nmorel-honours project

85
1 Energy Independent Wooden House Author: Nicolas Morel Supervisor: Mr. Dylan Ryan Matriculation: 40175752 Second Reader: Mr. Colin McGill Edinburgh Napier University Beng (Hons) Degree in Energy Engineering School of Engineering and Built Environment April 2016 2016

Upload: nicolas-morel

Post on 13-Apr-2017

122 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: NMorel-Honours project

1

Energy Independent Wooden House

Author: Nicolas Morel Supervisor: Mr. Dylan Ryan

Matriculation: 40175752 Second Reader: Mr. Colin McGill

Edinburgh Napier University Beng (Hons) Degree in Energy Engineering

School of Engineering and Built Environment

April 2016

2016

Page 2: NMorel-Honours project

2

Acknowledgements

I would like to first thank my supervisor Mr. Dylan Ryan for his disponibility which made

regular meetings possible and for his guidance during the completion of this final year

project.

Besides my supervisor, I would like to thank Mr. Tariq Muneer who also provided me

technical aid.

My sincere thanks also goes to Abdullah Miqdad, Hannah Wade for their suggestions

and Remi Chataing who challenged my ideas.

Finally, my thanks go to my family: my parents and sister, for their constant support

throughout life and without whom, none of this would have been possible.

Page 3: NMorel-Honours project

3

Abstract

A 30 m2 typical secondary wooden chalet is localized in Villard-de-Lans, in the French

Alps. Being far from the urban area, the house is not supplied in electricity neither in any

other sources of energy except a wood stove burner considered as a back-up solution. It

is consequently uninhabitable as no system is able to insure space or domestic water

heating necessary to provide the occupants with vital needs.

The solar power, clean and abundant resource especially at this location, is commonly

used for this purpose. It can be utilised in different ways of which the ground (warmed by

the sun), the thermal for heating space and water, and the photovoltaic for producing

electricity required to run different systems as it is the case of an off-grid installation.

In order to complete the tasks as well as possible, the feasibility of these three techniques

and their cost will be studied in this report, based on the analysis of heat losses of the

house and the needs in hot water and electricity.

As a first option, a solar photovoltaic (PV) system will be combined with a solar thermal

installation providing hot water, and an electric system for space heating. In the second

option, the PV system is combined with a ground source heat pump which allows both

types space and water heating.

After sizing adequately the different heating systems, it results that the second option was

the least electrically demanding over the year. It allowed four persons to live in the house

at any time between the months of February and October, inducing an investment of

about £15,000.

For £3,000 cheaper, the other option made the inhabitation possible from April to

September. As a notice, the wood strove burner could add two more months to the period

in each case.

Page 4: NMorel-Honours project

4

Table of Contents

1 Chapter One: Introduction ........................................................................................ 9

2 Chapter Two: Literature Review ............................................................................. 11

2.1 Solar Thermal Energy ...................................................................................... 11

2.2 Solar Photovoltaic Energy ................................................................................ 14

2.3 Solar data ......................................................................................................... 18

2.4 Ground Source Heat pump .............................................................................. 20

3 Chapter Three: Implementation .............................................................................. 24

3.1 House Characteristics And Dimensions ........................................................... 24

3.2 Solar Collecting Data ....................................................................................... 27

3.3 Analysis of the Needs ...................................................................................... 30

3.4 Solar Thermal Study ........................................................................................ 41

3.5 Ground Source Heat Pump Study .................................................................... 44

3.6 Solar Photovoltaic Study .................................................................................. 50

4 Chapter Four: Results and Findings ....................................................................... 54

4.1 Needs Analysis ................................................................................................ 54

4.2 Solar Thermal Study ........................................................................................ 57

4.3 Ground Source Heat Pump Study .................................................................... 60

4.4 Solar Photovoltaic Study .................................................................................. 62

4.5 Economic Analysis ........................................................................................... 70

5 Chapter five: Conclusion ......................................................................................... 73

5.1 Analysis ............................................................................................................ 73

5.2 Limitations ........................................................................................................ 75

5.3 Further work ..................................................................................................... 75

6 Bibliography ............................................................................................................ 76

7 Appendix A – House Solar Gains and Heat Losses ...........................................................78

8 Appendix B – Solar Thermal System Elements (1) .............................................................79

9 Appendix C - Solar Thermal System Elements (2) .............................................................80

10 Appendix D – GSHP Circuit Elements (1) ......................................................................81

11 Appendix E - GSHP Circuit Elements (2) .......................................................................82

12 Appendix F – PV Systems Elements (1) ........................................................................83

13 Appendix G – PV Systems Elements (2) .......................................................................84

14 Appendix E – Biowatt Energie Mail Exchange ...............................................................85

Page 5: NMorel-Honours project

5

Abbreviations

PV PhotoVoltatic

Ah Ampere hours

DC Direct Current

AC Alternative Current

DoD Depth of Discharge

GSHP Ground Source Heat Pump

MPPt Maximum Power Point tracker

Symbols

p – n postive – negative

C20 Battery capacity for a discharge over 20 hours

G Monthly-averaged daily solar radiation (kWh/m²/day)

k Thermal conductivity (W/m.K)

𝐼𝐺 Global solar irradiation hourly values (W/m²)

𝐼𝐷 Diffuse solar irradiation hourly values (W/m²)

𝐼𝐸 Extra-terrestrial irradiation hourly values (W/m²)

𝐼𝑏𝑒𝑎𝑚 Direct solar irradiation (W/m²)

𝐼𝑠𝑘𝑦 𝑑𝑖𝑓𝑓 Sky diffuse solar irradiation (W/m²)

𝐼𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓 Ground reflected solar irradiation (W/m²)

𝑇𝜃 Light glass transmission

𝜏𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓 Glass transmission coefficient of the ground reflected light

𝜏𝑠𝑘𝑦 𝑑𝑖𝑓𝑓 Glass transmission coefficient of the sky diffused light

�̅� Monthly-averaged diffuse ratio

𝑘𝑇̅̅̅̅ Monthly-averaged clearness index

𝑇𝜃 Transmission a pane of glass

𝑞𝑐𝑜𝑛𝑑 Rate of heat transfer by conduction (W)

𝑞𝑐𝑜𝑛𝑣 Rate of heat transfer by convection (W)

𝑒 Thickness (m)

𝑇𝑓 Film temperature (K)

ρ Density (kg/m3)

Cp Specific heat (J/kg.K)

Page 6: NMorel-Honours project

6

µ Dynamic viscosity (Pa.s)

ν Kinematic viscosity (m2/s)

α Thermal diffusity (m2/s)

β Volumetric thermal expansion coefficient (K-1)

𝑅𝑎 Rayleigh number

𝑅𝑒 Reynold number

𝑁𝑢 Nusselt number

ℎ𝑖 Internal heat transfer coefficient (W/m2.K)

U Thermal transmittance (W/m²K)

𝑅𝑐𝑜𝑛𝑑 Conduction resistance (W/m.K)

𝑅𝑐𝑜𝑛𝑣 Convection resistance (W/m.K)

Q Heat losses rate

g Gravitational acceleration (m/s2)

𝜀ℎ Hemispherical emissivity

ℎ𝑟 Internal radiation heat transfer coefficient (W/m2.K)

ℎ𝑟0 External radiation heat transfer coefficient (W/m2.K)

σ Stefan-Boltzmann constant (W/m2.K-*4)

n Air change rate per hour

𝑚 ̇ Mass flow rate (kg/s)

𝑞 Volume flow rate (m3/s)

m Mass (kg)

V Volume (L or m3)

𝑣 Velocity (m/s)

𝑅𝑅 Relative roughness

𝑅𝑠 Surface roughness

𝑓 Friction factor

ℎ Head losss (m)

𝐷𝑖 Internal diameter (m)

𝐷𝑒 External diameter (m)

𝑃𝑜𝑢𝑡 Pump hydraulic output (W)

I Current intensity (A)

V Current voltage (V)

P Power (W)

Page 7: NMorel-Honours project

7

List of Figures

FIGURE 1. FLAT PLATE COLLECTOR ........................................................................................................................................ 11 FIGURE 2. EVACUATED TUBE COLLECTOR ............................................................................................................................... 12 FIGURE 3. SOLAR THERMAL SYSTEM ..................................................................................................................................... 13 FIGURE 4. SOLAR ELECTRIC CYLINDER .................................................................................................................................... 14 FIGURE 5. TWIN COIL CYLINDER ........................................................................................................................................... 14 FIGURE 6. PHOTOVOLTAIC PANEL ON-ROOF MOUNTED ............................................................................................................ 14 FIGURE 7. PHOTOVOLTAIC CELL ........................................................................................................................................... 15 FIGURE 8. GENERATION SYSTEM SCHEME .............................................................................................................................. 16 FIGURE 9. MPPT BLUESOLAR............................................................................................................................................. 16 FIGURE 10. INVERTER MULTIPLUS ....................................................................................................................................... 17 FIGURE 11. SOLAR BATTERY RBS-1860 ............................................................................................................................... 17 FIGURE 12. COMPONENTS OF THE SOLAR RADIATION ............................................................................................................... 19 FIGURE 13. GROUND SOURCE HEAT PUMP AND ITS REFRIGERANT CYCLE ...................................................................................... 21 FIGURE 14. WOODEN HOUSE SCHEME .................................................................................................................................. 24 FIGURE 15. WALL MATERIAL COMPOSITION (TO SCALE 1/10) ................................................................................................... 25 FIGURE 16. ROOF MATERIAL COMPOSITION (TO SCALE 1/10) ................................................................................................... 25 FIGURE 17. THERMAL CONDUCTIVITIES OF THE MATERIALS (WIKIPEDIA, 2016) ............................................................................ 25 FIGURE 18. NASA WEBSITE SCREENSHOT .............................................................................................................................. 27 FIGURE 19. HEAT TRANSFER PHENOMENA THROUGH THE WALL ................................................................................................. 32 FIGURE 20. TEMPERATURE PROFILE THROUGH THE WALL.......................................................................................................... 33 FIGURE 21. MONTHLY AVERAGE TEMPERATURES .................................................................................................................... 36 FIGURE 22. HEAT TRANSFER THROUGH THE DOOR ................................................................................................................... 36 FIGURE 23. ROOF 𝜃 ANGLE SKETCH ...................................................................................................................................... 36 FIGURE 24. HEAT TRANSFER THROUGH A WINDOW ................................................................................................................. 37 FIGURE 25. TEMPERATURE PROFILE THROUGH A WINDOW........................................................................................................ 37 FIGURE 26. EXAMPLE OF THERMAL BRIDGES AT WALL/FLOOR JUNCTION ...................................................................................... 38 FIGURE 27. HEAT LOSSES OF A TRADITIONAL HOUSE (ADEME, 2016) ....................................................................................... 39 FIGURE 28. GROUND TEMPERATURE OVER THE YEAR ACCORDING TO THE DEPTH, IN FRANCE (COLLECTEURDEROSEE, 2015) ................. 44 FIGURE 29. PV INSTALLATION SCHEME ................................................................................................................................. 50 FIGURE 30.TOTAL ENERGY GAINED INSIDE THE HOUSE BY MONTH .............................................................................................. 55 FIGURE 31. TOTAL ENERGY LOST BY MONTH .......................................................................................................................... 56 FIGURE 32. ENERGY REQUIRED BY THE IMMERSION HEATER TO PRODUCE THE REST ........................................................................ 58 FIGURE 33. VOLUME OF HOT WATER PRODUCED OVER THE VOLUME REQUIRED, PER DAY (%) .......................................................... 58 FIGURE 34. PERCENTAGE OF THE LOAD COVERED .................................................................................................................... 65 FIGURE 35. PV SYSTEM ELECTRIC INDICATIONS ....................................................................................................................... 66 FIGURE 36. PV SYSTEMS NUMBER OF AUTONOMY DAYS ........................................................................................................... 68 FIGURE 37. FINAL PV DESIGN OVERVIEW .............................................................................................................................. 69

Page 8: NMorel-Honours project

8

List of Tables

TABLE 1. SPREADSHEET "CALC4-09" SCREENSHOT .................................................................................................................. 27 TABLE 2. SPREADSHEET CALC4-10 SCREENSHOT ..................................................................................................................... 29 TABLE 3. SLOPE BEAM (W/M²): ASPECT=180° - TILT=90° ...................................................................................................... 30 TABLE 4. SKY DIFFUSE/GROUND REFLECTION (W/M²): ASPECT=180° - TILT=90° ........................................................................ 31 TABLE 5. VALUES OF T (Θ) - ASPECT=180° - TILT=90° ............................................................................................................ 31 TABLE 6. GLASS AREAS AND TRANSMISSION COEFFICIENTS OF RADIATION ..................................................................................... 32 TABLE 7. GLOBAL AND DIFFUSE RADIATIONS (W/M²) FOR EACH MONTH OF THE YEAR AT VILLARD-DE-LANS ....................................... 41 TABLE 8. SLOPE GLOBAL AT VILLARD-DE-LANS (W/M²) - ASPECT=180° - TILT=30° ...................................................................... 41 TABLE 9. HOT WATER PRODUCTION (EXAMPLE) IN L//M² COLLECTOR ......................................................................................... 42 TABLE 10. LISTING OF TEMPERATURES OVER THE YEAR ............................................................................................................. 45 TABLE 11. HOUSE ELECTRIC LOAD ANALYSIS ........................................................................................................................... 51 TABLE 12. ENERGY ENTERING IN THE BUILDING IN KWH, DAILY .................................................................................................. 54 TABLE 13. ENERGY GAINED FROM HUMAN OCCUPATION .......................................................................................................... 54 TABLE 14. OVERALL HEAT LOSSES OF THE HOUSE .................................................................................................................... 55 TABLE 15. HEAT LOSSES, COLDEST DAY SCENARIO 3/1/1971 ................................................................................................... 55 TABLE 16. YEAR AVERAGE HEAT LOSSES REPARTITION (%) ........................................................................................................ 56 TABLE 17. HEAT LOST - HEAT GAINED PER DAY, OVERVIEW ....................................................................................................... 56 TABLE 18. CALCULATION OF THE ENERGY NEEDED FOR HEATING WATER ...................................................................................... 57 TABLE 19. HOURLY PRODUCTION OF HOT WATER (L) ACCORDING TO THE HEAT PRODUCED BY 3M2 COLLECTOR (W) - SOUTH ............... 57 TABLE 20. THERMAL COLLECTOR SPECIFICATIONS .................................................................................................................... 59 TABLE 21. CIRCULATING PUMP SIZING .................................................................................................................................. 59 TABLE 22. GSHP ENERGY PRODUCTION ................................................................................................................................ 60 TABLE 23. CIRCULATING PUMP SIZING .................................................................................................................................. 60 TABLE 24. GSHP SIZING CALCULATIONS ............................................................................................................................... 61 TABLE 25. ELECTRICAL APPLIANCES LOAD ANALYSIS (HEATING SYSTEM NOT INCLUDED) ................................................................... 62 TABLE 26. OPTION 2, TOTAL ELECTRICAL LOAD ANALYSIS (KWH/DAY) ......................................................................................... 63 TABLE 27. OPTION 1, TOTAL ELECTRICAL LOAD ANALYSIS (KWH/DAY) ......................................................................................... 63 TABLE 28. POWER DEMAND ANALYSIS (KW) .......................................................................................................................... 63 TABLE 29. PV SYSTEM EFFICIENCIES ..................................................................................................................................... 64 TABLE 30. PV ENERGY PRODUCTION ANALYSIS ....................................................................................................................... 64 TABLE 31. POWER PRODUCED BY THE PANELS ........................................................................................................................ 66 TABLE 32. BATTERY BANK SIZING ......................................................................................................................................... 67 TABLE 33. NUMBER OF DAYS OF AUTONOMY FOR BOTH OPTIONS ............................................................................................... 68 TABLE 34. THERMAL SYSTEM COST ANALYSIS ......................................................................................................................... 70 TABLE 35. PV SYSTEM COST ANALYSIS .................................................................................................................................. 71 TABLE 36. GROUND SOURCE HEAT PUMP COST ANALYSIS.......................................................................................................... 72 TABLE 37. TOTAL COST OF EACH OPTION ............................................................................................................................... 72

Page 9: NMorel-Honours project

9

1 Chapter One: Introduction

Solar energy is being used by humans since thousands years ago. Antique cultures used

it for starting fires to keep warm, and their buildings were designed so that the walls and

floors could collect solar heat during the day and release it at night.

The world we live in is constantly in a state of advancement. Technology is often changing

for the better.

Nowadays, the sun - the cleanest and most abundant renewable energy source, can be

converted into thermal or electrical energy so as to provide a comfortable interior

environment and heating water for domestic or other uses.

Theoretically, the sun can allow house energy independence depending on the home’s

consumption. Consumption which must be minimized by human lifestyle changes. If the

house is to be built, super-insulating material and efficient appliances must be chosen,

and passive solar heating must be envisaged.

According to Webster’s dictionary, the word “independent” means to be self-governing,

showing self-reliance, while “energy” is defined as the capacity to perform work.

Aiming at providing a house with full energy independence all over the year is a challenge.

Even more if this is of typical construction, not energy-optimized since the first step of its

design.

The aim of this study is to evaluate two options which are, each, a combination of energy

sources used for providing space and domestic water heating, and electricity. The

importance of identifying the most energy efficient system is imperative so as to determine

which one of the two options allows the longest period of time, during which four persons

can live in a fully energy-independent house.

