Page 1: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

Operating InstructionsCapactive high temperature probe for level detection

VEGACAP 67- two-wire

Document ID: 31317

Page 2: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

2

Contents

VEGACAP 67 • - two-wire

31317-EN-160331

Contents1 About this document

1.1 Function ........................................................................................................................... 41.2 Target group ..................................................................................................................... 41.3 Symbols used................................................................................................................... 4

2 For your safety2.1 Authorised personnel ....................................................................................................... 52.2 Appropriate use ................................................................................................................ 52.3 Warning about incorrect use ............................................................................................. 52.4 General safety instructions ............................................................................................... 52.5 Safety label on the instrument .......................................................................................... 62.6 CE conformity ................................................................................................................... 62.7 Safety instructions for Ex areas ........................................................................................ 62.8 Environmental instructions ............................................................................................... 6

3 Product description3.1 Configuration .................................................................................................................... 73.2 Principle of operation........................................................................................................ 93.3 Operation ....................................................................................................................... 103.4 Packaging, transport and storage ................................................................................... 103.5 Accessories and replacement parts ............................................................................... 11

4 Mounting4.1 General instructions ....................................................................................................... 124.2 Mounting instructions ..................................................................................................... 13

5 Connecting to power supply5.1 Preparing the connection ............................................................................................... 175.2 Connection procedure .................................................................................................... 175.3 Wiring plan, single chamber housing.............................................................................. 185.4 Wiring plan - version IP 66/IP 68, 1 bar ........................................................................... 205.5 Warm-up reaction ........................................................................................................... 20

6 Setup6.1 General information ........................................................................................................ 216.2 Adjustment elements ...................................................................................................... 21

7 Maintenanceandfaultrectification7.1 Maintenance .................................................................................................................. 237.2 Rectify faults ................................................................................................................... 237.3 Exchange of the electronics module ............................................................................... 257.4 Shortening of the probe .................................................................................................. 277.5 How to proceed if a repair is necessary .......................................................................... 27

8 Dismount8.1 Dismounting steps.......................................................................................................... 298.2 Disposal ......................................................................................................................... 29

9 Supplement9.1 Technical data ................................................................................................................ 309.2 Dimensions .................................................................................................................... 339.3 Industrial property rights ................................................................................................. 369.4 Trademark ...................................................................................................................... 36

Page 3: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

3

Contents

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Supplementary documentationInformation:Supplementary documents appropriate to the ordered version come withthedelivery.Youcanfindthemlistedinchapter"Product descrip-tion".

Instructions manuals for accessories and replacement partsTip:ToensurereliablesetupandoperationofyourVEGACAP67,weofferaccessories and replacement parts. The corresponding documenta-tions are:

• 30174 - Electronics module VEGACAP series 60• 34296 - Protective cover• 31088 - Flanges according to DIN-EN-ASME-JIS-GOST

Editing status: 2016-02-19

Page 4: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

4

1 About this document

VEGACAP 67 • - two-wire

31317-EN-160331

1 About this document

1.1 FunctionThis operating instructions manual provides all the information you need for mounting, connection and setup as well as important instruc-tionsformaintenanceandfaultrectification.Pleasereadthisinforma-tion before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device.

1.2 Target groupThis operating instructions manual is directed to trained specialist personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbols usedInformation, tip, noteThis symbol indicates helpful additional information.Caution: If this warning is ignored, faults or malfunctions can result.Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result.Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.

Ex applicationsThis symbol indicates special instructions for Ex applications.

SIL applicationsThis symbol indicates instructions for functional safety which must be taken into account particularly for safety-relevant applications.

• ListThe dot set in front indicates a list with no implied sequence.

→ ActionThis arrow indicates a single action.

1 Sequence of actionsNumbers set in front indicate successive steps in a procedure.

Battery disposalThis symbol indicates special information about the disposal of bat-teries and accumulators.

Page 5: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

5

2 For your safety

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

2 For your safety

2.1 Authorised personnelAll operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.During work on and with the device the required personal protective equipment must always be worn.

2.2 Appropriate useThe VEGACAP 67 is a sensor for point level detection.Youcanfinddetailedinformationabouttheareaofapplicationinchapter"Product description".Operational reliability is ensured only if the instrument is properly usedaccordingtothespecificationsintheoperatinginstructionsmanual as well as possible supplementary instructions.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.

2.3 Warning about incorrect useInappropriate or incorrect use of the instrument can give rise to application-specifichazards,e.g.vesseloverfillordamagetosystemcomponents through incorrect mounting or adjustment.

