O&M Manual

By Pedrollo Distribution

A PACKAGED SOLUTION FOR BOOSTING WATER

Page 2: O&M Manual - Powertank

General 3

Installation Checklist 4

Location Consideration 5

Installation Diagrams 6

Electrical Installation 7

Commissioning 9

Water Quality 10

Pump Specification 10

Controller Specific Instruction & Troubleshooting 12

Declaration of Conformity 18

Directives and National Implementation Provisions 19

Powertank Range 20

Commissioning Checklist 22

Table of Contents

POWERTANK

2

Page 3: O&M Manual - Powertank

3

General

Delivery and Handling

The weight and size of the Powertank may require the aid of lifting equipment and must be handled in a safe manner.

Inspection

On delivery, the Powertank should be inspected thoroughly and any damage reported to the supplier as soon as possible. This should be confirmed in writing within 48 hours.

Applications

The Powertank is designed for domestic and light commercial pressure boosting.

The Powertank should not be installed in areas that are classified as hazardous or where there is a risk of an explosion or harm to people. The manufacturer does not accept responsibility if the Powertank is used to pump liquids other than clean water unless suitability has previously been agreed in writing.

Warranty

All mechanical components of the Powertank are covered by a 12 month warranty against manufacturing defects. In case of failure please contact the Technical Department on 01543 415200.

Site Storage

Should a Powertank need to be stored before installation it should be in a safe place away from moisture, dust and frost.

POWERTANK

3

Page 4: O&M Manual - Powertank

Installation Checklist1. Check the unit for any visual defects. Contact your supplier immediately if any are found.

2. Choose a suitable location for installation. Please ensure the unit is fitted and supported in accordance with these instructions.

• Check that the cold water storage tank capacity is designed to meet your water consumption demands.

• Tank Drip Trays or bunded tanks are to be used for Installations that would be sensitive to leakage.

3. Connect the inlet pipe work and overflow pipe work as per the installation diagram.

• Good quality full bore Isolation Valves should be fitted before and after the unit to allow for reliable service or repair.

• We strongly advise that a suitably designed bypass is installed to allow for servicing.

• Pipe work should be easy to disassemble. Consider the use of “Speedfit” or similar plastic pipework systems, or flexible hosing with a suitable pressure rating, for the last 1.0 mtr (approx.) of pipe work connecting to the unit. This will reduce noise transmission and accommodate movement of the unit, avoiding stressing the Powertank connections.

• Pipework installations should be in accordance with local water authority regulations.

• The Powertank COMPACT is designed to accept a 40mm overflow pipe. Other tanks should be fitted with overflows in accordance with local regulations. Ensure that overflow water is piped away properly.

4. Fill the storage tank with water through the fill valve before connecting the discharge pipe work to allow air to escape from the pump. Please ensure the fill valve fitted is suitable for the incoming water pressure.

5. Once the tank is full, connect the discharge pipe work as per the installation diagram.

• The discharge pipe work must be, at a minimum, the same size as the Powertank inlet supply; if it is smaller the result will be reduced pressure and flow at the outlets.

• The discharge pipe work must be properly secured so once the Powertank is fitted there are no stressed internal pipe work.

6. In accordance with the latest IEE regulation all electrical connections should be carried out by a qualified electrician .The Powertank must be earthed. It is recommended that an earth leakage circuit breaker (ELCB) is fitted on the incoming electrical supply.

• Make sure the electrical supply is fully isolated and cannot be turned on before working on the pump, motor, controller or any part of the unit.

• Do not turn on electrical supply to the Powertank without ensuring all electrical fittings and all covers are intact and fully isolated from human touch during operation.

4

POWERTANK

Page 5: O&M Manual - Powertank

Location Consideration

The Powertank is not recommended to be fitted above ceilings.

Installations in loft areas are not recommended due to the weight of the tank when full of water and the increased potential for damage in the event of water leakage or spillage. Sound also travels through rafters and it is likely that such an installation will be noisy compared to an installation on a solid base.

Installations significantly higher than the mains water stop tap will reduce the refill rate of the tank.

1. The Powertank should be installed in a dry, well-ventilated area where it is not exposed to extreme temperature or frost. An ambient temperate below 20 °C is required to limit bacteria growth. Powertanks may be located outdoors in a weather, frost and rodent proof enclosure which should be adequately ventilated during warm weather.

2. All pipe work that may be exposed to freezing condition should be fully protected.

3. Powertank must be positioned such that there is safe access for examination and service in compliance with health and safety practice.

4. Bunded tank options and drip trays are available for some of the Powertank range and these can be used in areas where water spillages or leakages can cause damage.

5. A litre of water weighs 1kg so a 200 litre tank will weigh 200kgs plus the weight of the tank, pumps etc. See our technical data sheet for the dry weights of each Powertank. Please check that your proposed installation site can support this level of load evenly.

