  • OEM LOADCENTER INTERIOR ASSEMBLIES

    CIRCUIT BREAKERS AND ACCESSORIES

  • Page 1

    OEM INTERIORASSEMBLIES

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    OEM Loadcenter Interior Assemblies

    Type CH Indexpage(s)

    Type BR Index

    Type CH OEM LoadcenterInterior Assemblies ....................................... 4

    Type CH Loadcenter Accessories ..................... 5

    Type CH Circuit Breakers .................................. 6

    Plug-On .......................................................... 7

    Plug-On Special Application ................... 7-11

    Accessories ................................................. 12

    Type CH Interior Assemblies

    Single-Phase, Single-RowCopper Bus, 70 and 125 Amp .................... 13

    Single-Phase, Double-RowCopper Bus, 125, 200 and 225 Amp ..... 14-18

    Three-Phase, Double-RowCopper Bus, 125 and 225 Amp ............. 19-21

    Surge Protectors ............................................. 46

    Type BR OEM LoadcenterInterior Assemblies ..................................... 22

    Type BR Loadcenter Accessories ................... 23

    Type BR Circuit Breakers ................................ 24

    Plug-On ............................................... 25 & 30

    Plug-On Special Application ...... 26, 27, & 30

    Plug-On Duplex, Quadplex .................. 28, 29

    Accessories ................................................. 31

    Type BR Interior Assemblies

    Single-Phase, Single-RowAluminum Bus, 70 and 125 Amp ......... 32, 33

    Single-Phase, Double-RowAluminum Bus,125, 200 and 225 Amp ........................... 34-39

    Single-Phase, Double-RowCopper Bus, 125 and 200 Amp ............ 40, 41

    Three-Phase, Double-RowAluminum Bus,125, 150, 200 and 225 Amp ................... 42-44

    Three-Phase, Double-RowCopper Bus, 125 and 200 Amp .................. 45

    Surge Protectors ............................................. 46

    page(s)

  • OEMPage 2

    INTERIORASSEMBLIES

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Two Products OfferDesign FlexibilityAs a manufacturer of two lines ofloadcenters, we are in a uniqueposition to offer the broadest rangeof interiors in the market. Each linehas its own unique characteristicsthat appeal to various segments ofthe market. OEM interiors are ULrecognized components and are listedin either of the following UL files:E8741 or E52977.

    The interiors are designed for eitherhorizontal (single-row breakermounting), or vertical (double-rowbreaker mounting). To comply withNational Electrical Code® (NEC)requirements if mounted horizontally,when the breaker is ON, the handleshould be in the UP position. Whenmounted vertically, the handle togglesfrom left to right, so this is not a concern.

    Type CHThe CH interiors feature 100% copperbus and use the CH 3/4-inch wide(19.1 mm) circuit breaker, whichminimizes panel space. Recognizedby contractors for its sturdy design,the CH interior will appeal to thosecustomers seeking an industrialquality bolted bus bar and the spacesaving of 1/4-inch (6.4 mm) per busstab. With a typical 12 circuit CHinterior, this space savings amountsto an 1-1/2 inch (38.1 mm) savingsover its 1-inch (25.4 mm) counterparts.The stab rating of the CH interiors is140 amperes maximum, meaning thatthe handle rating of breakers mountedacross from one another may notexceed 140 amperes.

    Type BRThe BR interiors are manufactured offormed, plated aluminum or copper,and use the Cutler-Hammer Type BR1-inch wide (25.4 mm) circuit breaker.This design affords customers themost circuit flexibility as many ofthese interiors allow the installationof standard 1- and 2-pole breakersas well as duplex (2 poles in a 1-inchspace, 25.4 mm), or quadplex (4 polesin a 2-inch space, 50.8 mm) breakers.The stab rating of the BR interiors is200 amperes maximum, meaning thatthe handle rating of the breakers thatare mounted across from one anothermay not exceed 200 amperes.

    GeneralAs a leader in the electrical distribu-tion equipment business, Cutler-Hammer has a unique productoffering for equipment manufacturers,panel builders and virtually any OEMthat has a need for power distributionwithin their equipment. The OEMinterior offering consists of a widevariety of power distribution optionsutilizing components from Cutler-Hammer’s CH and BR Loadcenterproduct lines. With high-volume,standardized products, OEMs canexpect to receive high-qualityproducts in configurations meetingvirtually any power distribution need.

    Coupled with Cutler-Hammer’sexpertise in circuit breaker designand manufacturing, our OEM interiorsprovide solid power distribution andcircuit protection in a compact, easy-to-install package. Interiors are offeredfrom 2 to 42 circuits, and from 70 to225 amperes.

    QualityBuilt in our ISO 9002 certified manu-facturing facilities, customers can beassured of the process quality in placefor the manufacture of these products.Utilizing the latest in computer-controlled plating, painting, molding,stamping and welding processes,our customers have come to expectconsistent high quality from shipmentto shipment.

    Ordering InformationCutler-Hammer OEM interiors are aseasy to order as they are to install.Customers place orders by catalognumber in multiples of the standardpackage quantities. The products areeither stocked in Cutler-Hammerwarehouses or are shipped directlyfrom the plant. For those panelsshipping directly from the plant,shipping lead time is 10 working days.Distributors should refer to VISTA orthe Cutler-Hammer Price andAvailability Digest for pricing. Forinteriors not shown in this catalog,contact your local Cutler-Hammersales engineer or the CustomerSupport Center at 1-800-356-1243.

  • Page 3

    OEM INTERIORASSEMBLIES

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    OEM Loadcenter Interior Assemblies

    Specifications, ListingsClass CTLNEC Paragraph 384-15 requires branchcircuit panelboards to be providedwith physical means to prevent theinstallation of more overcurrentdevices than the number of which theenclosure was designed, rated andapproved. Class CTL duplex, quadplexand twin breakers (identified by acatalog number prefix BD, BQ, BQCand CHT) are equipped with a ULlisted rejection tab over the lineterminal. All OEM interiors haveappropriately notched stabs to acceptthese rejection tab Class CTL breakers.

    Duplex, quadplex and twin breakersmanufactured without the rejectiontab (identified by a catalog numberprefix BR, BRD and CHNT) areavailable for replacement purposesin older interiors.

    Federal SpecificationsAll loadcenter enclosures meetFederal Specifications W-P-115b,Type 1, and Class 2 requirements.

    All 120/240V breakers, both 1-inch(25.4 mm), 1/2-inch (12.7 mm) and3/4-inch (19.1 mm) per pole meet therequirement of Federal SpecificationsW-C 375B/Gen Type 1.

    Canadian Standards Association ListingAll 1-pole and 2-pole, 120/240Vbreakers, both 1-inch (25.4 mm),1/2-inch (12.7 mm) and 3/4-inch(19.1 mm) per pole, 225 amperemaximum, are listed as certified bythe Canadian Standards Association,Guide No. 69-11.19, Class 1432,File 18328.

    Underwriters Laboratories Inc. ListingAll grounding bars manufacturedcomply with Underwriters LaboratoriesInc. standards and are listed underGuide No. DHJR, File E31424, Volume W,Section 17.

    All circuit breakers 10 amperes andlarger comply with the UnderwritersLaboratories Inc. “Standard for BranchCircuit and Service Circuit Breakers”UL489, Guide No. 60 10.2 File E31424;and “Requirements for Wire Connec-tors and Soldering Lugs” UL486B,Guide No. 461 10-C File E7830.

    All Cutler-Hammer breakers wheremarked, are suitable for use with60/75°C rated wire, unless otherwisespecified.

    All devices comply with the 22,000 AIC– 10,000 AIC UL series connectedcomponents File DKSY2 of theRecognized Components Index.

    NEC 384-15

    Lighting and Appliance PanelboardsLighting and appliance branch circuitpanelboards are defined in NEC Article384 as “One having more than 10% ofits overcurrent devices rated 30amperes or less for which neutralconnections are provided.” Article 384also limits the number of overcurrentdevices (branch circuit poles) to amaximum of 42 in any one cabinet.When the 42 poles are exceeded, twoor more separate panels are required.

  • TYPE CH ASSEMBLIESPage 4

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CH 4 L 3 125 INT

    OEM Loadcenter Interior Assemblies

    Catalog Numbering System

    OEM InteriorAmpere RatingSingle-Phase: Blank / Three-Phase: 3

    Breaker TypeMaximum Single PolesMain Lug

    70 2 2 E8741 (1) #8–#2 AWG Cu/Al 1 CH9MB270 1 13

    125 2 2 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH2L125INT 2 13

    Type CH OEM Loadcenter Interior Assemblies

    Single-Phase Single-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire 125 4 4 E8741 (1) 2/0–#14 AWG Cu/Al 20 CH4L125INT 3 14

    125 8 8 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH8L125INT 4 14

    125 12 12 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH12L125INT 5 15

    125 16 16 E8741 (1) 2/0–#6 AWG Cu/Al 20 CH16L125INT 6 15

    200 12 12 E8741 (1) 300 kcmil–#4 AWG Cu/Al 20 CH12L200INT 7 16

    200 16 16 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH16L200INT 8 16

    225 24 24 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH24L225INT 9 17

    225 32 32 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH32L225INT 10 17

    225 42 42 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH42L225INT 11 18

    Three-Phase Double-Row Breaker Mounting – Copper Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125 12 12 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH12L3125INT 12 19

    125 18 18 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH18L3125INT 13 19

    125 24 24 E8741 (1) 2/0–#6 AWG Cu/Al 10 CH24L3125INT 14 20

    225 24 24 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH24L3225INT 15 20

    225 30 30 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH30L3225INT 16 21

    225 42 42 E8741 (1) 300 kcmil–#4 AWG Cu/Al 10 CH42L3225INT 17 21

    Ampere Maximum Number UL Main Terminal Wire Size Range Standard Catalog Diagram ReferenceRating 1-Inch (24.5 mm) File (Per Phase) Package Number Spaces Single Poles Reference Cu/Al 60°C or 75°C Quantity Number Page

  • TYPE CH ASSEMBLIESPage 5

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    B

    A .269(6.83)

    .844(21.44)

    2.360(59.94)

    CL of Mounting Hole CL of Mounting Hole

    1.187(30.15)

    1.182(30.02)

    B

    A

    2.000(50.80)

    .156(3.96)

    .688(17.47)

    CLof

    MountingHole

    .269(6.83)

    .344(8.74)

    .844(21.44)

    2.360(59.94)

    1.750(44.45)

    2.860(72.64)

    .250(6.35)

    .182 Diameter(4.62)

    .120(3.05)

    1.750(44.45)

    .750(19.05)

    .344(8.74)

    CL of Mounting Hole

    B

    A

    Neutral AssembliesAmpere UL Main Incoming Terminal Number of Terminals Standard Catalog Dimensions – Inches (mm)Rating File Wire Size Range Package Number

    Reference 60°C or 75°C Quantity

    125 E52977 #6–1/0 AWG Cu 10 – 20 10NEU125B 1 5.938 (150.83) 5.400 (137.16)#6–2/0 AWG Al

    125 E52977 #6–1/0 AWG Cu 17 – 20 17NEU125B 1 8.388 (213.06) 7.850 (199.40)#6–2/0 AWG Al

    125 E52977 #6–1/0 AWG Cu 20 – 20 20NEU125B 1 9.438 (239.73) 8.900 (226.06)#6–2/0 AWG Al

    225 E52977 #1–300 kcmil Cu/Al 24 1 20 24NEU225B 2 10.913 (277.19) 10.300 (261.62)

    225 E52977 #1–300 kcmil Cu/Al 35 1 20 35NEU225B 2 15.813 (401.65) 15.200 (386.08)

    125 — — 4 2 1 BINA 3 2.266 (57.56) 0.594 (15.09)

    #14–4 AWG #6–1/0 AWG Cu Figure Overall Length MountingCu/Al #6–2/0 AWG Al A B

    Figure 1

    Figure 3

    Figure 2

    Loadcenter Accessories

    Add-on Lugs for Neutral Assemblies

    Ground Bar Kits

    1

    Must be purchased in multiples of ordering quantities indicated.