2.4 General safety instructionsThis is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technicallyflawlessandreliablecondition.Theoperatorisresponsiblefor the trouble-free operation of the instrument.During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula-tions.The safety instructions in this operating instructions manual, the na-tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user.For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi-traryconversionsormodificationsareexplicitlyforbidden.The safety approval markings and safety tips on the device must also be observed.

Page 6: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

6

2 For your safety

VEGACAP 67 • - two-wire

31317-EN-160331

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must be observed.

2.6 CE conformityThisdevicefulfillsthelegalrequirementsoftheapplicableECguide-lines.ByattachingtheCEmark,VEGAprovidesaconfirmationofsuccessfultesting.YoucanfindtheCEconformitydeclarationinthedownloadareaof"www.vega.com".

2.7 Safety instructions for Ex areasPleasenotetheEx-specificsafetyinformationforinstallationandop-eration in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments.

2.8 Environmental instructionsProtection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro-tection.Theenvironmentmanagementsystemiscertifiedaccordingto DIN EN ISO 14001.Pleasehelpusfulfillthisobligationbyobservingtheenvironmentalinstructions in this manual:

• Chapter"Packaging, transport and storage"• Chapter"Disposal"

Page 7: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

7

3 Product description

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

3 Product description

3.1 ConfigurationThe scope of delivery encompasses:

• VEGACAP 67 point level switch• Documentation

– This operating instructions manual – SafetyManual"Functional safety (SIL)"(optional) – Supplementaryinstructionsmanual"Plug connector for level

sensors"(optional) – Ex-specific"Safety instructions"(withExversions) – Ifnecessary,furthercertificates

The VEGACAP 67 consists of the components:

• Processfittingwithprobe• Housing with electronics• Housing cover, optionally available with display and adjustment

module

Scope of delivery

Constituent parts

Page 8: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

8

3 Product description

VEGACAP 67 • - two-wire

31317-EN-160331

1

2

3

5

4

Fig. 1: VEGACAP 67 - with plastic housing1 Housing lid2 Housing with electronics3 Processfitting4 Supporting tube5 Ceramic insulator

Thetypelabelcontainsthemostimportantdataforidentificationanduse of the instrument:

Type label

Page 9: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

9

3 Product description

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

2

1

11

10

13

12

14

15

9

3

6

4

5

78

Fig. 2: Layout of the type label (example)1 Instrument type2 Product code3 Approvals4 Process and ambient temperature, process pressure5 Power supply and signal output, electronics6 Protection rating7 Probe length8 Order number9 Serial number of the instrument10 Material, wetted parts11 Symbol of the device protection class12 Reminder to observe the instrument documentation13 ID numbers, instrument documentation14 NotifiedauthorityforCEmarking15 Approval directives

With the serial number, you can access the delivery data of the instru-ment via www.vega.com,"VEGA Tools"and"serial number search".Youcanfindtheserialnumberontheinsideoftheinstrumentaswellas on the type label on the outside.

3.2 Principle of operationThe VEGACAP 67 is a point level sensor for bulk solids. The probe is designed for high temperature applications.

Probe, measured product and vessel wall form an electrical capacitor. Thecapacitanceisinfluencedbythreemainfactors.

Area of application

Functional principle

Page 10: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

10

3 Product description

VEGACAP 67 • - two-wire

31317-EN-160331

1

2

3

Fig. 3: Functional principle - Plate capacitor1 Distance between the electrode surfaces2 Size of the electrode surfaces3 Type of dielectric between the electrodes

The probe and the vessel wall are the capacitor plates. The measured product is the dielectric. Due to the higher dielectric constant of the product compared to air, the capacitance increases as the probe is gradually covered.The capacitance change is converted by the electronics module into a switching command.

Depending on your requirements, VEGACAP 67 with two-wire elec-tronicscanbeconnectedtodifferentsignalconditioninginstruments.Compatible signal conditioning instruments are listed in chapter "Technical data".Thedataforpowersupplyarespecifiedinchapter"Technical data".

3.3 OperationThe probe can be adapted to the dielectric constant of the product directly on the electronics module.A switching command can be triggered when the probe is covered or laid bare.Ontheelectronicsmoduleyouwillfindthefollowingdisplayandadjustment elements:

• Control lamp for indication of the device status.

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test based on ISO 4180.The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.

Voltage supply

Packaging

Page 11: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

11

3 Product description

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Transport must be carried out in due consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device.

The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or con-cealed defects must be appropriately dealt with.

Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside.Unless otherwise indicated, the packages must be stored only under the following conditions:

• Not in the open• Dry and dust free• Not exposed to corrosive media• Protected against solar radiation• Avoiding mechanical shock and vibration

• Storageandtransporttemperatureseechapter"Supplement - Technical data - Ambient conditions"

• Relative humidity 20 … 85 %

3.5 Accessories and replacement partsThe protective cover protects the sensor housing against soiling and intense heat from solar radiation.Youwillfindadditionalinformationinthesupplementaryinstructionsmanual"Protective cover"(Document-ID34296).

