Addendum No. 3
UNCW Randall Library Life Safety & ADA UpgradesWilmington, North Carolina SCO# 17-17589-01A PM# 5544BMG Project No. 2016280.00 November 3, 2017
The following items supplement, change, delete or add to the Construction Documents as though repeated in full therein. All general conditions, special conditions, etc., as originally specified shall apply to these items.
ITEM NO. 1 DRAWINGS
1) General Clarification:a. Partition Types 4 and 6 are intended to address the repair/finishing of walls
affected by the demolition of wall tile. The design intent is to remove existing bathroom wall tile as noted on plans. At CMU walls, tile will be removed, and the block prepared to receive a laminated layer of GWB, or where noted, GWB on furring channels, (this typically occurs on walls where we are providing power) At stud walls, the wall tile and substrate shall be removed, and new GWB installed on existing studs. The drawings reflect these conditions as we believe they occur, but due to the uncertainties of existing construction, some of these conditions may need to be determined and coordinated in the field during construction.
2) The following drawings have been revised to better clarify the previous statement:a. AD102b. AD104c. A102d. A104e. A501
3) A406: DOOR AND FINISH SCHEDULES - VCT and Rubber Cove base have been noted as “by owner”.
4) A502: PLAN DETAILS - Added sheet with details related to furring out walls at existing door and window frames.
Addendum No. 3 UNCW Randall Library Life Safety & ADA Upgrades Wilmington, North Carolina SCO# 17-17589-01A PM# 5544 BMG Project No. 2016280.00 November 3, 2017 The following items supplement, change, delete or add to the Construction Documents as though repeated in full therein. All general conditions, special conditions, etc., as originally specified shall apply to these items.
ITEM NO. 1 DRAWINGS
1) General Clarification: a. Partition Types 4 and 6 are intended to address the repair/finishing of walls
affected by the demolition of wall tile. The design intent is to remove existing bathroom wall tile as noted on plans. At CMU walls, tile will be removed, and the block prepared to receive a laminated layer of GWB, or where noted, GWB on furring channels. (this typically occurs on walls where we are providing power) At stud walls, the wall tile and substrate shall be removed, and new GWB installed on existing studs. The drawings reflect these conditions as we believe they occur, but due to the uncertainties of existing construction, some of these conditions may need to be determined and coordinated in the field during construction.
2) The following drawings have been revised to better clarify the previous statement: a. AD102 b. AD104 c. A102 d. A104 e. A501
3) A406: DOOR AND FINISH SCHEDULES – VCT and Rubber Cove base have been
noted as “by owner”.
4) A502: PLAN DETAILS – Added sheet with details related to furring out walls at existing door and window frames.
2016280.00 UNCW RANDALL LIBRARY ADDENDUM NO. 3 LIFE SAFETY & ADA UPGRADES
Page 2 of 3
ITEM NO. 2 QUESTIONS FROM BIDDERS
1) What type of Water and Drain lines are acceptable. Right now just a general spec appears to say Cast Iron and Copper. Just want to confirm this is what is speced on this job?
a. Response: Please refer to specifications
2) The fire alarm plans do not show locations available for fire alarm booster panels. Booster panels contain the control equipment (amplifiers, power supplies and required batteries) to provide power for strobes, speakers, optical smoke detectors and air sampling detectors. Please clarify available locations for this equipment. As a minimum, there will most likely be four of these cabinets needed, two on each floor. For load distribution purposes they should be located at each end or side of the building. Based on equipment layout, the end of the building is preferred.
a. Response: Locations for booster panels have not yet been determined. They will be coordinated with the university and finalized during the shop drawing phase.
3) Will the fire alarm equipment be supplied with power from an emergency generator circuit?
a. Response: There is no emergency generator serving Randall Hall.
4) Based on our previous experience with military mass notification projects, can an acoustical consultant be omitted from the requirements in the fire alarm specification. On previous projects we were held to a criteria of 0.7 (point seven) utilizing the STI scale. This project requires just 0.5 (point five) Additionally, it should be noted the responsibility of an acceptable system is on the fire alarm/emergency voice system supplier by specification.
a. Response: The acoustician's evaluation is needed as part of the shop drawing submittal.
5) Please clarify item 4 of section H Projected Beam Smoke Detection AND Item 7 of section I Aspirating Type Smoke Detection. Nuisance alarms have been defined by some as alarms caused by no fault of the device or the installer. Is it the intent that we provide a factory trained technician at no charge for issues caused by others?
a. Response: Nuisance tripping needs to be investigated by the contractor by any means necessary during the warranty period. This may include a factory technician's visit where the cause of the nuisance tripping cannot be determined expediently by the contractor's staff. Trouble conditions due to lack of maintenance (i.e. replacement of sampling air filters) or detector beam blockages are not considered nuisance tripping.
6) May the duct smoke detectors be removed from the project. This request is based on the appearance all areas serviced by the air handling units have 100% coverage by area smoke detection. Under this request, we are not asking for the removal of the requirement to shut down all air handling units upon the activation of any building fire alarm.
a. Response: The duct smoke detectors may not be removed per the ruling of the NC SCO.
2016280.00 UNCW RANDALL LIBRARY ADDENDUM NO. 3 LIFE SAFETY & ADA UPGRADES
Page 3 of 3
7) I am inquiring if we can use the Viega ProPress method for joining the copper tubing in lieu of soldered joints. We have used this in dozens of projects as well as on the UNCW campus with 100% success and zero leaks. It simply has become a better method than the old school method of soldering and the several mitigating factors that affect it.
a. Response: Yes, this is acceptable.
8) I do not see where the bid date and time are mentioned, however, in the prebid it was stated Nov 8th at 2:00 is that correct?
a. Response: Page NTB 1: First Paragraph. “Sealed proposals will be received by the University of North Carolina at Wilmington in Wilmington, North Carolina, Project Management Department, in the Facilities Administration Building, Conference Room #2, up to 2:00 PM on Wednesday November 8, 2017.”
9) The plans say Carpet tile by Owner but does not state that the VCT and rubber base are by Owner.
a. Response: Carpet, VCT, and rubber wall base are all by owner.
10) Ceramic tile by GC? a. Response: Yes.
11) It was mentioned in the prebid but do not see anywhere that it states bonds required?
a. Response: This is a formal project. A bid deposit/bond is required as well as Payment and Performance Bonds.
ITEM NO. 3 ATTACHMENTS DRAWINGS AD102, AD104, A102, A104, A406, A501, A502 End of Addendum No. 3
DEMOLITION KEY NOTES BECKERMORGAN
REMOVE EXISTING CEILING INCLUDING BUT NOT LIMITED TO, ACOUSTIC CEILING TILES, SUSPENSION GRID, LIGHT FIXTURES, AND MECHANICAL EQUIPMENT; SALVAGE CEILING TILES AND LIGHT FIXTURES FOR RE-USE. CEILING GRID AND ALL OTHER REMOVED ITEMS TO BE DISCARDED
8 9 Q», A »
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO, CARPET TILE, VINYL WALL BASE, AND ADHESIVE; PREPARE SLAB TO RECEIVE NEW FINISH. COORDINATE EXTENT OF FLOOR FINISH DEMOLITION WITH NEW FINISH PLAN
0 ARCHITECTUREPLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
J T I0 1
0 |
0\
SJ REMOVE DASHED PORTION OF EXISTING WALL\ 13\ TYPICAL 024\ REMOVE EXISTING DROP SOFFIT
WOMEN MEN|1009| |1008| 0 REMOVE BASE AND WALL MOUNTED CABINETS
TY 31 CAL 3 0 EXISTING INTERIOR FINISHES TO REMAINr _ n EXISTING STACKS TO BE EMPTIED AND CONTENTS TO BE
RELOCATED TO STORAGE. STACKS TO BE REMOVED AND RETURNED TO OWNER; COORDINATE WITH OWNER.
^0 1 I 0\18 181A I21 v 21J
0 REMOVAL AND RELOCATION OF FLAT FILES BY OTHERS26 24
0 REMOVAL AND RELOCATION OF PRINT STATIONS BY OTHERS24WORK 110201
I_____ J t = =28- r 0 NOT USED
A »NOT FOR
CONSTRUCTION
EXTENT OF CEILING DEMOLITION; COORDINATE WITH REFLECTED CEILING PLAN
Z j 0TY 31 CAL 19L J U = = =/= = l* TY 31 CALr 027 TEMPORARY DUST PARTITION - CONFIRM POSITION WITH OWNER- 208,
91 TY 31 CAL' (
= 10595 m: =
%V?vV*‘%0GTOn-0
"Hillin'"
24 01 STEEL COLUMN EXISTING TO REMAIN, TYPICALl\_ J
EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED; DOOR AND FRAME TO BE DISCARDED, HARDWARE TO BE RETURNED TO OWNER
EXISTING STOREFRONT SYSTEM INCLUDING BUT NOT LIMITED TO, GLAZING, AND ALUMINUM FRAME TO BE REMOVED AND DISCARDED
REMOVE PORTION OF EXISTING WALL AS REQUIRED TO ACCOMMODATE NEW OPENING; COORDINATE SIZE AND LOCATION WITH CONSTRUCTION PLAN
SAW-CUT AND REMOVE PORTION OF EXISTING CONCRETE SLAB FOR NEW MECHANICAL PENETRATION; COORDINATE SIZE AND LOCATION WITH MECHANICAL DRAWINGS
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO, FLOOR TILE, THICKSET, AND COVE TILE WALL BASE. PATCH, LEVEL, AND PREPARE SLAB TO RECEIVE NEW FINISH
J n-I— i—i -i--------r 0
o0 * 3 N.C. ./o/0A ..........
