trip-wire pilot light 5) 6)
NO2243
NO2242
NO2551
NO2556
Full voltage pilot light
Full voltage pilot light
Resistor and full voltage pilot light
Resistor and full voltage pilot light
12 V 4 W
24 V 4 W
110 V 4 W
260 V 4 W
55.1.50
wire support
55.1.52
wire clamp
2551
SES 110V lamp
55.2.46
Tension spring
55.1.51
Thimble / sleeve
Notes: 1) 55.2.46 tension spring is only suitable for NTW 55.4 trip-wire switches. 2) Supplied complete with gasket 55.2.17. 3) Use with clip 55.2.40. 4) Eye/Eye turnbuckle available contact NHP. 5) Other voltages available contact NHP. 6) Stock brought in to order on some voltages.
To suit
-
55.2.46
55.1.50
55.1.51
55.1.52
55.1.64
80.00
29.60
11.40
9.90
33.00
55.2.19NTW
55.2.46SS
55.1.50SS
55.1.51SS
55.1.52SS
55.1.64SS
Price $
316 Grade Stainless SteelCat. No.Description
‘D’ Shackle
Tension spring suits NTW 55.4 only 1)
Lanyard support bracket
5 mm thimble/sleeve
5 mm clamp/shackle
Turnbuckle hook and eye 10 mm x 145 mm 4)
Lanyard accessories
Price $
Gold contactCat. No.
Price $Cat. No.
55.2.17
55.2.37
55.2.16
55.2.16GW
55.2.16PL
Price $Cat. No.
Lid gasket
Shaft bellows 3)
Spare Lid for 55.4.00 2)
Spare Lid for 55.4.00GW 2)
Spare Lid for 55.4.01 2)
Spare parts
Voltage SES
2 - 16
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘A2’
Refer catalogue SAFT
NHP/Tufflex™ fibre lanyard rope
A unique combination of properties differentiates NHP/Tufflex™ fibre from other high-performance fibres and makes it the material of choice to meet performance requirements in demanding applications. The remarkable mechanical performance of NHP/Tufflex™ combined with the other unique properties, permit it to be used for a wide variety of purposes. NHP/Tufflex™ unique fibres are used in aerospace, ocean exploration and development, electronic support structures, safety materials, industrial applications, composites, protective apparel and high-pressure inflatables.NHP/Tufflex™ is a high-performance multi-filament yarn spun from liquid crystal polymer (LCP). It is the only commercially available melt-spun LCP fibre in the world exhibiting low weight and exceptional strength and rigidity. It is five times stronger than steel and ten times stronger than aluminium.
These unique properties characterise NHP/Tufflex™:
High strength and modulus Low coefficient of thermal expansion (CTE) Excellent creep resistance High dielectric strength High abrasion resistance Outstanding cut resistance Excellent flex/fold characteristics Excellent property retention at high/low temperatures Minimal moisture absorption Outstanding vibration damping characteristics Excellent chemical resistance High impact resistance
Per metre Price $Cat. No.
55.1.53P
Description
Wire rope 7 mm dia.
(4 mm wire coated in 3 mm RED UV resistant PVC)
Lanyard rope / Trip-wire
Developed to meet AS/NZS conveyor safety standard AS 1755-2000 these ropes are specially tested to work in conjunction with the NHP/Austrol NTW 55.4 series trip wire switches. Two types are available, i.e. PVC covered galvanised trip-wire, and the new NHP/Tufflex™ fibre lanyard rope.
Emergency stop trip-wire switch Type NTW
Accessories and spare parts
Price $Cat. No.
55.1.53RLR
55.1.53RLR-PM
Description
NHP/Tufflex™ RED fibre lanyard rope 7mm dia. (105 m roll)
NHP/Tufflex™ RED fibre lanyard rope 7mm dia. per metre
Ordering detailsRed PVC covered galvanised trip-wire
Ordering details
LCP Fibre lanyard rope
55.1.53P
See page 6 - 17 to 6 - 18 for set up instructions.
See page 6 - 15 for spare parts and accessories.
55.1.53RLR
2 - 17
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
• Individual maximum lengths of lanyard (shown as ‘X’ in the diagrams above) in a horizontal plane must not exceed:
– 100 m when using NHP/Tufflex™ Lanyard rope (Cat. No. 55.1.53RLR) – 60 m when using NHP red PVC coated galvanised steel cable (Cat. No. 55.1.53P)• NHP recommends the use of NHP/Tufflex™ as the lanyard when the conveyor system is operating over
a 5 degree incline from the horizontal. • NHP strongly recommends that pulleys are not used with the galvanised steel cable – i.e to curve the
tripwire/lanyard around conveyor bends, etc. – and that pulleys only be used with NHP/Tufflex™ as the lanyard.
Emergency stop trip-wire switch Type NTW – Protection class IP 65 and IP 67
Method of installationFor single and double-sided operation
Single-sided operationTripwire/lanyard connected to one side of the trip-wire switch (either left or right) and terminated with a return compensation (tension) spring.
Multiple double-sided installationsFor longer conveyor runs, must be installed as shown below:
Double-sided operationTripwire/lanyard connected to both left and right hand sides of the trip-wire switch. Both left and right hand lanyards are terminated with a return compensation (tension) spring.
X Metres Max.
TurnbuckleTension Spring
55.2.46 55.1.64
55.1.50
Wire Supports
4.0 4.0
X Metres Max.
Turnbuckle Tension Spring
X Metres Max.
TurnbuckleTension Spring
55.2.46 55.1.64
55.1.50
55.1.64 55.2.46
55.1.50
Wire Supports
4.0 4.0
Wire Supports
4.0 4.0
X Metres Max.
Turnbuckle Tension Spring
X Metres Max.
TurnbuckleTension Spring
55.2.46 55.1.64
55.1.50
55.1.64 55.2.46
55.1.50
Wire Supports
4.0 4.0
Wire Supports
4.0 4.0
X Metres Max.
Turnbuckle Tension Spring
X Metres Max.
TurnbuckleTension Spring
55.2.46 55.1.64
55.1.50
55.1.64 55.2.46
55.1.50
Wire Supports
4.0 4.0
Wire Supports
4.0 4.0
2 - 18
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
1. Firmly mount the trip-wire switch using the four (4) mounting points on the trip-wire unit: A. For Double-Sided Installations
• A maximum of 100 m from one end of the conveyor when using NHP/Tufflex™, or • A maximum of 60 m from one end of the conveyor when using NHP PVC coated
galvanised cable as the lanyard.
B. For Single-Sided Installation
Mount the trip-wire switch at one end of the conveyor, ensuring that the maximum length of the tripwire/lanyard does not exceed: • 100 m when using NHP/Tufflex™ or, • 60 m when using NHP PVC coated galvanised wire as the lanyard.
Note: If either of the above distances are to be exceeded, then a double-sided installation must be used.
2. Fit the return compensation (tension) spring: C. When using NHP/Tufflex™ as the lanyard:
A maximum of 100 m from each side of the trip-wire switch for double-sided installations, or a maximum of 100 m from one side of the trip-wire switch for single-sided installations.
D. When using NHP PVC coated galvanised steel wire as the lanyard:
A maximum of 60 m from each side of the trip-wire switch for double-sided installations, or a maximum of 60 m from one side of the trip-wire switch for single-sided installations.
3. Position lanyard wire supports at a maximum spacing of 4 m between the return compensation spring and the trip-wire switches. Smaller spacings will ensure higher performance of the trip-wire system.
4. Run the lanyard between the trip-wire switch and the return compensation springs.
5. Terminate the lanyard at the return compensation spring ends using thimbles and clamps. If using the PVC coated galvanised cable, remove outer PVC sheathing before clamping. Secure to the return compensation spring using ‘D’ shackle if necessary.
6. Unwind both ends of the turnbuckle/s to give maximum extension and hook one end to the shaft of the trip-wire switch using the provided ‘D’ shackle.
7. Terminate the other end of the lanyard to the turnbuckle/s using thimbles and clamps. If using the PVC coated galvanised cable, remove outer PVC sheathing before clamping. Before tightening clamp to lanyard, pull through all slack until taught, then tighten clamp.
8. Attach the external setting gauge/s using the screws provided, into the threaded holes, either above or below the external trip-wire switch shafts.
9. Adjust the turnbuckle/s until the end of the shaft is in-line with the end of the setting gauge.
10. Pull the lanyard numerous times to ‘bed-in’ the cable and remove any ‘deadband’ from the system. If necessary, re-adjust the turnbuckle until the end of the shaft is in-line with the end of the setting gauge. If desired, the setting gauge can now be removed.
11. The trip-wire switch set-up is now complete.
55.4.00 NBB Open view Schematic showing operating
lever centred in the middle of
the operating cam.
Emergency stop trip-wire switch Type NTW – Protection class IP 65 and IP 67
Method of installationFor single and double-sided operation
2 - 19
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Heavy-duty limit switches77 HL and 77 TL Series
Hatchway limit switch
double pole 77.1.10
with 77.2.40 lever
Track limit switch
double pole 77.2.11
with 77.2.39 lever
Lever- rod or chain
77.2.34
Double pole contact
block 77.1.31
Features of 77 series switches
Australian designed and manufactured Proven reliability in adverse conditions Durable cast construction Weatherproof and dustproof to IP 54 Double-break long life silver contacts 1) 10 Amp 440 V AC 12 Non-ferrous metal components Optional roller styles
(track limit switches only) Selectable side or bottom mounting
(hatchway only)
77.1.06
77.1.10
Price $Cat. No.Description
Hatchway limit switch with straight roller lever and
single pole contact
Hatchway limit switch with straight roller lever and
changeover contacts
Series 77 HL Cast aluminum Hatchway limit switch 1) (Spring return to centre)
1 N/O or 1 N/C
1 N/O + 1 N/C
Contacts 1)
77.2.50
77.2.11
Price $Cat. No.Description
Track limit switch without lever and single pole
contact - choose lever below
Track limit switch without lever, with changeover
contacts - choose lever below
Series 77 TL Cast iron Track limit switch 1) (Stayput)
1 N/O or 1 N/C
1 N/O + 1 N/C
Contacts 1)
77.1.30
77.1.31
77.2.34
77.1.21
77.1.25
77.2.40
77.2.39
Price $Cat. No.Description
Single pole contact blocks (spare part)
Changeover contact blocks (spare part)
Spare rod or chain lever - for 77 TL switches only
Spare cam for changeover contacts
Spare cam screw for changeover contacts
Spare lever straight - for HL switches
Spare lever fork - for TL switches
Accessories for series 77 HL and 77 TL switches
1 N/O or 1 N/C
1 N/O + 1 N/C
Contacts 1)
Oil impregnated bearing, needs no lubrication
Double break silver-to-silver contacts
Cast dustproof and weatherproof enclosure
Integrally cast mounting feet
Tapped conduit hole
Heavy duty toggle mechanism snap action
Malleable iron operating lever adjustable to any angular position
Plastic moulded cams
Notes: 1) Please state precise ohm value (1 to 50) when ordering. 2) Prices are per each (kit).
Price Schedule ‘B2’
2 - 20
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Safety controllers
Price Schedule 'B2'
Series SRM: Fail safe control unitMonitoring of E-stops, safety gate switches and Steute safety coded magnetic switches
0
Stop Cat.
SRM21RT2
Price $Cat. No.Safety Cat.Rating
4 2 N/C or
1 N/0 + 1 N/C
Sensor Config.
24 V DC
Voltage
2
Enabling paths
Auto/manual
Type reset
SRM21RT2
NSC02DB24DA
Series NSC: Fail safe control unitMonitoring of safety gate switches and Carlo Gavazzi safety coded magnetic switches
0
0
Stop Cat.
NSC13DB24DA
NSC13DB24DC
Price $Cat. No.Safety Cat.Rating
4
4
2 N/C or 1 N/C
2 N/C or 1 N/C
Sensor Config.
24 V AC / DC
24 V AC / DC
Voltage
3
3
Enabling paths
Auto/manual
Monitored
Type reset
Series MF1: Standstill monitor
-
Stop Cat.
MF1C
Price $Cat. No.Safety Cat.Rating
3 1 or 3 phase
Input Config.
24 V AC / DC
Voltage
2
Enabling paths
-
Type reset
MF1C
2 - 21
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B2’
Limit switches - Pull wire (non safety)Heavy / Medium Duty 4 A (Ithe) IP 65
Aluminium die-cast body Protection class IP 65 Slow action 2 contacts Spring return (impulse)
Pull Wire Switch 4 A (Ithe) Non-emergency
ES41…
Heavy - Duty Protection class IP 65 Aluminium die-cast body Spring return (impulse)
Price $Cat. No.
TQ441010YU
Contacts
1 N/C+1 N/C
Pull Wire Switch 4 A (Ithe) Non-emergency
TQ441…
Price $Cat. No.
ES41Z 101S
Contacts
1 N/O+1 N/C
2 - 22
2
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Foot operated switchesType GF, GFS
Series GFM - 4 A (Ithe), Series GF - 16 A (Ithe)
- foot switches aluminium, IP 65 General purpose and heavy duty types
Foot switch (guarded)
GFS/GFSM…
Foot switch (unguarded)
GF/GFM…
Notes: 1) Please state precise ohm value (1 KΩ to 50 KΩ) when ordering. 2) Prices are per each (kit).
Series GFS : Safety foot switch
Price $Cat. No.
GFS1SD 10VD
GFS2SD 20VD
IPRating
IP 65IP 65
Contacts
1 N/O + 1 N/C2 N/O + 2 N/CGFS Safety foot switch
ActionUnguardedCat. No. Price $
GuardedCat. No.
Slow
Snap
Snap
Slow
Slow
Slow
Slow
Slow
Slow
/Description
1 Pedal, 1 N/O 1 N/C
1 Pedal, 1 N/O 1 N/C
1 pedal 2 N/O 2 N/C
1 pedal 2 N/O 2 N/C
1 Pedal, 1 N/O 1 N/C
with pressure point
(2 stage)
1 Pedal, with
potentiometer 1)
2 Pedal, 1 N/O 1 N/C
2 Pedal, 2 N/O 2 N/C
Explosion proof
300.00
320.00
360.00
330.00
570.00
670.00
570.00
680.00
700.00
Price $
340.00
345.00
400.00
415.00
580.00
740.00
620.00
850.00
790.00
GF 101S
GFM 101S
GFM 202S
GF 2O2S
GF 10SD10S
GF POTI_OHM
GF2 10S10S
GF2 20S20S
EEX GF1O1S
GFS 101S
GFSM 1O1S
GFSM 2O2S
GFS 202S
GFS 10SD10S
GFS POTI_OHM
GFS2 10S/10S
GFS2 20S/20S
EEX GFS1O1S
Replacement Contacts Cat. No. Price $
1x ES 60GF
1x ZS23211
2x EM 40 GF KIT
2x ES 40 GF KIT
1x ES 40GF KIT
-
2x ES 60 GF
2x ES 40 GF KIT
-
Price Schedule ‘B2’
2 - 23
22
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Pressure switchesGeneral purpose and industrial type
Pressure range
GPS series – General purpose (IP 54)Features
Wide selection of transducer wetted materials suitable for air, water, oil and for corrosive fluid Field adjustable set points and differential Internal components and bellows are treated and chrome plated to ensure long life Provided with single C/O snap-action switch 1) 20 mm cable entry
Price $ Pressure differentialAllowable pressure Cat. No.
GPS-B015-FN4-VD
GPS-B025-FN4-VD
GPS-B045-FN4-VD
IPS series – Industrial range (IP 65)Features
Wide selection of transducer wetted materials suitable for air, water, oil and corrosive fluid Field adjustable set points and differential IP 65 enclosure with 20 mm cable entry Set point repeatability, ±1 % of operating range One changeover snap-action switch 1) Every internal part and bellows of the switch is chrome plated and treated to ensure long life Mounting bracket is provided with switch for ease of installation
IPS-B026-FN4-VD
IPS-B036-FN4-VD
IPS-B046-FN4-VD
1.45
2.90
5.80
10
20
40
500
700
1000
72.5
101.45
145
2.90
3.60
4.35
20
25
30
400
400
600
58
58
87
217
217
217
1500
1500
1500
43.5
87
145
300
600
1000
-
-
14.5
0
0
100
36.2
50.72
65.2
250
350
450
7.25
8.7
11.6
50
60
80
217
217
217
1500
1500
1500
GPS-B025-FN4-VD
Notes: 1) AC rating 240 V, 10 A. DC rating 24 V, 3 A.
Minimumallowable
kPa psi
Maximumallowable
kPa psi
Minimumallowable
kPa psi
Maximum allowable
kPa psi
Maximum
kPa psi
Pressure range Price $ Pressure differentialAllowable pressure Cat. No.
Minimumallowable
kPa psi
Maximumallowable
kPa psi
Minimumallowable
kPa psi
Maximum allowable
kPa psi
Maximum
kPa psi
Selecting desired ‘cut-off’ and differential
Calculating differential pressure – e.g. IPS-B026-FN4-VD
Specifications 1 N/O + 1 N/C contacts Female NPT ¼” connection port Bellows material: PBP-3 (phosphor bronse) 90ºC
Price Schedule ‘B3’
3- 1
3 Soft starters and drives
Electronic soft starters product selection guide 3 - 2S+S
PCS - introduction, specifications and ordering details 3 - 4AuCom
CSX and CSXi - introduction, specifications and ordering details 3 - 7EMX3 - introduction, specifications and ordering details 3 - 12Variable Speed Drives
Product selection guide 3 - 23Santerno SINUS Nano range - introduction, standard specifications and ordering details 3 - 24SINUS Micro range - introduction, standard specifications and ordering details 3 - 25SINUS Nano and Micro ranges - options 3 - 26SINUS Penta range - introduction, standard specifications and options 3 - 27SINUS Penta - range and selection (380 - 415 V) 3 - 32Input and output choke - ordering details 3 - 35Semiconductor fuses and accessories - ordering details 3 - 36Brake resistor selection by duty cycle 3 - 37Brake resistors and accessories - ordering details 3 - 38Rating and selection chart 3 - 40SINUS Penta - range and selection (660 - 690 V) 3 - 44SINUS Penta - multi-pump application and regenerative application 3 - 46SINUS Penta - options 3 - 48SINUS Penta - specifications 3 - 49
TTTSSSSSSSSOOOOOOOOOFFFFFFFFFTTTTTTTTTTTTTT SSSTTTAAARRTTEEERSSSSSS
SINUS SS NANOVARIABLE SPEED DRIIVVEE
SSSSIIINNNNUUUUSSSS SSSSSS MMMIICCRROOVVVAAARRRIIIAAAABBBBLLLEEE SSSPPPPEEEEEEEEDDDD DDDDRRRRIIIVVVVEEE
SSSIIINNNUUUSSS PPPEEENTAVVVAAARRRIIIAAABBBLLLEEE SSSPPPEEEEEEDDD DDDRRRIIIVVVEEESSSOOOFFFTTT SSSSSOOOOOOOOOOFFFFFFFTTTTTTT SSSTTTAAARRRTTTEEERRRSSSSSSSSSSTTTT
3 - 2
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersProduct selection guide
Introduction
NHP offers an extensive range of soft starter products to ensure your technical and commercial objectives are easily satisfied. The following table provides an overview of the features available from each model and an indication of the duty cycles (Light, Medium, Heavy & Severe) that the products are suited to. When used in conjunction with the table on page 3 - 3, accurate soft starter selection for your intended application is assured.
Note: 1) Optional extra
Power range
Voltage range
Strategy
Controlled
phases
Utilisation
category
User
adjustment
Start modes
Stop modes
Protection
Outputs
Inputs
Indication
Sundry
Applications
(Refer page 3-3)
Page
reference
1.1 - 45 kW, 3 wire2.2 - 75 kW, 6 wire200 - 480 V AC
Closed loop,controlled current
3
AC 53b,built-in bypass
DIP switch
Timed voltage ramp Current limitKick-start
Soft stop
Overload c/w adj. trip classPhase imbalancePhase sequenceLine fault/open loadStarter over-tempShorted SCR
1 x Fixed1 x Programmable1 x Optional
1 x Start1 x Stop
1 Flash coded LED
Various accessories tointegrate with S+Sswitchgear products 1)
Light & Medium dutyHeavy duty with derating
3 - 4
CSXi
7.5 - 110 kW, 3 wire
200 - 440 V AC
Closed loop,controlled current
2 with Equi-Vec TM
AC 53b,built-in bypass
Rotary switch
Constant current Timed current ramp
Soft stop
Overload c/w adj. trip classMotor thermistorExcess start timePhase imbalancePhase sequenceLine fault/open loadShorted SCRComms error
1 x Fixed1 x Programmable
1 x Start1 x Stop
2 Flash coded LEDs
Remote operator 1)Modbus module 1)DeviceNet Module 1)Profibus Module 1)Semiconductor fuses1)
Light, Medium &Heavy duty
3 - 9
CSX
7.5-110 kW, 3 wire
200 - 440 V AC
Open loop,controlled voltage
2 with Equi-Vec TM
AC 53b,built-in bypass
Rotary switch
Timed voltage ramp
Soft stop
Line fault/open load Shorted SCRComms errorSupply frequency
1 x Fixed
1 x Start1 x Stop
2 Flash coded LEDs
Remote operator 1)Modbus module 1)DeviceNet Module 1)Profibus Module 1)Semiconductor fuses 1)
Light, Medium &Heavy duty
3 - 7
Cat No. PCS EMX3
7.5 - 800 kW, 3 wire11-1500 kW, 6 wire
200 - 440 V AC200 - 690 V AC 1)
Closed loop,controlled current
3
AC 53a, continuousAC 53b, bypassed
Digital keypad
XLR-8 adaptive accelerationConstant currentCurrent limitKick-start
XLR-8 adaptive decelerationTVR soft stopBrake mode
Overload c/w progthermal modelMotor thermistorExcess start timePhase imbalancePhase sequenceElectronic shearpinUnder-currentAux. trip inputLine fault/open loadStarter over-tempShorted SCRComms error
1 x Fixed3 x Programmable
1 x 4-20 mA Prog1 x Start1 x Stop1 x Reset2 x Programmable1 x PT 100
Multi-line plain Englishgraphical display
Simulation modesDual parameter setsTrip logEvent logStarts / hours counterAuto-stopEmergency run modeModbus, DeviceNet, Profibus, USB 1)Remote mount keypad 1)690 V AC 1)Semiconductor fuses 1)Expansion I/O 1)RTD/ Ground fault module 1)
Light, Medium, Heavy & Severe duty
3 - 12
3 - 3
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersApplications and duty cycle categories
Severe
Medium
Medium
Severe
Severe
Severe
Severe
Severe
Severe
Medium
Medium
Light
Medium
Heavy
Severe
Severe
Heavy
Heavy
Severe
Medium
Severe
Severe
Light
Heavy
Duty
Heavy
Heavy
Light
Severe
Severe
Severe
Heavy
Severe
Heavy
Severe
Medium
Heavy
Medium
Severe
Medium
Medium
Medium
Severe
Medium
Medium
Medium
Severe
Medium
Severe
Duty
Agitator
Atomiser
Bottle washer
Centrifuge
Chipper
Compressor - Recip (Loaded)
Compressor - Recip (Unloaded)
Compressor - Screw (Loaded)
Compressor - Screw (Unloaded)
Conveyor - Belt
Conveyor - Roller
Conveyor - Screw
Crusher - Cone
Crusher - Jaw
Crusher - Rotary
Crusher - Vertical impact
Debarker
Dryer
Dust collector
Edger
Fan - Axial (Damped)
Fan - Axial (Un-damped)
Fan - Centrifugal (Damped)
Fan - Centrifugal (Un-damped)
Application
Fan - High pressure
Grinder
Hydraulic power pack
Mill
Mill - Ball
Mill - Hammer
Mill - Roller
Mixer
Palletiser
Planer
Press
Pump - Bore
Pump - Centrifugal
Pump - Positive displacement
Pump - Slurry
Re-pulper
Rotary table
Sander
Saw - Bandsaw
Saw - Circular
Separator
Shredder
Slicer
Tumbler
Application
Electronic soft startersSoft starter ratings are influenced by several factors but none more so than the starting time and starting current characteristics of the driven machine. The following table, when used in conjunction with the ratings matrices provided on the following pages, ensures accurate soft starter selection.
Note: The above table is intended as a guide only. Individual machine and motor characteristics will determine the actual start current and start time requirements.
AC 53a: 3-10: 50-10
Duty cycle
50 = Ratio of ON/OFF time 50 %10 = Operating cycles per hour
Start condition
3 = 3 x FLC10 = 10 seconds
Example 1Continuous operation
AC 53b: 3-10: 350
Example 2Bypassed operation
Category Continuous operation Bypassed operation
Light duty AC 53a: 3-10: 50-10 AC 53b: 3-10: 350
Medium duty AC 53a: 3.5-15: 50-10 AC 53b: 3.5-15: 345
Heavy duty AC 53a: 4-20: 50-10 AC 53b: 4-20: 340
Severe duty AC 53a: 4.5-30: 50-10 AC 53b: 4.5-30: 330
Duty category definition - Example
Time between ramps
350 = 350 seconds
Start condition
3 = 3 x FLC10 = 10 seconds
3 - 4
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersPCS series to 75 kW
PCS overviewThe PCS is a compact, simple to use soft starter product designed for 3 phase motors with ratings of up to 45 kW (3 wire) and 75 kW (6 wire).
Unlike competing compact soft starter products, the PCS controls all three phases to the motor, thereby further extending its application possibilities and minimising thermal stresses on the motor.
The basic PCS soft starter features built-in electronic motor protection with adjustable trip class together with a number of other motor and system protection functions. It also has a built-in bypass contactor, thus providing very low watts loss, smaller footprint dimensions, suitability for high density motor control panels and minimising installed cost.
The multiple starting and stopping modes offered by the PCS as standard make it suitable for a large variety of industrial applications.
The PCS is currently available in 2 voltage ranges, 200…480 V AC (stocked by NHP) and 200…600 V AC (available on indent basis) and are suitable for connection to 50 or 60 Hz supply systems.
Motor starting
PCS soft starters provide the user a selection of starting and stopping modes as standard. The ability to select and tailor the starting format ensures the full benefits of soft starting can be achieved in any industrial motor starting application.
Standard starting modesTimed voltage ramp
The timed voltage ramp soft start mode offered by the PCS has the most general application. User adjustments for initial torque and start ramp time allow the PCS to be configured for a variety of applications.
The initial torque can be adjusted from 15 % to 65 % of locked rotor torque. The start ramp time can be adjusted from 2 to 30 seconds.
Current limit
The current limit start mode is used when it is necessary to limit the maximum starting current.
The current limit setting can be adjusted to provide 150 %, 250 %, 350 % or 450 % of full load amps during start. The start time is also user adjustable from 2 to 30 seconds.
Note: If the motor is not up to speed after the selected time elapses, the PCS will transition to full voltage.
Kickstart
Kickstart
The kickstart function is intended for use on machines that present a high frictional starting characteristic. It provides a current pulse of 450 % FLC over a user adjustable period of 0 to 1.5 seconds, allowing the motor to develop the additional starting torque required to get the load moving.
Current limit
3 - 5
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Standard stopping modesSoft Stop
The soft stop function can be used to extend the stopping time of the motor and load. When enabled, the ramp down time can be set to either once, twice or three times the start ramp time setting.
The motor will stop when the output voltage from the PCS reaches the point where the load torque is greater than the motor torque.
PCS protection functionsElectronic motor overload protection with user
selectable trip class
The PCS soft starter provides electronic motor overload protection with adjustable trip class and automatic or manual reset selectivity as standard making it extremely versatile.
The motor full load current is user adjusted via a potentiometer located on the front panel. Overload trip class (either OFF, 10, 15 or 20 seconds) and automatic or manual reset operation are DIP switch selectable.
Note: The trip rating is 120 % of potentiometer setting.
Phase sequence protection
The PCS provides a user selectable (ON or OFF) phase sequence protection function as standard. When selected, the PCS will monitor the incoming phases before application of power to the motor.
Phase loss protection
The PCS provides phase loss protection as standard to ensure the motor will not attempt to start when there is a power phase missing. This protects the motor from burnout resulting from single phase starting conditions.
Open circuit output/open load protection
The PCS monitors the motor circuit to ensure the motor is connected throughout all phases of operation.
Phase imbalance protection
The PCS provides phase imbalance protection as standard. During run it continually monitors motor current through its internal current transformers. To prevent motor over-heating or damage, the PCS will trip if the phase imbalance exceeds specified limits.