The literature review focuses on building information from research in order to provide a

better understanding of the technologies the author will be working with. More specifically,

information detailing an overview of solar thermal and photovoltaic systems, and ground

source heat pump installations.

Page 10: NMorel-Honours project

10

The implementation focuses on the methodology used to undertake the calculations.

It details at first instance, the way the solar data were collected. Following, the

identification of the heat gains and losses according to the characteristics of the house

and finally, the feasibility studies and sizing of the different installations.

A CD-ROM associated with this report contains an excel file related to this work which

allowed the realisation of this project.

The next chapter is where the outcomes of the calculations will be presented. The

analysis of the findings will be detailed as well as the comparisons of data between, to

aid in the formulation of a conclusion.

The final chapter of this report covers a discussion on the findings in order to answer the

research question, ending by highlighting any limitations discovered during the whole

project and any areas of future work that can be expected.

Page 11: NMorel-Honours project

11

2 Chapter Two: Literature Review

2.1 Solar Thermal Energy

Solar water heating uses heat from the sun to provide hot water for space heating and/or

for personal hygiene and other domestic uses. The present study will be based solely on

the needs corresponding to personal uses.

The most solar energy available is in the sun’s rays from a clear sky however it is also

possible to collect heat on cloudy days. The use of this solar energy is required during

the heating season for space heating, yet it is not needed in the winter. Nevertheless, the

same quantity of water is needed throughout the full year. As there is less energy

availability during winter compared with summer, a very large collector would be needed

to supply all of the hot water requirements; making the collector greatly oversized in

summer. Consequently domestic water solar heating systems are then usually designed

to provide most, or all, of the hot water required in summer and only a part in winter.

This system is constituted of two parts: one is the solar collector that transfers energy to

the water flowing through it, and the other is a system which permits the transfer of this

heat to the water stored in the domestic tank. (Nicholls, 2008)

Types of solar collectors

Flat plate

The flat plate solar collector is composed of a black

coated surface under a glass cover, insulated to

the rear and sides. The transparent upper layer

allows the solar radiation to pass through to the

collector and reduces the heat losses by

convection. A heat transfer fluid, water or glycol

solution, circulates through the panel to transport

the energy collected away to where it will be used. Figure 1. Flat plate collector

Page 12: NMorel-Honours project

12

The container of these components is a frame made of steel or aluminium, holding the

components in place so that the structure can be mounted suitably south-facing.

(ViridianSolar, 2014)

Evacuated tube collectors

A dark-coloured absorber element is contained within an

evacuated glass tube, designed to concentrate radiation

to a central receiver; through which the solar fluid

circulates in a coaxial manner. A vacuum is also held in

the tube, providing an excellent thermal insulation to the

absorber.

One collector includes several glass tubes mounted in

rows into a manifold, the fluid passes by this last and

transports the heat away to the solar cylinder.

This type of collector is aesthetically difficult to integrate

and more suitable for industrial applications, so the flat plate collector which is cheaper,

is more adapted to this case study. (CIBSE Journal, 2016)

Figure 2. Evacuated tube collector

Page 13: NMorel-Honours project

13

System integration

Overview

When heat is to be collected from the panel, a solar controller activates the pump, which

pushes the heat transfer fluid over the circuit, this carries the heat produced in the

collector to the solar cylinder. The fluid is 40% propylene glycol with water ensuring freeze

protection down to -28 C and thermal stability at high temperature.

When the circulator switches off, the fluid flows back by gravity filling an expansion vessel.

This is a protection of the fluid from extreme temperature in winter and during stagnation

in summer. (EcoHiSolar, 2011)

Types of cylinder

The twin coil cylinder (Figure. 4 below) contains a solar heat exchange coil at the bottom

and another one above it, allowing both the boiler and the solar thermal system to heat

the water by convection. It is appropriate when an existing boiler is already installed in

the house.

Figure 3. Solar thermal system

Page 14: NMorel-Honours project

14

The solar electric cylinder (Figure. 5) comprises an indirect solar coil and an electric

immersion heater which can be powered by electricity generated by solar photovoltaic

panels. This cylinder is more suitable for the current project. (Gasappliance, 2013)

2.2 Solar Photovoltaic Energy

Solar photovoltaic panels are a clean way to produce electricity for use in buildings. The

power produced by a solar cell is directly proportional to the energy it receives. Although

solar array can be yielded and provide green electricity on dull days, more power will be

produced when there is more light coming from the sky.

Figure 6. Photovoltaic panel on-roof mounted

Figure 5. Twin coil cylinder Figure 4. Solar electric cylinder

Page 15: NMorel-Honours project

15

This is why it is important to minimise any obstructions which might overshadow the

panels; ensuring they are mounted in a space from which the sun is clearly visible will do

this. Ideally, the panels should face due south to ensure optimum light is received through-

out the year, however, this is dependent on application. In the case of roof-mounting, the

facing is entirely dependent on the position of the roof; nonetheless, an angle within 45

degrees of due south will provide satisfactory results in addition to a pitch comprised

between 20 and 50 degrees.

When sizing a system, energy consumption of the building and its occupants must be

assessed together with considerations on how to reduce consumption to minimum. (Hall

& Nicholls, 2008)

Photovoltaic cell operating

The simple structure of a photovoltaic cell is shown on the

figure. 7. The central element are crystals of silicon,

grouped together to form a panel of which the size ranges

from few watts to over 3 kW in terms of power.

Due to its atomic structure, an electric charge moves

naturally inside the crystal. Two types of silicon are joined

together; one is made by adding arsenic and acts as a

negative terminal and the other is made by adding boron

and acts as a positive terminal. In this manner the current

is influenced to flow in one direction. As the sunlight falls

on the p – n junction, more electrons are released increasing the electric current available

for collection. (Nicholls, 2008)

Types of cell

Two main types of PV cells are used for buildings; polycrystalline and monocrystalline.

Both types are made from silicon ingots, difference exists through a polycrystalline cell

consisting in multiple crystal structures whereas a monocrystalline cell contains a single

crystal. The purity of this monocrystalline cell is higher, inducing a better efficiency at a

bigger cost. (Renogy, 2015)

Figure 7. Photovoltaic cell

Page 16: NMorel-Honours project

16

Electricity generation system

PV panels mounted together form part of an entire electricity generation system

comprising charge controllers, inverters and batteries for off-grid systems which is the

case of this study.

MPPT

The electricity produced by a PV panel is dependent on the amount of energy hitting its

surface and its efficiency. The actual efficiency of a single crystal covers between 15%

and 18%, which may be further reduced by poor installation practice.

To overcome this and increase the global efficiency of the installation,

MPPT (maximum power point tracking) controllers are used. These

devices constantly check and sweep to find the maximum open

voltage of the PV array instead of having a fixed voltage dictated by

the battery. In this manner a higher voltage is permitted in the

installation, improving performance. (Dankoff, 2001)

Figure 8. Generation system scheme

Figure 9. MPPT BlueSolar

Page 17: NMorel-Honours project

17

Inverter

Solar panels produce direct current (DC) electricity at low voltage; DC is the type of

electricity that projects from the battery for the case of off-grid installations. By contrast,

the main electricity supplies are alternative current (AC), requiring an extra step between

PVs and the electricity wiring, covered by an inverter.

This device uses solid state electronics to turn low voltage DC into

high voltage AC at an appropriate frequency for the electricity

supply, 50 hertz in France. Care must be taken when sizing the

inverter according to the installation as it presents minimum and

maximum values of intensity and voltage input, and a maximum

intensity output.

Although the voltage increases, there is no concurrent production of electricity. As a result

of the increase in voltage, the available current decreases, so while the PV array produces

high current DC, the output of the inverter is at a lower current AC. (Dankoff, 2001)

Batteries

For off-grid systems, a battery solution for storage is

necessary when the electricity is not required at the time of

generation. Lead-acid batteries are now the most pragmatic

way of storing, still a storage of power as hydrogen gas is

currently developing and should become interesting in the

next couple of decades.

Deep-cycle lead-acid batteries

This type of battery is used for off-grid solar and wind power systems. They are designed

by the manufacturers to be able to charge with a small amount of current, taking

advantage of any available energy and having a good efficiency from 90 to 95%.

A starter battery can finish between 50 and 150 deep discharges whereas a deep-cycle

battery is able to complete around 1200 deep discharges cycles. As the worldwide price

Figure 11. Solar battery RBS-1860

Figure 10. Inverter MultiPlus

Page 18: NMorel-Honours project

18

of lead is high, the deep-cycle batteries are significantly more expensive than the others

due to the fact that they use more lead in their manufacture.

The amount of energy a battery can store is expressed in Amp hours (Ah), and this

capacity varies according to the period the battery will be discharged over. For most deep-

cycle batteries, the manufacturers provide a capacity rate over 20 or 100 hours meaning

that, for a battery rated at “200 Ah @ C20”, it is able to provide 200 Ah over 20 hours (at

constant 10 amps load). (CarbonNeutral, 2013)

For off-grid systems, the battery bank is sized relatively to the daily loads of the house. In

order to optimise the lifetime, a percentage of depth of discharge (DoD) rarely below 50%

is considered. This ratio gives several reserve days to the system, enough to prepare for

overcast days, in addition to the days of autonomy, which sizing also considers.

Deep-cycle batteries are manufactured in 2 volt cells. To provide the correct voltage

required by the installation they are assembled together in series. Similarly, if needed, the

capacity can be increased by joining parallel strings of batteries together (i.e. 2 parallel

strings of 6 x 2V, 1000 Ah batteries in series = 24V, 2000 Ah battery bank).

(CarbonNeutral, 2013)

2.3 Solar data

Solar energy or daylight utilisation at any location is dependent on the quantity of the

available flux which endures monthly and diurnal variations. Many locations in the world

have reliable and long-term measurements of the energy received from the sun, on

horizontal and sloped surfaces.

When undertaking solar thermal and photovoltaic studies, solar data must be collected in

order to find out the final power available for utilisation and to calculate the passive gains

in the building.

Page 19: NMorel-Honours project

19

Composition of solar radiation

The solar radiation filling the sky can be direct, diffuse or reflected.

The direct radiation defines the energy traveling on a straight line from the sun to the

surface of the earth.

The diffuse radiation is the sunlight which has been scattered by molecules and particles

present in the atmosphere.

The reflected radiation is sunlight that has been reflected by everything non-atmospheric,

such as the ground. (Watson, 2011)

Direct and Diffuse Irradiations

When the sun is high in a clear sky, direct radiation represents the large majority of the

global irradiation. As the sun descends, the amount of diffuse radiation increases to a

maximum of 40% of total radiation. Moreover, atmospheric conditions such as clouds and

pollution are factors increasing the amount of diffuse light. (T Muneer & Kambedezis,

2007)

Figure 12. Components of the solar radiation

Page 20: NMorel-Honours project

20

Global Irradiation

The global irradiation is the sum of direct, diffuse and ground reflected components of

sunlight; these can be collected from the NASA website for the wanted location. Precisely,

it is the monthly-averaged daily horizontal global irradiation G on a horizontal surface,

expressed in kWh/m²/day. This value can be disaggregated to produce hourly set,

allowing accurate solar collecting data according to the time of the day.

The energy hitting the surface of an object varies according to the time, location, its aspect

and tilt. The spreadsheets “calc4-09” and “4-10” available on the CD-ROM consider these

conditions and permit the decomposition of the solar radiation into its different

components. (Watson, 2011)

Different Study Considerations

When solar radiation passes through a window, each component is influenced in a

different manner; that is why the decomposition is useful and the procedure of calculating

solar gains in the building will be explained later.

When it comes to find out the power received by a solar panel, it is sufficient to consider

the slope global computed in the “calc4-10”, which is the final power received. (Muneer,

2000)

2.4 Ground Source Heat pump

Operation

Heat pumps use the refrigeration cycle to transfer heat from a source, to an internal space

through a heat distribution circuit. For the current study, the source of heat will be the

ground.

An antifreeze liquid is pumped through underground pipes, called ground loops, being

colder than the ground, the liquid absorbs energy which raises the temperature a few

degrees.

Page 21: NMorel-Honours project

21

At a given point of the circuit, the liquid passes through a heat exchanger; an evaporator

(see figure. 13). The heat is transferred from the liquid to a refrigerant circulating in

another circuit and causes its evaporation.

The vapour is now at low temperature and pressure and moves to a compressor to reach

high pressure as a result of the work completed by the compressor.

Then, the refrigerant gas enters a condenser where it releases heat, usually to a hot water

tank which then feeds heating and hot water systems.

Following, the refrigerant which is still in the form of a gas reduced in temperature and

pressure, moves to an expansion valve. This element lowers the pressure and

temperature again before the cycle starts again and repeats keeping the evaporator coil

constantly cold and the condenser coil constantly warm. (Hall & Nicholls, 2008)

These three components; compressor, condenser and evaporator are all contained in a

unit called heat pump.

Figure 13. Ground source heat pump and its refrigerant cycle

Page 22: NMorel-Honours project

22

Types of collector

The most common way to collect the heat from the ground is by using closed loop and

indirect circulation. A circulating pump circulates a mixture of water and antifreeze through

a closed loop of pipe.

After, the mixture passes through the heat pump where the heat absorbed in the ground

is extracted.

Alternatively, heat can be collected using “direct circulation”. In this case the heat pump

refrigerant is directly circulated through a copper pipe in the ground. This method doesn’t

require any circulating pump, however, a large volume of refrigerant is needed. For

ecological reasons, this type of collector is not of the most common, the refrigerant is

exposed to cause environmental damages due to its location in the circuit.

(QuelleEnergie, 2016)

Burial

The ground pipe is buried either horizontally in a shallow trench at depth comprised in

between 1 and 2 m, or vertically in a borehole, this is dependent on the area available for

the workings and the ground conditions.

Horizontal collectors require large areas and a soil depth of about 1.5 m. They are

particularly suitable for in rural locations where the properties are larger. (EnergyAgency,

2015)

In urban areas, the installation size can be limited and that is why it is wise to use vertical

collectors which can be buried up to 30m depth. Vertical collectors have an increased

price than horizontal collectors due to the amplified costs of trenching and drilling to a

deeper depth. However, vertical collectors have a better thermal efficiency as the ground

is warmer at escalated depth; and as a result, require less length of pipe.

(EnergySavingTrust, 2016)

Page 23: NMorel-Honours project

23

Sizing

The length of the pipe required and the size of the pump depend on the building loads, it

is important that they are designed together. The ground loop must be sized to meet the

peak thermal power load. The thermal power load that a loop can extract is expressed in

W/m and is dependent on the temperature difference the fluid and the ground

temperatures.

The more pipe used, the greater the amount of energy collected but the more expensive

is the installation. Oversizing is uneconomical. (HeatPumpAssociation, 2015)

Page 24: NMorel-Honours project

24

3 Chapter Three: Implementation

3.1 House Characteristics And Dimensions

The dimensions were assumed for the internal walls to be 4.5 x 6.5 x 2.7 m, for each

window 0.8 x 1 m and the door 0.88 x 1.86 m.

The door is wood made of spruce with a 6 cm thickness; the windows are argon-filled

double glazed, each pane of glass is 4 cm thick.

EAST

Figure 14. Wooden house scheme

Page 25: NMorel-Honours project

25

The walls are composed by an internal wood cladding in pine, a wood wool insulation, a

thin weather grille and an external cladding made in spruce. The thicknesses are

indicated in cm on both figures below. The total thickness is 25.5 cm.

The roof makes a 30° angle with the horizontal. It is covered by a steel sheet from the

outside and the insulation is slightly thicker. Its total thickness is 31.5 cm, the composition

is shown below (figure. 15). The thermal conductivity of each material is also given on

figure 16.

From the house dimensions, the volume and areas have been calculated.

The length (a), and (b) shown in the house scheme were obtained using basic

trigonometric equations:

a =5.1/2

Cos (30°) 𝑎𝑛𝑑 𝑏 = 𝑎 ∗ sin (30°)

The internal volume of the house is:

In In Out Out

Pine Spruce Weather grille Steel Wood wool Glass

k (W/m.K) 0.13 0.14 0.09 50 0.038 1

Figure 15. Wall material composition (to scale 1/10)

Figure 16. Roof material composition (to scale 1/10)

Figure 17. Thermal conductivities of the materials (Wikipedia, 2016)

Page 26: NMorel-Honours project

26

𝑉ℎ𝑜𝑢𝑠𝑒 = 4.5 ∗ 2.7 ∗ 6.5 + (2.25 ∗ 1.45) = 82.23 𝑚3

Assuming that the roof is 30 cm protruding on each side, the south-facing roof area is:

𝐴𝑟𝑜𝑜𝑓 𝑆 = (2.89 + 0.3) ∗ (7.01 + 2 ∗ 0.3) = 24.05 𝑚2

The internal area of the west-facing wall is:

𝐴𝑤𝑎𝑙𝑙 𝑊 = 4.5 ∗ 2.7 + (1.47 − 2.25) = 15.46 𝑚2

Internal area of the east-facing wall:

𝐴𝑤𝑎𝑙𝑙 𝐸 = 𝐴𝑤𝑎𝑙𝑙 𝑊 − (0.8 ∗ 1) = 14.54 𝑚2

Internal area of the north-facing wall:

𝐴𝑤𝑎𝑙𝑙 𝑁 = 6.5 ∗ 2.7 = 17.55 𝑚2

Internal area of the south-facing wall:

𝐴𝑤𝑎𝑙𝑙 𝑆 = 𝐴𝑤𝑎𝑙𝑙 𝑁 − (2 ∗ (0.8 ∗ 1) + (1.86 ∗ 0.88) = 14.07 𝑚2

These areas and volume will serve later in the calculations of heat losses for example.

