panasonic air conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · tube material copper...

85
1 Features 2 2 Functions 3 3 Product Specifications 6 3.1. CS-C7DKD CU-C7DKD 6 3.2. CS-C9DKD CU-C9DKD 8 3.3. CS-C12DKD CU-C12DKD 10 4 Dimensions 12 4.1. Indoor Unit & Remote Control 12 4.2. Outdoor Unit 13 5 Refrigeration Cycle Diagram 15 © 2004 Panasonic HA Air-Conditioning (M) Sdn Bhd (11969-T). All rights reserved. Unauthorized copying and distribution is a violation of law. CS-C7DKD CU-C7DKD CS-C9DKD CU-C9DKD CS-C12DKD CU-C12DKD 6 Block Diagram 16 7 Wiring Diagram 17 8 Operation Details 19 8.1. Cooling Operation 19 8.2. Soft Dry Operation 20 8.3. Automatic Operation 21 8.4. Operation Control 22 8.5. Indoor Fan Speed Control 25 8.6. Outdoor Fan Speed Control 27 8.7. Vertical Airflow Direction Control 27 Air Conditioner CONTENTS Page Page Order No. MAC0411046C3

Upload: others

Post on 17-Mar-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

1 Features 2 2 Functions 3 3 Product Specifications 6

3.1. CS-C7DKD CU-C7DKD 6

3.2. CS-C9DKD CU-C9DKD 8

3.3. CS-C12DKD CU-C12DKD 10

4 Dimensions 12 4.1. Indoor Unit & Remote Control 12

4.2. Outdoor Unit 13

5 Refrigeration Cycle Diagram 15

© 2004 Panasonic HA Air-Conditioning (M) Sdn Bhd(11969-T). All rights reserved. Unauthorized copyingand distribution is a violation of law.

CS-C7DKD CU-C7DKDCS-C9DKD CU-C9DKDCS-C12DKD CU-C12DKD

6 Block Diagram 16 7 Wiring Diagram 17 8 Operation Details 19

8.1. Cooling Operation 19

8.2. Soft Dry Operation 20

8.3. Automatic Operation 21

8.4. Operation Control 22

8.5. Indoor Fan Speed Control 25

8.6. Outdoor Fan Speed Control 27

8.7. Vertical Airflow Direction Control 27

Air Conditioner

CONTENTS Page Page

Order No. MAC0411046C3

Page 2: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.8. Horizontal Airflow Direction Control 28

8.9. Powerful Operation 28

8.10. Quiet Operation 29

8.11. Ionizer Operation 30

8.12. Timer Control 31

8.13. Random Auto Restart Control 31

8.14. Remote Control Signal Receiving Sound 31

9 Operating Instructions 32 10 Installation Instructions 38

10.1. Safety Precautions 38

10.2. Attached accessories 40

10.3. Select the best location 40

10.4. Indoor/Outdoor Unit Installation Diagram 40

10.5. Indoor unit 41

10.6. Outdoor unit 44

11 2-way, 3-way Valve 49 11.1. Evacuation of the Equipment 50

11.2. Air Purging of the Piping and Indoor Unit 56

12 Servicing Information 62 12.1. Distinction of Lead Free (PbF) Printed Circuit Board 62

12.2. Indoor Electronic Controller Removal Procedures 62

• High Efficiency

• Compact Design

• Wider range of horizontal discharge air.

• Air Filter with function to reduce dust and smoke.

• Automatic air swing and manual adjusted by RemoteControl for vertical airflow.

• Long installation piping. − CS/CU-C7DK, CS/CU-C9DK, long piping up to 10

meter. − CS/CU-C12DK, long piping up to 15 meter.

• Supersonic Air Purifying Device with SUPER alleru-buster. − Inactive various harmful airborne elements including

allergen, viruses and bacteria. − Generated supersonic waves enhance the ability to

collect dust and dirt in the air.

12.3. Indoor Fan Motor and Cross Flow Fan Removal

Procedures 63

12.4. Auto OFF/ON Button 64

12.5. Remote Control Reset 65

13 Troubleshooting Guide 66 13.1. Refrigeration cycle system 66

13.2. Relationship between the condition of the air conditioner

and pressure and electric current 67

13.3. Diagnosis methods of a malfunction of a compressor 67

14 Technical Data 68 14.1. Thermostat characteristics 68

14.2. Sensible Capacity Chart 68

14.3. Operation characteristics 69

15 Exploded View (Indoor Unit) 71 16 Replacement Parts List (Indoor Unit) 72 17 Exploded View (Outdoor Unit) 73 18 Replacement Parts List (Outdoor Unit) 75 19 Electronic Circuit Diagram 76

19.1. Indoor Unit 76

19.2. Remote Control 82

19.3. Print Pattern Indoor Unit Printed Circuit Board 83

• Quality Improvement − Random auto restart after power failure for safety restart

operation. − Gas leakage protection. − Prevent Compressor reverse cycle. − Inner protector to protect Compressor. − Noise prevention during soft dry operation. − Blue Coated Condenser for high resistance to corrosion.

• Operation Improvement − Quiet mode to provide quiet operation. − Powerful mode to reach the desired room temperature

quickly. − Ionizer control for generating negative ion in discharge

air. − 24-hour timer setting.

• Serviceability Improvement − Removable and washable Front Panel.

