nyb bulletin 221:nyb bulletin 221 - thermoandinathermoandina.com/pdf/tvc-df-221.pdf · is radial...

16

Upload: others

Post on 16-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from
Page 2: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 2

PLENUM FANSNew York Blower’s Plenum Fans are designedspecifically for application in pressurized plenumsfound in industrial and commercial air-handling sys-tems. The unhoused, compact design combined withthe choice of two AcoustaFoil® wheels provides theutmost in quiet and efficient operation.

DESIGN FEATURES

• Two wheel choices:High-efficiency AcoustaFoil® wheels, Sizes 12”-73”.Ultra-quiet AcoustaFoil-Q® wheels for

sound-sensitive applications, Sizes 18”-66”.

• Capacities to 160,000 CFM.

• Pressures to 12”WG.

• Aerodynamic, spun inlet cone.

• Choice of four horizontal arrangements:Arrangement 1 —Sizes 12” to 15”Arrangement 3 —Sizes 16” to 73”Arrangement 3-P—Sizes 16” to 40”Arrangement 4 —Sizes 12” to 60”

• Arrangement 3-V for vertical mounting in Sizes 16” to 73”.

• Designed and tested to eliminate all natural frequencies in the operating range.

• Temperatures to 120°F.

CONSTRUCTION FEATURES

• Formed structures for rigidity and improved fit.

• Bearings selected for average L10 life of 40,000hours at maximum speeds.

• Lifting eyes are standard.

• Wheels are dynamically balanced and fans arechecked at the specified operating speed.

APPLICATION ADVANTAGES

Copyright © 2008 by The New York Blower Company. ®AcoustaFoil and AcoustaFoil-Q are registered trademarks of The New York Blower Company. ® Registered trademark of The New York Blower Company.

Unhoused Plenum Fans were developed in response to thecontinuing push for greater system value and applicationflexibility in air-handler systems. For systems utilizing pres-surized plenums, these fans provide the airflows and pres-sures of conventional housed fan designs but in compact,more economical configurations. The result is reduced sizeand weight of air-handler cabinetry with maximum appli-cation flexibility. System air is supplied or returned to theair handler from virtually any direction with a minimum ofductwork. Plenum Fans offer system manufacturers theutmost in choice of sizes and configurations.

AIR HANDLER RETURNAIR

SUPPLYAIR

Size 243, Class I,Arrangement 4 with motor.

Size 333, Class II,Arrangement 3with optional screen enclosure.

Page 3: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

SUPERIOR PERFORMANCEFor all AcoustaFoil designs shaded areahighlights broad region of peak mechanicalefficiency superior to other airfoil designs.

020

20

40

60

80

100

120

40 60 80 100PERCENT CFM

PER

CEN

T B

HP

and M

E

STATIC PRESSURE

BRAKE HORSE

POWER

MEC

HAN

IC

AL

QUIET PERFORMANCECompared to typical airfoil designs, theAcoustaFoil-Q has a flatter sound profile andreduced sound levels in the noticeable loweroctave bands as illustrated by the shaded area.

1 2 3 4 5 6 7 8OCTAVE BAND

SO

UN

D L

EVEL

TYPICAL

A

IRFOIL

ACOUSTAFOIL-Q

PAGE 3

STABLE PERFORMANCECompletely stable pressure curve from wide-open to closed-off...ideal for variable air volumesystems.NON-OVERLOADINGHorsepower reaches a peak and then decreas-es as flow increases... allows calculation of themaximum brake horsepower at a given fanspeed so a motor can be selected that will notoverload if system pressure changes.

CHOICE OF TWO ACOUSTAFOIL® WHEEL DESIGNS

EFFICIENCYThe mechanical efficiency curveoffers a broad selection range withlittle horsepower variation.SOUNDThe superior efficiency of theAcoustaFoil wheel provides a lowsound level over a wide perform-ance range.

TRADITIONAL ACOUSTAFOIL® WHEEL

SOUNDAcoustically tuned wheel and conereduces sound power levels in thelower octave bands, flattens overallsound profile, and also minimizesblade-pass frequency turbulence.

ULTRA-QUIET ACOUSTAFOIL-Q® WHEEL...for sound-sensitive applications.After years of acoustical research and testing in two accredited sound testing laboratories,New York Blower’s time-tested AcoustaFoil technology is quietly taken to the next level.

STABLE AND EFFICIENT PERFORMANCESame efficiency and horsepower characteristicsas the traditional AcoustaFoil wheel.NEW SELECTIONSUnique performance offers alternative selectionsto the traditional AcoustaFoil wheel.

The New York Blower Companycertifies that the Plenum Fanswith AcoustaFoil-Q wheels shownherein are licensed to bear theAMCA Seal. The ratings shownare based on tests and proce-dures performed in accordancewith AMCA Publications 211and 311 and comply withrequirements of the AMCACertified Ratings Program.AMCA-licensed sound perform-ance can be found inEngineering Supplement ES-225, dated April 2003.

The New York Blower Companycertifies that the Plenum Fanswith AcoustaFoil wheels shownherein are licensed to bear theAMCA Seal. The ratings shownare based on tests and proce-dures performed in accordancewith AMCA Publication 211and comply with requirementsof the AMCA Certified RatingsProgram.

Page 4: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

ACCESSORIES AND MODIFICATIONS

Safety accessories are available from nyb, but selection of the appropri-ate devices is the responsibility of the system-designer who is familiarwith the particular installation, or application, and can provide for guardsfor all exposed moving parts as well as protection from access to high-velocity airstreams. Neither nyb nor its sales representatives is in a posi-tion to make such a determination. Users and/or installers should read“Recommended Safety Practices for Air Moving Devices” as published bythe Air Movement and Control Association, Arlington Heights, Illinois.

SAFETYEQUIPMENT

PAGE 4

1. INTERNAL INLET-VANE DAMPERCompact damper/cone assembly providessmooth control for systems that require efficient dampering of airflow. Available on Sizes 18 and larger.

2. INLET GUARDHeavy-gauge wire inlet guard covers completeinlet area.

3. INLET COLLARRolled-steel collar provides surface to attachflexible connector from ductwork or bulkhead.

4. EXTENDED LUBE LINESExtended bearing lubrication lines with externalfittings located for ease of service.

5.UNITARY BASEStructural-steel base provides common supportfor fan, motor, and drive components...alsoavailable with spring-type or rubber-in-shearisolators...flexible inlet-duct connection recommended for use with isolation bases.

6.BELT GUARDGuards constructed with solid sheet-metalbacks and sides and expanded metal coversfor maintenance viewing. Guards includetachometer opening with cap plug.

7.SCREEN ENCLOSUREExpanded sheet metal welded to rigid steelframe encloses the entire wheel assembly.

8.MOTORS AND DRIVESA wide array of motor and drive componentsare available factory-mounted.

Size 303, Class II,Arrangement 3-V,with optionalmotor and drives.

Size 333, Class II,Arrangement 3, with optionalscreen enclosure.

Page 5: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

ARRANGEMENTFLEXIBILITY

VARIABLE FLOWAPPLICATIONS

PAGE 5

The rising cost of energy requires that air-handling sys-tems be operated efficiently at less than maximum designairflow. The high efficiency and inherent stability of theAcoustaFoil wheel is particularly well-suited to variableairflow systems. The AcoustaFoil wheel design ensuresnot only maximum operating efficiency at design CFM but also at reduced airflow regardless of the controlmethod applied. This higher efficiency allows quieteroperation throughout the modulation range.

The New York Blower Company’s nationwide network oftrained sales engineers is familiar with each of these con-trol alternatives and can offer further assistance in select-ing the best control for a particular application.

INLET-VANEDAMPER CONTROL

Inlet-vane dampers affectthe fan’s output by spin-ning the air in the direction of wheel rota-tion. With this prespin,the wheel cannot developits full output, yielding areduced CFM at reducedhorsepower. Each dampersetting creates new pres-sure and horsepowercurves. With inlet-vanedampers, reduced airflowalways results in reducedhorsepower.

VARIABLE FREQUENCYMOTOR SPEEDCONTROL

Variable frequency motorspeed controllers provideenergy savings by directlycontrolling fan speed.From the fan laws, CFMvaries directly with thechange in fan speed andhorsepower varies by thechange in fan speedcubed. For example, a20% reduction in fanspeed yields a 20%reduction in airflow and a49% reduction in BHP.Controllers must havelockouts to prevent opera-tion beyond the maximumsafe speed of the fan.

ARRANGEMENT 3-P

ARRANGEMENT 3-V

ARRANGEMENT 4

ARRANGEMENTS1, 3For the widest range ofperformance. Fans canbe provided with unitaryand isolation bases forcommon mounting offan, motor, and drive.Arrangement 1 availablein Sizes 12” to 15”.Arrangement 3 availablein Sizes 16” to 73”.

Integral motor mountCompact, belt-drive de-sign. Fan with integralmotor mount availablepackaged with optionalmotor and drives. Avail-able in Sizes 16” to 40”.

Vertical mountIdeal for applications in-volving vertical airflow.Design eliminates transi-tion space requirementsand minimizes structuralsupport. Available withintegral motor and drivemounting. Available inSizes 16” to 73”.

Direct-drive designs forvery compact, light-weightapplications. Wheel widthscan be varied to meet spe-cific CFM requirements atdirect-drive motor speeds.Ideal for variable speedcontrol. Lockouts arerequired to prevent opera-tion beyond fan maximumsafe speeds. Available inSizes 12” to 60”.