Starter over-temperature protection
The PCS monitors the temperature of its power circuits (SCRs) by means of internal thermistors. When the maximum rated temperature of the power assembly is reached, the PCS switches off and a temperature fault is indicated via LED.
Shorted SCR protection
Prior to every start, the PCS will check the integrity of its power assembly (SCRs) and load connections to the motor. If the PCS detects a shorted SCR and/or open circuit on its output, the start will be aborted. This prevents damage from phase imbalance.
Fault indication
In all cases, when a fault is detected the PCS will trip in order to protect the motor and illuminate a fault LED. The fault LED is flash coded, to assist the user in identifying the trip cause thus simplifying the troubleshooting process.
PCS set-up procedureQuick and accurate set-up of the PCS is assured through a simple to use combination DIP switch selection panel and potentiometer.
Where only basic soft start and motor protection functionality is required, the user need only set the motor full load current.
PCS optional extrasAuxiliary contacts
The PCS provides 2 output relays as standard, one of which is programmable for instantaneous or up-to-speed operation. Should additional contacts be required, auxiliary contacts are available in a number of configurations.
Remote fault reset
Remote reset functionality can be achieved by installing a remote reset magnet onto the PCS. Reset magnets are available for all common AC control voltages.
Protective modules
Protective modules containing metal oxide varistors (MOVs) and snubber networks can be installed to protect the PCS against line transients and electrical noise.
PCS DIP
switch
selection
panel
Soft startersPCS series to 75 kW
3 - 6
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersPCS series - technical / ordering details
Catalogue Number construction The PCS is available in a variety of different formats to ensure individual user requirements are totally satisfied. Models stocked by NHP are those listed below. All other combinations are available on indent, POA.
PCS - 003 - 480V - 024
Three phase supply voltage
480V = 200 V AC - 480 V AC600V = 200 V AC - 600 V AC (Indent POA)
Product series designation
C = 3 wire, 6 wire motor connection
Current rating (3 wire)
Amps @ AC 53b:3.5-15:3585 Ambient temp. 50 °C, Altitude < 2000 m003 = 3 Amps, 009 = 9 Amps, 016 = 16 Amps, 019 = 19 Amps,025 = 25 Amps, 030 = 30 Amps, 037 = 37 Amps, 043 = 43 Amps,060 = 60 Amps, 085 = 85 Amps
Optional control supply
Blank = 100 V AC - 240 V AC024 = 24 V AC/DC
Notes: 1) Refer to PCS catalogue for starts/hour information. 2) Standard voltages 110 to 240 V AC 50/60 Hz. 3) When using the PCS in 6 wire mode, the overload current must be set to 58 % of the motor FLC. E.g. A 50 Amp motor in 6 wire
Ordering details
Price Schedule ‘A3’Opt. extras - Price Schedule ‘B4’
mode would use a PCS-030-480 V and the overload current setting would be set to 29 Amps.
PCS-PA-10
PCS-PA-20
PCS-PA-01
PCS-PA-11
PCS-23-CI23
PCS-37-CI37
PCS-25S-CC25
PCP-064-480V
PCP-147-480V
PCP-064-600V
PCP-147-600V
CMR7...V
PCV-064
Optional extrasAuxiliary contacts
Connection modules
Protective modules
Cooling fan
1 N/O contact
2 N/O contacts
1 N/C contact
1 N/O & 1 N/C contact
Connects PCS-003…019 to CA 7-9...23
Connects PCS-025…037 to CA 7-30...37
Connects PCS-003…025 to KT 7-25 S series breaker
480 V version suits all PCS models to 37 Amps
480 V version suits all PCS models 43 to 85 Amps
600 V version suits all PCS models to 37 Amps
600 V version for all models 43 to 85 Amps
Suits all PCS models 2)
Suits PCS models to 37 Amps
(Supplied as standard with PCS models 43 to 135 Amps)
Cat. No. Price $
Remote Reset Magnets
PCS starters are also available in enclosed format. Refer NHP for details.
PCS-003-480V
PCS-009-480V
PCS-016-480V
PCS-019-480V
PCS-025-480V
PCS-030-480V
PCS-037-480V
PCS-043-480V
PCS-060-480V
PCS-085-480V
890.00
910.00
980.00
1060.00
1230.00
1690.00
2020.00
2190.00
2600.00
3190.00
StandardCat. No.
PCS-003-480V-024V
PCS-009-480V-024V
PCS-016-480V-024V
PCS-019-480V-024V
PCS-025-480V-024V
PCS-030-480V-024V
PCS-037-480V-024V
PCS-043-480V-024V
PCS-060-480V-024V
PCS-085-480V-024V
24 V AC/DCControlCat. No.
Max. motor FLC3 Wire 6 Wire (A) (A)
Dimensions (mm)Height Width Depth
5.1
15
27
32
43
51
64
74
103
147
140
140
140
140
140
140
140
206
206
206
45
45
45
45
45
45
45
72
72
72
100
100
100
100
100
100
100
130
130
130
3
9
16
19
25
30
37
43
60
85
Overload 3) setting range (A) Price $
Ratings at 3.5 x FLC, 15 seconds 1)
1…3
3…9
5.3…16
6.3…19
8.3…25
10…30
12.3…37
14.3…43
20…60
28.3…85
Price $
Scan the QR code to view Motor
Control & Drives brochures.
3 - 7
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersCSX Series to 110 kW
CSX overviewThe CSX is a compact soft starter intended for use with 3 phase motors ranging from 7.5 to 110 kW at 400 V AC. Designed with the ‘first time’ soft start user in mind, the CSX incorporates a number of unique features aimed specifically at simplifying the installation and commissioning processes while also significantly reducing installed cost. In order to achieve this the CSX is provided with Equi-Vec™ balanced vector control technology and in-built bypass contactor.
In operation, the CSX provides smooth acceleration and deceleration of the motor and connected load, thereby minimising the electrical and mechanical stresses that would otherwise be encountered through the use of electromechanical motor starting methods.
Equi-Vec™ technology
Equi-Vec™ balanced vector control is state-of-the-art technology developed to enhance the performance of 2 phase soft start controllers. By balancing the current vectors during motor starting, the CSX is able to provide 3 phase like performance while maintaining the commercial and mechanical advantages normally associated with compact soft starter technology.
In-built bypass contactor
To further reduce installation complexity and cost the CSX is provided with an in-built bypass contactor as standard. This eliminates the need for purchase and installation of an external bypass contactor and/or the need to force ventilate the enclosure.
Standard starting modesTimed voltage ramp soft start
The timed voltage ramp start mode is ideally suited to those applications that exhibit a variable start torque requirement. It allows the user to program an initial start voltage and start ramp time to ensure electrical and mechanical stresses are minimised irrespective of motor loading.
CSX-007-V4-C1
Internal Bypass
Contactor
CSX set-up procedure
Quick and accurate set-up of the CSX is as simple as setting two rotary switches to deliver your preferred soft starting performance. For those applications that can benefit from soft stop, an additional rotary switch is provided.
CSX - 030 - V4 - C1
Control supply voltage
C1 = 110-240 V AC or 380-440 V ACC2 = 24 V AC/V DC (indent)
Three phase supply voltage
V4 = 200-440 V ACV6 = 200-575 V AC
Nominal motor kW rating @ 400 V AC
E.g. 007 = 7.5 kW, 110 = 110 kW
Catalogue Number construction
Time voltage ramp soft stop
Standard stopping modesTimed voltage ramp soft stop
During soft stop, the CSX gradually decreases output voltage over a user selected ramp time enabling driven machines to be stopped gently. This is of particular advantage in applications where machinery and/or product are adversely affected by sudden stopping. Examples include pumps and conveyors.
Notes: The soft stop feature can be disabled by selecting a ‘0’ stop time. The soft start and soft stop ramp times are independently adjustable.
Protection features
The CSX also offers an essential level of protection against; Power circuit faults Supply frequency faults Communications failure faults
3 - 8
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersCSX Series - technical / ordering details
Optional accessories
Remote operator
The RCM-02 is an IP 54 rated remote operator / display unit that allows the user to control and monitor CSX operations from a remote location.
Note: The RCM-02 connects to the CSX via the optional interface module PIM-RZ-01.
Fieldbus connectivity
A selection of fieldbus protocol gateways is available for the CSX thereby enabling connection to your preferred communication network.
Pump application interfaceThe pump application interface connects to the side of the CSX soft starter and provides enhanced functionality in pumping applications. Features include; Low pressure input, high pressure input, low water level input, a PT100 input and common fault relay. The digital inputs are assignable to normally open or normally closed whilst the PT100 input offers selectable trip temperature.
RCM-02
CSX soft starters are also available in enclosed format. Consult your nearest
NHP office for pricing and availability.
Finger guards for models 075-110
Fast acting semiconductor fuses (400 V AC applications, 3 required per starter)
For model CSX-007
For model CSX-015
For models CSX-018 and CSX-022
For model CSX-030
For models CSX-037 to CSX-055
For model CSX-075
For models CSX-090 and CSX-110
Semiconductor fuse holders (1 holder per fuse)
For 170M1314 to 170M1322
For 170M3022
Fieldbus communications modules
DeviceNet
Modbus
Profibus
Pump Application interface
Remote operator panel - CSX Remote operator/fault display unit
- Remote operator interface module
Price $
9950350300A
170M1314
170M1317
170M1318
170M1319
170M1321
170M1322
170M3022
170H1007
170H3003
PIM-DN-01
PIM-MB-01
PIM-PB-01
PIM-PA-01
RCM-02
PIM-RZ-01
Cat. No.Optional extras
Price Schedule ‘B3’
980.00
1180.00
1270.00
1370.00
1630.00
1700.00
1990.00
2120.00
2360.00
2870.00
3180.00
Price $
CSX-007-V4-C1
CSX-015-V4-C1
CSX-018-V4-C1
CSX-022-V4-C1
CSX-030-V4-C1
CSX-037-V4-C1
CSX-045-V4-C1
CSX-055-V4-C1
CSX-075-V4-C1
CSX-090-V4-C1
CSX-110-V4-C1
StandardCat. No.
Ordering detailsCurrent ratings based on 10 starts/hour equally spaced, 45 ºC, 3 wire motor connection.
Price $
CSX-007-V4-C2
CSX-015-V4-C2
CSX-018-V4-C2
CSX-022-V4-C2
CSX-030-V4-C2
CSX-037-V4-C2
CSX-045-V4-C2
CSX-055-V4-C2
CSX-075-V4-C2
CSX-090-V4-C2
CSX-110-V4-C2
Light duty3 x FLC, 10 sec
Medium duty3.5 x FLC, 15 sec Depth
24 V AC/DC ControlCat. No.
22
42
51
57
60
84
96
100
161
190
200
18
34
42
46
57
68
77
100
127
151
175
163
163
163
163
163
191
191
191
212
212
212
Heavy duty4 x FLC, 20 sec
16
29
35
38
47
57
63
82
103
123
143
Height Width
203
203
203
203
203
215
215
215
240
240
240
98
98
98
98
98
145
145
145
202
202
202
Dimensions (mm)
3 - 9
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersCSXi Series to 110 kW
CSXi overviewThe CSXi is a compact closed loop controlled current soft starter intended for use with 3 phase motors ranging from 7.5 to 110 kW at 400 V AC. Designed with the ‘first time’ soft start user in mind, the CSXi incorporates a number of unique features aimed specifically at simplifying the installation and commissioning processes while also significantly reducing installed cost. In order to achieve this the CSXi is provided with Equi-Vec™ balanced vector control technology, a comprehensive array of motor and system protection features including in-built bypass contactor and in-built thermal overload with adjustable trip class, all as standard.
In operation, the CSXi provides smooth acceleration and deceleration of the motor and connected load, thereby minimising the electrical and mechanical stresses that would otherwise be encountered through the use of electromechanical motor starting methods.
Equi-Vec™ technology
Equi-Vec™ balanced vector control is state-of-the-art technology developed to enhance the performance of 2 phase soft start controllers. By balancing the current vectors during motor starting, the CSXi is able to provide 3 phase like performance while maintaining the commercial and mechanical advantages normally associated with compact soft starter technology.
In-built motor & system protection
The CSXi provides a comprehensive array of motor and system protection features to further satisfy the most demanding of industrial motor control applications. This eliminates the need to purchase/install additional devices, thus acting to reduce installed cost.
In-built protection features are summarised as follows;
Motor overload (adjustable thermal model) Phase loss / imbalance Excess start time Phase sequence / rotation Motor thermistor input Power circuit fault (shorted SCR, supply fault) Supply frequency Communications failure Trip contact LED healthy / fault indicators
In-built bypass contactor
To further reduce installation complexity and cost the CSXi is provided with in-built bypass contactor as standard. This eliminates the need for external bypass contactors and/or the need to force ventilate enclosures.
Standard starting modesConstant current/current limit soft start
The constant current start mode is ideally suited to highly inertial applications. Due to the nature of this starting mode highly inertial loads are brought up to speed in the shortest time possible, thereby minimising thermal stresses on the motor.
CSXi-007-V4-C1
Timed current ramp soft start
The timed current ramp start mode allows the user to set minimum starting current, maximum starting current and a start ramp time. This method of starting is proven in applications that present a variable starting torque requirement, for example a conveyor that at times may start fully loaded and at other times will be lightly loaded, or to extend the start time of loads that easily break away.
Constant current
Current ramp
3 - 10
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersCSXi Series to 110 kW
Standard stopping modesTimed voltage ramp soft stop
During soft stop, the CSXi gradually decreases output voltage over a user selected ramp time enabling driven machines to be stopped gently. This is of particular advantage in applications where machinery and or product can be adversely affected by sudden stopping. Examples include pumps and conveyors.
Notes: The soft stop feature can be disabled by selecting a ‘0’ stop
time. The soft start and soft stop ramp times are independently
adjustable.
Protection features further explainedElectronic motor overload protection with user
adjustable motor thermal model.
The CSXi soft starter provides built-in motor overload protection with adjustable thermal model as standard.
The thermal model allows the user to select the tripping curve which most closely resembles the thermal withstand curve of the connected motor. This eliminates nuisance motor overload tripping, while maximising machine up-time and plant productivity.
User adjustable Motor FLC and thermal model via rotary switches located on the front panel.
Motor thermistor protection
In order to further enhance motor protection, the CSXi provides an input for direct connection of your motor thermistors.
Phase imbalance protection
The CSXi offers phase imbalance protection as standard. During both start and run, the CSXi monitors motor current through its internal current transformers. In order to prevent motor damage, burn out or over heating, the CSXi will trip if an imbalance exceeds specified limits or a phase loss occurs.
Power circuit protection
Prior to the application of power to the motor but following a start command, the CSXi monitors its line and load connection and the integrity of its SCRs. Should any abnormality be detected, the CSXi will trip thus ensuring the motor is not compromised.
Excess start time protection
The CSXi will trip if the starting time exceeds the motor’s safe starting time characteristics, ensuring the motor is not subjected to high currents for an excessive period of time. This feature will also ensure the load is not jammed or too large at start up.
Supply frequency error
The supply frequency during start and run may vary under some conditions including generator power situations. The CSXi monitors supply frequency to ensure that it is not operating outside its design parameters thus preventing damage to itself and the motor.
Phase sequence protection
Phase sequence protection is of particular advantage in applications that are rotation direction sensitive such as pumps, compressors etc. The CSXi will monitor the incoming phase rotation before application of power to the motor to prevent incorrect rotation of the motor. This feature is user configurable to fwd or any phase sequence application.
Communications failure
Automated plants utilise the communications features of the CSXi. Connection integrity is vital to maintain control and protection of the motor. The CSXi monitors the communications link to maintain supervisory control and displays a fault when a break occurs.
CSXi Set-up
Although the CSXi offers broad functionality, set-up is a simple process. A series of clearly labelled rotary switches is provided to ensure accurate and repeatable settings are easily made. Simply rotate these to the desired position (no need for a user manual) and you’re ready to go.
Fault & status information
Fault and status information is provided by on-board ‘flash coded’ LEDs. In addition, the RCM-02 remote operator is available for those who may require/benefit from remote control and monitoring.
CSXi - 030 - V4 - C1
Control supply voltage
C1 = 110-240 V AC or 380-440 V ACC2 = 24 V AC/V DC (indent)
Three phase supply voltage
V4 = 200-440 V ACV6 = 200-575 V AC
Nominal motor kW rating @ 400 V AC
E.g. 007 = 7.5 kW, 110 = 110 kW
Catalogue Number construction
Soft stop
3 - 11
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft startersCSXi Series - technical / ordering details
Optional accessoriesRemote operator
The RCM-02 is an IP 54 rated remote operator / display unit that allows the user to control and monitor CSXi operations from a remote location.
Note: The RCM-02 connects to the CSXi via the optional interface module PIM-RZ-01.
Fieldbus connectivity
A selection of Fieldbus protocol gateways is available for the CSXi thereby enabling connection to your preferred communication network.
Pump application interface
The pump application interface connects to the side of the CSXi soft starter and provides enhanced functionality in pumping applications. Features include; Low pressure input, high pressure input, low water level input, a PT100 input and common fault relay. The digital inputs are assignable to normally open or normally closed whilst the PT100 input offers selectable trip temperature. RCM-02
CSXi Soft starters are also available in enclosed format.
Consult your nearest NHP office for pricing and availability.
Finger guards for models 075-110
Fast acting semiconductor fuses (400 V AC applications, 3 required per starter)
For model CSXi-007
For model CSXi-015
For models CSXi-018 and CSXi-022
For model CSXi-030
For models CSXi-037 to CSXi-055
For model CSXi-075
For models CSXi-090 and CSXi-110
Semiconductor fuse holders (1 holder per fuse)
For 170M1314 to 170M1322
For 170M3022
Fieldbus communications modules
DeviceNet
Modbus
Profibus
Pump Application interface
Remote operator panel - Remote operator/fault display unit
Remote operator interface module
Price $
9950350300A
170M1314
170M1317
170M1318
170M1319
170M1321
170M1322
170M3022
170H1007
170H3003
PIM-DN-01
PIM-MB-01
PIM-PB-01
PIM-PA-01
RCM-02
PIM-RZ-01
Cat. No.Optional extras
Price Schedule ‘B3’
1470.00
1870.00
2050.00
2120.00
2350.00
2620.00
2830.00
2980.00
3150.00
4050.00
4260.00
Price $
CSXI-007-V4-C1
CSXI-015-V4-C1
CSXI-018-V4-C1
CSXI-022-V4-C1
CSXI-030-V4-C1
CSXI-037-V4-C1
CSXI-045-V4-C1
CSXI-055-V4-C1
CSXI-075-V4-C1
CSXI-090-V4-C1
CSXI-110-V4-C1
StandardCat. No.
Ordering detailsCurrent ratings based on 10 starts/hour equally spaced, 45 ºC, 3 wire motor connection.
Price $
CSXI-007-V4-C2
CSXI-015-V4-C2
CSXI-018-V4-C2
CSXI-022-V4-C2
CSXI-030-V4-C2
CSXI-037-V4-C2
CSXI-045-V4-C2
CSXI-055-V4-C2
CSXI-075-V4-C2
CSXI-090-V4-C2
CSXI-110-V4-C2
Light duty3 x FLC, 10 sec
Medium duty3.5 x FLC, 15 sec Depth
24 V AC/DC ControlCat. No.
18
34
42
48
60
75
85
100
140
170
200
18
34
42
46
57
68
77
100
127
151
175
163
163
163
163
163
191
191
191
212
212
212
Heavy duty4 x FLC, 20 sec
16
29
35
38
47
57
63
82
103
123
143
Height Width
203
203
203
203
203
215
215
215
240
240
240
98
98
98
98
98
145
145
145
202
202
202
Dimensions (mm)
3 - 12
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
OverviewThe EMX3 is an advanced digital soft start solution for motors from 7.5 kW to 1500 kW. EMX3 soft starters provide a complete range of motor and system protection features and have been designed for reliable performance in the most demanding installation situations.
Motor startingThe EMX3 puts you truly in control of motor starting. Depending on your application requirements you can select between the two best soft start control methods. For applications requiring precise control of motor start current EMX3 offers a choice of Constant Current or Current Ramp start modes. Or for superior control over acceleration or deceleration choose XLR-8 Adaptive Acceleration Control.
Standard starting modesXLR-8
XLR-8 adaptive acceleration control is a new intelligent motor control technique developed by AuCom. In an XLR-8 soft start, the EMX3 adjusts the current in order to start the motor within a specified time and using a selected acceleration profile.Every application has a particular starting profile, based on characteristics of the load and motor. XLR-8 offers three different starting profiles, to suit the requirements of different applications. Selecting an XLR-8 profile that matches the inherent profile of the application can help smooth out acceleration across the full start time. Selecting a dramatically different XLR-8 profile can somewhat neutralise the inherent profile. For example, using a late cubic profile to start an early cubic application will result in a more linear behaviour.
XLR-8 start profile
Early acceleration Constant acceleration Late acceleration Start ramp time
Constant current
Constant current is the traditional form of soft starting, which raises the current from zero to a specified level and keeps the current stable at that level until the motor has accelerated. Constant current starting is ideal for applications where the start current must be kept below a particular level.
Soft starters EMX3 for motors to 1500 kW @ 400 V AC and 690 V AC
Refer catalogue EMX3
Time
100
90
80
70
60
50
40
30
20
10
0
1
2
3
4
XLR-8 Adaptive acceleration control
Constant current
Kickstart
Current ramp
Timed current ramp
Current ramp soft starting raises the current from a specified starting level to a maximum limit, over an extended period of time. Current ramp starting can be useful for applications where:
The load can vary between starts (for example a conveyor which may start loaded or unloaded). Set the initial current to a level that will start the motor with a light load, and the current limit at a level that will start the motor with a heavy load.
The load breaks away easily, but starting time needs to be extended (for example a centrifugal pump where pipeline pressure needs to build up slowly).
The electricity supply is limited (for example a generator set), and a slower application of load will allow greater time for the supply to respond.
Kickstart
Kickstart provides a short boost of extra torque at the beginning of a start, and can be used in conjunction with current ramp or constant current starting. Kickstart can be useful to help start loads that require high breakaway torque but then accelerate easily (for example flywheel loads such as presses).
1
2
3
4
3 - 13
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft starters EMX3 series overview
Brake
When brake is selected, the EMX3 uses DC injection to slow the motor.
The EMX3 braking:• Does not require the use of a DC brake contactor• Controls all three phases so that the braking currents and
associated heating is evenly distributed through the motor.Braking has two stages: 1. Pre-brake: provides an intermediate level of braking to slow
motor speed to a point where full brake can be operated successfully (approximately 70 % speed).
2. Full brake: brake provides maximum braking torque but is ineffective at speeds greater than approximately 70 %.
Standard stopping modesXLR-8 Adaptive deceleration control
In an XLR-8 soft stop, the EMX3 controls the current in order to stop the motor within a specified time and using a selected deceleration profile. XLR-8 can be useful in extending the stopping time of low interia loads. Every application has a particular stopping profile, based on characteristics of the load and the motor. XLR-8 offers three different stopping profiles.
TVR Soft Stop
Braking
Time
100
90
80
70
60
50
40
30
20
10
0
1
23
4
XLR-8 Adaptive deceleration control
Choose the XLR-8 profile that best matches your application requirements.XLR-8 stop profile:
Early deceleration Constant deceleration Late deceleration Stop time
TVR soft stop
Timed voltage ramp reduces the voltage to the motor gradually over a defined time. The load may continue to run after the stop ramp is complete. Timed voltage ramp stopping can be useful for applications where the stop time needs to be extended, or to avoid transients on generator set supplies.
Standard protectionMotor thermal model
The EMX3 will verify whether the motor has sufficient thermal capacity for a successful start. The soft starter compares the motor’s temperature rise from the last motor start and only operates if the motor is cool enough to start successfully.
Excess start time
Excess start time is the maximum time the EMX3 will attempt to start the motor. If the motor does not reach full speed within the programmed limit, the starter will trip indicating a stalled condition.
Electronic shearpin protection
With electronic shearpin or instantaneous overcurrent protection the EMX3 can be configured to trip if the average current of all three phases exceeds a specified level while the motor is running. This would usually occur in a ‘stall’ or ‘locked rotor’ condition.
Undercurrent
The soft starter can be configured to trip if the average current of all three phases drops below a specified level while the motor is running. This undercurrent or under-load is usually indicative of a broken coupling between the motor and driven machine, a broken conveyer belt, loss of product or a dry pump.
Mains frequency
The EMX3 monitors mains frequency throughout operation, and can be configured to trip if the frequency varies beyond a specified tolerance.
Phase sequence
This feature selects which phase sequences the soft starter will allow at a start. During its pre-start checks, the starter examines the sequence of the phases at its input terminals and trips if the actual sequence does not match the selected option.
1
2
3
4
3 - 14
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft starters EMX3 series overview
Current imbalanceThe EMX3 can be configured to trip if the currents on the three phases vary from each other by more than a specified amount. The imbalance is calculated as the difference between the highest and lowest currents on all three phases, as a percentage of the highest current.
Auxiliary input tripAuxiliary input trip allows the connection of external fault detection devices, such as low pressure or no flow detectors, vibration sensors, etc.
Motor thermistor inputThe EMX3 has provisions for motor thermistor input and is able to detect excessive temperature in the motor windings generally caused by a stall or from inadequate ventilation.
RS 485 failureThe EMX3’s serial link is provided with a user adjustable time-out function which will trip if the maximum allowable period of RS 485 serial inactivity has been exceeded.
Optional protection functionsGround fault
The optional Ground fault/ RTD card allows the user to configure the soft starter to trip if ground fault exceeds a specified level while the motor is running. Ground fault is a dynamic trip based on phase current measurements every half-cycle.
RTD inputsThe optional Ground fault/RTD card allows the user to connect up to six PT100 RTD directly to the EMX3. This feature enables the EMX3 to measure the temperature of the RTDs and trip if overheating is detected. Trip levels are user programmed.
EMX3 specialist featuresGraphical display
In many cases we’ve done away with language altogether, using real-time graphs of motor operating performance and current to quickly and clearly illustrate exactly how your motor is performing.
Quick start set-upThe EMX3 has been designed for ease of use, and the user-friendly menu is no exception. A quick setup guide helps you configure the starter for common applications by suggesting a typical setting, which you can then fine tune to suit your needs.
Real language in real timeThe EMX3 gives real-language feedback messages instead of the usual alarm codes. With real-time metering displays and a 99-place event log recording time-stamped details of operation and performance, it has never been easier to track how your motor is behaving.
Remote mounting keypadControl pushbuttons, fault and status information available from the EMX3 can be brought out to the cubicle door via the remote mounting keypad option.
Metering and monitoringEMX3 delivers an extensive range of information to replace an additional powermeter. These include motor temperature, current data, motor power, last start information, date and time, performance graph, SCR conduction, trip log and the user-programmable screen.
3 - 15
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft starters EMX3 series overview
SimulationsThe EMX3 simulation functions let you test the soft starter’s operation, external control circuits and associated equipment without connecting the soft starter to line voltage or a motor. The EMX3 has three simulation modes:Run simulation: simulates a motor starting, running and stopping to ensure correct installation.Protection simulation: simulates activation of each protection mechanism to confirm correct protection response.Signaling simulation: simulates output signaling.
Emergency run operationEmergency Run is controlled by a two wire circuit connected to Input A (terminals C53-C54). Closing Input A causes the EMX3 to run the motor and ignore user specified trip conditions. This is useful when the cost of lost production out-weighs the potential cost of further equipment damage.
Unique wiring loomUsing the EMX3’s unique and flexible cable ways, cables can be efficiently organised for wiring from either the top, left or from below.
Removable terminal blocksInstallation is easy with plug-in control terminal blocks, simply unplug each block, complete the wiring and re-insert the block.
Adjustable power terminalsThe bus bars on models EMX3-0360C ~ EMX3-1600C can be adjusted for top and bottom input and output giving four options to ease installation. This flexibility allows you optimisation of your switchboard layout.
In addition, internally bypassed models EMX3-0350B - EMX3-1000B have input and output busbars at both the top and the bottom of the unit. The busbars do not need to be adjusted.
Optional accessoriesOptional accessories for the EMX3 include the following:
Communication modules enabling the soft starter to be controlled by protocols such as DeviceNet™, ProfiBus® and Modbus RTU
USB module enables communication between your PC and EMX3 via Win-Master software. Win-Master is available free of charge.
