NKU-SESH-M

voltage: low

LOW-VOLTAGE COMPLETESWITCHGEAR

443048, Samara, Krasnaya Glinka, Electroshield Samara+7 (846) 2 777 444 | [email protected]

http://electroshield.ru

Powering your future

Page 2: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 1

NKU-SESH-MLV switchgear is intended for receipt and distribution of the electric energy, protection of outgoing feeders line and drive technology against short-circuit currents and overloads.

Page 3: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru2

TABLE OF CONTENTS

Scopes of application 3Proposed solutions 4Innovation and design features 5Reference material 10Embedded digital control and monitoring system of NKU 18Description of the working area of distribution cabinets 20Functional units 22Overall dimensions of the cabinet 23Busbar configuration 31Configuration example and creation of layout arrangement 33Requirements for cabinets arrangement 35Transportation requirements 39Service solutions 40

The detailed technical information you can see in TI-205-2017 at the web site http://electroshield.ru

Page 4: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 3

The products contained in this catalogue are manufactured using the certified management system ISO9001. The certificate is issued by Bureau Veritas Certification Holding SAS - UK Branch.

NKU-SESH-M SCOPES OF APPLICATION

Oil and gas extraction and processing

Industrial enterprises

Grid companiesGeneration

Russian RailwaysUrban networks

Page 5: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru4

PROPOSED SOLUTIONSReceipt and distribution of electric energy

Electric drives control

Page 6: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 5

INNOVATION AND DESIGN FEATURESReliability and flexibility of operation

The modular construction principle of NKU provides the building flexibility of layout arrangement taking into account the technical requirements of the consumer.

• Convenient integration of the apparatus into the shell.

• Fast connection and cable laying.

• Interchangeability of the functional units.

• Embedded digital control and monitoring system of NKU.

Page 7: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru6

The soleplate allows changing NKU height and also gives it additional rigidity.

If necessary, you can install up to two soleplates one upon the other.

The unique soleplate structure is equipped with detachable panels. The soleplate allows transporting the cabinets during installation works in confined spaces using a forklift.

Movement of cabinets with a forklift at the installation site reduces the preparation time of the product during commissioning/

Page 8: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 7

The panels are equipped with a quick-release fastener, which provides quick access to embedded equipment in case of necessity.

Uninterruptible power supply

Fast access provision to the equipment and automatic circuit-breakers of outgoing lines when servicing.

The use of rotating panels, made in the same style with the plastrons of the cabinet.

The unique Linergy Evolution aluminum busbar system.

• Efficient heat dissipation.

• Initial short-circuit current up to 220 kA.

• Visual visibility of the contact area.

• Transition resistance reduction of the contact area.

• Wiring to the busbars without drilling holes.

Time reduction to perform routine maintenance of embedded equipment and automatic circuit-breakers.

Page 9: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru8

Safety of personnel and equipment

Switchgear protection against the unauthorized access by means of the transparent door with a lock.

• The possibility of visual control of the state of switching devices and apparatus is maintained.

• Visual control of the state of the automatic circuit-breakers and light signaling equipment.

• Access limitation to the switchgear.

Rigid external shell of the design provides the degree of protection against the mechanical shock as per IEC 62262 up to IK10.

Attractive external view

Cost reduction for the system performance of the object’s power supply, the increased cycle of routine maintenance

Page 10: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 9

Type tests reports and also compliance certificates are prepared by the laboratories certified in the accreditation national system “Rosaсcreditation”. However, the product meets the requirements of European standards ISO/IEC, which have stricter criteria.

