![Page 1: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/1.jpg)
Operating instructions Magnetic-inductive
flow meter
SM9004 SM2004
8000
0147
/ 00
0
4 / 2
013
UK
![Page 2: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/2.jpg)
2
Contents1 Preliminary note ���������������������������������������������������������������������������������������������������4
1�1 Symbols used ������������������������������������������������������������������������������������������������41�2 Warning signs used ���������������������������������������������������������������������������������������4
2 Safety instructions �����������������������������������������������������������������������������������������������53 Functions and features ����������������������������������������������������������������������������������������64 Function ���������������������������������������������������������������������������������������������������������������6
4�1 Measuring principle for volumetric flow monitoring ����������������������������������������64�2 Processing of the measured signals ��������������������������������������������������������������74�3 Flow rate measurement ���������������������������������������������������������������������������������74�4 Consumed quantity meter �����������������������������������������������������������������������������74�5 Temperature monitoring ���������������������������������������������������������������������������������84�6 Empty pipe detection �������������������������������������������������������������������������������������84�7 Volumetric flow or temperature monitoring / analogue function ���������������������94�8 Low flow cut-off (LFC) ����������������������������������������������������������������������������������104�9 Simulation ����������������������������������������������������������������������������������������������������10
5 Installation����������������������������������������������������������������������������������������������������������105�1 Recommended installation locations �����������������������������������������������������������105�2 Installation locations to be avoided ��������������������������������������������������������������125�3 Grounding ����������������������������������������������������������������������������������������������������135�4 Installation in pipes ��������������������������������������������������������������������������������������13
6 Electrical connection ������������������������������������������������������������������������������������������147 Operating and display elements ������������������������������������������������������������������������148 Menu ������������������������������������������������������������������������������������������������������������������15
8�1 Process value display ����������������������������������������������������������������������������������158�2 Main menu, Extended functions ������������������������������������������������������������������168�3 Basic settings ����������������������������������������������������������������������������������������������188�4 Min/max memory – Empty pipe – Simulation ����������������������������������������������208�5 Explanation simulation (SIM) �����������������������������������������������������������������������21
9 Set-up ����������������������������������������������������������������������������������������������������������������2110 Parameter setting ��������������������������������������������������������������������������������������������22
10�1 IO-Link �������������������������������������������������������������������������������������������������������2210�1�1 General information ��������������������������������������������������������������������������22
![Page 3: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/3.jpg)
3
UK
10�1�2 Device-specific information ���������������������������������������������������������������2210�1�3 Parameter setting tools ���������������������������������������������������������������������22
10�2 Changing the parameter value ������������������������������������������������������������������2310�2�1 Switching between the menu levels �������������������������������������������������2410�2�2 Locking / unlocking ���������������������������������������������������������������������������2410�2�3 Timeout ���������������������������������������������������������������������������������������������24
10�3 Setting the analogue value for volumetric flow ������������������������������������������2410�4 Setting the analogue value for temperature ����������������������������������������������2410�5 User settings (optional) ������������������������������������������������������������������������������25
10�5�1 Setting of the standard unit of measurement for temperature ����������2510�5�2 Setting of the standard unit of measurement for volumetric flow ������2510�5�3 Configuration of the standard display �����������������������������������������������2510�5�4 Changing the direction of the flow rate measurement ����������������������2510�5�5 Setting of measured value damping �������������������������������������������������2510�5�6 Setting of the error behaviour of the outputs ������������������������������������2510�5�7 Activating / deactivating empty pipe detection ����������������������������������2610�5�8 Time-delay empty pipe detection ������������������������������������������������������2610�5�9 Setting of the empty pipe detection ��������������������������������������������������2610�5�10 Setting of the low flow cut-off ����������������������������������������������������������26
