omnia installation manual

158

Upload: geoxoyz

Post on 28-Feb-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/25/2019 Omnia Installation Manual

    1/158

  • 7/25/2019 Omnia Installation Manual

    2/158

    BENTEL SECURITY srl reserves the right to modify the contents of this manual without prior notice.

    via Florida - Z.I. Valtesino63013 GROTTAMMARE (AP) - ITALY

    Installation manual:

    Expandable Multifunction Control Panel OmniaV4.2 BUI 2.0 111298

    ATTENTION The OMNIA 2.1 software release or successive releasemust be used for Control Panel programming.

  • 7/25/2019 Omnia Installation Manual

    3/158

    TABLE OF CONTENTS

    INTRODUCTION 7

    Overview . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    Main features . . . . . . . . . . . . . . . . . . . . . . . . 8

    Omnia system . . . . . . . . . . . . . . . . . . . . . . 10

    Specifications . . . . . . . . . . . . . . . . . . . . . . 14

    2.0 version update and new features . . . . . . . . . . 15

    PARTS IDENTIFICATION 17

    Main unit . . . . . . . . . . . . . . . . . . . . . . . . 17

    Control Keypad . . . . . . . . . . . . . . . . . . . . . 19

    Key reader and Electronic key . . . . . . . . . . . . . 22

    Input and Output expanders . . . . . . . . . . . . . . 23

    INSTALLATION 25

    Installation . . . . . . . . . . . . . . . . . . . . . . . . 25

    Terminal-board description . . . . . . . . . . . . . . . 31

    Main unit . . . . . . . . . . . . . . . . . . . . . . . . 31BPI devices . . . . . . . . . . . . . . . . . . . . . . . 33

    Connection diagrams . . . . . . . . . . . . . . . . . . 34

    BPI device connection . . . . . . . . . . . . . . . . . . 35

    Bus BPI length limitation . . . . . . . . . . . . . . . . 36

    Alarm sensor connection . . . . . . . . . . . . . . . . 37

    Fire sensors . . . . . . . . . . . . . . . . . . . . . . . 39

    Alarm-device connection . . . . . . . . . . . . . . . . 39

    Balanced tamper-line connection . . . . . . . . . . . 40

    Telephone-line connection . . . . . . . . . . . . . . . 41

    Power-supply connection . . . . . . . . . . . . . . . . 41

    PROGRAMMING 43

    Customer . . . . . . . . . . . . . . . . . . . . . . . . . 43

    Configuration . . . . . . . . . . . . . . . . . . . . . . 44

    Keypads . . . . . . . . . . . . . . . . . . . . . . . . 46

    Key readers . . . . . . . . . . . . . . . . . . . . . . . 46

    TABLE OF CONTENTS 3

  • 7/25/2019 Omnia Installation Manual

    4/158

    Zones . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    Zone chart . . . . . . . . . . . . . . . . . . . . . . . 47

    Description . . . . . . . . . . . . . . . . . . . . . . . 49

    Type . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    Attributes . . . . . . . . . . . . . . . . . . . . . . . . 50

    Balancing . . . . . . . . . . . . . . . . . . . . . . . . 51

    Cycles . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . 52

    Voice messages . . . . . . . . . . . . . . . . . . . . 53

    Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    Output chart . . . . . . . . . . . . . . . . . . . . . . . 55

    Description . . . . . . . . . . . . . . . . . . . . . . . 55

    Reserved . . . . . . . . . . . . . . . . . . . . . . . . 56

    Type . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Attribute . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Timing . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    Off Time . . . . . . . . . . . . . . . . . . . . . . . . . 57

    Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    Telephone . . . . . . . . . . . . . . . . . . . . . . . . 60

    Answer . . . . . . . . . . . . . . . . . . . . . . . . . 61

    Dial . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    Description tones . . . . . . . . . . . . . . . . . . . . 62

    Answering machine . . . . . . . . . . . . . . . . . . . 62

    Dialler . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    Messages . . . . . . . . . . . . . . . . . . . . . . . . 65

    Actions . . . . . . . . . . . . . . . . . . . . . . . . . 66

    Pulse communicator . . . . . . . . . . . . . . . . . . . 67Actions . . . . . . . . . . . . . . . . . . . . . . . . . 68

    Teleservice . . . . . . . . . . . . . . . . . . . . . . . . 69

    Event-Actions . . . . . . . . . . . . . . . . . . . . . . 71

    Event description . . . . . . . . . . . . . . . . . . . . 73

    Alarm events . . . . . . . . . . . . . . . . . . . . . . 74

    Control-panel General events . . . . . . . . . . . . . 76

    Spot events . . . . . . . . . . . . . . . . . . . . . . . 79

    DTMF communicator . . . . . . . . . . . . . . . . . . 81

    4 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    5/158

    Test event . . . . . . . . . . . . . . . . . . . . . . . . 82

    Keypad codes . . . . . . . . . . . . . . . . . . . . . . 83

    Parameters to be programmed by the installer . . . . . 83

    Parameters to be programmed by the user . . . . . . 88

    Code status . . . . . . . . . . . . . . . . . . . . . . . 88

    Programming . . . . . . . . . . . . . . . . . . . . . . 88

    Electronic keys . . . . . . . . . . . . . . . . . . . . . . 91

    Super keys . . . . . . . . . . . . . . . . . . . . . . . . 91

    Filter times . . . . . . . . . . . . . . . . . . . . . . . . 91

    Options . . . . . . . . . . . . . . . . . . . . . . . . . . 92

    Timer programmer . . . . . . . . . . . . . . . . . . . . 93

    LCD strings . . . . . . . . . . . . . . . . . . . . . . . . 93

    Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

    Installer code . . . . . . . . . . . . . . . . . . . . . . . 94

    Programming from local PC . . . . . . . . . . . . . . 95

    Programming from PC via telephone . . . . . . . . . 97

    Keypad programming . . . . . . . . . . . . . . . . . . 99

    Default reset . . . . . . . . . . . . . . . . . . . . . . . 99

    Default setting . . . . . . . . . . . . . . . . . . . . . . 100

    A basic system . . . . . . . . . . . . . . . . . . . . . . 102

    Connections . . . . . . . . . . . . . . . . . . . . . . 102

    Programming . . . . . . . . . . . . . . . . . . . . . . 102

    System use . . . . . . . . . . . . . . . . . . . . . . . 103

    KEYPAD OPERATIONS 105

    General rules for INSTALLER MENU use . . . . . . . 106

    INSTALLER MENU access . . . . . . . . . . . . . . . 106

    View logger . . . . . . . . . . . . . . . . . . . . . . . . 107

    Zones status . . . . . . . . . . . . . . . . . . . . . . . 108

    Outs managements . . . . . . . . . . . . . . . . . . . 109

    Clear call queue . . . . . . . . . . . . . . . . . . . . . 109

    Voice functions . . . . . . . . . . . . . . . . . . . . . 110

    Telephone-number Programming . . . . . . . . . . . 112

    Description Programming . . . . . . . . . . . . . . . . 113

    Installer code . . . . . . . . . . . . . . . . . . . . . . . 114

    User codes . . . . . . . . . . . . . . . . . . . . . . . . 114

    TABLE OF CONTENTS 5

  • 7/25/2019 Omnia Installation Manual

    6/158

    Electronic keys . . . . . . . . . . . . . . . . . . . . . . 117

    Enable . . . . . . . . . . . . . . . . . . . . . . . . . 121

    Parameter programming . . . . . . . . . . . . . . . . 122

    Firmware release . . . . . . . . . . . . . . . . . . . . . 122

    OmniaVOX 123Specifications . . . . . . . . . . . . . . . . . . . . . . 123

    Identification of the parts . . . . . . . . . . . . . . . . 123

    Installation . . . . . . . . . . . . . . . . . . . . . . . . 124

    Extension of the Listen-in areas . . . . . . . . . . . . 125

    Manual selection . . . . . . . . . . . . . . . . . . . . 126

    Automatic selection . . . . . . . . . . . . . . . . . . . 127

    Manual and automatic selection . . . . . . . . . . . . 128

    OmniaTIMER 129

    General characteristics . . . . . . . . . . . . . . . . . 129

    Identification of the parts . . . . . . . . . . . . . . . . 130

    Installation . . . . . . . . . . . . . . . . . . . . . . . . 130

    Programming . . . . . . . . . . . . . . . . . . . . . . . 134

    Applications . . . . . . . . . . . . . . . . . . . . . . . 138

    Timer Applications . . . . . . . . . . . . . . . . . . . . 140

    PC Connection . . . . . . . . . . . . . . . . . . . . . . 140

    APPLICATIONS 141

    Fast arming . . . . . . . . . . . . . . . . . . . . . . . . 141

    Temporary disarming (patrol) . . . . . . . . . . . . . . 142

    Management of a common Area . . . . . . . . . . . . 144

    Several outputs assigned to the same event . . . . . 146

    Multi-output event . . . . . . . . . . . . . . . . . . . . 147Recognition of multiple codes . . . . . . . . . . . . . 149

    Disarming under duress . . . . . . . . . . . . . . . . 150

    Solution no. 1 . . . . . . . . . . . . . . . . . . . . . . 150

    Solution no. 2 . . . . . . . . . . . . . . . . . . . . . . 151

    Dialler . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

    Alarm stop by means of Electronic key . . . . . . . . 157

    6 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    7/158

    INTRODUCTION

    Overview

    Omnia is an extremely powerful Control Panel of the latest generation.This flexible system is more than able to meet the most demanding instal-

    lation requirements.

    Omnia may be expanded, programmed and operated with great ease.

    There are 8 input Zones on the Control Panel, expandable to 80, and 4

    outputs on the basic board, expandable to 36.

