nordac2002

Upload: imadhuryya5023

Post on 10-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Nordac2002

    1/5

    Communication Possibilities for Remote Control and Condition Monitoring of

    Small-Scale Hydro Power Plant

    Tuomo Lindh

    Lappeenranta University of

    Technology

    Department of Electrical

    EngineeringP. O. Box 20,

    Lappeenranta, Finland

    +358 5 621 6779

    Fax +358 5 621 6799

    E-mail: [email protected]

    Jero Ahola

    Lappeenranta University of

    Technology

    Department of Electrical

    EngineeringP. O. Box 20,

    Lappeenranta, Finland

    +358 5 621 6761

    Fax +358 5 621 6799

    E-mail: [email protected]

    Jarmo Partanen

    Lappeenranta University of

    Technology

    Department of Electrical

    EngineeringP. O. Box 20,

    Lappeenranta, Finland

    +358 5 621 6702

    Fax +358 5 621 6799

    E-mail: [email protected]

    Heikki Pirttiniemi

    Waterpumps WP Oy

    Karhusuontie 39

    00780 Helsinki

    Helsinki, Finland

    +358 9 3855 907

    Fax +358 9 345 4002

    E-mail:[email protected]

    ABSTRACT

    In this paper we compare different remote controlling

    methods for a small-scale hydropower plant in terms of cost

    efficiency, complexity and capability to provide

    information. In addition, requirements of each solution for

    hardware software and communication media are

    discussed. Examples of different solutions are presented by

    implementations in laboratory conditions and in the pilot

    plants of Tirva HPP in Valkeala and Hiitolanjoen Voima

    HPP in Simpele. The costs of the presented controlling

    applications are much lower than in traditional remote

    control systems used in power plants.

    Keywords: Small-scale hydro power, remote controlling,

    remote access, condition monitoring.

    1 INTRODUCTION

    Small-scale hydropower plants can be profitable if both the

    investment costs and the running costs are low enough.

    Especially, if the government subsidises the small-scalerenewable energy production. However, because the amount of

    energy production is low, the plants controlling equipment

    should be inexpensive. On the other hand, the plant should be

    remote controllable so that the labour costs are minimised. The

    labour costs are normally very low in fully automated plants butthey will be increased as service visits are done. The optimum

    between investments in remote controlling and amount of

    labour costs depends on the type, size and location of the plant.

    In addition, controlling solution depends on the skills ofoperators. For example, if the controlling tasks require

    programming skills, normal operator is not able to control the

    plant or at least the risks of use are too high. Direct plantcontroller connection, field bus gateways, remote access server

    based controlling and SMS based controlling are the

    alternatives for the conventional distribution automation. Inaddition, web-based techniques can be applied in controlling

    tasks. The condition monitoring and remote diagnostics hasalso an important role in unmanned plants. It is an integrated

    part of the field level automation.

    2 TYPICAL INFRASTRUCTURE OF SMALL SCALE

    POWER PLANT

    The small-scale or micro-scale hydro power plant can have a

    power generation from approximately 50 kW to 2 MW (figure

    1). The main circuit of a small-scale hydro power plant is

    illustrated in figure 2. In the most usual cases the generators arelow voltage synchronous or asynchronous generators. The

    switchboard of the plant automatically runs startup and

    shutdown procedures and controls the power generation

    according to a set value. The set value is calculated for examplefrom the difference between actual level and aimed level of the

    up water. The energy produced by generators is fed to medium

    voltage network through distribution transformer. The energy is

    usually measured from low voltage side of the transformer.

    Figure 1. A small-scale power plant (1 MW) in rural area faraway from service personnel.

