p l a n vaults...for dual meter configuration 18" 12" min b f 2" test plug assumed...
TRANSCRIPT
![Page 1: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/1.jpg)
A
B
C
D
E
F
G
H
J
K90° RJDI BEND
NOT USED
RJDI REDUCING FLANGE
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
FIRE LINE
DOMESTIC SERVICE (SEE NOTE 8)
RJDI GATE VALVE
DOMESTIC SERVICE METER (SEE NOTE 8)
FLANGED TEE
DETECTOR METER (SEE NOTE 6)
L
M
1 of 1
LONG SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
DEPTH
VARIES
WATER M
AIN
P L A N
FINISHED GRADE,
F
D
E
"A"
M
N
SUMP PIT
N
12"
MIN.
±3"
GRASS PLOT
PAVEMENT
FINISHED GRADE,
L
18" DIA.
x 12"
DEEP
TAPPING SLEEVE W/ TAPPING VALVE & BOX
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
C
K
A
A
STANDARD FOR COMBINED FIRE SERVICE
& METER VAULT
FOR DUAL METER CONFIGURATION
18"
12" MIN
B
F
2" TEST PLUG
ASSUMED
ROAD R/W
L E G E N D
C
A
B
A
18"
MIN.
12"
MIN.
ACCESS HATCH
MIN.
30"
O
J
J
J
J
H
H
G
SUMP PUMP LIDP
P
METER PIT DETAILS
P
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A COMBINATION VAULT CAN BE USED ONLY IF METER IS LARGER THAN
2".
a. METERS TO BE LOCATED A MAXIMUM 18" FROM HINGE SIDE OF HATCH.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 3" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
* NO PIPING SHALL BE
LOCATED UNDER HATCH
![Page 2: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/2.jpg)
A
B
C
D
E
F
G
H
J
K90° RJDI BEND
RJDI TEE
RJDI REDUCING FLANGE
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
FIRE LINE
DOMESTIC SERVICE (SEE NOTE 8)
RJDI GATE VALVE
DOMESTIC SERVICE METER (SEE NOTE 8)
FLANGED TEE
DETECTOR METER (SEE NOTE 6)
L
M
1 of 1
SHORT SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
DEPTH
VARIES
WATER M
AIN
P L A N
FINISHED GRADE,
F
D
E
"A"
M
N
SUMP PIT
N
12"
MIN.
±3"
GRASS PLOT
PAVEMENT
FINISHED GRADE,
L
18" DIA.
x 12"
DEEP
TAPPING SLEEVE W/ TAPPING VALVE & BOX
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
C
K
A
STANDARD FOR COMBINED FIRE SERVICE
& METER VAULT
FOR DUAL METER CONFIGURATION
18"
12" MIN
B
F
2" TEST PLUG
ASSUMED
ROAD R/W
L E G E N D
A
12"
MIN.
C
A
B
A
MIN.
30"
18"
MIN.
ACCESS HATCH
O
J
J
J
J
H
H
G
METER PIT DETAILS
P
SUMP PUMP LIDP
P
* NO PIPING SHALL BE
LOCATED UNDER HATCH
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A COMBINATION VAULT CAN BE USED ONLY IF METER IS LARGER THAN
2".
a. METERS TO BE LOCATED A MAXIMUM 18" FROM HINGE SIDE OF HATCH.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 3" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
![Page 3: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/3.jpg)
P L A N
A
B
C
D
E
K
CORPORATION STOP
BALL VALVE W/ FLANGED END (SEE NOTE 8)
RJDI TEE
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
DOMESTIC SERVICE METER
FLANGED TEE
L E G E N D
L
M
LONG SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
WATER M
AIN
FINISHED GRADE,
FI
18"
MIN
.
D
E
MIN.
12"
"A"
M
N
SUMP PIT
12"
MIN.
±3"
GRASS PLOT
OR PAVEMENT
FINISHED GRADE
L
18" DIA.
x 12"
DEEP
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
ASSUMED
ROAD R/W
MIN.
