no. oc360 technical & service...
TRANSCRIPT
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
No. OC360
NOTE:• This manual does not
cover outdoor units.When servicing outdoorunits, please refer to theoutdoor unit`s servicemanual together with thismanual.
CONTENTS
1. REFERENCE MANUAL ······································22. PART NAMES AND FUNCTIONS ···················33. SPECIFICATIONS ············································64. DATA ······························································145. OUTLINES AND DIMENSIONS ·····················286. WIRING DIAGRAM ········································317. REFRIGERANT SYSTEM DIAGRAM ············328. TROUBLESHOOTING ···································349. FUNCTION SETTING·····································50
10. 4-WAY AIR FLOW SYSTEM ··························5711. SYSTEM CONTROL ······································6212. DISASSEMBLY PROCEDURE ······················7613. PARTS LIST ···················································7914. OPTIONAL PARTS ········································84
Indoor unit[Model names] [Service Ref.]
PLH-3AAK PLH-3AAKPLH-4AAK PLH-4AAKPLH-5AAK PLH-5AAKPLH-6AAK PLH-6AAKPLH-3AAKH PLH-3AAKHPLH-4AAKH PLH-4AAKHPLH-5AAKH PLH-5AAKHPLH-6AAKH PLH-6AAKH
February 2006
INDOOR UNIT
WIRED REMOTE CONTROLLER
WIRELESS REMOTECONTROLLER
ON/OFF TEMP
ON/OFF TEMP.
Model name indication
OC360--1.qxp 06.2.24 1:56 PM Page 1
2
1 REFERENCE MANUAL
Service Ref. Service Manual No.
PUH-3VKA2.TH-APUH-3YKA1.TH-APUH-4YKSA1.TH-APUH-5/6YKSA3.TH-APUH-3VKA.THPUH-3YKA.THPUH-4/5/6YKSA.THPUH-3NKA.THPUH-4/5/6TKSA.TH
OC156
OC354
OC325
1-1. OUTDOOR UNIT’S SERVICE MANUAL
OC360--1.qxp 06.2.24 1:56 PM Page 2
3
2 PART NAMES AND FUNCTIONS
● Operation buttons
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
Set Temperature buttons
Down
Up
Timer Menu button(Monitor/Set button)
Mode button (Return button)
Set Time buttons
Back
Ahead
Timer On/Off button(Set Day button)
Opening thedoor.
ON/OFF button
Fan Speed button
Filter button(<Enter> button)
Test Run button
Check button (Clear button)
Airflow Up/Down button
Louver button( Operation button)
To preceding operationnumber.
Ventilation button( Operation button)
To next operation number.
On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.
Auto Air Swing VaneDisperses airflow up anddown and adjusts the angleof airflow direction.
Grille
FilterRemoves dust and pollutantsfrom intake air
Horizontal Air OutletSets airflow of horizontal automaticallyduring cooling or dehumidifying.
Air IntakeIntakes air from room.
● Indoor Unit
● Wired remote controller
OC360--1.qxp 06.2.24 1:56 PM Page 3
4
● Display
For purposes of this explanation,all parts of the display are shownas lit. During actual operation, onlythe relevant items will be lit.
˚F˚C
˚F˚C
ERROR CODEAFTER
TIMERTIME SUN MON TUE WED THU FRI SAT
ON
OFF
Hr
AFTER
FILTERFUNCTION
ONLY1Hr.
WEEKLYSIMPLE
AUTO OFF
Identifies the current operationShows the operating mode, etc.* Multilanguage display is sup-
ported.
“Centrally Controlled” indicatorIndicates that operation of the re-mote controller has been prohib-ited by a master controller.
“Timer Is Off” indicatorIndicates that the timer is off.
Temperature SettingShows the target temperature.
Day-of-WeekShows the current day of the week.
Time/Timer DisplayShows the current time, unless the simple or Auto Offtimer is set.If the simple or Auto Off timer is set, shows the timeremaining.
“Sensor” indicationDisplayed when the remote controller sensor is used.
“Locked” indicatorIndicates that remote controller but-tons have been locked.
“Clean The Filter” indicatorComes on when it is time to clean thefilter.
Timer indicatorsThe indicator comes on if the corre-sponding timer is set.
Up/Down Air Direction indica-torThe indicator shows the direc-tion of the outcoming airflow.
“One Hour Only” indicatorDisplayed if the airflow is set toweak and downward during COOLor DRY mode. (Operation variesaccording to model.)The indicator goes off after onehour, at which time the airflow di-rection also changes.
Room Temperature displayShows the room temperature.
Louver displayIndicates the action of the swinglouver. Does not appear if thelouver is stationary.
(Power On indicator)Indicates that the power is on.
Fan Speed indicatorShows the selected fan speed.
Ventilation indicatorAppears when the unit is running inVentilation mode.
Caution● Only the Power on indicator lights when the unit is stopped and power supplied to the unit.● If you press a button for a feature that is not installed at the indoor unit, the remote controller will display the “Not Available”
message.If you are using the remote controller to drive multiple indoor units, this message will appear only if he feature is not present at the parent unit.
● When power is turned ON for the first time, it is normal that “PLEASE WAIT” is displayed on the room temperature indica-tion (For max. 2minutes). Please wait until this “PLEASE WAIT” indication disappear then start the operation.
OC360--1.qxp 06.2.24 1:56 PM Page 4
5
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
MODEL SELECT
NOT AVAILABLE
CHECK TEST RUNC̊
AMPM
AMPM
VANE CONTROL buttonUsed to change the air flow direction.
CLOCK button
RESET button
SET button
ON/OFF buttonThe unit is turned ON and OFF alternately each time the button is pressed.
LOUVER buttonThis switch the horizontal fan motion ON and OFF.
(Not available for this model.)
MODE SELECT buttonUsed to switch the operation mode between cooling, drying, blowing, heating and auto mode.
CHECK-TEST RUN buttonOnly press this button to perform an inspec-tion check or test operation.Do not use it for normal operation.
FAN SPEED SELECT buttonUsed to change the fan speed.
TIMER displayDisplays when in timer operation or when setting timer.
buttonSET TEMPERATURE button sets any desired room temperature.
CLOCK displayDisplays the current time.
“ ” “ ” displayDisplays the order of timer operation.
“ ” “ ” displayDisplays whether timer is on or off.
w In case the outdoor unit is cool only type, the heating mode is not available.
Buttons used to set the “hour and minute” of the current time and timer settings.
h and min buttons
displaySET TEMP. display indicates desired temper-ature set.
displayFAN SPEED display indicates which fan speed has been selected.
displayThe vertical direction of air flow is indicated.
displayBlinks when model is selected.
displayLights up while transmission to the indoor unit is mode using switches.
displayCHECK&TEST RUN display indicates that the unit is being checked or test-run.
displayOPERATION MODE displayOperation mode display indicates which op-eration mode is in effect.
TIMER CONTROL buttonsAUTO STOP (OFF timer): when this switch is set, the air conditioner will be au-tomatically stopped at the preset time.AUTO START (ON timer): when this switch is set, the air conditioner will be automatical-ly started at the preset time.
MODEL SELECT
CHECK TEST RUN
● Wireless remote controller
OC360--1.qxp 06.2.24 1:56 PM Page 5
6
SPECIFICATIONS3
PLH-3AAK(H)
Cooling 26,3007,7003.32
0.170.811.00
UNIT : 840(33-1/6)UNIT : 840(33-1/6)UNIT : 258(10-1/8)
UNIT : 24(53) [26(57)]
3.1513.82/5.16
58/37
Heating 28,700[35,800]8,400[10,500]
3.11[5.21]
0.17[2.27]0.81[9.47]1.00[9.7]
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
2.9412.89/4.81
58/37
PLH-3AAK(H)Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.07
15-20(530-705)0(direct blow)
[2.1]Remote controller & built-in
28-3432(1-1/4)
PUH-3VKA.TH, PUH-3VKA2.TH-A/PUH-3YKA.TH, PUH-3YKA1.TH-ASingle, 50Hz, 220-240V/3, 50Hz, 380-415V(4wires)
Munsell 5Y 7/1Capillary tube
HermeticNH52VNHT/NH52YDAT
2.2/2.4Line start
w1Plate fin coil
Propeller (direct) x10.085
50(1764)Reverse cycle
52870(34-1/4)
295+24 (11-5/8 add 1)850(33-1/4)
75(165)R-22
3.2(7.1)1.6<MS-32>
9.52 (3/8)15.88(5/8)
FlaredFlared
Max. 50mMax. 50m
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
w1 V …Internal Thermostat, HP switchY …Anti-phase protector, thermal relay, thermal switch, HP switch
Notes: Rating condition (ISO T1<JIS B8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°CHeating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 6
7
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-3AAK
Cooling w1/w2 23,200/27,3006,800/8,0004.29/3.68
0.160.771.00
UNIT : 840(33-1/6)UNIT : 840(33-1/6)UNIT : 258(10-1/8)
UNIT : 24(53)
4.13/3.5218.77/16.49
80
Heating w1 31,7009,3003.49
0.160.771.00
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
3.3315.680
PLH-3AAKSingle, 60Hz, 220V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.07
15-20(530-705)0(direct blow)
—Remote controller & built-in
28-3432(1-1/4)
PUH-3NKA.THSingle, 60Hz, 220V
Munsell 5Y 7/1Capillary tube
HermeticNHJ47NADT
2.2Line start
Internal thermostat, HP switchPlate fin coil
Propeller (direct) x10.085
50(1764)Reverse cycle
52870(34-1/4)
295+24 (11-5/8 add 1)850(33-1/4)
78(172)R-22
3.2(7.1)1.6<MS-32>
9.52 (3/8)15.88(5/8)
FlaredFlared
Max. 50mMax. 50m
Notes : w1.Rating condition (SSA 385)Cooling: Indoor : D.B. 29°C, W.B. 19°C
Outdoor: D.B. 46°C, W.B. 24°CHeating: Indoor : D.B. 21°C
Outdoor: D.B. 7°C, W.B. 6°C
w2.Rating condition (ISO T1<JIS 8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor: D.B. 35°C, W.B. 24°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 7
8
Cooling 33,1009,7003.46
0.261.252.0
UNIT : 840(33-1/6)UNIT : 840(33-1/6)UNIT : 298(11-3/4)
UNIT : 30(66)[32(71)]
3.205.2440
Heating 35,500[44,400]10,400[13,000]
3.45[6.05]
0.26[2.86]1.25[11.93]2.0[12.7]
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
3.195.2240
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-4AAK(H)
PLH-4AAK(H)Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
20-28(705-990)0(direct blow)
[2.6]Remote controller & built-in
33-4132(1-1/4)
PUH-4YKSA.TH, PUH-4YKSA1.TH-A3, 50Hz, 380V-415V(4wire)
Munsell 5Y 7/1Capillary tube
Hermetic NH56YDAT
2.7Line start
Anti-phase protector, Thermal relay, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.065+0.065
95(3550)Reverse cycle
54870(34-1/4)
295+24(11-5/8 add 1)1258(49-1/2)
94(207)R-22
4.2(9.2)1.6<MS-32>
9.52(3/8)19.05(3/4)
FlaredFlared
Max. 50mMax. 50m
Notes: Rating condition (ISO T1<JIS B8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°CHeating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 8
9
Cooling w1/w2 33,800/37,4009,900/10,950
5.26/4.93
0.251.192.0
UNIT : 840(33-1/6)UNIT : 840(33-1/6)UNIT : 298(11-3/4)
UNIT : 30(66)
5.01/4.1414.14/11.81
69
Heating w1 41,30012,1004.21
0.251.192.0
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
3.9611.369
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-4AAK
PLH-4AAKSingle, 60Hz, 220V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
20-28(705-990)0(direct blow)
—Remote controller & built-in
33-4132(1-1/4)
PUH-4TKSA.TH3, 60Hz, 220V
Munsell 5Y 7/1Capillary tube
HermeticNHJ56TKAT
2.7Line start
Anti-phase protector, Thermal relay, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.065+0.065
95(3550)Reverse cycle
55870(34-1/4)
295+24(11-5/8 add 1)1258(49-1/2)
94(207)R-22
4.7(10.4)1.6<MS-32>
9.52(3/8)19.05(3/4)
FlaredFlared
Max. 50mMax. 50m
Notes: w1.Rating condition (SSA 385)Cooling: Indoor : D.B. 29°C, W.B. 19°C
Outdoor: D.B. 46°C, W.B. 24°CHeating: Indoor : D.B. 21°C
Outdoor: D.B. 7°C, W.B. 6°C
w2.Rating condition (ISO T1<JIS 8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor: D.B. 35°C, W.B. 24°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 9
10
Cooling 42,30012,4004.51
0.301.432.0
UNIT : 840(33-1/16)UNIT : 840(33-1/16)UNIT : 298(11-3/4)
UNIT : 30(66) [32(71)]
4.216.8953
Heating 47,800[58,000]14,000[17,000]
4.46[7.46]
0.30[3.30]1.43[13.77]2.0[14.3]
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
4.166.8153
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-5AAK(H)
PLH-5AAK(H)Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
22-30(775-1,060)0(direct blow)
[3.0]Remote controller & built-in
35-4332(1-1/4)
PUH-5YKSA.TH, PUH-5YKSA3.TH-A3, 50Hz, 380-415V(4wire)
Munsell 5Y 7/1Capillary tube
HermeticZR61KC-TFD
3.5Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.085+0.085
95(3550)Reverse cycle
55970(38-3/16)
345+24(13-9/16 add 1)1258(49-1/2)
114(251)R-22
5.4(11.9)2.130<SONTEX-200LT>
9.52(3/8)19.05(3/4)
FlaredFlared
Max. 50mMax. 50m
Notes: Rating condition (ISO T1<JIS B8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°CHeating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 10
11
Cooling w1/w2 37,500/44,40011,000/13,000
6.78/5.58
0.261.242.0
UNIT : 840(33-1/16)UNIT : 840(33-1/16)UNIT : 298(11-3/4)
UNIT : 30(66)
6.52/5.3219.23/16.23
135
Heating w1 56,30016,5006.02
0.261.242.0
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL :5(11)
5.7617.38135
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-5AAK
PLH-5AAKSingle, 60Hz, 220V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
22-30(775-1,060)0(direct blow)
—Remote controller & built-in
35-4332(1-1/4)
PUH-5TKSA.TH3, 60Hz, 220V
Munsell 5Y 7/1Capillary tube
HermeticZR61KC-TF5
3.5Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.100+0.100100(3500)
Reverse cycle55
970(38-3/16)345+24(13-9/16 add 1)
1258(49-1/2)114(251)
R-225.4(11.9)
2.13<SONTEX-200LT>9.52(3/8)
19.05(3/4)FlaredFlared
Max. 50mMax. 50m
Notes: w1.Rating condition (SSA 385)Cooling: Indoor : D.B. 29°C, W.B. 19°C
Outdoor: D.B. 46°C, W.B. 24°CHeating: Indoor : D.B. 21°C
Outdoor: D.B. 7°C, W.B. 6°C
w2.Rating condition (ISO T1<JIS 8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor: D.B. 35°C, W.B. 24°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 11
12
PLH-6AAK(H)
Cooling 47,80014,0005.07
0.341.642.0
UNIT : 840(33-1/16)UNIT : 840(33-1/16)UNIT : 298(11-3/4)
UNIT : 32(71)[34(75)]
4.737.7474
Heating 54,900[65,200]16,100[19,100]
4.92[7.92]
0.34[3.34]1.64[13.94]2.0[14.3]
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL : 5(11)
4.587.5074
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-6AAK(H)Single, 50Hz, 220-240V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
22-30(775-1,060)0(direct blow)
[3.0]Remote controller & built-in
37-4532(1-1/4)
PUH-6YKSA.TH, PUH-6YKSA3.TH-A3, 50Hz, 380-415V(4wire)
Munsell 5Y 7/1Capillary tube
HermeticZR68KC-TFD
4.0Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.10+0.10100(3530)
Reverse cycle56
970(38-3/16)345+24(13-9/16 add 1)
1258(49-1/2)117(258)
R-225.0(11.0)
1.774<SONTEX-200LT>9.52(3/8)
19.05(3/4)FlaredFlared
Max. 50mMax. 50m
Notes: Rating condition (ISO T1<JIS B8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor : D.B. 35°C, W.B. 24°CHeating: Indoor : D.B. 20°C
Outdoor : D.B. 7°C, W.B. 6°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 12
13
PLH-6AAK
Cooling w1/w2 45,700/51,90013,400/15,200
7.32/6.15
0.281.342.0
UNIT : 840(33-1/16)UNIT : 840(33-1/16)UNIT : 298(11-3/4)
UNIT : 32(71)
7.04/5.8720.3/17.31
140
Heating w1 59,70017,500
6.7
0.281.342.0
PANEL : 950(37-3/8)PANEL : 950(37-3/8)PANEL : 30(1-3/16)
PANEL :5(11)
6.4218.51140
Service Ref.Power supply(phase, cycle,voltage)
External finishHeat exchangerFan
Booster heaterOperation control & ThermostatNoise level(Low-High)Unit drain pipe O.D.
Dimensions
WeightService Ref.Power supply (phase, cycle, voltage)
External finishRefrigerant controlCompressor
Heat exchangerFan
Defrost methodNoise level
Dimensions
WeightRefrigerant
Pipe size O.D.
Connection method
Between the indoor & outdoor units
InputRunning currentStarting current
Fan(drive) x No.Fan motor outputAirflow(Low-High)External static pressure
InputRunning currentStarting current
ModelMotor outputStarter typeProtection devices
Fan(drive) x No.Fan motor outputAirflow
ChargeOil<Model>
WDH
WDH
LiquidGas
Indoor sideOutdoor sideHeight differencePiping length
Function
Capacity
Total input
IND
OO
R U
NIT
OU
TD
OO
R U
NIT
RE
FR
IGE
RA
NT
PIP
ING
Item Service Ref.
Btu/hWkW
kWAA
kWK/ min (CFM)
PakW
dBmm(in.)mm(in.)mm(in.)mm(in.)kg(lbs)
kWAA
kW
kWK/ min (CFM)
dBmm(in.)mm(in.)mm(in.)kg(lbs)
kg(lbs)L
mm(in.)mm(in.)