6. There should ideally be adequate lighting in the location of the Powertank for ease of maintenance.

7. There should be sufficient space allowed above the tank to allow for correct installation of the pipe work and the removal of the pump from the tank for inspection and maintenance. We recommend the space allowed should be at least two-thirds the height of the tank.

Foundation & Mounting

Powertank must be mounted on a solid foundation to support the weight of the unit. Surfaces must be flat and level to spread weight load evenly. The recommended surface for a Powertank is a concrete plinth or floor. We do not recommend installation of Powertank units on wooden structures in any situation where noise or vibration may be an issue.

Storage Tank

Powertanks incorporate a cold water storage tank with a type AF Air gap as standard (AB Air gap for the Compact model) and when used with a mains connection must be installed in accordance with the water regulations. All the wetted parts of the Powertank are potable quality and suitable for use with drinking water. It should be noted that the quality of stored water deteriorates over time if ambient temperature is greater than 20 degrees Celsius (>20 °C). If the tank is to be left idle for any length of time, it is recommended that it is completely drained before being put back into use. It is recommended that tanks are drained and cleaned periodically, according to the conditions of use, to avoid any problems.

Slave Tank

Where additional water storage is required, a slave tank can be used to increase the capacity. It is important to maintain the “flow through” of all the water and to achieve this the incoming water supply should be delivered to the slave tank only. Please contact us for guidance on a particular installation.

5

POWERTANK

Page 6: O&M Manual - Powertank

Powertank Utility Installation DiagramCompact Domestic Installation Diagram

Installation Diagrams

InletOverflow

Water Supply

By-Pass LineWater Delivery

Typical example of installation

Water Supply

By-Pass LineWater Delivery

1

2

3

4

1. Tank drain off2. Overflow connection3. Integral overflow weir4. Fill valve

Typical example of installation

Selection of Drip Trays Available

Drip Tray for 200/300ltr tank Drip Tray for 500/750ltr Tank

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

603

R380

833

1

1

2

2

3

3

4

4

5

5

6

6

A A

B B

C C

D D

E E

F F

603

936

821

Pipework Installation

It is recommended to install a cold water mains bypass to allow an emergency water supply to the property to be maintained during service or failure. This allows the home owner to have a low pressure supply available while the unit is out of commission. The bypass must be installed in accordance with the water By-law regulations and should be drained to prevent water stagnation when not being used.

Location Consideration

Ø936

603

821

599

Ø760

Isolation ValveIsolation Valve

6

POWERTANK

Page 7: O&M Manual - Powertank

7

Electrical Installation

Powertanks supplied with a fitted plug may be used with a domestic 13A power socket. The plugs have a 13A fuse and, in the event of failure, should be replaced with the same value. Pumps supplied with only a power cable are designed for professional installation and should be connected by a suitably qualified electrician in accordance with the latest IEE regulations.

Ensure that the electrical supply is fully isolated before removing any electrical covers. The Powertank is fitted with a 3 core cable and the earth wire must be connected. It is recommended that an earth leakage circuit breaker (ELCB) is fitted on the incoming electrical supply.

Single phase Powertanks are suitable for voltage supply 230v +/- 10% with a suitable MCB or Fuse rated at a maximum of 13A. See below for the full load current of our different Powertank Pump options.

By-Pass LineWater Delivery

Manifold

Water Supply

1. Fill valve2. Overflow connection

Isolation Valve

2

Fill ValveOverflow

Tank Drain Off

Fill valve

Warning pipe

Overflow

1

Water Delivery

By-Pass Line

Water Supply

2

3

1. Fill valve2. Warning pipe3. Overflow connection

Isolation Valve

1

Pressure vesselPressure vessel

Drain off

Powertank Twin Pump Installation Diagram

Typical example of installation

Powertank Industrial Installation Diagram

Typical example of installation

POWERTANK

Page 8: O&M Manual - Powertank

8

Connect incoming power to RCD

Terminals 1 & 2 - Normally Closed alarm output

Terminals 3 & 4 - Level switch input, to be looped out if not required

Wiring Connections

The Powertank Industrial unit has provision for an external level switch input and a volt free general alarm output (BMS connection). Connections for these features are made within the main wiring box as per the diagrams below.

Powertank Model Full Load Current

Powertank Fixed Speed 3.4 Amps

Powertank Variable Speed (Compact Model) 5.2 Amps

Powertank Variable Speed 6.3 Amps

Powertank PLUS Variable Speed 9.3 Amps

Powertank TWIN Variable Speed 12.6 Amps

Powertank TRIPLE Variable Speed 18.9 Amps

Electrical Installation Continued

POWERTANK

Page 9: O&M Manual - Powertank

9

Commissioning

1. Make a visual check to make sure all pipe work and electrical connections are connected securely in a safe manner.

2. If present, close any isolation valves on the Bypass and disconnect the bypass if necessary to comply with water regulations.

3. Check that the Pre-charge air pressure in the pressure vessel is set 0.2 bar below the cut in pressure. For a standard fixed speed Powertank with a 1.5 bar Presflo this would be 1.3 bar. For variable speed units with user selectable start pressures it should be set according to your required duty point.