    Areas Omnia can manage 8 Areas, a feature which gives flexibility to system par-titioning and shared management. The 8 Areas may be armed or disarmed

    individually or as groups by means of Electronic keys, Codes or Control-panel inputs. It is possible to make Areas dependent on one another, for

    automatic management of the "Common Areas",

    Events and

    actionsInteractions among Inputs, Outputs and Telephone-dialler actions, whethervoice or digital, may be programmed according to requirements; in this

    way, the installer is ensured exceptional operational flexibility.

    The Omnia Control Panel can manage 443 events, the installer may select

    the actions the Control Panel must perform for each event.

    There are three basic actions: actions on outputs, actions on digital dialler

    and actions on voice dialler.This resourceful approach to security solutions makes Omnia adaptable to

    the most diverse needs. Moreover, factory programming permits install-and-go solutions for fast installation.

    Telephone

    funct ions

    The telephone dialler manages up to 32 telephone numbers.Four numbers may be assigned to the Pulse digital dialler, each with acustomer code and communication protocol, this makes communication

    between several Central Stations possible.

    A further four numbers may be assigned to the DTMF digital communica-

    tor, each number may be assigned to a customer code and a communica-tion protocol.

    4 telephone numbers are available for teleservice, these allow the Control

    Panel to communicate with the installer modem, even when it has beentemporarily moved to different premises.

    OmniaVOX The OmniaVOX board offers a telephone-dialler function, which can dial 16

    telephone numbers. Up to 14 different Voice messages may be sent by theControl Panel, these messages must be recorded by the installer.

    The OmniaVOX board provides the answering-machine function, one of

    the 14 messages may be assigned to this function.

    INTRODUCTION 7

  • 7/25/2019 Omnia Installation Manual

    8/158

    Once in voice contact with the Control Panel (either after receiving a dialler

    communication or when making a call to the Control Panel, which in turn isanswering with a recorded message), it is possible to perform many impor-

    tant actions such as: Listen-in, Two-way conversation, Input status inquiry

    with voice answer from the Control Panel, remote ON/OFF control of sys-tem devices, area arming/disarming, alarm reset, call block and so forth.

    All these operations are made possible by entering a secret code whichmay be invalidated, if necessary, soon after use.

    Programming A powerful management software in Windowsenvironment, makes Con-trol panel programming extremely flexible, the software permits program-

    ming and supervision of the Control Panel, by either connecting to the

    RS232 interface or to teleservice.

    The Control Panel may be programmed from the Keypads, thus, makingquick maintenance intervention possible.

    Timer

    programming

    The optional Timer-programmer board provides a wide range of functions

    for automatic management of the system and permits Area arming/disarm-ing on a daily/weekly basis. 8 fully independent daily timers are availablefor the management of all event types, furthermore, management of a par-

    allel or serial printer is also provided for.

    Main features

    Burg lar contro l panel

    r Up to 80 Alarm Zones: 8 on the Main unit, 64 on 16 Input expanders (4

    zones each), 8 on 8 Keypads (1 Zone each Keypad).r Up to 36 outputs: 2 relays and 2 open collectors on the Main unit, 32 on 8

    Output expanders (4 outputs each).

    r Up to 8 Keypads for system management, each with LCD.

    r Up to 16 electronic-Key readers.

    r Up to 2 Power stations, of 3 or 5 A, controlled by the Control Panel.

    r 4-wire shielded bus for remote device connections, protected against short cir-cuits.

    r Bus duplication for protection against tamper.

    r All Zones may be programmed as balanced, function and alarm type.

    r Each entrance Zone may be programmed to send specific commands to

    the Control Panel.

    r All outputs are programmable as bistable or cyclic with programmable cy-cle time and OFF time.

    r 8 programmable Areas each with its own Zones, Keypads, Key readers,

    outputs and times.

    r 31 user codes with programmable display, priority and functions.

    r 250 electronic-Key readers each with a programmable display.

    8 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    9/158

    r Each system object (Zones, Keypads, Key readers, Codes, Electronic

    Keys, Areas, etc.) may be identified with a 16-character name, which isdisplayed on the Keypad during user operations.

    r Storage of the last 200 events with date, time and user.

    r RS232 interface for Control Panel programming and monitoring.

    r WindowsSoftware for Control Panel programming, teleservice and tele-

    control.

    Telephone funct ion s

    r DTMF and pulse selection.

    r 32 telephone numbers available for telecontrol, teleservice and voice calls.

    r Built-in Digital multiprotocol communicator for DTMF and pulse protocolmanagement.

    r Possibility to carry out 10 different immediate alarm calls via Keypad.

    r Programmable test-call.

    r Possibility to enable recall.

    r Line sharing with another answering device.

    r 1200 baud FSK integrated modem for teleservice management.

    Telephon e func t ions with OmniaVOX optio nal board

    r Telephone dialler for the management of 14 different Voice messages, to

    be recorded by the installer for message communication to 16 differenttelephone numbers.

    r Remote-Inquiry to the Control Panel (using secret code) with voice answer.

    r Remote output-control, Area arming status and alarm reset from ControlPanel (using secret code).

    r Remote listen-in and multipoint telephone-conversation (using secret

    code).

    r Answering-machine function.

    Omn iaTIMER time prog rammer funct ions and p rinter interface

    r Management on daily, weekly and monthly basis.

    r Holiday and standard/summer-time management.

    r Overtime and timeout-to-arm management.

    r 2 arming and 2 disarming actions per day per Area.

    r 8 fully independent daily timer channels.

    r Centronics o RS232 parallel printer interface.

    INTRODUCTION 9

  • 7/25/2019 Omnia Installation Manual

    10/158

    Omnia system

    Basic Contro l

    PanelThe standard system is provided with the Main unit and a Control Keypadand is available in two models:

    Omnia/S Control Panel with 3 A switching power-supply.

    Omnia Control Panel with 1.5 linear power-supply.This manual is valid for both models, however, the differences in the two

    power supplies are explained in the following chapter.

    Expanders Omnia can manage up to 16 input expanders, each equipped with 4 Zonesand a maximum of 8 output expanders, each with 4 open-collector type

    outputs.

    Control d evices These may be connected to the Control Panel by means of up to 16 elec-

    tronic-key readers, and up to 8-LCD Keypads.

    Omnia Vox This is an optional board for voice call management and telearming func-tions.

    Timer

    programmer

    This is an optional board for automatic management of the systems andprinter interface.

    Management

    SoftwareThe management software in Windowsenvironment will prove to be anindispensable tool in achieving the full capacity of the Omnia system. In

    fact, the software makes it possible to carry out Control Panel program-ming, manage a complete customer file, and also supervise the ControlPanel in real time.

    OmniaMod

    modem

    By using the specific OmniaMod modem, the same software may be usedfor the management of both manual and automatic teleservice connec-

    tions, in this way, it is always possible to have a fully updated Customer-

    file. With the V2 modem version, it is possible to receive Central-Stationcalls for real-time information on events occurring on the systems under

    supervision.

    Remote po wer

    stationA 5 A capacity power-station is available for connection to the bus, thissupplies the required voltage to the remote devices during mains failure.

    The power station is completely controlled by the Control Panel, which

    manages the events generated by the remote power station (low or ineffi-cient battery, mains failure); two devices may be connected to the bus.

    10 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    11/158

    Items The following are the Omnia system items.

    OMNIA ---- 8-Zone Control Panel with Control Keypad and 1 A linear power-supply.

    OMNIA/S8-Zone Control Panel with Control Keypad and 3 A switching power-supply.

    OMNIA/TAST-R Additional Keypad with backlit LCD display.

    OMNIA/4IN 4-input expander module.OMNIA/4OUT 4-output expander module.

    OMNIA/VOX Voice function board.

    OMNIA/VOX-MS Microphone and loudspeaker for environmental listen-in.

    BPI3 Recess Key-reader model TICINO mag ic.

    BPI3LIV Recess Key-reader model TICINO livin g.

    BPI3INT Recess Key-reader model TICINO internation al.

    BPI3LGT Recess Key-reader model TICINO ligh t.

    BPI3GEW Recess Key-reader model GEWISS.BPI3GP Recess Key-reader model GEWISS playbu s.

    BPI3-GN Recess Key-reader model GEWISS no ir.

    BPI3DEL Recess Key-reader model DELTA.

    BPI3-DN Recess Key-reader model DELTA noi r.

    BPI3VI Recess Key-reader model VIMAR idea.

    BPI3VIB Recess Key-reader model VIMAR bianc o.

    BPI3-AVE Recess Key-reader model AVE.

    BPI3-AN Recess Key-reader model AVE noi r.BPI3W ---- Wall mounted Key-reader.

    DKC Electronic key.

    OMNIA/4R ---- 4-relay module for the output expanders.

    OMNIA/TIMER Timer programming and printer interface board.

    OMNIA/MOD-V1 ---- Teleservice modem.

    OMNIA/MOD-V2 ---- Teleservice and remote monitoring modem.

    CVSER/9F9F ---- Serial cable for PC connection.

    ADSER/9M25F ---- 25-pin adapter for serial ports.OMNIA/SW Management software.

    BXM12/30 ---- 3 A remote power-station.

    BXM12/50 ---- 5 A remote power-station.

    INTRODUCTION 11

  • 7/25/2019 Omnia Installation Manual

    12/158

    Figure 1 The Omnia system.