PLH-6AAKSingle, 60Hz, 220V
Grille : Munsell 0.70Y 8.59/0.97Plate fin coil
Turbo fan (direct) x 10.120
22-30(775-1,060)0(direct blow)
—Remote controller & built-in
37-4532(1-1/4)
PUH-6TKSA.TH3, 60Hz, 220V
Munsell 5Y 7/1Capillary tube
HermeticZR68KC-TF5
4.0Line start
Internal thermostat, Anti-phase protector, Thermal switch, HP switchPlate fin coil
Propeller (direct) x20.10+0.10100(3530)
Reverse cycle56
970(38-3/16)345+24(13-9/16 add 1)
1258(49-1/2)117(258)
R-225.0(11.0)
1.774<SONTEX-200LT>9.52(3/8)
19.05(3/4)FlaredFlared
Max. 50mMax. 50m
Notes: w1.Rating condition (SSA 385)Cooling: Indoor : D.B. 29°C, W.B. 19°C
Outdoor: D.B. 46°C, W.B. 24°CHeating: Indoor : D.B. 21°C
Outdoor: D.B. 7°C, W.B. 6°C
w2.Rating condition (ISO T1<JIS 8616>)Cooling: Indoor : D.B. 27°C, W.B. 19°C
Outdoor: D.B. 35°C, W.B. 24°CRefrigerant piping length(one way):5m(16ft)
OC360--1.qxp 06.2.24 1:56 PM Page 13
14
4 DATA
1. PERFORMANCE DATA [50Hz]1) COOLING CAPACITY(1)
PLH-3AAK(H)
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
Outdoor intake air D.B.(°C)
20 25 30Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
7768
8271
7768
8271
8779
7768
8271
8779
9293
7768
8271
8779
9293
7768
8271
8779
9293
7768
8271
8779
9293
7768
8271
8779
9293
7768
8271
8779
9293
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
4972
4301
5593
4963
4214
6214
5624
4916
4089
6836
6286
5619
4832
7147
6617
5970
5204
7457
6948
6321
5576
7768
7609
7023
6319
7768
8271
7726
7063
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.64
0.52
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
2.66
2.71
2.66
2.71
2.77
2.66
2.71
2.77
2.82
2.66
2.71
2.77
2.82
2.66
2.71
2.77
2.82
2.66
2.71
2.77
2.82
2.66
2.71
2.77
2.82
2.66
2.71
2.77
2.82
7555
8053
7555
8053
8573
7555
8053
8573
9115
7555
8053
8573
9115
7555
8053
8573
9115
7555
8053
8573
9115
7555
8053
8573
9115
7555
8053
8573
9115
4835
4188
5440
4832
4115
6044
5476
4801
4011
6649
6120
5487
4740
6951
6443
5830
5104
7253
6765
6173
5469
7555
7409
6858
6198
7555
8053
7544
6927
2.77
2.83
2.77
2.83
2.89
2.77
2.83
2.89
2.94
2.77
2.83
2.89
2.94
2.77
2.83
2.89
2.94
2.77
2.83
2.89
2.94
2.77
2.83
2.89
2.94
2.77
2.83
2.89
2.94
7278
7760
7278
7760
8267
7278
7760
8267
8799
7278
7760
8267
8799
7278
7760
8267
8799
7278
7760
8267
8799
7278
7760
8267
8799
7278
7760
8267
8799
4658
4035
5240
4656
3968
5822
5277
4630
3872
6404
5898
5291
4576
6696
6208
5622
4928
6987
6518
5952
5279
7278
7139
6614
5983
7278
7760
7275
6687
2.99
3.06
2.99
3.06
3.12
2.99
3.06
3.12
3.19
2.99
3.06
3.12
3.19
2.99
3.06
3.12
3.19
2.99
3.06
3.12
3.19
2.99
3.06
3.12
3.19
2.99
3.06
3.12
3.19
OC360--1.qxp 06.2.24 1:56 PM Page 14
15
COOLING CAPACITY(2)PLH-3AAK(H)
Outdoor intake air D.B.(°C)
35 40 45Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
6983
7452
6983
7452
7948
6983
7452
7948
8470
6983
7452
7948
8470
6983
7452
7948
8470
6983
7452
7948
8470
6983
7452
7948
8470
6983
7452
7948
8470
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
4469
3875
5028
4471
3815
5586
5067
4451
3727
6145
5664
5087
4405
6424
5962
5405
4743
6704
6260
5722
5082
6983
6856
6358
5760
6983
7452
6994
6437
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.68
0.56
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
0.64
0.52
0.72
0.60
0.48
0.80
0.68
0.56
0.44
0.88
0.76
0.64
0.52
0.92
0.80
0.64
0.52
0.96
0.84
0.72
0.60
1.00
0.92
0.80
0.68
1.00
1.00
0.88
0.76
3.20
3.28
3.20
3.28
3.36
3.20
3.28
3.36
3.44
3.20
3.28
3.36
3.44
3.20
3.28
3.36
3.44
3.20
3.28
3.36
3.44
3.20
3.28
3.36
3.44
3.20
3.28
3.36
3.44
6671
7130
6671
7130
7616
6671
7130
7616
8128
6671
7130
7616
8128
6671
7130
7616
8128
6671
7130
7616
8128
6671
7130
7616
8128
6671
7130
7616
8128
4269
3708
4803
4278
3656
5337
4848
4265
3576
5870
5419
4874
4227
6137
5704
5179
4552
6404
5989
5483
4877
6671
6559
6093
5527
6671
7130
6702
6178
3.42
3.51
3.42
3.51
3.60
3.42
3.51
3.60
3.70
3.42
3.51
3.60
3.70
3.42
3.51
3.60
3.70
3.42
3.51
3.60
3.70
3.42
3.51
3.60
3.70
3.42
3.51
3.60
3.70
6342
6793
6342
6793
7270
6342
6793
7270
7773
6342
6793
7270
7773
6342
6793
7270
7773
6342
6793
7270
7773
6342
6793
7270
7773
6342
6793
7270
7773
4059
3532
4566
4076
3490
5073
4619
4071
3420
5581
5163
4653
4042
5834
5434
4944
4353
6088
5706
5235
4664
6342
6250
5816
5286
6342
6793
6398
5908
3.64
3.73
3.64
3.73
3.84
3.64
3.73
3.84
3.97
3.64
3.73
3.84
3.97
3.64
3.73
3.84
3.97
3.64
3.73
3.84
3.97
3.64
3.73
3.84
3.97
3.64
3.73
3.84
3.97
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 15
16
COOLING CAPACITY(3)PLH-4AAK(H)
Outdoor intake air D.B.(°C)
20 25 30Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
9786
10419
9786
10419
11060
9786
10419
11060
11707
9786
10419
11060
11707
9786
10419
11060
11707
9786
10419
11060
11707
9786
10419
11060
11707
9786
10419
11060
11707
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
6752
5939
7535
6773
5862
8318
7606
6746
5736
9101
8440
7631
6673
9492
8856
8073
7141
9786
9273
8516
7609
9786
10107
9401
8546
9786
10419
10285
9483
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
2.77
2.83
2.77
2.83
2.88
2.77
2.83
2.88
2.94
2.77
2.83
2.88
2.94
2.77
2.83
2.88
2.94
2.77
2.83
2.88
2.94
2.77
2.83
2.88
2.94
2.77
2.83
2.88
2.94
9518
10145
9518
10145
10800
9518
10145
10800
11482
9518
10145
10800
11482
9518
10145
10800
11482
9518
10145
10800
11482
9518
10145
10800
11482
9518
10145
10800
11482
6567
5783
7329
6594
5724
8090
7406
6588
5626
8852
8217
7452
6545
9232
8623
7884
7004
9518
9029
8316
7464
9518
9841
9180
8382
9518
10145
10044
9301
2.89
2.95
2.89
2.95
3.01
2.89
2.95
3.01
3.07
2.89
2.95
3.01
3.07
2.89
2.95
3.01
3.07
2.89
2.95
3.01
3.07
2.89
2.95
3.01
3.07
2.89
2.95
3.01
3.07
9168
9775
9168
9775
10414
9168
9775
10414
11085
9168
9775
10414
11085
9168
9775
10414
11085
9168
9775
10414
11085
9168
9775
10414
11085
9168
9775
10414
11085
6326
5572
7059
6354
5520
7793
7136
6353
5431
8526
7918
7186
6318
8893
8309
7602
6762
9168
8700
8019
7205
.9168
9482
8852
8092
9168
9775
9685
8979
3.11
3.18
3.11
3.18
3.25
3.11
3.18
3.25
3.32
3.11
3.18
3.25
3.32
3.11
3.18
3.25
3.32
3.11
3.18
3.25
3.32
3.11
3.18
3.25
3.32
3.11
3.18
3.25
3.32
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 16
17
COOLING CAPACITY(4)PLH-4AAK(H)
Outdoor intake air D.B.(°C)
35 40 45Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
6070
5351
6773
6102
5307
7477
6853
6107
5228
8181
7604
6908
6082
8533
7980
7309
6509
8797
8355
7709
6936
8797
9106
8510
7789
8797
9388
9311
8643
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
0.69
0.57
0.77
0.65
0.53
0.85
0.73
0.61
0.49
0.93
0.81
0.69
0.57
0.97
0.85
0.73
0.61
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
1.00
1.00
0.93
0.81
3.34
3.42
3.34
3.42
3.50
3.34
3.42
3.50
3.59
3.34
3.42
3.50
3.59
3.34
3.42
3.50
3.59
3.34
3.42
3.50
3.59
3.34
3.42
3.50
3.59
3.34
3.42
3.50
3.59
8404
8982
8404
8982
9594
8404
8982
9594
10240
8404
8982
9594
10240
8404
8982
9594
10240
8404
8982
9594
10240
8404
8982
9594
10240
8404
8982
9594
10240
8797
9388
8797
9388
10012
8797
9388
10012
10670
8797
9388
10012
10670
8797
9388
10012
10670
8797
9388
10012
10670
8797
9388
10012
10670
8797
9388
10012
10670
5798
5120
6471
5838
5085
7143
6557
5852
5017
7815
7275
6620
5837
8151
7634
7003
6246
8404
7994
7387
6656
8404
8712
8155
7475
8404
8982
8922
8294
3.56
3.65
3.56
3.65
3.75
3.56
3.65
3.75
3.86
3.56
3.65
3.75
3.86
3.56
3.65
3.75
3.86
3.56
3.65
3.75
3.86
3.56
3.65
3.75
3.86
3.56
3.65
3.75
3.86
7989
8558
7989
8558
9159
7989
8558
9159
9792
7989
8558
9159
9792
7989
8558
9159
9792
7989
8558
9159
9792
7989
8558
9159
9792
7989
8558
9159
9792
5512
4878
6151
5562
4854
6790
6247
5587
4798
7430
6932
6320
5582
7749
7274
6686
5973
7989
7616
7052
6365
7989
8301
7785
7148
7989
8558
8518
7932
3.79
3.89
3.79
3.89
4.00
3.79
3.89
4.00
4.14
3.79
3.89
4.00
4.14
3.79
3.89
4.00
4.14
3.79
3.89
4.00
4.14
3.79
3.89
4.00
4.14
3.79
3.89
4.00
4.14
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 17
18
COOLING CAPACITY(5)PLH-5AAK(H)
Outdoor intake air D.B.(°C)
20 25 30Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
12510
13319
12510
13319
14138
12510
13319
14138
14965
12510
13319
14138
14965
12510
13319
14138
14965
12510
13319
14138
14965
12510
13319
14138
14965
12510
13319
14138
14965
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7881
6793
8882
7858
6645
9883
8924
7776
6435
10883
9990
8907
7632
11384
10522
9472
8231
11884
11055
10038
8830
12510
12121
11169
10027
12510
13186
12300
11224
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
3.61
3.69
3.61
3.69
3.76
3.61
3.69
3.76
3.83
3.61
3.69
3.76
3.83
3.61
3.69
3.76
3.83
3.61
3.69
3.76
3.83
3.61
3.69
3.76
3.83
3.61
3.69
3.76
3.83
12167
12969
12167
12969
13806
12167
12969
13806
14679
12167
12969
13806
14679
12167
12969
13806
14679
12167
12969
13806
14679
12167
12969
13806
14679
12167
12969
13806
14679
7665
6614
8639
7652
6489
9612
8689
7593
6312
10585
9727
8698
7486
11072
10245
9250
8073
11559
10764
9802
8660
12167
11802
10907
9835
12167
12839
12011
11009
3.77
3.85
3.77
3.85
3.92
3.77
3.85
3.92
4.00
3.77
3.85
3.92
4.00
3.77
3.85
3.92
4.00
3.77
3.85
3.92
4.00
3.77
3.85
3.92
4.00
3.77
3.85
3.92
4.00
11720
12496
11720
12496
13313
11720
12496
13313
14170
11720
12496
13313
14170
11720
12496
13313
14170
11720
12496
13313
14170
11720
12496
13313
14170
11720
12496
13313
14170
7384
6373
8321
7373
6257
9259
8373
7322
6093
10196
9372
8387
7227
10665
9872
8920
7794
11134
10372
9452
8360
11720
11372
10517
9494
11720
12371
11582
10628
4.06
4.15
4.06
4.15
4.24
4.06
4.15
4.24
4.33
4.06
4.15
4.24
4.33
4.06
4.15
4.24
4.33
4.06
4.15
4.24
4.33
4.06
4.15
4.24
4.33
4.06
4.15
4.24
4.33
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 18
19
COOLING CAPACITY(6)PLH-5AAK(H)
Outdoor intake air D.B.(°C)
35 40 45Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
11245
12001
11245
12001
12799
11245
12001
12799
13640
11245
12001
12799
13640
11245
12001
12799
13640
11245
12001
12799
13640
11245
12001
12799
13640
11245
12001
12799
13640
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7085
6120
7984
7080
6016
8884
8041
7040
5865
9783
9001
8064
6957
10233
9481
8575
7502
10683
9961
9087
8048
11245
10921
10111
9139
11245
11881
11135
10230
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
0.63
0.51
0.71
0.59
0.47
0.79
0.67
0.55
0.43
0.87
0.75
0.63
0.51
0.91
0.79
0.67
0.55
0.95
0.83
0.71
0.59
1.00
0.91
0.79
0.67
1.00
0.99
0.87
0.75
4.35
4.46
4.35
4.46
4.56
4.35
4.46
4.56
4.67
4.35
4.46
4.56
4.67
4.35
4.46
4.56
4.67
4.35
4.46
4.56
4.67
4.35
4.46
4.56
4.67
4.35
4.46
4.56
4.67
10743
11482
10743
11482
12264
10743
11482
12264
13090
10743
11482
12264
13090
10743
11482
12264
13090
10743
11482
12264
13090
10743
11482
12264
13090
10743
11482
12264
13090
6768
5856
7627
6774
5764
8487
7693
6745
5629
9346
8611
7726
6676
9776
9071
8217
7199
10206
9530
8708
7723
10743
10448
9689
8770
10743
11367
10670
9817
4.64
4.76
4.64
4.76
4.89
4.64
4.76
4.89
5.03
4.64
4.76
4.89
5.03
4.64
4.76
4.89
5.03
4.64
4.76
4.89
5.03
4.64
4.76
4.89
5.03
4.64
4.76
4.89
5.03
10212
10939
10212
10939
11708
10212
10939
11708
12518
10212
10939
11708
12518
10212
10939
11708
12518
10212
10939
11708
12518
10212
10939
11708
12518
10212
10939
11708
12518
6434
5579
7251
6454
5503
8068
7329
6439
5383
8885
8205
7376
6384
9293
8642
7844
6885
9702
9080
8313
7386
10212
9955
9249
8387
10212
10830
10186
9389
4.94
5.07
4.94
5.07
5.22
4.94
5.07
5.22
5.39
4.94
5.07
5.22
5.39
4.94
5.07
5.22
5.39
4.94
5.07
5.22
5.39
4.94
5.07
5.22
5.39
4.94
5.07
5.22
5.39
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 19
20
COOLING CAPACITY(7)PLH-6AAK(H)
Outdoor intake air D.B.(°C)
20 25 30Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
14124
15038
14124
15038
15962
14124
15038
15962
16896
14124
15038
15962
16896
14124
15038
15962
16896
14124
15038
15962
16896
14124
15038
15962
16896
14124
15038
15962
16896
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
8616
7369
9745
8572
7183
10875
9775
8460
6928
12005
10978
9737
8279
12570
11579
10375
8955
13135
12181
11014
9631
14124
13384
12291
10983
14124
14587
13568
12334
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
4.06
4.15
4.06
4.15
4.22
4.06
4.15
4.22
4.30
4.06
4.15
4.22
4.30
4.06
4.15
4.22
4.30
4.06
4.15
4.22
4.30
4.06
4.15
4.22
4.30
4.06
4.15
4.22
4.30
13737
14642
13737
14642
15587
13737
14642
15587
16573
13737
14642
15587
16573
13737
14642
15587
16573
13737
14642
15587
16573
13737
14642
15587
16573
13737
14642
15587
16573
8380
7175
9479
8346
7014
10578
9517
8261
6795
11677
10689
9508
8121
12226
11274
10132
8783
12776
11860
10755
9446
13737
13031
12002
10772
13737
14203
13249
12098
4.24
4.32
4.24
4.32
4.41
4.24
4.32
4.41
4.50
4.24
4.32
4.41
4.50
4.24
4.32
4.41
4.50
4.24
4.32
4.41
4.50
4.24
4.32
4.41
4.50
4.24
4.32
4.41
4.50
13232
14109
13232
14109
15031
13232
14109
15031
15998
13232
14109
15031
15998
13232
14109
15031
15998
13232
14109
15031
15998
13232
14109
15031
15998
13232
14109
15031
15998
8072
6913
9130
8042
6764
10189
9171
7966
6559
11247
10299
9169
7839
11777
10864
9770
8479
12306
11428
10371
9119
13232
12557
11574
10399
13232
13686
12776
11679
4.56
4.67
4.56
4.67
4.77
4.56
4.67
4.77
4.87
4.56
4.67
4.77
4.87
4.56
4.67
4.77
4.87
4.56
4.67
4.77
4.87
4.56
4.67
4.77
4.87
4.56
4.67
4.77
4.87
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 20
21
COOLING CAPACITY(8)PLH-6AAK(H)
Outdoor intake air D.B.(°C)
35 40 45Indoor
Intake airD.B.(°C)
IndoorIntake airW.B.(°C)
20
20
22
22
22
24
24
24
24
26
26
26
26
27
27
27
27
28
28
28
28
30
30
30
30
32
32
32
32
16
18
16
18
20
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
12696
13549
12696
13549
14451
12696
13549
14451
15401
12696
13549
14451
15401
12696
13549
14451
15401
12696
13549
14451
15401
12696
13549
14451
15401
12696
13549
14451
15401
CA SHC SHF P.C. CA SHC SHF P.C. CA SHC SHF P.C.
7745
6639
8760
7723
6503
9776
8807
7659
6314
10792
9891
8815
7546
11300
10433
9393
8162
11808
10975
9971
8778
12696
12059
11127
10010
12696
13143
12283
11242
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
0.61
0.49
0.69
0.57
0.45
0.77
0.65
0.53
0.41
0.85
0.73
0.61
0.49
0.89
0.77
0.65
0.53
0.93
0.81
0.69
0.57
1.00
0.89
0.77
0.65
1.00
0.97
0.85
0.73
4.89
5.01
4.89
5.01
5.13
4.89
5.01
5.13
5.25
4.89
5.01
5.13
5.25
4.89
5.01
5.13
5.25
4.89
5.01
5.13
5.25
4.89
5.01
5.13
5.25
4.89
5.01
5.13
5.25
12129
12963
12129
12963
13847
12129
12963
13847
14779
12129
12963
13847
14779
12129
12963
13847
14779
12129
12963
13847
14779
12129
12963
13847
14779
12129
12963
13847
14779
7399
6352
8369
7389
6231
9339
8426
7339
6059
10310
9463
8446
7242
10795
9982
9000
7833
11280
10500
9554
8424
12129
11537
10662
9606
12129
12574
11770
10789
5.22
5.35
5.22
5.35
5.50
5.22
5.35
5.50
5.65
5.22
5.35
5.50
5.65
5.22
5.35
5.50
5.65
5.22
5.35
5.50
5.65
5.22
5.35
5.50
5.65
5.22
5.35
5.50
5.65
11530
12351
11530
12351
13219
11530
12351
13219
14133
11530
12351
13219
14133
11530
12351
13219
14133
11530
12351
13219
14133
11530
12351
13219
14133
11530
12351
13219
14133
7033
6052
7956
7040
5948
8878
8028
7006
5795
9801
9016
8063
6925
10262
9510
8592
7491
10723
10004
9121
8056
11530
10992
10178
9187
11530
11981
11236
10317
5.55
5.70
5.55
5.70
5.87
5.55
5.70
5.87
6.06
5.55
5.70
5.87
6.06
5.55
5.70
5.87
6.06
5.55
5.70
5.87
6.06
5.55
5.70
5.87
6.06
5.55
5.70
5.87
6.06
CA : Capacity (W) SHC : Sensible heat capacity (W)P.C. : Power consumption (kW) SHF : Sensible heat factor
OC360--1.qxp 06.2.24 1:56 PM Page 21
22
Cooling capacity correction factorsRefrigerant piping length(one way)
5m1.001.001.001.00
10m0.9810.9890.9810.975
15m0.9680.9800.9680.955
20m0.9520.9700.9520.935
25m0.9400.9600.9400.918
30m0.9250.9500.9250.900
35m0.9130.9400.9130.884
40m0.9000.9300.9000.869
45m0.8860.9200.8860.855
50m0.8740.9100.8740.840
Service Ref.
PLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)
2) HEATING CAPACITY
Note C A :Capacity (W)P.C.:Power consumption (kW)
P.C.3.383.643.903.754.044.333.754.044.335.355.766.18
CA107521034010044133121280212435133121280212435206081981819250
P.C.3.103.343.583.443.703.973.443.703.974.905.285.66
CA959592358928
118801143411054118801143411054183911770017112
P.C.2.833.053.273.143.393.633.143.393.634.484.835.17
CA8516819878951054310150977410543101509774163221571315131
P.C.2.582.782.972.863.093.302.863.093.304.094.404.71
CA751472316944930389538597930389538597
144021385913309
P.C.2.342.532.692.602.802.992.602.802.993.714.004.26
CA659363346077816378427524
109881055710128126361214011647
P.C.2.122.292.432.352.542.692.352.542.693.363.623.84
CA575255085293712268206554958791808822
110261055710146
-10Outdoor intake air W.B.(°C)
-5 0 5 10 15Indoor
intake air D.B.(°C)
152025152025152025152025
Service Ref.
PLH-3AAK(H)
PLH-4AAK(H)
PLH-5AAK(H)
PLH-6AAK(H)
Refrigerant piping length(one way)5m
1.001.001.001.00
10m1.001.001.001.00
15m1.001.001.001.00
20m1.001.001.001.00
25m1.001.001.001.00
30m1.001.001.001.00
35m0.9980.9980.9980.998
40m0.9950.9950.9950.995
45m0.9930.9930.9930.993
50m0.9900.9900.9900.990
Service Ref.
PLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)
Heating capacity correction factors
Heating1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4-12-10 -5 0 5 10 15
OUTDOOR WB(°C)
INDOOR DB (°C)
INDOOR DB (°C)
152025
252015
TO
TA
L IN
PU
T (
RA
TIO
)C
AP
AC
ITY
(R
AT
IO)
Cooling1.4
1.2
1.0
0.8
0.6
1.4
1.2
1.0
0.8
0.6
0.4-5 5 15 25 35 46
OUTDOOR DB(°C)
TO
TA
L IN
PU
T (
RA
TIO
)C
AP
AC
ITY
(R
AT
IO) INDOOR WB(°C)
INDOOR WB(°C)
22201816
22201816
2. PERFORMANCE CURVEPLH-3AAK(H) / PLH-4AAK(H) / PLH-5AAK(H) / PLH-6AAK(H)
OC360--1.qxp 06.2.24 1:56 PM Page 22
23
P.C.
4.03
4.14
4.26
4.40
4.81
4.93
5.08
5.25
6.11
6.27
6.46
6.67
6.73
6.91
7.12
7.35
CA
6589
7058
7554
8076
9018
9660
10339
11054
10707
11469
12275
13124
12518
13410
14352
15345
P.C.
3.79
3.89
3.99
4.10
4.52
4.64
4.76
4.89
5.74
5.89
6.05
6.22
6.33
6.49
6.67
6.86
CA
6931
7408
7912
8445
9486
10139
10830
11559
11263
12037
12858
13723
13168
14074
15034
16046
P.C.
3.55
3.64
3.72
3.81
4.23
4.34
4.44
4.55
5.38
5.51
5.65
5.78
5.93
6.08
6.22
6.37
CA
7255
7742
8258
8800
9930
10597
11303
12045
11789
12581
13419
14301
13785
14711
15689
16721
P.C.
3.31
3.39
3.46
3.53
3.95
4.04
4.13
4.22
5.02
5.14
5.25
5.36
5.53
5.66
5.78
5.91
CA
7561
8062
8589
9142
10350
11035
11756
12513
12287
13101
13957
14856
14367
15318
16319
17370
P.C.
3.08
3.14
3.20
3.26
3.67
3.74
3.82
3.89
4.66
4.76
4.85
4.95
5.14
5.24
5.35
5.45
CA
7850
8367
8907
9470
10744
11452
12191
12962
12756
13596
14474
15389
14915
15897
16923
17993
P.C.
2.95
3.01
3.07
3.12
3.52
3.59
3.66
3.73
4.47
4.56
6.65
4.74
4.93
5.03
5.12
5.22
CA
8071
8593
9121
9655
11047
11762
12485
13215
13115
13964
14822
15690
15334
16327
17330
18345
20
Outdoor intake air D.B.(°C)
25 30 35 40 45
Indoor
intake air
W.B.(°C)
16
18
20
22
16
18
20
22
16
18
20
22
16
18
20
22
Service Ref.
PLH-3AAK
PLH-4AAK
PLH-5AAK
PLH-6AAK
3. PERFORMANCE DATA [60Hz]1) COOLING CAPACITY(1)
PLH-3AAK / PLH-4AAK / PLH-5AAK / PLH-6AAK
Cooling capacity correction factorsRefrigerant piping length(one way)
5m1.001.001.001.00
10m0.9810.9890.9810.975
15m0.9680.9800.9680.955
20m0.9520.9700.9520.935
25m0.9400.9600.9400.918
30m0.9250.9500.9250.900
35m0.9130.9400.9130.884
40m0.9000.9300.9000.869
45m0.8860.9200.8860.855
50m0.8740.9100.8740.840
Service Ref.
PLH-3AAK PLH-4AAK PLH-5AAK PLH-6AAK
Note C A :Capacity (W)P.C.:Power consumption (kW)
2) HEATING CAPACITY
Note C A :Capacity (W)P.C.:Power consumption (kW)
P.C.3.794.084.384.584.935.286.547.047.567.287.848.41
CA119041144811120154881489414468211202031019728224012154120924
P.C.3.483.754.024.204.524.856.006.466.936.687.197.71
CA10623102249885
138221330212861188481814017537199901923918600
P.C.3.183.433.673.844.134.435.495.916.336.116.587.05
CA942890778741122671180911372167271610415507177411708016447
P.C.2.903.123.343.503.774.035.005.395.765.566.006.41
CA831980067688
108241041610003147601420413640156551506514467
P.C.2.632.843.023.173.423.654.544.895.215.055.445.80
CA729970136728949791248753129501244211936137351319612660
P.C.2.382.572.722.873.093.294.114.434.704.574.935.23
CA636960985861828679347625
112991082010398119841147511028
-10Outdoor intake air W.B.(°C)
-5 0 5 10 15Indoor
intake air D.B.(°C)
152025152025152025152025
Service Ref.
PLH-3AAK
PLH-4AAK
PLH-5AAK
PLH-6AAK
Refrigerant piping length(one way)5m
1.001.001.001.00
10m1.001.001.001.00
15m1.001.001.001.00
20m1.001.001.001.00
25m1.001.001.001.00
30m1.001.001.001.00
35m0.9980.9980.9980.998
40m0.9950.9950.9950.995
45m0.9930.9930.9930.993
50m0.9900.9900.9900.990
Service Ref.