    2

    Distance between mounting holes is 1-3/4 inches (44.5 mm).

    3

    For 1- and 3-phase 400 and 600 ampere applications.

    4

    Distance between mounting holes is 2-11/32 inches (59.5 mm).

    Description Wire Size RangeCu/Al 60°C or 75°C

    OrderingQuantity

    1

    CatalogNumber

    Neutral/Ground LugAdd-On Neutral or Ground Lug

    #2/0 Maximum#3/0 Maximum300 kcmil Maximum

    111

    NL20NL30NL300

    Description(See Legend)

    LengthInches (mm)

    OrderingQuantity

    1

    CatalogNumber

    dssssds

    dssssdsj

    dssssdssssss

    dssssdssssssj

    dssssdssssssssss

    dssssdssssssssssj

    dssssdsssssssssssssssss

    dssssdsssssssssssssssssj

    ofodofooofodofooofo

    2.54 (64.5)3.59 (91.2)4.29 (109.0)5.34 (135.6)4.61 (117.1)5.69 (144.5)6.74 (171.2)8.14 (206.8)9.19 (233.4)5.78 (146.8)

    1111111111

    GBK5

    2

    GBK520

    2

    GBK10

    2

    GBK1020

    2

    GBK13

    2

    GBK14

    2

    GBK1420

    2

    GBK21

    2

    GBK2120

    2

    BRGBK39512

    34

    f d f f f k f d f k f f f

    Ground Bar Legend

    s

    j

    o

    d

    (3) #14

    #10 Cu/Al or (1) #14 – #4 Cu/Al(1) #6

    2/0 Cu/Al(1) #14

    #6 Cu/Al or (2) #14 – #12 Cu/Al(1) 1/0

    14 or (3) #10 – 12 Cu/Al(1) #14

    1/0 Cu/Al or (3) #14 – #10 Cu/Al(1) #6

    14 Cu/Al or (2) #1/0 – 14 Cu/AlMounting Hole

    f

    f

    GBK14

    BRGBK39512

    k

  • Page 6

    TYPE CH

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    CH Circuit BreakersCutler-Hammer Type CH plug-onbreakers are a 3/4-inch (19.1 mm)design with a UL listed 10 kA interrupt-ing rating. CH breakers can be used asmain or branch disconnect devices.Several ratings are SWD and HACRapproved. Typical ampacity range forCH breakers is 15 to 150 amperes.

    CH-GF People Protection BreakersCutler-Hammer Type CH-GF (groundfault circuit breakers) combine state-of-the-art electronic technology witha circuit breaker mechanism in acompact 3/4-inch (19.1 mm) package.The CH-GF automatically senses hotwire-to-ground faults in a 4 to 6 mArange and disconnects the power, thusproviding an extra margin of safetybeyond that of conventional circuitbreakers. CH-GF applications includebathrooms, cellar outlets, swimmingpools, outdoor branch circuits andkitchen branch circuits. Available in ULlisted 120 and 120/240V ratings. Cutler-Hammer also offers non-UL listedground fault breakers for internationalapplications as well as ground faultdevices for equipment protection.

    CH-EPD Equipment ProtectionBreakersThe Cutler-Hammer Type CH-EPDdevice is similar to the CH-GP exceptthat it is designed to protect equip-ment (not people) against damagefrom arcing ground faults. It isavailable with a 30 mA trip level.Applications include infrared heatingequipment, process control equip-ment, etc.

    Special Application BreakersAs the name implies, these devices aredesigned for special applications as re-quired by the National Electrical Code.

    Neutral Switching BreakerPrimary application for the Cutler-Hammer switching neutral breaker isfor protection of process equipmentsuch as gas pumps that utilizeflammable liquids. Non-automaticpole breaks the neutral power leg,minimizing the danger of arc conditions.

    2-Pole Breakers 120V or More to GroundUsed on Delta distribution systems,these Type CH breakers are applied onphase legs where voltage-to-ground isabove 120V.

    Arc Fault Circuit Interrupters (AFCIs)Reduce the risk of fire by detectingand interrupting electrical arcing faultswhich standard thermal magneticbreakers cannot. For more informa-tion, see page 9.

    CH-HM BreakersCH-HM breakers are designed withhigh magnetic trip settings. Single-and 2-pole CH-HM breakers (“HM”suffix) rated 15 and 20 amperes arerecommended for circuits withinherently high inrush currents.

    CH-M50 BreakersCH-M50 breakers are designed tooperate at a maximum temperatureof 50°C. Single- and 2-pole CH-M50breakers (“M50” suffix) rated 15 to50 amperes are recommended forapplications where the ambienttemperatures are above 40°C.

    CHP BreakersCHP breakers are designed with athree-position commercial trip (on-tripped-off). Single-, 2- and 3-poleCHP breakers rated 10 to 70 amperesare recommended for applicationsrequiring a breaker center trip position.

    Unique two-position trip. Helps to eliminate nuisance callbacks, breaker trips to “OFF,” homeowner simply turns to “ON,” no reset required.

    Plated steel latch lever provides load force for quick and reliable tripping during a thermal or magnetic trip condition.

    Latch spring provides consistent relatching operation of the breaker trip mechanism.

    Heavy-duty over-center toggle spring to ensure a quick and reliable “make-break” action.

    Tin-plated copper contact stabs for good conductivity and quick installations.

    Contact clip springfor solid bus stab connection. Eliminates expansion during envi-ronmental changes.

    Large silver tungsten contacts for good contact wear and conductivity.

    Magnetic armature place-ment spring ensures con-sistent low instantaneous trip on 15 and 30 ampere breakers.

    Calibrated one-piece bimetal for reliable thermal protection.

    Magnetic armature – assists in the instanta-neous tripping for short circuit protection.

    Glass polyester base and cover for superior con-struction and durability. One-piece molded base allows for repeatable quality every time.

    Heavy duty tin-plated copper box lugs for load termination. Rated for two 60/75 °C wire conductors.

    Calibration screw (under UL label) provides for accurate and predictable protection every time. Factory calibrated.

    Zinc-plated magnetic pole piece – works with magnetic armature to provide instantaneous tripping for short circuit protection.

    Large gas port allowing short circuit gases to safely exit the circuit breaker.

    All internal metal components are plated to provide a 100% non-corrosive circuit breaker.

    CH Breaker Section View

  • Page 7

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE CHCIRCUITBREAKERSPlug-On Circuit BreakersSpecial Application Plug-On Circuit BreakersType CH Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AICAmpereRating

    Wire Size RangeCu/Al60ºC or 75°C

    1-Pole 120/240V AC

    Requires One 3/4-inch (19.1 mm)Space

    2-Pole 120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    3-Pole 240V ACCommon TripRequires Three 3/4-inch (19.1 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC 10,000 AIC

    Catalog Number Catalog Number Catalog Number

    10 15 20 25 30

    (1) #14 – 8 1(2) #14 – 10 12(1) #14 – 6 3

    CH110CH115 45CH120 45CH125 5CH130 5

    CH210CH215 5CH220 5CH225 5CH230 5

    CH310CH315 5CH320 5CH325 5CH330 5

    35 #14 – 2 1#14 – 6 3

    CH135 5 CH235 5 CH335

    40 45 50 60 70 80 90100110125150

    #10 – 1/0 6#14 – 2 7#3/0 8

    CH140 5CH145 5CH150 5CH160 5CH170——————

    CH240 5CH245 5CH250 5CH260 5CH270CH280CH290CH2100CH2110CH2125CH2150 9

    CH340 5CH345 5CH350 5CH360 5CH370CH3080CH3090CH3100———

    CH Neutral Switching Breakers — 10,000 Amperes Interrupting Capacity — 120 or 120/240V ACType CH Neutral Switching Breakers, 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AICUsed to open the neutral along power line(s) for applications of gas pumps.

    1 For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space. 2 Switching duty rated.

    AmpereRating

    Wire SizeRangeCu/Al60ºC or 75°C

    2-Pole120V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    3-Pole120/240V ACCommon TripRequires Three 3/4-inch (19.1 mm) Spaces

    1 per Individual Carton 1 per Individual Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    1520304050

    #14 – 8 CH215SW 1CH220SW 1CH230SW 1CH240SW 1CH250SW 1

    CH315SW 2CH320SW 2CH330SW 2CH340SW 2CH350SW 2

    Neutral InNeutral Out(Hot leg)

    Neutral InNeutral OutPhasePhase

    CH-HID Circuit Breakers — 10,000 Amperes Interrupting Capacity — 120, 120/240 or 240V ACType CH-HID Circuit Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AICSuitable for use in circuits for fluorescent and High Intensity Discharge lighting. Also suitable for HACR applications.

    1 CH215HID is rated for 120/240V.

    AmpereRating

    Wire SizeRangeCu/Al60ºC or75°C

    1-Pole120/240V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    3-Pole240V ACCommon TripRequires Three 3/4-inch (19.1 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC 10,000 AIC

    Catalog Number Catalog Number Catalog Number

    152030

    #14 – 8 CH115HIDCH120HIDCH130HID

    CH215HID 1CH220HIDCH230HID

    CH315HIDCH320HIDCH330HID

    1 For 1- and 2-pole breakers.2 Solid and stranded wire can be used together.3 For 3-pole breakers.4 Switching duty rated.5 HACR rated.6 1-pole 60 – 70 amperes, 2-pole 80 – 125

    amperes, 3-pole 40 – 100 amperes.7 1-pole 40 – 50 amperes, 2-pole 40 – 70

    amperes.8 2-pole 150 amperes.9 CH2150 requires 4-pole spaces and is

    not suitable for use on 3-phase panels, not CSA certified.