20 DEMOLITION PLAN - FIRST FLOOR 0D102/ SCALE: 1/4’ = r-Q” ^gang/0
Gtatec Ur9r0 /0/?m /® V\ o
- 51922 s ■00
8.0 £& *3f.h OCaro
*'l2 3 0/vgto^;REMOVE EXISTING PLUMBING FIXTURES; SEE PLUMBING DRAWINGS0REMOVE AND DISCARD EXISTING TOILET PARTITIONS AND ALL ASSOCIATED HARDWARE
REMOVE AND DISCARD EXISTING TOILET ROOM ACCESSORIES INCLUDING BUT NOT LIMITED TO MIRRORS, TOILET PAPER DISPENSARIES, SOAP DISPENSERS, PAPER TOWEL DISPENSERS, AND SANITARY NAPKIN RECEPTACLES
0PROJECT TITLE
0/ \/ \
H 140 0F0 p r
I © I I o I L00J L00J
REMOVE EXISTING WALL TILE, MORTAR, AND SUBSTRATE; EXISTING STUDS TO REMAIN: TYPICAL FLOOR TO CEILING0/ 1222 1 I/
16 1 I■j-T
/=J| EXISTING DOOR AND FRAME TO REMAIN; HARDWARE TO BE
REMOVED AND RETURNED TO OWNER. SEE DOOR SCHEDULEI I 0L - 5-1" I I
18 22 r22 REMOVE EXISTING WALL TILE AND MORTAR; EXISTING SUBSTRATE AND WALL TO REMAIN, TYPICAL FLOOR TO CEILING. PREPARE SUBSTRATE TO RECEIVE NEW FINISH
WOMEN 0|1025|
RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
r 0!T ‘—i i—1 T EXISTING FLOOR FINISH TO REMAIN\
0 '/
18h-FLb 0 REMOVE EXISTING MILLWORK AND COUNTERTOP21rCM
_lREMOVE EXISTING BASE CABINETS. EXISTING COUNTERTOP TO REMAIN. PROVIDE TEMPORARY SUPPORT AS REQUIRED8 0I I 18 24 J- 0 1 Ü0I---------------- 141- 1 1
0 F0 601 S. College Rd.
Wilmington, NC 28403
PM# - 5544 SCO# - 17-17589-01A
111 REMOVE EXISTING MAIL SLOTS/I I I / TYPICALI I I 3/IT REMOVE EXISTING WALL FINISH BACK TO EXISTING TO REMAIN
BLOCK WALL. PREPARE BLOCK TO RECEIVE NEW FINISH./ 0n ^iH AMENL_\ TYPICAL|1028| 200I\
TYPICALr J \ j 19= =Pr = i18 o\ fr~ ii „
100 !! fesF0\
i2118~Tl-«—21 ]TYPICAL r1Il r 3 JWOMEN ^"-0 l 1
FTFo-_0j
SHEET TITLE« i
bLU = =J_ill. FIRST FLOOR DEMOLITION PLAN
CDH TYPICAL X20 \I 0 WOMEN\rr = 24|1030| TYPICAL\
1iri noi9iJw Ô^0Il L 1- « 18F-^TYPICAL 19 x 210 X 0\/ 18 L/ _____ i
TYPICALL = 21 24= =h0
30DEMOLITION PLAN - FIRST FLOOR TO DEMOLITION PLAN - FIRST FLOORD102/ SCALE: 1/4” = r-Q” D102/ SCALE: 1/4” = r-Q”
A ISSUE BLOCK
KEY PLANGENERAL NOTES1/ADI01
r 1L1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK. 7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233. 13. SEE GENERAL NOTES ON G001 A ADDENDUM 311/03/20172. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION. 8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION A ADDENDUM 110/30/2017
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/FACILITIES.
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS. . . . . U MARK DATE DESCRIPTION
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE, FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN. b PROJECT NO: 2016280.003/AD102
4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING, SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS. DATE: 08/19/201711. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED
PERSONS.SCALE:
5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS, RAMPS, ETC.
□ nDRAWN BY: NMY PROJ MGR: EWOi]□»f ;.. #1112. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE APPROVED BY THE OWNER. A6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE. AD102F : ihr
1/AD102 2/AD102 COPYRIGHT ^^2017
5'-1"
2'-0
"6
'-6
"
19
TYPICAL
20
TYPICAL
3
TYPICAL
14
22
14
14
14
14
14
14
16
1
21
18
1
21
18
1
21
18
1
18
1
18
12
24
TYPICAL
24
22
22
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK.
2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION.
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT
COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/
FACILITIES.
4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC.
6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE.
7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233.
8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE,
FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS.
11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED
PERSONS.
12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE
APPROVED BY THE OWNER.
13. SEE GENERAL NOTES ON G001
14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS
DEMOLITION KEY NOTES
REMOVE EXISTING CEILING INCLUDING BUT NOT LIMITED TO,
ACOUSTIC CEILING TILES, SUSPENSION GRID, LIGHT FIXTURES,
AND MECHANICAL EQUIPMENT; SALVAGE CEILING TILES AND LIGHT
FIXTURES FOR RE-USE. CEILING GRID AND ALL OTHER REMOVED
ITEMS TO BE DISCARDED
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO,
CARPET TILE, VINYL WALL BASE, AND ADHESIVE; PREPARE SLAB
TO RECEIVE NEW FINISH. COORDINATE EXTENT OF FLOOR FINISH
DEMOLITION WITH NEW FINISH PLAN
REMOVE DASHED PORTION OF EXISTING WALL
REMOVE EXISTING DROP SOFFIT
REMOVE BASE AND WALL MOUNTED CABINETS
EXISTING INTERIOR FINISHES TO REMAIN
EXISTING STACKS TO BE EMPTIED AND CONTENTS TO BE
RELOCATED TO STORAGE. STACKS TO BE REMOVED AND
RETURNED TO OWNER; COORDINATE WITH OWNER.
REMOVAL AND RELOCATION OF FLAT FILES BY OTHERS
REMOVAL AND RELOCATION OF PRINT STATIONS BY OTHERS
NOT USED
EXTENT OF CEILING DEMOLITION; COORDINATE WITH REFLECTED
CEILING PLAN
TEMPORARY DUST PARTITION - CONFIRM POSITION WITH OWNER
STEEL COLUMN EXISTING TO REMAIN, TYPICAL
EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED; DOOR
AND FRAME TO BE DISCARDED, HARDWARE TO BE RETURNED TO
OWNER
EXISTING STOREFRONT SYSTEM INCLUDING BUT NOT LIMITED TO,
GLAZING, AND ALUMINUM FRAME TO BE REMOVED AND
DISCARDED
REMOVE PORTION OF EXISTING WALL AS REQUIRED TO
ACCOMMODATE NEW OPENING; COORDINATE SIZE AND LOCATION
WITH CONSTRUCTION PLAN
SAW-CUT AND REMOVE PORTION OF EXISTING CONCRETE SLAB
FOR NEW MECHANICAL PENETRATION; COORDINATE SIZE AND
LOCATION WITH MECHANICAL DRAWINGS
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO,
FLOOR TILE, THICKSET, AND COVE TILE WALL BASE. PATCH, LEVEL,
AND PREPARE SLAB TO RECEIVE NEW FINISH
REMOVE EXISTING PLUMBING FIXTURES; SEE PLUMBING
DRAWINGS
REMOVE AND DISCARD EXISTING TOILET PARTITIONS AND ALL
ASSOCIATED HARDWARE
REMOVE AND DISCARD EXISTING TOILET ROOM ACCESSORIES
INCLUDING BUT NOT LIMITED TO MIRRORS, TOILET PAPER
DISPENSARIES, SOAP DISPENSERS, PAPER TOWEL DISPENSERS,
AND SANITARY NAPKIN RECEPTACLES
REMOVE EXISTING WALL TILE, MORTAR, AND SUBSTRATE;
EXISTING STUDS TO REMAIN: TYPICAL FLOOR TO CEILING
EXISTING DOOR AND FRAME TO REMAIN; HARDWARE TO BE
REMOVED AND RETURNED TO OWNER. SEE DOOR SCHEDULE
REMOVE EXISTING WALL TILE AND MORTAR; EXISTING SUBSTRATE
AND WALL TO REMAIN, TYPICAL FLOOR TO CEILING. PREPARE
SUBSTRATE TO RECEIVE NEW FINISH
EXISTING FLOOR FINISH TO REMAIN
REMOVE EXISTING MILLWORK AND COUNTERTOP
REMOVE EXISTING BASE CABINETS. EXISTING COUNTERTOP TO
REMAIN. PROVIDE TEMPORARY SUPPORT AS REQUIRED
REMOVE EXISTING MAIL SLOTS
REMOVE EXISTING WALL FINISH BACK TO EXISTING TO REMAIN
BLOCK WALL. PREPARE BLOCK TO RECEIVE NEW FINISH.
1
3
21
18
20
19
24
23
TYPICAL
TYPICAL
TYPICAL
1
21
18
23
TYPICAL
20
19
TYPICAL
TYPICAL
24
TYPICAL
13
3
TYPICAL
24
24
14 23
1
21
18
26
1
21
18
12
27
28
TYPICAL
24
AD102
FIRST FLOOR
DEMOLITION PLAN
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NOT FOR
CONSTRUCTION
A 10/30/2017 ADDENDUM 1
A
B 11/03/2017 ADDENDUM 3
B
B
B
DEMOLITION KEY NOTES BECKERMORGAN
REMOVE EXISTING CEILING INCLUDING BUT NOT LIMITED TO, ACOUSTIC CEILING TILES, SUSPENSION GRID, LIGHT FIXTURES, AND MECHANICAL EQUIPMENT; SALVAGE CEILING TILES AND LIGHT FIXTURES FOR RE-USE. CEILING GRID AND ALL OTHER REMOVED ITEMS TO BE DISCARDED
4 5 Q
», A »
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO, CARPET TILE, VINYL WALL BASE, AND ADHESIVE; PREPARE SLAB TO RECEIVE NEW FINISH. COORDINATE EXTENT OF FLOOR FINISH DEMOLITION WITH NEW FINISH PLAN
0 ARCHITECTUREPLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
AI I t = 0 A1r!