  • 8/8/2019 Nordac2002

    2/5

    MF MF

    F

    3

    200 kW

    690 /400Vcos=0.841500r/min

    1.1 kW

    400Vcos =0.81500r/min

    200kW

    690/ 400Vcos =0.841500r/min

    1.1kW

    400Vcos =0.81500r/min

    3~ 50Hz 380V

    V

    250kVAr

    3x185+50(Cu),

    150Cu

    1000A

    MKEM 3x2.5+2.5

    40A 40A

    Powerfactor cotroller

    Cu 30x10

    500 A 500 A

    63Aaux supply

    3x300Cu +120 Cu

    0Q0

    1Q0 2Q0

    VS1

    2x150Cu

    1Q1 2Q1

    0Q120A

    0FS2

    CONTROLCIRCUITS

    1F2

    1K2 2K2

    2F2

    MKEM 3x2.5+2.5

    CONTROLCIRCUITS

    Surge arrester

    2x(3x300 Cu) +2x120Cu)

    150Cu

    3x300Cu +120Cu

    3x185+50 (Cu),

    2x(180Cu)

    In=800A , Ip=65 kA

    3

    PE Bar

    Figure 2. The main circuit of a small-scale hydro power plant.

    The main components are illustrated using pictures.

    3 ALTERNATIVES FOR REMOTE CONTROLLING

    Some alternatives for remote controlling of small-scale power

    plant are presented in this chapter.

    Plant PLC and GSM- or PTT-modemThe simplest remote controlling or monitoring implementation

    requires only GSM- or PTT-modem and approximately 30 rows

    of programmable logic (PLC) program code (figure 3). This

    applies to one directional data transfer, usually a SMS message

    that alarms or just informs the personnel. If a PLC program canhandle the most usual abnormal situations this kind of an

    implementation can reduce the service costs delivering the

    necessary information about the failure or alarm. Based on this

    information can be determined whether the service visit is

    required or not. In pilot hydro plants, the typical messages areloss of mains or return of mains. The investment costs of this

    type of system is approximately 1000.

    This type of implementation can also receive SMS messages.However, it requires more PLC code than a simple

    unidirectional data communications and the complexity of thePLC program increases but the implementation costs still

    remain low. The number of feasible instructions is quite limiteddue to restrictions PLC (memory restriction).

    PLCPLC PLC

    PLC

    Plant Controller

    Generator Controllers

    Field Bus

    GSM GSM

    Figure 3. The simplest remote monitoring implementation, oneway data transfer from PLC to GSM using SMS.

    It is also possible to have a more sophisticated monitoring and

    remote control by using a very simple fieldbus protocol through

    a modem. This implementation requires that remote controllingof the plant (user side) is done by a computer instead of a GSM

    telephone. A schema of communications is illustrated in figure

    4 and implementation is illustrated in figure 5.The functionalityof the implementation is described in the text and the flowchart

    (figure 6) below.

    PLCPLC PLC

    PLC

    Plant Controller

    Generator Controllers

    Field Bus

    GSM GSM

    PC

    Remote

    Control

    Figure 4. Schema of simple PLC based remote control for a

    small-scale power plant.

    Figure 5. Implementation of PLC based remote control. Simplefieldus protocol is driven over a telephone line.

    When something abnormal happens in the plant the plant

    controller PLC changes modem to SMS mode and sends the

    SMS message to the remote controlling PC. Subsequently, the

    PLC changes the modem in normal mode and waits forconnection from the remote control program. When the call to

    modem is received, the PLC answers to the call and starts

    waiting for the fielbus command from remote PC that operates

    as master unit. Respectively, the plant controller PLC operates

    as slave. The whole data memory area of the plant controllerPLC can be read and written by the specially built PC program.

    The hardware costs are increased with a client side computer

    only. The implementation is still quite simple but the

    programming work both in plant side and in remote controller

    side are remarkably bigger that in previously presented cases.However, when the programs are made the costs remain very

    low with increased controlling capacity compared to previously

    presented communication structures.