    Plug-on Circuit Breakers

    Plug-On Circuit Breakers, Type CH10,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC

  • Page 8

    TYPE CH

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    Special Application Plug-On Circuit Breakers

    Plug-On Ground Fault Circuit Breakers, Type CH 10,000 Amperes Interrupting Capacity 120 or 120/240V AC

    Ground Fault Application NotesSingle-pole Type CHGFIs are designed for use in 2-wire, 120V AC circuits. Figure 4 shows a typical wiring configuration.

    Two-pole Type CHGFIs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multiwire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source.

    Figure 5 and Figure 6 illustrate typical wiring configurations for 120/240V AC multiwire circuits.

    Figure 7 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit.

    The figures are shown with a 120/240V AC, single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures the electrical operation of the Type CHGFI is not affected by the equipment ground.

    Type CH 1-Pole Type CH 2-Pole

    Type CH Ground Fault Circuit Breakers (5 Milliampere)3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    1 60 ampere breaker listed for 75°C Cu wire only.

    Type CH Ground Fault Equipment Protection Circuit Breakers (30 Milliampere)3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    1 60 ampere breaker listed for 75°C Cu wire only.

    Figure 4. 1-Pole

    Figure 5. 2-Pole

    AmpereRating

    Wire SizeRangeCu/Al60ºC or75°CAWG

    1-Pole120V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    1 per Shelf Carton 1 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    152025303540455060

    #14 – 6 1 CH115GFCH120GFCH125GFCH130GF—————

    CH215GFCH220GFCH225GFCH230GFCH235GFCH240GFCH245GFCH250GFCH260GF

    AmpereRating

    WireSizeRangeCu/Al60ºC or75°CAWG

    1-Pole120V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    1 per Shelf Carton 1 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    15202530405060

    #14 – 6 1 CH115EPDCH120EPDCH125EPDCH130EPD———

    CH215EPDCH220EPD—CH230EPDCH240EPDCH250EPDCH260EPD

    Figure 6. 2-Pole

    Figure 7. 2-Pole

  • Page 9

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE CHCIRCUITBREAKERSSpecial Application Plug-On Circuit Breakers

    Plug-On Arc Fault Circuit Breakers, Type CH 10,000 Amperes Interrupting Capacity 120 or 120/240V AC

    Type CH 1- and 2-PoleAFCI Circuit Breakers

    Type CH FIRE-GUARD™ AFCI Circuit Breakers3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    1 Common trip refers to 2-pole 240V load application sourced by 120/240V AC (see Figure 10).2 Independent trip refers to 2-pole shared neutral circuits (see Figure 9 and Figure 11).

    Figure 8. 1-Pole Single 120V Load Application Sourced by 120/240V AC

    Figure 9. 1-Pole Shared Neutral with Multi-Duplex Receptacle Application

    Poles AmpereRating

    Configuration Catalog Number

    Wire Size Range Cu/Al60ºC or 75ºC AWG

    1-Pole10 kAIC

    15 AFCI AFCI with GFCI

    CH115AFCH115AFGF

    #14 – 6

    20 AFCI AFCI with GFCI

    CH120AFCH120AFGF

    #14 – 6

    2-Pole10 kAIC 12

    15 AFCI Common TripAFCI Independent TripAFCI Common Trip with GFCI

    CH215AFCH215AFITCH215AFGF

    #14 – 6

    20 AFCI Common TripAFCI Independent TripAFCI Common Trip with GFCI

    CH220AFCH220AFITCH220AFGF

    #14 – 6

    N A B

    120/240V ACSource

    120VDuplexReceptacle

    1 Pole

    Line B

    Neutral

    Neutral

    Equipment Ground

    N A B

    120/240V ACSource

    2-120VDuplexReceptacles

    2 Pole

    Line B

    Line A

    Neutral

    Neutral

    Equipment Ground

    Figure 10. 2-Pole 240V Load Application Sourced by 120/240V AC

    Figure 11. 2-Pole Shared Neutral with Duplex Receptacle Application

    Line B

    N A B

    120/240V ACSource

    Line A 240VDuplexReceptacle

    2 Pole

    Neutral

    Equipment Ground

    N A B

    120/240V ACSource

    Line A

    120V DuplexReceptacle(With Line SideJumper Removed)

    2 Pole

    Line B

    Neutral

    Neutral

    Equipment Ground

  • Page 10

    TYPE CH

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    Special Application Plug-On Circuit Breakers

    CHP Commercial Breakers — 10,000 Amperes Interrupting Capacity120, 120/240 or 240V ACNote: CHP Breakers feature on-off and trip positions for commercial applications

    Type CHP Breakers, 3/4-inch (19.1 mm) per Pole 120, 120/240 or 240V AC, 10,000 AICNote: CHP Breakers offer on-off and trip positions for commercial applications

    1 For 1- and 2-pole breakers.2 Solid and stranded wire can be used together.3 For 3-pole breakers.4 Switching duty rated.5 HACR rated.6 1-pole 60 – 70 amperes, 2-pole 80 – 125 amperes, 3-pole 40 – 100 amperes.7 1-pole 40 – 50 amperes, 2-pole 40 – 70 amperes.

    CHP-GFCI Circuit Breakers — 10,000 Amperes Interrupting Capacity 120 or 120/240V ACNote: CHP Breakers offer on-off and trip positions for commercial applications.

    Type CHP-GFCI Breakers — 5 Milliampere — 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AICNote: CHP Breakers offer on-off and trip positions for commercial applications.

    AmpereRating

    Wire Size RangeCu/Al60ºC or 75°CAWG

    1-Pole120/240V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    3-Pole240V ACCommon TripRequires Three 3/4-inch (19.1 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC 10,000 AIC

    Catalog Number Catalog Number Catalog Number

    10 15 20 25 30

    (1) #14 – 8 1(2) #14 – 10 12(1) #14 – 6 3

    CHP110CHP115 45CHP120 45CHP125 5CHP130 5

    CHP210CHP215 5CHP220 5CHP225 5CHP230 5

    CHP310CHP315 5CHP320 5CHP325 5CHP330 5

    35 #14 – 2 1#14 – 6 3

    CHP135 5 CHP235 5 CHP335 5

    40 45 50 60 70 80 90100110125

    #10 – 1/0 6#14 – 2 7

    CHP140 5CHP145 5CHP150 5CHP160 5CHP170—————

    CHP240 5CHP245 5CHP250 5CHP260 5CHP270CHP280CHP290CHP2100CHP2110CHP2125

    CHP340 5CHP345 5CHP350 5CHP360 5CHP370——CHP3100——

    AmpereRating

    Wire Size RangeCu/Al 60ºC or 75°CAWG

    1-Pole120V ACRequires One 3/4-inch (19.1 mm) Space

    1 per Individual Carton

    10,000 AIC

    Catalog Number

    152030

    #14 – 6#14 – 6#14 – 6

    CHP115GFCHP120GFCHP130GF

    Ground Fault Application NotesSingle-pole Type CHP-GFI breakers are designed for use in 2-wire, 120V AC circuits. Figure 12 shows a typical wiring configuration.

    The figure is shown with a 120/240V AC, single-phase, 3-wire power source, but a 120/208V AC, 3-phase, 4-wire power supply is also applicable. Electrical operation of the Type CHPGFI is not affected by the equipment ground.

    Figure 12. Typical 1-Pole Wiring Diagram

  • Page 11

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE CHCIRCUITBREAKERSSpecial Application Plug-On Circuit Breakers

    CHP Neutral Switching Breakers 10,000 Amperes Interrupting Capacity 120 or 120/240V ACType CHP Neutral Switching Breakers, 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AICUsed to open the neutral along power line(s) for applications of gas pumps.

    1 For circuit breakers with shunt trip, add ST suffix. Shunt trip requires one additional pole space.

    CH-M50 High Ambient BreakerType CH-M50 High Ambient Breakers 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    CH-HM and CHP-HM High Magnetic BreakersType CH-HM and CHP-HM High Magnetic Breakers 3/4-inch (19.1 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    AmpereRating

    WireSizeRangeCu/Al60ºC or75°CAWG

    2-Pole120V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    3-Pole120/240V ACCommon TripRequires Three 3/4-inch (19.1 mm) Spaces

    1 per Shelf Carton 1 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    1520

    #14 – 8 CHP215SW 1CHP220SW 1

    CHP315SW 1CHP320SW 1

    AmpereRating

    Wire Size Range Cu/Al60ºC or 75°CAWG

    1-Pole120/240V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    15202530354045506070

    (1) #14 – 8(2) #14 – 10

    CH115M50CH120M50CH125M50CH130M50CH135M50CH140M50CH145M50CH150M50——

    CH215M50CH220M50CH225M50CH230M50CH235M50CH240M50CH245M50CH250M50CH260M50CH270M50

    AmpereRating

    Wire Size RangeCu/Al60ºC or 75°CAWG

    1-Pole120/240V AC

    Requires One 3/4-inch (19.1 mm) Space

    2-Pole120/240V ACCommon TripRequires Two 3/4-inch (19.1 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number Catalog Number

    1520

    (1) #14 – 8(2) #14 – 10

    CH115HMCH120HM

    CH215HMCH220HM

    1520

    (1) #14 – 8(2) #14 – 10

    CHP115HMCHP120HM

    CHP215HMCHP220HM

    Neutral InNeutral Out(Hot leg)

    Neutral InNeutral OutPhasePhase

  • Page 12

    TYPE CH

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    Accessories

    CHML

    CHSF3125

    CHSF2125

    CHPL

    Circuit Breaker Accessories

    Main and Sub-Feed Lug Blocks

    1 Must be purchased in multiples of ordering quantities indicated.2 Handle Ties: Typically used to join two similar independent single-pole breakers to form a 2-pole

    noncommon trip breaker.3 Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or

    “Off” position.4 Requires one additional pole space.5 Escutcheon Mounted: Device mounted semipermanently to the face of the circuit breaker and

    secured by the loadcenter deadfront.6 Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off”

    position. Handle Lockdogs are not padlockable devices.7 Handle Mounted: Device mounted above or below handle using spring pressure.8 Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main

    application. See NEC Article 384-16(g).9 Add suffix indicated to end of breaker catalog number.