WOMEN t| 2050A |
0 0 REMOVE DASHED PORTION OF EXISTING WALLMEN12052A |
A/l J 24 29/ 0 REMOVE EXISTING DROP SOFFIT
24 €= = =i221 Î4 m REMOVE BASE AND WALL MOUNTED CABINETSl------------1
19^ft 19& »TYPICAL TYPICAL/0/ EXISTING INTERIOR FINISHES TO REMAINJ-
22 Tlf^° fri=18 — 18 21 EXISTING STACKS TO BE EMPTIED AND CONTENTS TO BE RELOCATED TO STORAGE. STACKS TO BE REMOVED AND RETURNED TO OWNER; COORDINATE WITH OWNER.
n= =I 0 0\ 4 0llJj1 1TYPICAL^ 21/l J MEN0 /21 — fr iii i |2052| 0n— REMOVAL AND RELOCATION OF FLAT FILES BY OTHERSIl I=1/ \ = 3 H 0 0! I £0
20 = #= = iLJj iTYPICAL 0 2924l 16 0 REMOVAL AND RELOCATION OF PRINT STATIONS BY OTHERS26 00^ 24 /
Z J/
0r NOT USED■itr -U4
NOT FOR CONSTRUCTION
EXTENT OF CEILING DEMOLITION; COORDINATE WITH REFLECTED CEILING PLAN0
0 TEMPORARY DUST PARTITION - CONFIRM POSITION WITH OWNER23
0c,T W ////0 STEEL COLUMN EXISTING TO REMAIN, TYPICAL
2 EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED; DOOR AND FRAME TO BE DISCARDED, HARDWARE TO BE RETURNED TO OWNER
EXISTING STOREFRONT SYSTEM INCLUDING BUT NOT LIMITED TO, GLAZING, AND ALUMINUM FRAME TO BE REMOVED AND DISCARDED
REMOVE PORTION OF EXISTING WALL AS REQUIRED TO ACCOMMODATE NEW OPENING; COORDINATE SIZE AND LOCATION WITH CONSTRUCTION PLAN
SAW-CUT AND REMOVE PORTION OF EXISTING CONCRETE SLAB FOR NEW MECHANICAL PENETRATION; COORDINATE SIZE AND LOCATION WITH MECHANICAL DRAWINGS
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO, FLOOR TILE, THICKSET, AND COVE TILE WALL BASE. PATCH, LEVEL, AND PREPARE SLAB TO RECEIVE NEW FINISH
0 :£? ^ •= :c5 10595 m- * •'ii%V?vV*’
"Hillin'"
:29 O29 "y/ * c N.C. ./o/
0'0
..........WOMEN|2050| 0
^GANg^
Gtat ecUr0 4 s-' /29 Z/?
ÜJ o CÛ «
0 4 0 %
- 51922 s ■JL
0 % §0& 4,h' fh oCaroA *'i0/vgto^;REMOVE EXISTING PLUMBING FIXTURES; SEE PLUMBING
DRAWINGS020 DEMOLITION PLAN - SECOND FLOORREMOVE AND DISCARD EXISTING TOILET PARTITIONS AND ALL ASSOCIATED HARDWARE
REMOVE AND DISCARD EXISTING TOILET ROOM ACCESSORIES INCLUDING BUT NOT LIMITED TO MIRRORS, TOILET PAPER DISPENSARIES, SOAP DISPENSERS, PAPER TOWEL DISPENSERS, AND SANITARY NAPKIN RECEPTACLES
0D104/ SCALE: 1/4” = T-0”8 PROJECT TITLE
0vJ REMOVE EXISTING WALL TILE, MORTAR, AND SUBSTRATE;
EXISTING STUDS TO REMAIN: TYPICAL FLOOR TO CEILINGI 02 3\
\0 N
EXISTING DOOR AND FRAME TO REMAIN; HARDWARE TO BE REMOVED AND RETURNED TO OWNER. SEE DOOR SCHEDULE00
REMOVE EXISTING WALL TILE AND MORTAR; EXISTING SUBSTRATE AND WALL TO REMAIN, TYPICAL FLOOR TO CEILING. PREPARE SUBSTRATE TO RECEIVE NEW FINISH
0 0T Tr 0\ 0 0 1\ 0 - RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
I\ \\ 0 |
\ 0 EXISTING FLOOR FINISH TO REMAIN- J \ \HOUSEKEEPING24 \ \|2012| \
0 REMOVE EXISTING MILLWORK AND COUNTERTOP
18 18 REMOVE EXISTING BASE CABINETS. EXISTING COUNTERTOP TO REMAIN. PROVIDE TEMPORARY SUPPORT AS REQUIRED
WOMEN 0L |2040|^TYPICAL
STORAGE 0 601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01A
r n REMOVE EXISTING MAIL SLOTS|2013|
\ REMOVE EXISTING WALL FINISH BACK TO EXISTING TO REMAIN BLOCK WALL. PREPARE BLOCK TO RECEIVE NEW FINISH.000\
\24 \
-0T1T“18 181 /.0 i
0iI 00/ I "
21 214
19 26TYPICAL TYPICALIl II Il II Il II
U0 T
020 24 WOMEN24TYPICAL 1 Z 0| 2040A|/ SHEET TITLE
l Ip- alternate NO. 3i___ i------------ 14SECOND FLOOR DEMOLITION PLAN
ivru = = 24/vJT~~WOMEN MEN 0 ALL WORK ON SHEETS AD104, A104, A204, AND SUBSEQUENT MECHANICAL, ELECTRICAL, AND PLUMBING SHEETS RELATED TO THESE AREAS SHALL BE AN ALTERNATE
00» = J|2014| |20111 ^TYPICAL
Rr = T/ n
/ STORAGE/ 18 21\2 / \L = | 2042E | I/,/ \ A•n'0=0 19-J ~3 TYPICALU___I4 Ljr F = = 20= J TYPICAL4 r =/ 24 24 26 1_____/ \ AlZL =L \I I 241 .0J=LK13
JLK Il I L
A
3 A DEMOLITION PLAN - SECOND FLOOR AA DEMOLITION PLAN - SECOND FLOORD104/ SCALE: 1/4” = t-0” D104/ SCALE: 1/4” = T-0”
ISSUE BLOCK
KEY PLANGENERAL NOTES2/AD104 1/AD103
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK. 7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233. 13. SEE GENERAL NOTES ON G001 A A 11/03/2017 ADDENDUM 32. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION. 8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION A ADDENDUM 110/30/2017
T,3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/FACILITIES.
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS MARK DATE DESCRIPTION
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE, FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN. PROJECT NO: 2016280.00
X4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING, SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS. DATE: 08/19/20174BË1n11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED PERSONS.
SCALE:5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC. DRAWN BY: NMY PROJ MGR: EWO12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE APPROVED BY THE OWNER.
P06. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL. PROTECT SYSTEMS AND DEVICES FROM DAMAGE. AD 104
1/AD104 3/AD104COPYRIGHT ^^2017
2
1
21
19
TYPICAL
20
TYPICAL
3
TYPICAL
1
18
13
26
14
1
2
24
24
12
24
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK.
2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION.
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT
COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/
FACILITIES.
4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC.
6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE.
7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233.
8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE,
FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS.
11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED
PERSONS.
12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE
APPROVED BY THE OWNER.
13. SEE GENERAL NOTES ON G001
14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS
DEMOLITION KEY NOTES
REMOVE EXISTING CEILING INCLUDING BUT NOT LIMITED TO,
ACOUSTIC CEILING TILES, SUSPENSION GRID, LIGHT FIXTURES,
AND MECHANICAL EQUIPMENT; SALVAGE CEILING TILES AND LIGHT
FIXTURES FOR RE-USE. CEILING GRID AND ALL OTHER REMOVED
ITEMS TO BE DISCARDED
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO,
CARPET TILE, VINYL WALL BASE, AND ADHESIVE; PREPARE SLAB
TO RECEIVE NEW FINISH. COORDINATE EXTENT OF FLOOR FINISH
DEMOLITION WITH NEW FINISH PLAN
REMOVE DASHED PORTION OF EXISTING WALL
REMOVE EXISTING DROP SOFFIT
REMOVE BASE AND WALL MOUNTED CABINETS
EXISTING INTERIOR FINISHES TO REMAIN
EXISTING STACKS TO BE EMPTIED AND CONTENTS TO BE
RELOCATED TO STORAGE. STACKS TO BE REMOVED AND
RETURNED TO OWNER; COORDINATE WITH OWNER.
