nsf/ansi 49 nsf/ansi 49 - 22010 010 - mabsa mabsa presentation 2011-09.pdf · bsc installations....
TRANSCRIPT
1
UpdatesUpdates
NSF/ANSI 49 NSF/ANSI 49 -- 20102010
Copyright © 2011 Micro-Clean, Inc.
All Rights ReservedCopyright © NSF 2010
Micro-Clean, Inc. does not represent, endorse, or
recommend any BSC or filtration device
manufacturer, or type of device over another. Any
pictures, materials or descriptions presented here are
for educational purposes only.
DisclaimerDisclaimer
2
• Understand the latest NSF/ANSI Std 49
changes on how they impact current
BSC installations.
– Many older BSCs may not meet the current expectations of NSF
– Customers should routinely evaluate their safety and equipment processes as part of safety committees with key departments represented
ObjectivesObjectives
• have HEPA/ULPA filtered downflow air that is a portion of
the mixed downflow and inflow air from a common plenum (i.e., a plenum from which a portion of the air is exhausted from the cabinet and the remainder supplied to the work
area);
• may exhaust HEPA/ULPA filtered air back into the laboratory
or to the environment through an external exhaust system
connected to the cabinet with a canopy connection; and
• Type A1 cabinets are not suitable for work with volatile toxic chemicals and tracer amount of volatile radionuclides
BSC Types A1 / A2BSC Types A1 / A2
3
• have HEPA/ULPA filtered downflow air composed
largely of uncontaminated recirculated inflow air;
• exhaust most of the contaminated downflow air to an
external exhaust system through a dedicated duct
connected to cabinet with a direct connection and
exhausted to the atmosphere after passing through a
HEPA/ULPA filter; and
BSC Type B1BSC Type B1
• have HEPA/ULPA filtered downflow air drawn from the
laboratory or the outside air (i.e., downflow air is not recirculated from the cabinet exhaust air);
• exhaust all inflow and downflow air to the atmosphere
through an external exhaust system connected to cabinet
with a direct connection after filtration through a
HEPA/ULPA filter without recirculation in the cabinet or return to the laboratory; and
BSC Type B2BSC Type B2
4
• Canopy connection
• Direct connection
Other new definitionsOther new definitions
• Canopy connection – required for
externally vented A1 or A2 BSC (5.2)
• Direct connection – required for
externally vented B1 or B2 BSC (5.3)
Exhaust requirementsExhaust requirements
5
• All biologically contaminated ducts and
plenums in Types A1, A2, B1, and A2
cabinets shall be maintained under
negative pressure or enclosed within a
negative pressure zone. (5.4)
– B2 directly exhausted (nonrecirculated) negative pressure zone was dropped
Duct and Plenum designDuct and Plenum design
• Any Type A1 or A2 cabinet when
canopy connected shall have an audible
and visual alarm to indicate notifying the
user of a potential loss in canopy
containment (5.23.4)
A1 / A2 Exhaust AlarmsA1 / A2 Exhaust Alarms
6
Updated drawingsUpdated drawings
Copyright © NSF 2010
• Conforms to requirements of UL 61010-1
Resistance to overturningResistance to overturning
7
• The cabinet shall be tested by a National Recognized Testing Laboratory (NRTL) for compliance to the requirements of the current edition of any national standard that is based on IEC 61010-1. Compliance is demonstrated by cabinet listing, i.e. UL, CSA, or IECEE CB Scheme certificate.
Electrical SafetyElectrical Safety
• The manufacturer shall determine the aerosol
introduction point that provides the most uniform distribution (reference IEST-RP-CC-03422). The
location of the aerosol introduction point shall be
clearly described or indicated in a manner readily
available to the certifier. The location should be
described either on the cabinet data plate or with the
electrical schematic if the schematic is affixed to the
cabinet. (NSF 49 - 2009, A.2.3.1)
Annex A Annex A -- Filter Leak TestFilter Leak Test
8
• “BSC Selection, Installation, Life Span and
Decommissioning” section was moved from
Annex G (Decontamination) to Annex E,
now this title renames Annex E with this
new information.
– Formerly “Recommendations for Installation”
Annex G parts to Annex EAnnex G parts to Annex E
• E.1.Biosafety Consultation Prior to BSC Purchase
• Risk Assessment Procedure
• Selection of a BSC cabinet
• Prior to the Purchase [“Location” section from old Annex E
ended up in here]
• Inspection
• Moving a Permanently Installed Biosafety Cabinet
• Lifespan of BSCs
• E.8. Decommissioning process
Moved from Annex G to EMoved from Annex G to E
9
• Risk Management
Assessment Table was
reworked
• Biosafety Cabinet Selection
• Configuration drawings
added
E.2.8 Risk E.2.8 Risk
AssessmentAssessment
Copyright © NSF 2010
• What needs to be protected?
• What are all of the different types of work to be done in the cabinet?
• What types and quantities of chemical vapors will be
generated in the BSC?
• If the unit requires an exhaust system, is there an appropriate location for the cabinet and its ductwork?
• NEW QUESTION: If the volume of air moved by the BSC
exhaust system is reduced, or eliminated, due to a
malfunction, what is its effect on BSC performance, and
what is preferred by the user?
Deciding class and type now Deciding class and type now
determined by a new 5determined by a new 5thth questionquestion
10
• Question #4• E.3.1.4 (formerly) G.3.1.5. If the unit requires an exhaust
system, is there an appropriate location for the cabinet and its ductwork?
• 2nd para: When connected to a hard-ducted exhaust system, however,
the location of the cabinet becomes dependent on the location of the
exhaust system. The exhaust duct must be placed so it can penetrate
ceilings and floors without disturbing other ventilation or plumbing
systems. The exhaust system must also be designed to minimize
excessive lengths and elbows. The exhaust system configurations of
Type A and Type B BSCs are shown in figures E3 and E6,
respectively. Hard ducting Type A cabinets is not acceptable and
shall only be exhausted through a properly designed and fitted
exhaust canopy.
“Not acceptable” hard ducted A’s “Not acceptable” hard ducted A’s
• Work area outlet are limited in their
amperage rating due to other components
on the same power cord, blowers, lights, etc.
• Recommendation to add an external voltage
regulator when wall outlet line voltage
variations affect cabinet airflows.
E.3.3.2 Electrical OutletsE.3.3.2 Electrical Outlets
11
• Have a maximum height specified by
manufacturer to prevent BSC overturning;
this maximum should never be exceeded.
E.3.3.5. Base StandsE.3.3.5. Base Stands
• “Proper cabinet operation should be
confirmed by airflow smoke pattern at each
site of use. If a cabinet is relocated to
another facility, or subjected to excessive
shock and/or vibration during moving, the
BSC should be recertified to ensure it
is functioning in a proper manner.”
E.3.3.6 Mobile InstallationsE.3.3.6 Mobile Installations
NuAire
12
• E.4.2.1 Location of BSC– The cabinet should be located away from traffic patterns, doors, fans,
ventilation registers, fume hoods, and any other air-handling device that
could disrupt its airflow patterns.
• E.4.2.2 Clearances (NSF 2008 numbers in parentheses)– BSCs not connected to an exhaust system should have at least 6” (3”)
clearance from any overhead obstruction when the cabinet is in its final
operating position, to allow for testing of the Exhaust HEPA/ULPA filter.