    Description Ordering Quantity 1

    Catalog Number

    Handle Ties 2Handle tie bar for physically joining the handles of two adjacent 1-pole

    Type CH Circuit Breakers. (Molded Plastic Handle Cover) 25 CHHT

    Handle Lockoffs 34Padlockable device for locking the handle of 1-, 2-, or 3-pole

    Type CH Circuit Breakers (Escutcheon Mounted) 5 Padlockable device for locking the handle of a 1-, 2- or 3-pole

    Type CHGFI Circuit Breaker. (Escutcheon Mounted) 5

    1

    1

    CHPL

    CHPLGF

    Handle Lockdogs 46Device used to secure handle in “On” or “Off” position for

    1-pole Type CH Circuit Breakers. (Handle Mounted) 7 10 CHLO

    Hold-Down Kits 8Hold-down retainer kit for 1-, 2-, 3-pole Type CH Circuit Breakers. For

    6 – 24 circuit 125 ampere single- and 3-phase, 12 – 42 circuit single-phase 225 ampere and 24 – 42 circuit 3-phase 225 ampere MLO Type CH Loadcenters. 1 CH125RB

    Hold-Down Kits 8Hold-down retainer kit for 1-, 2-, 3-pole Type CH Circuit Breakers

    for 2 through 4 circuit MLO CH Loadcenters. 1 CH125RB24

    Mechanical InterlockType CH for 2-, 3- and 4-pole Breakers 10 CHML

    Shunt Trip for CH120V AC 1 ST 9

    Number of Poles

    Ampere Rating

    Number of 3/4-inch (19.1 mm)Spaces Needed

    Wire Size RangeCu/Al 60ºC or 75ºCAWG

    Ordering Quantity

    Catalog Number

    23

    125125

    23

    #1/0#1/0

    1 1

    CHSF2125CHSF3125

    CHHT

    CHPLGF

    CHLO

    CH125RB

  • TYPE CH ASSEMBLIESPage 13

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    70 AMP 2 SPACES 2 SINGLE POLES

    Single-Phase Single-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    DIAGRAM 1

    CH9MB270

    125 AMP 2 SPACES 2 SINGLE POLESDIAGRAM 2

    CH2L125INT

    2.000(50.80)

    2.250(57.15)

    3.563(90.50)

    2.688(68.28)

    1.063(26.99)

    Wire Range:(1) 2/0 - 14 AWG (Al/Cu)

    .598(15.19)

    MaximumHandleHeight

    2.844(72.24)

    .625(15.88)

    .156 Diameter Nib .031 x 45° Chamfer

    1 Nib Required

    1.812(46.02)

    4.588(116.54)

    1.782(45.26)

    .183(4.65)

    3.700(93.98)

    3.000(76.2)

    #10 MountingScrews

    .297(7.54)

    .156(3.96)

    .188(4.78)

    1.680(42.67)

    1.500(38.10)

    0.750(19.05)

    0.937(23.80)

    #8 - #2 AWG (Al/Cu)

    0.685(17.40)

    0.500(12.70)

    3.805(96.65)

    3.087(78.41)

    3.850(97.79)

    2.190(55.63)

    1.410(35.81)

    .188(4.78)

    0.200 ± 0.005 Diameter(5.08 ± 0.13)

    0.200 ± 0.005 Diameter(5.08 ± 0.13)

    MaximumHandleHeight

    Dimensions – Inches (mm)

    Legend

  • TYPE CH ASSEMBLIES

    Dimensions – Inches (mm)

    Legend

    Page 14

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    125 AMP 4 SPACES 4 SINGLE POLESDIAGRAM 3 DIAGRAM 4

    125 AMP 8 SPACES 8 SINGLE POLES

    CH4L125INT

    CH8L125INT

    1.063(26.99)

    2.250(57.15)

    2.844(72.24)

    1.625(41.28)

    .156 Diameter Nib .031 x 45° Chamfer

    1 Nib Required

    1.182(30.02)

    2.000(50.80)

    3.563(90.50)

    Wire Range:(1) 2/0 - 14 AWG (Al/Cu)

    #10 MountingScrews

    2.688(67.28)

    4.666(118.52)

    3.311(84.10)

    .781(19.84)

    2.041(51.84)

    6.332(160.83)

    MaximumHandleHeight

    .183(4.65)

    .188(4.78)

    .203 Diameter(5.16)

    .250(6.35)

    .169 Diameter(4.29)

    .169 Diameter(4.29)

    5.56(141.22)

    5.00(127.00)

    MaximumHandleHeight

    3.125(79.38)

    1.439(36.55)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.172(55.17)

    .203 Diameter(5.16)

    .750(19.05)

    .780(19.81)

    .780(19.81)

    6.00 (152.40)

    3.125(79.38)

    Wire Range:(1) 4/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.52(38.61)

    3.125(79.38)

  • TYPE CH ASSEMBLIESPage 15

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    125 AMP 12 SPACES 12 SINGLE POLESDIAGRAM 5

    125 AMP 16 SPACES 16 SINGLE POLESDIAGRAM 6

    CH12L125INT

    CH16L125INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    9.250(234.95)

    8.400(213.36)

    MaximumHandleHeight

    3.256(82.70)

    1.439(36.55)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    2.172(55.17)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:2/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.610(40.90)

    C Lbreaker

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    7.750(196.85)

    7.000(177.80)

    MaximumHandleHeight

    3.125(79.38)

    1.439(36.55)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    2.172(55.17)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:2/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.610(40.90)

    C Lbreaker

  • TYPE CH ASSEMBLIES

    Dimensions – Inches (mm)

    Legend

    Page 16

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    200 AMP 12 SPACES 12 SINGLE POLESDIAGRAM 7

    200 AMP 16 SPACES 16 SINGLE POLESDIAGRAM 8

    CH12L200INT CH16L200INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    13.625(346.08)

    12.875(327.03)

    MaximumHandleHeight

    3.124(79.35)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

    C Lbreaker

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    13.625(346.08)

    12.875(327.03)

    MaximumHandleHeight

    3.124(79.35)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

    C Lbreaker

  • TYPE CH ASSEMBLIESPage 17

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    225 AMP 24 SPACES 24 SINGLE POLESDIAGRAM 9

    225 AMP 32 SPACES 32 SINGLE POLESDIAGRAM 10

    CH24L225INT

    CH32L225INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    13.625(346.08)

    12.875(327.03)

    MaximumHandleHeight

    3.124(79.35)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

    .218 Diameter(5.54)

    .310(7.87)

    MaximumHandleHeight

    3.124(79.35)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    .218 (5.54)

    15.875(403.23)

    15.025(381.64)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

  • TYPE CH ASSEMBLIES

    Dimensions – Inches (mm)

    Legend

    Page 18

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    225 AMP 42 SPACES 42 SINGLE POLESDIAGRAM 11

    CH42L225INT

    .218 (5.54)

    19.625(498.48)

    18.875(479.43)

    .218 Diameter(5.54)

    .310(7.87)

    MaximumHandleHeight

    3.125(79.38)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

  • TYPE CH ASSEMBLIESPage 19

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    125 AMP 12 SPACES 12 SINGLE POLESDIAGRAM 12

    Three-Phase Double-Row Breaker Mounting – Copper Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

    125 AMP 18 SPACES 18 SINGLE POLESDIAGRAM 13

    CH12L3125INT

    CH18L3125INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    7.750(196.85)

    7.000(177.80)

    MaximumHandleHeight

    Wire Range:2/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.685(42.80)

    1.440(36.58)

    1.440(36.58)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.172(55.17)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    1.610(40.90)

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    10.750(273.05)

    10.000(254.00)

    MaximumHandleHeight

    1.685(42.80)

    1.440(36.58)

    1.440(36.58)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.172(55.17)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:2/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.610(40.90)

  • TYPE CH ASSEMBLIES

    Dimensions – Inches (mm)

    Legend

    Page 20

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Three-Phase Double-Row Breaker Mounting – Copper Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

    125 AMP 24 SPACES 24 SINGLE POLESDIAGRAM 14

    225 AMP 24 SPACES 24 SINGLE POLESDIAGRAM 15

    CH24L3225INT

    CH24L3125INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    12.250(311.15)

    11.500(292.10)

    MaximumHandleHeight

    1.685(42.80)

    1.440(36.58)

    1.440(36.58)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.172(55.17)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:2/0 - #6 AWG (Al/Cu)Torque Wire Screws*

    1.610(40.90)

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    13.625(346.08)

    12.875(327.03)

    MaximumHandleHeight

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    1.674(42.52)

    1.451(36.86)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    2.010(51.05)

  • TYPE CH ASSEMBLIESPage 21

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    225 AMP 30 SPACES 30 SINGLE POLESDIAGRAM 16

    225 AMP 42 SPACES 42 SINGLE POLESDIAGRAM 17

    Three-Phase Double-Row Breaker Mounting – Copper Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

    CH30L3225INT

    CH42L3225INT

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    15.875(403.23)

    15.025(381.64)

    MaximumHandleHeight

    1.687(42.85)

    1.438(36.53)

    1.438(36.53)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lbreaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

    .218 Diameter(5.54)

    .218 (5.54)

    .310(7.87)

    19.625(498.48)

    18.875(479.43)

    MaximumHandleHeight

    1.674(42.52)

    1.451(36.86)

    1.451(36.86)

    3.961(100.61)

    3.324(84.43)

    .188 (4.78)

    C Lof breaker

    2.797(71.04)

    .750(19.05)

    6.249 (158.72)

    3.125(79.38)

    Wire Range:(1) 300 kcmil - #4 AWG (Al/Cu) Torque Wire Screws: 225 lb-in

    2.010(51.05)

  • TYPE BR ASSEMBLIESPage 22

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    OEM Loadcenter Interior Assemblies

    Catalog Numbering System

    Bulk Pack / C Indicates Copper BusAmpere RatingSingle-Phase: Blank / Three-Phase: 3

    Maximum SpacesMaximum Single PolesInterior

    12 24 INT 3 125 B

    70 2 4 E8741 (1) #8–#2 AWG Cu/Al 20 24INT70B 18 32

    125 2 4 E8741 (1) 1/0–#14 AWG Cu 20 24INT125B 19 32 2/0–12 AWG Al

    125 6 12 E52977 (1) 2/0–#14 AWG Cu/Al 20 612INT125SRB 20 33

    Single-Phase Single-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire 125 4 8 E8741 (1) 2/0–#14 AWG Cu/Al 20 48INT125B 21 34

