pah f 20 -40 firefighting pumps data sheet · 10.1 vrhf 100 relief valve ... the danfoss range of...
TRANSCRIPT
danfoss.high-pressurepumps.com
Data sheet
PAHF 20/25/32/40 pumpsfor fire fighting
Data sheet
PAH F pumps for firefighting PAH F 20 / PAH F 25 / PAH F 32 / PAH F 40
hpp.danfoss.com.
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
2 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
Contents
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2. Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3. Application examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
4. Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44.1 PAH F 20-40. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
5. Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55.1 PAH F 20 – 40 typical flow curves at max pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
6. Motor requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
7. Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67.1 Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77.2 Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77.3 Open-system design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77.4 Closed-system design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8. Dimensions and connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98.1 PAH F 20/25/32/40 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9. Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
10. Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1010.1 VRHF 100 Relief valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1010.2 VRHF 100 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1210.3 PAH F Adaptor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1310.4 Adaptor Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
The Danfoss range of PAH F high-pressure pumps are especially designed for the high-pres-sure fire extinguishing industry. It is dedicated for the water mist market for both landbased and marine applications.Danfoss PAH F pumps are positive displacement pumps, with axial pistons that move a fixed amount of water in each cycle. Flow is propor-tional to the number of shaft revolutions (rpm). Unlike centrifugal pumps, they produce the same flow at a given speed independently of the discharge pressure.
1. Introduction
Table of Contents
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
3521B1113 | DKCFN.PD.010.A2.02 | 2017.10
2. Benefits • Zero risk of lubricant contamination: - Oil lubricants are replaced with the
pumped medium, water, so there is no contamination risk from the pump.
• Low maintenance costs: - Efficient design and all-stainless steel
construction ensure exceptionally long lifetime. Service intervals of up to 500 hours can be expected. Easy to service, can be carried out on site due to the simple design and few parts.
• Low energy costs: - The highly efficient axial piston design
provides the lowest energy consump-tion of any comparable pump in the market.
• Easy installation: - The lightest and most compact design
available.
- Pump can be installed horizontally or vertically.
- No pulsation dampeners needed due to low pressure pulsation.
- Can be powered by electric motors or reciprocating engines.
- Suitable for both boosted inlet pressure and water supply from a tank.
- No need for cooling circuits due to very high mechanical efficiency.
• Certified quality: Certificates:
ISO 9001, follows TS 16949 quality standards.
ATEX available on request
Below sectional drawing is an example of a PAH F pump.
3. Application examples The PAH F pumps can be used in both landbased and marine segments within the high-pressure water mist fire fighting market.High-pressure water mist prevents flooding and water damage. Furthermore it is the most efficient fire extinguish method known today.
Fire fighting within marine applications:• Engine room protection• Accommodations• Local area• Car deck• etc.
Fire fighting within land applications:• Airports• Hotels• Garages• Tunnels• Offices• Schools• etc.
1: Shaft sealing2: Mounting flange3: Retaining ring4: Piston/shoe5: Valve trust plate6: Swash plate with bearing7: Cylinder barrel8: Spring9: Port plate10: Connecting flange with bearing
1
2 10 34
6
9
5
7 8
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
4 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
4. Technical data 4.1 PAH F 20-40
Pump size 20 25 32 40
Code number 180B0092 180B0093 180B0094 180B0095
Housing material AISI 304 AISI 304 AISI 304 AISI 304
Geometric displacement
cm³/rev 20 25 32 40
in³/rev 1.2 1.5 1.9 2.4
Pressure
Min. outlet pressure
barg 30 30 30 30
psig 435 435 435 435
Max. outlet pressure
barg 160 160 160 160
psig 2,320 2,320 2,320 2,320
Inlet pressure, continuous1800 - 3600 RPM 2)
barg 1-6 1-6 1-6 1-6
psig 14.5-87 14.5-87 14.5-87 14.5-87
Inlet pressurecontinuous700 - 1800 RPM 2)
barg 0-6 0-6 0-6 0-6
psig 0-87 0-87 0-87 0-87
Max. inlet 1)
pressure, peakbarg 30 30 30 30
psig 435 435 435 435
Speed
BoostedMax. speed rpm 3600 3600 3600 3000
Tank supplyMax. speed
rpm 1800 1800 1800 1500
Min. speed rpm 700 700 700 700
Typical flow - Flow curves available in section 5
Typical motor size
1500 rpm at max. pressure
kW 11 15 15 18.5
1800 rpm at max. pressure
hp 15 20 25 30
Torque at max. spec.