– (NSF 2008 required 12” above if using TA for airflow on exhaust HEPA. This is no longer mentioned. MCI submitted change request to NSF)
– Maintain 6” (12”, 3” absolute minimum) clearance on sides, 12” (12”, 1.5”
absolute minimum) clearance behind unit, for service.
E.4. the former “Location” E.4. the former “Location”
section in Annex E section in Annex E
• It is recognized that there is interest in utilizing the increasingly sophisticated modulated flow exhaust ventilation systems where the exhaust from Type B1 or B2 cabinets, CFH, flexible exhaust hoses, and/or room exhausts are
modulated based on use to optimize containment, maintain appropriate pressure differentials, and maximize energy savings by reducing overall exhaust volume. These systems are required to maintain a high level of control of many complex factors over a number of years. Although the potential cost savings are great, the severity of the hazards contained by the
biological safety cabinets requires the use of simpler and more reliable constant flow systems for the cabinet exhaust.
• If a modulated flow exhaust system is used, it is recommended that the operation of the cabinet exhaust be verified under a variety of conditions over time. Furthermore, the type of exhaust alarm must be assessed in the light of
the type of sensors and controls used in the modulated flow system.
[2010 dropped] modulated [2010 dropped] modulated
flow exhaust systemflow exhaust system
13
• Exhaust System Performance – canopy connected Type A1 and A2 BSC F.7.3.3
– Using a visual medium source positioned to
demonstrate containment of BSC exhaust by the
canopy, reduce the external exhaust until the
alarm signals audibly. The alarm shall sound before visible canopy containment is lost. Direct connected Type A1 or A2 BSC shall not be considered in compliance with the standard.
Annex FAnnex F
• All new cabinets shall conform to the requirements of the current edition of any national standard that is based on IEC 61010-1. Cabinets initially qualified under versions of NSF/ANSI 49 prior to 2009 edition shall conform to UL 61010A-1 or may refer to NSF 49 – 1992 for Electrical leakage, ground circuit resistance, and polarity tests if necessary.
F.8F.8 Electrical leakage & ground Electrical leakage & ground
circuit resistance & polarity testscircuit resistance & polarity tests
14
• Annex K, “Protocol for the validation of
alternative biosafety cabinet decontaminating
methods and agents” was added to provide
guidance for anyone attempting to validate a
space decontamination gas other than
formaldehyde or chlorine dioxide.
New Annex KNew Annex K
QuestionsQuestions
15
Biological Safety Cabinet Biological Safety Cabinet Use, Maintenance and Use, Maintenance and
OperationOperation
NuAire
Germfree Laboratories
Baker Company
LabConCo Corporation
Thermo Scientific
ESCO
• Review new changes to NSF 49 that impact how BSCs
are used, installed, or require modification to stay current with today’s safety and health expectations.
• Understanding maintenance and operations of BSCs.
• “Don’ts” within a BSC
• BSC troubleshooting & problem diagnosis
• New technology and life expectancy of BSCs
ObjectivesObjectives
16
• Committee Process Review– Primary Investigator / Production Manager
– Industrial Hygienist / Safety
– Laboratory Ventilation Management Program overview / Chemical Hygiene Program
• BSC Type Selection based by use / hazards
• Venting from laboratory
• Recirculation
• Hazards– Biohazards
– Chemicals – volatility
– Radioisotopes
– Hazardous Drugs or Powders
– Prions
BSC SelectionBSC Selection
Class II Type A1 BSCClass II Type A1 BSC
• Offers product, personnel & environmental protection.
• 75fpm minimum intake velocity
• Downflow and Exhaust HEPA
filtered air from a common
positive pressure plenum
• A1s built after 2008, common plenums must be surrounded
by negative pressure
• No volatile toxic chemicals or radionuclides allowed
• Exhaust HEPA filtered air to
room or out of building via
canopy exhaust connection
Intake
Exhaust
17
Class II Type A2 BSCClass II Type A2 BSC• Same as Class II Type A1, plus
• 100fpm minimum intake velocity
• All common plenums
surrounded by negative
pressure
• Allows minute quantities of
volatile toxic chemicals or tracer
amounts of radionuclides only when vented through a properly functioning canopy exhaust connection
Intake
Exhaust
Canopy
Connection
Class II Type B1 BSCClass II Type B1 BSC• Product, personnel & environmental
protection
• 100fpm minimum intake velocity
• Downflow air composed largely of
uncontaminated recirculated inflow
air
• Exhaust contaminated downflow air
to facility external exhaust system
after passing through a
HEPA/ULPA filter.
• Allows minute quantities of volatile
toxic chemicals or tracer amounts
of radionuclides when used in
direct exhaust portion or when not
interferes with recirculation of
downflow air
Intake
Exhaust
18
Class II Type B2 BSCClass II Type B2 BSC• “Total Exhaust”, no recirculation
• Product, personnel and
environmental protection.
• Supply air from room or ducted
• 100fpm minimum intake velocity
• Exhaust all downflow and inflow
air after passing thru a HEPA/
ULPA filter then outside building
via hard-connection facility exhaust system
• Use volatile toxic chemicals and radionuclides required as an adjunct to microbiological studies.
Exhaust
Supply
Intake
• Industry standards
are updated over
time as studies
and research
reveal critical
improvements and
need for change to
enhance the
safety of BSC use.
Industry UpdatesIndustry Updates
Copyright © NSF 2010
19
• Two significant changes to the NSF 49
standard have ended the grace period from
making voluntary upgrades of BSC
installations to now-mandatory compliance
to be considered as an NSF-listed device
– A1/A2 exhaust configuration
– Ducted cabinets must have exhaust duct alarms
Voluntary to MandatoryVoluntary to Mandatory
Exhaust requirementsExhaust requirements
Copyright © 2011 Micro-Clean, Inc.
All Rights Reserved
Canopy connection – required for externally vented A1 or A2 BSC
Hard ducting Type A cabinets is NOT ACCEPTABLE and shall only be exhausted
through a properly designed and fitted exhaust canopy.
Direct connection – required for externally vented B1 or B2 BSC
CDC and NIH
CDC and NIH
20
• Any Type A1 or A2 cabinet when canopy
connected shall have an audible and visual
alarm to indicate notifying the user of a
potential loss in canopy containment.
• Type B1 and B2 BSC must be ducted to
operate so must already have an exhaust
alarm
A1 / A2 Exhaust AlarmsA1 / A2 Exhaust Alarms
Copyright © 2011 Micro-Clean, Inc.
All Rights Reserved
• Part 1 - Read the Manufacturer’s O & M Manual
• Part 2 - Plan workflow procedure– Safety
– Sterility
– Cross-contamination
• Part 3 - Develop BSC Cleaning & Maintenance schedule
• Part 4 - Ergonomics
• Part 5 - What not to do in a BSC
• Part 6 – Diagnosing problems
Getting StartedGetting Started
21
• How the BSC works
• Turn-on / Turn-off procedures
• Component descriptions
• Recommended cleaning/maintenance
• Alarm indications
• Troubleshooting
– Most modern BSC manuals are available on manufacturers’ websites
Part 1 Part 1 -- Read the Read the
Manufacturer’s O & M ManualManufacturer’s O & M Manual
• Not all BSCs come pre-labeled by their manufacturer.