    125 6 12 E8741 (1) 2/0–#14 AWG Cu/Al 20 612INT125B 22 34

    125 8 16 E8741 (1) 2/0–#14 AWG Cu/Al 20 816INT125B 23 35

    125 12 12 E52977 (1) 2/0–#14 AWG Cu/Al 20 1212INT125B 24 35

    125 12 24 E52977 (1) 2/0–#14 AWG Cu/Al 20 1224INT125B 25 36

    125 16 24 E52977 (1) 2/0–#14 AWG Cu/Al 20 1624INT125B 26 36

    125 20 24 E52977 (1) 2/0–#14 AWG Cu/Al 10 2024INT125B 27 37

    125 24 24 E52977 (1) 2/0–#14 AWG Cu/Al 10 2424INT125B 28 37

    200 8 16 E52977 (1) 300 kcmil –#1 AWG Cu/Al 20 816INT200B 29 38

    200 12 24 E52977 (1) 300 kcmil –#1 AWG Cu/Al 20 1224INT200B 30 38

    200 30 40 E52977 (1) 300 kcmil –#1 AWG Cu/Al 10 3040INT200B 31 39

    225 42 42 E52977 (1) 300 kcmil –#1 AWG Cu/Al 10 4242INT225B 32 39

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire 125 8 16 E52977 (1) 2/0–#14 AWG Cu/Al 20 816INT125BC 33 40

    125 12 12 E52977 (1) 2/0–#14 AWG Cu/Al 20 1212INT125BC 34 40

    200 12 24 E52977 (1) 300 kcmil –#1 AWG Cu/Al 20 1224INT200BC 35 41

    Three-Phase Double-Row Breaker Mounting – Aluminum Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125 12 24 E52977 (1) 2/0–#8 AWG Cu/Al 10 1224INT3125B 36 42

    150 18 36 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 1836INT3150B 37 42

    150 24 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 2442INT3150B 38 43

    200 30 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 3042INT3200B 39 43

    225 42 42 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 4242INT3225B 40 44

    Three-Phase Double-Row Breaker Mounting – Copper Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta 125 12 24 E52977 (1) 2/0–#8 AWG Cu/Al 10 1224INT3125BC 41 45

    200 12 24 E52977 (1) 300 kcmil–#2 AWG Cu/Al 10 1224INT3200BC 42 45

    Ampere Maximum Number UL Main Terminal Wire Size Range Standard Catalog Diagram ReferenceRating 1-Inch (24.5 mm) File (Per Phase) Package Number Spaces Single Poles Reference Cu/Al 60°C or 75°C Quantity Number Page

    Type BR Loadcenter Interior Assemblies

  • TYPE BR ASSEMBLIESPage 23

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Loadcenter Accessories

    B

    A .269(6.83)

    .844(21.44)

    2.360(59.94)

    CL of Mounting Hole CL of Mounting Hole

    1.187(30.15)

    1.182(30.02)

    B

    A

    2.000(50.80)

    .156(3.96)

    .688(17.47)

    CLof

    MountingHole

    .269(6.83)

    .344(8.74)

    .844(21.44)

    2.360(59.94)

    1.750(44.45)

    2.860(72.64)

    .250(6.35)

    .182 Diameter(4.62)

    .120(3.05)

    1.750(44.45)

    .750(19.05)

    .344(8.74)

    CL of Mounting Hole

    B

    A

    Figure 13

    Figure 15

    Figure 14

    Add-on Lugs for Neutral Assemblies

    Ground Bar Kits

    1 Must be purchased in multiples of ordering quantities indicated.2 Distance between mounting holes is 1-3/4 inches (44.5 mm).3 For 1- and 3-phase 400 and 600 ampere applications.4 Distance between mounting holes is 2-11/32 inches (59.5 mm).

    Description Wire Size RangeCu/Al 60°C or 75°C

    OrderingQuantity 1

    CatalogNumber

    Neutral/Ground LugAdd-On Neutral or Ground Lug

    #2/0 Maximum#3/0 Maximum300 kcmil Maximum

    111

    NL20NL30NL300

    Description(See Legend)

    LengthInches (mm)

    OrderingQuantity 1

    CatalogNumber

    dssssds

    dssssdsj

    dssssdssssss

    dssssdssssssj

    dssssdssssssssss

    dssssdssssssssssj

    dssssdsssssssssssssssss

    dssssdsssssssssssssssssj

    ofodofooofodofooofo

    2.54 (64.5)3.59 (91.2)4.29 (109.0)5.34 (135.6)4.61 (117.1)5.69 (144.5)6.74 (171.2)8.14 (206.8)9.19 (233.4)5.78 (146.8)

    1111111111

    GBK5 2GBK520 2GBK10 2GBK1020 2GBK13 2GBK14 2GBK1420 2GBK21 2GBK2120 2BRGBK39512 34

    f d f f f k f d f k f f f Ground Bar Legends

    j

    o

    d

    (3) #14 – #10 Cu/Al or (1) #14 – #4 Cu/Al(1) #6 – 2/0 Cu/Al(1) #14 – #6 Cu/Al or (2) #14 – #12 Cu/Al(1) 1/0 – 14 or (3) #10 – 12 Cu/Al(1) #14 – 1/0 Cu/Al or (3) #14 – #10 Cu/Al(1) #6 – 14 Cu/Al or (2) #1/0 – 14 Cu/AlMounting Hole

    f

    f

    GBK14

    BRGBK39512

    k

    Neutral AssembliesAmpere UL Main Incoming Terminal Number of Terminals Standard Catalog Dimensions – Inches (mm)Rating File Wire Size Range Package Number

    Reference 60°C or 75°C Quantity

    125 E52977 #6–1/0 AWG Cu 10 – 20 10NEU125B 13 5.938 (150.83) 5.400 (137.16)#6–2/0 AWG Al

    125 E52977 #6–1/0 AWG Cu 17 – 20 17NEU125B 13 8.388 (213.06) 7.850 (199.40)#6–2/0 AWG Al

    125 E52977 #6–1/0 AWG Cu 20 – 20 20NEU125B 13 9.438 (239.73) 8.900 (226.06)#6–2/0 AWG Al

    225 E52977 #1–300 kcmil Cu/Al 24 1 20 24NEU225B 14 10.913 (277.19) 10.300 (261.62)

    225 E52977 #1–300 kcmil Cu/Al 35 1 20 35NEU225B 14 15.813 (401.65) 15.200 (386.08)

    125 — — 4 2 1 BINA 15 2.266 (57.56) 0.594 (15.09)

    #14–4 AWG #6–1/0 AWG Cu Figure Overall Length MountingCu/Al #6–2/0 AWG Al A B

  • Page 24

    TYPE BR

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    BR Circuit BreakersCutler-Hammer Type BR plug-onbreakers in the standard 1-inch(25.4 mm) per pole package haveunique color-coded cases that indicateUL listed 10 kA or 22 kA interruptingratings and can be used as main orbranch disconnect devices. All are typeI.C. (interchangeable) devices; severalratings are SWD and HACR approved.Typical ampacity range for BRbreakers is 15 to 150 amperes.

    GFCB® People Protection BreakersCutler-Hammer Type GFCBs (groundfault circuit breakers) combine state-of-the-art electronic technology with acircuit breaker mechanism in acompact 1-inch (25.4 mm) per polepackage. The GFCB automaticallysenses hot wire-to-ground faults in a4 to 6 mA range and disconnects thepower, thus providing an extra marginof safety beyond that of conventionalcircuit breakers. GFCB applicationsinclude bathrooms, cellar outlets,swimming pools, outdoor branchcircuits and kitchen branch circuits.Available in UL listed 120 and 120/240Vratings. Cutler-Hammer also offersnon-UL listed GFCBs for internationalapplications as well as ground faultdevices for equipment protection.

    GFEP Equipment ProtectionBreakersThe Cutler-Hammer Type GFEP device issimilar to the GFCB, except that it isdesigned to protect equipment (notpeople) against damage from arcingground faults. It is available with a 30 mAtrip level. Applications include infraredheating equipment, computer equip-ment, process control equipment, etc.

    BJ Circuit BreakersAvailable in 125 through 200 ampereframes, Cutler-Hammer Type BJ plug-on breakers have 10 kA and 22 kAinterrupting ratings that can be usedas main or branch disconnect devices.Large extruded aluminum box lugs,complies with UL486B, provide cooloperation. Tripping mechanism hasthermal and magnetic protection forlong-life performance. Rupture gas issafely vented into box gutter.

    BD Circuit BreakersBD plug-on breakers have the sameconstruction as Cutler-Hammer Type BR1-inch (25.4 mm) per pole devicesexcept that two poles are in a space-saving 1-inch (25.4 mm) package.

    UL listed interrupting rating is 10 kA.Some ratings are SWD and HACRapproved. Exclusive CTL rejectionfeature allows only 42 circuits in thepanel in compliance with NEC Article384-15.

    BQ Circuit BreakersQuadplex® construction of Cutler-Hammer Type BQ plug-on breakersincorporates two duplex breakersassembled together to provide variouscombinations of 2-pole and single-poledevices in a 2-inch (50.8 mm) package,and allows compliance with NEC Article240-20(b). The 2-pole combinations ofCutler-Hammer Type BQ breakers aremarked “independent trip” meaningthat each pole of a 2-pole device tripsindependently of the other, but may beactuated jointly by means of the handletie. Independent trip devices may onlybe used on 3-wire Edison circuits wherethe neutral is present.

    BQC Circuit BreakersQuadplex construction of Cutler-Hammer Type BQC plug-on breakersincorporates a special internalcommon trip cam. BQC breakers areavailable in several combinations of2-pole and single-pole deviceswherein the 2-pole circuits have aninternal common trip mechanism.These breakers are labeled “commontrip” and meet all the requirements ofUL489 paragraph 9.1 requiringmultipole breakers to have commontrip. Common trip breakers arerequired on all 240V circuits wherethere is no neutral present such aswater heaters, baseboard heat, airconditioners and other motorloads.

    Special Application BreakersAs the name implies, these devices aredesigned for special applications asrequired by the National Electrical Code®.

    Water Heater BreakerSome watthour meters incorporaterate register switches used in conjunc-tion with off-peak rates. Water heaterbreakers do not derive their circuitfrom the loadcenter stab. The line andload side of the breaker are fed toterminals on the breaker. Except forthese terminations, the device offersnormal circuit breaker protection.

    Switching Neutral BreakerPrimary application for the Cutler-Hammer switching neutral breaker isfor protection of process equipmentsuch as gas pumps that utilize flam-mable liquids. Non-automatic polebreaks the neutral power leg, minimiz-ing the danger of arc conditions.

    2-Pole Breakers 120V or More-to-GroundUsed on Delta distribution systems,these Type BR breakers are applied onphase legs where voltage-to-ground isabove 120V.

    Non-Automatic Molded Case SwitchIdentical to comparable circuit breakerframes with this exception: non-automatic molded case switches do nothave thermal or magnetic elements.

    Arc Fault Circuit Interrupters (AFCIs)Reduce the risk of fire by detectingand interrupting electrical arcing faultswhich standard thermal magneticbreakers cannot. For more informa-tion, see page 27.