Nm 56.6 69.2 89.0 110.0
lbf-ft 41.7 51.1 65.7 81.0
Media tempera-ture
°C 2-50 2-50 2-50 2-50
°F 37-122 37-122 37-122 37-122
Ambient temperature
°C 0-50 0-50 0-50 0-50
°F 32-122 32-122 32-122 32-122
Weight kg 15.6 15.6 15.6 15.6
lbs 34.4 34.4 34.4 34.4
1) 1% per minute peak, 10% per minute during start up.2) PAH F 40 tank supply only 1500 RPM and boosted 3000 RPM
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
5521B1113 | DKCFN.PD.010.A2.02 | 2017.10
5. Flow The flow (Q eff
) at various pressure (pmax
) can be calculated with the following equation:
Q eff
= Q (th)
– [(Q (th)
– Q (p max
)) x (p / p max
)]
The theoretical flow can be calculated with the following equation:
V x nQ
(th) =
1000
At zero pressure the true flow equals the theoretical flow Q
(th).
Q (th)
: Theoretical flow (l/min / gpm)Q (p
max): Flows at max. pressure (l/min and
gpm), see 4.1-4.4p
max: Max pressure (barg / psig)
p: Pressure (barg / psig)V: Displacement (cm3 / rev.)n: Motor speed (rpm)
5.1 PAH F 20 – 40 typical flow curves at max pressure
0,00
20,00
40,00
60,00
80,00
100,00
120,00
140,00
700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
Flow
[l/m
in]
Speed [RPM]
700 900 1100 1300 1500 1700 1900
PAH F 40PAH F 32
PAH F 25
PAH F 20
2100 2300 2500 2700 2900 3100 3300 3500
Speed [RPM]
0.00
20.00
40.00
60.00
80.00
100.00
120.00
140.00
Flow
[l/m
in]
0,00
5,00
10,00
15,00
20,00
25,00
30,00
35,00
700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 3500
Flow
[GPM
]
Speed [RPM]Speed [RPM]
700 900 1100 1300 1500 1700 1900 2100 2300 2500 2700 2900 3100 3300 35000.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
Flow
[GPM
]
PAH F 40 PAH F 32
PAH F 25
PAH F 20
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
6 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
6. Motor requirements The required motor power can be calculated by using the following equation:
n x V x pP = 600.000 x η
From the flow curves in item 5, you can deter-mine the rpm of the pump at the desired flow.
The required torque is calculated as follows:
V x pM = 62.8 x η
To determine the correct motor size, both the power and torque requirement must be verified.
The mechanical efficiency of the pump, at max pressure, is as follows:
P: Power (kW)M: Torque (Nm)η: Mechanical efficiencyp: Pressure (barg)n: Motor speed (rpm)V: Displacement (cm3/rev.)
PAH F 20, 25, 32, 40 0.9
7. Installation See the figure below for instructions on how to mount the pump and connect it to an electric
motor or combustion engine.
A: Flexible couplingB: Bell housingC: Motor shaft
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
7521B1113 | DKCFN.PD.010.A2.02 | 2017.10
If alternative mounting is required, please contact your Danfoss sales representative for further information.
Note: Do not add any axial or radial loads to the pump shaft.
7.1 Filtration Proper filtration is crucial for the performance, maintenance and warranty of your pump.
Protect your pump, and the application in which it is installed, by always ensuring that filtration specifications are met, and by always changing filter cartridges according to schedule.
Since water has very low viscosity, Danfoss PAH pumps have been designed with very narrow clearances in order to control internal leakage rates and improve component performance. To minimize wear in the pump, it is therefore essential to filter inlet water properly.
