3M™ Fire Barrier Duct Wrap 615 Product Data and Installation Instructions

Surface Burning Characteristics (ASTM E 84 for 15A, 20A, 5A) Product Flame Spread Smoke DevelopedFoil Encapsulated Blanket 0 0Blanket 0 0

Duct Wrap Fire Protection Systems for Ventilation Air Ducts

OutsideThinking

TheBox

Page 2: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

1. Product Description3M™ Fire Barrier Duct Wrap 615 is a fire resistant wrap consisting of a bio-soluble ceramic fiber blanket encapsulated with a scrim-reinforced foil. As a single layer fire resistant wrap, it has passed ISO 6944 ‘Fire Resistance Tests – Ventilation Ducts’. This non-asbestos wrap contains a safer fiber construction and installs easily because of its high flexibility and strength. With its excellent insulating capabilities, low weight and thin profile, it is an ideal choice for a duct enclosure system.

Features

• One layer wrap for ventilation ducts

• High flexibility for installation ease

• Thin and lightweight

• Nominal 6pcf density

• Foil encapsulated for blanket protection, less dust and high wrap strength

• Center stitched for ease of handling and banding location

• Safer fiber construction*

2. Applications3M™ Fire Barrier Duct Wrap 615 is an ideal fire resistive enclosure for life safety system ducts. These duct systems are in place to allow occupants to safely leave a building in fire scenario. Dampers are frequently omitted from life safety ducts. 3M™ Fire Barrier Duct Wrap 615 installed around the duct creates a fire-resistive enclosure that maintains the integrity of the duct and prevents the passage of fire from one compartment to the next. Compared to conventional gypsum enclosures, 3M™ Fire Barrier Duct Wrap 615 is lighter weight, requires less space and typically has lower installation costs. It is a proven alternative to a 1- or 2-hour fire resistant rated shaft enclosure in protecting ventilation ducts as tested per ISO 6944-85 ‘Fire Resistance Tests – Ventilation Ducts’. Some smoke-control methods commonly used to achieve life safety objectives are:

• Mechanical Smoke Exhaust

• Stairwell Pressurization

• Ventilated Vestibules

• Zoned Smoke Control

• Elevator Smoke Control

• Smokeproof Enclosures with Mechanical Ventilation

• Engineered Ventilation Systems

Other types of duct assemblies that often require fire-resistive enclosure are:

• Dryer Exhaust Vents

• Toilet Exhaust Vents

3M™ Fire Barrier 1000 N/S, 1003 S/L, and 2000+ Silicone Sealant is used in combination with 3M™ Fire Barrier Duct Wrap 615 to firestop the duct when the duct penetrates fire rated floors and walls.

3. AvailabilityProduct Unit Size Units/ ctn. Wt./ ctn.

98-0400-5551-33M™ Fire Barrier Duct Wrap 615 Roll 1.5" x 24" x 25'

(38mm x 61cm x 762cm) 1 39.3 lbs. 17.8 kg

98-0400-5552-13M™ Fire Barrier Duct Wrap 615 Roll 1.5" x 48" x 25'

(38mm x 122cm x 762cm) 1 78.6 lbs. 35.7 kg

4. Typical Physical PropertiesBlanket Color Weight Per Area

White .75 lb/ft2 (3.66 kg/m2)

5. Performance3M™ Fire Barrier Duct Wrap 615 has been tested in accordance with the following:

ISO 6944, ASTM E 84, ULC/CAN S 102, ASTM E 814, UL 1479,

ASTM C 1338, ASTM C 411, ASTM C 518

Surface Burning Characteristics Test Method Flame Spread Smoke DevelopedFoil Encapsulated BlanketASTM E84 < 25 < 50

CAN/ULC S102-03 < 25 < 50

Thermal ConductivityTemperature btu•in./(hr.•ft2•F) W/m2•K500˚F (260˚C) 0.48 0.07

1000˚F (537˚C) 0.97 0.14

1500˚F (815˚C) 1.57 0.23

1800˚F (982˚C) 1.98 0.29

2000˚F (1093˚C) 2.23 0.33

Linear Shrinkage24 Hr @ 2012°F (1100°C)

1.2%

* Has been demonstrated to be soluble in the lungs according to EU guidelines 97/69/EC, for biopersistence.2

Page 3: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Ventilation Air Duct ListingsFire

Resistive Rating

Enclosure System Duct System

Through- Penetration

SystemListing Agency

1 or 2 Hours

1 layer of 3M™ Fire

Barrier Duct Wrap 615, 3" (76mm).

perimeter and longitudinal

overlaps

V-27 W-L-7180, W-J-7104

UL

3MU/FRD-120-15 3MU/PH 60-03 3MU/PV 120-23 3MU/PV 120-25

Intertek / (OPL)

This is only a partial list of design listings that utilized 3M™ Fire Barrier Duct Wrap 615. Please visit www.3M.com/firestop for a current list of third-party design listings.