1 Features

2

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 3: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

2 Functions

3

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 4: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

4

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 5: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

5

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 6: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3 Product Specifications3.1. CS-C7DKD CU-C7DKD

Unit Indoor unit Outdoor unitPower Source (Phase, Voltage, Cycle) ø, V, Hz Single, 220 - 230, 50Cooling Capacity kW (BTU/h) 2.00 - 2.02 (6,820 - 6,890)Moisture Removal l/h (Pint/h) 1.3 (2.7)

Airflow Method OUTLET

INTAKE

SIDE VIEW TOP VIEW

Air Volume Lo m3/min (cfm) 5.1 (179) - 5.1 (179) —Me m3/min (cfm) 5.9 (207) - 5.9 (207) —Hi m3/min (cfm) 6.5 (230) - 6.5 (230) 28.8 (1020) - 29.2 (1030)SHi m3/min (cfm) 7.2 (252) - 7.2 (250) —

Noise Level dB (A) High 33 - 33, Low 26 - 26 High 46 - 47Power level dB High 46 - 46 High 61 - 62

Electrical Data Input Power W 590 - 640Running Current A 2.8 - 2.9EER W/W (BTU/hW) 3.39 - 3.15 (11.6 - 10.8)Starting Current A 12.4

Piping Connection Port(Flare piping)

inchinch

G ; Half Union 3/8”L ; Half Union 1/4”

G ; 3-way valve 3/8”L ; 2-way valve 1/4”

Pipe Size(Flare piping)

inchinch

G ; (gas side) 3/8”L ; (liquid side) 1/4”

G ; (gas side) 3/8”L ; (liquid side) 1/4”

DrainHose

Inner diameter mm 19.5 —Length mm 650 —

Power Cord Length m 2.0 —Number of core-wire 3 (1.5 mm2) —

Dimensions Height inch (mm) 11 - 1/32 (280) 20 - 3/32 (510)Width inch (mm) 31 - 15/32 (799) 25 - 19/32 (650)Depth inch (mm) 7 - 7/32 (183) 9 - 1/16 (230)

Net Weight lb (kg) 20 (9) 49 (22)Compressor Description — Rotary (1 cylinder)

rolling piston typeMotor Type — Induction (2-poles)Rated Output W — 550

Fan Motor Description Cross-flow Fan Propeller FanMaterial AS + Glass Fiber 20% PP ResinType Induction (4-poles) Induction (6-poles)Input W 55.0 - 66.0 65.0 - 72.4Rated Output W 15 30Fan Speed Low rpm 860 - 860 —

Medium rpm 990 - 990 —High rpm 1,100 - 1,100 800 - 830SuperHigh rpm 1,210 - 1,210 —

Heat Exchanger Description Evaporator CondenserTube material Copper CopperFin material Aluminium (Pre Coat) Aluminium (Blue Coat)Fin Type Slit Fin Louver FinRow / Stage (Plate fin configuration, forced draft)

2 × 10 1 × 22FPI 18 17Size (W × H × L) mm 610 × 210 × 25.4 12.7 × 483 × 600

Refrigerant Control Device — Capillary TubeRefrigeration Oil (cm3) — SUNISO 4GDID or ATMOS M60

(290)Refrigerant (R-22) g (oz) — 450 (15.9)Thermostat — —

6

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 7: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Unit Indoor unit Outdoor unitProtection Device — 2 Stage Overload ProtectorCapillary Tube Length mm — 810

Flow Rate l/min — 9.9Inner Diameter mm — 1.5

Air Filter MaterialStyle

P.P.Honeycomb

Capacity Control Capillary TubeCompressor Capacitor µF, VAC — 20 µF, 370VACFan Motor Capacitor µF, VAC 1.5 µF, 440VAC 2.0 µF, 440VAC

Note: • Specifications are subjected to change without prior notice for further improvement.

7

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 8: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3.2. CS-C9DKD CU-C9DKDUnit Indoor unit Outdoor unit

Power Source (Phase, Voltage, Cycle) ø, V, Hz Single, 220 - 230, 50Cooling Capacity kW (BTU/h) 2.60 - 2.65 (8,870 - 9,040)Moisture Removal l/h (Pint/h) 1.6 (3.4)

Airflow Method OUTLET

INTAKE

SIDE VIEW TOP VIEW

Air Volume Lo m3/min (cfm) 5.0 (178) - 5.0 (178) —Me m3/min (cfm) 6.1 (216) - 6.1 (216) —Hi m3/min (cfm) 7.1 (250) - 7.1 (250) 28.8 (1,020) - 29.2 (1,040)SHi m3/min (cfm) 7.6 (267) - 7.6 (267) —

Noise Level dB (A) High 36 - 36, Low 26 - 26 High 46 - 47Power level dB High 49 - 49 High 61 - 62

Electrical Data Input Power W 800 - 825Running Current A 3.8 - 3.8EER W/W (BTU/hW) 3.25 - 3.21 (11.1 - 11.0)Starting Current A 18.0

Piping Connection Port(Flare piping)

inchinch

G ; Half Union 3/8”L ; Half Union 1/4”

G ; 3-way valve 3/8”L ; 2-way valve 1/4”

Pipe Size(Flare piping)

inchinch

G ; (gas side) 3/8”L ; (liquid side) 1/4”

G ; (gas side) 3/8”L ; (liquid side) 1/4”

DrainHose

Inner diameter mm 19.5 —Length mm 650 —

Power Cord Length m 2.0 —Number of core-wire 3 (1.5 mm2) —

Dimensions Height inch (mm) 11 - 1/32 (280) 20 - 3/32 (510)Width inch (mm) 31 - 15/32 (799) 25 - 19/32 (650)Depth inch (mm) 7 - 7/32 (183) 9 - 1/16 (230)

Net Weight lb (kg) 20 (9) 55 (25)Compressor Description — Rotary (1 cylinder)

rolling piston typeMotor Type — Induction (2-poles)Rated Output W — 750

Fan Motor Description Cross-flow Fan Propeller FanMaterial AS + Glass Fiber 20% PP ResinType Induction (4-poles) Induction (6-poles)Input W 55.0 - 60.5 896 - 924Rated Output W 15 30Fan Speed Low rpm 860 - 860 —

Medium rpm 1,040 - 1,040 —High rpm 1,210 - 1,210 780 - 830SuperHigh rpm 1,290 - 1,290 —

Heat Exchanger Description Evaporator CondenserTube material Copper CopperFin material Aluminium (Pre Coat) Aluminium (Blue Coat)Fin Type Slit Fin Louver FinRow / Stage (Plate fin configuration, forced draft)

2 × 10 1 × 22FPI 18 17Size (W × H × L) mm 610 × 210 × 25.4 12.7 × 483 × 600

Refrigerant Control Device — Capillary TubeRefrigeration Oil (cm3) — ATMOS M60 OR ATMOS 56M

OR SUNISO 4GDIDRefrigerant (R-22) g (oz) — 430 (15.2)

Thermostat — —Protection Device — 2 Stage Overload Protector

8

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 9: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Unit Indoor unit Outdoor unitCapillary Tube Length mm — 298

Flow Rate l/min — 9.0Inner Diameter mm — 1.2

Air Filter MaterialStyle

P.P.Honeycomb

Capacity Control Capillary TubeCompressor Capacitor µF, VAC — 30 µF, 370VACFan Motor Capacitor µF, VAC 1.5 µF, 440VAC 2.0 µF, 440VAC

Note: • Specifications are subjected to change without prior notice for further improvement.

