page 1 of 5 - campus facilitiesoperations-webapps.missouri.edu/pdc/adsite/projects/cp151701...page 1...
TRANSCRIPT
Page 1 of 5
ADDENDUM #2
DATE: December 14, 2017
TO CONTRACT DOCUMENTS ENTITLED: Memorial Student Union Maintenance Repairs & Second
Floor Renovation to North Wing; Life Safety Upgrades to North, South, & AP Green Chapel
PROJECT MANUAL FOR: Memorial Student Union Maintenance Repairs & Second Floor Renovation to
North Wing; Life Safety Upgrades to North, South, & AP Green Chapel
PROJECT NUMBER: CP151701
ADVERTISEMENT DATE: November 16, 2017
PREPARED FOR: The Curators of the University of Missouri
CONSULTANT: The Lawrence Group
319 N. 4th St. Ste 1000
St. Louis, MO 63102
314-231-5700
Drawings and Specifications for the above noted project and the work covered thereby are herein
modified as follows, and except as set forth herein, otherwise remain unchanged and in full force
and effect:
SPECIFICATION CHANGES:
1. Section: 1.A – Bid For Lump Sum Contract
Page 3 – Asbestos Removal: Revise the quantities for ACM materials as shown.
2. SECTION 02 8233 FRIABLE AND NON-FRIABLE ASBESTOS REMOVAL AND
UNIVERSAL WASTE/HARDOUS MATERIAL REMOVAL
A. Page 1, Item 4.A.a
DELETE and REVISE QUANTITY AS FOLLOWS:
Six thousand, six hundred eighty-five (6,685) square feet of ACM Air Handler Unit Insulation
from the penthouse;
B. Page 1, Item 4.A.c
DELETE AND REVISE QUANTITY AS FOLLOWS:
One hundred forty-five (145) ACM pipe fittings from the penthouse;
C. Page 2, Item 4.B.h
DELETE AND REVISE QUANTITY AS FOLLOWS:
Eighteen (18) ACM vibration dampeners from the penthouse;
D. Page 2, Item 4.B.i
DELETE AND REVISE QUANTITY AS FOLLOWS:
Five hundred twenty-five (525) linear feet of ACM Air Handling Unit Door Seam Tar from the
penthouse; and
E. Page 2, Item 5 DELETE
AND ADD:
The work shall include the removal and legal disposal of universal wastes/hazardous
Page 2 of 5
materials located on the 2nd
floor and within the penthouse including:
a) One hundred fifty-five (155) assumed PCB-containing ballasts;
b) Four hundred ninety-four (494) florescent bulbs;
c) Fifteen (15) exit/emergency light batteries and fire alarm strobe lights;
d) Nine (9) assumed mercury-containing thermostats;
e) Twenty-two (22) compact florescent light bulbs; and
f) Eighteen (18) containers of paints/aerosols.
3. Section: 072726 – Fluid-Applied Membrane Air Barriers
2.3-A-1-a: Add the following manufacturer: GE Elemax 2600 AWB
4. Section: 081113 – Hollow Metal Doors & Frames
2.1-A: Add the following manufacturer: Allegion-Republic
5. Section: 081416 – Flush Wood Doors
2.4-A: Add the following manufacturer: Oshkosh Door Company
2.4-B-2-a: Revise to be: Rift cut, White Oak.
6. Section: 102239 – Folding Panel Partitions
2.4-A-a: Add panel facing material.
2.6: Revise description of Storage Pocket Doors
7. Section: 122413 – Roller Window Shades
2.4-B-1: Revise to be: Type: 0200 Series, Color: Calico 0214, Openness Factor: 0%.
8. Section 26 29 23: Variable Frequency Drives Description: ADD 1.3.E. to read as follows: Sheet E500, Detail 9: VFD Mounting Detail. REVISE 3.2.E. to
read as follows: The service disconnect switch must be installed on the line side of the VFD. The disconnect
must be in a separate enclosure from the VFD. If conditions do not allow this disconnect to be located near
the motor within NEC requirements, then a second remote disconnect may be required at the motor. Consult
the project manager or University Engineer if this condition arises. All remote disconnects must be provided
with auxiliary contacts hardwired to VFD safety circuit to shut down VFD when disconnect is opened. This
may affect warranty on the drive so every attempt should be taken to install it per these design guidelines.
9. Section 23 09 00: JCI Control System (MU) Description: ADD section 2.01-C for steam control valves..
DRAWING CHANGES:
1. Sheet D100 – D104: DEMOLITION PLANS
GENERAL DEMOLITION NOTES: DELETE and REVISE notes to read:
E. NOT USED
F. SEE MECHANICAL, ELECTRICAL, PLUMBING, AND FIRE PROTECTION SHEETS
FOR DEMOLITION OF THIS SCOPE.
G. NOT USED.
H. NOT USED.
I. PARTITIONS TO BE DEMOLISHED SHALL INCLUDE ASSOCIATED BRACING,
DOORS, FRAMES, HARDWARE, BASE, ETC. IN THEIR ENTIRETY
2. Sheet D102N: Second Floor Demo Plan – North Wing
ADD Loading Dock Roof scope.
Page 3 of 5
3. Sheet D104: Roof Demo Plan – North Wing
ADD stair tower roof scope.
4. Sheet A102N: Second Floor Plan - North Wing
ADD loading dock roof scope.
5. Sheet A104N: Roof Plan – North Wing
REVISE detail 3/A104N as indicated.
6. Sheet A200: Exterior Elevations
REVISE Detail 4,5,&6/A200 as indicated.
7. Sheet 300: Wall Sections
REVISE Detail 1/A300 as indicated.
8. Sheet A500: Interior Elevations
Detail 3B/A500 - REVISE door for folding partition as indicated.
9. Sheet A700: Exterior Details
REVISE detail 3/A700 as indicated.
REVISE detail 10/A700 as indicated.
REMOVE detail 2/A700
10. Sheet A800: Interior Details
Detail 9/A800 - REVISE support for folding partition as indicated.
11. Sheet S103: Typical Details
Detail 11/S103 - Add detail.
12. Sheet S205: Partial Roof Framing Plan
Revise plan as indicated.
13. Sheet S206: High Roof Framing Plan
Revise plan as indicated.
14. Sheet S402: Framing Sections and Details
Detail 1/S402 - Revise detail as indicated.
15. Sheet F000: Fire Protection Cover Sheet
Description: ADD fire protection general note #23.
16. Sheet P000: Plumbing Cover Sheet
Description: ADD plumbing general note #23.
17. Sheet PD103N: Attic Floor Plan - North Wing - Plumbing - Demo
Description: REMOVE existing roof drains.
18. Sheet P101N: First Floor Plan - North Wing - Plumbing
Description: MODIFY sanitary pipe of water closet and floor drain.
19. Sheet P103N: Attic Floor Plan - North Wing - Plumbing
Description: ADD new roof drains on the same location of the existing.
Page 4 of 5
20. Sheet P400: Plumbing – Enlarged Plans
Description: MODIFY sanitary pipe for ADA water closet and adjust location of the floor drain
location in Janitor closet (N235).
21. Sheet MPD100: Sub Basement Floor Plan – Mechanical Piping - Demo
Description: REVISE tunnel steam pipes as shown in revised drawing MPD100.
22. Sheet MPD100.5N: Ground Floor Plan – North Wing - Piping - Demo
Description: REVISE tunnel steam pipes and general note as shown in revised drawing
MPD100.5N.
23. Sheet MPD101N: First Floor Plan – North Wing - Piping - Demo
Description: ADD existing panels as shown in revised drawing MPD101N.
24. Sheet MP100: Sub Basement Floor Plan – Mechanical Piping
Description: REMOVE unit heaters and MODIFY hydronic pipe. REVISE tunnel steam pipes.
ADD note as shown in revised drawing MP100.
25. Sheet MP100.5N: Ground Floor Plan – North Wing - Piping
Description: ADD steam and condensate pipes. ADD keynotes and thermostat as shown in revised
drawing MP100.5N
26. Sheet MP101N: First Floor Plan – North Wing - Piping
Description: ADD general note and keynote. REVISE notes of existing radiation panels as shown in
revised drawing MP101N.
27. Sheet MP102N: Second Floor Plan – North Wing - Piping
Description: ADD general note and REVISE pipe for VAV-4-212 as shown in revised drawing
MP102N.
28. Sheet MP400: Attic Enlarged Plan
Description: ADD general note and REMOVE MODs as shown in revised drawing MP400.
29. Sheet MP700: Piping Schedule
Description: ADD note in heat exchanger schedule as shown in revised drawing MP700.
30. Sheet MV102N: Second Floor Plan – North Wing - Ventilation
Description: REVISE ductwork as shown in revised drawing MV102N.
31. Sheet MV103N: Attic Floor Plan – North Wing - Ventilation
Description: REVISE location of REF-2 and ductwork as shown in revised drawing MV103N.
32. Sheet MV601: Ventilation Schedule
Description: REVISE schedules as shown in revised drawing MV601.
33. Sheet MV700: Ventilation Controls
Description: REVISE control diagram as shown in revised drawing MV700.
34. Sheet MV701: Ventilation Controls
Description: ADD control diagram as shown in revised drawing MV701.
35. Sheet EPD103N: Attic Floor Plan - North Wing - Electrical - Power - Demo
Description: ADD conduit and conductors to be demolished as shown in revised drawing EPD103N.
REVISE flood light demolition scope as shown in revised drawing EPD103N.
Page 5 of 5
36. Sheet EP103N: Attic Floor Plan - North Wing - Electrical - Power
Description: ADD receptacle in elevator hoistway as shown in revised drawing EP103N.
37. Sheet EP104N: Roof Plan - North Wing - Electrical - Power
Description: ADD keynote 3 as shown in revised drawing EP104N.
38. Sheet E700: Electrical Schedules
Description: REVISE Distribution Panel DP/AT2 schedule as shown in revised drawing E700.
39. Sheet EL801 – Lighting Schedules
a. Added approved equals.
END OF ADDENDUM 2
1.A - 1
SECTION 1.A BID FOR LUMP SUM CONTRACT
Date:____________________________ BID OF (hereinafter called "Bidder") a corporation* organized and existing under laws of the State of , a partnership* consisting of , an individual* trading as , a joint venture* consisting of . *Insert Corporation(s), partnership or individual, as applicable.
TO: Curators of the University of Missouri c/o Associate Vice Chancellor – Facilities General Services Building, Room L100 University of Missouri Columbia, Missouri, 65211
1. Bidder, in compliance with invitation for bids for construction work in accordance with Drawings and Specifications prepared by The Lawrence Group Architects, entitled "Memorial Student Union – Maintenance Repairs and Second Floor Renovation to North Wing; Life Safety Upgrades to North, South, and AP Green Chapel", project number CP151701, dated November 16, 2017 having examined Contract Documents and site of proposed work, and being familiar with all conditions pertaining to construction of proposed project, including availability of materials and labor, hereby proposes to furnish all labor, materials and supplies to construct project in accordance with Contract Documents, within time set forth herein at prices stated below. Prices shall cover all expenses, including taxes not covered by the University of Missouri’s tax exemption status, incurred in performing work required under Contract documents, of which this Bid is a part.
Bidder acknowledges receipt of following addenda:
Addendum No. Dated Addendum No. Dated Addendum No. Dated Addendum No. Dated 2. In following Bid(s), amount(s) shall be written in both words and figures. In case of discrepancy between words and figures, words shall govern.
3. BID PRICING
a. Base Bid: The Bidder agrees to furnish all labor, materials, tools, and equipment required to renovate the Second Floor and perform maintenance repairs in the North Wing, and perform life safety upgrades in the North Wing, South Wing, and AP Green Chapel; all as indicated on the Drawings and described in these Specifications for sum of:
DOLLARS ($ ).
1.A - 2
b. Additive Alternate Bids:
Above Base Bid may be changed in accordance with following Alternate Bids as Owner may elect. Alternates are as described in Section 1.H of Project Manual. Alternates are written in a priority order, but Owner is not required to accept or reject in order listed. This is a one (1) contract project, therefore, Alternates shall be studied by each Bidder to determine effect on Bids of Contractor and each Subcontractor and/or Material supplier.
(1) Additive Alternate No. 1: Masonry screen wall at loading dock. All for sum of:
DOLLARS ($ ).
(2) Additive Alternate No. 2: Upgrade Electrical service. All for sum of:
DOLLARS ($ ).
(3) Additive Alternate No. 3: Upgrade North Tower to DDC controls. All for sum of:
DOLLARS ($ ).
(4) Additive Alternate No. 4: Replace Electrical panels. All for sum of:
DOLLARS ($ ).
(5) Additive Alternate No. 5: Replace North Tower passenger elevator. All for sum of:
DOLLARS ($ ).
(6) Additive Alternate No. 6: Remove all abandoned piping and equipment. All for sum of:
DOLLARS ($ ).
c. Unit Prices:
(1) For changing specified quantities of work from those indicated by Contract Drawings and Specifications, upon written instructions of Owner, the following Unit Prices shall prevail in accordance with General Conditions.
(2) The following Unit Prices include all labor, overhead and profit, materials, equipment, appliances, bailing, shoring, shoring removal, etc., to cover all work.
(3) The following Unit Prices are required where applicable to particular Base Bid and/or Alternate being submitted. (4) Only a single Unit Price shall be given and it shall apply for either MORE or LESS work than that indicated on Drawings and called for in Specifications as indicated to be included in Base Bid and/or Alternates. In the event that more or less units than so indicated is actually furnished, Change Orders will be issued for increased or decreased amounts as
1.A - 3
approved by the Owner.
(5) Bidder understands that the Owner will not be liable for any Unit Price or any amount in excess of Base Bid and any Alternate(s) accepted at time of award of Contract, except as expressed in written Change Orders duly executed and delivered by Owner's Representative.
FILL IN ONLY ONE PRICE PER LINE
Asbestos Removal.
(a) Friable Asbestos AHU Insulation, Base Bid quantity = 6,685 lin. ft. $ /lin. ft.
(b) Friable Asbestos Pipe Insulation,
Base Bid quantity = 590 lin. ft. $ /lin. ft.
(c) Friable Asbestos Pipe Fitting, Base Bid quantity = 145 ea. $ /ea.
(d) Non-Friable Level 1 Asbestos Floor Tile and Adhesive Mastic, Base Bid quantity = 4,500 sq. ft. $ /sq. ft.
(e) Non-Friable Level 1Asbestos Cove Base Mastic, Base Bid quantity = 50 lin. ft. $ /lin. ft.
(f) Non-Friable Level 2 Asbestos Floor Tile, Base Bid quantity = 6,200 sq. ft. $ /sq. ft.
(g) Non-Friable Level 2 Asbestos Floor Tile and Mastic, Base Bid quantity = 4,045 sq. ft. $ /sq. ft.
(h) Non-Friable Level 2 Asbestos Cove Base Mastic, Base Bid quantity = 135 lin. ft. $ /lin. ft.
(i) Non-Friable Asbestos Door, Window & Louver Caulk, Base Bid quantity = 375 lin. ft. $ /lin. ft.
(j) Non-Friable Asbestos Window Glaze, Base Bid quantity = 290 lin. ft. $ /lin. ft.
(k) Non-Friable Asbestos Vibration Dampeners, Base Bid quantity = 18 ea. $ /ea.
(l) Non-Friable Asbestos AHU Door Seam Tar, Base Bid quantity = 525 lin. ft. $ /lin. ft.
(m) Non-Friable Asbestos Transite Electrical Panel, Base Bid quantity = 20 sq. ft. $ /sq. ft.
4. PROJECT COMPLETION
1.A - 4
a. Contract Period - Contract period begins on the day the Contractor receives unsigned Contract, Performance Bond, Payment Bond, and "Instructions for Execution of Contract, Bonds, and Insurance Certificates." Bidder agrees to complete project within Three Hundred Sixty-seven (367) calendar days from receipt of aforementioned documents. Fifteen (15) calendar days have been allocated in construction schedule for receiving aforementioned documents from Bidder.
b. Commencement - Contractor agrees to commence work on this project after the "Notice to Proceed" is issued by the Owner. "Notice to Proceed" will be issued within seven (7) calendar days after Owner receives properly prepared and executed Contract documents listed in paragraph 4.a. above.
c. Special scheduling requirements: (1) Sub-basement, chilled water pumps and all chilled water piping must be complete prior to April 1, 2018. (2) Electrical Service upgrade, may begin on May 14, 2018. (3) Work in Starbuck’s and Wheatstone Bistro may occur between May 14 – June 4, 2018, and July 1 – July 31, 2018. (4) Work in Stotler Lounge, Level 1 restrooms and the corridor outside Level 1 Restrooms may occur between July 1, 2018 – August 13, 2018.
(5) Work in Tower Lounge, Bengal Lair, Disability Center, AP Green Chapel and the Ground Floor of the North Wing may occur between May 14, 2018 – August 20, 2018.
(6) Ductwork from the Attic to Level 1, and work on the Attic modification must be complete prior to AHU Switchover.
(7) AHU installation and switchover must be complete by July 20, 2018.
(8) Penthouse demolition, Roof level carbon fiber installation, Level 2 transfer beams, Level 2 column removal, and Roof installation may begin after AHU switchover.
(9) Mechanical, Electrical, Plumbing, and Fire Protection system switchovers may require weekend or night work to complete – coordinate all switchovers with Owner’s Representative prior to completion.
5. SUBCONTRACTOR LIST:
Bidder hereby certifies that the following subcontractors will be used in performance of Work:
NOTE: Failure to list subcontractors for each category of work identified on this form or listing more than one subcontractor for any category of work without designating the portion of work performed by each shall be grounds for rejection of bid. List name, city, and state of designated subcontractor, for each category of work listed in Bid For Lump Sum Contract. If work within a category will be performed by more than one subcontractor, Bidder shall provide name, city, and state of each subcontractor and specify exact portion of work to be performed by each. If acceptance/non-acceptance of Alternates will affect designation of a subcontractor, Bidder shall provide information, for each affected category, with this bid form. If Bidder intends to perform any designated subcontract work by using Bidder's own employees, then Bidder shall list their own name, city, and state. The bidder may petition the Owner to change a listed subcontractor only within 48 hours of the bid opening. See Information For Bidders Section 16 List of Subcontractors for requirements.
1.A - 5
_______________________________________________________________________________________________ Work to be performed Subcontractor Name, City, State _______________________________________________________________________________________________
Mechanical Contractor
Electrical Contractor
Fire Protection Contractor
Fire Alarm Contractor
Elevator Contractor
6. SUPPLIER DIVERSITY PARTICIPATION GOALS
a. The Contractor shall have as a goal, subcontracting with Minority Business Enterprise (MBE) of ten percent (10%), with Service Disabled Veteran Owned Business (SDVE) of three percent (3%); and with Women Business Enterprise (WBE), Disadvantage Business Enterprise (DBE), and/or Veteran Owned Business of ten percent (10%)[Write out goal in words (numbers)] of awarded contract price for work to be performed.
b. Requests for waiver of this goal shall be submitted on the attached Application For Waiver form. A determination by the Director of Facilities Planning & Development, UM, that a good faith effort has not been made by Contractor to achieve above stated goal may result in rejection of bid.
c. The Undersigned proposes to perform work with following Supplier Diversity participation level: MBE PERCENTAGE PARTICIPATION: _____________________ percent ( %) SDVE PERCENTAGE PARTICIPATION: _____________ percent ( %) WBE, DBE, and/or VETERAN PERCENTAGE PARTICIPATION:___________ percent ( %)
d. A Supplier Diversity Compliance Evaluation form shall be submitted with this bid for each diverse subcontractor to be used on this project.
7. BIDDER'S ACKNOWLEDGMENTS
a. Bidder declares that he has had an opportunity to examine the site of the work and he has examined Contract Documents therefore; that he has carefully prepared his bid upon the basis thereof; that he has carefully examined and checked bid, materials, equipment and labor required thereunder, cost thereof, and his figures therefore. Bidder hereby states that amount, or amounts, set forth in bid is, or are, correct and that no mistake or error has occurred in bid or in Bidder's computations upon which this bid is based. Bidder agrees that he will make no claim for reformation, modifications, revisions or correction of bid after scheduled closing time for receipt of bids.
b. Bidder agrees that bid shall not be withdrawn for a period of Ninety (90) days after scheduled closing time for receipt of bids.
1.A - 6
c. Bidder understands that Owner reserves right to reject any or all bids and to waive any informalities in bidding.
d. Accompanying the bid is a bid bond, or a certified check, or an irrevocable letter of credit, or a cashier's check payable without condition to "The Curators of the University of Missouri" which is an amount at least equal to five percent (5%) of amount of largest possible total bid herein submitted, including consideration of Alternates.
e. Accompanying the bid is a Bidder's Statement of Qualifications. Failure of Bidder to submit the Bidder's Statement of Qualifications with the bid may cause the bid to be rejected. Owner does not maintain Bidder's Statements of Qualifications on file.
f. It is understood and agreed that bid security of two (2) lowest and responsive Bidders will be retained until Contract has been executed and an acceptable Performance Bond and Payment Bond has been furnished. It is understood and agreed that if the bid is accepted and the undersigned fails to execute the Contract and furnish acceptable Performance/Payment Bond as required by Contract Documents, accompanying bid security will be realized upon or retained by Owner. Otherwise, the bid security will be returned to the undersigned.
8. BIDDER'S CERTIFICATE
Bidder hereby certifies:
a. His bid is genuine and is not made in interest of or on behalf of any undisclosed person, firm or corporation, and is not submitted in conformity with any agreement or rules of any group, association or corporation.
b. He has not directly or indirectly induced or solicited any other bidder to put in a false or sham bid.
c. He has not solicited or induced any person, firm or corporation to refrain from bidding.
d. He has not sought by collusion or otherwise to obtain for himself any advantage over any other Bidder or over Owner.
e. He will not discriminate against any employee or applicant for employment because of race, color, religion, sex or national origin in connection with performance of work.
f. By virtue of policy of the Board of Curators, and by virtue of statutory authority, a preference will be given to materials, products, supplies, provisions and all other articles produced, manufactured, mined or grown within the State of Missouri. By virtue of policy of the Board of Curators, preference will also be given to all Missouri firms, corporations, or individuals, all as more fully set forth in "Information For Bidders."
1.A - 7
9. BIDDER'S SIGNATURE
Note: All signatures shall be original; not copies, photocopies, stamped, etc.
Authorized Signature Date
Printed Name Title
Company Name
Mailing Address
City, State, Zip
Phone No. Federal Employer ID No.
Fax No. E-Mail Address
Circle one: Individual Partnership Corporation Joint Venture
If a corporation, incorporated under the laws of the State of__________
Licensed to do business in the State of Missouri? ____yes _____no
(Each Bidder shall complete bid form by manually signing on the proper signature line above and supplying required information called for in connection with the signature. Information is necessary for proper preparation of the Contract, Performance Bond and Payment Bond. Each Bidder shall supply information called for in accompanying "Bidder's Statement of Qualifications.")
END OF SECTION
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 1
SECTION 102239 - FOLDING PANEL PARTITIONS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Manually operated, acoustical panel partitions.
B. Related Requirements:
1. Section 055000 "Metal Fabrications" for supports that attach supporting tracks to overhead structural system.
1.3 DEFINITIONS
A. NIC: Noise Isolation Class.
B. NRC: Noise Reduction Coefficient.
C. STC: Sound Transmission Class.
1.4 ACTION SUBMITTALS
A. Shop Drawings: For operable panel partitions.
1. Include plans, elevations, sections, attachment details. 2. Indicate stacking and operating clearances. Indicate location and installation
requirements for hardware and track, blocking, and direction of travel.
B. Samples for Initial Selection: For each type of exposed material, finish, covering, or facing.
1. Include Samples of accessories involving color selection.
1.5 INFORMATIONAL SUBMITTALS
A. Coordination Drawings: Reflected ceiling plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of the items involved:
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 2
1. Partition track, track supports and bracing, switches, turning space, and storage layout. 2. Suspended ceiling components. 3. Structural members to which suspension systems will be attached. 4. Size and location of initial access modules for acoustical tile. 5. Items penetrating finished ceiling.
B. Setting Drawings: For embedded items and cutouts required in other work, including support-beam, mounting-hole template.
C. Qualification Data: For Installer.
D. Product Certificates: For each type of operable panel partition.
1. Include approval letter signed by manufacturer acknowledging Owner-furnished panel facing material complies with requirements.
E. Product Test Reports: For each operable panel partition, for tests performed by a qualified testing agency.
F. Field quality-control reports.
1.6 CLOSEOUT SUBMITTALS
A. Operation and Maintenance Data: For operable panel partitions to include in maintenance manuals.
1. In addition to items specified in Section 017823 "Operation and Maintenance Data," include the following:
a. Panel finish facings and finishes for exposed trim and accessories. Include precautions for cleaning materials and methods that could be detrimental to finishes and performance.
b. Seals, hardware, track, track switches, carriers, and other operating components. c. Electric operator and controls.
1.7 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials, from the same production run, that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Panel Finish-Facing Material: Furnish full width in quantity to cover both sides of two panels when installed.
1.8 QUALITY ASSURANCE
A. Installer Qualifications: An entity that employs installers and supervisors who are trained and approved by manufacturer.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 3
1.9 DELIVERY, STORAGE, AND HANDLING
A. Protectively package and sequence panels in order for installation. Clearly mark packages and panels with numbering system used on Shop Drawings. Do not use permanent markings on panels.
1.10 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of operable panel partitions that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Faulty operation of operable panel partitions. b. Deterioration of metals, metal finishes, and other materials beyond normal use.
2. Warranty Period: Two years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 "Quality Requirements," to design seismic bracing of tracks to structure above.
B. Acoustical Performance: Provide operable panel partitions tested by a qualified testing agency for the following acoustical properties according to test methods indicated:
1. Sound-Transmission Requirements: Operable panel partition assembly tested for laboratory sound-transmission loss performance according to ASTM E 90, determined by ASTM E 413, and rated for not less than the STC indicated.
2. Noise-Reduction Requirements: Operable panel partition assembly, identical to partition tested for STC, tested for sound-absorption performance according to ASTM C 423, and rated for not less than the NRC indicated.
3. Noise-Isolation Requirements: Installed operable panel partition assembly, identical to partition tested for STC, tested for NIC according to ASTM E 336, determined by ASTM E 413, and rated for 10 dB less than STC value indicated.
C. Fire-Test-Response Characteristics: Provide panels with finishes complying with one of the following as determined by testing identical products by a testing and inspecting agency acceptable to authorities having jurisdiction:
1. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
a. Flame-Spread Index: 25 or less. b. Smoke-Developed Index: 450 or less.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 4
2. Fire Growth Contribution: Complying with acceptance criteria of local code and authorities having jurisdiction when tested according to NFPA 265 Method B Protocol or NFPA 286.
2.2 OPERABLE ACOUSTICAL PANELS
A. Operable Acoustical Panels: Partition system, including panels, seals, finish facing, suspension system, operators, and accessories.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Advanced Equipment Corporation. b. Hufcor, Inc. c. KWIK-WALL Company. d. Moderco Inc. e. Modernfold, Inc. f. Panelfold Inc.
B. Panel Operation: Manually operated, individual panels.
C. Panel Construction: As required to support panel from suspension components and with reinforcement for hardware attachment. Fabricate panels with tight hairline joints and concealed fasteners. Fabricate panels so finished in-place partition is rigid; level; plumb; aligned, with tight joints and uniform appearance; and free of bow, warp, twist, deformation, and surface and finish irregularities.
D. Dimensions: Fabricate operable acoustical panel partitions to form an assembled system of dimensions indicated and verified by field measurements.
1. Panel Width: As indicated.
E. STC: Not less than 47.
F. NRC: Not less than 0.60.
G. Panel Thickness: Minimum dimension of 3 inches (75 mm).
H. Panel Materials: 1. Steel Frame: Manufacturer's standard.
I. Panel Closure: Manufacturer's standard unless otherwise indicated.
J. Hardware: Manufacturer's standard as required to operate operable panel partition and accessories; with decorative, protective finish.
1. Hinges: Manufacturer's standard.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 5
2.3 SEALS
A. Description: Seals that produce operable panel partitions complying with performance requirements and the following:
1. Manufacturer's standard seals unless otherwise indicated. 2. Seals made from materials and in profiles that minimize sound leakage. 3. Seals fitting tight at contact surfaces and sealing continuously between adjacent panels
and between operable panel partition perimeter and adjacent surfaces, when operable panel partition is extended and closed.
B. Vertical Seals: Deep-nesting, interlocking steel astragals mounted on each edge of panel, with continuous, resilient acoustical seal.
C. Horizontal Top Seals: [ontinuous-contact, resilient seal exerting uniform constant pressure on track or resilient, mechanical, retractable, constant-force-contact seal exerting uniform constant pressure on track when extended.
D. Horizontal Bottom Seals: Manufacturer's standard continuous-contact seal exerting uniform constant pressure on floor.
2.4 PANEL FINISH FACINGS
A. Description: Finish facings for panels that comply with indicated fire-test-response characteristics and that are factory applied to operable panel partitions with appropriate backing, using mildew-resistant nonstaining adhesive as recommended by facing manufacturer's written instructions.
a. THE FINISH FACING WILL BE FABRIC TO MATCH THE EXISTING PARTITIONS IN THE STOTLER LOUNGE N103B. ADD.#2
b. Apply one-piece, seamless facings free of air bubbles, wrinkles, blisters, and other defects, with edges tightly butted, and with invisible seams complying with Shop Drawings for location, and with no gaps or overlaps.
2.5 SUSPENSION SYSTEMS
A. Tracks: Steel or aluminum mounted directly to overhead structural support, with adjustable steel hanger rods for overhead support, designed for operation, size, and weight of operable panel partition indicated. Size track to support partition operation and storage without damage to suspension system, operable panel partitions, or adjacent construction. Limit track deflection to no more than 0.10 inch (2.54 mm) between bracket supports. Provide a continuous system of track sections and accessories to accommodate configuration and layout indicated for partition operation and storage. 1. Head Closure Trim: As required for acoustical performance; with factory-applied,
decorative, protective finish.
B. Carriers: Trolley system as required for configuration type, size, and weight of partition and for easy operation; with ball-bearing wheels.
1. Multidirectional Carriers: Capable of negotiating intersections without track switches.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 6
C. Track Intersections, Switches, and Accessories: As required for operation, storage, track configuration, and layout indicated for operable panel partitions, and compatible with partition assembly specified. Fabricate track intersections and switches from steel or aluminum.
1. Curve-and-Diverter Switches: Allow radius turns to divert panels to an auxiliary track. 2. L Intersections: Allow panels to change 90 degrees in direction of travel. 3. T Intersections: Allow panels to pass through or change 90 degrees to another direction
of travel. 4. X Intersections: Allow panels to pass through or change travel direction full circle in 90-
degree increments, and allow one partition to cross track of another. 5. Multidirectional Switches: Adjustable switch configuring track into L, T, or X intersections
and allowing panels to be moved in all pass-through, 90-degree change, and cross-over travel direction combinations.
6. Center carrier stop.
D. Steel Finish: Manufacturer's standard, factory-applied, corrosion-resistant, protective coating unless otherwise indicated.
2.6 ACCESSORIES
A. Storage Pocket Door: Full height at end of partition runs to conceal stacked partition; CUSTOM AS INDICATED ON DRAWINGS. ADD.#2
B. Hinges in finish to match other exposed hardware.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine flooring, floor levelness, structural support, and opening, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of operable panel partitions.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install operable panel partitions and accessories after other finishing operations, including painting, have been completed in area of partition installation.
B. Install panels in numbered sequence indicated on Shop Drawings.
C. Broken, cracked, chipped, deformed, or unmatched panels are not acceptable.
D. Broken, cracked, deformed, or unmatched gasketing or gasketing with gaps at butted ends is not acceptable.
E. Light-Leakage Test: Illuminate one side of partition installation and observe vertical joints and top and bottom seals for voids. Adjust partitions for alignment and full closure of vertical joints
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2
FOLDING PANEL PARTITIONS 102239 - 7
and full closure along top and bottom seals. Perform test and make adjustments before NIC testing.
3.3 ADJUSTING
A. Adjust operable panel partitions, hardware, and other moving parts to function smoothly, and lubricate as recommended by manufacturer.
B. Adjust storage pocket doors to operate smoothly and easily, without binding or warping.
C. Verify that safety devices are properly functioning.
3.4 MAINTENANCE SERVICE
A. Maintenance Service: Beginning at Substantial Completion, maintenance service shall include three months' full maintenance by manufacturer's authorized service representative. Include quarterly preventive maintenance, repair or replacement of worn or defective components, lubrication, cleaning, and adjusting as required for proper operable-partition operation. Parts and supplies shall be manufacturer's authorized replacement parts and supplies.
3.5 DEMONSTRATION
A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain operable panel partitions.
END OF SECTION 102239
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2 – ENTIRE SECTION
WALL AND DOOR PROTECTION 102600 - 1
SECTION 102600 - WALL AND DOOR PROTECTION
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes: 1. Corner guards.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Include construction details, material descriptions, impact strength, dimensions of individual components and profiles, and finishes.
2. Include fire ratings of units recessed in fire-rated walls and listings for door-protection items attached to fire-rated doors.
B. Shop Drawings: For each type of wall and door protection showing locations and extent.
1. Include plans, elevations, sections, and attachment details.
C. Samples for Initial Selection: For each type of impact-resistant wall-protection unit indicated, in each color and texture specified.
D. Samples for Verification: For each type of exposed finish on the following products, prepared on Samples of size indicated below: 1. Corner Guards: 12 inches (300 mm) long. Include example top caps.
1.4 INFORMATIONAL SUBMITTALS
A. Product Certificates: For each type of handrail.
B. Material Certificates: For each type of exposed plastic material.
C. Sample Warranty: For special warranty.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2 – ENTIRE SECTION
WALL AND DOOR PROTECTION 102600 - 2
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: For each type of wall and door protection product to include in maintenance manuals.
1. Include recommended methods and frequency of maintenance for maintaining best condition of plastic covers under anticipated traffic and use conditions. Include precautions against using cleaning materials and methods that may be detrimental to finishes and performance.
1.6 MAINTENANCE MATERIAL SUBMITTALS
A. Furnish extra materials that match products installed and that are packaged with protective covering for storage and identified with labels describing contents.
1. Corner-Guard Covers: Full-size plastic covers of maximum length equal to 2 percent of each type, color, and texture of cover installed, but no fewer than ONE, 96-inch- long unit.
2. Mounting and Accessory Components: Amounts proportional to the quantities of extra materials. Package mounting and accessory components with each extra material.
1.7 DELIVERY, STORAGE, AND HANDLING
A. Store wall and door protection in original undamaged packages and containers inside well-ventilated area protected from weather, moisture, soiling, extreme temperatures, and humidity.
1. Maintain room temperature within storage area at not less than 70 deg F (21 deg C) during the period plastic materials are stored.
2. Keep plastic materials out of direct sunlight. 3. Store plastic wall- and door-protection components for a minimum of 72 hours, or until
plastic material attains a minimum room temperature of 70 deg F (21 deg C).
a. Store corner-guard covers in a vertical position.
1.8 WARRANTY
A. Special Warranty: Manufacturer agrees to repair or replace components of wall-protection units that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Structural failures including detachment of components from each other or from the substrates, delamination, and permanent deformation beyond normal use.
b. Deterioration of metals, metal finishes, plastics, and other materials beyond normal use.
2. Warranty Period: Five years from date of Substantial Completion.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2 – ENTIRE SECTION
WALL AND DOOR PROTECTION 102600 - 3
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Source Limitations: Obtain wall-protection products from single source from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Surface Burning Characteristics: Comply with ASTM E 84 or UL 723; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency.
1. Flame-Spread Index: 25 or less. 2. Smoke-Developed Index: 450 or less.
2.3 CORNER GUARDS
A. Flush-Mounted, Plastic-Cover Corner Guards: Manufacturer's standard, PVC-free assembly consisting of snap-on, resilient plastic cover that is flush with adjacent wall surface, installed over retainer; including mounting hardware; fabricated with 90- or 135-degree turn to match wall condition; full wall height.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Construction Specialties, Inc. b. InPro Corporation (IPC). c. JL Industries, Inc.; a division of the Activar Construction Products Group. d. Korogard Wall Protection Systems; a division of RJF International Corporation. e. Nystrom, Inc.
2. Cover: Extruded rigid plastic, minimum 0.100-inch (2.5-mm) wall thickness; as follows:
a. Profile: Nominal 2-inch- (50-mm-) long leg and 1/4-inch (6-mm) corner radius. b. Height: 8 feet (2.4 m). c. Color and Texture: As selected by Architect from manufacturer's full range.
3. Continuous Retainer: Minimum 0.060-inch- (1.5-mm-) thick, one-piece, extruded aluminum.
4. Retainer Clips: Manufacturer's standard impact-absorbing clips. 5. Aluminum Cove Base: Nominal 4 inches (100 mm) high.
2.4 MATERIALS
A. Plastic Materials: Chemical- and stain-resistant, high-impact-resistant plastic with integral color throughout; extruded and sheet material as required, thickness as indicated.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2 – ENTIRE SECTION
WALL AND DOOR PROTECTION 102600 - 4
B. Polycarbonate Plastic Sheet: ASTM D 6098, S-PC01, Class 1 or Class 2, abrasion resistant; with a minimum impact-resistance rating of 15 ft.-lbf/in. (800 J/m) of notch when tested according to ASTM D 256, Test Method A.
C. Fasteners: Aluminum, nonmagnetic stainless-steel, or other noncorrosive metal screws, bolts, and other fasteners compatible with items being fastened. Use security-type fasteners where exposed to view.
2.5 FABRICATION
A. Fabricate wall and door protection according to requirements indicated for design, performance, dimensions, and member sizes, including thicknesses of components.
B. Factory Assembly: Assemble components in factory to greatest extent possible to minimize field assembly. Disassemble only as necessary for shipping and handling.
C. Quality: Fabricate components with uniformly tight seams and joints and with exposed edges rolled. Provide surfaces free of wrinkles, chips, dents, uneven coloration, and other imperfections. Fabricate members and fittings to produce flush, smooth, and rigid hairline joints.
2.6 FINISHES
A. Protect finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.
B. Appearance of Finished Work: Noticeable variations in same piece are not acceptable. Variations in appearance of adjoining components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine substrates and wall areas, with Installer present, for compliance with requirements for installation tolerances, fire rating, and other conditions affecting performance of the Work.
B. Examine walls to which wall and door protection will be attached for blocking, grounds, and other solid backing that have been installed in the locations required for secure attachment of support fasteners.
1. For wall and door protection attached with adhesive, verify compatibility with and suitability of substrates, including compatibility with existing finishes or primers.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Complete finishing operations, including painting, before installing wall and door protection.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701 ADD.#2 – ENTIRE SECTION
WALL AND DOOR PROTECTION 102600 - 5
B. Before installation, clean substrate to remove dust, debris, and loose particles.
3.3 INSTALLATION
A. Installation Quality: Install wall and door protection according to manufacturer's written instructions, level, plumb, and true to line without distortions. Do not use materials with chips, cracks, voids, stains, or other defects that might be visible in the finished Work.
B. Accessories: Provide splices, mounting hardware, anchors, trim, joint moldings, and other accessories required for a complete installation.
1. Provide anchoring devices and suitable locations to withstand imposed loads.
3.4 CLEANING
A. Immediately after completion of installation, clean plastic covers and accessories using a standard ammonia-based household cleaning agent.
B. Remove excess adhesive using methods and materials recommended in writing by manufacturer.
END OF SECTION 102600
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 1
SECTION 230900 - JCI CONTROL SYSTEMS
PART 1 - GENERAL
1.01 SUMMARY
A. University of Missouri Controls Specification. B. This section contains requirements for, electric and digital control systems as indicated on the
contract drawings.
C. Contractor is responsible for providing, installing and connecting all sensors, control valves, control dampers, electrical components and electrical wiring between these devices and up to the Direct Digital Controller (DDC).
D. DDC controllers consist of Johnson Controls METASYS controllers, type NAE, DX, FEC, IOM,
AHU, VAV, VMA, or UNT controllers. Owner will provide Johnson Controls METASYS controllers for the contractor to install.
E. After all equipment has been installed, wired and piped, Owner will be responsible for all
termination connections at the DDC controller’s and for checking, testing, programming and start-up of the control system. Contractor must be on site at start-up to make any necessary hardware adjustments as required.
F. Once each mechanical system is completely operational under the new control system,
contractor shall make any final connections and adjustments. For controls renovation jobs, contractor shall remove all unused sensors, operators, panels, wiring, tubing, conduit, etc. Owner shall have the option of retaining any removed pneumatic controls.
1.02 RELATED SECTIONS
A. Drawings and general provisions of Contract, including General and Special Conditions apply to work of this section.
1.03 QUALITY ASSURANCE
A. Contractor's Qualifications: 1. Contractor shall be regularly engaged in the installation of digital control systems and
equipment, of types and sizes required. Contractor shall have a minimum of five years experience installing digital control systems. Contractor shall supply sufficient and competent supervision and personnel throughout the project in accordance with General Conditions section 3.4.1 and 3.4.4.
B. Codes and Standards:
1. Electrical Standards: Provide electrical components of control systems which have been UL-listed and labeled, and comply with NEMA standards.
2. NEMA Compliance: Comply with NEMA standards pertaining to components and devices for control systems.
3. NFPA Compliance: Comply with NFPA 90A "Standard for the Installation of Air Conditioning and Ventilating Systems" where applicable to controls and control sequences.
4. NFPA Compliance: Comply with NFPA 70 "National Electric Code."
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 2
1.04 SUBMITTALS
A. Shop Drawings: Submit shop drawings for each control system, containing the following information:
B. Product data for each damper, valve, and control device. C. Schematic flow diagrams of system showing fans, pumps, coils, dampers, valves, and control
devices. D. Label each control device with setting or adjustable range of control. E. Indicate all required electrical wiring. Clearly differentiate between portions of wiring that are
factory-installed and portions to be field-installed. F. Provide details of faces on control panels, including controls, instruments, and labeling. G. Include written description of sequence of operation.
H. Provide wiring diagrams of contractor provided interface and I/O panels.
I. Provide field routing of proposed network bus diagram listing all devices on bus.
PART 2 PRODUCTS
2.01 MATERIALS AND EQUIPMENT
A. Conduit and Raceway: 1. Electrical Metallic Tubing: EMT and fittings shall conform to ANSI C80.3. 2. Surface Metal Raceway and Fittings: Wiremold 500, Ivory, or approved equal. 3. Flexible Metal Conduit: Indoors, per National Electric Code for connection to moving or
vibrating equipment. 4. Liquidtight Flexible Conduit: Outdoors, per National Electric Code for connection to
moving or vibrating equipment. B. Control Valves: Provide factory fabricated electric control valves of type, body material, and
pressure class as indicated on the drawings. Butterfly style control valves are not acceptable except for two position applications. Equip control valves, with proper shutoff rating for each individual application. 1. Steam and Hot Water:
a) Manufacturer: Do not allow KMC valves and actuators. b) Water Service Valves: Equal percentage characteristics. c) Steam Service Valves: Equal percentage characteristics. d) Single Seated Valves: Cage type trim, providing seating and guiding surfaces for
plug on "top and bottom" guided plugs. e) Valve Trim and Stems: Polished stainless steel. f) Packing: Spring-loaded Teflon, self-adjusting. g) Control valves should have a minimum 100 psi close-off rating for chilled water
applications. 2. Hydronic Chilled Water and Heating Water:
a) Hydronic control valves shall be pressure independent. The flow through the valve shall not vary more than +/- 5% due to system pressure fluctuations across the valve in the selected operating range. The control valve shall accurately control
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 3
the flow from 1 to 100% full rated flow. b) The valve bodies shall be of cast iron, steel or bronze and rated for 150 PSI
working pressure. All internal parts shall be stainless steel, steel, Teflon, brass, or bonze.
c) Valves shall be DeltaP Valves manufactured by Flow Control Industries, Belimo P Series, Danfoss AB-QM Series, or approved equal. Belimo EV050 Series is not acceptable.
d) The valves shall have pressure taps across the valve for measuring the pressure drop across the valve. The pressure taps shall have ½-inch extensions for accessibility.
e) Control valves shall be installed with unions or flanges as necessary for easy removal and replacement.
f) Valve Tag shall include the model number, AHU being served, design flow, and maximum flow for that valve.
g) The control valves shall be delivered preset to the scheduled design flow and should be capable of reaching 110% of the design flow to allow for field adjustment for capacity changes.
C. Steam Control Valves
1. General: a) Two-position valves shall have a maximum pressure drop equal to 10% of the inlet
pressure. b) Modulating control valves shall have modified linear characteristics. c) Two modulating control valves in parallel shall have 1/3 – 2/3 capacities sequenced
so that the smaller valve opens first. d) The pressure drop through a modulating control valve with an inlet pressure less
than or equal to 15 psig gauge shall be equal to 80% of the inlet pressure. In no case shall the inlet pressure of the equipment after the valve be less than 2 psig gauge, except for integral face and bypass coils where the inlet pressure after the valve shall not be less than 5 psig gauge.
e) The pressure drop through modulating control valves with inlet pressures greater than 15 psig gauge shall be required to provide outlet pressure of 1 psi above the scheduled or specified inlet pressure of the equipment served.
f) Piping geometry correction factors for Cv ratings shall be used and stated for ball valves, butterfly valves, or non-characterized valves.