  • 7/25/2019 Omnia Installation Manual

    13/158

    INTRODUCTION 13

  • 7/25/2019 Omnia Installation Manual

    14/158

    Specifications

    Model OMNIA OMNIA/S

    Voltage 230 V 50 Hz 10%

    Max. input 0.2 A 0.5 A

    Max. power 45 W 115 W

    Insulation class Class I

    Power supply/Battery-charger 13.8 V 1.5 A 13.8 V 3 A

    Max. current available for

    external device supply1 A 2 A

    Battery(Make and Model)

    12 V - 7 Ah or 12 V - 17 AhYUASA

    NP 7-12 FR or NP 17-12 FR oran equivalent with a case flame class of

    UL94-V2 or better

    Operation temperature range 5 40 CDimensions (W x H x D) 330 x 460 x 100 mm

    Weight (without battery) 4.6 Kg

    Meets CEI standard

    EN 50081-1/1992EN 50082-1/1992EN 41003:1997

    EN 60950:1992 + A1:1993 + A2:1993 +A3:1995 + A4:1996

    79/2 2ndEd. 1993 - Performance level 2nd

    Article Absorption Dimensions (WxHxD)

    OMNIA/S Moth er Board 135 mA ----

    Keypad 50 mA 160 x 73 x 30 mm

    Recess Key-reader 30 mA ----

    Wall mou nted K ey-reader 30 mA 51 x 73 x 28 mm

    Input Expander 15 mA

    108 x 101 x 34 mmOutput Expander 20 mA

    4-relay mo dule 120 mA

    Voice board + Microph one-Loud speaker board

    20 mA ----

    Timer programm ing

    and Printer interface board40 mA ----

    Power station 20 mA 234 x 345 x 96 mm

    14 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    15/158

    2.0 version update and new features

    The following is a list of the new features, of the Omnia 2.1 Control Panel,

    and their descriptions.

    The page numbers of the CHAPTERS, PARAGRAPHS and the SUB-PAR. 1 are to be found in the TABLE OF CONTENTS, as follows:

    CHAPTER page

    Paragraph . . . . . . . . . . . . . . . . . . . . . . . page

    Subpar. 1 . . . . . . . . . . . . . . . . . . . . . . . page

    The SUBPAR. 2, however, are presented in the following way:

    Subpar. 2 Text.

    NEW FEATURE CHAPTER PARAGRAPH SUBPAR. 1 SUBPAR. 2

    Arming blocked on

    remote power sup-ply battery troub le

    PROGRAMMING Options ----

    Disable arming

    on batterytrouble

    Factory default

    modif icat ions

    PROGRAMMING

    Default settings ----Event-Actions

    Telephonedialler

    A basic system Programming

    Telephonenumbers

    Voicemessages

    Call queue prioritymanagement PROGRAMMING Event-Actions ---- Priority oftelephone

    actions

    Alarm Stop Control

    Panel alarm, using

    Electronic key

    PROGRAMMING Options ----Enable alarmstop on panelwith valid key

    New events

    PROGRAMMING Event-ActionsControl Panel

    General Events

    263 - Valid keyon panel

    361 -Telephone line

    monitor troubleTransmission of

    several events

    during the same

    telephone

    communicat ion

    PROGRAMMINGPulse

    Communicator---- ----

    INTRODUCTION 15

  • 7/25/2019 Omnia Installation Manual

    16/158

    Figure 2 Main unit parts

    16 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    17/158

    PARTS IDENTIFICATION

    In this chapter the parts and LEDs of the main components on the Omnia

    system are identified. The numbers in boldface in this manual refer to thecharts and diagrams in these pages.

    Main unit

    PARTS DESCRIPTION

    1 Screws (2) for securing front panel to back.

    2 Tamper switch.

    3 Holes (4) for securing back ( 5 mm).

    4 Extractable terminal boards.

    5Alarm block jumper: > alarm enabled (default);

    > alarm disabled.

    6 DB9 male connector for PC connection with serial cable.

    7

    Jumper (MEM) stores the programmed settings during power failure:

    > if power fails, programmed settings are lost (default); > ifpower fails, programmed settings are stored.

    8 Make / Break setting jumper.

    9 OmniaVOX board connector.

    10 BPI device connector.

    11 Cable hole.

    12 Housing for buffer battery 12 V - 17 Ah maximum.

    13 Supply block (see fig. 3).

    14 Pull-off block.

    15 Pull-off switch.

    16 BPI1 (F 3.15A 250V) bus terminal 22[+] protection fuse.

    17 BPI2 (F 3.15A 250V) bus terminal 18[+] protection fuse .

    18 Main unit (F 3.15A 250V) terminal [+F] protection fuse .19 terminal [+N], [+A] and [+B] (F 3.15A 250V) protection fuse.

    LED MEANING

    Mains.ON: supply voltage is present.

    Battery.ON: battery discharged or low.

    Bus communica tion .ON: trouble with device communication.

    PARTS IDENTIFICATION 17

  • 7/25/2019 Omnia Installation Manual

    18/158

    Figure 3 Parts of the switching and linear power supply units.

    18 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    19/158

    PARTS DESCRIPTION

    20 Red Led shows mains supply present.

    21 Output voltage (fine) adjustment Trimmer.

    22 External device supply terminals (13.8 V ).

    23 Mains voltage connection terminals (230 V / 50 Hz).

    24 Buffer-battery connectors.25 Plastic pin, to be removed, in order to open the switching-power supply.

    26

    Power supply protection fuse:Omnia = F 250 mA 250V;OmniaS = F 2A 250V.

    27Fuse (F 8A 250V) protection against accidental polarity inversion in thebuffer battery.

    Control Keypad

    ICONS MEANING

    Armed-Area signalling.

    Alarm-memory signalling.

    Control-Panel-malfunction signalling.

    Control-Panel door open.

    Tamper line alarm.

    Device tamper.

    False key on key reader.

    Configured devices cannot be reached.

    Teleservice enabled

    Answering device enabled

    Engaged telephone line.

    PARTS IDENTIFICATION 19

  • 7/25/2019 Omnia Installation Manual

    20/158

    PARTS DESCRIPTION

    28 Flap.

    29 View window for main LEDs (On, Alarm and Warning).

    30 Screws (4) for securing box to back.

    31 LCD display .

    32 Terminal identification tab in accordance with the device address.33 Reference pins (2) for board positioning.

    34 Connection terminals.

    35 Plastic hooks (2) for securing board.

    36 Pull-off switch.

    37 Device identification tab in accordance with dipswitch configuration 38.

    38 Tamper switch.

    39 Address setting dipswitches.

    40 Plastic hooks (2) for securing board.

    41 Cable hole.

    42 Holes (2) for securing back ( 4 mm).

    43 Hole for securing Pull-off switch.

    44 Buzzer.

    45 Buzzer connector.

    Figure 4 Control Keypad parts (external view).

    20 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    21/158

    Figure 5 Control Keypad parts (external view).

    PARTS IDENTIFICATION 21

  • 7/25/2019 Omnia Installation Manual

    22/158

    Key reader and Electronic key

    + The key reader is not provided with the Omnia Control panel. It may bepurchased separately and is available in several versions for recessmounting, and one version for wall mounting (see "Items").

    Figure 6 refers to the Magic-box version.

    PARTS DESCRIPTION

    46 Connection terminals.

    47 Address setting dipswitches.

    48 Device identification tab in accordance with dipswitch configuration 47.

    49 Cable holes.

    50 Fixing holes (2).

    51 Holes for securing the Pull-off switch.

    52 Pull-off switch.

    53 Tamper switch.

    54 Electronic key slot.

    55 Control button (on Electronic key).

    + In the first column of the following table, the word in inverted commas re-fers to the colour of the LED.

    LED MEANING

    "red" ON: Enabled Areas on the Key reader are armed.

    "amber" ON: Type A arming.

    "green" ON: Type B arming.

    Figure 6 Parts of the Magic (a) and wall-mounted (b) Key reader, and Electronic key (c).

    22 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    23/158

    Input and Output expanders

    PARTS DESCRIPTION

    56 BPI Bus connection terminal.

    57 Device identification tab in accordance with dipswitch configuration59.

    58 Input Zone connection terminal.

    59 Address setting dipswitches.

    60

    Tamper and Pull-off switch bypass jumper:

    > switches active.

    > switches bypassed (default);

    61 Pull-off switch.

    62 Tamper switch.

    63 Buzzer.

    64

    Buzzer operation mode selection jumper:

    > bypassed buzzer (default);

    > the buzzer sounds when the terminal [OC4] is open;

    > the buzzer sounds when the terminal [OC4] is earthed.

    65 Open-collector output terminal board, 150 mA maximum.

    66 Terminal identification tab in accordance with the device address.

    Figure 7 Parts of the Input and Output Expanders.

    PARTS IDENTIFICATION 23

  • 7/25/2019 Omnia Installation Manual

    24/158

    PARTS DESCRIPTION

    67 Box screws (4).

    68 Input or Output expander or 4 relay Module.

    69 Expander screws (2).

    70 Opening for cable duct or externally laid cables.

    71 Holes (2) for mounting on the model 503 box.72 Opening for cable duct.

    73 Holes (2) for wall mounting.

    74 Hole for the Pull-off block screw.

    75 Tooth for securing the tamper switch.

    Figure 8 Parts of the box for the Expanders and the 4 Relay module.

    24 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    25/158

    INSTALLATION

    Installation

    Before installing the security system devices, it is advisable to plan the lay-out and lay the necessary connection cables.

    Main uni t The Main unit must be installed in a protected, and if possible, hidden

    place. The chosen position must be within reach of the connection cablesof the other security system devices, the mains voltage supply (including

    the earth connection) and, if required, the telephone line.

    A Drill the necessary holes for the installation of the Main unit, and the pull-off block, 3 and14 in the diagram.

    B Pass the connection cables through the cable hole 11and fix the Main unitand the pull-off block in place.

    + Do not over tighten the screws, as this may damage the lugs on the pull-offblock.

    C Install any supplementary boards (Omnia4IN, Omnia4OUT, OmniaVOX,OmniaTIMER, etc.) in the Main unit, as described in the relevant para-

    graphs.

