NEW Product Data Sheet PDS 106-880.A01 February, 2005 OCX 8800 Two separate 4-20 mA signals are used as outputs for this transmitter. The two independent 4-20mA signals are used for the oxygen measurement and combustibles measurement. They are fully field-scalable to each processes requirement. The OCX comes with a NEMA 4 rating, but can be configured for hazardous area locations. The hazardous area ratings are CSA/FM Class 1, Zone 1 for North America and ATEX II 2 G EExd for the European community. The OCX also has Plantweb ® capability with the HART protocol accessible via a Model 375 Handheld Communicator or through a PC-based system using AMS software. Emerson Process Management's Plantweb field-based architecture allows technicians to view all diagnostic and operational parameters from any location where an on-line PC is running with AMS. This reduces both commissioning/start-up time as well as down-time due to trouble shooting the analyzer. The new vacuum fluorescent display is easier to see than an LCD and also allows for easy set-up and diagnostics without a Model 375 Communicator. The OCX 8800 also has a configurable relay output for alarms. The sensors are close-coupled to the process for minimal sample handling requirements. An eductor draws a sample past the filter in the sample block and past the sensors then returns it to the process. The sample block filter is easily maintained and accessible right at the OCX flange. Optional in situ filters and sample tube blow back are available for processes with particulate. Dilution air is added in the combustible sensor chamber to maintain a true combustibles measurement even in the absence of oxygen in the process. This feature allows measurements to be made while certain upset conditions exist such as burner fouling, process tube leaks, major variations in fuel BTU values and loss of flame. Enhanced Design of the Oxygen/ Combustibles Transmitter for Combustion Flue Gas Analysis Emerson has taken the proven performance of the Rosemount Analytical OCX 4400 and added a new combustibles sensor design and sensor housing up- grades to enhance the reliability of these measurements. The new sensor housing along with the new electronics design makes the OCX 8800 the most dependable oxygen/combustibles transmitter on the market and is so complete that it truly is an entirely new instrument. The OCX 8800 takes an easier, original rugged design of the OCX 4400 and adds a more stable sensor, electronics and software package. The time-tested and world- renowned zirconium oxide sensor used in the Oxymitter™ is still the basis for the oxygen measurement. This, coupled with the new patented combustibles sensor can detect oxygen and combustibles concentrations in flue gases with temperatures up to 2600 o F (1427 o C). Typical applications include: refinery process heaters petrochemical reactor furnaces small package hot water and steam boilers inert process atmospheres gas, oil and some coal boilers Visit our website at www.raihome.com On-line ordering available. Oxygen/Combustibles Transmitter OCX FEATURES Both oxygen and combustibles measurements in a single, easy-to-install transmitter design Integral- or remote-mounted electronics options Explosion-proof and weather-proof ratings (ATEX certification for European installations) New universal power supply Fully field-repairable HART ® , AMS/Plantweb ® compatible Simplified installation no electronics box, probe cable or conduit universal power supply provides automatic line voltage selection adaptable to any oxygen/combustibles installation

Upload: hatu

Post on 15-Aug-2018

231 views

Category:

Documents


0 download

TRANSCRIPT

NEWProduct Data SheetPDS 106-880.A01February, 2005 OCX 8800

Two separate 4-20 mA signals are used as outputs forthis transmitter. The two independent 4-20mA signalsare used for the oxygen measurement and combustiblesmeasurement. They are fully field-scalable to eachprocesses requirement. The OCX comes with a NEMA 4rating, but can be configured for hazardous area locations.The hazardous area ratings are CSA/FM Class 1, Zone 1for North America and ATEX II 2 G EExd for the Europeancommunity.

The OCX also has Plantweb® capability with the HARTprotocol accessible via a Model 375 HandheldCommunicator or through a PC-based system usingAMS software. Emerson Process Management'sPlantweb field-based architecture allows technicians toview all diagnostic and operational parameters from anylocation where an on-line PC is running with AMS. Thisreduces both commissioning/start-up time as well asdown-time due to trouble shooting the analyzer. The newvacuum fluorescent display is easier to see than an LCDand also allows for easy set-up and diagnostics without aModel 375 Communicator. The OCX 8800 also has aconfigurable relay output for alarms.