Page 27: NMorel-Honours project

27

3.2 Solar Collecting Data

A CD-ROM associated with the book “Windows in Building” (Muneer, 2000) contains

three excel spreadsheets which allowed, as a first step, the collection of the solar data.

Hourly values of global and diffuse irradiations

The first step was to obtain the daily-averaged solar radiation G from the NASA website

(NASA, 2016) searching by the location of Villard- de-Lans, for each month of the year.

By entering this value on the excel spreadsheet “calc4-09” (table 1), the number of the

month studied and the latitude of the location, the disaggregation of this global radiation

into hourly values from 5:30 to 11:30 am was obtained for each month.

Table 1. Spreadsheet "calc4-09" screenshot

Figure 18. NASA website screenshot

Calc4-09 Decomposition of averaged-daily irradiation into hourly values

Month Latitude G Hour Hourly values, W/m2

kWh/m2

IG

1 45.078 1.36 11.5 195

10.5 176

9.5 142

8.5 98

7.5 52

6.5 11

5.5 0

Daily totals 1350

Page 28: NMorel-Honours project

28

For the rest of the day (from 12:30 to 6:30 pm), a symmetric image of these values is

considered.

Knowing the global solar radiation emitted at each hour allows an accurate solar daily

study to be done afterward.

The diffuse irradiation 𝐼𝐷 for every hour is calculated using the three following equations

(Muneer et al, 2014):

𝑘𝑇̅̅ ̅ =𝐼𝐺

𝐼𝐸

�̅� = 𝐼𝐷𝐼𝐺

�̅� = 0.89𝑘𝑇̅̅ ̅2− 1.185𝑘𝑇̅̅ ̅ + 0.95

Hence, 𝐼𝐷 = �̅̅� ∗ 𝐼𝐺

Where 𝑘𝑇̅̅ ̅ and �̅� are the monthly-averaged clearness index and diffuse ratio given in the

article. 𝐼𝐺 and 𝐼𝐷 are the global and diffuse radiations on a horizontal surface expressed

in W/m². 𝐼𝐸 is defined as the extra-terrestrial radiation received under the absence of any

atmosphere (W/m²) (T Muneer & Kambedezis, 2007).

When calculating the production of a solar thermal or PV panel, the data required as the

“power received” in the calculations is called slope global (W/m²). It is a function of the

direct, diffuse and reflected radiations.

When calculating the solar gains through a window, each of the three components: direct

diffuse and reflected are influenced differently from the others, a coefficient will be then

applied to each of them.

Page 29: NMorel-Honours project

29

Hence, a complete solar data base is needed including the direct radiation (named as

slope beam in this study), sky diffuse, ground reflection and slope global for each hour of

the day and for each month. These are components of the global irradiation expressed in

W/m² and are obtained from the excel spreadsheet “calc4-10” (table 2). The solar angle

incidence will also be necessary to relieve (shown below as “solar inc”).

When using this excel file, the following primary information have to be entered:

Villard-de-Lans latitude/longitude: 45.078 N / 5.5514 E

Year: 2015

Month number: according to the month during which the solar data are collected.

Calc4-10 Slope irradiance

SURFACE

LAT 45.1 North=+ve Aspect 180

LONG 5.55 West=+ve Tilt 90

LSM 0 West=+ve Rho 0.2

Year 2015

Month 1

Day Hour IG ID EOT DEC Cor. Solar Solar Solar IDN ERAD Slope Sky Ground Slope

W/m2 W/m2 term alt. azim. inc. - W/m2 beam diffuse reflect. global

16 1 0 0 -0.16 -21.0 0.53 -65.2 16.9 113.7 16 0 0 0 0 0

16 2 0 0 -0.16 -21.0 0.53 -59.7 45.0 110.9 16 0 0 0 0 0

16 3 0 0 -0.16 -21.0 0.53 -51.0 64.5 105.7 16 0 0 0 0 0

16 4 0 0 -0.16 -21.0 0.53 -40.9 78.6 98.6 16 0 0 0 0 0

16 5 0 0 -0.16 -21.0 0.53 -30.4 90.0 90.0 16 0 0 0 0 0

16 6 0.0 0.0 -0.16 -21.0 0.53 -19.9 100.2 80.4 16 0 0 0 0 0

16 7 11.4 0.0 -0.16 -21.0 0.53 -9.6 110.1 70.2 16 0 0 0 1 1

16 8 52.3 33.0 -0.16 -21.0 0.53 2.2 123.1 56.9 16 55 0 20 5 26

16 9 98.0 57.8 -0.16 -21.0 0.53 8.5 131.5 49.1 16 209 178 73 10 260

16 10 141.8 89.6 -0.16 -21.0 0.53 15.7 143.8 39.0 16 381 150 74 14 238

16 11 176.2 113.5 -0.16 -20.9 0.53 20.9 157.5 30.3 16 502 152 84 18 254

16 12 195.2 126.3 -0.16 -20.9 0.53 23.6 172.4 24.8 16 565 156 90 20 266

16 13 195.2 126.3 -0.16 -20.9 0.53 23.6 187.6 24.8 16 565 156 90 20 266

16 14 176.2 113.5 -0.16 -20.9 0.53 20.9 202.5 30.3 16 503 152 84 18 253

16 15 141.8 89.7 -0.16 -20.9 0.53 15.7 216.2 39.0 16 382 150 74 14 238

16 16 98.0 57.9 -0.16 -20.9 0.53 8.6 228.5 49.1 16 210 176 72 10 258

16 17 52.3 32.6 -0.16 -20.9 0.53 2.2 237.0 57.0 16 55 0 20 5 26

16 18 11.4 0.0 -0.16 -20.9 0.53 -9.6 249.9 70.2 16 0 0 0 1 1

16 19 0.0 0.0 -0.16 -20.9 0.53 -19.8 259.9 80.5 16 0 0 0 0 0

16 20 0 0 -0.16 -20.9 0.53 -30.3 270.1 90.1 16 0 0 0 0 0

16 21 0 0 -0.16 -20.9 0.53 -40.8 281.5 98.7 16 0 0 0 0 0

16 22 0 0 -0.16 -20.9 0.53 -50.9 295.7 105.9 16 0 0 0 0 0

16 23 0 0 -0.16 -20.9 0.53 -59.5 315.2 111.1 16 0 0 0 0 0

16 24 0 0 -0.16 -20.8 0.53 -65.0 343.2 113.9 16 0 0 0 0 0

Table 2. Spreadsheet calc4-10 screenshot

Page 30: NMorel-Honours project

30

Surface:

Aspect: the angle in degree according to the orientation of the window or panel.

Tilt: the angle in degree of the surface with horizontal.

For example, for collecting solar radiations data on a south-oriented vertical window: the

aspect is 180° and the tilt, 90°.

Rho: 0.2 is an assumed value of the coefficient of reflectivity of the surrounding. (Muneer,

2000)

Day: 16, taken in the middle of the month for the study to be the most representative

possible.

The hourly values of 𝐼𝐺 and 𝐼𝐷 obtained previously can then be entered in the columns

designed for that purpose (filled in green on previous table), and all the solar radiation

components and angles data can be collected.

3.3 Analysis of the Needs

Passive gains

Solar gains through windows

Two windows of 0.8 m² area each are facing south and another of 0.8 m² is facing east.

Accordingly, two sets of solar components have been collected respectively for a 180°

and 90° aspect and both for a 90° tilt (vertical surfaces). The tables of solar data collected

for the south-facing windows are presented below as examples.

Table 3. Slope beam (W/m²): Aspect=180° - Tilt=90°

Hours January February March April May June July August September October November December

5.5 0 0 0 0 0 0 0 0 0 0 0 0

6.5 0 0 0 0 0 0 0 0 11 0 0 0

7.5 0 0 55 27 5 0 0 25 53 58 0 0

8.5 179 111 106 68 43 32 45 73 103 100 106 0

9.5 151 160 156 108 81 69 87 119 152 143 143 147

10.5 152 199 197 140 110 98 120 155 191 179 176 178

11.5 156 221 220 157 127 114 138 175 212 199 194 196

12.5 156 221 220 157 126 114 138 175 212 199 194 196

13.5 152 199 197 139 110 98 120 156 191 179 176 178

14.5 150 159 156 107 80 69 87 120 152 144 144 147

15.5 177 110 105 67 43 32 45 74 103 101 107 0

16.5 0 0 54 27 5 0 0 26 54 60 0 0

17.5 0 0 0 0 0 0 0 0 0 0 0 0

18.5 0 0 0 0 0 0 0 0 0 0 0 0

Page 31: NMorel-Honours project

31

The hourly power admitted through a vertical window is given by:

𝐼𝑣𝑒𝑟𝑡𝑖𝑐𝑎𝑙 𝑤𝑖𝑛𝑑𝑜𝑤 = ((𝐼𝑏𝑒𝑎𝑚 ∗ 𝑇(𝜃)) + (𝐼𝑠𝑘𝑦 𝑑𝑖𝑓𝑓 ∗ 𝜏𝑠𝑘𝑦 𝑑𝑖𝑓𝑓) + (𝐼𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓 ∗ 𝜏𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓)) ∗ 𝑔𝑙𝑎𝑧𝑒𝑑 𝑎𝑟𝑒𝑎 (W)

With 𝑇(𝜃) = 1.018 ∗ 𝑇0 ∗ (cos 𝜃 + sin3𝜃 ∗ cos 𝜃)

Where 𝐼𝑏𝑒𝑎𝑚, 𝐼𝑠𝑘𝑦 𝑑𝑖𝑓𝑓 and 𝐼𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓 are the slope beam, the sky diffuse and the ground

reflected radiations in W/m². 𝑇𝜃 is the transmission of a pane of glass at a given solar

angle of incidence 𝜃 in radians (= degrees * π

180).

𝑇0 is the glass transmission coefficient at normal incidence and is taken as 0.54

considering that the glazing’s are double coated. The coefficient is given in the book

“Windows in Building” (Tariq Muneer, 2000, p. 115) in the column solar radiant heat direct.

𝜏𝑔𝑟𝑜𝑢𝑛𝑑 𝑟𝑒𝑓 and 𝜏𝑠𝑘𝑦 𝑑𝑖𝑓𝑓 are the glass transmission coefficients of the ground reflected and

sky diffuse radiations, both equal to 𝑇(𝜃) at a 60° solar angle incidence.

A table listing the values of 𝑇(𝜃) for each aspect was added to the database before the

calculation, as the example below shows:

Table 4. Sky diffuse/Ground reflection (W/m²): Aspect=180° - Tilt=90°

Hours Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref. Sky diff. Grd ref.

5.5 3 1 14 6 23 10 21 10 14 4

6.5 1 10 3 23 10 36 16 45 21 44 21 32 15 19 6

7.5 20 5 18 5 48 13 61 20 71 27 69 33 70 34 71 27 57 17 33 7 6 2

8.5 72 10 64 14 89 24 97 32 106 39 111 44 116 47 111 40 97 29 67 16 47 9 20 6

9.5 74 14 99 23 128 35 131 42 138 50 143 55 151 58 149 52 135 40 100 25 76 16 67 12

10.5 84 18 127 30 158 44 157 50 163 58 167 63 179 67 178 61 165 49 125 32 99 21 89 17

11.5 90 20 143 34 175 49 171 55 176 62 180 67 193 72 193 65 181 53 140 36 112 25 101 20

12.5 90 20 143 34 175 49 171 55 176 62 180 67 193 72 193 65 181 53 140 36 112 25 101 20

13.5 84 18 127 30 158 44 157 50 163 58 167 63 179 67 178 61 165 49 126 32 99 21 89 17

14.5 74 14 99 23 127 35 131 42 138 50 143 55 151 58 149 52 135 40 100 25 76 16 67 12

15.5 72 10 64 14 89 24 97 32 106 39 111 44 116 47 111 40 97 29 67 16 48 9 20 6

16.5 20 5 18 5 48 13 61 20 71 27 69 33 70 34 71 27 57 17 33 7 6 2

17.5 1 10 3 23 10 36 16 45 21 44 21 32 15 19 6

18.5 3 1 14 6 23 10 21 10 14 4

OctoberJanuary February March April November DecemberMay June July August September

Hours January February March April May June July August September October November December

5.5 0.18 0.07 -0.08 -0.20 -0.33 -0.36 -0.34 -0.26 -0.05 0.02 0.15 0.21

6.5 0.34 0.32 0.13 -0.04 -0.16 -0.21 -0.18 -0.08 0.07 0.27 0.32 0.36

7.5 0.48 0.40 0.30 0.15 0.03 -0.03 0.00 0.11 0.25 0.37 0.46 0.49

8.5 0.52 0.49 0.42 0.31 0.19 0.13 0.16 0.27 0.39 0.47 0.51 0.52

9.5 0.53 0.53 0.49 0.41 0.31 0.25 0.28 0.37 0.47 0.52 0.53 0.53

10.5 0.54 0.53 0.52 0.46 0.38 0.33 0.35 0.44 0.51 0.53 0.54 0.54

11.5 0.54 0.54 0.53 0.48 0.41 0.36 0.39 0.46 0.52 0.53 0.54 0.54

12.5 0.54 0.54 0.53 0.48 0.41 0.36 0.39 0.46 0.52 0.53 0.54 0.54

13.5 0.54 0.53 0.52 0.46 0.38 0.33 0.35 0.44 0.51 0.53 0.54 0.54

14.5 0.53 0.52 0.49 0.41 0.31 0.25 0.28 0.38 0.47 0.52 0.53 0.53

15.5 0.52 0.49 0.42 0.30 0.19 0.13 0.16 0.27 0.39 0.47 0.51 0.52

16.5 0.48 0.40 0.30 0.15 0.02 -0.03 0.00 0.11 0.26 0.37 0.46 0.49

17.5 0.34 0.32 0.13 -0.04 -0.16 -0.21 -0.18 -0.08 0.07 0.27 0.32 0.36

18.5 0.18 0.07 -0.08 -0.21 -0.33 -0.36 -0.34 -0.26 -0.05 0.02 0.15 0.21

Table 5. Values of T (θ) - Aspect=180° - Tilt=90°

Page 32: NMorel-Honours project

32

As well as another listing of the glazed areas and transmission coefficients:

The power admitted can now be calculated using the previous formula for each hour of

the day of each month. Daily summing these hourly powers gives an energy gains in

Wh/day which can be converted in kWh/day, most explicit.

Sensible heat emission of humans

Due to their metabolic activity, the human bodies lose heat to the surrounding contributing

to the passive gains in the house.

Assuming that four people occupy the house during 12 hours a day, with a small degree

of activity which could be qualified as “seated, very light work”, their heat emission would

be equal to 70 W each. (ASHRAE, 2001)

The total energy gained in the house per day is calculated by:

𝐸 = 𝑂𝑐𝑐𝑢𝑝𝑎𝑛𝑡𝑠 𝑛𝑢𝑚𝑏𝑒𝑟 ∗ 𝑜𝑐𝑐𝑢𝑝𝑎𝑛𝑐𝑦 𝑑𝑢𝑟𝑎𝑡𝑖𝑜𝑛 (ℎ) ∗ ℎ𝑒𝑎𝑡 𝑒𝑚𝑖𝑠𝑠𝑖𝑜𝑛 (𝑊) (𝑊ℎ

𝑑𝑎𝑦)

Heat losses analysis

General methodology

The overall thermal losses studies have been done

separately on the roof, windows, door and each wall

using the same procedure each time even though,

depending on the element, few steps can be added or

removed.

The inside temperature is considered to be maintained

18°C all over the year insuring a thermal comfort for the

occupants.

Table 6. Glass areas and transmission coefficients of radiation

Figure 19. Heat transfer phenomena through the wall

Area (m² ) Ϯs. diff Ϯground ref

Window sclear coated (South) 1.6

Window clear coated (East) 0.80.45 0.45

Page 33: NMorel-Honours project

33

For each component, the heat transfer occurs via an internal convection, several

conductions through the element and an external convection releasing heat to the

environment (figure 19).

Taking the wall as an example, the approach consists in first

assuming an internal surface temperature 𝑇𝑖𝑖 (visible on

figure 20); this allows, after few calculations related to fluid

mechanics and which will be detailed later, to find out an

approximation of how much heat is transferred by the first

convection.

Considering a steady state, meaning that the energy

transferred by each heat flux is equal, it is admitted: 𝑞𝑐𝑜𝑛𝑣 1 =

𝑞𝑐𝑜𝑛𝑑1 = 𝑞𝑐𝑜𝑛𝑑2 = 𝑞𝑐𝑜𝑛𝑑3 = 𝑞𝑐𝑜𝑛𝑑4 = 𝑞𝑐𝑜𝑛𝑣 2

In this manner, a value of 𝑇𝑤𝑖 can be found by isolation using

the conduction heat transfer relation: 𝑞 =𝑘

𝑒∗ (𝑇𝑖𝑖 − 𝑇𝑤𝑖)

Where k and e are the thermal conductivity and the

thickness of the material known from previously.

All other intermediate temperatures at each contact point between materials 𝑇𝑤𝑖𝑖, 𝑇𝑤0′ and

𝑇𝑤0 are found the same way.

Now again, another series of calculations is done to obtain the external convection heat

transfer between 𝑇𝑤𝑜 and 𝑇𝑜𝑢𝑡.

