Outer tracker SiPM, A view on the thermal issues and cooling solutions Workshop on SiPM cooling for Fiber Tracker Bart Verlaat, Paolo Petagna, Antonio Pellegrino Something

Upload: karim

Post on 24-Feb-2016

31 views

Category:

Documents


0 download

DESCRIPTION

Outer tracker SiPM , A view on the thermal issues and cooling solutions. Something. Workshop on SiPM cooling for Fiber Tracker Bart Verlaat, Paolo Petagna , Antonio Pellegrino. SiPM thermal issues. - PowerPoint PPT Presentation

TRANSCRIPT

Page 1: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Outer tracker SiPM,

A view on the thermal issues and cooling solutions

Workshop on SiPM cooling for Fiber Tracker

Bart Verlaat, Paolo Petagna, Antonio Pellegrino

Something

Page 2: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

SiPM thermal issues

• -50⁰C cooling should not be the challenge, enough “commercial” options seem to be available.

• To my point of view the challenge is the overall thermal design.– No space for good insulation.– Thermal design is the driving

design factor for the mechanics.

– Sophisticated insulation methods or materials needed.

Page 3: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Cooling fluids.

• WRT cooling in inner detectors:– SiPM has a relative low heat load– SiPM has relative much space and no low mass

requirement.• Tubes can be larger

– Is radiation an issue? • Can we use more common refrigerants used in refrigeration?

• 2-phase or single phase?– Single phase has cold lines, is there space for insulation?– 2-phase can have warmer in or outlets and can be

designed with less or no insulation

Page 4: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

CO2 cooling

2PACL method Compressor cycleFr

eezi

ng li

ne

Freezing line

-50`C

-40`C

• CO2 freezes at -56 C⁰• 2PACL cycle (LHCb/Atlas/CMS) needs sub cooled liquid.

– Practical lower limit: -40 C⁰– Oil free– Cold lines

• Compressor cycle can be an option– Lower temperature possible -50 C⁰– Commercial available if oil is allowed– Oil free requires a not standard compressor – Warmer lines

Page 5: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Fluid comparison

P @ -50 ⁰C (bar)

Freezing point (⁰C) Latent heat (J/g) GWP

C3F8 0.53 -147.7 110 8830C2F6 3.7 -100 112 12200CO2 6.8 -56.6 339 1N2O 6.5 -90.8 326 298R404a 0.84 <-105 203 3300R508b 5.9 <-140 138 13400R125 0.92 -100.6 165 3500

N2O has most properties similar to CO2, except the freezing point…N2O=R744a=Laughing gas, CO2=R744

Fluids with high pressures can also be pumped in a 2PACL (oil free, more stable)

A 2PACL system is very stable and easy to control. Operation with N2O should be okay as it is similar to CO2.

Commercial choice for low temperatures

Page 6: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

R744 vs R744a

6

Similar properties, much lower freezing point

N2O, R744a

CO2, R744

Is a 2PACL with N2O an option? I have no idea about the impacts such as safety, radiation hardness etc. Thermally it looks interesting. N2O is used to foam cream, so it is not too bad I guess

Page 7: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Other commercial cooling options

• R404a in a 2-stage compressor cycle– Disadvantage: low pressure, oil.

• R508b + R404a in a cascade system. (Cascade R404a with CO2 also possible)– Disadvantage: oil

• Liquid brine– Disadvantage: Dirty fluids.

Page 8: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Known CERN cooling solutions:

• C3F8– Too low pressure 0.5 bar @ -50 C. ⁰

• C2F6– Could be a good candidate, pressure reasonable.

• 3.7 bar@-50 C⁰– Compressor seem not standard.– Expensive fluid

• FC Blends– I don’t see any reason for a blend, no pressure issue like in Atlas.

• FC liquid brines– Personally no experience, but seems like a known technology.– Cold lines

Page 9: Outer tracker  SiPM , A view on the  thermal issues and cooling solutions

Flexible vacuum insulation (Atlas IBL)

90 50 100 150 200 250 300-40

-30

-20

-10

0

10

20

30

Time

Tem

pera

ture

(C

) ⁰

50W

100W

150W

200W

250W

300W

Silicon

Cooling pipe

Dry-out at end of line

Cooldown

IBL operation

•16mm flexible vacuum below•4mm*0.5mm + 1.6x0.3mm concentric tube with CO2 •12m long•Flexible (like a cable)•-40 C inside, 18 C outside⁰ ⁰•Up to 300 watt cooling