9

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 10: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3.3. CS-C12DKD CU-C12DKDUnit Indoor unit Outdoor unit

Power Source (Phase, Voltage, Cycle) ø, V, Hz Single, 220 - 230, 50Cooling Capacity kW (BTU/h) 3.52 - 3.54 (12,000 - 12,100)Moisture Removal l/h (Pint/h) 2.1 (4.4)

Airflow Method OUTLET

INTAKE

SIDE VIEW TOP VIEW

Air Volume Lo m3/min (cfm) 6.6 (233) - 6.6 (233) —Me m3/min (cfm) 7.8 (274) - 7.8 (274) —Hi m3/min (cfm) 9.4 (330) - 9.4 (330) 30.9 (1,090) - 31.6 (1,120)SHi m3/min (cfm) 9.6 (340) - 9.6 (340) —

Noise Level dB (A) High 39 - 39, Low 29 - 29 High 48 - 49Power level dB High 52 - 52 High 63 - 64

Electrical Data Input Power kW 1.11 - 1.13Running Current A 5.3 - 5.2EER W/W (BTU/hW) 3.17 - 3.13 (10.8 - 10.7)Starting Current A 27.0

Piping Connection Port(Flare piping)

inchinch

G ; Half Union 1/2”L ; Half Union 1/4”

G ; 3-way valve 1/2”L ; 2-way valve 1/4”

Pipe Size(Flare piping)

inchinch

G ; (gas side) 1/2”L ; (liquid side) 1/4”

G ; (gas side) 1/2”L ; (liquid side) 1/4”

DrainHose

Inner diameter mm 19.5 —Length mm 650 —

Power Cord Length m 2.0 —Number of core-wire 3 (1.5 mm2) —

Dimensions Height inch (mm) 11 - 1/32 (280) 21 - 1/4 (540)Width inch (mm) 31 - 15/32 (799) 30 - 23/32 (780)Depth inch (mm) 7 - 7/32 (183) 11 - 3/8 (289)

Net Weight lb (kg) 20 (9.0) 71 (32.0)Compressor Description — Rotary (1 cylinder) rolling piston

typeMotor Type — Induction (2-poles)Rated Output W — 950

Fan Motor Description Cross-flow Fan Propeller FanMaterial AS + Glass Fiber 20% PP ResinMotor Type Induction (4-poles) Induction (6-poles)

Input W 55.0 - 66.0 1243 - 1265Rated Output W 15 31Fan Speed Low rpm 890 - 890 —

Medium rpm 1,050 - 1,050 —High rpm 1,270-1,270 815 - 850SuperHigh rpm 1,300-1,300 —

Heat Exchanger Description Evaporator CondenserTube material Copper CopperFin material Aluminium (Pre Coat) Aluminium (Blue Coat)Fin Type Slit Fin Louver FinRow / Stage (Plate fin configuration, forced draft)

2 × 15 1 × 24FPI 19 17Size (W × H × L) mm 610 × 315 × 25.4 12.7 × 508 × 745

Refrigerant Control Device — Capillary TubeRefrigeration Oil (cm3) — ATMOS M60 OR SUNISO

4GDIDRefrigerant (R-22) g (oz) — 630 (22.2)Thermostat — —Protection Device — —

10

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 11: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Unit Indoor unit Outdoor unitCapillary Tube Length mm — 605

Flow Rate l/min — 15.7Inner Diameter mm — 1.7

Air Filter MaterialStyle

P.P.Honeycomb

Capacity Control Capillary TubeCompressor Capacitor µF, VAC — 35 µF, 370VACFan Motor Capacitor µF, VAC 1.5 µF, 440VAC 2.0 µF, 440VAC

Note: • Specifications are subjected to change without prior notice for further improvement.

11

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 12: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

4 Dimensions4.1. Indoor Unit & Remote Control

12

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 13: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

4.2. Outdoor UnitCU-C7DKD/CU-C9DKD

13

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 14: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

CU-C12DKD

14

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 15: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

5 Refrigeration Cycle Diagram

15

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 16: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

6 Block Diagram

16

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 17: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

CS/CU-C7DKD CS/CU-C9DKD REMARKSB : BLUEBR : BROWNBL : BLACKGRY : GRAYO : ORANGEP : PINKR : REDW : WHITEY/G : YELLOW/GREEN

Power Supply Cord

Resistance of Indoor Fan Motor WindingsMODEL CS-C7DKD

CS-C9DKDCONNECTION CWA921181BLUE-YELLOW 390.0 ΩYELLOW-RED 390.0 Ω

Note: Resistance at 20°C of ambient temperature.

Resistance of Outdoor Fan Motor WindingsMODEL CU-C7DKD

CU-C9DKDCONNECTION CWA951379BLUE-YELLOW 285.0 ΩYELLOW-RED 281.0 Ω

Note: Resistance at 26°C of ambient temperature.

Resistance of Compressor WindingsMODEL CU-C7DKD

CONNECTION 2RS122D5BC02C - R 5.193 ΩC - S 5.557 Ω

Note: Resistance at 20°C of ambient temperature.

MODEL CU-C9DKDCONNECTION 2PS156D3BB02

C - R 3.501 ΩC - S 3.405 Ω

Note: Resistance at 25°C of ambient temperature.

7 Wiring Diagram

17

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 18: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

CS/CU-C12DKD REMARKSB : BLUEBR : BROWNBL : BLACKGRY : GRAYO : ORANGEP : PINKR : REDW : WHITEY/G : YELLOW/GREEN

Power Supply Cord

Resistance of Indoor Fan Motor WindingsMODEL CS-C12DKD

CONNECTION CWA921181BLUE-YELLOW 390.0 ΩYELLOW-RED 390.0 Ω

Note: Resistance at 20°C of ambient temperature.