REMOVAL AND RELOCATION OF FLAT FILES BY OTHERS
REMOVAL AND RELOCATION OF PRINT STATIONS BY OTHERS
NOT USED
EXTENT OF CEILING DEMOLITION; COORDINATE WITH REFLECTED
CEILING PLAN
TEMPORARY DUST PARTITION - CONFIRM POSITION WITH OWNER
STEEL COLUMN EXISTING TO REMAIN, TYPICAL
EXISTING DOOR, FRAME, AND HARDWARE TO BE REMOVED; DOOR
AND FRAME TO BE DISCARDED, HARDWARE TO BE RETURNED TO
OWNER
EXISTING STOREFRONT SYSTEM INCLUDING BUT NOT LIMITED TO,
GLAZING, AND ALUMINUM FRAME TO BE REMOVED AND
DISCARDED
REMOVE PORTION OF EXISTING WALL AS REQUIRED TO
ACCOMMODATE NEW OPENING; COORDINATE SIZE AND LOCATION
WITH CONSTRUCTION PLAN
SAW-CUT AND REMOVE PORTION OF EXISTING CONCRETE SLAB
FOR NEW MECHANICAL PENETRATION; COORDINATE SIZE AND
LOCATION WITH MECHANICAL DRAWINGS
REMOVE EXISTING FLOOR FINISH INCLUDING BUT NOT LIMITED TO,
FLOOR TILE, THICKSET, AND COVE TILE WALL BASE. PATCH, LEVEL,
AND PREPARE SLAB TO RECEIVE NEW FINISH
REMOVE EXISTING PLUMBING FIXTURES; SEE PLUMBING
DRAWINGS
REMOVE AND DISCARD EXISTING TOILET PARTITIONS AND ALL
ASSOCIATED HARDWARE
REMOVE AND DISCARD EXISTING TOILET ROOM ACCESSORIES
INCLUDING BUT NOT LIMITED TO MIRRORS, TOILET PAPER
DISPENSARIES, SOAP DISPENSERS, PAPER TOWEL DISPENSERS,
AND SANITARY NAPKIN RECEPTACLES
REMOVE EXISTING WALL TILE, MORTAR, AND SUBSTRATE;
EXISTING STUDS TO REMAIN: TYPICAL FLOOR TO CEILING
EXISTING DOOR AND FRAME TO REMAIN; HARDWARE TO BE
REMOVED AND RETURNED TO OWNER. SEE DOOR SCHEDULE
REMOVE EXISTING WALL TILE AND MORTAR; EXISTING SUBSTRATE
AND WALL TO REMAIN, TYPICAL FLOOR TO CEILING. PREPARE
SUBSTRATE TO RECEIVE NEW FINISH
EXISTING FLOOR FINISH TO REMAIN
REMOVE EXISTING MILLWORK AND COUNTERTOP
REMOVE EXISTING BASE CABINETS. EXISTING COUNTERTOP TO
REMAIN. PROVIDE TEMPORARY SUPPORT AS REQUIRED
REMOVE EXISTING MAIL SLOTS
REMOVE EXISTING WALL FINISH BACK TO EXISTING TO REMAIN
BLOCK WALL. PREPARE BLOCK TO RECEIVE NEW FINISH.
18
21
20
TYPICAL
3
TYPICAL
TYPICAL
1
2
1
18
1
21
19
TYPICAL
19
16
2
1
26
23
23
24
24
24
22
24
24
22
29
29
29
29
29
1
18
1
18
3
TYPICAL
1
18
21
19
TYPICAL
20
TYPICAL
1
18
21
26
TYPICAL
14
14
23
14
24
24
24
24
24
12
12
12
AD104
SECOND FLOOR
DEMOLITION PLAN
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NOT FOR
CONSTRUCTION
A
A
10/30/2017 ADDENDUM 1
A
ALTERNATE NO. 3
ALL WORK ON SHEETS AD104, A104,
A204, AND SUBSEQUENT MECHANICAL,
ELECTRICAL, AND PLUMBING SHEETS
RELATED TO THESE AREAS SHALL BE
AN ALTERNATE
A
B 11/03/2017 ADDENDUM 3
B
B
B
B
CONSTRUCTION KEY NOTES BECKERMORGAN8 9 m SEE FINISH SCHEDULE ON A406 FOR ALL INTERIOR FINISHES
0 EXISTING STEEL COLUMN, TYPICAL■ A0 SHELVING BY OTHERS
FURNISH AND INSTALL NEW MOP SINK; REFER TO PLUMBING DRAWINGS
0ARCHITECTUREPLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
2A502 0SIM NEW MECHANICAL CHASE; REFER TO MECHANICAL DRAWINGS
R______^
FURNISH AND INSTALL NEW FLOOR MOUNTED, OVERHEAD BRACED, TOILET PARTITION
0
J t= _11 4❖ m EXISTING MECHANICAL CHASEj
1 008,
0 PATCH/REPAIR WALLS TO MATCH ADJACENT SURFACES
❖ 0 PATCH/REPAIR/LEVEL FLOOR TO RECEIVE NEW FINISH
FURNISH AND INSTALL NEW WALL MOUNTED URINAL SCREEN. PROVIDE BLOCKING AS REQUIRED
01A INFILL ABANDONED OPENING IN EXISTING WALL; MATCH EXISTING
ADJACENT CONSTRUCTION
NEW CART STORAGE 36" BASE CABINET (AWI SERIES 162 W/ LOCKING DOORS). VERIFY DIMENSIONS IN FIELD; MATCH EXISTING FINISH
08 CONFERENCEAWORK |1008|13|1020| 0
NOT FOR CONSTRUCTIONA 0 NEW MAIL SLOTS BY OWNER7/A403
v\'>c,T W ////12
:£? ^ •CONSTRUCTION LEGEND = :c5 10595 m- * •'ii%V?'''/if'''
"AAGTOn-A"Ullllll"'
4 :o"y/ * c N.C. ./o/r
EXISTING WALL TO REMAIN .........
NEWWALL CONSTRUCTION
2A FLOOR PLAN - FIRST FLOOR © Gtatec Ur9rDIAPER CHANGING STATION;SEE 1/A401 FOR MOUNTING HEIGHT
s-' /A/?m I ©DÛ «
CA ^A o
- 51922 s ■AA102 J SCALE: 1/4’ = 1’-0”
© MOP BRACKET;SEE 1/A401 FOR MOUNTING HEIGHT
% §&
f.h OCaro*© 'l©NGTO0COAT HOOK;
SEE 1/A401 FOR MOUNTING HEIGHT
2 3 PROJECT TITLE
11 11 T—
H <>-
6 6IP57 1 025,
b RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
1LO 6 A5 26
OFFICE0-e- |1025|
:'-5" 8'-8"
-e- Y ^Êliiw \8 H1/.f à ro
K1/A4030 \s MEN 5 I 10281
TYPICAL (2)9<
OJ
601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01A
/ *'^\ 3/A4032 œ
A502A SIM ,1 028r~r
© © AH1
01 10STORAGE
A r,1 030| 1014-1
A 4/A403 \1r1 A |Wo MEN4 SHEET TITLE
A < 1030\ 55 6 FIRST FLOOR PLAN/r b6/A403\
CMï-o-
as119h
K K67 \
00 7/A403b TYPICAL (3)y !CD
§ TLT /I nôüi A -
i
/A) j1 i A:1 019,r\6
-e-
-é-
3A FLOOR PLAN - FIRST FLOOR ÏA FLOOR PLAN - FIRST FLOORA102 J SCALE: 1/4” = T-0” A102 J SCALE: 1/4’ = T-0” ISSUE BLOCKA A
KEY PLANGENERAL NOTES1/A101
X ’X1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK. 7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233. 13. SEE GENERAL NOTES ON G001A 11/03/2017 ADDENDUM 3
2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION. 8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.
14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION A ADDENDUM 110/30/201713. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT
COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/FACILITIES.
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS MARK DATE DESCRIPTION
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE, FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN.
<
PROJECT NO: 2016280.003/A1024. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS. DATE: 08/19/2017
11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED PERSONS.
SCALE:5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC.□ n
DRAWN BY: NMY PROJ MGR: EWOi]B ÉHÊÊM 'niITr. □12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE APPROVED BY THE OWNER. A6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE. A102itZIrtr
1/A102 2/A102COPYRIGHT ^^2017
12
'-3
"8
'-2
"5
'-0
"
8'-8"2'-5"
1/A403
3/A403
6/A403
4/A403
2/A
40
35
/A
40
3
7
1
1
9
9
1
9
1'-1
"
1'-1
"
11 11
10
11
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK.
2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION.
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT
COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/
FACILITIES.
4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC.
6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE.
7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233.
8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE,
FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS.
11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED
PERSONS.
12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE
APPROVED BY THE OWNER.
13. SEE GENERAL NOTES ON G001
14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS
1
8
9
11
12
13
7/A403
1
9
1
9
7/A403
8/A
40
3
6'-9
"1
'-3
1
4"
CONSTRUCTION KEY NOTES
SEE FINISH SCHEDULE ON A406 FOR ALL INTERIOR FINISHES
EXISTING STEEL COLUMN, TYPICAL
SHELVING BY OTHERS
FURNISH AND INSTALL NEW MOP SINK; REFER TO PLUMBING
DRAWINGS
NEW MECHANICAL CHASE; REFER TO MECHANICAL DRAWINGS
FURNISH AND INSTALL NEW FLOOR MOUNTED, OVERHEAD
BRACED, TOILET PARTITION
EXISTING MECHANICAL CHASE
PATCH/REPAIR WALLS TO MATCH ADJACENT SURFACES
PATCH/REPAIR/LEVEL FLOOR TO RECEIVE NEW FINISH
FURNISH AND INSTALL NEW WALL MOUNTED URINAL SCREEN.