12"
ACCESS HATCH
F
G
H
J
FIRE LINE
DOMESTIC SERVICE
NOT USED
RJDI GATE VALVE
I
TAPPING SLEEVE W/ TAPPING VALVE & BOX (
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
K
A
G
2" AND SMALLER
LOCATED
OUTSIDE VAULT
LOCATION TO
BE DETERMINED
BY INAWC
DETECTOR METER (SEE NOTE 8)
MIN. 30"
DEPTH
VARIES
B
B
O
STANDARD FOR FIRE SERVICE
& METER PIT FOR 2" AND SMALLER
METER CONFIGURATION
N
J
J
P
SUMP PUMP LID
P
METER PIT DETAILS
P
C
C
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A SEPARATE METER PIT/VAULT WILL BE USED FOR DOMESTIC
METERS. DISTRICT TO PROVIDE PIT/VAULT DETAILS.
a. CUSTOMER SHALL FURNISH BALL VALVES ON BOTH
SIDES OF THE DOMESTIC METER SETTING.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 2" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
c. DETECTOR METER TO BE LOCATED A MAXIMUM 18" FROM
HINGE SIDE OF HATCH.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
![Page 4: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/4.jpg)
SHORT SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
WATER M
AIN
P L A N
FINISHED GRADE,
F
I
18"
MIN
.
D
E
MIN.
12"
"A"
M
12"
MIN.
±3"
GRASS PLOT
OR PAVEMENT
FINISHED GRADE
L
18" DIA.
x 12"
DEEP
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
ASSUMED
ROAD R/W
ACCESS HATCH
A
B
C
D
E
K
CORPORATION STOP
BALL VALVE W/ FLANGED END (SEE NOTE 8)
NOT USED
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
DOMESTIC SERVICE METER
FLANGED TEE
DETECTOR METER (SEE NOTE 8)
L E G E N D
L
M
N
SUMP PIT
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
K
B
A
G
B
2" AND SMALLER
LOCATED
OUTSIDE VAULT
LOCATION TO
BE DETERMINED
BY INAWC
F
G
H
J
FIRE LINE
DOMESTIC SERVICE
NOT USED
NOT USED
I
TAPPING SLEEVE W/ TAPPING VALVE & BOX
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
DEPTH
VARIES
O
STANDARD FOR FIRE SERVICE
& METER PIT FOR 2" AND SMALLER
METER CONFIGURATION
N
30"
MIN.
SUMP PUMP LIDP
METER PIT DETAILS
P
P
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A SEPARATE METER PIT/VAULT WILL BE USED FOR DOMESTIC
METERS. DISTRICT TO PROVIDE PIT/VAULT DETAILS.
a. CUSTOMER SHALL FURNISH BALL VALVES ON BOTH
SIDES OF THE DOMESTIC METER SETTING.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 2" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
c. DETECTOR METER TO BE LOCATED A MAXIMUM 18" FROM
HINGE SIDE OF HATCH.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
![Page 5: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/5.jpg)
A
B
C
D
E
K
NOT USED
RJDI TEE
NOT USED
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
DOMESTIC SERVICE METER (SEE NOTE 8)
FLANGED TEE
L E G E N D
L
M
LONG SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
WATER M
AIN
P L A N
K
FINISHED GRADE,
FI
18"
MIN
.
D
E
MIN.
12"
"A"
M
N
SUMP PIT
N
12"
MIN.
12"
MIN.
±3"
GRASS PLOT
OR PAVEMENT
FINISHED GRADE
I
G
H
L
18" DIA.
x 12"
DEEP
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
ASSUMED
ROAD R/W
MIN.
12"
ACCESS HATCH
F
G
H
J
FIRE LINE
DOMESTIC SERVICE (SEE NOTE 8)
2" TEST PLUG (SEE NOTE 8)
RJDI GATE VALVE
I
TAPPING SLEEVE W/ TAPPING VALVE & BOX
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
DETECTOR METER (SEE NOTE 8)
J
MIN. 30"
DEPTH
VARIES
DOMESTIC SERVICE
LARGER THAN 2"
O
J
STANDARD FOR COMBINED FIRE SERVICE
& METER VAULT FOR 3" AND LARGER
SINGLE METER CONFIGURATION
J
P
SUMP PUMP LIDP
METER PIT DETAILS
P
B
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A COMBINATION VAULT CAN BE USED ONLY IF METER IS LARGER THAN
2".
a. METERS TO BE LOCATED A MAXIMUM 18" FROM HINGE SIDE OF HATCH.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 3" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
![Page 6: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/6.jpg)
SHORT SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
WATER M
AIN
P L A N
K
FINISHED GRADE,
F
I
18"
MIN
.
D
E
MIN.
12"
"A"
M
N
SUMP
12"
MIN.
12"
MIN.