4. Check and open the isolation valves on the inlet to the tank.

5. If the tank isn’t already filled, loosen the outlet connection to allow air to escape while the tank is filling.

6. Ensure the tank is full and there is no discharge from the overflow connection.

7. Check that the outlet connection has been correctly tightened again and close the valve you have fitted on the outlet pipe.

8. Open the closest cold water outlet to the tank.

9. Check that the unit is plugged in or the electrical supply cables are correctly connected to the mains isolator switch.

10. Turn on the power. The control unit should turn on and the pump start to run for up to 30 seconds.

11. Slowly open the Isolating valve to fill the pipe work with water, the pump should start automatically. If it does not then you may need to press the “reset” button or turn the power on again.

12. If the controller displays dry running after approximately 10 seconds it is likely that there is air trapped in the pump. Bleed this air out by loosening the lower connection of the control unit before resetting the controller. This is O ring sealed and does not need to be overtightened or have any joint sealer.

13. Check that water is flowing from the open tap/outlet and then close it and check that the pump turns off. There will always be a time delay of 10 – 20 seconds until the pump stops in normal operation.

14. Check all pipe work for leaks.

15. For variable speed Powertanks, check the operating pressure and adjust as required.

POWERTANK

Page 10: O&M Manual - Powertank

10

Pump Specification

Maximum Operating Conditions

Top Multi/ Top Multi Tech NK/UP

Liquid Temperature +40°C +40°C

Maximum Pressures 4.2bar 9.5 bar

Noises level of the Powertank Set ≥48-55dB ≥48-55dB

Pump Types specifications

Vessel Pre-charge Pressure

The air pre-charge in the pressure vessel should be set 0.2 bar below the pump start pressure for maximum effectiveness. It is recommended to check the Tank air pressure every 4-6 months. For fixed speed Powertanks the air pressure in the vessel should be 1.3 bar.

Fixed Speed Powertanks - Pressure Settings

The start pressure is 1.5 bar on a standard fixed speed Powertank and is not user adjustable. These Powertanks are not suitable for installations where the highest outlet is more than 12 vertical metres above the Powertank, please consult our Technical Department for heights greater than this.

Water Quality

In the event that the water remains unused inside the tank for an extended period, it should be drained and flushed to maintain water quality. Tanks may be drained by using the pump to empty it and/or via the drain plug at the base. For commercial applications the tank should be cleaned in accordance with the relevant regulations and it is recommended that domestic systems are drained and cleaned twice a year or as required by the circumstances of the installation.

Powertank ModelsPower

Pressure 1 Bar 2 Bar 3 Bar 4 Bar 5 Bar 6 BarkW HP

Fixed Speed 0.55 0.75 73 57 40 10 - -

Variable Speed 0.75 1 80 80 80 68 50 14

Variable Speed (Compact) 0.55 0.75 80 80 66 40 - -

Variable PLUS 1.5 2 160 160 138 107 50 -

Variable TWIN 1.5 2 160 160 160 136 100 28

Variable TRIPLE 2.25 3 240 240 240 204 150 42

Q l/min

POWERTANK

Page 11: O&M Manual - Powertank

11

To increase 0.1 bar press SIMULTANEOUSLY

To decrease 0.1 bar press SIMULTANEOUSLY

ENTER

ENTER

P 3.2

P 3.3

P 3.1

Variable Speed Powertanks – Pressure adjustment:

Variable Speed Powertanks - Pressure Settings

The constant operating pressure is factory set to 3.0 bar. This can be adjusted as detailed below. The maximum pressure setting should not be set higher than the pressure capability of the pump, this prevents the system operating correctly and will cause a false “no water” error. The maximum recommended settings are:Powertank (Compact): 4.0 barPowertank: 5.0 bar

POWERTANK

Page 12: O&M Manual - Powertank

12

Operation: Presflo - Fixed Speed Controller

PRESFLO® is switched off. Press briefly or hold down = nothing happens

Power is restored = PRESFLO® resumes NORMAL SERVICE and starts the pump (if necessary).

The pump has been stopped manually. The pump will remain inactive until a new command is given. Press briefly = nothing happens

Hold down= the pump resumes NORMAL SERVICE.See points 2a - 2b.

2a NORMAL SERVICE: the pump is inactive.

The system is pressurised. All taps are turned off. There is no demand for water. PRESFLO® detects an assembly pressure higher than that of the start-up pressure (Pm) and no flow.

Press briefly = the pump is started manually and runs for a few seconds before stopping again.

Hold down = the pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

A tap is turned on = as soon as the pressure falls below the start-up pressure (Pm), the pump is started.

4a ERROR: stopped temporarily due to DRY RUNNING

(See NOTE 1) PRESFLO® has detected that the pump is dry running and has therefore stopped it TEMPORARILY.

Press briefly = the pump is started and manually and resumes NORMAL SERVICE. See points 2a - 2b.

