notes: legend · 2. include legend and revised notes. 3. revised pob /linkway incomming isolator...
TRANSCRIPT
NOTES:1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED.
2. THIS DRAWING TO BE READ IN CONJUNCTION
WITH SPECIFICATIONS.
3. ALL ARCHITECTURE DETAILS TO ARCH’S APPROVAL.
4. CONTRACTOR SHOULD DO A SITE SURVEY BEFORE WORK COMMENCEMENT.
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
TO THE S.O. FOR APPROVAL PRIOR TO
COMMENCEMENT OF INSTALLATION.
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
FOR ALL LIGHTING.
7. CONTRACTOR TO DESIGN THE ELECTRICAL
INSTALLATION IN ACCORDANCE WITH THE
LATEST SS CP5.
8. OUTGOING CONTACTOR SHALL BE RATED
APPROPRIATELY.
9. OUTGOING LIGHTING CIRCUIT BREAKER
SHALL BE APPROPRIATELY DESIGN WITH
MINIMUM RATING OF 10A SPN MCB 10KA.
1 1
DOUBLE POLEDP
MCB
RESIDUAL CURRENT CIRCUIT BREAKERRCCB
ISOLATOR
T
C
2A
LEGEND:
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
S MOTION SENSOR
MINIATURE CIRCUIT BREAKER
NTS
L/ROAD/MES/SD/1002
LROADMES-SD1002A.dgnDescriptionRev. Date By App’dChk’d
MELVYNTHONGA DEC 2010
1. REVISED LIGHT FITTING DESCRIPTION
2. INCLUDE LEGEND AND REVISED NOTES.
3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO 32A AND SPPG DP MCB FROM 63A TO 32A.
JULI JULY 2007
NURLY
TAY K.C.
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG BOX
(POB/LINKWAY/TAXI STAND/BUS SHELTER)
LIGHTNING SURGE ARRESTOR
BI TERMINAL
ADRIAN CHEONG/HADI WIJAYA
WEATHERPROOF JUNCTION BOX
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
A
MALVIN HONURLY
STANDARD INSTALLATION DETAILS
SCALE NTS
TYPICAL SINGLE LINE DIAGRAM - FOR NEW OG-BOX (POB/LINKWAY/TAXI STAND/BUS SHELTER)
C
S
C
C
LSA LSA
LSA
BI
BI BI TERMINAL BI BI TERMINAL
(LTA COMPARTMENT) (LTA COMPARTMENT)
kwh
METER
(PG COMPARTMENT)
BI
BI SUPPLIED AND
INSTALLED BY PG
FROM POWERGRID
POWER GRID
NEW
OG-BOX
METERPOWER GRID
32A
40A DPRCCB(100mA)
2A
T
(10 KA)
SP
AR
E
SP
AR
E
LIG
HT
FIT
TIN
G
FO
R
CO
VE
RE
D
PO
B
WIT
H
CO
VE
RE
D
RA
MP
S
DP MCB
(TYPE B)
32A DP
CONTACTOR
7pm
TO 7am
MIDNIGHT
TO 7am
PROGRAMMABLE
TIMER
40A DPRCCB(100mA)
2A
T
32A DP
CONTACTOR
7pm
TO 7am
PROGRAMMABLE
TIMER
DP MCB
32A
(10 KA)
DP MCB
(TYPE B)
DP MCB
LIG
HT
FIT
TIN
G
FO
R
CO
VE
RE
D
PO
B
WIT
H
CO
VE
RE
D
RA
MP
S/
LIN
KW
AY
CONTACTOR
*SEE
NOTE
NO. 9
*SEE
NOTE
NO. 9
*SEE
NOTE
NO. 9
*SEE
NOTE
NO. 8
32A COMB BUSBAR32A COMB BUSBAR
32A COMB BUSBAR
INTELLIGENT
LIGHTING
CONTROL BOX
kwh
32A
(PROVIDED BY PG)DP MCB (TYPE C)
32A
(PROVIDED BY PG)DP MCB (TYPE C)
32A DPISOLATOR
32A DP
ISOLATOR
NEW DB
POB/LINKWAY
NEW DB
BUS SHELTER/
TAXI STAND
LIG
HT
FIT
TIN
G
TO
TE
CH
NIC
AL
SP
ECIFIC
ATIO
N
PE
RF
OR
MA
NC
E
ARMOURED CABLE IN
HEAVY DUTY UPVC PIPES
PVC CABLES IN
HEAVY DUTY UPVC PIPES
PVC CABLES IN
HEAVY DUTY UPVC PIPES
ARMOURED CABLE IN
HEAVY DUTY UPVC PIPES
E
RING CIRCUIT
SHALL BE LESS
THAN 1 ohm
NOTES:
OTHERWISE STATED.1. ALL DIMENSION ARE IN mm UNLESS
WITH SPECIFICATIONS.
2. THIS DRAWING TO BE READ IN CONJUNCTION
APPROVAL.3. ALL ARCHITECTURE DETAILS TO ARCH’S
BEFORE WORK COMMENCEMENT.4. CONTRACTOR SHOULD DO A SITE SURVEY
COMMENCEMENT OF INSTALLATION.
TO THE S.O. FOR APPROVAL PRIOR TO
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
DOUBLE POLEDP
MCB
RESIDUAL CURRENT CIRCUIT BREAKERRCCB
ISOLATOR
T
C
2A
LEGEND:
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
S MOTION SENSOR
MINIATURE CIRCUIT BREAKER
FOR ALL LIGHTING.
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
LATEST SS CP5.
INSTALLATION IN ACCORDANCE WITH THE
7. CONTRACTOR TO DESIGN THE ELECTRICAL
LIGHTNING SURGE ARRESTOR
BI TERMINAL
WEATHERPROOF JUNCTION BOX
(BUS SHELTER/TAXI STAND)
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX
L/ROAD/MES/SD/1003
1 1LROADMES-SD1003A.dgn
SCALE: NTS
TYPICAL SINGLE LINE DIAGRAM FOR NEW OG-BOX (BUS SHELTER / TAXI STAND )
METERPOWER GRID
32ADP MCB (TYPE C)
(PROVIDED BY PG)
3. INCLUSION OF TAXI STAND REQUIREMENT.
1. REVISED LIGHT FITTING DESCRIPTION
2. INCLUDE LEGEND AND REVISED NOTES.TAY K.CJUNE 2010A
NTS
NO. 8
NOTE
*SEE
MINIMUM RATING OF 10A SPN MCB 10KA.
SHALL BE APPROPRIATELY DESIGN WITH
8. OUTGOING LIGHTING CIRCUIT BREAKER
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYN
MALVIN HO
JULY 2007
NURLY
HADI WIJAYAADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
LSA
32A COMB BUSBAR
E
kwh METER kwh
(PG COMPARTMENT)
BI
INSTALLED BY PG
BI SUPPLIED AND
THAN 1 ohm
SHALL BE LESS
RING CIRCUIT
(PROVIDED BY PG)
(10KA)
FROM POWERGRID
OG-BOX
NEW
POWER GRID
40A DP
RCCB(100mA)
2A
T
C
CONTACTOR
32A DP
TIMERS
PROGRAMMABLE
7am
7pm TO
(10KA)
DP MCB (TYPE B)
32A
DP MCB (TYPE C)
DP ISOLATOR
TAXI STAND
BUS SHELTER/
NEW DB
SPARE COMPARTMENT
DP MCB
PE
RF
OR
MA
NC
E
TE
CH
NIC
AL
SP
ECIFIC
ATIO
N
LIG
HT
FIT
TIN
G
TO
63A
63A
SPARE COMPARTMENTFOR INTELLIGENT LIGHTING CONTROL BOX
HEAVY DUTY UPVC PIPES
PVC CABLES IN
HEAVY DUTY UPVC PIPES
ARMOURED CABLE IN
LSA
BI
BI
NOTES:
HEAVY DUTY UPVC PIPES
PVC CABLES IN
HEAVY DUTY UPVC PIPES
ARMOURED CABLE IN
OTHERWISE STATED.1. ALL DIMENSION ARE IN mm UNLESS
WITH SPECIFICATIONS.