±3"
GRASS PLOT
OR PAVEMENT
FINISHED GRADE
I
G
H
L
18" DIA.
x 12"
DEEP
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE OR
4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
STANDARD FOR COMBINED FIRE SERVICE
& METER VAULT FOR 3" AND LARGER
SINGLE METER CONFIGURATION
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
ASSUMED
ROAD R/W
ACCESS HATCH
A
B
C
D
E
K
NOT USED
NOT USED
NOT USED
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
DOMESTIC SERVICE METER (SEE NOTE 8)
FLANGED TEE
DETECTOR METER (SEE NOTE 8)
L E G E N D
L
M
N
SUMP PIT
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATOR
O
F
G
H
J
FIRE LINE
DOMESTIC SERVICE (SEE NOTE 8)
2" TEST PLUG (SEE NOTE 8)
RJDI GATE VALVE
I
TAPPING SLEEVE W/ TAPPING VALVE & BOX
(COORDINATE W/ LOCAL UTILITY SUPERINTENDENT/MANAGER)
MIN. 30"
DEPTH
VARIES
DOMESTIC SERVICE
LARGER THAN 2"
O
J
SUMP PUMP LIDP
METER PIT DETAILS
P
P
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL APPERTENCES
EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A COMBINATION VAULT CAN BE USED ONLY IF METER IS LARGER THAN
2".
a. METERS TO BE LOCATED A MAXIMUM 18" FROM HINGE SIDE OF HATCH.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 3" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP PUMP
IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP OF VAULT,
INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE SUPPORTS
MAY BE REQUIRED.
![Page 7: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/7.jpg)
A
B
C
D
E
F
G
H
J
K
NOT USED
NOT USED
NOT USED
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
FIRE LINE
NOT USED
NOT USED
NOT USED
NOT USED
FLANGED TEE
DETECTOR METER
L E G E N D
L
M
LONG SIDE VAULT DETAIL
VAULT
WALL SLEEVES
W/ GROUT (TYP.)
"A"
12"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
DE
PT
H V
AR
IE
S
WA
TE
R M
AIN
P L A N
FINISHED GRADE,
F
D
E
MIN.
12"
"A"
M
STANDARD FIRE SERVICE
NSUMP PIT
N
SUMP
12"
MIN.
30"
MIN.
±3"
GRASS PLOT
PAVEMENT
FINISHED GRADE,
L
18" DIA.
x 12"
DEEP
TAPPING SLEEVE W/ TAPPING VALVE & BOX (COORDINATE WITH LOCAL UTILITY
SUPERINTENDENT/MANAGER)
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE
OR 4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATORO
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
18"
MIN.
ASSUMED
ROAD R/W
ACCESS HATCH
O
P
SUMP PUMP LIDP
METER PIT DETAILS
P
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL
APPERTENCES EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A SEPARATE METER PIT/VAULT WILL BE USED FOR DOMESTIC
METERS. DISTRICT TO PROVIDE PIT/VAULT DETAILS.
a. CUSTOMER SHALL FURNISH BALL VALVES ON BOTH
SIDES OF THE DOMESTIC METER SETTING.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 2" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
c. DETECTOR METER TO BE LOCATED A MAXIMUM 18" FROM
HINGE SIDE OF HATCH.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP
PUMP IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP
OF VAULT, INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE
SUPPORTS MAY BE REQUIRED.
![Page 8: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/8.jpg)
A
B
C
D
E
F
G
H
J
K
NOT USED
NOT USED
NOT USED
DOUBLE CHECK DETECTOR ASSEMBLY
FLANGED OS & Y VALVE
FIRE LINE
NOT USED
NOT USED
NOT USED
NOT USED
FLANGED TEE
DETECTOR METER (SEE NOTE 8)
L E G E N D
L
M
SHORT SIDE VAULT DETAIL
WALL SLEEVES
W/ GROUT (TYP.)
"A"
S E C T I O N "A-A"
12
"
MIN
.
PIPE SUPPORTS
(2 MIN. REQ'D)
ACCESS HATCH
DE
PT
H V
AR
IE
S
WA
TE
R M
AIN
P L A N
FINISHED GRADE,
F
D
E
MIN.
12"
"A"
M
NSUMP PIT
N
12"
MIN.
30"
MIN.
±3"
GRASS PLOT
PAVEMENT
FINISHED GRADE,
L
18" DIA.
x 12"
DEEP
TAPPING SLEEVE W/ TAPPING VALVE & BOX (COORDINATE WITH LOCAL UTILITY
SUPERINTENDENT/MANAGER)
FIRE DEPT. CONNECTION
(PER FIRE DEPARTMENT'S
REQUIREMENTS)
6" STONE BASE
OR 4" CONCRETE
(PER FIRE
DEPARTMENT'S
REQUIREMENTS)
FLANGED OS&Y VALVE WITH PIT TYPE POST INDICATORO
NO PIPING SHALL
BE LOCATED
UNDER HATCH
*
18"
MIN.