PROVIDE BLOCKING AS REQUIRED
INFILL ABANDONED OPENING IN EXISTING WALL; MATCH EXISTING
ADJACENT CONSTRUCTION
NEW CART STORAGE 36" BASE CABINET (AWI SERIES 162 W/
LOCKING DOORS). VERIFY DIMENSIONS IN FIELD; MATCH EXISTING
FINISH
NEW MAIL SLOTS BY OWNER
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
CONSTRUCTION LEGEND
DIAPER CHANGING STATION;
SEE 1/A401 FOR MOUNTING HEIGHT
MOP BRACKET;
SEE 1/A401 FOR MOUNTING HEIGHT
COAT HOOK;
SEE 1/A401 FOR MOUNTING HEIGHT
A102
FIRST FLOOR PLAN
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NOT FOR
CONSTRUCTION
A 10/30/2017 ADDENDUM 1
A
B 11/03/2017 ADDENDUM 3
B
B
B
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
DIAPER CHANGING STATION;SEE 1/A401 FOR MOUNTING HEIGHT
MOP BRACKET;SEE 1/A401 FOR MOUNTING HEIGHT
COAT HOOK;SEE 1/A401 FOR MOUNTING HEIGHT
BECKERMORGAN
A
ARCHITECTURE PLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
NOT FOR CONSTRUCTION
v\'>c,T W ////
= 10595 m: =- * :u> o: * =y i
\'s\. N. c.44©.........
X-© \2\ O
S-'
Uj I ®m I 51922CT>
.8- 7& *3h' fh Caro
'i^//vgto^;
PROJECT TITLE
RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01ASHEET TITLE
SECOND FLOOR PLAN
ISSUE BLOCK
CONSTRUCTION LEGEND
ALTERNATE NO. 3ALL WORK ON SHEETS AD104, A104, A204, AND SUBSEQUENT MECHANICAL, ELECTRICAL, AND PLUMBING SHEETS RELATED TO THESE AREAS SHALL BE AN ALTERNATE
A
A MA
0 SEE FINISH SCHEDULE ON A406 FOR ALL INTERIOR FINISHES
0 EXISTING STEEL COLUMN, TYPICAL
[7] SHELVING BY OTHERS
FURNISH AND INSTALL NEW MOP SINK; REFER TO PLUMBING DRAWINGS
[7] NEW MECHANICAL CHASE; REFER TO MECHANICAL DRAWINGS
FURNISH AND INSTALL NEW FLOOR MOUNTED, OVERHEAD BRACED, TOILET PARTITION
0
0
0 EXISTING MECHANICAL CHASE
0 PATCH/REPAIR WALLS TO MATCH ADJACENT SURFACES
0 PATCH/REPAIR/LEVEL FLOOR TO RECEIVE NEW FINISH
FURNISH AND INSTALL NEW WALL MOUNTED URINAL SCREEN. PROVIDE BLOCKING AS REQUIRED
0
INFILL ABANDONED OPENING IN EXISTING WALL; MATCH EXISTING ADJACENT CONSTRUCTION
NEW CART STORAGE 36" BASE CABINET (AWI SERIES 162 W/0 LOCKING DOORS). VERIFY DIMENSIONS IN FIELD; MATCH EXISTING
FINISH
0
0 NEW MAIL SLOTS BY OWNER
CONSTRUCTION KEY NOTES5
3 Y3A502 A502SIM SIM
I
■HR
❖❖ ■■4
A502
1A
OFFICE8
|2052|A5
A502
❖PtJ
2052
I
A
3
11
A1 A8A
1" STEPi
\Afg V
6
A A A A A A A A A A A A A A A A
4
3A502SIM
AA
1 AOFFICE
8 |20501AA 2050B
A A
- SECOND FLOOR
v STORAGE1" STEP| 2042E |
- SECOND FLOORA A A A A A A A A A A
A
❖n
L J
2A502SIM
2050A 4ft■d__________
8 2A floor planA104 J SCALE: 1/4’ - T-O’
-
J 22A502SIM
11 11
JA2014
A
411
1
AOFFICE8 |2014|
AA
3 3fsMA502 A502A SIM A
LGK 1
3AFLOOR PLAN - SECOND FLOOR KA104 J SCALE: 1/4’ = r-o’ A
r\ FLOOR PLANA104 J SCALE: 1/4” = T-0”
A A A A A A A A A A A
KEY PLANGENERAL NOTES2/A104 1/A103
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK. 7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233. 13. SEE GENERAL NOTES ON G001 A 11/03/2017 ADDENDUM 3■jBt14*-I2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION. 8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION A 10/30/2017 ADDENDUM 1
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/FACILITIES.
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS 7 MARK DATE DESCRIPTION9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE,
FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN. PROJECT NO: 2016280.00& !><l X4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS. DATE: 08/19/2017o
D11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED PERSONS.
SCALE:5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC. DRAWN BY: NMY PROJ MGR: EWO12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE APPROVED BY THE OWNER.
6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL. PROTECT SYSTEMS AND DEVICES FROM DAMAGE. A104“ïrrarrw 3d
ex
1/A104 3/A104 COPYRIGHT ^^2017
0 © ©
1
8
9
1" STEP
1" STEP
9
9
9
11
1. LIMIT CONSTRUCTION ACTIVITIES TO DESIGNATED AREAS OF WORK.
2. THE BUILDING/ FACILITY WILL REMAIN IN USE/ OCCUPIED DURING CONSTRUCTION.
3. PROVIDE THE OWNER A MINIMUM 48 HOUR NOTICE AND OBTAIN APPROVAL FOR ACTIVITIES THAT
COULD INTERRUPT OR IMPACT THE USE OR OPERATION OF THE EXISTING BUILDINGS/
FACILITIES.
4. THE CONTRACTOR, SUBCONTRACTORS AND THEIR EMPLOYEES SHALL ABIDE BY ALL BADGING,
SECURITY, AND CONDUCT REQUIREMENTS REQUIRED BY THE OWNER.
5. MAINTAIN CORRIDORS AND PATHS OF EGRESS AT ALL TIMES. DO NOT BLOCK EXITS, STAIRS,
RAMPS, ETC.
6. BUILDING FIRE ALARM AND OTHER LIFE SAFETY SYSTEMS SHALL REMAIN OPERATIONAL.
PROTECT SYSTEMS AND DEVICES FROM DAMAGE.
7. CONTRACTOR SHALL DOCUMENT EXISTING CONDITIONS - SEE SPECIFICATIONS SECTION 013233.
8. CONTRACTOR SHALL PROTECT ALL EXISTING STRUCTURES, FINISHES, PARTITIONS, BUILDING
SYSTEMS AND OTHER ELEMENTS THAT REMAIN FROM DAMAGE.
9. CONTRACTOR IS RESPONSIBLE FOR ANY AND ALL DAMAGE TO EXISTING BUILDING, STRUCTURE,
FINISHES, PARTITIONS, BUILDING SYSTEMS AND OTHER ELEMENTS TO REMAIN.
10. ALL WORK SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES & REGULATIONS.
11. ALL AREAS OF CONSTRUCTION SHALL BE SECURED SO AS TO LIMIT ACCESS BY UNAUTHORIZED
PERSONS.
12. ALL FACILITIES WHERE CONSTRUCTION OCCURS SHALL BE SECURED DAILY UPON THE
COMPLETION OF THE WORK DAY. SECUREMENT METHODS & EMERGENCY ACCESS SHALL BE
APPROVED BY THE OWNER.
13. SEE GENERAL NOTES ON G001
14. SEE PLUMBING, MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
15. SEE 4/A501 AND 5/A501 FOR PLUMBING ROOF PENETRATION DETAILS
1
8
9
1
8
9
1
8
9
11
1111
CONSTRUCTION KEY NOTES
SEE FINISH SCHEDULE ON A406 FOR ALL INTERIOR FINISHES
EXISTING STEEL COLUMN, TYPICAL
SHELVING BY OTHERS
FURNISH AND INSTALL NEW MOP SINK; REFER TO PLUMBING
DRAWINGS
NEW MECHANICAL CHASE; REFER TO MECHANICAL DRAWINGS
FURNISH AND INSTALL NEW FLOOR MOUNTED, OVERHEAD
BRACED, TOILET PARTITION
EXISTING MECHANICAL CHASE
PATCH/REPAIR WALLS TO MATCH ADJACENT SURFACES
PATCH/REPAIR/LEVEL FLOOR TO RECEIVE NEW FINISH
FURNISH AND INSTALL NEW WALL MOUNTED URINAL SCREEN.