2. Two-Position or Modulating (Low Pressure: 15 psi or below): a) Globe 1/2" to 2”:
(1) Design Pressure: 100 psi Design Temperature: 337ºF
(2) Bronze body; stainless steel trim, plug, stem and seat; EPDM or PTFE packing; threaded ends.
b) Globe 2-1/2” to 6”: (1) Design Pressure: 100 psi
Design Temperature: 337ºF (2) Cast iron body; stainless steel trim, plug, stem and seat; EPDM or PTFE
packing; flanged ends.
D. Control Dampers: Ruskin CD-50 or approved equal.
1. Provide dampers with parallel blades for 2- position control. 2. Provide opposed blades for modulating control. 3. Dampers shall be low leakage design with blade and edge seals. 4. Provide multiple sections and operators as required by opening size and sequence of
operations, as indicated on the contract drawings.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 4
E. Electric Actuators: Johnson Controls, Bray, Belimo, TAC or approved equal. KMC actuators are not approved. Size electric actuators to operate their appropriate dampers or valves with sufficient reserve power to provide smooth modulating action or 2-position action as specified. If mixed air AHU has return air, exhaust air and outside air dampers that are not mechanically linked then static safety switch must be installed and wired to safety circuit. Spring return actuators should be provided on heat exchanger control valves or dampers or as specified on the drawings. Control signal shall be 0 to 10 VDC unless otherwise specified on drawings. Actuators with integral damper end switch are acceptable. For VAV reheat valves, actuators shall have a manual override capability to aid in system flushing, startup, and balancing.
F. Air and Hot Water Electronic Temperature Sensors:
1. All electronic temperature sensors shall be compatible with Johnson METASYS systems.
2. Sensors shall be 1,000 ohm platinum, resistance temperature detectors (RTDs) with two wire connections. Duct mounted sensors shall be averaging type. Contractor may install probe type when field conditions prohibit averaging type, but must receive permission from Owner's Representative.
3. Coordinate thermowell manufacturer with RTD manufacturer. Thermowells that are installed by the contractor, but are to have the RTD installed by owner, must be Johnson Controls Inc. series WZ-1000.
G. Electronic Temperature Sensors and Transmitters:
1. Chilled Water, Heating Hot Water, and Steam Temperature Sensors a) General: The RTD/Temperature Transmitter/Thermowell assembly shall come as
a complete assembly from a single manufacturer. The Assembly shall be suitable for use in the accurate measurement of Chilled/Tower/Hot Water and steam temperatures in a mechanical room environment.
b) Calibration: Each RTD must be match calibrated to the Transmitter via NIST traceable calibration standards. Results are to be programmed into the transmitter. Results are to be presented on report as after condition at the specified calibration points. Assembly shall not be approved for installation until Owner has received all factory calibration reports.
c) RTD: (1) RTD type: 2-wire or 3-wire 100 ohm platinum class A (2) Outside Diameter: 0.25 inch (3) Tolerance: +/- 0.06% Type A (4) Stability: +/- 0.1 % over one year. (5) TCR: 0.00385 (ohm/ohm/oC). (6) RTD shall be tip sensitive. (7) Resistance vs. Temperature table for the RTD must be provided to the
Owner. d) Transmitter:
(1) Transmitter shall be match calibrated to the RTD and assembled as a matched pair.
(2) Type: 2 wire (loop powered) (3) Input: 2 or 3 wire 100 ohm platinum class A or class B RTD (4) Output: Output shall be a 4-20 mA signal linear to temperature (5) Calibrated Span:
(a) Chilled Water: 30 oF to 130 oF. (b) Tower Water: 30 oF to 130 oF. (c) Hot Water: 100 oF to 250 oF. (d) Steam: 150 oF to 450 oF
(6) Calibration Accuracy, including total of all errors, of the Transmitter & RTD matched pair over the entire span shall be within +/- 0.2% of the calibrated span or +/- 0.18 oF, whichever is greater.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 5
(7) Supply Voltage: 24 VDC. (8) Ambient Operating Temp.: 32 to 122 oF (9) Epoxy potted for moisture resistance. (10) Mounting: Transmitter shall be mounted in the RTD connection head.
e) Thermowell (1) Thermowell shall be suitable for immersion in chilled/hot water and steam. (2) Thermowell shall be reduced tip. (3) Thermowell shall be one piece stainless steel machined from solid bar stock. (4) Thermowell shall have 1/2” NPT process connection to pipe thred-o-let. (5) Thermowell Insertion depth shall be ½ the inside pipe diameter but not to
exceed 10”. f) Assembly:
(1) Assembly configuration: Spring loaded RTD with thermowell-double ended hex-connection head.
(2) Connection head shall be cast aluminum with chain connecting cap to body, have 1/2” NPT process and 3/4” NPT conduit connections, and a sealing gasket between cap and body.
g) RTD/Temperature Transmitter/Thermowell assembly shall be the following or approved equal: (1) Manufacturer: Pyromation, Inc. (2) Chilled Water: RAF185L-S4C[length code]08-SL-8HN31,TT440-385U-S(30-
130)F with calibration SMC(40,60)F (3) Tower Water: RAF185L-S4C[length code]08-SL-8HN31,TT440-385U-
S(5130)F with calibration SMC(55,85)F (4) Hot Water: RAF185L-S4C[length code]08T2-SL-8HN31,TT440-385U-S(100-
250)F with calibration SMC(140,180)F (5) team: RAT185H-S4C[length code]08T2-SL-8HN31,TT440-385U-S(150-
450)F with calibration SMC(300,350)F
H. Occupant Override: Provide wall mounted occupant override button in locations shown on drawings.
I. Low Limit Controllers: Provide unit-mounted low limit controllers, of rod-and-tube type, with an
adjustable set point and a manual reset. Capillary shall be of adequate length to horizontally traverse face of cooling coil every 12". Multiple low limit controllers may be required for large coils. Controller shall have an extra set of contactors for connection to control panel for alarm status. Locate the thermostat case and bellows where the ambient temperature is always warmer than the set point. 1. Freeze Stats: Johnson Controls model A70HA-1 or approved equal.
J. Humidistats: Humidistats must be contamination resistant, capable of ±2% RH accuracy, have
field adjustable calibration and provide a linear proportional signal. 1. HD20K-T91 or equivalent.
K. Humidity High Limit
1. Multi-function device that can function as a high limit or proportional override humidity controller, as stand-alone proportional controller, or a stand-alone two-position controller. a) Johnson Controls TRUERH HL-67N5-8N00P or approved equal.
L. Carbon Dioxide Sensor:
1. Wall Mount: ACI Model ESENSE-R. 2. Duct Mount: ACI Model ESENSE-D.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 6
M. Fan/Pump Status: Status points for fan or pump motors with a VFD must be connected to the terminal strip of the VFD for status indication. Current switches: Current switches are required for fan and pump statuses that are not connected to a VFD. The switches must have an adjustable trip setpoint with LED indication and be capable of detecting broken belts or couplings. Units shall be powered by monitored line, UL listed and CE certified, and have a five year warranty. 1. Kele, Hawkeye or approved equal.
N. Relays Used for Fan and Pump Start/Stop: Must have LED indication and be mounted
externally of starter enclosure or VFD. 1. Kele, RIBU1C or approved equal.
O. Power Supply Used to Provide Power to Contractor-Provided Control Devices: Shall have
adjustable DC output, screw terminals, overload protection and 24 VAC and 24 VDC output. 1. Kele, DCPA-1.2 or approved equal.
P. Pressure Differential Switch:
1. Fans: NECC model DP222 or approved equal. Q. Differential Pressure Transmitter: Provide units with linear analog 4-20mA output proportional
to differential pressure, compatible with the Johnson METASYS Systems. 1. Water: Units shall be wet/wet differential pressure capable of a bi-directional pressure
range of +/- 50 psid. Accuracy shall be +/- 0.25% full scale with a compensated temperature range of 30 to 150 deg F and a maximum working pressure of 250 psig. Install transmitter in a pre-manufactured bypass valve assembly with shut-off valves, vent valves and a bypass valve, all enclosed in a NEMA 1 enclosure. a) Setra model 230 with Kele model BVA-5 bypass valve assembly, or approved
equal. 2. Air: Units shall be capable of measuring a differential pressure of 0 to 5 in. WC.
Accuracy shall be +/- 1.0% full scale with a compensated temperature range of 40 to 149 deg F and a maximum working pressure of 250 psig. a) Setra model 267, or approved equal. b) Shall be installed in control panel and piped 2/3 down the duct unless shown
otherwise or approved by owners representative.
R. Building Static Pressure: Transducer shall utilize a ceramic capacitive sensing element to provide a stable linear output over the specified range of building static pressure. Transducer shall be housed in a wall-mounted enclosure with LCD display. Transducer shall have the following capabilities: 1. Input Power: 24 VAC 2. Output: 0-10 VDC 3. Pressure Range: -0.25 to +0.25 inches w.g. 4. Display: 3-1/2 digit LCD, displaying pressure in inches w.g. 5. Accuracy: +/- 1.0% combined linearity and hysteresis 6. Temperature effect: 0.05% / deg C 7. Zero drift (1 year): 2.0% max 8. Zero adjust: Push-button auto-zero and digital input 9. Operating Environment: 0 to 140 deg F, 90% RH (non-condensing) 10. Fittings: Brass barbs, 1/8” O.D. 11. Enclosure: High-impact ABS plastic 12. Outdoor Sensing Tube Enclosure: UV stabilized thermoplastic or aluminum “can”
enclosure to shield outdoor pressure sensing tube from wind effects. 13. Transducer shall be Veris Industries Model PXPLX01S, equivalent from Setra, or
approved equal.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 7
S. High Static Pressure Limit Switch: Provide pressure high limit switch to open contact in fan circuit to shut down the supply fan when the inlet static pressure rises above the set point. Provide with an adjustable set point, a manual reset button, 2 SPST (normally closed) contacts, and ¼” compression fittings. 1. Kele model AFS-460-DDS, or approved equal.
T. Airflow/Temperature Measurement Devices: 1. Provide airflow/temperature measurement devices where indicated on the plans. Fan inlet
measurement devices shall not be substituted for duct or plenum measurement devices indicated on the plans.
2. The measurement device shall consist of one or more sensor probe assemblies and a single, remotely mounted, microprocessor-based transmitter. Each sensor probe assembly shall contain one or more independently wired sensor housings. The airflow and temperature readings calculated for each sensor housing shall be equally weighted and averaged by the transmitter prior to output. Pitot tubes and arrays are not acceptable. Vortex shedding flow meters are not acceptable.
3. All Sensor Probe Assemblies a) Each sensor housing shall be manufactured of a U.L. listed engineered
thermoplastic. b) Each sensor housing shall utilize two hermetically sealed, bead-in-glass thermistor
probes to determine airflow rate and ambient temperature. Devices that use “chip” or diode case type thermistors are unacceptable. Devices that do not have 2 thermistors in each sensor housing are not acceptable.
c) Each sensor housing shall be calibrated at a minimum of 16 airflow rates and have an accuracy of +/-2% of reading over the entire operating airflow range. Each sensor housing shall be calibrated to standards that are traceable to the National Institute of Standards and Technology (NIST). (1) Devices whose accuracy is the combined accuracy of the transmitter and
sensor probes must demonstrate that the total accuracy meets the performance requirements of this specification throughout the measurement range.
d) The operating temperature range for the sensor probe assembly shall be -20° F to 160 F. The operating humidity range for the sensor probe assembly shall be 0-99% RH (non-condensing).
e) Each temperature sensor shall be calibrated at a minimum of 3 temperatures and have an accuracy of +/-0.15° F over the entire operating temperature range. Each temperature sensor shall be calibrated to standards that are traceable to the National Institute of Standards and Technology (NIST).
f) Each sensor probe assembly shall have an integral, U.L. listed, plenum rated cable and terminal plug for connection to the remotely mounted transmitter. All terminal plug interconnecting pins shall be gold plated.
g) Each sensor assembly shall not require matching to the transmitter in the field. h) A single manufacturer shall provide both the airflow/temperature measuring
probe(s) and transmitter at a given measurement location. 4. Duct and Plenum Sensor Probe Assemblies
a) Sensor housings shall be mounted in an extruded, gold anodized, 6063 aluminum tube probe assembly. Thermistor probes shall be mounted in sensor housings using a waterproof marine grade epoxy resin. All wires within the aluminum tube shall be Kynar coated.
b) The number of sensor housings provided for each location shall be as follows: (1) Area (sq.ft.) Sensors
<2 4 2 to <4 6 4 to <8 8
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 8
8 to <16 12 >=16 16
c) Probe assembly mounting brackets shall be constructed of 304 stainless steel. Probe assemblies shall be mounted using one of the following options: (1) Insertion mounted through the side or top of the duct. (2) Internally mounted inside the duct or plenum. (3) Standoff mounted inside the plenum.
d) The operating airflow range shall be 0 to 5,000 FPM unless otherwise indicated on the plans.
5. Fan Inlet Sensor Probe Assemblies a) Sensor housings shall be mounted on 304 stainless steel blocks. b) Mounting rods shall be field adjustable to fit the fan inlet and constructed of nickel
plated steel. c) Mounting feet shall be constructed of 304 stainless steel. d) The operating airflow range shall be 0 to 10,000 FPM unless otherwise indicated on
the plans. 6. Transmitters
a) The transmitter shall have a 16 character alpha-numeric display capable of displaying airflow, temperature, system status, configuration settings and diagnostics. Configuration settings and diagnostics shall be accessed through a pushbutton interface on the main circuit board. Airflow shall be field configurable to be displayed as a velocity or a volumetric rate.
b) The transmitter shall be capable of independently monitoring and averaging up to 16 individual airflow and temperature readings. The transmitter shall be capable of displaying the airflow and temperature readings of individual sensors on the LCD display.
c) The transmitter shall have a power switch and operate on 24 VAC (isolation not required). The transmitter shall use a switching power supply fused and protected from transients and power surges.
d) All interconnecting pins, headers and connections on the main circuit board, option cards and cable receptacles shall be gold plated.
e) The operating temperature range for the transmitter shall be -20° F to 120° F. The transmitter shall be protected from weather and water.
f) The transmitter shall be capable of communicating with the host controls using one of the following interface options: (1) Linear analog output signal: Field selectable, fuse protected and isolated, 0-
10VDC and 4-20mA (4-wire). (2) RS-485: Field selectable BACnet-MS/TP, ModBus-RTU and Johnson Controls
N2 Bus. (3) 10 Base-T Ethernet: Field selectable BACnet Ethernet, BACnet-IP, ModBus-
TCP and TCP/IP. (4) LonWorks Free Topology.
g) The transmitter shall have an infra-red interface capable of downloading individual sensor airflow and temperature data or uploading transmitter configuration data to a handheld PDA (Palm or Microsoft Pocket PC operating systems).
7. The measuring device shall be UL listed as an entire assembly. 8. The manufacturer’s authorized representative shall review and approve placement and
operating airflow rates for each measurement location indicated on the plans. A written report shall be submitted to the consulting mechanical engineer if any measurement locations do not meet the manufacturer’s placement requirements.
9. Manufacturer a) Primary flow elements, sensors, meters and transducers shall be EBTRON, Inc.
Model GTx116-P and GTx116-F or approved equal.
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 9
b) The naming of any manufacturer does not automatically constitute acceptance of this standard product nor waive their responsibility to comply totally with all requirements of the proceeding specification.
U. Electrical Requirements: Provide electric switches, electrical devices, and relays that are UL-
listed and of type which meet current and voltage characteristics of the project. All devices shall be of industrial/ commercial grade or better. Residential types will be rejected. 1. EP Switches: Landis & Gyr Powers, Inc. Series 265 - Junction Box Type or approved
equal. 2. Relays: Relays shall have an LED status indicator, voltage transient suppression,
Closed-Open-Auto switch, plastic enclosure, and color coded wires. Kele model RIBU1C or approved equal.
PART 3 EXECUTION
3.01 INSTALLATION OF CONTROL SYSTEMS
A. General: Install systems and materials in accordance with manufacturer’s instructions, roughing-in drawings and details shown on drawings.
B. Raceway: Raceway is to be installed in accordance with the National Electric Code. Use of
flexible metal conduit or liquidtight flexible conduit is limited to 36" to connect from EMT to devices subject to movement. Flexible raceway is not to be used to compensate for misalignment of raceway during installation.
C. Control Wiring: Install control wiring in raceway, without splices between terminal points,
color-coded. Install in a neat workmanlike manner, securely fastened. Install in accordance with National Electrical Code. 1. Install circuits over 25-volt with color-coded No. 12 stranded wire. 2. Install electronic circuits and circuits under 25-volts with color-coded No. 18 stranded
twisted shielded pair type conductor. 3. N2 communications bus wire shall be 18 AWG, plenum rated, stranded twisted shielded,
3 conductor, with blue outer casing, descripted as 18-03 OAS STR PLNM NEON BLU JK distributed by Windy City Wire, constructed by Cable-Tek, or approved equivalent. a) Metastat wiring shall be minimum 20 AWG, plenum rated, stranded, 8 conductor
stranded wire. 4. FC communications bus wire shall be 22 AWG, plenum rated, stranded twisted shielded,
3 conductor, with blue outer casing, descripted as 22-03 OAS STR PLNM NEON BLU JK distributed by Windy City Wire, constructed by Cable-Tek, or approved equivalent. a) Network sensor wiring (SA Bus) shall be 22 gauge plenum rated stranded twisted
wire, 4 conductor. 5. All control wiring at control panel shall be tagged and labeled during installation to assist
owner in making termination connections at control panel. Label all control wires per bid documents.
D. All low voltage electrical wiring shall be run as follows: 1. Route electrical wiring in concealed spaces and mechanical rooms whenever possible. 2. Provide EMT conduit and fittings in mechanical rooms and where indicated on drawings. 3. Low voltage electrical wiring routed above acoustical ceiling is not required to be in
conduit, but wire must be plenum rated and properly supported to building structure. 4. Provide surface raceway, fittings and boxes in finished areas where wiring cannot be run
in concealed spaces. Route on ceiling or along walls as close to ceiling as possible. Run raceway parallel to walls. Diagonal runs are not permitted. Paint raceway and fittings to match existing conditions. Patch/repair/paint any exposed wall penetrations to
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 10
match existing conditions. E. All devices shall be mounted appropriately for the intended service and location.
1. Adjustable thermostats shall be provided with base and covers in occupied areas and mounted 48" above finished floor to the top of the device. Tubing and/or wiring shall be concealed within the wall up to the ceiling where ever possible. Surface raceway may only be used with approval of Owners Representative. Wall mounted sensors such as CO2, RH, and non-adjustable temperature sensors shall be mounted 54” above finished floor. Duct mounted sensors shall be provided with mounting brackets to accommodate insulation. Mounting clips for capillary tubes for averaging sensors are required.
2. All control devices shall be tagged and labeled for future identification and servicing of control system.
3. Preheat and mixed air discharge sensors must be of adequate length and installed with capillary tube horizontally traversing face of coil, covering entire coil every 24 inches bottom to top.
4. All field devices must be accessible or access panels must be installed. F. Install magnehelic pressure gage across each air handling unit filter bank. If the air handling
unit has a prefilter and a final filter, two magnehelic pressure gages are required. 3.02 ADJUSTING AND START-UP
A. Start-Up: Temporary control of Air Handling Units shall be allowed only if approved by the owner’s representative to protect finishes, etc., AHUs may be run using caution with temporary controls installed by contractor early in the startup process. All safeties including a smoke detector for shut down must be operational. Some means of discharge air control shall be utilized and provided by the contractor such as a temporary temperature sensor and controller located and installed by the Contractor.
B. The start-up, testing, and adjusting of digital control systems will be conducted by owner. Once all items are completed by the Contractor for each system, Contractor shall allow time in the construction schedule for owner to complete commissioning of controls before project substantial completion. This task should be included in the original schedule and updated to include the allotted time necessary to complete it. As a minimum, the following items are required to be completed by the Contractor for Owner to begin controls commissioning. 1. Process Control Network
a) The control boards and enclosures need to be installed in the mechanical rooms. b) The fiber optic conduit and box for the process control network needs to be
installed. Once in place, Owner needs to be contacted so the length of the owner provided fiber cable can be determined and ordered, if required. Coordinate with Owner to schedule the pull in and termination of the fiber cable. Power should be in place at that time. (Fiber for the process control network is required to allow metering of utilities prior to turn on.)
2. Heating System a) Pumps, heat exchangers, steam pressure reducing station, piping, control valves,
steam and/or hot water meter, feeder conduit and wire, VFDs, control panels and control wiring installed in the attic. The house keeping pads must be poured before pump operation. All must be in place in working order (pumps aligned, VFDs set up by vendor, motors checked for rotation, steam regulators set to required pressure, condensate pumps operational, heating system ready to circulate (all piping pressure tested, flushed, and insulated) with differential pressure sensors in place.
3. Cooling System a) Pumps, piping, control valves, feeder conduit and wire, VFDs, control panels and
control wiring installed in the mechanical room. The house keeping pads must be
UNIVERSITY OF MISSOURI 16253 MEMORIAL STUDENT UNION - MAINTENANCE REPAIRS AND 2ND FLOOR RENOVATION MU PROJECT #CP151701
JCI CONTROL SYSTEMS 23 09 00 - 11
poured before pump operation. All must be in place in working order (pumps aligned, VFDs set up by vendor, motors checked for rotation, cooling system ready to circulate (all piping pressure tested, flushed, and insulated) with differential pressure sensors in place.
4. VAVs-First Pass a) Power, (FC or N2 bus), and control wire installed before owner can make first
commissioning pass. First pass includes installation of VAV controller, termination of power, control and network communication wiring.
5. Air Handlers a) Prior to owner commissioning, at a minimum, the following items shall be
complete: Power wiring, motor rotation check, fire/smoke dampers open, control wiring including all safeties, IO cabinet, air handler cleaned, and filters installed as required. To protect the systems from dirt, outside air with no return will be used until the building is clean enough for return air operation.
6. VAVs-Second Pass a) After the air handlers are running and under static pressure control and the heating
water system is operating, a second pass can be made on the VAVs to download the control program and commission controllers to verify the VAV dampers, thermostat, and reheat control valves are working properly.
7. Exhaust Systems a) Exhaust fans need to be operational and under control before commissioned.
8. Some balance work can be done alongside the control work as long as areas are mostly complete and all diffusers are in place.
3.03 CLOSEOUT PROCEDURES
A. Contractor shall provide complete diagrams of the control system including flow diagrams with each control device labeled, a diagram showing the termination connections, and an explanation of the control sequence. The diagram and sequence shall be framed and protected by glass and mounted next to controller.
B. Contractor shall provide as built diagram of network bus routing listing all devices on bus, once wiring is complete prior to scope completion.
END OF SECTION 23 09 00
UP
UP
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
D04
D04
D10
D11
D11
D19
D22
D12D12
D12D12
D19
D22
D19
D22
D19
D22
D19
D22
D09
D09
D19
D22
D07
D23
D19
D19
D19
D19
D19
D22
D22
D22
D22D22
D19
D22
D06
D19
D22
D08
D08
D20
D21
D23
D20
D21
D23
D24
D19
D22
D19
D22
D19
D22
D19
D22
D06
D19
D22
D19
D22
D19
D22
D23
D09
D09
D09
D19
D22
D19
D22
D19
D22
D19
D22
D22
10.5
12
D11
EXISTING DOOR TO REMAIN
EXISTING DOOR - TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING PARTITION TO BE DEMOLISHED
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:3
4 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Second Floor DemoPlan - North Wing
D102N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"D102N
1 Second Floor Demolition Plan - North Wing
DEMOLITION LEGEND
0' 4' 8' 16' 32'
DEMOLITION PLAN KEYED NOTES
D04 REMOVE EXISTING DOOR AND FRAME.
D06 REMOVE PORTION OF MASONRY WALL FOR NEW WINDOWS
D07 REMOVE EXISTING CONCRETE STAIR
D08 REMOVE ALL PLUMBING FIXTURES
D09 REMOVE FOLDABLE PARTITIONS
D10 REMOVE EXISTING RTU - SEE MECHANICAL
D11 REMOVE EXISTING ROOFING MEMBRANE SYSTEM.
D12 REMOVE EXISTNG STRUCTURAL COLUMN. COORDINATE WITH NEWSTRUCTURAL WORK.
D19 REMOVE EXISTING CARPET/VCT FLOORING AND VINYL BASE
D20 REMOVE CERAMIC TILE FLOOR AND BASE.
D21 REMOVE CERAMIC WALL TILE.
D22 REMOVE SUSPENDED LAY-IN CEILING SYSTEM.
D23 REMOVE DRYWALL CEILING SYSTEM.
D24 EXISTING SHAFT TO REMAIN.
GENERAL DEMOLITION NOTES
A COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTIONSHOWN ELSEWHERE IN THE DRAWINGS. DUE CARE IS TO BETAKEN TO AVOID DAMAGE TO ADJACENT AREAS TO REMAIN.
B ERIFICATION OF THE LOCATION OF ALL UNDERGROUND UTILITIESIS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR ANDSHALL BE LOCATED PRIOR TO ANY GRADING OR DEMOLITION.
C CONTRACTOR TO PROVIDE NECESSARY PROTECTION TO ALLEXISTING TO REMAIN AND NEW CONSTRUCTION
D UNLESS NOTED OTHERWISE, ALL PARTITIONS INDICATED FORREMOVAL SHALL BE REMOVED TO UNDERSIDE OF STRUCTUREABOVE.
E NOT USED.
F SEE MECHANICAL, ELECTRICAL, PLUMBING, AND FIREPROTECTION SHEETS FOR DEMOLITION OF THIS SCOPE.
G NOT USED.
H NOT USED.
I PARTITIONS TO BE DEMOLISHED SHALL INCLUDE ASSOCIATEDBRACING, DOORS, FRAMES, HARDWARE, BASE, ETC. IN THEIRENTIRETY
J REMOVE ALL WINDOW COVERINGS, WINDOW BLIND, ETC. ANDTHEIR ASSOCIATED HARDWARE/MOUNTING BRACKETS.
K CONTRACTOR TO PROVIDE DUST CONTROL PARTITIONS TOPREVENT THE SPREAD OF DUST TO OCCUPIED PORTIONS OF THEBUILDING. CONTRACTOR TO PROVIDE MEASURES TO PROTECTBUILDING OCCUPANTS DURING CONSTRUCTION. SEE SPECSECTION 024119
L REMOVE SECONDARY DRYWALL CEILING ABOVE FINISH CEILINGSYSTEMS THROUGHOUT SECOND FLOOR NORTH WING.
No. Description Date
2 Addendum 2 12.14.17
2
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
SLO
PE
FLA
T
D17D17D17D26
D11
D18D18 D14D14
D18
D28
D17D17D17D17
D18 D18
10.5
D18D18 D14D14
EXISTING DOOR TO REMAIN
EXISTING DOOR - TO BE DEMOLISHED
EXISTING PARTITION TO REMAIN
EXISTING PARTITION TO BE DEMOLISHED
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:3
9 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Roof Demo Plan -North Wing
D104
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"D104
1 Roof Demolition Plan - North Wing
DEMOLITION LEGEND
0' 4' 8' 16' 32'
DEMOLITION PLAN KEYED NOTES
D11 REMOVE EXISTING ROOFING MEMBRANE SYSTEM.
D14 REMOVE EXISTING SLATE ROOF AND STRUCTURE. SALVAGE 200MINIMUM EXISTING SLATE FOR DELIVERY TO OWNER.
D17 REMOVE ROOF AND STRUCTURE.
D18 PORTION OF SLATE ROOF STRUCTURE TO REMAIN.
D26 EXISTING ROOF TO REMAIN.
D28 REMOVE EXISTING MODIFIED BIT ROOF SYSTEM
GENERAL DEMOLITION NOTES
A COORDINATE DEMOLITION WORK WITH NEW CONSTRUCTIONSHOWN ELSEWHERE IN THE DRAWINGS. DUE CARE IS TO BETAKEN TO AVOID DAMAGE TO ADJACENT AREAS TO REMAIN.
B ERIFICATION OF THE LOCATION OF ALL UNDERGROUND UTILITIESIS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR ANDSHALL BE LOCATED PRIOR TO ANY GRADING OR DEMOLITION.
C CONTRACTOR TO PROVIDE NECESSARY PROTECTION TO ALLEXISTING TO REMAIN AND NEW CONSTRUCTION
D UNLESS NOTED OTHERWISE, ALL PARTITIONS INDICATED FORREMOVAL SHALL BE REMOVED TO UNDERSIDE OF STRUCTUREABOVE.
E NOT USED.
F SEE MECHANICAL, ELECTRICAL, PLUMBING, AND FIREPROTECTION SHEETS FOR DEMOLITION OF THIS SCOPE.
G NOT USED.
H NOT USED.
I PARTITIONS TO BE DEMOLISHED SHALL INCLUDE ASSOCIATEDBRACING, DOORS, FRAMES, HARDWARE, BASE, ETC. IN THEIRENTIRETY
J REMOVE ALL WINDOW COVERINGS, WINDOW BLIND, ETC. ANDTHEIR ASSOCIATED HARDWARE/MOUNTING BRACKETS.
K CONTRACTOR TO PROVIDE DUST CONTROL PARTITIONS TOPREVENT THE SPREAD OF DUST TO OCCUPIED PORTIONS OF THEBUILDING. CONTRACTOR TO PROVIDE MEASURES TO PROTECTBUILDING OCCUPANTS DURING CONSTRUCTION. SEE SPECSECTION 024119
L REMOVE SECONDARY DRYWALL CEILING ABOVE FINISH CEILINGSYSTEMS THROUGHOUT SECOND FLOOR NORTH WING.
No. Description Date
2 Addendum 2 12.14.17
2
UP
UP
5
A200
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N231AMen
N235Jan
N232AWomen
N234Elec/AV
N201A
MeetingRoom 1
N201B
MeetingRoom 2
N201C
MeetingRoom 3
N204
MeetingRoom 4
N214A
MeetingRoom 5
N214B
MeetingRoom 6
N214C
MeetingRoom 7
N214D
MeetingRoom 8
N214E
MeetingRoom 9
N222Storage
N221Catering
N205Storage
DN
UP
N233Family
CN201APre-function
N234AI.T.
A500
1
A500
2
A5003B
107
107
101101
102
113
113
112
112
113
114
114114 114
114
116
10' - 0"1' - 2 5/8"
12
' - 1
0"
10' - 10" 1' - 8 1/8"
CN202Corridor
CN204Corridor
CN203Corridor
CN200Corridor
10.5
12
A500
4
A600
3
CN201Corridor
N230Clos.
SN200CStairs
N247Break
SN200BStair 1
N231Vest
N232Vest
SN200DStair 2
SN200EStairs
SN200E
N214D
N214E
N2
14C
1
N2
14C
2
N2
14
B1
N2
14
B2
N2
14A
1
N214A2
N2
21
N2
22
N2
35
SN200D
N2
30
N2
01A
1
N2
01A
2
N2
01
B1
N2
01
B2
N2
01C
1
N231N232
N2
34
N2
34A
N2
33
SN200B
N2
01C
2
N2
04A
N2
05
N2
04
B
N247
N204C
4
A200
6
A200
E3
E3
E6
E6 E3E3
A3
A3
A3
A3.1HR
D3C3
A3
A3 A3
A6
A3
E3
A3 A3
A3
A3
A3
A3
A3
C3
C3
C3
C3
C3
C3 C3
C3
A3.1HR
A800
12
TYP
A800
17
119
A500
3AEN200WElevator
C3
C3
C3
C3
C3
SN200B1Room
A500 3
4 7
/8"
C3
114
A800
11
112
1' -
4"
G41HR
G41HR
G41HR
G41HR
4 7/8" 5' - 1 1/2"4 7/8"
7' - 2 1/8"
1' - 4"
C3C3
7' - 4"
7' - 4"
4' - 0"
A800
14
123
123
A900
16Sim
A900
16Sim
A900
17Sim
124
124
128
A500
11
7' - 1 1/8"10
' - 0
"6
' - 6
1/8
"
EQ. EQ.EQ. EQ.
EQ. EQ.
1' - 0" 1' - 0"
CG
CG
CG
CG
CG CG CG CGCG CG CG
CGCG
CG CG CG
CG
CG
CG
CG
CG
CG
CGCG
CG
CG
CG
CG
C3
129
A800
13A800
13
A800
13A800
13A800
13
107
EXISTING DOOR TO REMAIN
NEW DOOR IN EXISTING PARTITION
EXISTING PARTITION TO REMAIN
NEW PARTITION
NEW DOOR AND PARTITION
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
1:4
7 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Second Floor Plan -North Wing
A102N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"A102N
1 Second Floor Plan - North Wing
FLOOR PLAN KEYED NOTES
101 NEW EXTERIOR WALL - STONE VENEER WITH CMU BACKUP
102 NEW MRL TRACTION ELEVATOR
107 NEW EPDM ROOF SYSTEM.
112 NEW FIRE RATED GLAZING SYSTEM.
113 NEW METAL MESH 42" H. GUARDRAIL ATTACHED TO EXISTING CENTERRAILINGS LOCATIONS. SEE SHEET A600
114 NEW HANGING ACOUSTICAL FOLDING PARTITION.
116 FLOOR INFILL AT EXISTING STAIR OPENING - SEE STRUCTURAL
119 NEW ELEVATOR CAB FLOORING, WALL PANELS, AND CEILING. SEESPECS AND FINISH LEGEND.
123 REPAIR ROOF DECK WHERE MECHANICAL EQUIPMENT HAS BEENREMOVED - SEE STRUCTURAL.
124 FIRE EXTIGUISHER CABINET - RECESSED
128 EXISTING STONE VENEER - FACE WITH PLYWOOD PRIOR TOINSTALLING ROOF MEMBRANE.
129 EXTEND GUARDRAIL TO WALL AT TOP LANDING.
FLOOR PLAN LEGEND
0' 4' 8' 16' 32'
No. Description Date
2 Addendum 2 12.14.17
FLOOR PLAN GENERAL NOTES
A ALL INTERIOR DIMENSIONS SHALL BE TO FACE OF FINISH ANDEXTERIOR DIMENSIONS SHALL TO BE OUTSIDE FACE OF STUD, U.N.O.
B ALL DOORS SHALL BE 4" OFF ADJACENT WALL AT HINGE JAMB AND 18"CLEAR FROM PERPENDICULAR WALL AT STRIKE JAMB, U.N.O.
C REFER TO LIFE SAFETY PLANS FOR REQUIRED RATED CONSTRUCTIONAS IT RELATES TO FIRESTOPPING, FIRE SAFING AND DAMPERLOCATIONS
D PROVIDE RATED GYPSUM BOARD BEHIND SEMI-RECESSED FIXTURESIN RATED WALLS AND CEILINGS
E PROVIDE DAMPERS AS REQUIRED TO MAINTAIN RATEDCONSTRUCTION. SEE MECH.
F PROVIDE GYPSUM BOARD CONTROL JOINTS IN WALLS AND CEILINGSAT SPACING RECOMMENDED BY GYPSUM BOARD ASSOCIATION (30'-0"MAX. INTERVALS IN CONTINUOUS DRYWALL SPANS). LOCATE AT ONESIDE OF DOOR OPENING (BOTH SIDES OF PARTITION), U.N.O. ONFLOOR PLANS AND REFLECTED CEILING PLANS.
G REFER TO EXTERIOR ELEVATIONS FOR BUILDING ENVELOPEINFORMATION.
H PATCH ALL WALLS AND CEILINGS WHERE EXISTING FIRE ALARMDEVICES HAVE BEEN REMOVED AND NOT REPLACED IN THE SAMELOCATION.
J PATCH ALL WALLS WHERE FIRE HOSE CABINETS HAVE BEENREMOVED.
2
5
A200
2
A200
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
1
A200
107
107
109109
107
108
107107
10.5
3
A200
4
A200
6
A200
7
A200
4
A700
TYP
120
108108
108
HIGH
HIG
H
HIGH
HIG
HH
IGH
HIG
H
HIGH
HIGH
HIGH
123
125125
126 126
126
126
126
2
A104N
3
A104N
3
A104N
Sim
127
126
107
HIG
H
16
A700
130
131
SHEET METAL CAP
ROOF MEMBRANE
EXISTING CURB
EPDM ROOF SYSTEM
6"
6"
6"
REINSTALL SLATE TILES
EPDM ROOF SYSTEM
EXISTING ROOF TRUSS
SELF ADHEREING SHEET UNDERLAYMENT ON EXISTING SHEATHING ON EXISTING FRAMING. - VERIFY CONDITION OF EXISTING SHEATHING AND FRAMING
EXTEND MEMBRANE 18" MIN.UNDER SLATE.
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
1:5
4 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Roof Plan - NorthWing
A104N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"A104N
1 Roof Plan - North Wing
FLOOR PLAN KEYED NOTES
107 NEW EPDM ROOF SYSTEM.
108 EXISTING SLATE ROOF TO REMAIN
109 NEW ROOF STRUCTURE WITH EPDM ROOF SYSTEM
120 ROOF WALKWAY PADS
123 REPAIR ROOF DECK WHERE MECHANICAL EQUIPMENT HAS BEENREMOVED - SEE STRUCTURAL.
125 REMOVE BOTTOM 4 ROWS OF SLATE TO ALLOW INSTALLATION OFEPDM ROOF. REPLACE SLATE TILES AFTER INSTALLATION.
126 MAINTAIN EXISTING LIGHTS THROUGHOUT CONSTRUCTION.REINSTALL CONDUIT AFTER ROOF WORK IS COMPLETE. COORDINATEWITH ELECTRICAL DRAWINGS.
127 MAINTAIN EXISTING ROOF ELEVATION DIVIDER. RE-ROOF ANDPROVIDE NEW SHEET METAL CAP
130 SCUPPER
131 ROOF LADDER
0' 4' 8' 16' 32'
No. Description Date
2 Addendum 2 12.14.17
1 1/2" = 1'-0"A104N
2 ROOF DIVIDER DETAIL
1 1/2" = 1'-0"A104N
3 SLATE ROOF DETAIL
FLOOR PLAN GENERAL NOTES
A ALL INTERIOR DIMENSIONS SHALL BE TO FACE OF FINISH ANDEXTERIOR DIMENSIONS SHALL TO BE OUTSIDE FACE OF STUD, U.N.O.
B ALL DOORS SHALL BE 4" OFF ADJACENT WALL AT HINGE JAMB AND 18"CLEAR FROM PERPENDICULAR WALL AT STRIKE JAMB, U.N.O.
C REFER TO LIFE SAFETY PLANS FOR REQUIRED RATED CONSTRUCTIONAS IT RELATES TO FIRESTOPPING, FIRE SAFING AND DAMPERLOCATIONS
D PROVIDE RATED GYPSUM BOARD BEHIND SEMI-RECESSED FIXTURESIN RATED WALLS AND CEILINGS
E PROVIDE DAMPERS AS REQUIRED TO MAINTAIN RATEDCONSTRUCTION. SEE MECH.
F PROVIDE GYPSUM BOARD CONTROL JOINTS IN WALLS AND CEILINGSAT SPACING RECOMMENDED BY GYPSUM BOARD ASSOCIATION (30'-0"MAX. INTERVALS IN CONTINUOUS DRYWALL SPANS). LOCATE AT ONESIDE OF DOOR OPENING (BOTH SIDES OF PARTITION), U.N.O. ONFLOOR PLANS AND REFLECTED CEILING PLANS.
G REFER TO EXTERIOR ELEVATIONS FOR BUILDING ENVELOPEINFORMATION.
H PATCH ALL WALLS AND CEILINGS WHERE EXISTING FIRE ALARMDEVICES HAVE BEEN REMOVED AND NOT REPLACED IN THE SAMELOCATION.
J PATCH ALL WALLS WHERE FIRE HOSE CABINETS HAVE BEENREMOVED.
2
Roof/Attic Floor
29' - 0"
2
A300
Roof - Existing Attic
43' - 1"
EXISTING SLOPED SLATE ROOF STRUCTURE
STONE VENEER WALLTO MATCH EXISTING BLDG.
INSULATED METAL PANEL SYSTEM
CONCRETE CURB W/ FLASHING
ROOF LADDER
N303
1' -
6"
First Floor
0"
Second Floor
15' - 6"
Roof/Attic Floor
29' - 0"
Roof - Existing Stair
39' - 0"
1
A300
ELEVATOR TOWER
NEW.
EXIST.BUILDING
.EXIST.
BUILDING
NEW STONE VENEER
NEW CAST STONE COPING & TRIM
Roof - New Elevator
46' - 0"
NEW CAST STONE TRIM TO MATACH EXISTINGBUILDING - ALIGN W/EXISTING
ALIGN W/ EXISTINGSTONE BAND
Roof/Attic Floor
29' - 0"
34
Roof - Existing Attic
43' - 1"NEW STONE VENEER MASONRY
NEW CAST STONE COPING TO MATCH EXISTING BUILDING
EXISTING SLATE ROOF
FLASHING
CONCRETE CURB
3
A300
16
A700
SCUPPER
Roof/Attic Floor
29' - 0"
3 4
Roof - Existing Attic
43' - 1"
INSULATED METAL WALLPANEL SYSTEM
CONCRETE CURB
PRE-FINISHEDMETAL ROOF EDGE
4
A300
First Floor
0"
Second Floor
15' - 6"
Roof/Attic Floor
29' - 0"
Roof - Existing Stair
39' - 0"
AB
Roof - New Elevator
46' - 0"
NEW CAST STONE COPINGTO MATCH EXISTINGBUILDING
NEW STONE VENEER TOMATCH EXISTING BUILDING
EXISTING ROOF STRUCTURE -SEE STRUCTURAL
REINSTALLED EXIST. STONEVENEER BELOW EXIST. ROOF STRUCTURE
SN300EStairs
5
A700
6
A700
Sim
First Floor
0"
Second Floor
15' - 6"
Roof/Attic Floor
29' - 0"
A B
Roof - New Elevator
46' - 0"
Roof - Exist. Elevator
41' - 6"
REINSTALLED EXISTINGSTONE VENEER BELOWEXISTING ROOF
EXISTING ROOF STRUCTURE-SEE STRUCTURAL
NEW STONE VENEER
NEW CAST STONE COPING& TRIM
5
A700
6
A700
Sim
Roof/Attic Floor
29' - 0"
9
Roof - New Elevator
46' - 0"
NEW CAST STONE COPING& TRIM TO MATCH EXISTINGBUILDING
NEW STONE VENEER
EXISTING ROOF STRUCTURE-SEE STRUCTURAL
5
A700
NEW STONE VENEER
6
A700
Sim
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:0
1 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Exterior Elevations
A200
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"A200
2 East Elevation - Mechanical Penthouse
1/8" = 1'-0"A200
5 North Elevation - New Elevator Tower
1/8" = 1'-0"A200
1 North Elevation - Mechanical Penthouse 1/8" = 1'-0"A200
3 South Elevation - Mechanical Penthouse
1/8" = 1'-0"A200
6 East Elevation - New Elevator Tower 1/8" = 1'-0"A200
4 West Elevation - New Elevator Tower
1/8" = 1'-0"A200
7 South Elevation - New Elevator Tower
0' 4' 8' 16' 32'
No. Description Date
2 Addendum 2 12.14.17
2
2
2
2
2
2
2
2
First Floor
0"
Second Floor
15' - 6"
Roof/Attic Floor
29' - 0"
Ground Floor
-14' - 0"
Sub Basement
-29' - 0"
T.O.W.- New Elevator
47' - 0"
A
Roof - New Elevator
46' - 0"
WALL CONSTRUCTION3 5/8" STONE VENEER2" AIR SPACE1 1/2" POLYSTYRENT ISULATIONWEATHER BARRIER8" NOM. CMU
ROOF MEMBRANE ONINSULATED METAL DECK
POURED IN PLACECONCRETEFOUNDATION WALL
ELEVATORSHAFT
WATERPROOFING MEMBRANEAND DRAINAGE BOARD
EXISTING FOUNDATIONWALL AND FOOTING
1' -
0"
17
' - 0
"2
9' -
0"
14
' - 0
"6
' - 0
"
1'-0
" M
IN
FINISHED GRADE -SEE CIVIL
ELEVATOR PIT SLABAND WALLS - SEESTRUCTURAL
67
' - 0
"
A700
1
A700
3
8"
4"
4"
2' -
0 1
/4"
4"
8"
8"
4"
8"
Roof/Attic Floor
29' - 0"
4
Roof - Existing Attic
43' - 1"
3" INSULATED METAL PANEL SYSTEM
EXISTING ROOF DECK
CONCRETE CURB-SEE STRUCT
12
' - 5
"1
' - 0
"
1' -
6"
A700
8
A700
7
Roof/Attic Floor
29' - 0"
C
Roof - Existing Attic
43' - 1"
14
' - 1
"
WALL CONSTRUCTION3 5/8" STONE VENEER2" AIR SPACE1 1/2" POLYSTYRENE INSULATIONWEATHER BARRIER5/8" GYP. SHEATHING6" METAL STUDSR19 BATT INSULATION5/8" GYP. BOARD
TERMINATION BAR, SEALANT, AND COUNTERFLASHING
CAST IN PLACECONCRETE CURB
STEEL BRACING -SEE STRUCTURAL
STEEL SUPPORT ANGLE -SEE STRUCTURAL
EXISTING SLATE ROOF
STEP FLASHING-REMOVE AND REINSTALL SLATE SHINGLES AS NECESSARY
ROOF UNDERLAYMENT
A700
9
A700
10
1' -
0"
Roof/Attic Floor
29' - 0"
H
Roof - Existing Attic
43' - 1"
Third Floor129' - 0"
Roof - Existing Stair139' - 0"
Roof - Existing Attic143' - 1"
H
3" INSULATED METAL PANEL SYSTEM
CONCRETE CURB
1' -
0"
12
' - 5
"5
1/4
"
STEEL BEAM - SEE STRUCT.
