optimized system for your bottom line system...3 chiller plant efficiency note: based on...

55
Optimized System for Your Bottom Line Trane Training Class 1 Dec, 2017

Upload: others

Post on 07-Apr-2020

2 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

Optimized System for Your Bottom Line

Trane Training Class

1 Dec, 2017

Page 2: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

2

Setting your system for great payback

A Balanced Approach, with a Focus on Efficiency

Where is money spent over

a 30 year lifetime?

Power 88.5%

Service 6.6%

First Cost 4.9%

30 Year Investment

Total Cost of Ownership

Page 3: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

3

Chiller Plant Efficiency

Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application

with 5.6C nominal chilled water supply temperature and open cooling towers sized for 29.4C

maximum entering condenser water temperature and 20% excess capacity

Page 4: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

4

Chiller Plant Efficiency

Optimal

Plant

Efficiency

= +

Guaranteed

chiller

performance

System

application &

control

strategy

Page 5: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

5

• Major Equipment for water-cooled chiller plant

- Chiller

- Pump

- Cooling Tower

Chiller Plant Efficiency

Page 6: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

6

8.0

ASHRAE Standard 90.1

Ch

ille

r e

ffic

ien

cy,

CO

P

6.0

4.0

2.0

0.0 “best”

available

Centrifugal >600 tons

Screw 150-300 tons

Scroll <100 tons

Reciprocating <150 tons

1977 1980 1989 1999

Chiller Performance History of Chiller Efficiency

Page 7: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

7 Comprehensive review to be conducted in 2018, 2021 and 2024 respectively.

Chiller Performance BEEO Requirement (2015)

Page 8: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

8

Chiller Performance

0.433 kW/ton (8.1 COP)

0.460 kW/ton (7.6 COP)

Theoretical Refrigerant

Efficiency 0.460 kW/ton (7.6 COP)

0.388 kW/ton (9.1 COP)

0.415 kW/ton (8.5 COP)

Centrifugal Chiller

Cycle Efficiency 0.415 kW/ton (8.5 COP)

100% 98.1% Drive Train Efficiency 97.9%

83.3% 80.4% Compressor Efficiency 81.8%

95.5% 95.0% Motor Efficiency 95.0%

0.415 kW/ton (8.5 COP)

100%

78.8%

97.0%

0.487 kW/ton (7.2 COP)

0.554 kW/ton (6.3 COP)

Chiller Efficiency 0.545 kW/ton (6.4 COP)

0.543 kW/ton (6.5 COP)

Direct Drive (Hermetic Mech)

Gear Drive (Hermetic Mech)

R-123 R-134a

Gear Drive (Open Mech)

Type of Refrigerant R-134a

0.460 kW/ton (7.6 COP)

Direct Drive (Hermetic Mag Lev)

R-134a

Multi Stage Single Stage Single Stage Multi Stage

Centrifugal Chiller

Page 9: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

9

AHRI Definition of Integrated Part Load Value (IPLV/NPLV)

Temperatures: Expected Entering Tower Water

AHRI Conditions: Chilled Water: 54°/44°F (12.2°/6.6°C)

Condenser Water: 3 GPM/Ton (0.054 L/S/kW)

A = kW/Ton @ 29.4°C (85°F) @100% Load

B = kW/Ton @ 23.9°C (75°F) @ 75% Load

C = kW/Ton @ 18.3°C (65°F) @ 50% Load

D = kW/Ton @ 18.3°C (65°F) @ 25% Load

1 IPLV =

1%

A 42%

B

12%

D + + +

45%

C

42%

23.9°C (75°F)

1% 29.4°C (85°F)

Real World Chillers Operate at Real World Conditions

57%

18.3°C (65°F)

Chiller Performance Efficiency Comparison – Index Rating

Page 10: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

10

55°F(13°C) 60°F(16°C) 65°F(18°C) 70°F(21°C) 75°F(24°C) 80°F(27°C) 85°F(30°C)

Hong Kong (Two Chiller Plant)

0

10

20

30

40

50

60

70

80

90

100

Entering Condenser Water Temp

Ch

ille

r L

oa

d (

%)

Custom Analysis versus Generic NPLV Estimates

13% of Operation

(IPLV = 12%)

18% of Operation

(IPLV = 42%)

5% of Operation

(IPLV = 45%)

64% of Operation

(IPLV = 1%)

Chiller Performance Efficiency Comparison – Index Rating vs. Real-World

Where Do The Chillers in Your Plant Run?

Page 11: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

11

Always, Always Remember … The Meter is On The BUILDING

Chiller Performance Real Payback Require Real Analysis

Page 12: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

12

Compliant calculation methodologies

TRACE 700 calculations apply techniques

recommended by the American Society of

Heating, Refrigerating and Air-Conditioning

Engineers (ASHRAE). The program is

tested in compliance with ASHRAE

Standard 140-2007/2011, Standard Method

of Test for the Evaluation of Building Energy

Analysis

Computer Programs, and it meets the

requirements for simulation software set by

ASHRAE Standard 90.1-2007/2010 and the

LEED® Green Building Rating System.