The sensors are close-coupled to the process for minimalsample handling requirements. An eductor draws asample past the filter in the sample block and past thesensors then returns it to the process. The sample blockfilter is easily maintained and accessible right at the OCXflange. Optional in situ filters and sample tube blow backare available for processes with particulate. Dilution air isadded in the combustible sensor chamber to maintain atrue combustibles measurement even in the absence ofoxygen in the process. This feature allows measurementsto be made while certain upset conditions exist such asburner fouling, process tube leaks, major variations in fuelBTU values and loss of flame.

Enhanced Design of the Oxygen/Combustibles Transmitter forCombustion Flue Gas AnalysisEmerson has taken the proven performance of theRosemount Analytical OCX 4400 and added a newcombustibles sensor design and sensor housing up-grades to enhance the reliability of these measurements.The new sensor housing along with the new electronicsdesign makes the OCX 8800 the most dependableoxygen/combustibles transmitter on the market and isso complete that it truly is an entirely new instrument.

The OCX 8800 takes an easier, original rugged design ofthe OCX 4400 and adds a more stable sensor, electronicsand software package. The time-tested and world-renowned zirconium oxide sensor used in the Oxymitter™is still the basis for the oxygen measurement. This,coupled with the new patented combustibles sensor candetect oxygen and combustibles concentrations in fluegases with temperatures up to 2600oF (1427oC). Typicalapplications include:

refinery process heaterspetrochemical reactor furnacessmall package hot water and steam boilersinert process atmospheresgas, oil and some coal boilers

Visit our website at www.raihome.comOn-line ordering available.

Oxygen/Combustibles Transmitter

OCX FEATURES• Both oxygen and combustibles measurements

in a single, easy-to-install transmitter design• Integral- or remote-mounted electronics options• Explosion-proof and weather-proof ratings

(ATEX certification for European installations)• New universal power supply• Fully field-repairable• HART®, AMS/Plantweb® compatible• Simplified installation

– no electronics box, probe cable or conduit– universal power supply provides automatic

line voltage selection– adaptable to any oxygen/combustibles

installation

OCX 8800 OXYGEN/COMBUSTIBLES TRANSMITTER FEATURES AND BENEFITS

OCX 8800 Housing and Electronics Stack Electronics Housing with Local Operator Interface

Features Benefits

HART communications All information from analyzer is updated constantly andprovided to the operator or technician. Low cost to maintain

Rapid, accurate and reliable measurement of excess Provides inputs for significant fuel savings which normally payoxygen and combustibles for the analyzer in less than one year

Integrated sensors and electronics simplifies installation Eliminates cost of mounting separate electronics as well as(optional) cabling and conduit between sensors and electronics

Temperature-controlled combustible sensor Minimize drift and better sensitivity

Field-replaceable sensors, temperature elements and Ease-of-maintenanceheaters

Suitable for process temperatures up to 2600°F (1427°C) Suitable for use in most combustion applications

Probe material of construction 316 LSS, Inconel 600 and High resistance to corrosion and high temperaturesceramic

Optional in situ filter for high particulate installation Improved sample handling – block temperature control

New robust combustibles sensor Longer life and higher resistance to sulphur

Automatic line voltage selections Automatically selects from 90 to 240 VAC and 50/60 Hz.without configuration or set-up

THE OCX 8800 TRANSMITTER IS COMPLETELY FIELD-REPAIRABLE

Page 2

The electronics can be attached to the sensor housingor separate to provide a convenient location for theelectronics and operator interface for integral mountedinstallations. We have built the oxygen/combustiblesmeasurement around the time-proven Oxymitter oxygencell and added a combustibles measurement with dilutionair. This means the combustibles measurement is validwith or without oxygen in the flue gas stream and isextremely useful in reducing conditions. This situation isideal for optimization of your fuel/air ratio or indication ofyour combustion process from a safety standpoint.

The OCX 8800 is fully field-repairable. The probe'sdesign provides convenient access to internal probecomponents and electronics so technicians can servicethe unit in-house. The sensing cell and heater/thermo-couple are fully field-replaceable. We offer sampleprobes in different materials and lengths up to 9 feet forflue gas temperatures up to 2600°F (1427°C).

New hardware design includes:• Vacuum fluorescence Local Operator Interface (LOI)• New combustibles chamber includes:

– Rugged sulfur-resistant catalytic bead sensor(patented design)

– Improved temperature control– Improved heater design

• Optional in-situ filter for high-particulate applications*• Cold junction compensation in sensor housing reduces

wiring costs• Completely redesigned electronic card stack• Line voltage filter

New software features Include:• LOI safety lock-out• Improved sensor and sample block temperature

stabilization• Line voltage diagnostics• Calibration check feature• Calibration abort feature• Easy-to-follow menu tree• Backward compatibility to upgrade your existing

OCX 4400

* Consult factory for applicability to processes.