STEEL BRACING - SEE STRUCT.
A700
12
A700
11
TERMINAL POST, SET IN CONC PIER
BASIS OF DESIGN: AMETCO , SATURN 100%
CONCRETE FOOTING -PER MANUF.
POST TOP FINIAL
6' -
0"
4"
MAN GATE
4"
GALVANIZED STEEL DROP ROD AND SLIP BOLT IN LOCKING HASP WITH GALVANIZED STEEL PIPE SLEEVE IN CONCRETE AT THRESHHOLD - LOCATE OUTSIDE OF ENCLOSURE - PAINT TO MATCH GATE -COORDINATE WITH UTILITY FOR LOCKING REQUIREMENTS
6' -
0"
SEE PLAN
1/4"
3 1/
2"
3"
STONE VENEER
CMU
CAST STONE CAP
1' - 1 1/4"
GRADE -SEE CIVIL
CONCRETEFOOTING-SEE CIVIL
CS-4
6' -
0"
FLASHING
8"
5' -
4"
4"
1' -
0"
1' -
0"
1' -
0"
1' -
0"
4"
4"
4"
1' -
8"
CONCRETEFOOTING-SEE CIVIL
STONE VENEER
CAST STONE CAP
CS-3
DECORATIVEALUMINUM FENCE
ANCHOR HORIZONTALS AT EACH END
STONE VENEER
FLASHING
1' -
8"
8"
4"
4"
4"
4"
3' -
3"
4"
2"
1' -
8"
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:0
2 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Wall Sections
A300
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/2" = 1'-0"A300
1 Wall Section - Elevator Tower
3/4" = 1'-0"A300
2 Wall Section - Mechanical Room 3/4" = 1'-0"A300
3 Wall Section - Mechanical Room North 3/4" = 1'-0"A300
4 Wall Section - Mechanical Room South0' 1' 2' 4'
1/4" = 1'-0"A300
7 SITE EQUIPMENT SCREEN
1/4" = 1'-0"A300
8 SITE EQUIPMENT SCREEN GATE
3" = 1'-0"A300
9 SITE EQUIPMENT SCREEN - DETAIL PLAN
3/4" = 1'-0"A300
5 Wall Section - Site Screen Wall 3/4" = 1'-0"A300
6 Wall Section - Site Screen Wall at Fence
No. Description Date
2 Addendum 2 12.14.17
2
2
2
WALLCOVERING (WC1)
PAINT (PT1)
MAHOGANY CHAIRRAIL (CR-1) AND BASE (WD-B1), STAIN TO MATCH PL1
WOOD DOORS TO MATCH STOTLER LOUNGE
WOOD VENEEER CASEWORKTO CONCEAL FOLDABLE PARTITIONS, STAIN TO MATCH PL1
MAHOGANY CROWN MOLDINGC (WD-CM)
2' -
8"
8"
SE
E E
LE
C.
EQ. EQ.
LIGHTING, WINDOW SHADE, &PROJECTION SCREEN CONTROLS ALERTUS DEVICE
WALLCOVERING (WC1)
PAINT (PT1)
MAHOGANY CHAIRRAIL (CR-1)AND BASE (WD-B1), STAIN TO MATCH PL1
WOOD DOORS TO MATCH STOTLER LOUNGE
2' -
8"
MAHOGANY CROWN MOLDING (WD-CM)
P.LAM. BASE CABINET (PL1)
SOLID SURFACE COUNTERTOP AND BACKSPLASH (SS1)
WALLCOVERING (WC1)
MAHOGANY BASE (WD-B1) AND CHAIRRAIL (CR-1),STAIN TO MATCH PL1
PAINT (PT1)
WOOD VENEER CASEWORKTO CONCEAL FOLDABLE PARTITIONS, STAIN TO MATCH PL1
MAHOGANY CROWN MOLDING (WD-CM)
15' - 10 1/2"
5 1/4" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 3' - 0" 5 1/4"
5' - 1 5/8"
3" 3' - 0" 1' - 6" 4 5/8"
2
A800
2
A800
D E F
5
6
7
A500 65
N231AMen
N232AWomen
N235Jan
A500
9
8
N233Family
TA07
TA06
TA08
TA04
TA04 TA04 TA04 TA04
TA03TA03TA04TA03
TA01 TA01
TA02
TA02
TA01
TA01
TA07
TA08
TA03
TA03
TA03
TA05TA05
TA05
TA01
TA03
TA06 TA08
TA07A500
7
10
D3
A3A3A3A6
A3
A3A3
A3
A6 A3A3
C3
A6
A3
11' - 10 3/8"
7' -
0 3
/4"
9' - 6 3/8" 6' - 11 3/8" 10' - 0" 3' - 11 1/4" 4' - 0"
3' -
0"
5' -
0"
1' -
6"
3' - 0" 3' - 0" 3' - 0" 3' - 0" 1' - 6"
TA09
TA09
TA02
5' -
1"
2' -
9"
5' -
1"
5' - 0"
1' -
0"
3' -
0"
1' -
1 1
/4"
1' -
5"
4' - 0 1/8" 4 7/8" 9' - 7 1/8" 4 7/8" 3' - 6 3/8"
6 3
/8"
4 7
/8"
9' -
1"
4 7
/8"
6' -
7 7
/8"
C3
7' -
0 3
/4"
1' -
2 7
/8"
7 1
/4"
2' -
4"
C3
A6
C3
A3
EQ
EQ
EQ
5' - 3 1/2"
1' -
9"
5' - 2"
2' - 4"
G41HR
G41HR
4' - 1"
TA06
8"
TA03
TA04
TA03
A500
11
TA02
CWT2A
CWT3
CWT33' -
6"
6"
TA07
TA08
TA06
CWT2A
CWT3 CWT3
CWT2B
SS1
6"
CWT3
CWT2A4' -
0"
9' - 0" F.V.
1
A800
2' -
10
"4
"
TA09
1' - 11 7/8"
CWT3
CWT2A
CWT3
3' -
6"
6"
TA08
TA06
TA07
CWT3
CWT3
SS1
CWT2A
3' -
6"
6"
2' -
10
"
3' -
6"
6"
9' - 7" F.V.
4' -
0"
1
A800
4"
TA09
EQEQTA02
CWT2B
CWT3
CWT2A
CWT3
3' -
6"
6"
TA08
TA06
TA02
CWT3
CWT2A
CWT3
CWT2B
SS1
2' - 9"
4' -
0"
2' -
10
"4
"
2' - 9"
6"
3' -
6"
1
A800
5' - 1"
TA08
TA06
TA07
STAINLESS STEEL ADA SINK WITH POLISHED CHROME FAUCET AND DISPOSAL (SS1)
SOLID SURFACE COUNTERTOP AND BACKSPLASH (SS1)
± 10' - 7 1/8"
RB1
2' -
10
"2
' - 0
"
5
A800
7' - 5 1/8"3' - 0"
2"
3
A800
15
A800
12" MAX
40" (39-41")
2' -
4"
7"
(33
-36
")
2' -
10
"
1' -
6"
40
" (3
9-4
1")
TA08
TA06
TA03TA04
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:1
7 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Interior Elevations
A500
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/4" = 1'-0"A500
1 Elevation - Typical Meeting Room
1/4" = 1'-0"A500
2 Elevation - Typical Corridor 1/4" = 1'-0"A500
3B Elevation - Small Meeting Rooms
1/4" = 1'-0"A500
4 Enlarged Restroom Plans 1/4" = 1'-0"A500
5 Men's Room - North 1/4" = 1'-0"A500
6 Men's Room - South
1/4" = 1'-0"A500
8 Women's Room - East 1/4" = 1'-0"A500
9 Women's Room - West
1/4" = 1'-0"A500
7 Family - East
1/4" = 1'-0"A500
10 Family - North
1/4" = 1'-0"A500
3A Elevation - Catering
1/4" = 1'-0"A500
3 Folding Partition Elevation
TOILET ACCESSORIES SCHEDULE
MARK ACCESSORY ITEM MANUFACTURER MODEL NO. FURNISHED BY COMMENTS
TA01 SOAP DISPENSER OF/CI
TA02 HAND DRYER DYSON AIRBLADE OF/CI
TA03 TOILET TISSUE DISPENSER ROYCE ROLLS RINGERCO.
TP-4 OF/CI
TA04 SANITARY NAPKIN DISPOSAL OF/OI
TA05 FRAMELESS MIRROR SEE SPECS SEE ELEVATIONS CF/CI
TA06 GRAB BAR - 48" BOBRICK B-5806 X 48 CF/CI
TA07 GRAB BAR - 36" BOBRICK B-5806 X 36 CF/CI
TA08 GRAB BAR - 18" BOBRICK B-5806 X 18 CF/CI
TA09 CHANGING TABLE KOALA KARE KB110-SSWM CF/CI
TA10 UTILITY SHELF BOBRICK B-296 CF/CI
No. Description Date
2 Addendum 2 12.14.17
1/4" = 1'-0"A500
11 Typical Restroom Elevation
2
Roof/Attic Floor
29' - 0"
10
12
" M
IN.
ROOF MEMBRANE
ROOF INSULATION &COVER BOARD OVEREXIST. ROOF DECK
EXIST. PARAPET WALL
EXIST. CAST STONECOPING - REMOVE AND REINSTALL AFTER FLASHING-SEAL ANCHOR PENETRATIONS
ROOF MEMBRANE -WRAP OVER TOP OF PARAPET
COPPER FLASHING CAP1
' - 1
1/4
"
TERMINATION BAR AND SEALANT
REMOVABLE COUNTER FLASHING
THRU FLASHING
REINSTALLED EXISTING STONE VENEER
DRAINAGE CAVITY MATERIAL
ROOF MEMBRANE
TAPERED ROOF INSULATION
3 5/8" 2"1 1/2"
7 5/8"
1' - 2 3/4"
1' -
4 1
/4"
GROUT SOLID
Roof/Attic Floor
29' - 0"
4
2 1
/2"
1' -
6 1
/2"
9 1
/2"
BASE EXTRUSION
TAPERED ROOF INSULATION
ROOF MEMBRANE
TERMINATION BAR AND SEALANT
3" INSULATED METAL PANEL SYSTEM
WALL PANEL SUPPORT TUBES
COUNTER FLASHING
PLYWOOD BACKING
CURB, SEE STRUCT.
BATT INSULATION
4
Roof - Existing Attic
43' - 1"
ROOF CONSTRUCTION:-EPDM MEMBRANE-1/2" COVERBOARD-TAPERED INSULATION-METAL DECK
SHEET METAL FLASHING
METAL PANEL SYSTEM
6"
COVER STRIP
WOOD BLOCKING
BATT INSULATION
C
Roof - Existing Attic
43' - 1"
CONTINUE EPDM MEMBRANE UNDER CAP
COPPER FLASHING CAP
SHEATHING & POLYSTYRENEINSULATION BOARD
CS-3
STRAP ANCHOR-SEAL ANCHOR PENETRATIONS
EXTERIOR WALL CONSTRUCTION:-STONE VENEER-AIR CAVITY-1 1/2" (R-7.5) EXTRUDED POLYSTYRENE INSULATION-SHEATHING W/ AIR BARRIER -6" MTL. STUDS-BATT INSULATION-5/8" GYP. BD.
STEEL BEAM - SEE STRUCTURAL
DRIP EDGE
1' -
0"
BATT INSULATION
C
TERMINATION BAR, SEALANT, AND REMOVABLE COUNTERFLASHING
EXISTING SLATE ROOF
STEP FLASHING-REMOVE AND REINSTALL SLATE SHINGLES AS NECESSARY
ROOF UNDERLAYMENT 1
0"
THROUGH-WALL FLASHING
3" INSULATED METAL PANEL SYSTEM
MIN
.
8"
STEP FLASHING-REMOVE AND REINSTALL SLATE SHINGLES AS NECSSARY
BASE EXTRUSION
COUNTER FLASHING
PLYWOOD BACKING
ROOF MEMBRANE
BATT INSULATION
4 1/2"
6"
SHEET METAL FLASHING
ROOF CONSTRUCTION:-EPDM MEMBRANE-1/2" COVERBOARD-TAPERED INSULATION-METAL DECK
METAL PANEL SYSTEM
COVER STRIP
WOOD BLOCKING
A
2"
2"
Roof - Existing Stair
39' - 0"
Roof - Exist. Elevator
41' - 6"
1' - 2 3/4"
ROOF CONSTRUCTION:-EPDM MEMBRANE-1/2" COVERBOARD-TAPERED INSULATION-EXISTING STRUCTURE
SHEET METAL FLASHING
SEALANT
STONE VENEER
SEE STRUCT.
EXISTING STRUCTURE
T.O.W.- New Elevator
47' - 0"
Roof - Existing Attic
43' - 1"
Roof - New Elevator
46' - 0"
8"
4"
4"
2' -
0"
3/8
"
EXTERIOR WALL CONSTRUCTION:-BRICK VENEER-AIR CAVITY-1 1/2" (R-7.5) EXTRUDED -POLYSTYRENE INSULATION-CMU
ROOF CONSTRUCTION:-EPDM MEMBRANE-1/2" COVERBOARD-TAPERED INSULATION-METAL DECK
CONTINUE MEMBRANE UNDER CAP
RIGID INSULATION
STRAP ANCHOR -SEAL ANCHOR PENETRATIONS
DRIP EDGE
CS-1
CS-1
STONE VENEER
CS-2
STONE VENEER
COPPER FLASHING CAP
First Floor
0"
8"
4"
8"
4"
8"
2' -
8"
F.V
.
CS-1
CS-1 GROUT SOLID
THRU WALL FLASHING W/ WEEPS AT 16"O.C.
STONE VENEER
STONE VENEER
CONCRETE FOUNDATION WALL-SEE STRUCT.
WALL CONSTRUCTION-3 5/8" STONE VENEER-2" AIR SPACE-1 1/2"POLYSTYRENE INSULATION-WEATHER BARRIER-8" NOM. CMU
SE
E C
IVIL
1' -
0"
MIN
.
3 5/8" 2"1 1/2"
7 5/8"
1' - 2 3/4"
7"
5/8
"
1 5/8" 3 5/8"
1' - 11 5/8" (NOT TO SCALE)
CS-1 CS-2
NOTE:
1) CAST STONE PROFILE CONFORM TO MODULAR BRICK SIZING
CS-3
1' - 6 1/8"
3 1
/4"
4 3
/8"
1' - 1 1/8"5 1/8"
3 1
/4"
3 5
/8"
3/8
"
1' - 2"
3/8"
3 5
/8"
3/8
"
3 5/8"
3/8"
CS-4
CAST IRON DRAIN STRAINER
CLAMPING RING
RIGID INSULATION W/ COVERBOARD - SLOPE 4' X 4' SUMPTO DRAIN
EXISTING CONCRETE ROOF DECK
DECK CLAMP
BEARING PAN
EPDM MEMBRANE
C
CS-3
EXTEND AND ADHERE ROOF MEMBRANE THRU SCUPPER, TO LIP OF SCUPPER
1' -
0"
SHEET MTL SCUPPER, 8" WIDE
3 3
/8"
9"
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:2
3 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Exterior Details
A700
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1 1/2" = 1'-0"A700
4 Detail - Parapet Flashing
1 1/2" = 1'-0"A700
5 Counter Flashing at Stone Veneer on CMU
1 1/2" = 1'-0"A700
7 ROOF DETAIL - MECH ROOM
1 1/2" = 1'-0"A700
8 ROOF COPING DETAIL - MECH ROOM
1 1/2" = 1'-0"A700
10 ROOF COPING DETAIL - MECH ROOM NORTH
1 1/2" = 1'-0"A700
9 ROOF DETAIL - MECH ROOM NORTH
1 1/2" = 1'-0"A700
11 ROOF DETAIL - MECH ROOM SOUTH
1 1/2" = 1'-0"A700
12 ROOF COPING DETAIL - MECH ROOM SOUTH
1 1/2" = 1'-0"A700
14 Enlarged Elevator Plan - Expansion Detail
1 1/2" = 1'-0"A700
6 Elevator Section - Callout 1
1 1/2" = 1'-0"A700
3 ELEVATOR TOWER - ROOF DETAIL - PARAPET
1 1/2" = 1'-0"A700
1 ELEVATOR TOWER - BASE DETAIL
3" = 1'-0"A700
15 Cast Stone Profiles CS-1 & CS-2 & CS-3 & CS-4
No. Description Date
2 Addendum 2 12.14.17
3" = 1'-0"A700
13 TYPICAL ROOF DRAIN DETAIL
1 1/2" = 1'-0"A700
16 SCUPPER DETAIL
2
2
22
2
2
SEE PLUMBING DWGS. FOR FIXT. INFO
FIRE TREATED WOOD BLOCKING AS REQ.
SOLID SURFACE COUNTER WITH INTEGRAL BOWLS
WRAP PIPES
1 1
/2"
2' -
8 1
/2"
2' - 1"
2' -
10"
PLASTIC LAMINATE BRACE REQUIRED FOR DOUBLE LAVATORY LOCATIONS
MAX.
6" 11" MIN.
MIN
.
9"
2' -
4"
MIN
.MIN.
8"
BARRIER FREE CLEARANCE
4"
4" BACKSPLASH
SCHEDULED BASE
ADJUSTABLE SHELF ON LINE BORE W/ SHELF PINS
FIRE TREATED WOOD BLOCKING AS REQ.
4" BACKSPLASH WHERE INDICATED ON INT. ELEV.
COUNTERTOP - SEE FIN. SCHEDULE
HARDWARE - SEE SPEC.
VA
RIE
S -
SE
E E
LE
V.
2' - 1"
1 1
/2"
6"
4"
P.LAM ON 3/4" SUBSTRATE - SEE FIN.
SCHED.
2' - 0"
3"
SCHEDULED BASE
SEE PLUMBING DWGS. FOR FIXT. INFO
COUNTERTOP - SEE FIN. SCHEDULE
HARDWARE - SEE SPEC.
1 1
/2"
4"
2' -
2 1
/2"
4"
SE
E E
LE
V.
3"
P.LAM ON 3/4" SUBSTRATE, SEE INT. ELEVATION
FIXED P.LAM PANEL
FIRE TREATED WOOD BLOCKING AS REQ.
BACKSPLASH WHERE INDICATED ON INT. ELEV.
5/8" GYP BD, TYP
3 5/8" MTL STUDS @ 16"OC HUNG FROM STRUCT ABOVE
5/8" GYP BD ON SUSPENDED CEILING SYSTEM
TYP CLG SUSPENSION SYSTEM
3 5/8" MTL STUD KICKERS @ 48"OC MAX
SE
E R
CP
6"
5/8" GYP BD, TYP
3 5/8" MTL STUDS @ 16"OC HUNG FROM STRUCT ABOVE
SE
E R
CP TYP APC CLG
CONST
6"
TYP CLG SUSPENSION SYSTEM
3 5/8" MTL STUD KICKERS @ 48"OC MAX
MAHOGANY CROWN MOLDING -SEE FINISH LEGEND
5/8" GYP BD, TYP, SEE RCP FOR BULKHEAD HT.
3 5/8" MTL STUDS @ 16"OC HUNG FROM STRUCT ABOVE
SE
E R
CP
TYP ACP CLG CONST
6"
TYP CLG SUSPENSION SYSTEM
STRUCTURE ABOVE
SEE RCP
SE
E R
CP
SLIDING PARTITION TRUSS ASSEMBLY
STEEL SUPPORT-SEE STRUCTURAL
CONT. SOUND BATT INSULATION
TRANSITION MOLDING
ACP CEILING, SEE RCP FOR CEILING HEIGHT
5/8" GWB ON SUSPENDEDCEILING SYSTEM
E
8
R 1' - 3"
GFRG COLUMN COVER
EXISTING CONCRETE COLUMN - VERIFY SIZE
METAL STUDS
ACCENT TILE FINISH
OUTLET - SEEELECTRICAL
4' - 8"
4' -
1"
15
A800
1"
A800
16
E3
A3
A3
SLIDING/FOLDING PARTITION
SLIDING TRACK IN SOFFIT ABOVE
WOOD VENEER DOORS (EXTEND FLOOR TO BULKHEAD ABOVE)
EQ EQCL
8' -
6"
1' -
9"
11
"
8"
2' -
8"
STAINED WD-C1
STAINED WD-C1
STAINED WOOD VENEER PANEL
STAINED WD-C1
CEILING
A3 PARTITION TYPE
A3 PARTITION TYPE
WOOD VENEER PANEL
WD-C1
WOOD VENEER PANEL
WD-C2
WOOD VENEER DOOR
VE
RIF
Y 2"
MIN
.
2" MIN.
FACE OF WALL
APLAN AT CABINET FILLER
FACE OF WALL
P.LAM FACED FILLER CUT TO FIT
P.LAM FACED FILLER CUT TO FIT
BPLAN AT CABINET FILLER - INSIDE CORNER
G
7
1 5/8" METAL STUDS
5/8" GYPSUM
4' - 6 1/4"
2' - 2 3/4" 1/2" 2' - 2 3/4"
3" 1' - 8 3/4" 3" 3" 1' - 8 3/4" 3"
1/2
"8
' - 5
"1/2
"
3"
1' -
8"
3"
3' -
3 1
/2"
9 1
/2"
1' -
9 1
/2"
4 1
/2"
2' -
8"
STAINED WOOD TRIM
STAINED WOODVENEER
STAINED WOOD TRIMWD-C1
EXISTING SOLID WOOD ROOF DECK
EXISTING LAMINATED WOOD SUPPORT ARCH
4"8"
EXISTING DECORATIVE WOODROOF BEAM - REMOVE AS NEEDED
NEW DECORATIVE WOODROOF BEAM - MATCH EXISTING
SPRINKLER HEAD AND PIPING
PROVIDE INTERMEDIATE BLOCKING FOR SPRINKLERLINE SUPPORT - COORD. W/FIRE PROTECTION CONTRACTOR
METAL SUPPORT BRACKET PROFILE
COUNTERTOP- REFER TO ELEVATION FOR MORE INFORMATION
EXTERIOR WALL SYSTEM SHOWN HATCHED
3/4" PLYWOOD CONT. BLOCKING LAID IN METAL STUD RUNNER HEADER, LEVEL
MOTORIZED ROLLER SHADE
CEILING SEE FINISH SCHEDULE, SEE RCP FOR HEIGHT
3 5/8" METAL STUD KICKERS @ 32" O.C.
3 5/8" METAL STUD FRAMING @ 16" O.C.
1' - 0" 4"
2"
OPERABLE PARTITION
WOOD TRIM - WD-C1
EXIST. EXTERIOR WALL
SOLID BLOCKING
GYP. PARTITION -SEE FLOOR PLAN
EQ. EQ.
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
Sheet Title:
12/1
4/2
01
71
1:2
2:2
9 A
MC
:\U
se
rs\jsh
ea
rer\
Do
cu
me
nts
\BIM
LO
CA
L\1
62
53
MU
Me
mo
ria
l S
tud
en
t U
nio
n_A
rch
v17
_C
en
tra
l_jim
.sh
eare
r@th
ela
wre
nce
gro
up
.co
m.r
vt
16253
Author
Interior Details
A800
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
3/4" = 1'-0"A800
1 COUNTERTOP - RESTROOM
3/4" = 1'-0"A800
2 CASEWORK - BASE CABINET- DRAWER
3/4" = 1'-0"A800
3 CASEWORK - BASE CABINET - SINK
1 1/2" = 1'-0"A800
6 CEILING DTL - GYP. BD. SOFFIT TO SUSP. GYP. BD., TYP.
1 1/2" = 1'-0"A800
7 CEILING DETAIL - GYP. BD. SOFFIT TO ACP, TYP.
1 1/2" = 1'-0"A800
9 CEILING DETAIL - SLIDING PARTITION BULKHEAD
1 1/2" = 1'-0"A800
8 CEILING DETAIL - GWB TO ACP TRANSITION
1 1/2" = 1'-0"A800
12 Detail - Column Cover
1/2" = 1'-0"A800
17 Plan Detail - Folding Partition
3" = 1'-0"A800
15 Section - Folding Partition
3" = 1'-0"A800
16 Jamb Detail - Folding Partition
3/4" = 1'-0"A800
4 CABINET FILLER
1 1/2" = 1'-0"A800
11 Detail - Column Furring
1/2" = 1'-0"A800
14 Elevation - Wood Veneer Door 1 1/2" = 1'-0"A800
10 DETAIL - CHAPEL CEILING
1 1/2" = 1'-0"A800
5 COUNTERTOP SUPPORT BRACKET
No. Description Date
2 Addendum 2 12.14.17
HARDWARE1) 2 CONTINUOUS HINGES - BLACK2) 1 PASSAGE LOCKET - ACTIVE LEAF3) 1 DUMMY - INACTIVE LEAF4) 1 SET MANUAL SURFACE MOUNTED SLIDE
BOLTS AT CEILING AND FLOOR - ON INSIDE OF INACTIVE LEAF
1 1/2" = 1'-0"A800
18 CEILING POCKET DETAIL - TYP. MEETING ROOMS
3" = 1'-0"A800
13 Operable Partition - Jamb
2
2
POCKET (E) MAS WALL FOR NEW BM,PROVIDE 1/4" MIN CLR ALL AROUNDBTWN BM & MAS, GROUT POCKET ATSTL BEAM
NEW STL BEAM, SEE PLAN
BRG PL 1/2x8xWIDTH OF BM +1"
(E) MASONRY WALL
MIN
8"
1" M
IN G
RO
UT
GRID
1 1/
2" +
/-
(E) COL VERT REINF
(E) CONC BEAM
(E) ROOF
RE-GROUT SOLID
REMOVE (E) COL WHERE APPLICABLE
INSTALL REBARTERMINATOR TOTOP (E) VERTCOL REBAR
CHIP AWAY TOP OF (E) CONC TO EXPOSE ENDSOF COL REBAR
NOTE:COLUMN TIES AND BEAM REINFNOT SHOWN FOR CLARITY
DETAIL REQUIRED AT COLUMNS: B-5, E-5, F-5, G-5, K-5, K-3 AND K-2
SECTION
MAX 2'-6"
PLAN
PAN JOIST WEB,DISTRIBUTION RIB
NO
LIM
IT O
N
OP
NG
LE
NG
TH
FULL DEPTH SLAB INFILLUSING NORMAL WT CONC.
MIN 2'-6"
MAX 5'-0"
#4 DWLS @ 12"oc DRILL AND GROUT 6" MIN INTO EXIST (ALL 4 SIDES)
5" MIN
FULL DEPTH SLAB INFILLUSING NORMAL WT CONC.
MIN 2'-6"
MAX 5'-0"
#4 DWLS @ 12"oc DRILL & GROUT6" MIN INTO EXIST, EXTEND 1'-0"MIN INTO OPENING (ALL 4 SIDES)
8"+
/-
#4 @ 12"oc EW
ALTERNATE SECTION
3/4" PLYWOOD FORM
#4 @ 12"oc EW
#4 DWLS @ 12"oc DRILL AND GROUT 6" MIN INTO EXIST (ALL 4 SIDES)
NOTE:L6x4x3/8 HEADER WHEN (1) JOIST IS CUT
REFLECTED PLAN VIEW
2"
(E) CONC JOIST
1" GROUT
8"+
/-
FIELD VERIFY ALLEXISTING DIMENSIONS
1/2" EXPANSIONANCHORS, TYP
NEWOPNG
9 1/
2"1 1/
2"1/
2"
8"
1 1/2" 1 1/2"
3/16
6"+/-
END PLATE DETAIL SECTION
PL 3/4x8x9 1/2EACH END
NEW FLOOR PENETRATIONS:
1.2.
In no case can a main Concrete Beam/Girder be core drilled or cut.Cored holes or cut holes of any size may be placed between joists, as long as the webs of the joists are not cut. Theclear distance between cored holes shall be a minimum of 8" in any direction. There is no limit on the number or sizeof cored holes that can be placed between any two adjacent joists.
12" MAX
ALTERNATE
16 GA METAL PLATE FASTENED TO UNDERSIDE OF (E) FLR SLAB w/ (4) SHOT PINS ( (1) EA CONER OF PL, 3" MINEDGE DISTANCE). EXTEND PL 3 1/2" BEYOND INFILL AREA ON ALL SIDES, TYP
SEE ARCH DWGS FORFLR & CLG FINISHES WIDEN (E) OPNG AT
TOP & TAPER SIDES AS INDICATED. ROUGHEN EDGES OF INFILL AREA
(E) OPNG
12" MAX
(E) CONCRETE FLOORSTRUCTURE
TYPICAL
1
8
FILL w/ LEAN CONC AS REQ'D
3 1/2" MIN
3" MIN
1" GROUT
(2) 3/4" DIA BOLTS IN SHORT SLOTTED HORIZ HOLES IN BEAM WEB
STRIP BOT FLANGE FOR DOUBLE ANGLE CONN
DOUBLE L6x4x3/8 w/ (4) 3/4" DIA ADHESIVE ANCHORS
1"
1 1/
2"8"
MIN4"
(E) CONC BEAM OR WALL
ADDITIONAL 3/4" DIA EXP ANCHORS INTO (E) CONC SEE 7/S103 FOR BALANCEOF INFO
6"
PL 1/2x4x4, TYP, w/ 1/2" SHIMS @ 48"oc +/- & 5/8" DIA EXP ANCHORS
(E) CONC SLAB
1" GROUT
NEW BEAM - SEE PLAN3/16
(E) CONC SLAB
NEW BEAM - SEE PLAN
CL BEAM OR JOIST CL BEAM OR JOIST
L6x6x3/8 TYP. UNDER RTU CURB
L3x3x1/4 AROUND OPENING
L6x6x3/8 UNDER RTU CURB
"A" "A"
PLAN VIEW
SECTION "A"-"A"
EQUIP. CURB PER MECH. MECH. UNIT
OPENING
CL BEAM OR JOIST CL BEAM OR JOIST
NOTE 3
L FRAME
3/16TYP
3/16TYP
1. COORDINATE SIZE & LOCATION OF OPENINGS w/ ARCHITECTURAL & MECHANICAL DRAWINGS.
2. PROVIDE FRAME FOR ALL OPENINGS OVER 12".3. PROVIDE BLOCKING BETWEEN DECK RIBS.4. LOCATE CURB OVER VERTICAL LEG OF L6x6.
MECH EQUIPMENT
VERIFY THE SIZE AND LOCATION OF ALL HOUSKEEPINGPADS WITH MECH CONTRACTOR BEFORE PLACINGDWLS IN SLAB ON GRADE.
(1) #4 CONT EA. SIDEAND #4 DWLS AT 24"ocAROUND PERIMETEROF PAD, DRILL & EPOXY DWLS. SEE GENERAL NOTES FOR ADHESIVE (EMBED 4")
TYP
"T"
SE
E
PLA
N
6"
(E) CONC SLAB5"
3"
2" T
YP
EQ
SP
A
(E) CONC WALLOR COLUMN
ADHESIVE ANCHORS PERSCHEDULE (w/ PLATE WASHER PER NOTE 1)
BEAM OFFSET1 1/2" MAX
PE
R S
CH
ED
ULE
CO
NN
PL
2" T
YP
3" T
YP
1/4
W10, STD HOLE SIZE
3/8" SHEAR TAB w/ (2) 3/4" DIA A325-N BOLTS IN 13/16" x 1 7/8" HORIZ LONGSLOTTED HOLES (w/ PLATEWASHERS PER NOTE 1)
2" TYP 6"
PE
R S
CH
ED
ULE
EM
BE
D
BEAM WEB
REMOVE (E) PLASTER AS REQ'D, TYP
SHEAR TAB PER SCHEDULEALIGN CL OF SHEAR TAB WITHIN 1" OF CL OF PL
3/8" CONN PL w/ 13/16" x 1 7/8"HORIZ LSH, # OF ANCHORS PER SCHEDULE, TYP (w/ PLWASHER PER NOTE 1)
AT RECTANGULAR COLUMN
CONNECTION TO EXISTING CONSTRUCTION SCHEDULE
CONNECTION TYPE
3/8" SHEAR TAB
CONNECTIONPLATE LENGTH
1'-6"
ANCHORSPER PLATE
(6) 3/4" DIA
EMBED DEPTH
6"
NOTES:1. PROVIDE MINIMUM 5/16" THICK COVER PLATE WASHER, TYP AT LSH. COVER PLATE SHALL COMPLETELY COVER SLOTS.
DRILL OR CORE-DRILL AT CORNERS OF (N) OPNG PRIOR TO SAW CUTTING. DO NOT OVERCUT PAST CORNER HOLES.
COORD w/ MEP
CO
OR
D w
/ ME
P
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
The Professional Engineer whose personal seal and signature Appears on this page assumes responsibility only for what appears on this page and disclaims (pursuant to Section 327.411 RSMo) any responsibility for all other pages, plans, specifications, estimates, reports, or other documents or instruments not sealed by this Professional Engineer relating to, or intended to be used for, any part or parts of the engineering project to which this page refers.
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
71
1:0
1:3
2 A
MC
:\U
se
rs\t
ah
intz
.KP
FF
-ST
L\D
ocu
me
nts
\17
00
11
9_M
em
ori
al S
tud
en
t U
nio
n_T
AH
v17
_C
en
tra
l_tim
.hin
tz@
kp
ff.c
om
.rvt
1700119
TAH
TYPICAL DETAILS
S103
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
3/4" = 1'-0"S103
1 TYPICAL POCKET FOR NEW STEEL BEAM IN EXISTING MASONRY WALL 3/4" = 1'-0"S103
2 TYPICAL TOP OF COLUMN LATERAL MITIGATION DETAIL AT THIRD FLOOR
N.T.S.S103
3 TYPICAL EXISTING FLOOR OPENING INFILL BETWEEN PAN JOISTS DETAIL
N.T.S.S103
4 TYPICAL RIB SLAB OPENING HEADER DETAIL (UNO)N.T.S.S103
5 TYPICAL FLOOR SLAB SMALL OPENING INFILL DETAIL 3/4" = 1'-0"S103
6 TYPICAL NEW BEAM CONNECTION TO EXISTING CONCRETE BEAM
N.T.S.S103
7 TYPICAL STEEL BEAM SUPPORTING EXISTING CONCRETE SLAB DETAIL (UNO)
3/4" = 1'-0"S103
8 TYPICAL ROOF TOP UNIT CURB SUPPORT DETAIL IN NEW CONSTRUCTION 12" = 1'-0"S103
9 TYPICAL HOUSEKEEPING PAD DETAIL
3/4" = 1'-0"S103
10 TYPICAL STEEL BEAM CONNECTION TO EXISING CONCRETE COLUMN / WALLN.T.S.S103
11 PLAN - TYPICAL NEW FLOOR/ROOF OPENING IN (E) CONC SLAB
2
No. Description Date
2 Addendum #2 12-14-17
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4
5
6
7
8
9
10
9.5
NOTE 1
W1
8X
86
W1
8X
86
W1
8X
86
W1
8X
86
W1
8X
86
W1
8X
86
W1
8X
86
W1
8X
86
G.8
W8X
24
W8X
24
W8X
24
W8X
24
W8X
24
W8X
24
VB
-01
VB
-02
VB-03
3
S401
RTU 12,000 # MAX
RTU 12,000 # MAX
NOTE 8
6
S401
4
S401
5
S401
POST
POST
POST
POST
POST
POST
1'-10"
NOTE 4
NOTE 4
NOTE 4 & 9
NOTE 5
NOTE 10
HSS 6x6x5/8
7
S4017
S401
WT8x18 @ OPERABLEPARTITION. COORDEXTENTS w/ PARTITIONSUPPLIER & ARCH
WT8x18 @ OPERABLEPARTITION. COORDEXTENTS w/ PARTITIONSUPPLIER & ARCH
WT8x18 @ OPERABLEPARTITION. COORDEXTENTS w/ PARTITIONSUPPLIER & ARCH
W10X22
9
S401
WT8X18
(HI)
(LO)
10.5
8
S401
10
S401
10
S401
(E)
B144
9.1
NOTE 11(17 PLACES)
L 6x4, SEE 4/S103
NOTE 13
NOTE 12
EQ EQ
W1
0X
15
W1
0X
15
W1
0X
15
W8X10
W8X10
W8X10
(E) BEAM
(E) BEAM
NOTE 12
3
S402
11
S401TYP
SIM
3
S401
3
S401
3
S401
6
S401
6
S401
6
S401
4
S401
4
S401
5
S401
5
S401
5
S401
1400# MAX FANON STL RAILS
1200# MAX FANON STL RAILS
HSS 6x6x5/8
3
S401
SEE 6/S103, TYP
(E) 4 1/2" ONE WAYSLAB
2
2
2
THE DIMENSIONS AND ELEVATIONS SHOWN FOR THE EXISTING CONSTRUCTION ARE NOT AS-BUILT DIMENSIONS BUT WERE OBTAINED FROM FIELD MEASUREMENTS, OTHER DRAWINGS, AND DOCUMENTS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND MEMBER SIZES AS REQUIRED PRIOR TO BEGINNING CONSTRUCTION, FABRICATION, ETC.
NOTES: 1. WHERE SHOWN ON PLAN, EXISTING WALL AND COLUMN TO BE REMOVED.2. INDICATES EXTENTS OF 4" NORMAL WEIGHT CONCRETE PAD.3. INDICATES EXTENTS OF FIBER REINFORCED POLYMER COMPOSITE STRENGTHENING. SEE DETAIL 5/S401.4. NEW 8" CMU WALL PARTIALLY GROUTED w/ #5 @ 32"oc. PROVIDE DOUBLE BOND BEAM w/ (2) #5 HORIZ BARS @ EA FLOOR LEVEL. DRILL & EPOXY BOND BEAM REINFORCING DOWELS INTO EXISTING FLOOR AT CMU WALL ENDS. 5. REMOVE EXISTING PENTHOUSE ROOF FRAMING BETWEEN GRIDS D to G.5 AND GRIDS 5 to 9.5. FULL REMOVAL OF EXISTING PENTHOUSE STRUCTURE IS REQUIRED PRIOR TO REMOVAL OF EXISTING CONCRETE COLUMNS IDENTIFIED IN NOTE 6.6. REMOVE CLOUMNS AT GRIDS: D-9, E-9, F-9 AND G-9 BETWEEN EXISTING SECOND FLOOR AND EXISTING THIRD FLOOR AFTER FULL INSTALLATION OF W18 TRANSFER GIRDERS SHOWN ON PLAN.7. SEE TYPICAL DETAIL 2/S103 FOR TOP OF COLUMN MITIGATION REQUIREMENTS AT GRIDS: B-5, E-5, F-5, G-5, K-5, K-3 AND K-2.8. PROVIDE FIBER REINFORCED POLYMER COMPOSITE STRENGTHENING FOR SHEAR AT BOTH ENDS OF BEAM B144 AS SHOWN ON PLAN. SHEAR CAPACITY SHALL BE INCREASED BY 3 KIPS EACH END.9. WHERE SHOWN ON PLAN, 8" CMU WALL PER NOTE 3 INSTALLED BETWEEN THIRD FLOOR SLAB TO UNDERSIDE OF EXISTING STAIR ROOF SLAB PRIOR TO EXISTING ELEVATOR SHAFT FRAMING REMOVAL IDENTIFIED IN NOTE 1.10. REMOVE EXISTING ROOF TOP EXTERIOR CHILLER AND SUPPORT STEEL FRAME.11. INDICATES NEW INFILL SLAB, SEE 3/S103.12. COORDINATE SHAFT LOCATIONS WHERE SHOWN ON PLAN TO AVOID CUTTING EXISTING SLAB RIBS. 13. NEW SLAB PENETRATIONS TO CUT ONE EXISTING SLAB RIB WHERE SHOWN ON PLAN , SEE 4/S103 FOR SUPPORT OF CUT JOIST RIB.14. REFER TO TYPICAL DETAIL 11/S103 AT ALL NEW SLAB PENETRATIONS.
1
B144 FIBER REINFORCED POLYMER COMPOSITE STRENGTHENING CRITERIA(SHEAR ONLY - BOTH ENDS)1. OVc = 3000 psi2. f'y = 40000 psi3. BEAM DIMENSIONS: 12" WIDE x 16" DEEP4. 1/4" DIAMETER STIRRUPS @ 6" oc (2 LEGS)5. STIRRUP EFFECTIVE DEPTH = 13.75"6. SERVICE DEAD LOAD END SHEAR = 13.6k7. SERVICE LIVE LOAD END SHEAR = 3.6k
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
The Professional Engineer whose personal seal and signature Appears on this page assumes responsibility only for what appears on this page and disclaims (pursuant to Section 327.411 RSMo) any responsibility for all other pages, plans, specifications, estimates, reports, or other documents or instruments not sealed by this Professional Engineer relating to, or intended to be used for, any part or parts of the engineering project to which this page refers.
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
71
1:0
1:3
6 A
MC
:\U
se
rs\t
ah
intz
.KP
FF
-ST
L\D
ocu
me
nts
\17
00
11
9_M
em
ori
al S
tud
en
t U
nio
n_T
AH
v17
_C
en
tra
l_tim
.hin
tz@
kp
ff.c
om
.rvt
1700119
TAH
PARTIAL ROOF FRAMINGPLAN
S205
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"S205
1 PARTIAL ROOF FRAMING PLAN
No. Description Date
2 Addendum #2 12-14-17
A
A
B
B
C
C
D
D
E
E
F
F
G
G
H
H
J
J
K
K
1
2
3
4
5
6
7
8
9
10
9.5
W1
0X
22
G.8
W10X12 W10X22 W10X22 W10X12 W10X12
12K1 12K1
12K1 12K1
12K1
(E) W12(E) W12 (E) W12 (E) W12 (E) W12 (E) W12
12K1 12K1 12K1 12K1
17'-1 1/2" +/-, FV 17'-1 1/2" +/-, FV 17'-3 1/2" +/-, FV 16'-5 1/2" +/-, FV 18'-4" +/-, FV
1'-10"
VB
-01
VB
-02
VB-03
4
S402
W1
0X
22
W1
0X
22
W1
0X
22
W1
0X
22
W1
0X
22
2
S402
1
S402
HO
IST
BE
AM
HSS 5x5x1/4LIFT LINE BEAM
NOTE 3
NOTE 4
NOTE 1
NOTE 6
NOTE 6
NOTE 6 & 7
10.5
*
EQ
*
EQ
9.1
(E)
W16
FV
5'-0" +/-
(E) SLOPEDJOIST
@ 4
'-0"o
c
L 6x
4x5/
16 (
LLV
)
EQ
6'-0
" M
AX
, TY
P
EQ
EQ
FV
12K1
12K1
12K1
12K1
12K1
12K1
EQ
EQ
EQ
SEE DET 8/S103 FORADD'L SUPPORT(TYP)
L 3x3x1/4
5
S402
NOTE 3
6
S402
EQ
EQ
NOTE 9
<A
=7k>
<A
=7k>
<A
=7k>
<A
=7k>
<A
=7k>
<A=+/- 8k> <A=+/- 8k>
FV
6"
.
SEE 8/S103(L 3x3)
NOTE 9
SEE 8/S103(L 3x3)
2
THE DIMENSIONS AND ELEVATIONS SHOWN FOR THE EXISTING CONSTRUCTION ARE NOT AS-BUILT DIMENSIONS BUT WERE OBTAINED FROM FIELD MEASUREMENTS, OTHER DRAWINGS, AND DOCUMENTS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS, ELEVATIONS AND MEMBER SIZES AS REQUIRED PRIOR TO BEGINNING CONSTRUCTION, FABRICATION, ETC.
NOTES: 1. WHERE SHOWN ON PLAN, EXISTING WALL AND COLUMN TO BE REMOVED.2. INDICATES SPAN OF METAL ROOF DECK.3. 1 1/2" x 20 GA METAL ROOF DECK. BMD = 13'-5" ABOVE EXISTING THIRD FLOOR.4. 3" x 22 GA METAL ROOF DECK. BMD = 16'-0" +/- ABOVE EXISTING THIRD FLOOR. VERIFY ELEVATION WITH ELEVATOR SUPPLIER.5. EXISTING SLOPED GABLE ROOF STRUCTURE REMOVED BETWEEN GRIDS 3 AND 4 FROM GRID C TO EXISTING TOWER.6. NEW 8" THICK CMU WALL PARTIALLY GROUTED w/ #5 @ 32"oc. PROVIDE DOUBLE BOND BEAM w/ (2) #5 HORIZONTALS AT EACH FLOOR LEVEL. DRILL AND EPOXY BOND BEAM DOWELS INTO EXISTING FLOOR STRUCTURE AT CMU WALL ENDS. 7. WHERE SHOWN ON PLAN , 8" CMU WALL PER NOTE 6 INSTALLED BETWEEN THIRD FLOOR SLAB TO UNDERSIDE OF EXISTING STAIR ROOF SLAB PRIOR TO EXISTING ELEVATOR SHAFT FRAMING REMOVAL IDENTIFIED IN NOTE 1.8. * VERIFY DIMENSION WITH ELEVATOR SUPPLIER.9. COORDINATE SHAFT OPENING SIZE AND LOCATIONS WITH MEP.