2. THIS DRAWING TO BE READ IN CONJUNCTION
APPROVAL.3. ALL ARCHITECTURE DETAILS TO ARCH’S
BEFORE WORK COMMENCEMENT.4. CONTRACTOR SHOULD DO A SITE SURVEY
COMMENCEMENT OF INSTALLATION.
TO THE S.O. FOR APPROVAL PRIOR TO
5. SINGLE LINE DIAGRAMS SHALL BE SUBMITTED
FOR ALL LIGHTING.
6. ALTERNATE CIRCUITING SHALL BE PROVIDED
LATEST SS CP5.
INSTALLATION IN ACCORDANCE WITH THE
7. CONTRACTOR TO DESIGN THE ELECTRICAL
ITEM MARKED * TO 32A RATING.
8. CONTRACTOR IS RESPONSIBLE TO REPLACE
APPROPRIATELY.
9. OUTGOING CONTACTOR SHALL BE RATED
MINIMUM RATING OF 10A SPN MCB 10KA.
SHALL BE APPROPRIATELY DESIGN WITH
10. OUTGOING LIGHTING CIRCUIT BREAKER
DOUBLE POLEDP
MCB
RESIDUAL CURRENT CIRCUIT BREAKERRCCB
ISOLATOR
T
C
2A
LEGEND:
C/W BYPASS SWITCH (SETTING 7pm TO 7am)
PROGRAMMABLE TIMER WITH RS 232 INTERFACE UNIT
S MOTION SENSOR
MINIATURE CIRCUIT BREAKER
LIGHTNING SURGE ARRESTOR
BI TERMINAL
WEATHERPROOF JUNCTION BOX
1. REVISED LIGHT FITTING DESCRIPTION
2. INCLUDE LEGEND AND REVISED NOTES.
32A AND SPPG DP MCB FROM 63A TO 32A.3. REVISED POB /LINKWAY INCOMMING ISOLATOR RATING TO
(DBO BUS SHELTER/POB/LINKWAY)
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX
JUNE 2010
NO. 10
NOTE
*SEE
NO. 10
NOTE
*SEE
NO. 9
NOTE
*SEE
NO. 10
NOTE
*SEE
TYPICAL SINGLE LINE DIAGRAM FOR EXISTING OG-BOX (DBO BUS SHELTER /POB /LINKWAY) SCALE: NTS
A TAY K.CDrawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYN
MALVIN HO
JULY 2007
NURLY
HADI WIJAYAADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
L/ROAD/MES/SD/1004
LROADMES-SD1004A.dgn
C
S
C
LSA
BI BI TERMINAL
DP MCB (TYPE C)
kwh METER
(PG COMPARTMENT)
BI
INSTALLED BY PG
BI SUPPLIED AND
(PROVIDED BY PG)
(10KA)
FROM POWERGRID
POWER GRID
OG-BOX
EXISTING
DBO BUS SHELTER
EXISTING
63A * (SEE NOTE 8)
32A
40A DPRCCB(100mA)
2A
T
(10 KA)
SP
AR
E
(TYPE B)
DP MCB
CONTACTOR
32A DPTO 7am
7pm
TIMER
PROGRAMMABLE
DP MCB
PO
B
WIT
H
CO
VE
RE
D
RA
MP
S/
LIN
KW
AY
LIG
HT
FIT
TIN
G
FO
R
CO
VE
RE
D
SP
AR
E
PO
B
WIT
H
CO
VE
RE
D
RA
MP
S
LIG
HT
FIT
TIN
G
FO
R
CO
VE
RE
D
TO 7am
MIDNIGHT
CONTACTOR
32A COMB BUSBAR
32A COMB BUSBAR
CONTROL BOX
LIGHTING
INTELLIGENT
kwh METERPOWER GRID
32ADP MCB (TYPE C)
(PROVIDED BY PG)
DP ISOLATOR63A * (SEE NOTE 8)
POB/LINKWAY
NEW OG-BOX
32A DP
ISOLATOR
HEAVY DUTY UPVC PIPES
PVC CABLES IN
HEAVY DUTY UPVC PIPES
ARMOURED CABLE IN
E THAN 1 ohm
SHALL BE LESS
RING CIRCUIT
LSA
BI
A
-
B
- 1
-
2
-
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
MELVYN THONG
N.T.S. JULI JULY 2007
L/ROAD/MES/SD/1006
LROADMES-SD1006A.dgn
NURLY
STANDARD INSTALLATION DETAILS
MALVIN HO
A
TYPICAL DETAIL OF POB/LINKWAY/
BUS SHELTER/TAXI STAND/OG-BOX
DescriptionRev. Date App’dChk’dDesigned
By
Drawn
By
A JUNE 2012 CHING ANGELINEHADI
WIJAYAADRIAN
CHEONG
1.
2.
3.
INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.
ADD SPACE TO HOUSE INTELLIGENT LIGHTING DETECTION
SYSTEM CONTROLLER INSIDE OG-BOX.
ADD PROVISION OF Ø50mm HEAVY DUTY UPVC PIPE FOR
INTELLIGENT LIGHTING DETECTION SYSTEM.
TYPICAL DETAIL OF POB / LINKWAY / BUS SHELTER / TAXI STAND / OG-BOXSCALE: NTS
UV STABILISEDPOLYCARBONATE
UV STABILISEDPOLYCARBONATE
REMOVABLE PLATE
3273-A
ABLOY
FIX PLATE
REMOVABLE PLATE
27.5
280
82.5
REMOVABLE PLATE
27.5
280
1Ø KWH
METER
POWER
GRID
T’wood= 230
70
Std= 235
T’wood= 230
Std= 235
188
138
188
138
T’wood= 230 T’wood= 230
560
1Ø KWH
METER
POWER
GRID
BI Supply
and Installed
By PG
T’w
ood
=300
T’w
ood
=300
3273-A
ABLOY
3273-A
ABLOY
Depth
=
mm
450
100
EXTERNAL FRONT DOOR
FIX PLATE
Front
Back
Front
Back
Std
Casing
=560
EXTERNAL BACK DOOR
GLASS
EXTERNAL VIEW INTERNAL FRONT VIEW
PLAN VIEW
EXTERNAL BACK VIEW
Front
Back
SUPPORT FOR BREAKER
PARTITION
SUPPORTFOR BREAKER
EXTERNALFRONTDOOR
PARTITION
EXTERNAL FRONT DOOR
2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING
2 NOS Ø100mm HEAVY DUTY UPVCLEAD IN C/W 90^ LONG BEND PIPESFOR POWER GRID INCOMING CABLING
PLINTH C/W OPENINGFOR CABLE ENTRY
Lock
Lock
Lock
min
Overall Length = min 1320mmOverall Length = min 1320mm
420
Overall H
eig
ht =
min 1300
mm
Overall H
eig
ht =
min 1300
mm
Ø50mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER ADVERTISING PANEL
Ø50mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER ADVERTISING PANEL
Ø100mm HEAVY DUTY UPVC PIPE FOR BUS SHELTER/TAXI STANDELECTRICAL DISTRIBUTION
BUS SHELTER/TAXI STAND
Ø100mm HEAVY DUTY UPVC PIPEFOR BUS SHELTER/TAXI STAND ELECTRICAL DISTRIBUTION
Depth = min 450mm
Depth = min 450mm
Back
Depth = min 450mm
Front
REMOVABLEPLATE
3273-A
ABLOY
Lock
ELEVATION 1 ELEVATION 2
INTERNAL SIDE VIEW
SECTION A-A
20070
PARTITION
SUPPORT FOR INTELLIGENTLIGHTING DETECTION SYSTEMCONTROLLER
EXTERNAL FRONT DOOR
EXTERNALFRONTDOOR
PARTITION
SUPPORT FORINTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLER
SECTION B-B
70200 70
INTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLERFOR POB
Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION
INTELLIGENTLIGHTINGDETECTIONSYSTEMCONTROLLERFOR POB
POB/LINKWAY
Ø100mm HEAVY DUTY UPVC PIPEFOR POB/LINKWAY ELECTRICAL DISTRIBUTION
SYSTEM FOR BUS SHELTER
TYPICAL LIGHTING AND LIGHTNING PROTECTION
LROADMES-SD1007A.dgn
L/ROAD/MES/SD/1007
TO M&E SPECIFICATIONPROPOSED LIGHT FITTING (IP65)
TO M&E SPECIFICATIONPROPOSED LIGHT FITTING (IP65)
1 1
ON SITE & TO SO APPROVAL)(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)
(LOCATION TO BE DETERMINED
0 0.5 1 1.5 2 2.5 Metres
Scale 1:50
TYPICAL LIGHTING LAYOUT PLAN
1:50
REVISED DETAILS
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
A
A
3°
FA
LL
FA
LL
ROOF EAVES ABOVE
MIN.