So each heat loss by convection has been calculated regarding different temperatures,

the first one: 𝑇𝑖𝑛 and 𝑇𝑖𝑖 ; the second one 𝑇𝑤𝑜 and 𝑇𝑜𝑢𝑡. In theory and since the system

was assumed to be in a steady state, they should be equal but it is not the case as 𝑇𝑖𝑖 is

only an approximation. That is where the “goal seek function” available in “Excel” takes

place, looking at a 0 value for the relation 𝑄𝑐𝑜𝑛𝑣 1 − 𝑄𝑐𝑜𝑛𝑣 2 by changing the internal

surface temperature of the element which then becomes the exact value.

Figure 20. Temperature profile through the wall

Page 34: NMorel-Honours project

34

The complete procedure is detailed below:

𝑇𝑖𝑖 is assumed, slightly lower than the inside temperature

The film temperature is calculated by 𝑇𝑓 =(𝑇𝑖,𝑖+𝑇𝑖𝑛𝑠𝑖𝑑𝑒)

2 (𝐾) allowing to find the air

properties: ρ, 𝐶𝑝, µ, ν, α and 𝑃𝑟 (defined below) at this same temperature.

Then the first set of calculations which will permit to find the coefficient of

convection is as follow:

𝛽 =1

𝑇𝑓 (𝐾−1)

Rayleigh number:

𝑅𝑎𝐿 =𝑔𝛽(𝑇𝑠𝑢𝑟𝑓𝑎𝑐𝑒,𝑖 − 𝑇𝑖𝑛𝑠𝑖𝑑𝑒)𝐿

3

𝜈𝛼

where ν is the kinematic viscosity in m²/s

α is the thermal diffusivity in m²/s

g is the gravitational acceleration in m/s²

β is the volumetric thermal expansion coefficient in K-1

L is the height of the surface studied

Nusselt number: 𝑁𝑢𝐿 =

(

0.8250 +0.387 𝑅𝑎𝐿

16

[1+(0.492/𝑃𝑟)916]

827

)

2

The coefficient of convection ℎ𝑖 can now be calculated, using ℎ𝑖 = 𝑁𝑢𝐿𝑘

𝐿 (W/m².K)

And the final value of the first convection heat transfer per 𝑚2: 𝑞𝑐𝑜𝑛𝑣1 =

ℎ𝑖 (𝑇𝑖𝑛𝑠𝑖𝑑𝑒 − 𝑇𝑖𝑖) (W/𝑚2)

In a steady state, 𝑞𝑐𝑜𝑛𝑣1 is equal to 𝑞𝑐𝑜𝑛𝑑1, so as to find 𝑇𝑤𝑖:

𝑞𝑐𝑜𝑛𝑑1 = 𝑞𝑐𝑜𝑛𝑣1 (W

𝑚2) =

𝑘

𝑒∗ (𝑇𝑖𝑖 − 𝑇𝑤𝑖) <=> 𝑇𝑤𝑖 = 𝑇𝑖𝑖 −

𝑒 ∗ 𝑞𝑐𝑜𝑛𝑣1

𝑘(𝐾)

Where k is the thermal conductivity in W/m.K and e the material thickness

in m.

And so on for the calculations of 𝑇𝑤𝑖𝑖, 𝑇𝑤0′ and 𝑇𝑤0 using the same relation.

At this stage, the focus is on the last convection.

A new film temperature (new air properties) is calculated considering, this time,

𝑇𝑤𝑜 and 𝑇𝑜𝑢𝑡. The following calculations are the same as above: 𝛽, 𝑅𝑎𝐿, 𝑁𝑢𝐿,

Page 35: NMorel-Honours project

35

according to the new 𝑇𝑓 are determined and permit to obtain the external

convection coefficient ℎ0, and then 𝑞𝑐𝑜𝑛𝑣2.

All transfers were determined, the aim is now to define the right internal surface

temperature of the wall. As 𝑇𝑖𝑖 is an assumption at the beginning and serves to

calculate everything else: both 𝑞𝑐𝑜𝑛𝑣 found are not equal.

The “goal seek” function is used finding the correct 𝑇𝑖𝑖 for Δ q = 𝑞𝑐𝑜𝑛𝑣1 − 𝑞𝑐𝑜𝑛𝑣2 =

0. The heat losses can be calculated.

To find out the quantity of heat lost through the wall, the thermal transmittance U

is needed:

𝑈 =1

𝑅𝑐𝑜𝑛𝑣 1+𝑅𝑐𝑜𝑛𝑑1,2,3,4+𝑅𝑐𝑜𝑛𝑣 2 (W/𝒎𝟐.K)

With 𝑅𝑐𝑜𝑛𝑣 =1

ℎ and 𝑅𝑐𝑜𝑛𝑑 =

𝑒

𝑘 (𝒎𝟐.K/W)

The thermal losses are finally found using 𝑄 = 𝑈𝐴(𝑇𝑖𝑛 − 𝑇𝑜𝑢𝑡) (W)

Where A is the wall area in 𝑚2

And so on for the other walls of which only the area differs.

The outside temperature 𝑇𝑜 is always taken as the average temperature of the month

corresponding (figure 21) obtained from the NASA website (NASA, 2016).

The methodology is the same for every element. Some can have more or less conduction

heat transfers through themselves: the door induces only one of them (figure 22).

Page 36: NMorel-Honours project

36

Difference in the approach for the roof

The roof can be compared to a sloping wall making an angle θ with the vertical as shown

in the figure 20. It induces the inclusion of cos(θ) in the calculation of the Rayleigh number

for both convections.

Hence, the equation becomes:

𝑅𝑎𝐿 =𝑔𝛽 cos(θ) (𝑇𝑠𝑢𝑟𝑓𝑎𝑐𝑒,𝑖 − 𝑇𝑖𝑛𝑠𝑖𝑑𝑒)𝐿

3

𝜈𝛼

Difference in the approach for the windows

Changes occur the most in the procedure when calculating the heat transfer through the

windows.

As it can be seen on the figure 24, there are three transfers by convection combined with

radiation, and conductions. According to “CIBSE guide C” (CIBSE, 2007), this implies the

use of some more radiation formulas.

Figure 22. Heat transfer through the door

Θ = 60°

Figure 23. Roof 𝜃 angle sketch

Taverage (°C)

January -0.8

February 0.3

March 3.7

April 6.7

May 11.8

June 15.6

July 18.2

August 17.9

September 13.5

October 9.2

November 3.3

December 0.3

Figure 21. Monthly average temperatures

Page 37: NMorel-Honours project

37

During the calculation of the first convection heat transfer, an

internal radiation heat transfer coefficient ℎ𝑟𝑖 (W/𝒎𝟐.K) must be

added to ℎ𝑖 which becomes:

ℎ𝑖 = 𝑁𝑢𝐿𝑘

𝐿+ ℎ𝑟𝑖 𝑤𝑖𝑡ℎ ℎ𝑟𝑖 = 5.3 ×

𝜀ℎ0.83

(W/𝒎𝟐. K)

Where 𝜀ℎ is the hemispherical emissivity of a coated surface

equal to 0.88.

The first conduction occurs the same way as previously.

Again, another internal radiation heat transfer coefficient is considered during the transfer

2 (shown on the figure 24), calculated differently this time:

ℎ𝑟2 =4 ∗ σ ∗ 𝑇𝑓

3

1𝜀ℎ + 1

+1

𝜀ℎ − 1

𝑎𝑛𝑑 ℎ2 =𝑁𝑢𝐿𝑘

𝐿+ ℎ𝑟2 (W/𝒎𝟐. K)

Where σ is the Stefan-Boltzmann constant equal to 5.67 x 10 -8 W/m2/K4.

The heat transferred by “Conv 2 + Rad 2” between the two panes of

glass has just been calculated. But here, the inside surface

temperature of the second pane of glass 𝑇𝑤𝑜 can’t be calculated as

the transfer did not occur by conduction (so the relation 𝑞 =𝑘

𝑒∗ (𝑇𝑤𝑖 −

𝑇𝑤𝑜) can’t be used as it was before).

Thus, a second assumption of temperature for 𝑇𝑤𝑜 is made so 𝑇𝑤𝑜𝑜

can be calculated.

For the external transfer, the heat transfer coefficient is given by:

ℎ2 =𝑁𝑢𝐿𝑘

𝐿+ 𝐸 × ℎ𝑟𝑜 𝑤𝑖𝑡ℎ ℎ𝑟𝑜 = 5.3 ×

𝜀ℎ0.83

(W/𝒎𝟐. K)

Where the emissivity factor 𝐸 is the product of the view factor equal to 0.81 and the

emissivity of the surface 𝜀ℎ.

Figure 24. Heat transfer through

a window

Figure 25. Temperature profile through a window

Page 38: NMorel-Honours project

38

All heat transfers can be determined and after that, the goal seek function can look at the

exact values for 𝑇𝑖𝑖 and 𝑇𝑤𝑜 working on both Δ q = 𝑞𝑐𝑜𝑛𝑣+𝑟𝑎𝑑 1 − 𝑞𝑐𝑜𝑛𝑣+𝑟𝑎𝑑 2 and Δq =

𝑞𝑐𝑜𝑛𝑣+𝑟𝑎𝑑 2 − 𝑞𝑐𝑜𝑛𝑣+𝑟𝑎𝑑 3 , simultaneously.

The U-value (thermal transmittance) and thermal losses can finally be calculated as

explained in the general method.

The thermal losses through the frame are also considered and are determined with the

same manner as the door.

Ventilation

The house is naturally ventilated. The outside air infiltrates through small gaps and

contributes to the ventilation as well as the window openings do.

The whole house air volume is assumed to be renewed every 2 hours, inducing an air

change rate n = 0.5/h.

The thermophysical properties of the air can be worked out for the average temperature

between the outside and inside which depends on the month studied. Thus, the air density

ρ (kg/ m3) and specific heat capacity 𝐶𝑝 (kJ/kg.K) are determined and the heat lost is

found:

𝑄 = 𝑛 ∗ 𝑚 ̇ 𝐶𝑝 ∆𝑇 (𝑊) 𝑤𝑖𝑡ℎ 𝑚 ̇ =𝑉ℎ𝑜𝑢𝑠𝑒3600

∗ ρ

Where 𝑚 ̇ is the mass flow rate in kg/s and ∆𝑇 is the temperature difference between inside

(18˚C) and outside the house.

Thermal bridges and floor

In order to quantify the heat lost by the areas which are not as

well insulated as their surroundings - the thermal bridges (figure

26), they are assumed to be the cause of 5 % of the overall

heat losses (ADEME, 2016).

Similarly for the floor through which usually; as it can be seen

on the figure 27, between 7 and 10 % of the heat is lost. 9% is

considered in this study. Figure 26. Example of

thermal bridges at wall/floor junction

Page 39: NMorel-Honours project

39

The following figure is taken from a French website and gives indicatives percentages of

heat lost for each element:

Hence, the losses through the thermal bridges and the floor are given by:

𝑄 = (% 𝑤𝑎𝑛𝑡𝑒𝑑

100 −% ℎ𝑒𝑎𝑡 𝑙𝑜𝑠𝑡𝑊+𝐷+𝑊+𝑅+𝑉) ∗ (

100 −% ℎ𝑒𝑎𝑡 𝑙𝑜𝑠𝑡𝑊+𝐷+𝑊+𝑅+𝑉% ℎ𝑒𝑎𝑡 𝑙𝑜𝑠𝑡𝑊+𝐷+𝑊+𝑅+𝑉

) ∗ ℎ𝑒𝑎𝑡 𝑙𝑜𝑠𝑡𝑊+𝐷+𝑊+𝑅+𝑉

Summing all these losses through each element obtained so far, gives the global heat

power loss of the house.

The daily quantity of energy lost in Wh is obtained by multiplying this power by 24 hours

and by subtracting the passive gains from them.

Also, a simulation of the heat lost during the coldest day that the city of Villard-de-Lans

has ever known will be done. This happened the 3rd of January 1971, and the temperature

went down to -27.1 ˚C (Wikipedia, 2016). The data obtained from it are really important

for sizing the energetic installations afterward.

Figure 27. Heat losses of a traditional house (ADEME, 2016)

Thermal bridges

Page 40: NMorel-Honours project

40

Hot water demand

The domestic hot water used for showers, hot water taps and others, is assumed to be

50 L per day and per person; and remains constant throughout the year.

Hence, the requirements for four persons are V = 200 L = 0.2 𝑚3 corresponding to a mass

𝑚 = 𝑉 ∗ 𝜌𝑤𝑎𝑡𝑒𝑟 with 𝜌𝑤𝑎𝑡𝑒𝑟 = 996 𝑘𝑔/𝑚3 , the water density.

Considering that this water has to be heated up from 15 to 65˚C (temperature of

deliveration), the energy required to meet the needs is calculated as follows:

𝑄𝑑𝑒𝑚𝑎𝑛𝑑 = 𝑚 𝐶𝑝𝑤𝑎𝑡𝑒𝑟 ∆𝑇 (𝐽) = 𝑚 𝐶𝑝𝑤𝑎𝑡𝑒𝑟∆𝑇

3600(𝑊ℎ)

Where 𝐶𝑝 is the water specific heat capacity equal to 4185 J/kg.K

The needs having been analysed, the procedure focuses now on the way they will be

met. In the first instance, the consideration is that the heat losses of the house found

earlier are compensated by an electric heating system. The feasibility of a solar thermal

system to meet the load in hot water is now studied (option 1).

Page 41: NMorel-Honours project

41

3.4 Solar Thermal Study

As said previously in the part “solar collecting data”, the data required in the calculation

of the solar thermal panel production is the slope global (W/m²).

The hourly values of 𝐼𝐺 and 𝐼𝐷 for each month were listed as the table below shows:

From them, the hourly values of the slope global were found.

The study has been done in the case where the collectors would cover the south-facing

roof area.

Therefore, the slope global was found via the spreadsheet “calc4-10” for a 180˚ aspect

for each month

Moreover, the roof making a 30˚ angle with the horizontal, 30˚ tilt was entered.

As obvious, the other information enounced previously remain the same.

The values of slope global were listed this way:

HOURS January February March April May June July August September October November December

5.5 0 0 0 6.5 80.7 139.9 135.9 24.7 0.0 0 0 0

6.5 0.15285376 0 17.9 92.9 162.9 218.9 219.6 145.3 48.9 0 0 0

7.5 32.3 31.7 83.9 170.1 247.0 302.7 309.0 230.9 122.1 42.5 11.6 0

8.5 52.9 80.9 155.9 247.2 328.6 383.9 396.0 316.0 197.8 84.5 50.6 34.8

9.5 81.8 128.7 222.4 315.8 399.9 454.4 471.9 391.3 266.6 136.6 90.3 69.6

10.5 103.5 150.6 273.6 367.3 452.8 506.5 528.2 447.6 318.9 177.1 121.4 98.7

11.5 115.2 172.8 301.6 395.0 481.1 534.3 558.2 477.8 347.2 199.2 138.5 114.8

12.5 115.2 172.9 301.7 395.1 481.1 534.3 558.2 477.7 347.1 199.1 138.5 114.8

13.5 103.6 151.0 273.9 367.5 452.9 506.6 528.1 447.4 318.6 176.8 121.4 98.7

14.5 81.9 128.8 222.9 316.1 400.1 454.4 471.8 391.0 266.1 136.1 90.2 69.6

15.5 53.0 81.0 156.5 247.5 328.8 384.0 395.8 315.6 197.3 83.9 50.5 34.827813

16.5 32.0 31.9 84.6 170.4 247.2 302.8 308.8 230.5 121.5 42.3 11.6 0

17.5 0.2 0 18.0 93.1 162.9 218.9 219.5 145.1 37.1 0.0 0 0

18.5 0 0 0 6.5 80.4 139.8 136.2 24.7 0.0 0 0 0

HOURS Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2) Ig (W/m2) Id (W/m2)

5.5 0.0 0.0 0.0 0.0 0.0 8.1 6.8 59.5 39.8 103.2 63.9 96.6 58.7 40.3 25.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0

6.5 11.4 0.0 0.0 0.0 26.1 18.8 97.6 63.6 159.8 100.7 209.3 126.3 211.0 124.9 147.3 89.3 60.9 39.0 0.0 0.0 0.0 0.0 0.0 0.0

7.5 52.3 33.0 50.2 33.2 128.6 81.0 204.5 127.7 274.0 166.7 326.7 193.0 338.9 196.3 271.3 159.9 170.0 104.1 70.5 46.6 16.6 12.2 0.0 0.0

8.5 98.0 57.8 140.5 88.6 243.7 147.1 317.4 192.3 390.7 232.0 444.5 258.2 467.9 266.8 399.8 230.6 288.8 171.3 159.9 101.6 85.1 55.5 55.9 36.2

9.5 141.8 89.6 230.7 140.9 354.0 207.9 421.5 250.0 496.2 289.6 549.5 315.3 583.3 329.3 516.9 294.1 400.4 232.5 247.6 152.7 155.6 98.9 119.5 76.3

10.5 176.2 113.5 303.5 181.6 440.8 254.8 501.7 293.7 576.3 332.8 628.4 358.0 670.4 376.3 606.3 342.2 487.4 279.4 317.6 192.1 213.4 133.0 172.6 108.1

11.5 195.2 126.3 344.1 203.9 488.6 280.4 545.3 317.2 619.5 356.0 670.8 380.8 717.3 401.6 654.7 368.2 535.0 304.9 356.4 213.6 245.8 151.7 202.6 125.7

12.5 195.2 126.3 344.1 203.9 488.6 280.4 545.3 317.2 619.5 356.0 670.8 380.8 717.3 401.6 654.7 368.2 535.0 304.8 356.4 213.6 245.8 151.7 202.6 125.7

13.5 176.2 113.5 303.5 181.6 440.8 254.8 501.7 293.7 576.3 332.8 628.4 358.0 670.4 376.3 606.3 342.1 487.4 279.3 317.6 192.1 213.4 132.9 172.6 108.1

14.5 141.8 89.7 230.7 141.0 354.0 208.0 421.5 250.1 496.2 289.6 549.5 315.3 583.3 329.3 516.9 294.0 400.4 232.4 247.6 152.6 155.6 98.8 119.5 76.3

15.5 98.0 57.9 140.5 88.8 243.7 147.2 317.4 192.4 390.7 232.0 444.5 258.2 467.9 266.8 399.8 230.6 288.8 171.1 159.9 101.4 85.1 55.4 55.9 36.2

16.5 52.3 32.6 50.2 33.3 128.6 81.2 204.5 127.9 274.0 166.8 326.7 193.0 338.9 196.3 271.3 159.7 170.0 103.9 70.5 46.4 16.6 12.2 0.0 0.0

17.5 11.4 0.0 0.0 0.0 26.1 18.9 97.6 63.8 159.8 100.8 209.3 126.4 211.0 124.9 147.3 89.1 60.9 38.8 0.0 0.0 0.0 0.0 0.0 0.0

18.5 0.0 0.0 0.0 0.0 0.0 0.0 8.1 6.8 59.5 39.9 103.2 63.9 96.6 58.6 40.3 25.7 0.0 0.0 0.0 0.0 0.0 0.0 0.0

DecemberJanuary February March April May June July August September October November

Table 7. Global and diffuse radiations (W/m²) for each month of the year at Villard-de-Lans

Table 8. Slope global at Villard-de-Lans (W/m²) - Aspect=180° - Tilt=30°

Page 42: NMorel-Honours project

42

Calculations of production

For each hour of the day in each month, the heat production per m²collector is found by:

𝑄𝑐𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟 = 𝑆𝑙𝑜𝑝𝑒 𝑔𝑙𝑜𝑏𝑎𝑙 ∗ % 𝑐𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟 𝑒𝑓𝑓𝑖𝑒𝑛𝑐𝑦 ( W/m²)

This power corresponds to the heat that 1 m² of collector can transfer to the solar fluid

circulating through.