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
The Professional Engineer whose personal seal and signature Appears on this page assumes responsibility only for what appears on this page and disclaims (pursuant to Section 327.411 RSMo) any responsibility for all other pages, plans, specifications, estimates, reports, or other documents or instruments not sealed by this Professional Engineer relating to, or intended to be used for, any part or parts of the engineering project to which this page refers.
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
71
1:0
1:3
8 A
MC
:\U
se
rs\t
ah
intz
.KP
FF
-ST
L\D
ocu
me
nts
\17
00
11
9_M
em
ori
al S
tud
en
t U
nio
n_T
AH
v17
_C
en
tra
l_tim
.hin
tz@
kp
ff.c
om
.rvt
1700119
TAH
HIGH ROOF FRAMINGPLAN
S206
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/8" = 1'-0"S206
1 HIGH ROOF FRAMING PLAN
No. Description Date
2 Addendum #2 12-14-17
(E) STAIR ROOF SLAB
NOTE:8" CMU WALL MUST BE INSTALLED PRIOR TO DEMO OF (E) ROOFSLABOVER ELEVATOR SHAFT
(E) BEAM BEYOND
DWL INTO (E) CONC BEAM
8" CMU WALL, SEE PLAN
BOND BEAM @ METALDECK ELEVATION
HSS 5x5 LIFE LINE BEAMSEE PLAN
W8 HOIST BEAMSEE PLAN
DEMO (E) ROOF SLAB@ ELEVATOR
L 4x4x3/8 w/ 3/4" DIAADHESIVE ANCHORS@ 16"oc, TYP ALL SIDES
DOUBLE BOND BEAM@ ROOF LEVEL SEE PLAN NOTES
8" CMU WALLSEE PLAN
(E) CONC STRUCTURETO REMAIN
1/2"x12"x12" PLw/ (4) 5/8" DIA EXP ANCHORS@ 32"oc
2
4
PER ARCH
PE
R A
RC
H 3/16 2-6
3/16 2-6
BMD EL SEE PLAN
5/16" x CONT BENT PL
VERT SLIP CONN
METAL PANEL 600S METAL STUD
4
6"
w/ ARCHCOORD
CONC CURB, REINF w/(1) #4, T & B, CONT
#3 DWLS @ 12"ocDRILL & EPOXY 2" INTO(E) SLAB & 6" INTO DIST RIB & (E) BEAM
PAF ATTACHMENTPER METAL STUDDESIGNER
600S METAL STUDS
THIRD FLOOR
METAL PANEL
C
2 5/8" +/-
3" BMD EL SEE PLAN
T/PARAPETPER ARCH
T/ (E) SLOPED ROOF DECK (FV)
1/4
1/4
VERT SLIP TRACK
600S METAL STUDS
HSS 10x6 BRACEPER 1/S501
L 8x6x3/8 (LLV) x 3'-0" LGHORIZ SEGMENTS (GALV)STEP w/ ROOF SLOPE
3/16 2-6
3/16 2-6EA JOIST
STONE CAP PER ARCH
1/4" x CONT BENT PL
CONT L 3x3x1/4(GALV)
1/4" BENT PL w/ 0.134 DIA PAF @ 6"oc, INTO (E) PRECASTPANEL
(E) PRECAST PANEL
(E) ROOF CHANNEL1/4
L 6x4 (LLV)SEE PLAN
ARCH
PER
STONE VENEER SEE ARCH
HSS 3x2 1/2x5/16, BETWEEN EAJOIST ALONG GRID C
2-6
2-6
w/o
HA
NG
ER
3" M
IN
1"
6"
PROVIDE L 6x4x3/8 HANGER@ EA END OF L 6x4 OR L 8x6WHERE 3" VERT ATTACHMENTIS NOT AVAILABLE
1/4
ELEVATION OF (E) SLOPEDROOF VARIES FROM HSS 10x6 BRACE
3/16@ EA SUPPORT L
H G.8
1'-2" +/-, FV
PAF ATTACHMENTPER METAL STUDDESIGNER
BMD EL SEE PLAN
T/PARAPETPER ARCH
3"
1" +/- FV
3/16 2-6
3/16 2-6 EA JOIST & HSSSHIM
1/4" x CONT BENT PL
VERT SLIP CONN
W10, SEE PLAN
(E) PRECAST PANEL
BRACED FRAME BRACE
(E) W16
HSS 3x2 1/2x5/16, BETWEEN EAJOIST ALONG GRID G.8
2-6
2-6
(E) ROOF PRECAST PANEL
1/4" x CONT BENT PL w/ 0.134 DIA PAFS @ 6"oc
3/16 2-6
3/16 2-6
SECOND FLOOR
3", EOS
1/4" BENT PL
3/16
3/16
CLOSURE PL PER ARCH
3" TO CL OF BM
2" MIN
ATTACHMENT PER 10/S103
NOTCH CLADDING BACKINGLOCALLY @ BEAM TO COLATTACHMENT, THEN REPATCH
INTERIOR CLADDING FACE
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
The Professional Engineer whose personal seal and signature Appears on this page assumes responsibility only for what appears on this page and disclaims (pursuant to Section 327.411 RSMo) any responsibility for all other pages, plans, specifications, estimates, reports, or other documents or instruments not sealed by this Professional Engineer relating to, or intended to be used for, any part or parts of the engineering project to which this page refers.
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
71
1:0
1:4
0 A
MC
:\U
se
rs\t
ah
intz
.KP
FF
-ST
L\D
ocu
me
nts
\17
00
11
9_M
em
ori
al S
tud
en
t U
nio
n_T
AH
v17
_C
en
tra
l_tim
.hin
tz@
kp
ff.c
om
.rvt
1700119
Author
FRAMING SECTIONS ANDDETAILS
S402
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
3/4" = 1'-0"S402
1 SECTION
3/4" = 1'-0"S402
2 SECTION
3/4" = 1'-0"S402
3 SECTION
3/4" = 1'-0"S402
4 SECTION
3/4" = 1'-0"S402
5 SECTION
3/4" = 1'-0"S402
6 SECTION
3/4" = 1'-0"S402
7 SECTION
No. Description Date
2 Addendum #2 12-14-17
FIRE PROTECTION SYMBOL LIST
SYMBOL: DESCRIPTION:
FIRE PROTECTIONFP
SERVICE WATER - POTABLEW
AIR PRESSURE MAINTENANCE DEVICE
AIR SUPERVISORY SWITCH
ANGLE VALVE
BUTTERFLY VALVE WITH MONITOR SWITCH
OS&Y GATE VALVE
OS&Y GATE VALVE WITH MONITOR SWITCH
PRESSURE SWITCHP
NO HATCHLIGHT HAZARD (0.10 GPM/SQ.FT.OVER 1500 SQ.FT WITH 250 GPM HOSE STREAM ALLOWANCE PER FM GLOBAL)
SPRINKLER - WALL MOUNTED
SPRINKLER
SPRINKLER - CONCEALED
SPRINKLER
SPRINKLER
SPRINKLER
SPRINKLERA
SPRINKLERA
INSPECTOR TEST AND DRAIN VALVE
MONITOR SWITCH
PIPE CAP
PIPE DOWN
INDICATES POINT OF CONNECTION BETWEEN NEW AND EXISTING
PIPE UP OR UP/DOWN
SHUTOFF VALVE NORMALLY OPEN
DRAINDFP
NOT ALL SYMBOLS MAY APPLY.
AUTOMATIC DRAIN VALVE
UNION/FLANGE
DIRECTION OF FLOW IN PIPE
CHECK VALVE
PRESSURE GAUGE (FURNISHED WITH BALL VALVE)P
ORDINARY HAZARD GROUP 1(0.20 GPM/SQ.FT.OVER 2500 SQ.FT WITH 250 GPM HOSE STREAM ALLOWANCE PER FM GLOBAL)
ORDINARY HAZARD GROUP 2(0.30 GPM/SQ.FT. OVER 2500 SQ.FT WITH 250 GPM HOSE STREAM ALLOWANCE PER FM GLOBAL)
FIRE PROTECTION ABBREVIATION KEY
AD ACCESS DOOR
BFP BACKFLOW PREVENTER
N.C. NORMALLY CLOSED
ABOVE FINISHED FLOORAFF
NC NEW CONNECTION
NOT IN CONTRACTNIC
NORMALLY OPENN.O.
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
I.E. INVERT ELEVATION
NOT ALL SYMBOLS MAY APPLY
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER IS THE BASIS OF DESIGN.
3. FIRE PROTECTION PIPE ROUTING IS SHOWN FOR GENERAL LAYOUT. DETERMINE EXACT NUMBER OF SPRINKLERS, PIPE SIZING, AND PIPE ROUTING.
4. CENTER SPRINKLERS IN CEILING TILES IN BOTH DIRECTIONS IN ALL AREAS. IN AREAS WITH 2’X4’ CEILING TILES CENTERING USING A 2’X2’ CEILING PATTERN IS ACCEPTABLE.
5. NEW SPRINKLERS SHALL BE QUICK RESPONSE TYPE, UNLESS OTHERWISE NOTED. CONTRACTOR SHALL NOT MIX STANDARD RESPONSE SPRINKLERS WITH QUICK RESPONSE SPRINKLERS IN UNPARTITIONED SPACES.
6. PROVIDE COVERAGE ABOVE AND BELOW ALL DUCTWORK GREATER THAN 48" WIDE. 7. PROVIDE COVERAGE ABOVE AND BELOW FLOATING CEILINGS, REFER TO ARCHITECTURAL
PLANS. 8. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, PIPING, ETC. ARE DIAGRAMMATIC AND
MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
9. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
10. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
11. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
12. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
13. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
14. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
15. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
16. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
17. SEAL ALL FLOOR, WALL PENETRATIONS AIRTIGHT WHERE PIPING PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
18. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
19. WHERE PIPES ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
20. DO NOT BLOCK TUBE PULL OR EQUIPMENT SERVICE CLEARANCES. 21. MAINTAIN MINIMUM NEC CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR
STARTERS, SWITCHES, AND DISCONNECTS.22. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER
NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
23. ALL VERTICAL PIPE PENETRATIONS SHALL BE FIELD COORDINATED TO MISS EXISTING CONCRETE BEAMS AND SLAB RIBS.
FIRE PROTECTION GENERAL NOTES:
2
LINE TYPE KEY:
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
FIRE PROTECTION RENOVATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR CONSTRUCTION MANAGER ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLTIONS WHICH REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
12" MAX.12" MAX.
ARMOVER TO SPRINKLER
FIRE PROTECTION BRANCH LINE OR CROSS MAIN.
ADJUSTABLE SWIVEL RING PIPE HANGER. (NOTE 3)
THREADED ROD TIGHT TO PIPE.
ESCUTCHEON (TYP.)
REFER TO SPRINKLER USAGE SCHEDULE FOR TYPE OF SPRINKLER HEAD.
CEILING(TYP.)
END-OF-LINE ARMOVER
NOTES:
1. THIS DETAIL APPLIES TO SPRINKLER PIPES ABOVE CEILING THAT SUPPLY PENDENT SPRINKLERS BELOW CEILINGS WHERE THE WATER PRESSURE EXCEEDS 100 PSIG (STATIC OR RESIDUAL).
2. ALSO APPLIES TO ARMOVER WHERE CUMULATIVE HORIZONTAL LENGTH IS GREATER THAN 12".
3. CLEVIS HANGERS AND ADJUSTABLE SWIVEL RING HANGERS WITH SURGE SUPPRESSORS ARE ALSO ACCEPTABLE, SEE NFPA 13.
(NOTE 2)
REFER TO SPRINKLER USAGE SCHEDULE FOR TYPE OF SPRINKLER HEAD.
THREADED ROD.(TYP.)
OVERSIZE HANGER TO ALLOW LONGITUDINAL PIPE EXPANSION AND PIPE INSULATION TO PASS THROUGH UNBROKEN. (TYP.)
UNI-STRUT OR EQUIVALENT
THREADED ROD.(TYP.)
INSTALL CLAMP ON ALL PIPES LESS THAN 4"Ø
THREADED ROD
CLEVIS HANGER
NOTES:
1. REFER TO SPECIFICATION SECTION 21 05 29.
CLEVIS HANGER
STRUCT CAMP HANGERSTRAPEZE HANGER
INSTALL AN ESCUTCHEON AROUND PIPES EXPOSED IN FINISHED ROOMS. FOR ALL INSULATED PIPING INSTALL A PLASTIC JACKET EXTENDING 6" BEYOND THE WALL TO PROTECT INSULATION FROM DAMAGE.
MAKE A SMOOTH ROUND OPENING IN WALL SLIGHTLY LARGER THAN OUTSIDE DIAMETER OF THE PIPE AND INSULATION.
ADD A BEAD OF NON-HARDENING CAULK IN THE ANNULAR SPACE.
NOTES:
1. THIS DETAIL APPLIES TO ALL PIPES. THE INTENTION IS TO CONTINUE THE INSULATION AND VAPOR BARRIER THROUGH ALL PENETRATIONS. PERMIT THERMAL EXPANSION WITHOUT DAMAGING INSULATION, AND TO SEAL AIRTIGHT AROUND INSULATED AND UNINSULATED PIPES FOR NOISE TRANSMISSION CONTROL.
2. FLOOR OPENINGS ARE SIMILAR SEE SPECIFICATION SECTION 21 05 29 FOR DIFFERENCES BETWEEN FLOOR AND WALL PENETRATIONS.
TEST DATE:
RESIDUAL HYDRANT #:LOCATION:STATIC PRESSURE:RESIDUAL PRESSURE:
FLOW HYDRANT #:LOCATION:
TOTAL FLOW:
SIZE OF MAIN:
FIRE HYDRANT FLOW TEST DATA
10/10/2017
MUH-202 WEST OF WHITTEN 60 PSI 48 PSI
MUH-031WEST OF WHITTEN
1761 GPM
8"
FIRE PROTECTION PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF SCHEDUALING REQUIREMENTS. REFER TO ARCHITECTS INSTRUCTIONS FOR MORE DETAILS, PHASING SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE SCHEDUALING CRITERIA.
2. REVIEW PROJECT SCHEDUALING REQUIREMENTS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
FIRE PROTECTION SHEET INDEXF000 FIRE PROTECTION COVER SHEET
FD100 SUB BASEMENT FLOOR PLAN - FIRE PROTECTION - DEMO
FD100.5N GROUND FLOOR PLAN - NORTH WING - FIRE PROTECTION - DEMO
FD101N FIRST FLOOR PLAN - NORTH WING - FIRE PROTECTION - DEMO
FD102N SECOND FLOOR PLAN - NORTH WING - FIRE PROTECTION - DEMO
FD103N ATTIC FLOOR PLAN - NORTH WING - FIRE PROTECTION - DEMO
F100 SUB BASEMENT FLOOR PLAN - FIRE PROTECTION
F100.5N GROUND FLOOR PLAN - NORTH WING - FIRE PROTECTION
F100.5S GROUND FLOOR PLAN - SOUTH WING - FIRE PROTECTION
F101N FIRST FLOOR PLAN - NORTH WING - FIRE PROTECTION
F101S FIRST FLOOR PLAN - SOUTH WING - FIRE PROTECTION
F102N SECOND FLOOR PLAN - NORTH WING - FIRE PROTECTION
F102S SECOND FLOOR PLAN - SOUTH WING - FIRE PROTECTION
F103N ATTIC FLOOR PLAN - NORTH WING - FIRE PROTECTION
F103S THIRD FLOOR PLAN - SOUTH WING - FIRE PROTECTION
F600 FIRE PROTECTION RISER DIAGRAM
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:12
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
FIRE PROTECTION COVERSHEET
F000
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFYQUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THEQUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THESPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THEFIRST LISTED MANUFACTURER IS THE BASIS OF DESIGN.
CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE,LOCAL GOVERNING AUTHORITIES. AND COMPLY WITH FM GLOBAL REQUIREMENTS.
FIRE PROTECTION MATERIAL LIST
TAG NAME DESCRIPTION MANF. & MODEL
ADV-1 AUTOMATIC DRIP VALVE, 175 PSI WP, BRASS BAR,BERYLLIUM COPPER SPRING AND RETAINING RING, CLOSINGPRESSURE 7 PSI WITH INCREASING PRESSURE, OPENINGPRESSURE 5 PSI WITH DECREASING PRESSURE, 1/2" NPTINLET AND 1/4" NPT DRAIN OUTLET.
VIKING B-1TYCO AD-1RELIABLE C
AV-1 ANGLE VALVE, 1/2" TO 2”, 175 PSI, BRONZE BODY, INTEGRALSEAT, SOFT DISC, HANDWHEEL, THREADED. UL.
UNITED 126S ULNIBCO KT-67-UL / T-301-WKENNEDY 98 SD, FPPI
BF-1 2" TO 12" BUTTERFLY VALVE, 175 PSI WP, LUGGED ORGROOVED TYPE, IRON BODY, ALUMINUM BRONZE OR EPDMCOATED IRON DISC, STAINLESS STEEL STEM AND SCREWS,EPDM SEAT, INTEGRAL MONITOR SWITCH, RATED FOR DEADEND SERVICE, UL/FM.
GEM 8000FPTYCO BFVKENNEDY 01NIBCO LD3510-8GD-4765-8NVICTAULIC 705-W
BFP-1 6" DOUBLE CHECK BACKFLOW PREVENTER WITH SPRINGLOADED CHECK VALVES. CAST IRON CONSTRUCTION, WITHBRONZE, PLASTIC OR STAINLESS STEEL INTERNAL PARTSAND STAINLESS STEEL SPRINGS. OS&Y RISING STEMSHUTOFF GATE VALVES ON BOTH SIDES OF CHECK VALVES.UNITS SHALL INCLUDE FOUR TEST COCKS WITH SHUT-OFFVALVES AND SHALL BE BACKFLOW TESTED AT THEFACTORY. RATED FOR 175 PSI AT 33 DEGREES F. TO 140DEGREES F. MAXIMUM PRESSURE DROP 8 PSI AT 10 FPSREGARDLESS OF SIZE. FLOW PRESSURE DROP CURVESSHALL BE SUBMITTED. ALL PARTS TO BE SERVICEABLEWITHOUT REMOVING UNIT FROM LINE. APPROVED BY: USCFCCC & HR, AWWA C510-92, ASSE 1015, IAPMO AND SBCCILISTED, UL/FM.
WATTS SERIES 007 & 709CONBRACO SERIES 40-100FEBCO 850WILKINS 950XL & 350
CK-16 2-1/2" TO 12" SWING CHECK VALVE, 175 PSI WP, FLANGED ORGROOVED, IRON BODY, BRONZE MOUNTED, BRONZE SEATRING AND RUBBER CLAPPER FACING, SWING TYPE, UL/FM.
VIKING D-1/G-1TYCO CV-2RELIABLE D OR GKENNEDY 126A OR 426
FDC-1 EXPOSED FIRE DEPT. WITH 4 INLET CONNECTIONS,POLISHED CHROME PLATED TWO-WAY INLET BODY WITHDROP CLAPPERS, PIN LUG SWIVELS, PLUGS, CHAINS KNOXSTAINLESS STEEL LOCKING FDC CAPS WITH MATCHINGTHREADS AND CHROME FINISH, POLISHED CHROME PLATEDWALL PLATE LABELED AUTO. SPR. UL. THREADS TO MATCHLOCAL FIRE DEPARTMENT.CONTRACTOR TO COORDINATE PURCHASE OF KNOXLOCKING CAP WITH LOCAL FIRE DEPARTMENT.
POTTER-ROEMER 5216, CROKER, GUARDIAN,ELKHART.
FS-1 FLOW SWITCH - VANE TYPE FOR USE ON WET PIPESPRINKLER SYSTEM TO DETECT A MINIMUM FLOW OF 10GPM. TWO SINGLE POLE DOUBLE THROW SWITCHES WITHPNEUMATIC RETARD-ADJUSTABLE FROM 0-90 SECONDSWITH AUTOMATIC RESET, TAMPER RESISTANT METALHOUSING. UL/FM.
SYSTEM SENSOR WFD SERIES, POTTER ELECTRICVSR-F
HV-1 2-1/2" HOSE VALVE, ANGLE TYPE, CAST BRASS BODY ANDTRIM, RISING STEM, CAP AND CHAIN, RED HAND WHEEL.HOSE THREADS TO MATCH LOCAL FIRE DEPARTMENT.
POTTER-ROEMER 4065CROKER 5035ELKHART U-25KENNEDY 936
IT-1 1" INSPECTOR'S TEST AND DRAIN VALVE WITH INTEGRALSIGHT GLASS, BALL VALVE WITH INTEGRAL LABELED PLATESHOWING OFF-TEST-DRAIN POSITIONS. FURNISHED WITHTEST ORIFICE GIVING FLOW EQUIVALENT TO ONESPRINKLER OF A TYPE HAVING THE SMALLEST ORIFICEINSTALLED ON THE SYSTEM, UL.
RELIABLE B W/1" BALL VALVETYCO F350AGF MODEL 1000
MS-1 MONITOR SWITCH - ELECTRIC, ONE SINGLE POLE, DOUBLETHROW CONTACT, CAST ALUMINUM HOUSING WITHCORROSION RESISTANT PARTS, WITH J-BOLTS FORMOUNTING. UL/FM. VERIFY ELECTRICAL CHARACTERISTICSWITH ELECTRICAL CONTRACTOR PRIOR TO PURCHASE.
POTTER ELECTRIC OSYSU-1SYSTEM SENSOR OSY2
NOTES: 1. SEE FLOOR PLANS FOR ZONING REQUIREMENTS. 2. SPRINKLER SHALL HAVE COLOR CODED BULB THERMAL ELEMENT. 3. ALL SPRINKLERS SHALL BE UL AND FM LISTED. 4. CONTRACTOR TO VERIFY SPRINKLER REQUIREMENTS BASED ON ACTUAL INSTALLATION, USAGE, ARCHITECTURAL CEILING PLAN AND NFPA 13
REQUIREMENTS. FOR RENOVATED AREAS MATCH TO EXISTING SPRINKLER HEAD TYPE. 5. TAG NAME IS PRIMARILY FOR IDENTIFIYING SPRINKLERS IN SUBMITTALS. IT MAY OR MAY NOT BE FOUND ELSEWHERE ON THE DRAWINGS.
CONTRACTOR TO SUBMIT ALL SPRINKLER TYPES TO BE USED. 6. AREAS ARE GENERAL IN NATURE. CONTRACTOR TO MATCH UNSCHEDULED AREAS TO SIMILAR SPACES.
FIRE SPRINKLER USAGE SCHEDULE
AREA TYPE(NOTE 1 & 6)
AREAHAZARD
SPRINKLER
TEMPERATURERATING MANUFACTURER & MODEL NOTES
TAG NAME(NOTE 4 & 5)
SPRINKLERTYPE
RESPONSECATEGORY FINISH
EXPOSED AREAS SEE PLANS SPR-1 UPRIGHT QUICK ROUGH BRASS 155 VIKING, RELIABLE F1FR, TYCO,VICTAULIC
NOTES 2, 3
FINISHED AREAS SEE PLANS SPR-2 CONCEALED QUICK CHROMEPLATED
155 VIKING, RELIABLE F1FR, TYCO,VICTAULIC
NOTES 2, 3
ELEVATOR SHAFT TOP SEE PLANS SPR-3 UPRIGHT QUICK ROUGH BRASS 135-170 VIKING, RELIABLE F1FR, TYCO,VICTAULIC
NOTES 2, 3
ELEVATOR SHAFTBOTTOM/SOUTHWING
3RD FLOOR OFFICE S303
SEE PLANS SPR-4 HORIZONTALSIDEWALL
QUICK ROUGH BRASS 135-170 VIKING, RELIABLE F1FR, TYCO,VICTAULIC
NOTES 2, 3
NO SCALE1SPRINKLER PIPE HANGER DETAIL
NO SCALE2PIPE SUPPORT DETAIL
NO SCALE3PIPE THROUGH NON-FIRE RATED WALL
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
2 ADDENDUM 2 12/14/2017
PLUMBING SYMBOL LIST
SYMBOL: DESCRIPTION:
PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD
PITCH PIPE IN DIRECTION
RD-16"(1000)
ROOF DRAIN PROPERTIES SYMBOLSIZE (ROOF SQ. FT.)
DIELECTRIC CONNECTION
UNION/FLANGE
BALANCING VALVE (NUMBER INDICATES GPM)GPM
CHECK VALVE
REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB
PIPE CAP
PIPE DOWN
PIPE UP OR UP/DOWN
DIRECTION OF FLOW IN PIPE
SHUTOFF VALVE NORMALLY OPEN
SHUTOFF VALVE NORMALLY CLOSED
COLD WATER - POTABLECW
DT DRAIN TILE
SANITARY DRAINAGE (GREASE LADEN)GSAN
HOT WATER RETRUN- POTABLEHWR
SUMP PUMPED DISCHARGESPD
SANITARY DRAINAGESW
STORM DRAINAGE (ROOF SQUARE FOOTAGE)ST(1,000)
STS STORM DRAINAGE (SECONDARY)
VENTSV
NOT ALL SYMBOLS MAY APPLY.
SOLENOID VALVE
SAFETY/RELIEF VALVE
HOT WATER - POTABLEHW
INDICATES POINT OF CONNECTION BETWEEN NEW AND EXISTING
PLUMBING ABBREVIATION KEY
CO CLEANOUT
DRINKING FOUNTAINDF
FLOOR CLEANOUTFCO
FLOOR DRAINFD
GREASE INTERCEPTORGI
HOSE BIBBHB
I.E. INVERT ELEVATION (FOR REFERENCE ONLY)
LAVATORYLAV
MOP BASINMB
ROOF DRAINRD
SINKSK
TRAP PRIMERTP
URINALUR
WATER CLOSETWC
WALL CLEANOUTWCO
ELECTRIC WATER COOLEREWC
VENT THROUGH ROOFVTR
AD ACCESS DOOR
ABOVE FINISHED FLOORAFF
BFP BACKFLOW PREVENTER
NC NEW CONNECTION
NOT IN CONTRACTNIC
ABBR: DESCRIPTION:
TYPICALTYP
UNLESS NOTED OTHERWISEUNO
EXISTINGE
WATER METERWM
CATCH BASINCB
CAST IRONCI
NOT ALL SYMBOLS MAY APPLY.
1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
4. INVERT ELEVATIONS ARE FROM EXISTING DRAWINGS AND MAY NOT BE ACCURATE. VERIFY ALL ELEVATIONS BEFORE BEGINNING WORK.
5. VERIFY UNDERGROUND PIPE SIZES, INVERT ELEVATIONS, AND LOCATIONS PRIOR TO BEGINNING ANY WORK.
6. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO PLUMBING FIXTURES.
7. EXISTING CONDITIONS ON DEMOLITION PLANS ARE PROVIDED TO INDICATE THE GENERAL SCOPE OF ITEMS TO BE REMOVED. SEE SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL DEMOLITION INFORMATION.
8. P.C. SHALL CUT AND PATCH EXISTING AS REQUIRED FOR NEW OR DEMOLITION WORK UNLESS NOTED OTHERWISE. SEE SPECIFICATION SECTION 22 05 05 FOR ADDITIONAL INFORMATION.
9. DRAWINGS SHOWING LOCATIONS OF PIPING ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF PIPING MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.
10. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.
11. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.
12. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.
13. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.
14. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.
15. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY AUDIO/VISUAL, AND OTHER MECHANICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES, OTHER THAN SPRINKLERS.
16. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.
17. IN AREAS WITH DRYWALL CEILINGS COORDINATE LOCATIONS OF ACCESS PANELS WITH THE GC FOR ACCESS TO VALVES, DUCTWORK ACCESSORIES, DAMPERS, ETC. COORDINATE PANEL TYPE AND COLOR WITH ARCHITECT. NOTIFY THE GC OF THE REQUIRED ACCESS PANELS PRIOR TO BIDDING.
18. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE PIPING PENETRATE. PENETRATIONS THROUGH ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.
19. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.
20. WHERE PIPES ARE SHOWN TO PENETRATE FLOORS, PROVIDE SLEEVED OPENINGS WITH THE TOP EDGE RAISED ABOVE FLOOR SURFACE IN ACCORDANCE WITH ALL RELEVANT SPEC SECTIONS. SEAL SLEEVE PERIMETER TO BE WATERTIGHT.
21. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.
22. NEW VERTICAL PLUMBING CONCRETE CORES TO AVOID EXISTING CONCRETE SLAB RIBS. IN EVENT THAT A SLAB RIB IS CUT, REFER TO STRUCTURAL DOCUMENTS FOR STRUCTURAL MITIGATION REQUIREMENTS.
23. ALL VERTICAL PIPE PENETRATIONS SHALL BE FIELD COORDINATED TO MISS EXISTING CONCRETE BEAMS AND SLAB RIBS.
PLUMBING GENERAL NOTES:
LINE TYPE KEY:
NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)
EXISTING TO BE REMOVED BY THIS CONTRACTOR(DARK SHORT DASHED LINE)
PLUMBING RENOVATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD SURVEYS, EXISTING BUILDING DOCUMENTS. VERIFY EXISTING CONDITIONS AND REPORT ANY CONFLICTS BEFORE PROCEEDING.
2. NOT ALL EXISTING PIPING IS SHOWN. VERIFY EXISTING CONDITIONS BEFORE STARTING WORK. NOTIFY ENGINEER OF ANY CONFLICTS WITH NEW WORK.
3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR DUCTWORK AND PIPING BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING FIELD CONDITIONS.
4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS WORK AND SHALL NOTIFY THE GENERAL CONTRACTOR ARCHITECT/ENGINEER PRIOR TO BIDDING IF OTHER UTILITIES ARE REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS AREA OF WORK.
5. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR CUTTING, REMOVAL AND PATCHING OF ROOFS, WALLS, AND FLOORS ASSOCIATED WITH WORK BY ALL CONTRACTORS. CONTRACTORS SHALL NOTIFY THE GC OF AFFECTED AREAS PRIOR TO BIDDING.
6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO BIDDING.
7. WHERE EXISTING MECHANICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER ARRANGE NEW EQUIPMENT, PIPING, OR DUCTWORK IN SUCH A FASHION THAT IT DOES NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING MECHANICAL SYSTEMS TO ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
8. PROVIDE TEMPORARY CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN SERVICE DURING CONSTRUCTION. MAINTAIN ACCESS TO EXISTING MECHANICAL INSTALLTIONS WHICH REMAIN ACTIVE.
9. OBTAIN PERMISSION FROM OWNER BEFORE SHUTTING DOWN ANY SYSTEM FOR ANY REASON. MAINTAIN SERVICE TO ALL COMPONENTS THAT ARE TO REMAIN UNTIL NEW SYSTEMS ARE INSTALLED.
10. MAINTAIN EXISTING SYSTEM IN SERVICE UNTIL NEW SYSTEM IS COMPLETE AND READY FOR TIE IN AND SWITCHOVER. DRAIN SYSTEM ONLY TO MAKE SWITCHOVERS AND CONNECTIONS. OBTAIN PERMISSION FROM OWNER BEFORE PARTIALLY OR COMPLETELY DRAINING SYSTEM. MAKE CHANGEOVER TO NEW SYSTEMS WITH MINIMUM OUTAGE.
11. DISCONNECT AND REMOVE MECHANICAL DEVICES AND EQUIPMENT SERVING EQUIPMENT THAT HAS BEEN REMOVED.
PLUMBING FIXTURE SCHEDULE GENERAL NOTES
THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.
CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.
CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.
ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874
PLUMBING PHASING NOTES:
1. REFER TO ARCHITECTURAL DRAWINGS FOR GENERAL DESCRIPTION OF SCHEDUALING REQUIREMENTS. REFER TO ARCHITECTS INSTRUCTIONS FOR MORE DETAILS, SCHEDULES AND FOR CONCURRENT WORK. MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS DEPICT THE INTENT OF THE FINAL DESIGN. THE MECHANICAL, ELECTRICAL, AND TECHNOLOGY DRAWINGS DO NOT DEPICT THE MEANS AND METHODS TO MEET THE REQUIREMENTS OF THE SCHEDUALING CRITERIA.
2. REVIEW PROJECT SCHEDUALING REQUIREMENTS TO COORDINATE DEMOLITION WORK, OUTAGES, ETC. WITH AFFECTED ADJACENT AREAS.
3. PROVIDE TEMPORARY PIPING, SHUTOFF VALVES, ZONE VALVES, ZONE ALARMS, ETC. AS NEEDED TO MAINTAIN SERVICE TO ALL AREAS DURING ALL PHASES OF PROJECT.
4. INSTALL TEMPORARY PIPING, SHUTOFF VALVES, ETC. AS NECESSARY TO KEEP ALL OCCUPIED SPACES OPERATIONAL THROUGHOUT ALL PHASES OF THE PROJECT
5. PHASE DEMOLITION WORK TO MINIMIZE DOWNTIME.
PLUMBING SHEET INDEXP600A PLUMBING RISER DIAGRAM ALT1
P000 PLUMBING COVER SHEET
PD100 SUB BASEMENT FLOOR PLAN - PLUMBING - DEMO
PD100.5N GROUND FLOOR PLAN - NORTH WING - PLUMBING - DEMO
PD101N FIRST FLOOR PLAN - NORTH WING - PLUMBING - DEMO
PD102N SECOND FLOOR PLAN - NORTH WING - PLUMBING - DEMO
PD103N ATTIC FLOOR PLAN - NORTH WING - PLUMBING - DEMO
PD104N ROOF PLAN - NORTH WING - PLUMBING - DEMO
P100 SUB BASEMENT FLOOR PLAN - PLUMBING
P100.5N GROUND FLOOR PLAN - NORTH WING - PLUMBING
P100.5S GROUND FLOOR PLAN - SOUTH WING - PLUMBING
P101N FIRST FLOOR PLAN - NORTH WING - PLUMBING
P102N SECOND FLOOR PLAN - NORTH WING - PLUMBING
P103N ATTIC FLOOR PLAN - NORTH WING - PLUMBING
P104N ROOF PLAN - NORTH WING - PLUMBING
P400 PLUMBING - ENLARGED PLANS
P500 PLUMBING DETAILS
P600 PLUMBING RISER DIAGRAM
P601 PLUMBING RISER DIAGRAM
NOTES: 1) SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2". 2) BRANCH PIPINGTO VERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" UNLESS NOTED OTHERWISE. 3) SIZES SHOWNARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED IN THESCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.
PLUMBING FIXTURE ROUGH-IN SCHEDULE
FIXTUREDESCRIPTION
DOMESTICCW
(NOTE 3)
DOMESTICHW
(NOTE 3)SANITARY(NOTE 3)
VENT(NOTE 3) REMARKS
ELECTRIC WATERCOOLER
1/2" - 2" 1 1/2" NOTE 1 & 2
FLOOR DRAIN - - 3" 1 1/2" NOTE 1
FLOOR SINK - - 3" 1 1/2" NOTE 1
HOSE BIBB 3/4" - - - NOTE 2
LAVATORY 1/2" - 2" 1 1/2" NOTE 1 & 2
MOP BASIN 3/4" 3/4" 3" 1 1/2" NOTE 1 & 2
SINK 3/4" 3/4" 2" 1 1/2" NOTE 1 & 2
URINAL 1" - 2" 1 1/2" NOTE 1 & 2
WATER CLOSET 2" - 4" 2" NOTE 1 & 2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:19
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
PLUMBING COVER SHEET
P000
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
PLUMBING FIXTURE SCHEDULETAG NAME DESCRIPTION MANF. & MODEL
UR-1 URINAL - NON- ACCESSIBLE, WALL MOUNTED, WHITEVITREOUS CHINA, FLUSH VALVE TYPE, SIPHON JET, LOWCONSUMPTION, EXTENDED FRONT, 3/4" TOP SPUD, 2"OUTLET.
FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERYPOWERED, 0.50 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECKVALVE WITH VANDAL RESISTANT CAP, HIGH BACKPRESSURE VACUUM BREAKER, NON-HOLD-OPENHANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING ANDFLANGE, WALL FLANGE WITH SET SCREW, MANUALOVER-RIDE, LOW BATTERY INDICATOR LIGHT, RANGEADJUSTMENT SCREW, CHLORAMINE RESISTANTMATERIALS, 3-YEAR WARRANTY.
CONTRACTOR OPTION: COMBINATION URINAL/FLUSHVALVE PACKAGED SYSTEM BY AMERICAN STANDARD,KOHLER, SLOAN, OR ZURN
ACCESSORIES - SUPPORT CARRIER WITH TOP ANDBOTTOM BEARING PLATES.
MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR.TOP OF BOWL RIM SHALL BE AT 17" (MAXIMUM) ABOVEFLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS.VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-INLOCATIONS.
URINAL - AMERICAN STANDARD(6590.505), KOHLERFLUSH VALVE - ZURN (ZER6003AV),SLOAN
UR-2 URINAL - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUSCHINA, FLUSH VALVE TYPE, SIPHON JET, LOWCONSUMPTION, EXTENDED FRONT, 3/4" TOP SPUD, 2"OUTLET.
FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERYPOWERED, 0.50 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECKVALVE WITH VANDAL RESISTANT CAP, HIGH BACKPRESSURE VACUUM BREAKER, NON-HOLD-OPENHANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING ANDFLANGE, WALL FLANGE WITH SET SCREW, MANUALOVER-RIDE, LOW BATTERY INDICATOR LIGHT, RANGEADJUSTMENT SCREW, CHLORAMINE RESISTANTMATERIALS, 3-YEAR WARRANTY.
CONTRACTOR OPTION: COMBINATION URINAL/FLUSHVALVE PACKAGED SYSTEM BY AMERICAN STANDARD,KOHLER, SLOAN, OR ZURN
ACCESSORIES - SUPPORT CARRIER WITH TOP ANDBOTTOM BEARING PLATES.
MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR.TOP OF BOWL RIM SHALL BE AT 17" (MAXIMUM) ABOVEFLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS.VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-INLOCATIONS.
URINAL - AMERICAN STANDARD(6590.505), KOHLERFLUSH VALVE - ZURN (ZER6003AV),SLOAN
WC-1 WATER CLOSET - NON-ACCESSIBLE, WALL MOUNTED,FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHONJET, WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD.
FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERYPOWERED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECKVALVE WITH VANDAL RESISTANT CAP, HIGH BACKPRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE,SPUD COUPLING AND FLANGE, WALL FLANGE WITH SETSCREW, MECHANICAL OVER-RIDE BUTTON, CHLORAMINERESISTANT MATERIALS, ADA COMPLIANT, 3 YEARWARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTIONMOLDED SOLID ANTI-MICROBIAL PLASTIC, CHECK HINGE,STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.
CONTRACTOR OPTION: COMBINATION WATERCLOSET/FLUSH VALVE PACKAGED SYSTEM BY AMERICANSTANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - WATER CLOSET SUPPORT CARRIERRATED FOR 500 LBS.
MOUNT WATER CLOSET WITH CARRIER BOLTEDSECURELY TO FLOOR. TOP OF SEAT SHALL BE AT 17"-19"ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTINGHEIGHT WITH MANUFACTURER). VERIFY EQUIPMENTREQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET - AMERICANSTANDARD, KOHLER (K-4325),
FLUSH VALVE - ZURN (ZR6000AV),SLOAN
WC-2 WATER CLOSET - ACCESSIBLE, WALL MOUNTED, FLUSHVALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET,WATER SAVING, ELONGATED BOWL, 1-1/2" TOP SPUD.
FLUSH VALVE - EXPOSED, SENSOR OPERATION, BATTERYPOWERED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN,CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECKVALVE WITH VANDAL RESISTANT CAP, HIGH BACKPRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE,SPUD COUPLING AND FLANGE, WALL FLANGE WITH SETSCREW, MECHANICAL OVER-RIDE BUTTON, CHLORAMINERESISTANT MATERIALS, ADA COMPLIANT, 3 YEARWARRANTY.
SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTIONMOLDED SOLID ANTI-MICROBIAL PLASTIC, CHECK HINGE,STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.
CONTRACTOR OPTION: COMBINATION WATERCLOSET/FLUSH VALVE PACKAGED SYSTEM BY AMERICANSTANDARD, KOHLER, SLOAN, OR ZURN
ACCESSORIES - WATER CLOSET SUPPORT CARRIERRATED FOR 500 LBS.
MOUNT WATER CLOSET WITH CARRIER BOLTEDSECURELY TO FLOOR. TOP OF SEAT SHALL BE AT 17"-19"ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTINGHEIGHT WITH MANUFACTURER). VERIFY EQUIPMENTREQUIREMENTS AND ROUGH-IN LOCATIONS.
WATER CLOSET - AMERICANSTANDARD, KOHLER (K-4325),
FLUSH VALVE - ZURN (ZR6000AV),SLOAN
WCO-1 WALL CLEANOUT - END CAP, CAST IRON ACCESS BODY,GAS AND WATERTIGHT BRONZE OR BRASS THREADEDPLUG, ROUND STAINLESS STEEL ACCESS COVER,EXTENDED MACHINE SCREW.
ZURN (Z-1441), SMITH, WADE, JOSAM,WATTS
WHA-1 WATER HAMMER ARRESTER - BELLOWS TYPE,PRE-CHARGED, ALL LEAD FREE STAINLESS STEELCONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED,RATED FOR 1-11 FIXTURE UNITS.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
ZURN (Z1700), JR SMITH, WADE, JOSAM,WATTS, MIFAB
WHA-2 WATER HAMMER ARRESTER - BELLOWS TYPE,PRE-CHARGED, ALL LEAD FREE STAINLESS STEELCONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED,RATED FOR 12-32 & 33-60 FIXTURE UNITS.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
ZURN (Z1700), JR SMITH, WADE, JOSAM,WATTS, MIFAB
PLUMBING FIXTURE SCHEDULETAG NAME DESCRIPTION MANF. & MODEL
RD-1 ROOF DRAIN - CAST IRON BODY, SECURED CASTIRON DOME, 15" ROUND, BOTTOM OUTLET, FLASHINGCLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARINGPAN, ADJUSTABLE EXTENSION TO MATCH INSULATIONTHICKNESS, OUTLET SIZE AS LISTED ON DRAWINGS.
ZURN (Z-100), SMITH, WADE, JOSAM,WATTS, MIFAB, SUN
RD-E
RDO-1 ROOF DRAIN OUTLET - LAMBS TONGUE DOWNSPOUTNOZZLE, BRONZE BODY, INTEGRAL ANCHORING FLANGE,REMOVABLE STAINLESS STEEL SCREEN, OUTLET SIZEAS LISTED ON DRAWINGS.
ZURN (Z-199)
SI-1 SOLIDS INTERCEPTOR - HIGH DENSITY POLYETHYLENEOR ACID RESISTANT COATED STEEL BODY, FLOORMOUNTED INSTALLATION, REMOVABLE STAINLESS STEELSEDIMENT BASKET WITH COARSE FILTER, GASKETEDCOVER, 2" SIDE INLET AND OUTLET.
MINIMUM CAPACITY 15 GALLONS
MAINTAIN REQUIRED CLEARANCE ABOVE INTERCEPTORFOR REMOVAL OF SEDIMENT BUCKET. PROVIDE COVERAND BASKET HANDLE EXTENSIONS AS REQUIRED FORIN-FLOOR INSTALLATIONS.
STRIEM (PS-15-S)
SK-1 SINK - SELF-RIMMING SINGLE COMPARTMENT WITHFAUCET DECK AND OVERFLOW, 18 GAUGE TYPE304STAINLESS STEEL, 19" SIDE-TO-SIDE x 18"FRONT-TO-BACK OVERALL SIZE, 16" x 11.5" x 6.5" DEEPBOWL, COMPLETELY UNDERCOATED, 3-1/2" DIAMETERDRAIN OUTLET LOCATION CENTERED IN BOWL,PERFORATED TYPE 304 STAINLESS STEEL GRIDSTRAINER. REMOVABLE TYPE 304 STAINLESS STEELBASKET STRAINER WITH NEOPRENE STOPPER.
SINK TRIM - SINGLE HANDLE MIXING FAUCET, BRASSCONSTRUCTION, CHROME-PLATED FINISH, NOMINAL 10"HIGH-RISE SWING SPOUT, CERAMIC CARTRIDGE,NOMINAL 9" REACH, PULL DOWN SPRAY HOSE WITHAERATOR STREAM / SPRAY SELECTOR, LEVER HANDLE.
MAXIMUM FLOW TO BE 2.2 GPM IN COMPLIANCE WITHENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARDA112.18.1M.FAUCET SHALL COMPLY WITH FEDERAL ACTS.3874. PROVIDE RESTRICTIVE DEVICE ANDESCUTCHEON PLATE AS REQUIRED.
