Asset: P.S./I.S. 113 - QUEENS, 78-23 87TH STREET, New York, 11385 Inspection Id Inspection Type Time In Last Edited SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09 PM Asset Data Question Answer Was the building fully accessible for inspection No Inspection Access Comment The following components are inaccessible: Interior/Locker Room/Cellar-Boys, Girls (Full of Storages) Principal(s) Information Principal Name Alejandro Megias Organization P.S./I.S. 113 - Queens Did you meet with this Principal? Yes Did this Principal provide feedback? Yes Summary of Principal's Feedback The Principal's comments are as follows: 1. The Building Management System (BMS) is not working to regulate the heating and cooling. 2. The Gymnasium flooring is damaged. Custodian Patrick Dorney Fireman Richard Balcerzak Building Square Footage 97000 Comments on the Area None Comments on the Stories (Floors) plus Basements 3+C+Attic+PH Comments on the Number of Classrooms 40 Comments on the Year Built 1928 Student Population 900 Staff Population 110 Weather Fair Facade Photo Corner of 87th Street and 79th Avenue-North View NYC Department of Education Architectural Inspection Building Condition Assessment Survey 2018 - 2019 Q113 PB/A&W Print Date: 6/21/2019 Page 1 of 34

Upload: others

Post on 21-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Asset: P.S./I.S. 113 - QUEENS, 78-23 87TH STREET, New York, 11385

Inspection Id Inspection Type Time In Last Edited

SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM

AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09 PM

Asset Data

Question Answer

Was the building fully accessible for inspection No

Inspection Access Comment The following components are inaccessible: Interior/LockerRoom/Cellar-Boys, Girls (Full of Storages)

Principal(s) Information

Principal Name Alejandro Megias

Organization P.S./I.S. 113 - Queens

Did you meet with this Principal? Yes

Did this Principal provide feedback? Yes

Summary of Principal's Feedback The Principal's comments are as follows:1. The Building Management System (BMS) is not working to regulatethe heating and cooling.2. The Gymnasium flooring is damaged.

Custodian Patrick Dorney

Fireman Richard Balcerzak

Building Square Footage 97000

Comments on the Area None

Comments on the Stories (Floors) plus Basements 3+C+Attic+PH

Comments on the Number of Classrooms 40

Comments on the Year Built 1928

Student Population 900

Staff Population 110

Weather Fair

Facade Photo

Corner of 87th Street and 79thAvenue-North View

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 1 of 34

Page 2: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Main Entrance Photo

Facade A - 87th Street

Roof Photo

Roof 6 - North View

Have any Systems/Major Building Components been upgraded? Yes

Systems: New Playground Installation

Year: 2015

Systems: Original Building: Partial Exterior Walls repointing, newRetaining Walls, Gutters and Leaders unclogged andRestoration, Coping repairs

Year: 2014

Systems: Foundation Wall Waterproofing at the Electric PanelRoom

Year: 2012

Systems: Original Building Exterior Door replacement,Assembly/Multipurpose Room upgrade, Exterior Wallrepointing, Foundation Wall repairs, Areaway Drainsconnected to Sewer System, New HC Toilet Accessoriesupgrading, Library renovation

Year: 2009

Systems: Original Building: Asphalt Shingle Roofing replacement(Roofs 1-5),

Year: 2002

Systems: Original Building Window Replacement

Year: 1996

Have there been any New Building Additions? Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 2 of 34

Page 3: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Comments on New Building Additions 2000+4500 SF; 2009+35,200 SF

Tandem Schools? No

Leased Space? No

Priority Condition

PriorityCondition ExistLast Year?

