optimizing central chilled water systems...chilled water plant efficiency • operating kw/ton...

51
Optimizing Central Chilled Water Systems Kent W. Peterson, PE, FASHRAE P2S Engineering, Inc. [email protected]

Upload: others

Post on 25-Jan-2021

21 views

Category:

Documents


2 download

TRANSCRIPT

  • Optimizing Central Chilled Water

    SystemsKent W. Peterson, PE, FASHRAE

    P2S Engineering, Inc.

    [email protected]

  • 2Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Presentation Outline

    • Foundation of CHW Plant Design• Hydronic System Design• Chiller Fundamentals• Optimizing Plant Performance• Building Interfaces

  • 3Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Foundation of Design

    • Why look “outside the plant”?• Understand how distribution system will

    operate• Understand how CHW ∆T will be effected by

    dynamics of the systems connected

    GOALDeliver CHW to all loads under various load

    conditions as efficiently as possible

  • 4Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Understanding Loads & Their Impact on Design

    • Overall plant capacity is determined by peak design load

    • Cooling load profile describes how the load varies over time is needed to design the plant to stage efficiently

  • 5Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Chilled Water Plant Efficiency

    • Operating kW/ton achievable in today’s plants (includes chillers, cooling towers and pumps)

    • 0.5 - 0.7 Excellent• 0.7 - 0.85 Good• >1.0 Needs Improvement

    • Do you really know how your chilled water plants are performing?

  • Discussionon Hydronics

  • 7Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Purpose of Pumping Systems

    Move enough water through the piping systemat the minimum differential pressurethat will satisfy all connected loads

  • 8Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Understanding Hydronics

    • The pumping system will be required to operate under various load conditions

    • Variable flow system differential pressures throughout the system will be dynamic

    • Hydronic systems should be hydraulically modeled to design or troubleshoot complex systems

  • 9Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Caution

    • Excessive pump head can cause systems to not function as designed and waste considerable energy

    • Pump Selection

  • 10 Inspire • Innovate • AchieveInspire • Innovate • Achieve

    System & Pump Curves

    Total Flow

    Tota

    l Pre

    ssur

    e

  • 11

    Hydronic FundamentalsVariable Flow System Dynamics

    VFD

    Load

    LoadDP

    100 GPM5 PSID

    100 GPM5 PSID

    5 PSID

    28 PSID

    5 PSID

    2 PSID

    12 PSID38 PSID45 PSID

    PUMP CLOSE LOAD REMOTE LOAD

    20

    60

    50

    40

    30

    10

    0

    70

    PR

    ES

    SU

    RE

    PS

    IG

  • 12

    Hydronic FundamentalsVariable Flow System Dynamics

    100 GPM5 PSID

    0 GPM0 PSID

    5 PSID

    2 PSID

    12 PSID

    0 PSID

    VFD

    Load

    Load

    DP

    12 PSID12 PSID19 PSID

    PUMP CLOSE LOAD REMOTE LOAD

    20

    60

    50

    40

    30

    10

    0

    70

    PR

    ES

    SU

    RE

    PS

    IG

  • 13

    Hydronic FundamentalsVariable Flow System Dynamics

    VFD

    DP

    100 GPM5 PSID

    0 GPM0 PSID

    5 PSID

    28 PSID

    38 PSID

    0 PSID

    BAD SENSORLOCATION

    Load

    Load

    38 PSID38 PSID45 PSID

    PUMP CLOSE LOAD REMOTE LOAD

    20

    60

    50

    40

    30

    10

    0

    70

    PR

    ES

    SU

    RE

    PS

    IG

  • 14

    Hydronic FundamentalsVariable Flow System Dynamics

    CONTROL VALVE ∆PAT VARIOUS LOAD CONDITIONS

    Case 1Full Flow

    Case 275% Flow

    Case 350% Flow

    Case 425% Flow

    Case 510% Flow

    Branch Flow (gpm) 100 75 50 25 10

    Branch ∆P 38 38 38 38 38

    Coil ∆P 5.0 2.8 1.3 0.3 0.1

    Balancing Valve ∆P 28.0 15.8 7.0 1.8 0.3

    Control Valve ∆P 5.0 19.4 29.8 35.9 37.7

  • 15Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Balancing ConsiderationsVariable Flow Systems

    • Too large a balancing valve pressure drop will affect the performance and flow characteristic of the control valve.• ASHRAE 2003 Applications Handbook, page