Resistance of Outdoor Fan Motor WindingsMODEL CU-C12DKD

CONNECTION CWA951263BLUE-YELLOW 281.0 ΩYELLOW-RED 251.0 Ω

Note: Resistance at 26°C of ambient temperature.

Resistance of Compressor WindingsMODEL CU-C12DKD

CONNECTION 2KS206D5AF04C - R (Main) 2.23 ΩC - S (Sub) 2.63 Ω

Note: Resistance at 25°C/20°C of ambient temperature.

18

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 19: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8 Operation Details8.1. Cooling Operation

• Cooling operation can be set using remote control. • This operation is applied to cool down the room temperature reaches the setting temperature set on the remote control. • The remote control setting temperature, which takes the reading of intake air temperature sensor, can be adjusted from 16°C

to 30°C. • During cooling operation, the compressor will stop running and restart as shown in below figure.

8.1.1. Cooling Operation Time Diagram

19

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 20: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.2.1. Soft Dry Operation Time Diagram

8.2. Soft Dry Operation

• Soft Dry operation can be set using remote control. • Soft Dry operation is applied to dehumidify and to perform a gentle cooling to the room. • This operation starts when the intake air temperature sensor reaches the setting temperature on the remote control. • When operation begins, Soft Dry will be switched “ON” for a maximum 10 minutes, then Soft Dry operation will be turned “OFF”

for a minimum 6 minutes. After that, the Soft Dry operation will be “ON” and “OFF” based on the setting temperature as shownin below figure.

• However after 3 minutes of compressor off, during Soft Dry “OFF” (within 6 minutes Soft Dry restart control), the indoor unit willstart to operate at normal Cooling mode if the intake temperature is higher than Cooling “ON” point.

20

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 21: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.3. Automatic Operation • Automatic operation can be set using remote control. • This operation starts to operate with indoor fan at SLo speed for 20 seconds to judge the intake air temperature. • After judged the temperature, the operation mode is determined by referring to the below standard.

• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the settingtemperature as shown in below table.

• The setting temperature for all the operations can be changed one level up or one level down from the standard temperatureas shown in below table by pressing on the temperature up or temperature down button at remote control.

• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open thecircuit of JX1 at indoor electronic controller.

21

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 22: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.4. Operation Control

8.4.1. Restart Control (Time Delay Safety Control) • When the thermo-off temperature (temperature which compressor stops to operate) is reached during:-

− Cooling/Heating operation - the compressor stops for 3 minutes (minimum) before resume operation. − Soft Dry operation - the compressor stops for 6 minutes (minimum) before resume operation.

• If the operation is stopped by the remote control, the compressor will not turn on within 3 minutes from the moment operationstop, although the unit is turn on again within the period.

• This phenomenon is to balance the pressure inside the refrigerant cycle.

(For 8.5.3. to 8.5.6. information applies only to Cooling and Soft Dry Operation)

8.4.2. 7 Minutes Time Save Control • The compressor will start automatically if it has stopped for 7 minutes and the intake air temperature falls between the

compressor ON temperature (A) and compressor OFF temperature (B) during the period. • This phenomenon is to reduce the built up humidity inside a room.

8.4.3. 60 Seconds Forced Operation • Once the air conditioner is turned on, the compressor will not stop within 60 seconds in a normal operation although the intake

air temperature has reached the thermo-off temperature. However, force stop by pressing the OFF/ON operation button at theremote control is permitted.

• The reason for the compressor to force operate at minimum 60 seconds is to allow the refrigerant oil run in a full cycle andreturn back to the outdoor unit.

8.4.4. Starting Current Control • When the compressor, outdoor fan motor and indoor fan motor are simultaneously started, the indoor fan motor will start to

operate at 1.6 second later. • The reason of the difference is to reduce the starting current flow.

22

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 23: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.4.5. Anti-Freezing Control • If the temperature of the indoor heat exchanger falls below 2°C continuously for 4 minutes or more, the compressor turns off.

The fan speed setting remains the same. • This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid form

returning to the compressor. • Compressor will restart again when the indoor heat exchanger temperature rises to 10°C (Recovery). • Restart control (Time Delay Safety Control) will be applied in this Control if the recovery time is too short.

8.4.6. Compressor Reverse Rotation Protection Control • If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and

indoor heat exchanger is 2.5°C or less for continuous 2 minutes, compressor will stop and restart automatically. • Time Delay Safety Control is activated before the compressor restart.

s T = Intake air temperature - Indoor heat exchanger temperature • This is to prevent compressor from rotate reversely when there is an instantaneous power failure.

8.4.7. Anti-Dew Formation Control • Purpose is to prevent dew formation on indoor unit discharge area. • When room temperature is constant (±1°C) the following condition occur for 30 minutes continuously, anti-dew formation will

activate:- Indoor intake temperature is more than 24°C and less than 30°C.- Remote Control setting temperature is less than 25°C.- Compressor is on.- Cooling Operation Mode.- Indoor fan motor operate at Low fan speed or QLo.

23

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 24: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

• Anti-Dew Formation is control by:- • Increasing Air Flow Volume

1. Lo fan speed.Lo fan speed is changed to Lo+ after 30 min to prevent dew formation.

2. QLo fan speed.Dew formation may occur at QLo cool, therefore QLo cool is operated only 1hr 30min (1 hr QLo, 30 min QLo + 80 rpm). Afterthat, it operates at QLo + 160 rpm (However Quiet LED remains on).

• Narrowing 1. Vertical Airflow Direction

During Anti-Dew condensation prevention, Airflow Direction Auto-control angle from 0° - 32° to 20° - 30° under cooling andSoft Dry operation mode.

24

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 25: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

During Anti-Dew condensation prevention, Airflow Direction Manual Control angle change from 10°, 15°, 20°, 32° to 22°,24°, 26°, 28°, 30°.

8.5. Indoor Fan Speed Control • Indoor Fan Speed can be set using remote control.

8.5.1. Fan Speed Rotation ChartSpeed Fan Speed

CS-C7DKD CS-C9DKD CS-C12DKDS Hi 1210 1290 1300Hi 1100 1210 1270Me 990 1040 1050

H Lo 940 940 980C Lo 860 860 890Lo- 810 810 840

S Lo 760 760 790SS Lo - - -Q S Hi - - -Q Hi 1000 1110 1170Q Me 890 940 950QH Lo - - -Q Lo 760 760 790

25

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 26: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.5.2. Automatic Fan Speed Control • When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the table.