Screwedflangesareavailableindifferentversionsaccordingtothefollowing standards: DIN 2501, EN 1092-1, BS 10, ASME B 16.5, JIS B 2210-1984, GOST 12821-80.Youcanfindadditionalinformationinthesupplementaryinstructionsmanual"Flanges according to DIN-EN-ASME-JIS".

Transport

Transport inspection

Storage

Storage and transport temperature

Protective cap

Flanges

Page 12: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

12

4 Mounting

VEGACAP 67 • - two-wire

31317-EN-160331

4 Mounting

4.1 General instructionsMake sure that all parts of the instrument coming in direct contact with the process, especially the sensor element, process seal and processfitting,aresuitablefortheexistingprocessconditions,suchas process pressure, process temperature as well as the chemical properties of the medium.Youcanfindthespecificationsinchapter"Technical data"andonthenameplate.

In general, VEGACAP 67 must be mounted vertically. The instrument must be mounted in such a way that the probe is at the height of the requested switching point.

Before beginning the welding work, remove the electronics module from the sensor. By doing this, you avoid damage to the electronics through inductive coupling.Ground the probe before welding directly on the rod or cable.

With threaded versions, the housing must not be used to screw in the instrument. Applying tightening forces on the housing can damage its internal parts.Use the hexagon for screwing in.

Usetherecommendedcables(seechapter"Connecting to power supply")andtightenthecablegland.You can give your instrument additional protection against moisture penetration by leading the connection cable downward in front of the cableentry.Rainandcondensationwatercanthusdrainoff.Thisap-plies mainly to outdoor mounting as well as installation in areas where highhumidityisexpected(e.g.throughcleaningprocesses)oroncooled or heated vessels.

Fig. 4: Measures against moisture ingress

Theprocessfittingmustbesealedifthereisgaugeorlowpressureinthe vessel. Before use, check if the seal material is resistant against the measured product and the process temperature.

Suitability for the process conditions

Switching point

Welding work

Handling

Moisture

Pressure/Vacuum

Page 13: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

13

4 Mounting

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Themax.permissiblepressureisspecifiedinchapter"Technical data"oronthetypelabelofthesensor.

Metal vesselMake sure that the mechanical connection of the probe to the vessel iselectricallyconductivetoensuresufficientgrounding.Use conductive seals, such as those made of copper or lead, etc. Insulatingmeasures,suchascoveringthethreadwithTeflontape,can interrupt the necessary electrical connection with metal vessels. For this reason, ground the probe on the vessel or use a conductive seal material.Non-conductive vesselsIn non-conductive vessels, e.g. plastic tanks, the second pole of the capacitor must be provided separately.

Metric threadsIn the case of instrument housings with metric thread, the cable glands are screwed in at the factory. They are sealed with plastic plugs as transport protection.You have to remove these plugs before electrical connection.

NPT threadIn the case of instrument housings with self-sealing NPT threads, it is not possible to have the cable entries screwed in at the factory. The free openings for the cable glands are therefore covered with red dust protection caps as transport protection.Prior to setup you have to replace these protective caps with ap-proved cable glands or close the openings with suitable blind plugs.

4.2 Mounting instructionsDuetotheeffectsofagitators,equipmentvibrationorsimilar,thelevelswitch can be subjected to strong lateral forces. For this reason, do not use an overly long electrode for VEGACAP 67, but check if you canmountashortlevelswitchonthesideofthevesselinhorizontalposition.

Iftheinstrumentismountedinthefillingstream,unwantedfalsemeasurement signals can be generated. For this reason, mount the instrument at a position in the vessel where no disturbances, e.g. from fillingopenings,agitators,etc.,canoccur.This applies particularly to instrument versions with a longer probe.

Vessel material

Cable entries - NPT threadCable glands

Agitatorsandfluidization

Inflowingmedium

Page 14: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

14

4 Mounting

VEGACAP 67 • - two-wire

31317-EN-160331

Fig.5:Inflowingmedium

The probe should protrude into the vessel to avoid buildup. For that reason,avoidusingmountingbossesforflangesandscrewedfittings.This applies particularly to use with adhesive products.

In silos with bulk solids, material cones can form which change the switching point. Please keep this in mind when installing the sensor in the vessel. We recommend selecting an installation location where the probe detects the average value of the material cone.The probe must be mounted in a way that takes the arrangement of thefillingandemptyingaperturesintoaccount.To compensate measurement errors caused by the material cone in cylindrical vessels, the sensor must be mounted at a distance of d/6 from the vessel wall.