10�6 Service functions ���������������������������������������������������������������������������������������2610�6�1 Reading the min/max values for the volumetric flow ������������������������2610�6�2 Reading the min/max values for the temperature �����������������������������2710�6�3 Simulation menu �������������������������������������������������������������������������������2710�6�4 Resetting all parameters to factory setting ���������������������������������������2710�6�5 Activating the IO-Link communication interface ��������������������������������27
11 Operation ���������������������������������������������������������������������������������������������������������2811�1 Reading the process value ������������������������������������������������������������������������2811�2 Reading the parameter value ���������������������������������������������������������������������2811�3 Error indications �����������������������������������������������������������������������������������������29
12 Technical data ��������������������������������������������������������������������������������������������������2913 Factory setting �������������������������������������������������������������������������������������������������30
![Page 4: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/4.jpg)
4
1 Preliminary note1.1 Symbols used
► Instruction> Reaction, result[…] Designation of keys, buttons or indications→ Cross-reference
Important note Non-compliance can result in malfunction or interference�Information Supplementary note�
1.2 Warning signs used
CAUTION Warning of personal injury� Slight reversible injuries may result�
NOTE Warning of damage to property�
![Page 5: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/5.jpg)
5
UK
2 Safety instructions• Please read this document prior to set-up of the unit� Ensure that the product is
suitable for your application without any restrictions�• Improper or non-intended use may lead to malfunctions of the unit or to un-
wanted effects in your application� That is why installation, electrical connec-tion, set-up, operation and maintenance of the unit must only be carried out by qualified personnel authorised by the machine operator�
• Check the compatibility of the product materials (see technical data) with the mediatobemonitoredinallapplications(→Technicaldataatwww.ifm.com).
CAUTION For medium temperatures above 50 °C some parts of the housing can heat up to over 65 °C�
► In this case do not touch the unit� ► Protect the housing against contact with flammable substances and uninten-tional contact�
► Do not press the pushbuttons manually� Instead use another object (e�g� ballpoint pen)�
NOTE This is a class A product� This unit may cause radio interference in domestic areas�
► If required, take appropriate EMC screening measures�
![Page 6: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/6.jpg)
6
3 Functions and featuresPressure Equipment Directive (PED): The units comply with section 3, article (3) of the Directive 97/23/EC and must be designed and manufactured for non-super-heated liquids of group 1 fluids in accordance with the sound engineering practice�The unit monitors liquid media�The unit detects the 3 process categories volumetric flow quantity, consumed quantity and medium temperature�Application areaConductive liquids with the following properties:• Conductivity:≥20µS/cm• Viscosity: < 70 mm2/s at 40°C
4 Function4.1 Measuring principle for volumetric flow monitoringThe magnetic-inductive measuring principle means that a magnetic field is gener-ated in the measuring pipe via current-carrying coils� When a conductive medium flows through the measuring pipe, the ions therein are diverted perpendicularly to the magnetic field� Positive and negative charge carriers flow in opposite direc-tions� The voltage induced is measured by two electrodes that are in contact with the medium� This signal voltage is directly proportional to the average flow veloc-ity� The volumetric flow quantity is derived from the internal pipe diameter�
3
1
2
4
5
1: Field coil2: Measuring pipe3: Electrode4: Charge carrier in the medium5: Magneticfield
![Page 7: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/7.jpg)
7
UK
Both electrodes must be wetted by the medium� Otherwise the signal [SEnS] for empty pipe is provided, if empty pipe detection is enabled�
4.2 Processing of the measured signalsThe unit displays the current process values�It generates 2 output signals according to the parameter setting�
OUT1/IO-Link: Parameter setting - Analogue signal for volumetric flow quantity (→10.3) - Communication interface (→10.6.5)
OUT2: Parameter setting - Analogue signal for temperature (→10.4)
4.3 Flow rate measurementAn analogue signal which is proportional to the volumetric flow (4���20 mA) is pro-vided on output 1 in case of medium flow in the measuring pipe� (On the analogue functions→4.7)In addition to the flow velocity, the unit also detects the flow direction� An arrow on the unit indicates the positive flow direction� Theflowdirectioncanbeinversed(→10.5.4).