    37.8

  • 16Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Hydronic Pumping Conclusions

    • Coil heat transfer is easier to control in low head (

  • What You Must KnowAbout CHW ∆T

  • 18Inspire • Innovate • AchieveInspire • Innovate • Achieve

    CHW Temperature Differential

    • Poor CHW ∆T is the largest contributor to poor CHW plant performance

    • To predict ∆T, you must know:• Characteristics of connected loads• Control valve requirements and limitations• Control valve control algorithms and setpoints• Heat exchanger characteristics

  • Chilled Water Coil Characteristics

    Assumes Constant Load

    CHWS Temperature °FCHWS Temperature °F

    CH

    W ∆

    T °F

    CH

    W ∆

    T °F

  • 20Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Factors that Degrade ∆TAssuming Coils are Selected for Desired ∆T

    • Higher CHWS temperature• Poor control valves

    • 3-way control valves• 2-position valves on fan coil units

    • Controls not controlling• Setpoint cannot be achieved• Valves not interlocked to close if load turns off

  • 21Inspire • Innovate • AchieveInspire • Innovate • Achieve

    ∆T Conclusions• Design, construction and operation

    errors that cause low ∆T can be avoided

    • Other causes for low ∆T can never be eliminated

    • ∆T degradation below design conditions is inevitable, therefore, system design must accommodate the level of degradation anticipated

  • Chiller Fundamentals

  • 23Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Understanding Refrigerant Lift

    • Lift = SCT - SST

    • Saturated Condensing Temperature (SCT) is dependent upon LEAVING condenser water temperature

    • Saturated Suction Temperature (SST) is based off of LEAVING chilled water temperature

  • Percent Loaded

    KW

    /ton

    Centrifugal Chiller without VFD1200T Low Pressure

  • Centrifugal Chiller with VFD1200T Low Pressure

    Percent Loaded

    KW

    /ton

  • Percent Loaded

    KW

    /ton

    Centrifugal Chiller without VFD1200T High Pressure

  • Centrifugal Chiller with VFD1200T High Pressure

    Percent Loaded

    KW

    /ton

  • Centrifugal Chiller Comparison

    Percent Loaded

    KW

    /ton

    Hig

    h P

    ress

    ure

    Low

    Pre

    ssur

    e

    Constant Speed Variable Speed

  • Optimizing Plant Performance

  • 30Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Primary-Secondary vs Variable Primary Flow

    • Variable primary flow plants can provide advantages over traditional primary-secondary configurations

    • Less plant space required for VPF• VPF is not conducive to CHW TES

  • 31Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Primary-Secondary Variable Flow

    Part Load Operation - 6000 Ton Plant

    Load

    3000 Ton Load3000 Ton Load58°F

    42°F54°F

    Load

    Load

    Load

    LoadVFD

    ∆P

    6000 GPM 4500 GPM

    1500 GPM

    1500 tons

    1500 tons

    OFF

    42°F

  • 32Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Primary-Secondary Variable Flow

    Effect of Low CHWR TemperatureLow ∆T Syndrome

    44°F

    52°F

    42°F54°F

    6000 GPM 7200 GPM

    1200 GPM

    Additional chiller will need to bestarted to maintain the secondaryCHWS temperature setpoint if load increases

    Loss of CHWStemp control

    1500 tons

    1500 tons

    OFF

    Load

    Load

    Load

    Load

    LoadVFD

    ∆P

    3000 Ton Load3000 Ton Load

  • 33Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Variable Primary FlowPart Load Operation - 6000 Ton Plant

    42°F

    CLOSED

    58°F

    VFD

    4500 GPMFM

    1500 tons

    1500 tons

    OFF

    Load

    Load

    Load

    Load

    Load

    ∆P

    Bypass is not needed if minimumflow through chiller is guaranteed 3000 Ton Load3000 Ton Load

  • 34Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Variable Primary FlowEffect of Low CHWR Temperature

    CLOSED

    54°F

    VFD

    6000 GPM

    1500 tons

    1500 tons

    OFF

    FM

    Load

    Load

    Load

    Load

    Load

    ∆P

    42°F

    3000 Ton Load3000 Ton Load

  • 35Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Series Arrangement

    •In applications with high lift, a series arrangement will improve overall plant performance