The consumer receives a low-voltage complete device NKU-SESH-M, the quality of which meets both the Russian and European standards

Page 11: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru10

REFERENCE MATERIALReceipt and distribution of electric energy

Lead-in cabinet

Distribution cabinet with outgoing lines

section with input apparatus of

withdrawable version

fixed apparatus

plug-inapparatus

Panel with a switching device

Page 12: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 11

Main technical specifications of the cabinets

Parameter description ValueRated insulation voltage Ui, V 1000Rated operational voltage Ue, V 400 - 690Rated impulse withstand voltage Uimp, kV 8, 12Air pollution degree as per GOST 15150 degree 3Rated frequency fn, Hz 50, 60Rated current of primary buses InA, A From 160 up to 4000Rated short-time current Icw, kA Up to 100Rated surge current Ipk, kА Up to 220Cabinet height (with one soleplate, without an eye bolt), mm 2100Cabinet width (frame), mm 300, 400, 600, 800, 1100Cable section width, mm 300, 400Depth of the cabinet of one-sided maintenance, mm 400, 600Depth of the cabinet of two-sided maintenance, mm 800, 1000Connection type of functional units as per IEC 61439-2 FFF, WWWCable connection arrangement from above, from belowNKU service type one-sided, two-sidedGround system type TN-S, TN-C, TT, ITInternal division type 1, 2b, 3b, 4bIP protection degree as per GOST 14254 or IEC 60529 30 31 54Protection degree against mechanical shock IK as per IEC 62262 07 08 10

Page 13: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru12

Cabinets areas arrangement

Collecting buses section area

Collecting buses section area

Main switch of collecting buses section area

Main switch of collecting buses section area

Power supply connection section (with the cable from below)

Section area for connection to vertical busbars

Section area with vertical busbars

BUS SECTION

LEAD-IN

Page 14: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 13

Section area with vertical busbars

METERING

Metering devices installation area

RELAY

Collecting buses section area

Functional terminals Functional terminals

Page 15: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru14

COMBINED

Collecting buses section area

Main switch of collecting buses section area

Functional section area

Section area for cable connection

DISTRIBUTION WITH AUTOMATIC CIRCUIT-BREAKERS

Collecting buses section area

Functional section area

Section area for connection to cable terminals

Section area with vertical busbars

Section area for cable harness

and connection

Page 16: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 15

DISTRIBUTION WITH VARIABLE FREQUENCY DRIVE AND SOFT STARTER

CABINET WITH A POWER-FACTOR CORRECTION UNIT

Collecting buses section area

Functional section area

Section area for connection to cable terminals

Collecting buses section area

Functional section area

Section area with vertical busbars

Page 17: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru16

Internal division types of NKU

For NKU-SESH-M cabinets 1, 2b, 3b, 4b division types are applied.Division of 2a, 3 a, 4a types has less strict requirements of their analogues with letter b.

Embedded variable-frequency drives (VFD)

• The latest type of VFD produced by Schneider Electric is Altivar Process.

• Rated power is from 0.75 up to 45 kW.

• Unified overall dimensions of the cabinet WxDxH - 600x600x2100 mm.

• Cabinet degree of protection is IP54.

• Installation of additional options - harmonic filters, bypass etc.

• Installation up to six VFD in one cabinet due to the power and additional options.

Page 18: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 17

Embedded soft starters (SS)

Embedded power-factor correction units (PFCU)

• The latest type of SS produced by Schneider Electric is Altistart 48.

• Rated power is from 5.5 up to 45 kW.

• Unified overall dimensions of the cabinet WxDxH - 600x600x2100 mm.

• Cabinet degree of protection from IP30 up to IP54.

• Installation of additional options – network flow metering valve, bypass contactor etc.

• Installation of up to three SS in one cabinet due to the power and additional options.

• Controller produced by KMB systems Czech Republic - NOVAR1106.

• Rated power is from 50 up to 500 kVAr.

• Minimum stage power is from 12.5 up to 50 kVar.

• Unified overall dimensions of the cabinet WxDxH - 800х600х2100 mm.

• Cabinet degree of protection is IP54.

• Installation of additional options – antiresonance filter, incoming switch etc.

Page 19: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru18

Embedded digital control and monitoring system of NKU

It is used as a local autonomous control system with remote wire and wireless connection.