SPECIFICATIONS 1

OCX 8800 OXYGEN/COMB TRANSMITTERNet O2 Range: 0-1% to 0-40% O2

Fully field-selectable via HART or LOICombustibles: 0-1000 ppm to 0-5%

Fully field-selectable via HART or LOIAccuracy: Oxygen : ± .75% of reading or .05% O2,

whichever is greater Combustibles: ± 2% F.S.System Response to Test Gas: O2: 10 sec T90 Combustibles: 25 sec T90Temperature Limits: Process: 32° to 2600°F (0° to 1427°C)SensorsHousing: -40° to 212°F (-40° to 100°C)ElectronicsHousing: -40° to 149°F (-40° to 65°C)Probe Lengths, Nominal and Approximate ShippingWeights: 18 in (457 mm) package: 54 pounds (24.5 kg) 3 foot (0.91 m) package: 55 pounds (24.5 kg) 6 foot (1.83 m) package: 57 pounds (26 kg) 9 foot (2.74 m) package: 59 pounds (26.8 kg)Mounting and Mounting Position: Sensors: Flange Electronics: Wall/PipeMaterials: Probes: 316L stainless steel – 1300°F (704°C)

Inconel 600 – 1832°F (1000°C)Ceramic – 2600°F (1427°C)

Enclosures: Low-copper aluminumCalibration: Semi-automatic or automaticCalibration Gas mixtures recommended:

0.4% O2, balance N2

8% O2, balance N2

1000 ppm CO, balance air

Calibration GasFlow: 7 scfh (0.5 l/m)

Reference Air: 2 scfh (1 l/m), clean, dry, instrument-quality air (20.95% O2), regulated to35 psi (238 kPa)

Eductor Air: 5 scfh (2.5 l/m), clean, dry,instrument-quality air (20.95% O2),regulated to 35 psi (238 kPa)

Dilution Air: .1 scfh (0.5 l/m), clean, dry,instrument-quality air (20.95% O2),regulated to 35 psi (238 kPa)

Blowback Air: Clean, dry, instrument quality air(Optional) (20.95% O2 ) regulated to 55 psi

(374 kPa)SensorsHousing: NEMA 4, IP55

Two 3/4" – 14 NPT conduit portsElectronicsHousing: NEMA 4, IP66

Two 3/4" – 14 NPT conduit portsElectrical Noise: EN 61326-1

EN 61000-3-2EN 61000-3-3

Optional HazardousArea Certifications: CSA/FM Class 1, Zone 1

Ex D IIB + H2 T3/T6AEx D IIB + H2 T3/T6ATEX II 2 G EEx D IIB + H2 T3/T6

The OCX 8800 complies with theEuropean Union PED 97/23/ECDirective by virtue of SEP.(Split architecture only)

Line Voltage: 100-240 VAC ± 10% 48-62 HzNo switches or jumpers required3/4” – 14 NPT conduit port

Isolated Output: O2, 4-20mAdc, 950 ohm maximumwith HART capability COMB,4-20mAdc, 950 ohm maximum

Alarm output relay: dry contact, 30mA and 30 VDCcapacity

Logic Signals: SPA HART ALARM module(optional) Low O2 alarm

High Comb alarmCalibration statusUnit failure

Power Consumption Limits: Power Consumption of Heaters: 750 W nominal maximum Power Consumption of Electronics: 50 W nominal maximum

1 All static performance characteristics are with operating variables constant.Specifications subject to change without notice.

Emerson Process Management has satisfied allobligations coming from the European Legislationto harmonize the product requirements in Europe.