I/O cards giving an added 2 x inputs, 3 x relay outputs, 1 x analogue input and 1 x analogue output.
RTD and Ground fault card providing 6 x PT100 RTD inputs 1 x ground fault input
Catalogue Number constructionThe EMX3 is available with a variety of options and formats to ensure individual user’s requirements are met. Models stocked by NHP are listed on the following 2 pages and all other combinations are available on indent, POA.
EMX3 – 0255 B – V4 – C1 – H
Keypad
H = Keypad fitted
Control voltage
C1 = 110-220 V AC & 230-440 V ACC2 = 24 V AC/DC
Three phase supply voltage
V4 = 200 V AC – 440 V ACV7 = 400 V AC – 690 V AC (indent)
Bypass
B = Internally BypassedC = Non-bypassed (indent)
Nominal current rating
Product series designation
Expansion input/
output card
6 way RTD and
ground fault
protection card
Communication
modules
3 - 16
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B3’
Soft StartersEMX3 maximum motor FLC ratings 2)3 wire - 400 / 415 V AC applications 1)
Light
Duty
3 x FLC,
10 sec
Medium
Duty
3.5 x FLC,
15 sec
Heavy
Duty
4 x FLC,
20 sec
Severe
Duty
4.5 x FLC,
30 sec
Frame
size
110-440 V AC Control
Standard Model 3)
Cat. No. Price $
24 V AC/DC Control
Variant Model
Cat. No. Price $
AC 53b: Internal bypass contactor
23 A 20 A 17 A 15 A G1B EMX3-0023B-V4-C1-H 2550.00 EMX3-0023B-V4-C2-H
43 A 37 A 31 A 26 A G1B EMX3-0043B-V4-C1-H 2870.00 EMX3-0043B-V4-C2-H
50 A 44 A 37 A 30 A G1B EMX3-0050B-V4-C1-H 3120.00 EMX3-0050B-V4-C2-H
53 A 53 A 46 A 37 A G1B EMX3-0053B-V4-C1-H 3510.00 EMX3-0053B-V4-C2-H
76 A 64 A 55 A 47 A G1B EMX3-0076B-V4-C1-H 3690.00 EMX3-0076B-V4-C2-H
97 A 82 A 69 A 58 A G1B EMX3-0097B-V4-C1-H 4260.00 EMX3-0097B-V4-C2-H
100 A 88 A 74 A 61 A G1B EMX3-0100B-V4-C1-H 4610.00 EMX3-0100B-V4-C2-H
105 A 105 A 95 A 78 A G1B EMX3-0105B-V4-C1-H 4910.00 EMX3-0105B-V4-C2-H
145 A 123 A 106 A 90 A G2B EMX3-0145B-V4-C1-H 5610.00 EMX3-0145B-V4-C2-H
170 A 145 A 121 A 97 A G2B EMX3-0170B-V4-C1-H 5980.00 EMX3-0170B-V4-C2-H
200 A 189 A 160 A 134 A G2B EMX3-0200B-V4-C1-H 7160.00 EMX3-0200B-V4-C2-H
220 A 210 A 178 A 148 A G2B EMX3-0220B-V4-C1-H 7430.00 EMX3-0220B-V4-C2-H
255 A 231 A 201 A 176 A G3B EMX3-0255B-V4-C1-H 8650.00 EMX3-0255B-V4-C2-H
350 A 306 A 266 A 230 A G3B EMX3-0350B-V4-C1-H 11710.00 EMX3-0350B-V4-C2-H
425 A 371 A 321 A 276 A G3B EMX3-0425B-V4-C1-H 12720.00 EMX3-0425B-V4-C2-H
500 A 445 A 383 A 326 A G4B EMX3-0500B-V4-C1-H 14320.00 EMX3-0500B-V4-C2-H
580 A 492 A 425 A 364 A G4B EMX3-0580B-V4-C1-H 15700.00 EMX3-0580B-V4-C2-H
700 A 592 A 512 A 438 A G4B EMX3-0700B-V4-C1-H 16510.00 EMX3-0700B-V4-C2-H
820 A 705 A 606 A 516 A G4B EMX3-0820B-V4-C1-H 20620.00 EMX3-0820B-V4-C2-H
920 A 804 A 684 A 571 A G4B EMX3-0920B-V4-C1-H 23830.00 EMX3-0920B-V4-C2-H
1000 A 936 A 796 A 664 A G4B EMX3-1000B-V4-C1-H 25650.00 EMX3-1000B-V4-C2-H
AC 53a: Continous operation (no internal bypass) 4)
255 A 222 A 195 A 171 A G3C EMX3-0255C-V4-C1-H 8130.00 EMX3-0255C-V4-C2-H
360 A 351 A 303 A 259 A G4C EMX3-0360C-V4-C1-H 9180.00 EMX3-0360C-V4-C2-H
380 A 380 A 348 A 292 A G4C EMX3-0380C-V4-C1-H 9320.00 EMX3-0380C-V4-C2-H
430 A 413 A 355 A 301 A G4C EMX3-0430C-V4-C1-H 12040.00 EMX3-0430C-V4-C2-H
620 A 614 A 515 A 419 A G4C EMX3-0620C-V4-C1-H 16020.00 EMX3-0620C-V4-C2-H
650 A 629 A 532 A 437 A G4C EMX3-0650C-V4-C1-H 16980.00 EMX3-0650C-V4-C2-H
790 A 790 A 694 A 567 A G4C EMX3-0790C-V4-C1-H 20790.00 EMX3-0790C-V4-C2-H
930 A 930 A 800 A 644 A G4C EMX3-0930C-V4-C1-H 23390.00 EMX3-0930C-V4-C2-H
1200 A 1200 A 1135 A 983 A G5C EMX3-1200C-V4-C1-H 24910.00 EMX3-1200C-V4-C2-H
1410 A 1355 A 1187 A 1023 A G5C EMX3-1410C-V4-C1-H 28410.00 EMX3-1410C-V4-C2-H
1600 A 1600 A 1433 A 1227 A G5C EMX3-1600C-V4-C1-H 31190.00 EMX3-1600C-V4-C2-H
Notes: 1) Representative image to aid soft starter product selection, does not constitute complete power circuit. 2) Ratings for models EMX3-0023B to EMX3-0053B are based on 10 starts per hour, equally spaced, 40 ºC
ambient. Ratings for models EMX3-0076B to EMX3-1000B and EMX3-0255C to EMX3-1600C are based on 6 starts per hour equally spaced, 40 ºC ambient.
3) Standard models with internal bypass contactor (EMX3-xxxxB) are generally stocked. 4) Intended for use in well vented enclosures and / or with external bypass contactor. Particularly suited to
applications with high overload trip class (>trip class 10) and those that may experience transient overload conditions as part of normal run time operation.
For application and duty category definitions refer to page 3 - 3. For 690 V AC applications refer to pages 3 - 18 and 3 - 19.
3 - 17
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B3’
Light
Duty
3 x FLC,
10 sec
Medium
Duty
3.5 x FLC,
15 sec
Heavy
Duty
4 x FLC,
20 sec
Severe
Duty
4.5 x FLC,
30 sec
Frame
size
110-440 V AC Control
Standard Model 3)
Cat. No. Price $
24 V AC/DC Control
Variant Model
Cat. No. Price $
AC 53b: Internal bypass contactor
34 A 30 A 26 A 22 A G1B EMX3-0023B-V4-C1-H 2550.00 EMX3-0023B-V4-C2-H
64 A 59 A 51 A 44 A G1B EMX3-0043B-V4-C1-H 2870.00 EMX3-0043B-V4-C2-H
75 A 66 A 55 A 45 A G1B EMX3-0050B-V4-C1-H 3120.00 EMX3-0050B-V4-C2-H
79 A 79 A 69 A 55 A G1B EMX3-0053B-V4-C1-H 3510.00 EMX3-0053B-V4-C2-H
114 A 96 A 83 A 70 A G1B EMX3-0076B-V4-C1-H 3690.00 EMX3-0076B-V4-C2-H
145 A 123 A 104 A 87 A G1B EMX3-0097B-V4-C1-H 4260.00 EMX3-0097B-V4-C2-H
150 A 132 A 112 A 82 A G1B EMX3-0100B-V4-C1-H 4610.00 EMX3-0100B-V4-C2-H
157 A 157 A 143 A 117 A G1B EMX3-0105B-V4-C1-H 4910.00 EMX3-0105B-V4-C2-H
217 A 184 A 159 A 136 A G2B EMX3-0145B-V4-C1-H 5610.00 EMX3-0145B-V4-C2-H
255 A 217 A 181 A 146 A G2B EMX3-0170B-V4-C1-H 5980.00 EMX3-0170B-V4-C2-H
300 A 283 A 241 A 200 A G2B EMX3-0200B-V4-C1-H 7160.00 EMX3-0200B-V4-C2-H
330 A 315 A 268 A 223 A G2B EMX3-0220B-V4-C1-H 7430.00 EMX3-0220B-V4-C2-H
382 A 346 A 302 A 264 A G3B EMX3-0255B-V4-C1-H 8650.00 EMX3-0255B-V4-C2-H
525 A 459 A 399 A 345 A G3B EMX3-0350B-V4-C1-H 11710.00 EMX3-0350B-V4-C2-H
638 A 557 A 482 A 414 A G3B EMX3-0425B-V4-C1-H 12720.00 EMX3-0425B-V4-C2-H
750 A 668 A 575 A 490 A G4B EMX3-0500B-V4-C1-H 14320.00 EMX3-0500B-V4-C2-H
870 A 738 A 637 A 546 A G4B EMX3-0580B-V4-C1-H 15700.00 EMX3-0580B-V4-C2-H
1050 A 889 A 768 A 658 A G4B EMX3-0700B-V4-C1-H 16510.00 EMX3-0700B-V4-C2-H
1230 A 1058 A 910 A 774 A G4B EMX3-0820B-V4-C1-H 20620.00 EMX3-0820B-V4-C2-H
1380 A 1206 A 1026 A 857 A G4B EMX3-0920B-V4-C1-H 23830.00 EMX3-0920B-V4-C2-H
1500 A 1404 A 1194 A 997 A G4B EMX3-1000B-V4-C1-H 25650.00 EMX3-1000B-V4-C2-H
AC 53a: Continous operation (no internal bypass) 4)
382 A 346 A 302 A 264 A G3C EMX3-0255C-V4-C1-H 8130.00 EMX3-0255C-V4-C2-H
540 A 540 A 465 A 395 A G4C EMX3-0360C-V4-C1-H 9180.00 EMX3-0360C-V4-C2-H
570 A 570 A 539 A 449 A G4C EMX3-0380C-V4-C1-H 9320.00 EMX3-0380C-V4-C2-H
645 A 645 A 552 A 464 A G4C EMX3-0430C-V4-C1-H 12040.00 EMX3-0430C-V4-C2-H
930 A 930 A 810 A 651 A G4C EMX3-0620C-V4-C1-H 16020.00 EMX3-0620C-V4-C2-H
975 A 975 A 842 A 683 A G4C EMX3-0650C-V4-C1-H 16980.00 EMX3-0650C-V4-C2-H
1185 A 1185 A 1071 A 868 A G4C EMX3-0790C-V4-C1-H 20790.00 EMX3-0790C-V4-C2-H
1395 A 1395 A 1244 A 992 A G4C EMX3-0930C-V4-C1-H 23390.00 EMX3-0930C-V4-C2-H
1800 A 1800 A 1800 A 1606 A G5C EMX3-1200C-V4-C1-H 24910.00 EMX3-1200C-V4-C2-H
2115 A 2115 A 1979 A 1671 A G5C EMX3-1410C-V4-C1-H 28410.00 EMX3-1410C-V4-C2-H
2400 A 2400 A 2400 A 2030 A G5C EMX3-1600C-V4-C1-H 31190.00 EMX3-1600C-V4-C2-H
Soft StartersEMX3 maximum motor FLC ratings 2)6 wire - 400 / 415 V AC applications 1)
Notes: 1) Representative image to aid soft starter product selection, does not constitute complete power circuit. 2) Ratings for models EMX3-0023B to EMX3-0053B are based on 10 starts per hour, equally spaced, 40 ºC
ambient. Ratings for models EMX3-0076B to EMX3-1000B and EMX3-0255C to EMX3-1600C are based on 6 starts per hour equally spaced, 40 ºC ambient.
3) Standard models with internal bypass contactor (EMX3-xxxxB) are generally stocked. 4) Intended for use in well vented enclosures and / or with external bypass contactor. Particularly suited
to applications with high overload trip class (>trip class 10) and those that may experience transient overload conditions as part of normal run time operation.
For application and duty category definitions refer to page 3 - 3. For 690 V AC applications refer to pages 3 - 18 and 3 - 19.
Scan the QR code to view EMX3
brochure.
3 - 18
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘B3’
Soft StartersEMX3 maximum motor FLC ratings 2)3 wire - 690 V AC applications 1)
Light
Duty
3 x FLC,
10 sec
Medium
Duty
3.5 x FLC,
15 sec
Heavy
Duty
4 x FLC,
20 sec
Severe
Duty
4.5 x FLC,
30 sec
Frame
size
110-440 V AC Control
Standard Model 3)
Cat. No. Price $
24 V AC/DC Control
Variant Model
Cat. No. Price $
AC 53b: Internal bypass contactor
23 A 20 A 17 A 15 A G1B EMX3-0023B-V7-C1-H 2860.00 EMX3-0023B-V7-C2-H
43 A 37 A 31 A 26 A G1B EMX3-0043B-V7-C1-H 3210.00 EMX3-0043B-V7-C2-H
50 A 44 A 37 A 30 A G1B EMX3-0050B-V7-C1-H 3500.00 EMX3-0050B-V7-C2-H
53 A 53 A 46 A 37 A G1B EMX3-0053B-V7-C1-H 3910.00 EMX3-0053B-V7-C2-H
76 A 64 A 55 A 47 A G1B EMX3-0076B-V7-C1-H 4110.00 EMX3-0076B-V7-C2-H
97 A 82 A 69 A 58 A G1B EMX3-0097B-V7-C1-H 4740.00 EMX3-0097B-V7-C2-H
100 A 88 A 74 A 61 A G1B EMX3-0100B-V7-C1-H 5130.00 EMX3-0100B-V7-C2-H
105 A 105 A 95 A 78 A G1B EMX3-0105B-V7-C1-H 5490.00 EMX3-0105B-V7-C2-H
145 A 123 A 106 A 90 A G2B EMX3-0145B-V7-C1-H 6250.00 EMX3-0145B-V7-C2-H
170 A 145 A 121 A 97 A G2B EMX3-0170B-V7-C1-H 6640.00 EMX3-0170B-V7-C2-H
200 A 189 A 160 A 134 A G2B EMX3-0200B-V7-C1-H 7980.00 EMX3-0200B-V7-C2-H
220 A 210 A 178 A 148 A G2B EMX3-0220B-V7-C1-H 8300.00 EMX3-0220B-V7-C2-H
255 A 231 A 201 A 176 A G3B EMX3-0255B-V7-C1-H 9580.00 EMX3-0255B-V7-C2-H
350 A 306 A 266 A 230 A G3B EMX3-0350B-V7-C1-H 12610.00 EMX3-0350B-V7-C2-H
425 A 371 A 321 A 276 A G3B EMX3-0425B-V7-C1-H 12720.00 EMX3-0425B-V7-C2-H
500 A 445 A 383 A 326 A G4B EMX3-0500B-V7-C1-H 15580.00 EMX3-0500B-V7-C2-H
580 A 492 A 425 A 364 A G4B EMX3-0580B-V7-C1-H 17110.00 EMX3-0580B-V7-C2-H
700 A 592 A 512 A 438 A G4B EMX3-0700B-V7-C1-H 18350.00 EMX3-0700B-V7-C2-H
820 A 705 A 606 A 516 A G4B EMX3-0820B-V7-C1-H 22990.00 EMX3-0820B-V7-C2-H
920 A 804 A 684 A 571 A G4B EMX3-0920B-V7-C1-H 26190.00 EMX3-0920B-V7-C2-H
1000 A 936 A 796 A 664 A G4B EMX3-1000B-V7-C1-H 28010.00 EMX3-1000B-V7-C2-H
AC 53a: Continous operation (no internal bypass) 4)
255 A 222 A 195 A 171 A G3C EMX3-0255C-V7-C1-H 9010.00 EMX3-0255C-V7-C2-H
360 A 351 A 303 A 259 A G4C EMX3-0360C-V7-C1-H 10090.00 EMX3-0360C-V7-C2-H
380 A 380 A 348 A 292 A G4C EMX3-0380C-V7-C1-H 10220.00 EMX3-0380C-V7-C2-H
430 A 413 A 355 A 301 A G4C EMX3-0430C-V7-C1-H 13110.00 EMX3-0430C-V7-C2-H
620 A 614 A 515 A 419 A G4C EMX3-0620C-V7-C1-H 17280.00 EMX3-0620C-V7-C2-H
650 A 629 A 532 A 437 A G4C EMX3-0650C-V7-C1-H 18400.00 EMX3-0650C-V7-C2-H
790 A 790 A 694 A 567 A G4C EMX3-0790C-V7-C1-H 22630.00 EMX3-0790C-V7-C2-H
930 A 930 A 800 A 644 A G4C EMX3-0930C-V7-C1-H 25750.00 EMX3-0930C-V7-C2-H
1200 A 1200 A 1135 A 983 A G5C EMX3-1200C-V7-C1-H 28530.00 EMX3-1200C-V7-C2-H
1410 A 1355 A 1187 A 1023 A G5C EMX3-1410C-V7-C1-H 32810.00 EMX3-1410C-V7-C2-H
1600 A 1600 A 1433 A 1227 A G5C EMX3-1600C-V7-C1-H 36460.00 EMX3-1600C-V7-C2-H
Notes: 1) Representative image to aid soft starter product selection, does not constitute complete power circuit. 2) Ratings for models EMX3-0023B to EMX3-0053B are based on 10 starts per hour, equally spaced, 40 ºC
ambient. Ratings for models EMX3-0076B to EMX3-1000B and EMX3-0255C to EMX3-1600C are based on 6 starts per hour equally spaced, 40 ºC ambient.
3) Standard models with internal bypass contactor (EMX3-xxxxB) are generally stocked. 4) Intended for use in well vented enclosures and / or with external bypass contactor. Particularly suited
to applications with high overload trip class (>trip class 10) and those that may experience transient overload conditions as part of normal run time operation.
For application and duty category definitions refer to page 3 - 3. For 400/415 V AC applications refer to pages 3 - 16 and 3 - 17.
3 - 19
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Light
Duty
3 x FLC,
10 sec
Medium
Duty
3.5 x FLC,
15 sec
Heavy
Duty
4 x FLC,
20 sec
Severe
Duty
4.5 x FLC,
30 sec
Frame
size
110-440 V AC Control
Standard Model 3)
Cat. No. Price $
24 V AC/DC Control
Variant Model
Cat. No. Price $
AC 53b: Internal bypass contactor
34 A 30 A 26 A 22 A G1B EMX3-0023B-V7-C1-H 2860.00 EMX3-0023B-V7-C2-H
64 A 59 A 51 A 44 A G1B EMX3-0043B-V7-C1-H 3210.00 EMX3-0043B-V7-C2-H
75 A 66 A 55 A 45 A G1B EMX3-0050B-V7-C1-H 3500.00 EMX3-0050B-V7-C2-H
79 A 79 A 69 A 55 A G1B EMX3-0053B-V7-C1-H 3910.00 EMX3-0053B-V7-C2-H
114 A 96 A 83 A 70 A G1B EMX3-0076B-V7-C1-H 4110.00 EMX3-0076B-V7-C2-H
145 A 123 A 104 A 87 A G1B EMX3-0097B-V7-C1-H 4740.00 EMX3-0097B-V7-C2-H
150 A 132 A 112 A 82 A G1B EMX3-0100B-V7-C1-H 5130.00 EMX3-0100B-V7-C2-H
157 A 157 A 143 A 117 A G1B EMX3-0105B-V7-C1-H 5490.00 EMX3-0105B-V7-C2-H
217 A 184 A 159 A 136 A G2B EMX3-0145B-V7-C1-H 6250.00 EMX3-0145B-V7-C2-H
255 A 217 A 181 A 146 A G2B EMX3-0170B-V7-C1-H 6640.00 EMX3-0170B-V7-C2-H
300 A 283 A 241 A 200 A G2B EMX3-0200B-V7-C1-H 7980.00 EMX3-0200B-V7-C2-H
330 A 315 A 268 A 223 A G2B EMX3-0220B-V7-C1-H 8300.00 EMX3-0220B-V7-C2-H
382 A 346 A 302 A 264 A G3B EMX3-0255B-V7-C1-H 9580.00 EMX3-0255B-V7-C2-H
525 A 459 A 399 A 345 A G3B EMX3-0350B-V7-C1-H 12610.00 EMX3-0350B-V7-C2-H
638 A 557 A 482 A 414 A G3B EMX3-0425B-V7-C1-H 12720.00 EMX3-0425B-V7-C2-H
750 A 668 A 575 A 490 A G4B EMX3-0500B-V7-C1-H 15580.00 EMX3-0500B-V7-C2-H
870 A 738 A 637 A 546 A G4B EMX3-0580B-V7-C1-H 17110.00 EMX3-0580B-V7-C2-H
1050 A 889 A 768 A 658 A G4B EMX3-0700B-V7-C1-H 18350.00 EMX3-0700B-V7-C2-H
1230 A 1058 A 910 A 774 A G4B EMX3-0820B-V7-C1-H 22990.00 EMX3-0820B-V7-C2-H
1380 A 1206 A 1026 A 857 A G4B EMX3-0920B-V7-C1-H 26190.00 EMX3-0920B-V7-C2-H
1500 A 1404 A 1194 A 997 A G4B EMX3-1000B-V7-C1-H 28010.00 EMX3-1000B-V7-C2-H
AC 53a: Continous operation (no internal bypass) 4)
382 A 346 A 302 A 264 A G3C EMX3-0255C-V7-C1-H 9010.00 EMX3-0255C-V7-C2-H
540 A 540 A 465 A 395 A G4C EMX3-0360C-V7-C1-H 10090.00 EMX3-0360C-V7-C2-H
570 A 570 A 539 A 449 A G4C EMX3-0380C-V7-C1-H 10220.00 EMX3-0380C-V7-C2-H
645 A 645 A 552 A 464 A G4C EMX3-0430C-V7-C1-H 13110.00 EMX3-0430C-V7-C2-H
930 A 930 A 810 A 651 A G4C EMX3-0620C-V7-C1-H 17280.00 EMX3-0620C-V7-C2-H
975 A 975 A 842 A 683 A G4C EMX3-0650C-V7-C1-H 18400.00 EMX3-0650C-V7-C2-H
1185 A 1185 A 1071 A 868 A G4C EMX3-0790C-V7-C1-H 22630.00 EMX3-0790C-V7-C2-H
1395 A 1395 A 1244 A 992 A G4C EMX3-0930C-V7-C1-H 25750.00 EMX3-0930C-V7-C2-H
1800 A 1800 A 1800 A 1606 A G5C EMX3-1200C-V7-C1-H 28530.00 EMX3-1200C-V7-C2-H
2115 A 2115 A 1979 A 1671 A G5C EMX3-1410C-V7-C1-H 32810.00 EMX3-1410C-V7-C2-H
2400 A 2400 A 2400 A 2030 A G5C EMX3-1600C-V7-C1-H 36460.00 EMX3-1600C-V7-C2-H
Soft StartersEMX3 maximum motor FLC ratings 2)6 wire - 690 V AC applications 1)
Notes: 1) Representative image to aid soft starter product selection, does not constitute complete power circuit. 2) Ratings for models EMX3-0023B to EMX3-0053B are based on 10 starts per hour, equally spaced, 40 ºC
ambient. Ratings for models EMX3-0076B to EMX3-1000B and EMX3-0255C to EMX3-1600C are based on 6 starts per hour equally spaced, 40 ºC ambient.
3) Standard models with internal bypass contactor (EMX3-xxxxB) are generally stocked. 4) Intended for use in well vented enclosures and / or with external bypass contactor. Particularly suited
to applications with high overload trip class (>trip class 10) and those that may experience transient overload conditions as part of normal run time operation.
For application and duty category definitions refer to page 3 - 3. For 400/415 V AC applications refer to pages 3 - 16 and 3 - 17.
Scan the QR code to view EMX3
brochure.
3 - 20
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price $Cat. No.Optional extras
Soft starters EMX3 series technical / ordering details
Note: 1) Two parallel connected fuses required per phase. 2) Fuse selection is based on a 400 % FLC start for 20 seconds in conjunction with standard published starts
per hour, duty cycle, 40 °C ambient temperature and up to 1000 m altitude. For installations operating outside these conditions, consult NHP.
170H1007
170H3003
170H3004
Refer NHP
PIM-MB-01
PIM-MT-01
PIM-DN-01
PIM-PB-01
PIM-PN-01
PIM-EI-01
PIM-USB-01
995-04803-00
995-04804-00
995-08133-00
995-04938-00
995-06348-00
Fast acting semiconductor fuses (400/415 V AC applications) 1)
For model EMX3-0023B (3 required)
For model EMX3-0043B (3 required)
For models EMX3-0050B and EMX3-0053B (3 required)
For model EMX3-0076B (3 required)
For models EMX3-0097B to EMX3-0145B (3 required)
For models EMX3-0170B to EMX3-0220B (3 required)
For model EMX3-0255B (3 required)
For model EMX3-0350B (3 required)
For model EMX3-0425B (3 required)
For model EMX3-0500B (6 required)
For model EMX3-0580B (3 required)
For model EMX3-0700B (3 required)
For model EMX3-0820B (3 required)
For model EMX3-0920B (3 required)
For model EMX3-1000B (3 required)
For model EMX3-0255C (3 required)
For model EMX3-0360C (3 required)
For models EMX3-0380C and EMX3-0430C (3 required)
For models EMX3-0620C and EMX3-0650C (3 required)
For model EMX3-0790C (3 required)
For model EMX3-0930C (3 required)
For model EMX3-1200C to EMX3-1600C (3 required)
170M1314
170M1316
170M1318
170M1319
170M1321
170M2621
170M2621
170M5011
170M6011
170M6008 2)
170M6013
170M5015
170M5017
170M6017
170M6018
170M2621
170M6010
170M6011
170M6015
170M6017
170M6019 2
)
Refer NHP
Semiconductor fuse holders (1 holder per fuse)
For 170M1314 to 170M2621
For 170M5011
For 170M5015 to 170M6017
For 170M6018 and 170M6019
Fieldbus communication modules
Modbus (RTU)
Modbus (TCP)
DeviceNet
ProfiBus
ProfiNet
Ethernet IP
USB module (EMX3 to PC via USB)
Input / Output cards
2 x digital inputs, 3 x relay outputs, 1 x analogue input
Additional protection card
RTD and ground fault card
Keypad remote mount kit
Keypad (Spare part)
Finger guards (for models 0145B-0220B) 3)
3 - 21
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft starters EMX3 series technical / ordering details
Dimensions (mm) and weights (kg)
A
EMX3-0023B to EMX3-0053B
EMX3-0076B
EMX3-0097B to EMX3-0105B
EMX3-0145B to EMX3-0220B
EMX3-0255B
EMX3-0350B to EMX3-0425B
EMX3-0500B to EMX3-0580B
EMX3-0700B to EMX3-1000B
EMX3-0255C
EMX3-0360C to EMX3-0430C
EMX3-0620C to EMX3-0930C
EMX3-1200C to EMX3-1600C
156
156
156
282
424
424
433
433
390
430
430
574
B
124
124
124
250
376
376
320
640
320
320
320
500
C
295
295
295
438
440
440
640
640
417
698
698
750
D
278
278
278
380
392
392
600
600
400
522
522
727
E
192
223
223
250
298
298
297
297
284
302
302
361
kg
3.2
3.5
4.8
16
26
30.2
49.5
60
25
50.5
53.5
140
Note: For EMX3-0145B to EMX3-1600C, dimensions A and C are the unit footprint. Busbars are not included as this dimension will vary with busbar configuration.