Allows integrating in the existing SCADA systems of high level.

Interactive operator panel realizes human-machine interface.

Page 20: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 19

- personal computer- laptop- tablet- smartphone

Remote access throughthe embedded interface

Information network

Communication equipment

Level of human-machine interface, remote access, integration in SCADA of high level

Level of controllers

Level of sensors and executive units

Inputs/outputs

Digital

SCADAof higher level

interfaces

Digitalinterfaces

BLOCK DIAGRAM OF DIGITAL CONTROL SYSTEM

Page 21: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru20

DESCRIPTION OF THE WORKING AREA OF DISTRIBUTION CABINETSHeight of module MWorking space for arrangement of panels with apparatus on height is divided for clarity. The height of one module (1M) is 50 mm (1M = 50 mm).

Maximum quantity of modules in the distribution cabinet is 30 M.

Section for cable connections can be located both on the left and on the right side of the distribution cabinet.

Page 22: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 21

PlastronFront panels or plastrons covering wiring boards with the apparatus installed on them have different configuration and are made in the same style and chosen due to their height in modules.

The plastrons are equipped with fast-release fastener and do not require special tools for demounting.

To provide easy access to the equipment and automatic circuit-breakers of the outgoing lines during maintenance the plastron can be installed on the hinges.

Time reduction to perform routine maintenance of embedded equipment and automatic circuit-breakers.

The quantity of the used modules for wiring boards with different automatic circuit-breakers can be clarified in TI-205-2017 at the company web-site http://electroshield.ru

Page 23: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru22

FUNCTIONAL UNITS

Receipt and distribution of electric energy

In, А Apparatus type Number of apparatus

External view of the

unit cabinet

From 630 up to 4000 Masterpact

NTNW

MTZ1MTZ2

EasyPactMVS

1 apparatus and relay panel

From 630 up to 3200 2 apparatus

Up to 630

CompactNSX

Vigi NSX

EasyPact CVSEZC

Vigi CVS Interpact

1 apparatus

up to 4 apparatus

Up to 125

Acti9NG125

INS GV2 GV3

up to 48 modules of 9 mm

The more detailed information for the variants of designs and additional options can be found in the technical information TI-205-2017 and in the diagram manual OGK.138.016, placed at the company web site http://electroshield.ru

Page 24: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 23

OVERALL DIMENSIONS OF THE CABINETLead-in cabinet

Example of layout arrangement

NKU service type

Apparatus characteristic

Dimensions WxDxH, mmPower input

methodType Rated current, A

one-sided

NT/NS 06/16

from 630up to 1600

600×400×2100

with the cable from

below or from above

800×400×2100

with the busbars from the right or

left

NW/MVS 08/32

from 800 up to 3200

800×600×2100

with the cable from

below or from above

(800+300)×600×2100

with the busbars from the right or

left

two-sided

NT/NS 06/16

from 630up to 1600 600×(400+400)×2100

with the cable from

below or from above;

with the busbars

NW/MVS 08/32

from 800 up to 3200 800×(600+400)×2100

NW/MVS 40 4000 (800+300)×(600+400)×2100

with the busbars from the right or

left

Note: if required the carcass depth can be chosen bigger than the indicated cabinet depth in the table

Page 25: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru24

Sectionalizing cabinet

Example of layout arrangement

NKU service type

Apparatus characteristicDimensions WxDxH, mm

Power input

methodType Rated

current, A

one-sided

NT/NS 06/16

from 630 up to 1600

600×400×2100

with the cable from

below or from above

800×400×2100

with the busbars from the right or

left

NW/MVS 08/32

from 800 up to 3200

800×600×2100

with the cable from

below or from above

(800+300)×600×2100

with the busbars from the right or

left

two-sided

NT/NS 06/16

from 630 up to 1600 600×(400+400)×2100 with the

cable from below

or from above;

with the busbarsNW/MVS

08/32from 800 up

to 3200 800×(600+400)×2100

NW/MVS 40 4000 (800+300)×(600+400)×2100

with the busbars from the right or

left

Note: if required the frame depth can be chosen bigger than the indicated cabinet depth in the table

Page 26: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 25

Metering cabinet

Relay cabinet

Example of layout arrangement

NKU service type

Number of counters,

pcs.