► Use the supplied label to mark the changed flow direction�
Direction of flow corresponds to "flow direction" > process value and display positive�Direction of flow against "flow direction" > process value and display negative�
Only positive process values are processed for the signal output�
4.4 Consumed quantity meterThe unit has an internal mass flow meter which continuously totals the volumetric flow quantity� The total corresponds to the current consumed quantity�• The quantity meter takes account of the flow direction for totalisation:
![Page 8: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/8.jpg)
8
- Flow according to the marked flow direction (arrow "flow direction"): meter adds�
- Flow against the marked flow direction: meter subtracts�The meter saves the totalled consumed quantity every 10 minutes� After a power failure this value is available as the current meter reading� So the possible data loss can be maximum 10 minutes�The current meter reading can be evaluated via an external parameter setting software(→10.6.5ActivatingtheIO-Linkcommunicationinterface).
4.5 Temperature monitoringAn analogue signal (4���20 mA) can be provided on output 2 for temperature moni-toring.Ontheanaloguefunctions→4.7).
4.6 Empty pipe detectionTheunitdetectswhenthetwoelectrodesarenotwettedbythemedium(→4.1Measuring principle for volumetric flow monitoring)� The empty pipe detection can beactivatedordeactivated(→10.5.7).Ifitisactiveandthepipeisempty,theunitreacts as follows:
> [SEnS] is indicated in the display� > The flow is set to zero�Theemptypipedetectioncanbesetastime-dependingornottimedepending(→10�5�8)�
![Page 9: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/9.jpg)
9
UK
4.7 Volumetric flow or temperature monitoring / analogue func-tionCurrent output
MEWAEPASP
12
80 100 110-40 -20-50 [°C]
[%]-130 -120 0 100 120 130
[mA]
Characteristics of the analogue output according to the standard IEC 60947-5-71: Output current2: Volumetricflowquantity3: Temperature4: Display range5: Measuring range6: Range between analogue start point and analogue end point7: The unit is in the error state (FOU = OFF)8: The process value transmitted in an analogue way is therefore below the display range9: Curve of the analogue signal at factory setting10: Curve of the analogue signal with shifted ASP and AEP11: The process value transmitted in an analogue way is therefore above the display range 12: The unit is in the error state (FOU = ON)�ASP = analogue start point: determines at which measured value the output signal is
4 mA�AEP = analogue end point: determines at which measured value the output signal is
20 mA�VMR = final value of the measuring range = 100 %
Minimum distance between ASP and AEP = 20 % of the measuring range�
In the set scaling range the output signal is between 4 and 20 mA�
![Page 10: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/10.jpg)
10
4.8 Low flow cut-off (LFC)Withthisfunctionsmallvolumetricflowquantitiescanbeignored(→10.5.10).Flows below the LFC value are evaluated by the sensor as standstill (Q = 0)�4.9 SimulationWiththisfunctionflowandtemperaturevaluescanbesimulated.(→10.6.3).Theoutputs operate as previously set�
5 Installation ► Avoid deposits, accumulated gas and air in the pipe system�
5.1 Recommended installation locationsExample of an optimised installation:
F
1
► Install the unit so that the measuring pipe is completely filled� ► Arrange for inlet and outlet pipe lengths� Disturbances caused by bends, valves, reductions, etc� are compensated for� It applies in particular: no shut-off and control devices are allowed directly in front of the unit�
![Page 11: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/11.jpg)
11
UK
F2 x D
S
3
F
S
5 x D2
S = disturbance; D = pipe diameter; F = flow direction
► Install in front of or in a rising pipe:
F
F
4
F
5
F = flow direction
With empty pipe detection: ► Install the unit according to figure 1, 4 or 5�
![Page 12: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/12.jpg)
12
5.2 Installation locations to be avoided• Directly in front of a falling pipe�• In a falling pipe�• On the suction side of a pump�• Directly in front of the spout of the pipe�• At the highest point of the pipe system�
F
FF
FF
F = flow direction
The unit can be installed irrespective of the orientation if the following is ensured:
- No air bubbles can form in the pipe system� - The pipes are always completely filled�
![Page 13: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/13.jpg)
13
UK
5.3 GroundingIf installed in an ungrounded pipe system (e�g� plastic pipes), the unit must be grounded (functional earth)�
GroundbracketsfortheM12connectorareavailableasaccessories(→www.ifm.com)�
5.4 Installation in pipesThe unit can be installed in pipes using adapters� The adapters have to be ordered separatelyasaccessories(→www.ifm.com).