− Fan speed rotates in the range of Hi and Me. − Deodorizing Control will be activated.

• Auto Fan Speed during cooling operation: 1. Indoor fan will rotate alternately between off and on as shown in below diagram. 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose. 3. For the first time the compressor operate, indoor fan will be switched to Hi fan speed from Lo- after 70 seconds from the

start of compressor. This cause the room temperature to achieve the setting temperature quickly. 4. During compressor stop, indoor fan will operate at Lo for the beginning 20 seconds to prevent higher volume of refrigerant

in liquid form returning to the compressor. 5. After the compressor at turn off condition for 3 minutes, indoor fan will start to operate at Lo- to circulate the air in the room.

This is to obtain the actual reading of the intake air temperature. 6. For the resume of compressor operation, indoor fan will operate at Me fan speed to provide comfort and lesser noise

environment, after 70 seconds from the restart of compressor.

26

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 27: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

• When the vertical airflow direction is set to Auto using theremote control, the louver swings up and down as shown inthe diagram.

• When stop operation using the remote control, thedischarge vent is reset, and stop at the closing position.

• During Cooling operation or Soft Dry operation, indoor fanmotor may stop to rotate at certain periods. At thatcondition, the louver will stop swinging and rest at the upperlimit.

• When the vertical airflow direction is set to Manual using theremote control, the automatic airflow is released and theairflow direction louver move up and down in the rangeshown in the diagram.

• The louver can be adjusted by pressing the button to thedesired louver position.

• When stop operation using the remote control, thedischarge vent is reset, and stop at the closing position.

• Auto Fan Speed during Soft Dry operation: 1. Indoor fan will rotate alternately between off and Lo-. 2. At the beginning of each compressor start operation, indoor fan will increase fan speed gradually for deodorizing purpose. 3. When compressor at turn off condition for 6 minutes, indoor fan will start fan speed at Lo- to circulate the air in the room.

This is to obtain the actual reading of intake air temperature.

8.5.3. Manual Fan Speed Control • Manual fan speed adjustment can be carried out by using the Fan Speed selection button at the remote control. • There are 3 types of fan speed settings: Lo, Me, Hi.

8.6. Outdoor Fan Speed Control • There is only one speed for outdoor fan motor. • When the air conditioner is turned on, the compressor and the outdoor fan will operate simultaneously. • Likewise, both compressor and outdoor fan will stop at the same time if the unit is turned off.

8.7. Vertical Airflow Direction Control8.7.1. Auto Control

8.7.2. Manual Control

27

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 28: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.8. Horizontal Airflow Direction Control • The horizontal airflow direction louvers can be adjusted manually by hand.

8.9. Powerful Operation • The Powerful operation is to achieve the setting temperature quickly. • When Powerful operation is set, the setting temperature will be automatically decreased 3°C internally against the present

setting temperature (Lower temperature limit: 16°C). • This operation automatically will be running under SHi Fan Speed (Cooling), Lo- Fan Speed (Soft Dry). • Vertical Airflow Direction:-

- In “Manual” setting, the vane will automatically shift down 10° lower than previous.- In “Auto” setting, the vane will automatically swing up and down. However the lower limit will be shifted 10° downward.

• Powerful Mode will operate for 15 minutes only and operation will shift back to previous setting mode. • Powerful operation stops when:-

- Powerful mode button is pressed again.- Stopped by OFF/ON operation button.- Timer OFF activates.- Quiet mode button is pressed.- Operation mode button is changed.

28

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 29: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.10. Quiet Operation(For Cooling Operation or cooling region of Soft Dry Operation) • The Quiet operation is to provide quiet/cooling operation condition compare to normal operation. • Once the Quiet Mode is set at the remote control, the Quiet Mode LED illuminated. The sound level will reduce around 2 dB(A)

for Lo fan speed or 3 dB(A) for Hi/Me fan speed against the present operation sound level. • Dew formation become severe at Quiet Lo cool, therefore Quiet Lo cool is operated only 1hr 30 min (1hr QLo, 30 min QLo +

80 rpm). After that, it goes back to Lo cool (However Quiet LED remains on). • Manual Airflow Direction:-

− RPM control during Lo cool

− RPM control during Hi cool

• Auto Airflow Direction:-

• Quiet operation stops when:- − Quiet button is pressed again. − Stopped by OFF/ON operation button. − Timer OFF activates. − Powerful button is pressed. − Operation mode button is changed.

29

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 30: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.11. Ionizer Operation • The Ionizer operation is to provide fresh air effect to user by producing minus ion in discharge air.

8.11.1. Operation Control

1. Ionizer individual operation a. When air-conditioner unit is at “OFF” condition (standby) and ION operation button at the remote control is pressed, the

Ionizer operation will turn on. Only ION LED will illuminates. Power LED maintain off. (1 → 2) b. Ionizer individual operation can be turned off by pressing the ION button again. (2 → 1) c. Fan speed can be adjusted later by customer during this operation.

d. Vertical airflow direction can be adjusted using remote control during Ionizer individual operation. e. During Ionizer individual operation, operated mode (Auto, Cool, Dry) can be activated by turning on the OFF/ON operation

button. (2 → 4) f. If power failure occur during Ionizer individual operation, after power resume, Ionizer operation will be activated immediately. g. When the Ionizer circuit feedback process error occur for 24 times (about 11hr 30 min.), Ionizer operation will turn off with

ION LED blinks continuously.(For details, please refer to Ionizer Error detection control)

2. Operation mode & Ionizer operation. a. When air-conditioner unit is at “ON” condition and ION operation button at the remote control is pressed, the Ionizer

operation will turn on. ION & Power LED will illuminate. (3 → 4) b. Ionizer operation stops when:

• ION operation button is press again. • Stopped by OFF/ON operation button. • Timer OFF activates. • Ionizer circuit feedback signal shows error.

c. Ionizer operation status is not memorised when the air conditioner has been switched off. The air-conditioner will operatewithout ionizer operation when it is turned on again. However, if power failure occurs during Ionizer operation together withCooling operation, air-conditioner will start to operate at Cooling operation with Ionizer operation when the power isresumed.