PriorityCategory

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Structural Engineer Required

StructuralCondition Type

ConditionDescription

ComponentAffected

LocationDescription

Person(s)Notified

Person(s) Title PhotoImage

No condition recorded

Accessibility

Accessibility Status Question Response

Is the primary or secondary entrance on an accessible route? Yes

Is the building a multi-story building? Yes

Are all floors of the building accessible through compliant means? Yes

Accessible classrooms exists on each floor? Yes

Boys and Girls or Unisex accessible toilets exist on at least every other floor? Yes

If the following spaces exist, are they ALL accessible? Art Room, Auditorium,Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs

Yes

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

FUNCTIONAL ACCESSIBILITY

Exterior Routes

Exterior Entrances & Exits Yes

Exterior H/C Lifts No No

Exterior Ramps and Railings Yes Yes

Interior Routes

Corridor and Lobby H/C Lifts No No

Interior Corridor Doors and Hardware Yes Yes

Interior Corridors and Lobbies Yes

Interior Elevators Yes Yes

Interior Lobby Doors and Hardware Yes

Interior Ramps Yes Yes

Rooms & Spaces

Art Rooms Room 107 Yes Yes

Auditorium No

Cafeteria Cellar Yes Yes No Yes

Classrooms Cellar, 1st-3rd Floors Yes Yes

Computer Rooms No

Gymnasium Cellar Yes Yes Yes Yes

Library Room 133 Yes Yes

Main Office Room 101 Yes Yes

Multi-purpose Room 2nd Floor Yes Yes Yes Yes

Nurse's Room Room 139 Yes Yes

Pool No

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 3 of 34

Page 4: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem

FireAlarmStrobe

Rooms & Spaces

Science Lab Room 201, 203 Yes Yes

Toilet Rooms (Boys) Cellar, 1st-2nd Floor Yes Yes

Toilet Rooms (Girls) Cellar, 1st-3rd Floors Yes Yes

Toilet Rooms (Staff) Cellar, 1st-3rd Floors Yes Yes

Building Template

Inspection

Question Response

Architectural

EXTERIOR Inspected

AREAWAY Inspected

InspectedInstance on AW1-AW12

Instance Condition 3 - Fair

Instance Quantity 12

Instance Quantity Uom EACH

Deficiency AREAWAY DRAINS: CLOGGED

Roof Plan reference

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 4 of 34

Page 5: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

AREAWAY

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

AW10

Violations No violations recorded.

AWNINGS AND CANOPIES Does not Exist

CHIMNEY Inspected

Material Type(s) Masonry

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

COPING Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CORNICE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOORS Inspected

DOORS AND FRAMES Inspected

Condition 3 - Fair

Deficiency METAL CLAD: DETERIORATED DOOR - MINORDETERIORATION

Roof Plan reference

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 5 of 34

Page 6: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Photo1

Facade B-Exit 5

Violations No violations recorded.

DOOR HARDWARE Inspected

Condition 3 - Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TRANSOM/SIDE LIGHT Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

EXTERIOR WALLS Inspected

Material Type(s) Masonry

Replacement Quantity 53,000

Replacement Uom S.F.

InspectedInstance on All Facades

Instance Condition 4 - Between Fair and Poor

Instance Quantity 53,000

Instance Quantity Uom S.F.

Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 6 of 34

Page 7: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1 No photo recorded

Violations No violations recorded.

Deficiency BRICK: MAJOR / THRU CRACKS

Roof Plan reference

Elevation

Deficiency Quantity 15

Quantity Uom S.F.

Potential Action REMOVE AND REBUILD

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 7 of 34

Page 8: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

EXTERIOR WALLS

Deficiency Photo1

Facade B

Violations No violations recorded.

Deficiency BRICK: MINOR CRACKS AND SPALLING

Roof Plan reference

Elevation

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action RESTITCH

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade F

Violations No violations recorded.

Deficiency BRICK: DETERIORATED MASONRY SILLS

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 8 of 34

Page 9: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

EXTERIOR WALLS

Roof Plan reference

Elevation

Deficiency Quantity 100

Quantity Uom L.F.

Potential Action REMOVE AND REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A

Violations No violations recorded.