Rated current of collecting buses, A

Dimensions WxDxH, mm

Execution variant of

the cabinetCounter type

one-sided

1–6

600×600×2100

free standing

Alfa SET SE

TSE PSCH

Mercury

It is possible to install the

counters of other

manufacturers

7–12 800×600×2100

1–4

from 630up to 3200

600×600×2100

as part of the assembly

5–8 800×600×2100

Note: cabinet depth is taken as per the lead-in cabinet depth

Example of layout arrangement NKU service type Dimensions WxDxH, mm

one-sided

600×400×2100

600×600×2100

two-sided

600×800×2100

600×1000×2100

Note: cabinet depth is taken as per the lead-in cabinet depth

Page 27: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru26

Combined cabinet LEAD-IN-DISTRIBUTION

Example of layout arrangement

NKU service type

Apparatus characteristicDimensions WxDxH, mm

Power input/

output typeType Rated current, A

Functional purpose

one-sided

NT/NS 06/16

from 630 up to 1600 lead-in

(800+300)×400

×2100

With the cable from below or

from above/ with the

cable from below or

from above

Compact NSX

from 100 up to 630

distribution

Compact NSX + Vigi

EasyPact CVS

EasyPact EZC

from 400 up to 630

two-sided

NT/NS 06/16

from 630 up to 1600 lead-in

800×(400+400)

×2100

With the cable or busbars

from above/with the

cable from below

Compact NSX

from 100 up to 630

distribution

Compact NSX + Vigi

EasyPact CVS

EasyPact EZC

from 400 up to 630

Note: if required the frame depth can be chosen bigger than the indicated cabinet depth in the table

Page 28: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 27

LEAD-IN-DISTRIBUTION

LEAD-IN-SECTIONALIZING

Example of layout arrangement

NKU service type

Apparatus characteristicDimensions WxDxH, mm

Input/output methodType Rated current, A Functional

purpose

one-sided

NT/NS from 630up to 1600 lead-in

800×400

×2100

With the cable from

above/

with the cable from

below

Compact NSX

EasyPact CVS

from 100up to 630

distribution

EasyPact EZC

from 400up to 630

Example of layout arrangement

NKU service

type

Apparatus characteristicDimensions WxDxH, mm

Input/output methodType Rated current, A Functional

purpose

one-sided

Compact NSX

EasyPact CVS

from 400up to 630

lead-in andsectionalizing

800×600

×2100

with a cable from

below

Page 29: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru28

Distribution cabinet WITH AUTOMATIC CIRCUIT-BREAKERS

Example of layout arrangement

NKU service type

Apparatus characteristicDimensions WxDxH,

mm

Power input

methodType Rated current, A

one-sided

Compact NSX

100–630(800+300)×400×2100(800+400)×400×2100(800+300)×600×2100(800+400)×600×2100

With a cable from

below

Compact NSX + Vigi

EasyPact CVS

Compact INS/INV

EasyPact EZC 400–630

two-sided

Compact INS/INV

100–630 800×(400+400)×2100800×(600+400)×2100

with the cable from

below or from above

Compact NSX

Compact NSX + Vigi

EasyPact CVS

Note: the width of cable connections section for the cabinets of one-sided maintenance is taken as per the technical task (the recommended width is 400 mm); cabinet’s depth is taken as per the lead-in cabinet depth

