operatherm operators manual

Upload: paul-herrada

Post on 04-Jun-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 Operatherm Operators Manual

    1/12

    Manual KanMed Operatherm Page 1

    Users ManualKanMed Operatherm 202 /200

    Contents1. INTENDED USE.......................................................................................................................... 22 SAFETY INSTRUCTIONS........................................................................................................... 23 TECHNICAL SPECIFICATIONS ................................................................................................. 54 DESCRIPTIONS OF FUNCTIONS.............................................................................................. 65

    USING THE UNIT........................................................................................................................ 9

    6 CHECKING OF SAFETY SYSTEMS ........................................................................................ 107 ACCESSORIES AND SPARE PARTS...................................................................................... 118 EMC COMPATIBILITY STATEMENT ....................................................................................... 119 WARRANTY STATEMENT. ...................................................................................................... 1110 MAINTENANCE ........................................................................................................................ 12

    NOTE:

    Patient warming equipment can harm the patient if not used correctly.

    Never use a unit that do not perform the Self Test according to this manual

    Make sure that the performance of the unit is regularly checked .

    This manual contains important information and must be kept for future reference. It is valid for all Operatherm 202 / 200 units.

    Manufactured by:KanMed AB, Grdsfogdevgen 18B, SE-168 66 Bromma SWEDENTel no: +46 8 564 80 630 Fax no: +46 8 564 80 639

    Users instructionKanMed Operatherm 202

    0413Art. Nr.:OP-202-050 / 5

  • 8/13/2019 Operatherm Operators Manual

    2/12

    Manual KanMed Operatherm Page 2

    1. INTENDED USE

    The intended use of the Operatherm 202 / 200 is to prevent or minimise heat loss from patients in the

    Operating Room.The Operatherm must be used in compliance with the instructions in this manual and in accordance to

    accepted hospital and clinical routines.

    2 SAFETY INSTRUCTIONS

    Please read the complete user manual carefully before using the equipment.

    W A R N I N GNever use a unit that do not perform the Self Test according to this manual.Never use a unit that has been dropped or fallen onto the floor before it has been examined by aqualified technician

    The Operatherm 202 is a very safe equipment. However certain combinations of heat, pressure,long term surgery and disinfectant fluids can cause skin damage. Therefore it is important toobserve the advice regarding pressure relief, excessive fluid and temperature selections givenlater in this section.

    2.2 EXPLANATION OF SYMBOLS

    Equipment not suitable for use in the presence of a flammable anaestheticmixture with air or with oxygen or nitrous oxide

    Protection grade BF, Defibrillation safe

    See users manual

    ~ AC current

    DC current

    ON OFF switch.

    / IPX1 Drip proof, Control Unit

    / IPX7 Water tight, Heating Pad

    0413

    Fullfills MDD 93/42 EEC.EC-Type examination certificate issued by a Notified Body( 0413= Intertech SEMKO, Sweden)

  • 8/13/2019 Operatherm Operators Manual

    3/12

    Manual KanMed Operatherm Page 3

    Key switch for temperatures 37C

    Temperature selector switch

    Alarm silence switch

    Heating Pad failure alarm

    Over temperature alarm

    Control Unit failure

    Earth potential equalisation connection point

    2.3 EXPLANATION OF PICTURES ON THE HEATING PAD

    1 Refer to users manual2 Heating Pads OP-200-xxx may

    only be used with Operatherm Control Unit OP-200/202

    3 Unauthorised persons are not allowed to open the Control Unit or the Heating Pad Connector.Any such interventions may endanger the patient safety.

    4 The Heating Pad cable may not be altered in length or repaired in any other way.5 See Users Manual section 10, concerning cleaning and maintenance of Heating Pads and

    Control Units

    6 Sharp objects must not penetrate the Heating Pad7 Place the Heating Pad flat on the operating table with the text side towards the patient.8 Gel Pads must be placed over the Heating Pad.9 When used with children, ensure that the gel pad Gel Pads covers the whole Heating Pad10 Ensure that the text side of the Heating Pad is towards the patient or ECG disturbance may

    occur.

