Oak Court 19 Green Lane
Northwood HA6 2UU
Instruction
We are instructed by David Charles Property Consultants to conduct a 5 year periodic inspection to
the landlords’ electrical installations at: Oak Court, HA6 2UU. We attended site on 25th July 2013 to
carry out our testing and inspections to current regulations BS7671 – 17th edition.
Property
Oak Court is a blocks of private flats over 3 floors (G+2) with a garage block to the rear built about
40 yrs ago. All flats are accessed via a common entrance with stairs to the upper levels. The
electrical intake position and landlords services are located in a cupboard under the stairs.
Page 2 of 4
Scope
Within the current requirements of BS7671- 17th edition and amendment No. 1 dated January 2012,
it is now a requirement to conduct a fuller range of inspections that require the shutdown of power
to all parts of the property being tested. In this instance there is a single service head with the
Landlords’ services separately fused from a bus-bar arrangement, all flats have a direct supply from
the bus chamber, therefore a full inspection was possible without interruption to the private flats.
Installation
There is a single service head for the whole property with direct supplies from the intake to each
flat, metering is within each flat. The landlords’ service is supplied via separate cut-outs from the bus
chamber with all metering and equipment under the stairs. The landlords’ arrangement is very dated
and has only 2 circuits, power & lighting. Lights are controlled via a time-clock and time lag switching
with outside lighting controlled via photocell.
Limitations
None
Page 3 of 4
Results
Oak Court is considered as one installation being supplied from separate cut-outs from the service
head. This report should be read in conjunction with certificate no. GM/250713/02.
The installation is about 40yrs old and generally installed to a good standard at the time, however
there have been numerous additions to a lower standard and now overall is in a poor state. Repairs
and upgrades now required to attain even the minimum requirements.
Overall the installation is considered UNSATISFACTORY with the following urgent repairs required
(C1), general repairs (C2) required and recommendations (C3) advised to upgrade to current
standards BS7671 – 17th edition:
Code
1. Live casing at isolator at intake C1 2. No earth at sockets C1 3. Unknown wiring configuration to front floodlight. C2 4. Upgrade burnt out fuse ways C2 5. Provide labelling to 17th edition C3 6. Fix loose cabling at intake position C3 7. Improve earthing to floodlights C3 8. Rear light not operational C3 9. Loose cabling at rear to floodlight C3
Page 4 of 4
Conclusion
A dated installation now requiring some upgrade works to bring the installations up to an acceptable
standard with recommendation made to achieve the current standard BS7671 – 17th edition.
For S & M Electrical Ltd. 25th July 2013.
Code Key
C1 Danger present
C2 Potentially dangerous
C3 Improvements recommended
GM/ 250713 /02 1 of 5
Section A : DETAILS OF CLIENT/PERSON ORDERING REPORT
Name
Address
Section B : REASON FOR PRODUCING THIS REPORT
Dates of inspection and testing : July 2013
Section C : DETAILS OF THE INSTALLATION WHICH IS THE SUBJECT OF THIS REPORT
Occupier
Address
Description of premises if other
Estimated age of wiring 40+ years
Evidence of additions/alterations <5 years
Installation records available (621.1) Date of last inspection
Section D : EXTENT AND LIMITATIONS OF INSPECTION AND TESTING
Extent of electrical installation covered by this report
Agreed limitations including reasons (634.2)
Agreed with N/A
Operational limitations including reasons
Section E : SUMMARY OF THE CONDITION OF THE INSTALLATION
General condition of the installation (in terms of electrical safety)
Overall assessment of the installation in terms of its suitability for continued use
Section F : RECOMMENDATIONS
Section G : DECLARATION
Inspected and tested by: Report authorised for issue by
Name Name S.FREEMAN
Position Position DIRECTOR
Date Date
Section H : Schedule(s)1 1
and this report is valid only when they are attached to it.
It should be noted that cables concealed within trunking and conduits, under floors, in roof spaces and generally within the fabric of the building or underground have NOT
INSPECTOR
S & M ELECTRICAL LTD. JUBLIEE HOUSE, STANMORE, HA7 4RY
An unsatisfactory assessment indicated that dangerous (code C1) and/or potentially dangerous (code C2) conditions have been identified
required to attain minimum requirements.