Socket

Material cone

Page 15: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

15

4 Mounting

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

d d

d 6

d 6

Fig. 6: Filling and emptying centred

d d 6

1

2

3

Fig. 7: Filling in the centre, emptying laterally1 VEGACAP 672 Discharge opening3 Filling opening

Page 16: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

16

4 Mounting

VEGACAP 67 • - two-wire

31317-EN-160331

Make sure that the max. permissible tensile load of the suspension cable is not exceeded. The danger of this happening exists particu-larly with very heavy solids and large meas. lengths. The max. permis-sibleloadisstatedinchapter"Technical data".

Tensile load

Page 17: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

17

5 Connecting to power supply

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

5 Connecting to power supply

5.1 Preparing the connectionAlways keep in mind the following safety instructions:

Warning:Connect only in the complete absence of line voltage.

• The electrical connection must only be carried out by trained personnel authorised by the plant operator.

• Alwaysswitchoffpowersupply,beforeconnectingordisconnect-ing the instrument.

Inhazardousareasyoumusttakenoteoftherespectiveregulations,conformityandtypeapprovalcertificatesofthesensorsandpowersupply units.

Connect the voltage supply according to the following diagrams. Take note of the general installation regulations. As a rule, connect VE-GACAP67tovesselground(PA),orincaseofplasticvessels,tothenext ground potential. On the side of the instrument housing there is a ground terminal between the cable entries. This connection serves todrainoffelectrostaticcharges.InExapplications,theinstallationregulationsforhazardousareasmustbegivenpriority.Thedataforpowersupplyarespecifiedinchapter"Technical data".

The instrument is connected with standard two-wire cable without screen. If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used.Use cable with round cross-section. A cable outer diameter of 5…9mm(0.2…0.35in)ensuresthesealeffectofthecablegland.Ifyouareusingcablewithadifferentdiameterorcross-section,exchange the seal or use a suitable cable gland.Inhazardousareas,useonlyapprovedcableconnectionsforVE-GACAP 67.

Take note of the corresponding installation regulations for Ex applica-tions.

5.2 Connection procedureWith Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present.

Proceed as follows:1. Unscrew the housing lid2. Loosen compression nut of the cable gland and remove blind

plug3. Removeapprox.10cm(4in)ofthecablemantle,stripapprox.

1cm(0.4in)ofinsulationfromtheendsoftheindividualwires4. Insert the cable into the sensor through the cable entry

Note safety instructions

Take note of safety instructions for Ex applications

Voltage supply

Connection cable

Connection cable for Ex applications

Page 18: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

18

5 Connecting to power supply

VEGACAP 67 • - two-wire

31317-EN-160331

5. Lifttheopeningleversoftheterminalswithascrewdriver(seefollowingillustration)

Fig. 8: Connection steps 5 and 6

6. Insert the wire ends into the open terminals according to the wir-ing plan

7. Press down the opening levers of the terminals, you will hear the terminal spring closing

8. Check the hold of the wires in the terminals by lightly pulling on them

9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable

10. If necessary, carry out a fresh adjustment11. Screw the housing lid back onTheelectricalconnectionisfinished.

5.3 Wiring plan, single chamber housing

1

444

2 3

Fig. 9: Material versions, single chamber housing1 Plastic (not with dust-Ex)2 Aluminium3 Stainless steel4 Filter element for pressure compensation or blind plug with version IP 66/

IP 68, 1 bar

Housing overview

Page 19: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

19

5 Connecting to power supply

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

4

1

2

3

Fig. 10: Electronics and terminal compartment1 DIL switch for measuring range selection2 Ground terminal3 Connection terminals4 Control lamp

For connection to a signal conditioning instrument. The sensor is powered by the connected signal conditioning instrument. Further in-formationisavailableinchapter"Technical data","Ex-technical data"areavailableinthe"Safety information".The wiring example is applicable for all suitable signal conditioning instruments.Take note of the operating instructions manual of the signal condition-ing instrument. Suitable signal conditioning instruments are listed in chapter"Technical data".

1

Fig. 11: Wiring plan1 Voltage supply

Electronics and terminal compartment

Wiring plan

Page 20: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

20

5 Connecting to power supply

VEGACAP 67 • - two-wire

31317-EN-160331

5.4 Wiring plan - version IP 66/IP 68, 1 bar

1

2

Fig. 12: Wire assignment, connection cable1 brown (+) and blue (-) to power supply or to the processing system2 Shielding

5.5 Warm-up reactionAfter connecting to voltage supply or after a voltage recurrence, the instrument passes a certain switch on routine.By lowering the current value when switching on, the instrument can outputbrieflyafaultmessage.