The objective now is to determine a reasonable area to meet the requirements. As said

in the literature review, the collectors can’t be sized to meet the 200 L hot water needs in

winter, they would be oversized in summer.

The hot water production in litres at terms of each hour of the sunshine duration, for a

typical day of each month, can be determined this way:

𝑉ℎ𝑜𝑡 𝑤𝑎𝑡𝑒𝑟𝑚2𝑐𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟

=𝑄𝑐𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟𝑄𝑑𝑒𝑚𝑎𝑛𝑑200

(𝐿

m2)

Where 𝑄𝑐𝑜𝑙𝑙𝑒𝑐𝑡𝑜𝑟 is the power provided by the collector during an hour which makes it an

amount of energy in Wh, and 𝑄𝑑𝑒𝑚𝑎𝑛𝑑/200 is the energy needed to heat 1 L of water.

An example of table presenting the volume of hot water

produced according to the collector production is shown on

the table 9.

In this manner, the quantity of water heated up over the day

can be seen accurately so as to be aware of when enough

hot water is available for use. Plus, summing these quantitites

gives the total water volume heated up at the end of the day

for 1 m² collector.

The collector area required in m² is finally found by:

𝐴𝑛𝑒𝑒𝑑𝑒𝑑 =𝑉𝐷𝑎𝑖𝑙𝑦 ℎ𝑜𝑡 𝑤𝑎𝑡𝑒𝑟 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑/m² (𝐿)

𝑉𝐻𝑜𝑡 𝑤𝑎𝑡𝑒𝑟 𝑤𝑎𝑛𝑡𝑒𝑑 (𝐿)

For the month studied

W/m² prod L hot water prod

5.5 0.0 0.0

6.5 0.0 0.0

7.5 0.0 0.0

8.5 20.0 0.3

9.5 130.0 2.2

10.5 140.0 2.4

11.5 170.0 2.9

12.5 180.0 3.1

13.5 180.0 3.1

14.5 170.0 2.9

15.5 140.0 2.4

16.5 130.0 2.2

17.5 20.0 0.3

18.5 0.0 0.0

Total (L/m²) 22.11

January

Table 9. Hot water production (example) in L//m² collector

Page 43: NMorel-Honours project

43

Once the collector area is chosen, the total daily hot water produced for each month is

known, so the amount of energy needed by another source to heat up the rest is

calculated monthly with:

𝑄𝑛𝑒𝑒𝑑𝑒𝑑 =((200 − 𝑉𝐷𝑎𝑖𝑙𝑦 ℎ𝑜𝑡 𝑤𝑎𝑡𝑒𝑟 𝑝𝑟𝑜𝑑𝑢𝑐𝑒𝑑) ∗ 𝜌𝑤𝑎𝑡𝑒𝑟 ∗ 𝐶𝑝𝑤𝑎𝑡𝑒𝑟 ∗ ∆𝑇)

3600(𝑊ℎ)

Both studies with different aspects can then be compared in terms of hot water production

and energy required from the photovoltaic system to meet the rest of the load.

Pump sizing

The system requires a circulating pump to insure the flow rate through the collector of

which the size is dependent on different factors and has to be calculated.

First of all, the velocity of the fluid circulating is:

𝑣 =𝑞

𝑆=

𝑞

(𝜋4 ∗ 𝐷𝑖

2)

Where q is the rated volume flow rate of fluid in 𝑚3/𝑠 given by the collector manufacturer

and 𝐷𝑖 the internal diameter of pipe in m.

The number of Reynold is found:

𝑅𝑒 =𝜌𝑉𝐷𝑖

2

µ

Where ρ = 1013 𝑘𝑔/𝑚3 and µ = 7.85 ∗ 10−5 𝑘𝑔/𝑚. 𝑠 are the fluid density and dynamic

viscosity found at 65˚C for a 40% propylene-glycol mixture.

The relative roughness:

𝑅𝑅 =𝑅𝑆𝐷𝑖

Where 𝑅𝑆 is the roughness of the pipe material which is equal to 1.5 ∗ 10−5 𝑚 for stainless

steel.

Page 44: NMorel-Honours project

44

The friction factor can be determined f, as well as the head loss h:

𝑓 =1.325

(ln (𝑅𝑆

3.7 ∗ 𝐷𝑖+5.74𝑅𝑒0.9

))2 ℎ =

𝑓𝑙𝑣2

2𝑔𝐷𝑖

Where 𝑙 is the pipe length in m and 𝑔 = 9.81 𝑚/𝑠2 is the acceleration of gravity.

The pump hydraulic output required is finally:

𝑃𝑜𝑢𝑡 = 𝜌𝑔(ℎ + 𝐻) ∗ 𝑞 (W)

Where H is the net height (m) difference between the collector and the water tank.

3.5 Ground Source Heat Pump Study

In this part, the focus will be on sizing the ground source heat pump in order to meet the

biggest load of the year (coldest month) in space heating and hot water.

Figure 28. Ground temperature over the year according to the depth, in France (Collecteurderosee, 2015)

Page 45: NMorel-Honours project

45

The quantity of heat collected for a given length of pipe is very dependent on the ground

temperature at the location.

The ground loops are usually buried at a depth comprised between 1 and 2 m, the

temperature at 1.5 m below the ground surface will be considered in this study.

The temperatures shown on the figure 28 are listed below as well as the temperatures at

which the fluid enters the ground heat exchanger for each month. These depend on the

ambient outside air temperature and have to be assumed.

A parameter to take into account is that the fluid used is a 13% glycol-ethylene mixture

offering relatively good performances with an acceptable freezing point at -4˚C.

Determination of the rate of heat absorption

The aim of the procedure explained here is to define the rate of heat absorption per meter

of underground pipe which will allow afterward, to size the pipe length necessary to meet

the load.

First, an outlet fluid temperature (temperature at which the fluid leaves the ground

exchanger) has to be assumed so as to determine the film temperature which in turn,

allows to determine the thermophysical fluid properties used in the calculations. This

outlet temperature reasonably assumed regarding the ground temperature, is redefined

theoretically later. Also, the volumetric flow rate is assumed to be 𝑞 = 6. 10−4𝑚3/𝑠.

𝑇𝑓 =𝑇𝑖𝑛𝑙𝑒𝑡 + 𝑇𝑜𝑢𝑡𝑙𝑒𝑡

2

The film temperature is entered in the excel file “Ethylene Glycol Thermophysical

properties” available on Moodle, the corresponding properties are found and the Reynold

number can be calculated:

𝑅𝑒 =𝜌𝑣𝐷𝑖

2

µ 𝑤𝑖𝑡ℎ 𝑣 =

𝑞

(𝜋4 𝐷𝑖

2)

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Ground temperature at 1.5 m (˚C) 6 4 4 5.5 6.5 9 12 14 16 16 12 7

Fluid inlet temperature (˚C) 1 1 1 3 3 3 5 5 5 3 2 1

Table 10. Listing of temperatures over the year

Page 46: NMorel-Honours project

46

Where ρ and µ are the fluid density and dynamic viscosity at 𝑇𝑓, 𝑣 is the fluid velocity in

m/s and 𝐷𝑖 is the internal pipe diameter.

The friction factor:

𝑓 =1.325

(ln (𝑅𝑆

3.7 ∗ 𝐷𝑖+5.74𝑅𝑒0.9

))2

Where 𝑅𝑆 = 3. 10−6 is the surface roughness of the polypropylene constituting the pipe

coil.

The Nusselt number:

𝑁𝑢 = 0.023 ∗ 𝑅𝑒45 ∗ 𝑃𝑟0.4

With Pr the Prandt number found at 𝑇𝑓.

𝑁𝑢 allows the calculation of the pipe internal heat transfer coefficient ℎ𝑖:

ℎ𝑖 =𝑁𝑢 ∗ 𝑘

𝐷𝑖 (𝑊

𝑚2. 𝐾)

Where k is fluid thermal conductivity at 𝑇𝑓 in W/m.k.

The total rate of heat absorption in W/m pipe is given by:

𝑄𝑇 =𝑈𝐴

𝐿 𝐿𝑀𝑇𝐷 ; 𝑤𝑖𝑡ℎ 𝐿𝑀𝑇𝐷 =

𝛥𝑇𝑖 − 𝛥𝑇𝑜

ln (𝛥𝑇𝑖𝛥𝑇𝑜

)

𝐴𝑛𝑑 𝐿

𝑈𝐴=

1

𝜋 ∗ 𝐷𝑖ℎ𝑖+ln (𝐷𝑒𝐷𝑖)

2𝜋𝑘𝑝𝑖𝑝𝑒+

ln(2𝑅𝐷𝑒)

2𝜋𝑘𝑔𝑟𝑜𝑢𝑛𝑑

Where 𝐷𝑒 is the external pipe diameter in m, 𝑘𝑝𝑖𝑝𝑒 = 0.45 𝑊/𝑚.𝐾 and 𝑘𝑔𝑟𝑜𝑢𝑛𝑑 =

1.2 𝑊/𝑚.𝐾 are the thermal conductivities of the pipe and the ground and R is the slinky

radius R = 1 m given by the pipe manufacturer.

The rate of heat absorption in W/m is now known, the following approach is to determine

the length of pipe as to deliver the heat demanded.

Page 47: NMorel-Honours project

47

Determination of the required pipe length

The potential rate of heat delivery from the ground is:

𝐻𝑒𝑎𝑡 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑦 = 𝑄 (𝑊

𝑚) ∗ 𝐿 + (

1

𝐶𝑂𝑃 − 1∗ 𝑄 (

𝑊

𝑚) ∗ 𝐿) (𝑊)

Where COP is the performance coefficient of the heat pump, also given by the

manufacturer.

Plus, the energy available for each month is:

𝐸𝑛𝑒𝑟𝑔𝑦 𝑎𝑣𝑎𝑖𝑙𝑎𝑏𝑖𝑙𝑖𝑡𝑦 = 𝐻𝑒𝑎𝑡 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑦 ∗ 24 ∗ 𝑁𝑑 (𝑊ℎ/𝑚𝑜𝑛𝑡ℎ)

Where 24 is the number of hours in a day and 𝑁𝑑 the number of days in the month

studied.

Even when the load is the biggest, the energy available must be equal to the energy

demand in space heating and hot water:

𝐸𝑛𝑒𝑟𝑔𝑦 𝑎𝑣𝑎𝑖𝑙𝑎𝑏𝑖𝑙𝑖𝑡𝑦 = 𝐿𝑜𝑎𝑑 (𝑤𝑎𝑡𝑒𝑟 + ℎ𝑒𝑎𝑡𝑖𝑛𝑔) = 𝐻𝑒𝑎𝑡 𝑑𝑒𝑙𝑖𝑣𝑒𝑟𝑦 ∗ 24 ∗ 𝑁𝑑

Where the load is the sum of the energy needed for space heating and providing hot

water, monthly.

Hence, 𝐸𝑛𝑒𝑟𝑔𝑦 𝑎𝑣𝑎𝑖𝑙𝑎𝑏𝑖𝑙𝑖𝑡𝑦 = 𝐿𝑜𝑎𝑑 = (𝑄 ∗ 𝐿 + (1

𝐶𝑂𝑃−1∗ 𝑄 ∗ 𝐿)) ∗ (24 ∗ 𝑁𝑑)

The length of pipe necessary to meet the load is finally found by isolation:

𝐿 =𝐿𝑜𝑎𝑑

(1 +1

𝐶𝑂𝑃 − 1) ∗ 𝑄 ∗ 24 ∗ 𝑁𝑑

Page 48: NMorel-Honours project

48

Reiterations and pumps sizing

For a given pipe length L, 𝑇𝑜𝑢𝑡𝑙𝑒𝑡 assumed earlier in the procedure is recalculated by:

𝑇𝑜𝑢𝑡𝑙𝑒𝑡 = (𝑄 ∗ 𝐿

�̇� ∗ 𝐶𝑝) + 𝑇𝑖𝑛𝑙𝑒𝑡 (˚C) 𝑤𝑖𝑡ℎ 𝑄 =

𝑈𝐴𝛥𝑇

𝐿(𝑊

𝑚)𝑎𝑛𝑑 𝛥𝑇 = 𝑇𝑔𝑟𝑜𝑢𝑛𝑑 − 𝑇𝑓𝑙𝑢𝑖𝑑 𝑖𝑛𝑙𝑒𝑡

�̇� (𝑘𝑔

𝑠) = 𝑞 (

𝑚3

𝑠) ∗ 𝜌𝑓𝑙𝑢𝑖𝑑𝑒(

𝑘𝑔

𝑚3) is the mass flow rate of the fluid, 𝐶𝑝 is its specific heat

capacity in J/kg.K at 𝑇𝑓, and 𝑈𝐴

𝐿=

1

𝐿/𝑈𝐴 calculated previously.

The new outlet temperature allows to find a new 𝑇𝑓 for the determination of the fluid

thermophysical properties which differ slightly from before. The procedure is reiterated

from the beginning until another and final 𝑇𝑜𝑢𝑡𝑙𝑒𝑡 is found; and considered in the new

calculation of the total rate of heat absorption 𝑄𝑇. Going through the other formulas, a

new length is determined.

The circulating pump which ensures the flow rate through the circuit must also be sized.

The hydraulic pump output required is:

𝑃𝑜𝑢𝑡 = 𝜌𝑔𝐻 ∗ 𝑞 (𝑊) 𝑤𝑖𝑡ℎ 𝐻 =𝑓𝑙𝑣2

2𝑔𝐷𝑖

Where 𝑔 = 9.81 𝑚/𝑠2 is the acceleration of gravity, 𝐻 is the pump head loss and 𝑙 is the

pipe length, both in m.

Once the pump is chosen, the realistic flow rate circulated must be revised as the power

output won’t exactly be equal to the theoretical one:

𝑞𝑟𝑒𝑎𝑙 =𝑃𝑜𝑢𝑡𝜌𝑔𝐻

𝑖𝑛 𝑚3/𝑠

Thanks to the flow rate, a new fluid velocity is determined and the whole process is

repeated for finding a more accurate and final length of pipe.

The pipe was sized to provide the energy necessary for heating space and water, now

the heat pump must be also able to provide enough power when the load is at its biggest

(W).

Page 49: NMorel-Honours project

49

The heating power demanded from the GSHP is the total energy required divided by the

time over which the heat is supplied:

𝑄ℎ𝑒𝑎𝑡𝑖𝑛𝑔 =𝐸𝑤𝑎𝑡𝑒𝑟 ℎ𝑒𝑎𝑡𝑖𝑛𝑔 (𝑊ℎ)

𝑡𝑤𝑎𝑡𝑒𝑟 ℎ𝑒𝑎𝑡𝑖𝑛𝑔 (ℎ)+𝐸𝑠𝑝𝑎𝑐𝑒 ℎ𝑒𝑎𝑡𝑖𝑛𝑔 (𝑊ℎ)

𝑡𝑠𝑝𝑎𝑐𝑒 ℎ𝑒𝑎𝑡𝑖𝑛𝑔 (ℎ) (𝑊)

It is considered that the water for domestic use should be heated over 10 hours (could be

overnight). For space heating, the power can be assumed to be delivered over 24 hours.