20

0

40

60

80

100

120

0 20 40 60 80 100 120 140 160

% P

RES

SUR

E

% VOLUME

100806040200

% VOLUME160140120

80

60

20

0

40

120

100

% IN

PU

T P

OW

ER%

PR

ESSU

RE 80

60

20

0

40

120

100

100806040200 160140120

% VOLUME

% IN

PU

T P

OW

ER

40

60

80

100

120

20

0

% VOLUME100200 40 8060 160140120

Page 6: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 6

HOW TO USE CAPACITY TABLESEXAMPLE: A fan is required for 3200 CFM at 41⁄2”WG at 100°F. and at 1000 ft. elevation. Plenum discharge

is radial with a 2 ft. x 2 ft. duct with no transition.

Select size, RPM, and BHP of fan from capacity tables.

For conditions other than standard, correctstatic pressure for actual altitude and tem-perature using Chart II.

Correct system static pressure for lossesassociated with the discharge from theplenum using Chart I.

Determine actual performance at operatingconditions by correcting SP and BHP.

Check maximum safe speed of fan at tem-perature using Chart III.

Chart I gives a 1.4 velocity pressure correction factor for radial discharge,no transition. Duct velocity is CFM ÷ duct area. 3200 CFM ÷ 4 = 800 FPM.Velocity pressure = (duct velocity ÷ 4005)2. (800 FPM ÷ 4005)2 = .04”WG.Correction is velocity pressure x correction factor, .04” x 1.4 = .06”WG.Static pressure required = 4.5”WG + .06”WG = 4.56”WG.

Chart II gives a 1.10 factor for 100°F and 1000 ft. Corrected SP is 4.56”WGx 1.10 = 5.0”WG at 70°F. Select fan from capacity tables for 3200 CFM at5.0”WG.

A Size 133 is selected for 3200 CFM at 5.0”WG at 3921 RPM and 4.87BHP.

Actual performance: 3200 CFM at 4.56”WG [5.0 ÷ 1.10] at 3921 RPMat 4.43 BHP [4.87 ÷ 1.10] at 100°F. and 1000 ft.

From the capacity table and Chart Ill, the maximum safe speed of a Size133 fan is 4287 RPM [4330 RPM x .99]. A Class II fan is satisfactory foroperation at 100°F.

PROCEDURES STEPS CALCULATIONS

CHART I PLENUM EFFECT LOSSES PLENUM DESIGN EXAMPLESRadial and ducted with belltransition

Radial and ducted with nobell transition

Radial without duct

Axial and ducted with belltransition

Axial and ducted with no belltransition

Axial without duct

1.1

1.4

1.9

1.6

1.9

2.4

CHART II CORRECTION FACTORS FOR TEMPERATURE AND ALTITUDE CHART IIITEMPERATURECORRECTIONFACTORS FOR

WHEEL SAFE SPEEDS

For temperatures above 105°F, note the safe speed derate shown in Chart III.

Temperature°F.

Altitude–feet above sea level0 500 1000 1500 2000 4000 6000 8000 10000

-50-25

02040607080

100120

.77

.82

.87

.91

.94

.981.001.021.061.09

.79

.84

.89

.93

.961.001.021.041.081.11

.80

.85

.91

.95

.981.021.041.061.101.13

.82

.87

.92

.971.001.041.061.081.121.16

.83

.89

.94

.981.021.061.081.101.151.18

.89

.951.011.061.091.141.161.181.231.26

.961.031.091.141.181.231.251.281.331.36

1.041.111.181.231.271.321.351.381.431.47

1.121.191.261.321.361.421.451.481.541.58

Temp.°F.

Wheel materialSteel Aluminum

-5070

120

1.001.00.98

1.001.00.98

Sizes 123, 133, and 153 andArrangement 4 Sizes 403 to603 wheels are aluminum only.

Outlet

Inlet

OutletInlet

Inlet

Outlet

Outlet

Inlet

No ducton outlet

Duct outlet Duct outlet

No ducton outlet

RADIAL DISCHARGE AXIAL DISCHARGE

Page 7: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 7

To obtain your copy of New York Blower’s Electronic Catalog contact your local New YorkBlower representative or go to www.nyb.com and click on SeIection/Engineering Tools.

ELECTRONIC CATALOGA complete New York Blower Catalog on one CD. No more manual calculations andbulky product catalogs. A critical tool for all system-designers and engineers who selectand specify air-moving equipment.

SELECTION BENEFITS

•Fast, accurate fan selection.•Automatic altitude, temperature,

and density corrections.•Sound levels by octave band.•Fan-performance curves.•Multiple model and size choices.•Metric or English units.

CATALOG CONTENTS

•Fan-selection program.•Complete product catalog in PDF including

drawings, dimensions, and design specifications.•Sample guide specifications.•New York Blower Engineering Letters.•Installation and Maintenance Manuals.•Listing of New York Blower representatives.

ACOUSTAFOILPERFORMANCE FOR PLENUM FANS WITH WHEELS

SIZE123Max. safe speedsClass I=3755 RPMClass II=4900 RPM

CFM1"SP

RPM BHP

11⁄2"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

7"SP

RPM BHP

8"SP

RPM BHP

1400 2138 0.46 2330 0.63 2548 0.48 2919 1.27 3233 1.72 3544 2.22 3829 2.73 4118 3.32 4387 3.941600 2334 0.58 2508 0.76 2679 0.96 3052 1.44 3365 1.94 3631 2.44 3897 2.98 4168 3.57 4422 4.191800 2533 0.71 2699 0.92 2849 1.13 3174 1.61 3498 2.16 3770 2.73 4010 3.29 4248 3.89 4492 4.532000 2733 0.86 2900 1.10 3041 1.33 3316 1.82 3612 2.38 3902 3.00 4144 3.62 4367 4.25 4584 4.91

2200 2934 1.03 3098 1.30 3239 1.56 3486 2.07 3738 2.62 4014 3.27 4286 3.98 4506 4.65 4711 5.332400 3140 1.22 3299 1.52 3439 1.81 3676 2.37 3902 2.94 4138 3.57 4398 4.29 4642 5.06 4845 5.772800 3562 1.71 3704 2.04 3836 2.38 4073 3.06 4273 3.70 4468 4.37 4662 5.07 4875 5.843200 3991 2.32 4119 2.69 4241 3.07 4468 3.86 4668 4.62 4849 5.38

SIZE133Max. safe speedsClass I=3320 RPMClass II=4330 RPM

CFM1"SP

RPM BHP

11⁄2"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

7"SP

RPM BHP

8"SP

RPM BHP

1600 1869 0.51 2060 0.72 2267 0.96 2598 1.45 2890 1.98 3188 2.58 3463 3.22 3728 3.94 3968 4.671800 2013 0.62 2180 0.83 2355 1.07 2702 1.63 2978 2.19 3236 2.78 3498 3.43 3752 4.14 3987 4.882000 2161 0.74 2314 0.97 2465 1.21 2795 1.79 3077 2.41 3323 3.04 3559 3.71 3797 4.43 4029 5.192200 2310 0.87 2460 1.13 2598 1.39 2886 1.97 3180 2.64 3423 3.32 3649 4.03 3866 4.77 4074 5.51

2400 2460 1.02 2609 1.31 2740 1.59 2991 2.18 3266 2.86 3527 3.61 3745 4.35 3944 5.09 4144 5.892800 2761 1.37 2907 1.72 3033 2.05 3255 2.70 3471 3.40 3705 4.17 3942 5.03 4154 5.903200 3073 1.81 3209 2.20 3330 2.59 3544 3.34 3733 4.09 3921 4.87 4116 5.713600 3390 2.35 3513 2.78 3632 3.22 3845 4.11 4021 4.92 4192 5.78

SIZE153Max. safe speedsClass I=2910 RPMClass II=3800 RPM

CFM1"SP

RPM BHP

11⁄2"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

7"SP

RPM BHP

8"SP

RPM BHP

2400 1907 0.87 2047 1.14 2190 1.45 2494 2.16 2743 2.89 2970 3.68 3189 4.49 3408 5.38 3609 6.262600 2015 1.00 2152 1.30 2278 1.60 2560 2.33 2821 3.13 3043 3.96 3247 4.80 3440 5.65 3645 6.602800 2123 1.13 2260 1.47 2382 1.80 2624 2.51 2889 3.35 3113 4.22 3313 5.11 3503 6.02 3694 7.003000 2232 1.29 2370 1.66 2486 2.00 2709 2.73 2956 3.59 3188 4.51 3386 5.43 3564 6.36 3742 7.35

3200 2344 1.46 2477 1.85 2592 2.22 2801 2.98 3016 3.81 3255 4.79 3456 5.75 3641 6.763600 2566 1.84 2693 2.27 2809 2.72 3002 3.54 3185 4.40 3386 5.38 3593 6.45 3788 7.564000 2793 2.30 2913 2.78 3027 3.28 3218 4.22 3388 5.16 3549 6.10 3726 7.174400 3025 2.84 3138 3.36 3243 3.90 3435 4.98 3598 6.00 3750 7.03

SIZE163Max. safe speedsClass I=2595 RPMClass II=3385 RPMClass III=4100 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

3000 1772 1.11 2023 1.83 2294 2.70 2523 3.62 2724 4.57 2915 5.56 3296 7.76 3647 10.2 3981 12.93400 1936 1.38 2167 2.18 2391 3.05 2630 4.07 2834 5.12 3015 6.20 3354 8.44 3692 10.9 4006 13.63800 2099 1.70 2328 2.61 2518 3.50 2726 4.53 2937 5.67 3125 6.86 3442 9.22 3754 11.8 4053 14.64200 2267 2.07 2490 3.09 2668 4.05 2841 5.07 3032 6.24 3230 7.54 3552 10.1 3837 12.8

4600 2437 2.49 2651 3.61 2830 4.71 2988 5.78 3148 6.93 3327 8.24 3666 11.0 3954 14.05000 2608 2.98 2816 4.20 2991 5.40 3140 6.55 3283 7.72 3440 9.05 3862 12.95800 2961 4.20 3146 5.56 3318 7.01 3463 8.37 3597 9.73 3720 11.16600 3317 5.73 3486 7.26 3644 8.87 3787 10.5 3920 12.1 4037 13.6

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

Page 8: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 8

ACOUSTAFOILPERFORMANCE FOR PLENUM FANS WITH WHEELS

SIZE183Max. safe speedsClass I=2305 RPMClass II=3005 RPMClass III=3790 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

4800 1856 1.97 2058 3.00 2236 4.06 2406 5.20 2564 6.37 2710 7.60 2965 10.1 3225 12.85200 1975 2.31 2166 3.41 2337 4.55 2498 5.74 2654 7.00 2800 8.31 3049 10.9 3277 13.6 3532 16.75600 2097 2.70 2278 3.87 2443 5.09 2596 6.34 2742 7.64 2887 9.03 3137 11.8 3361 14.6 3573 17.66000 2220 3.14 2394 4.41 2550 5.68 2700 7.02 2837 8.36 2972 9.76 3229 12.7 3449 15.7 3650 18.8

6400 2344 3.63 2509 4.96 2664 6.34 2806 7.75 2940 9.17 3065 10.6 3318 13.7 3542 16.9 3741 20.16800 2470 4.18 2629 5.59 2774 7.02 2910 8.48 3040 9.98 3166 11.5 3404 14.7 3625 18.07600 2723 5.45 2867 7.00 3002 8.58 3134 10.2 3253 11.9 3373 13.6 3595 17.08400 2980 6.99 3112 8.67 3240 10.4 3358 12.2 3473 14.0 3586 15.8

SIZE203Max. safe speedsClass I=2125 RPMClass II=2780 RPMClass III=3510 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

5600 1620 2.03 1796 3.15 1955 4.34 2098 5.58 2232 6.86 2366 8.24 2615 11.06000 1709 2.32 1878 3.52 2032 4.78 2173 6.09 2304 7.45 2428 8.85 2665 11.8 2904 14.96400 1800 2.64 1961 3.91 2111 5.25 2245 6.60 2373 8.02 2493 9.49 2715 12.4 2941 15.7 3172 19.26800 1891 3.00 2046 4.33 2188 5.72 2320 7.14 2444 8.63 2562 10.2 2782 13.3 2992 16.6 3194 20.0

7200 1983 3.38 2132 4.80 2270 6.26 2397 7.74 2519 9.30 2633 10.9 2847 14.2 3042 17.5 3242 21.18000 2171 4.28 2307 5.83 2438 7.46 2558 9.08 2672 10.7 2782 12.5 2985 16.0 3173 19.7 3358 23.58800 2360 5.34 2489 7.06 2607 8.78 2721 10.6 2833 12.4 2934 14.2 3127 18.0 3311 21.9 3477 25.99600 2550 6.56 2670 8.42 2784 10.3 2893 12.3 2993 14.2 3090 16.1 3281 20.2 3455 24.4

SIZE223Max. safe speedsClass I=1970 RPMClass II=2570 RPMClass III=3240 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

7500 1574 2.97 1725 4.47 1862 6.03 1989 7.67 2106 9.36 2216 11.1 2423 14.6 2634 18.58000 1658 3.39 1802 4.97 1936 6.64 2057 8.33 2171 10.1 2278 11.9 2478 15.6 2673 19.5 2878 23.88500 1743 3.84 1881 5.51 2007 7.23 2127 9.04 2235 10.8 2339 12.7 2538 16.7 2719 20.7 2905 25.09000 1829 4.35 1961 6.11 2084 7.93 2199 9.81 2305 11.7 2407 13.7 2601 17.8 2777 22.0 2948 26.3

10000 2002 5.51 2125 7.46 2240 9.47 2346 11.5 2449 13.6 2544 15.6 2729 20.1 2894 24.6 3060 29.411000 2177 6.87 2291 9.01 2398 11.2 2499 13.4 2596 15.7 2688 17.9 2861 22.6 3024 27.5 3181 32.612000 2354 8.48 2461 10.8 2562 13.2 2657 15.6 2747 17.9 2836 20.4 3004 25.5 3160 30.612500 2443 9.39 2547 11.8 2645 14.3 2738 16.8 2825 19.2 2913 21.8 3074 26.9 3231 32.4

SIZE243Max. safe speedsClass I=1790 RPMClass II=2335 RPMClass III=2940 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

9200 1450 4.01 1595 5.98 1723 7.99 1845 10.1 1961 12.4 2068 14.6 2252 19.2 2436 24.3 2619 29.59800 1525 4.58 1664 6.65 1788 8.79 1905 11.0 2015 13.3 2123 15.7 2313 20.6 2477 25.6 2643 30.9

10400 1601 5.19 1734 7.38 1855 9.65 1967 12.0 2071 14.3 2176 16.8 2366 21.9 2530 27.2 2690 32.811000 1678 5.89 1805 8.18 1920 10.5 2031 13.0 2134 15.5 2233 18.0 2422 23.4 2589 28.9 2736 34.4

11600 1755 6.64 1877 9.04 1991 11.5 2097 14.1 2195 16.6 2292 19.3 2477 24.9 2645 30.7 2788 36.212800 1911 8.35 2025 11.0 2131 13.7 2230 16.4 2325 19.3 2416 22.1 2589 28.0 2753 34.2 2900 40.414000 2068 10.4 2174 13.2 2274 16.1 2369 19.1 2459 22.2 2543 25.2 2706 31.5 2862 38.015200 2227 12.7 2327 15.8 2421 19.0 2511 22.2 2597 25.5 2679 28.8 2833 35.4

SIZE273Max. safe speedsClass I=1540 RPMClass II=2010 RPMClass III=2530 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

10800 1228 3.63 1354 5.62 1468 7.81 1570 10.0 1670 12.3 1765 14.7 1936 19.5 2117 24.911600 1300 4.18 1421 6.31 1529 8.57 1630 11.0 1724 13.4 1813 15.8 1982 21.0 2142 26.312400 1373 4.78 1488 7.05 1594 9.45 1687 11.9 1780 14.5 1867 17.1 2031 22.5 2185 28.1 2337 34.013200 1447 5.46 1557 7.87 1657 10.3 1750 12.9 1838 15.6 1923 18.4 2083 24.1 2232 29.9 2371 35.9

14000 1521 6.19 1625 8.72 1724 11.4 1814 14.0 1898 16.8 1981 19.8 2134 25.6 2283 31.9 2412 37.815600 1672 7.88 1766 10.7 1858 13.6 1944 16.5 2023 19.5 2101 22.7 2244 29.1 2381 35.6 2513 42.517200 1824 9.90 1912 13.0 1996 16.1 2075 19.3 2154 22.6 2227 26.0 2363 32.8 2495 40.118800 1978 12.3 2059 15.7 2136 19.1 2213 22.5 2284 25.9 2357 29.6 2485 36.9

SIZE303Max. safe speedsClass I=1385 RPMClass II=1805 RPMClass III=2275 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

14000 1149 4.92 1261 7.54 1358 10.2 1451 13.2 1535 16.1 1617 19.1 1770 25.3 1920 31.915000 1216 5.67 1320 8.41 1415 11.3 1504 14.4 1587 17.5 1664 20.6 1812 27.1 1950 33.9 2099 41.416000 1283 6.48 1382 9.39 1473 12.4 1559 15.6 1638 18.8 1717 22.3 1862 29.2 1996 36.3 2121 43.417000 1349 7.35 1445 10.5 1533 13.6 1616 16.9 1694 20.4 1768 23.9 1910 31.2 2040 38.6 2161 46.1

18000 1418 8.34 1508 11.6 1593 14.9 1673 18.3 1747 21.9 1821 25.6 1956 33.2 2083 40.8 2205 48.819000 1487 9.44 1573 12.9 1656 16.4 1733 19.9 1807 23.7 1876 27.5 2010 35.5 2134 43.6 2253 51.921000 1626 11.9 1704 15.7 1781 19.5 1854 23.4 1925 27.4 1989 31.5 2112 39.8 2232 48.723000 1766 14.8 1838 18.9 1908 23.1 1977 27.3 2045 31.6 2105 35.9 2226 45.1

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

Page 9: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 9

ACOUSTAFOILPERFORMANCE FOR PLENUM FANS WITH WHEELS

SIZE333Max. safe speedsClass I=1265 RPMClass II=1650 RPMClass III=2080 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