600
3000
3°
FA
LL
1 2 3
1 2 3
7500
A-
75030003000750
FA
LL
200
125
27
00
300
THERMOPLASTIC ROAD MARKING MATERIALS
200 WIDE YELLOW LINE IN HOT APPLIED
3
2
1
3
LINE OF ROAD KERB OR ROAD RESERVE LINE
4mm THK. TEMPERED GLASS
NOTICE BOARD WITH ALUM. FRAME C/W
MS ANGLE ROOF FASCIA TO ENGR’S DTL
MFR’S DTL
ROOF CAPPING @ 1500mm C/C TO
2
7500
75030003000750
1500150015001500
3000
27
00
300
L/ER373/AR/TD/5003
L/ER373/AR/TD/5003
L/ER373/AR/TD/5003
L/ER373/AR/TD/5003
L/ER373/AR/TD/5003
AL/ER373/AR/TD/5003
AL/ER373/AR/TD/5003
LATEST REVISION
DRAWING NO. L/CFADC/AR/BS/0005
LTA ARCHITECTURAL DESIGN CRITERIA
ONCOMING TRAFFIC IN ACCORDANCE TO
BUS SHELTER ADDRESS PLATE TO FACE
M.S. RHS POST BELOW (C1)
M.S. RHS POST (C1)
1400
75
0 (C
LE
AR)
300
GRANOLITHIC FINISHES TO SO’S APPROVAL
CONC. SLAB COMPLETE WITH 25mm THK
ALUM. BENCH ALUM. BENCH
POWDER COATED ALUM. ’F’ TYPE CAPPING
PANEL TO SO’S APPROVAL
TOP PANEL AND 0.7mm THK UNDERSIDE
ROOF PANEL COMPLETE WITH MIN. 1mm THK
MIN. 10mm THK. ALUM. HONEY COMB
LITTER BIN BY OTHERS
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYNA DEC 2010
MALVIN HO
JULY 2007
NURLY
TAY K.CHADI WIJAYA
ADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
HEAVY DUTY UPVC PIPEPVC CABLE IN Ø25mm
(TOTAL RESISTANCE < 10ohm)EARTH PIT(TOTAL RESISTANCE < 10ohm)
EARTH PIT
OG BOXNEW
FROM 0G-BOX TO ADVERTISING PANELUPVC PIPE C/W PULL WIRES 1 NO. Ø50mm HEAVY DUTY
INCOMING CABLEPIPES FOR SP POWERGRID’S UPVC HEAD-IN 90° LONG BEND 2 NOS. Ø100mm HEAVY DUTY
(SEE DETAIL "1")DOWNSTREAM EDGE OF BUS SHELTERPANEL TO BE LOCATED AT THE DRAW WIRES FOR ADVERTISEMENT1 NO. ELECTRICAL PIPE WITH
DOWN CONDUCTOR
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
SCALE 1:50
SITE
PANEL TO BE DETERMINED ON
LOCATION OF ADVERTISEMENT
DETAIL "1"NTS
AND POWERGRID’S APPROVAL
TO SITE CONDITIONS
SHALL BE SUBJECTED
(IP55) LOCATION
NEW OG BOX
PANEL
FROM OG-BOX TO ADVERTISING
UPVC PIPE C/W PULL WIRES
1NO. Ø50mm HEAVY DUTY
PANEL
ADVERTISEMENT
TYPICAL LIGHTNING PROTECTION SYSTEM (ROOF PLAN)
EARTH ROD
GROUND LEVEL
PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP
16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,
COUPLING
COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC
GALVANISED COVERHOT DIP
ALL AROUNDCONCRETE HAUNCH
50
LROADMES-SD1008A.dgn
L/ROAD/MES/SD/1008
Scale: N.T.S.
Scale: N.T.S.
BONDING TO STEEL SUPPORT POSTTYPE 1 - ELEVATION OF LIGHTNING
DETAIL 2
Scale: N.T.S.
SECTION H-H
25mm x 3mm COPPER TAPE
STEEL SUPPORT POST
ALUMINIUM OR
TO STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
B-BOND
(IP65) TO M&E SPECIFICATIONPROPOSED LIGHT FITTING
UPVC PIPEHEAVY DUTYIN Ø25mm PVC CABLECONCEALED
M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT
M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT
M&E SPECIFICATIONFITTING (IP65) TO PROPOSED LIGHT
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
JUNCTION BOXCONCEALED
PITEARTH
EARTH PIT
REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
FOR SP POWERGRID INCOMING CABLINGPIPES LEAD IN 90° LONG BEND PIPES2 NOS Ø100mm HEAVY DUTY UPVC
EARTH PIT
UPVC PIPEIN Ø25mm HEAVY DUTYCONCEALED PVC CABLE
POWERGRID’S APPROVALTO SITE CONDITIONS AND SP
LOCATION SHALL BE SUBJECTED NEW OG BOX (IP54)
SEE DETAIL ’3’
SEE DETAIL ’2’GROUND)150mm ABOVE COLUMN (MIN. STRUCTUREBONDING TO
SEE DETAIL ’3’
CABLE CONNECTIONCONCEALED JUNCTION BOX FOR
CABLE CONNECTIONCONCEALED JUNCTION BOX FOR
FOR CABLE CONNECTION CONCEALED JUNCTION BOX
REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
1:50
11
0 0.5 1 1.5 2 2.5 Metres
Scale 1:50
BUS SHELTER
TYPICAL ELECTRICAL INSTALLATION DETAILS FOR
REVISED DETAILS
SECTION PLAN
ELEVATION PLANSEE DETAIL ’3’ABOVE GROUND)COLUMN (MIN. 150mm BONDING TO STRUCTURE
SEE DETAIL ’3’
GROUND)SEE DETAIL ’2’COLUMN (MIN. 150mm ABOVE BONDING TO STRUCTURE
UPVC PIPE 1 NO. Ø100mm HEAVY DUTY ARMOURED CABLE IN
LATEST REVISION
DRAWING NO. L/CFADC/AR/BS/0005
LTA ARCHITECTURAL DESIGN CRITERIA
ONCOMING TRAFFIC IN ACCORDANCE TO
BUS SHELTER ADDRESS PLATE TO FACE
GLASS PANEL OF 900 X 900)
VIEW THROUGH THE FRONT
TO BE IN FULL UNOBSTRUCTED
OF POSTERS OF SIZE 940 X 940,
(SHALL ALLOW CLEAR MOUNTING
C/W 4mm THK. TEMPERED GLASS
NOTICE BOARD WITH ALUM. FRAME
A
ROAD
450
300
MIN. 6003000
2700300
–2
692
2300
–2388
–25
34
200 (
MIN.)