The main filter must have a filtration efficiency of 99.98% at 10 μm. We strongly recommend that you always use precision depth filter cartridges rated 10 μm abs. β
10 ≥ 5,000.
Please note that we do not recommend bag filters or string-wound filter cartridges, which typically have only 50% filtration efficiency. This means that out of 100,000 particles that enter such filters, 50,000 particles pass right through them; compare this to precision depth filters that are 99.98% efficient, and only allow 20 of the same 100,000 particles to pass through.
For more information on the importance of proper filtration, including explanation of filtration principles, definitions, and guidance on how to select the right filter for your pump, please consult our Filtration information and specifications (Danfoss document number 521B1009).
7.2 Noise Since the pump unit is mounted on a frame, the overall noise level can only be determined for a complete system. To minimize vibrations and noise throughout the system, it is therefore very important to mount the pump unit correctly on a frame with dampers and to use flexible hoses rather than metal pipes where possible.
The noise level is influenced by: • Pump speed:
High rpm makes more fluid/structure- borne pulsations/vibrations than low rpm.
• Discharge pressure: High pressures make more noise than low pressures.
• Pump mounting: Rigid mounting makes more noise than flexible mounting because of the structure-borne vibrations. Be sure to use dampers when mounting.
• Connections to pump: Pipes connected directly to the pump make more noise than flexible hoses because of structure-borne vibrations.
• Variable frequency drives (VFDs): Motors regulated by VFDs can produce more noise if the VFD does not have the right settings.
7.3 Open-system design
A Inlet line: Dimension the inlet line to obtain mini-mum pressure loss (large flow, minimum pipe length, minimum number of bends/connections, fittings with small pressure losses and restrictions).
B Inlet filter: Install the inlet filter (1) in front of the PAHF pump (2). Please consult the Danfoss filter data sheet for guidance on how to select the right filter.
C Monitoring pressure switch: Install the monitoring pressure switch (3) between the filter and the pump inlet. Set the minimum inlet pressure according to specifications described in item 4, technical data. The monitoring pressure switch stops the pump if inlet pressure is lower than the set minimum pressure.
D Monitoring temperature switch: Install the monitoring temperature switch (4) between the filter and the pump, on either side of the monitoring pressure switch. Set the temperature value accord-ing to technical data, item 4. The monitor-ing temperature switch stops the pump if
inlet temperature is higher than the set value.
E Hoses: Always use flexible hoses (5) to minimize vibrations and noise.
F Inlet pressure: In order to eliminate the risk of cavitation and other pump damage, pump inlet pressure must be maintained according to specifications described in item 4, technical data.
G Non-return valve (6): Should be installed after the outlet to prevent pump backspin, which may ruin the pump.
H Pressure relief valve: As the Danfoss PAH F pump begins to create pressure and flow immediately after start-up regardless of any counter pressure, a pressure relief valve (7) should be installed to prevent system damage.
Note: If a non-return valve is mounted in the inlet line, a low-pressure relief valve is also recommended between the non-return valve and the pump to protect against high-pressure peaks.
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
8 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
Reservoir
PI
System
PI
M
PI
System
PI
M
1
2
3
4
5 5
7
6
1
2
3
4
6 6 7
8
5
9
10
11
7.4 Closed-system design
A Inlet line: Dimension the inlet line to obtain mini-mum pressure loss (large flow, minimum pipe length, minimum number of bends/connections, fittings with small pressure losses and restrictions).
B Inlet filter: Install the filter (1) in front of the tank (2). Please consult the Danfoss filter data sheet for guidance on how to select the right filter.
C Monitoring pressure switch: Install the monitoring pressure switch (3) in front of the filter (1). Set the maximum inlet pressure to 2 barg (29.0 psig). The monitor-ing pressure switch will stop the pump (5) if inlet pressure is higher than 2 barg (29.0 psig), indicating that the filter element must be changed.
D Monitoring temperature switch: Install the monitoring temperature switch (4) in the tank. Set the temperature value according to technical data, item 4. The monitoring temperature stops the pump if inlet temperature is higher than the set value.