ACCESSORIES - 1-1/2" 17 GAUGE CHROME-PLATED BRASSTAILPIECE AND P-TRAP, QUARTER-TURN BALL VALVETYPE 3/8" CHROME-PLATED BRASS ANGLE SUPPLIESWITH STOPS, CHROME-PLATED SOFT COPPER SUPPLYLINES.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP,STOP VALVES, AND SUPPLY LINES.
SINK - ELKAY (LRADQ191855), JUST,FRANKE
SINK TRIM - AMERICAN STANDARD(4285.300), ZURN, SLOAN
INSULATION KIT - MCGUIRE (PROWRAP),JUST, PLUMBEREX, TRUEBRO
SP-1 SUMP PUMP - SIMPLEX SUBMERSIBLE, SINGLE-STAGE,SINGLE SEAL, CENTRIFUGAL, END-SUCTION PUMP,STAINLESS STEEL FASTENERS, GUARDS AND HANDLES,UL LISTED.
CASING - CAST IRON, INTEGRAL SUPPORT FEET, MINIMUM2" VERTICAL DISCHARGE. IMPELLER: CAST IRONSTATICALLY AND DYNAMICALLY BALANCED, SEMIOPENNONCLOG DESIGN, KEYED AND SECURED TO SHAFT,PASSES 3/4" SOLIDS MINIMUM. SHAFT - STEEL ORSTAINLESS STEEL WITH FACTORY SEALED,GREASE-LUBRICATED SLEEVE OR BALL BEARINGS,CARBON AND CERAMIC SEAL. MOTOR - 3450 RPM, OIL ORAIR-FILLED, HERMETICALLY SEALED WITH AUTO THERMALOVERLOAD PROTECTION, THREE CONDUCTORWATERPROOF POWER CABLE OF SUFFICIENT LENGTHWITH GROUNDING PLUG.
CAPACITY: 50 GPM, 25 FEET OF HEAD.
ELECTRICAL REQUIREMENTS - 1/2 HP, 120V, 1 PHASE.
FLOATS SHALL BE STAINLESS STEEL.
CONTROLS - INTEGRAL FLOAT SWITCH OR PIGGY-BACKFLOAT/DIAPHRAM SWITCH.
BASIN - 36" DIAMETER x 24" DEEP FORMED CONCRETEPIT BY OTHERS. PROVIDE CONTROL PANEL WITH HIGHWATER AND OIL PRESENT ALARM. REFER TO DRAWINGSFOR LOCATION.
PUMP - ZOELLER (160 SERIES), GOULDS
SP-2 SUMP PUMP - SIMPLEX SUBMERSIBLE, SINGLE-STAGE,SINGLE SEAL, CENTRIFUGAL, END-SUCTION PUMP,STAINLESS STEEL FASTENERS, GUARDS AND HANDLES,UL LISTED.
CASING - CAST IRON, INTEGRAL SUPPORT FEET, MINIMUM2" VERTICAL DISCHARGE. IMPELLER: CAST IRONSTATICALLY AND DYNAMICALLY BALANCED, SEMIOPENNONCLOG DESIGN, KEYED AND SECURED TO SHAFT,PASSES 3/4" SOLIDS MINIMUM. SHAFT - STEEL ORSTAINLESS STEEL WITH FACTORY SEALED,GREASE-LUBRICATED SLEEVE OR BALL BEARINGS,CARBON AND CERAMIC SEAL. MOTOR - 3450 RPM, OIL ORAIR-FILLED, HERMETICALLY SEALED WITH AUTO THERMALOVERLOAD PROTECTION, THREE CONDUCTORWATERPROOF POWER CABLE OF SUFFICIENT LENGTHWITH GROUNDING PLUG.
CAPACITY: 50 GPM, 25 FEET OF HEAD.
ELECTRICAL REQUIREMENTS - 1/2 HP, 120V, 1 PHASE.
FLOATS SHALL BE STAINLESS STEEL.
CONTROLS - INTEGRAL FLOAT SWITCH OR PIGGY-BACKFLOAT/DIAPHRAM SWITCH.
BASIN - 36" DIAMETER x 24" DEEP FORMED CONCRETEPIT BY OTHERS. PROVIDE CONTROL PANEL WITH HIGHWATER AND OIL PRESENT ALARM. REFER TO DRAWINGSFOR LOCATION.
PUMP - ZOELLER (160 SERIES), GOULDS
SP-3 SUMP PUMP - SIMPLEX SUBMERSIBLE, SINGLE-STAGE,SINGLE SEAL, CENTRIFUGAL, END-SUCTION PUMP,STAINLESS STEEL FASTENERS, GUARDS AND HANDLES,UL LISTED.
CASING - CAST IRON, INTEGRAL SUPPORT FEET, MINIMUM2" VERTICAL DISCHARGE. IMPELLER: CAST IRONSTATICALLY AND DYNAMICALLY BALANCED, SEMIOPENNONCLOG DESIGN, KEYED AND SECURED TO SHAFT,PASSES 3/4" SOLIDS MINIMUM. SHAFT - STEEL ORSTAINLESS STEEL WITH FACTORY SEALED,GREASE-LUBRICATED SLEEVE OR BALL BEARINGS,CARBON AND CERAMIC SEAL. MOTOR - 3450 RPM, OIL ORAIR-FILLED, HERMETICALLY SEALED WITH AUTO THERMALOVERLOAD PROTECTION, THREE CONDUCTORWATERPROOF POWER CABLE OF SUFFICIENT LENGTHWITH GROUNDING PLUG.
CAPACITY: 50 GPM, 30 FEET OF HEAD.
ELECTRICAL REQUIREMENTS - 1/2 HP, 120V, 1 PHASE.
FLOATS SHALL BE STAINLESS STEEL.
CONTROLS - INTEGRAL FLOAT SWITCH OR PIGGY-BACKFLOAT/DIAPHRAM SWITCH.
BASIN - 36" DIAMETER x 24" DEEP FORMED CONCRETEPIT BY OTHERS. PROVIDE CONTROL PANEL WITH HIGHWATER AND OIL PRESENT ALARM. REFER TO DRAWINGSFOR LOCATION.
PUMP - ZOELLER (160 SERIES), GOULDS
PLUMBING FIXTURE SCHEDULETAG NAME DESCRIPTION MANF. & MODEL
BFP-1 BACK FLOW PREVENTER - REDUCED PRESSURE ZONE,LEAD FREE BRONZE OR STAINLESS STEELCONSTRUCTION, SIZE SAME AS PIPE, NON-CORROSIVEINTERNAL PARTS, STAINLESS STEEL SPRINGS,DIFFERENTIAL PRESSURE RELIEF VALVE BETWEENSPRING-LOADED CHECK VALVES, SHUT-OFF VALVES ONINLET AND OUTLET OF UNIT, BALL STYLE SHUTOFFVALVES FOR 3/4"-2" AND GATE STYLE VALVES FOR 21/2"-10", AIR GAP DRAIN FITTING, TEST PORTS WITHSHUT-OFF VALVES, RATED FOR 175 PSI AT 33°F TO 140°F,15 PSI (MAXIMUM) PRESSURE DROP AT 10 FPS, FACTORYTESTED, ALL PARTS TO BE SERVICEABLE WITHOUTREMOVING UNIT FROM LINE, APPROVED BY USC FCCC &HR, AWWA C511-92, ASSE 1013, IAPMO AND SBCCI LISTED.
MOUNT WITHIN 60" OF FINISHED FLOOR. PROVIDE ANDINSTALL BRONZE OR EPOXY COATED STRAINERUPSTREAM OF EACH UNIT AND ADDITIONAL VALVEUPSTREAM OF EACH STRAINER. FLOW PRESSURE DROPCURVES SHALL BE SUBMITTED.
WATTS (LF919), WILKINS, ZURN
EWC-1 ELECTRIC WATER COOLER - WALL HUNG, RECESSEDCHILLER, TWO STAINLESS STEEL ROUND BASIN WITHSTAINLESS STEEL FINISH, PERFORATED DRAIN, STREAMPROJECTOR WITH PROTECTIVE HOOD, PUSH BAR ORLEVER OPERATING CONTROLS ON FRONT AND SIDES,BUILT-IN FLOW REGULATOR, PLASTIC P-TRAP ASSEMBLY,ADJUSTABLE THERMOSTAT, MOUNTING ACCESSORIES,TANK DRAIN AND ANGLE STOPS, HERMETICCOMPRESSOR TO OPERATE ON HFC-134a REFRIGERANT.COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS.
BOTTLE FILLING STATION - UNIT MOUNTED, STAINLESSSTEEL CONSTRUCTION AND FINISH, INTEGRAL DRAIN,SENSOR OPERATED WITH AUTOMATIC SHUTOFF, BOTTLECOUNTER, FILTER REPLACEMENT INDICATOR.
UNIT SHALL PROVIDE 8.0 GPH OF WATER FROM 80°F TO50°F AT 90°F AMBIENT. WATER SYSTEM SHALL BE OFLEAD FREE CONSTRUCTION. TANK SHALL BE TESTED TO125 PSIG.
ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHEDFLOOR. BOTTOM OF APRON SHALL BE AT 27" ABOVEFINISHED FLOOR IN COMPLIANCE WITH LATEST ADASTANDARDS.
ELECTRICAL REQUIREMENTS - 115V-1 PHASE, CORD ANDPLUG, 1/5 HP MOTOR
ELKAY (EZWS-EDFPBM117K)
FD-1 FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZEADJUSTABLE TOP, 6" ROUND, 3" BOTTOM OUTLET,FLASHING COLLAR,SURFACE MEMBRANE CLAMP, DEEPSEAL TRAP.
TRAP SEAL - 3", PLASTIC HOUSING WITH FLEXIBLEDIAPHRAGM, SEALING GASKETS, RECLOSES AND SEALSWHEN DISCHARGE IS COMPLETED, ASSE 1072.
FLOOR DRAIN - ZURN (Z-415B), SMITH,WADE, JOSAM, WATTS, MIFAB, SUN
TRAP SEAL - SURE SEAL (SS), PROVENT,SMITH , LIQUID BREAKER
FS-1 FLOOR SINK - CAST IRON BODY, NICKEL BRONZE RIM ANDGRATE, 12" SQUARE, 3" BOTTOM OUTLET, 6" DEEPRECEPTOR WITH ALUMINUM DOME STRAINER, ACIDRESISTANT COATED INTERIOR, SEEPAGE FLANGE WITHCLAMP, DEEP SEAL TRAP.
ZURN (Z1901), SMITH, WADE, JOSAM,WATTS, SIOUX CHIEF, SUN
GI-1 GREASE INTERCEPTOR - RECESSED, POLYETHYLENE,FIBERGLASS REINFORCED POLYESTER, OR EPOXYCOATED STEEL CONSTRUCTION, REMOVABLE ORCLEANABLE INTAKE AND DISCHARGE BAFFLES, INTERNALFLOW CONTROL FITTING IF NECESSARY FOR OPERATION,GASKETED COVER, PDI G101COMPLIANT, PDI APPROVED AND LISTED FOR USE, 30YEAR WARRANTY.
PROVIDE RISERS FOR EXTENDING COVER TO GRADE.PROVIDE TWO-WAY CLEANOUTS UPSTREAM ANDDOWNSTREAM OF GREASE INTERCEPTOR.
100 GPM FLOW, 1,076 LB. GREASE CAPACITY, 275GALLONS HOLDING CAPACITY, 4" PIPE INLET ANDOUTLET.
SCHIER (GB-250)
HB-1 HOSE BIBB - FOR INDOOR USE, BRASS CONSTRUCTION,STANDARD FINISH, ASSE APPROVED VACUUM BREAKER,3/4" MALE HOSE THREAD, METAL WHEEL HANDLE.
MOUNT AT 18" ABOVE FINISHED FLOOR.
PRIER, WOODFORD, CHICAGO FAUCET,ACORN, T&S BRASS, MIFAB
L-1 LAVATORY - UNDER COUNTER MOUNTED, OVAL,SELF-RIMMING, WHITE VITREOUS CHINA, 19"x16", SINGLEFAUCET HOLE, FRONT OVERFLOW
LAVATORY TRIM - SENSOR ACTIVATED NON-MIXINGFAUCET, BATTERY POWERED, BRASS CONSTRUCTION,CHROME-PLATED FINISH, SPOUT WITH AERATOR, SINGLEHOLE INSTALLATION, INTEGRAL CHECK VALVES,PERFORATED GRID STRAINER WITH 1-1/4" 17 GAUGETAILPIECE, EXTERNAL ADJUSTABLE TEMPERATURE,FAUCET MOUNTED CONTROLS AND BATTERIES.
MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITHENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARDA112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACTS.3874. PROVIDE RESTRICTIVE DEVICE ANDESCUTCHEON PLATE AS REQUIRED.
INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP,STOP VALVES, AND SUPPLY LINES.
ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATEDHEAVY BRASS ANGLE SUPPLY LOOSE KEY STOPS,CHROME PLATED SOFT COPPER SUPPLY LINES, 1-1/4" 20GAUGE CAST BRASS P-TRAP.
LAVATORY -AMERICAN STANDARD, KOHLER,SLOAN, TOTO, ZURN (Z5220)
LAVATORY TRIM - SLOAN, ZURN(Z6950)
INSULATION KIT - TRUEBRO(LAV-GUARD), BROCAR PRODUCTS,MCGUIRE, PLUMBEREX
MB-1 MOP BASIN - PRECAST TERRAZZO, 24"x24"x10",STAINLESS STEEL INTEGRAL DRAIN WITH REMOVABLESTRAINER, 3" OUTLET, CONTINUOUS STAINLESS STEELCAP ON ALL EDGES.
TRIM - EXPOSED TWO HANDLE MIXING FAUCET, BRASSCONSTRUCTION, CHROME-PLATED FINISH, SINGLE WINGHANDLES, 1/4 TURN CERAMIC DISC CARTRIDGE, 3/4"HOSE THREAD SPOUT WITH INTEGRAL VACUUMBREAKER, WALL BRACE, PAIL HOOK, CHECK STOPS ORINLINE CHECK VALVES TO PREVENT THERMALCROSSOVER. FAUCET SHALL COMPLY WITH FEDERALACT S.3874.
ACCESSORIES - MOP HANGER, HOSE AND HOSEBRACKET, DEEP SEAL TRAP
MOP BASIN - FIAT, ACORN, CREATIVEINDUSTRIES, WILLIAMS, ZURN(Z1996-24)
TRIM - DELTA , AMERICAN STANDARD(8344.012), CHICAGO FAUCETS, MOEN,SPEAKMAN, SYMMONS, ZURN
OD-1 OVERFLOW DRAIN - CAST IRON BODY, SECURED CASTIRON DOME, 15" ROUND, BOTTOM OUTLET, FLASHINGCLAMP, GRAVEL STOP, UNDERDECK CLAMP, BEARINGPAN, ADJUSTABLE EXTENSION TO MATCH INSULATIONTHICKNESS, 2" TALL EXTERNAL WATER DAM,OUTLET SIZEAS LISTED ON DRAWINGS.
ZURN (Z-100), SMITH, WADE, JOSAM,WATTS, MIFAB, SUN
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
2
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
3" SV DN
4" ST UP
3" SV DN 4" SV DN 3" SV DN
4" SV DN
4" ST DN
3" SV DN
4" SV DN
4" VTR4" SV DN
4" SV3" SV
4" SV
3" ST DN
3" RD UP
3" SV4" SV
3" SV
3" SV4" SV
3" SV
3" SV
4" SV
4" SV DN
3" SV DN
3" VTR 4" VTR
3" VTR
3" VTR
4" VTR
3" VTR
4" VTR
RD-E
RD-E
RD-E
RD-E
RD-E
RD-E
RD-E
RD-E
DEMOLISH ALL PLUMBING PIPING, ACCESSORIES, HANGERS, ETC. INSIDE THIS BOUNDARY.
REFER TO MEMORIAL UNION ORIGINAL CONSTRUCTION DOCUMENTS PROVIDED BY UNIVERSITY OF MISSOURI AS A REFERENCE FOR DEMOLITION OF EXISTING CONDITIONS.
3" VTR
3/4" HW DN
3/4" CW DN
RD-E
RD-E
3" SV UP & DN
4" ST UP
4" VTR
2
2
1
4" ST DN
RD-E
2
2
2
2
22
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:39
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
ATTIC FLOOR PLAN - NORTHWING - PLUMBING - DEMO
PD103N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - PLUMBING - DEMO
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
PHASING KEYNOTES:
1. WORK FOR ATTIC WILL BE PART OF SCHEDULING REQUIREMENT SR-6. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
2. WORK FOR ROOF AND DEMOLITION OF PENTHOUSE WILL BE PART OF SCHEDULING REQUIREMENT SR-8. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
#
No. Description Date
2 ADDENDUM 2 12/14/2017
DN
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N103B
StotlerLounge
N106ALounge
N107Men
N108Women
N106Seating Area
N123Starbucks
N126Seating Area
28Kitchen
N112Storage
LN101Lobby
VN100Vestibule
N114AFreezer
N117BStor
N117AOffice
VN120Vest.
N121Storage
N122Food Serv.
SN100EStairs
N106Seating Area
VN105Vest.
SN100BSTAIRS
N129AElec. Mech.
10.5
12
N116Office
SN100CSTAIRS
N111JAN.
N103
StotlerLounge
N103A
StotlerLounge
3" SV DN
2" SV DN
1/2" CW DN TO
ICE MACHINE
2" SV DN
1 1/2" SV UP1/2" HW DN
1/2" CW DN1 1/2" SV UP1/2" HW DN
1/2" CW DN
1 1/2" SV
DN
3" SV DN
4" ST DN
3" SV DN
3" SV UP
4" ST DN
CONNECT WITH EXISTING 3" SV COMING FROM FLOOR BELOW
4" ST UP
4" ST DN
6" ST CONNECT WITH EXISTING STORM PIPE ABOVE THE CEILING.
3" SV UP
6" ST DN
4" SW DN
3" SV CONNECT WITH EXISTING VENT
4"ST
3"SV
4"S
T
1/2"CW
1/2"CW
2"S
V
2"SV
1/2"HW1 1/2"SV
1/2"CW
1/2"HW3/4" HWR
1/2"CW
1/2"HW
1 1/2"SV
2"SV
1/2" CW DN
1/2" HW DN
1/2" HW / CW UP
FROM BELOW
TO WB-E
1/2" HW / CW DN
3" CW UP
CONNECT NEW 2'' CW PIPE TO EXISTING CW PIPE
3" CW DN
1'' HWR DN 4"S
W
CO
2" SW UP
2" SW UP
FD
WC
4"SW
3"SW 1 1/2" SV UP
CO
4"SW
4" SW UP
FD
4"SW
2" SW UP
CO
1 1/2" SV UP
4" SW UP
4"SW
FD
MB1 1/2" SV UP
3"SW
FD
1 1/2" SV UP
3"SWCO
3"S
W
4"SW
CO
SK 2"SW
4"SW
3" SV DN
6" ST UP
3" SV UP
3" SV UP
PROVIDE NEW CAP
3" SV UP
2'' HW DN
2"SV
4" SV UP
3"CW 3"CW
4"S
T
CO
4" ST UP 4"ST
FD
CO
3"SW
1 1/2" SV UP
3"SV
2'' HW UP
1'' HWR UP
4" ST CONNECT WITH EXISTING STORM PIPE
COCO
4" ST UP
SI-1
3"SW
1 1/2" SV UP
3" SW UP
MANHOLE FOR GREASE INTERCEPTOR
CO
4" ST UP
2" SW UP 4"SW
3"SW 3"SW
6" ST UP & DN
4" SW UP
2" GSAN
3" GSAN DN
PROVIDE NEW CONNECTION TO DISCHARGE OF EXISTING 3 COMPARTMENT SINK.
EXISTING 3
COMPARTMENT
SINK
PROVIDE NEW CAP
1
1
2
2
3
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:25
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
FIRST FLOOR PLAN - NORTHWING - PLUMBING
P101N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1FIRST FLOOR PLAN - NORTH WING - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL SHEET NOTES:
1. REFER TO P000 FOR GENERAL INFORMATION.
GENERAL PHASING NOTES:
1. DURING CONSTRUCTION OF FIRST/SECOND FLOOR, PLUMBING CONTRACTOR TO MAKE SURE ALL FIRST FLOOR PLUMBING WORK STAY IN OPERATION. 2. VENT AND SANITARY STORM PIPING NEED TO BE CONNECTED ON SECOND FLOOR TO ROOF IN ORDER FOR FIRST FLOOR PLUMBING SYSTEM TO WORK DURING CONSTRUCTION. CONTRACTOR TO PROVIDE TEMPORARY CONNECTION ON SECOND FLOOR TO KEEP VENT AND STORM PIPE IN OPERATION AS REQUIRED.
PHASING KEYNOTES:
1. WORK FOR STARBUCKS AND WHEATSTONE BISTRO WILL BE PART OF SCHEDULING REQUIREMENT SR-3. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
2. WORK FOR STOTLER LOUNGE AND RESTROOMS & COORIDOR WILL BE PART OF SCHEDULING REQUIREMENT SR-4. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
3. WORK FOR OTHER AREAS OF FIRST FLOOR WILL BE PART OF SCHEDULING REQUIREMENT SR-5. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
#
No. Description Date
2 ADDENDUM 2 12/14/2017
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N303Mechanical
10.5
N304Attic Storage
SN300EStairs
N302AElev Lobby
N302BElev. Eq.
FS-1 FS-1 FS-1
3" V
4" V
3" ST DN
3" ST UP
4" SV UP
BFP-1
HB-1
3/4" CW DN
3/4'' FOR HEATING WATER MAKEUP.REFER TO MECHANICAL HEATING DRAWINGS FOR ADDITIONAL INFORMATION.
2"SV
1 1/2" SV DN
FS-1
3/4"CW
3/4"CW4" ST UP
4" ST DN
RD-E
6"(1173)RD-E
4"(1190)
RD-E
3"(369)
RD-E
3"(790)
RD-16"(2176)
1 1/2" SV DN
1 1/2" SV DN
1 1/2" SV DN
RD-14"(769)
RD-14"(1686)
RD-14"(1140) RD-1
4"(1279)
RD-14"(1164)
RD-14"(2045)
OD-16"(2045)
RD-14"(2154)
OD-16"(2154)
CO
4" ST UP
4" ST DN
4" SV UP & DN
4" V
3" ST(412)
4" ST(1120)
4" ST(970)
RD-16"(1808)
OD-16"(1808)
2
1
Existing pipe to remain
3" SV
3" SV
3" SV
2
2
2
2
22
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:29
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
ATTIC FLOOR PLAN - NORTHWING - PLUMBING
P103N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - PLUMBING
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL SHEET NOTES:
1. REFER TO P000 FOR GENERAL INFORMATION.
PHASING KEYNOTES:
1. WORK FOR ATTIC WILL BE PART OF SCHEDULING REQUIREMENT SR-6. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
2. WORK FOR ROOF WILL BE PART OF SCHEDULING REQUIREMENT SR-8. REFER TO ARCHITECTURAL PLANS FOR MORE DETAILS.
#
No. Description Date
2 ADDENDUM 2 12/14/2017
D E F
5
6
7
N231AMen
N235Jan
N232AWomen
N234Elec/AV
N233Family
N234AI.T.
CN203Corridor
CN200Corridor
N230Clos.
N231Vest
N232Vest
WCO-1
2" SW DN
4" SW UNDER 2" SV.ROUTE VENT AT 5'-0"
4" SW DN
2" SV UP & 4" SW DN
2" SV UP & 4" SW DN
2" SV UP & 4" SW DN
1 1/2" SV DN
4" SW DN & 2" SV UP
1 1/2" SV DN
2" SW DN &1 1/2" SV UP
WCO-1
2" SW DN &1 1/2" SV UP2" SW DN
2" SW DN &1 1/2" SV UP
2" SW DN &1 1/2" SV UP
2" SW DN &1 1/2" SV UP
4" SW DN & 2" SV UP
1 1/2" SV DN
2" SW DN & 1 1/2" SV UP
2" SW DN & 1 1/2" SV UP
4" SW DN & 2" SV UP
1 1/2" SV DN
4" SW DN & 2" SV UP
2" SW DN &1 1/2" SV UP
3" SV DN
6" ST DN
4" ST DN
3" SV DN
3" SV DN
3" SV DN
3" SV DN
4" SW DN & 2" SV UP
2" SW DN & 1 1/2" SV UP
2"SV 3"SV
2"SV
4"SW
3"SV
3"SV 3"SV
1 1/2"SV
4"S
V 3
"SV
4"SV
3"S
V
1 1
/2"S
V
2" SW UNDER 1 1/2" SV. ROUTE VENT AT 5'-0".
4" SW UNDER 2" SV. ROUTE VENT AT 5'-0"
2" SW UNDER 1 1/2" SV. ROUTE VENT AT 5'-0"
2" SW UNDER 1 1/2" SV. ROUTE VENT AT 5'-0"
1 1/2" SV DN
REFER TO P102N SECOND FLOOR PLAN FOR CONTINUATION (TYP.)
4"S
T
4" ST DN
3" SW DN
3"S
W
1 1/2" SV DN
1 1/2"SV
3"SV
4" ST UP
6" STS UP
CO
4"S
T (
1,9
26
)
6"S
TS
(1
,926
)
2" SW DN
2"SV
1 1/2"SV
4" SW DN
WCO-1
4" ST (1926)
6"ST
4"ST
2
D E F
5
6
7
N231AMen
N235Jan
N232AWomen
N234Elec/AV
N233Family
N234AI.T.
CN203Corridor
N230Clos.
N231Vest
N232Vest
2 1/2"CW
1 1
/2"C
W
1 1/4"CW
2 1/2"CW
2 1/2"CW
2"CW
2"C
W
2 1/2"CW
1 1/2"CW
3/4"CW
1 1/4" CW DN
1 1/4" CW DN
1 1/4" CW DN
2" CW DN
3/4"CW
2" CW DN
2" CW DN
3/4" CW DN
2" CW DN 2" CW DN
2" CW DN
3" CW DN
REFER TO P102N SECOND FLOOR PLAN FOR CONTINUATION.(TYP.)
WHA-2
WHA-2
WHA-1
2"CW
3/4"HWR
3/4"HW
3/4" HW DN
2" CW DN
3"C
W 3
"CW
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/6
/201
7 1
:14
:34
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
502
90
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_d
hru
v.m
. sh
ah
.rvt
16253
DHRSHA
PLUMBING - ENLARGEDPLANS
P400
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
1/4" = 1'-0"1ENLARGED PLAN SECOND FLOOR REST ROOMS - PLUMBING SAN/VENT
1/4" = 1'-0"2ENLARGED PLAN SECOND FLOOR REST ROOMS - PLUMBING DOMESTIC
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL SHEET NOTES:
1. REFER TO P000 FOR GENERAL INFORMATION.
No. Description Date
2 ADDENDUM 2 12/14/2017
86 sf
11 sf
77 sf
904 sf
101 sf
2752 sf
659 sf
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
12
8"C
WS
8"CWS
8"C
WS
8"C
WR
8"CWS8"CWR
8"CWR
BUILDING CHILLED WATER PUMP
8"CWS
8"CWS8"CWR
6"CWS6"CWR
4"CWS4"CWR
REMOVE PORTION OF PIPE AS INDICATED AND PREPARE FOR NEW CONNECTION.
8" CWR UP & DN
8" CWS UP & DN
8" S(5) UP & DN
3" LPC UP & DN
4" S(5)
EXISTING 4"S(5)
FROM TUNNEL.
8" S(5)
10"
S(5
)
EXISTING 3" LPC
FROM TUNNEL.
EXISTING LPC FROM BUILDING.
2" LPC DN
2 1/2" LPC DN
3" LPC DN
2" LPC DN
EXISTING LPC FROM BUILDING.
2" LPC DN
8"C
WS
2 1/2"LPC
REMOVE EXISTING DUPLEX VACUUM CONDENSATE PUMP
CWS & CWR PIPING TO
SERVE GROUND FLOOR
AND SOUTH WING
CWS & CWR PIPING FROM UTILITY TUNNEL
3" S(5) UP
1 1/2" LPC UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/4" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
1 1/2" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP 1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
2 1/2" S(5) UP
1 1/4" S(5) UP
2" S(5) UP
1" LPC UP
2" S(5) UP
1" LPC UP
3/4" LPC
UP
2
BUILDING CONTROL
VALVE
REMOVE PORTION OF PIPE AS INDICATED AND PREPARE FOR NEW CONNECTION
REMOVE PORTION OF PIPE AS INDICATED AND PREPARE FOR NEW CONNECTION.
EXISTING LPC GOES TO TUNNEL
8" STEAM RELIEF VENT UP
EXISTING HEAT
EXCHANGER
1
8" CONDENSER WATER SUPPLY
8" CONDENSER WATER RETURN
8"CR 8"CS
ALTERNATE 6 : REMOVE EXISTING CONDENSER WATER SUPPLY AND RETURN PIPING.
EXISTING SERVICE
SINK
EXISTING CONTROL PANEL
FOR CHILLED WATER PUMP.
1 1/2" S(5) UP
3/4" LPC UP
REMOVE PORTION OF PIPE AS INDICATED AND PREPARE FOR NEW CONNECTION.
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" LPC UP
2" S(5) UP
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:1
5 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
SUB BASEMENT FLOOR PLAN- MECHANICAL PIPING - DEMO
MPD100
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1SUB BASEMENT FLOOR PLAN - MECHANICAL PIPING - DEMO
GENERAL NOTES:
1. VACUUM CONDENSATE PUMP SHALL BE INSTALLED DURING SUMMER.
2. COORDINATE REMOVAL OF METASYS CONTROL WITH MU ENERGY MANAGEMENT.ENERGY MANAGEMENT WILL SALVAGE CONTROLS PRIOR TO DO DEMOLITION.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
PHASING KEYNOTES:
1. ALL RENOVATION WORK RELATED TO REPLACING CHILLED WATER PUMP AND CHILLED WATER PIPING SHALL HAPPEN DURING SR-1 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS, TO AVOID CHILLED WATER OUTAGE.
2. REPLACE VACUUM CONDENSATE PUMP (VCP-1) IN BETWEEN MAY TO AUGUST. CONTRACTOR SHOULD KEEP TIME BETWEEN DEMO OF EXISTING AND INSTALLATION OF NEW PUMP TO MINIMUM.
#
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
12
RAD-E RAD-ERAD-ERAD-ERAD-E
RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/4" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP1" LPC UP
2" S(5) UP
3/4" LPC UP 1 1/2" S(5) UP3/4" LPC UP
1 1/2" S(5) UP 3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP 2 1/2" S(5) UP
1 1/4" S(5) UP
1 1/4" S(5) UP
2" S(5) UP
1" LPC UP
2" S(5) UP
1 1/2" S(5) UP
3/4" LPC UP
8" CWR UP & DN
8" CWS UP & DN
2" S(5) UP
1" LPC UP
2" S(5) UP
1" LPC UP
2" S(5) UP
8" S(5) UP & DN
3" LPC UP & DN
3/4" LPC
UP
2" S(5) UP & DN
3" S(5) UP & DN
1 1/2" LPC
UP & DN
3/4" LPC UP 1 1/2" S(5) UP
3/4" LPC DN
1 1/2" S(5) DN
8" STEAM RELIEF
VENT DN
8" STEAM RELIEF
VENT UP
1
1
1
1
1
1
1
1111
1
1
1
1
1
1
1
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN3/4" LPC UP & DN 3/4" S(5) UP & DN
3/4" LPC UP & DN
2
111
1
1
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:1
7 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
Author
GROUND FLOOR PLAN -NORTH WING - PIPING - DEMO
MPD100.5N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1GROUND FLOOR PLAN - NORTH WING - PIPING - DEMO
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
2 ADDENDUM 2 12/14/2017
GENERAL NOTES:
1. ALL WORK ON THIS SHEET SHALL BE PART OF ALTERNATE 3. WORK ON THIS SHEET SHALL HAPPEN DURING MAY TO AUGUST.
KEYNOTES:
1. REMOVE PORTION OF PIPE AND PREPARE FOR NEW CONNECTION.
#
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
12
RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E RAD-E
E-UH
CUH-E
RAD-E
E-UH
RADIATOR IN WALL
W/GRILLE ON SILL
EXISTING CONTINUOUS
CONVECTOR
EXISTING CONTINUOUS
CONVECTOR
RAD-E
2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP &
DN
3/4" LPC UP & DN
1 1/2" S(5) UP &
DN
3/4" LPC UP & DN
1 1/4" S(5) DN
1" LPC UP & DN
2" S(5) UP & DN
3/4" LPC UP & DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP & DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/4" S(5) UP
1 1/2" S(5) UP &
2 1/2" S(5) DN1 1/4" S(5) UP
3/4" LPC UP 3/4" LPC UP
1 1/4" S(5) UP & DN
1 1/4" S(5) UP & DN
3/4" LPC UP
3/4" LPC UP &
1" LPC DN
1 1/4" S(5) UP &
2" S(5) DN
3/4" LPC UP &
DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
8" S(5) DN
3" LPC DN
8" CWR DN
8" CWS DN
8" S(5) UP
3" LPC UP
8" CWR UP
8" CWS UP
2" S(5) UP &
3" S(5) DN
1" LPC UP &
1 1/2" LPC DN
3/4" LPC UP & DN
1 1/2" S(5) UP &
DN
11
1
1
1
1
1
1 1 1 1 1
1
1
1
1
1
3
2
8" STEAM RELIEF VENT UP
8" STEAM RELIEF
VENT DN
REMOVE PORTION OF PIPE AS INDICATED IN BETWEEN MAY-14 TO AUGUST-20 AND PREPARE FOR NEW CONNECTION. CONTRACTOR NEEDS TO COORDINATE WITH SHUT-DOWN OF STEAM SYSTEM
4
RAD-E
DEMO EXISTING PANELS
DEMO EXISTING PANELS
DEMO EXISTING PANELS
DEMO EXISTING PANELS
DEMO EXISTING PANELS
EXISTING ACCESS
PANEL
2
22
2
11 11
1
1
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:2
0 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
FIRST FLOOR PLAN - NORTHWING - PIPING - DEMO
MPD101N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1FIRST FLOOR PLAN - NORTH WING - PIPING - DEMO
KEYNOTES:
1. REMOVE PORTION OF PIPE TAKE OFF SERVING RADIATORS, AND PREPARE FOR NEW CONNECTION TO PLACE NEW CONTROL VALVE. THIS WORK SHOULD HAPPEN BETWEEN MAY TO AUGUST.
#
GENERAL NOTES:
1. COORDINATE REMOVAL OF METASYS CONTROLS WITH MU ENERGY MANAGEMENT.ENERGY MANAGEMENT WILL SALVAGE CONTROLS PRIOR TO DEMOLITION.
PHASING KEYNOTES:
2. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-3 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
3. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-5 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
4. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-4 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
MechanicalRoom
Mechanical &Electrical
RoomMechanical
Room
Pipe Trench
Pipe Trench
10.5
12
SNB00EStairs
8"C
WS
8"CWS
8"C
WS
8"C
WR
8"CWS8"CWR
8"CWR
8"CWS
8"C
WS
8"C
WR
6"CWS6"CWR
4"CWS4"CWR
CWP-1
CWP-2
8"CWS
6"CWS
6"CWS
8"CWS
8" CWR UP & DN
8" CWS UP & DN
8" S(5) UP & DN
3" LPC UP & DN
EXISTING 4"S(5)
FROM TUNNEL.
8"CWR8"CWS
EXISTING 10"S5
FROM BUILDING.
EXISTING 3" LPC FROM
TUNNEL.
3"L
PC
EXISTING LPC
FROM BUILDING.
1 1/2"LPC2"LPC
VCP-1
2" LPC DN
2 1/2" LPC DN
3" LPC DN2" PC DN2" LPC DN
2 1/2"LPC
CHILLED WATER PIPES
FROM UTILITY TUNNEL
1 1/4"CWR
1"CWS 1"CWR
CWP-3
3" S(5) UP
1 1/2" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP3/4" S(5) UP
3/4" LPC UP
3/4" S(5) UP
3/4" LPC UP3/4" S(5) UP
3/4" LPC UP
3/4" LPC UP
2" S(5) UP
1 1/2"LPC 2"LPC4"S(5)
1 1
/2"S
(5)
1"L
PC
3"S(5)1 1/2"LPC
4"S(5)
2"LPC
4"S
(5)
2"L
PC
1 1/2"LPC2 1/2"S(5)
1 1
/2"L
PC
2"L
PC
3"S
(5)
2"L
PC
4"S
(5)
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/4" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
1 1/2" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP 1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
2 1/2" S(5) UP
1 1/4" S(5) UP
2" S(5) UP
1" LPC UP
2" S(5) UP
1" LPC UP
3/4" LPC UP
1 1/4"CWS
1"CWS 1"CWR
1 1/4"CWS
MODULATING BUILDING
CONTROL VALVE
BCU-B01
BCU-B02
3/4" D DOWN, ROUTE TO NEAREST FLOOR DRAIN.
8"S(5)4"S(5)
10
"S(5
)
3/4" D DN, ROUTE TO SERVICE SINK.
3/4"D
3/4"D
EXISTING LPC GOES
TO TUNNEL
MODULATING CWP-3 SUMMER ISOLATION VALVE
3/4"HWS 3/4"HWR
8" STEAM RELIEF VENT UP
EXISTING HEAT
EXCHANGER
PROVIDE CLOSED SHUTOFF VALVE AND CAP FOR DRAINING SYSTEM AND FLUSHING.
EXISTING SERVICE SINK
ELECTRICAL
PANEL
EXISTING CONTROL
PANEL FOR CHILLED
WATER PUMP.
TO SERVE
GROUND FLOOR
2
DO NOT ROUTE PIPING OVER ELECTRICAL EQUIPMENT
2
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:39:5
3 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
SUB BASEMENT FLOOR PLAN- MECHANICAL PIPING
MP100
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1SUB BASEMENT FLOOR PLAN - MECHANICAL PIPING
GENERAL NOTES :
1. VACUUM CONDENSATE PUMP SHALL BE INSTALLED DURING SUMMER.
2. INSTALL MANUAL AIR VENT AT ALL HIGH POINT OF SYSTEM. THE VENTS SHOULD HAVE 3/4" MALE HOSE BIB FITTING.
3. RUN STEAM SYSTEM, SERVING THE NEW HEAT EXCHANGER, AT 12 PSI.
PHASING KEYNOTES:
1. ALL RENOVATION WORK RELATED TO REPLACING CHILLED WATER PUMP AND CHILLED WATER PIPING SHALL HAPPEN DURING SR-1 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS, TO AVOID CHILLED WATER OUTAGE. .
2. REPLACE VACUUM CONDENSATE PUMP (VCP-1) IN BETWEEN MAY TO AUGUST. CONTRACTOR SHOULD KEEP TIME BETWEEN DEMO OF EXISTING AND INSTALLATION OF NEW PUMP TO MINIMUM.
#
1
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
1
2
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
T
T
T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N052Office
N026
ComputerLab
CN27Corridor
CN026Corridor
LN050Lobby
N012HLab
N012Gallery
N3Mechanical
N049Reception
N052PConference
N052OOfficeN052N
OfficeN052MOffice
N052LOffice
N052KOffice
N052JBreak Rm.
N052IOffice
N052HOffice
N052GOffice
92Vest.
N019
Dry FoodStorage
N022
Dry FoodStor
N021Cust. Stor.
N020
CustodialStorage
N052F4Office
N052F5Office
N052F6Office
N052F7Storage
N26GMech.
N52-3Office
N52-2Office
N52-1Office
N052E3Office
N052E2Office
N028AFreezer
N052DOffice
N052COffice
N052BOffice
N051
Office/StudyRoom
N049COffice
N049BConference
N049AOffice
N018BOffice
N018Office/Study
N018AConference N5A
Office
N5BOffice
N5MU Veterans
N012IStorage
N012GWood Shop
N012FKiln
N012D1Lab
N012BOffice
N012AOffice
N17BOffice
N17Office
N17AOffice
N016Tele.
N007Men
N6Storage
N007AWomen
N6BMech
10.5
12
N028Inact.
N029Inact.
N031Inact.
SN000EStairs
SN000BStairs
N12ELab
N012DLab
N0__Office
Storage
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/4" S(5) UP
1" LPC UP
2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP
1 1/2" S(5) UP1" LPC UP
2" S(5) UP
3/4" LPC UP 1 1/2" S(5) UP3/4" LPC UP
1 1/2" S(5) UP 3/4" LPC UP
1 1/2" S(5) UP
3/4" LPC UP 2 1/2" S(5) UP
1 1/4" S(5) UP
1 1/4" S(5) UP
2" S(5) UP
1" LPC UP
2" S(5) UP
1 1/2" S(5) UP
3/4" LPC UP
8" CWR UP & DN
8" CWS UP & DN
2" S(5) UP
1" LPC UP
2" S(5) UP
1" LPC UP
2" S(5) UP
8" S(5) UP & DN
3" LPC UP & DN
3/4" LPC
UP
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
2" S(5) UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN
3/4" LPC UP & DN
3/4" S(5) UP & DN3/4" LPC UP & DN 3/4" S(5) UP & DN
3/4" LPC UP & DN
3" S(5) UP & DN
1 1/2" LPC
UP & DN
3/4" LPC UP 1 1/2" S(5) UP
3/4" LPC DN
1 1/2" S(5) DN
8" STEAM RELIEF
VENT DN
8" STEAM RELIEF
VENT UP
RAD-E RAD-ERAD-ERAD-ERAD-E
RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
2
3
4
4
4
56
67
7
8
8
1
RAD-E
RAD-E
RAD-E
1
1 1 1
PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA NEW THERMOSTAT PLACED IN ROOM N016. SIZE CONTRL VALVE FOR 2 LB/HR AND 5 PSI STEAM PRESSURE
2
2
2
2
2
2
2
2
2
22
2
2
2
2
2
2
2
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:39:5
5 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
GROUND FLOOR PLAN -NORTH WING - PIPING
MP100.5N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1GROUND FLOOR PLAN - NORTH WING - PIPING
GENERAL NOTES:
1. ALL WORK ON THIS SHEET SHALL BE PART OF ALTERNATE 3. WORK ON THIS SHEET SHALL HAPPEN DURING MAY TO AUGUST.
2. CONTROL WIRING FOR NEW RADIATOR CONTROL VALVE SHALL ROUTE ALONG THE WALL BASEBOARD TOWARDS THE EXISTING RACEWAYS AND COME UP TO THE CEILING. COORDINATE WITH ARCHITECT FOR EXACT LOCATION.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
KEYNOTES:
1. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA VAV-060 LOCATED IN ROOM N520 OFFICE. SIZE CONTRL VALVE FOR 3 LB/HR AND 5 PSI STEAM PRESSURE.
2. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA VAV-059 LOCATED IN ROOM N520 OFFICE. SIZE CONTRL VALVE FOR 10 LB/HR AND 5 PSI STEAM PRESSURE.
3. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA VAV-057 LOCATED IN ROOM N052P CONFERENCE. SIZE CONTRL VALVE FOR 2 LB/HR AND 5 PSI STEAM PRESSURE.
4. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA VAV-056 LOCATED IN ROOM N049 RECEPTION. SIZE CONTRL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE
5. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA VAV-065 LOCATED IN ROOM N017 OFFICE. SIZE CONTRL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
6. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA NEW THERMOSTAT PLACED IN ROOM N3A. SIZE CONTRL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
7. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA NEW THERMOSTAT PLACED IN LAB N012D3. SIZE CONTRL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE
8. PROVIDE NEW ELECTRIC CONTROL VALVE COMPATIBLE WITH DDC SYSTEM. CONNECT ELECTRIC VALVE TO BAS VIA NEW THERMOSTAT PLACED IN CORRIDOR CN27. SIZE CONTRL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE
#
No. Description Date
2 ADDENDUM 2 12/14/2017
2
DNDN
T
T
T
T
T
T
TT
T
T
T
T
T
T
T
T
T
T
T
T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N103B
StotlerLounge
N106ALounge
N107Men
N108Women
N106Seating Area
N123Starbucks
N126Seating Area
28Kitchen
N112Storage
LN101Lobby
VN100Vestibule
N114AFreezer
N117BStor
N117AOffice
VN120Vest.
N121Storage
N122Food Serv.
SN100EStairs
N106Seating Area
VN105Vest.
SN100BSTAIRS
N129AElec. Mech.
10.5
12
N116Office
SN100CSTAIRS
N111JAN.