For technical data and properties of 3M™ Fire Barrier 1000 N/S and 1000 N/S, 1003 S/L and 2000+ Silicone Sealants see separate product data sheets available from your 3M representative or go to www.3M.com/firestop.

Code Compliance

3M™ Fire Barrier Duct Wrap 615 can be used to comply with requirements of the following codes:

• NFPA 92A Standard for Smoke-Control System Utilizing Barriers and Pressure Differences, 2006 Edition – Section 6.6.2

• NFPA 92B Standard for Smoke Management Systems in Malls, Atria, and Large Spaces, 2005 Edition – Section 7.5.2

• NFPA 101® Life Safety Code®, 2006 Edition – Section(s) 8.6.7, 18.7.7

• International Mechanical Code®, 2006 Edition – Section 513.10.2

• International Building Code®, 2006 Edition – Section 909.10.2

This is only a partial list of code compliance. For the latest code and approval information go to www.3M.com/firestop or speak to your authorized 3M distributor or sales representative at (800) 328-1687.

6. Installation Techniques3M™ Fire Barrier Duct Wrap 615 system should be installed in accordance with the following installation instructions.

Material and Equipment

• 3M™ Fire Barrier Duct Wrap 615 Blanket, 1-1/2" (38mm) thick, 24" (61cm) or 48" (122cm) wide, 25' (762cm) standard length. The 48" (122cm) wide blanket helps to minimize waste.

• Aluminum foil tape.

• Minimum 1/2" (12.7mm) wide filament tape.

• Carbon steel or stainless steel banding material, minimum 1/2" (12.7mm) wide, minimum 0.015" (0.38mm) thick, with steel banding clips.

• Hand banding tensioner, crimping tool, and banding cutter.

• Minimum 12 gauge copper-coated steel insulation pins; galvanized steel speed clips, minimum 1-1/2" (38mm) square or 1-1/2" (38mm) diameter round, or equivalent sized insulated cup-head pins; capacitor discharge stud gun.

• Scrap pieces of 3M™ Fire Barrier Duct Wrap 615 Blanket.

• 3M™ Fire Barrier 1000 N/S, 1003 S/L and 2000+ Silicone Sealant.

Storage

The 3M™ Fire Barrier Duct Wrap 615 and 3M™ Fire Barrier 1000 N/S, 1003 S/L and 2000+ Silicone Sealants must be stored in a dry warehouse environment. Pallets should not be stacked.

Preparatory Work

3M™ Fire Barrier Duct Wrap 615 is installed with common tools, such as knives, banders and capacitor discharge guns for applying insulation pins. In order to install the duct firestop system, the surfaces of all the openings and penetrating items need to be clean, dry, frost free and free of dust.

Method

To minimize waste, 3M™ Fire Barrier Duct Wrap 615 material should be rolled out tautly before measuring. General instructions for installing the 3M™ Fire Barrier Duct Wrap 615 include a one-layer wrap construction applied directly to the duct. The 3M™ Fire Barrier Duct Wrap 615 Blanket is wrapped around the perimeter of the duct and is cut to a length to overlap itself not less than 3" (76mm). The overlap made by adjacent blankets forms the “longitudinal” overlap. Aluminum foil tape is used to seal all cut edges of the blanket and any tears in the foil scrim.

3

Page 4: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

There are three (3) approved installation techniques for installing the 3M™ Fire Barrier Duct Wrap 615

(See Figures 1A–1D and Figures 2A–2E):

1. Telescoping 3" (76mm) Overlap Wrap

With the telescoping overlap wrap method, each blanket overlaps one adjacent blanket and each blanket has one edge exposed and one edge covered by the next blanket as shown in Figure 1A and 1B. The visible edges of the perimeter overlaps all point in the same direction.