17000 1031 5.54 1124 8.68 1212 12.0 1297 15.4 1378 19.0 1454 22.7 1601 30.2 1747 38.618000 1080 6.19 1168 9.44 1252 12.9 1337 16.6 1413 20.3 1488 24.1 1631 32.1 1767 40.3 1896 49.019000 1130 6.90 1215 10.3 1296 13.9 1375 17.7 1450 21.6 1524 25.6 1659 33.8 1791 42.4 1921 51.520000 1179 7.66 1262 11.2 1339 15.0 1415 18.9 1490 23.0 1559 27.1 1692 35.7 1820 44.6 1946 54.0

21000 1229 8.48 1310 12.2 1383 16.1 1456 20.2 1528 24.4 1596 28.7 1727 37.7 1847 46.7 1969 56.423000 1330 10.3 1407 14.4 1475 18.6 1542 22.9 1607 27.4 1674 32.1 1798 41.7 1910 51.1 2026 61.525000 1431 12.5 1504 16.8 1570 21.4 1630 25.9 1692 30.7 1752 35.6 1870 45.7 1982 56.227000 1534 14.9 1604 19.7 1666 24.5 1725 29.4 1781 34.4 1837 39.6 1950 50.5 2056 61.4

SIZE363Max. safe speedsClass I=1110 RPMClass II=1450 RPMClass III=1825 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

20000 884 6.26 982 9.90 1072 13.9 1153 18.1 1228 22.4 1298 26.8 1428 35.7 1571 45.721000 919 6.88 1013 10.7 1099 14.7 1180 19.1 1253 23.6 1322 28.2 1450 37.5 1573 47.122000 953 7.54 1044 11.5 1128 15.7 1205 20.1 1281 25.0 1349 29.8 1470 39.2 1590 49.2 1719 60.223000 988 8.25 1077 12.4 1158 16.7 1233 21.2 1305 26.1 1372 31.0 1495 41.0 1607 51.1 1726 62.2

25000 1058 9.77 1141 14.2 1219 18.8 1292 23.7 1360 28.8 1426 34.1 1545 44.8 1653 55.6 1756 66.727000 1130 11.5 1207 16.2 1281 21.2 1350 26.3 1415 31.5 1480 37.2 1597 48.7 1706 60.6 1806 72.529000 1202 13.5 1275 18.5 1345 23.8 1412 29.2 1474 34.7 1535 40.5 1649 52.7 1756 65.331000 1275 15.8 1344 21.2 1410 26.6 1475 32.4 1533 38.1 1594 44.3 1703 56.9 1808 70.2

SIZE403Max. safe speedsClass I=1005 RPMClass II=1315 RPMClass III=1655 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

24600 795 7.87 877 12.5 957 17.4 1031 22.5 1099 27.6 1164 33.1 1279 43.826400 841 9.03 919 13.9 993 19.0 1066 24.5 1133 30.0 1196 35.7 1308 47.1 1420 59.428200 887 10.3 961 15.4 1031 20.9 1099 26.4 1165 32.2 1227 38.2 1339 50.5 1439 62.5 1554 76.930000 933 11.7 1005 17.1 1070 22.7 1136 28.6 1201 34.9 1262 41.2 1373 54.0 1469 66.8 1566 80.3

31800 980 13.2 1049 19.0 1113 25.0 1173 31.0 1236 37.5 1296 44.1 1404 57.5 1503 71.2 1592 84.935400 1074 16.7 1140 23.1 1197 29.5 1253 36.2 1309 43.1 1365 50.3 1471 65.0 1566 79.739000 1169 20.9 1232 27.9 1286 34.9 1338 42.2 1388 49.5 1439 57.2 1540 73.1 1632 88.942600 1264 25.7 1325 33.3 1376 40.9 1425 48.7 1472 56.7 1518 64.9 1611 81.8

SIZE443Max. safe speedsClass I=0910 RPMClass II=1190 RPMClass III=1495 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

30000 718 9.60 792 15.3 864 21.1 931 27.4 994 33.8 1050 40.1 1156 53.432000 756 10.9 825 16.7 895 23.1 960 29.6 1022 36.4 1076 43.0 1179 57.0 1282 72.034000 793 12.2 860 18.4 924 24.9 989 32.0 1048 38.8 1104 46.1 1205 60.8 1301 76.2 1399 92.336000 831 13.7 896 20.3 957 27.1 1017 34.2 1075 41.5 1131 49.1 1230 64.2 1319 79.7 1413 97.0

38000 869 15.3 933 22.3 991 29.4 1049 36.9 1104 44.4 1159 52.4 1256 68.1 1348 85.0 1431 10240000 908 17.2 970 24.4 1026 31.9 1080 39.5 1134 47.5 1186 55.6 1285 72.5 1375 89.9 1452 10644000 985 21.2 1045 29.2 1096 37.1 1146 45.4 1195 53.8 1246 62.9 1340 80.9 1427 99.448000 1063 25.9 1121 34.5 1170 43.3 1215 52.0 1262 61.3 1308 70.8 1398 90.1 1483 110

SIZE493Max. safe speedsClass I=0850 RPMClass II=1105 RPMClass III=1395 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

37500 667 12.3 733 19.3 797 26.7 857 34.3 914 42.4 965 50.3 1061 67.1 1162 85.340000 703 13.9 766 21.3 826 29.2 884 37.1 940 45.7 990 54.0 1081 71.0 1170 89.342500 739 15.8 798 23.5 856 31.7 912 40.1 965 48.8 1017 58.0 1105 75.7 1189 94.4 1277 11545000 774 17.7 832 25.8 887 34.5 940 43.3 991 52.2 1042 61.9 1132 81.0 1214 101 1291 121

47500 810 19.9 866 28.4 918 37.3 969 46.5 1018 55.9 1066 65.5 1158 86.0 1238 106 1313 12750000 846 22.2 902 31.3 951 40.4 998 49.9 1047 59.8 1094 70.1 1182 90.9 1260 112 1334 13355000 919 27.6 972 37.3 1018 47.5 1062 57.6 1105 68.2 1150 79.4 1234 102 1314 125 1385 14860000 992 33.7 1043 44.5 1087 55.4 1129 66.5 1168 77.7 1208 89.3 1288 113 1363 138

SIZE543Max. safe speedsClass I=0750 RPMClass II=0975 RPMClass III=1230 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

46000 604 15.2 662 23.7 720 32.7 774 42.1 827 52.1 873 62.0 958 82.1 1050 10549000 635 17.1 691 26.2 745 35.5 798 45.4 849 56.0 895 66.3 978 87.4 1059 11052000 666 19.3 720 28.7 771 38.6 822 48.9 870 59.6 918 71.0 999 93.0 1075 116 1152 14055000 698 21.6 750 31.6 800 42.1 847 52.6 895 64.1 939 75.5 1022 99.1 1094 122 1164 147

58000 729 24.1 781 34.6 827 45.5 872 56.6 919 68.4 963 80.4 1044 105 1114 129 1183 15561000 761 27.0 811 37.9 856 49.2 899 60.9 944 73.1 985 85.1 1065 111 1137 137 1205 16464000 793 30.0 842 41.5 885 53.2 928 65.5 970 78.2 1009 90.3 1088 117 1159 144 1226 17270000 858 36.9 905 49.3 945 61.9 984 74.9 1022 88.3 1061 102 1135 130 1204 159

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

Page 10: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 10

ACOUSTAFOILPERFORMANCE FOR PLENUM FANS WITH WHEELS

ACOUSTAFOIL-QPERFORMANCE FOR PLENUM FANS WITH WHEELS

SIZE603Max. safe speedsClass I=0675 RPMClass II=0880 RPMClass III=1110 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

52000 513 16.0 570 25.8 625 36.1 677 47.2 724 58.4 765 69.3 851 93.656000 543 18.3 597 28.7 650 39.9 700 51.5 746 63.3 788 75.5 866 100 947 12760000 574 21.0 625 32.0 675 43.8 723 56.0 768 68.6 810 81.3 883 107 957 13564000 605 23.9 654 35.6 700 47.7 747 60.7 789 73.5 830 86.8 904 114 974 143 1044 173

68000 637 27.1 683 39.3 728 52.3 771 65.6 813 79.4 854 93.6 927 122 992 151 1056 18272000 668 30.6 714 43.5 755 56.9 796 70.7 836 85.0 876 100 948 130 1015 161 1074 19280000 731 38.5 775 53.0 813 67.4 850 82.6 887 98.1 922 114 993 147 1057 18088000 794 47.9 836 63.6 873 79.8 907 95.9 940 112 974 130 1039 165 1102 201

SIZE663Max. safe speedsClass I=0615 RPMClass II=0800 RPMClass III=1010 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

60000 450 17.8 504 29.1 556 41.4 603 53.9 646 67.0 686 80.465000 478 20.5 529 32.7 578 45.6 624 59.1 666 73.0 703 86.6 778 11670000 507 23.6 555 36.7 601 50.4 645 64.6 687 79.3 725 94.4 793 124 863 15775000 536 27.1 581 40.8 625 55.2 667 70.2 708 86.0 746 102 812 133 877 168 946 204

80000 565 30.8 609 45.3 650 60.7 689 76.1 730 93.1 765 109 833 143 893 177 953 21485000 595 35.0 637 50.5 676 66.4 714 82.9 751 99.7 788 118 854 153 913 189 968 22695000 654 44.7 694 61.9 729 78.9 763 96.8 798 116 831 135 896 174 956 215 1009 256105000 713 56.2 752 74.9 786 94.2 816 113 848 134 879 154 939 196 995 239