    Heavy-duty mechanismspring for reliableoperation.

    Hardened cradle forpositive action underfault conditions.

    Non-abrasive integrallymolded pivot for quickmechanism response.

    One-piece movingcontact arm for quickon/off response.

    Heavy-duty line terminaland spring clip for quickload center installationand cool operation.

    Silver tungsten alloycontacts.

    Provision forhandle tie.

    Unique one-piece heavy-duty De-ionassembly for quick arc interruption.

    Black Molded Handle.

    Callibrated one-piece bimetal forreliable thermaltrip function.

    One-piece frameassembly fordimensional stabilityand reliable operation.

    Four-rivet constructionenhances strength andstructural integrity ofbreaker case.

    Common trip camassures simultaneouspole opening.

    Heavy-duty multi-strandflexible copper shunt forcool operation.

    UL 486B approved terminalassembly for use withcopper or aluminum wire.

    Large gas port for ventingshort circuit gases safelyinto load center gutter.

    One-piece moldedcase construction.

    Full width slot forchannel type leadcenter hold-downs.

    BR Breaker Section View

  • Page 25

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE BRCIRCUITBREAKERSPlug-On Circuit Breakers

    Plug-On Circuit Breakers, Types BR10,000/22,000/42,000 Amperes Interrupting Capacity 120, 120/240 or 240V AC

    BR120 BR215 BR320

    Type BR Breakers, 1-Inch (25.4 mm) per Pole 120, 120/240 or 240V AC, 10,000, 22,000 or 42,000 AICNote: All Type BR 1-, 2-, and 3-pole circuit breakers carry listing for HACR application. For circuit breakers with a shunt trip, add ST suffix.

    1 1-pole, 1-inch (25.4 mm) per pole circuit breakers are available with high magnetic setting for switching large tungsten lamp loads. Add-suffix H to catalog number.

    2 Switching duty rated.3 On the black handle breaker, add suffix “B” to the catalog number to obtain a tapped molded opening for proper use with hold-down kits.4 For use as a branch circuit breaker in 400 and 600 ampere panels only.

    AmpereRating

    Wire Size RangeCu/Al60°C or 75°CAWG

    1-Pole 120/240V AC Requires One 1-Inch (25.4 mm) Space

    2-Pole 120/240V AC Common Trip Requires Two 1-Inch (25.4 mm) Spaces

    3-Pole 240V ACCommon Trip Requires Three 1-Inch (25.4 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 22,000 AIC 10,000 AIC 22,000 AIC 42,000 AIC 10,000 AIC 22,000 AIC

    CatalogNumber

    CatalogNumber

    CatalogNumber

    CatalogNumber

    CatalogNumber

    CatalogNumber

    CatalogNumber

    10 15 20 25 30

    #14 – 4 BR110BR115 12BR120 12BR125BR130

    —BRH115BRH120BRH125BRH130

    BR210BR215 3BR220 3BR225 3BR230 3

    —BRH215BRH220BRH225BRH230

    —————

    BR310 BR315 12BR320 12BR325 BR330

    —BRH315 12BRH320 12BRH325BRH330

    35 40 45 50

    #14 – 4 BR135BR140—BR150

    BRH135BRH140BRH145BRH150

    BR235 3BR240 3BR245 3BR250 3

    BRH235BRH240 3BRH245BRH250 3

    ————

    BR335 BR340 BR345 BR350

    BRH335BRH340 BRH345BRH350

    55 #14 – 3 BR150 BRH155 BR255 BRH255 — BR355 BRH355

    60 70 80 90100110

    #4 – 1/0 BR160BR170————

    BRH160BRH170————

    BR260 BR270 BR280 BR290 BR2100 BR2110

    BRH260 BRH270 BRH280BRH290 BRH2100 BRH2110

    BRHH260 BRHH270 BRHH280 BRHH290 BRHH2100 BRHH2110

    BR360 BR370 BR380 BR390 BR3100—

    BRH360 BRH370 BRH380BRH390 BRH3100 —

    125150

    #4 – 2/0 ——

    ——

    BR2125 BR2150 4

    BRH2125 —

    BRHH2125 —

    ——

    ——

  • Page 26

    TYPE BR

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    Special Application Plug-On Circuit Breakers

    Ground Fault Application NotesSingle-pole GFCBs are designed for use in 2-wire, 120V AC circuits. Figure 16 shows a typical wiring configuration.

    Two-pole GFCBs are designed for use in 3-wire, 120/240V AC circuits, 120V AC multiwire circuits employing common, neutral and 2-wire, 240V AC circuits obtained from a 120/240V AC source.

    Figures 17 and 18 illustrate typical wir-ing configurations for 120/240V AC multiwire circuits.

    Figure 19 depicts a 240V AC, 2-wire circuit. Note the “panel neutral” conductor connects to the neutral bar, even though the neutral is not included in the load circuit. This connection is necessary to supply a 120V AC power source to the ground fault sensing circuit.

    The figures are shown with a 120/240V AC, single-phase, 3-wire power source, but are also applicable to a 120/208V AC, 3-phase, 4-wire power supply. For all figures, the electrical operation of the GFCB is not affected by the equipment ground.

    Type GFCB Ground Fault Circuit Breakers (5 Milliampere) 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC, 22,000 AIC

    1 Available with bell alarm or auxiliary switch. See circuit breaker accessories on Page 31.2 For use with copper wire only.

    Type GFEP Ground Fault Equipment Protectors (30 Milliampere)1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    Figure 16. 1-Pole

    Figure 17. 2-Pole

    AmpereRating

    Wire Size RangeCu/Al 60°C or 75°CAWG

    1-Pole120V ACRequires One 1-Inch (25.4 mm)Space

    2-Pole120/240V ACCommon TripRequires Two 1-Inch (25.4 mm) Spaces

    1 per Shelf Carton 1 per Shelf Carton

    10,000 AIC 22,000 AIC 10,000 AIC 22,000 AIC

    CatalogNumber 1

    Catalog Number

    152025304050

    #14 – 4 GFCB115GFCB120GFCB125GFCB130GFCB140—

    GFCBH115GFCBH120GFCBH125———

    GFCB215GFCB220GFCB225GFCB230GFCB240 2GFCB250 2

    GFCBH215GFCBH220GFCBH225GFCBH230——

    AmpereRating

    Wire Size RangeCu/Al 60°C or 75°CAWG

    1-Pole120V ACRequires One 1-Inch Space

    2-Pole120/240V ACCommon TripRequires Two 1-Inch Spaces

    1 per Shelf Carton 1 per Shelf Carton

    10,000 AIC 10,000 AIC

    Catalog Number

    Catalog Number

    152025304050

    #14 – 4 GFEP115GFEP120GFEP125GFEP130——

    GFEP215GFEP220GFEP225GFEP230GFEP240GFEP250

    Plug-On Ground Fault Circuit Breakers, Type GFCB and GFEP10,000/22,000 Amperes Interrupting Capacity120 or 120/240V AC

    Figure 18. 2-Pole

    Figure 19. 2-Pole

    Type GFCB 1-Pole

    Type GFCB 2-Pole

  • Page 27

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE BRCIRCUITBREAKERSSpecial Application Plug-On Circuit Breakers

    Plug-On Arc Fault Circuit Breakers, Type BR10,000 Amperes Interrupting Capacity120 or 120/240V AC

    Type BR 1- and 2-PoleAFCI Circuit Breakers

    Type BR FIRE-GUARD™ AFCI Circuit Breakers 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC

    1 Common trip refers to 2-pole 240V load application sourced by 120/240V AC (see Figure 22).2 Independent trip refers to 2-pole shared neutral circuits (see Figure 21 and Figure 23).

    Figure 20. 1-Pole, Single 120V Load Application Sourced by 120/240V AC

    Figure 21. 1-Pole Shared Neutral with Multi-Duplex Receptacle Application

    Poles AmpereRating

    Configuration CatalogNumber

    Wire Size Range Cu/Al60ºC or 75ºC AWG

    1-Pole10 kAIC

    15 AFCI AFCI with GFCI

    BR115AFBR115AFGF

    #14 – 4

    20 AFCI AFCI with GFCI

    BR120AFBR120AFGF

    #14 – 4

    2-Pole10 kAIC 12

    15 AFCI Common TripAFCI Independent TripAFCI Common Trip with GFCI

    BR215AFBR215AFITBR215AFGF

    #14 – 4

    20 AFCI Common TripAFCI Independent TripAFCI Common Trip with GFCI

    BR220AFBR220AFITBR220AFGF

    #14 – 4

    N A B

    120/240V ACSource

    120VDuplexReceptacle

    1 Pole

    Line B

    Neutral

    Neutral

    Equipment Ground

    N A B

    120/240V ACSource

    2-120VDuplexReceptacles

    2 Pole

    Line B

    Line A

    Neutral

    Neutral

    Equipment Ground

    Figure 22. 2-Pole 240V Load Application Sourced by 120/240V AC

    Figure 23. 2-Pole Shared Neutral with Duplex Receptacle Application

    Line B

    N A B

    120/240V ACSource

    Line A 240VDuplexReceptacle

    2 Pole

    Neutral

    Equipment Ground

    N A B

    120/240V ACSource

    Line A

    120V DuplexReceptacle(With Line SideJumper Removed)

    2 Pole

    Line B

    Neutral

    Neutral

    Equipment Ground

  • Page 28

    TYPE BR

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    CTL Plug-On Circuit Breakers, Type BD Duplex, BQ and BQC Quadplex10,000 Amperes Interrupting Capacity 120/240V AC

    Common Trip Quadplex BreakersClass CTL, 1-Inch (25.4 mm) per Pole 120/240V AC, 10,000 AIC — All circuit breakers have rejection tab feature.

    1 All Type BQC Quadplex circuit breakers carry listing for HACR applications.2 All 15 and 20 ampere single poles are switching duty rated.