10

I/mA

20,5

< 2,3

1,5 3 4,5 t/s

1

Fig. 13: Warm-up reaction1 Measured value

Wire assignment, con-nection cable

Page 21: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

21

6 Setup

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

6 Setup

6.1 General informationThefiguresinbracketsrefertothefollowingillustrations.

Ontheelectronicsmoduleyouwillfindthefollowingdisplayandadjustment elements:

• DIL switch for measuring range selection• Control lamp

Note:As a rule, always set the mode with the mode switch of the signal conditioning instrument before starting setup VEGACAP 67. The switching output will change if you set the mode switch afterwards. This could possibly trigger other connected instruments or devices.

6.2 Adjustment elements

4

1

2

3

Fig. 14: Electronics module - Two-wire output1 DIL switch for measuring range selection (with compensation button)2 Ground terminal3 Connection terminals4 Control lamp

Afailurecanbedisplayedwithclosedhousing(onlyplastichousing),seeoperatinginstructionsmanualofthe"Signal conditioning instru-ment".

Note:Screw the housing cover tightly up to the thread stop so that the inspectionglassisabovethecontrollamp(LED).

ToadjustVEGACAP67,firstofallremovethehousingcover.

Function/Configuration

Page 22: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

22

6 Setup

VEGACAP 67 • - two-wire

31317-EN-160331

With the potentiometer on the signal conditioning instrument and themeasuringrangeselectionswitch(1)onVEGACAP67youcanchange the sensitivity of the probe to the electrical properties of the product and the conditions in the vessel. This is necessary so that the level switch can also reliably detect products e.g. with very low or very highdielectricfigure.range 1: 0 … 20 pFRange 2: 0 … 85 pFRange 3: 0 … 450 pF

Control lamp for indication of the device status.

• green = instrument functions• red(flashing)=failureSeeoperatinginstructionsmanualofthe"Signal conditioning instru-ment".

The adjustment of the switching point is only possible in installed condition.The detailed adjustment of VEGACAP 67 is described in the operat-inginstructionsmanualofthe"Signal conditioning instrument".

Measuring range selec-tion switch (1)

Signal lamp (4)

Switching point adjust-ment

Page 23: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

23

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

7 Maintenanceandfaultrectification

7.1 MaintenanceIf the instrument is used properly, no special maintenance is required in normal operation.

7.2 Rectify faultsThe operator of the system is responsible for taking suitable meas-ures to rectify faults.

VEGACAP67offersmaximumreliability.Nevertheless,faultscanoc-cur during operation. These may be caused by the following, e.g.:

• Sensor• Process• Voltage supply• Signal processing

Thefirstmeasuretotakeistochecktheoutputsignal.Inmanycases,thecausescanbedeterminedthiswayandthefaultsquicklyrectified.

Should these measures not be successful, please call in urgent cases the VEGA service hotline under the phone no. +49 1805 858550.Thehotlineismanned7daysaweekround-the-clock.Sinceweofferthis service worldwide, the support is only available in the English language. The service is free, only standard call charges are incurred.

Reaction when malfunc-tion occurs

Causes of malfunction

Faultrectification

24 hour service hotline

Page 24: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

24

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

31317-EN-160331

Error Cause Rectification

– The instrument signals covered without cover-ing with the medium

– The instrument signals covered with cover-ing with the medium

Wrong mode se-lected on the signal condition-ing instrument

Set the correct mode on the mode switch of the signal conditioning in-strument(A:overflowprotection,B:dryrunprotection).Wiringshouldbecarried out according to the idle cur-rent principle.

Operating voltage too low

Check operating voltage

Shortcircuit in the probe, e.g. be-cause of moisture in the housing

Remove the electronics module. Check the resistance between the marked plug connections. See the fol-lowing instructions.

Electronics de-fective

Pushthemodeswitch(A/B)onthesignal conditioning instrument. If the signal conditioning instrument then changes the mode, the probe may be mechanically damaged. Should the switching function in the correct mode still be faulty, return the probe for repair.Check if there is buildup on the probe, and if so, remove it.

Unfavourable in-stallation location

Check if the probe is covered by build-up on the socket.Mount the instrument at a location in the vessel where e.g. no mounds can form.

Signallampflash-es red

Electronics mod-ule has detected a failure

Exchange the instrument or send it in for repair

Remove the electronics module. Check the resistance between the two plug connections.Theremustnolongerbeaconnection(highimpedance).Ifthereisstill a connection - exchange the instrument or return it for repair

Checking the switching signal

Check the resistance in the probe

Page 25: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

25

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

1 2 3

Fig. 15: Check the resistance in the probe1 Shielding2 Measuring probe3 Ground potential

Depending on the reason for the fault and the measures taken, the stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.