ASSUMED
ROAD R/W
ACCESS HATCH
STANDARD FIRE SERVICE
VAULT
O
SUMP PUMP LIDP
P
METER PIT DETAILS
P
NOTES:
2. VAULT CONSTRUCTION MATERIALS SHALL BE 8"x8"x16"
CMU, OR PRECAST, OR CAST-IN-PLACE
3. INSIDE DIMENSIONS PER DRAWING NOTES. VAULT
TO BE SET LENGTHWISE WITH SERVICE.
CONCRETE AT CUSTOMER'S SELECTION.
4. TOP OF VAULT TO BE CONCRETE, AT LEAST 4" THICK
WITH REINFORCING SUITABLE FOR ANTICIPATED LOADING.
WHEN VAULT IS CONSTRUCTED IN PAVED AREAS, PAVEMENT
IS TO BE LEVEL WITH TOP OF VAULT, AND THE TOP REINFORCED
AS REQUIRED TO SUPPORT TRAFFIC LOADS (i.e. H-20 WHEEL LOADS).
WHEN VAULT IS CONSTRUCTED IN GRASS PLOT, TOP OF VAULT
SHALL BE 3" ABOVE FINISHED GRADE.
1. CUSTOMER SHALL FURNISH & INSTALL VAULT, INCLUDING ALL
APPERTENCES EXCEPT AS NOTED BELOW.
6. DOUBLE CHECK DETECTOR ASSEMBLY SHALL BE A MODEL
APPROVED BY THE INDIANA DEPARTMENT OF
ENVIRONMENTAL MANAGEMENT, WITH FLANGED OS&Y GATE VALVE
ON INLET & OUTLET SIDES.
DETECTOR METER IS FURNISHED BY UTILITY AND
INSTALLED BY CUSTOMER. STAINLESS STEEL BOLTS ARE
REQUIRED.
8. A SEPARATE METER PIT/VAULT WILL BE USED FOR DOMESTIC
METERS. DISTRICT TO PROVIDE PIT/VAULT DETAILS.
a. CUSTOMER SHALL FURNISH BALL VALVES ON BOTH
SIDES OF THE DOMESTIC METER SETTING.
b. A 2" TEST PLUG SHALL BE INSTALLED AT LEAST 2 PIPE
DIAMETERS DOWNSTREAM OF 2" OR LARGER METERS.
5. BOTTOM OF VAULT TO BE EITHER A MINIMUM OF 6" OF CRUSHED
STONE OR 4" CONCRETE PER FIRE DEPARTMENT'S REQUIREMENT.
MINIMUM CLEARANCE OF 12" BELOW BOTTOM OF FIRE SERVICE
AND DOMESTIC SERVICE LINES IS REQUIRED.
c. DETECTOR METER TO BE LOCATED A MAXIMUM 18" FROM
HINGE SIDE OF HATCH.
10. THE LID AND RING THAT WILL BE REQUIRED IS FORD A53-TT OR
FORD A53-T. THE A53-TT WILL BE USED FOR ALL VAULTS WITH
THE DOMESTIC METER INSIDE. THE A53-T WITH BE USED FOR
ALL VAULTS WITH THE DCDA ONLY LOCATED INSIDE THE VAULT.
7. ACCESS HATCH IN TOP OF VAULT SHALL BE 30"x30"
ALUMINUM BILCO J-2AL, BILCO PCM-2, HALLIDAY
W1S3030 OR EQUAL. ACCESS HATCH SHALL HAVE
SAME OR GREATER LOADING CAPACITY AS VAULT LID.
PIPE HATCH FRAME DRAIN TO VAULT FLOOR OR SUMP,
AS APPLICABLE. IF THE LOCAL FIRE DEPARTMENT REQUIRES A SUMP
PUMP IN THE VAULT, ELECTRICAL DISCONNECT IS REQUIRED ON TOP
OF VAULT, INSTALLED ABOVE GRADE, PER LOCAL ELECTRICAL CODE.
9. AS DIRECTED BY LOCAL OPERATIONS, ADDITIONAL PIPE
SUPPORTS MAY BE REQUIRED.
![Page 9: P L A N Vaults...FOR DUAL METER CONFIGURATION 18" 12" MIN B F 2" TEST PLUG ASSUMED ROAD R/W L E G E N D C A B A 18" MIN. 12" ACCESS HATCH MIN. 30" O J J J J H H G PSUMP PUMP LID P](https://reader035.vdocument.in/reader035/viewer/2022071421/611a078f463a0661d73ea68e/html5/thumbnails/9.jpg)
NOTES: