on-site leaching chamber specifications & features...before beginning installation, please note...

32
On-Site Leaching Chamber Specifications & Features Design & Installation Manual – Maine

Upload: others

Post on 12-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

On-Site Leaching Chamber Specifications & Features

Design & Installation Manual – Maine

Page 2: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

2

•This manual provides general design and installation information for Arc/BioDiffuserLeachingChambers.

•AllArc/BioDiffuserchamberconfigurationsandinstallationsmustcomply withstateandlocalrules.

•Thismanual containsabriefdescription foreachchambermodeland generaldesignandinstallationprocedures.Formoredetailedinformation pleasecontactcustomerserviceat1-800-733-0535.

•ForCADdrawingsrefertoourwebsite:www.arc-chamber.com.

Contents

Introduction 2

ProductSpecificationsandTypicalConfigurations

Arc36System 4

Arc36HighCapacitySystem 6

11"StandardSystem 8

16"HighCapacitySystem 10

Arc18System 12

Bio2System 14

InstallationInstructions 16

TypicalInstallations:Trench,BedandSerial 18-20

AdditionalSystemConfigurations

MoundConfigurationSystem 21

PumpSystems 22-23

PressureDosingSystem 24

SidePortCouplerSystemOptions 25-26

SystemSizingCharts 27-30

Page 3: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

3

Arc 18 System•16”WideChamber•NewLightweightDesignwithArticulating JointsandPivotLockoutFeature•H–10loadratedwithproperinstallation.•SeePages12-13

Arc 36 System•34"WideChamber•NewLightweightDesignwithArticulatingJoints• H–10loadratedwithproperinstallation.•SeePages4-5

INCLUDED SYSTEMS

Arc 36 HC System•34"WideChamber•NewLightweightDesignwithArticulatingJoints• H–10loadratedwithproperinstallation.•SeePages6-7

11” Standard System•34”WideChamber•H–10loadratedwithproperinstallation.•SeePages8-9

16” High Capacity System•34”WideChamber•H–10loadratedwithproperinstallation.•SeePages10-11

Bio 2 System•15”WideChamber•H-10loadratedwithproperinstallation.•SeePages14-15

Page 4: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

4

Before beginning installation, please note the following engineered features of the Arc 36 model chambers and end caps.

Arc 36 System

60"EffectiveLength

PostEnd 7"InvertHeight

14"InstalledLength

34"

13"6.5" 9"

Arc 36 ChamberLength 63"

RepeatLength 60"OverallWidth 34"

SidewallHeight 7.13"InvertHeight 7.25"

OverallHeight 13"Capacity 8.04cuft(60.14gal)

Calculationsanddimensionsarenominal

Arc 36 Chamber—Top, Side, and End Views (nottoscale)

Arc 36 End Cap—Side, and End Views (nottoscale)

Side Port Coupler (SPC)

ArC 36 SYSTEM

Page 5: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

5

Arc 36 Features

•The post and dome creates a positive lock securing the chambersfor finalengagement.Lockanddropfeaturefor fasterinstallation.•TheArc36chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/venting knockout ports provide for inspection ofsystemperformanceaswellasaconvenientlocationfor drainfieldventilationpipes.•Eachchamberendhassmallknockoutsontheroofpositionedinthe“Post”endjoint.Whenremoved,theseknockoutsallowfortheuseofziptiestosupportpipingindosingsystems.

Arc 36 Universal End Cap

•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Knockouts can be removed with a knife or hole saw. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattachtothechamber’sdomeor postendinthesamefashionforeachendwiththeArc36 logofacingoutward.

Arc 36 Swivel Feature

•The engagement mechanism of the Arc 36 chamber is designedtoallowforapivotbetweenjoinedchambersofupto 10°ineitherdirection.

Arc 36 System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-25 (Serial,Pump,PressureDosing,andSidePortCouplerSystemOptions)

•ObservationPort

ArC 36 SYSTEM

•LockandDrop •LouversandFeet

Arc 36 Side Port Coupler

•SidePortCouplercomponentsnapsinplacetoallowsideentry atanyjointthroughoutthetrenchline.Thisaccessoryprovides avarietyofdesignandinstallationoptions.Refertopages22 and23fordesignconfigurations.

Page 6: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

6

Before beginning installation, please note the following engineered features of the Arc 36 HC model chambers and end caps.