  • 8/8/2019 Nordac2002

    3/5

    MESSAGESTO

    SEND

    WAIT FOR MODEMEVENTS

    MODEMCOMMUNICATION

    RUNNING

    CHANGE TO SMS MODE

    SEND THE MESSAGE

    BACK TO NORMAL MODE

    MODEMCALLS

    WAIT FOR FIELDBUSCOMMANDS

    FIELDBUSCOMMAND

    OK

    ESCAPE CODE

    NO

    NO

    NO

    NO

    SEND ERRORCODE

    NO

    YES

    YES

    YES

    YES

    YES

    PROCESS AND SEND

    Figure 6. Initialisation and execution of PLC remote control.

    Plant PLC, local PC-supervision, modem line and remote PCIf a versatile plan man machine interface (MMI) interface is

    required at the plant, one solution is industrial PC or in somecases even an ordinary PC (figure 7). In this implementation,the control and reporting possibilities become much better than

    in previous implementations and number of feasible functions

    increases. In this implementation also all the communication

    examples presented in previous paragraphs are possible.

    PLCPLC PLC

    PLC

    Plant Controller

    Generator Controllers

    Field Bus

    GSM GSM

    PC

    Remote

    Control

    PC

    Local

    Control

    Figure 7. Versatile PC based remote controlling for a small-

    scale power plant.

    Local PC can send SMS-messages and transfer data between plant controller PLC and the remote controlling computer.

    Local PC works as a fieldbus gateway. This type of

    implementation has some advantageous properties. The amount

    of transferred data between plant and remote controller is low

    when only the information that is needed is transferred. Thiskind of implementation has one drawback. The computer of the

    plant cannot be administered with this solution. If full

    administration is needed the remote access program can be used

    instead of this solution.

    The remote access programs such as PCAnywhere or VNCoffer cheap or free solution of remote controlling. They can be

    used in WAN-network or with modems also. When used with

    modems a dial-up Internet connection of PC is used. The local

    plant computer acts as a remote access master and remote useras slave. The advantage of the remote access program is that the

    user can control the plant computer as a local user. The user canopen programs, shut programs even re-program the plant PLC

    if needed. The disadvantage of the solution is that the amountof transferred data is big when the whole display of the plant

    computer is transferred to the user. Every action takes lot of

    time even if the display of the plant computer is transferred to

    user with minimum number of colours. Another drawback isthat the user can do everything that can be done locally

    meaning that even the removal of programs is possible. Theunauthorized use is prevented with passwords of remote access

    program and by restricting the access to plant from predefinedphone numbers only.

    Internet/JAVA techniques can be used with this hardware

    structure also. The same dial up Internet connection that is used

    with remote access programs can be used to provide WEB-

    services such as interactive applet with monitoring and

    controlling possibilities. The user only needs Internet browserand modem in the client side computer. The disadvantages of

    this kind of system are also the slow communication speed and

    the single user environment. The later restriction also applies to

    WAP connections.

    Integration to existing DA-systems of electricity companyIf the remote control of the plant (substation level automation)

    is made by systems separate from existing integrated DA-system of an electricity company the operational costs may

    increase. However, it is possible to integrate some of the

    systems presented previously to existing DA by very simple

    and low costs method. The leading DA/DSM systems utilizedatabases with ODBC and JDBC connectivity. The integration

    to DA/DSM can be done in control room by these methods and

    control of small-scale plant can be done utilizing the database

    services as will be presented.

    The communication infrastructure presented in this chapter

    allows multiple simultaneous users, which is not normally

    needed in controlling tasks in small-scale hydro power plants.However, it may be an attractive alternative for example in the

    cases where green energy is sold. The customers can view the

    energy production in Internet. Another reason to present this

    method here, as mentioned before, is that it supplies means forintegration of systems presented here to existing DA/DSM

    systems used in electricity companies. The system is described

    in detail in [Lin01].