SIZE733Max. safe speedsClass I=555 RPMClass II=725 RPMClass III=915 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

82000 443 26.6 487 41.9 530 57.9 572 75.1 610 92.6 644 110 709 14694000 494 34.8 535 51.8 573 69.8 610 88.4 647 108 680 127 742 168 798 209 857 254100000 520 39.6 559 57.4 595 76.5 631 95.8 666 116 700 138 759 179 814 222 868 269112000 573 50.4 609 70.4 642 91.3 675 113 706 135 737 157 797 204 850 251 899 300

124000 625 63.4 661 85.6 691 108 721 131 750 156 778 180 835 231 887 282136000 678 78.6 712 103 742 128 768 152 795 178 822 205 873 257142000 705 87.2 738 113 767 138 793 164 819 190 844 217 895 274148000 732 96.6 764 123 793 149 818 176 843 204 867 231

SIZE183Max. safe speedsClass I=2305 RPMClass II=3005 RPMClass III=3790 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

5000 1883 2.11 2080 3.19 2241 4.29 2395 5.45 2548 6.69 2690 7.95 2944 10.55500 2029 2.56 2218 3.74 2375 4.94 2520 6.20 2662 7.52 2798 8.85 3050 11.66000 2177 3.09 2358 4.36 2512 5.66 2650 7.00 2778 8.35 2907 9.79 3151 12.7 3378 15.86500 2327 3.69 2501 5.07 2649 6.45 2784 7.89 2909 9.37 3028 10.9 3262 14.0 3483 17.2 3688 20.6

7000 2479 4.38 2644 5.86 2791 7.35 2919 8.85 3040 10.4 3151 12.0 3374 15.3 3584 18.67500 2632 5.15 2788 6.73 2930 8.31 3060 9.94 3173 11.5 3286 13.3 3490 16.6 3695 20.28000 2785 6.01 2934 7.69 3074 9.40 3197 11.1 3312 12.8 3421 14.6 3618 18.28500 2941 6.99 3082 8.75 3215 10.6 3340 12.4 3453 14.2 3554 16.0 3749 19.8

SIZE203Max. safe speedsClass I=2125 RPMClass II=2780 RPMClass III=3510 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

5500 1649 2.10 1822 3.23 1960 4.39 2089 5.59 2220 6.89 2340 8.16 2573 11.0 2816 14.16000 1763 2.49 1934 3.73 2071 5.00 2189 6.26 2307 7.58 2427 9.01 2649 11.9 2854 14.9 3075 18.36500 1878 2.94 2047 4.29 2181 5.64 2294 6.97 2405 8.39 2516 9.87 2729 12.9 2922 16.0 3120 19.57000 1996 3.44 2158 4.89 2292 6.34 2404 7.78 2509 9.26 2612 10.8 2817 14.1 3009 17.4 3182 20.7

7500 2113 4.00 2270 5.55 2404 7.11 2515 8.64 2618 10.2 2715 11.9 2903 15.2 3093 18.7 3265 22.38000 2234 4.64 2384 6.29 2513 7.92 2628 9.59 2725 11.2 2820 12.9 2998 16.4 3174 20.0 3345 23.88500 2353 5.33 2495 7.06 2624 8.81 2737 10.6 2838 12.3 2932 14.2 3100 17.8 3266 21.5 3429 25.49500 2597 6.97 2728 8.90 2850 10.9 2963 12.9 3061 14.8 3152 16.8 3313 20.7 3464 24.8

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

Page 11: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 11

SIZE223Max. safe speedsClass I=1970 RPMClass II=2570 RPMClass III=3240 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

8000 1708 3.64 1858 5.28 1981 6.95 2087 8.66 2187 10.4 2281 12.1 2474 15.9 2649 19.7 2826 24.08500 1794 4.14 1942 5.90 2063 7.65 2167 9.44 2261 11.2 2354 13.1 2537 17.0 2712 21.1 2876 25.39000 1883 4.70 2024 6.54 2147 8.44 2249 10.3 2342 12.2 2430 14.1 2604 18.1 2773 22.3 2931 26.7

10000 2059 5.97 2191 8.00 2311 10.1 2411 12.1 2504 14.2 2584 16.3 2747 20.7 2902 25.2 3057 29.9

10500 2149 6.69 2276 8.82 2392 11.0 2496 13.2 2584 15.3 2668 17.6 2819 22.0 2971 26.7 3120 31.511000 2239 7.49 2363 9.74 2476 12.0 2578 14.3 2667 16.5 2751 18.9 2900 23.5 3043 28.3 3189 33.412000 2420 9.25 2535 11.7 2644 14.2 2743 16.6 2833 19.1 2916 21.6 3061 26.6 3194 31.713000 2602 11.3 2710 13.9 2813 16.6 2907 19.2 2999 22.0 3080 24.7 3226 30.1

SIZE243Max. safe speedsClass I=1790 RPMClass II=2335 RPMClass III=2940 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

10000 1522 4.70 1663 6.84 1778 9.00 1886 11.3 1991 13.7 2088 16.0 2279 21.2 2447 26.411000 1645 5.78 1779 8.12 1891 10.5 1995 13.0 2089 15.4 2184 18.0 2367 23.5 2532 29.0 2686 34.811500 1706 6.37 1837 8.81 1950 11.3 2048 13.8 2141 16.4 2234 19.1 2409 24.6 2576 30.5 2725 36.312000 1769 7.03 1896 9.56 2007 12.1 2107 14.8 2196 17.4 2284 20.2 2455 25.9 2619 31.9 2771 38.1

12500 1832 7.71 1955 10.4 2065 13.0 2161 15.7 2250 18.4 2337 21.3 2501 27.2 2666 33.5 2815 39.813000 1895 8.46 2014 11.2 2123 14.0 2219 16.7 2307 19.6 2389 22.5 2551 28.6 2708 34.9 2859 41.514000 2021 10.1 2135 13.0 2239 16.0 2335 19.0 2418 22.0 2499 25.1 2653 31.5 2799 38.115000 2149 11.9 2257 15.1 2356 18.2 2450 21.5 2534 24.7 2614 28.0 2761 34.8 2898 41.6

SIZE273Max. safe speedsClass I=1540 RPMClass II=2010 RPMClass III=2530 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

10000 1154 3.28 1292 5.28 1410 7.38 1517 9.54 1618 11.8 1709 14.1 1891 18.911000 1239 3.92 1371 6.09 1485 8.34 1589 10.7 1684 13.1 1776 15.7 1938 20.6 2113 26.212000 1326 4.62 1453 7.02 1561 9.40 1661 11.9 1753 14.5 1843 17.2 2004 22.7 2153 28.2 2311 34.312500 1371 5.04 1493 7.48 1601 9.99 1697 12.5 1789 15.2 1877 18.0 2036 23.6 2181 29.3 2328 35.4

13000 1416 5.46 1535 8.01 1641 10.6 1736 13.2 1827 16.0 1911 18.8 2072 24.8 2215 30.7 2352 36.714000 1505 6.38 1619 9.12 1724 11.9 1816 14.7 1902 17.6 1984 20.6 2137 26.8 2280 33.2 2411 39.615000 1597 7.44 1704 10.3 1804 13.3 1896 16.4 1978 19.3 2059 22.5 2208 29.0 2347 35.8 2474 42.516000 1688 8.60 1790 11.7 1886 14.8 1976 18.0 2055 21.2 2135 24.6 2277 31.3 2412 38.3

SIZE303Max. safe speedsClass I=1385 RPMClass II=1805 RPMClass III=2275 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

14000 1142 5.12 1259 7.90 1358 10.7 1450 13.7 1537 16.8 1617 19.9 1764 26.3 1911 33.115000 1206 5.87 1318 8.81 1418 11.9 1506 15.0 1588 18.2 1667 21.5 1810 28.2 1946 35.2 2084 42.716000 1271 6.69 1380 9.87 1475 13.0 1560 16.3 1641 19.6 1718 23.2 1863 30.5 1990 37.7 2111 44.917000 1336 7.62 1440 11.0 1533 14.3 1618 17.8 1695 21.2 1771 25.0 1909 32.4 2037 40.2 2155 47.9

18000 1403 8.62 1502 12.1 1593 15.7 1675 19.3 1751 23.0 1823 26.7 1958 34.5 2083 42.6 2203 51.019000 1469 9.71 1564 13.4 1654 17.2 1733 20.9 1809 24.8 1876 28.6 2010 36.8 2132 45.2 2249 53.920000 1536 10.9 1627 14.8 1714 18.7 1793 22.7 1866 26.7 1933 30.7 2064 39.3 2185 48.122000 1672 13.7 1756 17.9 1836 22.2 1913 26.6 1982 30.9 2048 35.3 2174 44.5

SIZE333Max. safe speedsClass I=1265 RPMClass II=1650 RPMClass III=2080 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

17000 1036 5.96 1134 9.20 1219 12.6 1299 16.1 1376 19.8 1448 23.4 1585 31.1 1713 39.1 1844 47.718000 1085 6.66 1179 10.0 1261 13.6 1338 17.3 1412 21.0 1482 24.9 1616 32.8 1739 41.1 1859 49.819000 1134 7.45 1226 11.0 1305 14.6 1379 18.5 1452 22.5 1518 26.4 1649 34.7 1769 43.3 1885 52.320000 1184 8.28 1271 12.0 1351 15.8 1422 19.8 1491 23.9 1557 28.1 1686 36.8 1803 45.7 1911 54.6