The longer the time, the smaller the pump required.

The COP in a way, corresponds to the pump efficiency. For a given heating power, the

electrical power required is:

𝑄𝑒𝑙𝑒𝑐 =𝑄ℎ𝑒𝑎𝑡𝑖𝑛𝑔

𝐶𝑂𝑃 (𝑊)

Page 50: NMorel-Honours project

50

3.6 Solar Photovoltaic Study

Electric load analysis

When undertaking a photovoltaic feasibility study, first of all,

the daily electric load of the house must be analysed for each

month.

In the case where the PV is combined with a GSHP for water

and space heating, the energy that the PV must supply to the

ground source heat pump is:

𝐸𝐺𝑆𝐻𝑃 =𝐷𝑎𝑖𝑙𝑦 𝑙𝑜𝑎𝑑 (𝑤𝑎𝑡𝑒𝑟 + ℎ𝑒𝑎𝑡𝑖𝑛𝑔)

𝐶𝑂𝑃𝐺𝑆𝐻𝑃 (𝑊ℎ)

For the option in which the PV is combined with a thermal

installation and an electric heating system, the energy which

is to supply to compensate the heat losses equals to the total

heat lost power of the house calculated previously multiplied

by 24 hours.

The energy consumption of each electrical appliance of the

house is added in each option:

𝐸𝑒𝑞𝑢𝑖𝑝𝑚𝑒𝑛𝑡 = 𝑃 ∗ 𝑡

Where P is the power (W) of the device and t is its running

time per day (h).

Figure 29. PV installation scheme

Page 51: NMorel-Honours project

51

According to the period of the year the total energy demand is analysed. Few differences

appear depending on the period and obviously whether the PV runs a GHSP or an electric

heating combined with thermal system.

The listing above shows several devices assumed to be in the house and their

corresponding daily running time.

The lights are supposed to be left on for longer in winter than in summer, their

consumption is higher. Inversely, the fridge would run for a shorter time in winter.

The consumptions missing in the table can be determined only after the sizing of the

installations.

In the option 1, an immersion heater in the water tank is needed to complete the water

heating, as the thermal can only do a part of it.

Furthermore, the photovoltaic installation must support peaks of power (W) as it can

occur in winter which is why a coldest day scenario was simulated. The installation must

theoretically be able to supply the power demanded by the all the appliances, plus the

water and space heating systems in the “coldest day”, all of them powered

simultaneously.

The compensation of the heat losses being the most important part of the electric load

and varying greatly over the year, the load will then be analysed monthly.

Quantity Power (W) Max hours/day W.h/day Max hours/day W.h/day

Living room/kitchen lights 3 21 4 84 2 42

Bathroom light 1 7 1.5 10.5 1 7

Light bedroom 1 1 12 1 12 0.5 6

Fridge 1 100 6.5 650 8 800

Laptop 1 60 2 120 2 120

Phone charger 1 5 2 10 2 10

Radio alarm 1 2 24 48 24 48

Either Option 1: PV + Thermal and electric heating systems

Thermal circulating pump 1 - 10 - 14 -

Water electric heater 1 - 0.5 - 0.5 -

Electric heating system 1 - 24 - 0.5 -

Or Option 2: PV + GSHP systems

GSHP 1 - 24 9

GSHP circulating pump 1 - 24 - 9 -

Winter Summer

Table 11. House electric load analysis

Page 52: NMorel-Honours project

52

Production of the panels

The load was determined, the focus is now the electricity that the system will be able to

produce.

As for the thermal part, the slope global was relieved in a table for a 180˚ aspect and 30˚

tilt.

For each hour of the day in each month, the power produced per m² panel is:

𝑄𝑃𝑉 = 𝑆𝑙𝑜𝑝𝑒 𝑔𝑙𝑜𝑏𝑎𝑙 ∗ % 𝑝𝑎𝑛𝑒𝑙 𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 ( W/m²)

The sum of all these hourly 𝑄𝑃𝑉 gives the energy finally produced at the end of the day.

The real energy available per m² panel is obtained by:

𝐸𝑎𝑣𝑎𝑖𝑙𝑎𝑏𝑙𝑒 = 𝐸𝑃𝑉 ∗ %𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 𝑃𝑉 𝑒𝑙𝑒𝑚𝑒𝑛𝑡𝑠 ( Wh/m²)

Where %𝑒𝑓𝑓𝑖𝑐𝑖𝑒𝑛𝑐𝑦 𝑃𝑉 𝑒𝑙𝑒𝑚𝑒𝑛𝑡𝑠 is the multiplication of the MPPt, batteries and inverter

efficiencies.

According to both the load and production found and to the available roof area, the surface

of the panels can be chosen; and the part of the load covered monthly can be analysed.

MPPt and inverter choice

The electricity coming out of the MPPt must be under the same operating voltage as the

battery bank which must be chosen regarding the power demand (W). The higher the

demand, the higher the voltage in order to help reduce the intensity required in the

system.

A rated intensity (A) is given by the manufacturer so the power that the MPPt can let pass

through is:

𝑃 = 𝐼𝑟𝑎𝑡𝑒𝑑 ∗ 𝑉𝑏𝑎𝑡𝑡𝑒𝑟𝑖𝑒𝑠 (𝑊)

Ideally, the product above must be superior or equal to the maximum power produced by

the collectors. The MPPt device must be well chosen according to its rated intensity so it

does not reduce the energy going to be stored in the batteries.

The inverter must be selected regarding the battery voltage and the specification of its

peak power load that it can handle.

Page 53: NMorel-Honours project

53

Battery bank sizing

The capacity storage must be sized according to the load in energy.

The required system electrical storage capacity is calculated by:

𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦 =𝐷𝑎𝑖𝑙𝑦 𝑙𝑜𝑎𝑑 ∗ 𝑁𝑏𝑑𝑎𝑦𝑠 𝑎𝑢𝑡𝑜𝑛𝑜𝑚𝑦

%𝐷𝑜𝐷𝑚𝑎𝑥 ∗ 𝑆𝑦𝑠𝑡𝑒𝑚 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 (𝐴ℎ)

Where 𝑁𝑏𝑑𝑎𝑦𝑠 𝑎𝑢𝑡𝑜𝑛𝑜𝑚𝑦 is the autonomy allowed to the installation to prevent from days

when the production is low, for example, on dull and cloudy days.

%𝐷𝑜𝐷𝑚𝑎𝑥 is the maximum depth of discharge of the batteries accorded to preserve their

lifetime. The daily load in Wh taken for batteries sizing is the biggest load of the year

obtained from previously.

The number of batteries in series (additive voltage) and the number of series strings

(additive capacity) must be determined according to the capacity and operating voltage

selected before.

𝑁𝑏𝑠𝑒𝑟𝑖𝑒 =𝑆𝑦𝑠𝑡𝑒𝑚 𝑣𝑜𝑙𝑡𝑎𝑔𝑒

𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝑣𝑜𝑙𝑡𝑎𝑔𝑒 𝑎𝑛𝑑 𝑁𝑏𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙𝑒 𝑠𝑡𝑟𝑖𝑛𝑔𝑠 =

𝐶𝑎𝑝𝑎𝑐𝑖𝑡𝑦

𝐵𝑎𝑡𝑡𝑒𝑟𝑦 𝑐𝑎𝑝𝑎𝑐𝑖𝑡𝑦

For the 𝑁𝑏𝑝𝑎𝑟𝑎𝑙𝑙𝑒𝑙𝑒 𝑠𝑡𝑟𝑖𝑛𝑔𝑠, the nearest whole number to the value found is taken in account.

Thus, the exact number of batteries is known and the rated capacity can be recalculated.

Page 54: NMorel-Honours project

54

4 Chapter Four: Results and Findings

The hourly values of 𝐼𝐺, 𝐼𝐷 and all the components as the slope global, slope beam, diffuse

and direct radiations needed for the calculations are registered in the excel file on the CD-

ROM provided with this report, as well as the calculations themselves.

4.1 Needs Analysis

Passive gains

Solar gains through windows

The hourly results of the solar gains for a typical day in each month of the year are given

in appendix A.

An overview is presented in the following table:

Sensible heat from humans

Between 2 and 3 kWh/day average energy gained over the year with a slight peak during the hot

period, as expected.Sensible heat emissions of humans

January February March April May June July August September October November December

South 1.67 1.96 2.25 1.90 1.79 1.79 1.97 2.15 2.29 1.94 1.65 1.37

East 0.36 0.45 0.72 0.88 1.07 1.22 1.32 1.11 0.89 0.53 0.33 0.22

Total 2.03 2.41 2.97 2.78 2.86 3.01 3.28 3.26 3.18 2.47 1.97 1.59

Table 12. Energy entering in the building in kWh, daily

Occupancy time 12 h

Heat emitted per occupants 70 W

Number of occupants 4

Total energy gained 3.36 kWh/dayTable 13. Energy gained from human occupation

Page 55: NMorel-Honours project

55

Heat losses

Energy lost

Taverage (°C) Walls Door + windows Roof Ventilation Thermal bridges (5%) Floor (9%) Total Total (kWh/day)

January -0.8 201.1 154.3 199.3 265.5 47.7 85.8 953.7 22.9

February 0.3 188.8 144.5 187.0 250.0 44.8 80.6 895.7 21.5

March 3.7 151.5 114.6 149.4 202.0 35.9 64.6 718.0 17.2

April 6.7 118.3 89.2 116.6 159.6 28.1 50.6 562.4 13.5

May 11.8 63.0 46.5 61.7 87.6 15.0 27.1 300.9 7.2

June 15.6 22.7 16.7 22.4 33.9 5.6 10.0 111.3 2.7

July 18.2 0 0 0 0 0 0 0 0

August 17.9 0 0 0 0 0 0 0 0

September 13.5 44.4 32.8 43.9 63.6 10.7 19.3 214.7 5.2

October 9.2 90.4 67.1 89.5 124.3 21.6 38.9 431.7 10.4

November 3.3 155.3 117.9 153.8 207.6 36.9 66.4 737.9 17.7

December 0.3 188.8 144.5 187.0 250.0 44.8 80.6 895.7 21.5

Heat losses (W)

Coldest day case scenario - 3/1/1971

Energy lost

Tmin (°C) Walls Door + Windows Roof Ventilation Thermal bridges Floor Total kWh/day

-27.1 493.1 394.30 498.30 639.90 117.6 211.7 2354.9 56.5

Heat loss (W)

Table 15. Heat losses, coldest day scenario 3/1/1971

Table 14. Overall heat losses of the house

Figure 30.Total energy gained inside the house by month

Page 56: NMorel-Honours project

56

A table of losses repartition which appears to be quite similar as the indicative values

seen in the implementation. A complete table of repartition for each month is given in

appendix A.

Finally, the total energy loss of the house:

The tendency over the year can be visualised below:

The losses are more important during December and January with 16.5 and 17.5 kWh

per day. It is the period which the study aims at sizing the installations according to.

January February March April May June July August September October November December

Heat lost (kWh) 22.9 21.5 17.2 13.5 7.2 2.7 0.0 0.0 5.2 10.4 17.7 21.5

Heat gains (kWh) 5.4 5.8 6.3 6.1 6.2 6.4 6.6 6.6 6.5 5.8 5.3 5.0

Total heat lost (kWh) 17.5 15.7 10.9 7.4 1.0 0 0 0 0 4.5 12.4 16.5

Table 17. Heat lost - heat gained per day, overview

Figure 31. Total energy lost by month

Walls Door + windows Roof Ventilation Thermal bridges Floor

20.9% 15.8% 20.7% 28.6% 5.0% 9.0%

Table 16. Year average heat losses repartition (%)

Page 57: NMorel-Honours project

57

Hot water demand

11.6 kWh/day for heating water all year represents the third of the total daily load in winter.

From this, the collector area required can be found and its corresponding production over

the year, evaluated.

4.2 Solar Thermal Study

Collector production

Table 18. Calculation of the energy needed for heating water

Table 19. Hourly production of hot water (L) according to the heat produced by 3m2 collector (W) - South

Panel area (m2) Efficiency

3 76%

W L W L W L W L W L W L

122.3 2.1 56.2 1.0 0 0 0 0 0 0 0 0

376.1 6.5 281.2 4.9 141.4 2.4 0 0 0 0 0 0

700.7 12.1 599.1 10.3 427.6 7.4 226.0 3.9 26.6 0.5 0 0

1034.6 17.9 935.6 16.2 746.4 12.9 472.6 8.2 323.1 5.6 80.6 1.4

1337.3 23.1 1246.6 21.5 1050.6 18.1 717.7 12.4 524.1 9.1 455.7 7.9

1567.6 27.1 1486.1 25.7 1289.6 22.3 914.9 15.8 691.7 11.9 611.4 10.6

1692.1 29.2 1616.5 27.9 1421.2 24.5 1025.0 17.7 786.5 13.6 700.6 12.1

1692.2 29.2 1616.7 27.9 1421.4 24.6 1025.2 17.7 786.7 13.6 700.6 12.1

1567.8 27.1 1486.5 25.7 1290.3 22.3 915.6 15.8 692.2 12.0 611.5 10.6

1337.6 23.1 1247.2 21.5 1051.6 18.2 718.7 12.4 525.1 9.1 455.9 7.9

1034.9 17.9 936.4 16.2 747.5 12.9 473.9 8.2 324.6 5.6 80.5 1.4

701.0 12.1 599.8 10.4 428.8 7.4 227.8 3.9 26.6 0.5 0.0 0.0

376.2 6.5 281.4 4.9 142.4 2.5 0 0 0 0 0 0

122.1 2.1 56.0 1.0 0 0 0 0 0 0 0 0

236.0 215.0 175.5 116.0 81.3 63.9

November DecemberJuly August September October

HOURS W L W L W L W L W L W L

5.5 0 0 0 0 0 0 14.7 0.3 82.7 1.4 133.1 2.3

6.5 0 0 0 0 40.9 0.7 197.1 3.4 296.1 5.1 371.8 6.4

7.5 74.5 1.3 72.9 1.3 347.9 6.0 466.5 8.1 578.5 10.0 667.3 11.5

8.5 462.4 8.0 449.3 7.8 661.7 11.4 759.3 13.1 875.9 15.1 969.2 16.7

9.5 507.5 8.8 707.9 12.2 966.3 16.7 1034.2 17.9 1149.2 19.9 1241.8 21.4

10.5 581.0 10.0 917.6 15.8 1208.0 20.9 1248.0 21.6 1359.0 23.5 1448.6 25.0

11.5 625.7 10.8 1034.8 17.9 1341.6 23.2 1364.9 23.6 1472.9 25.4 1560.3 27.0

12.5 625.6 10.8 1034.5 17.9 1341.4 23.2 1364.7 23.6 1472.8 25.4 1560.3 27.0

13.5 580.5 10.0 916.9 15.8 1207.4 20.9 1247.6 21.5 1358.7 23.5 1448.6 25.0

14.5 506.6 8.8 706.8 12.2 965.3 16.7 1033.6 17.9 1148.9 19.8 1241.7 21.4

15.5 460.1 7.9 447.8 7.7 660.4 11.4 758.6 13.1 875.5 15.1 969.2 16.7

16.5 73.8 1.3 73.3 1.3 346.5 6.0 465.8 8.0 578.1 10.0 667.2 11.5

17.5 0 0 0 0 41.1 0.7 196.8 3.4 296.0 5.1 371.8 6.4

18.5 0 0 0 0 0 0 14.7 0.3 82.9 1.4 133.1 2.3

Total (in L): 77.7 109.9 157.7 175.6 200.8 220.8

January February March April May June

HOURS W L W L W L W L W L W L

5.5 0 0 0 0 0 0 14.7 0.3 82.7 1.4 133.1 2.3

6.5 0 0 0 0 40.9 0.7 197.1 3.4 296.1 5.1 371.8 6.4

7.5 74.5 1.3 72.9 1.3 347.9 6.0 466.5 8.1 578.5 10.0 667.3 11.5

8.5 462.4 8.0 449.3 7.8 661.7 11.4 759.3 13.1 875.9 15.1 969.2 16.7

9.5 507.5 8.8 707.9 12.2 966.3 16.7 1034.2 17.9 1149.2 19.9 1241.8 21.4

10.5 581.0 10.0 917.6 15.8 1208.0 20.9 1248.0 21.6 1359.0 23.5 1448.6 25.0

11.5 625.7 10.8 1034.8 17.9 1341.6 23.2 1364.9 23.6 1472.9 25.4 1560.3 27.0

12.5 625.6 10.8 1034.5 17.9 1341.4 23.2 1364.7 23.6 1472.8 25.4 1560.3 27.0

13.5 580.5 10.0 916.9 15.8 1207.4 20.9 1247.6 21.5 1358.7 23.5 1448.6 25.0

14.5 506.6 8.8 706.8 12.2 965.3 16.7 1033.6 17.9 1148.9 19.8 1241.7 21.4

15.5 460.1 7.9 447.8 7.7 660.4 11.4 758.6 13.1 875.5 15.1 969.2 16.7

16.5 73.8 1.3 73.3 1.3 346.5 6.0 465.8 8.0 578.1 10.0 667.2 11.5

17.5 0 0 0 0 41.1 0.7 196.8 3.4 296.0 5.1 371.8 6.4

18.5 0 0 0 0 0 0 14.7 0.3 82.9 1.4 133.1 2.3

Total (in L): 77.7 109.9 157.7 175.6 200.8 220.8

January February March April May June

Water V (L) Tin (˚C) Tout (˚C) ΔT

200.0 15 65 50.0

Water V (m3) ρwater m (kg) Cp (J/kg.K) Q (kJ) Q (kWh)

0.2 996.0 199.2 4185.0 41683 11.6

Total energy

needed:

Page 58: NMorel-Honours project

58

Thanks to the tables above, the production of hot water can be monitored at each hour of

the day in each month of the year. It is noticed that there is always availability for use in

the evening.