    D Carry out the necessary connections, leaving the power supply connec-

    tions to the last.

    Control Keypad The Control Keypad should be positioned in a place that requires completecontrol of the security system.

    + The Keypad should be positioned at about 160 cm. from the ground, in or-der to allow full view of the display.

    INSTALLATION 25

  • 7/25/2019 Omnia Installation Manual

    26/158

    A Unscrew the screws 30and remove the Keypad box.

    B Remove the connector 45.

    C Using the thumbs, put pressure on the plastic clips 35in order to free the

    electronic board.

    D Drill the necessary holes for mounting the Control Keypad, and the pull-off

    block , 42 and43respectively in the diagram.

    E Pass the connection cable through the cable hole 41.

    F Fix the Keypad base and pull-off block in place.

    G Replace the electronic board and the connector 45.

    H Assign the identifier number to the keypad, by means of the dipswitches39, then carry out the connections on the terminal board 34.

    I Replace the Keypad box.

    Figure 9 Installation of a Control Keypad.

    26 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    27/158

    Recess Key

    reader

    The Key reader may be installed in a place where limited control of the se-

    curity system is sufficient.

    A Assign an identifier number to the Key reader, by means of the dipswitches

    47, then carry out the connections on the terminal board 46.

    B Fix the Key reader in place, in the same way as one would a household

    light switch or electric socket.

    ATTENTION For an installation that meets the Standard required,re-cess Key readers installed in places outside the protection of the se-curity system, must be equipped with a tamper device (see the

    example in figure 10a).

    Wall mounted

    Key-readerWall mounted Key-readers (art. BPI3W) function in the exact same way asrecess Key-readers, however, wall mounted Key-readers have boxes for

    wall mounting, whilst recess Key-readers require recess boxes. Wallmounted Key-readers are designed to allow the keypad and Key reader to

    be mounted side by side.

    A Open the Key reader.

    B Drill the necessary holes for the installation of the Key reader, and the pull-off block,50and 51respectively in the diagram.

    C Pass the connection cable through the cable hole 49.

    D Fix the Key reader and pull-off block in place.

    E Assign an identifier number to the Key reader, by means of the dipswitches47, then carry out the connections on the terminal board 46.

    F Close the Key reader.

    Figure 10 Installation of a recess Key reader (a) and a wall mounted Key reader (b).

    INSTALLATION 27

  • 7/25/2019 Omnia Installation Manual

    28/158

    Expanders and

    Relay modu les

    The Input and Output expanders and the Relay module must be placed as

    near as possible to the connected devices. They are equipped with eitheran on-view (for wall mounting) or recess box.

    A unscrew the screws 67and remove the front cover.

    B Unscrew the screws 69and remove the electronic board.

    C Open hole 70, or 72depending on the cable layout.

    D - If on-view mounting of the box is required, drill the necessary holes forthe box, and the pull-off block, 73and 74respectively in the diagram, (see

    fig. 11b);

    - if on-view mounting on a model 503 box is required, it is necessary todrill the hole for the pull-off block only (fig. 11c);

    - it is not necessary to drill any holes for recess installation (fig. 11a).

    E Pass the connection cables through the cable hole.

    F Fix the box and pull-off block in place.

    + The pull-off block must be positioned as shown in figure 11, for both walland recess mounting.

    G Replace the electronic board inside the box.

    H Assign an identifier number to the expander, by means of the dipswitches

    59, then carry out the connections on the terminal boards.

    I Remove the jumper 60(activated tamper and pull-off switches).

    J Set the function mode of the Output-expander buzzer, by means of thejumper 64.

    K Close the box.

    + Be careful not to damage the plastic tooth 75, as this must secure the tam-per switch in place.

    The Input and Output expanders and the relay module can be installed inthe Main unit, as shown in figure 12, by means of the suitable supports,

    supplied on request.

    ATTENTION The pull-off and tamper switches, of the Input and Out-put expanders installed inside the Main unit, must be bypassed by

    connecting the jumper 60.

    28 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    29/158

    Figure 11 Expander installation: (a) recess; (b) on view; (c) inside mod.503 box .

  • 7/25/2019 Omnia Installation Manual

    30/158

    PARTS DESCRIPTION

    76 Expanders (Omnis4IN, Omnia4OUT, Omnia4R): max. 3.

    77 Loudspeaker.

    78 Printer Interface - Timer Programmer (OmniaTIMER).

    79 Voltage supply.

    80 Battery 12 V - 17 Ah max.81 Voice board.

    82 Mother board.

    83 Microphone board.

    Figure 12 Maximum configuration of the Main unit.

    30 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    31/158

    Terminal-board description

    The following is a brief description of the Main unit terminal boards, and

    the devices that can be connected to the bus:

    the TERMINAL BOARDS column contains the sequential number and (in

    square brackets) the initial/s of the described terminal(s);

    the DESCRIPTION column contains a brief description of the terminal(s)listed in the M. column;

    the V column shows the voltage on the described terminal(s) (the symbol "/"

    shows that a voltage value cannot be specified);

    the Icolumn contains the maximum current value (in amperes) that maycirculate on the terminal(s) described (the symbol "/" shows that a voltage

    value cannot be specified); in this column the numbers in round bracketsare relevant to the notes at the bottom of the chart.

    Main unit

    TERMINALS DESCRIPTION V I

    1-2 [AC]Connected terminals

    (not in the model with switching power-supply)./ /

    3-4 [+B- ]External device power supply protected by fuse 19and

    supplied by the buffer battery during mains failure.13.8 (1)

    5-6-7[NA1-NC1-C1]

    RL1 output (free voltage exchange):

    normalC1 connected with NC1 and NO1 open;

    alarm C1 connected with NO1 and NC1 open.

    / 3

    8 [+A1]RL1 programmable output (positive):

    normal open terminal;

    alarmvoltage on terminal.

    13.8 (1)

    9 [+N1]

    RL1 programmable output :

    normal voltage on terminal;alarmopen terminal.

    13.8 (1)

    10-11-12[NA1-NC1-C1]

    RL2 programmable output (free voltage exchange):

    normalC2 connected with NC2 and NO2 open;

    alarm C2 connected with NO2 and NC2 open.

    / 3

    13 [+A2]

    RL2 programmable(positive) output:

    normal open terminal;alarmvoltage on terminal.

    13.8 (1)

    14 [+N2]

    RL2 programmable output:

    normal voltage on terminal;

    alarmopen terminal.

    13.8 (1)

    15 [OC1] Programmable open-collector output. 0 1

    16 [OC2] Programmable open-collector output. 0 1

    17 [ ] Ground. 0 /

    18-19-20-21

    [+-C-R- ]

    Device connection Bus BPI1 (LCD Keypads, Input Exp.,

    Output Exp., Key readers).(2) (1)

    INSTALLATION 31

  • 7/25/2019 Omnia Installation Manual

    32/158

    TERMINALS DESCRIPTION V I

    22-23-24-25

    [+-C-R- ]

    Device connection Bus BPI2 (LCD Keypads, Input Exp.,Output Exp., Key readers).

    (2) (1)

    26-27 [ - ASB]Balanced tamper line (terminal [ASB]) normally connected

    to the ground (terminal [ ) by means of a 10K. heater/ /

    28-31-34-37

    40-43-46-49 [ ] Input-line ground. 0 /

    29-32-35-38-41-44

    47-50 [L1L8]Programmable input lines. / /

    30-33-36-39-42

    45-48-51 [+F]

    Sensor power supply protected by fuse 18 and supplied by

    the buffer battery during mains supply failure.13.8 (1)

    52 [ ] Ground connection. 0 /

    53-54 [LE] Connection terminal for external telephone line. / /

    55-56 [LI]Connection terminal for further telephone devices on the

    same telephone line as Omnia (answering machines,telephones, fax machines, modems, etc.).

    / /

    (1) The sum of the current on terminals [+F], [+B], [+], [+A] and [+N] of the

    Main unit should not exceed 2 A with Omnia/Sand 1 A with Omnia.

    (2) On the [+] terminals of the Main unit a voltage of 13.8 V is present, pro-

    tected by fuse 16for BPI1, and by fuse 17for BPI2, this voltage is suppliedby the buffer battery during mains supply failure.

    (3) The current absorbed by the terminals [+] of the BPI devices is the following:

    - Keypad = 50 mA;- Key reader = 30 mA;- Input expander = 15 mA;

    - Output expander = 20 mA;- Power station = 20 mA.

    These absorptions do not include those of the power supply to the devices

    connected to the BPI devices.

    (4) The sum of the current absorbed by the Input expander terminals [+F]

    should not exceed 0.4 A.

    32 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    33/158

    BPI devices

    The BPI devices are: LCD Keypads, Electronic-key readers, Input ex-panders, Output expandersand Power stations. The following chart de-

    scribes the terminals, which are common to all BPI devices, for connectionto the BPI Busof the Control panel.

    TERMINALS DESCRIPTION V I

    [+] Supply: positive. 13.8 (3)

    [R]"Answer" terminal to be connected to the corresponding

    terminal on the Main unit./ /

    [C]"Command terminal to be connected to the corresponding

    terminal on the Main unit./ /

    [--] Supply: negative. 0 /

    Key reader The recess Key reader has only bus connection terminals whereas the wallmounted Key reader also has the following terminals:

    TERMINALS DESCRIPTION V I

    [AS]tamper switch:

    closed if switches 52and 53are closed;open if switches 52and 53are open.