21000 1234 9.19 1320 13.1 1395 17.0 1467 21.2 1533 25.5 1598 29.9 1721 38.9 1836 48.0 1946 57.622000 1283 10.2 1368 14.3 1441 18.3 1510 22.6 1576 27.2 1637 31.6 1759 41.1 1872 50.6 1980 60.523000 1334 11.2 1415 15.5 1489 19.8 1555 24.2 1618 28.8 1679 33.5 1796 43.2 1908 53.2 2013 63.325000 1435 13.6 1512 18.2 1582 22.9 1647 27.6 1707 32.5 1764 37.4 1872 47.5 1980 58.4

SIZE363Max. safe speedsClass I=1110 RPMClass II=1450 RPMClass III=1825 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

20000 939 7.58 1024 11.2 1097 14.9 1165 18.8 1234 22.9 1300 27.2 1425 36.1 1538 45.2 1671 55.722000 1015 9.24 1094 13.2 1166 17.3 1232 21.5 1294 25.9 1353 30.2 1474 39.7 1581 49.3 1685 59.423000 1054 10.2 1131 14.3 1201 18.5 1266 22.9 1325 27.3 1383 32.0 1498 41.6 1608 51.8 1704 61.824000 1093 11.2 1166 15.4 1236 19.9 1298 24.3 1357 29.0 1412 33.6 1526 43.7 1634 54.2 1733 65.0

25000 1133 12.3 1204 16.7 1271 21.3 1333 25.9 1389 30.6 1444 35.5 1553 45.8 1659 56.6 1756 67.526000 1173 13.5 1241 18.1 1307 22.8 1367 27.5 1423 32.4 1478 37.6 1579 47.8 1683 58.9 1783 70.628000 1252 16.1 1316 21.0 1378 25.9 1438 31.2 1492 36.3 1543 41.6 1640 52.5 1738 64.330000 1333 19.0 1393 24.2 1451 29.5 1507 34.9 1561 40.5 1610 46.0 1706 57.8 1795 69.7

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

ACOUSTAFOIL-QPERFORMANCE FOR PLENUM FANS WITH WHEELS

Page 12: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 12

SIZE403Max. safe speedsClass I=1005 RPMClass II=1315 RPMClass III=1655 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

26000 854 10.3 927 15.0 995 20.0 1060 25.3 1120 30.6 1178 36.2 1284 47.5 1381 59.2 1480 71.628000 908 12.1 978 17.2 1041 22.3 1104 27.9 1160 33.5 1217 39.5 1325 51.9 1415 63.8 1501 75.930000 963 14.0 1028 19.4 1090 25.0 1148 30.7 1205 36.7 1258 42.9 1360 55.7 1455 69.1 1539 82.032000 1019 16.3 1080 21.9 1139 27.8 1195 33.9 1249 40.2 1300 46.5 1400 60.1 1494 74.3 1575 87.6

34000 1075 18.8 1133 24.8 1189 31.0 1244 37.4 1295 43.9 1345 50.7 1438 64.4 1530 79.2 1613 93.836000 1132 21.6 1186 27.8 1240 34.4 1293 41.1 1342 47.9 1390 54.8 1482 69.4 1569 84.5 1650 99.738000 1188 24.6 1241 31.2 1292 38.1 1341 44.9 1390 52.3 1435 59.3 1524 74.3 1610 90.342000 1302 31.6 1351 38.9 1398 46.4 1444 54.1 1488 61.6 1531 69.5 1614 85.5

SIZE443Max. safe speedsClass I=0910 RPMClass II=1190 RPMClass III=1495 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

32000 777 12.8 842 18.6 904 24.7 961 31.0 1016 37.7 1069 44.6 1166 58.8 1251 72.8 1337 87.634000 817 14.5 879 20.6 939 27.2 995 33.8 1047 40.7 1097 47.7 1192 62.5 1279 77.7 1358 92.836000 858 16.5 917 22.9 974 29.6 1027 36.6 1077 43.6 1126 51.0 1220 66.6 1305 82.4 1382 98.138000 899 18.6 955 25.4 1009 32.3 1061 39.5 1111 47.0 1157 54.6 1250 71.0 1333 87.5 1413 105

40000 940 21.0 994 28.0 1046 35.3 1096 42.8 1144 50.6 1189 58.5 1278 75.3 1361 92.4 1438 11042000 982 23.6 1034 31.0 1084 38.6 1132 46.4 1180 54.6 1223 62.7 1309 80.0 1390 98.0 1466 11644000 1023 26.4 1073 34.1 1121 41.9 1169 50.1 1213 58.3 1256 66.9 1339 84.5 1419 103 1494 12248000 1107 32.6 1153 40.9 1198 49.6 1243 58.4 1284 67.0 1325 76.2 1404 95.2 1477 114

SIZE493Max. safe speedsClass I=0850 RPMClass II=1105 RPMClass III=1395 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

40000 723 16.5 782 23.8 837 31.4 888 39.2 936 47.3 984 56.1 1070 73.4 1147 90.9 1221 10944000 784 20.4 838 28.2 889 36.3 938 44.9 984 53.6 1026 62.4 1113 81.7 1191 101 1258 12046000 815 22.5 866 30.7 916 39.2 964 48.0 1007 56.9 1050 66.1 1133 85.7 1210 106 1279 12648000 846 24.9 895 33.3 943 42.1 989 51.1 1033 60.5 1076 70.3 1155 90.1 1231 111 1300 132

50000 877 27.4 925 36.2 972 45.3 1016 54.6 1058 64.0 1100 74.3 1177 94.5 1252 116 1323 13852000 908 30.0 955 39.2 1000 48.6 1042 58.1 1084 68.0 1124 78.3 1201 99.4 1272 121 1342 14456000 971 36.0 1015 45.8 1057 55.9 1097 66.0 1138 76.6 1176 87.4 1249 110 1317 132 1385 15760000 1034 42.8 1075 53.2 1115 63.8 1153 74.5 1191 85.8 1227 97.0 1298 121 1365 145

SIZE543Max. safe speedsClass I=0750 RPMClass II=0975 RPMClass III=1230 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

42000 576 14.7 636 22.5 690 30.8 742 39.7 789 48.6 835 58.1 915 76.6 998 96.746000 620 17.7 675 26.1 727 34.9 774 44.0 820 53.7 865 63.9 945 84.4 1015 104 1092 12750000 664 21.1 716 30.2 764 39.5 811 49.5 855 59.8 897 70.4 975 92.2 1045 114 1109 13654000 709 25.1 758 34.7 804 44.8 848 55.1 889 66.0 929 76.9 1005 100 1074 124 1139 148

58000 755 29.5 800 39.7 844 50.5 886 61.6 924 72.4 963 84.3 1037 109 1107 134 1170 16062000 800 34.4 843 45.4 885 56.6 925 68.4 963 80.1 999 92.0 1069 117 1137 145 1199 17166000 846 40.1 887 51.5 926 63.5 965 75.9 1002 88.3 1037 101 1104 127 1169 155 1230 18470000 893 46.3 931 58.5 969 71.1 1005 83.9 1040 96.8 1075 110 1138 137 1200 166

SIZE603Max. safe speedsClass I=0675 RPMClass II=0880 RPMClass III=1110 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

55000 550 20.7 602 30.8 648 41.3 692 52.4 734 64.2 776 76.6 847 101 911 12560000 591 24.8 639 35.7 683 47.0 726 59.0 764 70.9 802 83.7 874 110 939 137 997 16365000 632 29.5 677 41.2 719 53.4 759 65.8 797 78.9 833 92.2 903 121 967 149 1023 17770000 674 34.9 716 47.5 756 60.3 794 73.4 830 87.2 864 101 931 130 995 162 1050 192

75000 716 41.1 755 54.2 793 67.8 830 82.1 865 96.7 897 111 962 142 1022 174 1079 20780000 759 47.9 796 61.8 832 76.4 867 91.1 900 106 932 122 993 154 1053 188 1109 22385000 802 55.6 837 70.4 871 85.6 904 101 936 117 968 134 1025 166 1082 20190000 845 64.1 878 79.7 911 95.7 942 112 973 128 1003 146 1061 181

SIZE663Max. safe speedsClass I=0615 RPMClass II=0800 RPMClass III=1010 RPM

CFM1"SP

RPM BHP

2"SP

RPM BHP

3"SP

RPM BHP

4"SP

RPM BHP

5"SP

RPM BHP

6"SP

RPM BHP

8"SP

RPM BHP

10"SP

RPM BHP

12"SP

RPM BHP

60000 461 20.4 511 31.5 557 43.5 600 56.3 640 69.3 677 82.6 742 10965000 491 23.9 538 35.7 582 48.4 622 61.6 661 75.5 697 89.5 762 118 824 14870000 521 27.7 566 40.5 608 54.0 647 68.0 684 82.5 719 97.6 783 128 841 159 901 19275000 552 32.1 594 45.7 634 59.8 672 74.6 707 89.7 740 105 805 138 864 172 917 205

80000 583 37.2 623 51.5 661 66.1 697 81.6 730 97.2 763 114 828 149 883 183 937 22085000 615 42.6 652 57.7 689 73.4 724 89.5 756 106 787 123 849 159 906 197 956 23395000 678 55.4 712 72.0 746 89.5 778 107 809 125 838 143 895 182 948 222 1000 264105000 743 70.8 774 89.1 805 108 834 127 863 147 891 167 944 208 994 250

Performance shown is installation Type A: Free inlet, Free outlet. Power rating (BHP) does not include drive losses.Performance ratings do not include the effects of appurtenances in the airstream.