Hold down = the pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

The assembly requires water. One or more taps are turned on. PRESFLO® detects a flow; the assembly pressure is normally higher than the START-UP pressure, but it may also be lower.

Press briefly or hold down = the pump is stopped and put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

The taps are turned off = if there is no flow for a few seconds, the pump is stopped.

4b ERROR: temporary shut down due to FREQUENT START UP

(see NOTE 2)PRESFLO® has detected that the pump starting-up too often and has therefore stopped it TEMPORARILY.

Press briefly = the pump is started and manually and resumes NORMAL SERVICE. See points 2a - 2b.

Hold down = the pump will not restart and goes OUT OF ORDER. The pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

3 Out of service 1 No power supply

2b NORMAL SERVICE: the pump is running

Off On Flashing

Controller Specific Instructions & Troubleshooting

POWERTANK

Page 13: O&M Manual - Powertank

13

Troubleshooting: Presflo - Fixed Speed Controller

Problems Signals Possible causes Solutions

PRESFLO®will not turn on

POWER STATUS

No power Check the electrical connections

The pump will not start when a tap is turned on

POWER STATUS

PRESFLO® model with an inade-quate start-up pressure (Pm) for the chosen application

Relocate PRESFLO®to another position

Install a model with a higher start-up pressure (Pm)

POWER STATUS

Faulty electrical connections or pump out of service

Check the electrical connections and that the pump is working

POWER STATUS

PRESFLO® “OUT OF SERVICE” Reset PRESFLO® (See Operation, point 3).

POWER STATUS

PRESFLO® in temporary shut down due to “DRY RUNNING” due to lack of water

Wait for the automatic restart or press START to restart manually (See Operation, point 4a)

Maximum pump pressure is insufficient

Replace the pump with one with more suitable characteristics

Install a model with a lower start-up pressure (Pm)

POWER STATUS

PRESFLO® in temporary shut down due to “FREQUENT START-UP”

Wait for the automatic restart or press START to restart manually (See Operation, point 4b). Remove any cause of leakage from system or install an expansion tank

The pump delivers no or low pressure

POWER STATUS

Filters or pipes may be partly blocked Check the water pipes

PRESFLO®’s valve will not open completely

Check that the valve is not blocked by any foreign objects and clean if necessary

The pumps stops and starts repeat-edly

POWER STATUS

POWER STATUS

Leaks within the system (less than the shut-off flow rate Qa)

Check the hydraulic connections and repair any leaks. If a leak cannot be repaired, install an expansion tank

The pump will not stop

POWER STATUS

The flow rate is higher than the shut-off flow rate (Qa)

Make sure that all taps are turned off and that there are no leaks within the system

PRESFLO®’s check valve will not close or is damaged

Check that the valve is not blocked by any foreign objects and clean if necessary

On FlashingOff

Controller Specific Instructions & Troubleshooting

POWERTANK

Page 14: O&M Manual - Powertank

14

Press briefly or hold down = nothing happens

Power is restored = PRESFLO® resumes NORMAL SERVICE & starts the pump (if necessary).

Operation: Presflo Multi - Fixed Speed Controller

PRESFLO® is switched off. The pump has been stopped manually.

The pump will remain inactive until a new command is given. Press briefly = nothing happens Hold down = the pump resumes NORMAL SERVICE. See points 2a - 2b.

2a NORMAL SERVICE: the pump is inactive.

The system is pressurised. All taps are turned off. There is no demand

for water. PRESFLO® detects an assembly pressure higher than that of the start-up pressure (Pm) and no flow. Press briefly = the pump is started manually and runs for a few seconds before stopping again.Hold down = the pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3. A tap is turned on = as soon as the pressure falls below the start-up pressure (Pm), the pump is started.

4a ERROR: stopped temporarily due to DRY RUNNING

The assembly requires water. One or more taps are turned on. PRESFLO® detects a flow; the assembly pressure

is normally higher than the START-UP pressure, but it may also be lower. Press briefly or hold down = the pump is stopped and put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3. The taps are turned off = if there is no flow for a few seconds, the pump is stopped.

4b ERROR: temporary shut down due to FREQUENT START UP

PRESFLO® has detected that the pump is starting-up

too often and has therefore stopped it TEMPORARILY. Press briefly = the pump is started and manually and resumes NORMAL SERVICE. See points 2a - 2b. Hold down = the pump will not restart and goes OUT OF ORDER. The pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

Off On Flashing

3 Out of service 1 No power supply

2b NORMAL SERVICE: the pump is running

The system has just ceased to require water. All taps are closed. The pump is still in operation. Th system

is pressurised. PRESFLO® detects a system pressure higher than the start-up pressure (Pm) and no flow. Press briefly or hold down = the pump is stopped and put in STAND-BY. To reset see point 3. If the absence of flow lasts for a few seconds the pump is stopped.