BA DC B AD C
1� Screw the adapter (B) into the pipe (A)� 2� Place the seals (C) and install the unit according to the marked flow direction�3� Screw the adapter (B) with the threads (D) until it is hand-tight� 4� Tighten the two adapters in opposite direction (tightening torque: 30 Nm)�After installation air bubbles in the system can affect the measurement�Corrective measures:
► Rinse the system after installation for ventilation (rinsing quantity > 15 l/min�)�In case of horizontal installation: As a result of design requirements a small quan-tity of the medium always remains in the measuring channel after switching off the pump�
![Page 14: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/14.jpg)
14
6 Electrical connectionThe unit must be connected by a qualified electrician�The national and international regulations for the installation of electrical equipment must be adhered to�Voltage supply according to EN 50178, SELV, PELV�
► Disconnect power� ► Connect the unit as follows:
43
2 1L+
LOUT1OUT2
4:2:
4
2
1
3
Pin 1 Ub+Pin 3 Ub-Pin 4 (OUT1)
•Analogue signal for volumetric flow quantity•IO-Link
Pin 2(OUT2) •Analogue signal for temperature
7 Operating and display elements
Enter ▲
▼
1 to 8: indicator LEDs
![Page 15: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/15.jpg)
15
UK
•LEDs1-6=Unitofthecurrentlyrepresentednumericalvalue→11.1Readingtheprocess value
•LED 7 = current process value in 103
•LED 8 = not used9: Alphanumeric display, 4 digits•Current volumetric flow quantity (with setting [SELd] = [FLOW])•Current medium temperature (with setting [SELd] = [TEMP])•Parameters and parameter values10: [Enter] button•Selection of the parameters•Reading of the set values•Confirmation of the parameter valuesRepresentationin→8Menu:11: Buttons up [▲] and down [▼]•Selection of the parameters•Activation of the setting functions•Changing the parameter values•Change of the display unit in the normal operating mode (Run mode)•Locking / unlockingRepresentationin→8Menu: and
8 Menu8.1 Process value display
gpm °Fgphl/min °Cm3/h
↓Mainmenu
![Page 16: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/16.jpg)
16
8.2 Main menu, Extended functions
↑Processvaluedisplay
EF
8.3
8.4
8.4
8.4
→8.3Basicsettings→8.4Min/maxmemory–Emptypipe–Simulation
![Page 17: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/17.jpg)
17
UK
Explanation main menu
ASP1 Analogue start value for volumetric flowAEP1 Analogue end value for volumetric flowASP2 Analogue start value for temperatureAEP2 Analogue end value for temperatureEF Extended functions / opening of menu level 2
Explanation extended functions (EF)
rES Restore factory settingIO-L Activate IO-Link communicationCFG Submenu basic settingsMEM Submenu min/max memoryEPD Submenu empty pipeSIM Submenu simulation
![Page 18: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/18.jpg)
18
8.3 Basic settings↑Mainmenu
CFG
°°
EF
![Page 19: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/19.jpg)
19
UK
Explanation basic settings (CFG)FOU1 Behaviour of output 1 in case of an errorFOU2 Behaviour of output 2 in case of an errordAP Measured value damping / damping constant in secondsdiS Update rate and orientation of the displayUni�F Standard unit of measurement for volumetric flowUni�T Standard unit of measurement for temperature
SELd Standard measuring unit of the display: volumetric flow value / medium temperature
LFC Low flow cut-offFdir Direction of flow
![Page 20: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/20.jpg)
20
8.4 Min/max memory – Empty pipe – Simulation↑Mainmenu
EF
MEM
SIM
8.1
EPD
* Parameters are only displayed for the selection EP�On = On�
![Page 21: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/21.jpg)
21
UK