PROVIDE BLOCKING AS REQUIRED
INFILL ABANDONED OPENING IN EXISTING WALL; MATCH EXISTING
ADJACENT CONSTRUCTION
NEW CART STORAGE 36" BASE CABINET (AWI SERIES 162 W/
LOCKING DOORS). VERIFY DIMENSIONS IN FIELD; MATCH EXISTING
FINISH
NEW MAIL SLOTS BY OWNER
EXISTING WALL TO REMAIN
NEW WALL CONSTRUCTION
CONSTRUCTION LEGEND
DIAPER CHANGING STATION;
SEE 1/A401 FOR MOUNTING HEIGHT
MOP BRACKET;
SEE 1/A401 FOR MOUNTING HEIGHT
COAT HOOK;
SEE 1/A401 FOR MOUNTING HEIGHT
A104
SECOND FLOOR PLAN
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NOT FOR
CONSTRUCTION
ALTERNATE NO. 3
ALL WORK ON SHEETS AD104, A104,
A204, AND SUBSEQUENT MECHANICAL,
ELECTRICAL, AND PLUMBING SHEETS
RELATED TO THESE AREAS SHALL BE
AN ALTERNATE
A
A 10/30/2017 ADDENDUM 1
B 11/03/2017 ADDENDUM 3
B
B
B
OPG. NO. MK NAMEOFFICE STORAGE TOILET OFFICE
1008101410191025102810301046104610461046104620142050205020522082208220822082
MENWOMEN
A MEN B TELECOMM C FAMILY RESTROOM D WOMEN 1 MECHANICAL
OFFICE A OFFICE B OFFICE
OFFICE A MENB HOUSEKEEPING C FAMILY RESTROOM D WOMEN
FINISH LEGEND FINISH SCHEDULEACT ACCOUSTIC CEILING TILE
CRT TILE CA RPET TILE BY OWNER project UNCW Randall Library Restroom Design PROJECT NO: 2016044.00
CT CERAMIC TILEFLOOR BASESPACE WALLS CEILING REMARKS
GWB GYPSUM WALL BOARDNO. NAME NORTH EAST SOUTH WEST MAT FIN HT
PT PAINTMAT FIN MAT FIN MAT FIN MAT FIN
RCB RUBBER COVE BASE BY OWNER1008 OFFICE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 10'-4"
VCT VINYL COMPOSITION TILE BY OWNER1014 STORAGE VCT RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 10'-4"
1019 TOILET VCT RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-0"EX EXISTING
1020 WORK EX EX GWB PT GWB PT GWB PT GWB PT EX N/A EXN/A NOTAPPLICABLE
1025 OFFICE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 10'-4"
1028 MEN CT CT GWB PT / CT GWB/CT PT/CT GWB/CT PT/CT GWB/CT PT/CT ACT N/A 9'-0"A1030 WOMEN CT CT GWB PT/CT GWB/CT PT/CT GWB/CT PT/CT GWB/CT PT/CT ACT N/A 9'-0"
1046 CORRIDOR CRT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-0"
1046A MEN'S CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
1046B TELECOMM VCT RCB EX EX EX EX GWB PT EX EX EX EX EX
1046C RESTROOM CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
1046D WOMENS CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
1046E MECHANICAL VCT RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-0"
2014 OFFICE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-8"
2042E STORAGE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-8"
2050 OFFICE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-8"
2052 OFFICE CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-8"
2082 CORRIDOR CFT TILE RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-0"
2082A MEN'S CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
2082B HOUSEKEEPING VCT RCB GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-0"
2082C RESTROOM CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
2082D WOMENS CT CT GWB/CT PT GWB/CT PT GWB/CT PT GWB/CT PT ACT N/A 9'-0"
LIBRARY CFT TILE RCB0 GWB PT GWB PT GWB PT GWB PT ACT N/A 9'-6" PERIMETER OF NEW CONSTRUCTION
PLEASE REFER TO SPECS FOR ALL FINISH INFORMATION
SHEET: 1 of 1
HARDWARE SCHEDULE DATE 08/15/2017 SHEET: 1 of 1DOOR SCHEDULEPROJECT: UNCW RANDALL LIBRARY - LIFE SAFETY, ADA & RESTROOM IMPROVEMENTS PROJECT NO: 2016280.00 DATE 08/22/2017
PROJECT UNCW RANDALL LIBRARY LIFE SAFETY, ADA & RESTROOM IMPROVEMENTS PROJECT NO: 2016280.00LOCKSETTYPE
2" 2"
SEE SCHEDULE SEE SCHEDULE
CM
-e-
5/8" GWBBATT INSUL. SEE PARTITION
TYPELU LU
3-5/8" MTLSTUDSCAULK
=) =)Q QLU LUI I
/ O oCO COCAULK T LU LULU LUC/) C/)
0
5%"
H1/J1 ■é- ■é-
® OTYPICAL HM FRAME INTERIOR WALL
3VDOOR DETAILS 2\ DOOR FRAME TYPES n DOOR TYPESA406/ SCALE: 3/4” = T-0” A406/ SCALE: 1/2” = T-0” A406/ SCALB 1/2” = T-0”
DOOR FRAME HARDWAREDOOR#
SIZE DETAILS
WIDTH HEIGHT MAT TYPE FIN MAT TYPE FIN JAMB HEAD REMARKSSET NO.
1008 EX EX EX EX EX EX EX EX 3X
1014 EX EX EX EX EX EX EX EX 3X
1019 EX EX EX EX EX EX EX EX 3X
1025 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT 4
1028 3'-0" 7'_0" WOOD 1 STAIN HM A PAINT 5 CARD READER
1030 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT 5 CARD READER
1046A 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 H1 1
1046B 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 H1 3
1046C 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 Hi 2
1046D 3'-0" 7'_0" WOOD 1 STAIN HM A PAINT J1 Hi 1
1046E (2) 3’-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 H1 3
2014 EX EX EX EX EX EX EX EX 4X
2050A EX EX EX EX EX EX EX EX 4X
2050B 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 Hi 4
2052 EX EX EX EX EX EX EX EX 2X
2082A 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 Hi 1
2082B 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 Hi 3
2082C 3'-0" 7'_0" WOOD 1 STAIN HM A PAINT J1 Hi 2
2082D 3'-0" 7'-0" WOOD 1 STAIN HM A PAINT J1 H1 1
BECKERMORGAN
A
ARCH ITECTURE PLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
NOT FOR CONSTRUCTION
\S10595 $*fNie. y
\A A
m k 51922 “
•s
r ;£o
a;Y/?°ml®
& <3\>h' ih *3Caro
^//VGTOW
PROJECT TITLE
UNCWUNIVERSITY OF
NORTH CAROLINA WILMINGTON
RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01A
SHEET TITLE
DOOR AND FINISH SCHEDULES
ISSUE BLOCK
A 11/3/2017 ADDENDUM 3MARK DATE DESCRIPTION
PROJECT NO: 2016280.00DATE: 08/19/2017SCALE:
PROJ MGR: EWODRAWN BY: NMY
A406COPYRIGHT ©2017
SET
NO
.U
U to
u Li
ui kn ^
u.
T- I C
O I C
M I T-
KEY
GR
OU
P
UL L
AB
EL
FLU
SH B
OLT
S
THR
ESH
OLD
/WTH
. STR
IP
XX X X X X XXX
XX XXS
ILEN
CE
RS
XX
X XX
XX X
KIC
K PL
ATE
XX X X X X XXX
X X XX
WA
LL S
TOP
PIV
OTS
XX
HIN
GE
CO
NTA
CT
XX X X X X XXX
X X XX
BB
HIN
GE
S
XX X X X X XXX
X X XX
CLO
SER
XX
XX
PU
SH
/PU
LL
EX
IT D
EVIC
E
PAD
DLE
XX
CA
RD
REA
DE
R
XX
ELE
C D
OO
R H
AR
D
XX X
XX
STO
RE
RO
OM
XX
PRIV
ACY
PA
SS
AG
E
XX
OFF
ICE
CYL
IND
ER
EN
TRY
SE
E S
CH
ED
ULE
SEE SCHEDULE
2" 2"
2"
SE
E S
CH
ED
UL
E
SEE SCHEDULE
2"
5
3
4"
BATT INSUL.
SEE PARTITION
TYPE
CAULK
5/8" GWB
3-5/8" MTL
STUDS
CAULK
TYPICAL HM FRAME
INTERIOR WALL
H1/J1
A406
DOOR AND FINISH
SCHEDULES
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NORTH CAROLINAUNIVERSITY OF
WILMINGTON
NOT FOR
CONSTRUCTION
B 11/3/2017 ADDENDUM 3
B
BECKERMORGANCLEAN AND PREPARE PENETRATION
SURFACEALSAN FLASHING - EXTEND A MINIMUM OF 1" BEYOND REINFORCING FABRIC
■MECHANICAL EQUIPMENT■SEALANT - TO BE SUPPLIED & INSTALLED BYMECHANICAL CONTRACTOR ■ A k
REINFORCING FABRIC - EXTEND A MINIMUM OF 4" BEYOND THE ROOF SURFACE
NEW CURBNON-REMOVABLE CURB COUNTERFLASHING
ARCHITECTURE PLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, PE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
REINFORCING FABRIC FINGERS - EXTEND A MINIMUM OF 2" BEYOND THE PENETRATION
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
SHEET METAL COUNTERFLASHING
■REINFORCING FABRIC - EXTEND A MINIMUM OF 8" BEYOND THE PENETRATION
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
■FLASHING CAP SHEET CAP SHEETREMOVE / EMBED SURFACING AS REQUIRED
ALSAN FLASHING - EXTEND A MINIMUM OF 1" BEYOND REINFORCING FABRIC
■INSTALL FASTENER PLATE AROUND PENETRATION SPACED A MAXIMUM OF 12" APART
POLYESTER REINFORCED FLASHING BASE PLY - EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND BASE OF CURB
CAP SHEET
POLYESTER REINFORCED FLASHING BASE PLY - EXTEND FLASHING BASE PLY A MINIMUM OF 3" BEYOND FASTENER PLATES
■EXTEND FLASHING CAP SHEET A MINIMUM OF 1" BEYOND FLASHING BASE PLY
■INSTALL FASTENER PLATE A MINIMUM OF 1" BEYOND BASE OF CURB AND SPACED A MAXIMUM OF 12" ALONG WALL
NOT FOR CONSTRUCTIONEXISTING ROOF CONSTRUCTION
EXISTING ROOF CONSTRUCTION
W!,o”5 ?y
NOTE:PROVIDE ADDITIONAL STEEL FRAMING AS REQUIRED TO BOX OUT AND SUPPORT NEW ROOF CURB
5© plumbing roof penetration detail 4©PLUMBING ROOF PENETRATION DETAILA501 / SCALE: r = T-O” A5017 SCALE: r = T-O”
^GANg^©
/
Lu lj> ■o \ Ast om - 51922 s
% §to,-COMPRESSION TFRACK -
ATTACH TO STRUCTURECOMPRESSION TFRACK - ATTACH TO STRUCTURE
COMPRESSION TFRACK - ATTACH TO STRUCTURE
COMPRESSION TFRACK - ATTACH TO STRUCTURE
COMPRESSION TRACK - ATTACH TO STRUCTURE
COMPRESSION TRACK - ATTACH TO STRUCTURE
COMPRESSION TRACK - ATTACH TO STRUCTURE \'th oCaroVARIES VARIES *'l©NGTO©,
NOTE:PROVIDE SEALANT AT ALL JOINTS AND PENETfRATIONS, TYPICAL
NOTE:PROVIDE SEALANT AT ALL JOINTS AND PENETFRATIONS, TYPICAL
NOTE:PROVIDE SEALANT AT ALL JOINTS AND PENETFRATIONS, TYPICAL
NOTE:PROVIDE SEALANT AT ALL JOINTS AND PENETfRATIONS, TYPICAL
NOTE:PROVIDE SEALANT AT ALL JOINTS AND PENETFRATIONS, TYPICAL
PROJECT TITLE
b b b b b-©----
Y-è- -è- 0
YYY Y Y Y UNCWCEILING AS SCHEDULED CEILING AS SCHEDULED CEILING AS SCHEDULED CEILING AS SCHEDULED CEILING AS SCHEDULED CEILING AS SCHEDULEDCEILING AS SCHEDULED
6" MTL STUDS @ 16" O.C.