FFL
1 2 3
45
0 (B
EN
CH)
7500
75030003000750
23
00
–2
38
8
–2
692
1000 1000
97
01000
200
15
0
217
0
1500150015001500
ALUM. BENCH
ALUM. BENCH
GRANOLITHIC FINISHES TO SO’S APPROVAL
CONC. SLAB COMPLETE WITH 25mm THK
45
0
MS ANGLE ROOF FASCIA (T1)
M.S. SHS (R2)
M.S. ’C’ CHANNEL RAFTER (R1)
LIGHT FITTING TO M&E SPECS
M.S. RHS POST (C1)
POWDER COATED ALUM. ’F’ TYPE CAPPING
LITTER BIN BY OTHERS
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYNA DEC 2010
MALVIN HO
JULY 2007
NURLY
TAY K.CHADI WIJAYA
ADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
H-
H
-
SCALE NTS
SCALE 1:50
DETAIL 3
L/ROAD/MES/SD/1009
1 1LROADMES-SD1009A.dgn
FOR BUS SHELTER
TYPICAL EQUIPOTENTIAL BONDING DETAILS
REVISED DETAIL
1:50
IN Ø25mm HEAVY DUTY UPVC PIPE
6mÀ PVC EARTH BONDING CABLE
AND POWERGRID’S APPROVAL
TO SITE CONDITIONS
SHALL BE SUBJECTED
(IP55) LOCATION
NEW OG BOX
CABLING
POWERGRID INCOMING
BEND PIPES FOR
LEAD IN 90° LONG
DUTY UPVC PIPES
2 NOS Ø100mm HEAVY
DUTY UPVC PIPE
Ø25mm HEAVY
BONDING CABLE IN
6mÀ PVC EARTH
Scale 1:50
FOR BUS SHELTERTYPICAL EQUIPOTENTIAL BONDING DETAILS
LATEST REVISION
DRAWING NO. L/CFADC/AR/BS/0005
LTA ARCHITECTURAL DESIGN CRITERIA
ONCOMING TRAFFIC IN ACCORDANCE TO
BUS SHELTER ADDRESS PLATE TO FACE
GLASS PANEL OF 900 X 900)
VIEW THROUGH THE FRONT
TO BE IN FULL UNOBSTRUCTED
OF POSTERS OF SIZE 940 X 940,
(SHALL ALLOW CLEAR MOUNTING
C/W 4mm THK. TEMPERED GLASS
NOTICE BOARD WITH ALUM. FRAME
FFL
1 2 3
45
0 (B
EN
CH)
7500
75030003000750
23
00
–2
38
8
–2
692
1000 1000
97
01000
200
15
0
217
0
1500150015001500
ALUM. BENCH
ALUM. BENCH
GRANOLITHIC FINISHES TO SO’S APPROVAL
CONC. SLAB COMPLETE WITH 25mm THK
45
0
MS ANGLE ROOF FASCIA (T1)
M.S. SHS (R2)
M.S. ’C’ CHANNEL RAFTER (R1)
LIGHT FITTING TO M&E SPECS
M.S. RHS POST (C1)
POWDER COATED ALUM. ’F’ TYPE CAPPING
LITTER BIN BY OTHERS
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYNA DEC 2010
MALVIN HO
JULY 2007
NURLY
TAY K.CHADI WIJAYA
ADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
WATER INGRESS
SEALANT TO PREVENT
WITH APPROVED
UPVC PIPE SEALED
WITH CONCRETE SURFACE
TO HAVE DIRECT CONTACT
TO PREVENT ALUMINIUM TAPE
CONCRETE SURFACE PAINTED OVER
BOLTED ON BEARING PLATE.
ALUMINIUM CONDUCTOR TAPE
BI-METALLIC BOND/CLAMP AND
(SEE DETAIL X)
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
(SEE DETAIL X)
TO HAVE DIRECT CONTACT WITH CONCRETE SURFACE
PAINTED OVER TO PREVENT ALUMINIUM TAPE
BOLTED ON BEARING PLATE CONCRETE SURFACE
BI-METALLIC BOND/CLAMP AND ALUMINIUM CONDUCTOR TAPE
1 1
STANDARD INSTALLATION DETAILS
JULI JULY 2007
Drawing No. :
Drawn
Checked
ofSheet
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
A
MALVIN HONURLY
Scale
Designed
NTS
L/ROAD/MES/SD/1010
LROADMES-SD1010A.dgnDescriptionRev. Date App’dChk’d
Designed
By
Drawn
By
A JUNE 2012 CHINGWIJAYA
HADICHEONGADRIAN
TAY K.C.
A4
10x10mm CHAMFER
TO ROADSIDE DRAIN
12°
PILE CAP TO ENGR’S DETAIL
R.C. GRATING
2800
–3
84
22
00
–2
58
4
1100
100
85
514
5
370 2060 370
1800
MIN. 40 MIN. 40
EQEQ
FALL
75
0
75
67
5
7002200
75
675
625
15°
AND ROOF
´ OF POB DECK
EQ
EQ
25
25
25
17
00
TO ENGR’S DETAIL
TYPICAL CROSS BEAM
CHIPPING FINISHED TO S.O’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
RC COLUMN TO ENGR’S DETAIL WITH
200
600
10x10mm CHAMFER
TO ROADSIDE DRAIN
12°
PILE CAP TO ENGR’S DETAIL
2800
–3
84
22
00
–2
58
4
1100
100
85
514
5
370 2060 370
1800
MIN. 40 MIN. 40
EQEQ
FALL
75
0
75
67
5
7002200
75
675
625
15°
TO ENGR’S DETAIL
TYPICAL CROSS BEAM
CHIPPING FINISHED TO S.O’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
RC COLUMN TO ENGR’S DETAIL WITH
200
600
17
00
EQ
EQ
25
25
25
15
0
15
0
Ø45mm S.S. RAILING Ø45mm S.S. RAILING
COATING FINISH TO SO’S APPROVAL
TO ENGR’S DETAIL COMPLETE WITH SPRAY
CHS HOT-DIPPED GALVANISED M.S. POST
COATING FINISH TO SO’S APPROVAL
TO ENGR’S DETAIL COMPLETE WITH SPRAY
CHS HOT-DIPPED GALVANISED M.S. MEMBER
AND ROOF
´ OF POB DECK
COATING FINISH TO SO’S APPROVAL
TO ENGR’S DETAIL COMPLETE WITH SPRAY
CHS HOT-DIPPED GALVANISED M.S. POST
COATING FINISH TO SO’S APPROVAL
TO ENGR’S DETAIL COMPLETE WITH SPRAY
CHS HOT-DIPPED GALVANISED M.S. MEMBER
57
00 (
MIN.)
1000 (V
ARIE
S)
54
00 (
MIN.)
1000 (V
ARIE
S)
FALL FALL
CHIPPING FINISHED TO S.O’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
MEMBRANE TO SO’S APPROVAL
PLANTING TROUGH WITH WATERPROOFING
MEMBRANE TO SO’S APPROVAL
PLANTING TROUGH WITH WATERPROOFING
CHIPPING FINISHED TO S.O’S APPROVAL
20mm THK PRECASTED GRANOLITHIC
R.C. GRATING
TO OG BOX TO M&E SPECIFICATIONS
Ø50mm PVC PIPE FOR LIGHTING CIRCUITS
POB DECK
FFL OF
Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR Ø15mm S.S. ROD AT NOT MORE THAN 100mm CLEAR
POB DECK
FFL OF
FOOTPATH LEVEL
ROAD LEVEL
FOOTPATH LEVEL
ROAD LEVEL
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
WITH MIN. 1mm THK. TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEY COMB ROOF PANEL COMPLETE
SYSTEM AND REVISED DETAILS.
TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION
FOR COVERED PEDESTRIAN OVERHEAD BRIDGE
TYPICAL LIGHTNING PROTECTION SYSTEMFOR COVERED POB (EXPRESSWAY)
FOR COVERED POB (NON-EXPRESSWAY)
DETAIL X
EARTH ROD
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
EARTH ROD
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm ALUMINIUM CONDUCTOR TAPE
ENCASED IN Ø50mm HEAVY DUTY UPVC PIPE
25mm x 3mm COPPER CONDUCTOR TAPE
(TOTAL EARTH RESISTANCE 10ohms)
EARTH PIT
(TOTAL EARTH RESISTANCE 10ohms)
EARTH PIT
1500
1500
IN ACCORDANCE TO SS 555 REQUIREMENTS
CONTRACTOR TO ENSURE THAT BONDED
PURPOSE MADE BOND
TEST BOX AT POB)
(SEE TYPICAL LIGHTNING PROTECTION
IN ACCORDANCE TO SS 555 REQUIREMENTS
GROUND LEVEL (SURFACE MOUNT)
AT 1500mm HEIGHT FROM
150mm x 150mm TEST LINK BOX
IN ACCORDANCE TO SS 555 REQUIREMENTS
CONTRACTOR TO ENSURE THAT BONDED
PURPOSE MADE BOND
TEST BOX AT POB)
(SEE TYPICAL LIGHTNING PROTECTION
IN ACCORDANCE TO SS 555 REQUIREMENTS
GROUND LEVEL (SURFACE MOUNT)
AT 1500mm HEIGHT FROM
150mm x 150mm TEST LINK BOX
PROTECTION
TEST
BOX
LIGHTNING
NUT INSERTM5 COUNTERSUNK BOLT
SECTION Y-Y
TEST BOX AT POBTYPICAL LIGHTNING PROTECTION
(WITH COVER)ELEVATION VIEW
(WITHOUT COVER)ELEVATION VIEW
DUTY UPVC PIPES
ENCASED HEAVY
COVER PLATE
STAINLESS STEEL
DUTY UPVC PIPES
ENCASED HEAVY
R.C. COLUMNCOPPER TAPE
25mm x 3mm
CONNECTOR
BI-METALLIC
COVER PLATE
STAINLESS STEEL
ALUMINIUM TAPE
25mm x 3mm
CONNECTOR
BI-METALLIC
COPPER TAPE
25mm x 3mm
ALUMINIUM TAPE
25mm x 3mm
Y-
Y-
EARTH ROD
GROUND LEVEL
PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP
16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,
COUPLING
COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC
GALVANISED COVERHOT DIP
ALL AROUNDCONCRETE HAUNCH
50
DescriptionRev. Date App’dChk’dDesigned
By
Drawn
By
A JUNE 2012 CHINGWIJAYA
HADICHEONGADRIAN
TAY K.C.SYSTEM.
TO AMEND TO LATEST STANDARD FOR LIGHTNING PROTECTION
1 1
NTS
EARTHING ROD
25 x 3mm ALUMINIUM TAPE
GROUND LEVEL
HEAVY DUTY UPVC PIPE
Ø50mm HEAVY DUTY UPVC PIPE25 x 3mm COPPER TAPE ENCASED IN
BOND TO SUPPORT POST.25 x 3mm ALUMINIUM TAPE
L/ROAD/MES/SD/1011
LROADMES-SD1011A.dgn
(TOTAL EARTH RESISTANCE <10ohms>EARTH PIT REFER TO DETAIL ’3’
REFER TO DETAIL ’2’
(REFER TO DETAIL 1)ELECTRICALLY CONTINUOUS.THE NEW COVERED POB AND RAILING ARE LIGHTNING PROTECTION SYSTEM FORCONTRACTOR TO ENSURE THAT THE NEW
OVERHEAD BRIDGE
FOR NEW ROOF OVER EXISTING PEDESTRIAN
TYPICAL LIGHTNING PROTECTION SYSTEM
THAT BONDED IN ACCORDANCE TO LATEST SS 555.REQUIREMENT. CONTRACTOR TO ENSURE BONDING DETAILS TO NEW ROOF SPECIALIST
(LATEST SS 555)GROUND LEVEL (SURFACE MOUNT)AT 1500mm HEIGHT FROM 150mm x 150mm TEST LINK BOX
SCALE 1 : 50
OVERHEAD BRIDGE
FOR NEW ROOF OVER EXISTING PEDESTRIAN
TYPICAL LIGHTNING PROTECTION SYSTEM
ENGR’S DETAIL
WITH BOLTS/NUTS TO
PLATE WITH 90° ANGLE
12mm THK MS BEARING
ALUMINIUM TAPE
NEW 25mm x 3 mm
WITH CONCRETE SURFACE
TO HAVE DIRECT CONTACT
TO PREVENT ALUMINIUM TAPE
CONCRETE SURFACE PAINTED OVER
BOLTED ON BEARING PLATE.
ALUMINIUM CONDUCTOR TAPE
BI-METALLIC BOND/CLAMP AND
ENGR’S DETAIL
RAILING TO
DETAIL 1N.T.S.
COVER PLATE
STAINLESS STEEL
COPPER TAPE
25mm x 3mm
CONNECTOR
BI-METALLIC
DUTY UPVC PIPES
ENCASED Ø50mm HEAVY
ALUMINIUM TAPE
25mm x 3mm
DUTY UPVC PIPES
Ø50mm HEAVY
DETAIL 2N.T.S.
DETAIL 3N.T.S.
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYNA DEC 2010
MALVIN HO
JULY 2007
NURLY
TAY K.CHADI WIJAYA
ADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
A4
FFL
EXISTING POB DECK EQEQ EQEQ
EXISTING PLANTING TROUGHS
TYPICAL SECTION OF POB DECK
FFL
TYPICAL SECTION OF POB STAIRCASE
SCALE 1:20
TO VERIFY ON SITE FOR ACTUAL WIDTH OF POB DECK
ROOF EAVE TO EXTEND AT NOT MORE THAN HALF THE WIDTH OF PLANTING TROUGH
SCALE 1:20
REFER TO SECTION OF POB DECK FOR ANNOTATION
TO VERIFY ON SITE FOR ACTUAL WIDTH OF STAIRCASE
& COLUMN
EXISTING POB STAIRCASE
1100
100
855
100
45
6mm THK S.S. FLAT BAR
6mm THK S.S. FLAT BAR
FFL
Ø45mm S.S. RAILING
MORE THAN 100mm CLEAR
Ø15mm S.S. ROD AT NOT
MOUNTING DETAILS
REFER TO ENGR’S DWG. FOR
TYPICAL ELEVATION OF RAILING ON POB DECKSCALE 1:20
SPACING OF POSTS AT REGULAR INTERVAL TO ENGR’S DETAIL
EQEQEQEQ
TO SO’S APPROVAL
Ø45mm S.S. HANDRAIL
TO SO’S APPROVAL
Ø45mm S.S. RAILING
TO S.S. PLATE TO ENGR’S DETAIL
6mm THK. S.S. FLAT BAR TO BE WELDED
100mm CLEAR TO SO’S APPROVAL
Ø15mm S.S. ROD AT NOT MORE THAN
6mm THK S.S. FLAT BAR TO SO’S APPROVAL
SCALE 1:20
TYPICAL ELEVATION OF RAILING ON POB STAIRCASE
800
1100
30
TOP PANEL TO SO’S APPROVAL
PANEL COMPLETE WITH MIN. 1 mm THK
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
300VARIES DEPEND ON SITE300
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. SUPPORT POST TO ENGR’S DETAILMIN.
2100
FLEXIBLE CONDUIT IN SUPPORT POST
ELECTRICAL CABLE CONCEALED IN PVC
MIN.40
1100
S.S. ROD AT NOT MORE THAN 100mm CLEAR
S.S. FLAT BAR AT REGULAR INTERVAL AND
NEW Ø45mm S.S. RAILNG COMPLETE WITH
VARIES DEPEND ON SITE
300VARIES DEPEND ON SITE300
TO SO’S APPROVAL
WITH MIN. 1mm THK. TOP PANEL
COMB ROOF PANEL COMPLETE
MIN. 10mm THK. ALUM. HONEY
NOT MORE THAN 100mm CLEAR
INTERVAL AND S.S. ROD AT
S.S. FLAT BAR AT REGULAR
HARDRAIL COMPLETE WITH
NEW Ø45mm S.S. RAILNG AND
MIN.
2100
1100
800
M.S. SUPPORT POST TO ENGR’S DETAIL
TO ENGR’S DETAIL
M.S. SUPPORT POST
APPLICABLE RANGE 2700 TO 3600
TO SPECIFICATION
CONVENTIONAL BALLAST
SPECIFICATIONS
WITH THE AUTHORITY’S
LIGHT FITTING TO COMPLY
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A4
Date
Approved
Rev.
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
MELVYN THONG
N.T.S. JULI JAN 2010
L/ROAD/MES/SD/1012
LROADMES-SD1012A.dgn
SALIM
STANDARD INSTALLATION DETAILS
MALVIN HOADRIAN CHEONG/
A
FOR SINGLE POST COVERED LINKWAY
LIGHTNING PROTECTION SYSTEM
TYPICAL CABLE ENTRY DETAIL AND
DescriptionRev. Date App’dChk’dDesigned
By
Drawn
By
A JUNE 2012 CHING ANGELINEWIJAYA
HADICHEONGADRIAN
INCLUSION OF TAXI STAND OG-BOX REQUIREMENT.