Communicate with the OCX 8800 almost anywhere via the HART protocol

Page 3

OUTLINE DIMENSIONS FOR OCX 8800 OXYGEN/COMBUSTIBLE TRANSMITTER

Table I. Mounting PlateDimensions Dia. In. (mm) ANSI DIN

Flange (x) 6.00 7.5(153) (190)

StudSize 5/8" – 11 M12 X 1.75

4 Studs Eq. 4.75 BC 5.12 BCSp. on B.C.

Table II. Removal/lnstallatlon

Dim "A" Dim "B"Probe Insertion RemovalLength Depth Envelope18 in. (457 mm) 18.00 34.00Probes (457) (864)

3 ft. (0.91 m) 36.00 52.00Probes (914) (1321)

6ft.(1.83m) 72.00 88.00Probes (1829) (2235)

9ft. (2.74 m) 108.00 124.00Probes (2743) (3150)

Page 4

B A

Electronics Housing

Sensor Housing

Mounting Options

Page 5

BOTTOM VIEW OF THE OCX 8800 INTEGRAL CONFIGURATION

INTERNAL LOCAL OPERATION INTERFACE (LOI)HAS STANDARD ORIENTATION AS SHOWN ANDCAN BE ROTATED FOR DESIRED ORIENTATION(90° INCREMENTS) FOR VIEWING THROUGHTHE WINDOW.REFER TO MANUAL FOR DETAILS.

Page 6

Model Description OCX88A Oxygen /Combustibles Transmitter

Oxygen/Combustibles Transmitter Instruction Book

Level 1 Probe Length and Material 00 No probe or exhaust tube 11 18" (457mm) 316 SS, up to 1300°F (704°C) 12 3' (0.91m) 316 SS, up to 1300°F (704°C) 13 6' (1.83m) 316 SS, up to 1300°F (704°C) 14 9' (2.74m) 316 SS, up to 1300°F (704°C) 21 18" (457mm) Inconel 600, up to 1832°F (1000°C) 22 3' (0.91m) Inconel 600, up to 1832°F (1000°C) 23 6' (1.83m) Inconel 600, up to 1832°F (1000°C) 24 9' (2.74m) Inconel 600, up to 1832°F (1000°C) 31 18" (457mm) Ceramic, up to 2600°F (1426°C) 32 3' (0.91m) Ceramic, up to 2600°F (1426°C)

Level 2 Probe Mounting Assembly 10 (ANSI 2" 150 lb.) 6" diameter flange, 4.75" BC with 4 x .75" dia. holes (North American Std) 20 (DIN) 185mm diameter flange, 145mm BC with 4 x 18mm dia. holes (European Std)

Level 3 Mounting Hardware – Stack Side 0 No adapter plate ("0" must also be chosen under "Mounting Adapter – Probe Side" below) 1 New installation – square weld plate with studs 2 Model 218/240 mounting plate (with Model 218/240 shield removed) 3 Existing Model 218/240 support shield 4 Mounting to other mounting 5 Mounting to Model 132 adapter plate

Level 4 Mounting Hardware – Probe Side 0 No adapter plate probe side 1 Probe only (ANSI) probe side 4 Probe only (DIN) probe side

Level 5 Electronic Housing – NEMA 4, IP66 HART® Communications H1 HART communication, basic unit H2 HART communication, local operator interface H3 HART communication, calibration solenoids H4 HART communication, local operator interface and calibration solenoids

Level 6 Electronic Mounting 01 Integral to sensor housing electronics 02 Split electronics with no cable 03 Split electronics with 6m (20') cable 04 Split electronics with 12m (40') cable 05 Split electronics with 18m (60') cable 06 Split electronics with 24m (80') cable 07 Split electronics with 30m (100') cable 08 Split electronics with 45m (150') cable

Level 7 Accessories 00 No hardware 01 Cal-gas rotometer, flow rotometers and reference gas set 02 In situ filter kit (SST only) 03 In situ filter kit (SST only), cal gas, flow rotometer and reference gas set 11 Cal gas, flow rotometers and reference gas set, with blowback 12 In situ filter kit (SST only), only with blowback 13 In situ filter kit (SST only), cal gas, flow rotometer and reference gas set, with blowback

ORDERING INFORMATION FOR GENERAL PURPOSE

See Option Notes on back cover.