Deficiency BRICK: EFFLORESCENCE

Roof Plan reference

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 9 of 34

Page 10: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

EXTERIOR WALLS

Elevation

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 1

Purpose of Action LEVEL 1

Deficiency Photo1

Facade H

Violations No violations recorded.

Deficiency BRICK: OPEN JOINTS

Roof Plan reference

Elevation

Deficiency Quantity 1,000

Quantity Uom S.F.

Potential Action REPOINT

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 10 of 34

Page 11: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

EXTERIOR WALLS

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D

Violations No violations recorded.

EXTERIOR SOFFITS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOADING DOCK Does not Exist

LOUVER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

PARAPETS Inspected

Material Type(s) Masonry, Concrete

Replacement Quantity 4,400

Replacement Uom C.F.

InspectedInstance on All Facades

Instance Condition 2 - Between Good and Fair

Instance Quantity 4,400

Instance Quantity Uom C.F.

Deficiency CONCRETE: MINOR CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 11 of 34

Page 12: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

PARAPETS

Deficiency Photo1

Roof 6 - Facade J

Violations No violations recorded.

PLAZA DECK Does not Exist

ROOF Inspected

Roofing Inspected

Replacement Quantity 43,000

Replacement Uom S.F.

ROOF HATCH/SMOKE HATCH Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF BARRIER Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

ROOF CAGE Does not Exist

ROOF FENCE Does not Exist

ROOFING Inspected

InspectedInstance on Single Ply, Mechanically Fastened Roof: Roof 5A

Instance Condition 3 - Fair

Instance Quantity 1,300

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2000

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Asphalt Shingle: Roofs 1-5

Instance Condition 3 - Fair

Instance Quantity 13,600

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2003

Source of Installation Custodial Staff

Deficiency ASPHALT SHINGLE: ROOFING: DAMAGED, WORN-OUT ORMISSING SHINGLES CURLING UP

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 12 of 34

Page 13: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Roof Plan reference

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Roof 1

Violations No violations recorded.

InspectedInstance on IRMA: Roofs 6-10

Instance Condition 3 - Fair

Instance Quantity 28,100

Instance Quantity Uom S.F.

Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?

No

Installation Year 2009

Source of Installation Custodial Staff

Deficiency IRMA: ROOFING: MAJOR ACTIVE ROOF LEAKS ININSTRUCTIONAL SPACE

Roof Plan reference

Deficiency Quantity 30

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 13 of 34

Page 14: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

ROOF

Roofing

ROOFING

Quantity Uom S.F.

Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 2

Deficiency Photo1

Exit 4 Vestibule

Violations No violations recorded.

ROOFING DRAINS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Specialties Inspected

BULKHEAD/PENTHOUSE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

CUPOLA/ SPIRES/ TOWERS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DORMER Does not Exist

DUNNAGE STEEL Does not Exist

SKYLIGHT/ROOF VENT Does not Exist

ROOF/GRAVITY TANK Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

BUILDING CHEEK/FLANK WALLS Inspected

Condition 3 - Fair

Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR

Roof Plan reference

Deficiency Quantity 10

Quantity Uom S.F.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 14 of 34

Page 15: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade D - Exit 6

Violations No violations recorded.

RAILINGS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

STAIRS/RAMPS Inspected

Condition 3 - Fair

Deficiency STONE: CRACKS, SPALLING

Roof Plan reference

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade F - Exit 8

Violations No violations recorded.

WINDOWS Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 15 of 34

Page 16: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

EXTERIOR

WINDOWS

Replacement Quantity 8,000

Replacement Uom S.F.

EXTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LINTELS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

WINDOWS Inspected

Material Type(s) Aluminum

InspectedInstance on Aluminum - Double Hung: 1928 Original Building

Instance Condition 3 - Fair

Instance Quantity 3,700

Instance Quantity Uom S.F.

Installation Year 1996

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Aluminum - Double Hung: 2000 Addition

Instance Condition 3 - Fair

Instance Quantity 400

Instance Quantity Uom S.F.