2c NORMAL SERVICE: pump during shutdown

PRESFLO® has detected that the pump is dry running and

has therefore stopped it TEMPORARILY. Press briefly = the pump is started and manually and resumes NORMAL SERVICE. See points 2a - 2b. Hold down = the pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

4c ERROR: stop due to overload

PRESFLO® has detected a current exceeding the max.

allowed and has stopped the pump. Press briefly = the pump is started and manually and resumes NORMAL SERVICE. See points 2a - 2b. Hold down = the pump is put OUT OF SERVICE. For instructions on how to reactivate the pump, see point 3.

Controller Specific Instructions & Troubleshooting

POWERTANK

Page 15: O&M Manual - Powertank

15

Trouble Shooting: Presflo Multi - Fixed Speed Controller

Problems Signals Possible causes Solutions

PRESFLO®will not turn on

POWER ON

PUMP ON

No power Check the electrical connections

The pump will not start when a tap is turned on

POWER ON

PUMP ON

PRESFLO® model with an inad-equate start-up pressure (Pm) for the chosen application

Relocate PRESFLO® to another position

Install a model with a higher start-up pressure (Pm)

POWER ON

PUMP ON

Faulty electrical connections or pump out of service

Check the electrical connections and that the pump is working

POWER ON

PUMP ON

PRESFLO® “STAND-BY”” Reset PRESFLO® (See Operation, point 3).

POWER ON

PUMP ON

PRESFLO® in temporary shut down due to “DRY RUNNING” due to lack of water

Wait for the automatic restart or press START to restart manually (See Operation, point 4a)

Maximum pump pressure is insufficient

Replace the pump with one with more suitable characteristics

Install a model with a lower start-up pressure (Pm)

POWER ON

PUMP ON

PRESFLO® in temporary shut down due to “FREQUENT START-UP”

Wait for the automatic restart or press START to restart manually (See Oper-ation, point 4b). Remove any cause of leakage from system or install an expansion tank

POWER ON

PUMP ON

PRESFLO® stops due to “OVER-CURRENT”

Check if the setting of the maximum current (Imax) is congruent with the data of the pumps’ ratingplate. If after manually restarting the pump after correctly setting PRESFLO®, it again signals an anomaly, check that the motor has no mechanical or electrical problems.

The pump delivers no or low pressure

POWER ON

PUMP ON

Filters or pipes may be partly blocked

Check the water pipes

PRESFLO®’s valve will not open completely

Check that the valve is not blocked by any foreign objects and clean if necessary

The pumps stops and starts repeatedly

POWER ON PUMP ON

POWER ON PUMP ON

Leaks within the system (less than the shut-off flow rate Qa)

Check the hydraulic connections and repair any leaks. If a leak cannot be repaired, install an expansion tank

The pump will not stop

POWER ON

PUMP ON

The flow rate is higher than the shut-off flow rate (Qa)

Make sure that all taps are turned off and that there are no leaks within the system

PRESFLO®’s check valve will not close or is damaged

Check that the valve is not blocked by any foreign objects and clean if necessary

On FlashingOff

Controller Specific Instructions & Troubleshooting

POWERTANK

Page 16: O&M Manual - Powertank

16

Starting up: Steadypres - Variable Speed Controller

Switch on power to controller and wait the STARTING time (ab. 10 sec.)

By pressing the button START STOP you put IN SERVICE OUT OF SERVICE the inverter.

To increase 0.1 bar press SIMULTANEOUSLY

To decrease 0.1 bar press SIMULTANEOUSLY

ENTER

ENTER

P 3.2

P 3.3

P 3.1

Set pressure quick adjustment: Steadypres - Powertank Variable Speed Control

Light Signals: Steadypres - Powertank Variable Speed Control

Keyboard

ON OFF BLINKING

STATUSPOWER

STEADYPRES does not detect power supply. WARNING: cannot guarantee the absence of power supply, the electronic board may be faulty, but under tension

STATUSPOWER

STEADYPRES is live, but the pump is not running (STANDBY)

STATUSPOWER

STEADYPRES is live, and the pump is running

STATUSPOWER

STEADYPRES is live, but out of service; the re-arm is only manual

STATUSPOWER

is only manual STEADYPRES is in ALARM mode, re-arm

Controller Specific Instructions & Troubleshooting

POWERTANK

Page 17: O&M Manual - Powertank

17

Controller Specific Instructions & TroubleshootingAlarms: Steadypres - Variable Speed Controller

OVERCURRENT %

The current exceeded the allowable tolerance on the current set. The inverter stops the pump, the rearm is only manual.

CURRENTLIMIT

Occurs if, in the absence of flow, the pump cannot reach the SET pressure, but can reach at least a pre-determined percentage of the SET pressure, defined through the parameter Pd. The inverter does not stop the pump.

I DRY(Only with flow sensor)

Occurs if, in the absence of flow, the pump cannot reach the SET pressure, but can reach at least a pre-determined percentage of the SET pressure, defined through the parameter Pd. The inverter does not stop the pump.