The graphs showing the hot water produced and the energy required to complete the

heating are given below.

0.0

20.0

40.0

60.0

80.0

100.0

120.0

%

Figure 32. Energy required by the immersion heater to produce the rest

Figure 33. Volume of hot water produced over the volume required, per day (%)

Page 59: NMorel-Honours project

59

3 m2 of solar thermal collectors south-oriented seems reasonable so that there is no

overproduction in summer. Though, the theoretical production is a bit higher than required

in summer which can be considered as a margin. The collector area is sufficiently

important to meet 100% of the needs from May to September and can supply about the

half during the rest of the year. As shown on the figure 33, about 60% of the energy

required to heat the water must be supplied by the heater during the coldest months of

the year.

Pump sizing

The thermal panel chosen is a Clearline V30 of which the spreadsheet is given in

appendix B. The pump was sized according to its rated flow indicated in the specifications.

The pump needed is a low cost small motor.

Absorber area 3.0 m²

Aperture area 3.1 m²

Efficiency 76 %

Rated flow 150 l/h

4E-05 m3/s

Clearline V30 panel

Pipe disc surface 7.85E-05 m²

Velocity 5E-01 m/s

Re 36319.3

S roughness 1.50E-05

Relat. Roughness 1.50E-03

Friction factor 2.66E-02

Head losses 0.762 m

Poutput required 2.4 W

Circulating pump sizing

Table 20. Thermal collector specifications Table 21. Circulating pump sizing

Page 60: NMorel-Honours project

60

4.3 Ground Source Heat Pump Study

Production

The lowest rate of heat absorption and therefore, the lowest production of energy occurs

in February due to the low ground temperature. For this reason and even though the load

is not maximum at this period, it is the month over which the demand requires the highest

value of pipe length, in order to be fully covered. Thus, the pipe coil was sized according

to this fact and found equal to 155 m.

The results demonstrate that the system can insure the heating all over the year with a

certain margin in winter and could theoretically produce up to eight times more energy in

summer, when the demand only corresponds to the domestic hot water production.

Sizing of the pumps

Circulating pump

The theoretical power output of the circulating

pump was estimated at 24.5 W.

A 40 W “Grundfos” pump providing a 30 W

actual power output (75% efficiency) was

chosen (appendix D) so the actual flow rate

had been revised and the energy production

calculations, reiterated according to it.

Pipe coil length: 155 m

Month J F M A M J J A S O N D

(Space + water heating) load (kWh/month) 901.5 791.8 696.8 568.1 389.9 347.4 347.4 347.4 347.4 499.3 718.6 871.8

Rate of heat absorption (W/m) 8.4 5.1 5.1 4.2 5.9 10.1 11.8 15.2 18.6 21.9 16.9 10.1

Rate of heat absorption (kW) 1.3 0.8 0.8 0.7 0.9 1.6 1.8 2.4 2.9 3.4 2.6 1.6

Potential rate of heat delivery (kW) 1.8 1.1 1.1 0.9 1.2 2.1 2.5 3.2 3.9 4.6 3.6 2.1

Energy availability (kWh/month) 1325.7 795.7 795.7 663.6 927.8 1588.3 1855.6 2387.1 2924.9 3443.9 2657.6 1588.3

% of the load covered 147% 100% 114% 117% 238% 457% 534% 687% 842% 690% 370% 182%

Table 22. GSHP energy production

Basic flow rate 0.0006 m3/s

Relative roughness 0.0001

Friction factor 0.3065

Head loss 4.1 m

Poutput required 24.5 W

Electrical rating 40 W

Efficiency 75 %

Actual Poutput 30 W

Revised flow rate 0.00073 m3/s

Circulating pump sizing

Table 23. Circulating pump sizing

Page 61: NMorel-Honours project

61

GSHP

The ground source heat pump “Kensa” of which the specifications sheet is given in

appendix D has a COP which can be averaged to 4 over the year. It means that during a

typical day in January (month representing the biggest load), it would need 0.5 kW of

electrical power to insure the space and water heating over 24 and 10 hours respectively.

To envisage a very cold day, the pump must be able to provide 3.3 kW of heating power,

inducing an electrical power consumption of 0.8 kW that the PV system must make

available.

The GSHP chosen is in fact of 3 kW electrical power meaning that the energy required in

a typical day can be delivered over a period more than six times shorter than assumed,

which implies the circulating pump to run also during a shorter time, saving some energy.

Table 24. GSHP sizing calculations

Space Water

17.5 11.6

/ time (h) 24 10

Heating output (kW) 0.7 1.16

Tot. heating Output (kW)

COP

Electrical Pintput (kW) 0.5

January typical day

Heating load (kWh)

4

1.9

Space Water

51.1 11.6

/ time (h) 24 10

Heating output (kW) 2.1 1.16

Tot. heating Output (kW)

COP

Electrical Pintput (kW)

Heating load (kWh)

Coldest day

3.3

4

0.8

Page 62: NMorel-Honours project

62

4.4 Solar Photovoltaic Study

Electric load analysis

As a first step, the energy consumption of each electrical appliance (heating system not

included) was analysed in summer and in winter as well as the power that they would

demand if they were all running simultaneously.

In the option (1), it is logically considered that the circulating pump would be powered for

a period of time corresponding to the sunshine duration in a day, which differs according

to the period of the year. Also, the fridge runs longer in summer and so is the cause of a

higher energy consumption at this period.

In the option (2), the 3 kW GSHP could theoretically provide enough in energy to meet

the biggest load (January) in less than 3 hours but the heating time was maximally

assumed keeping a margin for the estimation of the circulating pump energy

consumption.

The second step was to analyse the total electric load by month including the consumption

of the water and space heating systems in both cases.

Table 25. Electrical appliances load analysis (heating system not included)

Quantity Power (W) Max hours/day W.h/day Max hours/day W.h/day

Living room/kitchen lights 3 21 4 84 2 42

Bathroom light 1 7 1.5 10.5 1 7

Light bedroom 1 1 12 1 12 0.5 6

Fridge 1 100 6.5 650 8 800

Laptop 1 60 2 120 2 120

Phone charger 1 5 2 10 2 10

Radio alarm 1 2 24 48 24 48

(1) Thermal circulating pump 1 2.4 10 24 14 33.6

(2) GSHP circulating pump 1 40 7 280 5 214.4

(1) Total 209.4 958.5 Wh/day 1066.6 Wh/day

(2) Total 247 1214.5 Wh/day 1247.4 Wh/day

Winter Summer

Page 63: NMorel-Honours project

63

The most important electric load occurs in January for both options. The sizing must be

undertaken in a way that the production is enough to meet the needs at this period.

In the first option compared to the second, the demand is lower in summer as the water

heating is insured without using any electric source of energy. Inversely in winter, the load

in the option 2 is widely lower thanks to the GSHP coefficient of performance.

The values indicated on the table above for the heating systems are the powers that they

would require to compensate the heat losses in a day as the coldest one simulated earlier.

The power provided by the electric heating system is equal to the heat lost power. The

GSHP demands 3 kW of electrical power in any case.

To complete the domestic water heating in the option 1, a 3 kW immersion heater is

included in the cylinder chosen (appendix E). The selection is explained later in the

economic part.

The PV system must be sized so that it can supply the power required in the case where

all the elements would be powered simultaneously (total shown on table 29).

Option 1 Option 2

Immersion heater 3 -

Heating system 2.4 3

Electrical applicances 0.21 0.25

Total 5.6 3.3

Table 27. Option 1, total electrical load analysis (kWh/day)

Table 26. Option 2, total electrical load analysis (kWh/day)

Table 28. Power demand analysis (kW)

Month J F M A M J J A S O N D

Total heating load 29.1 27.3 22.5 18.9 12.6 11.6 11.6 11.6 11.6 16.1 24.0 28.1

GSHP electrical load 7.3 6.8 5.6 4.7 3.1 2.9 2.9 2.9 2.9 4.0 6.0 7.0

Electrical applicances load 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2

Total electric load 8.5 8.0 6.8 6.0 4.4 4.1 4.1 4.1 4.1 5.2 7.2 8.2

Month J F M A M J J A S O N D

Space heating load 17.5 15.7 10.9 7.4 1.0 0.0 0.0 0.0 0.0 4.5 12.4 16.5

Immersion heater load 7.1 5.2 2.4 1.4 0 0 0 0 1.4 4.9 6.9 7.9

Electrical appliances load 1.0 1.0 1.0 1.1 1.1 1.1 1.1 1.1 1.1 1.0 1.0 1.0

Total electric load 25.6 21.9 14.3 9.9 2.1 1.1 1.1 1.1 2.5 10.4 20.3 25.4

Page 64: NMorel-Honours project

64

Production of the panels

Knowing the energy received, the PV production per m² was estimated assuming, at the

beginning, the efficiency of the panel. Hence, it was found that the most PV area possible,

according to the surface of the roof available, should be installed as in any case the load

would not be fully covered all year. Once the panel and the other elements constituting

the whole system were chosen, the realistic PV production and energy available were

recalculated taking the given efficiencies into account.

The PV panel suggested is the “Clearline PV 16/250” of which the specifications are given

in appendix F. Its efficiency is 15.6 %, global area: 1.63 m² allowing 1.6 m² to absorb the

sunlight.

24.05 m² of roof area permits the installation of 12 of them in the first option due to the

thermal system already having some space allocated, and 14 in the other one.

The solar energy being abundant with a load being the lowest from April to September,

the needs in electricity can be fully covered during this period in both options. The

theoretical energy available could even be up to about 15 times what is necessary in the

Battery losses 95%

Cabling losses 94%

MPPt 96%

Inverter 95%

Total 81%

Due to

Table 29. PV system efficiencies

Table 30. PV energy production analysis

Panels efficiency: 15.6 % January February March April May June July August September October November December

Energy received (kWh/m2/day) 2.0 2.8 4.0 4.5 5.1 5.6 6.0 5.5 4.5 2.9 2.1 1.6

PV production (kWh/m2/day) 0.3 0.4 0.6 0.7 0.8 0.9 0.9 0.9 0.7 0.5 0.3 0.3

Option 1 : Thermal + electric heating system - 12 panels = 19.2 m² absorber area

Total PV production (kWh/day) 5.9 8.4 12.0 13.4 15.3 16.8 17.9 16.3 13.3 8.8 6.2 4.9

Real energy available (kWh/day) 4.8 6.8 9.8 10.9 12.4 13.7 14.6 13.3 10.9 7.2 5.0 4.0

House electric load (kWh/day) 25.6 21.9 14.3 9.9 2.1 1.1 1.1 1.1 2.5 10.4 20.3 25.4

% load covered 19% 31% 68% 110% 603% 1282% 1370% 1248% 437% 69% 25% 16%

Option 2: GSHP - 14 panels = 22.4 m² absorber area

Total PV production (kWh/day) 6.9 9.8 14.0 15.6 17.8 19.6 20.9 19.1 15.6 10.3 7.2 5.7

Real energy available (kWh/day) 5.6 7.9 11.4 12.7 14.5 16.0 17.1 15.5 12.7 8.4 5.9 4.6

House electric load (kWh/day) 8.5 8.0 6.8 6.0 4.4 4.1 4.1 4.1 4.1 5.2 7.2 8.2

% load covered 66% 100% 167% 211% 330% 385% 416% 379% 306% 161% 82% 56%

Page 65: NMorel-Honours project

65

option 1 and 4 times in the option 2, during the hottest month – July. Though, it will be

seen later that the energy can only be stored to a certain extend.

During the rest of the year, using a GSHP combined with a PV system makes the

difference.

In February, March and October, this system allows a complete energy independence of

the house contrary to the option 1 case.

With this last, about 70 to 80 % of the load is covered which remains acceptable, in March

and October, whereas the same situation occurs in January and November with the other

option. Moreover, for the months of November, December, January and February, the

percentage of the demand covered is about 3 times higher.

0%

20%

40%

60%

80%

100%

120%

140%

160%

180%

January February March October November December

Thermal + elec. heating GSHP

Figure 34. Percentage of the load covered

Page 66: NMorel-Honours project

66

MPPt and inverter selection

The maximum slope global received and therefore the maximum power production of the

panels occurs in a day of July at 11:30am. This corresponds to the power going to the

batteries passing through the MPPt.

Moreover, the maximum power load being quite high in both options (3.3 and 5.6 kW as

seen before), a battery bank under 48 V is suitable, lowering the current in the installation.

This has also been confirmed by a supplier of PV system elements working for “Biowatt

Energie” (email exchange shown in appendix E).

Consequently, the MPPt was chosen regarding its rated current – 70 A, so that it does

not reduce the power transmitted from the panels to the batteries.

The specifications sheet of the “MPPt Blue Solar 150/70” selected for both options is in

the appendix G.

July (11:30am)

Slope global (W/m²) 742.2

Pmax produced opt. 1 2778.7

Pmax produced opt. 2 2408.2W

Table 31. Power produced by the panels

Figure 35. PV system electric indications

Page 67: NMorel-Honours project

67

Also, the maximum solar input power accepted – 4 kW for this device, had to be checked

to be higher than the one produced.

According to the load, the inverters selected are the “Vicron Multiplus 48/5000/70” for the

option 1 and “48/3000/70” for the other (spreadsheets in appendix G). They respectively

allow 5 kW and 3 kW of continuous power output with peaks of up to 10 and 6 kW.

Battery bank sizing

The capacity required was calculated to be able to store the equivalent of the energy

necessary for 4 days, with a 𝐷𝑜𝐷𝑚𝑎𝑥 = 60% chosen to preserve the battery life.

For the option 1, the sizing was first evaluated in January when the load is the biggest. It

results that it would need about twice more batteries than in March, inducing a cost twice

more important for a storage at a period during which the panels are able to produce only

the fourth of the load.

Consequently, it appeared reasonable to adapt the storage for March when 68 % of the

load is covered. The real capacity is slightly lower than the theoretical one so the storage

would equal a little less than 4 days of autonomy for the system in March.

Option 2

January March January

Load (kWh) 25.6 14.3 9.1

No days autonomy

System voltage (V)

DoDmax (%)

Capacity required (Ah) 3555.6 1986.1 1263.9

Number of batt. in series string

Number of // strings 1.9 1.1 1

Realistic number // strings 2 1 1

Tot. number of batteries 48 24 24

Rated capacity (Ah) 3720 1860 1860

Option 1

4

48

60

24

Battery model RBS - Capacity: 1860 Ah ; Voltage: 2 V

Table 32. Battery bank sizing

Page 68: NMorel-Honours project

68

In the second option, the system finally allows a storage of almost 6 days of the biggest

energy demand (January). Both storage solutions require a bank of 24 batteries.

The datasheet of the battery chosen is given in appendix F and was selected according

to economic criteria as it can be seen on the excel sheet “PV sizing”.

The exact number of autonomy days of the PV system and a tendency are given below,

by month and for each option:

January February March April May June July August September October November December

Option 1 2.1 2.4 3.7 5.4 25.9 50.2 50.2 50.2 21.5 5.2 2.6 2.1

Option 2 6.3 6.7 7.8 8.9 12.2 12.9 13.1 13.1 12.9 10.3 7.4 6.5

Table 33. Number of days of autonomy for both options

Figure 36. PV systems number of autonomy days

Page 69: NMorel-Honours project

69

Design overview

An overview of the final PV system design is presented above.

Each panel having a maximum voltage of 30.4 V and current of 8.2 A, the choice of

mounting them in 6 or 7 parallel strings (according to the option) of 2 panels in series

gives the above indicated maximum current and voltage output. It seems to be the best

combination, given the system operating intensity and voltage.

The MPPt starts its function when the PV voltage reaches 55 V (battery voltage + 7 V).

MPPt

Inverter 230 V

I depending on the demand

60.8 V

48 V

48 V

57.4 A 49.2 A

70 A

Option 1 : 6 // strings of 2 panels in series

Option 2 : 7 // strings of 2 panels in series

Figure 37. Final PV design overview

Page 70: NMorel-Honours project

70

4.5 Economic Analysis

The description/specifications sheet and cost of each element cited below is given in their

respective appendix.

Solar thermal installation

Most of the elements were found on the Viridian catalogue presenting very competitive

prices. The solar electric cylinder comprises a coil allocated to the thermal system circuit

to exchange the heat and an immersed water heater as explained in the second chapter.

A device controlling the fluid pressure of the installation as well as some temperature

sensors to insure the smooth running of the system. The pipe correspond are the

connection between the different elements.

The cost due to maintenance is negligible. The labour costs usually represent 30% of the

total installation cost depending on the roof surface covered and the size of the panels.