30

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 31: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

8.11.2. Error Detection Control • The error detection control is to inform user that error occurs at ionizer system and repairing job will be needed. • There are two types of error detection control:

a. When Ionizer is ON − If ionizer feedback = Lo for 24 times within 11hr 30min, ION LED blinks continuously.b. When ionizer is OFF − If ionizer feedback = Hi, ION LED blinks continuously.

• During ionizer at breakdown condition, if ionizer feedback voltage = Lo (become normal), ION LED will stop blinking. • The error detection control can be reset by:

i) Pressing the OFF/ON operation button to switch the operation OFF.ii) Pressing the Auto Operation button to force the operation OFF.iii) Setting the OFF Timer to stop the operation (Not applicable when ionizer is OFF).

8.12. Timer Control • There are 2 types of timer, ON and OFF timer. • Both ON and OFF timer can be set by pressing ON or OFF button respectively. • By pressing ON/OFF operation button, ON Timer or OFF Timer will not be cancelled. • To cancel the previous timer setting, press CANCEL button. • To activate the previous timer setting, press SET button once again. • If main power supply is switched off, the timer setting will be cancelled.

8.12.1. ON Timer • When ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will

reach nearly to the set temperature by the set time. • For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time. • For Automatic operation, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the

intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.

8.12.2. OFF Timer • When OFF Timer is set by using the remote control, the unit will stop operate according to the desired setting.

8.13. Random Auto Restart Control • If there is a power failure during operation, the air conditioner will automatically restart after 3 to 4 minutes when the power is

resumed. • It will start with previous operation mode and airflow direction. • If there are more than one air conditioner unit in operation and power failure occur, restart time for each unit to operate will be

decided randomly using 4 parameters:- intake air temperature, setting temperature, fan speed and air swing louver position. • This Random Auto Restart Control is not available when Timer is set. • This control can be omitted by open the circuit of JX2. (Refer Circuit Diagram)(Indoor PCB)

8.14. Remote Control Signal Receiving Sound • Long beep sound will be heard when:-

− Stopping the air conditioner using ON/OFF switch. − Stopping the Quiet Mode. − Stopping the Powerful Mode. − Stopping the Ion Mode.

• Short beep sound will be heard for others setting. • To switch off the beep sound:-

Press the “Auto Operation Button” (behind the front grille) continuously for 10 seconds or more (“beep” “beep” will be heard atthe 10th second). Repeat the above if you want to switch on the beep sound.

31

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 32: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

9 Operating Instructions

32

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 33: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

33

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 34: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

34

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 35: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

35

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 36: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

36

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 37: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

37

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 38: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

10 Installation InstructionsRequired tools for Installation Works

1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench

18 N.m (1.8 kgf.m)42 N.m (4.2 kgf.m)55 N.m (5.5 kgf.m)

3. Electric drill, hole core drill(ø70 mm)

7. Reamer 11. Thermometer 15. Vacuum pump

4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold

10.1. Safety Precautions • Read the following “SAFETY PRECAUTIONS” carefully before installation. • Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit

for the model to be installed. • The caution items stated here must be followed because these important contents are related to safety. The meaning of each

indication used is as below. Incorrect installation due to ignoring of the instruction will cause harm or damage, and theseriousness is classified by the following indications.

This indication shows the possibility of causing death or serious injury.

This indication shows the possibility of causing injury or damage to properties only.

The items to be followed are classified by the symbols:

Symbol with background white denotes item that is PROHIBITED from doing.

• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care andmaintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or

electrical shock.4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly

done, the set will drop and cause injury.5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single

outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.6. Use the specified cable (1.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no

external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will

cause heat-up at connection point of terminal, fire or electrical shock.8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into refrigeration cycle.

Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion and injury.

9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.

10. Do not modify the length of the power supply cord or use of the extension cord, and do not share the single outlet withother electrical appliances. Otherwise, it will cause fire or electrical shock.

38

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 39: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.

2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates atsurrounding of the unit, it may cause fire.

3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage thefurniture.

1. Selection of the installation location.Select a installation location which is rigid and strong enough to support or hold the unit, and select a location for easy maintenance.

2. Power supply connection to the room air conditioner.Connect the power supply cord of the room air conditioner to the mains using one of the following method.Power supply point shall be the place where there is ease for access for the power disconnection in case of emergency.In some countries, permanent connection of this room air conditioner to the power supply is prohibited. 1. Power supply connection to the receptacle using a power plug.

Use an approved 15A/16A power plug with earth pin for the connection to the socket.

2. Power supply connection to a circuit breaker for the permanent connection. Use an approved 16A circuit breaker for the permanentconnection. It must be a double pole switch with a minimum 3 mm contact gap.

3. Do not release refrigerant.Do not release refrigerant during piping work for installation, reinstallation and during repairing a refrigeration parts. Take care of theliquid refrigerant, it may cause frostbite.

4. Installation work.It may need two people to carry out the installation work.

5. Do not install this appliance in a laundry room or other location where water may drip from the ceiling, etc.

39

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 40: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Applicable piping kitCZ-3F5, 7AEN (C7DK, C9DK, A7DK, A9DK, )CZ-4F5,7, 10AN (C12DK, A12DK)

10.3. Select the best locationINDOOR UNIT

• There should not be any heat source or steam near theunit.

• There should not be any obstacles blocking the aircirculation.

• A place where air circulation in the room is good. • A place where drainage can be easily done. • A place where noise prevention is taken into

consideration. • Do not install the unit near the door way. • Ensure the spaces indicated by arrows from the wall,

ceiling, fence or other obstacles. • Recommended installation height for indoor unit shall be

at least 2.3 m.

OUTDOOR UNIT • If an awning is built over the unit to prevent direct

sunlight or rain, be careful that heat radiation from thecondenser is not obstructed.

• There should not be any animal or plant which could beaffected by hot air discharged.

• Keep the spaces indicated by arrows from wall, ceiling,fence or other obstacles.

• Do not place any obstacles which may cause a shortcircuit of the discharged air.

• If piping length is over the common length, additionalrefrigerant should be added as shown in the table.