PLH-3AAK PLH-4AAK PLH-5AAK PLH-6AAK
Heating capacity correction factors
OC360--1.qxp 06.2.24 1:56 PM Page 23
24
Input (kW)
Current (A)
Starting current (A)
Input (kW)Current (A)Starting current (A)
Mode
Capacity (W)
Total Input (kW)
Indo
orO
utdo
or
PLH-3AAK(H)Service Ref.
Cool
7,500
3.28
0.15
0.78
1.0
3.13
14.67/5.23
54/34
Heat8,200[9,950]3.07[4.83]0.15[1.91]0.78[8.69]1.0[8.9]2.92
13.68/4.8854/34
PLH-4AAK(H)
Cool
9,500
3.41
0.24
1.25
2.0
3.17
5.29
37
Heat10,200[12,400]
3.40[5.58]0.24[2.42]1.25
[11.02]2.0
[11.8]3.165.2837
PLH-5AAK(H)
Cool
12,200
4.47
0.28
1.43
2.0
4.19
7.32
60
Heat13,600[16,120]
4.41[6.93]0.28[2.80]1.43
[12.74]2.0
[13.3]4.137.2160
PLH-6AAK(H)
Cool
13,800
4.96
0.32
1.64
2.0
4.64
8.10
68
Heat15,700[18,220]
4.88[7.40]0.32[2.84]1.64
[12.93]2.0
[13.3]4.567.9668
4. ELECTRICAL DATAIndoor unit … 220V 50Hz 1phaseOutdoor unit…220V 50Hz 1phase / 380V 50Hz 3phase
Input (kW)
Current (A)
Starting current (A)
Input (kW)Current (A)Starting current (A)
Mode
Capacity (W)
Total Input (kW)
Indo
orO
utdo
or
PLH-3AAK(H)Service Ref.
Cool
7,600
3.30
0.16
0.79
1.0
3.14
14.22/5.21
56/36
Heat8,300
[10,200]3.09[5.02]0.16[2.09]0.79[9.09]1.0[9.3]2.93
13.27/4.8656/36
PLH-4AAK(H)
Cool
9,600
3.44
0.25
1.25
2.0
3.19
5.23
39
Heat10,300[12,700]
3.43[5.82]0.25[2.64]1.25
[11.49]2.0
[12.2]3.185.2239
PLH-5AAK(H)
Cool
12,300
4.49
0.29
1.43
2.0
4.20
7.05
63
Heat13,800[16,560]
4.44[7.20]0.29[3.05]1.43
[13.28]2.0
[13.9]4.156.9763
PLH-6AAK(H)
Cool
13,900
5.02
0.33
1.64
2.0
4.69
7.87
71
Heat15,900[18,660]
4.90[7.66]0.33[3.09]1.64
[13.46]2.0
[13.8]4.577.6771
Indoor unit … 230V 50Hz 1phaseOutdoor unit…230V 50Hz 1phase / 400V 50Hz 3phase
Input (kW)
Current (A)
Starting current (A)
Input (kW)Current (A)Starting current (A)
Mode
Capacity (W)
Total Input (kW)
Indo
orO
utdo
or
PLH-3AAK(H)Service Ref.
Cool
7,700
3.32
0.17
0.81
1.0
3.15
13.82/5.16
58/37
Heat8,400
[10,500]3.11[5.21]0.17[2.27]0.81[9.47]1.0[9.7]2.94
12.89/4.8158/37
PLH-4AAK(H)
Cool
9,700
3.46
0.26
1.25
2.0
3.20
5.24
40
Heat10,400[13,000]
3.45[6.05]0.26[2.86]1.25
[11.93]2.0
[12.7]3.195.2240
PLH-5AAK(H)
Cool
12,400
4.51
0.30
1.43
2.0
4.21
6.89
65
Heat14,000[17,000]
4.46[7.46]0.30[3.30]1.43
[13.77]2.0
[14.3]4.166.8165
PLH-6AAK(H)
Cool
14,000
5.07
0.34
1.64
2.0
4.73
7.74
74
Heat16,100[19,100]
4.92[7.92]0.34[3.34]1.64
[13.94]2.0
[14.3]4.587.5074
Indoor unit …240V 50Hz 1phaseOutdoor unit…240V 50Hz 1phase / 415V 50Hz 3phase
Refer to 3SPECIFICATIONS regarding the combination ofPUH-3NKA or PUH-4/5/6TKSA.
OC360--1.qxp 06.2.24 1:56 PM Page 24
25
CapacityInputIndoor unit Service Ref.Phase, HzVoltsAmperes
Outdoor unit Service Ref.
Phase,HzVoltsAmperes
Discharge pressure
Suction pressure
Discharge temperatureCondensing temperatureSuction temperatureRef. pipe length
Intake airtemperatureDischarge air temperature
Intake airtemperature
SHF
BF
Mode
Tot
al
WkW
VA
VA
MPa(kgf/F)
MPa(kgf/F)
°C°C°Cm°C°C°C°C°C
PLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)Service Ref.
Cooling7,7003.32
Heating8,4003.11
13.82/5.162.01
(20.5)
0.51(5.2)
84413.952719
13.23524
0.740.12
12.89/4.811.89
(19.3)
0.42(4.3)
77—
-2.052015
42.876——
0.81 0.81
PLH-3AAK(H)1, 50240
PLH-4AAK(H)1, 50240
PLH-5AAK(H)1,50240
PLH-6AAK(H)1,50240
PUH-3VKA.THPUH-3YKA.TH
1/3,50240/415
Cooling9,7003.46
Heating10,4003.45
5.241.81
(18.5)
0.49(5.0)
8041
10.55
2719
13.73524
0.790.08
5.221.73
(17.6)
0.36(3.7)
75—1.05
2015
39.976——
1.25 1.25
PUH-4YKSA.TH
3,50415
Cooling12,4004.51
Heating14,0004.46
6.891.85
(18.9)
0.44(4.5)
76464.052719
12.53524
0.730.10
6.811.94
(19.8)
0.36(3.7)
81—1.152015
45.576——
1.43 1.43
PUH-5YKSA.TH
3,50415
Cooling14,0005.07
Heating16,1004.92
7.741.90
(19.4)
0.42(4.3)
74394.65
2719
11.23524
0.710.06
7.502.01
(20.5)
0.37(3.8)
76—0.35
2015
49.876——
1.64 1.64
PUH-6YKSA.TH
3,50415E
lect
rical
circ
uit
Ref
riger
ant c
ircui
tIn
door
si
deOu
tdoo
r sid
e
D.B.W.B.D.B.D.B.W.B.
Air flowAir speedCoverage range
K/mim(CFM)m/Wm
PLH-4AAK(H)28(990)
4.97.4
PLH-3AAK(H)20(705)
4.05.7
PLH-6AAK(H)30(1,060)
6.68.9
PLH-5AAK(H)30(1,060)
5.27.9
Standard
5. STANDARD OPERATION DATA
6. OUTLET AIR SPEED AND COVERAGE RANGE
wThe air coverage range is the value up to the position where the air speed is 0.25m/sec.When air is blown out horizontally from the unit at the Hi notch position.The coverage range should be used only as a general guideline since it varies according to the size of the room and thefurniture inside the room.
The unit of pressure has been changed to Mpa based on the international SI system.The conversion factor is : 1(Mpa)=10.2(kgf/ FF)
OC360--1.qxp 06.2.24 1:56 PM Page 25
26
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROTIMATETERESHOLD OFREARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L,
BAND CENTER FREQUENCIES, Hz
(0d
B=0
.000
2 µ
BA
R)
PLH-4AAK(H)High
NOTCH
Low41
SPL(dB)
33
LINE
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROTIMATETERESHOLD OFREARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, (
0dB
=0.0
002
µ B
AR
)
BAND CENTER FREQUENCIES, Hz
PLH-3AAK(H)HighLow
34SPL(dB)
28
LINENOTCH
7. NOISE CRITERION CURVES
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROTIMATETERESHOLD OFREARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L,
BAND CENTER FREQUENCIES, Hz
(0d
B=0
.000
2 µ
BA
R)
PLH-6AAK(H)High
NOTCH
Low45
SPL(dB)
37
LINE
90
80
70
60
50
40
30
20
1063 125 250 500 1000 2000 4000 8000
APPROTIMATETERESHOLD OFREARING FORCONTINUOUSNOISE
NC-60
NC-50
NC-40
NC-30
NC-20
NC-70
OC
TAV
E B
AN
D S
OU
ND
PR
ES
SU
RE
LE
VE
L, (
0dB
=0.0
002
µ B
AR
)
BAND CENTER FREQUENCIES, Hz
PLH-5AAK(H)High
NOTCH
Low43
SPL(dB)
35
LINE
OC360--1.qxp 06.2.24 1:56 PM Page 26
27
UNIT
1.5m
MICROPHONE
CEILING Ambient temperature 27:
Test conditions are based on JIS Z8731
OC360--1.qxp 06.2.24 1:56 PM Page 27
28
5 OUTLINES AND DIMENSIONS
Unit : mm
Air outlet hole
Vane motor
Auto vane
Drain hole
Grille
Drain pipeVP-25connection(O.D.{32)
Branch duct hole(Cut out hole)
Ceiling surface
Sus
pens
ion
bolt
pitc
h
Cei
ling
hole
Branchduct hole
Suspension bolt pitch
Ceiling hole
Air
outle
t hol
e
Air
inta
ke h
ole
411
Air intake holeAir intake grille
ReceiverOperation lamp
DEFROST/STAND BY lamp
Emergency operation switch (cooling)
High efficiency filter& Fresh air intake casement (option)
A (WIRELESS PANEL)
Emergency operation switch (heating)
Power line entrySuspension bolt lower edge
Suspension bolt M10or W3/8
Control wire entry
Feeding hole(Drain pump)
577
374286
840
197 159
60
17+
5 0
17+
5 013
5
30
190
159
605
159
192
170
140
50~
70
98 89 C
840
860~
910
20~
4520
~45
20~4520~45
Fresh air intake
Branch duct hole
860~910
810
159
1610
5
AB
77 51
M
M
M
A
1
2
M
950
5177
950
577
411
Terminal block
Deteil drawing of fresh air intake
{175
{150
14 - {2.8Burring hole
3 - {2.8Burring hole
{100(Cut out hole){125
Ceiling surface
PLH-3AAK(H)
Models 1 2
PLH-4,5,6AAK(H)
Refrigerant pipe(9.52mm dia.)
flared connection3/8F
Refrigerant pipe(9.52mm dia.)
flared connection3/8F
Refrigerant pipe(15.88mm dia.)
flared connection5/8F
241
281
A
258
298
B
80
84
C
Refrigerant pipe(19.05mm dia.)
flared connection3/4F
350
120_
120_
158
90
70_
100 100 90
100
130
155
167
1. INDOOR UNIT PLH-3AAK(H)PLH-4AAK(H)PLH-5AAK(H)PLH-6AAK(H)
OC360--1.qxp 06.2.24 1:56 PM Page 28
29
WIRED REMOTE CONTROLLER Unit : mm
130
12
0
19
OC360--1.qxp 06.2.24 1:56 PM Page 29
30
WIRELESS REMOTE CONTROLLER Unit : mm
159.
3
55
58
19
OC360--1.qxp 06.2.24 1:56 PM Page 30
31
6 WIRING DIAGRAM
PLH-3AAK PLH-4AAK PLH-5AAK PLH-6AAKPLH-3AAKH PLH-4AAKH PLH-5AAKH PLH-6AAKH
321
321
531
MF
FAN(WHT)
RE
DW
HT
BLK
BLK
X1
X4
X1X4
C
BCR
31
DP
D.U.MCNP(BLU)
YLW
YLW
31 31 3 31
YLW
YLW
D.HEATERCNC(RED)
RE
DW
HT
WH
T
POWERCNDK(RED)
POWERCND(ORN)
21 21POWERCN2D(WHT)
21OUTDOOR
CN30(BLK)
CN41CN51 CN2L
CN329
WIRELESSCN90(WHT)
BZ
5
VANECN6V(GRN)
CN2S(WHT)
CNSK(RED)
W.B
LED2
CNB
LED1
SW1 SW2RU
21
2211
REMOCONCN22(BLU)
TB5
TRANSMISSION WIRES DC12V
TB6
R.B
BLU
BLU
321 21 21
D.SENSORCN31(WHT)
INTAKECN20(RED)
HEATERCN24(YLW)
LIQUIDCN21(WHT)
DS
TH2
TH1
LED2 LED1
SW6
ONOFF
SWE
Refer to tables 1. 2 and 3.
SW2SW1 SW5
9 5 1076321 84
5
MV
5
MV
55
MV
5
MV
GRILLE
H2
TB2
TB2
I.B
HEATER CN24(YLW)
[PLH-AAKH models only]
POWER SUPPLY~(1PHASE)220-240V 50Hz220V 60Hz
POWER SUPPLY~(1PHASE)220-240V 50Hz220V 60Hz
88H FS1
26H
FS2
H1
L RED
REDBLU
RED REDBLUGRN/YLW
GRN/YLW
WHT
WHTWHTGRY
N
TO OUTDOOR UNIT
LN
DC13.1V 1
223
21
2
65
1
1
P.B
ZNR
FUS
E
I.B
YLWORNBRN
88H
YLW
RE
DB
LU
YLW
1 2 3 4 5
ONOFF
MODELS
Table 1SW1Manufacture/Service
PLH-AAK
1 2 3 4 5ONOFF
MODELS
Table 2SW2
Manufacture/Service
PLH-3AAKPLH-3AAKH
PLH-4AAKPLH-4AAKH
PLH-5AAKPLH-5AAKH
PLH-6AAKPLH-6AAKH
1 2 3 4 5ONOFF
1 2 3 4 5ONOFF
MODELS Manufacture/Service
1 2 3 4 5ONOFF
1 2 3 4 5
ONOFF
1 2ONOFF
PLH-AAKH
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ONOFF
MODELS
Table 3SW5Manufacture/Service
PLH-AAK
ONOFF
PLH-AAKH
NOTES:1.Symbols used in wiring diagram above are, : Connector, : Terminal (block).2.Indoor and outdoor connecting wires are made with polarities, make wiring matching terminal numbers (1, 2, 3).3.Since the outdoor side electric wiring may change be sure to check the outdoor unit electric wiring for servicing.
Please set the voltage using theremote controller.For the setting method. please refer tothe indoor unit Installation Manual.
21
3
TB4
PLH-AAKH (with heater)
Posi t ion of 88H.( for Control box)
88HC
TB2TB4
INDOOR POWER BOARD
[LEGEND]
P.BINDOOR CONTROLLER BOARDI.BFUSE(T6.3AL250V)FUSE
CN2L
VARISTORZNR
CONNECTOR(LOSSNAY)CN32
FAN CONTROL ELEMENTBCR
CONNECTOR(REMOTE SWITCH)CN41 CONNECTOR(HA TERMINAL-A)CN51 CONNECTOR(CENTRALLY CONTROL)
SW1 SWITCH(MODEL SELECTION)WSee table 1SWITCH(CAPACITY CORD)WSee table 2SW2
SW5 SWITCH(SYSTEM SELECTION)WSee table 3SW6 SWITCH(EMERGENCY OPERATION)SWE CONNECTOR(EMERGENCY OPERATION)
X1 RELAY(DRAIN PUMP)X4 RELAY(FAN MOTOR)
LED1 POWER SUPPLY(I.B)LED2 POWER SUPPLY(R.B)
SYMBOL NAME SYMBOL NAME SYMBOL NAMEC CAPACITOR(FAN MOTOR)MF FAN MOTORMV VANE MOTOR
DP DRAIN-UP MACHINEDS DRAIN SENSOR
H2 DEW PREVENTION HEATER
TB4 TERMINAL BLOCK (INDOOR/OUTDOOR CONNECTING LINE)
TB2 TERMINAL BLOCK (POWER SUPPLY)
TB5, TB6 TERMINAL BLOCK(REMOTE CONTROLLER TRANSMISSION LINE)
TH1 ROOM TEMP.THERMISTOR(0:/15k",25:/5.4k" DETECT)
TH2 PIPE TEMP.THERMISTOR/LIQUID(0:/15k",25:/5.4k" DETECT)
R.B WIRED REMOTE CONTROLLER BOARD
W.B
HEATER
WIRELESS REMOTE CONTROLLER BOARDRU RECEIVING UNIT
FS1 THERMAL FUSE(72:, 16A)FS2 THERMAL FUSE(104:, 16A)H1 HEATER26H HEATER THERMAL SWITCH88H HEATER CONTACTOR
BZ BUZZERLED1 LED(RUN INDICATOR)LED2 LED(HOT ADJUST)SW1 SWITCH(HEATING ON/OFF)SW2 SWITCH(COOLING ON/OFF)
[Self-diagnosis]1.For details on how to operate self-diagnosis with the wireless remote control, refer to the technical manuals etc.2.For the wired remote control:When you quickly press twice the CHECK switch on the remote control, the unit begins self-diagnosis. and Check Codes generated in the past appear on the display. For Check Codes and symptoms refer to the table below.
Check CodeP1P2P4P5
Abnormality of room temperature thermistor (TH1).Abnormality of pipe temperature thermistor/Liquid (TH2).Abnormality of drain sensor (DS).Malfunction of drain-up machine.
Symptom
P6 Freezing / overheating protection is working.
P8E0-E5
Abnormality in outdoor unit. Refer to outdoor unit wiring diagram.Abnormality of the signal transmission between remote controller and indoor unit.
----FFFF
No trouble generated in the past.No corresponding unit.
Fb Abnormality of indoor controller board.
[Emergency operation procedure]1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly Emergency Operation. WNote on the wireless remote control: when the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote controller.2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) and switch (SW6) on the indoor controller. SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working. SW6-1 : ON • Emergency operation of cooling mode. SW6-1,2 : ON • Emergency operation of heating mode.3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when: • the outdoor unit malfunctions. • the indoor fan malfunctions. • when it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control etc,dose not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions. (6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate position.
OC360--2.qxp 06.2.24 1:55 PM Page 31
32
REFRIGERANT SYSTEM DIAGRAM7
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)15.88mm({5/8")(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Serviceport
Serviceport
High pressurecontrol switch
Outdoor unitOutdoor heat exchanger
ThermistorRT
Capillarytube
Restrictorvalve
O.D.4.0 o I.D.2.4 -L1070
Strainer
Bypass valve
Compressor
Accumulator
Ball valve(with service port)
Refrigerant pipe(option)9.52mm({3/8")(with heat insulator)Capillary
tube
Restrictorvalve
Distributorwith strainer
ThermistorTH2
Strainer Flaredconnection
Refrigerant flow in coolingRefrigerant flow in heating
<R.V.coil>Heating ONCooling OFF
Unit : mm
O.D.4.0 o I.D.2.0 - L200
PLH-3AAK(H)/ PUH-3VKA.TH · PUH-3VKA 2.TH-APUH-3YKA.TH · PUH-3YKA 1.TH-A
PLH-3AAK/PUH-3NKA.TH
PLH-4AAK(H)/PUH-4YKSA.TH · PUH-4YKSA 1.TH-A
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)15.88mm( 5/8")(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Serviceport(check)
High pressurecontrol switch
Outdoor unitOutdoor heat exchanger
ThermistorRT
Capillarytube
Restrictorvalve
Strainer Capillary tube
Bypass valve Muffler
Compressor
Accumulator
Ball valve(with service port)
Refrigerant pipe(option)9.52mm( 3/8")(with heat insulator)Capillary
tube
Restrictorvalve
Distributorwith strainer
ThermistorTH2
Strainer Flaredconnection
O.D.4.0 ✕ I.D.2.0 - L200
Serviceport(check)
O.D. 3.2 ✕ I.D. 1.2 - L1250
O.D. 4.0 ✕ I.D. 2.4 - L600
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)19.05mm([ 3/4")(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Serviceport
Serviceport
Outdoor unitOutdoor heat exchanger
Thermistor RT
Capillarytube
Restrictorvalve
Strainer
Bypass valve
CompressorAccumulator
Ball valve(with service port)
Refrigerant pipe(option)9.52mm([ 3/8")(with heat insulator)
Capillarytube
Restrictor valve
Distributorwith strainer
Thermistor TH2
Strainer Flaredconnection
O.D. 4.0 o I.D. 2.0 - L 250
(O.D. 3.2 o I.D. 2.0 - L 820) o2
High pressureswitch
OC360--2.qxp 06.2.24 1:55 PM Page 32
33
PLH-5AAK(H)/PUH-5YKSA.TH · PUH-5YKSA 3.TH-APLH-6AAK(H)/PUH-6YKSA.TH · PUH-6YKSA 3.TH-A
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)19.05mm( [3/4")(with heat insulator)
Flexible tube
Ball valve
Strainer
4-way valve
Oil separator
Serviceport
Serviceport
High pressurecontrol switch
Outdoor unitOutdoor heat exchanger
ThermistorRT
Capillarytube
Restrictorvalve
Strainer
Bypass valve
Compressor
Capillary tube
Accumulator
Ball valve(with service port)
Refrigerant pipe(option)9.52mm({3/8")(with heat insulator)
Capillarytube
Restrictorvalve
Distributorwith strainer
ThermistorTH2
Strainer Flaredconnection
Restrictor valve
Muffler
O.D. 4.0 ✕ I.D. 2.0 - L 250
O.D. 3.2 ✕ I.D. 1.2 - L 1,250
(O.D. 3.2 ✕ I.D. 2.0 - L820) ✕ 2
PLH-4AAK/PUH-4TKSA.TH
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)19.05mm([3/4")(with heat insulator)
Flexible tube
Ball valveStrainer
4-way valve
Oil separator
Serviceport
Serviceport
Outdoor unitOutdoor heat exchanger
Thermistor RT
Capillary tube
Restrictorvalve
Strainer
Bypass valve
CompressorAccumulator
Ball valve(with service port)
Thermal SwitchRefrigerant pipe(option)r9.52mm([3/8")(with heat insulator)Capillary
tube
Restrictor valve
Distributorwith strainer
Thermistor TH2
Strainer Flaredconnection
PLH-5 O.D. 4.0 o I.D. 3.0 - L 550
Capillary tube
PUH-5 (O.D. 4.0 o I.D. 2.4 - L 840) o2 PUH-6 (O.D. 4.0 o I.D. 2.4 - L1200) o2
PLH-6 O.D. 4.0 o I.D. 3.0 - L 380
High pressurecontrol switch
Indoor coilthermistorTH2
Thermal switch
Indoor unit
Indoor heat exchanger
Refrigerant pipe(option)19.05mm([3/4")(with heat insulator)
Flexible tube
Ball valveStrainer
4-way valve
Oil separator
Serviceport
Serviceport
High pressurecontrol switch
Outdoor unitOutdoor heat exchanger
Capillarytube
Restrictorvalve
Strainer
DPR
Bypass valve
CompressorAccumulator
Ball valve(with service port)
Refrigerant pipe(option)9.52mm([3/8")(with heat insulator)
Capillarytube
Distributorwith strainer
Strainer Flaredconnection
PLH-5 O.D. 4.0 ✕ I.D. 3.0 ✕ L 550
Capillary tube
PUH-5 (O.D. 4.0 ✕ I.D. 2.4 - L 840) ✕ 2PUH-6 (O.D. 4.0 ✕ I.D. 2.4 - L 740) ✕ 2
PLH-6 O.D. 4.0 ✕ I.D. 3.0 ✕ L 380
Restrictorvalve
Outdoor coilthermistor
(RT)
PLH-5AAK/PUH-5TKSA.THPLH-6AAK/PUH-6TKSA.TH
OC360--2.qxp 06.2.24 1:55 PM Page 33
34
8 TROUBLESHOOTING
<Error code display by self-diagnosis and actions to be taken for service (summary)>Present and past error codes are logged and displayed on the wired remote controller or controller board of outdoor unit.Actions to be taken for service,which depends on whether or not the the inferior phenomenon is reoccurring at service, aresummarized in the table below. Check the contents below before investigating details.