Installation Year 2000

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

InspectedInstance on Aluminum - Other: 2009 Addition

Instance Condition 2 - Between Good and Fair

Instance Quantity 3,900

Instance Quantity Uom S.F.

Installation Year 2009

Source of Installation Custodial Staff

Deficiency No deficiencies recorded

INTERIOR Inspected

POOLS Does not Exist

STRUCTURAL Inspected

COLUMNS/BEAMS/BEARING WALLS Inspected

Condition 4 - Between Fair and Poor

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED MASONRYFIREPROOFING

Deficiency Location/Instance Basement- Oil Tank Room

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 16 of 34

Page 17: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STRUCTURAL

COLUMNS/BEAMS/BEARING WALLS

Deficiency Photo1

Basement- Oil Tank Room

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Basement- Cellar Boiler Room, Mechanical Equipment Room, Attic at1928 Original Building

Deficiency Quantity 270

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

Deficiency Photo1

Basement - Boiler Room

Violations No violations recorded.

FLOOR STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED

Deficiency Location/Instance Basement- Boiler Room, B05 Storage

Deficiency Quantity 60

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 17 of 34

Page 18: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE Inspected

Deficiency Photo1

Boiler Room

Violations No violations recorded.

FOUNDATION WALLS Inspected

Material Type(s) Concrete

Condition 3 - Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance 1st Floor-Electrical Panel Room, Cellar Boiler Room

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

1st Floor-Electrical Panel Room

Violations No violations recorded.

Deficiency CONCRETE: WATER INFILTRATION IN ELECTRICAL PANELROOM

Deficiency Location/Instance Cellar Floor, 1st Floor - Electrical Panel Room

Deficiency Quantity 50

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

Urgency of Action PRIORITY 5

Purpose of Action LEVEL 6

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 18 of 34

Page 19: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STRUCTURAL

FOUNDATION WALLS Inspected

Deficiency Photo1

Cellar - Electrical Panel Room

Violations No violations recorded.

ROOF STRUCTURE Inspected

Condition 3 - Fair

Deficiency CONCRETE: CRACKED/SPALLED/REINFORCEMENTEXPOSED

Deficiency Location/Instance PH, Attic at 1928 Original Building

Deficiency Quantity 500

Quantity Uom S.F.

Potential Action REPAIR

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 5

Deficiency Photo1

PH

Violations No violations recorded.

Deficiency STEEL COLUMNS/BEAMS: DETERIORATED CONCRETEFIREPROOFING

Deficiency Location/Instance Attic

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 4

Purpose of Action LEVEL 5

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 19 of 34

Page 20: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STRUCTURAL

ROOF STRUCTURE Inspected

Deficiency Photo1

Attic

Violations No violations recorded.

VAULTS-BUNKERS Does not Exist

AUDITORIUM Does not Exist

CAFETERIA Inspected

InspectedInstance on Cellar

Ceiling

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on Cellar

Floor Finish

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on Cellar

Stage

Does not ExistInstance on Cellar

Walls

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Cellar

CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency ACOUSTIC TILES: DAMAGED/MISSING

Deficiency Location/Instance Room 203 Corridor near Room 203, 211

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 20 of 34

Page 21: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Ceiling

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 203

Violations No violations recorded.

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 335

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 335

Violations No violations recorded.

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

Deficiency Location/Instance Room 253, 254 Corridor near Room 139, 238B, 241, and others

Deficiency Quantity 300

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 21 of 34

Page 22: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Floor Finish

Deficiency Photo1

Corridor near Room 238B

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency GYPSUM BOARD: DETERIORATED

Deficiency Location/Instance Corridor near Room 201, 211

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Corridor near Room 201

Violations No violations recorded.