E Hoses: Always use flexible hoses (6) to minimize vibrations and noise.
F Inlet pressure: In order to eliminate the risk of cavitation and other pump damage, pump inlet pressure must be maintained according to specifications described in item 4, technical data.
G Non-return valve (7): Should be installed after the outlet to prevent pump backspin, which may ruin the pump.
H Pressure relief valve: As the Danfoss PAHF pump begins to create pressure and flow immediately after start-up regardless of any counter pressure, a pressure relief valve (8) should be installed to prevent system damage.
I System water filling: To ensure proper filtration of new water (10) supplied to the system, always use the filling valve (9).
J Minimum level switch: Install the minimum level switch (11) above
the outlet of the reservoir. The level switch must stop the pump if the water in the reservoir is below the switch, which indicates that the reservoir is empty.
Reservoir
PI
System
PI
M
PI
System
PI
M
1
2
3
4
5 5
7
6
1
2
3
4
6 6 7
8
5
9
10
11
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
9521B1113 | DKCFN.PD.010.A2.02 | 2017.10
8. Dimensions and connections
8.1 PAH F 20/25/32/40
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
10 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
9. Service Danfoss PAH F pumps are developed for 500 hours lifetime. The pumps are maintenance free overtheir entire service life. To achieve the maximumservice life, proper water supply and filtration aremandatory.The life of a pump may be greatly shortened if Danfoss recommendations concerning system design and operation are not followed.
In our experience, poor filtration is the number one cause of pump damage.
Other factors that affect pump performance and lifetime include:
• running the pump at speeds outside specifications
• supplying the pump with water at temper-atures higher than recommended
• running the pump at inlet pressures outside specifications
• running the pump at outlet pressures outside the specifications.
10. Accessories 10.1 VRHF 100 Relief valveThe relief valve type VRHF is designed to be mounted directly on PAH F 20-40 pumps, by means of 4 x M8 screws. A thread G¾ is then added to the pump.The relief valve is used for protecting the components of a system against overload as a result of pressure peaks.Further, the valve is designed for controlling/limiting the system pressure by draining off the surplus water from the pressure side.The valve is designed for tap water, ie. without additives of any kind to the medium. (EU-drink-ing water directive 98/83/EC).
The VRHF relief valve has.• Excellent functional characteristics• Easy-to-clean surface• Corrosion-proof parts (stainless steel, AISI
304, W. No. 1.4301)
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
11521B1113 | DKCFN.PD.010.A2.02 | 2017.10
Description Unit VRHF 100
Code number / Thread G¾ 180G0011
Pressure settingbarg 80-140
psig 1,160-2,030
Setting screw, from min. to max.mm 6.2
in 0.24
Flow max.l/min 100
gpm 21.9
Media temperature°C 2-50
°F 37-122
Ambient temperature°C 50
°F 122
Internal leakage 20% below max. setting pressurel/min up to 1
gpm up to 0.2
Filtration 10 μm abs. β10 ≥ 5,000
Weightkg 2.8
lb 6.2
P/Q Characteristic
0
20
40
60
80
100
120
140
160
180
0 10 20 30 40 50 60 70 80 90 100
Q [l/min]
P [b
ar]
140bar-10l/min
80bar- 10/min
Pressure setting range: 80 - 140 barg [1,160-2,030 psig]
80 to 140 barg
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
12 521B1113 | DKCFN.PD.010.A2.02 | 2017.10
10.2 VRHF 100 Dimensions
Data sheet | PAH F 20/25/32/40 pumps for fire fighting
13521B1113 | DKCFN.PD.010.A2.02 | 2017.10
10.3 PAH F Adaptor
An adaptor can be mounted directly on PAH F 20-40 pump by means of 4 M8 screws. The adapter is adding a thread G¾.
Type Code number
Adaptor - Thread G¾ 180B0096
10.4 Adaptor Dimensions
© Danfoss | DCS (im) |2017.10 521B1113 | DKCFN.PD.010.A2.02 | 14
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/SHigh Pressure PumpsNordborgvej 81DK-6430 NordborgDenmark