ACOUSTAFOIL-QPERFORMANCE FOR PLENUM FANS WITH WHEELS

Page 13: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 13

MATERIAL SPECIFICATIONS U.S. standard sheet gauge to 7 gauge.Dimensions in inches, weights in pounds. WR2 in lb.-ft2.

SHAFTS AND BEARINGS

Size

Arrangements 1, 3, and 3-PShaft

ClassI

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassI, II

ClassIII

ClassIII

ClassIII

ClassIII

ClassIII

ClassIII

ClassII

ClassIII

ClassIII

Arr. 4,Cl. II*

Arr. 4,Cl. II

Arr. 4,Cl. II*

Arr. 4,Cl. II

ClassII

ClassII

ClassIII

Class I Class II Class III ClassI, II

Class I Class IIDriveDriveDriveDriveDrive InletInletInletInletInlet

ShaftBearings BearingsArrangement 3-V

123133153163183203223243273303333363403443493543603663733

AAAAAAAAAAAAAAAAAAA

BBBAAAAAAAAAAAAAAAA

BBBAEFFFFFFFFFFFFFF

———AAAAABDDDDDDEEFF

———EFFFFFFFFFFFFFFF

———EEEEEEFFFFFFFFFG

———FFFFFFFFFFFFFFHH

———FFFFFFFF

*F**F**F**F**F**F**F**F*

———E

*E**E**E**E**E*

FFFFFFFF

*F**F*

AAAAAAAABBEEDDDDDFF

1111113⁄1617⁄1617⁄1617⁄16

17⁄16111⁄16111⁄16115⁄1623⁄16

211⁄16211⁄16211⁄16211⁄1637⁄16†

13⁄1613⁄1613⁄16113⁄1613⁄1617⁄1617⁄1617⁄16

17⁄16111⁄16111⁄16115⁄1623⁄16

211⁄16211⁄16211⁄16211⁄1637⁄16†

———

13⁄16

17⁄1617⁄1617⁄16111⁄16111⁄16

115⁄16115⁄1623⁄1623⁄1627⁄16

211⁄16215⁄16215⁄1637⁄1637⁄16

———

13⁄16

13⁄1613⁄1617⁄1617⁄1617⁄16

17⁄16111⁄16111⁄16115⁄1623⁄16

211⁄16211⁄16211⁄16211⁄1637⁄16†

WEIGHTS AND WR2

Size

AcoustaFoil bare fans AcoustaFoil-Q bare fansAcoustaFoil wheels AcoustaFoil-Q wheelsArr. 1, 3 Arr. 1, 3Arr. 3-P Arr. 3-PArr. 3-V Arr. 3-VArr. 4 Arr. 4Approx. weights Approx. weightsWR2 WR2

‡123‡‡133‡‡153‡

163183203223243273303333363403443493543603663733

677181

102135145174211249310380530620767

10141174141218142435

8101327323846627291

119159188259344409527819

1052

2338

111724385587

130219321523843

1252192637155873

————

121834405893

139236360577931

138621204114—

————

1726386492

150197374555836

1593247634415774—

————————————160234397689

1038——

———

101321295478

120172301441747

12382017294148087637

————138148178215254316388542643794

1049121814651902—

————166184209277316409463717827

10371396196022682947—

————210226258306354413492574665933

1213139016482100—

————

505967

105120157181272325414650809941

1273—

————169150174210278337396623664812

128016701960——

————354150667797

127171211286380453580907—

————190201230275327397472640744——————

————224243268360395497—————————

———127163181205273311403455705805

101513601917221528593448

———176207223254301349407484562642906

11781346159520132666

———

32475663

100115151173260302387614765888

11851460

707385

112166147170204273331388611642785

124516271906——

———155187198226270322391646628720——————

———185221240263355390491—————————

————————————081103145204258——

————————————094116162225284——

————————————112183312465716——

MATERIAL GAUGE

SizeClass I, II Class III

Inletpanel

Inletpanel

Bearingbar

Bearingbar

Sidepanel

Sidepanel

123133153163183203223243273303333363403443493543603663733

77777777777

1⁄41⁄41⁄41⁄41⁄41⁄41⁄41⁄4

———1⁄41⁄41⁄41⁄41⁄41⁄41⁄41⁄43⁄83⁄83⁄83⁄83⁄83⁄83⁄83⁄8

———1⁄41⁄41⁄41⁄41⁄41⁄41⁄41⁄43⁄83⁄83⁄83⁄83⁄83⁄83⁄83⁄8

77777777777

1⁄41⁄41⁄41⁄41⁄41⁄41⁄41⁄4

———77777777

1⁄41⁄41⁄41⁄43⁄83⁄83⁄83⁄8

———77777777

1⁄41⁄41⁄41⁄43⁄83⁄83⁄83⁄8

A-Link-Belt P3-U200, B-Sealmaster SPM, D-Sealmaster MPD, E-Link-Belt P-300, F-Link-Belt P-B22400, G-Link-Belt P-B6800, H-Link-Belt P-B6900m.The right is reserved to substitute bearings of equal ratings. *Denotes expansion bearing. † Turned down to 211⁄16 at inlet bearing.

‡ Sizes 123, 133, and 153 wheels are aluminum only. * Arrangement 4 fans, Sizes 4O3 to 603, use aluminum wheels as standard. Arrangement 4Class Ill wheel weights are: Size 493, 190 lbs.; Size 543, 244 lbs.; WR2’s are 433 lb.-ft.2 and 706 lb-ft.2 respectively.

MOTOR LIMITS

SizeArrangement 3-P Arrangement 3-V Arrangement 4

Max. motor frameClass I, II Class I, IIClass III

Max.C-NW

Max. motor fr. Max.C-NW

Motorframe limits

123133153163183203223243273303333363403443493543603663733

48-184T143T-184T143T-184T182T-215T182T-256T143T-184T143T-215T182T-215T182T-256T213T-286T254T-326T284T-365T324T-405T324T-405T

*324T-405T**324T-445T*

404T-449T——

———

213T215T215T254T284T324T326T326T326T326T——————

———

213T215T215T254T284T324T326T326T326T326T405T405T405T405T445T445T

———

151⁄2175⁄819203⁄8233⁄8251⁄228301⁄2327⁄8351⁄2391⁄4433⁄8463⁄4511⁄4551⁄4633⁄8

———

215T256T256T286T326T326T326T—————————

———

171⁄4183⁄8193⁄4211⁄8235⁄8251⁄4283⁄4311⁄4355⁄8381⁄4——————

* For Class III Arrangement 4 fans: Size 493, 405T-445T; Size 543, 404T-449T.

Page 14: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 14

DIMENSIONS Dimensions not to be used for construction unless certified. [All dimensions in inches]

ARRANGEMENT

3-PMotor location as viewed

from drive side; Sizes163-223 centered overwheel, Sizes 243-403mounted on the left.

ARRANGEMENT

4

*See page 13 for motor size limitations. **Use dimension G as a guide only, as motor length varies by manufacturer. Tolerance: ± 1⁄8”

The New York Blower Company has a policy of continual product improvementand reserves the right to change designs and specifications without notice.

SizeMotorframesizes*

A BC

Arr.4

Arr.3-P

G**Arr.4

HArr.4

Arr. 3-PK

Arr.4

Arr. 3-PP

Arr.4

SArr.4

VArr.4

Baseholes

TArr.4

Arr.4

Arr.3-P

Arr.3-P

RO

Cl. I, II Cl. I, II Cl. I, IICl. III Cl. III Cl. III123133153163183203223243273303333363403443493543603663733

17⁄817⁄835⁄845⁄811⁄835⁄843⁄843⁄811⁄833⁄463⁄841⁄241⁄241⁄261⁄261⁄251⁄261⁄251⁄2

233⁄4241⁄4247⁄828365⁄830313⁄8343⁄8431⁄247491⁄2543⁄4573⁄8601⁄8711⁄4743⁄4831⁄8783⁄4871⁄8

———

211⁄4223⁄8241⁄4261⁄8291⁄8311⁄4351⁄4373⁄4421⁄8451⁄4——————

———

221⁄4233⁄8251⁄4271⁄8295⁄8311⁄4343⁄4—————————

———3331⁄2441⁄2551⁄251⁄251⁄26——————

———4441⁄25555—————————

131⁄214145⁄8173⁄4187⁄8201⁄4215⁄8245⁄8261⁄4293⁄4321⁄4343⁄4373⁄8401⁄8431⁄4463⁄4463⁄4503⁄4503⁄4

———

181⁄4193⁄8203⁄4221⁄8245⁄8261⁄4293⁄4321⁄4365⁄8391⁄4——————

———

181⁄4193⁄8203⁄4221⁄8245⁄8261⁄4293⁄4—————————

———35⁄833⁄447⁄851⁄865⁄863⁄873⁄875⁄887⁄891⁄8——————

———

10111⁄212131⁄215161⁄2181⁄2201⁄2221⁄2241⁄2——————

44446444666

111⁄4111⁄4111⁄4141⁄2141⁄2141⁄2141⁄2141⁄2

113⁄4113⁄4113⁄4113⁄4191⁄4111⁄4113⁄4111⁄4193⁄4193⁄4203⁄4211⁄8221⁄223283⁄4301⁄2365⁄831375⁄8