    At the control centre level or at the plant level the systems canbe integrated using databases. The control room level software

    is illustrated in figure 8. On the other hand, the samefunctionality can be installed at the plant level (figure 10). All

    measurement data or registers of devices are read and writtenthrough database tables. Global connection is available for user

    by a standard web-browser. When a connection to http-portof server is opened, an applet with graphical user interface

    (GUI) and connection data is loaded to the browser. Based onthe log data, the system determines the actions that are allowed

    for user. The user can execute only the functions that are codedto the applet.

    LAN

    DA/DSM

    Data Interface

    CONTROL CENTER LEVEL

    Data Storage

    Management

    ODBC client OPC client

    Data managerDataStoragedb

    (WINDOWS service )

    PLANT CONTROLLER

    Fieldbus Master

    MODEM LINE

    Fieldbus Slave

    Figure 8. Integration between existing DA/DSM and remote

    control of small-scale plant.

  • 8/8/2019 Nordac2002

    4/5

    At program level, a connection to a database is formed withJDBC API. The JDBC is a standardised interface that provides

    connectivity to a wide range of SQL databases. JDBC driver isloaded with Java applet. Installation of programs or any other

    files is not needed in a client computer. In our demonstration,

    type 3 JDBC driver is used which means that calls are not made

    from client to DBMS-server directly. The JDBC driver

    translates JDBC calls to a protocol that server side data servertranslates to a DBMS protocol.

    The connection to local databases can be done using standard

    ODBC or OPC interfaces. In our demonstration it was donewith OPC connection. The OPC server handles connections to

    the Profibus and serves simultaneously multiple OPC clients.

    The server is capable of reading and writing registers ofindividual device connected to field bus.

    Database server acts as the software interface between web

    applications or control centre applications (DA/DSM) andapplications performing data transmission between control

    centre level and field level. The database server is a standard

    Microsof SQL Server. Measured values, configuration of

    field device registers (OPC tags) and requests for changes of

    registers are all stored in the database tables.

    A Windows NT service was developed for this demonstration.It consists of OPC client part, ODBC client part and of service

    routines. The service monitors the changes in configuration

    tables. Based on these changes, the service transfers data

    through OPC and ODBC interfaces between the fieldbus

    devices and database server.

    4 REQUIREMENTS OF CONDITION MONITORING

    There are needs for condition monitoring also in small-scale

    power plants. The small-scale plants are typically unmanned

    due to economical limitations. Therefore, the condition

    monitoring should be based on automatic and remotediagnostics. The condition monitoring and diagnostics system

    have two requirements. It should detect possible failures before

    they lead to emergency shutdown of the plant. Secondly, thesystem should be robust and not to alarm when a real failure

    does not exist.

    For example, in small-scale hydro power plants there are

    numerous important objects that should be monitored. The most

    important objects to be monitored are generator and turbine.

    Overheating can destroy the windings of the generator.

    Respectively, an increase of humidity indicates a leakage inturbine-generator package. The bearings are also possible

    reason for generator failure. Therefore, also a bearing

    monitoring should be introduced.

    The condition monitoring equipment can be connected into theplants field bus and the remote diagnostics can be realised by

    communications methods presented in previous chapters.

    Generally it can be assumed that the condition monitoringfunctions do not need large data transfer capacity. The need of

    capacity depends mainly on the fact, where the condition

    monitoring data is analysed. Local analysis and intelligent

    sensors shrink the needed bandwidth. Respectively, transferringof raw measurement data dramatically increases need of the

    bandwidth.

    Condition monitoring functions for underwater hydro powergenerators have been developed. A microprocessor based

    sensor can be installed inside the generators frame. The sensortakes supply power directly from the terminals of the generator.

    The sensor measures and analyses for example vibrations,temperature and humidity. The analysed data is transferred

    from the sensor using generators feeder cable as a

    communications channel. Based on [Aho02], low voltage

    power cables are applicable for power-line communications. In

    system under development, the master unit is located at theswitchboard. It receives the data that the sensor has sent and

    links it into plants field bus. Thus, the condition monitoring

    data is available for remote diagnostics.