    11 The Heating Pad should be stored using the Pad Hanger or rolled with a diameter not smallerthan 150mm. Don't bend or fold the Heating Pad so that sharp crease arises.

  • 8/13/2019 Operatherm Operators Manual

    4/12

    Manual KanMed Operatherm Page 4

    2.4 DIATHERMY EQUIPMENT AND DEFIBRILLATORSDuring normal use the Operatherm is not disturbed by this equipment.However, if diathermy or defibrillation is set at very high outputs, the Operatherm might go into alarmstate. In such a case, switch off the Operatherm and restart and observe that the self test performs as

    usual. Note that housing including handle of control unit is electrically connected to earth.

    2.5 ECG EQUIPMENTWarning: Under unfavourable conditions there is a risk of interference occurring on ECG tracesif ECG electrodes are not applied strictly to the manufactures instructions or if the Heating Padtext side is facing downwards.In most cases the problem is solved by making sure that the correct ECG cables and electrodes arebeing used and by ensuring that the electrodes have proper skin contact.

    2.6 FLUIDS BETWEEN THE PATIENT AND THE HEATING PADAny collection of fluids, especially disinfecting fluids, can cause skin irritations.

    2.7 ALWAYS USE GEL PADSThe Operatherm Heating Pad shall be covered with Gel Pads. For operations that will last many hoursand for patients sensitive to pressure (f.i. diabetes), the combination of immobility, skin pressure andwarming may prove an bad combination and you may consider not to use the Operatherm at all.KanMed Gel Pads will achieve a surface temperature that is about 1-2C lower than the selectedHeating Pad temperature. The Gel Pads will also increase the contact surface and thereby increase theamount of heat transferred to the patient

    2.8 TEMPERATURE SETTINGUnder normal conditions and with KanMed Gel Pads under the patient the maximum temperature 39Cshould be selected. During long interventions one must consider a lower temperature setting.If the OR-table surface is hard, blood pressure is low i.e. bad circulation, old patients, patients withdiabetes, etc. 37C should be the highest temperature.

    2.9 USE WITH CHILDREN AND PRE-TERM BABIESSmall children, especially pre-term babies, are easily influenced by surrounding temperatures. They canget cold fast or may get fever by being warmed too much.Never ever use the Operatherm without gel pads especially when treating a child.

    A Gel Pad acts as a heat buffer and assures an even heat distribution as well as increased heat transferand comfort.

    2.10 AREAS WITH NO BLOOD FLOWBy planned internal vessel shut off the Heating Pad must be placed where heat is mostly needed. Heatsupply to tissue with no blood flow may increase the risk of tissue damage. Place the pad where there iscirculation alternatively shut the Operatherm off during the period of no blood flow.

    2.11 PRE-WARMED GEL PADSPre-warmed Gel Pads are very efficient warmers and should preferably be heated to 42C. KanMed Geland Fluid warming Cabinet is made for this purpose. At 42C there is a very small chance that the warmgel pads may trigger the over temperature alarm of the Operatherm. If so happens, wait about 10minutes before switching on the unit again.

    2.12 HEATING PAD CONNECTION CABLE.Never alter the length of the pad cable or repair the pad cable or the pad connector. The pad willafterwards have an incorrect temperature, which might be higher than displayed on the Control Unit.Never change the electronics in the Heating Pad connector.

  • 8/13/2019 Operatherm Operators Manual

    5/12

    Manual KanMed Operatherm Page 5

    3 TECHNICAL SPECIFICATIONS

    Heating Pad Standard Art. no.:OP-200-002Voltage 30 Volt DC

    Power 200 WattDimension L 1040 mm W 450mm H 2 mmWeight 2 kgLength of cable 3,5 meter approx. ( Other lengths may be ordered )Water protection Watertight, except connectorSurface, electrical properties Not electrical conductive

    Heating Pad Small Art. no.: OP-200-012Voltage 30 Volt DCPower 100 WattDimension L 630 mm W 430 mm 2 mmWeight 1,5 kgLength of cable 3.5 metre approx. (Other lengths may be ordered)Water protection Watertight, except connector