2. Checkerboard 3" (76mm) Overlap Wrap

With the 3" (76mm) checkerboard overlap wrap method, blankets with both edges exposed alternate with blankets with covered edges, as shown in Figure 1C. The visible edges of the perimeter overlaps alternate their directions and appear on every other blanket.

3. Butt Joint With Collar

With the butt joint and collar method, adjacent blankets are butted tightly together and a 6" (152mm) wide collar of 3M™ Fire Barrier Duct Wrap is centered over the joint, overlapping each blanket by 3" (76mm) minimum as shown in Figure 1D.

In all three overlap techniques, the perimeter overlap can occur at any location on the duct. The blanket is mechanically attached to the duct by steel banding or by welded insulation pins and clips for all three installation methods listed above.

For Banding Only (See Figures 1A–1D)

Filament tape can be used to temporarily hold the blanket in place until the banding is applied. The steel banding is applied around the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers. The banding is placed around the material and tightened so as to sufficiently hold the 3M™ Fire Barrier Duct Wrap 615 in place against the duct, compressing the foil but not cutting the foil.

Additional Pinning to Prevent Sagging of the Wrap

For ducts 24" (60cm) and larger in width, additional pins are needed to support the blanket on the bottom horizontal surface and on the outside face of a vertical duct run. Space pins a maximum of 10-1/2" (26.7cm) apart in the direction of the blanket width, and a maximum of 12" (30cm) apart in the direction of the blanket length. Refer to the following paragraph for more information on Mechanical Fastening with Pins.

For Mechanical Fastening with Pins Only

(See Figure 2A–2E)

Insulation pins are welded to the duct in the centers of the overlaps a minimum of 1-1/2" (38mm) from each edge of the blanket, and spaced a maximum of 10-1/2" (26.7cm) on center along perimeter overlap, and a maximum of 10-1/2" (26.7mm) on center along longitudinal overlaps. The blanket is impaled over the pins and held in place by galvanized speed clips. Insulation pins that extend beyond the blanket wrap shall be turned down to eliminate sharp points. Insulated cup-head pins can be used at the same spacing requirements of the insulation pins.

NOTE: Support hangar systems do not need to be wrapped provided the hangar rods are at least a minimum of 3/8" (9.53mm) diameter and spaced a maximum of 60" (152cm) on center along the length of the duct. Use a minimum 1-1/2" x 1-1/2" x 1/4" (38mm x 38mm x 6.35mm) steel angle steel support channel or SMACNA equivalent support system. For ducts greater than 1440 in2 and less than 2040 in2, the trapeze requirements increase to a minimum of 2" x 2" x 1/4".

Penetrations (See Figures 3A–3F)

When the duct penetrates a fire rated wall, ceiling or floor, an approved firestop system must be employed. Figures 3A–3F illustrate typical conditions.

To firestop the duct where it passes through rated assemblies, follow the installation parameters detailed in the Intertek Testing Services (ITS) or Underwriter’s Laboratories (UL) design listings.

Other Applications

Refer to Figures 5–11 for additional typical conditions.

4

Page 5: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

7. MaintenanceNo maintenance is required when installed in accordance with the 3M Installation Instructions. Once installed, if any section of the 3M™ Fire Barrier Duct Wrap 615 is damaged so that the blanket is damaged, the following procedures will apply:

• The damaged section should be removed by cutting the steel banding or removing the clips holding it in place.

• A new section of the same dimension should be cut from a roll of 3M™ Fire Barrier Duct Wrap 615, either 24" (60.9cm) or 48" (121cm) wide.

• The new section should be placed and fitted, ensuring the same overlap that existed previously.

• The steel banding should be placed around the material and tensioned so as to sufficiently hold the 3M™ Fire Barrier Duct Wrap 615 in place.

• If the blanket has not been damaged but the foil has ripped, seal the rips with aluminum foil tape.

8. Purchase Information3M Fire Barrier products are available through a network of nationwide distributors. For information on where to buy, go to www.3M.com/firestop.

9. Safe Handling InformationConsult Material Safety Data Sheet prior to handling and disposing of 3M™ Fire Barrier Duct Wrap 615.

5

Page 6: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Figure 1A—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Telescoping Technique with Banding

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. Steel Banding 1/2" (13mm) Wide Minimum Typical

3. 3" (76mm) Minimum Longitudinal Overlap

4. 3" (76mm) Minimum Perimeter Overlap

System integrity is limited by quality of installation.

6

NOTES Ducts >24" wide require pinning on the bottom side. Pinning may be omitted by banding max. 5-1/4" O.C. Ensure that material is held tightly to the duct.

Page 7: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Figure 1B—Telescoping Overlap Wrap OptionCross Sectional View

Figure 1C—Checkerboard Overlap Wrap OptionCross Sectional View

Figure 1D—Butt Joint With Collar OptionCross Sectional View

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. Steel Banding 1/2" (13mm) Wide Minimum Typical

3. 3" (76mm) Minimum Longitudinal Overlap

4. 3" (76mm) Minimum Perimeter Overlap

5. 6" (152mm) Wide Collar Made From 3M™ Fire Barrier Duct Wrap 615

6. Firmly Butted Joint

System integrity is limited by quality of installation.

7

Page 8: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Figure 2A —3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Telescoping Wrap Technique With Weld Pins

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. 1-1/2" Square (38mm) or 1-1/2" Diameter (38mm) Galvanized Speed Clips Over 12 Gauge Steel Impaling Pins

3. 3" (76mm) Minimum Longitudinal Overlap

4. 3" (76mm) Minimum Perimeter Overlap

System integrity is limited by quality of installation.

8

Page 9: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Figure 2B—Telescoping Overlap Wrap OptionCross Sectional View

Figure 2C—Checkerboard Overlap Wrap OptionCross Sectional View

Figure 2D—Butt Joint With Collar OptionCross Sectional View

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. 1-1/2" Square (38mm) or 1-1/2" Diameter (38mm) Galvanized Speed Clips Over 12 Gauge Steel Impaling Pins

3. 3" (76mm) Minimum Longitudinal Overlap

4. 3" (76mm) Minimum Perimeter Overlap

5. 6" (152mm) Wide Collar Made From 3M™ Fire Barrier Duct Wrap 615

6. Firmly Butted Joint

System integrity is limited by quality of installation.

9

Page 10: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 2E—Pinning TechniquesIsometric View

1. Duct

2. 3M™ Fire Barrier Duct Wrap 615

3. Impaling Pin

4. Speed Clip

5. Insulated Cup Head Pin

System integrity is limited by quality of installation.

10

NOTES

After speed clips are installed over impaling pin, cut off excess pin length or bend pins flush.

Impaling pins shall be 12 gauge copper-coated steel.

Typical Impaling Pin Length: Min. 4-1/2"

Typical Impaling Pin Spacing: Max. 10-1/2" O.C. along duct length. Max. 12" O.C. across duct width.

A cup head pin length shall be chosen that ensures the 3M™ Fire Barrier Duct Wrap 615 material is held tightly to the duct.

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Page 11: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3A—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration Systems Concrete Floor or Wall Assembly

Firestopped to Bare Duct

1. Concrete Floor/Ceiling or Wall Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D.

3M™ Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant For Wall Assembly Apply Sealant at Both Faces of Wall. For Floor Assembly, Sealant Required at Top of Floor Only. 3M™ Fire Barrier 1003 S/L Not Suitable For Wall Applications.

3E. 24" Wide Collar (1 layer of 3M™ Fire Barrier Duct Wrap 615)

System integrity is limited by quality of installation.

11

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 12: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3B—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration SystemsConcrete Floor or Wall Assembly

Firestopped to Duct Wrap Envelope

12

1. Concrete Floor/Ceiling or Wall Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D.

3M™ Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant For Wall Assembly Apply Sealant at Both Faces of Wall. For Floor Assembly, Sealant Required at Top of Floor Only. 3M™ Fire Barrier 1003 S/L Not Suitable For Wall Applications.

3E. 24" Wide Collar (1 layer of 3M™ Fire Barrier Duct Wrap 615)

System integrity is limited by quality of installation.

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 13: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3C—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration SystemsGypsum Wallboard Assembly

13

1. Gypsum Wall Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D. 3M™ Fire Barrier 1000 N/S or 2000+ Silicone Sealant

3E. 24" Wide Collar (1 layer of 3M™ Fire Barrier Duct Wrap 615)

System integrity is limited by quality of installation.

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 14: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3D—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration SystemsShaftwall Assembly

14

1. Gypsum Wall Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D. 3M™ Fire Barrier 1000 N/S or 2000+ Silicone Sealant

3E. 24" Wide Collar (1 layer of 3M™ Fire Barrier Duct Wrap 615)

System integrity is limited by quality of installation.

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 15: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3E—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration SystemsFire Rated Wood/Gypsum—Floor/Ceiling Assembly

15

1. Floor—Ceiling Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D. 3M™ Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant

3E. 24" Wide Collar (1 layer of 3M™ Fire Barrier Duct Wrap 615)

System integrity is limited by quality of installation.

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 16: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 3F—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Through-Penetration SystemsFire Rated Concrete Roof Assembly

16

1. Roof Assembly

2. Duct

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D. 3M™ Fire Barrier 1000 N/S, 1003 S/L or 2000+ Silicone Sealant

3E. 24" Wide Collar (1 Layer of 3M™ Fire Barrier Duct Wrap 615)

4. Roof Flashing

5. Vent Flashing

System integrity is limited by quality of installation.

NOTES

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 1440 in2 the through-penetration designs do not require collars.

Page 17: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 4—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Suggested Three Sided Wrap

17

1. Concrete Slab

2. One Layer 3M™ Fire Barrier Duct Wrap 615

3. Concrete Fasteners — Minimum 1/4" (6mm) Diameter Steel Concrete Anchors

4. 1/8" (3mm) Thick x 2"–3" (50mm–76mm) Wide Bar Stock Perforated 12" (30cm) O.C.

5. Duct

6. Banding

7. Banding Clips

System integrity is limited by quality of installation.

Page 18: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 5—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Suggested Two Sided Wrap

18

1. Concrete Slab

2. One Layer 3M™ Fire Barrier Duct Wrap 615

3. Concrete Fasteners — Minimum 1/4" (6mm) Diameter Steel Concrete Anchors

4. 1/8" (3mm) Thick x 2"–3" (50mm–76mm) Wide Bar Stock Perforated 12" (30cm) O.C.

5. Duct

6. Banding

7. Banding Clips

System integrity is limited by quality of installation.

Page 19: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 6—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Suggested 90° Shaft Wall Transition

19

1. Gypsum Shaft Enclosure

2. One Layer 3M™ Fire Barrier Duct Wrap 615

3. 3" (76mm) Minimum Overlap

4. Steel Bands and Clips

5. 1/4" Steel Toggle Bolts

6. Bar Stock 2" Wide 1/8" Thick Perforated 12" O.C.

7. Packing Material

8. 3M™ Fire Barrier 1000 N/S or 2000+ Silicone Sealant

System integrity is limited by quality of installation.

NOTES

This scenario depicts penetration into a rated shaft enclosure and the firestop system is asymmetric. For this reason, the fire protective characteristic of this system is relevant only to fires existing external to the shaft construction. It does not apply to fires internal to the shaft enclosure.

Page 20: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 7—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Suggested Horizontal Shaft Wall Transition

1. Shaft Enclosure

2. Shaft Clearance, per Building Code (If Required)

3. Duct

4. One Layer 3M™ Fire Barrier Duct Wrap 615

5. Steel Bands and Clips

6. 2" x 1/8" Thick Bar Stock Perforated 12" O.C.

7. Toggle Bolts

8. Concrete Floor/Ceiling

9. Concrete Anchor with Washer

System integrity is limited by quality of installation.

20

Page 21: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Figure 8—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

Rectangular/Square Duct 1 or 2 Hour Suggested Shaft Wall Termination

1. Gypsum Shaftwall Assembly

2. Duct— Rectangular/Spiral Wound Round

3A. One Layer 3M™ Fire Barrier Duct Wrap 615

3B. Banding or Pinning

3C. Packing Material

3D. 3M™ Fire Barrier 1000 N/S or 2000+ Silicone Sealant

3E. 24" Wide Collar (1 Layer 3M™ Fire Barrier Duct Wrap 615) (If Applicable)

4. Retaining Angles (If Applicable)

System integrity is limited by quality of installation.

21

NOTES

This scenario depicts penetration into a rated shaft enclosure and the firestop system is asymmetric. For this reason, the fire protective characteristic of this system is relevant only to fires existing external to the shaft construction. It does not apply to fires internal to the shaft enclosure.

Individual Intertek (OPL) Fire Penetration Seal Design Listing are available from the Intertek Directory of Listed Products

Underwriters Laboratories Inc. (UL) Through-Penetration Firestop Systems are available from the UL Online Certifications Directory

Systems are also available at 3M.com/firestop

For duct sizes ≥ 1440 in2 the through-penetration designs include retaining angles.

For duct sizes ≤ 720 in2 the through-penetration designs do not require collars.