Page 30: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 29

WITH A VARIABLE FREQUENCY DRIVE

WITH A SOFT STARTER

Example of layout arrangement

NKU service type

Frequency converter characteristicDimensions WxDxH, mm

Power input

methodType Rated current, A

one-sided

ATV630U07N4 ATV930U07N4 2.2

600×600

×2100

With a cable from

below

ATV630U15N4 ATV930U15N4 4

ATV630U22N4 ATV930U22N4 5.6

ATV630U30N4 ATV930U30N4 7.2

ATV630U40N4 ATV930U40N4 9.3

ATV630U55N4 ATV930U55N4 12.7

ATV630U75N4 ATV930U75N4 16.5

ATV630D11N4 ATV930D11N4 23.5ATV630D15N4 ATV930D15N4 31.7ATV630D18N4 ATV930D18N4 39.2ATV630D22N4 ATV930D22N4 46.3ATV630D30N4 ATV930D30N4 61.5ATV630D37N4 ATV930D37N4 74.5ATV630D45N4 ATV930D45N4 88

Example of layoutarrangement

NKU service type

Soft starter characteristicDimensions WxDxH, mm

Power input

methodType Rated current, A

one-sided

ATS48D17Q от 12 до 17

600×600×2100

With a cable from

below

ATS48D22Q от 17 до 22

ATS48D32Q 22

ATS48D32Q 32

ATS48D38Q от 32 до 38

ATS48D47Q от 38 до 47

ATS48D62Q от 47 до 62

ATS48D75Q от 62 до 75ATS48D88Q 75ATS48D88Q 88

Page 31: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru30

CABINET WITH A POWER-FACTOR CORRECTION UNIT

Example of layout arrangement

NKU service type

Reactive power of the cabinet,

kVar

Antiresonant filter

Dimensions WxDxH, mm

Power input

method

one-sided

50

yes

600×600×2100With a

cable from below

75

100

125

150

175

200

one-sided

100

no

125

150

175

200

225

250

275

300

350

400

450

500

.

Page 32: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 31

Flat copper busbars

BUSBAR CONFIGURATION

Allowable busbar current at ambient air temperature 35 °С, А Busbar cross section, mmIP30, IP31 natural ventilation IP54 forced ventilation

800 750 60 × 51000 900 80 × 51200 1080 50 × 101400 1250 60 × 101800 1600 80 × 102050 1850 2 × (50 × 10)2300 2000 2 × (60 × 10)2820 2500 2 × (80 × 10)3300 2900 2 × (100 × 10)4300 4000 2 × (150 × 10)

VERTICAL BUSBARS

Allowable busbar current at ambient air temperature 35 °С, А Busbar cross section, mmIP30, IP31 natural ventilation IP54 forced ventilation

800 750 60 × 51000 900 80 × 51200 1080 50 × 101400 1250 60 ×101800 1600 80 × 102150 1900 100 × 102820 2500 2 × (80 × 10)3200 2900 2 × (100 × 10)4000 3750 2 × (150 × 10)

HORIZONTAL BUSBARS

Page 33: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru32

Linergy Evolution aluminum busbars

HORIZONTAL AND VERTICAL BUSBARS

Allowable busbar current at ambient air temperature 35 оС, А Busbar cross section, mmIP30, IP31 natural ventilation IP54 forced ventilation

630 530 60 × 23800 680 60 × 23

1000 850 60 × 231250 1050 60 × 231650 1480 60 × 232000 1650 100 × 312440 2100 100 × 313200 2800 150 × 313620 3350 150 × 31

Page 34: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 33

MAIN TECHNICAL SPECIFICATIONS OF THE DISTRIBUTION DEVICE

Rated insulation voltage 1000 VOperating voltage 415 VCurrent of collecting buses 3200 AShort-circuit current 70 kAPeak current 154 kAFrequency 50 HzMaterial of collecting buses CopperInsulation of collecting buses AirSectioning form 4bProtection degree of the cabinet shell IP42Protection degree inside the cabinet IP20Auxiliary circuit voltage 230 VIncoming line CableOutgoing line CableAmbient air temperature +35 °CAltitude above sea level up to 1000 m