Arc 36 HC System

60"EffectiveLength 34"

Arc 36 HC ChamberLength 63"

RepeatLength 60"OverallWidth 34"

SidewallHeight 10.75"InvertHeight 10.75"

OverallHeight 16"Capacity 10.7cuft(80gal)

Calculationsanddimensionsarenominal

Arc 36 HC Chamber—Top, Side, and End Views (nottoscale)

Arc 36 HC End Cap—Side, and End Views (nottoscale)

ArC 36 HC SYSTEM

PostEnd 10.5"Invert Height

14"InstalledLength

16"

9.5"

12.5"

Side Port Coupler (SPC)

Page 7: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

7

Arc 36 HC Features

•The post and dome creates a positive lock securing the chambersfor finalengagement.Lockanddropfeaturefor fasterinstallation.•TheArc36HCchamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/venting knockout ports provide for inspection ofsystemperformanceaswellasaconvenientlocationfor drainfieldventilationpipes.•Eachchamberendhassmallknockoutsontheroofpositionedinthe“Post”endjoint.Whenremoved,theseknockoutsallowfortheuseofziptiestosupportpipingindosingsystems.

Arc 36 HC Universal End Cap

•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Knockouts can be removed with a knife or hole saw. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattachtothechamber’sdomeor postendinthesamefashionforeachendwiththeArc36 logofacingoutward.

•ObservationPort

ArC 36 HC SYSTEM

•LockandDrop •LouversandFeet

Arc 36 HC Swivel Feature

•The engagement mechanism of the Arc 36 chamber is designedtoallowforapivotbetweenjoinedchambersofupto 10°ineitherdirection.

Arc 36 HC System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-25 (Serial,Pump,PressureDosing,andSidePortCouplerSystemOptions)

Arc 36 HC Side Port Coupler

•SidePortCouplercomponentsnapsinplacetoallowsideentry atanyjointthroughoutthetrenchline.Thisaccessoryprovides avarietyofdesignandinstallationoptions.Refertopages22 and23fordesignconfigurations.

Page 8: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

8

Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps.

11” Standard System

• Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.

11” Std ChamberLength 76”

RepeatLength 75”OverallWidth 34”

SidewallHeight 6.35”InvertHeight 6.5”

OverallHeight 11”Capacity 9.21cuft(68.42gal)

Calculationsanddimensionsarenominal

75”EffectiveLength 34”

11” STANDArD SYSTEM

11” Standard Chamber — Top, Side, and End Views(nottoscale)

11” Standard End Cap — Side, and End Views(nottoscale)

Page 9: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

9

11” Standard Features

•The post and dome creates a positive lock securing the chambersforfinalengagement.•The11”Standardchamberfeetaredesignedwithanextra largesurfaceareatoprovidesupport,particularlyinsandy soils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsallfortheuseofziptiestosupportpipingindosing systems.

11” Standard Universal End Cap

•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattach thechamber’sdomeor postend.

11” Standard System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)

•Interlockingjoint •LouversandFeet

•ObservationPort •ZipTieKnockouts

11” STANDArD SYSTEM

Page 10: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

10

Before beginning installation, please note the following engineered features of the 16” High Capacity model chambers and end caps.

16” High Capacity System

• Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.

16” High Capacity Chamber

Length 76”RepeatLength 75”OverallWidth 34”

SidewallHeight 11.17”InvertHeight 11.6”

OverallHeight 16”Capacity 13.6cuft(101.0gal)

Calculationsanddimensionsarenominal

75”EffectiveLength 34”

16” HIGH CAPACITY

16” High Capacity Chamber — Top, Side, and End Views(nottoscale)

16” High Capacity End Cap — End View(nottoscale)

Page 11: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

11

16” High Capacity Features

•The post and dome creates a positive lock securing the chambersforfinalengagement.•The16”HighCapacitychamberfeetaredesignedwithanextra largesurfaceareatoprovidesupport,particularlyinsandy soils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsallfortheuseofziptiestosupportpipingindosing systems.

16” High Capacity Universal End Cap

•Upperand lowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.•Endcapsaredesignedtoattach thechamber’sdomeor postend.

16” High Capacity System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)

•Interlockingjoint •LouversandFeet

•ObservationPort •ZipTieKnockouts

16” HIGH CAPACITY

Page 12: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

12

Arc 18 System •Each chamber end is either marked “Dome” or “Post” on the roundobservation/ventknockoutports.Theseindicatedirectionof assembly,domeoverpost.

Before beginning installation, please note the following engineered features of the Arc 18 model chambers and end caps.

Arc 18 ChamberLength 67”

RepeatLength 60”OverallWidth 16”

SidewallHeight 7.7”InvertHeight 6.24”

OverallHeight 12”Capacity 3.42cuft(25.6gal)

Calculationsanddimensionsarenominal

60”EffectiveLength 16”

ArC 18 SYSTEM

Arc 18 End Cap — Side, and End Views(nottoscale)

Arc 18 Chamber — Top, Side, and End Views(nottoscale)

Page 13: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

13

Arc 18 Features

• Baseflangesonthechambersendsoverlockduringfinal engagementtoformaverystrongjoint.

• TheArc18chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupportparticularlyinsandysoils.

• Sidewall louversaredesignedtoalloweffluenttoexitthe chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.

• Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswellasaconvenient location for drainfieldventilationpipes.

• Each chamber end has small knockouts on the roof positioned in the “Post” end joint.When removed, these knockoutsarefortheuseofziptiestosupportpipingindosing systems.

Arc 18 End Cap

• UpperandlowerknockoutsaccommodatebothSchedule 40 and SDR 35 piping. Dimples are also offered for thepositioningofholesawpilotdrills.

•Endcapsaredesignedtoattachthechamber’sdomeor postend.

Arc 18 System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)

•OverlockingEnds •LouversandFeet

•ObservationPort •ZipTieKnockouts

ArC 18 SYSTEM

Arc 18 Swivel Feature

•Eachchamber’spostendhasswivellockouttabsateitherbase flange.When removed, the incoming chamberwillturn up to ten degrees in the direction of the removedlockouttab.Withoutremovaloftheswivellockouttab,thechamberswillaligninastraightpattern.

•Swivellockouttabsmayberemovedcarefullywithautilityknife.

Page 14: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

14

Before beginning installation, please note the following engineered features of the Bio 2 model chambers and end caps.

Bio 2 System

• Each chamber end has either a rectangular dome or “H” postTheseindicatedirectionofassembly,domeoverpost.

Bio 2 ChamberLength 87”

RepeatLength 86”OverallWidth 15”

SidewallHeight 9.03”InvertHeight 6.95”

OverallHeight 12”Capacity 5.0cuft(37.1gal)Weight 19lbs

Calculationsanddimensionsarenominal

86”EffectiveLength 15”

Bio 2 System

Bio 2 Chamber - Top, Side, and End Views (nottoscale)

Bio 2 End Cap - Side, and End Views (nottoscale)

Page 15: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

15

Bio 2 Features

•Sideflangesonthechambersendsover lockduringfinal engagementtoformaverystrongjoint.•TheBio2chamberfeetaredesignedwithanextralarge surfaceareatoprovidesupport,particularlyinsandysoils.•Sidewall louversaredesigned toalloweffluent toexit the chambersidewallsinhighflowsituations,whilepreventing soilsfrommigratingintothechambervoid.•Observation/ventingknockoutportsprovideforinspectionof systemperformanceaswell as a convenient location for drainfieldventilationpipes.•Eachchamberpostendhassmallholesoneithersideof thepost.Whenremoved,theseallowfortheuseofzipties tosupportpipinginlowpressuredosingsystems.•BioDiffuserchamberscanbeinstalledtomeetanH-10live load(16,000lbs/axle).Backfillingwithaminimumof12”of properly compacted cover is required for these applications.

Bio 2 Universal End Cap

•UpperandlowerknockoutsaccommodatebothSchedule40 (4.5” OD) and SDR 35 (4.25” OD) pipes. Dimples arealsoofferedforthepositioningofholesawpilotdrills.•Endcapsaredesigned toattach thechamber’sdomeor postend.

Bio 2 System Configurations

•TrenchInstallation:Page18•BedInstallation:Page19•AdditionalConfigurations:Pages20-23 (Serial,PumpandPressureDosingOptions)

•OverLockingEnds •LouversandFeet

•ObservationPort •ZipTieOpenings

Bio 2 System

Page 16: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

16

Installation of End Caps & Pipe Connections•Prior to installing end caps, remove the appropriate knockout for pipe connections. Snap an end cap on each end of the drain lines with the product or company logo facing out (knockouts can be removed withaknifeora4"holesaw).

•Upperendcap4"knockouts—alwaysusedasinletfor eachline.Afour-inchholesawmaybeused.•Lowerendcap4"knockouts—usedforreturnlinesor continuouscircuitpipingperstateor localcode.These lower knockouts may also be used to create turns in the drain lines greater than the ten degrees provided bythechamberswivelfeature.

Splash Plates

•Splashplatesmustbeinstalledoneachinletendcap.•SplashplatesareprovidedwithArcsystemendcaps.•Knockoutmaterialmaybeused ifscrewedto thebase flangeoftheendcapwithastainlesssteelscrew.

Preparation•Excavatetoproperwidthanddepthasdescribedinthe systemdesignorpermitandasrequiredbystateand localcodes.•Smoothirregularitiesintheexcavationandclearanylarge rocksordebrisfromthebottomsurfacearea.Slopeof the bottom area shall be determined by the system design, as well as state and local codes. For bed installations,aminimumof6inchesisrequiredbetween chamberrows.

Installation

•Installation of the any ADS/Hancor Arc/BioDiffuser leachingsystembeginswithlayingthefirstchamberonto thepreparedbottomsurfacearea,withthe“dome”end ofthechamberattheheaderendoftheexcavation.Each additionalincomingchamberistheninstalledbyplacing itsdomeoverthepostofthechamberalreadyinplace. Asyoulowerthechambertotheground,pullittowards youtoengagethelockingmechanism.

•As the incoming chamber is lowered down onto the excavationbottom,thetwochambersfullyengageina straight-linepatterncreatingaverystrongjoint.

(Note: if the followingchamber issimply laidonto the precedingchamberthejointwillnotbefullyengaged.)

Turns

•TheArc36,Arc36HCandArc18chambersaredesigned withanarticulatingjointthatallowsforaturnofupto20°, withmaximumof10°ineitherdirection.

(Note:TheArc18isdesignedwithlockouttabs)

•IfaturnapplicationisdesiredwiththeArc18chamber, the lockout tabshouldberemovedbefore installing the incomingchamber.Thelockouttabislocatedatthebase flangeofthepreviously–installedchamber(onits“Post”end).•Remove the lockout tab and clean any remaining tab materialawayfromthechamber.

ArC/BIODIFFUSEr LEACHING SYSTEMS: INSTALLATION PrOCEDUrES

Page 17: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

17

•AllArc/BioDiffuserchambersareH–10 load rated. Wherevehicularloadingisanticipated,H–10loading (16,000 lbs/axle) is achieved by backfilling with aminimumof12"ofproperlycompactedcover.

•Do not drive heavy equipment over a system comprisedofnon-compactedcovermaterialwithout first bridging the excavation. Use lightweight or trackedequipmenttopushthesoilontothesystemto theproperheightsetforthbylocalandstatecodes.

Final Grade •Makecertainthatstormwaterisdivertedawayfrom the drain field. System final grade should be crested or sloped, never left flat or concave. Channelwaterawayfromthedrainfield.•Final grading subcontractors and landscapers shouldbealertedandinstructedtopropercovering procedures, cover materials, and finish contours andelevations.•Finalgradematerialshouldbeslightlytomoderately limitedsoiltohelpmaintainanaerobicstateinthe drainfield.•Stabilize the drain field area with grass-type vegetationpriortoheavyrainsifpossible.

Mound Installation Procedure

• Review Plans and stake out the entire leachingbed area. Confirm elevations of the septic tank,distributionboxandchambers.

•Clearandscarifyentireleachfieldareaincludingfillextensions.

•Confirm backfill material meets the Maine 804.2Backfill Standard. Place backfill material and usetheteethonthebuckettomixwiththeoriginalsoil.Placebackfillmaterialin12inlifts(300mm),compactusing a track vehicle. Continue placing backfillmaterialtothebottomelevationofthechambers.

•Refer tostandard installationproceduresonpage16andcontinuefromInstallationheading.