AMENDMENT TO LIGHTNING PROTECTION SYSTEM.2.
1.
TEAKWOOD FOR MOUNTING
CABLE GLAND FOR ARMOURED CABLE
300x300x20 THK MS PLATE
C1 WELDED ALL-ROUND TO
10mm THK NON SHRINK GROUT
MOUNTED ON TEAKWOOD BLOCK
TERMINAL BLOCK CONNECTOR
FLAT BAR TO SUPPORT TEAKWOOD BLOCK
FROM OG BOX TO FIRST LIGHTING POINT
ARMOURED CABLE IN Ø100mm HEAVY DUTY UPVC PIPE
UPVC PIPE
IN Ø50mm HEAVY DUTY
COPPER TAPE
25mm x 3mm
IN PVC COATED FLEXIBLE STEEL CONDUIT
PVC CABLE + 2.5mÀ EARTH CABLE
<10 ohms)
RESISTANCE
(TOTAL EARTH
PROTECTION SYSTEM
FOR LIGHTNING
EARTH PIT
500
DETAIL 1
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
FLEXIBLE STEEL CONDUIT TO M&E DWG. & SPEC.
PVC CABLE CONCEALED IN PVC COATED
FOR PVC CABLES TO M&E DWG. & SPEC.
G.I. CONDUIT ALONG BACK OF M.S. FASCIA
FOR INCOMING CABLES TO M&E DETAIL
PVC COATED FLEXIBLE STEEL CONDUIT
FOR PVC CABLES TO M&E DWG. & SPEC.
G.I. CONDUIT ALONG BACK OF M.S. FASCIA
FLEXIBLE STEEL CONDUIT IN SUPPORT POST
PVC CABLE CONCEALED IN PVC COATED
ROOF SPECIALIST’S REQUIREMENTS.
BONDING DETAILS TO
´
A
GASKET
S/S SCREW
´
3° FALL
S/S SCREW
ALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEENALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEEN
1500
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
SECTION J-J
ALUM. ROOF FRAME & M.S. MEMBER
ISOLATOR / BONDING TAPE BETWEEN
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
40
40
FFL
B-
B-
´
´
MS BASE PLATE TO ENGR’S DETAIL
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
BY POST CAPPING
OPENING FOR INCOMING CABLES COVERED
20mm THK GRANOLITHIC FINISHES TO SO’S APPROVAL
CONC. SLAB TO ENGR’S DTL COMPLETE WITH
RC FOOTING TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
50 x 50 x 3 ALUM ANGLE PLATE
MS RHS TO ENGR’S DETAIL
100 100
10
750
REF. DWG. NO. L/STLLW/AR/STD/1002
Scale 1:5
300 TOP PANEL TO SO’S APPROVAL
PANEL COMPLETE WITH MIN. 1mm THK.
MIN. 10mm THK. ALUM. HONEYCOMB ROOF
WITH MIN. 1mm THK.TOP PANEL TO SO’S APPROVAL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL COMPLETE
TO SO’S APPROVAL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
TO SO’S APPROVAL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
750
–81
750
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
ALUM FLASHING PIECE BOLTED AT BOTH END
3°
3°
(TO BE PROVIDED AT 1ST & LAST POST ONLY)
BY POST CAPPING
OPENING FOR INCOMING CABLES COVERED
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
15
0
C-
C-
SECTION C-C
M.S. ’C’ CHANNEL RAFTER TO ENGR’S DETAIL
TO SO’S APPROVAL
COMPLETE WITH MIN. 1mm THK. TOP PANEL
MIN. 10mm THK. ALUM. HONEYCOMB ROOF PANEL
ALUM. ROOF CAPPING FOR ROOF PANEL TO MFR’S DETAIL
TO MFR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF PANEL
M.S. ANGLE ROOF FASCIA TO ENGR’S DETAIL
M.S. RHS POST @ 3000 mm C/C TO ENGR’S DETAIL
TO MFR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF PANEL
K-
K-
M.S. ’C’ CHANNEL RAFTER @ 3000 mm C/C TO ENGR’S DETAIL
2100 (
MIN.) (N
TS)
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC. & SHALL NOT PROTRUDE FROM M.S. RAFTER /
LIGHT FITTING MOUNTING BRACKET TO CONTRACTOR PROPOSAL
CONTRACTOR TO PROPOSE FIXING BRACKET FOR LIGHT FITTING
LIGHT FITTING TO M&E SPEC & SHALL NOT PROTRUDE FROM M.S. RAFTER /
(DESIGN TO REFER TO ARCH DWG)
LIGHT FITTING TO M&E SPEC
FLEXIBLE STEEL CONDUIT IN SUPPORT POST
PVC CABLE CONCEALED IN PVC COATED
SEE DETAIL X
SECTION K-K
SECTION B-B
SECTION C-C
DETAIL X
TYPICAL CROSS SECTION FOR SINGLE POST COVERED LINKWAY
TYPICAL LONGITUDINAL CROSS SECTION AT ROOF WITH LEVEL DIFFERENCE
SECTION Y-Y
25mm x 3mm COPPER TAPE
STEEL SUPPORT POST
TO STEEL SUPPORT POSTM8 COPPER BOLT
Y-
Y-
EARTH ROD
GROUND LEVEL
PROTECTION EARTH LABELINCLUSIVE OF LIGHTNINGEARTH ROD CLAMP
16mm DIA COPPER)(min. 2 Nos. 1.8m LENGTH,
COUPLING
COPPER CONDUCTOR TAPEPIPE C/W 25mm X 3mmØ50mm HEAVY DUTY UPVC
GALVANISED COVERHOT DIP
ALL AROUNDCONCRETE HAUNCH
50
SECTION E-E
ALUMINIUM TAPE
SUPPORT POST
ALUMINIUM OR STEEL
Scale: N.T.S.
B-BOND
COPPER TAPE
Scale: N.T.S.
M8 STAINLESS STELL BOLT
M8 COPPER BOLT
CONNECTOR
BI-METALLIC
E-
E
-
SECTION H-HScale: N.T.S.
Scale: N.T.S.
BONDING TO STEEL SUPPORT POSTTYPE 1 - ELEVATION OF LIGHTNING
DETAIL 2
25mm x 3mm COPPER TAPE
STEEL SUPPORT POST
ALUMINIUM OR
TO STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
B-BOND
FOR COVERED LINKWAY
TYPICAL LIGHTNING PROTECTION SYSTEM
H
-
H-
ROOF TO STEEL SUPPORT POSTELEVATION OF BONDING FROM
DETAIL 1
0 2 3 4 5 Metres0.5
Scale 1:100
1.51
A
1:100
REVISED DETAILS L/ROAD/MES/SD/1014
LROADMES-SD1014A.dgn 1 1
Scale: N.T.S.
DETAIL 3
LIGHTNING PROTECTION SYSTEM LAYOUT PLAN
FRONT ELEVATION (LIGHTNING PROTECTION SYSTEM SHALL BE APPLIED FOR ALL TYPE OF LINKWAY)
FRONT ELEVATION 1
Scale 1:50
STRUCTUREEXISTING BONDED TO
PITEARTH
PITEARTH
PITEARTH
PITEARTH
SEE DETAIL 2(MIN 150mm ABOVE FLOOR LEVEL)BONDING TO STRUCTURE COLUMN
SEE DETAIL 2(MIN 150mm ABOVE FLOOR LEVEL)BONDING TO STRUCTURE COLUMN
Scale 1:100
Scale 1:100
SEE DETAIL 2ABOVE FLOOR LEVEL)COLUMN (MIN 150mm BONDING TO STRUCTURE
SEE DETAIL 3
SEE DETAIL 3
SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
SEE DETAIL 1SPECIALIST’S REQUIREMENTS)(BONDING DETAILS TO ROOFLIGHTNING PROTECTION SYSTEMBONDING TO UPPER ROOF
SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
SEE DETAIL 1REQUIREMENTSROOF SPECIALIST’S BONDING DETAILS TO
SEE DETAIL 3
SEE DETAIL 2
PITEARTH
SEE DETAIL 3
SEE DETAIL 2FLOOR LEVEL)(MIN 150mm ABOVE STRUCTURE COLUMN BONDING TO
Scale 1:50
Scale 1:50
1 2 3 4 5 6 7
1 2 4 5 7
FRONT ELEVATION 1 (WITHOUT LEVEL DIFFERENCE)
FRONT ELEVATION WITH LEVEL DIFFERENCE
3 86 9 10
FFL
(CLEAR)
TO POWERGRID’S APPROVAL)
(LOCATION TO BE DETERMINED ON SITE &
OG BOX ON CONC. PLINTH TO M&E DTLS
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
PANEL TO MFR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF
TOP PANEL TO SO’S APPROVAL
PANEL COMPLETE WITH MIN. 1mm THK.
MIN. 10mm THK. ALUM. HONEY COMB ROOF
M.S. RHS POST TO ENGR’S DETAIL
15001500 15001500 15001500 15001500 1500150015001500
750300030003000300030003000750
820
12
00
15
0
200
2100 (
MIN.)
–2
35
2
–2
107 (
MIN.
2100
CL
EA
R)
–2
45
OG BOX
OG BOX
FFL
FFL
ALUM FLASHING PIECE
FFL(CLEAR)
TO POWERGRID’S APPROVAL)
(LOCATION TO BE DETERMINED ON SITE &
OG BOX ON CONC. PLINTH TO M&E DTLS
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
PANEL TO MFR’S DETAIL
ALUM. ROOF CAPPING FOR ROOF
TOP PANEL TO SO’S APPROVAL
PANEL COMPLETE WITH MIN. 1mm THK.
MIN. 10mm THK. ALUM. HONEY COMB ROOF
TO ENGR’S DETAIL
M.S. ANGLE ROOF FASCIA
75030003000750
1500 1500 1500 1500750 3000 3000 750
1500150015001500750 3000 3000 3000 750
150015001500150015001500 –81
–81
–2
107 (
MIN.
2100
CL
EA
R)
2100 (
MIN.)
–2
35
2
–2
107 (
MIN.
2100
CL
EA
R)
–2
45
M.S. RHS POST TO ENGR’S DETAIL
M.S. RHS POST TO ENGR’S DETAIL
82012
00
15
0200
2100
–2
35
2
–2
107 (
MIN.
2100
CL
EA
R)
–2
45
EL/ER187/AR/TD/3006
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
A
DescriptionRev. Date By App’dChk’d
THONG
MELVYNA DEC 2010
MALVIN HO
JULY 2007
NURLY
TAY K.CHADI WIJAYA
ADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
0 0.5 1 1.5 2 2.5 Metres
Scale 1:501 1
LIGHT FIXTURE TO M&E SPECIFICATION
SCALE 1 : 501:50
L/ROAD/MES/SD/1015
LROADMES-SD1015-.dgn
-
SCALE 1 : 50
LIGHT FIXTURE TO M&E SPECIFICATION
AND NEW ROOF OVER EXISTING POB
TYPICAL LIGHTING SYSTEM FOR NEW POB
TAY K.C HADI WIJAYAADRIAN CHEONG/
CNV NOV 2010
H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm
FLEXIBLE CONDUIT FOR LIGHTINGPVC CABLE IN PVC COATED
FLEXIBLE CONDUIT FOR LIGHTINGPVC CABLE IN PVC COATED
ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN
H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm
TYPICAL LIGHTING SYSTEM
FOR NEW COVERED POB
TYPICAL LIGHTING SYSTEM
FOR NEW ROOF OVER EXISTING POB
CABLES IN PIPE SLEEVE
END OF POB
IN GI CONDUIT PVC CABLE
JUNCTION BOXWEATHERPROOF
JUNCTION BOXWEATHERPROOF
JUNCTION BOXWEATHERPROOF
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
DescriptionRev. Date By App’dChk’d
STANDARD INSTALLATION DETAILS
1000
1500
200600
17
00
EQ
EQ
25
25
25
FOOTPATH LEVEL
ROAD LEVEL
5680 (
MIN.
54
00)
900 (V
ARIE
S)
2800
–384
2200
–2584
1100
100
855
14
5
370 2060 370
1800MIN. 40 MIN. 40
EQEQ
750
75
67
5
7002200
75
675
625
150
15°
12°
MIN.
300
1000
1500
200600
17
00
EQ
EQ
25
25
25
FOOTPATH LEVEL
ROAD LEVEL
5680 (
MIN.
54
00)
900 (V
ARIE
S)
2800
–384
2200
–2584
1100
100
855
14
5
370 2060 370
1800MIN. 40 MIN. 40
EQEQ
750
75
67
5
7002200
75
675
625
150
15°
12°
MIN.
300
LEGEND:
1 1
MIN.
54
00
A-
PROPOSED HIGH COVERED LINKWAY
ALUM WEATHER SHIELDPROPOSED LOCATION OF
THE 2.4m WIDE COVERED LINKWAYROOF TO HAVE THE SAME RADIUS AS PROPOSED HIGH COVER LINWAY CURVED
END OF HIGH COVER LINKWAYPROPOSED ALUM WEATHER SHIELD AT BOTH
PROPOSED 2.4m WIDE COVERED LINKWAY34
00
NTS
LIGHT FITTINGCOLUMN MOUNTED
LIGHT FITTINGCOLUMN MOUNTED
LIGHT FITTINGCOLUMN MOUNTED
LIGHT FITTINGCOLUMN MOUNTED
LIGHT FITTINGCOLUMN MOUNTED
LIGHT FITTINGCOLUMN MOUNTED
LIGHTINGSLINKWAY
CONNECT TO
LIGHTINGSLINKWAYCONNECT TO
24
00
54
00
600
4200
600
5400
6004200600
2400
16200
L/ROAD/MES/SD/1016
LROADMES-SD1016-.dgn
LIGHT FITTINGCOLUMN MOUNTED
-
HIGH COVERED LINKWAY
TYPICAL LIGHTING SYSTEM FOR
HADI WIJAYAADRIAN CHEONG/
NOV 2010CNV
TAY K.C
JUNCTION BOX
ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN
ENCASED IN COLUMNØ100mm HD uPVC PIPE
PVC CABLE IN
JUNCTION BOX
H.D uPVC PIPE FROM OG BOXARMOURED CABLE IN Ø100mm
ENCASED IN COLUMNØ100mm HD uPVC PIPE PVC CABLE IN
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
JULI
DescriptionRev. Date By App’dChk’d
HADI WIJAYAADRIAN CHEONG/
STANDARD INSTALLATION DETAILS
Scale: N.T.S.
Scale: N.T.S.
Scale: N.T.S.
SECTION A-A
ROOF PLAN (HIGH COVERED LINKWAY)
TYPICAL COLUMN MOUNTED LIGHT FITTING
FRONT VIEW SIDE VIEW
ISOMETRIC VIEW
SPECIFICATIONLIGHT FITTING TO M&E COLUMN MOUNTED
EARTH ROD
GROUND LEVEL
EARTH ROD CLAMPINCLUSIVE OF LIGHTNINGPROTECTION EARTH LABEL
(min. 2 Nos. 1.8m LENGTH,16mm DIA COPPER)
COUPLINGØ50mm HEAVY DUTY UPVCPIPE C/W 25mm X 3mmCOPPER CONDUCTOR TAPE
HOT DIP GALVANISED COVER
CONCRETE HAUNCH ALL AROUND
50
TAY K.C
CNV NOV 2010
EARTH PIT(TOTAL RESISTANCE < 10ohm)
(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)
EARTH PIT(TOTAL RESISTANCE < 10ohm)
(LOCATION TO BE DETERMINEDON SITE & TO SO APPROVAL)
LEGEND:
SECTION E-E
SECTION H-H
25mm x 3mm COPPER TAPE
ALUMINIUM OR
STEEL SUPPORT POST
M8 ALUMINIUM COPPER BOLT
TO STEEL SUPPORT POST
ALUMINIUM TAPE
ALUMINIUM OR STEEL
SUPPORT POST
Scale: N.T.S.