Frame
G1B
G1B
G1B
G2B
G3B
G3B
G4B
G4B
G3C
G4C
G4C
G5C
3 - 22
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Soft starters EMX3 series specifications
Supply
Supply voltage EMX3-XXXX-V4-XX-X
Supply voltage EMX3-XXXX-V7-XX-X
Electronics supply EMX3-XXXX-XX-C1-X
EMX3-XXXX-XX-C2-X
Supply frequency
Control inputs
Start (Terminals C23, C24)
Stop (Terminals C31, C32)
Reset (Terminals C41, C42)
Programmable input A (Terminals C53, C54)
Programmable input B (Terminals C63, C64)
Outputs
Run output
Programmable output A (Terminals 13, 14)
Programmable output B (Terminals 31, 32, 34)
Programmable output C (Terminals 41, 42, 44)
Analogue output (Terminals B10, B11)
Sundry
Enclosure rating EMX3-0023B ~ EMX3-0105B
Enclosure rating EMX3-0145B ~ EMX3-1000B
Enclosure rating EMX3-0255C ~ EMX3-1600C
Rated insulation voltage to earth
Rated impulse withstand voltage
Form designation
EMC emissions
Operating temperatures
Relative humidity
Standards / approvals
CE
UL/C-UL
CCC
C
Marine
RoHS
200 V AC ~ 440 V AC (± 10 %)
380 V AC ~ 690 V AC (± 10 %) (earthed star supply system only)
110 ~ 220 V AC and 220 ~ 440 V AC (+ 10 % / - 15 %) (standard)
24 V AC AC/24 V DC (± 20 %) (optional)
45 Hz (50 Hz supply) to 66 Hz (60 Hz supply)
N/O, Active 24 V DC, 8 mA approx.
N/C, Active 24 V DC, 8 mA approx.
N/O or N/C, Active 24 V DC, 8 mA approx.
N/O or N/C, Active 24 V DC, 8 mA approx.
N/O or N/C, Active 24 V DC, 8 mA approx.
N/O 10 A at 250 V AC resistive
5 A at 250 V AC, AC 15 pf 0.3
N/O 10 A at 250 V AC resistive
5 A at 250 V AC, AC 15 pf 0.3
C/O 10 A at 250 V AC resistive
5 A at 250 V AC, AC 15 pf 0.3
C/O 10 A at 250 V AC resistive
5 A at 250 V AC, AC 15 pf 0.3
0-20 mA or 4-20 mA
IP 20
IP 00
IP 00
600 V AC
4 kV
Bypassed or continuous, semiconductor motor starter Form 1
IEC 60947-4-2 Class B
40 ºC, max 60 ºC with derating
5 % to 95 %
IEC 60947-4-2
UL 508
GB 14048-6
IEC 60947-4-2
Lloyds Marine No 1 Specification
Compliant with EU Directive 2002/95/EC
EMX3 specifications
3 - 23
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Cat. No.
Rated power
Supply voltage
Load type
Ambient temperature
Enclosure protection
EMC Filter
Display
Removable keypad
Keypad potentiometer
Overload capacity
Starting torque
Control type
Analogue inputs
Analogue outputs
Logic inputs
Logic outputs
Communication
Dynamic brake module 8)
PID function
Encoder feedback
Page reference
SINUS N (NANO)
0.4-2.2 kW
200-230 V
Internal First
environment
–
5 programmable
1 multifunction relay 1 prog logic
–
–
3 - 21
SINUS M (MICRO)
0.4-22 kW
200-230 V / 380-480 V
Internal Second
environment 2)
–
8 programmable
1 prog relay 2 prog logic
Internal
–
3 - 22
SINUS PENTA
2.2-2010 kW
380-690 V
Light (120 %) Standard (140 %) Heavy (175 %) Strong (200 %)
50 °C 1)
IP 20 / IP 54
Internal Second environment 2)
4 line backlit 7) LCD display
–
120 % / 140 % / 175 % / 200 % for 60 sec 3)
Up to 200 % for 120 sec
IFD = V/f VTC - vector torque control (open or closed loop)
FOC = Field oriented control
3 x configurable inputs 4) +10 V DC or 0 (4) - 20 mA
3 x configurable outputs 4) +10 V DC or 0 (4) - 20 mA
3 fixed 4) 5 prog (multiples possible)
2 prog relay 2 prog logic
RS 485/Modbus 5), Profibus®, DeviceNet™, Interbus, ControlNet, Ethernet
Internal 1)
3 - 24
Notes: 1) Dependant on size. 6) Enclosed versions available to IP 54. 2) First environment (Class B) filter as option. 7) Remote mount keypad option.
3) Corresponding to selected rating. 8) Requires external resistor. 4) Expandable. 5) Standard protocol.
Variable speed drives Product Selection Guide
NHP offer a wide range of Variable Speed Drives (VSD) to cover the many applications and control methods available. The selection table below provides a summary of the ratings and features of each product in the NHP range. Identify the ratings and features required for your application and select the VSD that is right for you. For additional information see the relevant pages as indicated at the bottom of the table.
If further assistance is required in selecting a VSD to suit your specific application, please contact your nearest NHP sales office.
Cat. No.
Rated power
Supply voltage
Load type
Ambient temperature
Enclosure protection
EMC Filter
Display
Removable keypad
Keypad potentiometer
Overload capacity
Starting torque
Control type
Analogue inputs
Analogue outputs
Logic inputs
Logic outputs
Communication
Dynamic brake module 8)
PID function
Encoder feedback
Page reference
Variable / constant torque
50 °C
IP 20 6)
7 segment LED
150 % for 60 sec
150 %
IFD = V/f Sensorless Vector Control
2 x analogue inputs 0-10 V DC and 4-20 mA
0-10 V DC
RS 485/Modbus 5), Profibus®, Ethernet, Interbus, DeviceNet™, Canopen, ControlNet
SINUS PENTA
2.2-2010 kW
380-690 V
Light (120 %) Standard (140 %) Heavy (175 %) Strong (200 %)
50 °C 1)
IP 20 / IP 54
Internal Second environment 2)
4 line backlit 7) LCD display
–
120 % / 140 % / 175 % / 200 % for 60 sec 3)
Up to 200 % for 120 sec
IFD = V/f VTC - vector torque control (open or closed loop)
FOC = Field oriented control
3 x configurable inputs 4) +10 V DC or 0 (4) - 20 mA
3 x configurable outputs 4) +10 V DC or 0 (4) - 20 mA
3 fixed 4) 5 prog (multiples possible)
2 prog relay 2 prog logic
RS 485/Modbus 5), Profibus®, DeviceNet™, Interbus, ControlNet, Ethernet
Internal 1)
3 - 24
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Variable speed drivesSINUS Nano
The SINUS Nano is an economical and compact micro drive by Santerno that incorporates both Sensorless Vector Control and V/f control. The digital keypad is included as standard and navigation through the menu structure is straightforward with its easy to use menu structure. The SINUS Nano is suitable for both constant and variable torque applications with automatic and manual torque boost for high inertia applications. A dwell function is included as standard which makes the drive suitable for hoisting applications. Furthermore, the SINUS Nano includes a motor auto-tuning function to ensure the drive is optimised for high performance motor operation. The SINUS Nano conforms to EMC requirements for C-Tick first environment.
--
Supplyvoltage (V)
SN 0001 2S XB K2
SN 0002 2S XB K2
SN 0003 2S XB K2
SN 0005 2S XB K2
0.4
0.75
1.5
2.2
2.5
5
8
12
Motorrating(kW)
Ratedoutputcurrent (A) Cat. No. Price $H
143
143
143
143
W
79
79
156
156
D
143
143
143
143
Dimensions (mm)
Ordering details SINUS Nano
Features at a glance:
Capacity 0.4 kW to 2.2 kW Single phase 200-230 V AC supply 2 control modes – V/f and sensorless vector control Front panel stop/start and potentiometer controls IP 20 enclosure Motor auto-tuning for increased performance PID functionality Integral EMC input filter complies with C-Tick first environment (domestic & industrial) Fixed height and depth throughout the range
Options:
Input/output chokes Communications card RS 485/Modbus Communications device for DeviceNet™/Profibus®/Ethernet/Interbus/Canopen/ControlNet
including programming cable and software
Standard Specifications:
Input voltage: Single phase 200-240 V ACControl system: Inverter frequency drive (V/f) and sensorless vector controlOverload current rating: 150 % overload capacity (for 1 minute)Protection functions: Over/undervoltage, overcurrent, inverter overheat, motor overheat, I/O phase
loss, external I/O input fault, speed command loss, hardware fault, CPU error, overload, external device fault
Frequency setting: External potentiometer, digital keypad, communication (Modbus), 0-10 V DC, 0-20 mA.
Protection: IP 20Environmental: -10 to +50 °C operational, -20 to +65 °C storage, 0 to 90 % RH non-condensing
WattLoss (w)
7
25
48
73
3 - 25
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Variable speed drivesSINUS Micro
Features at a glance: Capacity 0.4 kW to 22 kW Single/three phase 200-230 V AC and three
phase 380-480 V AC supply V/f and sensorless vector control modes Built-in RS 485/Modbus IP 20 enclosure Motor auto-tuning for increased performance PID functionality Fire mode for HVAC applications Internal fan control
Integral EMC input filter complies with C-Tick second environment (industrial) optional first environment EMC filter available
Integrated braking unitOptions:
EMC filters for first environment (domestic) Input/output chokes Braking resistors Remote mounting keypad Full range of high-level communications
available
The SINUS Micro is a fully featured compact drive with the smallest sized footprint in its class. With Sensorless Vector Control and V/f control for both constant and variable torque applications, plus the addition of manual and automatic torque boost, this drive is suitable for all types of applications. Extremely easy to use, the SINUS Micro is compatible with the Remote Drive software and complies with EMC requirements.
Standard Specifications:
Input voltage: Single/three phase 200-240 V AC and three phase 380-480 V AC Control system: Inverter frequency drive (V/f) and sensorless vector controlOverload current rating: 150 % overload capacity (for 1 minute)Dynamic braking: 20 % without brake resistor. Average 150 % with external brake resistorProtection functions: Over/undervoltage, overcurrent, inverter overheat, motor overheat,
external I/O input fault, I/O phase loss, speed command loss, ground fault current detection, output phase open, fan trip, hardware fault, overload, communication error
Frequency setting: Digital keypad, communication - Modbus/Fieldbus (option) 0-10 V DC, 0-20 mA. Protection: IP 20Environmental: -10 to +50 °C operational, -20 to +65 °C storage, 0 to 90 % RH non-condensing
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
200-240, 1/3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
380-480, 3 phase
Supplyvoltage (V)
SM 0001 2ST BA2K2
SM 0002 2ST BA2K2
SM 0003 2ST BA2K2
SM 0005 2ST BA2K2
SM 0007 2ST BA2K2
SM 0011 2ST BA2K2
SM 0014 2ST BA2K2
SM 0017 2ST BA2K2
SM 0020 2ST BA2K2
SM 0025 2ST BA2K2
SM 0030 2ST BA2K2
SM 0001 4T BA2K2
SM 0002 4T BA2K2
SM 0003 4T BA2K2
SM 0005 4T BA2K2
SM 0007 4T BA2K2
SM 0011 4T BA2K2
SM 0014 4T BA2K2
SM 0017 4T BA2K2
SM 0020 4T BA2K2
SM 0025 4T BA2K2
SM 0030 4T BA2K2
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
0.4
0.75
1.5
2.2
4.0
5.5
7.5
11
15
18.5
22
2.5
5
8
12
17
24
32
46
60
74
88
1.25
2.5
4
6
9
12
16
24
30
39
45
H
128
128
128
128
128
220
220
320
320
410
410
128
128
128
128
128
220
220
320
320
410
410
W
70
70
100
140
140
180
180
235
235
260
260
70
70
100
140
140
180
180
235
235
260
260
D
130
130
130
155
155
170
170
190
190
210
210
130
130
130
155
155
170
170
190
190
210
210
Motorrating(kW)
Ratedoutputcurrent (A) Cat. No. Price $
Dimensions (mm)
Ordering details SINUS Micro
WattLoss (w)
13
28
18
56
106
73
70
290
683
759
799
9
22
32
47
94
84
113
293
608
759
1019
3 - 26
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
First environment EMC filterIf compliance to the first environment is required (domestic installations) then an additional foot print EMC filter is required when using the SINUS Micro. The SINUS Nano incorporates a first environment (domestic installation) and second environment (industrial installation) EMC filter as standard.
Braking resistorsThe SINUS Micro incorporates an internal brake module which allows the connection of an external IP 55 brake resistor which may be required in applications where fast deceleration is required or where there is a high intertia load and avoids nuisance tripping caused by regeneration.
Inverter ModelSM-XXXX-XXX-BA2K2
Current Rating (A)
Dimensions (mm) L W H
Cat. No. Price $
0001-0002 2ST
0003 2ST
0005-0007 2ST
0011 2ST
0014 2ST
0001-0002 4T
0003 4T
0005-0007 4T
0011-0014 4T
5
12
20
30
50
5
6
11
30
175
177
177
266
270
175
177
177
266
SME00022ST
SME00032ST
SME00072ST
SME00112ST
SME00142ST
SME00024T
SME00034T
SME00074T
SME00144T
Inverter ModelSM-XXXX-XXX- BA2K2
Resistor Specification Watts Resistance (W) ( )
Dimensions (mm)L W H
Brake resistor Cat. No. Price $
0001 2ST
0002 2ST
0003 2ST
0005 2ST
0007 2ST
0011 2ST
0014 2ST
0001 4T
0002 4T
0003 4T
0005 4T
0007 4T
0011 4T
0014 4T
350
350
350
350
350
1100
1100
350
350
350
350
350
550
1100
200
200
200
200
200
320
320
200
200
200
200
200
195
320
RE2644200
RE2644100
RE2643560
RE2643560
RE2643560
RE3083500
RE3083500
RE2644400
RE2644400
RE2644200
RE2644200
RE2644200
RE3063750
RE3083500
Description Cat. No. Price $
MODBUS/RS485 Communications card
Door mount kit for remote keypad mounting
(includes IP 66 keypad, gasket, 3 m cable)
PC Software kit for use with Remote Drive(includes cable, USB/RS485 converter – Remote Drive software available from www.nhp.com.au/santerno)
Profibus® DP serial gateway 1)
DeviceNet™ serial gateway 1)
Ethernet serial gateway 1)
Interbus serial gateway 1)
CANOpen serial gateway 1)
ControlNet serial gateway 1)
To suit range
SN
SM
SNSM
SN 2)/SM
SN 2)/SM
SN 2)/SM
SN 2)/SM
SN 2)/SM
SN 2)/SM
WW1420000
SMDMK
SPUSB
ZZ4600030
SNMDEVNT
SNMETHNT
SNMINTBS
SNMCANOP
SNMCTLNT
Additional options
Notes: 1) Contact NHP for further information. 2) WW1420000 required for fieldbus communication when using SINUS Nano.
Variable speed drivesSINUS Nano and Micro options
77
108
147
185
190
77
107
147
186
40
40
45
60
60
40
40
45
60
35
35
35
35
35
95
95
35
35
35
35
35
68
95
30
30
30
30
30
30
30
30
30
30
30
30
13
30
200
100
56
56
56
15
15
400
400
200
200
200
75
50
To suit range
SM
SM
SM
SM
SM
SM
SM
SM
SM
To suit range
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
SM
3 - 27
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Refer catalogue ESD-C
The SINUS PENTA is the latest fully featured drive to be released by Santerno of Italy. This model boasts an extensive range of features to allow easy adaptation to a wide variety of applications while being easy to use, with a 4 line alphanumeric display with all text in plain English. All drives feature a full metal enclosure to provide robustness to suit the demands of industrial environments. In addition the metal enclosure minimises radiated EMC. The full range of drives up to 1 MW, 415 V and 2 MW, 690 V contain internal EMC filters complying with C-Tick Second Environment (Class A). With the addition of a ferrite core, the standard drive is also suitable for use in the First Environment (Class B) up to frame size S50. Further flexibility is also achieved with the inclusion of an IP 54 version for sizes up to S30 (132 kW). The IP 54 drive is a stand-alone wall mounted device which can be expanded to include a choke and additional pushbuttons and switches.
Features at a glance: Wide power and voltage range. 2.2-2010 kW, 380-690 V IP 20 and IP 54 standard solutions Selectable overload from 120 % to 200 % Built-in EMC filters to comply with for the entire range 3 year warranty Five built-in control types (see below) Regenerative/Active front end option 4 line alphanumeric display Extensive I/O configuration Fire mode solution to suit HVAC application Zero speed Fluxing (in VTC mode) Wide range of options available Integral brake chopper up to 132 kW ModBus RTU communications standard Optional fieldbus for all major protocols Cabinet solution available PC communication software with internet connectivity Extensive fault history record Safety stop function to IEC 61800-5-2
Options (see pages 3 - 35 and 3 - 44) EMC filter conforming to C-Tick
first environment Dynamic braking resistors AC line choke Output choke Semiconductor fuses
Keypad mounting kit I/O expansion cards Encoder cards PC software and cables Communication and fieldbus
cards Harmonic filters
Variable speed drives for AC motorsIntroduction to SINUS PENTA
PENTA – Five integrated control functions
The SINUS PENTA incorporates five built-in control functions to accommodate a wide range of applications. This allows the one product to be adapted to many types of control philosophies and therefore provide the best performance for your application. These include the following functions.
IFD = Inverter Frequency DriveThis function offers an adjustable V/f pattern for general purpose applications.
VTC Open Loop = Vector Torque Control Open LoopThrough Sensorless Vector Direct Torque Control, the VTC function allows for improved torque performance without the need for feedback.
VTC Closed Loop = Vector Torque Control Closed LoopThe VTC function allows for fast dynamic response through encoder feedback for high torque or demanding applications.
FOC = Field Oriented ControlFOC is the ultimate in vector speed control providing high accuracy through encoder feedback for high torque precision and a wide speed range.
SYN = SynchronousThis control function provides a vector function for the control of brushless synchronous permanent magnet motors. This provides high torque accuracy combined with energy efficiency.
3 - 28
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
User friendly interfaceThe 4 line alphanumeric keypad provides clear plain English text messaging for monitoring, parameter configuration and fault annunciation making the SINUS PENTA extremely user friendly. To simplify local operation, the keypad incorporates dedicated keys for Start, Stop, direction of rotation, local/remote selection, jog and reset. These keys are in addition to the standard programming keys. Status monitoring is made easy with the use of 11 LEDs to indicate conditions such as run, alarm, direction of rotation and local control active. The keypad has built-in intelligence to enable parameters to be uploaded and downloaded directly from the keypad.
To simplify commissioning and parameters set-up, the drive has three selectable access levels. Basic level is designed for simple applications, advanced is for applications requiring additional flexibility and engineering for applications requiring full configuration. The accessible parameters are minimised to suit the control function used and the access level selected. This allows the drive to have as few as 30 parameters for basic application or as many as 500 parameters for the most sophisticated applications.
Flexible connectionThe SINUS PENTA is designed for flexibility. This flexibility is incorporated into the extensive range of I/Os available. The SINUS PENTA incorporates as standard three programmable analogue inputs and outputs. Also included are eight digital inputs, two digital outputs and two relay outputs. Inputs are programmable with the ability for dual assignment for activation of two functions simultaneously. Outputs incorporate both timing and logic for added flexibility. In addition, option boards are available to extend the number of I/Os. Having flexible inputs and outputs allows the SINUS PENTA to easily adapt to a wide range of control solutions.
ConnectivityConnectivity to a PC is possible using the "Remote Drive" software, which offers tools for the control of the drive, trending functions, setting and storage of parameters and online monitoring. Remote Drive allows the added benefit of providing a remote communication service by using a simple internet connection. The remote drive software and chat line allows fast communication between the inverter’s user and our engineers.Extensive connectivity is achieved by the use of a wide range of communication interfaces available. The drive incorporates Modbus-RTU and RS 485 as standard and with the addition of an option board, which can be mounted within the drive, all the other major fieldbus protocols can be accommodated such as Profibus DP, DeviceNet, CanBus, Interbus, Ethernet and many more currently in development.
Robust constructionThe SINUS PENTA range are designed for robustness to meet the demands of industrial applications. The complete series includes a full metal enclosure for durability. The robustness extends to the full system. With a high level of quality and reliability as well as strict adherence to international standards such as ISO 9001, Santerno is able to offer a three year warranty. This dependability provides the confidence that the drive can meet the challenge of demanding applications.
IP 54 solutionFor many applications it is advantageous to install the drive directly on a machine, close to the motor, or on a wall. For this reason a higher enclosure protection is required. The SINUS PENTA is available in sizes up to 132 kW providing an economical and convenient solution. This solution is particularly suited to HVAC applications, irrigation, the food industry or applications requiring dispersed motor control. The robust IP 54 frame provides a removable gland plate, space to mount additional components if required and the ability to add additional controls to the front of the drive. For applications requiring the addition of a choke, a dedicated IP 54 option can be added to the drive construction.
Enclosed systemsBy calling on the extensive range of options and products available an enclosed drive package can be tailored to suit the specific requirements of an application. The system can be customised to include options such as contactors, chokes, semiconductor fuses, dynamic braking solutions, communications options and many more. Please contact your NHP representative to discuss your specific requirements.
Variable speed drives for AC motorsIntroduction to SINUS PENTA
3 - 29
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
First Environment Environment that includes domestic premises, or establishments directly connected without intermediate transformers to a low-voltage power supply network which supplies buildings used for domestic purposes.
Second Environment Environment that includes all establishments than those directly connected to a low-voltage power supply network which supplies buildings used for domestic purposes.
PDS of Category C1
PDS of rated voltage less than 1000 V, intended for use in the first environment.
PDS of Category C2 PDS of rated voltage less than 1000 V, which is neither a plug-in service nor a movable device and, when used in the first environment, is intended to be installed and commissioned only by a professional.
PDS of Category C3 PDS of rated voltage less than 1000 V, intended for use in the second environment.
PDS of Category C4 PDS of rated voltage equal or above 1000 V, or rated current equal or above 400 A, or intended for use in complex systems in the second environment.
Below are the AS 61800-3 2005 definitions on emission limits: (PDS = power drive system)
EMC Requirements
EMI (Electromagnetic Interference) is normally caused by commutations in many devices. The high frequency interference can affect the operation of other devices and can create noises in measurement and communication systems. All these combined effects can create unexpected breakdowns. Two areas can be affected by the above: immunity and emissions.
AS 61800-3 is the product-specific drives standard that defines both immunity and emission levels required for those devices designed to operate in different environments. The SINUS PENTA range is designed to operate under different conditions, therefore they are all provided with a strong immunity against RFI that allows them to be reliable in all environments. Furthermore the complete range of drives in the SINUS PENTA series are C-Tick approved with integral EMC filters and conform to category C3 for the Second Environment. With the addition of a ferrite core, the drives can comply to category C1 for the First Environment. To simplify installation of analogue signals screen terminations are also included as standard.
Variable speed drives for AC motors Introduction to SINUS PENTA
Engineered solutions
For applications requiring more specialised solutions, Engineered systems can be developed. Solutions that are available include 12 or 18 pulse input configuration for reduced harmonic distortion and fully regenerative solutions to allow regenerated energy to be fed back to the supply. Special application software is also available to fulfill the requirements of specific applications such as multi-pump control, servo-diameters, axis control and positioning applications. These applications can be loaded into a standard SINUS PENTA drive. For further details on these specialised areas please contact NHP.
3 - 30
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Step 8Step 7
Step 3
Step 5 Step 6
Variable speed drives for AC motorsDrive selection
Selection of a SINUS PENTA variable drive system is
extremely simple by following the steps shown below:
Step 1 Step 2Using the application overload table on section 3 - 28 identify your application which matches closest with those shown in the list. Once an application has been selected, identify the correct overload rating based on the location of the mark. If unsure, contact NHP.If two overload ratings are selected, choose the overload rating that best suits your application.
For 380-500 V AC drives, based on your drive model selection from step 2 and using the table on page 3 - 30, identify the correct part number and price in either IP 20/00 or IP 54 (to 132 kW) models.OR
For 660-690 V AC drives, use the table on page 3 - 40 to identify the correct part number and price in IP 20/00 models.
From the selection table on page 3 - 29, identify the column that contains the selected overload rating from step 1 and choose the 380-500 V AC drive model that matches or exceeds your motor full load current.OR
From the selection table on page 3 - 40 use the same process to select your 660-690 V AC drive model.
For 380-500 V AC drives, contact NHP for first environment EMC filters for use in domestic installations, input semi-conductor fuses + accessories to protect the drive in the event of short circuit upstream of the drive on page 3 - 33. OR
For 575-690 V AC drives and optional first environment filters and fuses + accessories, contact NHP.
For 380-500 V AC and 575-690 V AC drives, select optional braking resistors and braking units (>S40) using the selection table on page 3 - 34 and then view technical details and pricing on table 3 - 35.
For additional information:• 380-500 V AC selection
table including isolators, contactors, etc. on pages 3 - 36 to 3 - 39
• Multipump application page 3 - 42
• Regenerative application page 3 - 43
For all SINUS PENTA drives, refer to page 3 - 44 for details on options such as fieldbus communications, remote door mount kits, harmonic filters, etc.
Step 4 For 380-500 V AC drives, select optional input/output chokes on page 3 - 32 based on the drive size – e.g. SP0014, and available in IP 20 and IP 54 versions. For long cable runs and drives >S50, input and output chokes are recommended.OR
For 575-690 V AC drives, select input/output chokes on page 3 - 41.
3 - 31
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Application Light Standard Heavy Strong
Agitator
Atomiser
Axis control
Bottle washer
Calenders
Centrifuge
Chipper
Compressor – piston (loaded)
Compressor – piston (unloaded)
Compressor – screw (loaded)
Compressor – screw (unloaded)
Conveyor – belt
Conveyor – roller
Conveyor – screw
Crusher – cone
Crusher – jaw
Crusher – rotary
Crusher – vertical impact
Debarker
Drawplates
Drill
Dryer
Dust collector
Edger
Elevator
Extruder
Fan – axial (damped)
Fan – axial (undamped)
Fan – centrifugal (damped)
Fan – centrifugal (undamped)
Fan – high pressure
Forming machine
Grinder
Application Light Standard Heavy Strong
Hoist/crane
Hydraulic power pack
Injection moulding – screw
Injection moulding – hydraulic power pack
Loom
Mill – ball
Mill - hammer
Mill - roller
Mixer
Paint stirrer Palletiser
Planer
Press
Pulper
Pump – bore
Pump – centrifugal
Pump – positive displacement/ submersible
Pump – slurry
Rotary table
Sander
Saw – band
Saw – Circular
Shears
Separator
Shredder
Slicer
Spinner
Tumbler
Vibrating screen
Washer – industrial
Winding/Unwinding
Variable speed drives
Typical application overload requirements
Light up to 120 % overload
Standard up to 140 % overload
Heavy up to 175 % overload
Strong up to 200 % overload
3 - 32
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
IpeakCat. No.Size kW A kW A kW A kW A A A
Inom = Inverter nominal continuous current ratingImax = Inverter maximum current for 120 sec every 20 min up to S30 and 60 sec every 10 min all other sizes1 peak = Inverter maximum current for 30 sec
Light Standard Heavy Strong Inom Imax
S15 1)
S05 1)
Variable speed drives SINUS PENTA Range and selection
Power Supply 380-415 V AC
S12 1)
S20 1)
S30 1)
S60
S65 2)
4.5 9 4 8.4 3 6.4 2.2 4.9 10.5 11.5 14 5.5 11.2 4.5 9 4 8.4 3 6.4 12.5 13.5 167.5 14.5 5.5 11.2 4.5 9 4 8.4 16.5 17.5 197.5 14.8 7.5 14.8 5.5 11.2 4.5 9 16.5 21 257.5 14.8 7.5 14.8 7.5 14.8 5.5 11.2 16.5 25 30
11 21 9 18 9 18 7.5 15 27 30 3615 29 11 21 9 18 7.5 15 30 32 3715 29 15 29 11 21 9.2 18 30 36 4322 41 18.5 35 15 29 11 21 41 48 5822 41 22 41 18.5 35 15 29 41 56 6730 55 25 46 22 41 18.5 35 57 63 76
30 55 30 55 25 46 22 41 60 72 8637 67 30 55 25 46 22 41 72 80 8845 80 37 67 30 55 25 46 80 96 115
50 87 45 80 37 67 30 55 88 112 13455 98 55 98 45 80 32 59 103 118 14265 114 65 114 50 87 37 67 120 144 17375 133 75 133 55 98 45 80 135 155 186
100 180 90 159 75 133 55 98 180 200 240110 191 100 180 80 144 65 114 195 215 258120 212 110 191 90 159 75 133 215 270 324132 228 132 228 110 191 90 159 240 290 324
160 273 150 264 132 228 110 191 300 340 408200 341 160 273 160 273 132 228 345 420 504220 375 220 375 185 321 150 260 375 460 552250 425 250 425 220 375 185 321 425 450 672280 480 280 480 250 421 200 341 480 600 720315 528 315 528 280 480 220 375 550 680 792 400 680 400 680 355 589 280 480 680 850 1020400 680 400 680 315 528 280 480 720 880 1056450 765 450 765 355 589 315 528 800 960 1152
500 841 500 841 400 680 355 589 900 1100 1320560 939 560 939 500 841 400 680 1000 1300 1560710 1200 630 1080 560 939 450 765 1200 1440 1728
900 1480 800 1334 710 1200 560 939 1480 1780 21361000 1646 900 1480 800 1334 710 1200 1700 2040 24481170 1950 1100 1874 900 1480 800 1334 1950 2340 3024
Light up to 120 % overloadStandard up to 140 % overload
Heavy up to 175 % overloadStrong up to 200 % overload
Note: 1) Available in IP 54 version 2) Require input and output chokes 3) NHP standard model
SP 0005 4TBA2K2SP 0007 4TBA2K2SP 0009 4TBA2K2SP 0011 4TBA2K2SP 0014 4TBA2K2SP 0016 4TBA2K2SP 0017 4TBA2K2SP 0020 4TBA2K2SP 0025 4TBA2K2SP 0030 4TBA2K2SP 0034 4TBA2K2SP 0036 4TBA2K2SP 0040 4TBA2K2SP 0049 4TBA2K2SP 0060 4TBA2K2SP 0067 4TBA2K2SP 0074 4TBA2K2SP 0086 4TBA2K2SP 0113 4TBA2K2SP 0129 4TBA2K2SP 0150 4TBA2K2SP 0162 4TBA2K2SP 0180 4TXA2KOSP 0202 4TXA2K0SP 0217 4TXA2K0SP 0260 4TXA2K0SP 0313 4TXA2K0SP 0367 4TXA2K0SP 0402 4TXA2K0SP 0457 4TXA2K0SP 0524 4TXA2K0SP 0598 4TXA2K0SP 0748 4TXA2K0SP 0831 4TXA2K0SP 0964 4TXA2K0SP 1130 4TXA2K0SP 1296 4TXA2K0
Catalogue Number Construction
Range
S = SINUS 3)SB = SINUS BOXSC = SINUS CABINET
Voltage rating
2 = 200-240 V4 = 380-500 V 3)5 = 500-575 V6 = 575-690 V
EMC Filter
I = NoneA1 = First env. category C2A2 = Second env. 3) category C3 B = First env. category C1
IP Rating
0 = IP 002 = IP 203 = IP 24-314 = IP 425 = IP 54C = Air Cond.
