nozzles for fixed fire suppression -...

6
® NOZZLES FOR FIXED FIRE SUPPRESSION Manual No. 104.FF ®2004, BETE Fog Nozzle, Inc. All rights reserved

Upload: vukhuong

Post on 07-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

®

NOZZLES FOR FIXED FIRE SUPPRESSION

Manual No. 104.FF

®2004, BETE Fog Nozzle, Inc. All rights reserved

®

Choosing the Best Nozzles

Consider First the Company with theGreatest Experience in Designing SprayNozzles for Fire ProtectionBETE has been developing specialized nozzles for fire protection sincethe early 1950's. BETE's early growth was assured with a large order tosupply the newly developed BETE spiral nozzles to Sinclair RefiningCompany for protection of their catalytic cracking units. BETE has contin-ued to build on this early experience to become pre-eminent in supplyinghigh performance nozzles for fixed fire protection on off-shore drilling andproduction platforms, petroleum storage and transfer stations, and a widevariety of industrial and commercial installations. Working with individualcompanies and industry consortia, BETE's newest design innovations arerewriting the books on platform and well-head protection, water curtains, and the mitigation of toxic gas releases. BETE's success is built on itsability to carefully engineer its nozzle designs to deliver the specific sprayperformance required to efficiently suppress and extinguish many differenttypes of fires.

Consider: Type of Protection Needed, Nozzle Design, Spray Performance and Spray Density

Consider: Do you need to conserve fire water supplies for lowpressure contingencies? The spiral design is the most efficient direct-pressure atom-izer, producing sprays 30-50% finer at a given pressure thanequivalently rated whirl nozzles. This translates into more droplet surface area over which heat transfer can occur, yielding significant improvements in fire suppression andcooling effectiveness. Their greater efficiency allow theBETE spiral nozzles (TF, TFXP, TFXPW, TF-150, TF29-180and N series) to be operating at lower pressures and lowerflow rates without compromising the level of protection.

Is your deluge system exposed to average winds above 10 mph? If so, the BETE TFXPW series provides the proven fineatomization of the spiral design and a carefully engineeredinner spray cone to punch through cross-winds and vigorousconvective plumes.

Consider:

®2004, BETE Fog Nozzle, Inc., All rights reserved.

®

For Fixed Fire ProtectionAre you protecting a lightly packed, enclosed storage space? The BETE TF29-180 series combines a unique extra-widecoverage high-energy spray able to project through gratingswith fine droplets characteristic of the spiral design. Devel-oped by BETE for Naval Sea Systems Command, this series was designed to provide critical fire control and cooling withinthe tight quarters of densely paqcked ship-board magazines.

Is your "dry" system plagued with scale or your firewater supply with plugging solids (sand, rust scale,algae, invertebrates etc.)? The nozzles in a fixed water spray system need to be pro-tected from pluggage screening out particulates with diametersexceeding 50% of the minimum nozzle passage-way ("free pas-sage diameter"). The BETE MaxiPass and TF-XP series ofmaximum free passage nozzles provide reliable protectionagainst plugging. These nozzle series deliver free passagesthree to four times larger than competing designs-increasingreliability and reducing system complexity and maintenance.

Do you need to provide water curtain protection tocommand and control centers, evacuation staging areas,or critical structural components? When mounted to spray horizontally, the extra-wide cover-age of the BETE TF-150 and -170 series 150˚ and 170˚ full-cone spirals function particularly effectively as a water curtainradiation barrier - protecting personnel, control centers and emergency mustering areas from intense heat, smoke and toxicfumes. Three separate cones work in concert to deliver assured protection remarkably resistant to flame and radiation "punch-through" and wind-induced spray pattern deformation.

Does your installation require nozzles approved byLloyd's Factory Mutual or the U.S. Coast Guard? BETE's N series nozzles are the only spiral design nozzlesin the industry that are Coast Guard and Factory Mutualapproved. All N series models are Factory Mutual approved.The BETE N9 model is designed to meet FM's requirementsfor use in fixed deluge installations protecting industrial trans-formers. The entire N series is certified for use on ships andoff-shore installations by Lloyd's Register. The N3, 4 and 5and N3W, 4W and 5W models are approved by the U.S. Coast Guard.

Consider:

®2004, BETE Fog Nozzle, Inc., All rights reserved.

