p54x_en_m_ka4+kb4
TRANSCRIPT
-
7/23/2019 p54x_en_m_ka4+kb4
1/2
Application Notes P54x/EN AP/Ja4
MiCOM P543, P544, P545 & P546 (AP) 6-85
AP
6.7 Worked example for CT requirements
The Power system and the line parameters (Line length: 100 km) as given in section 3.2 isused here to calculate CT requirements.
6.7.1 Important notes to be considered
Current differential Both If and X/R are to be calculated for a through fault
Distance Zone1 reach point case Both If and X/R are to be calculated for a fault atZone1 reach point
For calculating the CT requirements, the bus bar short time symmetrical fault rating shallbe considered as the bus fault level.
When there are only indicative X/Rs available, then the circuit breakers dc breakingcapacity shall be used to arrive at the primary time constant (and hence the primarysystem X/R). The derivation shall be obtained from the circuit breaker manufacturer;practical primary time constants arrived in such a way vary between 50 ms (applicablefor 66 kV and 132 kV breakers) and 120 ms (applicable for 220 kV and 400 kVbreakers). 150 ms is a practical figure for generator circuit breakers.
6.7.2 System data
In the following example, the following parameters have been considered for the CTcalculations:
System voltage - 230 kV
System frequency - 50 Hz
System grounding - solid
Single circuit operation between Green Valley and Blue River
CT ratio - 1200/1
Line length - 100 kms
Line positive sequence impedance Z1 = 0.089 + j 0.476 ohm / km
Bus fault level - 40 kA
Primary time constant = 120 ms
6.7.3 Calculation of Primary X/R
Primary X/R till the Green Valley bus = 2 * pi * f * primary time constant in s
= 2 * pi * 50 * 0.12
Primary X/R till the bus = 37.7
6.7.4 Calculation of Source Impedance Zs
Source Impedance Zs = 230 kV / (1.732 * 40 kA)= 3.32 ohms
Source angle = tan-1 (X/R)
= tan-1 (37.7)= 88.48 deg
Hence, Zs = 0.088 + j 3.317 ohms
-
7/23/2019 p54x_en_m_ka4+kb4
2/2
P54x/EN AP/Ja4 Application Notes
(AP) 6-86 MiCOM P543, P544, P545 & P546
AP
6.7.5 Calculation of full line impedance (full 100 kms)
Z1 = 0.089 + j 0.476 ohm / km
ZL = 8.9 + j 47.6 ohms
ZL = 48.42 ohms with an angle 79.4 deg
6.7.6 Calculation of total impedance till remote bus bar
ZT = Zs + ZL = 8.988 + j 50.917 ohms
= 51.7 ohms with an angle of 80 deg
6.7.7 Calculation of through fault X/R
X/R thro = 50.917 / 8.988
= 5.66
6.7.8 Calculation of through fault If
If thro = 230kV / (1.732 * 51.7 )
= 2568.5 A primary
= 2.14 A (secondary)
6.7.9 Calculation of line impedance till Zone1 reach point (80kms)
Zzone1 = 0.8 * ZL = 7.12 + j 38.08 ohms
= 38.73 ohms with an angle of 79.4 deg
6.7.10 Calculation of total impedance till Zone1 reach point
ZTzone1 = Zs + Zzone1
= 7.208 + j 41.397 ohms
= 42.019 ohms with an angle of 80 deg
6.7.11 Calculation of X/R till Zone1 reach point
X/R zone1 = 41.397 / 7.208
= 5.74
6.7.12 Calculation of fault current till Zone1 reach point
If zone1 = 230 kV / (1.732 * 42.019)
= 3160.34 A (primary) = 2.63 A (secondary)