    Surface, electrical properties. Not electrical conductive

    Heating Pad 150cm Art. no.: OP-200-221Voltage 30 Volt DCPower 200 WattDimension L 1500 mm W 450 mm H 2 mmWeight 2,8 kgLength of cable 3,5 metre approxWater protection Watertight, except connectorSurface, electrical properties Not electrical conductive

    Control UnitVoltage 220 -240 V AC ( 100 and110-120 V AC is also available )Frequency 50/60 HzPower 285 VA (max)

    Temperature range 32C and 35-39C in steps of 0.5CAccuracy 0.5CIndicators LEDResolution 0.5C

    Over-temperature alarm level 40,25C 0.75CDimensions L 255 mm approx. W 150 mm approx H 120 mm approxWeight 5 Kg approx.Fuses 220 - 240 Volts T 4A, 110 120 Volts T 8AMode of use Continuous

    Heating up timeElements inside the Heating Pad about 8-10 minutes at room temperatureHeating Pad surface about 25 minutes when tested under conditions of

    ADEQUATE HEAT DISCHARGE (IEC601-2-35):

    EnvironmentOperating temperature 15C - 40CShipping and storage -20C - + 60CRelative humidity 10 - 85 % non condensing

    Safety Standards EN60601-1, EN60601-1-2, IEC60601-2-35Protection type BF, Defibrillator safeProtection class Class IMDD classification Class IIB

    0413

    NOTE: Specifications are subject to changes at any time.

  • 8/13/2019 Operatherm Operators Manual

    6/12

    Manual KanMed Operatherm Page 6

    4 DESCRIPTIONS OF FUNCTIONS

    4.1 THE CONTROL UNITThe Control Unit contains a microprocessor based heating control system that regulates the

    temperature of each of the 8 (4) elements in the Heating Pad. The temperature is continuouslymonitored and the average temperature is displayed in steps of 0.5C by the temperature LED's.

    The safety system in the Control Unit is continuously monitoring the main voltage, internal voltages, runparameters, the pad connection, the pad condition and the temperature of each element.

    A safety circuit, totally independent of the microprocessor based operating system, can at any time stopthe warming should conditions occur that can cause over temperature.If a fault is detected the Control Unit will alarm visually and acoustically and switch off the heating. Thetype of alarm is indicated on the alarm display. It may be pad fault, Control Unit fault, over-temperatureor a combination.

    4.2 SELF TESTEvery time the Operatherm is switched on it will perform a self-test of all functions including the internal

    safety-circuit.This is how the self test runs:When pressing the ON /OFF button all front panel indicators and the beeper are activated.

    After about 0.5 sec the red ALARM indicators and the beeper are turned off.About 2 sec. later temperature indicators are turned off.Simultaneously the red indicators and the beeper are activated again for about 2 seconds. Thisindicates that the safety-test has been successfully completed.The Operatherm will then automatically start at 37C, providing the self test went well.

    Do not use the unit if the self test does not perform correctly!

    If a fault is detected during the test the Operatherm will not start automatically and the type of fault beindicated by the corresponding alarm LED and the acoustic alarm will sound.

    Switch off the unit and check heating pad connection. Switch on the Operatherm again. If it still alarmsthen switch it off and contact a qualified technician.

    4.3 LAYOUT FRONT PANEL

    1 Over-temperature

    2 Pad fault

    3 CU. Fault

    4 Temperature Selection button

    5 Key switch for temp.>37C and 32C

    6 To cancel alarm

    7 Heating Pad connector

    8 ON/OFF button

  • 8/13/2019 Operatherm Operators Manual

    7/12

    Manual KanMed Operatherm Page 7

    4.4 TEMPERATURE INDICATIONSelected and actual pad temperature is indicated. The selected value is indicated by a continuously litLED.

    Actual temperature - if different from the selected - is indicated by a flashing LED.In case the pad temperature is lower than 32C or higher than 39C respective LED will flicker.

    4.4.1 TEMPERATURE SELECTIONThe control unit automatically selects 37C as start temperature (default).Use temperature selection button to change within the range 35C - 37C.Pressing the Key switch + temperature selection button allows temperatures up to 39C or 32C.This is a safety feature to prevent unintended selection of temperatures outside the range 35-37C.

    4.5 ALARM FUNCTIONS

    Operatherm supervises the following fault conditions

    Over-temperature

    Pad fault

    Control Unit fault

    These alarms are indicated by a red light under each symbol and an acoustic alarm.

    4.5.1 OVER-TEMPERATURE ALARMThis alarm will be activated if any one or more of the 8 elements in the standard and long pad or of the4 elements in the short pad should become warmer than 40,25C.The visual and acoustic alarm will be activated and the over heated element(s) will be switched off for90 sec.The acoustic alarm can be reset but the over-temperature indicator will stay lit. If, during the 90 sec.period, the temperature of the alarming element (s) drops below 40,25C the visual alarm willautomatically cancel itself and Operatherm will continue to operate as usual.If, after 90 sec, the temperature of any element remains above 40,25C + - .75C the acoustic alarmwill be activated again and can only be cancelled by switching the unit off.

    4.6 HEATING PADThe standard Heating Pad and the 150 cm Pad consists of 8 individual heating elements and theshorter heating Pad OP-200-012 of 4 individual elements. Each element is regulated separately.Thanks to this unique feature the heat is supplied to the part of the pad where it is most needed.The individual elements are insulated from each other with a Mylar plastic foil. They are hermetically

    sealed into the soft hospital grade yellow foil.They are watertight and easy to clean. The voltage in the elements is only 30 Volts DC.The pad is connected to the front of the Control Unit.

  • 8/13/2019 Operatherm Operators Manual

    8/12

    Manual KanMed Operatherm Page 8

    4.6.1 HEATING PAD ALARMThis alarm will be activated if the pad is not connected, or not properly connected, or if any of the8 (4) heating elements deviates from normal electrical resistance, or if there is a fault in the connectingcable, in the pad connector or in the regulator power switch.In case of a pad failure being detected during the self-test, the Operatherm will not warm until the pad

    failure has been corrected.If, during use, a pad fault occurs that affects 3 or more of the 8 heating elements the unit will alarmvisually and acoustically and switch off the heating. On short pads the heating will be switched off if 2 ormore of the 4 elements are faulty.In case the fault affects maximum 2 of the 8 elements or 1 of the short Pad elements, the unit will alarmvisually as follows:

    1 element faulty - slow flashing Pad fault LED

    2 elements faulty - slow double flashing Pad fault LED

    If the Heating Pad gets disconnected during normal use, the pad fault indicator and the 32oC LED willbe lit. The beeper will also sound. Switch the unit off and reconnect the Heating Pad. Restart the unitand observe a correct self test.

    4.7 CONTROL UNIT FAULTAny fault in the Control Unit will lit the Control Unit fault symbol and activate the acoustic alarm. Theheating will be switched off.Switch the unit off and try a restart. Observe that a correct self test takes place and that the unitbehaves normally and indicates temperatures as described in this manual. If in the slightest doubt aboutthe correct function of the unit, do not use it. Contact a qualified technician.

    4.8 MAINS FAILURE ALARMIn case of a mains failure, the Operatherm alarms by flashing the C. U. LED and sounding the beeperintermittently.The mains failure alarm is kept active for at least 10 min.

    After return of the mains power the Operatherm restarts with a self test and at the temperature selected

    before the mains failure occurred.

    4.9 REAR-PANELThe rear-panel contains information about manufacturer, serial number, voltage, fuses, etc. Mains cordis also connected here.

    FIG. 2 REAR PANEL

  • 8/13/2019 Operatherm Operators Manual

    9/12

    Manual KanMed Operatherm Page 9

    5 USING THE UNIT

    5.1 PREPARATIONS.

    The Heating PadPlace the pad on the OR-table and make sure it is not folded.Cover the Heating Pad with Gel Pads, preferably pre warmed and a sheet. (See also chapter 2)

    Connecting the Heating PadConnect the pad to the control unit and make sure that the connector engages correctly. Secure theconnector with the safety clips.

    Mains Connection

    Connect the unit with the supplied mains cable or that supplied by your medical technical department.

    Placing the Control Unit

    Place the Control Unit where it can easily be observed. It can be hung on it's handle. Note the handleand the enclosure is electrically connected to earth.

    5.2 STARTSwitch on the unit and observe the Self Test. Check that the beeper and ALARM indicators areactivated shortly (approx. 0.5 sec) and that all temperature LED's will be lit for approx. 2 sec. Then theygo out and the alarm indicators will instead be lit and the alarm shall sound. This indicates thatOperatherm has made a self test, a pad test and a test of the safety functions.The heating of the pad will now start automatically at 37C (default).

    NOTE: If the unit do not react as described above it must not be used and shall beexamined by a technician.

    5.3 SELECTING TEMPERATUREIn case you wish to select another temperature than 37C then do as described in chapter 4.4.1It will take about 8 15 minutes for the elements in the pad to reach the set temperature depending on

    surrounding conditions.NOTE: Please refer to section 2 regarding choice of temperature.

    5.4 GEL PADSAlways use Gel Pads to get an even heat distribution, a greater contact surface and to minimise the riskof pressure sores. KanMed Gel Pads are best suited for this purpose.

    Always place the Gel Pad on top of the Heating Pad. A sheet can be placed between the Gel Pads andthe patient.It is advantageous to pre-warm the Gel Pads to maximum 42C by, for instance the KanMed Gel

    Warming Cabinet. A cold Gel Pad will drain heat from the patient during the first 20 -40 minutes. This isthe time it takes for the Operatherm to warm a KanMed Gel Pad (with a patient lying on it) to skintemperature.

    After about one hour the skin temperature will be in the region of selected temperature less 1-2C.

    5.5 WARM STARTAvoid placing the patient on cold Gel Pads and a cold Heating Pad. Operatherm is designed to be leftswitched on continuously so that it can warm gel pads and be ready for use at any time. If you have noreliable warming cabinet it is possible to roll the Heating Pad with Gel Pads to get a faster warming up.It can even be left like that so that everything is properly warm for the next patient.

  • 8/13/2019 Operatherm Operators Manual

    10/12

    Manual KanMed Operatherm Page 10

    5.6 ALARMSIn case the Operatherm alarms, observe the alarm type indicated and switch the unit off. Try toeliminate the cause for the alarm. Restart the unit and observe a correct self test.In case the alarm comes back without an apparent reason the unit must be checked by a technician.

    6 CHECKING OF SAFETY SYSTEMS

    SAFETY SYSTEMS AVAILABLEAlarms will be activated in any of the following situations:

    1 Self test when the unit is switched on2 Mains power failure alarm and restarting3 Faults in the heating pad4 Over-temperature5 Technical faults arising during use (cannot be tested by the user)

    The safety system can be tested as follows below.

    6.1 TESTING THE SAFETY SYSTEM

    6.1.1 SELF TEST WHEN THE UNIT IS SWITCHED ON

    Connect the Heating Pad to the control unit and the control unit to the mains.

    Switch on the unit and check that:-The beeper beeps shortly (0.5 sec)-That, all temperature indicators are lit for about 2 seconds.-That after the 2 sec. all red ALARM indicators and the beeper are activated for 2 seconds.-That the heating starts automatically at 37C.

    6.1.2 MAINS POWER FAILURE ALARM AND RESTARTING

    Connect the Heating Pad to the Control Unit and the Control Unit to the mains. Switch on the unit and wait for the self test to be completed.

    Disconnect the power cord.- The alarm shall sound for at least 10 minutes.

    Reconnect the power cord

    The unit shall perform the self test and then warm at the temperature that was selected before poweroff.

    6.1.3 FAULTS IN THE HEATING PAD Connect the Heating Pad to the unit and the control unit to the mains.

    Switch on the unit and wait for the self test to be completed. Disconnect the Heating Pad and check that the red pad LED is lit and that the buzzer sounds.

    Switch the unit off and reconnect the Heating Pad. Restart the unit and observe a correct self test.

    Reconnect the Heating Pad and press the ALARM button.