    Figure 24. CTL and Non-CTL Breakers

    Type BQC Quadplex Common Trip Center Poles (UL Type BRD)

    Wire SizeRangeCu/Al65°C or75°CAWG

    Type BQC Quadplex Common Trip Center and Outer Poles (UL Type BRD)

    2-Pole 1 and 1-Pole 2

    2-Pole 1

    Requires Two 1-Inch (25.4 mm) Spaces Requires Two 1-Inch (25.4 mm) Spaces

    5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC

    120V AC 120/240V AC 120V AC CatalogNumber

    120/240V AC CatalogNumberAmpere Rating Ampere Rating

    Outer Left1-Pole

    Center 2-PolesCommon Trip

    Outer Right1-Pole

    Outer 2-PolesCommon Trip

    Center 2-PolesCommon Trip

    1515151515———

    2025304050———

    1515151515———

    BQC2202115BQC2252115BQC2302115BQC2402115BQC2502115———

    #14 – 4 1515152020202020

    1520301520304050

    BQC215215BQC215220BQC215230BQC220215BQC220220BQC220230BQC220240BQC220250

    202020202020

    152025304050

    202020202020

    BQC2152120BQC2202120BQC2252120BQC2302120BQC2402120BQC2502120

    #14 – 4 252530303030—

    253015304050—

    BQC225225BQC225230BQC230215BQC230230BQC230240BQC230250—

    30————

    50————

    20————

    BQC2502030————

    #14 – 4 4040405050

    3040502050

    BQC240230BQC240240BQC240250BQC250220BQC250250

    120V AC

    120V AC120/240V AC

    120/240V AC

    120/240V AC

    NotchedBus Stab

    UnnotchedBus Stab

    Type BR orType BD Duplex, (CTL),Type BQ and BQC Quadplex

    Type BR Notched Stab Non-CTL

    Non-CircuitLimiting Type BR

    Type BDDuplex

    CTL CircuitLimitingFeature

    RejectionTab

    BQC2302115 BQC230230

  • Page 29

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE BRCIRCUITBREAKERS

    Duplex and Independent Trip Quadplex BreakersClass CTL, 1-Inch (25.4 mm) per Pole 120 or 120/240V AC, 10,000 AIC — All circuit breakers have rejection tab feature.

    1 All 15 and 20 ampere single poles are switching duty rated.2 All Type BD Duplex and BQ Quadplex circuit breakers carry listing for HACR applications.

    Type BD Duplex (UL Type BRD)

    Wire Size RangeCu/Al 65°C or 75°CAWG

    Type BQ Quadplex Independent Trip (UL Type BRD)

    Type BQ Quadplex Independent Trip (UL Type BRD)

    1-Pole 1 2-Pole 2 and 1-Pole 1

    2-Pole

    Requires One 1-Inch (25.4 mm) Space

    Requires Two 1-Inch (25.4 mm) Spaces

    Requires Two 1-Inch (25.4 mm) Spaces

    10 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    AmpereRating

    10,000 AIC 10,000 AIC 10,000 AIC

    120V AC 120V AC 120/240V AC 120V AC CatalogNumber

    120/240V AC CatalogNumberCatalog

    NumberAmpere Rating Ampere Rating

    Outer Left1-Pole

    Center2-PolesIndependentTrip

    Outer Right1-Pole

    Outer2-PolesIndependentTrip

    Center2-PolesIndependentTrip

    10 – 1015 – 1515 – 2015 – 3020 – 1520 – 2020 – 3025 – 2530 – 1530 – 2030 – 3030 – 4030 – 5050 – 30

    BD1010BD1515BD1520BD1530BD2015BD2020BD2030BD2525BD3015BD3020BD3030BD3040BD3050BD5030

    #14 – 4 1520152015201520——————

    2020303040405050——————

    1520152015201520——————

    BQ2202115BQ2202120BQ2302115BQ2302120BQ2402115BQ2402120BQ2502115BQ2502120——————

    152020202025303030404050——

    152030405025304050405050——

    BQ215215BQ220220BQ220230BQ220240BQ220250BQ225225BQ230230BQ230240BQ230250BQ240240BQ240250BQ250250——

    120/240V AC120/240V AC

    120V AC

    120V AC120/240V AC

    120/240V AC

    120/240V AC

    BD2020 BQ2302115 BQ230230

  • Page 30

    TYPE BR

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    CIRCUITBREAKERS

    Plug-On Circuit BreakersSpecial Application Plug-On Circuit Breakers

    Plug-On Circuit Breakers, Types BJ and BJH10,000/22,000 Amperes Interrupting Capacity120/240 or 240V ACFor Use in 1-Phase and 3-Phase Loadcenters150 Amperes and Above

    Types BJ and BJH Breakers, 1-Inch (25.4 mm) per Pole, 120/240 or 240V AC, 10,000, 22,000 AICNote: If BJ or BJH breakers are used as a main or a back feed device, a hold-down kit is required. See Page 31.

    1 Breaker uses two 1-Inch (25.4 mm) pole spaces on left side and two 1-Inch (25.4 mm) pole spaces on right side of loadcenter.2 Breaker uses three 1-Inch (25.4 mm) pole spaces on left side and three 1-Inch (25.4 mm) pole spaces on right side of loadcenter.

    Plug-On Special Application Circuit Breakers10,000 Amperes Interrupting Capacity120, 120/240 or 240V AC

    Special Application Circuit Breakers, 1-Inch (25.4 mm) per Pole, 120, 120/240 or 240V AC

    AmpereRating

    2-Pole120/240V ACCommon TripRequires Four 1-Inch (25.4 mm) Spaces 1

    Wire SizeRangeCu/Al60°C or 75°C

    3-Pole240V ACCommon TripRequires Six 1-Inch (25.4 mm) Spaces 2

    10 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 22,000 AIC 10,000 AIC 22,000 AIC

    CatalogNumber

    CatalogNumber

    CatalogNumber

    CatalogNumber

    125150175200

    BJ2125BJ2150BJ2175BJ2200

    BJH2125BJH2150BJH2175BJH2200

    #2 AWG – 300 kcmil

    BJ3125BJ3150BJ3175BJ3200

    BJH3125BJH3150BJH3175BJH3200

    Water Heater Breakers Switching Neutral Breakers Wire SizeRangeCu/Al60°C or 75°CAWG

    240V Breakers Non-Automatic Molded Case Switches

    2-Pole120/240V ACCommon TripRequires Two 1-Inch (25.4 mm) Spaces

    2-Pole120V ACCommon TripRequires Two 1-Inch (25.4 mm) Spaces

    2-Pole240V ACCommon TripRequires Two 1-Inch (25.4 mm) Spaces

    2-Pole240V AC

    Requires Two 1-Inch (25.4 mm) Spaces

    With Isolated Line Terminals for Separately Metered Water Heaters

    With Switching Neutral Pole for Gasoline Pump Applications

    Where Voltage toGround is 240V AC

    For Use as Disconnect Contains No Magnetic or Thermal Trip Properties

    5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton 5 per Shelf Carton

    10,000 AIC 10,000 AIC 10,000 AIC 5,000 AIC

    AmpereRating

    CatalogNumber

    AmpereRating

    CatalogNumber

    AmpereRating

    CatalogNumber

    AmpereRating

    CatalogNumber

    152030———————

    BRWH215BRWH220BRWH230———————

    15202530——————

    BRSN215BRSN220BRSN225BRSN230——————

    #14 – 4 10 15 20 25 30 35 40 45 50 55

    BR210HBR215HBR220HBR225HBR230HBR235HBR240HBR245HBR250HBR255H

    ————————

    50—

    ————————BR250NA—

    —————

    —————

    —————

    —————

    #4 – 1/0 60 70 80 90100

    BR260HBR270HBR280HBR290HBR2100H

    60———100

    BR260NA———BR2100NA

    LINE

    LOADOUTIN

    NEUTRAL

    Type BJ

    BRWH215Water Heater Breaker

    BRSN220Switching Neutral Breaker

  • Page 31

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    TYPE BRCIRCUITBREAKERSAccessories

    Circuit Breaker Accessories

    FIeld Installation Kits and Parts

    1 Must be purchased in multiples of ordering quantities indicated.2 Handle Ties: Typically used to join two similar independent single-pole breakers to form a 2-pole noncommon trip breaker.3 Handle Lockoffs: Devices that use a padlock to lock the circuit breaker’s handle in the “On” or “Off” position.4 Escutcheon Mounted: Device mounted semipermanently to the face of the circuit breaker and secured by the loadcenter deadfront.5 Handle Mounted: Device mounted directly to the handle by the use of a set screw.6 Handle Lockdogs: Devices that are used to secure a circuit breaker’s handle in the “On” or “Off” position. Handle Lockdogs are not padlockable devices.7 Hold-Down Kits: Devices used to secure the circuit breaker to the loadcenter for back-feed main application. See NEC Article 384-16(g).8 Add suffix indicated to end of breaker catalog number.

    Description OrderingQuantity 1

    CatalogNumber

    Handle Ties 2Handle tie bar for physically joining the handles of two adjacent 1-pole

    Type BR Circuit Breakers. (Metal Cylinder Pin Type)Handle tie bar for joining two independent outside poles of Types BQ and

    BQC Quadplex and outside poles of two Type BD Duplex Circuit Breakers.Handle tie bar for joining two adjacent outside poles of Types BQ and BQC

    Quadplex and outside poles of two Type BD Duplex Circuit Breakers.

    10

    10

    10

    BHT

    THOW

    THS1

    Handle Lockoffs 3Padlockable device for locking the handle of 1-, 2-, or 3-pole Type BR

    Circuit Breakers and 1-pole of a Type BD Duplex or one independent outside pole of a Type BQ or BQC Quadplex Circuit Breaker. (Escutcheon Mounted) 4

    Padlockable device for locking the handle of a 1-pole Type BR Circuit Breaker. (Handle Mounted) 5

    Padlockable device for locking the handle of a 2- and 3-pole Type BR Circuit Breaker. (Handle Mounted) 5

    Padlockable device for locking the handle of a 1-pole Type BD Duplex, BQ or BQC Quadplex Circuit Breaker. (Handle Mounted) 5

    Padlockable device for locking the handle of the two center poles and the two outer poles of a 2-pole Type BQ and BQC of Type BQ and BQC Quadplex Circuit Breakers. (Escutcheon Mounted) 4

    10

    10

    10

    10

    10

    BRLW

    BRLW1

    BRLW2

    BRDL1

    BRQLW

    Handle Lockdogs 6Device used to secure handle in “On” or “Off” position for 1-, 2-, or 3-pole Type

    BR Circuit Breakers and 1-pole of Type BD Duplex and one independent outside pole of Type BQ or BQC Quadplex Circuit Breakers. (Escutcheon Mounted) 4

    Device used to secure handle in “On” or “Off” position for 1-pole Type BR Circuit Breakers. (Handle Mounted) 5

    Device used to secure handle in “On” or “Off” position for 2- and 3-poleType BR Circuit Breakers. (Handle Mounted) 5

    Device used to secure handle in “On” or “Off” position for 1-pole Type GFCB Ground Fault Circuit Breakers. (Handle Mounted) 5

    Device used to secure handle in “On” or “Off” position for one independent outside pole of Types BQ and BQC Quadplex or 1-pole Type BD Duplex Circuit Breakers. (Handle Mounted) 5

    10

    10

    10

    10

    10

    BHLW

    BHLW1

    BHLW2

    BHGW

    HLW1

    Hold-Down Kits 7Hold-down screw kit for 2-pole Type BR Circuit Breakers in 1-phase MLO

    Loadcenters through 125 amperes.Hold-down screw kit for 2-pole Type BR Circuit Breakers in MLO Loadcenters 150

    through 225 amperes (1-phase only).Hold-down screw kit for 2-pole Types BJ and BJH Circuit Breakers in MLO

    Loadcenters 125 through 225 amperes.Hold-down screw kit for 3-pole Types BJ and BJH Circuit Breakers in MLO

    Loadcenters 125 through 225 amperes.