CONFIGURATION EXAMPLE AND CREATION OF LAYOUT ARRANGEMENTONE-LINE DIAGRAM OF THE DISTRIBUTION DEVICE

Page 35: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru34

DEFINITION OF TYPE, DIMENSIONS AND QUANTITY OF CABINETSle

ad-in

800

x100

0

lead

-in 8

00x1

000

distribution 800x1000 distribution 800x1000 distribution 800x1000

sect

iona

lizin

g 11

00x1

000

Page 36: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 35

REQUIREMENTS FOR CABINETS ARRANGEMENTFIXATION TO THE FLOOR AND WEIGHT OF CABINETS

Cabinets of one-sided maintenance

single-framed cabinets

Page 37: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru36

double-framed cabinets

Page 38: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 37

double-framed cabinets

Cabinets of two-sided maintenance

four-framed cabinets

Page 39: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru38

Minimum allowable free space around the cabinet

CABINETS OF ONE-SIDED MAINTENANCE CABINETS OF TWO-SIDED MAINTENANCE

It is required to leave enough space to open completely any door of the cabinet.

When connecting the input with the cable or busbar bridge from above, it is required to leave free space not less than 600 mm above the cabinet.

Page 40: NKU-SESH-M - Electroshield

NKU-SESH-M http://electroshield.ru 39

TRANSPORTATIONREQUIREMENTS

NKU-SESH-M is supplied as transport groups consisting of one or several cabinets connected together.

The package can be of two types:

• wooden pallet with wrapping in inhibited heat shrinkable film;

• wooden container.

The equipment is supplied on the pallets or guide blocks. Final unpacking of the equipment shall be made, if possible, before installation.

When unloading NKU-SESH-M one shall transport lifting it from below or gripping it from above.

When lifting from below the equipment can be lifted from the front or back side with a stacking truck or a fork lift truck. It is required to follow safety rules, equipment shall be fixed with safety belts during transportation.

When using an overhead crane gripping the equipment from above, it is required to use the corresponding slings. They shall be enough strong and in good condition. The slings shall be fixed to four lifting rings on the equipment. It is required to adjust the length of the slings as per the size of the distribution device in such a way that the angle between the slings does not exceed 60°.

In cases when a transport group includes more than two cabinets connected with each other, it is required to use the cross-beam with direct mount to support elements of the distribution device.

Page 41: NKU-SESH-M - Electroshield

NKU-SESH-Mhttp://electroshield.ru40

SERVICE SOLUTIONSElectroshield Samara provides a warranty and post-warranty service of its own manufactured equipment, as well as modernization of the obsolete equipment of other manufacturers.

The aim of the service team is to provide the complex service support and safe, effective equipment usage.

Advantages of Electroshield Samara:• Installation supervision and commissioning worksThe specialists of Electroshield Samara make the efforts to implement the project as efficiently as possible and deliver it on time.• Inspection and modernization of equipmentAt the stage of reconstruction of switchgears, the specialists of Electroshield Samara are ready to inspect, develop recommendations and implement a project for modernization (replacement) of obsolete equipment based on solutions of the equipment manufactured by Electroshield Samara.• Restoring to working conditionSpecialists of Electroshield Samara provide the necessary measures to restore the equipment operability to the specified performance characteristics.• Personnel traineeshipHighly qualified personnel is one of the key factors of reliable operation of equipment. The set of training programs and their practical orientation will help the personnel to operate correctly and safely.• Spare parts supplyFor repair and quick recovery of equipment operability, availability of spare parts has great importance. The specialists of Electroshield Samara developed the extended sets of SPTA. They can be purchased together with the equipment or separately.• Equipment repairFor inspection of equipment and performing repair works, service engineer promptly visits the site.

Answers to your questions can be obtained at our website: www.electroshield.ru