Ventilation Drainfieldventilationisrecommended,butnotrequired,toallowoxygentoaccessthedrainfieldespeciallywhencoversoilqualityisquestionable.•Knockoutsareprovidedonthe11"Standard,Arc36, andBio3chambers.Thedome/postfeatureoftheArc 18chamberalsoactsasaknock-outforobservation/ ventports.HereaPVCpipemaybeintroducedintothe chamberandventedtoatmosphere.•Makecertaintheventisassembledinsuchafashion astopreventrainwaterfromentering,effluentwaterfrom exiting,andpossibleodorsfromcausingissues.•Severaloutletproductsareavailableforthispurpose.

Backfilling

•After chamber assembly is completed, fill to top ofchamberswithpreferablycompactible,slightlylimitedtomoderatelylimitedsoil.

•Backfill material to meet Maine Backfill standard:804.2Backfillstandards:Thebackfillmaterialshallbeacoarsesandtoagravellycoarsesandwhichmeetsthefollowingrequirements:

804.2.1 Coarse fragments: The upper limit ofcoarsefragmentsshallbe3inchesindiameterandapproximately5%byvolume;

804.2.2Texturalanalysis:Thesoiltextureforbackfill,unlessotherwiseauthorizedbythiscode,iscoarsesandtogravellycoarsesandwithapproximately4to8%ofthesand,siltandclayfractionpassinga#200sieve.Theupperlimitofclaysizedparticlesinthesand,silt,andclay fractionshallbeapproximately2%.Thebackfillshallcontainapproximately15%to30%(byweight)coarsefragments(gravel2mmto3inches).

•Modestly compact the sidewall area backfill material by simply walking down the sides of the chambers. Sidewall compaction is important to begin the stabilization process of the soil, to support the chamber sidewalls, and help prevent fine sand migration into the chamber louvers. This procedure may be accomplished any time duringtheinstallationorcoveringprocess.

ArC/BIODIFFUSEr LEACHING SYSTEMS: INSTALLATION PrOCEDUrES

Page 18: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

18

Typical Trench: Cross Section

36"Typ

34"

6"MinTopsoil

Backfill

Sewer&Drainand/orTripleWallorPer LocalRegulation

SepticTankD-Box

InspectionPorts EndCapsMustbeInstalledonBothEndsofEveryChamberRow

DeterminedbyStateandLocalCodes

Typical Installation: I. Trench Configuration•Thetypicalinstallationisusedinmostapplications.

Typical Trench: Plan View

Page 19: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

19

Typical Installation:

II. Bed Configuration

Typical Bed: Cross Section

36"Typ

34"

6"MinTopsoil

Backfill

Typical Bed: Plan View

Sewer&Drainand/or TripleWallorPer LocalRegulation

SepticTankD-Box

InspectionPorts

EndCapsMustbeInstalledonBothEndsofEveryChamberRow

DeterminedbyStateandLocalCodes

Page 20: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

20

Typical Configurations: III. Serial Configuration – Direct (End Cap-to-End Cap)

36"Typ34"

6"MinTopsoilBackfill

Center-to-CenterPerCode

Serial to Direct: Cross Section (slope)

Serial to Direct: Plan View

Sewer&Drainand/or TripleWallorPer LocalRegulation

D-Box

InspectionPorts

EndCapsMustbeInstalledonBothEndsofEveryChamberRow

DeterminedbyStateandLocalCodes

SepticTank

HighFlowSplashPlate(notshown)

Page 21: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

21

Additional Configurations: I. Mound Configuration

Cross Section:

3inor4inSolidPVCSewerPipe 24inMaxCover12inofCoverH-10LoadRated(Including4in-6inTopSoil)

34inArcChamber

SpecifiedFillExistingGrade

SidePortCoupler

EndCap

DeterminedbyStateandLocalCodes

Page 22: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

22

Additional Configurations: II. Pump Systems: Pump to D-Box – For Equal Length Chamber rows

Pump to D-Box: D-Box Section View

Pump to D-Box: Plan View

Sewer&Drainand/or TripleWallorPer LocalRegulation

PumpTank

D-Box

InspectionPorts

EndCapsMustbeInstalledonBothEndsofEvery

ChamberRow

DeterminedbyStateandLocalCodes

SepticTank

HighFlowSplashPlate(notshown)

3"to4"OverflowtoTopInletofEndPipe

ForceMainfromPumpTank

1/4"HoleFacingWallofD-Box

D-Box(D-BoxEnlargedView)

Page 23: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

23

Additional Configurations: III. Pump Systems: Pump to Serial – For Sloping Terrain