    1

    1

    1

    1

    BREQS125

    BRHDK125

    BJHDS

    BJHDS3P

    Mechanical InterlocksTypes BR for 2-, 3- and 4-pole Breakers 10 BRML

    Shunt Trips for BR120V 1 ST 8

    Alarm Contacts for Type GFCB (1-Pole)Alarm Contact for GFCB (1-Pole)(1) N.O. and (1) N.C.

    1 1

    W1 8W2 8

    Numberof Poles

    AmpereRating

    Number of 1-inch (25.4 mm)Spaces Needed

    Wire Size RangeCu/Al 60°C or 75°C

    OrderingQuantity1

    CatalogNumber

    Main and Sub-Feed Lug Blocks2 125

    150225

    222

    #8 – 2/0 AWG#8 – 2/0 AWG#2 AWG – 300 kcmil

    1 1 1

    BRSF125BRSF150BRS225

    3 150225

    33

    #8 – 2/0 AWG#2 AWG – 300 kcmil

    1 1

    3BRSF1503BRS225

    BREQS125 BRHDK125

    THS1 BHLW2

    BRLW2

    BRQLW

    BHLW

    THOW (Installed) BRML

    BRSF125

    3BRS225

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 32

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Single-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    70 AMP 2 SPACES 4 SINGLE POLESDIAGRAM 18

    125 AMP 2 SPACES 4 SINGLE POLESDIAGRAM 19

    24INT70B

    24INT125B

    2.000(50.80)

    2.250(57.15)

    1.063(26.99)

    3.563(90.50)

    2.688(68.28)

    .703(17.86)

    #10 MountingScrews

    1.063(26.99)

    #2/0 to 12 AWG (Al)

    .625(15.88)

    MaximumHandleHeight

    3.545(90.04)

    3.000(76.20)

    .187(4.75)

    1.625(41.28)

    .297(7.54).625

    (15.88).156(3.96)

    .156 Diameter Nib .031 x 45° Chamfer

    1 Nib Required

    1.782(45.26)

    .183(4.65)

    4.359(110.72)

    1.812(46.02)

    2.000(50.80)

    2.250(57.15)

    1.063(26.99)

    3.563(90.50)

    2.688(68.28)

    1.782(45.26)

    1.812(30.02)

    4.359(110.72)

    .703(17.86)

    #10 MountingScrews

    1.063(27.00)

    #14 - 2 AWG (Al/Cu)

    .625(15.88)

    MaximumHandleHeight

    3.345(84.96)

    3.000(76.2)

    .156(3.96)

    .187(4.75)

    .156 Diameter Nib .031 x 45° Chamfer

    1 Nib Required

    1.625(41.28)

    .297(7.54).625

    (15.88)

  • TYPE BR ASSEMBLIESPage 33

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Single-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    125 AMP 6 SPACES 12 SINGLE POLESDIAGRAM 20

    612INT125SRB

    .218 (5.54)

    9.250(235.00)

    8.500(215.90)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    4.152(105.46)

    2.868(72.85)

    MaximumHandleHeight

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - 14 AWG (Al/Cu)

    .187 (4.75)

    ( )

    2.146(54.51)

    1.795(45.59)

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 34

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    125 AMP 4 SPACES 8 SINGLE POLESDIAGRAM 21

    48INT125B

    125 AMP 6 SPACES 12 SINGLE POLESDIAGRAM 22

    612INT125B

    2.250(57.15)

    1.063(26.99)

    2.688(68.28)

    1.812(46.02)

    5.874(149.20)

    .703(17.86)

    1.063(26.99)

    1.782(45.26)

    3.545(90.04)

    3.000(76.20)

    .625(15.88)

    MaximumHandleHeight

    #10 MountingScrews

    2.000(50.80)

    3.563(90.50)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    XXXX(XXXX)

    XXXX(XXXX)

    .187(4.75)

    .156 Diameter Nib .031 x 45° Chamfer

    1 Nib Required

    .218 (5.54)

    7.249(184.12)

    6.401(162.59)

    .220 Diameter(5.59)

    .310(7.87)

    C Lbreaker

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

  • TYPE BR ASSEMBLIESPage 35

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    125 AMP 8 SPACES 16 SINGLE POLESDIAGRAM 23

    816INT125B

    125 AMP 12 SPACES 12 SINGLE POLESDIAGRAM 24

    1212INT125B

    .218 (5.54)

    7.249(184.12)

    6.401(162.59)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

    .218 (5.54)

    9.250(235.00)

    8.500(215.90)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 36

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    125 AMP 12 SPACES 24 SINGLE POLESDIAGRAM 25

    1224INT125B

    125 AMP 16 SPACES 24 SINGLE POLESDIAGRAM 26

    1624INT125B

    .218 (5.54)

    9.250(235.00)

    8.500(215.90)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

    .218 (5.54)

    11.250(285.75)

    10.500(266.70)

    .220 Diameter(5.59)

    .310(7.87)

    2.388*(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    .187 (4.75)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

  • TYPE BR ASSEMBLIESPage 37

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    125 AMP 20 SPACES 24 SINGLE POLESDIAGRAM 27

    2024INT125B

    125 AMP 24 SPACES 24 SINGLE POLESDIAGRAM 28

    2424INT125B

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    .218 (5.54)

    13.250(336.55)

    12.500(317.50)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    C Lbreaker

    .218 (5.54)

    15.250(387.35)

    14.500(368.30)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 38

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    200 AMP 8 SPACES 16 SINGLE POLESDIAGRAM 29

    816INT200B

    200 AMP 12 SPACES 24 SINGLE POLESDIAGRAM 30

    1224INT200B

    .218 (5.54)

    9.625(244.48)

    8.875(225.43)

    .220 Diameter(5.59)

    .310(7.87)

    2.762(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.530(38.86)

    2.100(53.34)

    3.655(92.84)

    3.110(78.99)

    .187 (4.75)

    Wire Range:300 kcmil - #6 AWG (Al/Cu)

    2.671(67.84)

    MaximumHandleHeight

    1.391(35.33)

    2.954(75.03)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 300 kcmil - #6 AWG (Al/Cu)

    .187 (4.75)

    1.500(38.10)

    C Lbreaker

    MaximumHandleHeight

    1.391(35.33)

    2.954(75.03)

    3.655(92.84)

    3.110(78.99)

    Wire Range:300 kcmil - #1 AWG (Al/Cu)

    .187 (4.75)

    .218 (5.54)

    9.625(244.48)

    8.875(225.43)

    .220 Diameter(5.59)

    .310(7.87)

    2.762(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    1.500(38.10)

    C Lbreaker

  • TYPE BR ASSEMBLIESPage 39

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Aluminum Bus120/240V AC, 3-Wire

    200 AMP 30 SPACES 40 SINGLE POLESDIAGRAM 31

    3040INT200B

    225 AMP 42 SPACES 42 SINGLE POLESDIAGRAM 32

    4242INT225B

    .218 (5.54)

    25.625(650.88)

    24.875(631.83)

    .220 Diameter(5.59)

    .310(7.87)

    2.762(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.391(35.33)

    2.954(75.03)

    3.655(92.84)

    3.110(78.99)

    Wire Range:300 kcmil - #1 AWG (Al/Cu)

    .187 (4.75)

    1.500(38.10)

    C Lbreaker

    .218 (5.54)

    19.625(498.48)

    18.875(479.43)

    .220 Diameter(5.59)

    .310(7.87)

    2.762(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.391(35.33)

    2.954(75.03)

    3.655(92.84)

    3.110(78.99)

    Wire Range:300 kcmil - #1 AWG (Al/Cu)

    .187 (4.75)

    1.500(38.10)

    C Lbreaker

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 40

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    125 AMP 8 SPACES 16 SINGLE POLESDIAGRAM 33

    816INT125BC

    125 AMP 12 SPACES 12 SINGLE POLESDIAGRAM 34

    1212INT125BC

    .218 (5.54)

    7.249(184.12)

    6.401(162.59)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

    .218 (5.54)

    9.250(235.00)

    8.500(215.90)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.795(45.59)

    2.146(54.51)

    3.655(92.84)

    3.110(78.99)

    Wire Range:(1) 2/0 - #14 AWG (Al/Cu)

    .187 (4.75)

    1.389(35.28)

    C Lbreaker

  • TYPE BR ASSEMBLIESPage 41

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    Single-Phase Double-Row Breaker Mounting – Copper Bus120/240V AC, 3-Wire

    200 AMP 12 SPACES 24 SINGLE POLESDIAGRAM 35

    1224INT200BC

    MaximumHandleHeight

    1.391(35.33)

    2.954(75.03)

    3.655(92.84)

    3.110(78.99)

    Wire Range:300 kcmil - #1 AWG (Al/Cu)

    .187 (4.75)

    .218 (5.54)

    9.625(244.48)

    8.875(225.43)

    .220 Diameter(5.59)

    .310(7.87)

    2.762(70.15)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    1.500(38.10)

    C Lbreaker

  • TYPE BR ASSEMBLIES

    Dimensions – Inches (mm) Notched Bus Stab Solid Bus Stab

    Legend

    Page 42

    For more information contact Cutler-Hammer at: www.ch.cutler-hammer.com/catalog

    125 AMP 12 SPACES 24 SINGLE POLESDIAGRAM 36

    1224INT3125B

    Three-Phase Double-Row Breaker Mounting – Aluminum Bus208Y/120V AC, 4-Wire – 240V AC, 3-Wire – 120/240V AC, 4-Wire Delta

    150 AMP 18 SPACES 36 SINGLE POLESDIAGRAM 37

    1836INT3150B

    2.811(71.40)

    Wire Range:#8 - 2/0 AWG (Al/Cu)

    .218 (5.54)

    13.250(336.55)

    12.500(317.50)

    .220 Diameter(5.59)

    .310(7.87)

    2.388(60.66)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    1.612(40.94)

    Unuseable Space

    C Lbreaker

    .218 (5.54)

    13.625(346.08)

    12.875(327.03)

    .220 Diameter(5.59)

    .310(7.87)

    3.760(95.50)

    1.000(25.40)

    5.736 (145.69)

    2.868(72.85)

    MaximumHandleHeight

    1.570(39.88)

    1.500(38.10)

    1.500(38.10)

    3.655(92.84)

    3.110(78.99)

    W