Denomination Brand/Reference Indications Source Cost (£)

Thermal collector Clearline V30 250 Wp Viridian catalogue 929.38

Solar electric cylinder Steflow 210 DS 210 L, heater 3 kW Viridian catalogue 873.82

Expansion vessel Solar plus 18 L Advancedwater.co.uk 48.22

Pressure controller Clearline V210R Viridian catalogue 150

Temperature sensors Clearline V228 Viridian catalogue 22

Solar fluid Clearline V225 40% prop. Glycol Viridian catalogue 33.88

Pre-insulated pipe Clearline V5110 L = 10 m, Di = 10 cm Viridian catalogue 149.61

Circulating pump Brushless Banggood.com 14.22

Labour 1000

Total £3,221Table 34. Thermal system cost analysis

Page 71: NMorel-Honours project

71

Solar photovoltaic installation

The first option requires an inverter 5 kW costing about £800 more than the 3 kW one

used in the second option. As a compensation, two panels less are used which balances

the final costs. The fact that this installation is off-grid makes it expensive, the batteries

being part of more than 50% of the total cost.

On the excel sheets “PV sizing” for both options, it can be seen that the economic analysis

of several PV panels, MPPts and batteries was carried out, the selection of each device

is underlined in green.

Table 35. PV system cost analysis

Qty Denomination Brand/Reference Source Cost (£)

1 MPPt Blue Solar 150/70 windandsun.co.uk 485.52

24 Battery Rolls S-1860Ah windandsun.co.uk 6670.9

12 PV collector Clearline PV16/250 Viridian catalogue 2592

1 Inverter Victron Multiplus 5000 windandsun.co.uk 1748.88

14 PV collector Clearline PV16/250 Viridian catalogue 3024

1 Inverter Victron Multiplus 3000 windandsun.co.uk 1096.2

Labour 300

Total Option 1: £11,797

Option 2: £11,577

1 st option

2nd option

Page 72: NMorel-Honours project

72

Ground source heat pump installation

The ground source heat pump represents the half of the price. To keep an optimal thermal

exchange, it is advised to replace the fluid every 5 years. It is also important to monitor

the pressure in the installation and to set up a regular checking which can be under the

form of a few years contract.

The cylinder is typical for heat pump comprising a coil for exchanging the heat from the

ground with the domestic water, and an immersed heater for boost and emergency back-

up.

The total costs for both options are finally given below:

Slightly more than £3,000 supplementary to invest in the second option, offering better

advantages. Is that worth it? The next part of this report will help answer this question,

among other.

Denomination Brand/Reference Indications Source Cost (£)

GSHP Kensa 3 kW kensaheatpumps.com 2950

Circulating pump Grandfos 40 W anchorpumps.com 77.5

HP cylinder Gledhill TEC210-HP 210 L plumbnation.co.uk 1208.34

GSHP fluid Thermox DTX20 To replace every 5 years hydratech-shop.co.uk 60.6

Pipe coil BHF L = 250 m ebay.co.uk 400

Labour 2000

Installation checking every 3 years 100

Total £6,796Table 36. Ground source heat pump cost analysis

Table 37. Total cost of each option

Option 1: PV + Thermal systems £15,018

Option 2: PV + GSHP systems £18,373

Page 73: NMorel-Honours project

73

5 Chapter five: Conclusion

5.1 Analysis

A quite constant amount of heat is gained into the house with a 4 to 6.5 kWh/day range

over the year. Similar fact for the 11.6 kWh/day required for heating domestic water.

However, the overall heat lost is very fluctuating due to temperatures variation that the

different systems must handle.

The ground temperature being the lowest in February, it is the month during which the

GSHP installation requires the maximum length of pipe coil – 155 m, to meet the heating

demand even though this last is only the third biggest of the year. This length then insures

enough heat to be removed from the ground for the needs to be fully covered at all time

of the year.

The 3 kW electrical power of the GSHP is more than enough to provide the energy

necessary during a typical day of January as well as to envisage a very cold day scenario

as happened in 1971 when the temperature went down to -27.1 °C.

Talking about the other option, 3 m² of solar thermal collector is enough to provide all the

hot water desired from April to September without overproducing and so, going over the

capacity of the water tank. A bigger cylinder and collector area could have been imagined

but this would affect the capacity of the PV system to produce electricity by reducing the

roof space available.

During the rest of the year, the system allows the acceptable production of about the half

of what is needed. A 3 kW water immersed heater would complete the task when needed.

Also, the water being heated up over the sunshine duration and even though some hot

water use can occur during the day, a large amount of hot water is available from around

6pm in summer allowing showers to be taken and other important consumptions.

In winter, thanks to the COP, the GSHP allows the electrical load to be about three times

lower than with using electric and solar thermal heating systems. In summer, the load is

in turn superior as only the domestic water must be heated, which is done by electric

means contrary to the other option case.

Page 74: NMorel-Honours project

74

Still thanks to the COP, the maximal power load to envisage is also lower with 3.3 against

5.6 kW. In both cases, a 48 V operating voltage was chosen to help reduce the current

needed in the installation to meet the load, and according to which two different inverters

to include in the PV system were selected.

With 19.2 and 22.4 m² of PV panel absorbing areas, the maximum peak power produced

may occur in July with 2.4 and 2.8 kW. These values being close to each other, the MPPt

able to cope with it remains common in both installations.

The water and space heating systems were sized and optimised for meeting their task in

both options while the ability of the PV system to complete its own differs.

In the option 1, the house can be electrically completely independent during the 6 warmest

months of the year while in the option 2, it is the case for a 9 months period (February to

October).

However, the house could be inhabited for 2 months supplementary in each case. In

effect, during the period when three quarters of the load would be covered, the power of

the space heating systems could be reduced and the wood stroke burner which was

considered as a back-up solution so far, could complete the heating. A study must be

done so as to obtain confirmation of the suitability.

Thanks to the 24 batteries storage solution, the option 2 system has a greater autonomy

over the year with about 7 days in winter against 3 for the other option. This is a very

significant parameter to take into account. In mountain, several dull or cloudy days in a

row is not rare, especially during winter.

Around £18,000 against £15,000, the heat pump installation induces the cost to be £3,000

higher for the second option, more performant. The deal seems balanced. Though, if the

investment has for objective to make the house inhabitable mostly during summer, then

the cheapest option is sufficient. If the investment aims at spending winter time in the

house which is most likely the case in view of the location, it is advised to choose the

other option.

Page 75: NMorel-Honours project

75

5.2 Limitations

The heat losses representing the main part of the demand, the sizing of the installations

was mostly based on it. Consequently, it was really important to identify them properly

and a lot of time was spent on it due to the complex methodology of calculation.

Additionally, a sufficient amount of time needs to be allocated in order to fully understand

the scientific theory behind the GSHP study.

Furthermore, a delicate fact to deal with was that everything is linked together which

means that if a parameter changes somewhere due to recalculation, a lot of elements

already found may be affected and procedures may need to be reiterated.

5.3 Further work

The ground source heat pump feasibility was studied considering the pipe coil horizontally

buried which requires a certain availability of space. To increase the system performance,

the ground heat exchanger could be envisaged to be vertically buried even though the

cost would neatly increase.

Also in order to push the study further, the way of laying out the different elements of the

installations could be looked at. The battery bank is quite bulky, the location and manner

the batteries are settled together so as to save some space is a significant factor.

Similarly for the different elements constituting the solar thermal system remaining

numerous. The height separating them and the way they are connected together

according to the house shape would give more information of fluid pressure and would

allow more accurate results.

Finally, the space could be studied to be heated by means of other sources of energy

such as biomass, the natural resources being abundant at the house localisation.

The wind power is also a possible solution for providing electrical energy in this case. The

feasibility study of a hybrid system combining PV and hydro turbine seems to have the

potential to show good performances.

Page 76: NMorel-Honours project

76

6 Bibliography ADEME, 2016. Isolation de la maison. [Online]

Available at: http://franche-comte.ademe.fr/contenu.php?id=327

[Accessed March 2016].

ASHRAE, H., 2001. Fundamentals. [Online]

Available at: http://www.cambeep.eng.cam.ac.uk/References/internalheat

[Accessed February 2016].

Biowatt, 2016. [Interview] (29 February 2016).

CarbonNeutral, 2013. Deep-Cycle Batteries for Off-Grid & Remote Power Systems. [Online]

Available at: http://www.solar-wind.co.uk/deep-cycle-dryfit-batteries-battery-uk.html

[Accessed December 2015].

CIBSE Journal, Y. E., 2016. Solar thermal – solar hot water heating. [Online]

Available at: http://www.cibsejournal.com/cpd/modules/2009-02/

[Accessed October 2015].

CIBSE, 2007. CIBSE guide c, s.l.: CIBSE.

Collecteurderosee, 2015. Température du sol en fonction de la profondeur. [Online]

Available at:

http://www.collecteurderosee.fr/evolution%20temperature%20du%20sol/evolution%20temperat

ure%20du%20sol.html

[Accessed February 2016].

Dankoff, W., 2001. How to choose an inverter for an independent Energy System.

EcoHiSolar, 2011. Solar Thermal Systems. [Online]

Available at: http://www.ecohisolar.co.uk/solar-thermal/

[Accessed November 2015].

EnergyAgency, 2015. Ground source Heat pump. [Online]

Available at: http://www.energyagency.org.uk/en/ground-source-heat-pump_46650/

[Accessed February 2016].

EnergySavingTrust, 2016. Ground source heat pumps. [Online]

Available at: http://www.energysavingtrust.org.uk/domestic/ground-source-heat-pumps

[Accessed February 2016].

Gasappliance, 2013. Domestic Hot Water Cylinders Explained. [Online]

Available at:

http://www.gasapplianceguide.co.uk/Direct%20and%20Indirect%20Cylinders%20Explained.htm

#Categories_of_hot_water_cylinder_

[Accessed November 2015].

Hall, K. & Nicholls, R., 2008. Green Building Bible, Volume 1. 4th ed. Llandsyul: Green Building

Press.

Page 77: NMorel-Honours project

77

HeatPumpAssociation, 2015. Heat pump data. [Online]

Available at:

http://www.heatpumps.org.uk/PdfFiles/HeatPumpGroundToWaterDataSheetNo.2Domestic.pdf

[Accessed February 2016].

Muneer et al, 2014. Monthly-averaged, k - kt relationship. Journal of Building Services

Engineering Research & Technology.

Muneer, T., 2000. Windows in buildings. Oxford: Architectural Press.

NASA, 2016. EOSWEB. [Online]

Available at: https://eosweb.larc.nasa.gov/cgi-

bin/sse/retscreen.cgi?&[email protected]&p

Nicholls, R., 2008. Green Building Bible, Volume 2. 4th ed. Llandsyul: Green Building Press.

QuelleEnergie, 2016. Pompe à chaleur géothermique. [Online]

Available at: http://www.quelleenergie.fr/economies-energie/pompe-chaleur-geothermique/

[Accessed February 2016].

Renogy, 2015. Monocrystalline v. Polycrystalline: What Difference?. [Online]

Available at: http://renogy.com/monocrystalline-v-polycrystalline-what-difference/

[Accessed December 2015].

T Muneer, T. C. G. & Kambedezis, H., 2007. Solar radiation and daylight models. 2nd 2007 ed.

s.l.:United Kingdom : MyiLibrary.

Tariq Muneer, 2000. Glazing daylight and solar radiation transmission. In: Windows in buildings.

s.l.:Oxford : Architectural Press , p. 115.

ViridianSolar, 2014. Different Types of Solar Panel. [Online]

Available at: http://www.viridiansolar.co.uk/Solar_Energy_Guide_3_2.htm

[Accessed October 2015].

Watson, D. E., 2011. Direct, Diffuse and Reflected Radiation. [Online]

Available at: http://www.ftexploring.com/solar-energy/direct-and-diffuse-radiation.htm

[Accessed December 2015].

Wikipedia, 2016. Climat de l'Isère. [Online]

Available at: https://fr.wikipedia.org/wiki/Climat_de_l%27Is%C3%A8re

[Accessed February 2016].

Wikipedia, 2016. List of thermal conductivities. [Online]

Available at: https://en.wikipedia.org/wiki/List_of_thermal_conductivities

[Accessed December 2015].

Page 78: NMorel-Honours project

78

7 Appendix A – House Solar Gains and Heat Losses

HOURS January February March April May June July August September October November December

5.5 1.9 9.0 14.9 13.8 7.9

6.5 0.5 5.5 14.6 23.3 29.7 29.5 20.9 12.2

7.5 11.6 10.2 43.8 40.9 44.3 45.6 46.7 46.9 46.5 39.7 3.6

8.5 129.1 89.6 95.6 78.8 73.4 74.0 80.1 87.6 96.6 84.7 79.3 11.5

9.5 120.0 138.9 150.1 121.8 109.2 106.3 118.6 134.9 149.9 130.3 117.3 114.1

10.5 127.3 177.2 193.4 157.7 140.8 135.6 153.1 175.1 192.6 165.9 148.1 143.1

11.5 133.1 198.0 216.8 177.7 159.1 152.7 173.0 197.6 215.9 185.2 165.4 159.9

12.5 133.1 197.9 216.7 177.7 159.0 152.7 173.0 197.7 216.0 185.3 165.5 160.0

13.5 127.1 176.9 193.1 157.5 140.7 135.6 153.2 175.3 192.9 166.2 148.4 143.2

14.5 119.6 138.4 149.7 121.5 109.0 106.2 118.7 135.2 150.3 130.7 117.8 114.2

15.5 128.1 89.0 95.1 78.5 73.3 74.0 80.2 87.9 97.0 85.2 80.0 11.5

16.5 11.5 10.2 43.4 40.8 44.3 45.6 46.7 47.0 46.9 40.4 3.6

17.5 0.5 5.5 14.6 23.4 29.7 29.5 20.9 11.4

18.5 1.9 9.1 14.9 13.7 7.9

GAINS 1.7 2.0 2.3 1.9 1.8 1.8 2.0 2.1 2.3 1.9 1.6 1.4

(kWh/day)

HOURS January February March April May June July August September October November December

5.5 1.9 90.7 134.8 148.4 8.6

6.5 0.5 5.8 114.8 138.0 167.9 185.2 166.3 124.8

7.5 12.8 10.7 134.1 148.3 168.4 191.2 210.7 195.1 158.8 101.1 3.7

8.5 147.0 119.7 160.0 165.7 181.7 198.3 218.1 207.2 177.3 120.2 93.6 11.5

9.5 88.9 119.6 156.5 158.7 170.3 181.3 198.3 191.5 168.6 119.0 90.7 80.8

10.5 59.1 93.1 121.8 126.0 135.5 142.8 153.9 147.9 130.1 93.6 70.2 61.2

11.5 38.5 61.4 81.9 90.6 99.8 105.5 110.6 103.3 88.1 63.6 46.4 39.2

12.5 29.0 48.2 66.9 75.4 84.9 91.2 96.6 88.5 72.9 50.3 35.4 29.3

13.5 26.1 42.8 60.7 69.6 79.3 85.7 90.5 82.1 66.7 45.1 30.9 25.1

14.5 20.8 33.0 49.3 59.1 68.7 75.3 79.0 70.4 55.3 35.6 22.8 17.6

15.5 13.7 20.5 34.6 45.1 54.8 61.4 63.8 54.9 40.4 23.5 12.7 11.6

16.5 12.7 10.7 18.8 29.7 39.1 45.6 46.7 37.8 24.3 10.6 3.7

17.5 0.5 5.8 14.6 23.4 29.7 29.5 20.9 9.0

18.5 1.9 9.1 14.9 13.7 7.9

GAINS 0.4 0.4 0.7 0.9 1.1 1.2 1.3 1.1 0.9 0.5 0.3 0.2

(kWh/day)

Hourly solar gains in W/ 𝑚² - Aspect=180 (South), Windows area=1.6 𝑚²

Hourly solar gains in W/ 𝑚² - Aspect=90 (East), Window area=0.8 𝑚²

Walls Door + windows Roof Ventilation Thermal bridges (5%) Floor (9%)

January 21.1% 16.2% 20.9% 27.8% 5.0% 9.0%

February 21.1% 16.1% 20.9% 27.9% 5.0% 9.0%

March 21.1% 16.0% 20.8% 28.1% 5.0% 9.0%

April 21.0% 15.9% 20.7% 28.4% 5.0% 9.0%

May 20.9% 15.5% 20.5% 29.1% 5.0% 9.0%

June 20.4% 15.0% 20.1% 30.5% 5.0% 9.0%

July - - - - - -

August - - - - - -

September 20.7% 15.3% 20.4% 29.6% 5.0% 9.0%

October 20.9% 15.5% 20.7% 28.8% 5.0% 9.0%

November 21.0% 16.0% 20.8% 28.1% 5.0% 9.0%

December 21.1% 16.1% 20.9% 27.9% 5.0% 9.0%

Heat losses (%)

Heat loss repartition, by month (%)

Page 79: NMorel-Honours project

79

8 Appendix B – Solar Thermal System Elements (1)

Circulating pump Clearline collector V30 Specifications

Solar electric cylinder

Page 80: NMorel-Honours project

80

9 Appendix C - Solar Thermal System Elements (2)

Expansion vessel

Pre-insulated pipe

Controller and temperature sensors

Page 81: NMorel-Honours project

81

10 Appendix D – GSHP Circuit Elements (1)

Ground Source Heat Pump

GSHP fluid Circulating pump

Page 82: NMorel-Honours project

82

11 Appendix E - GSHP Circuit Elements (2)

Water cylinder 210 L

Underground pipe coil 250 m

Page 83: NMorel-Honours project

83

12 Appendix F – PV Systems Elements (1)

PV16/250 Specifications Battery RBS1860 specifications

Page 84: NMorel-Honours project

84

13 Appendix G – PV Systems Elements (2)

Maximum Power Point tracker

Inverter specifications

Page 85: NMorel-Honours project

85

14 Appendix E – Biowatt Energie Mail Exchange