Consider:

Consider:

TFXPTFXP60-50 psi52-300 gpm90˚ - 120˚lumpy liquidsspiral full cone

N60-50 psi52-340 gpm90˚ - 120˚FM approvedspiral full cone

MPMP60-120 psi47-178 gpm90˚ - 120˚lumpy liquidswhirl full cone

TF150TF15060-150 psi52-300 gpm150˚wide coveragespiral full cone

TFXPWTFXPW60-50 psi116-327 gpm150˚lumpy liquidsspiral full cone

N60-150 psi52-340 gpm90˚ - 120˚FM approvedspiral full cone

CWCW40-200 psi0.25-2.2 gpm80˚ - 120˚whirl full orhollow cone

TF29-180TF29-18060-150 psi9.3-65 gpm180˚wide coveragespiral full cone

SASA40-100 psi0.3-19 gpm20˚ - 40˚23-115 scfmhomogeneous fog

TFXPTFXP60-50 psi52-300 gpm90˚ - 120˚lumpy liquidsspiral full cone

NFNF60-120 psi20-195 gpm90˚ - 120˚

flat fan

FFFF20-80 psi17-150 gpm145˚wall wettingflat fan

TF150TF15060-150 psi52-300 gpm150˚wide coveragespiral full cone

TF170TF17060-170 psi52-300 gpm170˚horiz. sprayspiral full cone

Nozzle Selection by Application(Listed with preferred choice first)(Listed with preferred choice first)

Fire Protection:Fire Protection:DelugeDelugeProtect off-shoreProtect off-shoreplatforms, storageplatforms, storagetanks, hazardoustanks, hazardousloading areas, andloading areas, andequipment baysequipment bays

Fire Protection:Fire Protection:SpecialSpecialProtect coal con-Protect coal con-veyors, fueling andveyors, fueling andvulcanizing cabi-vulcanizing cabi-nets, warehouses,nets, warehouses,and munitions and munitions storagestorage

Fire Protection:Fire Protection:Water WallWater WallProtect personnel,Protect personnel,evacuation musterevacuation musterareas, equipment,areas, equipment,and structuresand structuresfrom heat radiationfrom heat radiation

Comparison of Spray Wind Resistance for the BETE N6 and N9 Deluge Nozzles(operated at 60 psig. Modeled in 10, 20 and 35 mph Crosswinds)(operated at 60 psig. Modeled in 10, 20 and 35 mph Crosswinds)

Consider:

HORIZONTAL AND VERTICAL TRAVELIN 10 MPH CROSS WINDS

HORIZONTAL AND VERTICAL TRAVELIN 20 MPH CROSS WINDS

HORIZONTAL AND VERTICAL TRAVELIN 35 MPH CROSS WINDS

HORIZONTAL (feet) For N6= DV0.9 = 988 microns;N9= DV0.9 = 141.1 microns

HORIZONTAL (feet) For N6= DV0.9 = 988 microns;N9= DV0.9 = 141.1 microns

HORIZONTAL (feet) For N6= DV0.9 = 988 microns;N9= DV0.9 = 141.1 microns

HO

RIZ

ON

TAL

RE

AC

H (

feet

)

HO

RIZ

ON

TAL

RE

AC

H (

feet

)

HO

RIZ

ON

TAL

RE

AC

H (

feet

)

N6 N9

®2004, BETE Fog Nozzle, Inc. All rights reserved

®2004, BETE Fog Nozzle, Inc. All rights reserved

System Set-upsDeluge, Enclosed Area and Water Curtain

Deluge Protection of outdoor propane or LPGStorage Tanks Using BETE N Series Nozzles

Water Curtain Used forPersonnel Protection on Off-Shore Oil Platform

Detail

Restaurant Kitchen Area(Enclosed Area) Fire ProtectionUsing BETE CW Nozzles

Distance of Spray Header(when Mounted Above) to Tank

Distance of Spray Header (when Mounted below) to TankDistance BetweenTanksDistance

BetweenNozzleson SprayHeaders

DistanceBetweenNozzleson SprayHeaders

®2004, BETE Fog Nozzle, Inc. All rights reserved

BETE Fog Nozzle, Inc.PO Box 1438, 50 Greenfield StreetGreenfield, MA 01302-311 USA