Pump to Serial: Plan View

Sewer&Drainand/or TripleWallorPer LocalRegulation

PumpTank

InspectionPorts

EndCapsMustbeInstalledonBothEndsofEvery

ChamberRow

DeterminedbyStateandLocalCodes

SepticTank

HighFlowSplashPlate(notshown)

Page 24: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

24

Additional Configurations: IV. Pressure Dosing System

SepticTank

InspectionPorts

EndCapsMustbeInstalledonBothEndsofEveryChamberRow

DeterminedbyStateandLocalCodes

PumpTank

SpitterValve

Pressure Dosing: Plan ViewPressurePipeDetail

Pressure Dosing:Pipe Support Installation Cross Section

36"Typ

34"

6"MinTopsoil

Backfill Chamber

PressurePipewithHolesat12O’clock

InstallaPipeSupportEvery10'toMaintainPositionandPreventPipeRotation

Chamber

PressurePipewithHolesat12O’clock

PressurePipewithAllWeatherPipeStrapsatEveryChamberConnection

Pressure Dosing:Pipe Support Installation Cross Section

Page 25: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

25

Additional Configurations: V. Side Port Layout – Header- Middle - radius

Page 26: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

26

Additional Configurations: VI. Side Port Layout – Serial

Page 27: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

27

Sizing of ArC 36 Standard Chamber For Trench SystemsChambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 22 33 43 53 65 12

2 18 26 35 43 52 9

3 18 26 35 43 52 9

4 15 22 28 35 42 8

5 15 22 28 35 42 8

6 15 22 28 35 42 8

7 18 26 35 43 52 9

8 22 33 43 53 65 12

9 26 39 52 65 78 13

Notes: 1.TheeffectivelengthoftheARC36standardchamberis60-inches. 2.SizingcreditfortheArc36standardchamberequals35sq.ft.perchamberor7.0sq.ft.linearfoot.3.Arc36SPCsizingcreditof6.0sq.ft.perunit.

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 19 29 38 47 57 10

2 15 23 30 38 45 8

3 15 23 30 38 45 8

4 13 19 24 30 37 7

5 13 19 24 30 37 7

6 13 19 24 30 37 7

7 15 23 30 38 45 8

8 19 29 38 47 57 10

9 23 34 45 57 68 12

Sizing of ArC 36 High Capacity Chamber For Trench SystemsChambers are to be installed with 3 foot trench separation from edge to edgeThe following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.TheeffectivelengthoftheARC36highcapacitychamberis60-inches.2.SizingcreditfortheARC36highcapacitychamberequals40sq.ft.perchamberor8.0sq.ft.perlinearfoot.3.Arc36highcapacitySPCsizingcreditof6.0sq.ft.perunit.

Page 28: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

28

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 17 26 34 42 51 9

2 14 21 27 34 41 7

3 14 21 27 34 41 7

4 11 16 22 27 32 6

5 11 16 22 27 32 6

6 11 16 22 27 32 6

7 14 21 27 34 41 7

8 17 26 34 42 51 9

9 21 31 41 52 62 11

Sizing of 1100BD Standard Chamber For Trench Systems Chambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.Theeffectivelengthofthe1100BDstandardchamberis75-inches.2.Sizingcreditforthe1100BDchamberequals44sq.ft.perchamberor7.0sq.ft.perlinearfoot.

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 27 39 52 65 77 14

2 21 32 42 52 60 11

3 21 32 42 52 60 11

4 18 26 33 42 50 10

5 18 26 33 42 50 10

6 18 26 33 42 50 10

7 21 32 42 52 60 11

8 27 40 52 65 77 14

9 33 48 64 79 95 16

Sizing of 1500BD Bio 2 Narrow Chamber For Trench Systems

Chambers are to be installed with 18-inch trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.Theeffectivelengthofthe1500BDBio2narrowchamberis86-inches.2.Sizingcreditforthe1500BDBio2narrowchamberequals28.8sq.ft.perchamberor4.0sq.ft.perlinearfoot.