7.3 Exchange of the electronics moduleIn general, all electronics modules of series CP60 can be inter-changed.Ifyouwanttouseanelectronicsmodulewithadifferentsignal output, you can download the corresponding operating instruc-tions manual from our homepage under Downloads.Proceed as follows:1. Switchoffpowersupply2. Unscrew the housing lid3. Lift the opening levers of the terminals with a screwdriver4. Pull the connection cables out of the terminals5. Loosenthetwoscrewswithascrewdriver(TorxsizeT10orslot

4)

Reaction after fault recti-fication

Page 26: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

26

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

31317-EN-160331

2

1

Fig. 16: Loosen the holding screws1 Electronics module2 Screws (2 pcs.)

6. Pull out the old electronics module7. Compare the new electronics module with the old one. The type

label of the electronics module must correspond to that of the old electronics module. This applies particularly to instruments used inhazardousareas.

8. Compare the settings of the two electronics modules. Set the adjustment elements of the new electronics module to the same setting of the old one.

Information:Make sure that the housing is not rotated during the electronics ex-change.Otherwisetheplugmaybeinadifferentpositionlater.

9. Insert the electronics module carefully. Make sure that the plug is in the correct position.

10. Screw in and tighten the two holding screws with a screwdriver (TorxsizeT10orPhillips4)

11. Insert the wire ends into the open terminals according to the wir-ing plan

12. Press down the opening levers of the terminals, you will hear the terminal spring closing

13. Check the hold of the wires in the terminals by lightly pulling on them

14. Check cable gland on tightness. The seal ring must completely encircle the cable.

15. Mount the probe into the vessel. Make sure that the probe is uncovered.

Page 27: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

27

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

21

Fig. 17: Compensation key1 Measuring range selection switch (compensation key)2 Control lamp

16. Keepthemeasuringrangeselectionswitch(1)pusheduntilthecontrollamp(2)flashesgreen.

17. Carryouttheadjustmentagain.Seechapter"Set-up, adjustment elements".

18. Screw the housing lid back onTheelectronicsexchangeisnowfinished.

7.4 Shortening of the probeThe rod of the probe can be shortened to any length.1. Shorten the rod probe to the requested length with a metal saw.2. Mount the probe into the vessel. Make sure that the probe is

uncovered.

21

Fig. 18: Compensation key1 Measuring range selection switch (compensation key)2 Control lamp

3. Keepthemeasuringrangeselectionswitch(1)pusheduntilthecontrollamp(2)flashesgreen.

4. Hencetheprobeiscompensatedtothemodifiedlength.5. Carryouttheadjustmentagain.Seechapter"Set-up, adjustment

elements".

7.5 How to proceed if a repair is necessaryYoucanfindaninstrumentreturnformaswellasdetailedinfor-mation of the procedure in the download area on our homepage: www.vega.com.By doing this you help us carry out the repair quickly and without hav-ing to call back for needed information.If a repair is necessary, please proceed as follows:

• Printandfilloutoneformperinstrument

Page 28: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

28

7Maintenanceandfaultrectification

VEGACAP 67 • - two-wire

31317-EN-160331

• Clean the instrument and pack it damage-proof• Attach the completed form and, if need be, also a safety data

sheet outside on the packaging• Please contact the agency serving you to get the address for

thereturnshipment.Youcanfindtheagencyonourhomepagewww.vega.com.

Page 29: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

29

8 Dismount

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

8 Dismount

8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc.

Takenoteofchapters"Mounting"and"Connecting to power supply"and carry out the listed steps in reverse order.With Ex instruments, the housing cover may only be opened if there is no explosive atmosphere present.

8.2 DisposalThe instrument consists of materials which can be recycled by spe-cialised recycling companies. We use recyclable materials and have designed the parts to be easily separable.

WEEE directive 2002/96/EGThis instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a spe-cialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.Correctdisposalavoidsnegativeeffectsonhumansandtheenviron-ment and ensures recycling of useful raw materials.Materials:seechapter"Technical data"If you have no way to dispose of the old instrument properly, please contact us concerning return and disposal.