Specialties Does not Exist

GYMNASIUM Inspected

InspectedInstance on Cellar

Ceiling

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 22 of 34

Page 23: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

GYMNASIUM

Floor Finish

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Seating

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage

Does not ExistInstance on Cellar

Walls

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Window Curtains/Shades/Blinds

Does not ExistInstance on Cellar

INTERIOR DOOR HARDWARE Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

INTERIOR GUARDS Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

KITCHEN Inspected

InspectedInstance on Cellar

Ceiling

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Cellar

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIBRARY Inspected

InspectedInstance on Room 133

Built-in Furnishing

Does not ExistInstance on Room 133

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 23 of 34

Page 24: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

LIBRARY

Ceiling

InspectedInstance on Room 133

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on Room 133

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish

InspectedInstance on Room 133

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on Room 133

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LOCKER ROOM Inspected

InaccessibleInstance on Cellar - Boys (162 lockers)

InaccessibleInstance on Cellar - Girls

MULTI-PURPOSE ROOM Inspected

InspectedInstance on 2nd Floor

Ceiling

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s)

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Fixed Equipment

Does not ExistInstance on 2nd Floor

Floor Finish

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Sliding-folding Partition

Does not ExistInstance on 2nd Floor

Stage

InspectedInstance on 2nd Floor

Stage Inspected

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtain Rigging Inspected

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stage Curtains Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 24 of 34

Page 25: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Stage

Stage Curtains

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency SALT GLAZED BRICK: CRACKS/SPALLING

Deficiency Location/Instance Near Entrance

Deficiency Quantity 30

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Near Entrance

Violations No violations recorded.

Window Curtains/Shades/Blinds

InspectedInstance on 2nd Floor

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SCIENCE DEMO ROOM Does not Exist

SCIENCE LAB Inspected

InspectedInstance on Room 201, 203

Alternative use No

Fixed Equipment

InspectedInstance on Room 201, 203

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SCIENCE PREP ROOM Inspected

InspectedInstance on Room 201A, 203A

Alternative use No

Fixed Equipment

InspectedInstance on Room 201A, 203A

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SHOWER ROOM Does not Exist

STAIRS/RAMPS: INTERIOR Inspected

Do Letter Stair Signs Exist? Yes

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 25 of 34

Page 26: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 4 - Between Fair and Poor

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Stair E/1 (Exit Vestibule 5)

Deficiency Quantity 2

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair E/1 (Exit Vestibule 5)

Violations No violations recorded.

Partition Does not Exist

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs and Landings Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: BROKEN/MISSING

Deficiency Location/Instance Exit Vestibule 8, 9

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit Vestibule 8

Violations No violations recorded.

Deficiency VINYL TILES: DETERIORATED SUBSTRATE

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 26 of 34

Page 27: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

Deficiency Location/Instance Stair D/1

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Stair D/1

Violations No violations recorded.

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

TOILET ROOMS - STAFF Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Floor Finish Inspected

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 238

Deficiency Quantity 10

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 238

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 27 of 34

Page 28: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

TOILET ROOMS - STAFF

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency STONE: CRACKS/SPALLING

Deficiency Location/Instance Room 238

Deficiency Quantity 20

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 238

Violations No violations recorded.

TOILET ROOMS - STUDENTS Inspected

Ceiling Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Door(s) Inspected

Condition 3 - Fair

Deficiency WOOD: DETERIORATED DOOR

Deficiency Location/Instance Room 214C

Deficiency Quantity 1

Quantity Uom EACH

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 214C

Violations No violations recorded.

Floor Finish Inspected

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 28 of 34

Page 29: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

INTERIOR

TOILET ROOMS - STUDENTS

Floor Finish

Condition 2 - Between Good and Fair

Deficiency CERAMIC TILE: BROKEN/MISSING TILES

Deficiency Location/Instance Room 140

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Room 140

Violations No violations recorded.

Stalls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

LIFE SAFETY Inspected

F.D. HOLDING AREA Does not Exist

STEEL STAIRS Inspected

Condition 3 - Fair

Deficiency MINOR RUSTING

Deficiency Location/Instance Facade A - Entry 10

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action MAINTENANCE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Facade A - Entry 10

Violations No violations recorded.