Drive size Brake chopper
X = NoneB = Integral
Keypad
X = NoneK = Integral 3)Power supply
T = Three phase 3)S = Single phaseC = DC FedD = 12 Pulse input
Model
PENTA 3)
S P 0005 4 T B A2 K 2
S41
S75 2)
S51
3 - 33
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Variable speed drivesSINUS PENTA - 380-415 V IP 20 / IP 00
S20
S05
S75
S15
S05
Ordering details
S12
S20
S30
S60
S65
1980
225
170
215
279
302
890
980
1400
466
340
401
610
748
1310
1400
560
331
175
225
332
421
530
560
IP 00
IP 20
IP 20
IP 20
IP 20
IP 20
IP 00
IP 00
Size WDimensions (mm)
H D IP Rating WeightLosses at Inom (W) Cat No. Price $
77777
10.510.510.511.511.512.512.522.522.53636363651515151117117121121141141141260260440440440550550550
2152403153153154304904905205206807108209501050125013501500215023002450270025503200345039504400490063007400840097501075012900154001700018600
SP 0005 4TBA2K2
SP 0007 4TBA2K2
SP 0009 4TBA2K2
SP 0011 4TBA2K2
SP 0014 4TBA2K2
SP 0016 4TBA2K2
SP 0017 4TBA2K2
SP 0020 4TBA2K2
SP 0025 4TBA2K2
SP 0030 4TBA2K2
SP 0034 4TBA2K2
SP 0036 4TBA2K2
SP 0040 4TBA2K2
SP 0049 4TBA2K2
SP 0060 4TBA2K2
SP 0067 4TBA2K2
SP 0074 4TBA2K2
SP 0086 4TBA2K2
SP 0113 4TBA2K2
SP 0129 4TBA2K2
SP 0150 4TBA2K2
SP 0162 4TBA2K2
SP 0180 4TXA2K0
SP 0202 4TXA2K0
SP 0217 4TXA2K0
SP 0260 4TXA2K0
SP 0313 4TXA2K0
SP 0367 4TXA2K0
SP 0402 4TXA2K0
SP 0457 4TXA2K0
SP 0524 4TXA2K0
SP 0598 4TXA2K0
SP 0748 4TXA2K0
SP 0831 4TXA2K0
SP 0964 4TXA2K0
SP 1130 4TXA2K0
SP 1296 4TXA2K0
S41
S51
500 882 409 IP 00
578 882 409 IP 00
Frame S41 & S51: no more pre-charge bypass contactor and resistor offers you improved reliability compared to traditional pre-charge systems. Check availability with NHP.
NEW
3 - 34
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
S30
S05
S15
S05
Ordering details
S12
S20
S30
288
214
250
339
359
715
577
622
842
1008
366
227
268
366
460
IP 54
IP 54
IP 54
IP 54
IP 54
SizeWDimensions (mm)
H D IP Rating Weight Losses at Inom (W) Cat No. Price $
15.715.715.715.715.722.322.322.323.323.324.324.34040
54.254.2575776767676
21524031531531535038042052552568071082095010501250135015002150230024502700
SP 0005 4TBA2K5
SP 0007 4TBA2K5
SP 0009 4TBA2K5
SP 0011 4TBA2K5
SP 0014 4TBA2K5
SP 0016 4TBA2K5
SP 0017 4TBA2K5
SP 0020 4TBA2K5
SP 0025 4TBA2K5
SP 0030 4TBA2K5
SP 0034 4TBA2K5
SP 0036 4TBA2K5
SP 0040 4TBA2K5
SP 0049 4TBA2K5
SP 0060 4TBA2K5
SP 0067 4TBA2K5
SP 0074 4TBA2K5
SP 0086 4TBA2K5
SP 0113 4TBA2K5
SP 0129 4TBA2K5
SP 0150 4TBA2K5
SP 0162 4TBA2K5
Variable speed drives
Price Schedule ‘M5’
3 - 35
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Input and output choke - 380-415 V
Input choke:
When installing a VSD of size S40 (230 kW) or less, a choke is recommended in the following situations:
to reduce the impact of mains instability to reduce harmonics to protect against the effects of switching devices on the mains to improve wave shape
For sizes S50 and above, it is recommended to always use a line reactor (choke) unless a dedicated transformer is used. DC chokes are available on request.
Output choke:
When installing a VSD of size S40 (230 kW) or less, an output choke is recommended in the following situations:
Long motor output cables Reduce reflected waves Reduce dV/dt to the motor When multiple motors are connected to one VSD
For sizes S50 and above, it is recommended to always use an output reactor (choke).
IP 54 ChokeA separate choke is available in IP 54, specifically designed to integrate into the IP 54 VSD solution. This choke fits under the drive to allow for connections. The choke can be used on either the input or output side of the drive.
Ordering details 380-415 V Chokes IP 20/ IP 00
Ordering details 380-415 V Chokes IP 54
Variable speed drivesInput and output choke
m
S05 - S12
S15 - S30
S40
S50 - S75
30 60 90 120 150 >150
2-4-6 pole motorsMotor wiring with unscreened cables
Up to S12
Up to S30
Up to S40
from S40
20 40 80 > 80 m
2-4-6 pole motorsMotor wiring with screened cables
Legend:
Output chokes are required.
Output chokes are optional
00050007-00140016-00200025-00300034-00380040-00600067-00860113-01620179-02020216-02600312-03990402-05980748-08310964-11300964-113012961296
Input & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInputOutputInputOutput
11173243689214225236241066294512602 x 9456 x 9502 x 12606 x 1250
21.270.70.70.30.240.160.090.0610.0540.0330.0230.0180.0230.0240.0180.018
120120150150180180240240300300300300300300385300385
125135175175160160210210260290290320320320430320430
7590105125150155170220220230230260260260260260260
IP 20IP 20IP 20IP 20IP 20IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00
2.935691024.524.537535367852 x 672 x 1002 x 822 x 100
2948709615018327234240750050075210702 x 7526 x 9402 x 10706 x 940
IMO126004
IM0126044
IM0126084
IM0126124
IM0126144
IM0126164
IM0126204
IM0126244
IM0126284
IM0126324
IM0126364
IM0126404
IM0126444
2 X IM0126404
6 X IMO141782
2 X IM0126444
6 X IMO141782
To suit size
SP...4T...
Suitable for
input/output
Rating
(A) (mH)
Dimensions (mm)
L H D
IP
Rating
Weight
(kg)
Losses at
Inom (W) Cat. No. Price $
00050007-00140016-00200025-00300034-00360038-00600067-00860113-0162
Input & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & OutputInput & Output
111732436892142252
2.01.270.70.70.30.240.160.09
214214214214280280310310
225225225225270270360360
214214214214244244318318
IP 54IP 54IP 54IP 54IP 54IP 54IP 54IP 54
6.57.09.51014152633
29487096150183342342
ZZ0112010
ZZ0112020
ZZ0112030
ZZ0112040
ZZ0112045
ZZ0112050
ZZ0112060
ZZ0112070
To suit size
SP...4T...
Suitable for
input/output
Rating
(A) (mH)
Dimensions (mm)
L H D
IP
Rating
Weight
(kg)
Losses at
Inom (W) Cat. No. Price $
3 - 36
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Description
To suit size
SP ---4T BA2K2 Cat. No. Price $
Semiconductor fuses are recommended to protect the rectifier in the event of a short circuit. Standard fuses and circuit breakers alone are generally not adequate due to slower switch-off times.
When used in conjunction with the internal A2 (second environment) EMC filter, this ferrite allows the VSD to be suitable for use in the First Environment (class B) for residential and commercial use. The ferrite is installed between the output of the VSD and the motor by passing the three phases through the centre of the ferrite.
Details upon request.
Dimensions (mm)
For three fuses incl. base
Accessories
Semiconductor fuses
EMC Filter for first environment
Variable speed drivesSemiconductor fuses and EMC filters
Notes: 1) One fuse required per phase. 2) Two fuses required per phase.
0005-0007
0009-0011
0014-0020
0025-0030
0034-0049
0060-0067
0074
0086
0113-0129
0150
0180
0162-0200
0202
0216-0217
0260-0313
0250-0367
0312-03990402
0457
0524
0598-0748
0831
0964
1130
1269
16 A
25 A
40 A
63 A
100 A
125 A
160 A
200 A
250 A
315 A
350 A
400 A
500 A
550 A
630 A
700 A
800 A
900 A
1000 A
1250 A
1400 A
2 x 800 A
2 x 1000 A
2 x 1250 A
2 x 1400 A
146
146
146
146
146
146
146
146
146
146
146
146205
205
205
205
205
205
205
205
205
410
410
410
410
120
120
120
120
120
120
120
120
120
120
120
120120
258
258
258
258
258
258
258
258
258
258
258
258
68
68
68
68
68
68
68
68
68
68
68
6868
104
104
104
104
104
104
104
115
115
104
104
115
20 412 04 16
20 412 04 25
20 412 20 40
20 412 20 63
20 412 20 100
20 412 20 125
20 412 20 160
20 412 20 200
20 412 20 250
20 412 20 315
20 412 20 350
20 412 20 400
20 622 32 500
20 622 32 550
20 622 32 630
20 622 32 700
20 622 32 800
20 622 32 900
20 622 32 1000
20 622 32 1250
20 632 32 1400
20 632 32 800 2)
20 632 32 1000 2)
20 632 32 1250 2)
20 632 32 1400 2)
L H D Cat. No 1) Price $RatingTo suit size SP---4T...
21 189 01
21 313 02
28 002 02
28 001 04
0005-0200
0202-+
0005-0200
0202-+
Fuse base (one per fuse, three required per drive)
Fuse base (one per fuse, three or six required per drive)
Auxiliary switch
Auxiliary switch
3 - 37
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Variable speed drives Brake resistor selection by duty cycle
SP 0005 4TBA2K2SP 0007 4TBA2K2SP 0009 4TBA2K2SP 0011 4TBA2K2SP 0014 4TBA2K2SP 0016 4TBA2K2SP 0017 4TBA2K2SP 0020 4TBA2K2SP 0025 4TBA2K2SP 0030 4TBA2K2SP 0034 4TBA2K2SP 0036 4TBA2K2SP 0040 4TBA2K2SP 0049 4TBA2K2SP 0060 4TBA2K2SP 0067 4TBA2K2SP 0074 4TBA2K2SP 0086 4TBA2K2SP 0113 4TBA2K2SP 0129 4TBA2K2SP 0150 4TBA2K2SP 0162 4TBA2K2SP 0179 4TXA2K2SP 0200 4TXA2K2SP 0216 4TXA2K2SP 0250 4TXA2K2SP 0180 4TXA2K2SP 0202 4TXA2K2SP 0217 4TXA2K2SP 0260 4TXA2K2SP 0312 4TXA2K0SP 0366 4TXA2K0SP 0399 4TXA2K0SP 0313 4TXA2K2SP 0367 4TXA2K2SP 0402 4TXA2K2SP 0457 4TXA2K0SP 0524 4TXA2K0
Built-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-inBuilt-in
2 x BU200 2 x BU200 3 x BU200 3 x BU200BU700 2-4TBU700 2-4TBU700 2-4TBU700 2-4T4 x BU2004 x BU2004 x BU200BU700 2-4TBU700 2-4TBU700 2-4T5 x BU2005 x BU200
50 - 1100 W 50 - 1100 W 50 - 1100 W 50 - 1500 W 50 - 1500 W 50 - 2200 W50 - 2200 W50 - 4000 W 25 - 4000 W 25 - 4000 W20 - 4000 W 20 - 4000 W 15 - 8000 W 10 - 12000 W10 - 12000 W 10 - 12000 W10 - 16000 W10 - 16000 W2 x 3.3 - 8000 W 1)2 x 3.3 - 8000 W 1)2 x 10 - 12000 W 2)2 x 10 - 12000 W 2)2 x 6.6 - 12000 W 3) 2 x 6.6 - 12000 W 3)3 x 6.6 - 12000 W 3)3 x 6.6 - 12000 W 3)1 x 3.6 - 32000 W1 x 3.0 - 48000 W1 x 2.8 - 48000 W1 x 2.4 - 48000 W4 x 6.6 - 12000 W 3) 4 x 6.6 - 12000 W 3)4 x 6.6 - 12000 W 3) 1 x 1.8 - 64000 W1 x 1.8 - 64000 W2 x 2.8 - 48000 W5 x 10 - 12000 W 3)5 x 10 - 12000 W 3)
RE3083500
RE3083500
RE3083500
RE3093500
RE3093500
RE3113500
RE3113500
RE3483500
RE3483250
RE3483250
RE3483200
RE3483200
RE3783150
RE4023100
RE4023100
RE4023100
RE4163100
RE4163100
RE3762330
RE3762330
RE4023100
RE4023100
RE4022660
RE4022660
RE4022660
RE4022660
RE4362360
RE4462300
RE4462280
RE4462240
RE4022660
RE4022660
RE4022660
RE4562180
RE4562180
RE4462280
RE4023100
RE4023100
50 - 4000 W50 - 4000 W50 - 4000 W50 - 4000 W50 - 4000 W50 - 8000 W50 - 8000 W50 - 8000 W20 - 12000 W20 - 12000 W20 - 16000 W20 - 16000 W15 - 24000 W15 - 24000 W10 - 24000 W10 - 24000 W2x15 - 24000 W2x15 - 24000 W6 - 64000 W6 - 64000 W5 - 64000 W5 - 64000 W3 x 10 - 24000 W 3)3 x 10 - 24000 W 3)3 x 10 - 24000 W 3)4 x 10 - 24000 W 3)1 x 6.6 - 48000 W1 x 6.0 - 64000 W1 x 5.0 - 64000 W1 x 5.0 - 64000 W4 x 10 - 24000 W 3)6 x 10 - 24000 W 3)6 x 10 - 24000 W 3)1 x 1.6 - 48000 W1 x 1.6 - 48000 W1 x 1.4 - 64000 W8 x 10 - 24000 W 3)10 x 10 - 24000 W 3)
RE3503500
RE3503500
RE3503500
RE3503500
RE3503500
RE3783500
RE3783500
RE3783500
RE4053200
RE4053200
RE4163200
RE4163200
RE4293150
RE4293150
RE4293100
RE4293100
RE4293150
RE4293150
RE4562600
RE4562600
RE4562500
RE4562500
RE4293100
RE4293100
RE4293100
RE4293100
RE4462660
RE4562600
RE4552500
RE4552500
RE4293100
RE4293100
RE4293100
RE4462160
RE4462160
RE4562140
RE4293100
RE4293100
S05
S12
S15
S20
S30
S40
S50
S60
S41
S51
Size Model
Braking
Unit Rating Cat. No.
Duty Cycle 50 % 4)
Rating Cat. No.
Duty Cycle 20 % 4)
Power Supply 380-500 V AC 5)
Notes: 1) Series connected resistors. 2) Parallel connected resistors. 3) Refer SINUS PENTA Installation Manual for correct wiring of resistors and braking unit available at www.nhp.com.au/santerno. 4) 10 % duty cycle brake resistors also available. Contact NHP for further details. 5) 200-240 V AC (2T) resistors for all duty cycles (10 %, 20 %, 50 %) also available. Contact NHP for further details. Contact NHP for 690 V drive brake resistors.
505050505050505020202015151010108.58.56655101010101.11.11.11.11010101.11.11.11010
Min.
Resistance
11111111111111111122222233111144411255
Qty.
111111111111111111111133341111466111810
Qty.
* Power supply 660 - 690 V AC
3 - 38
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Dynamic braking allows a standard VSD to fully control the operation of the motor even when the motor acts as a generator. This can be the case when fast stopping times are required or the load has a high inertia. The use of a brake resistor allows the energy produced to be consumed, to avoid an alarm condition.
Drives up to frame S30 (132 kW) come standard with an integral brake module. In order to utilise this braking function, an external resistor is required. For larger sizes an external brake unit (BU200) is required.
The resistors in the table on page 3 - 34 are rated for full braking but need to be selected based on the required duty cycle of operation. There are three selections possible. These are 10 %, 20 % and 50 % to cover the wide range of applications and requirements.
Variable speed drivesBrake resistors
Rating
W
Dimensions (mm)
L H D
IP
Rating Cat. No. Price $
Description To suit Cat. No. Price $
Accessories
Adjustable thermal probe
BU200 380-500 V AC
BU1440 380-500 V AC
BU720 660-690 V AC
BU1440 660-690 V AC
BU700 380-500 V AC
IP 23 Resistors
S40-S60
S65+
S65
S65-S80
S41+S51
WW0030460
ZZ0063010
ZZ0063040
ZZ0063050
ZZ0063072
ZZ0063020
Ordering details
50 - 1100 W
50 - 1500 W
50 - 2200 W
15 - 4000 W
20 - 4000 W
25 - 4000 W
50 - 4000 W
50 - 4000 W
3.3 - 8000 W
10 - 8000 W
50 - 8000 W
6.6 - 12000 W
10 - 12000 W
20 - 12000 W
15 - 16000 W
10 - 24000 W
0.8 - 64000 W
1.2 - 48000 W
1.6 - 48000 W
6 - 48000 W
0.8 - 64000 W
1.2 - 64000 W
1.6 - 64000 W
2.4 - 64000 W
5 - 64000 W
IP 55
IP 54
IP 54
IP 20
IP 20
IP 20
IP 20
IP 23
IP 20
IP 20
IP 23
IP 20
IP 20
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
IP 23
320
320
380
620
620
620
620
650
620
620
650
620
620
650
650
650
650
650
650
650
650
650
650
650
650
95
120
196
100
100
100
100
320
160
160
380
200
200
460
550
750
990
750
750
750
990
990
990
990
990
30
40
67
250
250
250
250
375
250
250
375
250
250
375
375
375
730
730
730
730
730
730
730
730
730
RE3083500
RE3093500
RE3113500
RE3483150
RE3483200
RE3483250
RE3483500
RE3503500
RE3762330
RE3763100
RE3783500
RE4022660
RE4023100
RE4053200
RE4163150
RE4293100
RE4561800
RE4462120
RE4462160
RE4462600
RE4561800
RE4562120
RE4562160
RE4562240
RE4562500
Price Schedule ‘M5’
0800 NHP NHP nhp-nz.com1300 NHP NHP nhp.com.au
Service Team
Our dedicated Service Team are on call, easy
to access, and are importantly experts in their
own right, able to understand the challenges
which need to be worked through to compete
and be successful in the global market.
Take the guesswork out of your project.
Think Sales Service and Support. Think NHP.
THINK SALES SERVICE AND SUPPORT. THINK NHP.NHP has the largest product management, technical and engineering support and sales team in the Australasian electrical industry available 24 hours a day, 7 days a week, 365 days a year.
3 - 40
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
0016 0017 0020 0025 0030 0034 0036
11 15 15 22 22 30 30
21 29 29 41 41 55 55
9 11 15 18.5 22 25 30
18 21 29 35 41 46 55
9 9 11 15 18.5 22 25
18 18 21 29 35 41 46
7.5 7.5 9.2 11 15 18.5 22
15 15 18 21 29 35 41
40 A 63 A 100 A
DTCB6340D DTCB6363D S125GJ/100
40 A 63 A 100 A
SLB40P3P SLB63P3P SLB100P3P
40 A 63 A 100 A
204122040 204122063 2041220100
65 A AC 1 100 A AC 1
CA 7-30 CA 7-60
32 A, 0.7 mH 43 A, 0.51 mH 68 A, 0.3 mH
IMO126084 IMO126124 IMO126144
32 A 64 A
AC1810302 AC1810402
50 , 2200 W 50 , 25 , 4000 W 15 , 4000 W 4000 W
RE3113500 RE3483500 RE3483250 RE3483150
50 , 8000 W 20 , 12000 W 20 ,16000 W
RE3783500 RE4053200 RE4163200
0005 0007 0009 0011 0014
4.5 5.5 7.5 7.5 7.5
9 11.2 14.5 14.8 14.8
4 4.5 5.5 7.5 7.5
8.4 9 11.2 14.8 14.8
3 4 4.5 5.5 7.5
6.4 8.4 9 11.2 14.8
2.2 3 4 4.5 5.5
4.9 6.4 8.4 9 11.2
16 A 25 A 32 A
DTCB6316D DTCB6325D DTCB6332D
20 A 25 A 32 A
SLB20P3P SLB25P3P SLB32P3P
16 A 25 A 40 A
204120416 204120425 204122040
32 A AC 1
CA 7-9
11 A, 2.0 mH 17 A, 1.27 mH
IMO126004 IMO126044
32 A
AC1810302
50 , 1100 W 50 , 1500 W
RE3083500 RE3093500
50 , 4000 W
RE3503500
380-415 V 50 HzS05 S12
Cat. No.SP_____4T BA2K2
Power (kW)
Current (A)
Power (kW)
Current (A)
Power (kW)
Current (A)
Power (kW)
Current (A)
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating and selection chart
Standard duty rating (140 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Light duty rating (120 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Heavy duty rating (175 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Strong duty rating (200 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Recommended circuit breaker
Isolator switch
Recommended line contactor (Refer to Part A, section 1 for more information)
Input/output choke
Output EMC ferrite ring (for compliance to the first environment in addition to the built-in A2 filter)
Semi-conductor fuses
Dynamic brake resistor - 50 % duty cycle
Dynamic brake resistor - 20 % duty cycle
3 - 41
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
0113 0129 0150 0162
100 110 120 132
180 191 212 228
90 100 110 132
159 180 191 228
75 80 90 110
133 144 159 191
55 65 75 90
98 114 133 159
250 A 400 A
S250GJ/250 S400NJ/400
250 A 315 A 400 A
SLB2503P SLB3153P SLB4003P
250 A 315 A 400 A
2041220250 2041220315 2041220400
250 A AC1 350 A AC1
CA 6-140 CA 6-210
252 A, 0.09 mH
IM0126244
180 A 375 A
AC1810604 AC1811004
2 x 3.3 , 8000 W 2 x 10 , 12000 W
2 x RE3762330 2 x RE4023100
6 , 64000 W 5 , 64000 W
RE4562600 RE4562500
0040 0049 0060 0067 0074 0086
37 45 50 55 65 75
67 80 87 98 114 133
30 37 45 55 65 75
55 67 80 98 114 133
25 30 37 45 50 55
46 55 67 80 87 98
22 25 30 32 37 45
41 46 55 59 67 80
100 A 125 A 160 A
S125GJ/100 S125GJ/125 S160GJ/160
100 A 125 A 125 A 160 A 200 A
SLB100P3P SLB1253P SLB1253P SLB1603P SLB2003P
100 A 125 A 160 A 200 A
2041220100 2041220125 2041220160 2041220200
100 A AC1 160 A AC1
CA 7-60 CA 6-95
92 A, 0.24 mH 92 A, 142 A, 0.16 mH 0.24 mH
IM0126164 IM0126164 IM0126204
155 A 155 A
AC1810603 AC1810603
15 , 8000 W 10 , 12000 W 10 , 12000 W 10 , 16000 W
RE5783150 RE4023100 RE4023100 RE4163100
15 , 24000 W 10 , 24000 W 2 x 15 24000 W
RE4293150 RE4293100 RE4293150
S15 S20 S30
3 - 42
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
1 x 6.6 , 48000 W
1 x 6.0 , 64000 W
1 x 5.0 , 64000 W
1 x 1.6 , 48000 W
1 x 1.4 , 64000 W
Notes: 1) A brake unit BU200 is required for each resistor used. 2) Standard ACB + Basic OCR (AGR-11).
630 A
AC1811202
375 A
AC1811004
662 A, 0.033 mH
IM0126364
410 A, 0.054 mH
IM0126324
362 A, 0.061 mH
IM0126284
780 A AC1
CA 5-550
450 A AC1
CA 6-300
0180 0202 0217 0260 0313 0367 0402
160 200 220 250 280 315 400
273 341 375 425 480 528 680
150 160 220 250 280 315 400
264 273 375 425 480 528 680
132 160 185 220 250 280 355
228 273 321 375 421 480 589
110 132 150 185 200 220 280
191 228 260 321 341 375 480
Cat. No.SP_____4T XA2K2
Power (kW)
Current (A)
Power (kW)
Current (A)
Power (kW)
Current (A)
Power (kW)
Current (A)
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
Rating
Cat. No.
630 A
S630CE/630
800 A
SLB8003P
800 A
2062232800
400 A
S400NJ/400
400 A
SLB4003P
500 A
SLB5003P
350 A
2041220350
550 A
2062232550
630 A
2062232630
1 x 3.0 , 48000 W
S41 S51380-415 V 50 Hz
630 A
S630CE/630
800 A
XS800NJ/800
800 A
SLB8003P
500 A AC1
CA 6-420
Rating and selection chart
500 A
2062232500
700 A
2062232700
1000 A
20622321000
945 A, 0.025 mH
IM0126404
RE4362360
1 x 3.6 , 32000 W
1 x 2.8 , 48000 W
1 x 2.4 , 48000 W
1 x 1.8 , 64000 W
2 x 2.8 , 48000 W
RE4462300 RE4462280 RE4462240 RE4562180 RE4462280
RE4462660 RE4562600 RE4552500 RE4462160 RE4562140
Light duty rating (120 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Standard duty rating (140 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Heavy duty rating (175 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Strong duty rating (200 % overload for 120 seconds every 20 minutes) - see application table page 3 - 28 for recommended duty
Isolator switch
Semi-conductor fuses
Recommended line contactor
Input / output choke
Output EMC ferrite ring (for compliance to the first environment in addition to the built-in A2 filter)
Dynamic brake resistor - 20 % duty cycle
Dynamic brake resistor - 50 % duty cycle
Recommended circuit breaker
3 - 43
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Notes: 1) A brake unit BU200 is required for each resistor used. 2) Standard ACB + Basic OCR (AGR-11).