3-5/8" MTL STUDS @ 16" O.C.
3-5/8" MTL STUDS @ 16" O.C.
3-5/8" MTL STUDS @ 16" O.C.
3-5/8" MTL STUDS @ 16" O.C.
2-1/2" MTL STUDS @ 16" O.C.
2-1/2" MTL STUDS @16" O.C. UNIVERSITY OF
NORTH CAROLINA WILMINGTON
N N N NN N N N
1 LAYER 5/8" GWB EACH SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8" GWB EACH SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8" GWB EACH SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8" GWB ONE SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8" GWB ONE SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8” GWB ONE SIDE (MOISTURE RESISTANT IN WET AREAS)
1 LAYER 5/8" GWB ONE SIDE (MOISTURE RESISTANT IN WET AREAS)
RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
EXISTING STRUCTURESOUND BATTS SOUND BATTS SOUND BATTS SOUND BATTS
FLOOR RUNNER FLOOR RUNNER FLOOR RUNNER FLOOR RUNNER FLOOR RUNNER FLOOR RUNNER FLOOR RUNNER
BASE AS SCHEDULED BASE AS SCHEDULED BASE AS SCHEDULED BASE AS SCHEDULED BASE AS SCHEDULED BASE AS SCHEDULED BASE AS SCHEDULED
601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01A
/ / L
EXISTING NEWTYPE 1NON-RATED
TYPE 2NON-RATED
TYPE 2ANON-RATED
TYPE 3NON-RATED
TYPE 3ANON-RATED
TYPE 5NON-RATEDTYPE 4
NON-RATED
A3©PARTITION TYPESA5017 SCALE: 1/2” = T-O”
SHEET TITLE
PARTITION TYPES/ PLAN DETAILS
© ©COMPRESSION TRACK - ATTACH TO STRUCTURE
COMPRESSION TRACK - ATTACH TO STRUCTURE FILL WALL CAVITY WITH SOUND
ATTENUATING BATT INSULATION TYPICAL
FILL WALL CAVITY WITH SOUND ATTENUATING BATT INSULATION TYPICALNOTE:
PROVIDE SEALANT AT ALL JOINTS AND PENETRATIONS, TYPICAL
I" MOISTURE RESISTANT GYPSUM WALL BOARD, TYPICAL TOILET ROOM SIDE
I" MOISTURE RESISTANT GYPSUM WALL BOARD, TYPICAL TOILET ROOM SIDE
6" METAL STUDS AT 16" O.C. MAX.CEILING AS SCHEDULED CEILING AS SCHEDULED 6" METAL STUDS AT 16" O.C. MAX.
NOTE:PROVIDE ACOUSTIC SEALANT AT ALL JOINTS AND PENETRATIONS, TYPICAL
NOTE:PROVIDE ACOUSTIC SEALANT AT ALL JOINTS AND PENETRATIONS, TYPICAL
6" MTL STUDS @ 16" O.C.
EXISTING STRUCTURE
ISSUE BLOCK
EXISTING STRUCTURE
© EXISTING STRUCTURE
©1 LAYER 5/8" GWB ONE SIDE (MOISTURE RESISTANT IN WET AREAS)
1 NEW LAYER 5/8" GWB ONE SIDE SECURED TO EXISTING STRUCTURE (MOISTURE RESISTANT IN WET AREAS)
2 METAL STUDS AT 16" O.C. MAX.2 METAL STUDS AT 16" O.C. MAX.
I" GYPSUM WALL BOARDSOUND BATTSI" GYPSUM WALL BOARD
5tfc--1 CORNER BEAD, TYPICAL AT
ALL OUTSIDE CORNERS1FLOOR RUNNER FLOOR RUNNER NOTE:
ALL NEW WALLS SLATED TO RECEIVE WALL TILE TO HAVE 5/8" CEMENT BOARD SUBSTRATE IN LIEU OF GWB; COORDINATE WITH FINISH SCHEDULE.
CORNER BEAD, TYPICAL AT ALL OUTSIDE CORNERS A 11/3/2017 ADDENDUM 3BASE AS SCHEDULED BASE AS SCHEDULED
MARK DATE DESCRIPTION
£PROJECT NO: 2016280.00
EXISTING NEWTYPE 5ANON-RATED
DATE: 08/19/20172© PLAN DETAIL 1© PLAN DETAILTYPE 6
NON-RATEDSCALE:
A501 y SCALE: 1-1/2” = T-O” SCALE: 1-1/2’ = T-O”A501 DRAWN BY: NMY PROJ MGR: EWO
A501ACOPYRIGHT ^^2017
3-5/8" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB EACH SIDE
(MOISTURE RESISTANT IN
WET AREAS)
6" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB EACH SIDE
(MOISTURE RESISTANT IN
WET AREAS)
COMPRESSION TRACK -
ATTACH TO STRUCTURE
3-5/8" MTL STUDS
@ 16" O.C.
VARIES
CEILING AS SCHEDULEDCEILING AS SCHEDULED
SOUND BATTSSOUND BATTS
FLOOR RUNNERFLOOR RUNNER
BASE AS SCHEDULEDBASE AS SCHEDULED
NON-RATEDNON-RATED
TYPE 1 TYPE 2 TYPE 3
NON-RATED
CEILING AS SCHEDULED
1 LAYER 5/8" GWB ONE
SIDE (MOISTURE
RESISTANT IN WET AREAS)
BASE AS SCHEDULED
FLOOR RUNNER
COMPRESSION TRACK -
ATTACH TO STRUCTURE
COMPRESSION TRACK -
ATTACH TO STRUCTURE
3-5/8" MTL STUDS
@ 16" O.C.
VARIES
TYPE 3A
NON-RATED
CEILING AS SCHEDULED
1 LAYER 5/8" GWB ONE
SIDE (MOISTURE
RESISTANT IN WET AREAS)
BASE AS SCHEDULED
FLOOR RUNNER
COMPRESSION TRACK -
ATTACH TO STRUCTURE
SOUND BATTS
2-1/2" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB ONE SIDE
(MOISTURE RESISTANT IN
WET AREAS)
CEILING AS SCHEDULED
FLOOR RUNNER
BASE AS SCHEDULED
NON-RATED
TYPE 4
COMPRESSION TRACK -
ATTACH TO STRUCTURE
2-1/2" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB ONE SIDE
(MOISTURE RESISTANT IN
WET AREAS)
CEILING AS SCHEDULED
SOUND BATTS
FLOOR RUNNER
BASE AS SCHEDULED
NON-RATED
TYPE 5
COMPRESSION TRACK -
ATTACH TO STRUCTURE
6"
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
3-5/8" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB EACH SIDE
(MOISTURE RESISTANT IN
WET AREAS)
CEILING AS SCHEDULED
FLOOR RUNNER
BASE AS SCHEDULED
NON-RATED
TYPE 2A
COMPRESSION TRACK -
ATTACH TO STRUCTURE
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
6"
6"
6"
6"
EXISTING STRUCTURE
NEWEXISTING
5
8
" MOISTURE RESISTANT
GYPSUM WALL BOARD, TYPICAL
TOILET ROOM SIDE
6" METAL STUDS AT 16" O.C. MAX.
FILL WALL CAVITY WITH SOUND
ATTENUATING BATT INSULATION,
TYPICAL
EXISTING STRUCTURE
5
8
" GYPSUM WALL BOARD
2
1
2
" METAL STUDS AT 16" O.C. MAX.
NOTE:
PROVIDE ACOUSTIC SEALANT AT ALL
JOINTS AND PENETRATIONS, TYPICAL
CORNER BEAD, TYPICAL AT
ALL OUTSIDE CORNERS
5
8
" GYPSUM WALL BOARD
2
1
2
" METAL STUDS AT 16" O.C. MAX.
CORNER BEAD, TYPICAL AT
ALL OUTSIDE CORNERS
5
8
" MOISTURE RESISTANT
GYPSUM WALL BOARD, TYPICAL
TOILET ROOM SIDE
6" METAL STUDS AT 16" O.C. MAX.
FILL WALL CAVITY WITH SOUND
ATTENUATING BATT INSULATION,
TYPICAL
EXISTING STRUCTURE
NOTE:
PROVIDE ACOUSTIC SEALANT AT ALL
JOINTS AND PENETRATIONS, TYPICAL
NON-RATED
TYPE 5A
6" MTL STUDS
@ 16" O.C.