DRYRUNNING(applications WITH flow Sensor)

Occurs if, in the absence of flow, the pump falls to reach the pressure of the set but does not even reach a predeterminded percentage of the SET pressure, expressed by the parameter Pd; the inverter stops the pump . The error is reset after the time TP and the inverter re-starts in automatic mode.

DRYRUNNING PF(only T/T models)

Occurs if the electrical parameter COSFI (power factor) falls to value indicating the unload operation of engine. the inverter stops the pump. the error is reset after the time TP.

LOW PRESS Occurs if the pump is running at maximum frequency (50/60 Hz), in the presence of flow, and the pressure doesn’t reach 0.3 bar; the inverter stops the pump. the error is reset after the time TP and the inverter re-starts in automatic mode.

VOLTAGEERROR L

A voltage drop has occurred beyond minimum operating threshold. The inverter stops the pump. The error is reset after one minute, and the inverter re-starts in automatic mode.

HIGH TEMP.BOX(Only T/T models)

The temperature inside the inverter has reached 65°C; is automatically limited the maximum frequency of 5 Hz but the drive continues to run, the error is reset below 60°C.

OVER TEMP.BOX(Only T/T models)

The temperature Inside the Inverter has reached 80°C, the inverter stops the pump, the error is reset below 60°C and the drive will restart automatically

HIGH TEMP.MOD

The module temperature has reached the first alarm threshold; the maximum working frequency is automatically limited, but the drive continues to run, the error is reset when the module temperature returns below 70°C.

OVER TEMP.MOD

The module temperature has reached the second alarm threshold, the inverter stops the pump, the error is reset when the module temperature returns below 70°C and the drive will restart automatically.

INPUTERROR

There has been a reversal of the power connections / output to the motor . the in-verter is locked, the error is reset by connecting the cables correctly in the terminal.

COM ERROR Communication has been interrupted between the control board and the power board; the cause could be integrity of the cable and the connection ports or an electronic board fault.

PHASEERROR

(Only for models with three-phase output) lack of phase towards the motor during operation. The inverter stops the pump; reset is manual only.

LOW LEVEL This occurs when the digital input EL is configured as “WATER LEVEL” (level signal) and there is no signal. When the signal returns, the message disappears and the inverter operates normally again.

EXT OFF This occurs when the digital input EL is configured as “EXT ENABLE” (control enabled from outside) and there is no signal. When the signal returns (external enabling) the message disappears and the inverter operates normally again.

POWERTANK

Page 18: O&M Manual - Powertank

18

We, Pedrollo Distribution Ltdof Crossfield Fort Crossfield Road Industrial Estate Lichfield WS13 6RJ Telephone: 01543 415 200 Fax: 01543 415900 [email protected]

in accordance with the following Directives: Refer to page 19 for list of directives

Hereby declare that:Equipment: Powertank Range

is in conformity with the applicable requirements of the following documents: Refer to page 19 for list of national implementation provisions

I hereby declare that the equipment above has been designed and assembled to comply with the relevant section of the above referenced specifications. The unit complies with all applicable Essential Requirement of the Directives.

The Technical Construction File is maintained at: Pedrollo Distribution Ltd Crossfield Fort Crossfield Road Industrial Estate Lichfield WS13 6RJ Telephone: 01543 415 200 Fax: 01543 415900 [email protected]

DECLARATION OF CONFORMITY

PLEASE KEEP THIS DOCUMENT IN A SAFE PLACE

Signed: Managing Director, Pedrollo Distribution

Date:

20/01/2021

POWERTANK

Page 19: O&M Manual - Powertank

19

Pump Range Provisions

Top Multi Top Multi-Tech NK UP

EN 60335-1EN60034-1IEC 60335-1IEC 60334-1CIE 61-150CIE 2-3

Fitting Type ProvisionsNylon Fittings EN 60335-1

Pipe Type Provisions

MDPE Blue Pipe

AS/NZS 4020BS EN 12201-2BS EN 1717:2000BS EN 12201

Valve Type ProvisionsCheck Valve EN 1717:2000Flow Valve BS 1212/1Fill Valve WRAS Approved 1203001

Tank Type ProvisionsHolding Tank BS 6920-1:2000

Controllers

Steadypress

Directives2006/95/CEE Low Voltage Directive2002/95/CEE Dangerous substances in electromagnetic compliances( RoHS)2002/96/CEE e 2003/108/CEE Dangerous substances in electronic appliances (WEEE)2004/108/CE Electromagnetic Compatibility Directive(EMC)EN 5501-1 (emissions)Provisions EN 61000-3-2 (emissions)EN 61000-3-3 (emissions)EN 55014-2 (immunity)EN 61000-4 (immunity)

Pressflo Multi

Directives2006/95/CEE Low Voltage Directive2002/95/CEE Dangerous substances in electromagnetic compliances( RoHS)2002/96/CEE e 2003/108/CEE Dangerous substances in electronic appliances (WEEE)2004/108/CE Electromagnetic Compatibility Directive(EMC)ProvisionsEN 60730-2-6EN 61000 6-3