8-1. TROUBLESHOOTING
Unit conditions at service Error code Actions to be taken for service (summary)
The inferior phenomenon isreoccurring.
Displayed
Not displayed
Judge what is wrong and take a corrective action according to “SELF-DIAGNOSIS ACTION TABLE” (8-3).
Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (8-4).
The inferior phenomenon is not reoccurring.
Logged
Not logged
1Consider the temporary defects such as the work of protection devices in the refrigerant circuit including compressor, poor connection of wiring, noise and etc. Re-check the symptom, and check the installation environment, refrigerant amount, weather when the inferior phenomenon occurred, and wiring related. 2Reset error code logs and restart the unit after finishing service.3There is no abnormality in electrical components, controller boards, and remote controller.
1Recheck the abnormal symptom.2Identify the cause of the inferior phenomenon and take a corrective action according to “TROUBLESHOOTING BY INFERIOR PHENOMENA ” (8-4).3Continue to operate unit for the time being if the cause is not ascertained.4There is no abnormality in electrical components, controller boards, remote controller etc.
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
ERROR CODE
ERROR CODE
ERROR CODE
1 Turn on the power.2 Press the [CHECK] button twice.3 Set address with [TEMP] button if system control is used.4 Press the [ON/OFF] button to stop the self-check.
A CHECK button
B Address
C TEMP. button
D IC : Indoor unit OC: Outdoor unit
E Check code
F Unit No.
A
F
C
B
B
E
E
D
8-2. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER<In case of trouble during operation>When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to informunusual stop.
■ Wired remote controller
OC360--2.qxp 06.2.24 1:55 PM Page 34
35
[Procedure]1. Press the CHECK button twice.
2. Press the temperaturebuttons.
3. Point the remote controller at the sensor on the indoor unit andpress the HOUR button.
4. Point the remote controller at thesensor on the indoor unit andpress the ON/OFF button.
• "CHECK" lights, and address "00" flash-es.
• Check that the remote controller'sdisplay has stopped before continuing.
• Select the address of the indoor unitfor the self-diagnosis.
Main indoor unit : “00”Sub indoor unit : “01”
• If an air conditioner error occurs, theindoor unit's sensor emits an intermit-tent buzzer sound, the operation lightflashes, and the error code isoutput.(It takes 3 seconds at most for error code to appear.)
• The check mode is cancelled.
<Malfunction-diagnosis method at maintenance service>■ Wireless remote controller
ON/OFF TEMP
FAN
VANEMODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESETSET CLOCK
CHECKCHECKdisplay
Temperaturebutton
CHECKbutton
Addressdisplay
HOURbutton
ON/OFFbutton
[Output pattern A] Errors detected by indoor unit
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on, there are no error records.
*2 If the beeper sounds three times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial two beeps to confirm the self-check start signal was received, the specified refrigerant address is incorrect.
OPERATIONINDICATORlamp flashpattern
Beep Beep Beep Beep Beep Beep Beep
OffApprox. 2.5 sec.
On0.5 sec.
On0.5 sec.
On0.5 sec.
On0.5 sec.
OffApprox. 2.5 sec.
On0.5 sec.
On0.5 sec.
· · · Repeated
Number of flashes/beeps in pattern indicates the checkcode in the following table (i.e., n=5 for “P5”)
Number of flashes/beeps in pattern indicatesthe check code in the following table
nth1st 2nd 3rd 1st 2nd
Self-checkstarts(Start signalreceived)
Beeper sounds
• Refer to the following tables for details on the check codes.[Output pattern A]
• On wireless remote controller2The continuous buzzer sounds from receiving section of indoor unit.3Blink of operation lamp• On wired remote controller1Check code displayed in the LCD.
Beeper sounds/OPERATIONINDICATOR lamp flashes 1 Check code
Symptom Remark
(Number of times)
Wireless remote controller Wired remote controller
1 P1 Intake sensor error2 P2 Pipe (TH2) sensor error4 P4 Drain sensor error
5P5PA
Drain pump errorForced compressor stop
6 P6 Freezing/ Overheating safeguard operation8 P8 Pipe temperature error / Outdoor unit error9 E4, E5 Remote controller signal receiving error
10 –
11 –
–
–
12 Fb Indoor unit control system error (memory error, etc.)– E0, E3– E1, E2 Remote controller control board error
Remote controller transmission error
OC360--2.qxp 06.2.24 1:55 PM Page 35
36
SymptomCause
Wired remote controller
On the wireless remote controller with condition above, following phenomena takes place.• No signals from the remote controller are accepted.• Opration lamp is blinking.• The buzzer makes a short piping sound.
PLEASE WAIT
PLEASE WAIT → Error code
Display messages do not appear even when operation switch is turned ON (operation lamp does not light up).
For about 2minutes follow-ing power-on
After about 2minutes hasexpired follow-ing power-on
•For about 2 minutes following power-on,op-eration of the remote controller is not possible due to system start-up. (Correct operation)
•Connector for the outdoor unit’s protection device is not connected.
•Reverse or open phase wiring for the outdoor unit’s power terminal block
•Incorrect wiring between indoor and outdoorunits
•Remote controller wire short
Note:Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2) provided on the indoor controller, refer to the following table.
LED1 (power for microcomputer) Indicates whether control power is supplied. Make sure that this LED isalways lit.
LED2 (power for wired remote controller) Indicates whether power is supplied to the wired remote controller. This LED lights only in the case of the main indoor unit.
• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.
OC360--2.qxp 06.2.24 1:55 PM Page 36
37
8-3. SELF-DIAGNOSIS ACTION TABLENote: Refer to the manual of outdoor unit for the details of display
such as F, U, and other E.
Error Code Meaning of error code and detection method Cause Countermeasure
P1
Abnormality of room temperature thermistor (TH1)1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if theunit does not reset normally after threeminutes. (The unit returns to normaloperation, if it has normally reset.)
2 Constantly detected during cooling, drying, and heating operation.Short: 90: or moreOpen: -40: or less
1 Defective thermistor characteristics.
2 Contact failure of connector(CN20) on the indoor controllerboard. (Insert failure)
3 Breaking of wire or contact failure of thermistor wiring.
4 Defective indoor controllerboard.
1–3 Check resistance value of thermistor.0: ······15.0k"10: ····9.6k"20: ····6.3k"30: ····4.3k"40: ····3.0k"If you put force on (draw or bend) the lead wirewith measuring resistance value of thermistorbreaking of wire or contact failure can bedetected.2 Check contact failure of connector (CN20) on
the indoor controller board. Refer to 8-7.Turn the power on again and check restartafter inserting connector again.
4 Check room temperature display on remotecontroller.Replace indoor controller board if there isabnormal difference with actual room temperature.
Turn the power off, and on again to operate after check.
P2
Abnormality of pipe temperature thermistor/Liquid (TH2)1 The unit is in three-minute resume
prevention mode if short/open of thermistor is detected. Abnormal if theunit does not reset normally after threeminutes. (The unit returns to normaloperation, if it has normally reset.)
2 Constantly detected during cooling, drying, and heating (except defrosting)operation.Short: 90: or moreOpen: -40: or less
1 Defective thermistor characteristics.
2 Contact failure of connector(CN21) on the indoor controllerboard. (Insert failure)
3 Breaking of wire or contact failure of thermistor wiring.
4 Defective refrigerant circuit iscausing thermistor temperatureof 90: or more or -40: orless.
5 Defective indoor controller board.
1–3 Check resistance value of thermistor.For characteristics, refer to (P1) above.2 Check contact failure of connector (CN21) on
the indoor controller board. Refer to 8-7. Turnthe power on and check restart after insertingconnector again.
4 Check pipe <liquid> temperature with remotecontroller in test run mode. If pipe <liquid>temperature is exclusively low (in coolingmode) or high (in heating mode), refrigerantcircuit may have defective.
5 Check pipe <liquid> temperature with remotecontroller in test run mode. If there is exclusivedifference with actual pipe <liquid> temperature,replace indoor controller board.
Turn the power off, and on again to operate after check.
P4
Abnormality of drain sensor (DS)1 Suspensive abnormality, if short/open of
thermistor is detected for 30 secondscontinuously.Turn off compressor and indoor fan.
2 Short/open is detected for 30 secondscontinuously during suspensive abnormality.(The unit returns to normal operation, if it has normally reset.)
3 Detect the following condition.• During cooling and drying operation.• In case that pipe <liquid> temperature
- room temperature <-10deg(Except defrosting)
• When pipe <liquid> temperature orroom temperature is short/open temperature.
• During drain pump operation.
1 Defective thermistor characteristics
2 Contact failure of connector(CN31) on the indoor controllerboard. (Insert failure).
3 Breaking of wire or contact failure of drain sensor wiring.
4 Defective indoor controller board.
1–3 Check resistance value of thermistor.0: ······6.0k"10: ····3.9k"20: ····2.6k"30: ····1.8k"40: ····1.3k"2 Check contact failure of connector (CN31) on
the indoor controller board. Refer to 8-7. Turnthe power on again and check restart afterinserting connector again.
4 Replace indoor controller board if drain pump operates with the line of drain sensorconnector CN31-1 and 2 is short-circuited,and abnormality reappears.
Turn the power off, and on again to operate after check.
P5
Malfunction of drain pump (DP)1 Suspensive abnormality, if thermistor
of drain sensor is let heat itself and temperature rises slightly. Turn off compressor and indoor fan.
2 Drain pump is abnormal if the conditionabove is detected during suspensiveabnormality.
3 Constantly detected during drain pumpoperation.
1 Malfunction of drain pump2 Defective drain
Clogged drain pumpClogged drain pipe
3 Attached drop of water at thedrain sensor• Drops of drain trickles from
lead wire.• Clogged filter is causing
wave of drain.4 Defective indoor controller board.
1 Check if drain-up machine works.2 Check drain function.3 Check the setting of lead wire of drain sensor
and check clogs of the filter.4 Replace indoor controller board if drain
pump operates with the line of drain sensorconnector CN31-1 and 2 is short-circuitedand abnormality reappears.Refer to 8-7.
Turn the power off, and on again to operate after check.
OC360--2.qxp 06.2.24 1:55 PM Page 37
38
<Heating mode>When 10 seconds have passed after thecompressor starts operation and the hotadjustment mode has finished, the unit isdetected as abnormal whencondenser/evaporator pipe temperature isnot in heating range within 20 minutes.
Note 3) It takes at least 27 minutes todetect abnormality.
Note 4) It excludes the period of defrosting(Detection restarts when defrostingmode is over)
Heating range : 3 deg [ (TH2-TH1)
Error Code Meaning of error code and detection method Cause Countermeasure
P6
Freezing/overheating protection isworking1 Freezing protection (Cooling mode)
The unit is in six-minute resume preventionmode if pipe temperature stays under -15: for three minutes, three minutesafter the compressor started. Abnormalif it stays under -15: for three minutesagain within 16 minutes after six-minuteresume prevention mode.<Frost prevention mode>If pipe temperature is 2: or below when 16 minutes has passed after com-pressor starts operating, unit will start operating in frost prevention mode which stops compressor operation. After that, when pipe temperature stays 10: or more for 3 minutes, frost prevention mode will be released and compressor will restart its operation.
2 Overheating protection (Heating mode)The units is in six-minute resume prevention mode if pipe temperature isdetected as over 70: after the com-pressor started. Abnormal if the temper-ature of over 70: is detected againwithin 10 minutes after six-minuteresume prevention mode.
P8
1 Slight temperature differencebetween indoor room temperature and pipe tempera-ture thermistor• Shortage of refrigerant• Disconnected holder of pipe
thermistor• Defective refrigerant circuit
2 Converse connection of extension pipe (on plural unitsconnection)
3 Converse wiring of indoor/outdoor unit connecting wire(on plural units connection)
4 Defective detection of indoorroom temperature and pipetemperature thermistor
5 Stop valve is not opened completely.
(Cooling or drying mode)1 Clogged filter (reduced airflow)2 Short cycle of air path3 Low-load (low temperature)
operation beyond the tolerancerange
4 Defective indoor fan motor• Fan motor is defective.• Indoor controller board is
defective.
5 Defective outdoor fan control6 Overcharge of refrigerant7 Defective refrigerant circuit
(clogs)
(Heating mode)1 Clogged filter (reduced airflow)2 Short cycle of air path3 Over-load (high temperature)
operation beyond the tolerancerange
4 Defective indoor fan motor• Fan motor is defective.• Indoor controller board is
defective.
5 Defective outdoor fan control6 Overcharge of refrigerant7 Defective refrigerant circuit
(clogs)8 Bypass circuit of outdoor unit
is defective.
(Cooling or drying mode)1 Check clogs of the filter.2 Remove shields.
4 Measure the resistance of fan motor's winding.Measure the output voltage of fan's connector(FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 8-7.
5 Check outdoor fan motor. 67 Check operating condition of refrigerant
circuit.
(Heating mode)1 Check clogs of the filter.2 Remove shields.
4 Measure the resistance of fan motor's winding.Measure the output voltage of fan's connector(FAN) on the indoor controller board. WThe indoor controller board should be
normal when voltage of AC 220~240V is detected while fan motor is connected. Refer to 8-7.
5 Check outdoor fan motor. 6~8Check operating condition of refrigerant
circuit.
Abnormality of pipe temperature<Cooling mode>Detected as abnormal when the pipe tem-perature is not in the cooling range 3 min-utes later of compressor start and 6 min-utes later of the liquid pipe is out of coolingrange.Note 1) It takes at least 9 min. to detect.Note 2) Abnormality P8 is not detected in
drying mode.Cooling range : -3 deg ] (TH2-TH1) TH2: Liquid pipe temperature TH1: Intake temperature
1~4 Check pipe temperature with room temperature display on remote controller.
23Check converse connection of extension pipe or converse wiring of indoor/outdoor unit connecting wire.
1 Wrong wiring of indoor/outdoorconnecting wire
2 Reversed phase3 Protection device is working4 Damaged outdoor coil thermis-
tor
Abnormality in outdoor unit 1 Check the indoor/outdoor connecting wire.2 Change the connection of electric wiring.3 Check the protection device.4 Measure the resistance of the outdoor coil
thermistor. If the resistance is normal,replace the outdoor controller board.
OC360--2.qxp 06.2.24 1:55 PM Page 38
39
Error Code Meaning of error code and detection method Cause Countermeasure
E0orE4
Remote controller transmissionerror(E0)/signal receiving error(E4)1 Abnormal if main or sub remote con-
troller can not receive normally anytransmission from indoor unit of refriger-ant address “0” for three minutes.(Error code : E0)
2 Abnormal if sub remote controller couldnot receive for any signal for two min-utes. (Error code: E0)
1 Abnormal if indoor controller board cannot receive normally any data fromremote controller board or from otherindoor controller board for three minutes.(Error code: E4)
2 Indoor controller board cannot receiveany signal from remote controller for twominutes. (Error code: E4)
1 Check disconnection or looseness of indoorunit or transmission wire of remote controller.
2 Set one of the remote controllers “main”.If there is no problem with the action above.
3 Check wiring of remote controller.• Total wiring length: max.500m
(Do not use cable x 3 or more)• The number of connecting indoor units:
max.16units• The number of connecting remote con-
troller: max.2units
When it is not the above-mentioned problem of1~34 Diagnose remote controllers.
a) When “RC OK” is displayed,Remote controllers have no problem. Put the power off, and on again to check.If abnormality generates again, replaceindoor controller board.
b) When “RC NG” is displayed,Replace remote controller.
c) When “RC E3” is displayed,d) When “ERC 00-06” is displayed,[ c),d)→Noise may be causing abnormality. ]
∗ If the unit is not normal after replacingindoor controller board in group control,indoor controller board of address “0”may be abnormal.
E3orE5
Remote controller transmissionerror(E3)/signal receiving error(E5)1 Abnormal if remote controller could not
find blank of transmission path for sixseconds and could not transmit.(Error code: E3)
2 Remote controller receives transmitteddata at the same time, compares thedata, and when detecting it, judges different data to be abnormal 30 continuous times. (Error code: E3)
1 Abnormal if indoor controller board couldnot find blank of transmission path.(Error code: E5)
2 Indoor controller board receives trans-mitted data at the same time, comparesthe data,and when detecting it, judgesdifferent data to be abnormal 30 continuous times. (Error code: E5)
1 Set a remote controller to main, and theother to sub.
2 Remote controller is connected with only oneindoor unit.
3 The address changes to a separate setting.
4~6 Diagnose remote controller.a) When “RC OK”is displayed, remote con-
trollers have no problem.Put the power off,and on again to check.When becoming abnormal again, replaceindoor controller board.
b)When “RC NG”is displayed, replaceremote controller.
c)When “RC E3”or “ERC 00-66”is displayed,noise may be causing abnormality.
1 Contact failure at transmissionwire of remote controller
2 All remote controllers are setas “sub” remote controller. Inthis case, E0 is displayed onremote controller, and E4 isdisplayed at LED (LED1, LED2)on the outdoor controller circuitboard.
3 Mis-wiring of remote controller.4 Defective transmitting receiving
circuit of remote controller5 Defective transmitting receiving
circuit of indoor controller boardof refrigerant address “0”.
6 Noise has entered into thetransmission wire of remotecontroller.
1 Two remote controller are setas “main.” (In case of 2 remote con-trollers)
2 Remote controller is connectedwith two indoor units or more.
3 Repetition of refrigerantaddress.
4 Defective transmitting receivingcircuit of remote controller.
5 Defective transmitting receivingcircuit of indoor controllerboard.
6 Noise has entered into trans-mission wire of remote con-troller.
OC360--2.qxp 06.2.24 1:55 PM Page 39
40
Error Code Meaning of error code and detection method Cause Countermeasure
Fb
Abnormality of indoor controller boardAbnormal if data cannot be normally readfrom the nonvolatile memory of the indoorcontroller board.
1 Defective indoor controllerboard.
1 Replace indoor controller board.
E1orE2
Abnormality of remote controller con-trol board1 Abnormal if data cannot be normally
read from the nonvolatile memory of theremote controller control board.(Error code: E1)
2 Abnormal if the clock function of remotecontroller cannot be normally operated.(Error code: E2)
1 Defective remote controller. 1 Replace remote controller.
PA(2502)(2500)
Forced compressor stop (due to water leakage abnormality)1 When the intake temperature subtracted
with liquid pipe temperature is less than-10:, drain sensor is detected whether it is soaked in the water or not at the interval of 90 seconds. (Drain pump will start operatingwhen the drain sensor is detected to be soaked in the water.)
2 The unit has a water leakage abnormality when the following conditions, a and b, aresatisfied while the above-mentioned detectionis performed.a) The drain sensor is detected to be
soaked in the water 10 times in a row.b) The intake temperature subtracted with
liquid pipe temperature is detected to beless than -10: for a total of 30 minutes.(When the drain sensor is detected to be NOT soaked in the water, the detectionrecord of a and b will be cleared.)
3 The drain sensor detection is performed in operations other than cooling. (When the unit stops operating, during heating or fan operation, when the unit stops because of some abnormality)
*Once the water leakage abnormality is detected, abnormality state will not be released until the main power is reset.
1) Drain pump trouble
2) Drain defective· Drain pump clogging· Drain pipe clogging
3) Open circuit of drain sensor side heater
4) Contact failure of drain sensor connector
5) Dew condensation on drain sensor
· Drain water descends along lead wire.
· Drain water waving due to filterclogging.
6) Extension piping connection difference at twin, triple,quadruple system.
7) Mis-wiring of indoor/ outdoorconnecting at twin, triple,quadruple system.
8) Room temperature thermistor /liquid pipe temperature thermis-tor detection is defective.
Check the drain pump. PerformancePlease confirm whether water can be drained.
Confirm the resistance of the drain sensor sideheater.
Check the connector contact failure.
1 Check the drain sensor leadwire mounted.2 Check the filter clogging
Check the piping connection.
Check the indoor/ outdoor connecting wires.
Check the room temperature display of remotecontroller.Check the indoor liquid pipe temperature dis-play of outdoor controller board.
OC360--2.qxp 06.2.24 1:55 PM Page 40
41
8-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
• When LED1 on indoor controller board is also off.1 Power supply of 220~240V AC is not supplied to
indoor unit.
2 Defective indoor controller board.
3 Defective indoor power board.
Phenomena Cause Countermeasure(1)LED2 on indoor controller board
is off.
• When LED1 on indoor controller board is lit.1 Mis-setting of main/sub for indoor unit
(There is no unit corresponding to main unit.)
1 Reconfirm the setting of main/sub forindoor unitSet the main unit.Set main/sub using SW5-3 on indoor controller board.
1 Check the voltage of indoor power supplyterminal block (L,N).• When AC220~240V is not detected.
Check the power supply wiring.• When AC220~240V is detected.
-Check 2 (below).2 Check voltage output from CNDK on
indoor controller board.• When AC220~240V is not detected.
Check the fuse on indoor controllerboard.Check the wiring connection betweenindoor power supply terminal block andCND on indoor controller board.
• When AC220~240V is detected.-Check 3 (below).
3 Check voltage output from CN2S onindoor power board.• When no voltage output.
Check the wiring connection betweenCNDK on indoor controller board andCNSK on indoor power board.If no problem are found,indoor powerboard is defective.
• When DC12.5~13.7V is detected.Check the wiring connection betweenCN2S on indoor power board andCN2D on indoor power board.If no problem are found,indoor con-troller board is defective.
(2)LED2 on indoor controller board is blinking.
• When LED1 on indoor controller board is also blinking.Connection failure of indoor/outdoor unit connecting wire
• When LED1 is lit.1 Mis-wiring of remote controller wires
When 2 indoor units are wired in one refrigerant system, each indoor unit sets main unit. (SW5-3)
2 Short-cut of indoor/outdoor unit connecting wire.
3 Short-cut of remote controller wires4 Defective remote controller
Check indoor/outdoor unit connecting wirefor connection failure.
1 Check the connection of remote con-troller wires in case of twin triple indoor unit system. When 2 or more indoor units are wired in one refrigerant system, connect remote controller wires to one ofthose units.
2 Remove indoor/outdoor connecting wiresand check LED2 on indoor controllerboard.
• When LED2 is blinking, check the short-cut of indoor/outdoor connecting wires.
• When LED2 is lit, connect indoor/outdoorconnecting wires again, and; if LED2 isblinking, outdoor unit’s controller board isdefective; if LED2 is lit, connection failureof indoor/outdoor terminal block etc. hasreturned to normal.
34 Remove remote controller wires and check LED2 on indoor controller board.
• When LED2 is blinking, check theshort-cut of remote controller wires.
• When LED2 is lit, connect remote controller wires again and:if LED2 is blinking, remote controller is defective; if LED2 is lit, connection failure of remote controller terminal block etc. has returned to normal.