Page 22: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

22

Figure 9A—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Round Duct Elbow Configuration Installation Recommendation

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. Round Duct

3. 3" (76mm) Minimum Overlap

4. 1/2" Steel Bands

System integrity is limited by quality of installation.Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Page 23: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

23

1. Perimeter

2. 3" Overlap

3. Hole Cut Off—Center

System integrity is limited by quality of installation.

Figure 9B—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Rectangle Duct Elbow Installation Recommendation

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

NOTES

Place overlap on opposite side of horizontal pattern.

Page 24: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

24

Figure 9C—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Banding Pattern Suggested Installation

1. Duct

2. One Layer 3M™ Fire Barrier Duct Wrap 615

3. 3" (76mm) Minimum Overlap

4. 1/2" Steel Bands

5. Chalker bands added on all sides to secure wrap when 10-1/2" spacing cannot be maintained

System integrity is limited by quality of installation.Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Page 25: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

25

Figure 9D—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

1 or 2 Hour Vertical Duct Runs Installation Recommendation

1. One Layer 3M™ Fire Barrier Duct Wrap 615

2. 1-1/2" Square or 1-1/2" Round Galvanized Speed Clips Over 12 Gauge Galvanized Steel Impaling Pins

3. 3" (76mm) Minimum Longitudinal Overlap (Not Shown)

4. 3" (76mm) Minimum Perimeter Overlap

5. 1/2" Steel Bands

System integrity is limited by quality of installation.Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Page 26: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

26

Figure 10—3M™ Fire Barrier Duct Wrap 615Fire Rated Ductwork

Hanging Support Details

THIS INFORMATION SHOULD BE PROVIDED TO THE MECHANICAL CONTRACTOR FOR USE IN LAYING OUT THEIR DUCT HANGER LOCATIONS.

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

NOTES

In order to facilitate the application of 3M™ Fire Barrier Duct Wrap 615 to the installed ductwork, so the rods trapeze hangers are outside the wrap envelope, the carbon steel thread hanging support rods shall be:

1. Installed to provide a 3-1/2" to 4-1/2" clearance between the rod and the side of the duct.

2. The rods should be cut 2-1/2" longer than normally required in order to permit the cradles to be reinstalled onto the threaded rods after the duct has been wrapped.

Page 27: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

27

1. All Thread Rod

2. Trapeze Hanger

3. 3M™ Fire Barrier Duct Wrap 615

4. 1/2" Crown of CP 25WB+ Caulk

System integrity is limited by quality of installation.

Figure 11—3M™ Fire Barrier Duct Wrap 615Ventilation Air Duct Systems

Suggested Wrap Around Trapeze Hanger & Rod

NOTE: CREATE OPENING IN WRAP SO IT CLOSELY FOLLOWS THE CONTOUR OF THE PENETRATING TRAPEZE

Consult current independent testing laboratories (UL, Intertek) for systems or design details.

Page 28: OutsideBoxmultimedia.3m.com/mws/media/518116O/fire-barrier-duct-wrap-615-product-data...the duct 1-1/2" (38mm) from each edge of the blanket, and maximum 10-1/2" (26.7cm) centers

Building and Commercial Services Division 3M Center 223-2S-24St. Paul, MN 55144-1000 Phone 800-328-1687Fax 888-362-2737 www.3M.com/firestop

Warranty and Limited RemedyThis product will be free from defects in material and manufacture for a period of ninety (90) days from date of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OR MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user's method of application. If this 3M product is proved to be defective within the warranty period stated above, your exclusive remedy and 3M's sole obligations shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the product.

Limitation of LiabilityExcept where prohibited by law, 3M will not be liable for any loss or damages arising from the use of this 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.

Please recycle. Printed in U.S.A© 3M 2008. All rights reserved.98-0213-4371-4

3M is a trademark of 3M Company. All other trademarks are the property of their respective owners.

Warnock Hersey

INTERTEK

CM

C US

OM

EGA POIN

T

LABORATORIE

SC US

DUCT WRAP MATERIALS FOR USE IN THROUGH-PENETRATION

FIRESTOP SYSTEMS SEE UL DIRECTORY OF PRODUCTS

CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY

90G9

BATTS AND BLANKETS FOR USE IN FIRE RESISTIVE DUCT ASSEMBLIES

SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND SEE UL FIRE RESISTANCE DIRECTORY

90G9