Sealant Type Provisions

Thread Sealant WRAS ApprovedCertified NSF P1. sealant paste “green”, no risk phrases, blank MSDS

Directives and National Implementation Provisions

POWERTANK

Page 20: O&M Manual - Powertank

Model Type Volume[LTR]

Length[MM]

Width [MM]

Height [MM]

Inlet [Inch]

Outlet [Inch]

Over-flow

Drain off

[Inch]

Weight (Empty Tank) (kg)

POWERTANK 10ltr CAT 5 - Fixed Speed 10 500 300 670 ¾” BSP 1" BSP 40mm - 14

POWERTANK 125ltr Compact - Fixed Speed 125 560 490 850 ½" BSP 1" BSP 1 ½" 1" BSP 27

POWERTANK 125ltr Compact - Variable Speed 125 560 490 850 ½" BSP 1" BSP 1 ½" 1" BSP 33

POWERTANK 200ltr DG PED - Variable Speed 200 570 512 1211 ½" BSP 1” BSP 1 ¼” BSP 1" BSP 34

POWERTANK 200ltr Slimline - Fixed Speed 200 584 584 1190 ½" BSP 1” BSP 1 ¼” BSP 1" BSP 26

POWERTANK 200ltr Slimline - Variable Speed 200 584 584 1190 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 32

POWERTANK 350ltr Slimline - Fixed Speed 300 584 584 1656 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 29

POWERTANK 350ltr Slimline - Variable Speed 300 584 584 1656 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 35

POWERTANK 200ltr Coffin - Fixed Speed 200 1106 475 770 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 30

POWERTANK 200ltr Coffin - Variable Speed 200 1106 475 770 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 37

POWERTANK 270ltr Coffin - Fixed Speed 270 1571 475 751 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 32

POWERTANK 270ltr Coffin - Variable Speed 270 1571 475 751 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 39

POWERTANK 340ltr Coffin - Fixed Speed 340 1571 475 980 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 34

POWERTANK 340ltr Coffin - Variable Speed 340 1571 475 980 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 40

POWERTANK 450ltr Coffin - Fixed Speed 450 1765 580 846 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 36

POWERTANK 450ltr Coffin - Variable Speed 450 1765 580 846 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 42

POWERTANK 300ltr Rectangular - Fixed Speed 300 1045 665 940 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 34

POWERTANK 300ltr Rectangular - Variable Speed 300 1045 665 940 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 40

POWERTANK 500ltr Rectangular - Fixed Speed 500 1190 727 1030 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 39

POWERTANK 500ltr Rectangular - Variable Speed 500 1190 727 1030 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 45

POWERTANK 500ltr Rectangular - Variable Speed - Twin Pump 500 1190 727 1030 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 59

POWERTANK 500ltr Utility - Fixed Speed 500 760 760 1393 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 34

POWERTANK 500ltr Utility - Variable Speed 500 760 760 1393 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 40

POWERTANK 500ltr Utility - Variable Speed - Twin Pump 750 760 760 1393 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 52

Powertank Range

POWERTANK

20

Page 21: O&M Manual - Powertank

Model Type Volume[LTR]

Length[MM]

Width [MM]

Height [MM]

Inlet [Inch]

Outlet [Inch]

Over-flow

[Inch]

Drain off

[Inch]

Weight (Empty Tank) (kg)

POWERTANK 750ltr Utility - Fixed Speed 750 760 760 2113 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 49

POWERTANK 750ltr Utility - Variable Speed 750 760 760 2113 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 55

POWERTANK 750ltr Utility - Variable Speed - Twin Pump 750 760 760 2113 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 69

POWERTANK 650ltr Utility - Fixed Speed 650 1083 669 1283 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 54

POWERTANK 650ltr Utility - Variable Speed 650 1083 669 1283 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 60

POWERTANK 1000ltr Utility - Fixed speed 1000 1688 563 1640 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 74

POWERTANK 1000ltr Utility - Variable Speed 1000 1688 563 1640 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 80

POWERTANK 1000ltr Utility - Variable Speed - Twin Pump 1000 1688 563 1640 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 96

POWERTANK 250ltr Bunded - Fixed Speed 250 760 760 1478 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 49

POWERTANK 250ltr Bunded - Variable Speed 250 760 760 1478 ½" BSP 1" BSP 1 ¼” BSP 1" BSP 55

POWERTANK 650ltr Bunded - Fixed Speed 650 752 1200 1174 ½” BSP 1" BSP 1 ¼” BSP 1" BSP 94

POWERTANK 650ltr Bunded - Variable Speed 650 752 1200 1174 ½” BSP 1” BSP 1 ¼” BSP 1” BSP 100

Model Type Volume[LTR]

Length[MM]

Width [MM]

Height [MM]

Inlet [Inch] Outlet [Inch] Overflow

[Inch]

Warning pipe

[Inch]