25/07/2013 26/07/2013
if yes, age
schedule(s) of inspections schedule(s) of test results are attached. The attached schedule(s) are part of this document
Subject to the necessary remedial action being taken , I recommend that the installation is further inspected and tested by: 24/07/2018
Landlords installation for common parts as detailed
been inspected unless specifically agreed between the client and inspector prior to inspection
N/A
Oak Court, 19 Green Lane, NORTHWOOD, Middx., HA6 2UU
N/A
240610
29 High Steet, PINNER, HA5 5PJ
Where the overall assessment of the suitability of the installation for continued use above is stated as UNSATISFACTORY, I recommend that any
observations classed as "Danger present" (code C1) or "Potentially dangerous" (code C2) are acted upon as a matter of urgency. Investigations without
delay is recommended for observations identified as "Further investigations required". Observations classified as "Improvements recommended"
(code C3) should be given due consideration .
The inspection and testing detailed in this report and accompanying schedules have been carried out in accordence with BS7671:2008 (IET wiring regs) 17th /1
ELECTRICAL INSTALLATION CONDITION REPORT ECA
in the schedule of test results.
Domestic
None
25th
N/A
Member Number
5 year periodic test and inspection report (PIR)
YES
Certificate number
G.MARSHALL
I being the person responsible for the inspection and testing of the electrical installation (as indicated by my signature below), particulars of which
are described above, having excerised reasonable skill and care when carrying out the inspection and testing, hereby declare that the information
in this report, including the observations and the attached schedules, provides an accurate assessment of the condition of the electrical installation
taking into account the stated extent and limitations in Section D of this report.
UNSATISFACTORY. Repairs and upgrades
Sheet
Landlord
David Charles Property Consultants
UNSATISFACTORY
NO
ELECTRICAL INSTALLATION CONDITION REPORT
Sheet 2 of 5
Section I : SUPPLY CHARACTERISTICS AND EARTHING ARRANGEMENTS
TN-C a.c. x d.c. Nominal voltage U/Uo 415 V BS(EN)
TN-S 1 phase, 2 wire 2 wire Nominal frequency, f 50 Hz
TN-C-S X 2 phase, 3 wire 3 wire Prospective fault current, Ipf 4.00 kA Type
TT 3 phase, 3 wire External loop impedence, Ze 0.06 Oh
IT 3 phase, 4 wire x Rated 100 A
Confirmation of polarity x Note: By enquiry or measurement
Other sources of supply (as detailed on attached schedule
Section J: PARTICULARS OF INSTALLATION REFFERED TO IN REPORT
Distributors facility x Type
Location
Resistance to earth Ohms
Main Protective conductors
Earthing conductor Material Csa 35 mm2 Connection verified X
Main protective bonding conductors Material Csa x mm2 Connection verified
To incoming water service To incoming gas supply To incoming oil service To structural steel
To lightning protection To other incoming services Specify:
Main switch/Switch fuse/ circuit breaker/RCD If RCD main switch
Location Current rating A Rated operating current Idn N/A mA
BS(EN) Fuse /device rating A Rated time delay N/A ms
No. poles Voltage rating V Measured operating time (at Idn) N/A ms
Section K : OBSERVATIONS
x
C1 Danger present, Risk of injury, Immediate action required.
C2 Potentially dangerous, Urgent remedial action required
C3 Improvement recommended
One of the following codes, as appropriate, has been allocated to each of the observations made to indicate to the
person responsible for the installation the degree of urgency for remedial action required.