Explanation min/max memory (MEM)HI�F Max� value flowLO�F Min� value flowHI�T Max� value temperatureLO�T Min� value temperature
Explanation empty pipe (EPD)EP�On Empty pipe detection on / offdEP�E� Delay time empty signaldEP�F Delay time full signalEP�Pr Current measured value of empty pipe detectionEP�SP Switch point of empty pipe detection
8.5 Explanation simulation (SIM)S�FLW Simulation flow valueS�TMP Simulation temperature valueS�Tim Simulation timeS�On Simulation start
9 Set-upAfter power on and expiry of the power-on delay time (approx� 5 seconds) the unit is in the normal operating mode� It carries out its measurement and evaluation functions and generates output signals according to the set parameters� For the analogue output 2 (OUT2), the output signal is 20 mA during the power-on delay time�In the first 2 seconds, analogue output 1 (OUT1) is passive and available for IO-Link communication� During the remaining power-on delay time, the output signal is at 20 mA�
![Page 22: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/22.jpg)
22
10 Parameter settingParameters can be set before installation and set-up of the unit or during opera-tion�
If you change parameters during operation, this will influence the function� ► Ensure that there will be no malfunctions in your plant�
During parameter setting the unit remains in the operating mode� It continues to monitor with the existing parameter until the parameter setting has been com-pleted�
10.1 IO-Link10.1.1 General informationThis unit has an IO-Link communication interface for a point-to-point connection with a USB adapter cable�You will find more detailed information about IO-Link at www�ifm�com/gb/io-link�10.1.2 Device-specific informationYou will find the IODDs necessary for the configuration of the IO-Link unit and detailed information about process data structure, diagnostic information and parameter addresses at www�ifm�com/gb/io-link� 10.1.3 Parameter setting toolsYou will find all necessary information about the required IO-Link hardware and software at www�ifm�com/gb/io-link�
► The memory plug (E30398) must not remain connected to the unit, because it falsifies the analogue output� It must only be connected for parameter setting�
![Page 23: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/23.jpg)
23
UK
10.2 Changing the parameter valueSelect parameter1� Press [Enter] briefly�2� Press[▲]or[▼]untiltherequested
parameter is displayed.
21
Changing the parameter value3� Press [Enter] briefly�
> The currently set value is displayed�4� Keep[▲]or[▼]pressedfor1s.
> Display flashes first, then permanent�5� Changevaluebypressing[▲]or[▼].
Keep[▲]or[▼]pressed. > Faster cycle of the numerical
values�
4
5
3
Confirm the parameter value6� Press [Enter] briefly�
> The parameter is displayed again� The new setting value is saved�
6
Finish parameter setting and change to the process value display: ► Wait for 30 seconds
or ► Change from the submenu to the main menu, from the main menu to the process value displaywith[▲]or[▼].
If [C�Loc] is displayed when an attempt is made to modify a parameter value, an IO-Link communication is active (temporary locking)� If [S�Loc] is displayed, the sensor is permanently locked via software� This locking can only be removed with a parameter setting software�
![Page 24: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/24.jpg)
24
10.2.1 Switching between the menu levels
Change to the submenu
Switching to the next submenu via the parameters [EF], [CFG], [MEM], [EPD] or [SIM]�
► Selectasubmenuwith[▲]or[▼]andswitchtothesubmenuby pressing [Enter]�
Back to the process value display
► Wait for 30 secondsor
► Change from the submenu to the main menu, from the main menutotheprocessvaluedisplaywith[▲]or[▼].