ORDERING INFORMATION FOR HAZARDOUS AREA

Page 7

Model Description OCX88C Oxygen /Combustibles Transmitter – Flameproof

Oxygen/Combustibles Transmitter

Level 1 Probe Length and Material 00 No probe or exhaust tube 11 18" (457mm) 316 SST 12 3' (0.91m) 316 SST 13 6' (1.83m) 316 SST 14 9' (2.74m) 316 SST 21 18" (457mm) Inconel 600 22 3' (0.91m) Inconel 600 23 6' (1.83m) Inconel 600 24 9' (2.74m) Inconel 600 31 18" (457mm) Ceramic 32 3' (0.91m) Ceramic

Level 2 Probe Mounting Assembly 10 (ANSI 2" 150 lb.) 6" dia. flange, 4.75" BC with 4 x .75" dia. holes 20 (DIN) 185mm dia. flange, 145mm BC with 4 x 18mm dia. holes

Level 3 Mounting Hardware – Stack Side 0 No adapter plate ("0" must also be chosen under "Mounting Adapter – Probe Side" below) 1 New installation – square weld plate with studs 2 Model 218/240 mounting plate (with Model 218/240 shield removed) 3 Existing Model 218/240 support shield 4 Competitor's Mount 5 Model 132 adapter plate

Level 4 Mounting Hardware – Probe Side 0 No adapter plate 1 Probe only (ANSI) 4 Probe only (DIN)

Level 5 Electronic Housing – NEMA 4, IP66 HART® Communications H1 HART electronics, basic unit H2 HART electronics, local operator interface H3 HART electronics, calibration solenoids H4 HART electronics, local operator interface and calibration solenoids

Level 6 Electronic Mounting 02 Split electronics and no cable

Level 7 Accessories 00 None 01 Cal. gas/flow rotometers and ref. gas set 02 In situ filter kit (SST only) 03 In situ filter kit (SST only), cal. gas/flow rotometers and ref. gas set 11 Cal. gas/flow rotometers and ref. gas set, with blowback 12 In situ filter kit (SST only), with blowback 13 In situ filter kit (SST only), cal. gas/flow rotometers and ref. gas set, with blowback

See Option Notes on back cover.

Emerson Process ManagementRosemount Analytical Inc.Process Analytic Division6565 P Davis Industrial ParkwaySolon, OH 44139 USAT 330.682.9010Toll Free in US and Canada 800.433.6076F 330.684.4434e-mail: [email protected]

© Rosemount Analytical Inc., 2005. All rights reserved.Printed in U.S.A. on recycled paper.

ORDERING INFORMATION (Continued)

The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not tobe construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales aregoverned by our terms and conditions, which are available on request. We reserve the right to modify or improve the designs or specifications of our productsat any time without notice.

Option Notes

General Notes: Oxygen / Combustibles Transmitter

High Sulfur Service.

High sulfur cell can be selected for any probe; add a line item note to your purchase order requesting the high sulfurZrO2 cell in place of the standard ZrO2 cell. Add 4232 UOM to the system matrix UOM total.

Example:Note: Delete

Level 3: Option: 4Where possible, specify SPS number; otherwise provide details of the existing mounting plate as follows:

Plate with studs: Bolt circle diameter, number and arrangement of studs, stud thread, stud height above mounting plate.

Plate without studs: Bolt circle diameter, number and arrangement of holes, thread, depth of stud mounting plate with accessories.

Level 5: Option: H1, H2If the Local Operator Interface (LOI) is not implemented remote access and functionality are available via the HART Model375 Handheld Communicator with O2/Combustibles device descriptor (DD) required.

General Notes: Oxygen / Combustibles Transmitter – Explo-Proof

High Sulfur Service.

High sulfur cell can be selected for any probe; add a line item note to your purchase order requesting the high sulfurZrO2 cell in place of the standard ZrO2 cell. Add 4232 UOM to the system matrix UOM total.

Example:Note: Delete – standard cell P/N 4847B63G01

Add – high sulfur cell P/N 4847B63G02

Cell replacement kits for high sulfur service are also available. Consult P/N 4849B94XX in the Combustion SolutionsCenter Spare Parts list.

AccessoriesPart # Description1A99119G05 Cal gas regulators kit1A99119G06 Wall bracket kit1A99119H01 Oxygen bottles 0.4% balance N

2

1A99119H02 Oxygen bottles 8.0% balance N2

1A99292H01 Alarm/site programmable6A00146G01 20' power cable*6A00147G01 20' signal cable*6A00146G02 40' power cable*6A00147G02 40' signal cable*6A00146G03 60' power cable*6A00147G03 60' signal cable*6A00146G04 80' power cable*6A00147G04 80' signal cable*6A00146G05 100' power cable*6A00147G05 100' signal cable*6A00146G06 150' power cable*6A00147G06 150' signal cable*

* "Hazardous area equipment must be installed according to local regulations in order to meet the local requirements."