    5 EXPERIMENTS FROM PILOT PLANTS

    The first pilot, Tirva HPP, was equipped with the GSM-modem

    connected to PLC as in figure 3. With this very simple schemathe number of service visits was reduced remarkably. The

    problem was that the SMS message could not inform the

    personnel as much as they wanted. For example, alarms for

    intruders were many (surveillance of the yard was included),but no harm was done when checked in plant. Also the need for

    local reporting with event log was discovered. The local PC

    was added and because there was an existing telephone line at

    the plant the PTT modem was installed in parallel with theGSM modem. Further, the remote access program was installed

    so that events can be checked remotely. The system includes

    also the WEB-camera that shows the view at the dam. The

    number of unnecessary service visits was further decreased.The repayment of investment is estimated to be two years. The

    final schema is presented in figure 7.

    PLCPLC PLC

    PLC

    Plant Controller

    Generator Controllers

    Field Bus

    GSM GSM

    PC

    Remote

    Control

    PC Local

    Control

    Modem ModemTelephone line

    Figure 9. The structure of the controlling system in pilot plantin Tirva.

    Second pilot in Simpele also includes local PC-controlling

    program. The wired telephone line is used for the energy

    measurement collection use only. Therefore the GSM have to

    be used in communication between plant and the service personnel. The principal structure of the communication is as

    presented in Fig. 3. The investment costs of communicationsare low but the operational costs are higher than in previous

    example because of the higher costs of communication.

    6 CONCLUSIONS

    It is too expensive to connect micro scale or small scale power

    plant as a part of the conventional distribution automation

    system with local RTU, (perhaps local SCADA), radio

    communication and remote SCADA. This does not mean thatthe unmanned use is too expensive nor that the system cannot

    be integrated to existing DA/DSM. GSM-modem or PTT-

    modem connected to plant controller PLC offer the very low

    cost methods for remote control. The service cost reductions pay the investment practically in all cases where unmanned

    operation of plant is in use and also if the plant is partiallymanned (not 24 hours per day).

    If the monitoring of plants operation is needed locally and the

    local environmental conditions are good enough the use of PC

    is justified. Furthermore, if only the one directional

  • 8/8/2019 Nordac2002

    5/5

    communication is used, the personnel have to visit the plantalmost weekly in order to be sure that the no service actions are

    needed. Fieldbus gateway through modem and loacal computerrequires less communication capacity than the use of the remote

    access programs when only the needed information is

    transferred. However, the remote access programs make

    possible more versatile control of the plant. The integration to

    existing DA/DSM can be done at control room level using opendata interfaces. The condition monitoring functions can be

    integrated as a part of automation systems of a plant and thus as

    a part of the remote controlling schema.

    WWW -Browser

    INTERNET

    WAN

    Plant ControllerPLC

    Field Bus

    G G

    Hydropower Plant

    Process Control Level

    ProtectionRelay

    GeneratorControllerPLC

    Condition

    MonitoringDevice

    I V f

    Process

    GeneratorControllerPLC

    0

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1 2 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3

    Local Web server

    Local Controlling Computer

    Figure 10. Plant level Internet connection.

    REFERENCES

    [Lin01] Tuomo Lindh, Jero Ahola, Jarmo Partanen, Sauli

    Antila, Pertti Jrventausta, Kimmo Kivikko, PekkaVerho, Pekka Ruupunen, Web-based monitoring

    functions utilising data management system,DistribuTECH Europe 2001, Berlin, Germany, 6-8

    November 2001.

    [Aho02] Jero Ahola, Tuomo Lindh, Jarmo Partanen,

    Determination of Properties of Low Voltage Power

    Cables at Frequency Band 100 kHz 30 MHz ,ICEM 2002, Bruges, Belgium 26-28 August, 2002.