Page 30: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

30

9 Supplement

VEGACAP 67 • - two-wire

31317-EN-160331

9 Supplement

9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Processfitting G1½, 1½ NPTMaterials, wetted parts

Ʋ Processfitting-thread 316L Ʋ Processfitting-flange 316L Ʋ Process seal Klingersil C-4400 Ʋ insulation(partlyinsulated) Ceramic(KER221accordingtoDIN40685) Ʋ Probe - rod, ceramic partly insulated (ø15mm/0.591in)

316L

Ʋ Probe - cable, ceramic partly insulated (ø8mm/0.315in)1)

316(1.4401)

Ʋ Gravity weight 316LMaterials, non-wetted parts

Ʋ Plastic housing plasticPBT(Polyester) Ʋ Aluminium die-casting housing Aluminium die-casting AlSi10Mg, powder-coated - basis:

Polyester Ʋ Stainless steel housing - precision casting

316L

Ʋ Stainless steel housing, electropol-ished

316L

Ʋ Seal between housing and housing lid NBR(stainlesssteelhousing,precisioncasting),silicone(aluminium/plastichousing;stainlesssteelhousing,electropolished)

Ʋ Ground terminal 316L Ʋ Cable gland PA, stainless steel, brass Ʋ Sealing, cable gland NBR Ʋ Blind plug, cable gland PA

Processfittings Ʋ Pipethread,cylindrical(DIN3852-A) G1½ Ʋ American pipe thread, conical (ASMEB1.20.1)

1½ NPT

Ʋ Flanges DINfromDN50,ASMEfrom2"Weight

Ʋ Instrumentweight(dependingonprocessfitting)

0.8…4kg(0.18…8.82lbs)

Ʋ Gravity weight 1800g(64oz) Ʋ Rodweight:ø15mm(0.591in) 1400g/m(15oz/ft) Ʋ Cableweight:ø8mm(0.315in) 400g/m(4.3oz/ft)

1) Cable connected electrically conductive with the gravity weight.

Page 31: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

31

9 Supplement

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Sensorlength(L) Ʋ Rod(ø15mm/0.591in) 0.275…6m(0.902…19.69ft) Ʋ Cable(ø8mm/0.315in) 0.53…40m(1.74…131.23ft)

Supporting tube length L1 0.2…5.6m(0.656…18.37ft)Max. lateral load 10Nm(7.4lbfft)Max.tensileload(cable)

Ʋ Ceramicpartlyinsulated:ø8mm(0.315in)

10KN(2248lbf)

Max.torque(processfitting-thread) 80Nm(58lbfft)Torque for NPT cable glands and Conduit tubes

Ʋ Plastic housing max.10Nm(7.376lbfft) Ʋ Aluminium/Stainless steel housing max.50Nm(36.88lbfft)

Measuring frequency 430kHz

Output variableOutput Two-wire outputSuitable signal conditioning instruments VEGATOR 141, 142, 620, 621, 622Output signal >4…<20mA(notstandardised)Fault message < 2.3 mASwitching delay

Ʋ When immersed 0.7 s Ʋ When laid bare 0.7 s Ʋ In the event of a fault 1 s

Accuracy (according to DIN EN 60770-1)Reference conditions according to DIN EN 61298-1

Ʋ Temperature +18…+30°C(+64…+86°F) Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860…1060mbar/86…106kPa(12.5…15.4psig)

Deviation due to strong, high-frequency electromagneticfieldsacc.toEN61326

< 3 % of the adjusted measuring range2)

Influenceoftheambienttemperature < 0.15 %/10 K of the adjusted measuring range3)

Ambient conditionsAmbient temperature on the housing -40…+80°C(-40…+176°F)Storage and transport temperature -40…+80°C(-40…+176°F)

Process conditionsProcess pressure -1…16bar/-100…1600kPa(-14.5…232psig)Processtemperature(threadorflangetemperature)

Ʋ Standard -50…+300°C(-58…+572°F)

2) Distancefromtheprocessfittingstothesetswitchingpoint3) Distancefromtheprocessfittingstothesetswitchingpoint

Page 32: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

32

9 Supplement

VEGACAP 67 • - two-wire

31317-EN-160331

Ʋ with external housing -50…+400°C(-58…+752°F)

2

13

200�°C(292�°F)

300 °C(572�°F)

100�°C(212�°F)

400�°C(752�°F)

0�°C(32�°F)

-50�°C(-58�°F)

16 bar(232psi)

Fig. 19: Process temperature - Process pressure1 Process temperature2 Process pressure3 Temperature range with external housing

Dielectric constant ≥1.5

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug4)

Ʋ Single chamber housing – 1xcableglandM20x1.5(cable:ø5…9mm),1xblind plug M20 x 1.5

or: – 1 x closing cap ½ NPT, 1 x blind plug ½ NPT

or: – 1␣xplug(dependingontheversion),1␣xblindstopperM20␣x␣1.5

Spring-loaded terminals forwirecross-sectionupto1.5mm²(AWG16)

Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry

Ʋ Single chamber housing – 1xIP68cableglandM20x1.5;1xblindplugM20 x 1.5

or: – 1 x closing cap ½ NPT, 1 x blind plug ½ NPT

Connection cable Ʋ Wire cross-section >0.5mm²(AWG20) Ʋ Wire resistance <0.036Ω/m(0.011Ω/ft) Ʋ Tensile strength <1200N(270lbf) Ʋ Standard length 5m(16.4ft) Ʋ Max. length 1000m(3280ft) Ʋ Min. bending radius 25mm(0.984in)with25°C(77°F) Ʋ Diameter approx. 8mm(0.315in) Ʋ Colour - standard PE Black Ʋ Colour - standard PUR Blue Ʋ Colour - Ex-version Blue

4) DependingontheversionM12x1,accordingtoISO4400,Harting,7/8"FF.