10.2.2 Locking / unlockingThe unit can be locked electronically to prevent unintentional settings� On delivery: not locked�Locking is also possible via an IO-Link capable parameter setting tool�Locking ► Make sure that the unit is in the normal operating mode�
► Press[▲]and[▼]simultaneouslyfor10s. > [Loc] is displayed�
During operation: [Loc] is briefly displayed if you try to change parameter values�
Unlocking ► Press[▲]and[▼]simultaneouslyfor10s. > [uLoc] is displayed�
10.2.3 TimeoutIf no button is pressed for 30 s during parameter setting, the unit returns to the operating mode with unchanged parameter�
10.3 Setting the analogue value for volumetric flow ► Select [ASP1] and set the value at which the minimum value is provided� ► Select [AEP1] and set the value at which the maximum value is pro-vided�
10.4 Setting the analogue value for temperature ► Select [ASP2] and set the value at which the minimum value is provided� ► Select [AEP2] and set the value at which the maximum value is pro-vided�
![Page 25: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/25.jpg)
25
UK
10.5 User settings (optional)10.5.1 Setting of the standard unit of measurement for temperature
► Select [Uni�T] and set the unit of measurement: [°C] or [°F]�
10.5.2 Setting of the standard unit of measurement for volumetric flow ► Select [Uni�F] and set the unit of measurement: [Lmin], [m3h], [gpm] or [gph]
10.5.3 Configuration of the standard display ► Select [SELd] and determine the standard measuring unit:
- [FLOW] = the current volumetric flow value in the standard unit of measurement is displayed�
- [TEMP] = the current medium temperature is displayed� ► Select [diS] and set the update rate and orientation of the display:
- [d1] = update of the measured values every 50 ms� - [d2] = update of the measured values every 200 ms� - [d3] = update of the measured values every 600 ms� - [rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°� - [OFF ] = the display is switched off in the operating mode�
10.5.4 Changing the direction of the flow rate measurement ► Select [Fdir] and set the direction of flow: [+] = flow in the direction of the flow arrow (= factory setting) [-]=flowagainsttheflowarrow►labeloverthearrow
10.5.5 Setting of measured value damping ► Select[dAP]andsetthedampingconstantinseconds(τvalue63%).
10.5.6 Setting of the error behaviour of the outputs ► Select [FOU1] and set the value:
- [On ] = the analogue signal goes to the upper fault value� - [OFF ] = the analogue signal goes to the lower fault value� - [OU] = the analogue signal corresponds to the measured value�
► Select [FOU2] and set the value: - [On ] = the analogue signal goes to the upper fault value� - [OFF ] = the analogue signal goes to the lower fault value� - [OU] = the analogue signal corresponds to the measured value�
![Page 26: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/26.jpg)
26
10.5.7 Activating / deactivating empty pipe detection ► Select [EP�On] and set the function: - [OFF] = empty pipe detection deactivated� - [On] = empty pipe detection activated�
10.5.8 Time-delay empty pipe detection ► Select [dEP�E] and set the delay time from 0…30 s, at which the signal should be provided when the pipe is empty�
► Select [dEP�F] and set the delay time from 0…30 s, at which the signal should be provided when the pipe is full�
10.5.9 Setting of the empty pipe detection ► Select [EP�Pr] to display the current value of the empty pipe detection in percent�
► Select [EP�SP] and set the switch point of empty pipe detection�
10.5.10 Setting of the low flow cut-off
► Select [LFC] and set the limit value�
10.6 Service functions10.6.1 Reading the min/max values for the volumetric flow
► Select [HI�F] or [LO�F][HI�F] = max� value, [LO�F] = min� value�
Delete memory: ► Select [HI�F] or [LO�F]� ► Press [Enter] briefly� ► Keep[▲]or[▼]pressed.
> [----] is displayed� ► Press [Enter] briefly�
It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first time�
![Page 27: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/27.jpg)
27
UK
10.6.2 Reading the min/max values for the temperature ► Select [HI�T] or [LO�T][HI�T] = max� value, [LO�T] = min� value�
Delete memory: ► Select [HI�T] or [LO�T]� ► Press [Enter] briefly� ► Keep[▲]or[▼]pressed.