N103
StotlerLounge
N103A
StotlerLounge
RAD-E RAD-E RAD-E RAD-E RAD-E RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E
RAD-E RAD-E
E-UH
CUH-E
RAD-E
E-UH
RADIATOR IN WALL
W/GRILLE ON SILL
EXISTING CONTINUOUS
CONVECTOR
EXISTING CONTINUOUS
CONVECTOR
RAD-E
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/4" S(5) DN
1" LPC UP & DN
2" S(5) UP & DN
3/4" LPC UP & DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP & DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
3/4" LPC UP & DN1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
1 1/4" S(5) UP
1 1/2" S(5) UP &
2 1/2" S(5) DN1 1/4" S(5) UP
3/4" LPC UP 3/4" LPC
UP
1 1/4" S(5) UP & DN
1 1/4" S(5) UP & DN
3/4" LPC
UP
3/4" LPC UP &
1" LPC DN
1 1/4" S(5) UP &
2" S(5) DN
3/4" LPC UP & DN
1 1/4" S(5) UP &
1 1/2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
3/4" LPC UP &
1" LPC DN
1 1/2" S(5) UP &
2" S(5) DN
1 1/2" S(5) UP & DN
3/4" LPC UP & DN
8" S(5) DN
3" LPC DN
8" CWR DN
8" CWS DN
8" S(5) UP
3" LPC UP
8" CWR UP
8" CWS UP
2" HWR UP
2" HWS UP
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-04 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-04 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE..
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-112 A & B TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-112 A & B TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-112C & 113 CTSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-113B & 113A TSTAT. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-109 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-106 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-107 TSTAT. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-108 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
VAV-5-110
VAV-5-109
VAV-4-111
VAV-5-104
VAV-5-106
VAV-5-107
VAV-5-108
VAV-5-101
VAV-5-103
VAV-5-102
VAV-5-105A
PROVIDE NEW ELECTRIC CONTROL VALVE AND THERMOSTAT COMPATIBLE WITH DDC.
PROVIDE NEW ELECTRIC CONTROL VALVE , CONTROLLED FROM VAV-5-101.
PROVIDE NEW ELECTRIC CONTROL VALVE AND THERMOSTAT COMPATIBLE WITH DDC.
PROVIDE NEW CONTROL VALVE. PROVIDE NEW ELECTRIC CONTROL
VALVE AND THERMOSTAT COMPATIBLE WITH DDC. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE NEW DDC CONTROL VALVE AND T-STAT FOR THIS HEATER.
PROVIDE NEW ELECTRIC CONTROL VALVE AND THERMOSTAT COMPATIBLE WITH DDC.
2" S(5) UP & DN3" S(5) UP & DN
1 1/2" LPC UP & DN
3/4" LPC UP & DN
1 1/2" S(5) UP & DN
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-107 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
VAV-4-112AVAV-4-112B VAV-4-112C VAV-4-113C
VAV-4-113B VAV-4-113A
1"HWS
1"HWR
1 1/4" HWR UP
1 1/4" HWS UP
VAV-5-105B
1"HWS 1"HWR
2"HWR 2"HWS
1 1/2"HWS
1 1/2"HWR
1 1/4"HWS 1 1/4"HWR
1 1/4"HWR 1 1/4"HWS
1 1/4"HWS
1 1/4"HWR
CUH-1
3/4"HWR 3/4"HWS
DP
DIFFERENTIAL PRESSURE SENSOR FIELD SET AT 6 PSI.
RAD-E
RAD-E
1 1/2"HWS
1 1/2"HWR
INSTALL BYPASS FOR SYSTEM FLUSHING, AFTER FINISHED WITH FLUSHING, INSTALL 1" AUTOMATIC BALANCING VALVE. BALANCE FOR 1 GPM.
1 1/4"HWS
1 1/4"HWR
INSTALL BYPASS FOR SYSTEM FLUSHING, AFTER FINISHED WITH FLUSHING, INSTALL 1" AUTOMATIC BALANCING VALVE. BALANCE FOR 1 GPM.
8" STEAM RELIEF
VENT DN
8" STEAM RELIEF VENT UP
CONTRACTOR NEEDS TO COORDINATE ROUTING OF THIS PIPE WITH SHUT-DOWN OF STEAM SYSTEM.
NEW STEAM PIPE SHALL BE INSTALLED DURING MAY TO AUGUST
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-112 A & B TSTAT. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-4-112C & 113 CTSTAT. SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE. .
PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-109 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
2"HWS 2"HWR
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
21 11
1
1
2 2
2
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:39:5
7 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
FIRST FLOOR PLAN - NORTHWING - PIPING
MP101N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1FIRST FLOOR PLAN - NORTH WING - PIPING
2
1
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL NOTES:
1. CONTROL WIRING FOR NEW RADIATOR CONTROL VALVE SHALL ROUTE ALONG THE WALL BASEBOARD TOWARDS THE EXISTING RACEWAYS AND COME UP TO THE CEILING. COORDINATE WITH ARCHITECT FOR EXACT LOCATION.
2. INSTALL MANUAL AIR VENT AT ALL HIGH POINT OF SYSTEM. THE VENTS SHOULD HAVE 3/4" MALE HOSE BIB FITTING.
3. ALL VERTICAL PIPE PENETRATIONS SHALL BE FIELD COORDINATED TO MISS EXISTING CONCRETE BEAMS AND SLAB RIBS.
3
3
PHASING KEYNOTES:
1. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-3 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
2. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-5 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
3. ALL RENOVATION WORK ON THIS AREA SHALL HAPPEN DURING SR-4 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
#
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
2
KEYNOTES:
1. PROVIDE CONTROL VALVE FOR RADIATION PANEL AT TAKEOFF. CONTROL FROM VAV-5-101 TSTAT.SIZE CONTROL VALVE FOR 5 LB/HR AND 5 PSI STEAM PRESSURE.
#
TT
T
TC
2
TC
2
TC2
T
T
T
T
T
T T TT C2
C2C2C2
T
T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N231AMen
N235Jan
N232AWomen
N234Elec/AV
N201A
MeetingRoom 1
N201B
MeetingRoom 2
N201C
MeetingRoom 3
N204
MeetingRoom 4
N214A
MeetingRoom 5
N214B
MeetingRoom 6
N214C
MeetingRoom 7
N214D
MeetingRoom 8
N214E
MeetingRoom 9
N222Storage
N221Catering
N205Storage
N233Family
CN201APre-function
N234AI.T.
CN202Corridor
CN204Corridor
CN203Corridor
CN200Corridor
10.5
12
CN201Corridor
N230Clos.
SN200CStairs
N247Break
SN200BStair 1
N231Vest
N232Vest
SN200DStair 2
SN200EStairs
EN200WElevator
SN200B1Room
8" S5 DN
3" LPC DN
8" CWR DN
8" CWS DN
2" HWR DN
2" HWS DN
4" HWR UP4" HWS UP
6" S(5) UP2" LPC UP
6"
S(5
)
RAD-3 RAD-8RAD-4 RAD-5 RAD-6 RAD-7
RAD-19 RAD-13RAD-14RAD-15RAD-16RAD-17RAD-18
RAD-2
RAD-1
RAD-12
RAD-11
RAD-10
8"CWS
8"CWR6" S(5)
2"L
PC
RAD-9
VAV-5-201
VAV-5-202
VAV-5-204
VAV-4-211 VAV-4-210 VAV-4-209
VAV-4-214
VAV-4-208
VAV-4-215
VAV-4-207
VAV-4-206
VAV-4-205
VAV-5-203
VAV-4-212
VAV-4-213
CONTROLLED FROM VAV-4-205 TSTAT.
CONTROLLED FROM VAV-4-205 TSTAT.
CONTROLLED FROM VAV-4-206 TSTAT.
CONTROLLED FROM VAV-4-206 TSTAT.
CONTROLLED FROM VAV-4-207 TSTAT.
CONTROLLED FROM VAV-4-207 TSTAT.
CONTROLLED FROM VAV-4-208 TSTAT.
CONTROLLED FROM VAV-4-205 TSTAT.
CONTROLLED FROM VAV-4-205 TSTAT.
CONTROLLED FROM VAV-4-209 TSTAT.
CONTROLLED FROM VAV-4-209 TSTAT.
CONTROLLED FROM VAV-4-210 TSTAT.
CONTROLLED FROM VAV-4-210 TSTAT.
CONTROLLED FROM VAV-4-211 TSTAT.
CONTROLLED FROM VAV-4-211 TSTAT.
CONTROLLED FROM VAV-5-201 TSTAT.
2" S(5) UP & DN
1 1/2" S(5) UP & DN
3/4" PC UP & DN
4"H
WR
8" CWR UP
8" CWS UP
1"HWR
1"HWS
1"HWR 1"HWS
1"HWR 1"HWS
1"HWR 1"HWS
1 1/4"HWR
1 1/4"HWS
1 1/4" HWR DN
1 1/4" HWS DN
1"HWR
1"HWS
1"HWR 1"HWS
1"HWS 1"HWR
1 1/4"HWS
1 1/4"HWR
1"HWS
1"HWR 1"HWR
1"HWS
1"HWR
1"HWS
1"HWS 1"HWR
3"HWR 3"HWS
2"LPC
4"HWS
4"HWR
3"HWR 3"HWS
1 1/4"HWS 1 1/4"HWR
1"H
WR
1"H
WS
6" S(5)
1
T-1
T-1
T-1
2"L
PC
INSTALL BYPASS FOR SYSTEM FLUSHING, AFTER FINISHED WITH FLUSHING, INSTALL 1" AUTOMATIC BALANCING VALVE. BALANCE FOR 1 GPM.
1"HWS
1"HWR
INSTALL BYPASS FOR SYSTEM FLUSHING, AFTER FINISHED WITH FLUSHING, INSTALL 1" AUTOMATIC BALANCING VALVE. BALANCE FOR 1 GPM.
8" STEAM RELIEF VENT PIPE UP
INSTALL CONTROL VALVE OVER THE LAY IN CEILING. (TYP. ALL)
INSTALL BYPASS FOR SYSTEM FLUSHING, AFTER FINISHED WITH FLUSHING, INSTALL 1" AUTOMATIC BALANCING VALVE. BALANCE FOR 1 GPM.
2
CONTROLLED FROM VAV-4-209 TSTAT.
CONTROLLED FROM VAV-4-209 TSTAT.
CONTROLLED FROM VAV-4-209 TSTAT.
TIE-IN VALVE (TYP.4)
CONNECT PIPE WITH TIE-IN VALVE BEFORE SWITCH OVER.
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:0
4 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
SECOND FLOOR PLAN -NORTH WING - PIPING
MP102N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1SECOND FLOOR PLAN - NORTH WING - PIPING
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL NOTES :
1. INSTALL MANUAL AIR VENT AT ALL HIGH POINT OF SYSTEM. THE VENTS SHOULD HAVE 3/4" MALE HOSE BIB FITTING.
2. ALL VERTICAL PIPE PENETRATIONS SHALL BE FIELD COORDINATED TO MISS EXISTING CONCRETE BEAMS AND SLAB RIBS.
PHASING KEYNOTES:
1. ROUTE PIPE IN BETWEEN MAY 14 TO AUGUST 20.2. INSTALL PORTION OF PIPE IN THIS AREA AND TIE-
IN VALVES PRIOR TO APRIL 1.
#
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/14/2017
2
T
T
T
B C D E F G H
1
2
3
4
N303Mechanical
2
MV301
HEX-1
HEX-2
ET-1
VAV-4-301
AIR SEPARATOR
UH-301
4"HWS
4" HWR DN
4" HWS DN
6" S(5) DN
2" LPC DN
CAP FOR FUTURE AHU
PROVIDE 140X126 SIZE PLENUM.
VAV-4-301
4"H
WS
SPACE FOR FUTURE AHU
58
x2
6
60x36
36
x1
8
26x16
60x408" CWR DN
8" CWS DN
CAP TO SERVE FUTURE AHU
CAP TO SERVE FUTURE AHU
TAKE 108X72 OA DUCT TAKE OFF FROM PLENUM AND CONNECT WITH ROOF HOOD
4"CWS
4"CWR
4"CWR
4"CWS
24
x1
6
4'-0"
4"CWR
4"CWS
FIRE DAMPER IN VERTICAL DUCT AT FLOOR PENETRATION
18x38 SA DN, MAKE TRANSITION IN VERTICAL DUCT TO 50x14 SA BEFORE PENETRATING THE FLOOR. PROVIDE FIRE DAMPER IN VERTICAL DUCT AT FLOOR PENETRATION
1
MV301
AHU-4
AHU-5
WALKWAY
4"CWS
4"CWR
8"C
WS
8"C
WR
2"HWS
2"HWR
4"C
WR
4"C
WS
2"H
WR
2"H
WS
3"HWS 3"HWR
4"HWR
4"HWS
4"HWS
4"HWR
4"HWS 4"HWR
6" S(5)
EF-1
HWP-4 HWP-3
HWP-1
HWP-2
T-2
T-2
3/4"HWR 3/4"HWS
REFER TO MP103N FOR CONTINUATION.
3/4"HWR
3/4"HWS
1 1/2" D, ROUTE TO NEAREST FLOOR DRAIN.
DP
2 1/2"HWS
2 1/2"HWR
3"HWS
3"HWR
1 1/2"D ROUTE TO NEAREST FLOOR DRAIN
42
x2
85
8x3
6
6"S(5)
6"S(5)
3
MV301
44x1844x16 RA DN & 44x18 RA UP
FIRE DAMPER IN VERTICAL DUCT AT FLOOR PENETRATION
115x29 PLENUM BOX
42x28
42x28 DUCT DN TO CONNECT WITH PLENUM BOX
44x28
44
x2
8
44x28
123x23 DUCT
CAP FOR FUTURE AHU
SG-1
36x18/3200
24x16
BALANCE FOR 3200 CFM
18x38
INSTALL EXHAUST FAN AT 3'-0" ABOVE FLOOR FOR EASE OF ACCESS
ELECTRICAL
PANEL
ELECTRICAL
PANEL
ELECTRICAL
PANEL
BAS CONTROL PANEL.
MOD-2
MOD-1
MOD-3
MOD-4
DS-1
DS-2
2
2
MOD-7
MOD-7 IN VERTICAL DUCT
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:0
7 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
ATTIC ENLARGED PLAN
MP400
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/4" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - ENLARGED PLAN
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
PHASING KEYNOTES:
1. ALL RENOVATION WORK INSIDE THE ATTIC SHALL BE COMPLETED PRIOR TO AHU SWITCHOVER UNLESS NOTED OTHERWISE.
2. INSTALL NEW AHUS AND SWITCHOVER DURING SR-7 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS, PRIOR TO REMOVING THE EXISTING PENTHOUSE. ALL ATTIC EQUIPMENT SHALL BE FULLY OPERATIONAL PRIOR TO SWITCHOVER AND READY FOR TESTING AND BALANCING.
#
1 2
No. Description Date
2 ADDENDUM 2 12/14/2017
GENERAL NOTES :
1. INSTALL MANUAL AIR VENT AT ALL HIGH POINT OF SYSTEM. THE VENTS SHOULD HAVE 3/4" MALE HOSE BIB FITTING.
2. ALL VERTICAL PIPE PENETRATIONS SHALL BE FIELD COORDINATED TO MISS EXISTING CONCRETE BEAMS AND SLAB RIBS.
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
5/2
01
77
:40:1
1 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
PIPING SCHEDULE
MP700
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
RADIATION SCHEDULE
TAGNAME AREA SERVED MBH GPM
ELEMENT CABINET AVERAGEWATER TEMP
°FCONTROL
TYPE MANUFACTURER MODEL NOTESMAT'LLENGTH
FT.PIPESIZE
FINS PERFOOT HEIGHT DEPTH
RAD-1 2ND FLOOR MTG. ROOM 1 4.29 0.5 STEEL 7' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-2 2ND FLOOR MTG. ROOM 1 3 0.5 STEEL 5' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-3 2ND FLOOR MTG. ROOM 1 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-4 2ND FLOOR MTG. ROOM 1 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-5 2ND FLOOR MTG. ROOM 2 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-6 2ND FLOOR MTG. ROOM 2 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-7 2ND FLOOR MTG. ROOM 3 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-8 2ND FLOOR MTG. ROOM 3 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-9 2ND FLOOR MTG. ROOM 4 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-10 2ND FLOOR MTG. ROOM 5 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-11 2ND FLOOR MTG. ROOM 5 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-12 2ND FLOOR MTG. ROOM 5 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-13 2ND FLOOR MTG. ROOM 5 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-14 2ND FLOOR MTG. ROOM 5 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-15 2ND FLOOR MTG. ROOM 6 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-16 2ND FLOOR MTG. ROOM 6 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-17 2ND FLOOR MTG. ROOM 7 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-18 2ND FLOOR MTG. ROOM 7 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
RAD-19 2ND FLOOR MTG. ROOM 8 5.51 0.5 STEEL 9' - 0" 3/4" 32 8.6" 2" 160 NOTE 1 RUNTAL UFLT-3 NOTE 1, 2, 3, 4 & 5
PUMP SCHEDULE
TAGNAME AREA SERVED GPM
PUMP FT.HEAD ATDESIGN
MINIMUMPUMP
EFFICIENCYINLETSIZE
IMPELLERSIZE ( INCH)
ELECTRICAL
MANUFACTURER MODEL NOTESHP
(NOTE E) RPM VOLTAGE PHASES
DISCONNECT CONTROLLER/ STARTER
BY(NOTE A)
TYPE(NOTE B)
BY(NOTE A)
TYPE(NOTE C)
CWP-1 NORTH & SOUTH WING 510 70 83.4 8" 9.125 15 1770 208 3 EC - EC VFD B & G E-1510 SERIES NOTE 1
CWP-2 NORTH & SOUTH WING. 510 70 83.4 8" 9.125 15 1770 208 3 EC - EC VFD B & G E-1510 SERIES NOTE 1
CWP-3 BCU-1 & 2 12 15 51.8 1 1/4" 4.000 0.25 1800 208 1 EC - MFR MS B & G SERIES E-90 NOTE 2
HWP-1 LEVEL 1 & 2 200 50 73.1 3" 8.125 5 1800 460 3 EC - EC VFD B & G E-1510 SERIES NOTE 1
HWP-2 LEVEL 1 & 2 200 50 73.1 3" 8.125 5 1800 460 3 EC - EC VFD B & G E-1510 SERIES REDUNDANT PUMP
HWP-3 AHU-1 24 15 55.9 2" 4.250 0.25 1800 120 1 EC - EC FV B & G SERIES E-90
HWP-4 AHU-2 22 15 55.9 2" 4.250 0.25 1800 120 1 EC - EC FV B & G SERIES E-90
HEAT EXCHANGER SCHEDULE - STEAM TO WATER
TAG NAMEAREA
SERVED
WATER STEAM HEATINGSURFACE
FT² MANUFACTURER MODEL NOTESGPMW.P.D. FT.
HEAD EWT °F LWT °F PSIG LB/HR
HEX-1 LEVEL 1& 2 200.0 3.6 140 180 5 3748 85.8 B & G SU-143-4 NOTE-1,2,3
HEX-2 LEVEL 1& 2 200.0 3.6 140 180 5 3748 85.8 B & G SU-143-4 NOTE-1,2,3
G. CURB TYPE:MFR = STANDARD CURB BY MANUFACTURERGC = BY GENERAL CONTRACTORSAC = SOUND ATTENUATOR CURB
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAMEPLATE RATING.
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE, WITHTHE SCHEDULED WHEEL TYPE.
C. CONTROLLER STARTER TYPE:FV = FULL VOLTAGEWYE = WYE-DELTASS = SOLID STATE (SOFT START)MS = MANUAL STARTERVFD = VARIABLE FREQUENCY DRIVEVFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
B. DISCONNECT TYPE:F = FUSEDNF = NON-FUSED
A. DISCONNECT AND CONTROLLER STARTER FURNISHED ANDINSTALLED BY:MFR = MANUFACTUREREC = ELECTRICAL CONTRACTOR.MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BYELECTRICAL CONTRACTOR.MFR/EC = FURNISHED LOOSE BY MANUFACTURER INSTALLED BYELECTRICAL CONTRACTOR....
SCHEDULE GENERAL NOTES:
NOTES:1) PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13. ALL SHAFT GROUNDING SYSTEMS ARE TO
BE REVIEWED BY THE VENDOR AS THEY ARE INSTALLED.2) ECM MOTOR PROVIDED BY MFR.
NOTES: 1) SEE SPECIFICATION SECTION 23 09 00 FOR DESCRIPTION OF CONTROL TYPE/SENSOR. SEE CONTROL DETAILS.2) ELEMENT LENGTH LISTED IS ACTIVE FINISHED LENGTH, FIELD VERIFY LENGTH OF ELEMENT PIPING.3) ALL RADIANT PANELS ARE WALL MOUNTED. 4) PROVIDE END TRIM TO COVER PIPING ASSEMBLY AND END CAP ON NON-PIPE END. 5) REFER TO DRAWING FOR PIPING CONFIGURATION.6) PROVIDE END TRIM TO COVER PIPING ASSEMBLY AND END CAP ON NON-PIPE END.7) REFER TO DRAWING FOR PIPING CONFIGURATION.
NOTES: 1) STEAM PRESSURE INDICATED IS THE PRESSURE AVAILABLE DOWNSTREAM OF THE CONTROL VALVE.2) HEX IS FULLY REDUNDANT.3) HEX SELECTION IS BASED ON 100% WATER SOLUTION.4) PROVIDE CAST IRON FLANGED HEAD. THREADED PIPE CONNECTIONS ON 4" ARE NOT PERMITTED. 5) MAXIMUM LENGTH OF EQUIPMENT SHOULD NOT EXCEED 44".
VACUUM CONDENSATE PUMP
TAGNAME
AREASERVED CONFIGURATION
LB/HR(NOTE 1)
CONDENSATETEMPERATURE °F
RECEIVERCAPACITY(GALLONS)
RECEIVERPRESSURE
RATING(PSIG)
ELECTRICAL
MANUFACTURER MODEL
CONDENSATE PUMPS VACUUM PUMPS DISCONNECTCONTROLLER/
STARTER
QTYGPM
(NOTE2)
DISCHARGEPRESSURE
(PSI) HP VOLTAGE PHASES QTYCFM
(NOTE3)
VACUUMINCHES Hg @
160° F HP VOLTAGE PHASEBY
(NOTE A)TYPE
(NOTE B) BY (NOTE A)
VCP-1 BUILDING DUPLEX 6221 210 50 0 2 30 35 2 208 3 2 18 5.5 2 208 3 MFR F MFR B & G VDC 50D4
NOTES:1) LB/HR IS ACTUAL MAXIMUM LOAD OF SYSTEM. 2) GPM IS CAPACITY PER EACH PUMP AND HAS A SAFETY FACTOR OF TWO.3) CFM IS CAPACITY PER PUMP.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
TRAP SCHEDULE1TAG
NAME AREA SERVED TYPESAFETYFACTOR SIZE
CAPACITY LB HR(NOTE 1)
PRESSUREDIFFERENTIAL MANUFACTURER MODEL NOTES
T-1 MAIN DRIPS I.B. 1 1" 210 5 ARMSTRONG 811 NOTES 5,6, & 7
T-2 HEAT EXCHANGER F & T 1 2" 2750 0.5 ARMSTRONG 30A 8 NOTES 2, 3, 4 & 7
NOTES: 1) CAPACITY LISTED IS FOR EACH TRAP AND INCLUDES SAFETY FACTOR.2) SUITABLE TO 30 PSIG, SIDE INLET & OUTLET , SS FLOAT MECHANISM AND VALVE, CAST IRON BODY,
BALANCED PRESSURE THERMOSTATIC AIR VENT, ALL INTERNALS REPLACEABLE IN-LINE.3) ORIFICE SIZE IS 9/16" AS BASIS OF DESIGN.4) WITH INTEGRAL VACUUM BREAKER.5) SIDE INLET AND OUTLET INVERTED BUCKET TRAP. 250 PSIG RATE. CAST IRON BODY, ALL INTERNAL
COMPONENTS OF STAINLESS STEEL AND REPLACEABLE INLINE.6) ORIFICE SIZE 7/64" AS BASIS OF DESIGN.7) REFER TO DRAWINGS FOR LOCATION AND NUMBER OF TRAPS REQUIRED.
No. Description Date
2 ADDENDUM 2 12/14/2017
2
TT
T
TC
2
TC
2
TC2
T
T
T
T
T
T T TT C2
C2C2C2
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N231AMen
N235Jan
N232AWomen
N234Elec/AV
N201A
MeetingRoom 1
N201B
MeetingRoom 2
N201C
MeetingRoom 3
N204
MeetingRoom 4
N214A
MeetingRoom 5
N214B
MeetingRoom 6
N214C
MeetingRoom 7
N214D
MeetingRoom 8
N214E
MeetingRoom 9
N222Storage
N221Catering
N205Storage
N233Family
CN201APre-function
N234AI.T.
CN202Corridor
CN204Corridor
CN203Corridor
CN200Corridor
10.5
12
CN201Corridor
N230Clos.
SN200CStairs
N247Break
SN200BStair 1
N231Vest
N232Vest
SN200DStair 2
SN200EStairs
EN200WElevator
SN200B1Room
82X18 RA DN.
92X18 SA DN.
18X18 SA DN
72X18 SA DN.
56X18 RA DN
18X10 EA DN
48X18 RA DN40X18 SA DN
40x18
60
x3
6
18x18
10x8
16x12
10x10
18
x1
4
60x36 SA UP
42x28
34x18 RA UP
58x26 RA UP
58
x2
6
20
x1
2
42x16
26
x1
428
x1
4
34x14
50x14 SA UP
52x18
56
x1
8
56x18
56
x1
8
24
x1
2
16x12
28x14
44x14
18x12
26x12
58
x3
6
58X36 RA UP
60X30 SA UP
22x14 EA UP
VAV-5-201
VAV-5-204
VAV-4-211
VAV-4-210
VAV-4-209
22
x1
4
22x14
VAV-4-214
VAV-4-208VAV-4-215
VAV-4-207
VAV-4-206VAV-4-205
42x28
10x8
VAV-5-203
26
x8
26x8 EA DN
VAV-4-213
36X18 EA DN
56x18
60x30
82x18 92x18
PROVIDE NEW KITCHEN EXHAUST FAN EF-2
CONNECT TO EXISTING DUCT
14x8
VAV-4-205
VAV-4-206
VAV-4-215
VAV-4-207
VAV-4-208
VAV-4-213
VAV-4-214
VAV-4-212
VAV-5-204
VAV-4-209
VAV-4-210VAV-4-211
VAV-5-203
VAV-5-202
VAV-5-201
32
x1
22
4x1
2
14x12
CD-1
10/300(TYP.9)
RG-1
RG-1
RG-1
RG-1
RG-1
RG-1RG-1
RG-1
24x24 TD
32x26 TD
20x12 TD
CD-1
8/205(TYP.9)
12x10
18
x1
2
16x1210x10
22x14
16x12
10x10
CD-1
8/245
CD-1
8/245
24x12
RG-1 RG-1 RG-1 RG-1 RG-1RG-1 RG-122x12
20x14
26
x1
4
14x12
CD-1
10/295(TYP.9)
CD-1
10/265(TYP.9)
26
x1
4
CD-1
10/275(TYP.9)
18
x1
4
24
x1
0
CD-1
8/240(TYP.6)
10x8
CD-1
8/170
CD-1
8/170
SG-1
30x18/1940
SG-1
30x12/1285
CD-1
6/50
12x10
RG-1
RG-2
12x6/240
10x8 TD
RG-1
CD-1
8/240
SG-1
12x8/240
12x8
CD-1
8/180
CD-1
8/180
CD-1
8/180
CD-1
8/180
10x10
SG-1
8x8/210
RG-2
8x8/210
CD-1
8/200
CD-1
6/150
10x8
CD-1
8/180
VAV-5-202
CD-1
8/250
CD-1
8/250
RG-1RG-1
10x8 TD
10x8 TD
8x8
EG-1
6x6/50
EG-1
8x6/150
EG-1
8x6/150EG-1
8x6/150
EG-1
8x6/150
12x10
34x18
24x24 TD
24x10
8x8
8x8
18x10
26x8
12x12
16x14
D
26
x1
2
D24
x1
2
CD-1
6/240 D
R
D
R
R
R
R50x14
R
D
R
D
RR
R
D
R
CD-1
8/215(TYP.9)
D
R CD-1
10/300
32x12
14x12
R
10x10
42x28 EA UP
PHASING KEYNOTES:
1. RESTROOMS EXHAUST DUCT AND FAN SHALL BE INSTALLED PRIOR TO INSTALLING NEW SUPPLY AND RETURN DUCT.
2. CONNECT NEW DUCTWORK WITH THE EXISTING DUCT IN SHAFT, WHICH IS SERVING FIRST FLOOR, DURING SR-6 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
#
COORDINATE REPLACEMENT OF FAN WITH THE CAMPUS DINING SERVICES.
8x8
RG-1
1
1
2
2
2
VAV-4-212
EG-1
8x6/50
RG-1
COORDINATE WITH STRUCTURAL HANGERS. ROUTE IN BETWEEN TWO HANGERS. REFER TO STRUCTURAL PLAN FOR MORE INFOMRATION.
CD-1
8/205
2
PROVIDE ACCESS PANEL IN CEILING. COORDINATE WITH ARCHITECT
44
x1
6
44x16 RA UP
BALANCE FOR 450 CFM
30x10
30x8
14x128x6
RG-2
30x18/1940
RG-2
30x12/1240
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/8
/201
7 5
:20
:41
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
SECOND FLOOR PLAN -NORTH WING - VENTILATION
MV102N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1SECOND FLOOR PLAN - NORTH WING - VENTILATION
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL NOTES :
1. REFER TO ELECTRICAL POWER DRAWING FOR OCCUPENCY SENSORS LOCATION.
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/08/2017
T
T
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N303Mechanical
10.5
N304Attic Storage
SN300EStairs
N302AElev Lobby
N302BElev. Eq.
34
x1
8
58
x2
6 60
x3
6
58x2658x26
60
x3
6
58
x3
6
60x40
60
x3
0
34x18 RA DN
60x36 SA DN
58x26 RA DN
58x36 RA DN
60x30 SA DN
26x16
ROUTE DUCT APPROXIMATELY 36" ABOVE ROOF LEVEL.
ROUTE DUCT APPROXIMATELY AT 10'-6" ABOVE ROOF LEVEL.
ROUTE DUCT ABOVE DOOR AT 10"-10" CLOSE TO THE WALL.
SPACE FOR FUTURE AHU
1
MP400
ROUTE DUCT APPROXIMATELY AT 10'-6" ABOVE ROOF LEVEL.
ROUTE DUCT APPROXIMATELY 36" ABOVE ROOF LEVEL
2 2
1
PROVIDE BIRD SCREEN
CONSTRUCT A OUTLET PLENUM BOX TO KEEP THE WATER AND DEBRIS OUT OF THE FAN.
DUCT ANGLE DOWN.
PROVIDE BIRD SCREEN
CONSTRUCT A OUTLET PLENUM BOX TO KEEP THE WATER AND DEBRIS OUT OF THE FAN.
DUCT ANGLE DOWN.
REF-1
58x36
60x34
60
x3
4
REF-2
60x36
46
x3
4
60
x4
0
ROUTE DUCT APPROXIMATELY AT 10'-6" ABOVE ROOF LEVEL.
44x18
ROUTE DUCT APPROXIMATELY AT 3'-0" ABOVE ROOF LEVEL.
ROUTE DUCT APPROXIMATELY 36" ABOVE ROOF LEVEL.
1
1
1
1
DS-3
DS-4
EXISTING TOWER
FLOOD LIGHT
EXISTING TOWER
FLOOD LIGHT
2
MOD-6
MOD-5
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/8
/201
7 5
:20
:44
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
ATTIC FLOOR PLAN - NORTHWING - VENTILATION
MV103N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - VENTILATION
PHASINGKEYNOTES:
1. INSTALL NEW DUCTWORK DURING SR-6 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS.
2. INSTALL NEW AHU IN THE ATTIC DURING SR-7 PER THE ARCHITECTURAL SCOPE SEQUENCING PLANS. .
#
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
GENERAL NOTES:
1. ALL DUCTWORK EXPOSED ON ROOF SHALL BE KOOL DUCT
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/08/2017
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/8
/201
7 5
:20
:50
PM
C:\
Re
vit Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
VENTILATION SCHEDULES
MV601
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
GRILLES REGISTERS & DIFFUSERS SCHEDULE
TAGNAME MATERIAL CONFIGURATION
MARGIN(NOTE 1)
INLET SIZE(IN.) (NOTE 2)
FACE SIZE(IN.)
VOLUMEDAMPER
REQUIRED FINISH MANUFACTURER MODEL NOTES
CD-1 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI
EG-1 STEEL 35 DEGREEDEFLECTION
1 1/4" SEE DWG. INLET +2 YES WHITE TITUS 350R
EG-2 STEEL PANEL FACE LAY-IN SEE DWG. 24x24 NO WHITE TITUS OMNI
RG-1 ALUMINUM EGGCRATE LAY-IN NA 24x24 NO WHITE TITUS 50F
RG-2 STEEL 35 DEGREEDEFLECTION
1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 350R
SG-1 STEEL DOUBLE DEFLECTION 1 1/4" SEE DWG. INLET +2 NO WHITE TITUS 300R FRONT BLADES VERTICAL UNLESS NOTED OTHERWISE
AIR HANDLING SCHEDULE
TAGNAME
AREASERVED
SUPPLY FAN
MINIMUMOUTSIDE AIR
CFMHEATING
CFM VOLTAGE PHASESMCA(A)
HEATING COIL - WATER COOLING COIL FILTER
MANUFACTURER MODEL REMARKCFMEXT.S.P. TYPE
RPM(NOTE D)
BHP(NOTE E)
MHP(NOTE E)
DISCONNECTCONTROLLER/
STARTER SOUND (DB)
EAT°F LAT °F
EWT°F
LWT°F GPM MBH
MAX.A.P.D.
IN. W.C.
W.P.D.FEETHEAD
EATDB °F
EATWB°F
LATDB °F
LATWB °F
EWT°F
LWT°F GPM
TOTALMBH
MAX.A.P.D.
IN. W.C.
W.P.D.FEETHEAD
PRE-FILTER FINAL-FILTER
BY(NOTE A)
TYPE(NOTE B)
BY(NOTE A)
TYPE(NOTE C) 63 HZ
125HZ
250HZ
500HZ
1 KHZ
2 KHZ
4 KHZ
8 KHZ TYPE
PRESSUREDROP TYPE
PRESSUREDROP
AHU-4 LEVEL 1& 2 32000 5.0 BAI 1233 51 60 EC NF EC VFD 102 100 102 100 98 93 90 81 7500 14,730 460 3 90 18.0 55.0 180 140 21.5 430 0.013 1.3 80.0 67.0 53.0 52.9 46 60 188.8 1322 0.6 13.5 MERV8 0.590 MERV12 0.717 Trane CLIMATE CHANGER, 80 NOTE 1, 2, 3 & 4
AHU-5 LEVEL 1 & 2 27000 5.2 BAI 1426 46.2 50 EC NF EC VFD 100 97 102 96 94 89 85 77 7755 15,765 460 3 73.75 6.0 55.0 180 140 24.0 480 0.013 1.5 81.0 67.5 53.0 52.9 46 60 171.0 1199 0.6 14.1 MERV8 0.610 MERV12 0.733 Trane CLIMATE CHANGER, 66 NOTE 1, 2, 3 & 4
FAN SCHEDULE
TAG NAME AREA SERVED CFMS.P. IN.
W.C.WHEEL DIA.
INCHESFAN RPM(NOTE F)
DRIVETYPE
MAX. AMCASONES
BACKDRAFTDAMPER TYPE
CURB TYPE(NOTE G)
ELECTRICAL
MANUFACTURER MODEL NOTESBHP MHP VOLTAGE PHASES
DISCONNECT CONTROLLER/ STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A) TYPE (NOTE C)
EF-1 REST ROOM 3100 0.75 16.5 1439 DIRECT 19.4 MOTORIZED MFR 0.965 1.5 460 3 MFR NF EC FV COOK SQN-B
EF-2 FIRST FLOOR KITCHEN 6000 1.20 27 746 BELT 13.3 MOTORIZED MFR 1.2 2 460 3 MFR NF EC FV COOK CPA NOTE 2
REF-1 AHU-1 30500 2.50 49 594 BELT 23 NA NA 18 20 460 3 MFR NF EC VFD COOK CPA
REF-2 AHU-2 19700 2.60 40.2 721 BELT 22 NA NA 11.8 15 460 3 MFR NF EC VFD COOK CPA
TERMINAL AIR BOX SCHEDULE - SINGLE DUCT
TAG NAME AREA SERVED
CFM HEATING COIL (NOTES 5, 6)
MIN. INLETSIZE (IN.) DIA.
MIN. INLET SIZE (IN.)
CONTROLTYPE MANUFACTURER
MODEL(NOTES 1, 2) NOTES
COOLINGMAX.
HEATINGMAX. MIN. EAT °F LAT °F EWT °F LWT °F # ROWS
MAX.GPM WIDTH HEIGHT
VAV-4-111 LOUNGE 1105 1105 340 55.0 95.0 185 128 2 2.1 6" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-112A STOTLER LOUNGEN103
1380 800 455 55.0 95.0 180 128 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-112B STOTLER LOUNGEN103
1380 800 455 55.0 95.0 180 128 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-112C STOTLER LOUNGEN103
1380 800 455 55.0 95.0 180 128 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-113A STOTLER LOUNGEN103A
1380 800 455 55.0 95.0 180 128 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-113B STOTLER LOUNGEN103A
1380 800 455 55.0 95.0 180 128 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-113C STOTLER LOUNGEN103A
1380 800 455 55.0 95.0 180 129 2 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2, 7
VAV-4-205 01 MTG ROOM 2660 1125 580 55.0 95.0 180 123 1 2.6 16" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-206 02 MTG ROOM 2380 610 580 55.0 95.0 180 139 1 0.9 16" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-207 03 MTG ROOM 2500 850 580 55.0 95.0 180 141 1 1.8 16" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-208 04 MTG ROOM 1430 480 325 55.0 95.0 180 141 1 1.1 14" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-209 05 MTG ROOM 2710 970 580 55.0 95.0 180 135 1 1.9 16" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-210 06 MTG ROOM 1865 535 450 55.0 95.0 180 122 1 0.8 14" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-211 07 MTG ROOM 1925 585 450 55.0 95.0 180 122 1 0.9 14" NOTE 3 TITUS DESV NOTES 1, 2, 8
VAV-4-212 ELEC AV 1940 0 230 55.0 55.0 0 0 0 0.0 14" NOTE 3 TITUS DESV NOTES 1, 2
VAV-4-213 IT 1285 0 230 55.0 55.0 0 0 0 0.0 12" NOTE 3 TITUS DESV NOTES 1, 2
VAV-4-214 LOBBY 630 630 340 55.0 95.0 180 136 2 1.8 8" NOTE 3 TITUS DESV NOTES 1, 2
VAV-4-215 CORRIDOR 1190 1190 615 55.0 95.0 180 136 2 2.3 10" NOTE 3 TITUS DESV NOTES 1, 2
VAV-4-301 ATTIC 3200 0 1400 55.0 55.0 0 0.0 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-101 SEATING 4720 4535 1400 55.0 95.0 180 121 3 6.8 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-102 MGR OFFICE 1055 1055 625 55.0 95.0 180 124 2 1.9 10" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-103 STARBUCKS 1620 450 450 55.0 95.0 180 131 1 0.7 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-104 ASST MGR OFFICE 1320 985 910 55.0 95.0 180 132 2 1.8 10" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-105A KITCHEN 2216 738 738 55.0 95.0 180 132 1 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-105B KITCHEN 2216 738 738 55.0 95.0 180 122 1 1.3 12" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-106 DINING 2500 580 580 55.0 95.0 180 122 1 0.9 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-107 DINING 2500 580 580 55.0 95.0 180 122 1 0.9 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-108 DINING 2900 1400 1400 55.0 95.0 180 114 2 1.8 24 16 NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-109 STAFF OFFICE 2100 2100 450 55.0 95.0 180 126 2 3.6 16" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-110 CORRIDOR 720 715 430 55.0 95.0 180 118 2 1.2 8" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-201 08 MTG ROOM 990 365 240 55.0 95.0 180 148 2 0.5 10" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-202 09 MTG ROOM 295 165 165 55.0 95.0 185 125 1 0.5 6" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-203 STORAGE 315 305 185 55.0 95.0 185 140 2 0.5 6" NOTE 3 TITUS DESV NOTES 1, 2
VAV-5-204 CORRIDOR 1055 1055 350 55.0 95.0 180 134 2 2.3 8" NOTE 3 TITUS DESV NOTES 1, 2
INTAKE HOOD SCHEDULE
TAGNAME
AREASERVED CFM
THROAT SIZE THROATVELOCITY
(FPM)
STATICPRESSURE
DROP CONFIGURATION
MAX. HEIGHT (TOP OFCURB TO TOP OF
EQUIP.)CURBTYPE MANUFACTURER MODEL
WIDTH(INCH)
LENGTH(INCH)
IAH-1 AHU-1&2 59000 72 108 1065 0.14 GRAVITY HOOD 36 MFR Greenheck FGI
G. CURB TYPE:MFR = STANDARD CURB BY MANUFACTURERGC = BY GENERAL CONTRACTORSAC = SOUND ATTENUATOR CURB
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAMEPLATE RATING.
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE, WITHTHE SCHEDULED WHEEL TYPE.
C. CONTROLLER STARTER TYPE:FV = FULL VOLTAGEWYE = WYE-DELTASS = SOLID STATE (SOFT START)MS = MANUAL STARTERVFD = VARIABLE FREQUENCY DRIVEVFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
B. DISCONNECT TYPE:F = FUSEDNF = NON-FUSED
A. DISCONNECT AND CONTROLLER STARTER FURNISHED ANDINSTALLED BY:MFR = MANUFACTUREREC = ELECTRICAL CONTRACTOR.MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BYELECTRICAL CONTRACTOR.MFR/EC = FURNISHED LOOSE BY MANUFACTURER INSTALLED BYELECTRICAL CONTRACTOR....
SCHEDULE GENERAL NOTES:
NOTES: 1) PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13. 2) BHP LISTED IS TOTAL FOR THE UNIT .3) MHP LISTED IS TOTAL FOR THE UNIT. 4) SEE SPECIFICATION SECTION 23 05 48 FOR VIBRATION ISOLATION SCHEDULE.5) COOLING COIL SHALL BE MAXIMUM 8 ROWS AND 120 FINS PER FOOT, AND SHALL HAVE STAINLESS STEEL COIL CASING AND DRAIN PAN.6) HEATING COIL SHALL BE MAXIMUM 8 ROWS AND 120 FINS PER FOOT.
NOTES: 1) PROVIDE SHAFT GROUNDING AS REQUIRED IN THE MOTOR SPECIFICATION 23 05 13.2) PROVIDE ECM MOTOR.
NOTES: 1) NEITHER RADIATED NOR DISCHARGE SOUND LEVELS SHALL EXCEED NC 35 AT 1.5" INLET STATIC PRESSURE WHEN TESTED PER AHRI STANDARD 885-2008 USING 5/8" 20-LB DENSITY MINERAL FIBER CEILING TILE. 2) TOTAL AIR PRESSURE DROP OF TAB AND REHEAT COIL SHALL NOT EXCEED 0.50" WC. 3) SEE SPECIFICATION SECTION 23 09 00 FOR DESCRIPTION OF CONTROL TYPE. 4) SENSOR TYPES: 1 - SENSOR ONLY, 2 - SENSOR WITH ADJUSTMENT, 3 - SENSOR WITH OVERRIDE, 4 - SENSOR WITH ADJUSTMENT AND OVERRIDE. 5) HEATING COIL IS BASED ON HEATING AIR FLOW. WATER PRESSURE DROP OF REHEAT COILS SHALL NOT EXCEED 5'. PROVIDE REHEAT COILS SEPARATE FROM BOXES IF REQUIRED TO MEET WATER PRESSURE DROP REQUIREMENTS. WHEN LAT °F, EWT °F, AND GPM VALUES ARE BLANK, HEATING COIL IS NOT REQUIRED FOR TAB. 6) HEATING COIL SELECTION SHALL BE BASED ON A FIXED LEAVING AIR TEMPERATURE AND VARIABLE FLOW (GPM). PROVIDE FINAL MAXIMUM FLOW RATE (GPM) TO TEST & BALANCE TERMPERATURE CONTROLS CONTRACTORS.7) THIS VAV HAS OCCUPANCY SENSOR IN ROOM.8) THIS VAV HAS CO2 SENSOR IN ROOM.
NOTES: 1) CONTRACTOR SHALL DETERMINE PROPER MARGIN STYLE TO MATCH CEILING CONSTRUCTION. 2) ALL RUN OUT DUCTWORK TO DIFFUSERS SHALL BE NECK SIZE UNLESS OTHERWISE NOTED. 3) 20x20 GRILLE WITH LAY-IN BORDER FOR 24X24 GRID. PROVIDE W/ 6" DEEP SQUARE PLENUM
BLOWER COIL UNIT SCHEDULE - HYDRONIC
TAGNAME AREA SERVED CFM
EXT.S.P. INW.C.