  • 36Inspire • Innovate • AchieveInspire • Innovate • Achieve

    85°F95°F

    Series versus ParallelWith High Lift Requirement

    40°F56°FCH-1

    CH-240°F56°F

    40°F56°F

    0.60 KW/ton

    Parallel-Parallel

  • 37Inspire • Innovate • AchieveInspire • Innovate • Achieve

    7% KW Reduction on Chillersor

    450 KW Reduction on 10,000 ton Plant

    30 feet head increase on condenser water would result in 230 KW increase in pump power

    220

    Series versus ParallelWith High Lift Requirement

    CH-1 CH-2

    95°F 85°F90°F

    0.52 KW/ton 0.59 KW/ton

    0.555 KW/ton

    Series-Counterflow

    40°F56°F 48°F

  • 38Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Series versus ParallelWith High Lift Requirement

    CH-1 CH-240°F56°F 48°F

    0.50 KW/ton 0.61 KW/ton

    7% KW Reductionor

    450 KW Reduction on 10,000 ton Plant

    0.555 KW/ton

    Series-Parallel

    85°F95°F 85°F95°F

  • 39Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Optimize Heat Rejection• Oversized cooling towers can decrease

    approach to lower chiller lift requirements and improve plant KW/ton

    • Approximately 1.5% chiller KW reduction per °F lift reduction

    Lowering CWS by from 95°F to 93°F3% Chiller KW Reduction

    or180 KW Reduction on 10,000 ton Plant

  • 40Inspire • Innovate • AchieveInspire • Innovate • Achieve

    CHW ∆TOption 1

    40°F56°F16°F

    10,000 tons15,000 gpm

    200 feet head667

    38% Pump KW Reductionor

    254 KW Reduction on 10,000 ton Plant

    Option 2

    38°F58°F20°F

    10,000 tons12,000 gpm

    146 feet head413

    CHWS TempCHWR TempCHW ∆TPlant SizeCHW FlowHeadPump KW

    87

  • 41Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Thermal Energy Storage

    • Chilled water thermal storage is a viable means of reducing peak electrical demand and increasing plant efficiency

    • Less chiller and cooling tower capacity required

    • Keep it simple!

  • Building InterfaceConsiderations

  • 43Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Building Interface Considerations

    Energy Transfer Stations Using Heat Exchangers

    • Heat exchangers designed with lower approaches will typically yield higher CHW ∆T

    • Always focus on supplying load with proper CHWS temperature

  • 44Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Building Interface Considerations

    without Heat Exchangers

    • Avoid chilled water tertiary loops• Remember cooling coil fundamentals

    • A variable speed booster pump should be used to boost differential pressure when needed

  • 45Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Building Interface Considerations

    without Heat Exchangers

    BuildingLoad Tertiary Loop

    BuildingLoad

    VFD

    Boosted Secondary

  • 46Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Control Design Issues

    • Control strategies should consider impact on complete system

    • Aim to continually optimize COP for entire system

    • Reliable industrial-grade controls are essential

    • Keep it simple

  • 47Inspire • Innovate • AchieveInspire • Innovate • Achieve

    A Case for Metering

    • Most efficiently designed systems are horribly inefficient after several years of operation

    • How can we improve operation if we don’t evaluate the metrics?

    • Calibrate regularly

  • 48Inspire • Innovate • AchieveInspire • Innovate • Achieve

    A Case for Commissioning

    • Commissioning is a systematic process of assuring that systems perform in accordance with the design intent and owner’s operational needs

    • Retro-commissioning

  • 49Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Summary• Understand parameters that affect

    chiller plant and overall system performance

    • Optimize operation through equipment selection and control sequences to deliver CHW to all loads as efficiently as possible throughout the year

    • Commission plant

  • 50 Inspire • Innovate • AchieveInspire • Innovate • Achieve

    Albert Einstein

    50

    “Everything should be as simple as possible,but no simpler”

    “Everything should be as simple as possible,but no simpler”

    “Insanity: doing the same thing over and overand expecting different results”

    “Insanity: doing the same thing over and overand expecting different results”

  • 51Inspire • Innovate • AchieveInspire • Innovate • Achieve

    For More Information

    • Join ASHRAE• ASHRAE Self Directed Learning Course

    “Fundamentals of Water System Design”

    • ASHRAE 2004 HVAC Systems and Equipment Handbook

    • ASHRAE Transactions and Journal articles• Hydronic System Design & Operation by E.G.

    Hansen