No
Yes
Yes
Yes
Further investigations
required
Exposed live parts at intake
Repairs required as detailed within report
C1
C2
C2
C3
ObservationsClassification
code
Poor earthing throughout installation
Recommendations detailed within report
Referring to the attached schedules of inspection and test results, and subject to the limitations specified in the Extent and
Limitations of inspection and testing section
Copper
x
Intake cupboard
Lim
1 240
Details of earth electrode (where applicable)
Installation earth
electrode
N/A
88
HRC
ECA
No remedial action is required The following observations are made
Earthing arrangements Number and type of live conductors Nature and type of supply parameters
15
15
Supply protective device
Means of earthing
Sheet 3 of 5
Note: This form is suitable for many types of smaller installations not exclusively domestic
a C1 or C2 C3 Not verified NV Limitation Lim Not applicable N/A
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.0
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
4.0
4.1
4.2
4.3
4.4
4.5
4.6
4.7
4.8
4.9
4.10
4.11
4.12
4.13
4.14
4.15
4.16
4.17
4.18
4.19
Presence and condition of distributors earthing arrangement (542.1.2.3; 542.1.2.2)
Presence and condition of earth electrode where applicable (542.1.2.3)
RCDs provided for fault protection - including RCBO's (411.4.9;411.5.2;431.2)
RCDs provided for additional protection - including RCBO's (411.3.3;415.1)
Presence of alternative supply warning notice at or near the consumer unit/distribution board
(514.15)
Presence of other required labelling (please specify) (Section 514)
Condition of service head
Condition of tails -distributor
Condition of tails -consumer
Condition of metering equipment
Condition of isolator (where present)
Accessibility and condition of earthing conductor at MET (543.3.2)
PRESENCE OF ADEQUATE ARRANGEMENTS FOR SECONDARY OR ALTERNATE SOURCES SUCH
AS MICROGENERATION (551.6;551.7)
EARTHING/BONDING ARRANGEMENTS (411.3; chap 54)
Provision of earthing/bonding labels at all appropriate locations (514.13.1)
Confirmation of earthing conductor size (542.3; 543.1.1)
Protection against mechanical damage where cables enter consumer unit/distribution board
(522.8.1;522.8.11)
Protection against electromagnetic effects where cables enter consumer unit/distribution
board / enclosures (521.5.1)
Presence of main linked switch (as required by 537.1.4)
Operation of main switch (functional check) (612.13.2)
Manual operation of circuit breakers and RCD's to prove disconnection (612.13.2)
Correct identification of circuit details and protective devices (514.8.1;514.9.1)
Presence of RCD quarterly test notice present at or near consumer unit/distribution board
(514.12.2)Presence of non-standard (mixed) cable colour warning notice at or near the consumer
unit/distribution board (514.14)
Confirmation of main protective bonding conductor size (544.1)
Condition and accessibility of main protective bonding conductor connections (543.3.2;
544.1.2)Accessibility and condition of all protective bonding connections (543.3.2)
CONSUMER UNITS/DISTRIBUTION BOARDS
Adequacy of working space/accessibilty to consumer unit/ distribution board (132.12;513.1)
Security of fixings (134.1.1)
Condition of enclosure in terms of IP rating etc (416.2)
Condition of enclosure in terms of fire rating etc (526.5)
Enclosure not damaged/deteriorated so as to impair safty (621.2 iii)
N/A
N/A
C2 NoExamination of protective device(s) and base(s) ; correct type and rating (no signs of
unacceptable thermal damage, arcing or overheating ) (421.1.3)
Single pole protective devices in line conductor only (132.14.1;530.3.2)
C2 No
C2 No
N/A
C3 Yes
a
N/A
C3 No
N/A
a
a
N/A
C3 Yes
C3 Yes
C3 Yes
a
a
C3 Yes
N/A
N/A
C3 Yes
N/A
N/A
a
N/A
a
a
N/A
a
a
a
Description
DISTRIBUTORS/SUPPLY INTAKE EQUIPMENT
Service cable condition a
ECA
Unacceptable
conditionImprovement
recommended
Acceptable
condition
CONDITION REPORT INSPECTION SCHEDULE
OUTCOMES
Item No.Further
investigationsOutcome
Sheet 4 of 5
5.0
5.1
5.2
5.3
5.4
- to include the integrity of the conduit and trunking systems (metallic and plastic)
5.5
5.6
5.7
5.8
5.9
5.10
5.11
5.12
- For supply to mobile equipment not exceeding 32a rating for use outdoors (411.3.3)
- For cables concealed in walls or partitions (522.6.102;522.6.103)
5.13
5.14
5.15
5.16
5.17
5.18
5.19
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
7.0 OTHER PART 7 SPECIAL INSTALLATIONS OR LOCATIONS
7.1
Name: Signature Date
No
Suitability of current-using equipment for a particular position within the location (701.55)
List all other special installations or locations present, if any (record seperately the results of
particular inspections applied).