9⁄169⁄169⁄169⁄16

9⁄169⁄169⁄163⁄43⁄43⁄43⁄47⁄87⁄87⁄87⁄8

1111

881⁄291⁄2

101⁄2113⁄4121⁄2133⁄4151⁄4163⁄4181⁄2201⁄2221⁄2241⁄2271⁄2293232351⁄2351⁄2

31⁄431⁄237⁄847⁄851⁄261⁄863⁄877⁄875⁄887⁄891⁄897⁄8

101⁄4111⁄2131⁄8137⁄8137⁄8157⁄8157⁄8

41⁄241⁄241⁄251⁄251⁄251⁄266789

1011111112121212

———23262730333640444852——————

18192123262730333640444852581⁄86268687575

18193⁄422243⁄826283⁄8311⁄4343⁄43640431⁄24852573⁄4635⁄8693⁄4693⁄47777

97⁄8107⁄812131⁄4141⁄8151⁄2171⁄41919211⁄4231⁄8251⁄2273⁄4303⁄4341⁄8371⁄2371⁄2413⁄8413⁄8

AllAllAllAllAllAllAllAllAllAllAllAllAllAllAll

324T-445T477T-449T404T-445T447T-449T

DIMENSIONS [INCHES]

C

A

B

H

OK

R R

T

T

93/4"

O

C

B

A

V

V

S

OH G

(MAX.)

P R R

O

T

T

Drive side view

Drive side view

Page 15: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

PAGE 15

DIMENSIONS Dimensions not to be used for construction unless certified. [All dimensions in inches]

ARRANGEMENTS

1, 3Sizes 123, 133, and

153 are Arrangement 1design with both bearingsmounted on the drive side.

ARRANGEMENT

3-VVERTICAL

MOUNTING

SizeA

Arr.1, 3

Arr.1, 3

Arr.1, 3

Arr.3-V

Arr.3-V

Arr.3-V

DArr.3-V

EArr.3-V Cl. I, II Cl. III

B C H K O P TArr. 1, 3 Arr. 3-V

Cl. I, IIClassI, II

ClassIII

ClassI, II

ClassIII

ClassI, II

ClassIII

Arr.1, 3

Arr.3-V

WArr.3-V

R Baseholes

123133153163183203223243273303333363403443493543603663733

123133153163

183203223243273

303333363403443

493543603663733

131⁄2147⁄8161⁄219

203⁄4221⁄2251⁄8275⁄8301⁄4

335⁄8367⁄841443⁄4493⁄4

543⁄4601⁄467731⁄2811⁄2

21⁄421⁄431⁄441⁄4

41⁄441⁄441⁄441⁄441⁄4

47⁄847⁄857⁄867⁄867⁄8

67⁄87779

1⁄41⁄4

11⁄411⁄4

11⁄411⁄411⁄411⁄411⁄4

7⁄87⁄87⁄8

17⁄817⁄8

17⁄8222*4*

———

161⁄817183⁄8201⁄8217⁄8213⁄4241⁄826281⁄4305⁄834373⁄8403⁄4445⁄8483⁄4535⁄8

———30315⁄83437403⁄8415⁄8455⁄8491⁄8535⁄8575⁄8641⁄4701⁄8761⁄4831⁄2911⁄8

100

———

285⁄8315⁄8325⁄8355⁄8385⁄8415⁄8455⁄8495⁄8535⁄8575⁄8645⁄8681⁄2741⁄2811⁄2871⁄2971⁄2

———67⁄867⁄867⁄867⁄867⁄867⁄867⁄867⁄867⁄867⁄87777761⁄2

201⁄221215⁄8203⁄4217⁄8233⁄4255⁄8291⁄8311⁄4351⁄4373⁄4421⁄8451⁄4483⁄4533⁄8571⁄4621⁄4663⁄4743⁄8

———

213⁄4227⁄8243⁄4265⁄8295⁄8311⁄4343⁄4381⁄4415⁄8451⁄4481⁄4533⁄8571⁄4613⁄4681⁄4753⁄8

———

21221⁄824257⁄8293⁄8311⁄2351⁄2381⁄2423⁄8451⁄2483⁄4533⁄8571⁄4621⁄4663⁄4743⁄8

3333331⁄2441⁄2551⁄251⁄261⁄2771⁄2881⁄2991⁄2

10

———

15157⁄817181⁄2201⁄4207⁄8227⁄8241⁄2267⁄8287⁄8321⁄835381⁄8413⁄4451⁄250

———4441⁄255556677881⁄281⁄2

1010

———

173⁄4187⁄8201⁄4215⁄8245⁄8261⁄4293⁄4321⁄4355⁄8381⁄4411⁄4453⁄8483⁄4531⁄4581⁄4653⁄8

———51⁄251⁄251⁄266789

1011111112121415

———83⁄877⁄883⁄897⁄893⁄8

107⁄8107⁄8127⁄8177⁄8177⁄8187⁄8203⁄4213⁄4251⁄4261⁄4311⁄4

———81⁄277⁄881⁄297⁄893⁄8

107⁄8107⁄8127⁄8177⁄8177⁄8187⁄8207⁄8217⁄8253⁄8261⁄232

131⁄214145⁄8173⁄4187⁄8201⁄4215⁄8245⁄8261⁄4293⁄4321⁄4355⁄8381⁄4411⁄4435⁄8483⁄4531⁄4571⁄4643⁄8

9⁄169⁄169⁄16

9⁄16

9⁄169⁄169⁄163⁄43⁄43⁄43⁄47⁄87⁄87⁄87⁄8

1111

881⁄291⁄2

101⁄2113⁄4121⁄2133⁄4151⁄4163⁄4181⁄2201⁄2221⁄2241⁄2271⁄22932351⁄2381⁄243

31⁄431⁄237⁄847⁄851⁄261⁄863⁄877⁄875⁄887⁄891⁄8

103⁄8105⁄8121⁄8141⁄4147⁄8171⁄8181⁄8203⁄4

41⁄241⁄241⁄251⁄251⁄251⁄266789

1011111112121314

18192123262730333640444852581⁄86268758191

18193⁄4221⁄8243⁄826283⁄8311⁄4343⁄43640431⁄24852573⁄4635⁄8693⁄477845⁄8931⁄2

97⁄8107⁄812131⁄4141⁄8151⁄2171⁄41919211⁄4231⁄8251⁄2273⁄4303⁄4341⁄8371⁄2413⁄8451⁄2503⁄8

DIMENSIONS [INCHES]

Tinted area shows Arrangement 1 fans. Tolerance: ± 1⁄8”

Size L (OD) Q U

OPTIONAL INLET COLLAR DIMENSIONS

L(O.D.)

Inlet

Inlet

QU

panel

cone

* Class III U Dimension: Size 663 = 1", Size 733 = 3"

O

C

A

B

H

K

T

T

RRP

ODrive side view

WWD

B

T

T

C

A

K

H

ECenter holes onlyon Sizes 363-733

Page 16: NYB Bulletin 221:NYB Bulletin 221 - Thermoandinathermoandina.com/pdf/TVC-DF-221.pdf · is radial with a 2 ft. x 2 ft. duct with no transition. Select size, RPM, and BHP of fan from

COMPLETE SELECTION OFAIR-MOVING EQUIPMENTThe New York Blower Company offers thousands of different types, models, andsizes of air-moving equipment. Contact your nyb representative for assistance inidentifying the best fan for your application.

Leading the industry forward since 1889

DUST/MATERIALHANDLING

Wide range of duty available with unique fan lines capable of handling light dust to heavymaterial. Typical applicationsinclude dust-collection and high-pressure process along with material-conveying.

ROOF VENTILATORSIncluding both hooded and upblast ventilators, propeller fans, and centrifugal roof exhausters. These units are ideal for industrial, commercial,and institutional applications.

PROCESS/FANCOMPONENTSPlug fans, plenum fans, wheels, inlet cones, and housings for a wide variety of OEM applications. Process/fan components are used in air-handling units, ovens, dryers, freezer tunnels, and filtration systems.

HEATINGPRODUCTSIndustrial-duty steam unit heaters with steam heating coils are availablefor facility heating andprocess-heat transfer.

AIR-HANDLING[CENTRIFUGAL]

Designed for clean to moderatelydirty gas streams. Commercial and industrial HVAC, process cooling, light material-conveying,heat removal, and dryer exhaustare just a few of the numeroussample applications

AIR-HANDLING[AXIAL]

For the ideal handling of cleanto moderately dirty airstreams.Commercial and industrial HVAC,drying and cooling systems, fumeextraction, and process-heatremoval are typical applications.

FIBERGLASSREINFORCED

PLASTIC [FRP]Choice of performance and duty forcorrosive gas streams. Applicationsinclude chemical process, wastewatertreatment, laboratory hood exhaust,and tank aeration.

CUSTOM PRODUCTSDesigned for unique applications. Variety of configurations, temperatures, flows, and pressures. Wide range of modifications and accessories are available to meet the most demanding specifications.