OC360--2.qxp 06.2.24 1:55 PM Page 41
42
(3)Upward/downward vane performance failure
1 The vane is not downward during defrosting andheat preparation and when the thermostat is OFF inHEAT mode. (Working of COOL protection function)
2 Vane motor does not rotate.• Defective vane motor• Breaking of wire or connection failure of connector• Up/down vane setting is “No vanes”.
3 Upward/downward vane does not work.• The vane is set to fixed position.
1 Normal operation (The vane is set to hor-izontal regardless of remote control.)
2 Check 2 (left).• Check the vane motor. (Refer to “How
to check the parts”.)• Check for breaking of wire or connec-
tion failure of connector.• Check “Up/down vane setting”. (Unit
function selection by remote controller).3 Normal operation (Each connector on
vane motor side is disconnected.)
Phenomena Cause Countermeasure
(4)Receiver for wireless remote controller
1 Weak batteries of wireless remote controller.
2 Contact failure of connector (CNB) on wirelessremote controller board.(Insert failure)
3 Contact failure of connector (CN90) on indoor con-troller board.(Insert failure)
4 Contact failure of connector between wirelessremote controller board and indoor controller board.
1 Replace batteries of wireless remote con-troller.
2~4Check contact failure of each connector.If no problems are found of connector,replace indoor controller board.When the same trouble occurs even ifindoor controller board is replaced,replace wireless remote controllerboard.
8-5. TEST RUN AND EMERGENCY OPERATION8-5-1. Before test run4 After completing installation and the wiring and piping of the indoor and outdoor units, check for refrigerant leakage, looseness in the power supply or control wiring, wrong polarity, and no disconnection of one phase in the supply.4 Use a 500-volt megohmmeter to check that the resistance between the power supply terminals and ground is at least 1.0M".4 Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:Do not use the air conditioner if the insulation resistance is less than 1.0M".Insulation resistance
8-5-2. Test run (Using wired remote controller)
BEF
C
HG I M
A
D
ûC
ûCSIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
TEST RUNCOOL, HEAT
A ON/OFF buttonB Test run displayC Indoor temperature liquid line temperature displayD ON/OFF lampE Power display
F Error code display Test run remaining time displayG Set temperature buttonH Mode selection buttonI Fan speed buttonM TEST button
1 Turn on the power at least 12 hours before the test run.2 Press the [TEST] button twice. ➜ "TEST RUN" liquid crystal display3 Press the [Mode selection] button. Make sure that wind is blown out.4 Press the [Mode selection] button and switch to the cooling (or heating) mode. ➜ Make sure that cold (or warm) wind is blown out.5 Press the [Fan speed] button. ➜ Make sure that the wind speed is switched.6 Check operation of the outdoor unit fan.7 Release test run by pressing the [ON/OFF] button. ➜ Stop8 Register a telephone number.
The telephone number of the repair shop, sales office, etc., to contact if an erroroccurs can be registered in the remote controller. The telephone number will bedisplayed when an error occurs. For registration procedures, refer to the operationmanual for the indoor unit.
OC360--2.qxp 06.2.24 1:55 PM Page 42
ON/OFF TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESETSET CLOCK
TEST RUN
3,4
7
2
6
A
5
1 Turn on the power to the unit at least 12 hours before the test run.
2 Press the button twice continuously. (Start this operation from the status of remote controller display turned off.) A and current operation mode are displayed.
TEST RUN
TEST RUN
3 Press the button to activate mode, then check whether cool air is blown out from the unit.
MODE
4 Press the button to activate mode, then check whether cool air is blown out from the unit.
MODE
COOL
HEAT
5 Press the button and check whether fan speed changes.FAN
6 Press the button and check whether the auto vane operates properly.VANE
7 Press the ON/OFF button to stop the test run.
Note:• Point the remote controller towards the indoor unit receiver while following steps 2 to 6.• It is not possible to run the in FAN or DRY mode.
43
ReceiverOperation lamp
Emergency operation switch (cooling)
Emergency operation switch (heating)
8-5-4. When wireless remote controller troubles or its battery is exhausted1. Emergency operation is available in such a case using emergency operation switch equipped next to the receiver of indoor
unit.2. To start operation
• Cooling Operation·······Press (Cooling) switch.
• Heating Operation·······Press (Heating) switch.
wWhen the unit starts operating, the operation lamp is lit.
3. To stop operation• Press either emergency operation switch (cooling/heating).
Mode Cooling Heating
Set temperatureFan speed
Airflow direction
24:High
Downward (70deg)
24:High
Horizontal (30deg)
wEmergency operation will be performed as follows.
8-5-3. Test run (Using wireless remote controller)
8-5-5. When wired remote controller or indoor unit micro computer troubles
1.When the wired remote control or the indoor unit microcomputer has failed,but all other compornents work if you set the switch (SWE, SW6) on the indoor control board, the indoor unit will begin properly Emergency Operation. WNote on the wireless remote control: when the remote control does not function, it is possible to activate Emergency Operation by using the indoor unit emergency operation switch (SW1,SW2 of the wireless signal receiver board). However,if the indoor unit microcomputer has failed,it is nesessary to proceed with points 2 and 3 below as in the case of the wired remote controller.2.When you activate emergency operation of the cooling or heating, you have to set the switch (SWE) and switch (SW6) on the indoor controller. SWE : ON • Indoor fan is running at high speed. • Drain-up machine is working. SW6-1 : ON • Emergency operation of cooling mode. SW6-1,2 : ON • Emergency operation of heating mode.3.Before you activate emergency operation, check the following points: (1) Emergency operation cannot be activated when: • the outdoor unit malfunctions. • the indoor fan malfunctions. • when it has detected the malfunction of drain-up machine during self-diagnosing. (2) Emergency operation becomes continuous only by switching the power source on/off. ON/OFF on the remote control or temperature control etc,dose not function. (3) Avoid operating for a long time when the outdoor unit begins defrosting while emergency operation of the heating is activated, because it will start to blow cold air. (4) Emergency cooling should be limited to 10 hours maximum (The indoor unit heat exchanger may freeze). (5) After emergency operation has been deactivated, set the switches etc.to their original positions. (6) Movement of the vanes does not work in emergency operation, therefore you have to slowly set them manually to the appropriate position.
OC360--2.qxp 06.2.24 1:55 PM Page 43
44
8-6. HOW TO CHECK THE PARTSPLH-3AAK PLH-4AAK PLH-5AAK PLH-6AAKPLH-3AAKH PLH-4AAKH PLH-5AAKH PLH-6AAKH
Parts name Check points
Disconnect the connector then measure the resistance using a tester.(Surrounding temperature 10:~30:)
Measure the resistance between the terminals using a tester.(Surrounding temperature20:)
Measure the resistance between the terminals using a tester.(Winding temperature 20:)
Measure the resistance between the terminals using a tester.Measure the resistance after 3 minutes have passed since the power supply was intercepted.(Surrounding temperature 0:~60:)
Vane motor
Drain pump
Drain sensor
(Refer to the thermistor)
(Refer to the thermistor)
Room temperaturethermistor (TH1)
Pipe temperaturethermistor/liquid(TH2)
1
3
YLW
YLW
123
Normal
4.3k"~9.6k"
Abnormal
Open or short
Abnormal
Open or short
Normal
0.6k"~6.0k"
Normal Abnormal
15k" Open or short
Normal Abnormal
290" Open or short
Measure the resistance between the terminals using a tester.(Winding temperature 20:)
Fan motor
11
22
33
Red
White
Black
Relay connector
Protector OFF:130: ON :80i20:
Abnormal
Open or shortRed-Black
White-Black
Motor terminalor
Relay connector
Normal
87.2"
104.1"
PLH-3AAK(H) PLH-4,5,6AAK(H)
28.7"
41.6"
OC360--2.qxp 06.2.24 1:55 PM Page 44
45
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
< Thermistor for lower temperature >
Temperature (:)
Res
ista
nce
(K"
)
<Thermistor Characteristic graph>
Room temperature thermistor(TH1)Pipe temperature thermistor/liquid(TH2)
Thermistor R0=15k' ± 3%Fixed number of B=3480 ± 2%
Rt=15exp { 3480( ) }
0: 15k'10: 9.6k'20: 6.3k'25: 5.4k'30: 4.3k'40: 3.0k'
Thermistor R0=6.0k' ±5%Fixed number of B=3390 ±2%
Rt= 6 exp { 3390( ) }
0: 6.0k'10: 3.9k'20: 2.6k'25: 2.2k'30: 1.8k'40: 1.3k'60: 0.6k'
Thermistor for lower temperature
1273+t
1273
1273+t
1273
-20 0 20 40 60 80
< Thermistor for drain sensor >
Temperature (:)
0
1
2
3
4
5
6
7
8
9
10R
esis
tanc
e (K
")
Thermistor for drain sensor
OC360--2.qxp 06.2.24 1:55 PM Page 45
46
8-7.TEST POINT DIAGRAM8-7-1. Power boardPLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)
CNSKConnect to the indoor controller board(CNDK)Between 11 to 33 220-240V AC
CN2SConnect to the indoor controller board (CN2D)Between 11 to 33 12.6-13.7V DC (Pin11 (+))
OC360--2.qxp 06.2.24 1:55 PM Page 46
47
8-7-2. Indoor controller board PLH-3AAK(H) PLH-4AAK(H) PLH-5AAK(H) PLH-6AAK(H)
CN2DConnect to the indoorpower board (CN2S)(12.5~13.7V DC)
CNDKConnect to the indoorpower board (CNSK)(220~240V AC)
FUSE(6.3 A 250 V)
CN22Connect to the terminalblock(TB5)(Remote controller connectingwire)(10.4~14.6V DC)
CN21Pipe temperature thermistor/Liquid (TH2)
CN20Room temperature thermistor (TH1)
CN41Connector (HA terminal-A)
CN6VVane motor output(MV)
CN90Connect to the wirelessremote controller board(CNB)
CN31Drain sensor (DS)
CN51Centrally control
CN24Heater output (12V DC)
SW1Model setting
SW2Capacity setting
SWEEmergency operation
LED1Power supply (I.B)
LED2Power supply (R.B)
FANFan motor output
Jumper wire J41, J42 Pair number setting withwireless remote controller
CNDPower supply input(220~240V AC)
CNPDrain-pump output(DP)(220~240V AC)
CN2LConnector(LOSSNAY)
CN30Transmission (indoor/outdoor)
CN105/CN92(RED)
SW5System setting
SW6Emergency operation
CN32Remote switch
OC360--2.qxp 06.2.24 1:55 PM Page 47
4848
SW1
Setting by the dip switch and jumper wireFunctionsJumper wire
Modelsettings
SW5 Systemsettings
Capacitysettings
Pair numbersetting withwireless remotecontroller
Remarks
SW2
J41J42
012
3 ~ 9
Wireless remotecontroller setting
Control PCB settingJ41 J42
<Settings at time of factory shipment>Wireless remote controller: 0Control PCB: (for both J41 and J42)Four pair number settings are supported. The pair number settings of the wireless remote controller and indoor control PCB (J41/J42) are given in the table on the left.(' ' in the table indicates the jumper line is disco-nnected.)
SW5-3 Main/Sub setting OFF : Main ON : SubSW5-4 Rotaion operation setting OFF : Not avairable ON : avairable
MODELS SW1
MODELS SW5
MODELS SW2
1 2 3 4 5
ONOFF
PLH-AAK
1 2 3 4 5ONOFF
PLH-3AAKPLH-3AAKH
PLH-4AAKPLH-4AAKH
PLH-5AAKPLH-5AAKH
PLH-6AAKPLH-6AAKH
1 2 3 4 5ONOFF
1 2 3 4 5ONOFF
1 2 3 4 5ONOFF
1 2 3 4 5
ONOFF
PLH-AAKH
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ONOFF
PLH-AAK
ONOFF
PLH-AAKH
8-8. FUNCTIONS OF DIP SWITCH AND JUMPER WIREEach function is controlled by the dip switch and the jumper wire on control p.c. board.
OC360--2.qxp 06.2.24 1:55 PM Page 48
49
8-9 OUTDOOR UNIT SERVICE FUNCTIONS (OUTDOOR CONTROLLER BOARD)(1) Compulsory defrosting
1When all of the following conditions are satisfied, pressing SW2 starts the compulsory defrosting.● During HEAT mode● The compressor is ON.● The outdoor coil temperature is being displayed by LED. (Outdoor controller board dip switch SW3-1 : OFF, SW3-2 :
ON)● The outdoor coil thermistor reads 8°C or below.
2The operation state and the termination conditions of the compulsory defrosting are the same as those of the normaldefrosting. As an exception, the defrost interval after the defrosting completion is 50 minutes.
(2) Fixed fan-outputWhile the compressor is operating (except during defrosting) and the fan output step is indicated by LED, pressing SW2fixes the fan output. The fixed fan-output can be released when any of the following conditions are satisfied.1SW2 is pressed again.2SW3 setting is changed.3The compressor stops.4Defrosting operation starts.
(3) Function of switches on the outdoor controller boardSW1: Clears the check code memory (push-button switch)SW2: Switches the output state indication and the check code display (push-button switch)SW3-1,2: Switches the output state indication items (dip switch)
(4) 100% fan outputFan output is fixed to 100% by shorting the connector CN22. However, the fan stops during compressor OFF or defrosting.Open-circuit of CN22 restarts the normal fan control.
(5) Time shorteningShort circuit of the connector CN21 shortens the time as follows1Fan control period: 30 seconds → 3 seconds2Three-minutes time delay function : 3 minutes → 3 seconds3Max. time of defrosting : 15 minutes → 15 seconds4Defrost interval : 30 ~ 120 minutes → 3 ~ 12 seconds5Compressor ON/OFF time for bypass valve ON/OFF : 30 minutes → 3 seconds6Compressor ON time to start other functions : x minutes → x seconds7Crankcase heater operation : 1 hour → 6 seconds
(6) Crankcase heater control1With jumper wire J3
The crankcase heater is ON from when the power is turned ON until the compressor starts, and then turns ON one hourafter the compressor stops.
2Without jumper wire J3The crankcase heater is ON from when the power is turned ON until the compressor starts, and repeats 1-hour ON and 1-hour OFF, after the compressor stops.
OC360--2.qxp 06.2.24 1:55 PM Page 49
50
9 FUNCTION SETTING
Function Settings No.Mode
No.Setting
Initial setting (Factory setting)- : Not available
4-Way cassetteCeiling
concealedCeiling
suspendedWall
mountedFloor
standing
PLH-AAK(H)PEH-EAK(H) PCH-GAK(H)
PKHGAKL(H)PSH-GAK(H)PEHD-EAK(H) PKA-FAKL(H)
Filter sign 100Hr 12500Hr 07 2No filter sign indicator 3
Air flow Quiet Standard 1 - - -(Fan speed) Standard High ceiling1 08 2 - - -
High ceiling High ceiling2 3 - - -No.of air outlets 4 directions 1 - - - -
3 directions 09 2 - - - -2 directions 3 -- - - -
Optional high efficiency Not supported10
1 - - -filter Supported 2 - - -Vane setting No vanes (Vane No.3 setting:PLH-AAK(H)only) 1 - - -
Vane No.1 setting 11 2 - - -Vane No.2 setting 3 - - -
Energy saving air Disabled 121 - - -
flow (Heating mode) Enabled 2 - - -Optional humidifier Not supported 13
1 - - - -(PLH-AAK(H) only) Supported 2 - - - -Vane differential setting No.1 setting (TH2: 24-28:) 1 - -in heating mode No.2 setting (Standard, TH2:28-32:) 14 2 - -(cold wind prevention) No.3 setting (TH2: 32-38:) 3 - -Swing Not available 23
1 - -Available 2 - -
Set temperature in heating Available 241
mode (4 deg up) Not available 2Fan speed when the Extra low 1heating thermostat is OFF Stop 25 2
Set fan speed 3Quiet operation mode Disabled (Standard)
261 - - - -
of PLH-AAK(H)(Fan speed) Enabled (Quiet operation mode) 2 - - - -Fan speed when the Set fan speed
271
cooling thermostat is OFF Stop 2Detection of abnormality of Available 28
1the pipe temperature (P8) Not available 2
} PLH-AAK(H)
PLH-KAK(H)
-
--
-
Function Settings Mode No. Setting No. Initial setting
(when sent from the factory) Remarks
Power failure automatic recoveryIndoor temperature detecting
LOSSNAY connectivity
Power supply voltageFrost prevention temperatureHumidifier control
Rotation
OFFONIndoor unit's (Main) internal sensor
Remote controller's internal sensorNot supportedSupported (indoor unit not equipped with outdoor air intake)Supported (indoor unit equipped with outdoor air intake)240V220V,230V1: (Normal)-3: When the compressor operates, the humidifier also operates.When the fan operates, the humidifier also operates.24h cycle168cycleBack up function
12123123121212123
01
02
03
04
15
16
20
The setting is applied to all the units in the same refrigerant system.
9-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLEREach function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1.
<Table 1> Function selections(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor standing models.
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number.• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number.• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number.
OC360--2.qxp 06.2.24 1:55 PM Page 50
51
Rotation setting (Function setting mode No.20)
Function setting Features Indoor controller boardMode No.
This system can correspond only by the pattern of two refrigerant group by 1 : 1 (indoor and outdoor unit combination) systems.
Setting No. SW5-3 setting SW5-4 setting19 01
(24hourscycle)
02ON
OFF : MainON : Sub(168hours
cycle)
03(Back upfunction)
When abnormality occurs while operating, it changes as a back up unit, and operating continues.
Each system operates alternately for 24hours.
Each system operates alternately for 168hours.
Example of unit's operation(Setting No. = 01 or 02)
Main Unit is abnormalOperation starts Main➝Sub Sub➝Main
(Setting No. = 02 • • • 168hours cycle)
Outdoorunit
(Setting No. = 03)Main Unit is abnormal
Indoor
Operation starts Main➝Sub
unit
RemoteController
Main➝Sub
24h 24h
Subindoorunit
ON
OFF
OFF
Mainindoorunit
ON
OFF
Subindoorunit
Mainindoorunit
ON
ON
OFF
Main Sub
9-1-1. Selecting functions using the wired remote controllerFirst, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the roomtemperature detection position is given.For actual operations, refer to steps 1 to 0 .
Setting number Address Unit number
Mode number
F
E
G
C D
J
B
A
I
Modes 01 to 13 can be activatedby pressing buttons A and Bsimultaneously, and modes 15 to28 by pressing buttons B and J .
OC360--2.qxp 06.2.24 1:55 PM Page 51
52
6 Select mode No. 02 (room temperature detection position).7 Select setting No. 03 (remote controller fixed). (Use F and G .)
8 Enter the setting. (Press E .)
Finished
0 Function selection end screen (Press A and B at the same time.)
Example:Selecting room temperaturedetection position
YES
YES
NO
NO
9
Selecting functions using the wired remote controller
1 Check the function selection setting.
For modes 15 and higher,press J and B at the same time.
3 Specify address4 Specify unit No.
Refer to address unit No. to the figure below (Use C and D .)
5 Enter the setting. (Press E .)
(Specified indoor unit:BLOW operation)
Change refrigerantaddress unit No.
2 Switch to function setting mode. (Press A and B at the same time with the remote controller stopped.)
The above procedure must be carried out only if changes are necessary.
1 : 1 system Simultaneous twin system Rotation system
Indoor unit address = 00 unit No. = 01
Main indoor unit address = 00 unit No. = 01
Sub indoor unit address = 01 unit No. = 02
Outdoor unit
Indoor unit
Remote controller
Outdoor unit Outdoor unit Outdoor unit
Main indoor unit
Sub indoor unit
Remote controller
Main indoor unit address = 00 unit No. = 01
Sub indoor unit address = 01 unit No. = 01
Main indoor unit
Sub indoor unit
Remote controller
OC360--2.qxp 06.2.24 1:55 PM Page 52
53
[Operating Procedure]1 Check the setting items provided by function selection.
If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual.
2 Switch off the remote controller.A Hold down the FILTER B and ( mode 15 or more) TEST
buttons simultaneously for at least two seconds. FUNCTIONSELECTION will start to flash,
and then the remote controller's display content will change as shown below.
3 Set the outdoor address.C Press the [ CLOCK] buttons ( and ) to select the desired
address. The address changes from "00" to "15".
* If the unit stops after FUNCTIONSELECTION flashed for two seconds or "88" flashes in the room temperature display area for two seconds, a transmission error may have occurred.
Check to see if there are any sources of noise or interference near the transmission path.
NoteIf you have made operational mistakes during this procedure, exit function selection (see step 0 ), and then restart from step 2 .
4 Set the indoor unit number.
D Press the ON/OFF button so that "- -" flashes in the unit number displayarea.
C Press the [ CLOCK] buttons ( and ) to select the unit numberof the indoor unit for which you want to perform function selection. The unitnumber changes to "00", "01", "02","03",04" and "AL" each time a button ispressed.
* To set modes 01 to 06 or 15 to 22 select unit number "00".* To set modes 07 to 14 or 23 to 28 carry out as follows:
• To set each indoor unit individually, select "01" to "04".• To set all the indoor units collectively, select "AL".
5 Confirm the address and unit number.E Press the MODE button to confirm the address and unit
number.After a while, "- - " will start to flash in the mode number display area.
E When the address and unit number are confirmed by pressing the
MODE button, the corresponding indoor unit will start fan operation. This
helps you find the location of the indoor unit for which you want to perform functionselection. However, if "00" or "AL" is selected as the unit number, all the indoorunits corresponding to the specified address will start fan operation.
* "88" will flash in the room temperature display area if the selected address does not exist in the system.Furthermore, if "F" appears and flashes in the unit number display area and theaddress display area also flashes, there are no units that correspond to theselected unit number. In this case, the address and unit number may be incorrect,so repeat steps 2 and 3 to set the correct ones.
* When grouping different systems, if an indoor unit other than theone to which the address has been set performs fan operation,there may be another address that is the same as the specified one.In this case, check the DIP switch of the outdoor unit to see whether such a address exists.
6 Select the mode number.
F Press the [ TEMP] buttons ( and ) to set the desired modenumber.(Only the selectable mode numbers can be selected.)
7 Select the setting content for the selected mode.
G Press the MENU button. The currently selected setting number willflash, so check the currently set content.
F Press the [ TEMP] buttons ( and ) to select the desired setting
number.
8 Register the settings you have made in steps 3 to 7 .
E Press the MODE button. The mode number and setting number will startto flash and registration starts.
The mode number and setting number will stop flashing and remain lit, indicating theend of registration.
* If " - - - " is displayed for both the mode number and setting number and " " flashes in the room temperature display area, a transmission error may have occurred.Check to see if there are any sources of noise or interference near the transmission path.
9 If you wish to continue to select other functions, repeat steps 3 to 8 .
0 Complete function selection.
A Hold down the FILTER TEST buttons simultaneously for at least two seconds.After a while, the function selection screen will disappear and the air condi-tioner OFF screen will reappear.
* Do not operate the remote controller for at least 30 seconds after completingfunction selection. (No operations will be accepted even if they are made.)
NoteIf a function of an indoor unit is changed by function selection after installation is complete, make sure that a " " mark, etc., is given in the "Check" column of Table1 to indicate the change.
Addressdisplay section
Unit numberdisplay section
Mode numberdisplay section
00 address
Indoor unit
Fan draftRemote controller
Main Sub
Outdoor unit
Designate operation
Example) When the address is set to 01 and the unit number is 02.