Scale: N.T.S.
Scale: N.T.S.
DC BONDING
BONDING
DETAIL 2TYPE 1 - ELEVATION OF LIGHTNING
BONDING TO STEEL SUPPORT POST
B-BOND
COPPER TAPE
Scale: N.T.S.
B-BOND
M8 STAINLESS STELL BOLT
M8 COPPER BOLT
BI-METALLIC
CONNECTOR
DC
1 1
MIN.
54
00
A-
PROPOSED HIGH COVERED LINKWAY
PROPOSED LOCATION OFALUM WEATHER SHIELD
PROPOSED HIGH COVER LINWAY CURVED ROOF TO HAVE THE SAME RADIUS AS THE 2.4m WIDE COVERED LINKWAY
PROPOSED ALUM WEATHER SHIELD AT BOTHEND OF HIGH COVER LINKWAY
PROPOSED 2.4m WIDE COVERED LINKWAY
NTS
BONDING DETAILS TO ROOF SPECIALIST’S REQUIREMENT
SEE DETAIL 1
EARTH PIT
SEE DETAIL 3
SEE DETAIL 2
BONDING DETAILS TO ROOF SPECIALIST’S REQUIREMENT
SEE DETAIL 1
600
54
00
42
00
600
24
00
16200
5400
6004200600
2400
TYPICAL LIGHTNING PROTECTION SYSTEM FOR
HIGH COVERED LINKWAY
L/ROAD/MES/SD/1017
LROADMES-SD1017-.dgn
STANDARD INSTALLATION DETAILS
-
ADRIAN CHEONG/HADI WIJAYA
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet A3
Date
Approved
Rev.
Project Title :
CAD File Name:
Drawing Title :
LTA Endorsement :
MELVYN THONG
DescriptionRev. Date By App’dChk’d
THONG
E-
H
-
H-
E
-
EARTH PIT
BONDING
DOWN CONDUCTORDC
SECTION A-A
ROOF PLAN (HIGH COVERED LINKWAY)
DETAIL 1ELEVATION OF BONDING FROM ROOF TO
STEEL SUPPORT POST
Scale: N.T.S.
Scale: N.T.S.
Scale: N.T.S.
DETAIL 3
Ø 32mm STAINLESS STEEL PIPE
R.C. COLUMN
EXISTING GROUND LEVEL
EXISTING ROAD LEVEL
FACING PAVEMENT FACING ROAD
COUPLING INLET
TYPICAL LAYOUT COUPLING INLET AT 1000mm ABOVE GROUND
1. NUMBER OF HOLES SHOWN ARE INDICATIVE ONLY (NOT ACTUAL NUMBER).
NOTE:
OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD
NOTE : FOR LESS THAN 8m RADIUS FROM COLUMN OF POB TO THE MIDPOINT
SCALE NTS
OF LAYBY SUBJECT TO APPROVAL BY NATIONAL PARKS BOARD
NOTE : FOR MORE THAN 8m RADIUS FROM COLUMN AT POB TO THE MIDPOINT
SCALE 1 : 20
1000
ABOVE GROUND
ISOLATION VALVE AT 1500mm
CAD File Name :
Drawing No. :
Scale
Designed
Drawn
Checked
ofSheet 1 1 A1
Date
Approved
Rev.
-
Drawing Title :
Project Title :
LTA Endorsement :
Qualified Person Endorsement :
DescriptionRev. Date By App’dChk’d
MELVYN THONG
AS SHOWN JAN 2011CNV
L/ROAD/MES/SD/2001
LROADMES-SD2001-.dgn
TAN BOON TONGLIM KWEE CHEW /
VERON
FOR INFORMATION ONLY
STANDARD INSTALLATION DETAILS
AND SECTIONS FOR NEW POB
TYPICAL IRRIGATION INSTALLATION DETAILS
B
-
PLATFORM AND ABOVE THE SOIL LEVELTHE PLANTER TROUGH THAT ABUT THEBE FIXED TO THE INNER WALL OFBOTTOM OF THE PIPE AND SHOULDCENTRE TO CENTRE ALONG THE *3mm HOLES AT 400mm APART*25mm STAINLESS STEEL PIPE WITH
SECTION A - A
TYPICAL SECTION OF PEDESTRIAN OVERHEAD BRIDGE
1500mm ABOVE GROUNDSTAINLESS STEEL PIPE AT FOR 2 NOS. OF EXPOSED *32mm 2 NOS. OF ISOLATION VALVE
PIPE BURIED UNDERGROUND*32mm STAINLESS STEEL
STEEL PIPE SLEEVE*50mm GALVANISED
SEE DETAIL A
STEEL PIPE RISER*32mm STAINLESS
600
250 x 250 HANDICAPPED SIGN
1000
1500
200600
17
00
EQ
EQ
25
25
25
FOOTPATH LEVEL
ROAD LEVEL
5680 (
MIN.
54
00)
900 (V
ARIE
S)
2800
–384
2200
–2584
1100
100
855
14
5
370 2060 370
1800MIN. 40 MIN. 40
EQEQ
750
75
67
5
7002200
75
675
625
150
15°
12°
MIN.
300
DescriptionRev. Date By Chk’d
FOR INFORMATION ONLY
SECTION B-BSCALE 1:20
STEEL PIPE RISER2 NOS. *32mm STAINLESS
50
200
150
80
200
2000
2000
SCALE NTS
SCALE NTS
SCALE NTS
400mm
5030050
50
300
50
COUPLING INLET
GROUND LEVEL
1000
400
SECTION X-X DETAIL ASCALE NTS
Ø3mm HOLE
END CAP
END CAP
STEEL PIPE
*32mm STAINLESS
*32mm STAINLESS STEEL PIPE RISER
BURIED UNDERGROUND
Ø32mm STAINLESS STEEL PIPE
CONCRETE FILLED
NEAREST OPEN DRAIN
OVERFLOW PIPE TO WITH HAUNCH END
UNDERGROUND PIPE
WATER WAGON CONNECTION
QUICK RELEASE COUPLING FOR
Ø38mm (1�INCH)
PIPING SUPPORTS
HOT-DIPPED GALVANISED
STAINLESS STEEL OR
WITH RETRACTABLE HANDLE
4.5mm ALUMINIUM CHEQUERED PLATE
Ø32mm STAINLESS STEEL PIPE
1500mm ABOVE GROUND
ISOLATION VALVE AT
AND ABOVE THE SOIL LEVEL
THAT ABUTS THE PLATFORM
INNER WALL OF THE TROUGH
SHOULD BE FIXED TO THE
THE BOTTOM OF THE PIPE
400mm APART C/C ALONG
WITH Ø3mm HOLES AT
Ø25mm STAINLESS STEEL PIPE
(UNDERGROUND)
CONNECTION
FOR WATER WAGON
QUICK RELEASE COUPLING
Ø38mm (1�INCH)
400mm
1500mm ABOVE GROUND
ISOLATION VALVE AT
AND ABOVE THE SOIL LEVEL
THAT ABUTS THE PLATFORM
INNER WALL OF THE TROUGH
SHOULD BE FIXED TO THE
THE BOTTOM OF THE PIPE
400mm APART C/C ALONG
WITH Ø3mm HOLES AT
Ø25mm STAINLESS STEEL PIPE
Ø3mm HOLE
END CAP
END CAP
STEEL PIPE
*32mm STAINLESS
*32mm STAINLESS STEEL PIPE RISER
UNDERGROUND COUPLING INLETISOMETRIC DIAGRAM WITH
SURFACE COUPLING INLETISOMETRIC DIAGRAM WITH
NEAREST OPEN DRAIN
OVERFLOW PIPE TO
WITH HAUNCH END
UNDERGROUND PIPE
CONCRETE FILLED
ABOVE GROUND
AT 1000mm
CONNECTION
FOR WATER WAGON
QUICK RELEASE COUPLING
Ø38mm (1 1/2 INCH)
X
-