Page 29: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

29

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 15 23 30 37 45 8

2 12 18 24 30 36 6

3 12 18 24 30 36 6

4 10 15 19 24 29 5

5 10 15 19 24 29 5

6 10 15 19 24 29 5

7 12 18 24 30 36 6

8 15 23 30 37 45 8

9 18 27 36 45 54 9

Sizing of 1600BD High Capacity Chamber For Trench Systems

Chambers are to be installed with 3 foot trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.Theeffectivelengthofthe1600BDhighcapacitychamberis75-inches.2.Sizingcreditforthe1600BDhighcapacitychamberequals50sq.ft.perchamberor8.0sq.ft.perlinearfoot.

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 38 58 75 93 113 20

2 30 45 60 75 90 15

3 30 45 60 75 90 15

4 25 38 48 60 73 13

5 25 38 48 60 73 13

6 25 38 48 60 73 13

7 30 45 60 75 90 15

8 38 58 75 93 113 20

9 45 68 90 113 135 23

Sizing of ArC 18 Narrow Chamber For Trench Systems

Chambers are to be installed with 18-inch trench separation from edge to edge The following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.TheeffectivelengthoftheARC18narrowchamberis60-inches.2.SizingcreditfortheARC18narrowchamberequals20sq.ft.perchamberor4.0sq.ft.perlinearfoot.

Page 30: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

30

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 26 40 52 65 79 14

2 21 32 42 52 63 11

3 21 32 42 52 63 11

4 18 26 33 42 51 9

5 18 26 33 42 51 9

6 18 26 33 42 51 9

7 21 32 42 52 63 11

8 26 40 52 65 79 14

9 32 47 63 79 94 16

Sizing of ArC 36 & 36 High Capacity Chambers For Cluster Systems recommended 6-inch separation between chamber rowsThe following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.TheeffectivelengthoftheARC3613BD2&3616BD2chambersis60-inches.2.SizingcreditfortheARC3613BD2&3616BD2chambers(bottomareaonly)equals29sq.ft.perchamberor5.8sq.ft.perlinearfoot.

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 21 31 41 52 62 11

2 17 25 33 42 50 9

3 17 25 33 42 50 9

4 13 20 26 33 39 7

5 13 20 26 33 39 7

6 13 20 26 33 39 7

7 17 25 33 42 50 9

8 21 31 41 52 62 11

9 25 38 50 63 75 13

Sizing of 1100BD & 1600BD Chamber For Cluster Systems

recommended 6-inch separation between chamber rows The following table will determine the minimum number of chambers needed (For residential Use)

Notes:1.Theeffectivelengthofthe1100BD&1600BDchambersis75-inches.2.Sizingcreditforthe1100BD&1600BDchambers(bottomareaonly)equals36sq.ft.perchamberor5.76sq.ft.perlinearfoot.

Page 31: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

31

Notes:1.TheeffectivelengthoftheARC3613BD2&3616BD2chambersis60-inches.2.SizingcreditfortheARC3613BD2&3616BD2chambers(bottomareaonly)equals29sq.ft.perchamberor5.8sq.ft.perlinearfoot.

Soil NumberofBedrooms Additional

Profile 2 3 4 5 6 Bedroom

180GPD 270GPD 360GPD 450GPD 540GPD 90GPD

1 21 31 41 52 62 11

2 17 25 33 42 50 9

3 17 25 33 42 50 9

4 13 20 26 33 39 7

5 13 20 26 33 39 7

6 13 20 26 33 39 7

7 17 25 33 42 50 9

8 21 31 41 52 62 11

9 25 38 50 63 75 13

Page 32: On-Site Leaching Chamber Specifications & Features...Before beginning installation, please note the following engineered features of the 11” Standard model chambers and end caps

1-800-821-6710 www.ads-pipe.com

888-FOR PIPE (367-7473) www.hancor.com

Innovation in product, process and technology.

That’s ADS and Hancor.

Beginning with single wall corrugated polyethylene pipe, ADS and Hancor have

continually introduced drainage products that have set the industry standard –

bringing to market a remarkable alternative to concrete and steel pipe. Our

commitment to being the best means that we continue to refine the structural

design of our pipe and redefine the limits of its application in the structural

design community.

Advanced Drainage Systems, the ADS logo, the green stripe, “The Most Advanced Name in Drainage Systems” and ARC™ are registered trademarks of Advanced Drainage Systems, Inc. Hancor is a

registered trademark of Hancor, Inc. ADS “Terms and Conditions of Sale” are available on the ADS website, www.ads-pipe.com. © 2009 Advanced Drainage Systems, Inc.

INS10636/0909