Mode numberdisplay section
Mode number 02 = Indoor temperature detection
Setting number display section Setting number 3 = Remote controller built-in sensorSetting number 1 = Indoor unit operating average
and ( mode 15 or more)
OC360--2.qxp 06.2.24 1:55 PM Page 53
54
By setting unit number with the button, specified indoor unit starts performing fan operation. Detect which unit is assigned to which number using this function. If unit number is set to AL, all the indoor units in same refrigerant system start performing fan operation simultaneously.
[Operating instructions]1 Check the function settings.2 Press the button twice continuously. → CHECK is lit and “00” blinks.
Press the temp button once to set “50”. Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
3 Set the unit number.Press the temp button to set the unit number. (Press “01” to specify the indoor unit whose unit number is 01.) Direct the wireless remote controller toward the receiver of the indoor unit and press the button.
* If a unit number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the unit number setting.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the unit number setting.
4 Select a mode.Press the temp button to set a mode. Press “24” to turn on the function that raises the set temperature by 4 degree during heat operation. Direct the wireless remote controller toward the sensor of the indoor unit and press the button.→ The sensor-operation indicator will flash and beeps will be heard to indicate the current setting number.Current setting number: 1 = 1 beep (one second)
2 = 2 beeps (one second each)3 = 3 beeps (one second each)
* If a mode number that cannot be recognized by the unit is entered, 3 beeps of 0.4 seconds will be heard. Reenter the mode number.
* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the mode number.
5 Select the setting number.Press the temp button to select the setting number. (02: Not available)Direct the wireless remote controller toward the receiver of the indoor unit and press the button.→ The sensor-operation indicator will flash and beeps will be heard to indicate the the setting number.
Setting number: 1 = 2 beeps (0.4 seconds each)2 = 2 beeps (0.4 seconds each, repeated twice)3 = 2 beeps (0.4 seconds each, repeated three times)
* If a setting number that cannot be recognized by the unit is entered, the setting will turn back to the original setting.* If the signal was not received by the sensor, you will not hear a beep or a “double beep” may be heard. Reenter the setting number.6 Repeat steps 4 and 5 to make an additional setting without changing unit number.7 Repeat steps 3 to 5 to change unit number and make function settings on it.8 Complete the function settings
Press button.* Do not use the wireless remote controller for 30 seconds after completing the function setting.
ON/OFF TEMP
FAN
VANEMODE
CHECK LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
CHECK
RESETSET CLOCK
h
CHECK
min
h
The flow of the function selection procedure is shown below. This example shows how to turn off the function that raises the set temperature by 4 degrees during HEAT operation . The procedure is given after the flow chart.
1 Check the function selection setting.
2 Switch to function selection mode.(Enter address "50" in troubleshootingmode, then press the HOUR button.)
Troubleshooting mode is the mode entered whenyou press the INSPECT button twice to display"INSPECT".
3 Specify unit No. "01" (since the function applies to unit 01).(Set address "01" while still in troubleshooting mode, then press the MINUTE button.)
Note: You can't specify the refrigerant address.
4 Select mode No. "24" (function that raises set temperature by 4 degrees during HEAT operation).(Set address "24" while still in troubleshooting mode, then press the HOUR button.)
6
Finished
8 End function selection mode.(End troubleshooting mode.)
YES
NO
Note: When you switch to function selection modeon the wireless remote controller's operationarea, the unit ends function selection modeautomatically if nothing is input for 10 minutesor longer.
5 Select setting No. "02" (OFF).(Set address "02" while still in troubleshooting mode, then press the HOUR button.)
Change unit No.
YES
NO
7
[Flow of function selection procedure]
9-1-2. Selecting functions using the wireless remote controller (Type C)Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger-ant system with wireless function. Address cannot be specified by the wireless remote controller.
h
min
OC360--2.qxp 06.2.24 1:55 PM Page 54
55
9-2. FUNCTION SELECTION OF REMOTE CONTROLLER
The setting of the following remote controller functions can be changed using the remote controller function selection mode.Change the setting when needed.
Item 11.Change Language("CHANGE LANGUAGE")2.Function limit("FUNCTION SELECTION")
3.Mode selection("MODE SELECTION")
4.Display change("DISP MODE SETTING")
Item 3 (Setting content)• Display in multiple languages is possible.
• Setting the range of operation limit (operation lock)• Setting the use or non-use of "automatic" operation mode• Setting the temperature adjustable range (maximum, minimum)• Selecting main or sub remote controller
* When two remote controllers are connected to one group, one controller must be set to sub.• Setting the use or non-use of clock function• Setting the timer type• Contact number display in case of error• Setting the telephone number• Setting the temperature unit (: or °F) to display• Setting the use or non-use of the display of indoor (suction) air temperature• Setting the use or non-use of the display of "Cooling" or "Heating" display during operation with automatic mode
Item 2Language setting to display
(1) Operation function limit setting (operation lock) ("LOCKING FUNCTION")(2) Use of automatic mode setting ("SELECT AUTO MODE")(3) Temperature range limit setting ("LIMIT TEMP FUNCTION")(1) Remote controller main/sub setting ("CONTROLLER MAIN/SUB")
(2) Use of clock setting ("CLOCK")(3) Timer function setting ("WEEKLY TIMER")(4) Contact number setting for error situation ("CALL.")
(1) Temperature display :/°F setting ("TEMP MODE :/°F")(2) Suction air temperature display setting ("ROOM TEMP DISP SELECT")(3) Automatic cooling/heating display setting ("AUTO MODE DISP C/H")
[Function selection flowchart] Refer to next page.[1] Stop the air conditioner to start remote controller function selection mode. [2] Select from item1. [3] Select from item2. [4] Make the setting.(Details are specified in item3) [5] Setting completed. [6] Change the display to the normal one. (End)
➔➔➔
➔ ➔
[Detailed setting][4] -1. CHANGE LANGUAGE settingThe language that appears on the dot display can be selected.• Press the [ MENU] button to change the language.1 Japanese (JP), 2English (GB), 3German (D), 4Spanish (E),5 Russian (RU), 6 Italian (I), 7Chinese (CH), 8 French (F)
[4] -2. Function limit(1) Operation function limit setting (operation lock)• To switch the setting, press the [ ON/OFF] button.1 no1 : Operation lock setting is made on all buttons other than
the [ ON/OFF] button.2 no2 : Operation lock setting is made on all buttons.3 OFF (Initial setting value) : Operation lock setting is not made* To make the operation lock setting valid on the normal screen, it is
necessary to press buttons (Press and hold down the [FILTER]and [ ON/OFF] buttons at the same time for two seconds.) onthe normal screen after the above setting is made..
(2) Use of automatic mode settingWhen the remote controller is connected to the unit that has auto-matic operation mode, the following settings can be made.• To switch the setting, press the [ ON/OFF] button.1 ON (Initial setting value) : The automatic mode is displayed when
the operation mode is selected.2 OFF : The automatic mode is not display
when the operation mode is selected.
[4] -3. Mode selection setting(1) Remote controller main/sub setting• To switch the setting, press the [ ON/OFF] button.1 Main : The controller will be the main controller.2 Sub : The controller will be the sub controller.
(2) Use of clock setting• To switch the setting, press the [ ON/OFF] button.1 ON : The clock function can be used.2 OFF: The clock function cannot be used.
(3) Timer function setting• To switch the setting, press the [ ON/OFF] button (Choose one of
the followings.).1 WEEKLY TIMER (initial setting on MA deluxe):
The weekly timer can be used.2 AUTO OFF TIMER: The auto off timer can be used.
SIMPLE TIMER (Default setting on MA smooth):The simple timer can be used.
4
3
TIMER MODE OFF: The timer mode cannot be used.* When the use of clock setting is OFF, the "WEEKLY TIMER" cannot be
used.
(4) Contact number setting for error situation• To switch the setting, press the [ ON/OFF] button.1 CALL OFF: The set contact numbers are not displayed in case of error.2 CALL **** *** **** : The set contact numbers are displayed in case
of error.
(3) Temperature range limit settingAfter this setting is made, the temperature can be changed within the set range.• To switch the setting, press the [ ON/OFF] button.1 LIMIT TEMP COOL MODE :
The temperature range can be changed on cooling/dry mode.2 LIMIT TEMP HEAT MODE :
The temperature range can be changed on heating mode.3 LIMIT TEMP AUTO MODE :
The temperature range can be changed on automatic mode.4 OFF (initial setting) : The temperature range limit is not active.* When the setting, other than OFF, is made, the temperature range limit setting
on cooling, heating and automatic mode is made at the same time. Howeverthe range cannot be limited when the set temperature range has not changed.
• To increase or decrease the temperature, press the [ TEMP ( ) or ( )] button.• To switch the upper limit setting and the lower limit setting, press the [ ]
button. The selected setting will flash and the temperature can be set. • Settable range
Cooling/Dry mode : Lower limit: 19 : ~ 30: Upper limit: 30 : ~ 19:Heating mode : Lower limit: 17 : ~ 28: Upper limit: 28 : ~ 17:Automatic mode : Lower limit: 19 : ~ 28: Upper limit: 28 : ~ 19:
CALL_ : The contact number can be set when the display is asshown on the left.
• Setting the contact numbersTo set the contact numbers, follow the following procedures.Move the flashing cursor to set numbers. Press the [ TEMP. ( ) and( )] button to move the cursor to the right (left). Press the [ CLOCK( ) and ( )] button to set the numbers.
[4] -4. Display change setting(1) Temperature display :/ F setting• To switch the setting, press the [ ON/OFF] button.1: : The temperature unit : is used.2 F: The temperature unit
°
° °F is used.
(2) Suction air temperature display setting• To switch the setting, press the [ ON/OFF] button.1 ON : The suction air temperature is displayed.2 OFF: The suction air temperature is not displayed.
(3) Automatic cooling/heating display setting• To switch the setting, press the [ ON/OFF] button.1 ON : One of "Automatic cooling" and "Automatic heating" is displayed
under the automatic mode is running.2 OFF: Only "Automatic" is displayed under the automatic mode.
OC360--2.qxp 06.2.24 1:55 PM Page 55
56
OFF
on1
on2
OFF
ON
OFF
ON
OFF
OFF
CALL-
ON
OFF
ON
OFF
:
°F
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION CLEAR
TEST
TEMP.
MENU
BACK DAYMONITOR/SET
CLOCK
ON/OFF
F
E
G
C D
H
B
A
I
G
G
G
G
G
G
E
E
G
G
G
G
E
G
E
G
G
G
G
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
D
EN
GE
ES
RU
IT
ZH
FR
JA
Hold down the E button and press the D button for 2 seconds.
Hold down the E button and press the D button for 2 seconds.
Remote controller function selection mode
E Press the operation mode button.G Press the TIMER MENU button.D Press the TIMER ON/OFF button.
Item1 Item2 Dot display
Item3
Room air temperature is not displayed.
One of "Automatic cooling" and "Automatic heating" is displayedunder the automatic mode is running. (Initial setting value)
Only "Automatic" is displayed under the automatic mode.
Normal display(Display when the air condition is not running)
ChangeLanguage
Functionselection
Modeselection
Displaymode setting
Operation lock setting is not used.(Initial setting value)
Operation lock setting is except On/Off buttons.
Operation lock setting is All buttons.
The automatic mode is displayed when the operation mode isselected. (Initial setting value)
The automatic mode is not displayed when the operation mode is selected.
The temperature range limit is not active. (Initial setting value)
The temperature range can be changed on cooling/dry mode.
The temperature range can be changed on heating mode.
The temperature range can be changed on automatic mode.
The remote controller will be the main controller. (Initial setting value)
The remote controller will be the sub controller.
The clock function can be used. (Initial setting value)
The clock function can not be used.
Weekly timer can be used. (Initial setting value)
Auto off timer can be used.
Simple timer can be used.
Timer mode can not be used.
The set contact numbers are not displayed in case of error.(Initial setting value)
The set contact numbers are displayed in case of error.
The temperature unit : is used. (Initial setting value)
The temperature unit °F is used.
Room air temperature is displayed. (Initial setting value)
Flowchart of Function SettingSetting language (English)
OC360--2.qxp 06.2.24 1:55 PM Page 56
57
4-WAY AIR FLOW SYSTEM10
1. Placement of the air outlets• For this grille, the blowout direction comes in 11 patterns.
Also,by unit function setting by the remote controller, you can adjust the air flow and speed. Select the settings from Tableaccording to the location in which you want to install the unit.
1) Decide on the pattern of the airflow direction.
Blo
wou
t dire
ctio
npa
ttern
4-direction<Table 1> 3-direction 2-direction Note1.For 3 and 2-directional,please use the air outletshutter plate (option).
Pattern 1 Factory setting Pattern 4 One air outletfully closed
Pattern 6 Two air outletfully closed
2. Fresh air intake (Installation of site)• At the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and whenrequired.
Note : Be sure to add135mm to the dimensions in the diagram that are marked with a “w” if installing a multi function casement(Option)
2) According to the number of air outlets and height of the ceiling to install the unit, be sure to setthe unit function setting by the remote controller.Correspondence of ceiling heights to numbers of air outlets.
Fresh air intake hole
Fresh air intake hole diagram
3 - {2.8Burring hole
{125Burring hole pitch
{100(Cut out hole)
Refrigerant pipe Drain pipe Ceiling surface
120_
120_
w15
8
4 direction 2.7m
3.0m
3.0m
3.3m
3.5m
3.5m
3.3m 3.5m —
Ceiling height & discharge direction(Unit : m)
3 direction
2 direction
Standard High ceiling 1 High ceiling 2
4 direction 3.2m
3.6m
3.6m
4.0m
4.2m
4.2m
4.0m 4.2m —
3 direction
2 direction
Standard High ceiling 1 High ceiling 2
PLH-3AAK(H)
PLH-4, 5, 6AAK(H)
OC360--2.qxp 06.2.24 1:55 PM Page 57
58
Static pressure [Pa]
Air flow [m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6
Static pressure [Pa]
Air flow [m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6
Static pressure [Pa]
Air flow [m3/min]
50
-50
-100
-150
-200
01 2 3 4 5 6
Static pressure [Pa]
Air flow[m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6 7 8 9
Static pressure [Pa]
Air flow[m3/min]
2 intakes
1 intake
50
-50
-100
-150
-200
01 2 3 4 5 6 7 8 9
Static pressure [Pa]
Air flow [m3/min]
50
-50
-100
-150
-200
01 2 3 4 5 6 7 8 9
ll PLH-3AAK(H)Multifunction casement + Standard filter
22 PLH-4 · 5 · 6AAK(H)
Multifunction casement + High efficiency filter
Taking air into the unit
Multifunction casement + Standard filter Multifunction casement + High efficiency filter
Taking air into the unit
3. Fresh air intake amount & static pressure characteristics
Q
0
BA C
1 Curve in theleft praphs.
Duct characteristicsat site
Q
AE
C
2
Q
Qa
AD
3
Q…Planned amount of fresh air intake
A…Static pressure loss of fresh airintake duct system with air flowamount Q
B…Forced static pressure at air condi-tioner inlet with air flow amount Q
C…Static pressure of booster fan withair flow amount Q
D…Static pressure loss increaseamount of fresh air intake dust sys-tem for air flow amount Q <Pa>
E…Static pressure of indoor unit with airflow amount Q
Qa…Estimated amount of fresh airintake with out D <m3/min>
<m3/mim>
<Pa>
<Pa>
<Pa>
<Pa>
How to read curves
OC360--2.qxp 06.2.24 1:55 PM Page 58
59
5. BRANCH DUCT(Installation atsite)Discharge by branch duct becomes possible by installing a branch duce at site. Knockout holes on the wall panel of the indoorunit must be removed.
5-1 Branch Duct Installation ProcedureAt the time of installation, use the duct holes (cut out) located at the positions shown in following diagram, as and whenrequired.
Note :The figure marked with ww in the drawing represent the dimensions of the main unit excluding those of the optionalmulti function casement.When installing the optional multi function casement, add 135 mm to the dimensions marked on the figure.When installing the branch ducts, be sure to insulate adequately. Otherwise condensation and dripping may occur.
Fresh air intake hole
Refrigerant pipe Drain pipe
Branch duct hole(Cut out hole)
Branch duct hole diagram (view from either side)
Branch duct hole
{175Burring hole pitch
{150Cut out hole
14 - {2.8Burring hole
350
90
70_
100 100 90
100
130
w15
5
w16
7
Branch duct hole
Fig 1. Branch duct mounting position Fig 2. Branch duct connection details
Multiple remotecontroller adapterPAC-SA88HA-E
Indoor controller board
Distance between indoorcontroller board and relaymust be within 10m.
CN51
Be sure to secure insulationmaterial by tape and such
5 Green
Yellow
OrangeConnector (5P)
Package sideMultiple remotecontroller adapterPAC-SA88HA-E
Be sure to secure insulationmaterial by tape and such
Installation at site
CN51onindoorcontrollerboard Red
Brown
1 MB
~
4. Interlocking operation method with duct fan (Booster fan)
●Whenever the indoor unit is operating, the duct fan alsooperates.(1)Connect the optional multiple remote controller
adapter(PAC-SA88HA-E)to the connector CN51 on theindoor controller board.
(2)Drive the relay after connecting the 12V DC relaybetween the Yellow and Orange connector lines.
(w)Use a relay under 1W.MB: Electromagnetic switch power relay for duct fan.
X: Auxiliary relay (12V DC LY-1F)
OC360--2.qxp 06.2.24 1:55 PM Page 59
60
6. Air flow & Static pressure characteristics of Branch Duct (Air flow( Fan speed) at “Standard”)
Staticpressure
[Pa]
Air flow [m3/min]
30
20
10
01 2 3 4 5 6
Hi
Lo
Staticpressure
[Pa]
Air flow [m3/min]
30
20
10
01 2 3 4 5 6
HiLo
Staticpressure
[Pa]
Air flow [m3/min]
50
40
30
20
10
01 2 3
Hi
Lo
4 5 6 7 8 9 10
Staticpressure
[Pa]
Air flow [m3/min]
50
40
30
20
10
01 2 3
Hi
Lo
4 5 6 7 8 9 10
Staticpressure
[Pa]
Air flow [m3/min]
50
40
30
20
10
01 2 3
Hi
Lo
4 5 6 7 8 9 10
Staticpressure
[Pa]
Air flow [m3/min]
50
40
30
20
10
01 2 3
Hi
Lo
4 5 6 7 8 9 10
Rounded ductPLH-3AAK(H)
PLH-4AAK(H)
PLH-5, 6AAK(H)
Staticpressure
[Pa]
Air flow [m3/min]
30
40
50
60
20
10
01 2 3 4 5 6 7 8 9
Hi
Lo
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100
4030
20100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12 13 14
Staticpressure
[Pa]
Air flow [m3/min]
50
607080
90
100
4030
20100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12 13 14
PLH-3AAK(H)
PLH-4AAK(H)
3 direction airflow (Horizontal vane)Angled duct
PLH-5, 6AAK(H)
Staticpressure
[Pa]
Air flow [m3/min]
30
40
50
60
20
10
01 2 3 4 5 6 7 8 9
Hi
Lo
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100
4030
20100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12 13 14
Staticpressure
[Pa]
Air flow [m3/min]
50
60
708090
100
403020100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12 13 14
PLH-3AAK(H)
PLH-4AAK(H)
PLH-5, 6AAK(H)
Rounded duct
4 direction airflow (Horizontal vane)Angled ductPLH-3AAK(H)
PLH-4AAK(H)
APLH-5, 6AAK(H)
OC360--2.qxp 06.2.24 1:55 PM Page 60
61
Staticpressure
[Pa]
Air flow [m3/min]
30
40
50
60
70
80
90
100
20
10
01 2 3 4 5 6 7 8 9 10 11
Hi
Lo
Staticpressure
[Pa]
Air flow [m3/min]
30
40
50
60
70
80
90
100
20
10
01 2 3 4 5 6 7
Hi
Lo
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100110120
403020100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12131415 16
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100110120
403020100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12131415 16
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100110120
403020100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12131415 16
Staticpressure
[Pa]
Air flow [m3/min]
5060708090
100110120
403020100
1 2 3
Hi
Lo
4 5 6 7 8 9 10 11 12131415 16
Rounded ductPLH-3AAK(H) PLH-3AAK(H)
PLH-4AAK(H) PLH-4AAK(H)
2 direction airflow (Horizontal vane)Angled duct
PLH-5, 6AAK(H) PLH-5, 6AAK(H)
OC360--3.qxp 06.2.24 1:52 PM Page 61
62
SYSTEM CONTROL11
11-1. VARIETY OF SYSTEM CONTROL FUNCTIONS
System Name System Diagram FeaturesParts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
Indoor unit
RemoteController
Outdoorunit
A.Remote control-ler operation(Standard)
B.Remote control-ler operation
Use of two con-trollers enablesoperation of the airconditioner bothfrom a distanceand nearby.
C.Group controloperation
Uses one remotecontroller to con-trol multiple airconditioners withthe same settingssimultaneously.
D.Remote/handheldcombined controloperation
Allows start/stopof the air condi-tioner from a dis-tance, and prohib-its/permits start/stop from remotecontrollers.
E.Operation byexternal signal
F.Control and remotedisplay by externalsignal (extractionof monitor signal)
Enables you todisplay the op-eration state andcontrol start/stopfrom a distance.
• There are two types of remote controllers: wired typeand wireless type.
• Simultaneous twin indoor units are started or stoppedsimultaneously.
• Up to two remote controllers can be connected toone group.
• Simultaneous twin units are counted as each unit.• Operation control by the latest command (last en-
tered priority)• Wired and wireless remote controllers can be com-
bined as a pair.
• One group can consist of up to 16 indoor units, andthey can be started sequentially by connecting theremote controller to them and assigning an addressto each inter face.
• Simultaneous twin units are counted as one unit.• All the units belonging to the same group are oper-
ated in the same mode, but thermostats can beturned ON/OFF individually for each indoor unit.
• Up to two remote controllers can be connected.
• All the air conditioners can be turned ON/OFF collectivelyfrom a distance.
• Operation can be switched between the remote operat-ing panel and handheld controller.
• Operations (e.g., temperature adjustment, airflow, air-flow direction) except for start/stop operations can beperformed even if the remote controller is being oper-ated.
• In the case of simultaneous twin, triple and quad units,connect the controller to one indoor unit only. If con-nected to two or more indoor units, an error (operationstop) may occur.
• Control by an external timer is possible by connecting it.
• Use of optional "remote operation adapter" enablesremote control via relay. (Level signal)
Extraction of non-voltage contact output• Use of optional "remote operation adapter" and
"remote display panel" (installation required) pro-vides non-voltage contact outputs of signals (opera-tion, error) and operation/stop input function.
Extraction of DC12 V contact output• Use of optional "remote display adapter" and "re-
mote display panel" (installation required) providesDC12 V contact outputs of signals (operation, error)and operation/stop input function.
Indoorunit
RemoteController
* One of the wired remote con-trollers must be set as a subremote controller.
IndoorunitOutdoorunit
Inter face
RemoteController
Indoor unit
Remote Controller
Relay box
Remote operating panel
Remotedisplay kit
Remote display (operation, error)
Indoor unit
Remote Controller
Wired remote controller (addi-tional)(PAR-21MAA)For models PK(H)-GAKL(H)/FAKL(H), use remotecontroller (PAR-21MAAT-E).