    / /

    Keypad The Keypad, in addition to the bus connection terminals, has the following

    terminals:

    TERMINALS DESCRIPTION V I

    [L1] Programmable input line. / /

    [ ] Input-line ground. 0 /

    Input expander In addition to the bus connection terminals, the input expander has the fol-

    lowing terminals:

    TERMINALS DESCRIPTION V I

    [L1] [L2] [L3] [L4] Programmable input lines. / /

    [ ] Input-line ground. 0 /

    [+F] Sensor supply protected by resettable fuse. 13.8 (4)

    Outpu t expander In addition to the bus connection terminals the output expander has the fol-lowing terminals:

    TERMINALS DESCRIPTION V I

    [+12V]Power supply for any devices that may be connected to

    open-collector outputs, protected by resettable fuse.13.8 0.4

    [OC1] [OC2]

    [OC3] [OC4]Programmable open-collector outputs. 0 0.15

    [ ] Ground terminals. 0 /

    Power stat ion Please refer to the manual provided with the device.

    INSTALLATION 33

  • 7/25/2019 Omnia Installation Manual

    34/158

    Connection diagrams

    The following pages contain the connection diagrams of the Omnia Main

    unit, and all the necessary information on the BPI devices and variousother items of an Omnia security system.

    In order to make the connections clear, each device group (BPI devices,

    sensors, alarms devices etc.), is dealt with separately.

    + The connections should be made with shielded cable, one end of the cablemust be connected to ground and the other left free.

    The examples shown are for reference only, as it would be impossible to il-

    lustrate all the applications available.

    Diagram

    symbolsThe diagrams have been simplified to facilitate understanding.

    The terminals for the input and open-collector-output zones can be either

    Main unit or expander terminals.

    The terminals are displayed one by one.

    The terminals may not be in the exact same position on the actual board,differences may occur, as connection crossing in the diagram has been re-

    duced to the minimum.

    + The negative terminals are indicated by the symbol on the Main unitmother board, and by the symbol on all other boards.

    Figure 13 Connection example of 3 BPI devices to the bus.

    34 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    35/158

    BPI device connection

    The Control Panel permits the following connections to the bus:

    up to 8 control Keypads;

    up to 16 electronic-key readers;

    up to 16 input expanders;

    up to 8 output expanders;

    up to 2 power stations.

    Electr ical

    connect ions

    The BPI devices are all connected to the bus in the same way; all devices

    require parallel connection on terminals [+], [C], [R], [ ] of the communi-cation bus.

    Double bus The communication bus is physically doubled, in fact the terminals relativeto the bus are (18-19-20-21 and 22-23-24-25). The two buses are pro-

    tected by several fuses, in this way, a short-circuit on one bus does notdamage the other.

    One bus must be used for the installation of outdoor BPI devices, and the

    other for the remaining devices, in this way, any tamper attempt on the out-

    side (signalled by the Control Panel), does not damage the functional ca-pacity of the other line of the bus.

    Figure 13 illustrates the connection of 3 devices, which may be Keypads,key readers, input expanders, output expanders or power stations.

    If the system provides for more than one device of the same type, these

    must be given different addresses. This operation is called "device coding".

    Device cod ing The BPI device coding is carried out by means of the dipswitches: 39 for

    Keypads, 47for Key readers and 59for input and output expanders.

    + For power stations, see the manual provided.

    The address is assigned according to the position of the dipswitches. Thefollowing table shows the 16 possible combinations.

    Microswitch N.Address

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

    1 off off off off off off off off ON ON ON ON ON ON ON ON2 off off off off ON ON ON ON off off off off ON ON ON ON

    3 off off ON ON off off ON ON off off ON ON off off ON ON

    4 off ON off ON off ON off ON off ON off ON off ON off ON

    + The assigned addresses must be different for each device of the sametype. Although, devices of different types may have the same address.

    + A maximum of 8LCD Keypads and Output expanders may be con-nected to the bus. Dipswitch no.1 does not affect these devices.

    + It is not necessary to follow any particular order when assigning codes,however, all codes must be different.

    INSTALLATION 35

  • 7/25/2019 Omnia Installation Manual

    36/158

    Bus BPI length limitation

    The voltage drops and stray capacitance caused by the BPI bus connec-tions of the Main unit, make length limitation necessary.

    Proper functioning of the BPI devices is ensured by a supply voltage between

    terminals [+] and [ ] higher or equal to 10 V otherwise, it is possible to:

    increase the wire section that carries the power to the device (those wires

    connecting terminals [+] and [ ] of the Main unit, terminals [+] and [ ] ofthe device) respectively;

    restore supply by means of a power station;

    limit the BPI device current absorption, by supplying the connected devices

    by means of a Power station.

    In all cases, due to the stray capacitance caused by the connection cable,a BPI device cannot be connected to the Main unit by a cable of more than

    500 m, and the overall length of the cables connected to each BPI bus of

    the Main unit must not be longer than 1,000 m.

    Figure 14 Sensor connection to Normally Closed line.

    36 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    37/158

    Alarm sensor connection

    Omnia has 8 Zones on the Main unit board, for the connection of sensors,

    4 Zones on each input expander and 1 Zone on each Control Keypad. Thetotal number of Zones is: 8 + 4 x16 + 1 x 8 = 80.

    The terminals corresponding to the input Zones are those labelled with [Ln]

    (n is the zone number), each Zone has its own supply from the terminals

    [+F] and [ ]. All these terminals are available on the Main unit, on the in-put and output expanders and on the Keypads.

    + Terminal [+F], which supplies power to the connected sensor, is not pre-sent on the Keypad; however, it is possible to use terminal [+] of the com-

    munication bus power supply .

    Each terminal may be connected to one or more sensors, although, it isadvisable to connect only one sensor to each terminal, in this way, the sen-

    sor in alarm status is easily identified.

    It is possible to connect sensors with a normally open alarm-switch, and

    sensors with a normally closed alarm-switch. All the input Zones are pro-grammable as NC, NO, Balanced or Double balanced.

    If Zones are to be used as Balanced or Double Balanced Zones , use the

    10 K resistors provided.

    If programming of the Zones as NC (Normally Closed) or NO (NormallyOpen) is required, balancing resistors are not necessary.

    Figure 15 Sensor connection to Balanced line.

    INSTALLATION 37

  • 7/25/2019 Omnia Installation Manual

    38/158

    Double

    balancing

    By means of the double balancing mode, and by connecting 4 wires to the

    sensors, it is possible to obtain information on both sensor alarm and tam-per. In this way, it is possible to identify the sensor signalling alarm.

    The diagrams show the connections for the three balancing types (NC,

    Balanced, Double Balanced), required for the connection of an alarm sen-sor to a Zone.

    The sensor supply is protected by fuse 18, burnout of this fuse is shown bythe LED on the LCD Keypad.

    + The tamper-switch connection (terminals A.S.) is dealt with separately inthe Balanced tamper-line connection" paragraph.

    Figure 16 Sensor connection to Double Balanced line.

    Figure 17 Connection of three fire detectors.

    38 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    39/158

    Fire sensors

    Omnia control panel is able to manage fire sensors, providing that thesecan operate with 12 V supply voltage and are equipped with an alarm re-

    peat output (for example the BENTEL sensors RT101-102 or RF501).

    For the connection of one or more fire sensors proceed as shown in fig-ure 17.

    The fire sensor outputs should be connected to an Omnia Zone, pro-grammed as Fire. Sensors are supplied by terminal +F, whilst ground

    should be taken from an Omnia output (in the example the auxiliary output

    15 [OC1] is used), programmed as 20 seconds, monostable, NC. The out-put must be assigned to an event intended for fire sensor reset, for exam-

    ple Control Panel Default or "Area Default".

    + Please remember that terminal 15 [OC1] can support a max. 1 A currentvalue.

    Alarm-device connection

    Alarm devices signal alarm conditions, typical alarm devices are self-pow-ered sirens, indoor sirens, telephone diallers and so forth.

    These devices may be classified according to their activation mode in thefollowing way:

    stand-alone safety devices, enabled by voltage failure on the specific ter-

    minal; self-powered sirens belong to this category.

    Positive alarm line devices, enabled by a positive (12 V) on the specific ter-

    minal; indoor sirens usually belong to this category.

    Negative alarm-line devices, enabled by ground on the specific terminal.

    Balanced alarm-line device, enabled by the impedance offset on the spe-cific terminal.

    Figure 18 Connection of self-powered siren and indoor siren.

    INSTALLATION 39

  • 7/25/2019 Omnia Installation Manual

    40/158

    Omnia is provided with terminals 8 [+A1] and 13 [+A2] for the connection

    of two indoor sirens, and terminals 9 [+N1] and 14 [+N2] for the connectionof self-powered sirens (fig. 18).

    The free-voltage exchanges of the two alarm relays (terminals 5, 6, 7 and

    10, 11, 12) are for the connection of all types of signalling devices.

    + Although there are two alarm relays with relevant terminals, as described

    above, Omnia also has a further 34 open-collector outputs (2 on themother board and 4 on each of the 8 connectible output expanders), each

    of these may be programmed as an alarm output and may pilot a relay.

    The diagram below illustrates a connection example of a self-powered si-

    ren and an indoor siren, connected to the first alarm relay.

    + The connection of tamper switches (terminals [S] and [S1]), is dealt withseparately in the "Balanced tamper-line connection" paragraph.

    Balanced tamper-line connection

    Omnia is provided with a 24h balanced-type tamper line, for the connectionof the tamper switches on the security-system devices. Connection is to becarried out as follows (see fig.19):

    Connect the tamper switches of the security system in series.

    Connect one end of the series to terminal 27[ASB] and the other to termi-

    nal 26[ ]; connect the balance resistor to the last device.

    When making use of the tamper line, the information relevant to the tam-

    pered device is not available. If this information is required, when connect-

    ing sensors, use the Double Balancing mode or, a 24h zone for tamperdetection on other devices.

    Figure 19 Connection of tamper switches.