    Check that the heating has resumed.NOTE: This is the intended reaction of the Operatherm control unit to a disconnected Heating Pad. Thereis however a small possibility that the Control Unit will react differently in case the Heating Pad happens tobe disconnected during a non heating period of the electronics. In this case both red and yellow indicatorsmight be lit. If this happens, heating cannot be restarted by pressing the ALARM button. Instead you haveto switch the mains switch off and on again.

  • 8/13/2019 Operatherm Operators Manual

    11/12

    Manual KanMed Operatherm Page 11

    6.1.4 OVER-TEMPERATURE

    Connect the Heating Pad to the Control Unit and the Control Unit to the mains.

    Switch on the unit and wait for the self test to be completed.

    Select 39C

    Roll the Heating Pad (diameter more than 15 cm) and put the pad or part of the pad into for instance abucket of lukewarm water. It is enough to dip approx. 1/2 of the Pad under the water.

    Check the water temperature

    Slowly add warm water.

    When the temperature has reached 40,25C +- 0.75C the over-temperature indicator shall be lit andthe buzzer shall sound.NOTE: It may take a minute or two for the Heating Pad to assume the water temperature, thereforerise the water temperature slowly when approaching 40,25C.

    7 ACCESSORIES AND SPARE PARTS

    STANDARD DELIVERYA normal delivery normally includes a Control Unit, User manual in your language, various HeatingPads, Heating Pad hanger, Power Cord and Gel Pads. Manuals can be downloaded fromwww.kanmed.se

    For information about accessories and spare parts please see www.kanmed.seor contact your localdealer.

    8 EMC COMPATIBILITY STATEMENTPlease see www.kanmed.se section downloads Operatherm

    9 WARRANTY STATEMENT.

    KanMed warrants the purchaser that the Operatherm Control Unit and Heating Pads shall be free fromdefects in material and workmanship for a period of 12 month from the date of purchase.The sole obligation of KanMed with respect to any such defect is limited to the repair with new or re-manufactured parts or, at the discretion of KanMed, replacement of the equipmentor refunding of the purchase price.This warranty shall not apply if the product has been modified, adjusted or repaired other than byKanMed or by organisations authorised by KanMed or modified, adjusted or not repaired in accordance

    with written instructions provided by KanMed or if the equipment has been subject to misuse,negligence or accident. These warranties are made on the conditions that promptnotification of a defect is given to KanMed or its authorised dealers within the warranty period.KanMed shall have the sole right to determine whether a defect exists.KanMed shall not in any case be liable for special or consequential damages arising from the breach ofwarranty, breach of contract, negligence or any other legal theory.

  • 8/13/2019 Operatherm Operators Manual

    12/12

    Manual KanMed Operatherm Page 12

    10 MAINTENANCE

    10.1 CLEANING / DISINFECTING

    WARNING: Always disconnect mains power cord before any cleaning procedure.

    THECONTROL UNITWipe off with a moist cloth and if necessary use your normal cleaning agent.

    THE HEATING PAD:Clean the watertight Heating Pad with soap or your usual cleaning agent. Disinfect the pad with alcoholor any other disinfectant.NOTE: Do not autoclave the pad.

    Do not submerge the connector in any liquid.In case liquid enters the pad connector, the technical department should be

    contacted for checking and if required repairing.

    10.2 PERIODICAL INSPECTIONS AND CHECKS

    A C T I O N I N T E R V A L

    Inspections carried out by the user/operator.

    Self test at Power ON Every time the equipment is switched on.

    Visual inspection of pad, cable and connector Before every use

    Checks carried out by technical personnel.

    Alarm functions Once a yearMains failurePad failureOver-temperature

    Temperature control Once a year

    Electrical safety Once a year

    Exchange of connector saver Once a year

    10.3 STORINGThe Heating Pad shall be stored hanging or lying flat. Avoid folds that may shorten the lifetime.

    10.4 TECHNICAL DOCUMENTATIONThe supplier will make available on request circuit diagrams, component parts lists, descriptions, orother information which will assist the user's appropriately qualified technical personnel to exchangethose parts of the equipment which are designated by the manufacturer as exchangeable.

    Only the KanMed factory is authorised to perform repairs on the main PCB.