EAT COOLING COIL HEATING COIL ELECTRICAL
MANUFACTURER MODEL NOTESDB °F WB °FTOTALMBH
SENSIBLEMBH GPM EWT °F LWT °F
W.P.D.FT. HD
TOTALMBH GPM EWT °F
W.P.D.FT. HD HP VOLTAGE PHASES
DISCONNECTCONTROLLER/
STARTER
BY (NOTE A) TYPE (NOTE B) TYPE (NOTE A)
BCU-B01 SUB BASEMENT MECHANICALAND ELECTRICAL ROOM
2400 0.2 75.0 62.5 52 52 7.5 46 60 4.30 0 0.0 0 0.0 1 208 3 EC - MFR TRANE BCHD
BCU-B02 SUB- BASEMENT 1400 0.3 75.0 62.5 31 31 4.5 46 60 2.66 40 1.9 180 0.06 0.5 208 3 EC - MFR TRANE BCHD
MOTOR OPERATED DAMPER SCHEDULETAG
NAMEAREA
SERVED
SIZE CFM BLADECONFIGURATION BLADE ORIENTATION INSULATED
ACTUATOR TYPE(NOTE 1) ACTUATOR STYLE
POWER FAILUREPOSITION
POSITIVE POSITIONFEEDBACK REQUIRED NOTESWIDTH HEIGHT MAX. MIN.
MOD-1 AHU-4 82 24 24500 0 OPPOSED HORIZONTAL Yes ELECTRIC PROPORTIONALPOSITION
NORMALLY CLOSED Yes AT OUTSIDE AIR DUCT
MOD-2 AHU-4 36 24 7500 0 OPPOSED HORIZONTAL Yes ELECTRIC PROPORTIONALPOSITION
NORMALLY CLOSED Yes AT OUTSIDE AIR DUCT
MOD-3 AHU-5 82 20 19245 0 OPPOSED HORIZONTAL Yes ELECTRIC PROPORTIONALPOSITION
NORMALLY CLOSED Yes AT OUTSIDE AIR DUCT
MOD-4 AHU-5 36 20 7755 0 OPPOSED HORIZONTAL Yes ELECTRIC PROPORTIONALPOSITION
NORMALLY CLOSED Yes AT OUTSIDE AIR DUCT
MOD-5 AHU-4 60 34 30500 0 OPPOSED HORIZONTAL Yes ELECTRIC TWO POSITION NORMALLY CLOSED Yes AT RELIEF DUCT
MOD-6 AHU-5 46 34 19700 0 OPPOSED HORIZONTAL Yes ELECTRIC TWO POSITION NORMALLY CLOSED Yes AT RELIEF DUCT
MOD-7 EF-1 14 22 3100 0 OPPOSED VERTICAL No ELECTRIC TWO POSITION NORMALLY CLOSED Yes AT EXHAUST FAN
NOTES: 1) COORDINATE DAMPER ACTUATOR LOCATION AND MOUNTING REQUIREMENTS WITH TEMPERATURE CONTROL CONTRACTOR.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
CONDENSING UNIT SCHEDULE
TAG NAME AREA SERVEDNOMINAL
DESIGN TONS REFRIGERANTAMBIENTTEMP °F
ELECTRICAL
MANUFACTURERMODEL
(NOTE 1)VOLTAGE PHASES RLA MCA MOCP
DISCONNECTCONTROLLER/
STARTER
BY (NOTEA)
TYPE (NOTEB) BY (NOTE A)
CU-1 ELEVATORMACHINE ROOM
2 R-410A 95.0 208 1 10.3 17 20 MFR F MFR DAIKIN RZQ24PVJU
SPLIT SYSTEM UNIT SCHEDULE
TAG NAME AREA SERVED
INDOOR UNIT
CFM MCA VOLTAGE PHASECOOLING
MBH MANUFACTURER
SSU-1 ELEVATOR MACHINE ROOM 635 0.6 208 1 24 DAIKIN
CABINET HEATER SCHEDULE - HOT WATER
TAG NAME AREA SERVED CONFIGURATIONNOMINAL
CFM MBH GPMEWT
°FLWT°F
MAX W.P.D.FT. HD
CONTROLTYPE
CABINET (NOTE 1) ELECTRICAL
MANUFACTURER MODEL NOTESHEIGHT WIDTH DEPTH FAN HP RPM VOLTAGE PHASES
DISCONNECTCONTROLLER/
STARTER
BY (NOTE A) TYPE (NOTE B) BY (NOTE A)
CUH-1 VESTIBULE VN-105 HORIZONTALRECESSED
800 80 2.7 180 140 1.28 T STAT 10" 78" 30" 0.22 1094 120 1 MFR NF MFR TRANE FFEB12 NOTES 1
UNIT HEATER SCHEDULE - HOT WATER
TAGNAME AREA SERVED CONFIGURATION CFM MBH GPM EWT °F LWT °F
W.P.D.FT.
HEAD
ELECTRICAL
MANUFACTURER MODELHP RPM VOLTAGE PHASES
DISCONNECTCONTROLLER/
STARTER
BY(NOTE A)
TYPE(NOTE B) BY (NOTE A)
UH-301 ATTIC HORIZONTAL 2600 81 4.5 180 140 0.53 0.33 1140 115 1 EC - MFR TRANE S-156
UH-302 ATTIC HORIZONTAL 1400 40 2.8 180 140 0.29 0.08 1000 115 1 EC - MFR TRANE S-96
NOTES:1) COORDINATE COLOR SELECTION WITH ARCHITECT. 2) PROVIDE FRONT DUCT COLLAR OUTLET AND BOTTOM STAMPED LOUVER INLET3) CONNECT TO METASYS. REFER TO DETAIL 4/M701.
NOTES:1) SINGLE POINT POWER CONNECTION UNIT.
NOTES:1) CONNECT TO METASYS, REFER TO DETAIL 4/M701.
NOTES:1) UNIT NEEDS TO BE CONTROLLED BY METASYS..
NOTES: 1. PRESSURE DROP VALUES LISTED ARE PER ASTM E477-99 TEST PROCEDURE AND DO NOT INCLUDE SYSTEM EFFECTS. 2. WITH FIBERGLASS CLOTH SEPARATING MEDIA FROM AIRSTREAM. 3. SILENCER SHALL BE CONSTRUCTED TO KEEP THE BREAKOUT NOISE CONTRIBUTION TO THE AFFECTED ROOM BELOW 40
Dba. SILENCER SHALL BE FACTORY MANUFACTURED AND ALL EXPOSED SURFACES SHALL BE SHEETMETAL (EXCEPT FOR SPECIFIED EXTERNAL DUCT INSULATION FOR UNITS THAT DO REQUIRE DUAL-WALL CONSTRUCTION.)
DUCT SILENCER SCHEDULE
TAGNAME
AREASERVED
DIMENSIONS (INCHES)
CFMVELOCITY
(FPM)
MAX. S.P.DROP IN. W.C.
(NOTE 1)
ACOUSTICAL PERFORMANCE AT +1000 FPM
MANUFACTURER MODEL NOTESWIDTH HEIGHT LENGTH
MINIMUM DYNAMIC INSERTION LOSS IN DB
OCTAVE BAND CENTER FREQUENCY
63 125 250 500 1000 2000 4000 8000
DS-1 AHU-4 58 36 48 24500 2000 0.16 4 7 11 16 14 14 11 8 VIBRO ACOUSTICS RD-UHV-F1-L21068 NOTE 1,2,3
DS-2 AHU-5 58 26 48 19500 2000 0.16 4 7 11 16 14 14 11 8 VIBRO ACOUSTICS RD-UHV-F1-L21068 NOTE 1,2,3
DS-3 AHU-4 60 40 84 32000 1920 0.23 9 10 13 24 27 27 20 18 VIBRO ACOUSTICS RED-UHV-F1-L21068 NOTE 1,2,3
DS-4 AHU-5 60 36 84 27000 1800 0.20 9 10 13 24 27 27 20 18 VIBRO ACOUSTICS RED-UHV-F1-L21068 NOTE 1,2,3
No. Description Date
1 ADDENDUM 1 11/27/2017
2 ADDENDUM 2 12/08/2017
2
2
NA NA NA NA
2
1. ASC CONTROLLERS ARE SUPPLIED BY OWNER AND MOUNTED BY
CONTRACTOR.
2. KEEP ALL LOW VOLTAGE CONTROL WIRING ( UNDER 25V) AND LOW
VOLTAGE POWER WIRING (OVER 25V) SEPARATED. (RUN IN
SEPARATE CONDUIT).
3. PLYWOOD SIZE IS BASED ON THE NUMBER OF CONTROLLERS IN
EACH LOCATION. COORDINATE WITH OWNERS REPRESENTATIVE.
4/0 BOX WITH PULL CHAIN.18W LED LIGHT WITH GUARD.
4'x4'x3/4" PLYWOOD (MIN)(PAINT FRONT AND
ENDS MACHINE GRAY.)
1-1/2" UNISTRUTCHANNEL (2)
6" x 6" WIRE TROUGH
3/4" CONDUIT
120 VAC INPUT POWER
DEDICATED 15A CIRCUIT
1" CONDUITMINIMUM
I/O
6"x6" WIRETROUGH
1-1/2" UNISTRUTCHANNEL (2)
4'x4'x3/4" PLYWOOD (MIN)(PAINT FRONT AND ENDSMACHINE GRAY)
3/4" CONDUIT
4/0 BOX WITHPULL CHAIN. 18WLED WITH GUARD.
ASC ASC
BY DIVISION 16
2" MIN. CONDUIT (2)
POSTBASE (2)
BRACEFITTING (2)
NOTES:
FRONT VIEW SIDE VIEW
EXP.ANCHORS
3' MIN DISTANCE
3'-6
" T
YP
ICA
L
FLOORFLOOR
OPTIONAL FLOORMOUNT
WA
LL
EF M
EXHAUSTAIR
EF
-S
601
ST/ECM
EF
-C
602
EF
-O
603
ME
TA
SY
S (
HS
-A)
RF VFD
METASYS (RF-C)
R4RRF-C
METASYS (RF-O)R4RR1R
24 VAC
METASYS (SF-C)
VFDO2A-O2B
CONTACTS ON R3
METASYS(SF-S)
METASYS(LT-A)
METASYS(HS-A)
FREEZE STATAUX CONTACTS
CONTACTS R5
R3STATUSRELAY
R2RSF-C
DMPRELAY
CONTACTSON R3
R1R
HTGRELAY
FACONTACTS R5
R6
24 VAC
F-CC
ST-CC
OUT2B
OUT2A
STATUS
R5 HSRELAY
HIGHSTATICSWITCH
V1-11CC
METASYS (RF-S)
O2A AND O2BON VFD
SF VFD
METASYS (SF-O)
R2RR1R
F-CC
ST-CC
OUT2B
OUT2A
STATUS
V1-11CCSF-SAFTEY
LT-A R6LT-A
RELAY
LOCATE DPT AS SHOWNON MECH PLANS
J-BOX12 X 12 X 6
BY TCC
REQUIRED POWER
SPACEROUTE TO
DAMPENER
DPT
H L
ROOF
OA PRESSURESTATION
FC COMMUNICATION BUSWIRE DAISY CHAINED TOPREVIOUS VMA CNTRLR
LOW VOLTAGEWIRE
AIR FLOWMEASURING
TAPS
AIR IN
FC COMMUNICATION BUSWIRE DAISY CHAINED TONEXT VMA CONTROLLER
DDC VMA
CONTROLLER
AIR VALVEDAMPER
NETWORKSENSOR
T
M
1. CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.
PROGRAMMING AND COMMISSIONING WILL BE DONE BY OWNER.
2. NETWORK SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. NETWORK SENSOR WILL BE JCI NS
SERIES.
3. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE
OUTER CASING, DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED
BY CABLE-TEK, OR APPROVED EQUIVALENT.
4. CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
5. VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE. PROVIDED,
INSTALLED, & WIRED TO CONTROLLER BY CONTRACTOR.
6. FUSE LOCATED WITHIN 2 FT. OF VMA CONTROLLER.
7. LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
8. SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS OTHERWISE
NOTED, ALL CONTROL WORK SHALL BE BY CONTRACTOR.
CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
1.
2.
SA BUSWIRE
SUPPLY AIRSENSOR
AIR OUT
KEYNOTES:
NOTES:
FC COMMUNICATION BUSWIRE DAISY CHAINED TOPREVIOUS VAV CNTRLR
LOW VOLTAGEWIRE
AIR FLOWMEASURING
TAPS
AIR IN
FC COMMUNICATION BUSWIRE DAISY CHAINED TONEXT VAV CONTROLLER
DDC VMA
CONTROLLER
HWR HWS
SUPPLY AIRSENSOR
AIR OUT
AIR VALVEDAMPER
NETWORKSENSOR
T
M
SA BUSWIRE
S
OCCUPANCYSENSOR
1. CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL MS-VMA-16XX SERIES.
PROGRAMMING AND COMMISSIONING WILL BE DONE BY OWNER.
2. ZONE SENSOR WILL BE FURNISHED BY OWNER & INSTALLED BY CONTRACTOR. ZONE SENSOR WILL BE JCI NC SERIES.
3. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR, WITH BLUE
OUTER CASING, DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU JK DISTRIBUTED BY WINDY CITY WIRE CONSTRUCTED
BY CABLE-TEK, OR APPROVED EQUIVALENT.
4. INSTALLATION OF OCC SENSOR IS WORK OF DIVISION 26, SEE E-SERIES SHEETS FOR FINAL LOCATIONS. A CONTROL
CIRCUIT SHALL BE CONNECTED TO ALL OCC SENSORS AS WORK OF DIVISION 23. A CONTROL SIGNAL SHALL BE RELAYED
TO THE VAV TERMINAL UNIT THAT SERVES THAT SPACE. IN LOCATIONS WHERE MULTIPLE OCC SENSORS ARE PRESENT,
ALL SENSORS SHALL BE MONITORED AND TRANSMIT A SIGNAL TO THE VAV TERMINAL UNIT WITHIN THAT SPACE. ALL
SENSORS SHALL BE WIRED IN PARALLEL.
5. CONTROLLER MUST HAVE A MINIMUM OF 18 INCHES OF ACCESSIBLE CLEARANCE.
6. VAV SUPPLY TEMP SENSOR 1000 OHM PLATINUM RTD LOCATED APPROX. 8 FT. FROM VAV BOX DISCHARGE.
7. FUSE LOCATED WITHIN 2FT. OF VMA CONTROLLER.
8. LOW VOLTAGE WIRE BY DIVISION 23. SEE ELECTRICAL DRAWINGS FOR SOURCE.
9. JOHNSON VG1000 FORGED BRASS VALVE WITH PROPORTIONAL 0-10 VOLT ACTUATOR OR EQUIVILENT
10. SA BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 4 CONDUCTOR.
11. PERIMETER HEAT CONNECT TO ALL VALVES IN AREA SERVED BY VAV BOX AND COORDINATE WITH OWNER PROVIDED
SIGNAL AMPLIFIER AS REQUIRED.
12. CO2 SENSOR. SEE PLANS FOR LOCATIONS.
ELECTRICACTUATOR
1. VMA TERMINAL INCLUDES CONSTANT VOLUME (CV) UNITS & VARIABLE AIR VOLUME (VAV) UNITS. UNLESS
OTHERWISE NOTED, ALL CONTROL WORK SHALL BE BY CONTRACTOR.
2. CAPS FOR VAV DP TEST PORTS MUST BE 1/4" BRASS PLUGS.
NC
CO2
CO2SENSOR
KEYED NOTES:
NOTES:
EXTEND 3/4" PLYWOOD 6" WIDERTHAN VFD ON BOTH SIDES
SIZE FOR MOTOR LOADPOWER REQUIREMENTS
3/4" PLYWOOD PAINT BOTHSIDES & ENDS MACHINE GRAY
1. VARIABLE FREQUENCY DRIVE (VFD) IS PROVIDED AND INSTALLED BY CONTRACTOR.
2. KEEP ALL LOW VOLTAGE CONTROL WIRING (UNDER 25V) AND HIGH VOLTAGE POWER
WIRING (OVER 25V) SEPARATED. (RUN IN SEPARATE CONDUIT).
3. PLYWOOD SIZE IS BASED ON ONE VFD IN EACH LOCATION. FOR MULTIPLE VFD'S,
COORDINATE WITH OWNER'S REPRESENTATIVE.
4. POWER TO DRIVE AND LEADS TO MOTOR MUST BE IN SEPARATE CONDUIT.
5. INSTALL ISO TRANSFORMER IF REQUIRED.
6. DO NOT PLACE ISO TRANSFORMER BELOW VFD.
7. IF REMOTE SERVICE DISCONNECT IS REQUIRED IT MUST BE HARDWIRED TO VFD SAFTEY
CIRCUIT TO SHUT DOWN DRIVE IF DISCONNECT IS OPENED.
FLOOR
1-1/2" UNISTRUTCHANNEL (2)
EXTEND 3/4" PLYWOOD1" BELOW BOTTOM OF VFD
SIZE FOR VFD POWERREQUIREMENTS
EXTEND 3/4" PLYWOOD3" ABOVE TOP OF VFD
6" x 6" WIRE TROUGH
3/4" (MIN)
FLOOR
EXP. ANCHORS
CHANNEL (2)1-1/2" UNISTRUT
VFD
WA
LL
3'-6
" T
YP
ICA
L
8"
(MIN
)
VFD
(TYPICAL)
VFDDISCONNECT
TO POWER
DO NOT PLACEISO BELOW VFD
POSTBASE (2)
BRACEFITTING (2)
OPTIONAL FLOOR MOUNT
NOTES:
FRONT VIEW SIDE VIEW
AHU-4 SYSTEM DDC POINTPANEL LOCATION : PENTHOUSE
KEYNOTES:
1. SEE AHU START CIRCUIT DETAIL.2. LOCATE AS SHOWN ON MECH PLANS.3. LOCATE ON NORTH FACE OF BUILDING W/
WEATHER COVER.
GENERAL NOTES
1. SEE SPECIFICATIONS FOR DEVICE SPECIFICATIONS.
2. ANY DEVICE REQUIRING POWER MUST BE POWERED BY CONTRACTOR.
TAG# TYPE POINT NAME DESCRIPTION DEVICE101 AI OA-T OUTSIDE AIR TEMP SOFTWARE POINT102 AI MA-T MIXED AIR TEMP RTD/DUCT AVERAGING103 AI PH-T PREHEAT TEMP RTD/DUCT AVERAGING104 AI CC-T COOLING COIL TEMP RTD/DUCT AVERAGING105 AI SA-T SUPPLY AIR TEMP RTD/DUCT AVERAGING106 AI RA-T RETURN AIR TEMP RTD/DUCT AVERAGING107 AI SF-PRS SUPPLY FAN STATIC PRESS DIFF PRESS TRANSMITTER108 AI OA-F OUTSIDE AIR FLOW AIRFLOW STATION/TRANSMITTER109 AI BLDG-PRS BLDG STATIC PRESS DIFF PRESS TRANSMITTER110 AO MA-D MIXED AIR DAMPER ELECT ACTUATOR W/SPRING RT111 AO SF-O SUP FAN OUTPUT VFD112 AO RLF-O RELIEF FAN OUTPUT VFD113 AO CLG-O COOLING COIL VALVE OUTPUT ELECT ACTUATOR W/SPRING RTN114 AO PHT-O PREHEAT COIL VALVE OUTPUT ELECT ACTUATOR W/SPRING RTN115 BI SF-S SUPPLY FAN STATUS CURRENT SWITCH116 BI RLF-S RELIEF FAN STATUS CURRENT SWITCH117 BI PHP-S PREHEAT PUMP STATUS CURRENT SWITCH118 BI LT-A LOW TEMP ALARM DUCT FREEZE STAT119 BI HS-A DUCT HI STATIC ALARM DUCT DIFF PRESS SWITCHES120 BO SF-C SUPPLY FAN COMMAND CONTROL RELAY121 BO RLF-C RELIEF FAN COMMAND CONTROL RELAY122 BO PHP-C PREHEAT PUMP COMMAND CONTROL RELAY123 AO MIN OA-D MINIMUM OUTSIDE AIR DAMPER ELECT ACTUATOR W/SPRING RTN
1
1
1
1 11
1
2
2
3
SMK
AIR
SUPPLY
SF
-PR
S
107
DPT
CWR
CWS
RA
-T
106
PH
-T
LT
-A
CLG
-O
SF
-C
SF
-S
SF
-O
SA
-T
RELIEFAIR
DM
NO
RETURN
AIR
DPS
119 105113118103 111115120
DM
FILTERS
VFD
HS
-A
SF
35 F
MCO
IL
CO
OLIN
G
NC
NC
OUTSIDE
AIR
114
PH
T-O
117 122
HWS
PH
P-S
HWR
PH
P-C
NO
PR
EH
EA
T
M
CO
IL
SMK
MA
-T
102
AFS
OA
-F
108
BLD
G-P
RS
109
DPT
110
MA
-D
CC
-T
104
DPS
119
HS
-A
DPS
119
HS
-A
RLF
-C
RLF
-S
RLF
-O
112116121
VFD
RLF
M
DM
NC
ES
MIN OAD
ECONOMIZER DAMPER
DM
123
TAG# TYPE POINT NAME DESCRIPTION DEVICE601 BI EF-S EXH FAN STATUS CURRENT SWITCH602 BO EF-C EXH FAN COMMAND CONTROL RELAY603 AO EF-O EXH FAN OUTPUT ECM CONTROLLER
EXHAUST FANS DDC POINT LIST
GENERAL NOTES:
1. CONNECT POINTS TO NEAREST EMCS CONTROLLER.
2. POINT 603 FOR EF-1 ONLY.
DM
2
ES
NC
KEYNOTES:
1. FAN RELAYS AND CONTROL VALVE WIRING SHALL BE CONNNECTED TO A TERMINAL STRIP IN THE FCU AT THE FACTORY.
2. ALL CONDUIT AND WIRING SHALL BE BY CONTRACTOR. WIRING SHALL BE PROVIDED FROM FCU TERMINAL STRIP TO THE THERMOSTAT LOCATION WITH AN EXTRA 4-FOOT LENGTH OF WIRE AT THE THERMOSTAT LOCATION.
3. THERMOSTAT CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL TEC SERIES. CONTRACTOR SHALL ROUGH-IN CONDUIT AND BOX FOR MOUNTING REMOTELY LOCATED THERMOSTATS. OWNER WILL TERMINATE, PROGRAM, AND COMMISSION CONTROLLER AFTER POWER IS ENERGIZED TO FCU.
4. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR. FC BUS TO BE PULLED BY CONTRACTOR AND SHALL BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES. SEE FC LAYOUT DETAIL. LEAVE EXTRA 4-FOOT OF WIRE AT THERMOSTAT LOCATION. LABEL WIRES WITH "IN FROM XXX" OR "OUT FROM XXX", WHERE XXX DESIGNATES THE ROOM NUMBER
5. SERVICE DISCONNECT/SWITCH AND TRANSFORMER PROVIDED AND INSTALLED BY CONTRACTOR.
6. CONDUCTOR 22 GAUGE TWISTED, SHIELDED, STRANDED WIRE
M
XXX XX X X X XX
FAN COIL UNIT (FCU)
FA
N C
OIL
U
NIT
(F
CU
)
4
5
CWR
CWS
1
6
3
TEC
AIR
OU
T
2
R1R 24VAC RIBIUCR2R 24VAC RIBIUCR3 24VAC CONTROL RELAY -2POLER4R 24VAC RIBIUCR5 24VAC CONTROL RELAY -2POLER6 24VAC CONTROL RELAY -2POLEDMP RELAY 24VAC CONTROL RELAY -2POLEHTG RELAY 24VAC CONTROL RELAY -2POLE
DEVICES (SEE SPECS):
GENERAL NOTES:
1. KEEP ALL LOW VOLTAGE CONTROL WIRING
(UNDER 25V) AND LOW VOLTAGE POWER WIRING
(OVER 25V) SEPARATED. (RUN IN SEPARATE
CONDUIT.)2. PROVIDE RELAYS WITH MULTIPLE CONTACTS AS
REQUIRED.
3. ANY DISCONNECT WITH AUX CONTACTS WILL BE
ADDED TO SAFETY CIRCUIT.4. MOUNT R1, R2, AND R4 ON GUTTER UNDER VFD
10
4
12
211
9
6
1
5
79
33
8
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
79
:51:1
7 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
VENTILATION CONTROLS
MV700
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO SCALE1AHU-4 CONTROLS (TYP AHU-5)
NO SCALE2ASC PANEL MOUNTING DETAIL
NO SCALE9EXHAUST FAN CONTROL DETAIL
NO SCALE3BLOWER COIL UNIT DETAIL
NO SCALE6MA VFD START CIRCUIT
NO SCALE5SPACE DIFF PRESSURE TRANSMITTER
NO SCALE8VAV BOX CONTROL DIAGRAM WITHOUT REHEAT
NO SCALE7
VAV BOX CONTROL DIAGRAM WITHREHEAT & PERIM HEAT
NO SCALE4VFD MOUNTUING DETAILS
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
3
8
4
6
7
3
1
5
2
No. Description Date
2 ADDENDUM 2 12/14/2017
2
2
2
SIGNAL TO ASC
LOCATE VENTS AT ALL HIGH POINTS IN TUBING LINES.
DPT MUST BE ACCESSIBLE AND LOCATED 5' ABOVE FLOOR UNLESS
APPROVED BY OWNERS REPRESENTATIVE. SEE MECH. DRAWINGS FOR
LOCATION.
BYPASS VALVE ASSEMBLY TO BE PRE-MANUFACTURED. SEE
SPECIFICATIONS.
ENERGIZE DPT PER MANUFACTURER'S RECOMMENDATIONS TO ENSURE
MEMBRANE IS NOT DAMAGED.
1.
2.
3.
4.
REQUIRED
POWER BY TCC
GAGE COCK(TYPICAL)
VENT
1/2" BALL VALVE
DPT
L
VENT
BYPASS VALVEASSEMBLY
H
VENT
4-20 mA
1/2" NPTTHRED-O-LET
VENT
NOTES:
C/H WATERRETURN PIPE
C/H WATERSUPPLY PIPE
3/8" COPPERTUBING (TYP.)
VAV
AH11HEX3 AH12
VAV
VAV VAV
EXISTHEX1
EXISTNAE16
EXISTN2 BUS
EXISTVAV060
EXISTVAV
EXISTAHU-1
SUB-BASEMENT
BASEMENT
FIRST FLOOR
SECOND FLOOR
ATTIC/PENTHOUSE
NOTES:
1. FC BUS TO BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES. CONNECTIONS CAN BE MADE
AT EQUIPMENT ONLY. SEE PLANS FOR QUANTITY AND LOCATIONS OF VAV/FCU
CONTROLLERS.
2. OWNER WILL MAKE TERMINATION CONNECTIONS AT PANELS. LOCATE PANELS IN SAME
ROOM AS EQUIPMENT SERVED.
3. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG, PLENUM RATED, TWISTED SHIELDED, 3
CONDUCTOR, WITH BLUE OUTER CASING, DESCRIPTED AS 22-03 OAS STR PLNM NEON BLU
JK DISTRIBUTED BY WINDY CITY WIRE, CONSTRUCTED BY CABLE-TEK, OR APPROVED
EQUIVALENT.
4. COORDINATE FIELD ROUTING WITH OWNERS REPRESENTATIVE.
5. EXISTING FC BUS TO BE MODIFIED AS SHOWN. FC BUS TO REMAIN OPERATIONAL
THROUGHOUT CONSTRUCTION. COORDINATE OUTAGES WITH OWNERS REP.
6. EXISTING N2 BUS TO REMAIN OPERATIONAL THROUGHOUT CONSTRUCTION. COORDINATE
OUTAGES AND ROUTING WITH OWNERS REP. REROUTE BUS AS REQUIRED TO REMOVE
FROM REMODELED AREAS.
CWS BCU001
BCU002
OAT HWS-SP
20 180
60 140
THE EMCS SYSTEM WILL START THE LEAD HOT WATER PUMP (HWP1-C) AND OPEN
ITS ISOLATION VALVE (HX1-ISO) WHEN THE OUTSIDE AIR TEMP (OA-T) IS BELOW 85
DEG F. ONCE THE PUMP STATUS (HWP1-S) IS PROVEN, THE STEAM VALVES WILL
MODULATE (HX1-V13 FIRST AND THEN HX1-V23 SECOND) TO MAINTAIN HOT WATER
SUPPLY TEMPERATURE (HWS-T). THE HOT WATER SUPPLY SETPOINT WILL BE
CONTINUOUSLY RESET AS FOLLOWS:
THE EMCS SYSTEM WILL MODULATE THE VFD (HWP-O) OF THE LEAD PUMP TO
MAINTAIN THE DIFFERENTIAL PRESSURE (HW-DP) SETPOINT.
IF THE LEAD PUMP FAILS OR THE LEAD HEAT EXCHANGER CAN NOT MAINTAIN
TEMPERATURE OR PRESSURE, THE LAG HEAT EXCHANGER AND PUMP WILL START
AND CONTROL THE SAME AS THE LEAD SYSTEM.
1. LOCATE DPT AS SHOWN ON PLANS. CONTROL WIRING FROM DPT MUST BE RUN
BACK TO SAME CONTROLLER WITH HOT WATER PUMP SPEED CONTROL
OUTPUT.
HW
S-T
HX-2
POINT NAME
OA-T
HWS-T
HWR-T
HW-DP
HX1-V13
HX1-V23
HX2-V13
HX2-V23
HWP1-O
HWP2-O
HWP1-S
HWP2-S
HWP1-C
HWP2-C
HX1-ISO
HX2-ISO
TYPE
AI
AI
AI
AI
A0
AO
AO
AO
AO
AO
BI
BI
BO
BO
BO
BO
TAG#
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
LPR
LPR
DESCRIPTION
OUTSIDE AIR TEMP
HW SUPPLY TEMPERATURE
HW RETURN TEMPERATURE
HW DIFFERENTIAL PRESSURE
HEX1 1/3 VALVE
HEX1 2/3 VALVE
HEX2 1/3 VALVE
HEX2 2/3 VALVE
HW PUMP 1 OUTPUT
HW PUMP 2 OUTPUT
HW PUMP 1 STATUS
HW PUMP 2 STATUS
HW PUMP 1 COMMAND
HW PUMP 2 COMMAND
HEX 1 ISOLATION VALVE
HEX 2 ISOLATION VALVE
DEVICE
SOFTWARE
RTD/THERMOWELL
RTD/THERMOWELL
DIFF. PRESS. TRANSMITTER
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
VFD
VFD
CURRENT SWITCH
CURRENT SWITCH
CONTROL RELAY
CONTROL RELAY
2-POS ELECT ACTUATOR
2-POS ELECT ACTUATOR
503
HW
R-T
HW
P1-
O
510
HX-1
LPS
502
HW
P2-
O
509
HWP-1
HW
P1-
S
512
HW
P1-
C
514
HWR
DPT
HW
-DP
504
HWS
HWP-2
HW
P2-
S
511
HW
P2-
C
513
HX1-V23506
LPS
HX2-V23508
HX
2-IS
O
516
HX
1-IS
O
515
2/3 NC
1/3 NC
2/3 NC
VFD
M
M
VFD
1/3 NC
HX1-V13505
HX2-V13507
SEQUENCE OF OPERATION
KEYNOTES:
HOT WATER SYSTEM DDC POINTS LISTPANEL LOCATION: MR1110
OAT HWS-SP
20 180
60 140
THE EMCS SYSTEM WILL START THE LEAD HOT WATER PUMP (HWP1-C) AND OPEN
ITS ISOLATION VALVE (HX1-ISO) WHEN THE OUTSIDE AIR TEMP (OA-T) IS BELOW 85
DEG F. ONCE THE PUMP STATUS (HWP1-S) IS PROVEN, THE STEAM VALVES WILL
MODULATE (HX1-V13 FIRST AND THEN HX1-V23 SECOND) TO MAINTAIN HOT WATER
SUPPLY TEMPERATURE (HWS-T). THE HOT WATER SUPPLY SETPOINT WILL BE
CONTINUOUSLY RESET AS FOLLOWS:
THE EMCS SYSTEM WILL MODULATE THE VFD (HWP-O) OF THE LEAD PUMP TO
MAINTAIN THE DIFFERENTIAL PRESSURE (HW-DP) SETPOINT.
IF THE LEAD PUMP FAILS OR THE LEAD HEAT EXCHANGER CAN NOT MAINTAIN
TEMPERATURE OR PRESSURE, THE LAG HEAT EXCHANGER AND PUMP WILL START
AND CONTROL THE SAME AS THE LEAD SYSTEM.
1. LOCATE DPT AS SHOWN ON PLANS. CONTROL WIRING FROM DPT MUST BE RUN
BACK TO SAME CONTROLLER WITH HOT WATER PUMP SPEED CONTROL
OUTPUT.
HW
S-T
HX-2
POINT NAME
OA-T
HWS-T
HWR-T
HW-DP
HX1-V13
HX1-V23
HX2-V13
HX2-V23
HWP1-O
HWP2-O
HWP1-S
HWP2-S
HWP1-C
HWP2-C
HX1-ISO
HX2-ISO
TYPE
AI
AI
AI
AI
A0
AO
AO
AO
AO
AO
BI
BI
BO
BO
BO
BO
TAG#
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
LPR
LPR
DESCRIPTION
OUTSIDE AIR TEMP
HW SUPPLY TEMPERATURE
HW RETURN TEMPERATURE
HW DIFFERENTIAL PRESSURE
HEX1 1/3 VALVE
HEX1 2/3 VALVE
HEX2 1/3 VALVE
HEX2 2/3 VALVE
HW PUMP 1 OUTPUT
HW PUMP 2 OUTPUT
HW PUMP 1 STATUS
HW PUMP 2 STATUS
HW PUMP 1 COMMAND
HW PUMP 2 COMMAND
HEX 1 ISOLATION VALVE
HEX 2 ISOLATION VALVE
DEVICE
SOFTWARE
RTD/THERMOWELL
RTD/THERMOWELL
DIFF. PRESS. TRANSMITTER
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
ELECT ACTUATOR W/SPRG RTN
VFD
VFD
CURRENT SWITCH
CURRENT SWITCH
CONTROL RELAY
CONTROL RELAY
2-POS ELECT ACTUATOR
2-POS ELECT ACTUATOR
503
HW
R-T
HW
P1-
O
510
HX-1
LPS
502
HW
P2-
O
509
HWP-1
HW
P1-
S
512
HW
P1-
C
514
HWR
DPT
HW
-DP
504
HWS
HWP-2
HW
P2-
S
511
HW
P2-
C
513
HX1-V23506
LPS
HX2-V23508
HX
2-IS
O
516
HX
1-IS
O
515
2/3 NC
1/3 NC
2/3 NC
VFD
M
M
VFD
1/3 NC
HX1-V13505
HX2-V13507
SEQUENCE OF OPERATION
KEYNOTES:
HOT WATER SYSTEM DDC POINTS LISTPANEL LOCATION: MR1110
1. ALL CONDUIT AND WIRING SHALL BE BY CONTRACTOR.
2. CONNECT CONTROL POINTS TO NEAREST DDC CONTROLLER.
3. TWO POSITION ELECTRIC ACTUATOR.
4. 1000 OHM PLATINUM ZONE SENSOR LOCATED IN AREA SERVED BY UNIT HEATER.
DO NOT INSTALL IN DIRECT PATH OF UNIT HEATER DISCHARGE.
AIR OUTAIR IN
HOT WATERHEATING COIL
T
ZONE SENSOR
M
ELECTRIC
ACTUATOR
HW
S
HW
R
DEVICE
ZONE SENSOR
CONTROL RELAY
POINT NAME
MR-T
UH-SS
TAG#
551
552
TYPE
AI
BO
DESCRIPTION
MECH ROOM TEMP
UNIT HEATER S/S
UNIT HEATER DDC POINT LIST
552UH-SS
551MR-T
KEYNOTES:
T
NOTES:
CONNECT CONTROL POINTS TO NEAREST FEC CONTROLLER.
CONNECT RADIATOR SIGNAL TO MULTIPLE VALVES AS SHOWN ON PLANS.
ANY DEVICE REQUIRING POWER MUST BE POWERED BY CONTRACTOR.
1.
2.
3.
RADIATOR
ZONE SENSOR
DEVICE
ZONE SENSOR
0-10V ELECT ACTUATOR
POINT NAME
ZN-T
RAD-VLV
TAG#
551
552
TYPE
AI
AO
DESCRIPTION
ZONE TEMP
RADIATOR VALVE
RHP DDC POINT LIST
552RAD-VLV
551ZN-T
NC
LPS
WHEN OUTSIDE AIR TEMP (OA-T) IS ABOVE THE COOLING ENABLE SETPOINT (55 DEG ADJ), THE EMCS SYSTEM WILL MODULATE OPEN THE BUILDING PUMP VALVE (BP-VLV) TO MAINTAIN BUILDING CHILLED WATER DIFFERENTIAL PRESSURE (BCW-DP) SETPOINT. IF BUILDING DIFFERENTIAL PRESSURE CAN NOT BE MAINTAINED WITH LOOP PRESSURE (BP-VLV > 90% OPEN), THEN THE EMCS SYSTEM WILL START THE LEAD BUILDING CHILLED WATER PUMP (BP-C). ONCE THE PUMP STATUS (BP-S) IS PROVEN, THE PUMP SPEED (BP-O) WILL BE MODULATED TO MAINTAIN BUILDING CHILLED WATER DIFFERENTIAL PRESSURE (BCW-DP) SETPOINT. IF BUILDING VALVE (BP-VLV) DROPS BELOW 50% OPEN, THE LEAD BUILDING CHILLED WATER PUMP (BP-C) WILL BE SHUT OFF. IF THE LEAD CHILLED WATER PUMP FAILS OR IS OPERATING AT 100% SPEED FOR 10 MINUTES AND CAN NOT MAINTAIN DIFFERENTIAL PRESSURE SETPOINT, LAG CHILLED WATER PUMP WILL BE STARTED AND OPERATED AT SAME SPEED AS LEAD PUMP. WHEN PUMP SPEED DROPS BELOW 50%, LAG PUMP WILL BE SHUT OFF. WINTER PUMP (BP3) SHALL OPERATE WITH A SIMILAR SEQUENCE WHEN OA-T IS LESS THAN 55 DEG.
KEYNOTES:
1. LOCATE DPT AS SHOWN ON PLANS. CONTROL WIRING FROM DPT MUST BE RUN BACK TO SAME CONTROLLER WITH CHILLED WATER PUMP SPEED CONTROL OUTPUT.
TAG# TYPE POINT NAME DESCRIPTION DEVICE251 AL BCWS-T BLDG CW SUPPLY TEMP EXISTING252 AL BCWR-T BLDG CW RETURN TEMP EXISTING253 AL BCW-F BLDG CW FLOW EXISTING254 AL BCW-DP1 CW DIFF PRESS EXISTING255 AL BCW-DP2 CW DIFF PRESS CW DIFF PRESS256 AO BP1-O BLDG CW PUMP 1 OUTPUT VFD257 AO BP2-O BLDG CW PUMP 2 OUTPUT VFD258 AO BP3-O BLDG CW PUMP 3 OUTPUT ECM259 AO BP-VLV1 BLDG CW PUMP ISO VALVE ELECT ACTUATOR W/ SPRING RTN260 AO BP-VLV2 BLDG CW PUMP ISO VALVE ELECT ACTUATOR W/ SPRING RTN261 BI BP1-S BLDG CW PUMP 1 STATUS CURRENT SWITCH262 BI BP2-S BLDG CW PUMP 2 STATUS CURRENT SWITCH263 BI BP3-S BLDG CW PUMP 3 STATUS CURRENT SWITCH264 BO BP1-C BLDG CW PUMP 1 COMMAND CONTROL RELAY265 BO BP2-C BLDG CW PUMP 2 COMMAND CONTROL RELAY266 BO BP3-C BLDG CW PUMP 3 COMMAND CONTROL RELAY
CW BLDG PMP SEQUENCE OF OPERATION
CWR
CWS
BC
WS
-T
251
CWP1
BP
1-S
261
M
BP
1-C
264
VFD
BP
1-O
256
BCW-DP1254 DPT
BC
WR
-T
252
BC
W-F
253
RETURN
LOOP
SUPPLY
LOOP
BP-VLV1259
TT
TT
FC
CWP2
BP
2-S
262
M
BP
2-C
265
VFD
BP
2-O
257
CWP3
BP
3-S
263
M
BP
3-C
266
ECM
BP
3-O
258
BP-VLV2260
BCW-DP2255 DPT
3
4
XXX XX X X X XX
1. FAN RELAYS AND CONTROL VALVE WIRING SHALL BE CONNNECTED TO A TERMINAL STRIP IN THE BCU AT THE FACTORY.
2. ALL CONDUIT AND WIRING SHALL BE BY CONTRACTOR. WIRING SHALL BE PROVIDED FROM BCU TERMINAL STRIP TO THE THERMOSTAT LOCATION WITH AN EXTRA 3-FOOT LENGTH OF WIRE AT THE THERMOSTAT LOCATION.
3. THERMOSTAT CONTROLLER WILL BE FURNISHED AND INSTALLED BY OWNER. CONTROLLER WILL BE JCI MODEL TEC SERIES. CONTRACTOR SHALL ROUGH-IN CONDUIT AND BOX FOR MOUNTING REMOTELY LOCATED THERMOSTATS. OWNER WILL TERMINATE, PROGRAM, AND COMMISION CONTROLLER AFTER POWER IS ENERGIZED TO BCU.
4. FC COMMUNICATION BUS WIRE SHALL BE 22 AWG PLENUM RATED, TWISTED SHIELDED, 3 CONDUCTOR. FC BUS TO BE PULLED BY CONTRACTOR AND SHALL BE CONTINUOUS DAISY CHAIN WITHOUT SPLICES. SEE FC LAYOUT DETAIL. LEAVE EXTRA 3-FOOT OF WIRE AT THERMOSTAT LOCATION.
5. SERVICE DISCONNECT/SWITCH AND TRANSFORMER PROVIDED AND INSTALLED BY CONTRACTOR.
6. 8 CONDUCTOR 22 GAUGE TWISTED, SHIELDED, STRANDED WIRE
BLOWER COIL UNIT
KEYNOTES:
HWR
HWR
CWR
CWS
M
AIR
OU
TR
ET
UR
N
AIR
IN
3
TEC
6
2
1
4
5
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
79
:51:1
7 P
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
29
0.0
1_M
U M
em
oria
l S
tud
en
t U
nio
n_C
en
tral_
mis
hra
as@
kjw
w.c
om
.rvt
16253
ASHMIS
VENTILATION CONTROLS
MV701
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO SCALE1CHILLED WATER CONTROL SCHEMATIC
NO SCALE2TYPICAL BLDG-DP DPT ARRANGEMENT
NO SCALE3FC BUS SCHEMATIC DIAGRAM
NO SCALE5HOT WATER SYSTEM CONTROL SCHEMATIC
NO SCALE4UH/CUH DETAIL
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
1
No. Description Date
2 ADDENDUM 2 12/14/2017
NO SCALE6BLOWER COIL UNIT DETAIL - CW & HW
2
NO SCALE7RADIATOR HEAT DETAIL
NOTE:
1) THIS DETAIL APPLY ONLY FOR ALTERNATE 3.
NOTES:
J J J
JJ
J
J
J
J
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
DEMOLISH ALL ELECTRICAL POWER ITEMS (RECEPTACLES, DISCONNECTS, ELECTRICAL CONNECTIONS TO EQUIPMENT, ETC) INSIDE THIS BOUNDARY, UNLESS SHOWN OTHERWISE.
REFER TO MEMORIAL UNION ORIGINAL CONSTRUCTION DOCUMENTS PROVIDED BY UNIVERSITY OF MISSOURI AS A REFERENCE FOR THE DEMOLITION OF EXISTING CONDITIONS.EXISTING PANEL P2 TO
BE REMOVED.
EXISTING FLOOD LIGHT AND
CONDUIT TO BE REMOVED FOR
ROOF REPLACEMENT AND RE-
INSTALLED UPON COMPLETION
OF ROOF REPLACEMENT.
EXISTING FLOOD LIGHT AND CONDUIT TO
BE REMOVED FOR ROOF REPLACEMENT
AND RE-INSTALLED UPON COMPLETION
OF ROOF REPLACEMENT.
EXISTING FLOOD LIGHT AND CONDUIT TO
BE REMOVED FOR ROOF REPLACEMENT
AND RE-INSTALLED UPON COMPLETION OF
ROOF REPLACEMENT.
EXISTING FLOOD LIGHT AND CONDUIT TO
BE REMOVED FOR ROOF REPLACEMENT
AND RE-INSTALLED UPON COMPLETION
OF ROOF REPLACEMENT.
EXISTING FLOOD LIGHT AND
CONDUIT TO BE REMOVED FOR
ROOF REPLACEMENT AND RE-
INSTALLED UPON COMPLETION OF
ROOF REPLACEMENT.
EXISTING FLOOD LIGHT AND
CONDUIT TO BE REMOVED FOR
ROOF REPLACEMENT AND RE-
INSTALLED UPON COMPLETION OF
ROOF REPLACEMENT.
EXISTING TOWER FLOOD
LIGHT TO REMAIN
EXISTING TOWER FLOOD
LIGHT TO REMAIN
EXTERIOR SURFACE MOUNTED CONDUIT(TYPICAL)
EXTERIOR FLOOD LIGHTING LIGHTING CIRCUITS (2)208V/1PHASE 20AMP CIRCUITS AND (2)120V/1PHASE 20AMP CIRCUITS TO RE-FED FROM NEW ATTIC PANEL. REFER TO NEW WORK ON SHEET EP104N
LIGHTING PANEL K TO BE REMOVED
2
22
2
2
2
DEMOLISH EXISTING CONDUIT AND CONDUCTORS SERVING WOOD SHED.