    40 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    41/158

    Telephone-line connection

    If the telephone communicator functions are used, the telephone line must

    be connected to terminals 53, 54 [LE]. If the telephone line is shared withanother telephone, the latter must be connected to terminals 55, 56 [LI], inthis way Omnia always gives priority to the telephone device connected tothe [LI] terminals and commutes it only when necessary.

    The ground [ ] terminal must be connected to the ground connector of theelectrical system, in order to protect the electronic card from surges thatmay come from the telephone line.

    ATTENTION The safety protection of the telecommunication network

    depends on the perfect condition of the entire ground protection.

    Power-supply connection

    The Omnia Control Panel is supplied by a mains voltage of 230 V / 50 Hzand by means of :

    an integrated power supply on the electronic board of the OMNIA model;

    a switching power supply located at the bottom of the OMNIA/S model box.

    The mains supply wires must be connected to the terminals 23, whilst the

    buffer battery must be connected to the connectors 24.

    ATTENTION Connect the phase to terminal [L] (marked [F] in the

    Omnia control panel) and connect terminal [ ] (marked [ ] in the

    Omnia control panel) to ground. Please remember that all the territorialregulations in force must be respected.

    As soon as power is supplied to the Main unit, the green LED , on thefront panel will switch ON, whereas, after the initial configuration stage the

    red LEDs and will switch OFF.

    + The buffer battery should be connected before the mains voltage.

    Figure 20 Telephone line connection diagram.

    INSTALLATION 41

  • 7/25/2019 Omnia Installation Manual

    42/158

    Auto

    configurat ion

    On first startup the Control Panel performs an Auto-configuration cycle.

    During this cycle the Control Panel acquires the configuration of the de-vices connected to the bus. This becomes the basic configuration of the

    Control Panel and may only be modified by the installer. This step lasts

    about 15 seconds and is indicated by the flashing of the red LED .

    At the end of this step, which is signalled by the following configuration on

    the Keypad display , insert jumper 7(MEM) whichenables the non-volatile memory to store the programmed data even dur-

    ing mains supply failure.

    ATTENTION On startup the storage memory is completely down.About 1 hour is required to charge it to a level that will ensure storage

    of the programmed data for 1 month of complete power supply failure

    (both external supply from the mains network and from the auxiliarysupply, provided by the battery housed at the bottom of the Main unit

    container). In order to charge the storage battery jumper 7 (MEM)mustbe connected.

    + There is no Open-Control-Panel alarm on startup, as this is disabled untilthe Control Panel cover is closed. Similarly, when quitting a programming

    session, either via Keypad or local/remote PC connection, the Open-Con-

    trol-Panel alarm results disabled until the cover is replaced, afterwhich,opening of the Control Panel provokes a tamper alarm.

    If the network voltage fails, supply is ensured by the buffer battery and fail-

    ure is signalled:

    on the front panel of the Main unit, by the LED switching OFF;

    on the Control Keypads, by the LED switching ON;

    by event no. 223 - Warning mains failure- that may be assigned to anaction on an output or on the communicator (this event may be delayed, by

    a programmable timeout).

    Causes of malfunction must always be found and eliminated before thebattery runs down. When the buffer battery is low, and therefore requiring

    immediate action, if functionality loss is to be avoided, it is signalled by

    event no. 224 - Warning low battery, which may be assigned to an actionon an output or on the communicator. However, when power is restored,

    the Control Panel regains its previous configuration, this is due to the non-volatile memory which logs all the status changes that occur during Control

    Panel functioning.

    : 1 1996/ 5/ 3DDDDDDDD

    42 Expandable Multifunction Control Panel Omnia

  • 7/25/2019 Omnia Installation Manual

    43/158

    PROGRAMMING

    All Omnia parameters may be defined in the optional program, which runs

    in Windowsenvironment, or may be programmed from the Control PanelKeypad. Programming from the PC is much easier than programming from

    the Keypad, therefore, the program in Windowsenvironment is used forthe Omnia parameter descriptions.

    + For a complete description of the Omnia program, see the "Omnia-Norma-Com software" manual.

    Omnia parameter programming is divided into several pages, which grouptogether parameters concerning the same feature. The following para-graphs describe the programming pages, as displayed by the Omnia pro-gram.

    Customer

    This page is for Customer details: the data entered in the Address, City,

    Customer tel.num and Installation description fields are for installeruse, and are not fundamental to programming. However, the data enteredin the following fields are essential.

    Name This is the name the program uses to identify a customer, and to display

    the data defined in the various pages.

    Instal lat ion tel .

    num.

    This is the telephone number the Control Panel is connected to. This num-

    ber is dialled by the OmniaMOD modem, when the Connectingcommand

    from the Modemmenu is selected.

    The Installation tel. num. field accepts digits from 0 through 9 and also

    the comma (,): the comma is for pauses, for example, between a tele-

    phone number and area code.

    Customer code When an Omnia Control Panel calls the OmniaMOD modem (for teleserv-

    ice or the test call) the modem recognizes the Control Panel by the code

    entered in this field; therefore, each Control Panel must have a differentCustomer Code. If a duplicate Customer Code is assigned, the existence

    of the code, and the Control Panel it is assigned to, will be signalled whenan attempt to save modifications is made.

    + The Customer Code specified in this page is the same as the code in the{Teleservice} page, therefore, any changes made to either code will affectthe other automatically.

    Firmw are release This field cannot be modified within the Customer page; by selecting theFirmware releasecommand from the Optionmenu, the field displays the

    set value and indicates the parameters that may be defined in the pro-gram, according to the version of the connected Control Panel.

    PROGRAMMING 43

  • 7/25/2019 Omnia Installation Manual

    44/158

    Date of Last

    change

    This parameter cannot be modified manually, and it is updated automat-

    ically to the date of the last modification for the selected customer.

    Notes This button opens a window for notes on the selected customer and sys-

    tem. These notes do not appear in the Installation descriptionfield. If the

    note pad is empty, the icon on the button shows an empty page, otherwise,a full page is shown.

    Configuration

    The definition of the Control-Panel configuration is essential for proper pro-

    gramming and functioning. The Control Panel must be able to recognizethe communication-bus configuration, and detect the removal of any de-

    vice from the communication bus, as this may be due to tamper.

    On initial Startup the Control Panel performs an auto-configuration cycle,

    which sets the configuration of the BPI bus devices (see the "Power supply

    connection" paragraph). Any changes in the configuration must be carriedout by the installer.

    + If the Control Panel is connected to a PC, the configuration may be read byselecting the Load > Pagecommand on the Programmingmenu (see the

    relevant paragraph).

    The configuration programming page is divided into different sections, onefor each device type (Keypads, Key readers, Input expanders, Output ex-

    panders, Power stations).

    Figure 21 Client description page.

    44 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    45/158

    Each section has a series of boxes, a number indicating the device ad-

    dress is situated near each box. This address is set by means of the dip-switches on the various peripheral devices (see the "Peripheral device

    connection" paragraph).

    In order to set the configuration, it is necessary to select the required pe-ripheral devices. If a marker is present, the device is already in the configu-

    ration; if not (white box), the device is not in the configuration. Devices notincluded in the configuration are not controlled by the Control Panel andshould be considered as "virtually disconnected".

    After setting the device configuration, it is possible to program some of thecharacteristics in the Detailswindows. The parameters for all device types

    (Keypads, Key readers, Input expanders, Output expanders and Power

    Stations) must be specified in the Detailswindow; it is also necessary todefine the Keypad and Key reader parameters, according to the instruc-

    tions in the relevant paragraphs.

    no . This is the peripheral device ID number (the device address), which de-

    pends on the configuration of its dip-switches.

    Descript ion It is possible to assign a name, with a maximum of 16 characters, to eachdevice, this name is used as the device identifier in all the operations it is

    involved in.

    Figure 22 System configuration page.

    PROGRAMMING 45

  • 7/25/2019 Omnia Installation Manual

    46/158

    Keypads

    1 ... 8 This specifies the Areas a Keypad can operate on (Arm, Disarm, etc.).

    + A Keypad may be unable to operate on any Area, however, it may be usedfor programming, display and all other functions that do not involve Areas.

    Key readersOmnia functions may be checked by simply inserting a valid Electronic keyinto a Key reader, for functions such as:

    Area arming;

    Area disarming;

    Type A or B arming;

    Alarm stop on Areas.

    Omnia can manage up to 16 Key readers and up to 250 Electronic keys.

    The parameters described in the following paragraphs can be defined foreach Key reader, whereas, Electronic key programming may be carried outvia Keypad, as described in the "Electronic keys" paragraph.

    RED spot m arker This indicates the Areas the Key reader can operate on (arm, disarm, and

    stop warning signals): Areas are indicated by their identifier number (1through 8); cells containing "Yes" (where the row indicated by the RED

    spot marker slices the Area identifier number row) indicate the Key reader

    is enabled on the corresponding Area; by double-clicking or pressing theENTERkey on the selected cell, the status of the corresponding Area can

    be changed.

    AMBER spot

    marker

    This indicates the Areas to be armed (A) and those to be disarmed (D),among those enabled, on extraction of the Electronic key when the AM-

    BER LED is ON: in order to change an Area status double click or pressthe ENTERkey on the corresponding cell.

    GREEN spo t

    marker

    This indicates the Areas to be armed (A) and those to be disarmed (D),

    among those enabled, on extraction of the Electronic key when theGREEN LED on the Key reader is ON.

    46 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    47/158

    Zones

    Omnia is provided with 8 input Zones on the Main unit, that can be ex-

    panded to 80 by means of Keypads, each equipped with 1 Zone, and by 4Zone Input expanders, these are available on request.

    Omnia Zones (terminals [Zx]) may be programmed as Alarm or Command

    Zones.