1 LAYER 5/8" GWB ONE SIDE
(MOISTURE RESISTANT IN
WET AREAS)
COMPRESSION TRACK -
ATTACH TO STRUCTURE
CEILING AS SCHEDULED
SOUND BATTS
FLOOR RUNNER
BASE AS SCHEDULED
NOTE:
PROVIDE SEALANT AT ALL
JOINTS AND PENETRATIONS,
TYPICAL
EXISTING STRUCTURE
1 NEW LAYER 5/8" GWB ONE
SIDE SECURED TO EXISTING
STRUCTURE (MOISTURE
RESISTANT IN WET AREAS)
CEILING AS SCHEDULED
FLOOR RUNNER
BASE AS SCHEDULED
NON-RATED
TYPE 6
COMPRESSION TRACK -
ATTACH TO STRUCTURE
NEWEXISTING
NOTE:
ALL NEW WALLS SLATED TO RECEIVE
WALL TILE TO HAVE 5/8" CEMENT BOARD
SUBSTRATE IN LIEU OF GWB;
COORDINATE WITH FINISH SCHEDULE.
ALSAN FLASHING - EXTEND A MINIMUM OF1" BEYOND REINFORCING FABRIC
ALSAN FLASHING - EXTEND A MINIMUM OF 1"BEYOND REINFORCING FABRIC
CLEAN AND PREPARE PENETRATIONSURFACE
REINFORCING FABRIC - EXTEND A MINIMUMOF 4" BEYOND THE ROOF SURFACE
INSTALL FASTENER PLATE AROUNDPENETRATION SPACED A MAXIMUM OF 12"APART
EXISTING ROOF CONSTRUCTION
POLYESTER REINFORCED FLASHING BASEPLY - EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND FASTENER PLATES
REINFORCING FABRIC FINGERS - EXTEND AMINIMUM OF 2" BEYOND THE PENETRATION
CAP SHEET
REINFORCING FABRIC - EXTEND A MINIMUMOF 8" BEYOND THE PENETRATION
SHEET METAL COUNTERFLASHING
CAP SHEET
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
NON-REMOVABLE CURB COUNTERFLASHING
FLASHING CAP SHEET
FASTEN AT 8" O.C. ALONG TOP LEADING EDGE
EXTEND FLASHING CAP SHEET A MINIMUMOF 1" BEYOND FLASHING BASE PLY
INSTALL FASTENER PLATE A MINIMUM OF 1"BEYOND BASE OF CURB AND SPACED AMAXIMUM OF 12" ALONG WALL
EXISTING ROOF CONSTRUCTION
REMOVE / EMBED SURFACING AS REQUIRED
POLYESTER REINFORCED FLASHING BASEPLY - EXTEND FLASHING BASE PLY AMINIMUM OF 3" BEYOND BASE OF CURB
NEW CURB
MECHANICAL EQUIPMENTSEALANT - TO BE SUPPLIED & INSTALLED BYMECHANICAL CONTRACTOR
NOTE:PROVIDE ADDITIONAL STEEL FRAMING AS REQUIREDTO BOX OUT AND SUPPORT NEW ROOF CURB
A501
PARTITION TYPES/
PLAN DETAILS
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NORTH CAROLINAUNIVERSITY OF
WILMINGTON
NOT FOR
CONSTRUCTION
B 11/3/2017 ADDENDUM 3
B
B
BECKERMORGAN
A2 3" METAL STUDS AT 16" O.C. MAX
ARCHITECTURE PLANNING
Wilmington, NC3205 Randall Parkway, Suite 211
Wilmington, NC 28403 910.341.7600
Salisbury, MD312 West Main St. Suite 300
Salisbury, MD 21801 410.546.9100Dover, DE
309 S Governors Ave Dover, DE 19904
302.734.7950
www.beckermorgan.com
|" GYPSUM WALL BOARD
EXISTING CMU WALL
2 3" METAL STUDS AT 16" O.C. MAX
2 METAL STUDS AT 16" O.C. MAX.
|" GYPSUM WALL BOARD
GYPSUM WALL BOARD
[ EXISTING CMU WALLPROVIDE SEALANT AT JOINT
EXISTING WALL FINISHEXISTING WOOD WINDOW FRAME
PROVIDE SEALANT AT JOINT
PROVIDE SEALANT AT JOINT EXISTING WALL FINISHEXISTING HOLLOW METAL DOOR FRAME NOT FOR
CONSTRUCTIONEXISTING BLOCK WALL
W!,o”5 5y7VHEADER DETAIL 6VHEADER DETAIL 5YPLAN DETAILA5027 SCALE; 1-1/2’ = T-0’ A5027 SCALE: 1-1/2’ = T-0’ A5021 SCALE: 1-1/2’ = T-0’
“ II 51922 1 °
<T
LU I®
I §to,- Ah' th Caro
'i
PROJECT TITLE
EXISTING WINDOW
EXISTING WINDOW FRAME TJMCW7A50ZPROVIDE SEALANT AT JOINT
UNIVERSITY OF NORTH CAROLINA
WILMINGTONEXISTING CMU WALL
RANDALL LIBRARY LIFE SAFETY, ADA
& RESTROOM IMPROVEMENTS
EXISTING STUD WALL
vPROVIDE SEALANT AT JOINT
EXISTING CMU WALLEXISTING WALL FINISH
I" GYPSUM WALL BOARD
2 3" METAL STUDS AT 16" O.C. MAX. 601 S. College Rd. Wilmington, NC
28403
PM# - 5544 SCO# - 17-17589-01A
I" GYPSUM WALL BOARD
3Nplan detail4Vplan detailA502J SCALE: 1-1/2” = T-0’502 J SCALE: 1-1/2” = T-0*
SHEET TITLE
PLAN/HEADER DETAILS
EXISTING CMU WALLPROVIDE SEALANT AT JOINT
2 3" METAL STUDS AT 16" O.C. MAX.
I" GYPSUM WALL BOARD
I" GYPSUM WALL BOARD
6 2 J' METAL STUDS AT 16" O.C. MAX.A502,
It ISSUE BLOCK
J PROVIDE SEALANT AT JOINT
EXISTING CMU WALLEXISTING WALL FINISH
EXISTING WALL FINISH
EXISTING HOLLOW METAL DOOR FRAME
A 11/3/2017 ADDENDUM 3MARK DATE DESCRIPTION
PROJECT NO: 2016280.00
DATE: 08/19/2017
2NPLAN DETAIL A PLAN DETAIL SCALE:
A502/ SCALE: 1-1/2’ = 1’-0” A502/ SCALE: 1-1/2’ = 1’-0” DRAWN BY: NMY PROJ MGR: EWO
A502COPYRIGHT ^^2017
2
1
2
" METAL STUDS AT 16" O.C. MAX.
5
8
" GYPSUM WALL BOARD
EXISTING CMU WALL
EXISTING WALL FINISH
PROVIDE SEALANT AT JOINT
2
1
2
" METAL STUDS AT 16" O.C. MAX.
EXISTING WALL FINISH
5
8
" GYPSUM WALL BOARD
EXISTING CMU WALL
EXISTING HOLLOW METAL
DOOR FRAME
PROVIDE SEALANT AT JOINT
EXISTING CMU WALL
5
8
" GYPSUM WALL BOARD
2
1
2
" METAL STUDS AT 16" O.C. MAX.
EXISTING WINDOW
EXISTING WINDOW FRAME
PROVIDE SEALANT AT JOINT
EXISTING CMU WALL
EXISTING STUD WALL
EXISTING WALL FINISH
PROVIDE SEALANT AT JOINT
5
8
" GYPSUM WALL BOARD
2
1
2
" METAL STUDS AT 16" O.C. MAX.
EXISTING WALL FINISH
EXISTING BLOCK WALL
PROVIDE SEALANT AT JOINT
5
8
" GYPSUM WALL BOARD
EXISTING WALL FINISH
EXISTING CMU WALL
EXISTING HOLLOW METAL
DOOR FRAME
2
1
2
" METAL STUDS AT 16" O.C. MAX
5
8
" GYPSUM WALL BOARD
PROVIDE SEALANT AT JOINT
EXISTING CMU WALL
EXISTING WOOD WINDOW FRAME
2
1
2
" METAL STUDS AT 16" O.C. MAX
5
8
" GYPSUM WALL BOARD
PROVIDE SEALANT AT JOINT
A502
PLAN/HEADER DETAILS
PROJECT TITLE
SCALE:
DATE: 08/19/2017
DRAWN BY:
2016280.00PROJECT NO:
ISSUE BLOCK
MARK DATE DESCRIPTION
SHEET TITLE
EWOPROJ MGR:
RANDALL LIBRARY
LIFE SAFETY, ADA
& RESTROOM
IMPROVEMENTS
www.beckermorgan.com
E
ALP
RA C
NN
IH T U
NI
C T
G
ER
Salisbury, MD
410.546.9100
Salisbury, MD 21801
312 West Main St. Suite 300
Dover, DE
Dover, DE 19904
302.734.7950
309 S Governors Ave
910.341.7600
Wilmington, NC
3205 Randall Parkway, Suite 211
Wilmington, NC 28403
NMY
COPYRIGHT C 2017
601 S. College Rd.
Wilmington, NC
28403
W
I
L
M
I
N
G T
O
N
,
N
C
BE
C
K
E
R
M
O
R
G
AN
G
R
O
U
P
,
I
N
C
.
R
e
g
is
te
r
e
d
A
r
c
h
i
tec
u
r
a
l
C
o
r
p
o
ra
ti
o
n
N
o
r
t
h
Ca
ro
l
i
n
a
PM# - 5544SCO# - 17-17589-01A
NORTH CAROLINAUNIVERSITY OF
WILMINGTON
NOT FOR
CONSTRUCTION
B 11/3/2017 ADDENDUM 3