* For models equipped with a ter-minal block.
Inter face MAC-397IF-E
Remote ON/OFF adapter(PAC-SE55RA-E)Relay box(Installation required)Remote operating panel(Installation required)
Remote ON/OFF adapter(PAC–SE55RA-E)
A-control operation display kit(PAC-SF40RM-E)Remote display panel(Installation required)
Remote display adapter(PAC-SA88HA)Remote display panel(Installation required)
OC360--3.qxp 06.2.24 1:52 PM Page 62
63
Outdoorunit
Indoorunit
SubMain
RemoteController
System Name System Diagram FeaturesParts Required in Addition to Standard System
Components (Indoor/Outdoor Units, Remote Controller)
G. Timer operation
Enables controlof start and stop.
* For control by external timer,refer to Remote/handheld com-bined control op-eration".
H.Interlock opera-tion with periph-eral equipment
Enables control ofMitsubishi Lossnayventilator by remotecontroller.
I.Rotation
• Weekly timer:In addition to ON/OFF, up to eight temperaturepatterns can be set for each day of the week.
* Only one timer can be selected; the auto off, simpleand weekly timers cannot be combined.
• Simple timer: Start and stop operations can each beperformed once within 72 hours (canbe set in 1-hour increments).
• Auto off timer: Operation is stopped when the presettime elapses following the start ofoperation.The time can be set from 30 minutesto 4 hours in 30-minute increments.
* Only one timer can be selected; the simple and autooff timers cannot be combined.
• Connecting a Lossnay ventilator and an indoor unitenables control of interlock/solo ventilation opera-tion and airflow.(Only the microcomputer type Lossnay ventilatorcan be used.)
•
•
MA Remote controller(PAR-21MAA)
Indoor unit
RemoteController
Lossnayventilator
When abnormality occurs while operating, it changes into operating the back up unit, and operating is continued.(Unit function Mode No. 20 setting No.3 , Indoor controller board SW-5-4 ON) Main / Sub settingMain : Indoor controller board SW5-3 : OFFSub : Indoor controller board SW5-3 : ONEach system operates alternately for 24 hours or 168 hours.(Unit function Mode No. 20 setting No.1: 24 hours/No.2 : 168 hours, Indoor controller board SW 5-4 ON)Main / Sub settingMain : Indoor controller board SW5-3 : OFFSub : Indoor controller board SW5-3 : ON
This system can correspond only bythe pattern of two refrigerant groupby 1 : 1 (indoor and outdoor unit combination) systems.
OC360--3.qxp 06.2.24 1:52 PM Page 63
64
11-2. ONE REMOTE CONTROLLER (STANDARD) OPERATION(1) One Wired Remote Controller(OC: Outdoor unit IC: Indoor unit R: Remote controller (for wireless type: optical receiver adapter)
Slim Air Conditioners System
Remote controller connection circuit (Controller cable)
Outdoor unit OC
Indoor unit IC
Wired remote controller R
Indoor/Outdoor connection cable
Remote controller cable
OC
IC-1
R
IC-2
3
2
OC
IC-1
R
3
2
Standard 1:1 Simultaneous Twin Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
(Reference)11 If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions. 22 Electrical wiring diagram
OC IC
12
LN
Power source wiring
123
12
R
(No polarity)
Outdoor unit Indoor unit Remote controller
Power source wiring
(Polarity)
123
• Power supply terminal block L, N• Indoor/outdoor connection cable terminal
block 1,2 (Polarity)• Remote controller cable terminal block
1,2 (No polarity)
(2) Wireless remote controller
Slim Air Conditioners System
Remote controller optical receiver section connection circuit
Outdoor unit OC
Indoor unit IC
Wireless remote controller receiver section R'
Indoor/Outdoor connection cable
OC
IC-1
R'
IC-2
3
29
OC
IC-1
R'
3
9
Standard 1:1 Simultaneous Twin
Wireless remotecontroller cable
Wireless remotecontroller cable
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
(Reference)11 If simultaneous twin connect the remote controller to indoor units. Can control all functions of the indoor unit even if dif-
ferent models (different types) are mixed. Note that there may be some restrictions of the functions. 22 Electrical wiring diagram
CN90
Controller board
Indoor unit IC
9
CNB
1 2
Wireless remote controller optical receiver section R’
Remote controller cable terminal block
OC360--3.qxp 06.2.24 1:52 PM Page 64
65
11-3. TWO-REMOTE CONTROLLER OPERATION(1) Two Wired Remote Controllers
(R: Wired remote controller)
Slim Air Conditioner System Standard 1:1 Simultaneous Twin
[Reference]1 In the case of free component multi type systems consisting of simultaneous twin units, connect the remote controllers to each indoor unit.
All the functions of the connected indoor units can be controlled even if the system consists of different models. However, some function may berestricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiring3 Set one of the remote controllers as the main controller (factory setting) and the other as the sub controller using the remote controller's function
selection.
(2) Two Wireless Remote Controllers
Slim Air Conditioner System Standard 1:1 Simultaneous Twin
Remotecontrollerconnectioncircuit(Controllercable)
Outdoor unitOC
Indoor unit IC
Wired remotecontroller R
Outdoor unitOC
Indoor unit IC
Wired remotecontroller R
OC
3
2
IC
R-1 R-2
2Remotecontrollercable
Indoor/outdoorconnection cable
OC3
2
IC-1 IC-2
R-1 R-2
2
2
2
OC
2
IC
R-1 R-2
3
OC
2
IC-1 IC-2
R-1 R-2
2
3
Remotecontrollerreceiverconnectioncircuit
Outdoor unitOC
Indoor unit IC
Wireless remote controller re-ceiver section R'
—
OC3
IC-1 IC-2
R'-1 R'-2
9 9Receiverconnectioncable
Indoor/outdoorconnection cable
* Numbers given in ( ) apply when power is supplied to the indoor and outdoor units separately.[Reference]1 In the case of free component multi type systems consisting of simultaneous twin units, connect two wireless remote controller receivers
(one each) to any two of the indoor units. All the functions of the connected indoor units can be controlled even if the system consists of differenmodels. However, some functions may be restricted.
2 In the case of free component multi type systems consisting of simultaneous twin units, the indoor units should be connected by crossover wiringIn the case of "standard 1:1" connection, it is not possible to connect two remote controller receivers to the indoor units. However, with system3
consisting of simultaneous twin units, it is possible to connect a remote controller receiver to two indoor units. In this case, all the pair numberwill be "0" (factory setting, no change necessary), and all the units will be turned ON/OFF simultaneously.
4 When using two or more wireless remote controllers, the display contents on the remote controllers may differ from the actual settings, since theoperation made last by any of the remote controllers will be effective.
(3) One Wired and One Wireless Remote Controller(R: Wired remote controller, R': Wireless remote controller receiver)
Slim Air Conditioner System Standard 1:1 Simultaneous Twin
Remotecontrollerreceiverconnectioncircuit
Outdoor unitOC
Indoor unit IC
•Wired remote controller R•Receiver R'
OC
3
2
IC
R R'
9Remotecontrollercable
Indoor/outdoorconnection cable
Receiverconnectioncable
OC3
2
IC-1 IC-2
R R'
9
(R': Wireless remote controller receiver)
2
2
2
Remote controller cable
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
Indoor controller board switch setting
SW5-3
OFF
ON
Indoor unit IC
IC-1 (Main)
IC-2 (Sub)
OC360--3.qxp 06.2.24 1:52 PM Page 65
66
2.Connecting the remote control interface with each system(For details on each system, see the relevant instruction manual.)
• Replace the interface unit mounting cord clamp with a supplied mounting cord clamp based on the thickness of theconnecting cable used for each system.
• The cables connected to the Indoor unit should be mounted on or near the Indoor unit. If the connecting cable is not securely mounted, the connector may detach, break, or malfunction.
• Set the interface dip switch (SW500–502) settings before turning on the power.• If the interface dip switch (SW500–502) settings are not set correctly, the system will not function properly.
Connecting cable for each system
Mounting screws 4 o 16
Electrical wire mountingbracket
Mounting cord clamp
Mounting screws 4 o 10
Mounting cord clamp
Mounting screws (black) 3.5 o 12Interface unit mounting cord clamp or mountingcord clamps
11-4. GROUP CONTROL OPERATION (COLLECTIVE OPERATION AND CONTROL OF MULTIPLE REFRIGERANT SYSTEMS (2 to 16))
●
●
●
●
Group control can be operated by using MAC-397IF-E.
The setting of wired remote controller is subjected to variation according to the function of the indoor unit.
(for mode operation, setting temperature, fan step, air direction)
The display of remote controller and operating the indoor unit might be different.
Neither the test run nor the function setting can be done by MA remote controller connected with MAC-397IF-E.
1.Connecting the MA& CONTACT TERMINAL Interface to the Indoor Unit
• Connect the interface unit and the indoor control board using the connecting cable that came with the interface.• Extending or shortening the connecting cable that comes out of the interface may cause it to malfunction. Also,
keep the connecting cable as far as possible away from the electrical wires and ground wire. Do not bundle them together.
Indoor control board
CN105or
CN92
Connect the connecting cable that comes with theinterface unit to the connectorCN105 or CN92 on the indoor control board.
INDOOR
OC360--3.qxp 06.2.24 1:52 PM Page 66
67
Use as a Wired Remote Control (Using the MA Remote Controller)
Note:
1. Be sure the Auto Heating/Cooling Display Setting on the MA remote controller is set to OFF before use.• For information on how to set the Auto/Heating Cooling Display Setting, see the MA remote controller
instruction manual.• The actual operating status of the unit may differ from what is shown on the remote controller display
2. A test run cannot be initiated using the test run switch on the MA remote controller..3. The horizontal vanes on the unit cannot be operated using the louver switch.4. The range of room temperature indication is between 10: and 38:.
CN560
TB580
2
1
2
A
B
Indoor unit
Remote control cord that came withthe MA remote controller (Non polarity)
Dip switch settings
SW500 does not have to be set.
SW501:SW501- No. 1-4: Refrigerant address• Set this switch when multiple indoor units (and remote control interfaces) are connected to a single MA remote controller.• Always start the refrigerant address at "0".
1
Even when connecting multiple outdoor units, set a different refrigerant address for each indoor unit.
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
1Outdoor unit2Outdoor unit3Indoor unit4Interface5MA remote controller
Refrigerantaddress
0
1
2
15
SW501- No. 5–6
ON
5 6
When the model of Mr. SLIM exists in the same group, it sets it to turning ON.
Set them to ON only when using the room temperature sensor installed in the MA remote controller.* This can be switched when an accurate room temperature cannot be detected by the air conditioner unit.PLH-AAK(H) series do not have a room temperature sensor on their MA remote controllers.
No. 5 should normally be set to OFF.Under the following conditions, No.6 should normally be set to ON.
Interface unit
Refrigerantaddress "0"
Refrigerantaddress "1"
Refrigerantaddress "2"
MA remote controller(PAR-21MAA)* PAR-20MAA cannot be used
with this interface.
1 1 2
3 3 3 3
4
5
4 4
OC360--3.qxp 06.2.24 1:52 PM Page 67
68
SW501: Settings to accommodate MA remote controller and settings to accommodate outdoor units
SW No.
No. 1
No. 2
No. 3
No. 4
Functions OFF ON Comments
Only specify these settings when connecting anMA remote controller.
Functions
Room temperature detector
The model of Mr. SLIM exists in the same group.
This should normally be set to ON.
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
Refrigerant address 0
Refrigerant address 1
Refrigerant address 2
Refrigerant address 3
Refrigerant address 4
Refrigerant address 5
Refrigerant address 6
Refrigerant address 7
Refrigerant address 8
Refrigerant address 9
Refrigerant address 10
Refrigerant address 11
Refrigerant address 12
Refrigerant address 13
Refrigerant address 14
Refrigerant address 15
OFF
Indoor unit
Not mixed
ON
Remote control
Mixed
Comments
This should normally be set to OFF.
SW No.
No. 5
No. 6
OC360--3.qxp 06.2.24 1:52 PM Page 68
69
* Fan speed 2 step model : An actual fan speed is 2 step though the display of remote controller becomes 4 step or 3 step.
3. Test Run (Check Operations)
Interface status monitorYou can check the status of the interface by the LED lamp on the interface unit board.
LED lamp no.
LED521
LED522
LED523
Lamp off
DC 12 V is not being supplied from theair conditioner.
Device is not communicating properlywith the air conditioner.
Device is not communicating properlywith the MA remote controller.
Lamp on
DC 12 V is being supplied from the airconditioner.
–
–
Blinking
–
Blinking at approx. 1 second intervals: Device iscommunicating normally with the air conditioner.
Blinking at approx. 8 second intervals: Device is com-municating normally with the MA remote controller.
* Use the table above to check the device operations.
SW502 : Air Conditioner Function SettingsSW No.
No. 1
No. 2
No. 3
No. 4
No. 5
No. 6
No. 7
No. 8
Functions
Cooling only type/ Heat pump type
Auto mode
Fan speed
Vane
Swing
Not in use
Fan mode
OFF
Heat pump type
Not available(setting No.3 disabled)
Available(unit)
Available
Available
–
Not available
ON
Cooling only type
Available(setting No.3 enabled)
Available(remote controller)
Not available
Not available
–
Available
Comments
Set to OFF.
Permanently set to OFF.
4 speeds 3 speeds (2-speedmodel set ON)
When operating a 2-speed model with the 3-speed setting (ON), the MA remote controller display will indicate 3 fan speeds.The table below shows the displays and the actual outputs at that time.
Display Meaning Indoor unit output
Low speedLow speed
Medium speed High speed
High speed
Set the mode in accordance with the operation manual for the indoor unit.
Heat pump type : Set to ON.Cooling only type : Set to OFF.
The Vane function of either of indoor unit :When the function is provided, it is Available (OFF).When the function is not provided, it is Not available (ON).
The Swing function of either of indoor unit :When the function is provided, it is Available (OFF).When the function is not provided, it is Not available (ON).
Set to ON.
High speed
4. Mounting the Remote Control Interface Unit
The Interface unit should be placed in a location where the connecting cable from the interface can reach an indoor unit.The device will not function properly if the connecting cable is extended so the connecting cable should not be extended.Mount the interface unit securely to a pillar or wall using 2 or more screws.
■ When Using Wall Mounting Brackets
1 Attach the wall mounting brackets to the interface unit using 2 mounting screws.
2 Mount the unit to a pillar or wall using 2 mounting screws.
Interface unit Wall mountingbrackets
Mounting screws Mounting screws
Mounting screws
Cord clamp forwiring
OC360--3.qxp 06.2.27 9:00 AM Page 69
70
■ When Mounting Directly to a Wall
Mount the interface unit case to the wall using the mountingscrews.
Interface casemounting screws
Mountingscrews
When mounting the interface unit inside a ceilingor wall, install an access door to facilitate mainte-nance.
When the interface unit is mountedabove an indoor unit, it should bepositioned 40 mm or more away from theunit to ensure that ceiling grills can beremoved.
40 mm or more
Attach the interface unit connecting cable here.Store extra connecting cable in the ductwork spacebehind the indoor unit.
* If there is any slack in the connecting cable, use afastener to keep it in place.
* When mounting the interface unit using a cushioningmaterial , be sure to mount it in a location where it will not fall.
Interface unit
Cushioning material
OC360--3.qxp 06.2.24 1:52 PM Page 70
71
11-5. POWER OUTAGE AUTOMATIC RECOVERY OPERATION• Whenever a power outage or switching of the power supply causes the power supply of an operating air conditioner to go
from OFF to ON, this function will automatically restore the operation of the air conditioner to its previous operating mode.w If the power is turned from OFF to ON when the air conditioner is not in operation, the air conditioner will not automatically
be turned on. However, the timer operation will be cancelled if the air conditioner is in timer operation (including when theunit is waiting for its start time). Setting for timer operation must be performed once again.
• If there is a momentary power outage of less than one second while the air conditioner is in operation, there may not be aclear determination of whether or not there was a power failure. When it has been determined that there has been a powerfailure, recovery will take approximately four minutes after the power is restored. Please wait. (Once "PLEASE WAIT" hasappeared on the display, a protection system will operate to prevent the unit from restarting for three minutes.) When it has been determined that there has been no power failure, operation will continue as is.
• Settings can be made by function selections from the remote controller. • When there is group control, selection of all refrigerants is required.
11-6. INDIVIDUAL CONTROL OPERATION FROM A SEPARATE ROOM• By simply centralizing the remote controllers installed in each room in a separate control room, individual control or central-
ized monitoring of the air conditioners in each room can be attained.• Air conditioner control can be performed up to a total of 500 meters away by connecting the indoor units and remote con-
trollers with 0.3 to 1.25 mm2 2-core cable.
• If a remote controller is installed in a room and control room, refer to the section on operating with two remote controllers.
Indoor unit Indoor unit Indoor unit
Remote controller
Control room room 1 room 2 room 3
11-7. COMBINED REMOTE/HAND-HELD CONTROL• Operation/remote controller prohibit/ stop can be controlled from a remote location by routing the remote stop/start adapter
(PAC-SE55RA-E sold separately) through the relay box installed on site. When this remote control is cancelled, the hand-held remote controller can be used for operating and stopping the air conditioner.1. Basic system wiring• Use the remote start/stop adapter (PAC-SE55RA-E) and connect the "Start/Stop Circuit From Remote Location" that comes
from the relay box and remote/hand-held selection switch and connect it to the CN32 connector on the printed circuit boardfor the indoor unit
W The AC for the control room is usually disconnected from the remote/hand-held control system.
Indoor unit
Relay box Relay box Relay box
Indoor unit
Control circuit power supply
Indoor unit Indoor unit
Remote controller
Remote/Hand-held selection switch
Control room W room 1 room 2 room 3
Remote controller
Remote controller
Remote controller
11 Match the rated power supply voltage of the remote/hand-held selection switch and relay (X2) with the power supply for thecontroller.
22 When performing group control of multiple outdoor unit using a timer, be sure to arrange the timer so that all units do not startat the same time. If this is not performed, all of the units will start at one time creating an over current that will cause the circuitbreaker to operate.
33 An on-delay system is one that includes specifications for operating a limited time when an on signal is received and has a tem-porary off timer for recovery operations.
44 Use a connecting relay when the wiring length exceeds 10 meters, such as when performing remote wiring. If this is not pro-vided, abnormal operation will occur.
<Points of precaution>
(1). System diagram
OC360--3.qxp 06.2.24 1:52 PM Page 71
72
Note: When using group address, connect to refrigerant address "0" on the inside.
Control circuitpower supply
Dedicated short circuit prevention device
Remote/Hand-held selection switch
No.1 unitrelay box
No.2 unitrelay box 3 Relay box2 Adapter for
remote start/stop1 Remote/Hand-held selection switch
T Timer (On delay system)X Relay
Model PAC-SE55RA-E (Sold separately)
(Example)Single polarity single-throw switch (125V rating)
To next unit
T
Brown
Red
X2 X2
TOne method of easily distinguishing the on/off status of SW1 and SW2 is to use together with a "illuminated switch R" or pilot lamp.
T
X2
SW1
SW2
T
X2
Orange OrangeBrown
Red
• Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
• Starting/stopping with remote controller disabled.• AC is in operation.• Starting/stopping by remote operation enabled.
• Starting/stopping with remote controller disabled.
• Starting/stopping by remote operation enabled.
• Starting/stopping with remote controller disabled.• AC is in operation.• Starting/stopping by remote operation enabled.
Remote control OFFON
Description of functions
OFFON
SW1
SW2 OFFONRemote/Hand-held selection switch
(2). Basic wiring diagram (3). Part specifications
2. Examples of system applicationsIn any of the following examples, there is a five to six second delay from the time the operating command is issued until theoperation begins.11 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping by
the remote controller is to be prohibited. Indoor unit circuit board
CN32
Orange
Red
BrownOn site wiring On site wiring
On site wiring
Timer
Timer
For remote operation
On site wiring
On site wiring
This is not used.Protect exposed wire by wrapping with insulating tape
On site wiring
SW1
Indoor unit circuit board
CN32
Orange
Red
Brown
SW1
SW2
Indoor unit circuit board
CN32
Orange
Red
BrownSW2
Indoor unit circuit board
CN32
Orange
Red
BrownSW2
Indoor unit circuit board
CN32
Orange
Red
Brown
Indoor unit circuit board
CN32
Orange
Red
BrownSW2
For remote operation
For timer operation
22 This is when starting and stopping is performed by remote operation or external timer and when starting and stopping bythe remote controller is to be separated.
33 This is when starting and stopping is performed by remote operation and then allowing starting or stopping by remote con-trol at any time.
44 This is when permitting or prohibiting operation by remote controller is performed by external circuit.
If SW2 is on, operation by remote controller cannot beperformed.If SW2 is off, operation by remote controller is permitted.
Use momentary switch for SW2. (Manual operation/automatic recover switch ontime is more than one second.)Press SW2 (on time is more than one second) and operation starts. After this hasbeen done, stopping or restarting can be down by remote controller.
OC360--3.qxp 06.2.24 1:52 PM Page 72
73
11-8. OBTAINING REMOTE DISPLAYUse the A control operating display kit (PAC-SF40RM-E) to provide operation/error non-voltage contact output and on/off inputfunction.
(1). Wiring method
CN90 CN1
CN41
Wireless3
TB3External input
TB2Error
TB1Operation2
A control indoor control circuit board A control operating display kit
5
External input
Error output
(No voltage momentary "a" contact)
Operating output
(No voltage momentary "a" contact)
No voltage(Momentary "a" contact)
HA
..Caution TB3 is a dedicated terminal for contact point input. Never input voltage. It will damagethe indoor control circuit board.
<Connections on the indoor unit side>11 When using external output function
Insert the 9-prong connector (3-core) of the attached cable to CN90 on the indoor control circuit board.22 When using the external input function
Insert the 4-prong connector (2-core) of the attached cable to CN41 on the indoor control circuit board.W The connector is direction-sensitive. Use care not to make an error when inserting.
Never force the connectors. This will result in damage.
(2). Locally procured parts
Item Name Model and specifications
External output function External output signal wire Use sheathed vinyl coated cord or cable.Wire type: CV, CVS or equivalent.Wire size: Stranded wire 0.5mm2 to 1.25mm2
Single straged: {0.65mm to 1.25mm
Display lamp, etc. No voltage “a” contact AC200V (DC30V), 1A or less
External input function External input signal wire Use sheathed vinyl coated cord or cable.Wire type: CV, CVS or equivalent.Wire size: Stranded wire 0.5mm2 to 1.25mm2
Single straged: {0.65mm to 1.2mm
Switch No voltage “a” contact(Start and stop operation is switched by inputting apulse of 200ms or more)
11-9. TIMER OPERATION● Timer operation can be performed by setting the wired or wireless remote controller timer. Start and stop times can be set in
10-minute increments within a 24-hour period.● When used in combination with the central control remote controller of the M-NET control system for the outdoor unit, one
program timer can be used for individual timer settings for each group of the central control system. (Each timer setting canbe stored in data memory so timer settings for up to 50 groups can be set individually.)
W Please refer to the MELANS catalog or technical information for details about the central control remote controller.
1.Operating with on-site timer(1). Summary of system
If the “Remote ON/OFF adapter” (PAC-SE55RA-E) (sold separately) is used, theon-site timer can be operated to turn eachunit on and off.