10.4. Indoor/Outdoor UnitInstallation Diagram

• This illustration is for explanation purposes only.The indoor unit will actually face a different way.

10.2. Attached accessories

40

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 41: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

10.5.1. SELECT THE BEST LOCATION(Refer to “Select the best location”section)

10.5.2. HOW TO FIX INSTALLATIONPLATE

The mounting wall is strong and solid enough to prevent it fromthe vibration.

The centre of installation plate should be at more than 450 mmat right and left of the wall.The distance from installation plate edge to ceiling should morethan 67 mm.From installation plate left edge to unit’s left side is 74 mm.From installation plate right edge to unit’s right is 94 mm.

:

:

:

For left side piping, piping connection for liquid should beabout 15 mm from this line.For left side piping, piping connection for gas should beabout 45 mm from this line.For left side piping, piping connecting cable should beabout 800 mm from this line.

1. Mount the installation plate on the wall with 5 screws ormore.(If mounting the unit on the concrete wall consider usinganchor bolts.) • Always mount the installation plate horizontally by

aligning the marking-off line with the thread and using alevel gauge.

2. Drill the piping plate hole with ø70 mm hole-core drill. • Line according to the arrows marked on the lower left

and right side of the installation plate. The meeting pointof the extended line is the centre of the hole. Anothermethod is by putting measuring tape at position asshown in the diagram above. The hole centre isobtained by measuring the distance namely 150 mmand 125 mm for left and right hole respectively.

• Drill the piping hole at either the right or the left and thehole should be slightly slanted to the outdoor side.

10.5.3. TO DRILL A HOLE IN THE WALLAND INSTALL A SLEEVE OFPIPING

1. Insert the piping sleeve to the hole. 2. Fix the bushing to the sleeve. 3. Cut the sleeve until it extrudes about 15 mm from the wall.

CautionWhen the wall is hollow, please be sure to use thesleeve for tube ass’y to prevent dangers caused bymice biting the connecting cable.

4. Finish by sealing the sleeve with putty or caulkingcompound at the final stage.

10.5.4. INDOOR UNIT INSTALLATION 1. For the right rear piping

2. For the right and right bottom piping

10.5. Indoor unit

41

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 42: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3. For the embedded piping

(This can be used for left rear piping & left bottom piping also.)

42

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 43: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

10.5.5. CONNECT THE CABLE TO THEINDOOR UNIT

1. The inside and outside connecting cable can be connectedwithout removing the front grille.

2. Connecting cable between indoor unit and outdoor unitshall be approved polychloroprene sheathed 3 (C7DK,C9DK, C12DK) or 5 (A7DK, A9DK, A12DK) × 1.5 mm2

flexible cord, type designation 245 IEC 57 or heavier cord. • Ensure the color of wires of outdoor unit and the

terminal Nos. are the same to the indoor’s respectively. • Earth lead wire shall be longer than the other lead wires

as shown in the figure for the electrical safety in case ofthe slipping out of the cord from the anchorage.

• Secure the cable onto the control board with the holder(clamper).

INSTALLATION OF SUPER ALLERU-BUSTER FILTER

1. Open the front panel. 2. Remove the air filters.

3. Remove Supersonic air purifying device.Open the Supersonic air purifying device frame.Insert the super alleru-buster filter and close the Supersonicair purifying device frame as shown in illustration at below.

HOW TO TAKE OUT FRONT GRILLE

Please follow the steps below to take out front grille ifnecessary such as when servicing. 1. Open the intake grille and remove the screw at the front of

the front grille. 2. Set the vertical airflow direction louver to the horizontal

position.

43

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 44: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3. Slide down the 2 caps on the front grille as shown in theillustration at right, and then remove the 2 mounting screws.Pull the lower section of the front grille towards you toremove the front grille.

When reinstalling the front grille, first set the verticalairflow direction louver to the horizontal position andthen carry out above steps 2 - 3 in the reverse order.

AUTO SWITCH OPERATION

The below operations will be performed by pressing the“AUTO” switch. 1. AUTO OPERATION MODE

The Auto operation will be activated immediately once theAuto Switch is pressed.

2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICINGPURPOSE)The Test Run operation will be activated if the Auto Switchis pressed continuously for more than 5 sec. to below 10sec. A “pep” sound will occur at the fifth sec., in order toidentify the starting of Test Run operation

3. REMOTE CONTROLLER RECEIVING SOUND ON/OFFThe ON/OFF of Remote Controller receiving sound can bechange over by the following steps:a) Release the Auto Switch after Test Run operation isactivated.b) Then, within 20 sec. after (a), press Auto Switch for morethan 5 sec..A “beep” “beep” sound will occur at the fifthsec., then release the Auto Switch.c) Within 20 sec. after (b), press Auto Switch again.Everytime Auto Switch is pressed (within 20 sec. interval),remote controller receiving sound status will be reversedbetween ON and OFF.Long “beep” sound indicates that remote controllerreceiving sound is OFF.Short “beep” sound indicates that remote controllerreceiving sound is ON.

10.6. Outdoor unit10.6.1. SELECT THE BEST LOCATION

(Refer to “Select the best location”section)

10.6.2. INSTALL THE OUTDOOR UNIT

• After selecting the best location, start installation accordingto Indoor/Outdoor Unit Installation Diagram.

1. Fix the unit on concrete or rigid frame firmly and horizontallyby bolt nut. (ø10 mm).

2. When installing at roof, please consider strong wind andearthquake. Please fasten the installation stand firmly withbolt or nails.

10.6.3. CONNECTING THE PIPINGConnecting The Piping To Indoor UnitPlease make flare after inserting flare nut (locate at joint portionof tube assembly) onto the copper pipe. (In case of using longpiping)Connect the piping • Align the center of piping and sufficiently tighten the flare

nut with fingers. • Further tighten the flare nut with torque wrench in specified

torque as stated in the table.

