National Plumbing Regulators Forum
NPRF ADVISORY NOTEIssued 19 August 2011
WATER SERVICES - PN16 CROSS LINKED POLYETHYLENE
PIPES AND FITTINGS
PURPOSE
The purpose of this Advisory Note is to advise that plastic pipes and fittings including PN16 Cross-linked polyethylene (PE-X) are suitable for use in water services where the pressure supplied from
the property service exceeds 500 kPa and when an authorised pressure regulating device isinstalled.
BACKGROUND
There are a number of types of plastic pipes and fittings used in plumbing installations throughoutAustralia. For example:
• PVC-U Unplasticised polyvinyl chloride• PVC-M Modified polyvinyl chloride• PVC-O Oriented polyvinyl chloride• PE Polyethylene• PP Polypropylene• PE-X Cross-linked polyethylene• ABS Acrylonitrile butadiene styrene• PB Polybutylene
PE-X pipes and fittings are certified against Australian Standard AS/NZS 2492:2007 Cross-linked polyethylene (PE-X) pipe for hot and cold water applications and AS/NZS 2537 Fittings for use with CrossLinked Polyethylene Pipes for hot and cold water applications. Australian Standard AS/NZS 3500:2003Plumbing and drainage Part 1: Water services, Clause 2.3 require materials and products used in awater service to be selected from Appendix B of the Standard. Appendix B Acceptable pipes and fittings lists cross-linked polyethylene (PE-X) pipes and fittings along with a range of pipes and fittingslisted above as being acceptable for use in water services.
Pipes and fittings used in a cold water service must have a maximum allowable operating pressure(MAOP) of at least 1200 kPa at 20°C. Cross-linked polyethylene (PE-X) pipes and fittings areavailable at PN16 and PN20 pressures ratings, reflecting a maximum water pressure of 1600 kPaand 2000 kPa respectively at 20°C.
In installations downstream of the water meter, AS/NZS 3500.1:2003, Clause 3.3.4 provides thatwater at any outlet within a building shall not exceed 500 kPa which is within the capabilities of PN16 cross-linked polyethylene (PE-X) pipes and fittings.
![Page 2: NPRF Advisory Note PN 16 Poly Issued 19 Aug 2011](https://reader036.vdocument.in/reader036/viewer/2022082621/577cd9521a28ab9e78a33c09/html5/thumbnails/2.jpg)
7/30/2019 NPRF Advisory Note PN 16 Poly Issued 19 Aug 2011
http://slidepdf.com/reader/full/nprf-advisory-note-pn-16-poly-issued-19-aug-2011 2/2
National Plumbing Regulators Forum
This maximum pressure requirement is essentially required because pressures above 500 kPa cancause damage, excessive noise in the system and reduce the life of appliances taps and fittings.
Given the requirements set out in AS/NZS 3500.1:2003 the pipe pressures beyond the regulatingdevice are within the tested performance capabilities of PN16 Cross-linked polyethylene (PE-X)pipes and fittings.
PRESSURE REDUCING VALVES
Where the delivery from the water authority exceeds the maximum pressure of 500 kPa, break tanks, pressure ratio or pressure reducing valves should be installed to maintain the desiredpressure within the system. These methods represent a plumbing solution in accordance with thePlumbing Code of Australia.
CONCLUSION
PN16 Cross-linked polyethylene (PE-X) pipes and fittings, when selected and installed correctly withthe specified pressure regulating devices, are suitable for use in plumbing installations throughoutAustralia. For additional technical information regarding pressure control devices refer to NPRFAdvisory Note “Pressure Control Valves” issued 22 August 2011on the NPRF web site.
Pressure Reducing Valve installation Pressure Limiting Valve installation
For further information contact www.plumbingregulators.org or your state or territory plumbing regulator
==================================================================================
This document has been produced and published by the National Plumbing Regulators Forum (NPRF). Although every care hasbeen taken in the production of the work, no responsibility is accepted for the accuracy, completeness, or relevance to the user'spurpose, of the information. Those using it for whatever purpose are advised to verify it with the relevant Government
Department, local Government body or other source and to obtain any appropriate professional advice. The NPRF, its officers,employees and agents do not accept liability however arising, including liability for negligence, for any loss resulting from the useof or reliance upon the information and/or reliance on its availability at any time.