1000 A AC1
CA 5-700
1000 A AC1
CA 5-700
0457 0524 0598 0748 0831 0964 1130 1296
400 450 500 560 710 900 1000 1170
680 765 841 939 1200 1480 1646 1950
400 450 500 560 630 800 900 1100
680 765 841 939 1080 1334 1480 1874
315 355 400 500 560 710 800 900
528 589 680 841 939 1200 1334 1480
280 315 355 400 450 560 710 800
480 528 589 680 765 939 1200 1334
1000 A
SLB10003P
1600 A
SLB16003P
1400 A
2063231400
1000 A
206223-21000
1250 A
206223-21250
945 A, 0.023 mH
IM0126404
945 A, 0.023 mH
IM0126404
S60 S65
2 x 1000 A
2 X 20632321000
2 x 1250 A
2 X 20632321250
2 x 1400 A
2 X 20632321400
2 x 800 A
2 X 206 3232800
1260 A, 0.018 mH
IM0126444
2 x 945 A, 0.023 mH input, 6 x 950 A, 0.024 mH output
2 x IM0126404 input, 6 x
IM0140674 output
5 x 10 , 12000 W
5 X RE40231001)
2 x 1.6 , 64000 W
2 X RE4562160
3 x 2.4 , 64000 W
3 X RE4562240
4 x 2.4 , 48000 W
4 X RE4462240
4 x 2.4 , 64000 W
4 X RE4562240
2 x 2.4 , 64000 W
2 X RE45622401)
1250 A
SLB12503P
800 A
XS800NJ/800
1000 A
XS1250SE/1000
1250 A
XS1250SE/1250 AR216S2) AR220S2) AR325S2) AR325S2)
2000 A
SLB20003P
2500 A
SLB25003P
1200 A AC1
CA 5-1000
2 x 945 A, 0.023 mH input, 6 x 1250 A, 0.018 mH output
2 x IM0126404 input, 6 x
IM0140774 output
2 x 1260 A, 0.018 mH input, 6 x 1250 A, 0.018 mH output
2 x IM0126444 input, 6 x
IM0140774 output
4 x 0.8 , 64000 W
4 X RE45618001)
8 x 1.6 , 48000 W
8 X RE44621601)
8 x 1.2 , 48000 W
8 X RE44621201)
8 x 1.2 , 64000 W
8 X RE45621201)
4 x 1.2 , 64000 W
4 X RE45621201)
10 x 10 , 24000 W
10 X RE42931001)
8 x 10 , 24000 W
8 X RE42931001)
S75
3 - 44
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Variable speed drivesSINUS PENTA 660-690 V range and selection
S65Power supply 660-690 V AC
Inom = Inverter nominal continuous current ratingImax = Inverter maximum current for 60 sec every 10 minIpeak = Inverter maximum current for 5 sec
Light up to 120 % overloadStandard up to 140 % overload
Heavy up to 175 % overloadStrong up to 200 % overload
Size Cat. No.
Light Standard Heavy Strong Inom
A
Imax
A IpeakkW A kW A kW A kW A
S14
SP 0003 6TBA2K2 5.5 6.3 4 4.8 4 4.8 3 3.7 7 8.5 10SP 0004 6TBA2K2 7.5 8.4 5.5 6.3 4 4.8 4 4.8 9 11 13SP 0006 6TBA2K2 7.5 8.4 7.5 8.4 7.5 8.4 5.5 6.3 11 13.5 16SP 0012 6TBA2K2 11 12.1 7.5 8.4 7.5 8.4 7.5 8.4 13 16 19SP 0018 6TBA2K2 15 16.8 11 12.1 11 12.1 9.2 10.2 17 21 25SP 0019 6TBA2K2 15 16.8 11 12.1 11 12.1 9.2 10.2 21 25 30SP 0021 6TBA2K2 22 23 18.5 21 15 16.8 11 12.1 25 30 36SP 0022 6TBA2K2 30 33 22 23 22 23 18.5 21 33 40 48SP 0024 6TBA2K2 37 39 30 33 22 23 22 23 40 48 58SP 0032 6TBA2K2 45 46 37 39 37 39 30 33 52 63 76
S22
SP 0042 6TBA2K2 55 56 45 46 37 47 30 33 60 72 86SP 0051 6TBA2K2 75 78 55 56 55 56 45 46 80 96 115SP 0062 6TXA2K2 75 80 75 80 65 67 55 60 85 110 132SP 0069 6TXA2K2 90 95 90 95 75 80 55 60 100 130 156
S32
SP 0076 6TXA2K2 110 115 110 115 90 95 75 80 125 165 198SP 0088 6TXA2K2 132 140 132 140 110 115 90 100 150 200 240SP 0131 6TXA2K2 160 165 160 165 132 140 110 115 190 250 300SP 0164 6TXA2K2 200 205 200 205 160 165 132 140 230 300 360
S42
SP 0181 6TXA2K0 250 250 250 250 220 205 185 190 290 380 456SP 0201 6TXA2K0 315 310 315 310 250 250 220 220 330 420 504SP 0218 6TXA2K0 355 350 315 310 315 310 220 205 360 465 558SP 0259 6TXA2K0 400 390 400 390 355 341 315 310 400 560 672
S52
SP 0290 6TXA2K0 450 440 450 440 400 390 315 310 450 600 720SP 0314 6TXA2K0 500 480 450 450 450 440 355 341 500 650 780SP 0368 6TXA2K0 560 544 500 480 500 480 375 360 560 720 864SP 0401 6TXA2K0 630 626 630 626 560 544 450 440 640 850 1020
2 x S42 SP 0459 6TXA2K0 710 696 710 696 630 626 560 544 720 1000 1200
2 x S52
SP 0526 6TXA2K0 800 773 710 696 710 696 630 626 800 1050 1260SP 0600 6TXA2K0 900 858 800 773 800 773 630 626 900 1100 1320SP 0750 6TXA2K0 1000 954 1000 954 900 858 710 696 1000 1300 1560SP 0828 6TXA2K0 1200 1150 1100 1086 1000 954 800 773 1150 1440 1728
3 x S52SP 0960 6TXA2K0 1400 1360 1400 1360 1200 1150 1000 954 1400 1800 2160SP 1128 6TXA2K0 1650 1550 1400 1360 1400 1360 1000 954 1600 2000 2400
S75 SP 1130 6TXA2K0 1750 1700 1620 1569 1400 1360 1100 1086 1700 1700 2448S80 SP 1296 6TXA2K0 2010 1950 1850 1800 1610 1560 1380 1337 1950 2340 2528
3 - 45
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Ordering details - SINUS PENTA - 660-690 V IP 00
Variable speed drivesSINUS PENTA 660-690 V range and selection
Size
Dimensions (mm)
IPRating
Weight(kg)
Losses
at Inom (W) 1) Cat No. Price $W H D
S14 1) 1) 1)
IP 20 1) 1) SP 0003 6TBA2K2
IP 20 1) 1) SP 0004 6TBA2K2
IP 20 1) 1) SP 0006 6TBA2K2
IP 20 1) 1) SP 0012 6TBA2K2
IP 20 1) 1) SP 0018 6TBA2K2
IP 20 1) 1) SP 0019 6TBA2K2
IP 20 1) 1) SP 0021 6TBA2K2
IP 20 1) 1) SP 0022 6TBA2K2
IP 20 1) 1) SP 0024 6TBA2K2
IP 20 1) 1) SP 0032 6TBA2K2
S22 1) 1) 1)
IP 20 1) 1) SP 0042 6TBA2K2
IP 20 1) 1) SP 0051 6TBA2K2
IP 20 128 1300 SP 0062 6TXA2K0
IP 20 128 1450 SP 0069 6TXA2K0
S32 1) 1) 1)
IP 20 128 1700 SP 0076 6TXA2K0
IP 20 128 1950 SP 0088 6TXA2K0
IP 20 128 2300 SP 0131 6TXA2K0
IP 20 128 2750 SP 0164 6TXA2K0
S42 500 968 409
IP 00 128 3450 SP 0181 6TXA2K0
IP 00 128 3900 SP 0201 6TXA2K0
IP 00 136 4550 SP 0218 6TXA2K0
IP 00 136 4950 SP 0259 6TXA2K0
S52 578 968 409
IP 00 160 5950 SP 0290 6TXA2K0
IP 00 160 6400 SP 0314 6TXA2K0
IP 00 160 7000 SP 0368 6TXA2K0
IP 00 160 7650 SP 0401 6TXA2K0
S65 980 1400 560
IP 00 440 5000 SP 0250 6TXA2K0
IP 00 440 6100 SP 0312 6TXA2K0
IP 00 440 6900 SP 0366 6TXA2K0
IP 00 440 8000 SP 0399 6TXA2K0
IP 00 440 9150 SP 0457 6TXA2K0
IP 00 440 9800 SP 0524 6TXA2K0
IP 00 440 11250 SP 0598 6TXA2K0
IP 00 440 12450 SP 0748 6TXA2K0
S80 2230 1400 560IP 00 990 21900 SP 1130 6TXA2K0
IP 00 990 24000 SP 1296 6TXA2K0
Output Chokes - 660-690 V
Applicable size SP---6TXA2K0 Cat No. Price $
02500312-03990457-05980748-08310963-1130
1296
4106629451260
6 x 9006 x 1050
0.0930.0580.0400.0300.0580.040
300360360420TBATBA
290310390410TBATBA
220250270290TBATBA
IP 00IP 00IP 00IP 00IP 00IP 00
527988110TBATBA
58174611931438
6 x 4006 x 500
IM0127324
IM0127364
IM0127404
IM0127444
6 x IM0141724
6 x IM0141784
A mH
Rating
L H P
IP Rating
Weight (kg)
Losses at
Inom (W)Dimensions (mm)
Options to suit SINUS PENTA 6T models
Input Chokes - 660-690 VApplicable size SP---6TXA2K0 Cat No. Price $
02500312-03990457-0598
07480831096411301296
4106629451260
2 x 6622 x 9453 x 6623 x 1050
0.0930.0580.0400.0300.0580.0400.0580.040
300360360420360360360360
290310390410310390310390
220250270290250270250270
IP 00IP 00IP 00IP 00IP 00IP 00IP 00IP 00
527988110
2 x 792 x 883 x 793 x 88
58174611931438
2 x 7462 x 11933 x 7463 x 1193
IM0127324
IM0127364
IM0127404
IM0127444
2 x IM0127364
2 x IM0127404
3 x IM0127364
3 x IM0127404
A mH
Rating
L H P
IP Rating
Weight (kg)
Losses at
Inom (W)Dimensions (mm)
Notes: 1) Refer to NHP for data and availabilityPrice Schedule ‘M5’
3 - 46
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
The SINUS PENTA Variable Speed Drive when combined with special software becomes a high level integrated pump control system. This software can be added to any SINUS PENTA drive and is field loadable using the Remote Drive PC software package or can be supplied, pre-installed on request. The software provides a high level of control with flexible options for configuration, control and monitoring.
The multi-pump system can be used to control a system of up to 5 pumps including the master. The drive can be used to control this system without any additional hardware. The drive utilises the internal PID loop and control functionality to control the operation of not only the master but the slave drives also.
Variable speed drivesSINUS PENTA - Multi-pump application
Application software
SW Multi-pump operationOn-site commissioning and application support
Cat. No.
ZZ4590010
NHPSERVICE
Price $
Fixed speed operation
The fixed speed operation provides an economical Multi-pump solution where the master SINUS PENTA drive is used to control the process and the slaves are operated at fixed speed and bought on-line by the master when the capacity of the master is exceeded. When demand reduces, the master sheds the pumps off the system to maintain the process demand. A fixed speed system can be configured using a combination of Direct On-Line (DOL), Star-Delta or Soft Starters and connected using either standard I/O wiring or Modbus communication.
Variable speed operation
Variable speed operation allows for the most efficient and energy saving option for a pump system. By using variable speed drives on all pumps and varying their speed, the pumps can all be run at the lowest level to ensure the lowest energy usage level. As a result the operation of a variable system provides the same energy savings of a single pump, multiplied across all of the pumps. The master will determine which drives are required in order to maintain the demand based on user defined minimum and maximum operation levels. A complete variable speed system has the added benefit of providing a faster response to changing load conditions and is able to maintain a more stable system.
Multi-master control
In order to provide ultimate redundancy, the Multi-pump application incorporates Multi-master control. Multi-master control allows two drives to act as master and therefore the loss of the master will not effect the system operation. With Multi-master if the master becomes unavailable for use, control transfers to the second Multi-master. This allows the system to continue to function in the same way as if a slave was lost. The Multi-master drives operate continuously to calculate the required output even if the particular drive is not acting as the master at that time. This way it is always ready to take over the process with no interruption to operation. A combination of fixed and variable speed slaves can be used in this configuration.
Price Schedule ‘M5’SINUS PENTA MUP primary master with SINUS PENTA
secondary master and SINUS Micro slave
SINUS PENTA MUP master controllinga fixed speed DOL and AuCom soft starter
AC MAINS
FILLING
EMPTYING
FLOW
PRESSURE
P…n
P2
P1
Q
M2
M1
M…n
SLAVE 1
SLAVE 2
SINUS PENTAMUP MASTER
AC MAINS
FILLING
EMPTYING
FLOW
PRESSURE
P…n
P2
P1
Q
M2
M1
M…n
MUPSECONDARYMASTER
SLAVE 1
MUP PRIMARYMASTER
AC MAINS
FILLING
EMPTYING
FLOW
PRESSURE
P…n
P2
P1
Q
M2
M1
M…n
SLAVE 1
SLAVE 2
SINUS PENTAMUP MASTER
SINUS PENTA MUP master with SINUS Nanoand SINUS Micro variable speed slaves
3 - 47
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Price Schedule ‘M5’
Variable speed drivesSINUS PENTA - Regenerative application
The entire SINUS PENTA range of drives can be offered using an Active Front End (commonly referred to as an AFE) for use as a regenerative power supply system. It is defined as an AFE as the inverter becomes an active front end power supply unit that absorbs or sends sinusoidal current in the mains with unity power factor which has been regenerated from the load. The AFE has a stabilised direct voltage (DC link) as an output that is used to power one or more SINUS PENTA inverters through a direct DC connection. The AFE and the motor inverter drive are identical SINUS PENTA units except for the regenerative application software installed on the AFE inverter unit.
Inductances are used between the AFE and the power mains in order to filter the pulse width modulated (PWM) voltage on the inverter output terminals and to make the current exchanged with the mains sinusoidal. It is also necessary to use a line contactor and a regenerative interface which are supplied complete with capacitive filters.
Application software
Regenerative OperationOn-site commissioning and application support
Cat. No
ZZ4590010
NHPSERVICE
Price $
100 % braking torque is able to be absorbed by the AFE system making it perfectly suited for high inertia load applications such as:
• Lifts
• Conveyors
• Fans
• Centrifuges, etc.
which require fast deceleration times without the need for additional braking resistors and braking units.
When using braking resistors and braking units, this excess energy is dissipated in the form of heat which requires greater ventilation requirements and cabinet sizes. When using an AFE system, the excess energy is transferred through the AFE back into the mains grid connection which if properly monitored can save thousands of dollars in annual energy bills.
The use of a SINUS PENTA inverter as a regenerative unit has four main benefits over a standalone unit:
1. Unity power factor
2. Almost 0 % THD
3. 100 % braking torque
4. Line regeneration back into the grid
By the very nature of the AFE system using two inverters connected inversely to each other, the system is able to present to the mains power unity power factor which removes the need for additional power factor correction systems. In addition to this, requirements imposed by electricity distributors to minimise total harmonic distortion levels to levels generally <5 % are easily achieved using an AFE system without the need for additional harmonic filters hence saving significant savings in initial cost and cabinet space.
3 - 48
3
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Notes: 1) Kit includes metal cover with buttons and wiring loom. 2) Replace ‘xx’ with frame size number. 3) SINCOS and resolver/ encoder card with repeater available
Remote mounting kits
Remote mounting kit for keypad to IP 55 with a 3 m cableRemote mounting kit for keypad to IP 55 with a 5 m cable
ZZ0095699
ZZ0095700
Heatsink segregation kit for frame S05Heatsink segregation kit for frame S12
ZZ0095210
ZZ0121920
ES 847 I/O Expansion card (required for some special application software)8 digital inputs, 6 digital outputs and 4 analogue inputs or PT100This card mounts in the I/O slot within the drive.ES 870 I/O Expansion card12 digital inputs and 6 relay outputsThis card mounts in the I/O slot within the drive.ES 914 Isolated aux 24 V DC supply RS485
ZZ0101812
ZZ0101840
ZZ0101790
ES 822 Insulated card for RS 232 and/or RS 485 communication and is suggested for Modbus networks.
This card mounts in the communications slot within the drive.
ZZ0095850
These cards mount in the communications slot within the drive.
Profibus® DP card (kit hardware and software)DeviceNet™ card (kit hardware and software)Interbus card (kit hardware and software) CANOpen card (kit hardware and software) ControlNet card (kit hardware and software) Ethernet+IT card (kit hardware and software) Lonworks cardMetesys Nz cardBacNet 485 cardBacNet Ethernet cardES 851 Datalogger / energy monitor, WEB server, ethernet, modem
ZZ4600040
ZZ4600050
ZZ4600060
ZZ4600070
ZZ4600080
ZZ4600100
ZZ4600085
ZZ0102406
ZZ0102402
ZZ0102404
ZZ0101820
This card mounts in the encoder slot within the drive.
ES 836 Encoder card with internal 5-24 V encoder supply ZZ0095834 3)
Kit for use with remote drive software includes cable and USB/RS 485 converter. Download remote drive from www.nhp.com.au/santerno
SPUSB
A range of harmonic filters to suit all SINUS PENTA drives are availablewhich limits the THD to 5 %.Contact NHP for further information for correct selection.
Refer NHP
Potentiometer and start / stop pushbuttonsPotentiometer and forward / off / reverse selector switchEmergency stop and local / off / remote selector switchOther combinations available to suit the specific application
SP501- XX 2)
SP502- XX 2)
SP500- XX 2)
Encoder card
Description Cat. No. Price $
IP 54 customised control kits to suit SP --- 4T BA2K5 models 1)
Harmonic Filters
PC software kits
Communication option cards
Variable speed drivesSINUS PENTA - Options
I/O Expansion cards
Price Schedule ‘M5’
Added 24 V aux control supply and more comms cards
3 - 49
33
For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Power range: 2.2-1170 kW / 5 - 1950 A (4T)75 -2010 kW / 278 - 1950 A (6T)
Input voltage: AC Supply
DC Supply
4T - 380-500 V AC, 3 phase, - 15 % + 10 %6T - 525-690 V AC, 3 phase, - 15 % + 10 %4T - 530-705 V DC, -15 % + 10 %4T - 810-970 V DC, -15 % + 10 %
Input frequency: 50-60 Hz, +/- 10 %
Output voltage: 0-Vin + 2 %
Control system: IFD - V/f controlVTC - (open/closed loop) - Vector torque controlFOC - Field orientated closed loop controlRGN - Regenerative front end (option)MUP - Multipump application (option)
Overload current rating: In accordance with overload selected for 120 secs every 20 mins up to frame S30 and 60 secs every 10 mins for all other sizes.
Starting torque: Max 240 % for a short time and up to 200 % for 120 secs (dependent on overload selected)
Frequency/Speed resolution: 0.1 Hz IFD, 1 rpm VTC, 0.01 rpm FOC
Speed accuracy: Open loop + 0.5 % of max. speedClosed loop < 0.01 % of max. speed
Carrier frequency: 0.8 -16 kHz with silent mode, dependent on size and control typeBraking: 30 % DC braking
20 % dynamic braking without brake resistorUp to 150 % with internal brake module and external resistor (up to frame S30) or external brake unit and resistor for all other sizes.
Protection functions: Overcurrent, overvoltage, undervoltage, overload, inverter thermal protection, motor thermal protection, mains failure, communications error, auxiliary fault, encoder error.
Frequency setting: Digital keypad, external potentiometer, 0 to 10 V, 4 to 20 mA, preset speeds, up/down control, serial interface.
Control setting: Digital keypad, digital inputs, serial interfaceAnalogue inputs: 3 inputs, selectable between 0-10 V and 0 (4) - 20 mA (12 bit resolution)
Input AIN2 can also be used for PTC thermistor monitoring
Digital inputs: 8 inputs - 3 fixed, 5 programmable (multiple assignment possible)
Analogue outputs: 3 outputs, selectable between 0-10 V, -10-+10 V and 0 (4)-20 mA
Digital outputs: 1 push-pull transistor output (20-48 V DC, 50 mA max.)1 open collector transistor output (5-48 V DC, 50 mA max.)2 relay outputs with changeover contacts (250 V AC, 30 V DC, 3A)
Keypad: 4 line alphanumeric display 11 status LEDsDedicated keys for start, stop, fwd/rev, jog, reset, loc/rem, tx/rx
Enclosure protection: IP 20 from size S05 to size S40IP 00 from size S41 to size S80IP 54 from size S05 to Size S30
Environmental: 0 to +40 °C operation or to 50 °C with derating5 to 95 % RH non-condensing
Communication: Standard Optional
Modbus / RS 485Profibus®, DeviceNet™, Interbus, CANOpen, ControlNet, Ethernet, Lonworks, BacNet, NZ
EMC: AS 61800-3, category C3, second environment or Category C2, first environment with optional ferrite.
Safety: Safe torque off, SIL 3, to IEC standard.