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
71
0:2
2:0
4 A
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
290
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_sh
olla
12
. rvt
16253
ERIPER
ATTIC FLOOR PLAN - NORTHWING - ELECTRICAL - POWER- DEMO
EPD103N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - ELECTRICAL - POWER - DEMO
GENERAL SHEET NOTES :
1. REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, ELECTRICAL RENOVATION NOTES AND ELECTRICAL INSTALLATION.
2. ALL CONDUIT AND WIRING TO BE DEMOLISHED SHALL BE REMOVED FROM ITS DEVICE TO ITS SOURCE.
3. COORDINATE WITH OWNER PRIOR TO DISPOSAL OF ANY EQUIPMENT. COORDINATE ALL EQUIPMENT TO BE SAVAGED WITH OWNER.
4. COORDINATE DOWN TIME WITH OWNER.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
2 ADDENDUM 2 12/14/2017
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
J
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
N303Mechanical
10.5
N304Attic Storage
SN300EStairs
N302AElev Lobby
N302BElev. Eq.
DS-60
VFD-15
REF-2
DS-200DS-200
VFD-60
DS-30
VFD-20
DS-60
FCS-30
UH-1, UNIT HEATER,120V, 1PH, 0.3HP
UH-2, UNIT HEATER,120V, 1PH, 0.1HP
HWP-1, HEATING WATERPUMP, 480V, 3PH, 5HP
HWP-2, HEATING WATERPUMP, 480V, 3PH, 5HP
AHU-1, AIR HANDLING UNIT,480V, 3PH, 60HP
HWP-3, HEATING WATERPUMP, 120V, 1PH, 0.25HP
AHU 120VLIGHTING/ACCESSORIES
AHU-2, AIR HANDLING UNIT,480V, 3PH, 50HP
HWP-4, HEATING WATERPUMP, 120V, 1PH, 0.25HP
AHU 120VLIGHTING/ACCESSORIES
ELEVATOR
FDS-30L
EDS-100
W
W
DS-30VFD-5
SSU-1, SPLIT SYSTEM, 208V,1PH, 0.2KVA
CU-1, CONDENSING UNIT,208V, 1PH, 2.8KVA
ATTIC-14
ATTIC-22
ATTIC-20
(DP/AT2)-1
ATTIC-13
ATTIC-18
EF-1, EXHAUST FAN,480V, 3PH, 1HP
ATTIC-17
8
19
(DP/AT1)-4
(DP/AT1)-6
FCS-30
(DP/AT1)-1
7
19
19
(DP/AT2)-2 (DP/AT1)-2
PANEL ATTIC VFD-50
TR-15
5
DP/AT2
(DP/AT2)-5 5
DP/AT1
ATTIC-19
6
ATTIC-12 ATTIC-11
ATTIC-10
MX-1S-1A
ATTIC-9
MX-1S-1A
19
(DP/AT1)-7
(DP/AT1)-8
19
VFD-5
REF-1
ATTIC-21BAS PANEL
22
TOP OF HOISTWAY
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
71
0:2
2:0
0 A
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
290
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_sh
olla
12
. rvt
16253
ERIPER
ATTIC FLOOR PLAN - NORTHWING - ELECTRICAL - POWER
EP103N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ATTIC FLOOR PLAN - NORTH WING - ELECTRICAL - POWER
GENERAL SHEET NOTES :
1. REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, ELECTRICAL RENOVATION NOTES AND ELECTRICAL INSTALLATION.
2. ALL CONDUIT AND WIRING TO BE DEMOLISHED SHALL BE REMOVED FROM ITS DEVICE TO ITS SOURCE.
3. COORDINATE WITH OWNER PRIOR TO DISPOSAL OF ANY EQUIPMENT. COORDINATE ALL EQUIPMENT TO BE SAVAGED WITH OWNER.
4. COORDINATE DOWN TIME WITH OWNER.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
KEYNOTES:
1. CONNECT TO EXISTING SUMP PUMP 120V/1PH CIRCUIT IN PANEL P1B SECTION 1 USING 2#12 AND 1#12GND IN 3/4" C. REFER TO PLUMBING DRAWINGS FOR CONTROL PANEL LOCATION AND WIRING REQUIREMENTS.
2. CONNECT TO MANUFACTURER PROVIDED DISCONNECT. CIRCUIT TO EXISTING SPARE 30A/3P FUSIBLE SWITCH IN PANEL P1B SECTION 2 USING 3#12 AND 1#12GND IN 3/4" C. PROVIDE 3-20AMP FUSES COMPATIBLE WITH SQUARE D CAT. NO. QMB321TW FUSIBLE SWITCH.
3. CIRCUIT TO EXISTING CP-1 200A FUSIBLE SWITCH IN PANEL P1B SECTION 2 USING 3#3 AND 1#8GND IN 1-1/4" C. PROVIDE 3-100AMP FUSES COMPATIBLE WITH SQUARE D CAT. NO. QMB324W FUSIBLE SWITCH. TAP CONDUCTORS FROM NEW CWP-1 FEED TO REDUNDANT CWP-2 DISCONNECT.
4. CONNECT TO MANUFACTURER PROVIDED STARTER. CIRCUIT TO EXISTING SPARE 30A/3P FUSIBLE SWITCH IN PANEL P1B SECTION 2 USING 3#12 AND 1#12GND IN 3/4" C. PROVIDE 2-15AMP FUSES COMPATIBLE WITH SQUARE D CAT. NO. QMB321TW FUSIBLE SWITCH.
5. REFER TO ONE-LINE DIAGRAM ON SHEET E600.6. ROUTE 3#12 AND 1#12GND IN 3/4" C. TO RELIEF
EXHAUST FAN REF-2 ON 2ND FLOOR ROOF. REFER TO SHEET EP104N FOR CONTINUATION.
7. ROUTE 3#12 AND 1#12GND IN 3/4" C. TO EXHAUST FAN EF-2 ON 1ST FLOOR ROOF. REFER TO SHEET EP102N FOR CONTINUATION.
8. ROUTE 3#12 AND 1#12GND IN 3/4" C. TO RELIEF EXHAUST FAN REF-1 ON 2ND FLOOR ROOF. REFER TO SHEET EP104N FOR CONTINUATION.
#
No. Description Date
2 ADDENDUM 2 12/14/2017
E
J
J
JJ
E
J
J
J
J
A B C D E F G H J K
1
2
3
4
5
6
7
8
9
10
11
10.5
REF-2, EXHAUST FAN, 480V,3PH, 15HP
EXISTING FLOOD LIGHT
EXISTING FLOOD LIGHT
EXISTING FLOOD LIGHTEXISTING FLOOD LIGHT
EXISTING FLOOD
LIGHT
2
1
REF-1, EXHAUST FAN, 480V,3PH, 20HP
2
EXISTING TOWER
FLOOD LIGHT
EXISTING
TOWER FLOOD
LIGHT
EXISTING FLOOD LIGHT
3
3 3 3
3
3
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
71
0:2
2:0
3 A
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
290
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_sh
olla
12
. rvt
16253
ERIPER
ROOF PLAN - NORTH WING -ELECTRICAL - POWER
EP104N
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
NO R
HT
1/8" = 1'-0"1ROOF PLAN - NORTH WING - ELECTRICAL - POWER
GENERAL SHEET NOTES :
1. REFER TO SHEET E000 FOR GENERAL ELECTRICAL NOTES, ELECTRICAL RENOVATION NOTES AND ELECTRICAL INSTALLATION.
2. ALL CONDUIT AND WIRING TO BE DEMOLISHED SHALL BE REMOVED FROM ITS DEVICE TO ITS SOURCE.
3. COORDINATE WITH OWNER PRIOR TO DISPOSAL OF ANY EQUIPMENT. COORDINATE ALL EQUIPMENT TO BE SAVAGED WITH OWNER.
4. COORDINATE DOWN TIME WITH OWNER.
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
KEYNOTES:
1. RE-CIRCUIT EXISTING ROOF LIGHTING TO ATTIC PANEL CIRCUITS 2,3,4 AND 5. USING 1" C. REFER TO PANEL SCHEDULES ON SHEET E700 FOR WIRING REQUIREMENTS. REFER TO ELECTRICAL EL LIGHTING PLANS FOR LIGHTING CONTROL REQUIREMENTS. RE-USE EXISTING JUNCTION BOXES AND CONDUIT AS INSTALLATION ALLOWS.
2. CONNECT TO MANUFACTURER PROVIDED DISCONNECT. ROUTE CONDUIT AND CONDUCTORS TO VFD IN ATTIC. REFER TO SHEET EP103N FOR CONTINUATION. PROVIDE CONTROL WIRING TO INTERLOCK MANUFACTURER PROVIDED DISCONNECT WITH VFD.
3. SHALL BE RE-INSTALLED UPON COMPLETION OF ROOF REPLACEMENT. PROVIDE NEW CONDUIT AND CONDUCTORS AS REQUIRED TO COMPLETE INSTALLATION.
#
No. Description Date
2 ADDENDUM 2 12/14/2017
2
TRANSFORMER SCHEDULETYPE: REMARKS:
TP1 - NEMA TP 1 DRY TYPE AUT - AUTOTRANSFORMER AL - ALUMINUM WINDINGS
K4 - K4 RATED TP 1 DRY TYPE BB - BUCK-BOOST CP - COPPER WINDINGS
K13 - K13 RATED TP 1 DRY TYPE LIQ - LIQUID FILLED RS - EPOXY RESIN ENCAPSULATED
PE - NEMA PREMIUM EFFICIENCY FL - FILTERED
HM - HARMONIC MITIGATING TP 1 NV - NON-VENTILATED
NL - 200% RATED NEUTRAL
EL - ELECTROSTATIC SHIELD
ENCLOSURE: NEMA 1 UNLESS SPECIFIED OTHERWISE
MAX.TEMP.RISE C.
KVARATING
PRIMARY SECONDARY TAPS
ITEM TYPE VOLTS PH VOLTS PH % REG #(+) #(-) REMARKS APPROVED MANUFACTURERS
TR-15 15 TP-1 150 480 3 208Y/120
3 2.5 2 4 AL SQUARE D 7400 EE15T3HCUTLER-HAMMER TYPE DT-3GENERAL ELECTRIC TYPE QL
TR-112 112.5 BB 115 208 3 480Y/277
3 2.5 2 4 AL SQUARE DCUTLER-HAMMERGENERAL ELECTRIC
TR-150 150 BB 115 208 3 480Y/277
3 2.5 2 4 AL SQUARE DCUTLER-HAMMERGENERAL ELECTRIC
DTR-1000 1000 LIQ 13,800 3 208Y/120
3 REFER TO SPECIFICATION SECTION33 73 13
DISTRIBUTION PANEL: DP/AT1 CONNECTED 106.3 KVA
TYPE: BOLT-ON MAIN: 200A/3P CB
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 480Y / 277
FED FROM: 200A FEEDER VIA TR-112 VIA 400A OCP GROUND BUS PHASE: 3
K SCCR: 42,000 WIRE: 4 K
E NOTES: E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
1 EXHAUST FAN EF-2 2HP 12 2.7 20 3 150 3 61.3 1 AHU-1 60HP 2
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
3 SPARE 20 3 60 3 21.5 4 RELIEF EXHAUST FAN REF-1 20HP 4
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
5 SPARE 15 3 20 3 1.7 12 EXHAUST FAN EF-1 1HP 6
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
7 HEATING WATER PUMP HWP-2 5HP(REDUNDANT)
12 20 3 20 3 6.1 12 HEATING WATER PUMP HWP-1 5HP 8
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
9 SPACE 3 3 SPACE 10
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
11 SPACE 3 3 SPACE 12
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
13 SPACE 3 35 3 13 PANEL ATTIC VIA TR-15 14 *O
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
KEY: *G=GROUND FAULT INTERRUPT *H=LOCK ON *C=THRU CONTACTOR *I=ISOLATED GROUND *S=SHUNT TRIP *P=PADLOCK HASP *D=HID LIGHTING *M=BRANCH CIRCUIT MONITOR *O=REFER TO ONE-LINE DIAGRAM
DISTRIBUTION PANEL: DP/AT2 CONNECTED 120.3 KVA
TYPE: BOLT-ON MAIN: 225A/3P CB
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 480Y / 277
FED FROM: 225A FEEDER VIA TR-150 VIA 500A OCP GROUND BUS PHASE: 3
K SCCR: 42,000 WIRE: 4 K
E NOTES: E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
1 ELEVATOR 50HP 3 51.8 100 3 125 3 51.8 3 AHU-2 50HP 2
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
3 SPARE 20 3 20 3 SPARE 4
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
5 RELIEF EXHAUST FAN REF-2 15HP 6 16.7 45 3 20 3 SPARE 6
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
7 SPACE 3 3 SPACE 8
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
9 SPACE 3 3 SPACE 10
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
11 SPACE 3 3 SPACE 12
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
13 SPACE 3 3 SPACE 14
------ -- -- -- -- -- -- -- -- ------
------ -- -- -- -- -- -- -- -- ------
KEY: *G=GROUND FAULT INTERRUPT *H=LOCK ON *C=THRU CONTACTOR *I=ISOLATED GROUND *S=SHUNT TRIP *P=PADLOCK HASP *D=HID LIGHTING *M=BRANCH CIRCUIT MONITOR
PANEL NAME: L2EAST CONNECTED 27.6 KVA
TYPE: BOLT-ON MAIN: 125A/3P CB
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 208Y / 120
FED FROM: EXISTING 200A FEEDER GROUND BUS PHASE: 3
K SCCR: 10,000 WIRE: 4 K
E NOTES: E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
1 LTG - CN202,CN204,N221, N222 12 0.8 20 1 20 1 1.0 12 2 VAV POWER SUPPLIES 2
3 LTG - CENTER 12 0.7 20 1 20 1 SPARE 4
5 LTG - N214A 12 0.9 20 1 20 1 1.0 12 4 MONITOR RECEPTS 6
7 LTG - N214B 12 0.8 20 1 20 1 0.6 12 3 PRE-FUNCTION RECEPTS 8
9 LTG - 214C 12 0.9 20 1 30 1 0.2 10 1 IT RECEPT 10
11 LT G- N214D, N214E 12 0.3 20 1 20 1 0.4 12 2 IT RECEPT 12
13 2 AV RACK RECEPT 12 0.4 20 1 20 1 0.4 12 2 IT RECEPT 14
15 2 AV RACK RECEPT 12 0.4 20 1 20 1 1.0 12 5 CORR, JANITOR, ELEC RM RECEPTS 16
17 1 CATERING RECEPT 12 0.2 20 1 20 1 0.8 12 4 CATERING, STORAGE RM RECEPTS 18
19 1 CATERING RECEPT 12 0.2 20 1 20 1 1.0 10 5 CORR RECEPTS 20
21 5 MTG RM 9 RECEPTS 10 1.0 20 1 20 1 1.0 12 5 MTG RM 8 RECEPTS 22
23 4 MTG RM 7 RECEPTS 10 0.8 20 1 20 1 0.6 12 3 MTG RM 7 RECEPTS 24
25 MTG RM 7 PROJECTION SCREEN,PROJECTOR
10 1.0 20 1 20 1 1.0 12 MTG RM 6 PROJECTION SCREEN,PROJECTOR
26
27 4 MTG RM 6 RECEPTS 12 0.8 20 1 20 1 0.8 12 4 MTG RM 6 RECEPTS 28
29 5 MTG RM 5 RECEPTS 12 1.0 20 1 20 1 1.0 12 5 MTG RM 5 RECEPTS 30
31 MTG RM 7 PROJECTION SCREEN,PROJECTOR
10 1.0 20 1 20 1 0.4 12 2 MTG RM 5, CORR RECEPTS 32
33 1 MTG RM 5 RECEPTS 12 0.2 20 1 20 1 1.0 12 SHADE CONTROLLER 34
35 SPARE 20 1 20 1 1.0 12 SHADE CONTROLLER 36
37 SPARE 20 1 20 1 1.0 12 SHADE CONTROLLER 38
39 SPARE 20 1 20 1 1.0 12 SHADE CONTROLLER 40
41 SPARE 20 1 20 1 1.0 12 SHADE CONTROLLER 42
KEY: *G=GROUND FAULT INTERRUPT *H=LOCK ON *C=THRU CONTACTOR *I=ISOLATED GROUND *S=SHUNT TRIP *P=PADLOCK HASP *D=HID LIGHTING *M=BRANCH CIRCUIT MONITOR
PANEL NAME: L2WEST CONNECTED 31.1 KVA
TYPE: BOLT-ON MAIN: 125A/3P CB
MOUNTING: RECESSED SOLID NEUTRAL VOLTS: 208Y / 120
FED FROM: EXISTING 200A FEEDER GROUND BUS PHASE: 3
K SCCR: 10,000 WIRE: 4 K
E NOTES: E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
1 LTG - N201A 12 0.9 20 1 20 1 0.5 12 FA - POWER SUPPLY N234 2
3 LTG - N201B 12 0.9 20 1 20 1 0.8 10 4 MTG RM 1 RECEPTS 4
5 LTG - N201C 12 0.8 20 1 20 1 0.8 10 4 MTG RM 1 RECEPTS 6
7 LTG - N204, N205 12 0.8 20 1 20 1 1.0 10 MTG RM 1 PROJECTION SCREEN,PROJECTOR
8
9 LTG - CN200, N247 12 0.7 20 1 20 1 0.6 12 3 MTG RM 2 RECEPTS 10
11 MTG RM 4 PROJECTION SCREEN,PROJECTOR
12 1.0 20 1 20 1 0.8 12 4 MTG RM 2 RECEPTS 12
13 3 MTG RM 4 RECEPTS 12 0.6 20 1 20 1 1.0 12 MTG RM 2 PROJECTION SCREEN,PROJECTOR
14
15 2 MTG RM 4 RECEPTS 12 0.4 20 1 20 1 0.6 12 3 MTG RM 3 RECEPTS 16
17 3 STOR RM RECEPTS 12 0.6 20 1 20 1 0.8 12 4 MTG RM 3 RECEPTS 18
19 6 CORRIDOR RECEPTS 10 1.2 20 1 20 1 1.0 12 MTG RM 3 PROJECTION SCREEN,PROJECTOR
20
21 4 CORR, REST RM RECEPTS 12 0.8 20 1 20 1 1.6 12 HAND DRYER 22 *P
23 ELECTRIC WATER COOLER EWC-1 12 1.0 20 1 20 1 1.6 12 HAND DRYER 24 *P
25 SHADE CONTROLLER 12 1.8 20 1 20 1 1.6 12 HAND DRYER 26 *P
27 SHADE CONTROLLER 12 1.8 20 1 20 1 1.6 12 HAND DRYER 28 *P
29 SHADE CONTROLLER 12 1.8 20 1 20 1 SPARE 30
31 SHADE CONTROLLER 12 1.8 20 1 20 1 SPARE 32
33 SPARE 20 1 20 1 SPARE 34
35 SPARE 20 1 20 1 SPARE 36
37 SPARE 20 1 20 1 SPARE 38
39 SPARE 20 1 20 1 SPARE 40
41 SPARE 20 1 20 1 SPARE 42
KEY: *G=GROUND FAULT INTERRUPT *H=LOCK ON *C=THRU CONTACTOR *I=ISOLATED GROUND *S=SHUNT TRIP *P=PADLOCK HASP *D=HID LIGHTING *M=BRANCH CIRCUIT MONITOR
PANEL NAME: ATTIC CONNECTED 13.0 KVA
TYPE: BOLT-ON MAIN: 60A/3P CB
MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 208Y / 120
FED FROM: (DP/AT1)-14 GROUND BUS PHASE: 3
K SCCR: 10,000 WIRE: 4 K
E NOTES: E
Y CKT WIRE LOAD BREAKER BREAKER LOAD WIRE CKT Y
* NO. LOAD DESCRIPTION SIZE KVA AMP P AMP P KVA SIZE LOAD DESCRIPTION NO. *
1 ATTIC LIGHTING 12 0.2 20 1 20 2 0.8 10 FLOOD LIGHTING 2
3 TOWER FLOOD LIGHTING 10 1.0 20 1 -- -- -- -- ------ 4
5 TOWER FLOOD LIGHTING 10 1.0 20 1 20 2 0.8 10 FLOOD LIGHTING 6
7 LIGHTING CONTACTOR 12 0.1 20 1 -- -- -- -- ------ 8
9 HEATING WATER PUMP HWP-3 0.25HP 12 0.67 20 1 20 1 0.7 12 HEATING WATER PUMP HWP-4 0.25HP 10
11 AHU-1 ACCESSORIES 12 1.0 20 1 20 1 1.0 12 AHU-2 ACCESSORIES 12
13 CONDENSING UNIT CU-1 12 2.8 20 2 20 2 0.2 12 SPLIT SYSTEM SSU-1 14
15 ------ -- -- -- -- -- -- -- -- ------ 16
17 UNIT HEATER UH-1 12 0.8 20 1 20 1 0.2 12 UNIT HEATER UH-2 18 *P
19 7 ATTIC RECEPTS 10 1.4 20 1 20 1 0.1 10 ELEV LIGHTING 20
21 BAS PANEL 12 0.1 20 1 20 1 0.2 10 ELEV RECEPT 22
23 24
25 26
27 28
29 30
31 32
33 34
35 36
37 38
39 40
41 42
KEY: *G=GROUND FAULT INTERRUPT *H=LOCK ON *C=THRU CONTACTOR *I=ISOLATED GROUND *S=SHUNT TRIP *P=PADLOCK HASP *D=HID LIGHTING *M=BRANCH CIRCUIT MONITORVARIABLE FREQUENCY DRIVE SCHEDULE
STARTER TYPE: REMARKS:
PWM - PULSE WIDTH MODULATED SA - STANDARD ACCESSORIES TA - TWO CONVERTIBLE AUXILIARY CONTACTS
12PWM- 12 PULSE PWM (INCLUDES * ITEMS) ISO - ISOLATION TRANSFORMER
18PWM- 18 PULSE PWM *MA - MANUAL SPEED ADJUSTMENT *SHZ - SKIP FREQUENCY CAPABILITY
LINE DISCONNECT *ET - ELECTRONIC THERMAL OVERLOADS RSS - REMOTE START-STOP
EDS - EXTERNAL DISCONNECT SWITCH *CT - CONTROL TRANSFORMER, FUSED,120V
RDR - REMOTE DRIVE RUN
FDS - FUSIBLE DISCONNECT SWITCH RFT - REMOTE FAULT TRIP
CB - CIRCUIT BREAKER *HA - HAND-OFF-AUTO DOOR SWITCH LR - INPUT LINE REACTOR
CONTROL: TO - MELTING THERMAL OVERLOADS HAR - PASSIVE HARMONIC FILTER
PN - 3-15 PSI PRESSURE TRANSDUCER MOL - MULTIPLE MOTOR OVERLOADS
420 - 4-20mA FOLLOWER INPUT
VOLTAGE DRIVE
ITEM
LINEDISC.
DRIVEBYPASS CONTROL INPUT OUTPUT PH.
H.P.RATING TYPE
NEMAENCLOSURE REMARKS APPROVED MANUFACTURERS
VFD-5 EDS N/A 420 460 460 3 5 PWM 1 SA' 'LR'VARIABLETORQUE
TOSHIBA Q9 SERIES
ABB ACH 550 SERIES
YASKAWA Z1000
VFD-15 EDS N/A 420 460 460 3 15 PWM 1 SA' 'LR'VARIABLETORQUE
TOSHIBA Q9 SERIES
ABB ACH 550 SERIES
YASKAWA Z1000
VFD-20 EDS N/A 420 460 460 3 20 PWM 1 SA' 'LR'VARIABLETORQUE
TOSHIBA Q9 SERIES
ABB ACH 550 SERIES
YASKAWA Z1000
VFD-50 EDS N/A 420 460 460 3 50 PWM 1 SA' 'LR'VARIABLETORQUE
TOSHIBA Q9 SERIES
ABB ACH 550 SERIES
YASKAWA Z1000
VFD-60 EDS N/A 420 460 460 3 60 PWM 1 SA' 'LR'VARIABLETORQUE
TOSHIBA Q9 SERIES
ABB ACH SERIES
YASKAWA Z1000
NOTE: REFER TO VFD MOUNTING DETAILS 6/E.500 AND 9/E.500.
DISCONNECT AND STARTER SCHEDULEREMARKS:
STARTER TYPE: SA - STANDARD ACCESSORIES (INCLUDES * ITEMS)
FV - FULL VOLTAGE *CT - CONTROL TRANSFORMER,FUSED 120V
PF - PHASE FAILURE RELAY(5 HP OR GREATER) YD - WYE - DELTA
RE - REVERSING *EO - ELECTRONIC OVERLOAD TO - MELTING THERMAL OVERLOADS
TW - 2 SPEED, 2 WINDING *HA - HAND-OFF-AUTO IN DOOR TS - 2 SPEED SELECTOR SWITCH IN DOOR
SW - 2 SPEED, 1 WINDING *RP - RED (RUN) PILOT LIGHT INDOOR
GP - GREEN (OFF) PILOT LIGHT IN DOOR
RV - REDUCED VOLTAGE AUTOXFMR FA - 4-CONVERTIBLE AUXILIARY CONTACTS
SS - SOLID STATE *TA - TWO CONVERTIBLEAUXILIARY CONTACTS
EI - ELECTRICAL INTERLOCK (2)-N.O.& (2)-N.C
MD - MOTOR DISCONNECT SS - START-STOP PUSHBUTTON IN DOOR
MS - MANUAL STARTER S/N - INSULATED NEUTRALASSEMBLY
HL - HANDLE PADLOCK HASP
MX - MANUAL SWITCH
FS - FUSED SWITCH
DISCONNECT TYPE & RATING STARTER
ITEM FUSEDNON-
FUSEDCIRCUIT
BREAKER VOLTAGE POLESNEMASIZE TYPE
NEMAENCLOSURE REMARKS APPROVED MANUFACTURERS
DS-30 30A 600 3 1 SQUARE D 3110 HU361CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
DS-60 60A 600 3 1 SQUARE D 3110 HU362CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
DS-100 100A 600 3 1 SQUARE D 3110 HU363CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
DS-200 200A 600 3 1 SQUARE D 3110 HU364CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
FDS-30L 30A 120/240 2 1 S/NLIGHT DUTY,FUSED PERELEV MFRREQUIREMENT
SQUARE D 3130 L221NCUTLER-HAMMERGENERAL ELECTRIC
FDS-100 100A 240 3 1 FUSED AT 100AMPS
SQUARE D 3110 H323NCUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
FDS-200 200A 240 3 1 FUSED AT 175AMPS
SQUARE D 3110 H324NCUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
FDS-400 400A 240 3 1 FUSED AT 225AMPS
SQUARE D 3110 H325CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
FED-100 100A 600 3 1 ELEVATORSHUNT TRIP,CT, FUSEDPER ELEV MFRREQUIREMENT
BUSSMANN PS1T48R2MERSEN ES1T48R2CUTLER-HAMMER ES3T48R2LITTELFUSE LPS1T48R2
MX-1 120 1 MX 1 RP, 115 VOLTPILOT LIGHTCIRCUIT
SQUARE D 2510 KG1ACUTLER-HAMMER TYPE MSGENERAL ELECTRIC TYPE TC
S-1A 120 1 1 FV 1 TA, HA, TO, RP SQUARE D 8536 SCG1CUTLER-HAMMER CLASS ECNGENERAL ELECTRIC CR306
FCS-30 30A 480 3 1 FV 1 SA, FUSED AT6AMPS
SQUARE D 8538 SCG34CUTLER-HAMMER TYPE ECNGENERAL ELECTRIC CR308
EDS-100 100A 600 3 1 FUSEDPER ELEV MFRREQUIREMENT
SQUARE D 3110 H363CUTLER-HAMMER TYPE DHGENERAL ELECTRIC TYPE TH
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rred
Main
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
This drawing and details on it are the sole property of the architect and may be used for this specific project only. It shall not be loaned, copied or reproduced, in whole or part, or for any other purpose or project without the written consent of the architect.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
12/1
4/2
01
71
0:2
2:0
0 A
MC
:\R
evi
t Lo
ca
l F
iles\
ME
PT
17
_0
01
50
290
.01
_M
U M
em
ori
al S
tud
en
t U
nio
n_C
en
tra
l_sh
olla
12
. rvt
16253
ERIPER
ELECTRICAL SCHEDULES
E700
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
REFERENCE SCALE IN INCHES
0 1 2 3
Missouri State Certificate of Authority E-2017008530
PROJECT #
7381 WEST 133RD ST, SUITE 210OVERLAND PARK, KS 66213913.956.6636 FAX: 913.956.6670www.imegcorp.com
00150290.01
No. Description Date
2 ADDENDUM 2 12/14/2017
2
2
Project Number:
Drawn By:
Issue Date:
Sheet Number:
Sheet Title:
Project Title:
Professional Seal:
Project Team:
Se
co
nd
Flo
or
Re
no
vatio
ns a
nd
D
efe
rre
d M
ain
ten
an
ce
The Professional Architect's seal affixed to this sheet applies only to the material and items shown on this sheet. All drawings, instruments or other documents not exhibiting this seal shall not be considered prepared by this architect, and this architect expressly disclaims any and all responsibility for such plans, drawings or documents not exhibiting this seal.
Office:
Austin Carolinas New York St. Louis
pf
Civil Engineer Civil Design, Inc.1552 South 7th StreetSt. Louis, MO 63104314-880-4427
MU
Pro
ject
#C
P1
51
70
1
MONICA S. SANTOS - ELECTRICAL
MO# E2000174546
Antella Consulting Engineers, inc. - EngineerMissouri Certificate of Authority #: E-2005013590
1600 Genessee, Suite 260 Tele 816-421-0950Kansas City, Missouri 64102email: [email protected]
12/1
4/2
017
11
:57
:48
AM
C:\
Use
rs\M
on
ica
.Sa
nto
s\D
ocu
me
nts
\A2
15
-15
ELE
C v
17
_m
on
ica
.san
tos.r
v t
16253
BPA, SAM
LIGHTING SCHEDULES
EL801
518
Hitt
Str
eet,
Co
lum
bia
, M
O
Mem
orial S
tud
en
t U
nio
n
11.16.17
319 N. 4th Street
St. Louis, MO 63102314-231-5700314-231-0816
Antella Consulting Engineers, Inc1600 Genesee Street, Suite 260Kansas City, MO 64102816-421-0950
IMEG Corp.7381 W. 133rd St., Suite 210Overland Park, KS 66213913-956-6636913-956-6670
KPFF Consulting Engineers1610 Des Peres Road, Suite 100St. Louis, MO 63131314-835-0524314-835-0749
StructuralEngineer
MPFP Engineer
ElectricalEngineer
Suite 1000
LG
A2.5
LUMINAIRE SCHEDULETYPE MOUNTING LAMPS LUMENS
COLORTEMP.
CRI WATTS VOLTAGE MANUFACTURER DESCRIPTIONEQUALS EQUALS
A PENDANT LED 4400 lm 3500 K 90 52 120VISA - COSMOCP1325-L35K-H-MVOLT-90CRI-SNA-14OR PRE-APPROVED EQUAL
34" SUSPENDED BOWL3-5/8" TALL1% - 100% DIMMING DRIVER
B RECESSED LED 1000 lm 3500 K 90 11 120EATON - PORTFOLIOLD4B-10-DE010-EU4B-1020-90-35-4LB-M-2-H-HB26OR PRE-APPROVED EQUAL
4" RECESSED CYLINDER DOWNLIGHT5-1/2" TALL1% - 100% DIMMING DRIVER
PHILIPS LIGHTOLIER - CALCULITE LED GEN 3C4-R-N; C4L-10-835-M-Z10-U; C4-R-DL-CD
GOTHAM - EVO LEDEVO-35/10-4AR-MD-LD-MVOLT-EZ1-TRW
D WALL LED 1500 lm 3500 K 80 14 120VISA - WEDGECB6471-L35K-MVOLT-L35K-MED-SNAOR PRE-APPROVED EQUAL
BIDIRECTIONAL WALL SCONCE18-3/4" TALL0-10V DIMMING
EF6RECESSEDHARD CEILING
LED 430 lm 3500 K 80 24 120PRUDENTIAL - STREAMSTR4-LED35-LO-6'-TMW-D1-SC-UNV-X3-DM10OR PRE-APPROVED EQUAL
6' RECESSED LINEAR STRIP4-5/8" TALL0-10V DIMMINGLUMENS LISTED ARE /FT VALUES
LUMENWERX - CAVA LEDCAVR-RLO-LED-80-500-35-6FT-UNV-D1-1-DTR-W
EF8RECESSEDHARD CEILING
LED 430 lm 3500 K 80 32 120PRUDENTIAL - STREAMSTR4-LED35-LO-8'-TMW-D1-SC-UNV-X3-DM10OR PRE-APPROVED EQUAL
8' RECESSED LINEAR STRIP4-5/8" TALL0-10V DIMMINGLUMENS LISTED ARE /FT VALUES
LUMENWERX - CAVA LEDCAVR-RLO-LED-80-500-35-8FT-UNV-D1-1-DTR-W
EG6RECESSEDGRID
LED 430 lm 3500 K 80 24 120PRUDENTIAL - STREAMSTR4-LED35-LO-6'-TMW-D1-SC-UNV-X1M-DM10OR PRE-APPROVED EQUAL
6' RECESSED LINEAR STRIP4-5/8" TALL0-10V DIMMINGLUMENS LISTED ARE /FT VALUESCONFIRM CEILING TYPE WITH ARCHITECTPRIOR TO ORDERING
LUMENWERX - CAVA LEDCAVR-RLO-LED-80-500-35-6FT-UNV-D1-1-TB9-W
EG8RECESSEDGRID
LED 430 lm 3500 K 80 32 120PRUDENTIAL - STREAMSTR4-LED35-LO-8'-TMW-D1-SC-UNV-X1M-DM10OR PRE-APPROVED EQUAL
8' RECESSED LINEAR STRIP4-5/8" TALL0-10V DIMMINGLUMENS LISTED ARE /FT VALUESCONFIRM CEILING TYPE WITH ARCHITECTPRIOR TO ORDERING
LUMENWERX - CAVA LEDCAVR-RLO-LED-80-500-35-8FT-UNV-D1-1-TB9-W
EG12RECESSEDGRID
LED 430 lm 3500 K 80 48 120PRUDENTIAL - STREAMSTR4-LED35-LO-R12'-TMW-D1-SC-UNV-X1M-DM10OR PRE-APPROVED EQUAL
12' RECESSED LINEAR STRIP4-5/8" TALL0-10V DIMMINGLUMENS LISTED ARE /FT VALUESCONFIRM CEILING TYPE WITH ARCHITECTPRIOR TO ORDERING
LUMENWERX - CAVA LEDCAVR-RLO-LED-80-500-35-12FT-UNV-D1-1-TB9-W
F PENDANT LED 5500 lm 3500 K 80 44 120H. E. WILLIAMS - 75 LED75S-4-L40/835-DRV-UNVOR PRE-APPROVED EQUAL
4' SUSPENDED LINEAR STRIP3" TALL
DAY-BRITE - FLUXSTREAMFSW-4-55L-835-U-NV-DIM
LITHONIA - CLX LEDCLX-L47-7000LM-SEF-FDL-MVOLT-GZ10-35K-80CRI-WH
G RECESSED LED 3000 lm 3500 K 80 33 120H. E. WILLIAMS - HETHET-G-S-1-4-L30/835-A-DIM-UNVOR PRE-APPROVED EQUAL
4' RECESSED LINEAR STRIP3-5/8" TALL0-10V DIMMING
METALUX - 14CZ LED14CZ-LD5-29-UNV-835-CD-1
LITHONIA -VTL4 LEDVTL4-30L-ADP-EZB-LP835
H RECESSED LED 1000 lm 3500 K 80 14 120EATON - HALOPD6-10-ED010-PDM6A-835-61V-HOR PRE-APPROVED EQUAL
6" RECESSED CYLINDER DOWNLIGHT7" TALL0-10V DIMMING
LITHONIA - LDN6LDN6-35/10-LO6-AR-LD-MVOLT-EZ10
J WALL LED 1100 lm 3500 K 80 10 120VISA - POSHCB5518-L35K-L-MVOLT-SNAOR PRE-APPROVED EQUAL
LINEAR WALL SCONCE27-3/4" LONG
K SURFACE LED 4000 lm 3500 K 82 40 120HE WILLIAMS - 96 LED96-4-L40-835-HIAFR-DRV-277OR PRE-APPROVED EQUAL
4' SURFACE MOUNT LINEAR STRIP4-1/8" TALLFULL ENCLOSED & GASKETED INDUSTRIAL
METALUX - VAPORTITE LED4VT2-LD4-4-DR100-W-UNV-L835-CD1-WL-U
LITHONIA - FEM LEDFEM-L48-4000LM-IMAFL-MD-MVOLT-GZ10-35K-80CRI
L WALL LED 5611 lm 3000 K 70 58 120EATON - XTOR CROSSTOUR MAXX LEDXTOR6B-Y-BK-MS-L20OR PRE-APPROVED EQUAL
WALL-MOUNTED AREA LIGHT11" TALLINTEGRAL MOTION SENSOR
XA WALL/CEILING LED 3 120PHILIPS - 44RER44RLDU-1-RMOR PRE-APPROVED EQUAL
UNIVERSAL EDGE-LIT LED EXIT SIGNSINGLE FACEINTEGRAL BATTERYSELF-DIAGNOSTICSAPPLY ARROWS IN QUANTITY AND DIRECTIONAS NOTED ON DRAWINGS
LITHONIA - EDGEDG-1-RMR-EL-SD
XB WALL/CEILING LED 3 120PHILIPS - 44RER44RLDU-2-RMOR PRE-APPROVED EQUAL
UNIVERSAL EDGE-LIT LED EXIT SIGNDOUBLE FACEINTEGRAL BATTERYSELF-DIAGNOSTICSAPPLY ARROWS IN QUANTITY AND DIRECTIONAS NOTED ON DRAWINGS
LITHONIA - EDGEDG-2-RMR-EL-SD
XC WALL/CEILING LED 1092 lm 12 120DUAL-LITE - EVHCEVHC-12-I-06LOR PRE-APPROVED EQUAL
THERMOPLASTIC LED EMERGENCY LIGHTHIGH MOUNTING APPLICATIONSINTEGRAL BATTERY, 6W HEADSSELF-DIAGNOSTICS
PHILIPS - CHLORIDETPU-D-N-LM7-W-ICT
XD WALL/CEILING LED 290 lm 4 120DUAL-LITE - EV SERIESEV-4-I-02LOR PRE-APPROVED EQUAL
THERMOPLASTIC LED EMERGENCY LIGHTARCHITECTURAL APPLICATIONSINTEGRAL BATTERY, 2W HEADSSELF-DIAGNOSTICS
PHILIPS - CHLORIDETPU-D-N-LM5-W-ICT
NOTES:1) PRE-APPROVAL FOR EQUALS MUST BE SUBMITTED PRIOR TO BIDS PER THE FRONT END DOCUMENTATION. SUBSTITUTIONS WILL NOT BE ENTERTAINED POST BIDS.2) CONTRACTOR SHALL SUBMIT INDIVIDUAL PRICING. LOT PRICING WILL NOT BE ACCEPTED.3) CONTRACTOR SHALL COORDINATE ALL LUMINAIRES WITH THE CEILINGS THEY ARE TO BE MOUNTED IN. PROVIDE ALL MATERIAL AND EQUAL AS REQUIRED TO MOUNT IN THE CEILING TYPE WHERE SHOWN.REFER TO ARCHITECTURAL PLANS FOR CEILING TYPES.4) LIGHT FIXTURE VOLTAGES SHALL MATCH THE CIRCUIT VOLTAGE AS SHOWN PER PLANS.
LIGHTING CONTROL DEVICE SCHEDULETYPE MOUNTING DESCRIPTION MANUFACTURER MODEL COVERAGE COLOR
L1 WALL DIGITAL LIGHTING MANAGEMENT SYSTEM(DLM) SWITCHLOW VOLTAGE PUSHBUTTON SWITCHONE BUTTON SWITCH
WATTSTOPPER LMSW-101 - COORDINATE FINALCOLOR WITHDEVICE COLORAS SELECTED BYARCHITECT
L5 WALL DIGITAL LIGHTING MANAGEMENT SYSTEM(DLM) SWITCHLOW VOLTAGE PUSHBUTTON SWITCHFIVE BUTTON SWITCH
WATTSTOPPER LMSW-105 - COORDINATE FINALCOLOR WITHDEVICE COLORAS SELECTED BYARCHITECT
LD WALL DIGITAL LIGHTING MANAGEMENT SYSTEM(DLM) SWITCHLOW VOLTAGE PUSHBUTTON SWITCH
WATTSTOPPER LMDM-101 - COORDINATE FINALCOLOR WITHDEVICE COLORAS SELECTED BYARCHITECT
MS WALL PASSIVE INFRARED LOW VOLTAGE WALL SWITCH OCCUPANCY SENSORWITH ISOLATED RELAY AND INTELLIGENT TECHNOLOGYSTAND ALONE, NOT PART OF DLMPROVIDE WITH DUAL VOLTAGE POWER PACKHOLD OFF AND HOLD ON FUNCTION
WATTSTOPPER PW-100-24
BZ-100
- COORDINATE FINALCOLOR WITHDEVICE COLORAS SELECTED BYARCHITECT
MS(1) CEILING DUAL TECHNOLOGY ULTRASONIC ANDPASSIVE INFRARED CEILING SENSORIT IS A DIGITAL SENSOR PART OF DIGITALLIGHTING MANAGEMENT SYSTEM (DLM)BY WATTSTOPPER
WATTSTOPPER LMDC-100 1000 SQFT WHITE
PS CEILING MULTI-ZONE DAYLIGHT PHOTOSENSOROPEN LOOP WITH CONTINUOUS DIMMINGCOMPONENT OF DIGITAL LIGHTING MANAGEMENT INTEGRATED CONTROLSYSTEM
WATTSTOPPER LMLS-500 WHITE
RC ABOVE ACCESSIBLECEILING
PLENUM RATED CONTROLLER WITH LINE VOLTAGE RELAYAND SWITCHING POWER SUPPLYCOMPONENT OF DIGITAL LIGHTING MANAGEMENTINTEGRATED CONTROL SYSTEM PLUG TO COMPONENTSWITH CAT 5E CABLES WITH RJ45 CONNECTORSPROVIDE WITH ISOLATED RELAY INTERFACE FOR HVAC CONTROL(PROVIDE ONE PER ROOM)
(SEE NOTE BELOW)
WATTSTOPPER LMRC-101LMRC-102
LMRL-100
- -
RC(D) ABOVE ACCESSIBLECEILING
PLENUM RATED CONTROLLER WITH LINE VOLTAGE RELAY(S)AND ON/OFF/0-10 VOLT DIMMING POWER SUPPLYCOMPONENT OF DIGITAL LIGHTING MANAGEMENTINTEGRATED CONTROL SYSTEMCONNECT TO COMPONENTS WITH CAT 5E CABLES WITH RJ45 CONNECTORSPROVIDE WITH ISOLATED RELAY INTERFACE FOR HVAC CONTROL (PROVIDEONE PER ROOM)
(SEE NOTE BELOW)
WATTSTOPPER LMRC-211LMRC-212LMRC-213
LMRL-100
- -
TS WALL TIMER SWITCHSTAND ALONE, NOT PART OF DLMTIME-OUT ADJUSTMENTS FROM 5 MIN TO 12 HOURS
WATTSTOPPER TS-400 - COORDINATE FINALCOLOR WITHDEVICE COLORAS SELECTED BYARCHITECT
NOTES:1) PROVIDE REQUIRED NUMBER OF ROOM CONTROLLERS AND RELAYS TO ACCOUNT FOR THE PROPER SWITCHING CONFIGURATION OF LOADS. ONLY ONE SYMBOL IS SHOWN IN PLAN FOR CLARITY.2) CABLING USED TO INTER-CONNECT DLM SYSTEM DEVICES TO BE WHITE (OR PRE-APPROVED COLOR BY OWNER). ALL CABLING TO BE OF SAME COLOR. MULTIPLE COLORS SHALL NOT BE PERMITTED REGARDLESS OF LENGTHS. (GREEN AND YELLOW ARE RESERVED FOR TELECOME WIRING AND NOT TO BE USED FOR LIGHTING CONTROL WIRING)3) PROGRAM ALL MOTION SENSORS TO BE OCCUPANCY SENSORS. THEY ARE TO TURN LIGHTS ON AUTOMATICALLY AND SHUT OFF WITHIN 30 MINUTES OF AN OCCUPANT LEAVING THE SPACE.4) WATTSTOPPER IS A BASIS OF DESIGN. CONTRACTOR SHALL SUBMIT ANY EQUALS PRIOR TO BID FOR PRE-APPROVAL PER FRONT END DOCUMENTS. SUBSTITIONS WILL NOT BE ENTERTAINED POST BIDS.
No. Description Date
2 ADDENDUM 2 12/14/2017
2