• 29 CFR part 1910.145 “Specifications for accident prevention
signs and tags”
BSC Hazard LabelingBSC Hazard Labeling
29 CFR 1910.145(f)(8)(i)
“Biological hazard tags shall be used
to identify the actual or potential
presence of a biological hazard and to
identify equipment, containers, rooms,
experimental animals, or combinations
thereof, that contain or are
contaminated with hazardous
biological agents.”
22
• Rudimentary Controls– Blower
– Lights
– Outlets
• Technology breeds sophistication– Airflow automation
– Sash controls
– Remote controls
– Exhaust system controls
Simple or Sophisticated ControlsSimple or Sophisticated Controls
ThermoFisher
Scientific
ThermoFisher
Scientific
• Alarms are for YOUR
SAFETY
• Never disable the audible
alarm
• If alarm persists, seek
maintenance or
certifier help
Alarm IndicationsAlarm Indications
23
• Know the safe work area in BSC
• Minimize room activity
• Avoid BSC air curtain disruptions
• Utilize aseptic technique
• Use unidirectional air to your advantage
• Safe removal of components from BSC
Part 2 Part 2 -- Plan workflow procedurePlan workflow procedure
Safe work area in BSCSafe work area in BSC
Rear of BSC
Safe Work Zone Area
Front intake grille (non-safe)
Armrest
Airfoil
Front of BSC
Sash
Top view of BSC
S
I
D
E
W
A
L
L
S
I
D
E
W
A
L
L
24
• BSC placement should not be affected by – Door motion
– Room supply vents
– Air Conditioners / windows
– Equipment exhaust fans
• Unnecessary personnel movements create disruptive air currents near inflow opening
• Person walking past BSC – Creates draft up to 175 FPM
– May disrupt inflow (100-110 FPM)• Loss of containment
• Compromised sterility
Minimize room activityMinimize room activity
• Minimize hand / arm exit from sash opening
• No quick moves, especially from intake
• Minimum number of items to perform task
• Do not overload work surface
• Do not use open flame or burners unless
absolutely necessary and approved
Avoid air curtain disruptionsAvoid air curtain disruptions
25
• Avoid contact transmission of contaminants
• Touch contact of contaminated surfaces is
leading cause of non-sterile product or
transfer of contaminants outside BSC
• Final wipe down (sterility) of BSC should be
done in single directions
• Sterile wipe down of components into BSC
• Use “First Air”
Utilize aseptic techniqueUtilize aseptic technique
• Keep sterile product upstream of
contaminants
• Sweeping action of air
• Keep contaminated,
discarded items to rear
Use unidirectional air to your Use unidirectional air to your
advantageadvantage
First
Air
Side View
HEPA Filter
Contaminant
s
26
Rear of BSC
Safe Work Zone Area
Front intake grille (non-safe)
Armrest
Airfoil
Front of BSC
Sash
Top view of BSC
S
I
D
E
W
A
L
L
S
I
D
E
W
A
L
L
• Turn-off UV lamp
• Set sash height to manufacturer’s value
• Turn-on blower and fluorescent light
• Allow cabinet to purge for minimum 5 minutes
• Wash arms and hands
• Don PPE appropriate for tasks
StartStart--upup
27
• Perform “Daily” scheduled cleaning
CleaningCleaning
BakerSG-400
SL-12345VSept 2011
10
• Apply absorbent matting (if needed)
• Do not obstruct front, side or rear grills
• Load and clean materials
• After loading is complete, wait 2-3
minutes to purge contaminants
• Start your work
Loading material & EquipmentLoading material & Equipment
28
Courtesy: CDC/NIH Primary Containment for Biohazards: Selection, Installation and Use of Biological Safety Cabinets, 3rd edition
Clean to Dirty layoutClean to Dirty layout
• Upon work completion, allow BSC to run 2-3
minutes to purge airborne contaminants
• Surface decontaminate any equipment that
came in contact with contaminated material
• Cover / cap all trays and containers before
removing from the BSC
Final PurgingFinal Purging
29
• Surface wipe down the interior surfaces of the cabinet with 70% IPA, or suitable disinfectant
– Disinfectants containing Chlorides and Halogens may
damage stainless steel
– Limit contact times
– These disinfectants are followed by a final wipe of 70%
IPA or non-corrosive, anti-microbial agent
• All surfaces to air dry
• Remove PPE and wash hands / arms
Cabinet DisinfectionCabinet Disinfection
• Turn-off BSC lights and blower*
• Close sash
– Use UV light, if preferred
• *NOTE: Certain BSC types or configurations
require 24-hour operation. “What not to do”
ShutShut--downdown
30
• Daily
• Weekly
• Monthly / Quarterly
• Annually / Biannually
• Schedules can be adjusted based on trended cleaning and operating results
Part 3 Part 3 -- Develop BSC Cleaning & Develop BSC Cleaning &
Maintenance scheduleMaintenance scheduleMonth / Year __________ / ______ Mon Tues Wed Thurs Fri
Daily
Blower/Lights/Outlets ON/UV OFF TC KBF TC TC TC
Exhaust Alarm GREEN/Enabled TC KBF TC TC TC
Prep Aseptic Cleaning TC KBF TC TC TC
Set Sash height to ___ inches TC KBF TC TC TC
Pressure Gauge Reading 0.65 0.66 0.65 0.66 0.66
Post-work Cleaning TC KBF TC TC TC
Weekly
Inspect backwall paper catch
Clean external sash glass
UV Bulb cleaning
Quarterly - Mar-Jun-Sep-Dec
Interior / Exterior cleaning
Gas Valve soap bubble test
Annual - DECEMBER
Replace UV bulb
Biannual - DEC - Even years
Replace Fluorescent Bulbs
Comments:
• Document gage readings – trend results
• Work surface cleaning– 70% IPA
– Suitable disinfectant
– Refer to Mnfr. O&M
manual for recommended
cleaning agents
– CETA CAG-004-2007– http://www.cetainternational.org/
reference/CAG0042007i.pdf
Daily ScheduleDaily Schedule
Starve Load
+
31
• Disinfect the inside surfaces of the cabinet
• Inspect pre-filters under / behind work surface
• Clean side walls, back wall, intake and rear grills
• Sash glass – use glass cleaner – both sides
• UV light cleaning– Lint-free cloth dampened with alcohol or ammonia water
• CAUTION: Do NOT spray airflow sensors, diffuser or HEPA filter. Do not touch HEPA filter– Results in permanent damage to HEPA - leaks,
contamination
– Spraying airflow sensor affects its electrical resistance –compromises inflow/downflow accuracy and your safety
WeeklyWeekly
• Using disinfectants– Clean underside of work surface
– Drain trough – drain valve installed
• Inspect and clean rear paper catch
• Inspect all service valves for proper operation
• Clean BSC exterior – front, sides and top with damp cloth – dust removal
• CAUTION: Do not touch or spray Exhaust HEPA filter. Do not remove or touch exhaust guards, screens, plates or damper settings
• Perform weekly cleaning
Monthly / QuarterlyMonthly / Quarterly
32
• Replace UV lamp, if equipped– Effective life is ~ 7000 hours
• Annual certification (sooner if critical or regulatory requirements)
• All monthly / quarterly activities
AnnuallyAnnually
BiannuallyBiannually
• Replace the fluorescent lamp(s)
• Creates a safer, efficient, healthful, more
comfortable work environment
– Posture
– Body, hand, arm, leg positioning
– Work habits
Part 4 Part 4 -- ErgonomicsErgonomics
33
• Feet solidly comfortably on floor / footrest
– Don’t dangle feet / compress thighs
• Vary leg positions throughout day
– Avoid concentrated pressure points along the underside of your thigh near the knee and the backside of your lower leg
• Get up and walk around at least every hour
Feet, knees & legsFeet, knees & legs
• Chair should fully support your body
• Distribute your weight
• Use the entire seat and backrest
– Don’t slouch
• Shared chairs – don’t assume the chair
is set for you – adjust as necessary
Your backYour back
34
• Keep forearms, wrists and hands in a
straight, natural position
– Don’t anchor your wrists
– Don’t rest your palms on the work surface while working
Forearms, wrists and handsForearms, wrists and hands
• Adjust chair or BSC height so your
shoulders are relaxed
• Elbows should hang comfortably at your
sides
• Relax – muscles that build tension such
as shoulders
Shoulders and elbowsShoulders and elbows
35
• Take breaks– Short, frequent breaks are more beneficial than
fewer, longer breaks
• Vary your tasks– Break up your routine
• Reduce sources of stress– Physical
– Psychological
• Breath fresh air deeply and regularly– BSC intense work may tend to lead to breath-holding
or shallow breathing
Work habitsWork habits
• …use a BSC without a valid certification
label attached
Part 5 Part 5 –– What not to do in a BSC What not to do in a BSC
Do not
SPECIALISTS IN CLEAN AIR CERTIFICATIONP.O. BOX 21806
LEHIGH VALLEY, PA 18002-1806
1-800-523-9852
Date Tested: _________________________________________ August 3, 2010
Test Report No.:
Date Due Retest:
Tested By James T. Technician
_____________________________
Other _____________________________
_____________________________
0810-0301-500F
August 2011
James T. Technician
36
• … overload the work surface area
• … block front, side, or rear grills
• … obstruct any part of the front intake
opening
Don’tDon’t
Rear of BSC
Safe Work Zone Area
Front intake grille (non-safe)
Armrest
Airfoil
Front of BSC
Sash
Top view of BSC
S
I
D
E
W
A
L
L
S
I
D
E
W
A
L
L
• Alcohol bottle in intake
• Mat on intake grille
• Container blocking
back wall
• Sash height?
• Drain valve missing
• Current certification
label missing
• No Biohazard Warning
Label on front of BSC
What’s wrong with this picture??
37
• … change or disable the exhaust low flow
exhaust alarms
• … use a BSC
while in alarm
Don’tDon’t
• … place items on top of the BSC
blocking or damaging the exhaust filter
Don’tDon’t
supplies
38
• … turn off the supply blower or close
the sash to hard-ducted BSCs
• May damage the sash, if closed.
• Causes premature loading of exhaust HEPA
filter
and / or
• Non-updated A1 / A2 cabinets may develop
contamination issues from reverse airflow
through clean side of the supply HEPA filter
• Exceptions:
– Roof exhaust can be turned off at the BSC location
– Roof blower is interlocked to the supply blower
Don’tDon’t
• … operate the UV light while working in
the hood or when people are occupying
the lab
Don’tDon’t
39
Troubleshooting Troubleshooting
Unidirectional Unidirectional
Flow Devices & Flow Devices &
BSCsBSCs
ThermoFisher Scientific
NuAire
Germfree Laboratories Baker Company
LabConCo Corporation
Pressure GaugesPressure Gauges• Monitors plenum
pressure (+) or motor suction (-)
– Positive 0-2” range
– Neg 0-0.25”,0.5 or 1”
40
Negative
PositiveGermfree Laboratories
Velocity vs. Pressure Velocity vs. Pressure
RelationshipRelationship
• High pressure – low velocity =
loaded HEPA
• Low pressure – low velocity =
restricted or starved of air
– Positive pressure gauges
(1 - 2” W.C.) responds
as above. Starve Load
41
Negative Pressure GaugesNegative Pressure Gauges
• Negative (0.25” - <1.0” W.C. gauge size) reads blower suction or negative plenum pressures
• Opposite of Positive Pressure Gauge
• Filter loading will give
lower pressure readings
• Starved HEPAs show
higher pressure
BSC Most Common FailuresBSC Most Common Failures
• Motor/Blower failures– Worn bearings (age)
– AC Motor Cooling Vent restrictions – overheat, thermal overload
– Thermal overload – high current thru motor trips safety circuit breaker inside motor (motor shuts down to cool off, starts up on own once cooled)
– Motors are most-likely to thermally overload after a HEPA filter change (lesser pressure load)
– AC Motors are most-efficient when under load (dirty HEPA filter) – AC current drops
• Speed control failures
42
Work Surface VibrationWork Surface Vibration
• Foreign material in blower impeller
– Throws balanced blower wheel out of balance, like car tire weights – vibrates if unbalanced
– Remove foreign material
• Unbalanced impeller
– Replace impeller
• That’s where that missing pipette wrapper
went!!
Grainger
Grainger
Scraping noiseScraping noise
• Blower impeller rubbing against
blower housing– Loosen, center, or tighten impeller
setscrew
– If impeller is out-of-round – replace
43
Fluttering NoiseFluttering Noise• Foreign material in impeller
• Foreign material in filter plenum– Remove foreign material
• Foreign material in back wall, under
work surface– Remove foreign material
• Loose or torn blower boot or plenum bag– Reattach or replace blower boot or bag
• Simple BSCs have blower &
lights on same circuit breaker
• Outlets on separate breaker
• Energy efficiency in forefront
• Current production BSCs
– microprocessors, membrane touch panels, solid-state relays, display screens, energy efficient ballasts and lamps
– DC or 3-phase AC blower motors for improved energy efficiency
– Sophistication breeds complications, problems, increased upfront and replacement parts cost
Electrical ProblemsElectrical Problems
44
• First modern BSCs were developed in 1960s
• Motor used at the time was Permanent Split
Capacitor (PSC) motor controlled by simple Triac
speed control that “chopped” unneeded voltage
• Not very efficient
• Heat waste byproduct
Permanent Split Capacitor MotorsPermanent Split Capacitor Motors
Excerpt from CETA Performance Review – April 2009
• 3-phase Induction Motor
• Brushless DC motor
• Hybrid AC circuits controlling DC motors
– All produce less heat, less damage to
associated wiring
– Other advantages
Energy Efficient AlternativesEnergy Efficient Alternatives
Excerpt from CETA Performance Review – April 2009 Excerpt from CETA Performance Review – April 2009
Excerpt from CETA Performance Review – April 2009
45
• Three Manufacturers: “A”, “B”, & “C”
• Four foot 10” sash A2 operating amperage (A) between
last revision of PSC motor to newest Energy Efficient
motor
• All information from Mfr O&M manuals
PSC motor Energy Efficiency
“A” 6.6 A 4.0-6.0 A
“B” 9 A 2.9 A
“C” 13.5 FLA 8 FLAFLA – Full Load Amperage
Energy Use ComparisonsEnergy Use Comparisons
• Reduced heating issues to motors / wiring will reduce
failures from heat-related issues
• Fewer thermal overloads, equipment shutdown
• Less BTUs generated by BSCs – less cooling
needed for labs
• One BSC manufacturer has gone as far as extending its repair warranty from 36 to 60 months for BSCs equipped with energy-saving motors
• One manufacturer is offering retrofits from older AC
PSC motors to DC motors
Unseen advantagesUnseen advantages
46
NuAire PTB0186 NU-425 DC ECM motor upgrade info Rev2.pdf
NuAire PTB0186 NU-425 DC ECM motor upgrade info Rev2.pdf
47
• “With sophistication comes cost”
• Most motors must be “taught” or
programmed as to what type cabinet
they are to be installed
• Most motors must be ordered from
manufacturers who must program
• Delays in getting failed BSCs back into
service
DisadvantagesDisadvantages
• Most BSCs have a life expectancy of 15 years
• Manufacturers may stop supporting older BSCs
– Typically do support common parts, if parts are available from
suppliers
• Common OEM components may no longer be available from suppliers to BSC Manufacturers
– AC Permanent Split Capacitor Motors
– Speed Controls
– Wiring harnesses
– Switches
– Light Ballasts for Fluorescent and UV lamps
– Light bulbs – Fluorescent T12 bases
Older BSCsOlder BSCs
Component unavailability may result from actions of the U.S. government and international groups
48
Technology UpdateTechnology Update• Many T12 fluorescent bulbs are inefficient, being phased out
• In September 2000, the U.S. Department of Energy (DOE) published
the Fluorescent Lamp Ballast Energy Conservation Standards (10 CFR,
Part 430), which established new minimum ballast efficacy factor
(BEF) standards
• Energy Policy of Act of 2005 (EP Act 2005) extend the coverage of BEF
standards, which will result in the phased elimination and sale of most
magnetic ballasts in new fixtures, including those designed to operate
34W T12 lamps, starting in 2009, and replacement ballasts in 2010.
Action 2005 BEF Standards for Full-Wattage T12 Lamps
2009 BEF Standards for Energy-Saving T12 Lamps
Ballast manufacturers can no longer make ballasts that do
not pass the new requirements for use in new fixtures. April 1, 2005 July 1, 2009 Ballast manufacturers cannot sell ballasts that do not pass
the new requirements to U.S. fixture manufacturers. July 1, 2005 October 1, 2009 Fixture manufacturers cannot sell fixtures that include
ballasts that do not pass the new requirements. April 1, 2006 July 1, 2010
Department of Energy will prohibit the manufacture of T12 magnetic ballasts solely for replacement purposes.
July 1, 2010 July 1, 2010
QuestionsQuestions
49
Decontamination Decontamination –– Alternative Alternative
TechniquesTechniques
ObjectivesObjectives
• Discuss general steps in performing a
BSC decontamination
• Chemical-Specific Issues
– Methodologies
– Advantages / Disadvantages
• Comparison
50
Why Decontaminate?Why Decontaminate?
• BSC’s protect personnel and environment from hazards or protects product
• If one needs to work on equipment that has been exposed to biological viables, decontamination is required to protect the technician and the surrounding space
• If a BSC is to be used for cultivating viables for a new program, need to protect from viables of prior work
Typical ApplicationsTypical Applications
• Maintenance or other need to access
contaminated plenums
• Moving of BSC
• HEPA filter replacement
• Clean-up of a contamination event
• End or change of work program
51
Requirements for aRequirements for a
Successful DeconSuccessful Decon• Disinfection – typically looking for a
log 4-6 kill of test bacterial spores
• Choice of disinfectant
• Penetration to all surfaces
• Penetration through HEPA filter and into “dead legs”
• Temperature and humidity control
• Containment of fumigant
Requirements for a Requirements for a
Successful Decon (cont’d.)Successful Decon (cont’d.)
• Disposal of disinfectant
– Vent, neutralize, scrub
• Validation of disinfection
– Biological indicators
• Material compatibility
• Safety
52
General Preparation OptionsGeneral Preparation Options
• Seal BSC when decontamination required
• Construct BSC with decontamination facilities included
• Permanently modify BSC for specific decon type
• Ensure gas-tight damper if ducted to building
• Insert recirculation (optional)
General Preparation General Preparation ––
Biological IndicatorsBiological Indicators
• Given 7-day test time, typically assume decontamination method already validated
• If using indicators, often B. atrophaeus or G. stearothermophilus
• Use appropriate substrate (not cellulose for HP)
• Upstream and/or downstream of HEPA filters
• Log-Kill enumeration versus Go / No Go
• Controls
53
General Preparation General Preparation –– FinalFinal
• Establish and measure proper humidity
and temperature
• Final seal
• Pressure check (neutral to adjacent area)
• Establish safety perimeter
• Meet OSHA requirements
General ProcedureGeneral Procedure
• Fumigant generation to a steady state concentration
• Environmental monitoring for leakage
– e.g., Draeger pumps, infrared analyzers
• Appropriate personnel protective equipment (PPE)
– Full face respirator, gloves, lab coat
• Neutralization or scrubbing � Ventilation
54
General Procedure (Cont’d.)General Procedure (Cont’d.)
• Validation of BSC Decontamination
– Biological Indicators (opt.)
– Monitoring of relative humidity, space temperature, and/or decontaminant concentration during process
Choice of DecontaminantsChoice of Decontaminants
• Formaldehyde Gas
• Hydrogen Peroxide Vapor
• Chlorine Dioxide Gas – MCI preferred
55
Formaldehyde Gas (CHFormaldehyde Gas (CH22O)O)
• Typically via depolymerization of Paraformaldehyde (PF)
• NSF standard 0.3 gm/ft3 � ~8000 ppm
• Mechanism: methylization of DNA
• Requires relative humidity > 60%
• Target contact time > 6 hr
• Use Bacillus atrophaeus as B.I.
Formaldehyde Gas (Cont’d.)Formaldehyde Gas (Cont’d.)
• Neutralization with ammonia gas (NH3)– Decomposition of ammonium carbonate (at 1.0-
1.1 times PF weight)
– Or ammonium bicarbonate (at 1.6 time PF weight)
– ~ 1 hour contact time
• Vent and environmental monitoring
• Clean “fall-out”– Mixture of methenamine and PF
– Can limit PF polymerization with humidity control
56
Formaldehyde GasFormaldehyde Gas
Formaldehyde Gas Formaldehyde Gas ––
AdvantagesAdvantages
• “True” gas
• Relatively inexpensive
• General material compatibility
• Industry accepted
• Validated
57
Formaldehyde Gas Formaldehyde Gas –– IssuesIssues
• “Fall-out” residue
– Added clean-up time
• Carcinogen
• Potential residual odor
• Polymerization on cold surfaces
Formaldehyde Operating Formaldehyde Operating
ConditionsConditions
• Cabinet preparation – 30-60 min
• Gas generation – 15-30 min
• Contact time – 6-12 hours
• Neutralization and venting – 60-90 min
• Clean-up 30-60 min
Total – 9-15 hours
58
Hydrogen Peroxide Vapor (HHydrogen Peroxide Vapor (H22OO22))
• Typically delivered by flash vaporization of aqueous peroxide mixture– The mixture is generally close to or above
saturation in air
• Two major vendors of generators with significant differences
• Mechanism: oxidation
• Requires contact time less than formaldehyde
• Use Geobacillus stearothermophilus as B.I.
HP Vapor HP Vapor –– STERIS (VHP)STERIS (VHP)
• Avoids condensation on surfaces to minimize corrosion and optimize distribution
• Typically two portals into BSC for VHP inlet and return
• Design cabinet with appropriate circulation paths
• Dehumidify to < 30% relative humidity
– In order to avoid condensation of VHP
– VHP generation introduces humidity
59
HP Vapor HP Vapor –– STERIS (cont’d.)STERIS (cont’d.)
• Typical 1-2 mg/liter, 750-1500 ppm(D ~ 1-2 min)
– D Value – amount of time to achieve 1-log
reduction
• Target 70-85% RH during decontamination
• Continually introduce HP, decomposing HP in return
• Cycle Phases: Dehumidification / Conditioning / Decontamination / Aeration
HP Vapor HP Vapor –– BIOQUELL BIOQUELL
((ClarusClarus))
• Seeks “micro-condensation”
– BQ believes D ~ 2 min requires liquid presence
• Swiveling source to inject high-speed
droplets to all surfaces
– Condensate “bounces”
• Monitor for onset of condensation
60
HP Vapor AdvantagesHP Vapor Advantages
• Safe by-products (water and oxygen)
• No residue
• Industry accepted
• Automated
• Relatively short cycle time if properly
engineered
HP Vapor IssuesHP Vapor Issues
• Instability of HP toward decomposition– Flow pattern is critical to “beat”
decomposition rate
• Decomposition may block access of decontaminant
• Condensation may cause control issues– Heat-tracing or pre-thermal treatment
• Capital equipment cost
61
HP Vapor Issues (cont’d.)HP Vapor Issues (cont’d.)
• Cellulose materials absorb or decompose– May effect decontamination or aeration
• Some material issues – nylon, cellulose, copper, lead, iron oxide, epoxy– Condensation may effect painted surfaces
• Potential reaction to materials used in testing cleanrooms / BSCs or filter components– Titanium tetrachloride or TiO2 may act as a catalyst
on filter surfaces – from Steris
– Glycol on surfaces may oxidize when in HP contact – from Bioquell
SetSet--Up Example of VHP 1000Up Example of VHP 1000
62
HP Operating ConditionsHP Operating Conditions(based upon limited information)(based upon limited information)
• Set-up / Tear-down:30-60 min
(depends if cabinet is reconfigured)
• Typical duration from conditioning through decontamination:
2-4 hours
• Typical aeration:2-4 hours
Total – 5 - 9 hrs
Chlorine Dioxide Gas (ClOChlorine Dioxide Gas (ClO22))
• Mechanism: Oxidation (no chlorination)
• Generated on site via reaction:
– Cl2(g) + 2NaClO2 � 2ClO2(g) + 2NaCl
• Visible yellow-green gas
• Humidification required, 65-90% RH
• 1700 ppm concentrationMCS system – DRS Laboratories
63
Copyright © NSF 2010
Chlorine Dioxide Gas (Cont’d.)Chlorine Dioxide Gas (Cont’d.)
• Scrubbing– Wet, with alkaline solutions
– Dry, via adsorption (e.g., charcoal)
• Direct venting option (use by paper industry)
• Monitor concentration and relative humidity
• Use Bacillus atrophaeus as B.I.
• DRS Laboratories – Halide Group, ClorDiSys Solutions, Sabre
Oxidation Technologies (different reaction)
64
Chlorine Dioxide Gas Chlorine Dioxide Gas ––
AdvantagesAdvantages
• Safe by-products (oxygen and salt)
• No residue
• Not flammable / explosive
• “True gas” – no condensation issues
• Reputation for use in Anthrax
decontamination
Chlorine Dioxide Chlorine Dioxide -- IssuesIssues
• Less well-known or characterized
• Mild corrosion/discoloring to cold steel, copper, brass,– Particularly in the presence of water
• Potentially corrosive if chlorine gas (Cl2) is present– Care to avoid Cl2 in synthesized CD
– Care to avoid Cl2 creation by UV exposure
• Low PEL limit (0.1 ppm)
65
CD Operating ConditionsCD Operating Conditions
• Set-up / Tear-down:60 - 90 min
• Typical duration from humidification through decontamination:
60 - 90 min
• Typical aeration:15 - 30 min
Total: 3 - 4 hr
NSF/ANSI 49 NSF/ANSI 49 –– 2008 Annex G2008 Annex G
“Prior to decontamination with an alternative method [note added: other than depolymerized paraformaldehyde or chlorine dioxide gas] (such as vaporous hydrogen peroxide [VHP]), cycle parameters and validation of those parameters must be developed for each model and size of BSC.”
Recommended decontamination methods
66
Issue Formaldehyde
Gas
Hydrogen Peroxide
Vapor
Chlorine Dioxide
Gas
Sporocidal effectiveness + + +
Effective through HEPA filters+ + / ? +
Non Carcinogenic - + +
Toxicity (TWA PEL) 0.75 ppm 1.0 ppm 0.1 ppm
Humidity requirement (RH)60-90%
30% (VHP) or ambient
(Clarus)65-90%
No residue - + +
+ (VHP) / + /
? (Clarus) - (with chlorine)
Method of removal Neutralizer Catalytic breakdown Scrubbing
Limited development effort + - +
Limited cost + - - / +
Cycle Time (hr) 9 to 15 4 to 7 3 to 4
Non-corrosive +
ComparisonComparison
References (partial)References (partial)• Formaldehyde
– Kruse, R. H et al. (1991). Biological Safety Cabinetry. Clinical Microbiology Reviews, 4, 207-241.
– The National Sanitation Foundation (2002). Annex G – Recommended microbiological decontamination procedure, National Sanitation Foundation: Standard No. 49 for Class II (Laminar Flow) Biohazard Cabinetry, G1-G3.
– Taylor, L.A. et al. (1969). Paraformaldehyde for Surface Sterilization and Detoxification. Applied Microbiology, 17, 614-618.
– Fink, R. et al. (1988). Biological safety cabinets, decontamination or sterilization with paraformaldehyde. Am. Ind. Hyg. Assoc. J., 49, 277-279.
• Hydrogen Peroxide
– Hillman, D. (2004). Vapor phase hydrogen peroxide gas decontamination of a BSC. Performance Review, 10, 10-16.
– Watling, D. et al. (2002). Theoretical analysis of the condensation of hydrogen peroxide gas and water vapour as used in surface decontamination. PDA J. Pharma Sci Technol., 56, 291-299.
– Jones, R. et al. (1994-5). ACUMEN, 1, No. 1-4, Baker Company.
67
References (Partial)References (Partial)
• Chlorine Dioxide– Luftman, H., Regits, M., Lorcheim P., Lorcheim K., & Paznek D. (2008)
“Validation Study for the Use of Chlorine Dioxide Gas as a Decontaminant for Biological Safety Cabinets” Applied Biosafety: Journal of the American Biological Safety Association, 13(4), 199-212.
– Luftman, H. S., & Regits, M. A. (2008). B. Atrophaeus and G. Stearothermophilus biological indicators for chlorine dioxide gas decontamination. Applied Biosafety: Journal of the American Biological Safety Association, 13(3), 143-157.
– Luftman, H. S., Regits, M. A., Lorcheim, P., Czarneski, M. A., Boyle, T., Aceto, H., et al. (2006). Chlorine dioxide gas decontamination of large animal hospital intensive and neonatal care units. Applied Biosafety: Journal of the American Biological Safety Association, 11(3), 144-154.
– Jeng, D.K. and Woodworth, A.G. (1990). Chlorine dioxide gas sterilization under square-wave conditions. Appl. Environ. Microbiol., 56, 514-519.
– Leo, F.P. et al. (2005). Design, development and qualification of a microbiological challenge facility to assess the effectiveness of BFS aseptic processing. PDA J. Pharm. Sci. Technol., 59, 33-48.
QuestionsQuestions
68
Economic Alternatives for Economic Alternatives for Laboratory ContainmentLaboratory Containment
• Discuss the advantages and
disadvantages of alternatives to
conventional laboratory containment
devices
– Ductless fume hoods
– Balance enclosures
ObjectivesObjectives
69
• Containment devices that may utilize
HEPA/ULPA filters or an assortment of
chemi-sorbent filtration systems to
contain process contaminants.
Ductless Fume HoodsDuctless Fume Hoods
Captair ErlabLabconco Corp AirClean Systems
• AFNOR NF X 15-211 “Enclosures for
Toxics with Recirculating Air Filtration”
• ASHRAE 110 – 1995 “Method of
Testing Performance of Laboratory
Fume Hoods”
• SEFA 9 – 2010 “Recommended
Practices for Ductless Enclosures”
Industry Factory TestingIndustry Factory Testing
70
• Offers simple containment devices
without costly venting out of laboratory
• Saves energy costs
• Space saver
• Ideal for low hazard experimentation
• No ductwork contamination
AdvantagesAdvantages
• Ductless fume hoods are not
recommended for use with unknown
chemicals or reactions.
• Limited to manufacturer-approved
applications
• Requires strict adherence to chemical
hygiene program
• Abuse can be catastrophic
DisadvantagesDisadvantages
71
• Thorough risk assessment and hazard
determinations should be investigated
before selecting use of this type of
device, and any other device.
– Are all ductless fume hoods alike?
– Can they be used safely?
– What materials may I use in a DFH?
Safety ConcernsSafety Concerns
• NFPA 45 "Standard on Fire Protection for
Laboratories Using Chemicals" 2010 Edition, Annex A (Explanatory Material), paragraph A.8.4.1
• "Ductless chemical fume hoods that pass air from the hood interior through an absorption filter and then discharge the air into the laboratory are only applicable for use with nuisance vapors and dusts that do not present a fire or toxicity hazard."
National Fire Protection National Fire Protection
AssociationAssociation
72
• No !!!
– Uses
• liquid, powder, combinations of both
– Types of filtrations
• HEPA, carbon filter, proprietary blends
– Layers of filtration
• Single, double (safety filter), HEPA-carbon combo
– Protection mechanisms from chemical breakthrough
• How will the user know if the filter reaches saturation?
Are all DFHs alike?Are all DFHs alike?
• Single or double layer of filtration
– Safety filter usually has detection port or mechanism for breakthrough
– Only allows failure of 1st stage
Filtration LayersFiltration Layers
PrimaryPrimary
Safety
73
• Electronic chemical detection sensors
• Chemical reactive tubes
• Banana oil (Isoamyl Acetate)
• Nose
Warning mechanismsWarning mechanisms
PrimaryPrimary
Safety
• Detection sensors and chemical
reactive tubes can quantify the
amount of breakthrough
Warning mechanismsWarning mechanisms
Drager
95 fpm
0.00 ppm
Labconco Corp.
74
• Most DFH manufacturers offer
application specialists or chemical use
survey form to determine the best
option for your expected use.
• Ultimately, the decisions will be up to
the end user and their safety committee
ConsultationsConsultations
• Same advantages as DFH plus:
– Set airflow specific to your application
• 60 to 100 fpm ideal for containment while not
disrupting balance operation
• Won’t scatter lightweight powders during weighing operations
– May be used for higher toxicity powders when precautions are taken
– More options available
Lab Balance EnclosuresLab Balance Enclosures
75
• Material hazards
– Powders
– Volatility (option to duct out of facility)
• Canopy exhaust connection recommended
• Plan on how to handle filter replacement
– BIBO capability
• Spot filtration or distant filtration
– Contamination to ductwork
ConsiderationsConsiderations
• Numerous configurations based on need and
location
• Laboratory weighing to bulk powder
applications
Labconco Corp.Baker Co.
Flow Sciences
76
QuestionsQuestions
ASHRAE 110 UpdatesASHRAE 110 Updates
77
Objectives Objectives
• Discuss general procedure and future
changes of the ASHRAE 110
performance test that yields quantitative
data about laboratory chemical hood
containment in a more accurate
method, with repeatable results.
Chemical Hood Test MethodsChemical Hood Test Methods
• Face Velocity Testing
– Cheapest, but least accurate.
• ASHRAE 110 Testing
– More expensive, but produces better results.
– Takes into account such things as turbulence.
• Personal Air Sampling
– Very expensive and time consuming, but is the most accurate.
78
ASHRAE SAFETYASHRAE SAFETY
• Why is ASHRAE 110 testing so important?
– Normal face velocity
and smoke tests do
nothing to show
containment when someone is standing at the hood opening (as a mannequin would be).
– Airflow patterns can vary significantly.
SEFA vs. SEFA vs. ASHRAE 110ASHRAE 110
• Advantages of ASHRAE 110– Safety
• Tests more of the laboratory chemical hoods containment capabilities
– More tests• Large Volume Smoke Study
– Challenge hood with smoke from a smoke generator
• Tracer gas test
– Four different types of tracer gas tests
79
SEFA vs. ASHRAE 110 TestsSEFA vs. ASHRAE 110 TestsSEFA ASHRAE 110
X Room Ventilation Test
X X Face Velocity Test
X X Alarm Verification
X X Local Volume Visualization Test
X Large Volume Visualization Test
X Tracer Gas Containment Test
�Positional Control Test
�Leakage Test
�Sash Movement Effect Test
�Walk-by Test
Room Ventilation TestRoom Ventilation Test
• Check baffle configuration
– should be 3/4” open at top
• Pass smoke source 4-6” outside hood opening
• Record all disruptions of normal airflow and corrective actions taken
80
Face Velocity ProfileFace Velocity Profile
• Set sash to designed height
• Measure opening to determine access area
• Form grid starting 6” in on all sides
– Grid not to exceed 1 sq. ft.
• Record avg. velocity and calculate volume
• Velocities must be monitored for 5 seconds in each position
• Sampling time and data averaging
• … anemometer shall be used to take and record twenty velocity readings, taken at the rate of one per second, at the center of each grid rectangle. Calculate the average of the twenty readings…”
Upcoming changesUpcoming changes
81
VAV Response TestVAV Response Test• At 50% open, anemometer
is placed in the ringstandand sash is closed to approximately 25%
• Stopwatch for response
• Return to 50%, raise the sash to the full open (or 100%) position
• Record the time it takes for the velocities to return to within 10% of the initial 50% value
• Anemometer probe placement change
– either placed in the exhaust ductwork or
– hood “slot” velocity (the opening at the rear of the hood between the baffle plates).