    Alarm Zones Violation of an Alarm Zone generates an alarm event Alarm on zone no..It is possible to assign one or more actions to an alarm event (activation ofsirens, digital communicator, telephone dialler etc.).

    Before generating an alarm event the Control Panel checks whether the Zone

    Area is armed (see "Areas").

    If the Zone is not an Entry delayor Last exit zonetype (see "Type"), theControl Panel starts alarm status detection as soon as the Zone Area is

    armed, otherwise, the alarm starts when the Exit time for the Areas has

    expired (see "Areas").

    The alarm status occurs when the Zone is unbalanced (see "Balancing")

    for the programmed number of times and timeout (see "Sensitivity").Each Zone can generate the Zone Alarm event for the programmed num-

    ber of times only (see "Cycles").

    Command Zones When Command Zones are violated (or activated), they generate one ofthe following actions:

    Area status commutation;

    Area arming only;

    Area disarming only;

    Area reset;

    Control Panel reset;

    Clear call queue.

    In order to acknowledge a Command Zone as activated, it must be unbal-anced (see "Balancing") for the programmed number of times and timeout

    (see "Sensitivity").

    Zone chart

    The left side of the programming page holds a chart which shows theZones available, in accordance with the expanders indicated in the {Con-fig.} page. Data must be entered on the right side of the page, whichshows the programming relevant to the Zone selected on the left. The fol-

    lowing parameters are indicated, on the left, for each Zone.

    no . This is the Zone ID number, that is used instead of the full description (see

    "Description"): for example, when performing a Control Panel status en-quiry via telephone.

    PROGRAMMING 47

  • 7/25/2019 Omnia Installation Manual

    48/158

    Posit ion This is the description of the hardware component the Zone is assigned to:

    this description may be changed in the {Config.} page and may be used,for example, to indicate the installation position of a device.

    Device This is the device identifier number (address) of the peripheral the Zone is

    assigned to.

    It is a number from 1 through 8 for Keypad Zones, and a number from 1

    through 16 for Input-Expander Zones. This parameter is not present on Main-Unit Zones.

    Ter. These are the initials that identify the Zone on the terminal board of the de-

    vice the Zone resides on. This parameter is also the sequential number ofthe Zone on the device.

    Descript ion This field accepts a maximum of 16 characters, and is for the name which

    identifies the Zone. This name will be used as Zone identifier, in all parts ofthe program and in the event logger.

    Area This indicates the Area the Zone is assigned to (Zone Area). If the Zonetype is a Command Zone, an asterisk is displayed in this field.

    All the programmable parameters, of the Zone selected in the Zone Chart

    in the programming page, may be modified in the right side.

    These parameters are described as follows.

    Figure 23 Zone programming page.

    48 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    49/158

    Description

    This modifiable field accepts a maximum of 16 characters, and is for aname that will identify a Zone. This name will be used in all parts of the

    program as Zone identifier. This description is shown in the left side of the{Zones} page. The sequential number of the Zone is shown to the left ofthe description field, by a number from 1 through 80.

    Type

    This shows the intervention times of the Alarm Zones, that is, whether theymust signal an alarm condition immediately or with a delay, independent of

    the status of the latter.

    + This parameter definition determines, amongst other things, if Zone viola-tion will generate Fire, 24h or Burglar type alarm events, at both Area and

    Control Panel level. If the Zone is not defined as Fire or 24h type, it will be

    implicitly regarded as Burglar type.

    Immediate When the Zone is violated, the following events are generated immedi-ately:

    Alarm on zone no.;

    Burglar alarm on area no., Generic alarm on area no. and Ge-neric+Tamper alarm on area no.on the Zone Area;

    Burglar alarm on panel, Generic alarm on paneland Generic+Tamper

    alarm on panel.

    Entry d elay When the Zone is violated, and the Entry timeset for the Zone Area is ac-

    tive, no event is generated; if the Area is not disarmed after timeout, or ifthe Zone is violated after this period, the events indicated for the Immedi-

    atetype are generated.

    The first Zone that must be violated on the path to a disarm-point of theZone Area, should be of this type.

    Entry path When the Zone is violated after an Entry delayZone, the events specified

    for the Immediatetype are generated, after the Entry time has expired.

    If the Entry timeis not active or has expired, the events shown for the Im-mediatetype are generated.

    Zones that must be violated on the path to a disarm-point of the ZoneArea, should be of this type.

    Exit delay If a Zone is violated during the Exit timeof the Zone Area, no events aregenerated; otherwise, the events specified for the Immediatetype are gen-erated.

    Zones that must be violated in order to exit the Zone Area, should be of

    this type.

    PROGRAMMING 49

  • 7/25/2019 Omnia Installation Manual

    50/158

    Last exit zone If a Zone is violated during the Exit timeof the Zone Area, no events are

    generated, but this modifies the Exit time in accordance with the settingfor the Last exit timeof the Zone Area, otherwise, the events indicated for

    the Immediatetype are generated.

    The last Zone violated on Zone Area exit, should be of this type.

    24h When a Zone is violated, whether the Zone Area is armed or disarmed, the fol-

    lowing events are generated:

    Alarm on zone no.;

    24h alarm on area no., Generic alarm on area no.and Generic+Tam-per alarm on area no.on the Zone Area;

    24h alarm on panel, Generic alarm on panel and Generic+Tamper

    alarm on panel.

    Fire When a Zone is violated, whether the Zone Area is armed or disarmed, thefollowing events are generated:

    Alarm on zone no.;

    Fire alarm on area no., Generic alarm on area no.and Generic+Tam-

    per alarm on area no.on the Zone Area;

    Fire alarm on panel, Generic alarm on panel and Generic+Tamperalarm on panel.

    Attributes

    + The following parameters affect the Alarm Zones only, and do not affectthe Command Zones.

    Not By passable If this attribute is selected, the Zone cannot be bypassed.

    Chime If the Zone Area is disarmed, violation generates the Chime on area no.event, and there is a beep signal on the enabled Keypads of the Zone

    Area. If the Zone Area is armed, it performs as specified in the Typepa-

    rameter.

    + The Chimeattribute does not affect the 24hor FireZones.

    Test The Zone is operative to all effects, but instead of generating the eventAlarm on zone no. it stores the message in the Control Panel event logger: in this way, it is possible tocheck the status of a suspect Zone, without provoking alarm signalling. By

    means of the Optionswindow in the Programming menu, it is possible toselect whether the event logger should log events only when the Area is

    armed (default), or also when the Area is disarmed.

    Autobypassable If this attribute is selected, the Control Panel can bypass the Zone, whenthe Zone results violated during Zone Area arming. The Zone is un-by-

    passed automatically, on the successive disarming of the Zone Area.

    + The Autobypassableattribute does not affect the Exit delayZone types.

    50 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    51/158

    Balancing

    This specifies the electrical conditions that must be present on the inputterminal, in order for the Control Panel to acknowledge violation on the cor-

    responding Zone.

    + The following conditions must be present for at least 300 mS (milliseconds= 0.3 seconds), in order for them to be recognized by the Control Panel.

    Normal ly open When normal, the Zone must be open; when it is connected to ground the

    Control Panel acknowledges Zone violation (e.g. connections to fire detec-

    tors).

    Normal ly closed When normal, the Zone must be connected to ground; when the Zone is

    open the Control Panel acknowledges Zone violation.

    Balanc ed 10K When normal, the Zone must be connected to ground with a 10K (10,000

    ohm) resistance; if short-circuited to ground the Control Panel acknow-ledges tamper and generates the following events:

    Tamper on zone no.;

    Tamper alarm on area no.and Generic+Tamper alarm on area no.on

    the Zone Area;

    Tamper alarm on paneland Generic+Tamper alarm on panel.

    In all other cases (unbalanced, open Zones etc.) the Control Panel ac-knowledges Zone violation (see "Type").

    Doub le balanced The Zone must be connected to ground with two10 K (10,000 ohm) resis-

    tances; if one of these is disconnected, the Control Panel generates events

    according to the Zone Type (see the "Type"); in all other cases (openZones, Zones connected to ground, etc.), the Control Panel acknowledgestamper and generates the events indicated for tamper on the balanced

    Zone with 10K.

    By means of just 2 wires, this balancing type allows detection of both theopening of the alarm switch and the tamper switch of the connected sen-sors (see "Alarm sensor connection").

    + There is no reason to program Double balancing for a Command Line, asevent recognition Tamper on zone no.does not generate any actions.

    PROGRAMMING 51

  • 7/25/2019 Omnia Installation Manual

    52/158

    Cycles

    This parameter shows the number of times the Zone being programmedcan signal an alarm condition before being bypassed on the analysis. The

    following values are possible.

    0 Violations on the Zone are ignored.

    1 254 The Zone signals the alarm condition for the set number of times, it is thenbypassed until one of the following conditions, which will clear the alarm-cycle counter, occurs:

    status change of the Zone Area;

    reset of the Zone Area;

    quitting of the Stop-Alarm condition for the Zone Area (via Keypad by

    means of a Code or via Key reader by means of a Electronic key);

    quitting of a programming session (via Keypad or by means of local or re-

    mote connection).

    Repetit ive The number of times the Zone can signal an alarm condition is unlimited.

    + Zones with a persistent alarm status (e.g. due to a malfunction) generateonly one alarm cycle. This function mode is explicitly required by CEI 79/2regulations. They may generate a new cycle only if the alarm counters are

    cleared or if the Zones are un-bypassed.

    Area

    Alarm Zone Command Zone

    This shows the Zone Area of theZone being programmed andtherefore, the enabled Codes, Keys

    and also function times: each AlarmZone should be assigned to one Area

    only; it is unnecessary to assign aZone to several Areas, as Omnia

    manages Area dependency (see

    "Areas").