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 29 of 34

Page 30: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

SITE Inspected

CONTAINERIZATION Does not Exist

Drainage System for Asphalt Inspected

Catch Basins/Manhole - Surrounded by asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Asphalt Covering Does not Exist

Drainage System for Concrete Inspected

Catch Basins/Manhole - Surrounded by concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Concrete Covering Does not Exist

Drainage System for Soil Inspected

Catch Basins/Manhole - Surrounded by Soil Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Culverts - Soil Covering Does not Exist

DRINKING FOUNTAINS Does not Exist

FENCES Inspected

Condition 3 - Fair

Deficiency CONCRETE CURB: DAMAGED/DETERIORATED

Deficiency Location/Instance 87th Street, 79th Avenue

Deficiency Quantity 40

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

87th Street

Violations No violations recorded.

Deficiency WROUGHT IRON: DAMAGED/DETERIORATED

Deficiency Location/Instance 79th Avenue

Deficiency Quantity 80

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 30 of 34

Page 31: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

SITE

FENCES

Deficiency Photo1

79th Avenue

Violations No violations recorded.

IRRIGATION SYSTEM Does not Exist

PAVING Inspected

Student Non-Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

Student Use Inspected

Gravel Exists? No

Asphalt Inspected

Condition 3 - Fair

Deficiency CRACKS - MAJOR

Deficiency Location/Instance Schoolyard

Deficiency Quantity 100

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Schoolyard

Violations No violations recorded.

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavers Does not Exist

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 31 of 34

Page 32: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

SITE

PAVING

Site Sidewalks & Walkways Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 2 - Between Good and Fair

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance Exit to 87th Street

Deficiency Quantity 25

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

Exit to 87th Street

Violations No violations recorded.

Pavers Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

DOT Sidewalk Inspected

Asphalt Does not Exist

Concrete Inspected

Condition 3 - Fair

Deficiency DAMAGED CURBS

Deficiency Location/Instance 87th Street

Deficiency Quantity 40

Quantity Uom L.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

87th Street

Violations No violations recorded.

Deficiency HEAVING

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 32 of 34

Page 33: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

Deficiency Location/Instance 79th Avenue, 88th Street

Deficiency Quantity 125

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

88th Street

Violations No violations recorded.

Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS

Deficiency Location/Instance 78th Avenue, 79th Avenue , 88th Street

Deficiency Quantity 225

Quantity Uom S.F.

Potential Action REPLACE

Urgency of Action PRIORITY 3

Purpose of Action LEVEL 2

Deficiency Photo1

78th Avenue

Violations No violations recorded.

Pavers Does not Exist

PLAYGROUNDS Inspected

InspectedInstance on Schoolyard

Benches

Does not ExistInstance on Schoolyard

Fence

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Pavement

InspectedInstance on Schoolyard

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 33 of 34

Page 34: NYC Department of Education - NYCSCA · SA : Q113 Architectural - Senior 2018-11-21 8:40 AM 2019-06-05 5:17 PM AA : Q113 Architectural - Associate 2018-11-21 8:51 AM 2018-11-29 3:09

Question Response

SITE

PLAYGROUNDS

Pavement

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Play Equipment

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Safety Surfacing

InspectedInstance on Schoolyard

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Unpaved Area

Does not ExistInstance on Schoolyard

PLAYING SURFACE Does not Exist

RETAINING WALLS Inspected

Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?

No

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

SEATING Inspected

Benches Inspected

Concrete Does not Exist

Metal/Wood/Plastic Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Bleachers Does not Exist

SITE WALLS (NOT RETAINING WALLS) Does not Exist

STAIRS/RAMPS: EXTERIOR Inspected

Railings Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Site Cheek/flank Walls Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

Stairs/ramps Inspected

Condition 2 - Between Good and Fair

Deficiency No deficiencies recorded

NYC Department of Education

Architectural Inspection

Building Condition Assessment Survey 2018 - 2019

Q113

PB/A&W Print Date: 6/21/2019Page 34 of 34