• Measurements are recorded on a data logger while
opening and closing the sash. The test performed spans
5 minutes (30-60-30-60-30-60-30). The sash is closed
for 30 seconds and opened to the design opening for 60
seconds during each cycle and closed at the end of the
test. The results documented are the:
– 1. Speed of Response
– 2. Time to Steady State
– 3. Repeatability of Flow Response
Upcoming changesUpcoming changes
82
Local Volume Smoke StudyLocal Volume Smoke Study
• Pass smoke source
– Under front airfoil
– Around entire sash
opening, 6” behind sash
– In an 8” diameter circle
along the back wall of the hood
– Along all equipment and at the work top of the hood
Large Volume Smoke StudyLarge Volume Smoke Study
• Release large volume of smoke along centerline, 6” behind sash.
• Report where all refluxing or escapage of air is coming from.
• Record all corrective actions taken.
83
• Large volume smoke at same locations as local
volume smoke study
– Under the airfoil
– Along the side walls
– Along the work surface
– Around any equipment inside the hood
– Inside the hood, above the bottom of the sash
– For horizontal or combination sash hoods, release smoke
behind the sash
– In the cavity above the hood opening
– Outside the hood
Upcoming changesUpcoming changes
Tracer Gas TestsTracer Gas Tests
• Positional Control Test
• Leakage Test
• Sash Movement Effect Test
• Walk-by Test
84
• Height of mannequin change
– Anthropomorphic data acquired states the
average laboratory worker height is 5’ 4.5” tall.
• Lowers the breathing zone creates a bigger challenge
to the hood, as the breathing zone is now closer to an
18” design opening.
• Common leakage from a Chemical Hood is seen along
the bottom of the sash, when opened (another
common point of leakage is in front of large equipment
placed in the hood).
Upcoming changesUpcoming changes
• Positional Control Test
– A 30 second “delay” is initiated prior to the 5-
minute Positional Test to allow the analyzer cell to fill completely.
• Peripheral Scan
– In addition to the normal scan around the sash
opening, a scan is performed under the airfoil.
Upcoming ChangesUpcoming Changes
85
• Sash Movement Effect Test
– The test is performed in the same manner as the
1995 ASHRAE 110 Standard, however the time
for each section has changed:
• 60 seconds after the start of gas generation, start the
analyzer to log readings every 1 second
• After 60 seconds, open the sash to the design sash
opening
• After 60 seconds, close the sash
• Repeat three times
• Calculate the 45-second rolling average for each test.
Record the maxim rolling average associated with each
opening of the sash
• The SME is the maximum rolling average determined
Upcoming changesUpcoming changes
WalkWalk--by Test (New)by Test (New)
• Tester walks behind mannequin at a rate of 3 feet per second
• Parallel to sash at a distance of 24” away from sash plane.
• Simulates lab personnel movement effect by an operator of a laboratory chemical hood.
• Report the maximum concentration
86
QuestionsQuestions
Cleanroom and Cleanroom and Containment Suite Containment Suite
UpdatesUpdates
87
Two Types of Areas inTwo Types of Areas in
• Pharmaceutical Sterile Manufacturing Facilities
Review of Typical Sterile Review of Typical Sterile Manufacturing SuiteManufacturing Suite
• Class 1,000 to Class 100,000 (ISO Class 6 to ISO Class 8) Non-Unidirectional Support Areas (Controlled Areas)– Dilution control
• Class 100 (ISO Class 5) UnidirectionalFilling Areas
(Critical Areas)– Flow Control
88
Filling Room
Class 100 (ISO Class 5)
Critical Area
Gown Room
Class 100,000
Controlled
Area
Equipment
Pass-Thru
Class 100,000
Controlled
Area
Corridor Class 10,000 Controlled Area
Filling Room
Class 100 (ISO Class 5)
Critical Area
Typical Pharmaceutical Cleanroom LayoutTypical Pharmaceutical Cleanroom Layout
Warehouse / Ambient / Uncontrolled
ISO Class 8 ISO Class 8
ISO Class 7
Class 100 VLF
Isolator
BSC
Class 100,000 Corridor
Class 10,000 Room
Class 10,000 Room
Typical Pharmaceutical Cleanroom LayoutTypical Pharmaceutical Cleanroom Layout
(ISO Class 7) (ISO Class 7)
(ISO Class 5)
(ISO Class 8)
89
Critical AreasCritical Areas
• The “critical” area is where sterilized product or container/ closures are exposed to the environment.
Unidirectional Airflow Rooms Unidirectional Airflow Rooms
(Laminar)(Laminar)• Most common application of unidirectional
Room is vertical flow. Air flows in a downward direction from filters located in room ceiling and returns to sidewall returns or perforated flooring. IMPORTANT
– Pharmaceutical industry does not use perforated flooring.
• Airflow in unidirectional rooms may be horizontal flow walls with 100% coverage in supply side wall.
• Unidirectional – previously referred to as Laminar Flow
90
HEPA
RETURN RETURN
Unidirectional Room
HEPAHEPAHEPA HEPA
FLOW CONTROL
Controlled AreasControlled Areas
• The “controlled” area is where unsterilized product, in process
materials, & container/closures are
prepared.
91
Nonunidirectional Airflow Nonunidirectional Airflow RoomsRooms
• Air flows from filters in various ceiling or wall locations and is returned through ceiling or low wall returns. IMPORTANT
• Filters may be distributed at equal intervals or be clustered over critical process areas.
HEPAHEPA
RETURN RETURN
Non - Unidirectional Room
DILUTION CONTROL
92
93
94
• ISO Std 14644-1:1999 “Cleanrooms and
associated controlled environments - part
1 Classification of Air Cleanliness”
– Is currently in FDIS status with areas still under review and serious contention
• 5.0 um reporting on classification chart
• Use of statistical analysis or drop
• Determining minimum number of sample locations
• Requiring particle counters to be calibrated by ISO Std 21501-4 methods
Industry UpdatesIndustry Updates
• Useful reference sources
– CDC/NIH Biosafety in Microbiological and Biomedical Laboratories – 5th edition
• HHS Pub No (CDC) 21-1112
• General guidance, little actual acceptance criteria
– Primary Containment for Biohazards: Selection, Installation, and Use of Biosafety Cabinets. 3rd edition
• Now Appendix A of 5th Edition
• Ref: http://www.cdc.gov/biosafety/publications/
Containment Suite InformationContainment Suite Information
95
– Takes over where BMBL 5th edition leaves off
– Provides specific guidance on room pressurization, alarm conditions
• Formerly called the NIH Design Policy and Guidelines
Other SourcesOther Sources
NIH Design Requirements
Manual for Biomedical
Laboratories and Animal
Research Facilities (DRM)
• Manual 242.1 USDA ARS Facilities Design Standards
– Biosafety Level 1 (BSL-1).
– Biosafety Level 2 (BSL-2).
– Biosafety Level 3 (BSL-3).
– Biosafety Level 3 Agriculture (BSL-3Ag). Used with pathogens that present a risk of causing infections
of animals and plants and causing a great economic
harm. (Example: Foot and Mouth Disease)
– Biosafety Level 4 (BSL-4).
Other SourcesOther Sources
96
Questions – Raise your hand or contact us by email: [email protected] or
telephone (800) 523-9852