TRACE

700

Chiller Plant

Analyzer

Chiller Performance Real Payback Require Real Analysis

Page 13: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

13

Chiller Plant Efficiency

• Hydraulic Power Ph(kW) = q ρ g h / (3.6 x106) - q = flow capacity (m3/h)

- ρ = density of fluid (kg/m3)

- g = gravity (9.81 m/s2)

- h = pump head (m)

• Pump Head is the total resistance that a pump must

overcome

- Static Head

- Friction Head

- Pressure Head

- Velocity Head

Pump Performance

Page 14: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

14

•Never oversize pump

•Select pump duty point for

best efficiency

Pump Performance Pump Head Calculation

Page 15: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

15

Pump Performance Reduce Friction Loss

Page 16: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

16

Pump Performance

BEC 2015 Chapter 6 Energy Efficiency Requirements for Air-conditioning Installation

Pump Head Calculation – BEC 2015

CIBSE Guide C4

Flow of Fluids in Pipes and Ducts

• Pressure drop per unit length

- 2.5m/s @ 200mm pipe

- 240 Pa/m with 89.7kg/s

Page 17: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

17

• Friction Losses in Elbow (equv. length)

- 18 Feet (90°Elbow)

• Pressure drop

18 / 3.3 x 240 Pa/m

= 1.309kPa

• Pump Power Consumption

1.309 x 89.7 / 0.7 / 0.93 / 1,000

= 0.18 kW

• Annual Operation Cost

0.18 x 12 x 365 x 1.2

= HKD946

Pump Performance Pump Head Calculation

Page 18: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

18

• Friction Losses in Elbow (equv. length)

- 10 Feet (45°Elbow)

- 18 Feet (90°Elbow)

• Pressure drop difference

(18-10) / 3.3 x 240 Pa/m x 2

= 1,164Pa = 1.164kPa

• Pump Power Consumption

1.164 x 89.7 / 0.7 / 0.93 / 1,000

= 0.16 kW

• Annual Operation Cost

0.16 x 12 x 365 x 1.2

= HKD841

Pump Performance Pump Head Calculation

Page 19: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

19

Pump Performance Reduce Friction Loss

Page 20: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

20

Pump Performance Reduce Friction Loss

Page 21: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

21

Pump Performance Reduce Friction Loss

Page 22: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

22

Pump Performance Reduce Friction Loss

Page 23: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

23

Pump Performance Reduce Friction Loss

Optimal chiller plant layout and careful selection of low pressure drop devices reduces pressure losses

Page 24: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

24

• Friction Loss in 100% open balancing valve

- Nominal Size: 200mm

- Flow Rate: 89.7l/s

- Pressure drop = 17.8kPa

• Pump Power Consumption

17.8 x 89.7 / 0.7 / 0.93 / 1,000

= 2.45 kW

• Annual Operation Cost

2.45 x 12 x 365 x 1.2

= HKD12,877

Pump Performance Simplify Piping Layout

Page 25: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

25

Pump Performance Simplify Piping Layout

Water-cooled chiller

Chilled water pump

Condensing

water pump

Cooling

tower

Water

tank

Page 26: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

26

Pump Performance Simplify Piping Layout

Equal pipe length for self-balancing

•Eliminate balancing equipment

Apply low friction loss fitting

•Reduce overall pressure drop

Page 27: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

27

Pump Performance Reduce Friction Loss

• Increase the pipe diameter of the system

• Minimize the length of the piping in the system

• Simplifying the layout as much as possible

• Minimize the number of elbows, tees, valves, fittings

and other obstructions in the piping system

• Reduce the flow rate

Page 28: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

28

Cool More or Pump More?

• Pump efficiency ≈ 70%

COP ≈ 0.7

• Chiller COP ≈ 7.0

• Chiller COP ≈ 10x the pump COP

Page 29: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

29

+/-$

air handlers

+/-$

+/-$

+/-$

controls

chillers

+/-$ piping

~/–$

ductwork

~/–$

System Enhancement

• Low Flow

• Low Temperature

• High Efficiency Systems

Earthwise Application

Page 30: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

30

Temperature differential

Supply temperature Flow rates Fans

Ductwork

Pump

Piping

System Enhancement Earthwise Application

Page 31: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

31

System Enhancement

• Chiller control sophistication

• Operating cost savings

- Pump energy

- Response to low DT Syndrome

Why Consider Variable Primary Flow (VPF) Now?

Page 32: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

32

• Reduces capital investment

• Saves mechanical-room space

• Simplifies control

• Improves system reliability

• Improved chiller performance

Variable Primary Flow (VPF) Advantages

Page 33: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

33

Variable Primary Flow (VPF) Improve chiller performance

0.45

0.50

0.55

0.60

0.65

0.70

0.75

0.80

10 20 30 40 50 60 70 80 90 100

CenTraVac P art Load P erformance CTV-1% Lo ad v s . k W /to n -- u s in g AR I R elief Meth o d

Vers io n 2 4 .0 8 , R EVL 5 5 0 6 6

kW/to

n

% Load

Page 34: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

34

0.55

0.60

0.65

0.70

0.75

0.80

0.85

0.90

0.95

20 30 40 50 60 70 80 90 100

CenTraVac P art Load P erformance CTV-1% Lo ad v s . k W /to n -- u s in g C o n s tan t C o n d en ser M eth o d