Pow
er s
uppl
y fo
r co
ntro
ller
Timer control panel (on-site)
Remote controller
Indoor unit
Remote controller
Indoor unit
Remote controller
Indoor unit
OC360--3.qxp 06.2.24 1:52 PM Page 73
74
(2). Basic pattern for timer controlUse a no-voltage contact point output timer (one that has separate circuits for the load side and timer power supply).a) Timer-independent control b) Combined control by timer and remote controller
OrangeAs selected by remote controller operation switch.
From indoor unitRed
Brown
T
SW ONSW OFF
Timer controlRemote controller control
SW
OrangeFrom indoor unit
Red
Brown
T
(3). Basic system5-7 Refer to the section on combined control by remote control and hand-held remote controller.
11-10. LINKED OPERATION WITH PERIPHERAL AIR CONDITIONERS EQUIPMENT■ Lossnay operation
● Linked operation with a Lossnay unit can be obtained by connecting Lossnay linkage cable (Model PAC-SB81VS - soldseparately) to the CN2L (Remote kit) on the circuit board of the indoor unit. This function must be selected from theremote controller.
11 Summary of wiring● Connect the Lossnay linkage cable (Model PAC-
SB81VS) connector to CN2L on the indoor unit on thecircuit board of the indoor unit.
● Connect the lead wire of the Lossnay linkage cable tothe Lossnay external control input terminal blocks (1)and (2).(At this time, the input terminal blocks (1) and (2)have no polarity.)
Wiring diagram
Control circuit board
Slim indoor unit
Lossnay
Lossnay linkage (PAC-SB81VS)
External controlinput terminal
block
1
2
3Connector
(CN2L)
22 Precautions when wiring● The Lossnay linkage cable can be extended up to a maximum of 500 meters.
When extending the Lossnay linkage cable, be sure to connect securely and take proper steps to ensure insulation.(Extension cable specifications: Sheathed vinyl cord or cable 0.5 to 0.75mm2)
● Lossnay linked cable● Arrange wiring so that there can be no contact between the Lossnay linkage cable and the power supply cord. Contact
may cause malfunctioning. (Separate by 5cm or more.)
11-11. OBTAINING HUMIDIFIER SIGNAL● The humidifier signal that is linked to the AC heating operation (indoor unit ventilator) can be obtained by connecting the
adapter for the humidifier signal to connector CN25 on the printed circuit for the indoor unit and wiring it to the humidifierunit via the on-site relay box. There is no output when the thermostat is off, during heating preparation and duringdefrosting.
Basic wiring
X: Relay(DC12V) CN25 (Indoor unit circuit board)
System example
Remote controller
Indoor unit
Relay box(On-site tinstallation)
Relay box(On-site tinstallation)
Remote controller
Hum
idifi
er u
nit
Humidifier unit
W Please consult your nearest Mitsubishi Electricrepresentative for information about obtaining theadapter for humidifier signal.
11-12. EXTERNAL MOUNTING OF TEMPERATURE SENSOR● Temperature control from an alternative external location can be performed by connecting the temperature sensor (Model
PAC-SE41TS-E - sold separately) to the CN20 connector on the circuit board for the indoor unit.● The wired remote controller also has an internal temperature sensor. Function selection from the remote controller is
required.Refer to “FUNCTION SETTING” for information of installation manual about selecting functions with the remote controller.
OC360--3.qxp 06.2.24 1:52 PM Page 74
75
11-13. MULTIPLE REMOTE CONTROL DISPLAYYou can control several units with a multiple remote control display, bywiring an optional multiple display adapter (PAC-SA88HA-E) with relaysand lamps on the market.How to wire(1) Connect the multiple display adapter to the connector CN51 on the
indoor controller board.(2) Wire three of the five wires from the multiple display adapter as shown
in the figure below.
[Notes on Signs]X1:Relay (for operation lamp)X2:Relay (for check lamp)RL:Operation LampGL:Check Lamp[Field supplied parts]Relays:12V DC with rated coil power
consumption below 0.9W.Lamps:Matching to power supply voltage.
CN51
connector(5P)
GREEN
Powersupply
Electrical insulation is needed.
Wiring at the actual placeOptional multiple displayadapter
The maximum distance betweenindoor board and relay is 10m.
YELLOW
ORANGERED
BROWN
5X2
X2 GL
RLX1X1
1
<Wiring >
Powersupply
Remotecontrollercable
Relay box(Field supply)
Remotecontroller
Remotecontroller
Remotecontroller
3wires3wires3wires
2wires No.1 unit No.2 unit No.3 unit
Muitiple remote controlON-OFF display(Field supply)
(Operation check)
<System>
Powersupply
RL-1
GL-1
Multiple Remote Control Display
Multiple remote controller adapter
connect tothe connector CN51
Relay box
5
X1-1
X2-1 1
<Wiring diagram>
RL-2
GL-2
RL-3
No.1 unit
GL-3
X1-1
X2-1
X1-2
X1-3
X2-3
X2-2 5
1
No.2 unit
5
1No.3 unit
X1-2
X2-2
X1-3
X2-3
Indoor controller board
●Whenever the indoor unit is operating,the duct fan operates.(1)Connect the optional multiple remote
controller adapter(PAC-SA88HA-E)tothe connector CN51 on the indoorcontroller board.
(2)Drive the relay after connecting the12V DC relay between the Yellow andOrange connector lines.
Use a relay under 1W.MB: Electromagnetic switch power relay
for duct fan.X: Auxiliary relay (12V DC LY-1F)
Be sure to secure insulationmaterial by tape and such
5 Green
Yellow
OrangeConnector (5P)
Package sideMultiple remotecontroller adapterPAC-SA88HA-E
Be sure to secure insulationmaterial by tape and such
Installation at site
CN51onindoor controllerboard Red
Brown
1
~
MB
11-14. INTERLOCKING OPERATION METHOD WITH DUCT FAN (Booster fan)
Indoor controller board
CN51
OC360--3.qxp 06.2.24 1:52 PM Page 75
Bell mouth
Photo 1
Screws
Roomtemperaturethermistor
Air intake grille
76
12 DISASSEMBLY PROCEDURE
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
1. Removing the air intake grille(1) Slide the knob of air intake grille to the direction of the
arrow 1 to open the air intake grille.(2) Remove the string hook from the panel to pretend the
grille from dropping.(3) Slide the shaft in the hinge to the direction of the arrow2
and remove the air intake grille.
3. Removing the electrical box(1) Disconnect the lead wire of the vane motor from the clamp,
and disconnect the white connector (10P).(2) Remove the room temperature thermistor with the holder.(3) Remove the bell mouth.(See photo 1)(4) Disconnect the relay connector in the electrical box.
Red (3P) for fan motor power supplyGreen (6P) for auxiliary heater
(5) Disconnect the connector on the indoor controller board inthe electrical box.White (2P) for pipe temperature detecting thermistorBlue (2P) for drain pumpWhite (3P) for drain sensor
(6) Remove the 3 screws from the electrical box, loosenanother 2 screws to remove the box.
<Electrical parts in the electrical box>Indoor controller boardPower supply boardTerminal blockCapacitorHeater contactor
PLH-3AAKH Be careful on removing heavy parts.
Photo 2
Figure 1
Air intake grille
Grille
Nut
Air intake grille knob
2. Removing the room temperature thermistor(1) Remove the screw(✕1) in the room temperature thermistor
holder to remove the holder and the room temperaturethermistor.
(2) Remove the 1 screw from the bell mouth, and unscrew theanother 2 screws (fixed to the oval hole which has differentdiameter) to remove the bell mouth.
(3) Hold the holder claw, and remove the room temperaturethermistor and holder.
(4) Disconnect the connector (red) in the indoor control board.
Indoor controller board Connector
Terminalblock
Electricalbox
Powersupplyboard
Turbo fan Capacitor
Heatercontactor
OC360--3.qxp 06.2.24 1:53 PM Page 76
77
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
5. Removing the pipe temperature thermistor(1) Remove the bell mouth.(See photo 2)(2) Remove the electrical box.(See photo 3)(3) Remove the turbo fan.(4) Remove the screw of the service panel.(5) Remove the service panel.(6) Remove the pipe temperature thermistor which is inserted
into the holder installed to the thin copper pipe.(7) Disconnect the 2-pin white connector.
6. Removing the panel(1) Remove the air intake grille.(See figure 1)Corner panel (See figure 2)(1) Remove the screw of the corner.(2) Slide the corner panel to the direction of the arrow3, and
remove the corner panel.Panel (See photo 5)(1) Disconnect the connector that connects with the unit.(2) Remove the 2 screws from the panel and loose another 2
screws, which fixed to the oval hole, have different diameter.(3) Rotate the panel a little to remove the screws.(Slide the
panel so that the screw comes to a large diameter of theoval hole, which has two different diameters.)
Photo 6
Photo 5
Photo 4
4. Remove the fan motor(1) Remove the bell mouth.(See photo 1)(2) Remove the electrical box.(See photo 2)(3) Remove the turbo fan nut.(4) Pull out the turbo fan.(5) Disconnect the connector of the fan motor lead wire.(6) Remove the 4 nuts of the fan motor.
Photo 3Fan motor
Nut Connector
Pipe temperature thermistor
Service entrance
7. Removing the drain pan(1) Remove the panel. (See photo 5)(2) Remove the drain plug (Larger one), drain the remaining
water in the drain pan.(3) Remove the corner cover. (2 screws)(4) Remove the bell mouth (See photo 1)(5) Remove the electrical box. (See photo 2)(6) Remove the lead wire holder. (1 screw)(7) Remove the 4 screws and pull out the drain pan.
w Pull out the left and right of the pan gradually.Be careful not to crack or damage the pan.
Figure 2
Cornerpanel
ScrewCornerpanel Panel
PanelScrew
Connector Screw
Screw Screw
Screw
Screw
Drain pan
Drain plug(Larger one) Corner cover
Leadwireholder
Nut
OC360--3.qxp 06.2.24 1:53 PM Page 77
78
OPERATING PROCEDURE PHOTOS&ILLUSTRATIONS
9. Removing the heat exchanger(1) Remove the panel. (See photo 5)(2) Remove the bell mouth. (See photo 1)(3) Remove the electrical box. (See photo 2)(4) Remove the drain pan. (See photo 6)(5) Remove the turbo fan. (See photo 3)(6) Remove the 3 screws of the piping cover, and pull out
piping cover.(7) Remove the 4 screws of the outer wall cover, and pull out
the outer wall cover.(8) Remove the screw of the coil support.(9) Remove the 2 screws of the coil.(10) Pull out the heat exchanger.
8. Removing the drain pump and drain sensor(1) Remove the panel. (See photo 5)(2) Remove the bell mouth. (See photo 1)(3) Remove the electrical box. (See photo 2)(4) Remove the drain pan. (See photo 6)(5) Remove the 3 screws of the drain pump.(6) Cut the drain hose band, pull out the drain hose from the
drain pump.(7) Pull out the drain pump.(8) Remove the drain sensor and the holder.
Photo 8
Screw
Screw
Drain sensor
Drain pumpDrain hose
Fixing band
Photo 9
Photo 10
Heat exchanger
Coilsupport
Coil screwsCoil support
Coilsupport
Screw
Outer wall cover Piping coverScrews ofpiping cover
10. Removing the heater(1) Remove the panel. (See photo 5)(2) Remove the electrical box. (See photo 2)(3) Remove the bell mouth.(See photo 1)(4) Remove the drain pan.(See photo 6)(5) Remove the turbo fan.(See photo 3)(6) Remove the 5 screws of the heater assembly.(7) Remove the clamp(1 screw) securing the lead wire.(8) Pull the heater assembly out.
Heaterassembly
Heater screw
Lead wire clamp
OC360--3.qxp 06.2.24 1:53 PM Page 78
79
13 PARTS LIST
1
13
2
3
4
5
6
14
12
11
10
9
8
7
GEAR
GEAR(VANE)
VANEBUSH
VANEMOTOR
ON/OFF TEMP
MODEL SELECT
NOT AVAILABLE
CHECK TEST RUNC̊
AMPM
AMPM
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODEFILTER
TEST RUNFUNCTION
˚C1Hr.
NOT AVAILABLESTAND BY DEFROST
TEMP.
17
PANEL PARTSPLP-6AAPLP-6AAL
No. Parts No. Parts Name Specification
Q'ty / set
WIRELESSWIRED
PLP-6AALPLP-6AARemarks
(Drawing No.)
WiringDiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
123456789101112131415161718
AIR OUTLET GRILLEVANECORNER PANEL (RECEIVER)CORNER PANELL.L FILTERGRILLE ASSYRECEIVING UNITWIRELESS REMOTE CONTROLLER BOARDVANE MOTORVANE BUSHGEAR (VANE)GEARREMOTE CONTROLLERWIRELESS REMOTE CONTROLLERREMOTE CONTROLLER DOORREMOCON HOLDERCABLE ASSYSCREW ASSY
14
411
48441
11
141311114844
111
1
RUW.BMV
R.B
T7W E10 003R01 E00 002R01 E02 638R01 E03 638R01 E00 500R01 E00 691R01 24K 658R01 E00 317R01 E00 223R01 E00 063R01 E00 040R01 E01 040T7W E08 713T7W E06 714R01 E01 049R01 E00 075T7W E01 305R01 E00 673
Including H2
15 16
Part numbers that is circled is not shown in the figure.
RECEIVER
OC360--3.qxp 06.2.24 1:53 PM Page 79
80
No. Parts No. Parts Name
Q'ty / setPLH-AAK
3 4 6
WiringDiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
1
23
4
5
6
78
9
10
11
12
BASEBASELEGLEGTURBO FANTURBO FANSPL WASHERHEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERRISTRICTOR VALVEPIPE TEMPERATURE THERMISTORINNER COVERINNER COVERLEGFAN MOTORFAN MOTORRUBBER MOUNT
TH2
MFMF
————
R01 E28 114R01 E29 114R01 08K 097R01 E06 480R01 E07 480R01 E08 480R01 E09 480R01 E06 418T7W E06 202
———
T7W E06 762T7W E07 762R01 A41 105
1
211
11
111
11
4
121
11
1
11
11
14
121
11
111
11
14
(RG00G462G34)(RG00G462G32)(RG02G374H05)(RG02G374H06)
(RG00G165G45)(RG00G165G47)(RG02G375H01)
Remarks(Drawing No.)
D17B6P70MSD176P120MS
Specification
121
11
1
11
11
14
5
3
6
5
4
2
1
12 11
10
9
8
FUNCTIONAL AND STRUCTURE PARTSPLH-3AAKPLH-4AAKPLH-5AAKPLH-6AAK
PIPE TEMPERATURE THERMISTOR
SPL WASHER
7 RESTRICTORVALVE
OC360--3.qxp 06.2.24 1:53 PM Page 80
81
FUNCTIONAL AND STRUCTURE PARTSPLH-3AAKHPLH-4AAKHPLH-5AAKHPLH-6AAKH
3
7
6
5
4
2
1
16 15
14
13
10
9
11
12 THERMAL FUSE
HEATER THERMALSWITCH
PIPE TEMPERATURE THERMISTOR
SPL WASHER
8 RESTRICTOR VALVE
No. Parts No. Parts NameQ'ty / set Wiring
DiagramSymbol
Recom-mended
Q'ty Unit
Price
1
23
4
5
6
7
89
101112
13
14
15
16
BASEBASELEGLEGTURBO FANTURBO FANSPL WASHERHEATER ELEMENT HEATER ELEMENT HEATER ELEMENT HEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERHEAT EXCHANGERRESTRICTOR VALVEPIPE TEMPERATURE THERMISTORINSULATORHEATER THERMAL SWITCHTHERMAL FUSEINNER COVERINNER COVERLEGFAN MOTORFAN MOTORRUBBER MOUNT
H1H1H1
TH2
26HFS2
MFMF
240V/700W240V/867W240V/1000W
50°C OFF104°C, 16A
D17B6P70MSD176P120MS
————
R01 E28 114R01 E29 114R01 08K 097T7W E07 300T7W E06 300T7W E05 300R01 E06 480R01 E07 480R01 E08 480R01 E09 480R01 E00 418T7W E06 202R01 20J 303R01 46K 700T7W E02 706
———
T7W E06 762T7W E07 762R01 A41 105
1
211
13
1
111111
11
4
121
11
3
1
11111
11
14
121
11
3
111111
11
14
Specification Remarks(Drawing No.) Amount
PLH -AAKH3 5 64
121
11
3
1
11111
11
14
(RG00G462G34)(RG00G462G32)(RG02G374H05)(RG02G374H06)
(RG00G165G62)(RG00G165G63)(RG02G375H01)
OC360--3.qxp 06.2.24 1:53 PM Page 81
82
No. Parts No. Parts NameWiring
DiagramSymbol
Recom-mended
Q'ty Unit Amount
Price
1
2345678910111213
14
151617
DRAIN PANDRAIN PANDRAIN PANDRAIN SOCKETDRAIN PUMPDRAIN SENSORSENSOR HOLDERINDOOR POWER BOARDFUSEINDOOR CONTROLLER BOARDCONTROL COVER ASSYROOM TEMPERATURE THERMISTORTERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCK CAPACITORCAPACITORCORNER COVERDRAIN PLUGDRAIN PLUG
1
1111111111111
111
1
111111111111
1111
(RG00A239GP4)
(RG00G623G05)
DPDS
P.BFUSE
I.B
TH1TB5TB4TB2
CC
6.3A 250V
2P (1, 2)3P (1, 2, 3)3P (L, N, ;)3.5+ 440V7.0+ 440V
R01 E02 529R01 E00 529R01 E01 529R01 A41 523T7W E08 355R01 E00 266R01 31K 241T7W E24 313R01 E02 239T7W E47 310
—R01 E00 202T7W 512 716T7W E27 716T7W A14 716R01 17T 255T7W E02 255
—R01 A48 524R01 A41 524
Q'ty / setPLH-AAK
3 4,5Specification
Remarks(Drawing No.)
1111111111111
1111
6
FUNCTIONAL AND STRUCTURE PARTSPLH-3AAKPLH-4AAKPLH-5AAKPLH-6AAK
9
5
6
8
4
3
2
10
14
12
11
15
CAPACITOR
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
1
16
17
DRAIN PLUG
DRAIN PLUG
7FUSE
13 TERMINAL BLOCK
OC360--3.qxp 06.2.24 1:53 PM Page 82
83
FUNCTIONAL AND STRUCTURE PARTSPLH-3AAKHPLH-4AAKHPLH-5AAKHPLH-6AAKH
No. Parts No. Parts NameWiring
DiagramSymbol
Recom-mended
Q'ty Unit
Price
1
234567891011121314
15
161718
DRAIN PANDRAIN PANDRAIN PANDRAIN SOCKETDRAIN PUMPDRAIN SENSORDRAIN SENSOR HOLDERPOWER BOARDFUSEINDOOR CONTROLLER BOARDCONTROL COVER ASSYROOM TEMPERATURE THERMISTORTERMINAL BLOCK TERMINAL BLOCK TERMINAL BLOCKRELAYCAPACITORCAPACITORCORNER COVERDRAIN PLUGDRAIN PLUG
1
11111111111111
111
1
1111111111111
1111
DPDS
P.B
I.B
TH1TB5TB4TB288H
CC
2P (1, 2)3P (1, 2, 3)3P (L, N, ;)JC-1A DC12V3.5+ 440V7.0+ 440V
R01 E02 529R01 E00 529R01 E01 529R01 A41 523T7W E08 355R01 E00 266R01 31K 241T7W E24 313R01 E02 239T7W E47 310
—R01 E00 202T7W 512 716T7W E27 716T7W A14 716R01 71G 215R01 17T 255T7W E02 255
—R01 A48 524R01 A41 524
Q'ty / set
Specification Remarks(Drawing No.) Amount
PLH -AAKH
3 4 5 6
1
1111111111111
1111
11111111111111
1111
(RG00A239GP4)
(RG00G623G05)
8
5
6
7
4
3
2
1
9
14
13
12
11
10
15 CAPACITOR
RELAY
TERMINAL BLOCK
TERMINAL BLOCK
TERMINAL BLOCK
ROOM TEMPERATURE THERMISTOR
17
16
DRAIN PLUG
DRAIN PLUG
18
OC360--3.qxp 06.2.24 1:53 PM Page 83
84
OPTIONAL PARTS14
Note 1. How to connect refrigerant pipes.Factory supplied optional refrigerant pipings contain refrigerant at the above atmospheric pressures. As long as theconnection takes no more than 5 minutes, no air will enter, and there will be no need for air purging.Remove the blind caps and make the connections within 5 minutes. After the connections for the indoor and outdoorunits are made, open the stop valve on the outdoor unit to allow refrigerant gas to flow.
Note 2. The following main parts are contained in the optional refrigerant piping kit.Heat insulating cover, vinyl tapes, nipples, sleeve and flange (for wall hole).
12345
BRNREDORNYLWGRN
2. MULTIPLE REMOTE CONTROLLER ADAPTERThis adapter is needed for remote indication (operation/check).
1. REFRIGERANT PIPESService Ref. : PLH-3AAK(H)
Service Ref. : PLH-4AAK(H), PLH-5AAK(H), PLH-6AAK(H)
Part No. PAC-05FFS-E PAC-07FFS-E PAC-10FFS-E PAC-15FFS-EPipe length 5m 7m 10m 15mPipe size O.D . Liquid:[9.52 Gas:[15.88Connection method Indoor unit: Flared Outdoor unit: Flared
Part No. PAC-PC51PI-E PAC-SC52PI-E PAC-SC53PI-E PAC-SC54PI-EPipe length 5m 7m 10m 15mPipe size O.D. Liquid:[9.52 Gas:[19.05Connection method Indoor unit: Flared Outdoor unit: Flared
PAC-SF40RM-E
PLH-3/4/5/6AAK(H)
Part No.
Applicable Service Ref.
5. REMOTE OPERATION ADAPTER
PAC-SE55RA-E
PLH-3/4/5/6AAK(H)
Part No.
Applicable Service Ref.
PAC-SE41TS-E
PLH-3/4/5/6AAK(H)
4. REMOTE SENSOR
Part No.
Applicable Service Ref.
3. REMOTE ON/OFF ADAPTER
Part No.
Applicable Service Ref.
PAC-SA88HA-E
PLH-3/4/5/6AAK(H)
OC360--3.qxp 06.2.24 1:53 PM Page 84
85
PAC-SG06SP-E
PLH-3/4/5/6AAK(H)
Part No.
Applicable Service Ref.
8. AIR OUTLET SHUTTER PLATE (20set, 2pcs/set)
PAC-SG03TM-E
PLH-3/4/5/6AAK(H)
Part No.
Applicable Service Ref.
PAC-SG01KF
PLH-3/4/5/6AAK(H)
7. HIGH EFFICIENCY FILTER ELEMENT (PAC-SG03TM-E is needed)
Part No.
Applicable Service Ref.
6. MULTI FUNCTION CASEMENT (For HIGH EFFICIENCY FILTER AND FRESH AIR INTAKE)
OC360--3.qxp 06.2.24 1:53 PM Page 85
HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
© Copyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO.,LTD.Distributed in Feb. 2006 No.OC360 PDF 9Made in Japan
New publication, effective Feb. 2006Specifications subject to change without notice
TM
OC360--3.qxp 06.2.24 1:53 PM Page 86