Page 33: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

33

9 Supplement

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Adjustment elementsDIL switch for measuring range selection

Ʋ range 1 0 … 20 pF Ʋ range 2 0 … 85 pF Ʋ range 3 0 … 450 pF

Voltage supplyOperating voltage 10…36VDC(viathesignalconditioninginstrument)

Electrical protective measuresProtection rating

Ʋ Plastic housing IP66/IP67(NEMA4X) Ʋ Aluminium and stainless steel stand-ard

IP66/IP68(0.2bar),NEMA6P5)

Ʋ Aluminium and stainless housing (optionallyavailable)

IP66/IP68(1bar),NEMA6P

Protection class II

9.2 Dimensions

Housing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar

321 4

~ 69 mm(2.72")

ø 79 mm(3.11")

117

mm

(4.6

1")

M20x1,5/½ NPT

~ 59 mm(2.32")

ø 80 mm(3.15")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 69 mm(2.72")

ø 79 mm(3.03")

112

mm

(4.4

1")

M20x1,5/½ NPT

~ 116 mm (4.57")

ø 86 mm (3.39")

116

mm

(4.5

7")

M20x1,5M20x1,5/½ NPT

Fig. 20: Housing versions in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar1 Plastic housing2 Stainless steel housing, electropolished3 Stainless steel housing, precision casting4 Aluminium housing

5) A suitable cable is required for maintaining the protection rating.

Page 34: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

34

9 Supplement

VEGACAP 67 • - two-wire

31317-EN-160331

Housing in protection IP 66/IP 68 (1 bar)

117

mm

(4.6

1")

~ 103 mm(4.06")

ø 77 mm(3.03")

116

mm

(4.5

7")

~ 150 mm(5.91")

ø 84 mm(3.31")

M20x1,5 M20x1,5M20x1,5

1 2

Fig. 21: Housing versions with protection rating IP 66/IP 68 (1 bar)1 Stainless steel housing, precision casting2 Aluminium housing

Page 35: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

35

9 Supplement

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

242

mm

(9.5

3")

L

L1

120

mm

(4.7

2")

23 m

m(0

.91"

)

100

mm

(3.9

4")

ø 40 mm(1.58")

ø 38 mm(1.5")

ø 15 mm(0.59")

ø 8 mm(0.32")

200

mm

(7.8

7")

SW46

G1 ½A/NPT1 ½

Fig. 22: VEGACAP 67, threaded version G1½ (ISO 228 T1) and 1½ NPT, -50 … +300 °C (-58 … +572 °F) Version -50 … +400 °C (-58 … +752 °F) only with external housing. See supplementary instructions manual "External housing - VEGACAP, VEGACAL"L Sensor length, see chapter "Technical data"L1 Supporting tube length, see chapter "Technical data"

Page 36: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

36

9 Supplement

VEGACAP 67 • - two-wire

31317-EN-160331

9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights. Further information see www.vega.com.VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte.Nähere Informationen unter www.vega.com.Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellec-tuelle. Pour plus d'informations, on pourra se référer au site www.vega.com.VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad indus-trial. Para mayor información revise la pagina web www.vega.com.Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте www.vega.com.VEGA系列产品在全球享有知识产权保护。进一步信息请参见网站<www.vega.com。

9.4 TrademarkAll the brands as well as trade and company names used are property of their lawful proprietor/originator.

Page 37: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

37

Notes

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Page 38: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

38

Notes

VEGACAP 67 • - two-wire

31317-EN-160331

Page 39: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

39

Notes

VEGACAP 67 • - two-wire

3131

7-EN

-160

331

Page 40: Operating Instructions - Insatech - · PDF fileThis operating instructions manual provides all the information you . ... GOST 12821-80. You can find additional information in the supplementary

Printing date:

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany

3131

7-E

N-1

6033

1

All statements concerning scope of delivery, application, practical use and operat-ing conditions of the sensors and processing systems correspond to the information available at the time of printing.Subject to change without prior notice

© VEGA Grieshaber KG, Schiltach/Germany 2016