POWERTANK Industrial 500ltr - Variable Speed 500 1180 680 1040 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 1000ltr - Variable Speed 1000 1180 1180 1095 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 1500ltr - Variable Speed 1500 1705 1205 1095 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 2000ltr - Variable Speed 2000 2205 1205 1095 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 2500ltr - Variable Speed 2500 2205 1265 1345 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 3000ltr - Variable Speed 3000 2205 1205 1595 ¾" TSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 4000ltr - Variable Speed 4000 2195 2195 1095 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

POWERTANK Industrial 5000ltr - Variable Speed 5000 2695 2195 1095 ¾" BSP 1" BSP -Single2" BSP - Twin/Triple 1 ¼” BSP ¾" BSP

Powertank Industrial Range

POWERTANK

21

- Industrial dimensions for tank only

Page 22: O&M Manual - Powertank

22

Size of Tank (L): 10L 125L 200L 300L

340L 350L 500L 650L

750L 1000L 1500L 2000L

2500L 3000L 4000L 5000ltr

Bunded Option: 250L 650L

Tank Serial Number*:

Build Ref*:

Date Installed:

Commission Date:

System type:

Installer Name:

Address:

Email:

Mobile No:

Powertank Commissioning Checklist

INSTALLER DETAILS

TANK DETAILS

Build reference Number*

Tank Serial Number*

Name:

Address:

Email:

Mobile No:

CLIENTS DETAILS

Construction Co:

Project ID:

Engineer:

Mobile No:

PROJECT DETAILS

Place of Purchase:

Plumber/Installer:

Email:

Mobile No:

PURCHASE DETAILS

Compact

Rectangular Coffin

Slimline

Utility Industrial

Fixed Speed

Variable Speed

Variable Plus

Variable Twin

Variable Triple

X/3 or X/5 CAT5

Page 23: O&M Manual - Powertank

23

Bypass

Mains Water Supply

Over�ow to drain from tank

Over�ow to drain from drip tray

Outlet

2

6

4

213

* The use of a drip tray and insulation jacket are recommended with every installation

57

2

1. Ball cockIsolation valve Powertank over�owTundish

Drip tray

2.3.4.5.

7. Drip tray over�ow

Powertank drain o�6.

POWERTANK 200ltr, 350ltr, 500ltr & 750ltr Schematic

POWERTANK

Bypass

Mains Water Supply

Outlet Supply

2

6

2

8

75

3

1

2

4

Tundish

1. Ball cock

Powertank over�ow

Separate drip tray over �ow

Powertank drain o�Drip tray

2.3.4.5.6.7.

Removable lid with pump8.& controller inbuilt

Isolation valve

* The use of a drip tray and insulation jacket are recommended with every installation

POWERTANK 200ltr, 270ltr, 345ltr & 450ltr Schematic

POWERTANK

Bypass

Mains Water Supply

Over�ow to drain from tank

Over�ow to drain from drip tray

Outlet

2

6

4

213

* The use of a drip tray and insulation jacket are recommended with every installation

57

2

1. Ball cockIsolation valve Powertank over�owTundish

Drip tray

2.3.4.5.

7. Drip tray over�ow

Powertank drain o�6.

POWERTANK 200ltr, 350ltr, 500ltr & 750ltr Schematic

POWERTANK

200ltr, 270ltr, 345ltr & 450ltr 200ltr, 350ltr, 500ltr & 750ltr

* The use of a drip tray and insulation jacket are recommended with every installation

INSTALLATION AND COMMISSIONING CHECKLISTITEM STATUS COMMENT

Visual inspection of Powertank for any defects Yes No

Is a Powertank installation label on tank? Yes No

Is the Powertank positioned in a safe location? Yes No

Is the Powertank installed away from direct sunlight? Yes No

Is there a bypass unit fitted around system? Yes No

Is there a shut off valve fitted on inlet of tank? Yes No

Is a drip tray fitted with correct size overflow? Yes No

Is an insulation jacket fitted? Yes No

Has the correct overflow pipe been selected for Powertank? Yes No

Has the correct overflow pipework been selected for drip tray? Yes No

Have overflows been piped separately, without any sharp edges which could cause restriction? Yes No

Has incoming water pressure been tested and has the correct ballcock been selected and tested? Yes No

Has the Powertank been fitted in a ventilated area? Yes No

Has the unit’s power supply to electrical supply been connected in accordance with current regulations and by a qualified, trained person?

Yes No

Has a full test of overflow pipes been done? Yes No

Has the system been correctly installed and fully tested? Yes No

Any pressure reducing valves fitted on line?

If yes, has the control unit been adjusted to the correct parameters for operation? Yes No

Incoming water pressure to Powertank Bar

Powertank cut in pressure Bar

Powertank close valve pressure Bar

Yes No

Print Name (Installer): Signed: Position: Date:

Print Name (Engineer): Signed: Position: Date:

Page 24: O&M Manual - Powertank

t: 01543 415200e: [email protected]

Pedrollo Distribution Ltd Crossfield Fort

Crossfield Road Industrial EstateLichfield

WS13 6RJ

powertank.co.ukRef 01/12/21