    This shows the Areas of theCommand Zone in question: eachCommand Zone can operate on

    more than one Area.It is not possible to specify the

    Areas for the Panel Reset andClear Calls commands, as this

    parameter is not influential for this

    command.

    Sensitivity

    Standard This shows the number of times the Zone must be violated (see Pulses)

    during the programmed delay time (see Within parameter), before the

    Control Panel acknowledges alarm status.

    Low In order for the Control Panel to acknowledge the Zone as in alarm status,

    it is necessary that violation is detected for the programmed time (seePulse length). Please note the time is programmed in full minutes and the

    programmable time ranges from 1 through 16 minutes. Although, for theKeypad Zones, the time is to be estimated with a margin of about 30 sec-onds less than that actually set.

    52 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    53/158

    Voice messages

    This parameter permits the assignment of two of the 14 Voice messages,that Omnia is able to record, to the Zone being programmed; in this way,

    by means of the Omnia inputs, it is possible to check the status of an ap-pliance (e.g. heating system) via telephone.

    Standby This message is played when the Zone is in standby status.

    + If there is no Voice message indicated in the Standby field, the standbystatus of the Zone is signalled by a beep.

    Alarm This message is played when the Zone is violated.

    + If no Voice message is displayed in the Alarmfield, the Alarm status of theZone is signalled by two beeps.

    Messages... This button opens a window, similar to that in figure 28, for the 16-charac-ter description of each of the 14 messages that Omnia is able to record:the changes made in this window may be programmed on the ControlPanel by using the Sendbutton on the Messageswindow.

    + Recording, playback and deletion of Voice messages is carried out via theControl Keypad, and requires installation the OmniaVox kit (Voice board +Microphone board + loudspeaker), available on request.

    PROGRAMMING 53

  • 7/25/2019 Omnia Installation Manual

    54/158

    Outputs

    Omnia has 4 outputs on the Main unit, that may be expanded to 36, by

    means of up to 8 Output expanders of 4 outputs each, these are availableon request.

    All outputs are programmable and may be assigned to the events man-

    aged by the Control Panel for the signalling of alarm status, by means of

    sirens, flashers etc., outputs may also be used for signalling operating ormalfunction conditions, and also to provide control signals for other de-

    vices, and so forth.

    The outputs may also be programmed for the remote control of appliances

    (e.g. the heating system), via telephone.

    All the outputs on the expanders are 150 mA open-collectors, that is, terminalsthat can earth a maximum current of 150 mA or result open; each expander

    board is equipped with a buzzer that may be connected to output 4 (terminal

    [OC4]) with positive or negative logic, according to the position of jumper 64.

    The Control Panel is equipped with two 1 A open-collector outputs and two3 A relays.

    Each of these forms a Stand-Alone security output, marked +Nx for control

    of the 12 V self-powered siren, a positive output marked +Ax for indoor si-

    rens and 12 V flashers and a free exchange on terminals Cx, NCx e NAxfor the connection of those devices that cannot be directly connected to the

    above mentioned terminals (e.g. 24 V indoor and self-powered sirens, 24 Vflashers for fire systems).

    Outputs and

    Events

    The description of the action that each activated output will perform, is to

    be defined in the {Outputs} page. Specifications as to when an output is tobe armed (or disarmed), are to be made in the {Event-Actions} page. Theprogramming definition of an output, as shown, coincides with the action

    description. Therefore, when assigning an output action in the {Event-Ac-tions} page, it is necessary to indicate the required output only, as the ac-

    tion the output performs is completely defined by its programming.

    Several events may activate the same output. When checking program-ming, it may be helpful to have a list of all the events that activate a given

    output.

    The Eventsbutton, in the {Outputs} page is for this purpose.

    On selecting this button the program shows the list of events that activatethe output selected in the output chart (left side of the programming page).

    In this way, there are two distinct ways of displaying the allocation of the

    Events and Actions to the outputs:

    the {Event-Actions} page shows which outputs are activated for each

    event;

    the {Outputs} page shows which events activate each output.

    54 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    55/158

    Output chart

    The left side of the page shows the Outputs available, according to the ex-panders shown in the {Config.} page. It is not possible to enter data in this part

    of the page. Data may be entered in the right side of the page where the pro-gramming of the Output selected in the left side is shown. The following pa-rameters are displayed, for each Output, on the left side of the page.

    no . This is the ID number to be specified in the {Event-Actions} page, in orderto assign the corresponding output to the required events.

    Posit ion This is the description of the hardware device on which the output is lo-

    cated: this description may be changed in the {Config.} page and may beused, for example, to indicate the installation position of the expander,

    making it easy to locate when necessary.

    Device This is the ID number (address) of the device the output resides on.

    Therefore, for Output expander Output, this may be a number from 1 to 8.

    This parameter is not available for the Main unit Outputs.

    Ter. Shows the initials that identify the output on the terminal, the output re-

    sides on. This parameter is also the sequential number of the output on the

    device. The 2 relays on the Main unit are generally identified as RL1 andRL2.

    Descript ion Shows the description given to the Output.

    Type Shows whether the output is programmed as Bistable(B) or Monostable

    (M).

    At t r ib . Shows whether the output is programmed as Normally closed (NC) orNormally open(NO).

    Reserv. Shows whether a Output is Reserved for manual use by the user. Themanual arming of an output is available to the user via the system Key-pads (USER MENU, Outs management) or via telephone.

    Timing If the output is programmed as Monostable, this field shows the pulsetime the output emits when activated by an event. If the output is pro-

    grammed as Bistablethis field is empty.

    All programmable parameters concerning the output selected in the Outputchart of the programming page, may be modified in the right side of thispage. The following is the description of these parameters.

    Description

    This is a modifiable field, with a maximum of 16 characters, for the name

    assigned to each output, this name is used in all other parts of the programas the output identifier. This description is immediately transferred into the

    left side of the {Outputs} page. The sequential number of the output is indi-

    cated to the left of the description field, by a number from 1 through 36,

    PROGRAMMING 55

  • 7/25/2019 Omnia Installation Manual

    56/158

    Reserved

    Omnia outputs may be used for remote control of electrical appliances(switch ON - switch OFF), both via Keypad or via telephone.

    If this option is selected the output cannot be assigned to Omnia events

    and therefore, its status is determined exclusively by the commands givenvia Keypad or via telephone.

    Monostable programming is not necessary, for outputs programmed inthis way, as the output is armed and disarmed by the user.

    (Please see the "Output activation" paragraph and the "TELEPHONE OP-ERATIONS" chapter in the USER MANUAL).

    Type

    Bistable This is activated when at least one of the assigned events occurs; it is re-set when all the assigned events end.

    Monostable This is activated, if not already so, each time at least one of the assignedevents occurs; it remains active for the programmed On time, then returnsto standby status for the programmed Off Time, at least.

    Attribute

    This specifies the normal electrical status of the output being programmed.

    Normal ly open The open-collector outputs (terminals [OCx]) are open; the Stand-Alone

    outputs (terminals [+Nx]) are open; on the positive outputs (terminals[+Ax]) is the positive (13.8 V); the Common contacts of the free voltage ex-

    change of the output relays (terminals [Cx]) are closed on the correspond-ing Normally open contacts (terminals [NAx]).

    Normal ly closed Negative is on the open-collector output (terminals [OCx]); positive

    (13.8 V) is on the Stand-Alone outputs (terminals [+Nx]); the positive out-

    puts (terminals [+Ax]) are open; the Common contacts of the free voltageexchange of the output relays (terminals [Cx]) are closed on the corre-

    sponding Normally Closed contacts (terminals [NCx]).

    Timing

    On t ime This is the maximum activation time for the output being programmed.

    + The On timeis relevant only to the Monostableprogrammed outputs, asthe Bistableoutput is reset when all the assigned events end.

    Each Monostableoutput may have a different On time:

    from 0.0 through 25.4 seconds, with steps of 0.2 seconds, if the Sec.op-

    tion is selected;

    from 1 through 128 minutes with steps of 1 minute, if the Min.option is selected.

    The default On timefor each Monostable output is 3 minutes.

    56 Expandable Multifunction Control Panel OMNIA

  • 7/25/2019 Omnia Installation Manual

    57/158

    Off Time

    This is the minimum time that must elapse before the output may be acti-vated again.

    + There is only one Off Timefor all Monostableoutputs, which is irrelevantfor Bistableoutputs.

    It is possible to set an Off Timeof 0.0 through 127.5 seconds, with stepsof 0.5 second (default = 6.0 seconds).

    Figure 24 Output programming page.

    PROGRAMMING 57

  • 7/25/2019 Omnia Installation Manual

    58/158

    Areas

    An Area is a group of Zones that Omnia manages separately (Virtual Con-

    trol Panel). It is possible to define control codes, timers, output actions andother parameters, for each Area; these may be different to those definedfor other Areas that, however, may interact with one another.

    Omnia can manage up to 8 Areas, the composition of which is defined in

    the {Zones} page.

    + Each Area may be made up of many input Zones, however, each Zonemay be assigned to one Area only.

    the Area parameters, described in the following paragraphs, are to be de-

    fined in this page.

    no . This is the non-modifiable Area ID number, to be used when it is not possi-ble to use the Area description (see following paragraph): e.g. status en-quiry via telephone.

    Descript ion This is a modifiable field, with a maximum of 16 characters, for the as-signed name of an Area, this name will be used in all other parts of theprogram and in the event logger, and will allow clear identification of the

    Area.

    Entry t ime This determines the timeout delay that is generated by Zone violation of aEntry delay-Zone Type. The Entry timeis signalled by:

    the event activation Entry time on area no.relevant to the violated Area;

    an acoustic signal on every enabled Keypad relevant to the violated Area.

    If the Area is disarmed before the timeout expires, no alarm occurs.

    Exit t ime It is possible to violate an armed Exit delayZone, during th