Approvals:
Variable speed drivesSINUS PENTA Specifications
2 For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
1170H1007 3 - 8170H1007 3 - 11170H1007 3 - 20170H3003 3 - 8170H3003 3 - 11170H3003 3 - 20170H3004 3 - 20170M1314 3 - 8170M1314 3 - 11170M1314 3 - 20170M1316 3 - 20170M1317 3 - 8170M1317 3 - 11170M1318 3 - 8170M1318 3 - 11170M1318 3 - 20170M1319 3 - 8170M1319 3 - 11170M1319 3 - 20170M1321 3 - 8170M1321 3 - 11170M1321 3 - 20170M1322 3 - 8170M1322 3 - 11170M2621 3 - 20170M3022 3 - 8170M3022 3 - 11170M5011 3 - 20170M5015 3 - 20170M5017 3 - 20170M6008 3 - 20170M6009 3 - 20170M6010 3 - 20170M6011 3 - 20170M6013 3 - 20170M6015 3 - 20170M6017 3 - 20170M6018 3 - 20170M6019 3 - 20
220 412 04 16 3 - 3620 412 04 25 3 - 3620 412 20 100 3 - 3620 412 20 125 3 - 3620 412 20 160 3 - 3620 412 20 200 3 - 3620 412 20 250 3 - 3620 412 20 315 3 - 3620 412 20 350 3 - 3620 412 20 40 3 - 3620 412 20 400 3 - 3620 412 20 63 3 - 3620 622 32 1000 3 - 3620 622 32 1250 3 - 3620 622 32 500 3 - 3620 622 32 550 3 - 3620 622 32 630 3 - 3620 622 32 700 3 - 3620 622 32 800 3 - 3620 622 32 900 3 - 3620 632 32 1000 3 - 3620 632 32 1250 3 - 3620 632 32 1400 3 - 3620 632 32 800 3 - 3621 189 01 3 - 3621 313 02 3 - 3628 001 04 3 - 3628 002 02 3 - 36289-506 1 - 12
440.51 24 VDC 1 - 12
555150 2 - 955.1.50 2 - 1555151 2 - 955.1.51 2 - 1555152 2 - 955.1.52 2 - 1555164 2 - 955.1.64 2 - 1555.2.16 2 - 1555.2.17 2 - 15
55.2.37 2 - 1555.2.46 2 - 1555.1.50SS 2 - 1555.1.51SS 2 - 1555.1.52SS 2 - 1555153P 2 - 955.1.53P 2 - 1655.1.53RLR 2 - 1655.1.53RLR-PM 2 - 1655.1.64SS 2 - 1555.2.16GW 2 - 1555.2.16PL 2 - 1555.2.19NTW 2 - 1555.2.46SS 2 - 1555.4.00GWNBB 2 - 1455.4.00LHGWNBB 2 - 1455.4.00LHNBB 2 - 1455.4.00NBB 2 - 1455.4.00RHGWNBB 2 - 1455.4.00RHNBB 2 - 1455.4.01LHNBB 2 - 1455.4.01NBB 2 - 1455.4.01RHNBB 2 - 1455.4.01STRANBB 2 - 14554LVKIT 2 - 15
7750-300 1 - 21750-304 1 - 21750-305 1 - 21750-306 1 - 21750-310 1 - 21750-312 1 - 21750-313 1 - 21750-314 1 - 21750-315 1 - 21750-316 1 - 21750-319 1 - 21750-319/004-000 1 - 21750-320 1 - 21750-331 1 - 21750-333 1 - 21750-333/025-000 1 - 25750-334 1 - 21750-337 1 - 21750-337/025-000 1 - 25750-338 1 - 21750-339 1 - 21750-340 1 - 21750-341 1 - 21750-342 1 - 21750-343 1 - 21750-344 1 - 21750-345 1 - 21750-346 1 - 21750-347 1 - 21750-348 1 - 21750-350 1 - 21750-351 1 - 21750-370 1 - 21750-400 1 - 22750-400/025-000 1 - 25750-401 1 - 22750-402 1 - 22750-402/025-000 1 - 25750-403 1 - 22750-404 1 - 24750-405 1 - 22750-406 1 - 22750-408 1 - 22750-409 1 - 22750-410 1 - 22750-411 1 - 22750-412 1 - 22750-414 1 - 22750-415 1 - 22750-418 1 - 22750-421 1 - 22750-422 1 - 22750-423 1 - 22750-424 1 - 22750-425 1 - 22750-427 1 - 22750-428 1 - 22
750-430 1 - 22750-430/025-000 1 - 25750-431 1 - 22750-432 1 - 22750-433 1 - 22750-435 1 - 28750-436 1 - 22750-437 1 - 22750-438 1 - 28750-452 1 - 23750-453 1 - 23750-454 1 - 23750-454/025-000 1 - 25750-455 1 - 23750-455/025-000 1 - 25750-456 1 - 23750-457 1 - 23750-459 1 - 23750-460 1 - 23750-461 1 - 23750-465 1 - 23750-466 1 - 23750-466/025-000 1 - 25750-467 1 - 23750-468 1 - 23750-469/00000 1 - 23750-469/000001 1 - 23750-469/000002 1 - 23750-469/000003 1 - 23750-469/000006 1 - 23750-469/000008 1 - 23750-469/000012 1 - 23750-469/003000 1 - 23750-472 1 - 23750-473 1 - 23750-474 1 - 23750-475 1 - 23750-476 1 - 23750-477 1 - 23750-478 1 - 23750-479 1 - 23750-480 1 - 23750-481 1 - 28750-482 1 - 23750-483 1 - 23750-485 1 - 28750-491 1 - 23750-491/000-001 1 - 23750-492 1 - 23750-493 1 - 23750-493/000-001 1 - 23750-501 1 - 22750-502 1 - 22750-504 1 - 22750-504/025-000 1 - 25750-506 1 - 22750-508 1 - 22750-509 1 - 22750-511 1 - 24750-512 1 - 22750-513 1 - 22750-514 1 - 22750-516 1 - 22750-517 1 - 22750-519 1 - 22750-522 1 - 22750-523 1 - 22750-530 1 - 22750-530/025-000 1 - 25750-531 1 - 22750-532 1 - 22750-535 1 - 28750-536 1 - 22750-537 1 - 22750-550 1 - 23750-552 1 - 23750-553 1 - 23750-554 1 - 23750-555 1 - 23750-556 1 - 23750-557 1 - 23750-559 1 - 23750-560 1 - 23
3For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
750-585 1 - 28750-600 1 - 24750-601 1 - 24750-602 1 - 24750-602/025-000 1 - 25750-603 1 - 24750-604 1 - 24750-609 1 - 24750-610 1 - 24750-611 1 - 24750-612 1 - 24750-613 1 - 24750-614 1 - 24750-615 1 - 24750-616 1 - 24750-621 1 - 24750-622 1 - 24750-623 1 - 24750-624 1 - 24750-625 1 - 28750-626 1 - 24750-627 1 - 24750-628 1 - 24750-630 1 - 24750-631/000-004 1 - 24750-634 1 - 24750-635 1 - 24750-636 1 - 24750-637 1 - 24750-638 1 - 24750-640 1 - 24750-641 1 - 24750-642 1 - 24750-643 1 - 24750-644 1 - 24750-645 1 - 24750-645 1 - 30750-650/003000 1 - 24750-651 1 - 24750-653/003000 1 - 24750-653/025-000 1 - 25750-653/025-018 1 - 25750-654 1 - 24750-655 1 - 24750-655 1 - 31750-655KIT 1 - 34750-660 1 - 29750-665 1 - 29750-666 1 - 29750-670 1 - 24750-671 1 - 24750-804 1 - 21750-806 1 - 21750-812 1 - 21750-812/025-000 1 - 25750-814 1 - 21750-815 1 - 21750-815/025-000 1 - 25750-816 1 - 21750-819 1 - 21750-830 1 - 21750-833 1 - 21750-833/025-000 1 - 25750-833KIT 1 - 34750-837 1 - 21750-838 1 - 21750-840 1 - 21750-841 1 - 21750-841/025-000 1 - 25750-841KIT 1 - 34750-842 1 - 21750-842KIT 1 - 34750-849 1 - 21750-860 1 - 21750-871 1 - 21750-873 1 - 21750-881 1 - 21750-920 1 - 25750-920 1 - 27750-920 1 - 33750-921 1 - 24750-921 1 - 25750-921 1 - 27
750-921 1 - 33750-923 1 - 25750-923 1 - 27750-923 1 - 33750-925 1 - 24750-925 1 - 30750-960 1 - 25750-961 1 - 25750-962 1 - 25750-963 1 - 25750-965 1 - 25750-970 1 - 25751-3001 1 - 31751-3002 1 - 31751-3501 1 - 31751-3502 1 - 31751-4001 1 - 31751-4501 1 - 31751-5201 1 - 31751-5202 1 - 31751-5701 1 - 31751-5702 1 - 31753-110 1 - 37753-150 1 - 37753-400 1 - 36753-401 1 - 36753-402 1 - 36753-403 1 - 36753-404 1 - 37753-405 1 - 36753-406 1 - 36753-408 1 - 36753-409 1 - 36753-410 1 - 36753-411 1 - 36753-412 1 - 36753-415 1 - 36753-418 1 - 36753-421 1 - 36753-422 1 - 36753-423 1 - 36753-424 1 - 36753-425 1 - 36753-427 1 - 36753-428 1 - 36753-430 1 - 36753-431 1 - 36753-432 1 - 36753-433 1 - 36753-434 1 - 36753-440 1 - 36753-452 1 - 37753-453 1 - 37753-454 1 - 37753-455 1 - 37753-456 1 - 37753-457 1 - 37753-459 1 - 37753-461 1 - 37753-465 1 - 37753-466 1 - 37753-467 1 - 37753-469 1 - 37753-472 1 - 37753-474 1 - 37753-475 1 - 37753-476 1 - 37753-477 1 - 37753-478 1 - 37753-479 1 - 37753-480 1 - 37753-482 1 - 37753-483 1 - 37753-492 1 - 37753-501 1 - 36753-502 1 - 36753-504 1 - 36753-506 1 - 36753-507 1 - 36753-509 1 - 36753-512 1 - 36753-513 1 - 36753-514 1 - 36
753-516 1 - 36753-517 1 - 36753-530 1 - 36753-531 1 - 36753-534 1 - 36753-540 1 - 36753-550 1 - 37753-552 1 - 37753-554 1 - 37753-556 1 - 37753-557 1 - 37753-559 1 - 37753-603 1 - 37753-604 1 - 37753-614 1 - 37753-635 1 - 37753-638 1 - 37753-646 1 - 37753-650 1 - 37753-653 1 - 37753-661 1 - 29753-662 1 - 29753-667 1 - 29758-912 1 - 24759-302 1 - 31759-302 1 - 33759-332 1 - 33759-333 1 - 3377.1.06 2 - 1977.1.10 2 - 1977.1.21 2 - 1977.1.25 2 - 1977.1.30 2 - 1977.1.31 2 - 1977.2.11 2 - 1977.2.34 2 - 1977.2.39 2 - 1977.2.40 2 - 1977.2.50 2 - 19787-602 1 - 25787-612 1 - 25787-692 1 - 25787-692 1 - 31
8810-900/000-001 1 - 25810-901/000-001 1 - 25810-902/000-001 1 - 25857-400 1 - 27857-411 1 - 27857-412 1 - 27857-420 1 - 27857-421 1 - 27857-423 1 - 27857-451 1 - 27857-452 1 - 27857-800 1 - 27857-801 1 - 27857-810 1 - 27857-811 1 - 27
9955-04938-00 3 - 2095AZB1 2 - 295AZB5 2 - 29950350300A 3 - 89950350300A 3 - 11995-04803-00 3 - 20995-04804-00 3 - 20995-06348-00 3 - 20995-08133-00 3 - 20
AACTWINCD 1 - 9ACTWINH 1 - 9ACTWINH 1 - 13ACTWINM1 1 - 9ADAPT1605 1 - 47ADROIT1500RC 1 - 66ADROIT1500SI 1 - 66ADROIT1500SI-A 1 - 66ADROIT150RC 1 - 66ADROIT150SI 1 - 66ADROIT150SI-A 1 - 66ADROIT25000RC 1 - 66ADROIT25000SI 1 - 66
4 For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
ADROIT25000SI-A 1 - 66ADROIT2500RC 1 - 66ADROIT2500SI 1 - 66ADROIT2500SI-A 1 - 66ADROIT300RC 1 - 66ADROIT300SI 1 - 66ADROIT300SI-A 1 - 66ADROIT30RC 1 - 66ADROIT30SI 1 - 66ADROIT30SI-A 1 - 66ADROIT5000RC 1 - 66ADROIT5000SI 1 - 66ADROIT5000SI-A 1 - 66ADROIT750RC 1 - 66ADROIT750SI 1 - 66ADROIT750SI-A 1 - 66ADROIT75RC 1 - 66ADROIT75SI 1 - 66ADROIT75SI-A 1 - 66ADROITULRC 1 - 66ADROITULSI 1 - 66ADROITULSI-A 1 - 66AL-210-MRA 1 - 4AL-210-MRD 1 - 4AL2-14AC-KIT 1 - 4AL2-14DC-KIT 1 - 4AL-214-MRA 1 - 4AL-214-MRD 1 - 4AL2-24AC-KIT 1 - 4AL2-24DC-KIT 1 - 4AL-224-MRA 1 - 4AL-224-MRD 1 - 4AL2-2DA 1 - 5AL2-2PT-ADP 1 - 4AL2-2TC-ADP 1 - 4AL-232-CAB 1 - 4AL2-4EX 1 - 5AL2-4EX-A2 1 - 5AL2-4EYR 1 - 5AL2-4EYT 1 - 5AL2-EEPROM-2 1 - 4AL2-GSM-CAB 1 - 4AL-DVD 1 - 4ALPHAGSMMODEM 1 - 4ALPHANXGMODEM 1 - 4ANT1 1 - 47AZM415202SA3D 2 - 5AZM415202SR3D 2 - 5AZM415 B1 2 - 5AZM415 B2 2 - 5AZM415 B3 2 - 5
BBZ1602D 2 - 7BZ1602U 2 - 7BZ1602V 2 - 7BZ1611D 2 - 7BZ1611U 2 - 7BZ1611V 2 - 7BZ16B1 2 - 7
CCBL-1509 1 - 9CBL-1509 1 - 13CBL-1509 1 - 54CBL90H 1 - 54CMR7110VA 3 - 6CMR712VDC 3 - 6CMR7230VA 3 - 6CMR724VA 3 - 6CMR724VDC 3 - 6CSX-007-V4-C1 3 - 8CSX-007-V4-C2 3 - 8CSX-015-V4-C1 3 - 8CSX-015-V4-C2 3 - 8CSX-018-V4-C1 3 - 8CSX-018-V4-C2 3 - 8CSX-022-V4-C1 3 - 8CSX-022-V4-C2 3 - 8CSX-030-V4-C1 3 - 8CSX-030-V4-C2 3 - 8CSX-037-V4-C1 3 - 8CSX-037-V4-C2 3 - 8CSX-045-V4-C1 3 - 8CSX-045-V4-C2 3 - 8
CSX-055-V4-C1 3 - 8CSX-055-V4-C2 3 - 8CSX-075-V4-C1 3 - 8CSX-075-V4-C2 3 - 8CSX-090-V4-C1 3 - 8CSX-090-V4-C2 3 - 8CSX-110-V4-C1 3 - 8CSX-110-V4-C2 3 - 8CSXI-007-V4-C1 3 - 11CSXI-007-V4-C2 3 - 11CSXI-015-V4-C1 3 - 11CSXI-015-V4-C2 3 - 11CSXI-018-V4-C1 3 - 11CSXI-018-V4-C2 3 - 11CSXI-022-V4-C1 3 - 11CSXI-022-V4-C2 3 - 11CSXI-030-V4-C1 3 - 11CSXI-030-V4-C2 3 - 11CSXI-037-V4-C1 3 - 11CSXI-037-V4-C2 3 - 11CSXI-045-V4-C1 3 - 11CSXI-045-V4-C2 3 - 11CSXI-055-V4-C1 3 - 11CSXI-055-V4-C2 3 - 11CSXI-075-V4-C1 3 - 11CSXI-075-V4-C2 3 - 11CSXI-090-V4-C1 3 - 11CSXI-090-V4-C2 3 - 11CSXI-110-V4-C1 3 - 11CSXI-110-V4-C2 3 - 11
DD32124000 1 - 47D38920000024 1 - 46D38920000115 1 - 46D38920000230 1 - 46D63696475024 1 - 47D63696475230 1 - 47DT01 1 - 47DT02 1 - 47DUPDATACC 1 - 47DUPSERVADD 1 - 47DUPSERVSW 1 - 47
EEEX GF1O1S 2 - 22EEX GFS1O1S 2 - 22EEXST-14-10/1S 5M 2 - 2EEXZS-71 10/1S WVD 2 - 9EEXZS-73 10/1S WVD 2 - 9EH-A14AS 1 - 7EH-A14DR 1 - 7EH-A14EDR 1 - 8EH-A20DR 1 - 7EH-A23DRP 1 - 7EH-A28AS 1 - 7EH-A28DR 1 - 7EH-A28DRP 1 - 7EH-A28EDR 1 - 8EH-A40DR 1 - 7EH-A4ERTD 1 - 8EH-A64DR 1 - 7EH-A64EDR 1 - 8EH-A6EAN 1 - 8EH-A6ERTD 1 - 8EH-AX44 1 - 13EH-AX8H 1 - 13EH-AX8I 1 - 13EH-AX8IO 1 - 13EH-AX8V 1 - 13EH-AXH8M 1 - 13EH-AY22 1 - 13EH-AY2H 1 - 13EH-AY4H 1 - 13EH-AY4I 1 - 13EH-AY4V 1 - 13EH-AYH8M 1 - 13EH-BS11 1 - 11EH-BS3 1 - 11EH-BS5 1 - 11EH-BS8 1 - 11EH-CB10 1 - 11EH-CBLCU 1 - 12EHCBLIN32 1 - 12EHCBLOUT32NPN 1 - 12
EHCBLOUT32PNP 1 - 12EH-CPU104 1 - 11EH-CPU208 1 - 11EH-CPU316 1 - 11EH-CPU516 1 - 11EH-CPU548 1 - 11EH-CU 1 - 12EH-CUE 1 - 12EH-D10DR 1 - 7EH-D10DTN 1 - 7EH-D10DTP 1 - 7EH-D14DR 1 - 7EH-D14DTN 1 - 7EH-D14DTP 1 - 7EH-D14DTPS 1 - 7EH-D14EDR 1 - 8EH-D14EDTN 1 - 8EH-D14EDTP 1 - 8EH-D14EDTPS 1 - 8EH-D16ED 1 - 8EH-D16ER 1 - 8EH-D16ETN 1 - 8EH-D16ETPS 1 - 8EH-D20DR 1 - 7EH-D20DTN 1 - 7EH-D20DTPS 1 - 7EH-D23DRP 1 - 7EH-D28DR 1 - 7EH-D28DRP 1 - 7EH-D28DTN 1 - 7EH-D28DTP 1 - 7EH-D28DTPS 1 - 7EH-D28EDR 1 - 8EH-D28EDTN 1 - 8EH-D28EDTP 1 - 8EH-D28EDTPS 1 - 8EH-D40DR 1 - 7EH-D40DTN 1 - 7EH-D40DTPS 1 - 7EH-D4ERTD 1 - 8EH-D64DR 1 - 7EH-D64DT 1 - 7EH-D64DTPS 1 - 7EH-D64EDR 1 - 8EH-D64EDT 1 - 8EH-D64EDTPS 1 - 8EH-D6EAN 1 - 8EH-D6ERTD 1 - 8EH-D8ED 1 - 8EH-D8EDR 1 - 8EH-D8EDTN 1 - 8EH-D8EDTPS 1 - 8EH-D8ER 1 - 8EH-D8ETN 1 - 8EH-D8ETPS 1 - 8EH-DUM 1 - 13EH-ETH2 1 - 11EH-IOCD 1 - 11EH-IOCH 1 - 11EH-IOCP 1 - 11EH-LINK 1 - 11EH-MBAT 1 - 9EH-MBATL 1 - 9EH-MBATLC 1 - 9EH-MCB01 1 - 8EH-MCB05 1 - 8EH-MCB10 1 - 8EH-MEMD 1 - 11EH-MEMP 1 - 11EH-OB232 1 - 8EH-OB232 1 - 9EH-OB485 1 - 8EH-OB485 1 - 9EH-OBMEM 1 - 9EH-OBUSB 1 - 9EH-OLINK 1 - 11EH-POS 1 - 13EH-POS4 1 - 13EH-PSA 1 - 11EH-PSD 1 - 11EH-PT4 1 - 13EHRLY16 1 - 12EH-RMD 1 - 11
5For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
EH-RMP 1 - 11EH-SIO 1 - 11EH-TC8 1 - 13EHTRM32 1 - 12EH-XA16 1 - 12EH-XAH16 1 - 12EH-XD16 1 - 12EH-XD32 1 - 12EH-XD32E 1 - 12EH-XD64 1 - 12EH-XD8 1 - 12EH-XDL16 1 - 12EH-XDL32 1 - 12EH-XDL32E 1 - 12EH-YR12 1 - 12EH-YR16 1 - 12EH-YR8B 1 - 12EH-YS16 1 - 12EH-YS4 1 - 12EH-YT16 1 - 12EH-YT32 1 - 12EH-YT32E 1 - 12EH-YT64 1 - 12EH-YT8 1 - 12EH-YTP16 1 - 12EH-YTP16S 1 - 12EH-YTP32 1 - 12EH-YTP32E 1 - 12EH-YTP64 1 - 12EH-YTP8 1 - 12EM 40 GF KIT 2 - 22EM411O1S 2 - 12EM41D1O1S 2 - 12EM41DS1O1S 2 - 12EM41R1O1S 2 - 12EM41TL1O1S 2 - 12EM954K1O1S 2 - 11EM95D1O1S 2 - 11EM95DD1O1S 2 - 11EM95DS1O1S 2 - 11EM95R1O1S 2 - 11EM95TK1O1S 2 - 11EM95TL1O1S 2 - 11EM95W1O1S 2 - 11EMX3-0023B-V4-C1-H 3 - 16EMX3-0023B-V4-C1-H 3 - 17EMX3-0023B-V4-C2-H 3 - 16EMX3-0023B-V4-C2-H 3 - 17EMX3-0023B-V7-C1-H 3 - 18EMX3-0023B-V7-C1-H 3 - 19EMX3-0023B-V7-C2-H 3 - 18EMX3-0023B-V7-C2-H 3 - 19EMX3-0043B-V4-C1-H 3 - 16EMX3-0043B-V4-C1-H 3 - 17EMX3-0043B-V4-C2-H 3 - 16EMX3-0043B-V4-C2-H 3 - 17EMX3-0043B-V7-C1-H 3 - 18EMX3-0043B-V7-C1-H 3 - 19EMX3-0043B-V7-C2-H 3 - 18EMX3-0043B-V7-C2-H 3 - 19EMX3-0050B-V4-C1-H 3 - 16EMX3-0050B-V4-C1-H 3 - 17EMX3-0050B-V4-C2-H 3 - 16EMX3-0050B-V4-C2-H 3 - 17EMX3-0050B-V7-C1-H 3 - 18EMX3-0050B-V7-C1-H 3 - 19EMX3-0050B-V7-C2-H 3 - 18EMX3-0050B-V7-C2-H 3 - 19EMX3-0053B-V4-C1-H 3 - 16EMX3-0053B-V4-C1-H 3 - 17EMX3-0053B-V4-C2-H 3 - 16EMX3-0053B-V4-C2-H 3 - 17EMX3-0053B-V7-C1-H 3 - 18EMX3-0053B-V7-C1-H 3 - 19EMX3-0053B-V7-C2-H 3 - 18EMX3-0053B-V7-C2-H 3 - 19EMX3-0076B-V4-C1-H 3 - 16EMX3-0076B-V4-C1-H 3 - 17EMX3-0076B-V4-C2-H 3 - 16EMX3-0076B-V4-C2-H 3 - 17EMX3-0076B-V7-C1-H 3 - 18EMX3-0076B-V7-C1-H 3 - 19EMX3-0076B-V7-C2-H 3 - 18
EMX3-0076B-V7-C2-H 3 - 19EMX3-0097B-V4-C1-H 3 - 16EMX3-0097B-V4-C1-H 3 - 17EMX3-0097B-V4-C2-H 3 - 16EMX3-0097B-V4-C2-H 3 - 17EMX3-0097B-V7-C1-H 3 - 18EMX3-0097B-V7-C1-H 3 - 19EMX3-0097B-V7-C2-H 3 - 18EMX3-0097B-V7-C2-H 3 - 19EMX3-0100B-V4-C1-H 3 - 16EMX3-0100B-V4-C1-H 3 - 17EMX3-0100B-V4-C2-H 3 - 16EMX3-0100B-V4-C2-H 3 - 17EMX3-0100B-V7-C1-H 3 - 18EMX3-0100B-V7-C1-H 3 - 19EMX3-0100B-V7-C2-H 3 - 18EMX3-0100B-V7-C2-H 3 - 19EMX3-0105B-V4-C1-H 3 - 16EMX3-0105B-V4-C1-H 3 - 17EMX3-0105B-V4-C2-H 3 - 16EMX3-0105B-V4-C2-H 3 - 17EMX3-0105B-V7-C1-H 3 - 18EMX3-0105B-V7-C1-H 3 - 19EMX3-0105B-V7-C2-H 3 - 18EMX3-0105B-V7-C2-H 3 - 19EMX3-0145B-V4-C1-H 3 - 16EMX3-0145B-V4-C1-H 3 - 17EMX3-0145B-V4-C2-H 3 - 16EMX3-0145B-V4-C2-H 3 - 17EMX3-0145B-V7-C1-H 3 - 18EMX3-0145B-V7-C1-H 3 - 19EMX3-0145B-V7-C2-H 3 - 18EMX3-0145B-V7-C2-H 3 - 19EMX3-0170B-V4-C1-H 3 - 16EMX3-0170B-V4-C1-H 3 - 17EMX3-0170B-V4-C2-H 3 - 16EMX3-0170B-V4-C2-H 3 - 17EMX3-0170B-V7-C1-H 3 - 18EMX3-0170B-V7-C1-H 3 - 19EMX3-0170B-V7-C2-H 3 - 18EMX3-0170B-V7-C2-H 3 - 19EMX3-0200B-V4-C1-H 3 - 16EMX3-0200B-V4-C1-H 3 - 17EMX3-0200B-V4-C2-H 3 - 16EMX3-0200B-V4-C2-H 3 - 17EMX3-0200B-V7-C1-H 3 - 18EMX3-0200B-V7-C1-H 3 - 19EMX3-0200B-V7-C2-H 3 - 18EMX3-0200B-V7-C2-H 3 - 19EMX3-0220B-V4-C1-H 3 - 16EMX3-0220B-V4-C1-H 3 - 17EMX3-0220B-V4-C2-H 3 - 16EMX3-0220B-V4-C2-H 3 - 17EMX3-0220B-V7-C1-H 3 - 18EMX3-0220B-V7-C1-H 3 - 19EMX3-0220B-V7-C2-H 3 - 18EMX3-0220B-V7-C2-H 3 - 19EMX3-0255B-V4-C1-H 3 - 16EMX3-0255B-V4-C1-H 3 - 17EMX3-0255B-V4-C2-H 3 - 16EMX3-0255B-V4-C2-H 3 - 17EMX3-0255B-V7-C1-H 3 - 18EMX3-0255B-V7-C1-H 3 - 19EMX3-0255B-V7-C2-H 3 - 18EMX3-0255B-V7-C2-H 3 - 19EMX3-0255C-V4-C1-H 3 - 16EMX3-0255C-V4-C1-H 3 - 17EMX3-0255C-V4-C2-H 3 - 16EMX3-0255C-V4-C2-H 3 - 17EMX3-0255C-V7-C1-H 3 - 18EMX3-0255C-V7-C1-H 3 - 19EMX3-0255C-V7-C2-H 3 - 18EMX3-0255C-V7-C2-H 3 - 19EMX3-0350B-V4-C1-H 3 - 16EMX3-0350B-V4-C1-H 3 - 17EMX3-0350B-V4-C2-H 3 - 16EMX3-0350B-V4-C2-H 3 - 17EMX3-0350B-V7-C1-H 3 - 18EMX3-0350B-V7-C1-H 3 - 19EMX3-0350B-V7-C2-H 3 - 18EMX3-0350B-V7-C2-H 3 - 19EMX3-0360C-V4-C1-H 3 - 16EMX3-0360C-V4-C1-H 3 - 17
EMX3-0360C-V4-C2-H 3 - 16EMX3-0360C-V4-C2-H 3 - 17EMX3-0360C-V7-C1-H 3 - 18EMX3-0360C-V7-C1-H 3 - 19EMX3-0360C-V7-C2-H 3 - 18EMX3-0360C-V7-C2-H 3 - 19EMX3-0380C-V4-C1-H 3 - 16EMX3-0380C-V4-C1-H 3 - 17EMX3-0380C-V4-C2-H 3 - 16EMX3-0380C-V4-C2-H 3 - 17EMX3-0380C-V7-C1-H 3 - 18EMX3-0380C-V7-C1-H 3 - 19EMX3-0380C-V7-C2-H 3 - 18EMX3-0380C-V7-C2-H 3 - 19EMX3-0425B-V4-C1-H 3 - 16EMX3-0425B-V4-C1-H 3 - 17EMX3-0425B-V4-C2-H 3 - 16EMX3-0425B-V4-C2-H 3 - 17EMX3-0425B-V7-C1-H 3 - 18EMX3-0425B-V7-C1-H 3 - 19EMX3-0425B-V7-C2-H 3 - 18EMX3-0425B-V7-C2-H 3 - 19EMX3-0430C-V4-C1-H 3 - 16EMX3-0430C-V4-C1-H 3 - 17EMX3-0430C-V4-C2-H 3 - 16EMX3-0430C-V4-C2-H 3 - 17EMX3-0430C-V7-C1-H 3 - 18EMX3-0430C-V7-C1-H 3 - 19EMX3-0430C-V7-C2-H 3 - 18EMX3-0430C-V7-C2-H 3 - 19EMX3-0500B-V4-C1-H 3 - 16EMX3-0500B-V4-C1-H 3 - 17EMX3-0500B-V4-C2-H 3 - 16EMX3-0500B-V4-C2-H 3 - 17EMX3-0500B-V7-C1-H 3 - 18EMX3-0500B-V7-C1-H 3 - 19EMX3-0500B-V7-C2-H 3 - 18EMX3-0500B-V7-C2-H 3 - 19EMX3-0580B-V4-C1-H 3 - 16EMX3-0580B-V4-C1-H 3 - 17EMX3-0580B-V4-C2-H 3 - 16EMX3-0580B-V4-C2-H 3 - 17EMX3-0580B-V7-C1-H 3 - 18EMX3-0580B-V7-C1-H 3 - 19EMX3-0580B-V7-C2-H 3 - 18EMX3-0580B-V7-C2-H 3 - 19EMX3-0620C-V4-C1-H 3 - 16EMX3-0620C-V4-C1-H 3 - 17EMX3-0620C-V4-C2-H 3 - 16EMX3-0620C-V4-C2-H 3 - 17EMX3-0620C-V7-C1-H 3 - 18EMX3-0620C-V7-C1-H 3 - 19EMX3-0620C-V7-C2-H 3 - 18EMX3-0620C-V7-C2-H 3 - 19EMX3-0650C-V4-C1-H 3 - 16EMX3-0650C-V4-C1-H 3 - 17EMX3-0650C-V4-C2-H 3 - 16EMX3-0650C-V4-C2-H 3 - 17EMX3-0650C-V7-C1-H 3 - 18EMX3-0650C-V7-C1-H 3 - 19EMX3-0650C-V7-C2-H 3 - 18EMX3-0650C-V7-C2-H 3 - 19EMX3-0700B-V4-C1-H 3 - 16EMX3-0700B-V4-C1-H 3 - 17EMX3-0700B-V4-C2-H 3 - 16EMX3-0700B-V4-C2-H 3 - 17EMX3-0700B-V7-C1-H 3 - 18EMX3-0700B-V7-C1-H 3 - 19EMX3-0700B-V7-C2-H 3 - 18EMX3-0700B-V7-C2-H 3 - 19EMX3-0790C-V4-C1-H 3 - 16EMX3-0790C-V4-C1-H 3 - 17EMX3-0790C-V4-C2-H 3 - 16EMX3-0790C-V4-C2-H 3 - 17EMX3-0790C-V7-C1-H 3 - 18EMX3-0790C-V7-C1-H 3 - 19EMX3-0790C-V7-C2-H 3 - 18EMX3-0790C-V7-C2-H 3 - 19EMX3-0820B-V4-C1-H 3 - 16EMX3-0820B-V4-C1-H 3 - 17EMX3-0820B-V4-C2-H 3 - 16EMX3-0820B-V4-C2-H 3 - 17EMX3-0820B-V7-C1-H 3 - 18EMX3-0820B-V7-C1-H 3 - 19
6 For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