Vers io n 2 4 .0 8 , R EVL 5 5 0 6 6

kW/to

n

% Load

Variable Primary Flow (VPF) Improve chiller performance

primary/secondary

variable primary

Page 35: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

35

• Chillers must be able to accommodate a change of

flow of at least 10% per minute; 30% or even 50%

is even better

• Minimum and maximum flows must not be violated

• A bypass is required to maintain minimum flow

Variable Primary Flow (VPF) Three Key Application Requirements

Page 36: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

36

condenser water temperature, °F

400

22

en

erg

y c

on

su

mp

tio

n, kW

24 26 28 30 20

300

200

100

0 32

tower

chiller

total

optimal

control point

Chiller-Tower Optimization (CTO) Optimal condenser water control

Page 37: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

37

Chiller-Tower Optimization (CTO)

• Chilled water plant

- Tower design

- Chiller design

Centrifugal

Helical rotary

Variable speed drive

Absorption

- Changing conditions

Chiller load

Ambient wet bulb

Dependent On?

Page 38: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

38

System Enhancement

• EarthWise Application

- Low flow, low temperature and large ∆T system

• Variable Primary Flow

• Chiller-tower Optimization

Page 39: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

39

Energy Approach

Page 40: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

40

-

200,000

400,000

600,000

800,000

1,000,000

1,200,000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Ele

ctr

icit

y T

ari

ff (

HK

$)

Electricity Fee

2008

2009

2010

Energy Approach Baseline Energy Consumption

Page 41: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

41

• Correctly Size the New Equipment

• Proper Chiller plant design

- System Schematic

- Layout

• Implement of Chiller Plant Control

Energy Approach Strategies for chiller upgrades & optimization

Page 42: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

42

• Determine actual building load

- From BMS/operation log

- Estimated from electric bill

-

200,000

400,000

600,000

800,000

1,000,000

1,200,000

Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Ele

ctr

icit

y T

ari

ff (

HK

$)

Electricity Fee

2008

2009

2010

Electricity Fee for Chiller Plant = HKD5,662,191 (65% of overall)

Annual Electricity Fee– HKD8,711,063 @ 2008

Energy Approach Correctly Size the New Equipment

Page 43: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

43

• Determine actual building load

- From BMS/operation log

- Estimated from electric bill

• Downsize Chiller if possible

- Match with cooling load profile

- Reduce initial cost and payback period

• Replace with higher efficiency chiller

- Improve overall savings

Energy Approach Correctly Size the New Equipment

Page 44: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

44

• Energy Analysis

- Employ TRACE 700 Chiller Plant Analyzer for plant

configuration comparisons

- Input existing energy profile for analysis

- Calculate the energy and economic effects on different

configuration

Energy Approach Correctly Size the New Equipment

Page 45: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

45

Energy Approach Correctly Size the New Equipment

Page 46: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

46

• Alternative 1

- 2 no 600 TR water-cooled centrifugal chiller

- 1 no 600 TR water-cooled centrifugal chiller c/w AFD

• Alternative 2

- 2 no 750 TR water-cooled centrifugal chiller

- 1 no 300 TR water-cooled screw chiller

Total 1,800TR cooling capacity will be

provided

Energy Approach Correctly Size the New Equipment

Page 47: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

47

Alternative 1 Alternative 2

Annual Saving:

HKD 2,287,377 (40%) HKD 2,084,079 (36.6%)

Energy Approach Correctly Size the New Equipment

Page 48: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

48

• Review of Existing System Arrangement

• Consideration of System Change-over / Migration

• Select chilled / condensing water distribution system

• Decide equipment design condition (e.g. Chilled Water Temp, Cooling Tower Approach)

• Properly size pipe sizes

• Associated system design (e.g. Make-up / bleed off system, chemical treatment system)

Energy Approach Chiller Plant Design (Schematic)

Page 49: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

49

Bleed off

System

Chiller

Make up system

Condensing

Water

Pump

Cooling Tower

Chilled Water

Pump

Chemical

Treatment

Energy Approach Chiller Plant Design (Schematic)

Page 50: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

50

• Satisfy statutory requirement

• Sufficient space for maintenance and service

• Minimize water pressure drop

Energy Approach Chiller Plant Design (Layout)

Page 51: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

51

Energy Approach Chiller Plant Design (Layout)

Page 52: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

52

Comprehensive control system with Cooling Tower Optimization

Energy Approach Chiller Plant Control

Page 53: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

53

• Fully Automation

• Trend log for major

equipment

• Alarm Management

Energy Approach Chiller Plant Control

Page 54: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C

54

• System analysis for plant configuration design

• Select high efficiency for better energy saving

• Consider pressure drop and future maintenance

during pipework and layout design

• Reliable Chiller Plant Control System

• Monitor the system performance after installation

Energy Approach Summary

Page 55: Optimized System for Your Bottom Line System...3 Chiller Plant Efficiency Note: Based on electrically driven centrifugal chiller plants in comfort conditioning application with 5.6C