> [----] is displayed� ► Press [Enter] briefly�
It makes sense to delete the memories as soon as the unit operates under normal operating conditions for the first time�
10.6.3 Simulation menu
► Select [S�FLW] and set the flow value to be simulated� ► Select [S�TMP] and set the temperature value to be simulated� ► Select [S�Tim] and set the time of the simulation in minutes� ► Select [S�On] and set the function: - [On]: The simulation starts� The values are simulated for the time set at [S�Tim]� [SIM] is displayed simultaneously with the process values� Cancel with [Enter]�
- [OFF]: The simulation is not active�
10.6.4 Resetting all parameters to factory setting ► Select [rES]� ► Press [Enter] briefly� ► Keep[▲]or[▼]pressed.
> [----] is displayed� ► Press [Enter] briefly�
Forthefactorysettingspleaserefertotheendoftheseinstructions→13.We recommend taking down your own settings in that table before carrying out a reset�
10.6.5 Activating the IO-Link communication interface ► Select [IO-L] and set the function: - [OFF] = IO-Link interface deactivated� - [On] = IO-Link interface activated�
The analogue output OUT1 is deactivated when the IO-Link interface is activated�
![Page 28: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/28.jpg)
28
11 Operation11.1 Reading the process valueThe LEDs 1-6 signal which process value is currently displayed� The process value to be displayed as standard (temperature, flow velocity) can bepreset.→10.5.3Configurationofthestandarddisplay.Astandardunitofmeasurement can be defined for the flow velocity (l/min, m3/h,gpmorgph)→10�5�2)� For temperature measurement, °C or °F can be selected as standard unit ofmeasurement(→10.5.1).Further process values can be read in addition to the preset standard display:
► Press the buttons [▲] or[▼]� > The LED of the selected process value display is lit and the current process
value is displayed� > After 30 seconds the display changes to the standard display�
LED Process value display Unit1 Current flow volume per minute l / min2 Current flow volume per hour m3 / h3 Current flow volume per minute gal / min4 Current flow volume per hour gal / h5 Current medium temperature °C6 Current medium temperature °F7 Current flow volume in 103
11.2 Reading the parameter valueTake the following steps to display the currently set parameter value:
![Page 29: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/29.jpg)
29
UK
Select parameter1� Press [Enter] briefly2� Press[▲]or[▼]untiltherequested
parameter is displayed.
21
Display the parameter value3� Press [Enter] briefly
> The currently set value is displayed for 30 s�
By pressing [Enter] briefly several times, the display switches between parameter and parameter value�
3
Switching to the process value display ► Wait for 30 seconds
or ► Change from the submenu to the main menu, from the main menu to the process value displaywith[▲]or[▼].
11.3 Error indicationsWarning message
[OL] Detection zone of volumetric flow or temperature exceeded�[UL] Below the detection zone of volumetric flow or temperature�[Err] •Unit faulty / malfunction�
•Measured value outside the detection zone�[C�Loc] Setting pushbuttons locked, parameter change rejected�
Active IO-Link communication�[S�Loc] Setting pushbuttons locked, parameter change rejected�
Unlock using parameter setting software�[SEnS] Sensor signal invalid�
•Measuring pipe not sufficiently filled� •Medium with a too low conductivity�
[IOE�n] Malfunction� The unit is faulty and must be replaced�
12 Technical dataTechnical data and scale drawing at www.ifm.com→Datasheetsearch→Articlenumber.
![Page 30: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/30.jpg)
30
13 Factory settingFactory setting User setting
ASP1 (FLOW) 0 % *AEP1 (FLOW) 100 % *ASP2 (TEMP) -20 °CAEP2 (TEMP) 80 °CIO-L OFFFDir +FOU1 OFFFOU2 OFFdAP 0.6 sdiS d2Uni.F LminUni.T °CSELd FLOWLFC 5 l/minEP.On OFFdEP.E 0 sdEP.F 2 sEP.SP 75 %S.FLW 20 % *S.TMP 20 °CS.Tim 2 minS.On OFF
* of VMR
More information at www�ifm�com
![Page 31: Operating instructions Magnetic-inductive flow …8 2 Main menu, Extended functions 16 8 3 Basic ... The magnetic-inductive measuring principle means that a magnetic field is gener-ated](https://reader034.vdocument.in/reader034/viewer/2022043009/5f9d41b49959d25f28063c37/html5/thumbnails/31.jpg)