EMX3-0820B-V7-C2-H 3 - 18EMX3-0820B-V7-C2-H 3 - 19EMX3-0920B-V4-C1-H 3 - 16EMX3-0920B-V4-C1-H 3 - 17EMX3-0920B-V4-C2-H 3 - 16EMX3-0920B-V4-C2-H 3 - 17EMX3-0920B-V7-C1-H 3 - 18EMX3-0920B-V7-C1-H 3 - 19EMX3-0920B-V7-C2-H 3 - 18EMX3-0920B-V7-C2-H 3 - 19EMX3-0930C-V4-C1-H 3 - 16EMX3-0930C-V4-C1-H 3 - 17EMX3-0930C-V4-C2-H 3 - 16EMX3-0930C-V4-C2-H 3 - 17EMX3-0930C-V7-C1-H 3 - 18EMX3-0930C-V7-C1-H 3 - 19EMX3-0930C-V7-C2-H 3 - 18EMX3-0930C-V7-C2-H 3 - 19EMX3-1000B-V4-C1-H 3 - 16EMX3-1000B-V4-C1-H 3 - 17EMX3-1000B-V4-C2-H 3 - 16EMX3-1000B-V4-C2-H 3 - 17EMX3-1000B-V7-C1-H 3 - 18EMX3-1000B-V7-C1-H 3 - 19EMX3-1000B-V7-C2-H 3 - 18EMX3-1000B-V7-C2-H 3 - 19EMX3-1200C-V4-C1-H 3 - 16EMX3-1200C-V4-C1-H 3 - 17EMX3-1200C-V4-C2-H 3 - 16EMX3-1200C-V4-C2-H 3 - 17EMX3-1200C-V7-C1-H 3 - 18EMX3-1200C-V7-C1-H 3 - 19EMX3-1200C-V7-C2-H 3 - 18EMX3-1200C-V7-C2-H 3 - 19EMX3-1410C-V4-C1-H 3 - 16EMX3-1410C-V4-C1-H 3 - 17EMX3-1410C-V4-C2-H 3 - 16EMX3-1410C-V4-C2-H 3 - 17EMX3-1410C-V7-C1-H 3 - 18EMX3-1410C-V7-C1-H 3 - 19EMX3-1410C-V7-C2-H 3 - 18EMX3-1410C-V7-C2-H 3 - 19EMX3-1600C-V4-C1-H 3 - 16EMX3-1600C-V4-C1-H 3 - 17EMX3-1600C-V4-C2-H 3 - 16EMX3-1600C-V4-C2-H 3 - 17EMX3-1600C-V7-C1-H 3 - 18EMX3-1600C-V7-C1-H 3 - 19EMX3-1600C-V7-C2-H 3 - 18EMX3-1600C-V7-C2-H 3 - 19ES13SB101S 2 - 4ES 40 GF KIT 2 - 22ES41 2 - 12ES41D1O1S 2 - 12ES41DS1O1S 2 - 12ES41R1O1S 2 - 12ES41Z 101S 2 - 21ES 60 GF 2 - 22ES61SR101S 2 - 10ES954K1O1S 2 - 11ES95AZ101S 2 - 2ES95AZ20 2 - 2ES95D1O1S 2 - 11ES95DD1O1S 2 - 11ES95DS1O1S 2 - 11ES95R1O1S 2 - 11ES95SB101S 2 - 4ES95SB20 2 - 4ES95T5C101S 2 - 4ES95TK1O1S 2 - 11ES95TL1O1S 2 - 11ES95W1O1S 2 - 11ETHCONV2 1 - 46ETHCONV3 1 - 46EX55400GWNBB 2 - 14EX55400NBB 2 - 14EX55401NBB 2 - 14
GG21104401700 1 - 43G21205501700 1 - 43G21205502700 1 - 43G21305511700 1 - 44G21305521700 1 - 44
G21404421700 1 - 45G21404422700 1 - 45G21405510700 1 - 45G21405520700 1 - 45G32101111 1 - 46G32101112 1 - 46G32101113 1 - 46G32101161 1 - 46G32385138230 1 - 46G34105501 1 - 43G34205501024 1 - 43G34205501115 1 - 43G34205501230 1 - 43G34205501800 1 - 43G34205502024 1 - 43G34205502115 1 - 43G34205502230 1 - 43G34205502800 1 - 43G34296470024 1 - 46G34296470115 1 - 46G34296470230 1 - 46G34296470800 1 - 46G34301149024 1 - 44G34301149115 1 - 44G34301149230 1 - 44G34301149800 1 - 44G34302249024 1 - 44G34302249115 1 - 44G34302249230 1 - 44G34302249824 1 - 44G34304249024 1 - 44G34304249115 1 - 44G34304249230 1 - 44G34304249824 1 - 44G34304443024 1 - 44G34304443115 1 - 44G34304443230 1 - 44G34304443824 1 - 44G34304445024 1 - 44G34304445115 1 - 44G34304445230 1 - 44G34305511024 1 - 44G34305511115 1 - 44G34305511230 1 - 44G34305511800 1 - 44G34305521024 1 - 44G34305521115 1 - 44G34305521230 1 - 44G34305521800 1 - 44G34305545024 1 - 44G34305545115 1 - 44G34305545230 1 - 44G34396470024 1 - 46G34396470115 1 - 46G34396470230 1 - 46G34396470800 1 - 46G34404443024 1 - 45G34404443115 1 - 45G34404443230 1 - 45G34404443824 1 - 45G34485134230 1 - 44G34485234230 1 - 44G34485238230 1 - 44G34850000 1 - 47G34860058230 1 - 46G34900000024 1 - 42G34900000115 1 - 42G34900000230 1 - 42G34900000824 1 - 42G34910000024 1 - 46G34910000115 1 - 46G34910000230 1 - 46G34910040024 1 - 46G34910040115 1 - 46G34910040230 1 - 46G34910090024 1 - 46G34910090115 1 - 46G34910090230 1 - 46G34920000230 1 - 46G34930000230 1 - 46G34960000700 1 - 42G34960001700 1 - 42G34960002700 1 - 42
G34960003700 1 - 42G34960004700 1 - 42G34960005700 1 - 42G34960006700 1 - 42G34960007700 1 - 42G34960008700 1 - 42G34960009700 1 - 42G34960010700 1 - 42G34960011700 1 - 42G34960012700 1 - 42G38000015230 1 - 42G38000015800 1 - 42G38000016230 1 - 42G38000016800 1 - 42G38000036230 1 - 42G38000036800 1 - 42G38001015230 1 - 42G38001015800 1 - 42G38001016230 1 - 42G38001016800 1 - 42G38001036230 1 - 42G38001036800 1 - 42G38305543024 1 - 44G38305543115 1 - 44G38305543230 1 - 44G38305543824 1 - 44G38900014230 1 - 43G38900014800 1 - 43G38910020230 1 - 43G38910021230 1 - 43G38910050230 1 - 43G38910051230 1 - 43G38910052230 1 - 43G38910120230 1 - 43G40855562 1 - 47G41855531 1 - 47G42484134724 1 - 44G43111120 1 - 46G44207401230 1 - 43G44207401724 1 - 43G50101106 1 - 43G50102206 1 - 43G54606606024 1 - 47G54606606115 1 - 47G54606606230 1 - 47G61101145 1 - 43G61101145-1 1 - 43G63910240 1 - 46G81103394 1 - 46G81104406 1 - 45G81104407 1 - 45G81112211 1 - 46G81113315 1 - 46G81452574 1 - 45G81864407703 1 - 45G82104406 1 - 45G82452574 1 - 45G82864406703 1 - 45G85101101 1 - 45G85102201 1 - 45G85103301 1 - 45G86111010 1 - 46G88101102 1 - 43G88104401 1 - 43G88301143 1 - 44G88405521 1 - 45G89101101 1 - 43G89101101-G 1 - 43G89101127 1 - 43G89102116 1 - 43G89102217 1 - 43G89111010 1 - 46GAP1605 1 - 47GF 101S 2 - 22GF 10SD10S 2 - 22GF2 10S10S 2 - 22GF2 20S20S 2 - 22GF 2O2S 2 - 22GFM 101S 2 - 22GFM 202S 2 - 22GF POTI_OHM 2 - 22GFS 101S 2 - 22GFS 10SD10S 2 - 22
7For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
GFS1SD 10VD 2 - 22GFS 202S 2 - 22GFS2 10S/10S 2 - 22GFS2 20S/20S 2 - 22GFS2SD 20VD 2 - 22GFSM 1O1S 2 - 22GFSM 2O2S 2 - 22GFS POTI_OHM 2 - 22GH34404412 1 - 45GH34850000724 1 - 46GH64404412 1 - 45GHTU8 1 - 47GPS-B015-FN4-VD 2 - 23GPS-B025-FN4-VD 2 - 23GPS-B045-FN4-VD 2 - 23GT01-C30R2-6P 1 - 5GT1030HBD2 1 - 5GTI50 1 - 46GTU8 1 - 47
HHSSI4101S 2 - 7HSSI420 2 - 7
IIM0126044 3 - 35IM0126084 3 - 35IM0126124 3 - 35IM0126144 3 - 35IM0126164 3 - 35IM0126204 3 - 35IM0126244 3 - 35IM0126284 3 - 35IM0126324 3 - 35IM0126364 3 - 35IM0126404 3 - 35IM0126444 3 - 35IM0127324 3 - 45IM0127364 3 - 45IM0127404 3 - 45IM0127444 3 - 456 X IM0141724 3 - 456 X IMO141782 3 - 356 X IM0141784 3 - 45IMO126004 3 - 35IPS-B026-FN4-VD 2 - 23IPS-B036-FN4-VD 2 - 23IPS-B046-FN4-VD 2 - 23
LLIBAT-H 1 - 13
MMC30 2 - 6MC4 2 - 7MC56 2 - 6MF1C 2 - 20
NNBAFP 2 - 15NBAG 2 - 15NBBFP 2 - 15NBBG 2 - 15NO2242 2 - 15NO2243 2 - 15NO2551 2 - 15NO2556 2 - 15NSC13DB24DA 2 - 20NSC13DB24DC 2 - 20
PPCNET 1 - 50PCNET 1 - 51PCNET 1 - 54PCP-064-480V 3 - 6PCP-064-600V 3 - 6PCP-147-480V 3 - 6PCP-147-600V 3 - 6PCS-003-480V 3 - 6PCS-003-480V-024V 3 - 6PCS-009-480V 3 - 6PCS-009-480V-024V 3 - 6PCS-016-480V 3 - 6PCS-016-480V-024V 3 - 6PCS-019-480V 3 - 6PCS-019-480V-024V 3 - 6PCS-025-480V 3 - 6PCS-025-480V-024V 3 - 6
PCS-030-480V 3 - 6PCS-030-480V-024V 3 - 6PCS-037-480V 3 - 6PCS-037-480V-024V 3 - 6PCS-043-480V 3 - 6PCS-043-480V-024V 3 - 6PCS-060-480V 3 - 6PCS-060-480V-024V 3 - 6PCS-085-480V 3 - 6PCS-085-480V-024V 3 - 6PCS-23-CI23 3 - 6PCS-25S-CC25 3 - 6PCS-37-CI37 3 - 6PCS-PA-01 3 - 6PCS-PA-10 3 - 6PCS-PA-11 3 - 6PCS-PA-20 3 - 6PCV-064 3 - 6PIM-DN-01 3 - 8PIM-DN-01 3 - 11PIM-DN-01 3 - 20PIM-MB-01 3 - 8PIM-MB-01 3 - 11PIM-MB-01 3 - 20PIM-PA-01 3 - 8PIM-PA-01 3 - 11PIM-PB-01 3 - 8PIM-PB-01 3 - 11PIM-PB-01 3 - 20PIM-RZ-01 3 - 8PIM-RZ-01 3 - 11PIM-USB-01 3 - 20PROTFILM10 1 - 54PROTFILM12 1 - 54PROTFILM6 1 - 54PS21LMS11P0M00 2 - 11PS21LMS11PRM00 2 - 11PS21LMS11R1M00 2 - 11PS21LMS11RTM00 2 - 11PS21LMT11P0M00 2 - 11PS21LMT11PRM00 2 - 11PS21LMT11R1M00 2 - 11PS21LMT11RTM00 2 - 11PS31LMS11P0T00 2 - 12PS31LMS11PRT00 2 - 12PS31LMS11R1T00 2 - 12PS31LMS11RTT00 2 - 12PS31LMS11RVT00 2 - 12PS31LMT11P0T00 2 - 12PS31LMT11PRT00 2 - 12PS31LMT11R1T00 2 - 12PS31LMT11RTT00 2 - 12PS31LMT11RVT00 2 - 12
RRCM-02 3 - 8RCM-02 3 - 11RCSI56101S5M 2 - 6RCSI56205M 2 - 6RCSIM30101S5M 2 - 6RCSIM30205M 2 - 6RE2643560 3 - 26RE2644100 3 - 26RE2644200 3 - 26RE2644400 3 - 26RE3063750 3 - 26RE3083500 3 - 26RE3083500 3 - 38RE3093500 3 - 38RE3113500 3 - 38RE3483150 3 - 38RE3483200 3 - 38RE3483250 3 - 38RE3483500 3 - 38RE3503500 3 - 38RE3762330 3 - 38RE3763100 3 - 38RE3783500 3 - 38RE4022660 3 - 38RE4023100 3 - 38RE4053200 3 - 38RE4163150 3 - 38RE4293100 3 - 38RE4462120 3 - 38
RE4462160 3 - 38RE4462600 3 - 38RE4561800 3 - 38RE4562120 3 - 38RE4562160 3 - 38RE4562240 3 - 38RE4562500 3 - 38RVT5009 1 - 50
SS900 2 - 9SC207A0101 1 - 48SM 0001 2ST BA2K2 3 - 25SM 0001 4T BA2K2 3 - 25SM 0002 2ST BA2K2 3 - 25SM 0002 4T BA2K2 3 - 25SM 0003 2ST BA2K2 3 - 25SM 0003 4T BA2K2 3 - 25SM 0005 2ST BA2K2 3 - 25SM 0005 4T BA2K2 3 - 25SM 0007 2ST BA2K2 3 - 25SM 0007 4T BA2K2 3 - 25SM 0011 2ST BA2K2 3 - 25SM 0011 4T BA2K2 3 - 25SM 0014 2ST BA2K2 3 - 25SM 0014 4T BA2K2 3 - 25SM 0017 2ST BA2K2 3 - 25SM 0017 4T BA2K2 3 - 25SM 0020 2ST BA2K2 3 - 25SM 0020 4T BA2K2 3 - 25SM 0025 2ST BA2K2 3 - 25SM 0025 4T BA2K2 3 - 25SM 0030 2ST BA2K2 3 - 25SM 0030 4T BA2K2 3 - 25SMDMK 3 - 26SME00022ST 3 - 26SME00024T 3 - 26SME00032ST 3 - 26SME00034T 3 - 26SME00072ST 3 - 26SME00074T 3 - 26SME00112ST 3 - 26SME00142ST 3 - 26SME00144T 3 - 26SN 0001 2S XB K2 3 - 24SN 0002 2S XB K2 3 - 24SN 0003 2S XB K2 3 - 24SN 0005 2S XB K2 3 - 24SNMCANOP 3 - 26SNMCTLNT 3 - 26SNMDEVNT 3 - 26SNMETHNT 3 - 26SNMINTBS 3 - 26SP 0313 4TXA2K0 3 - 33SP 0367 4TXA2K0 3 - 33SP 0402 4TXA2K0 3 - 33SP 0457 4TXA2K0 3 - 33SP 0524 4TXA2K0 3 - 33SP 0598 4TXA2K0 3 - 33SP 0748 4TXA2K0 3 - 33SP 0831 4TXA2K0 3 - 33SP 0964 4TXA2K0 3 - 33SP 1130 4TXA2K0 3 - 33SP 1296 4TXA2K0 3 - 33SP 0003 6TBA2K2 3 - 45SP 0004 6TBA2K2 3 - 45SP 0005 4TBA2K2 3 - 33SP 0005 4TBA2K5 3 - 34SP 0006 6TBA2K2 3 - 45SP 0007 4TBA2K2 3 - 33SP 0007 4TBA2K5 3 - 34SP 0009 4TBA2K2 3 - 33SP 0009 4TBA2K5 3 - 34SP 0011 4TBA2K2 3 - 33SP 0011 4TBA2K5 3 - 34SP 0012 6TBA2K2 3 - 45SP 0014 4TBA2K2 3 - 33SP 0014 4TBA2K5 3 - 34SP 0016 4TBA2K2 3 - 33SP 0016 4TBA2K5 3 - 34SP 0017 4TBA2K2 3 - 33SP 0017 4TBA2K5 3 - 34SP 0018 6TBA2K2 3 - 45SP 0019 6TBA2K2 3 - 45SP 0020 4TBA2K2 3 - 33
8 For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE CAT. NO. PAGE CAT. NO. PAGE
SP 0020 4TBA2K5 3 - 34SP 0021 6TBA2K2 3 - 45SP 0022 6TBA2K2 3 - 45SP 0024 6TBA2K2 3 - 45SP 0025 4TBA2K2 3 - 33SP 0025 4TBA2K5 3 - 34SP 0030 4TBA2K2 3 - 33SP 0030 4TBA2K5 3 - 34SP 0032 6TBA2K2 3 - 45SP 0034 4TBA2K2 3 - 33SP 0034 4TBA2K5 3 - 34SP 0036 4TBA2K2 3 - 33SP 0036 4TBA2K5 3 - 34SP 0040 4TBA2K2 3 - 33SP 0040 4TBA2K5 3 - 34SP 0042 6TBA2K2 3 - 45SP 0049 4TBA2K2 3 - 33SP 0049 4TBA2K5 3 - 34SP 0051 6TBA2K2 3 - 45SP 0060 4TBA2K2 3 - 33SP 0060 4TBA2K5 3 - 34SP 0062 6TXA2K0 3 - 45SP 0067 4TBA2K2 3 - 33SP 0067 4TBA2K5 3 - 34SP 0069 6TXA2K0 3 - 45SP 0074 4TBA2K2 3 - 33SP 0074 4TBA2K5 3 - 34SP 0076 6TXA2K0 3 - 45SP 0086 4TBA2K2 3 - 33SP 0086 4TBA2K5 3 - 34SP 0088 6TXA2K0 3 - 45SP 0113 4TBA2K2 3 - 33SP 0113 4TBA2K5 3 - 34SP 0129 4TBA2K2 3 - 33SP 0129 4TBA2K5 3 - 34SP 0131 6TXA2K0 3 - 45SP 0150 4TBA2K2 3 - 33SP 0150 4TBA2K5 3 - 34SP 0162 4TBA2K2 3 - 33SP 0162 4TBA2K5 3 - 34SP 0164 6TXA2K0 3 - 45SP 0180 4TXA2K0 3 - 33SP 0181 6TXA2K0 3 - 45SP 0201 6TXA2K0 3 - 45SP 0202 4TXA2K0 3 - 33SP 0217 4TXA2K0 3 - 33SP 0218 6TXA2K0 3 - 45SP 0250 6TXA2K0 3 - 45SP 0259 6TXA2K0 3 - 45SP 0260 4TXA2K0 3 - 33SP 0290 6TXA2K0 3 - 45SP 0312 6TXA2K0 3 - 45SP 0314 6TXA2K0 3 - 45SP 0366 6TXA2K0 3 - 45SP 0368 6TXA2K0 3 - 45SP 0399 6TXA2K0 3 - 45SP 0401 6TXA2K0 3 - 45SP 0457 6TXA2K0 3 - 45SP 0524 6TXA2K0 3 - 45SP 0598 6TXA2K0 3 - 45SP 0748 6TXA2K0 3 - 45SP 1130 6TXA2K0 3 - 45SP 1296 6TXA2K0 3 - 45SP500- XX 3 - 48SP501- XX 3 - 48SP502- XX 3 - 48SPUSB 3 - 26SPUSB 3 - 48SRM21RT2 2 - 20ST14-10/1S 2 - 2ST14-20 2 - 2ST14 B1 2 - 2ST14 B3 2 - 2ST14 B5 2 - 2ST6110/1S 2 - 3ST6120 2 - 3ST61 B1 2 - 3ST61 B5 2 - 3STM295202SA 2 - 5STM295202SR 2 - 5STM295 B1 2 - 5STM295 B5 2 - 5SYCON 1 - 13
TTQ4410101YU 2 - 21TQ441 01/01 YUR 2 - 9TQ441 01/01 YUR 137 2 - 9TQ441 01/01 YUR 157 2 - 9TQZ-73 20 WVD 2 - 9TQZS-70 10/1S VD 2 - 9TQZS70KIT10M 2 - 8TQZS-71 10/1SWVD 2 - 9TQZS-71 20 WVD 2 - 9TQZS71KIT20M 2 - 8TQZS-73 10/1SWVD 2 - 9TQZS73KIT50M 2 - 8TQZS-75 10/1S WVD 2 - 9TQZS-75 20/2S WVD 2 - 9TQZS75KIT50M 2 - 8TQZS-80 20/2S WVD 2 - 9TQZS80KIT50M 2 - 8TQZSTS150N 2 - 9TQZSTS250N 2 - 9
UUSB-COM 1 - 4USB-COM 1 - 5USB-COM 1 - 9USB-COM 1 - 13
VVFBC 2 - 15VT050 1 - 50VT060 1 - 50VT150W 1 - 50VT150W DP 1 - 50VT155W 1 - 52VT155W 000DP 1 - 52VT155W 000ET 1 - 52VT160W 1 - 50VT160W DP 1 - 50VT170W A 1 - 50VT185W 1 - 52VT185W 000ET 1 - 52VT190W A 1 - 50VT190W AP 1 - 50VT300W A 1 - 51VT300W AP 1 - 51VT310W A 1 - 51VT310W AP 1 - 51VT320W A 1 - 51VT320W AP 1 - 51VT330W APM 1 - 51VT330W APT 1 - 51VT505H 1 - 52VT505W 1 - 52VT505W 000ET 1 - 52VT505W DP 1 - 52VT515W 1 - 52VT515W 000DP 1 - 52VT515W 000ET 1 - 52VT525H 1 - 52VT525W 1 - 52VT525W 000DP 1 - 52VT525W 000ET 1 - 52VT555W A 1 - 52VT555W AP 1 - 52VT555W AP0DP 1 - 52VT560W A 1 - 53VT560W A0M 1 - 53VT565W A 1 - 53VT565W A0M 1 - 53VT565W AP 1 - 53VT565W APM 1 - 53VT580W 0PTDP 1 - 53VT580W 0PTET 1 - 53VT580W APT 1 - 53VT585W BPT 1 - 53VT585W BPTDP 1 - 53VT585W BPTET 1 - 53VT595W 0PTDP 1 - 53VT595W 0PTET 1 - 53VT595W APT 1 - 53VT5ESABUS 1 - 50VTBUTTONCELL 1 - 50VTBUTTONCELL 1 - 51VTBUTTONCELL 1 - 54VTCBL2515 1 - 54
VTCBL2545 1 - 54VTCBLADP 1 - 54VTCBLXFR 1 - 54VTPROFI/DP 1 - 50VTPROFI/DP 1 - 51VTPROFI/DP 1 - 54VTWINLITE 1 - 50VTWINLITE 1 - 51VTWINLITE 1 - 54
WWW0030460 3 - 38WW1420000 3 - 26
XXCSA120BC 1 - 68XCSA120CB 1 - 68XCSA120DC 1 - 68XCSB150C 1 - 68XCSB150D 1 - 68XCSBC 1 - 68XCSBD 1 - 68XCSD15B 1 - 68XCSD30C 1 - 68XCSD50B 1 - 68XCSD70C 1 - 68XCSF120B 1 - 68XCSF120CP 1 - 68XCSF120D 1 - 68XCSF240B 1 - 68XCSF240CP 1 - 68XCSF240D 1 - 68XCSF500C 1 - 68XCSF85CP 1 - 68XCSG2400C 1 - 68XCSG240C 1 - 68XCSG42 1 - 68XCSG500C 1 - 68XCSG720C 1 - 68XCSL120C 1 - 68XCSL240C 1 - 68XCSL85C 1 - 4XCSL85C 1 - 68XCSP120C 1 - 4XCSP120C 1 - 9XCSP120C 1 - 13XCSP85C 1 - 9XCSP85C 1 - 13XCSP85C 1 - 50XCSP85C 1 - 51XCSP85C 1 - 54
ZZS23211 2 - 22ZS73SR101S 2 - 10ZS75SR101S 2 - 10ZS75SR202S 2 - 10ZS90SR10S10S 2 - 10ZZ0063010 3 - 38ZZ0063020 3 - 38ZZ0063040 3 - 38ZZ0063050 3 - 38ZZ0063072 3 - 38ZZ0095210 3 - 48ZZ0095699 3 - 48ZZ0095700 3 - 48ZZ0095834 3 - 48ZZ0095850 3 - 48ZZ0101790 3 - 48ZZ0101812 3 - 48ZZ0101820 3 - 48ZZ0101840 3 - 48ZZ0102402 3 - 48ZZ0102404 3 - 48ZZ0102406 3 - 48ZZ0112010 3 - 35ZZ0112020 3 - 35ZZ0112030 3 - 35ZZ0112040 3 - 35ZZ0112045 3 - 35ZZ0112050 3 - 35ZZ0112060 3 - 35ZZ0112070 3 - 35ZZ0121920 3 - 48ZZ4590010 3 - 46ZZ4590010 3 - 47
9For further information please contact Sales 1300 NHP NHP or visit nhp.com.au GST not included
Alp
han
um
eric
Ind
ex
CAT. NO. PAGE
ZZ4600030 3 - 26ZZ4600040 3 - 48ZZ4600050 3 - 48ZZ4600060 3 - 48ZZ4600070 3 - 48ZZ4600080 3 - 48ZZ4600085 3 - 48ZZ4600100 3 - 48
1. Download
In order to scan one of the QR Codes
you need to download a QR Code
reader app to your smartphone. Try
simply searching ‘QR Code’ in your app
store.
2. Scan
Open your QR Code reader app and
point the device’s camera at the relevant
QR code.
3. View
Once scanned the QR Code will
automatically open the relevant
location.
HO
W T
O A
CT
IVA
TE
YO
UR
QR
CO
DE
S
WWEBQR CODE
With NHP’s Price Lists available for download online, you can now access product information anytime, anywhere!
Scan the QR code below or go to www.nhp.com.au to download the latest NHP catalogues and price lists.
34
VictoriaRichmond
Laverton
Dandenong
Albury / Wodonga
TasmaniaHobart
Launceston
New South WalesSydney
Newcastle
Canberra
Wollongong
Western AustraliaPerth
Northern TerritoryDarwin
QueenslandBrisbane
Townsville
Rockhampton
Toowoomba
Cairns
South AustraliaAdelaide
1 Ballarat
2 Bendigo
3 Geelong
4 Shepparton
5 Gippsland
6 Mildura
7 Whyalla
8 Mt Gambier
9 Kalgoorlie
10 Bunbury
11 Karratha
12 Port Hedland
13 Mackay
14 Gladstone
15 Sunshine Coast
16 Gold Coast
17 Griffith
18 Wagga Wagga
19 Dubbo
20 Gosford
21 Coffs Harbour
22 Tamworth
23 Lithgow
North IslandAuckland
Hamilton
Napier
Wellington
New Plymouth
South IslandChristchurch
Dunedin
24 Bay of Plenty
Cairns
Townsville
Rockhampton
Brisbane
NewcastleSydney
Wollongong
Auckland
Hamilton
LauncestonDandenongLaverton
12
3 5
67
13
14
15
16
17
18
19
20
2122
23
24
8
9
10
11 12
Adelaide
NHP Branch OfficesNHP Resident Sales Staff
Perth
Darwin
Melbourne
AlburyCanberra
Hobart
Napier
Wellington
Christchurch
Dunedin
Toowoomba
4
New Plymouth
Australian Branches
New Zealand Branches
Australian Regional Representation
New Zealand Regional Representation
NHP Electrical Engineering Products Pty LtdA.B.N. 84 004 304 812
NPLISTDC © Copyright NHP 2013
AUSTRALIAnhp.com.au
SALES 1300 NHP NHP
VICTORIAMelbourne
43-67 River Street Richmond VIC 3121 Tel +61 3 9429 2999
Laverton
104-106 William Angliss Drive Laverton North VIC 3026 Tel +61 3 9368 2901
Albury / Wodonga
847 Ramsden Drive Albury NSW 2640 Tel +61 2 6049 0600
Dandenong
40-42 Cyber Loop Dandenong South VIC 3175 Tel +61 3 8773 6400
TASMANIA
Hobart
Unit 2 65 Albert Street Moonah TAS 7009 Tel +61 3 6228 9575
Launceston
Unit 3 13-17 Merino Street Kings Meadows TAS 7249 Tel +61 3 6345 2600
NEW SOUTH WALESSydney
30-34 Day Street North Silverwater NSW 2128 Tel +61 2 9748 3444
Newcastle
575 Maitland Road Mayfield West NSW 2304 Tel +61 2 4960 2220
Wollongong
34 Industrial Road Unanderra NSW 2526 Tel +61 2 4272 5763
ACT
Canberra
Unit 1 187 Gladstone Street Fyshwick ACT 2609 Tel +61 2 6280 9888
WESTERN AUSTRALIA
Perth
38 Belmont Ave Rivervale WA 6103 Tel +61 8 9277 1777
NORTHERN TERRITORYDarwin
3 Steele Street Winnellie NT 0820 Tel +61 8 8947 2666
QUEENSLANDBrisbane
16 Riverview Place Murarrie QLD 4172 Tel +61 7 3909 4999
Townsville
5 Leyland Street Garbutt QLD 4814 Tel +61 7 4779 0700
Rockhampton
1 Lawson Street Parkhurst QLD 4702 Tel +61 7 4927 2277
Toowoomba
Cnr Carroll Street and Struan Court QLD 4350 Tel +61 7 4634 4799
Cairns Unit 2 1 Bramp Close Portsmith QLD 4870 Tel +61 7 4035 6888
SOUTH AUSTRALIA
Adelaide
36-38 Croydon Road Keswick SA 5035 Tel +61 8 8297 9055
NEW ZEALANDnhp-nz.com
SALES 0800 NHP NHP
PO Box 62-009
Sylvia Park
Auckland 1644
New Zealand
Auckland
118a Carbine Road Mt Wellington 1060 Tel +64 9 276 1967
Hamilton
78 Rostrevor Street Hamilton 3204 Tel +64 7 849 0257
Napier
126 Taradale Road Onekawa 4110 Tel +64 6 843 6928
New Plymouth
2 Dean Place Waiwhakaiho 4312 Tel 0800 NHP NHP
Wellington
52 Victoria Street Lower Hutt 5010 Tel +64 4 570 0634
Christchurch
27 Iversen Terrace Waltham 8011 Tel +64 3 377 4407
Dunedin
30 Fox Street South Dunedin 9012 Tel 0800 NHP NHP