MARSHALL
N/A
N/A
N/A
Tested by:
Item No. Description
25/07/2013
OutcomeFurther
investigations
C3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
C2 No
C2 No
a
a
a
a
25%
a
NV
NV
NV
N/A
N/A
C3 No
a
C2 No
C3 Yes
C1 Yes
a
a
a
C3 Yes
C3 No
Where used as a protective measure, requirements for SELV or PELV met (701.414.4.5)
Shaver sockets comply with BS EN 61558-2-5 formerly BS 3535 (701.512.3)
Suitability of equipment for external influences for installed location in terms of IP rating
(701.512.2)
Presence of supplimentry bonding conductors , unless not required by BS7671:2008
(701.415.2)
Low voltage (eg 230v) socket outlets sited at least 3m from zone 1 (701.512.3)
Suitability of equipment for installation in a particular zone (701.512.3)
- Connections of live conductors adequately enclosed (526.5)
- Adequately connected at point of entry to enclosure (glands, bushes etc) (522.8.5)
Condition of accessories including socket outlets, switches and joint boxes (621.2 iii)
Suitability of accessories for external influences (512.2)
LOCATIONS CONTAINING A BATH OR SHOWER
Additional protection for all low voltage (LV) circuits by RCD not exceeding 30mA (701.411.3.3)
Cables segregated / seperated from communication cabling (528.2)
Cables segregated / seperated from non electrical services (528.3)
-For all socket outlets of rating 20a or less provided for use by ordinary persons unless an
exception is permitted (411.3.3)
Termination of cables at enclosures - indicate extent of sampling in section D of the report
(section 526)
- Cables soundly made and under no undue strain (562.6)
- No basic insulation of a conductor visible outside enclosure (526.8)
Wiring system(s) appropriate for the type and nature of the installation and external influences
(section 522)
Concealed cables installed in prescribed zones (see Section D: Extent and limitations)
(522.6.101)Consealed cables incorporating earthed armour or sheath, or run within earthed wiring system,
or otherwise protected against mechanical damage from nails, screws and the like (see section
D: Extent and limitations) (522.6.101;522.6.103)
Provision of additional protection by RCD not exceeding 30mA
Provision of fire barriers, sealing arrangements and protection against thermal effects (section
527)
Band II cables segregated / seperated from band I cables (528.1)
Adequacy of cables for current-carrying capacity with regard for the type and nature of the
installation (Section 523)
Co-ordination between conductors and overload protective devices (433.1;533.2.1)
Adequacy of protective devices: type and rated current for fault protection (411.3)
Presence and adequacy of circuit protective conductors (411.3.1.1; Section 543.1)
FINAL CIRCUITS
Identification of conductors (514.3.1)
Cables correctly supported throughout their run (522.8.5)
Condition of insulation of live parts (416.1)
Non sheathed cables protected by enclosure in conduit, duct or trunking (521.10.1) a
Location
Name Marshall Type Ref No.
Date 25/07/13 Size mm2 ZS Ohms 9104044Title Tester Protection PFC ka
Earth Fault RCD
Trip Time
1 ka @1n
Ref Description Amps
Installed
Method
Live
mm2
CPC
mm2 Zs Ohns ms
1 Lighting in & out 15 X 1.5 1.0 1.89 x x x <5 <5 ok 2.16
2 Socket & door 15 X 2.5 1.5 0.08 x x x >50 >50 ok >2000
Comments
Sheet 5 of 5
ECA
Remarks
No earth
N-N
Ohm
E-E
Ohm
3036
3036
Installed Circuits Test Results
Other
Tests
CircuitsCopper
Ring Loop
ImpedanceR1
+R2
Ohm
P-P
Ohm
04/03/2013
88 4.00
Tester Details Sub- Main Dist Board UnderstairsTails 2 x Mem 20a Instrument Type Verified
S & M Electrical Ltd. Schedule of Test ResultsJubliee House, Stanmore, Middx.
Property : Oak Court, 19 Green Lane, NORTHWOOD, Middx., HA6 2UU
10 0.06 Fluke 1651
Type
Overcurrent device
short circuit capacity
Conductors Continuity
Insulation
Resistance
Po
larity
L-E
Moh
N-E
Moh