MODEL Piping size (Torque)Gas Liquid

C7DK, C9DK, A7DK, A9DK 3/8” (42 N.m) 1/4” (18 N.m)C12DK, A12DK 1/2” (55 N.m) 1/4” (18 N.m)

Connecting The Piping To Outdoor UnitDecide piping length and then cut by using pipe cutter. Remove

44

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 45: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

burrs from cut edge. Make flare after inserting the flare nut(located at valve) onto the copper pipe.Align center of piping to valves and then tighten with torquewrench to the specified torque as stated in the table.CUTTING AND FLARING THE PIPING

1. Please cut using pipe cutter and then remove the burrs. 2. Remove the burrs by using reamer. If burrs is not

removed, gas leakage may be caused.Turn the piping end down to avoid the metal powderentering the pipe.

3. Please make flare after inserting the flare nut onto thecopper pipes.

45

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 46: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

10.6.4. EVACUATION OF THE EQUIPMENT

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TO EVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPES in thefollowing procedure.

1. Connect a charging hose with a push pin to the Low and High side of a charging set and the service port of the 3-way valve. • Be sure to connect the end of the charging hose with the push pin to the service port.

2. Connect the center hose of the charging set to a vacuum pump. 3. Turn on the power switch of the vacuum pump and make sure that the needle in the gauge moves from 0 cmHg (0 MPa) to

-76 cmHg (-0.1 MPa). Then evacuate the air approximately ten minutes. 4. Close the low side valve of the charging set and turn off the vacuum pump. Make sure that the needle in the gauge does not

move after approximately five minutes.Note: BE SURE TO FOLLOW THIS PROCEDURE IN ORDER TO AVOID REFRIGERANT GAS LEAKAGE.

5. Disconnect the charging hose from the vacuum pump and from the service port of the 3-way valve. 6. Tighten the service port caps of the 3-way valve at torque of 18 N.m with a torque wrench. 7. Remove the valve caps of both of the 2-way valve and 3-way valve. Position both of the valves to “OPEN” using a hexagonal

wrench (4 mm). 8. Mount valve caps onto the 2-way valve and the 3-way valve.

• Be sure to check for gas leakage.

CAUTION • If gauge needle does not move from 0 cmHg (0 MPa) to -76 cmHg (-0.1 MPa), in step 3 above take the following measure:

• If the leak stops when the piping connections are tightened further, continue working from step 3.

• If the leak does not stop when the connections are retightened, repair the location of leak.

• Do not release refrigerant during piping work for installation and reinstallation. Take care of the liquid refrigerant, it may causefrostbite.

10.6.5. CONNECT THE CABLE TO THE OUTDOOR UNIT 1. Remove the control board cover from the unit by loosening the screw. 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 3 × 1.5 mm2 flexible cord,

type designation 245 IEC 57 or heavier cord.

3. Secure the cable onto the control board with the holder (clamper). 4. Attach the control board cover back to the original position with the screw.

46

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 47: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

DISPOSAL OF OUTDOOR UNIT DRAIN WATER

• If the drain elbow is used, the unit should be placed on astand which is taller than 3cm.

• If the unit is used in an area where temperature falls below0° C for 2 or 3 days in succession, it is recommended not touse a drain elbow, for the drain water freezes and the fanwill not rotate.

CHECK THE DRAINAGE

• Open front panel and remove air filters.(Drainage checking can be carried out without removing thefront grille.)

• Pour a glass of water into the drain tray-styrofoam. • Ensure that water flows out from drain hose of the indoor

unit.

EVALUATION OF THE PERFORMANCE

• Operate the unit at cooling operation mode for fifteenminutes or more.

• Measure the temperature of the intake and discharge air. • Ensure the difference between the intake temperature and

the discharge is more than 8°C.

10.6.6. PIPE INSULATION 1. Please carry out insulation at pipe connection portion as mentioned in Indoor/Outdoor Unit Installation Diagram. Please wrap

the insulated piping end to prevent water from going inside the piping. 2. If drain hose or connecting piping is in the room (where dew may form), please increase the insulation by using POLY-E FOAM

with thickness 6 mm or above.

47

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 48: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

CHECK ITEMS

Is there any gas leakage at flare nut connections?

Has the heat insulation been carried out at flare nutconnection?

Is the connecting cable being fixed to terminal board firmly?

Is the connecting cable being clamped firmly?

Is the drainage OK?(Refer to “Check the drainage” section)

Is the earth wire connection properly done?

Is the indoor unit properly hooked to the installation plate?

Is the power supply voltage complied with rated value?

Is there any abnormal sound?

Is the cooling operation normal?

Is the thermostat operation normal?

Is the remote control’s LCD operation normal?

Is the super alleru-buster filter installed?

48

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 49: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11 2-way, 3-way Valve2-way Valve (Liquid Side) 3-way Valve (Gas Side)

Works Shaft Position Shaft Position Service Port

Shipping Close Close Close(With valve cap) (With valve cap) (With cap)

Evacuation Close Close Open(Installation and (Counter-Clockwise) (Clockwise) (Push-pin)Re-installation)

Operation Open Open Close(With valve cap) (With valve cap) (With cap)

Pumping down Close Open Open(Transferring) (Clockwise) (Counter-Clockwise) (Connected manifold

gauge)

Evacuation Open Open Open(Servicing) With vacuum pump

Gas charging Open Open Open(Servicing) (With charging cylinder)

Pressure check Open(Servicing) Open Open (Connected manifold

gauge)

Gas releasing Open(Servicing) Open Open (Connected manifold

gauge)

49

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 50: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11.1.1. Evacuation of Installation

WHEN INSTALLING AN AIR CONDITIONER, BE SURE TOEVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPESin the following procedure.

1. Connect a charging hose with a push pin to the Lowside of a charging set and the service port of a 3-wayvalve. • Be sure to connect the end of the charging hose with the

push pin to the service port. 2. Connect the centre hose of the charging set to a

vacuum pump. 3. Turn on the power switch of the vacuum pump and

make sure that the needle in the gauge moves from 0MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuatethe air for approximately ten minutes.

4. Close the Low side valve of the charging set and turnoff the vacuum pump. Make sure that the needle in thegauge does not move after approximately five minutes.BE SURE TO TAKE THIS PROCEDURE IN ORDER TOAVOID GAS LEAKAGE.

If air remain in the indoor unit and refrigeration pipes, it willaffect the compressor, reduce to cooling capacity, and couldlead to a malfunction.

5. Disconnect the charging hose from the vacuum pumpand from the service port of the 3-way valve.

6. Tighten the service port cap at a torque of 18 N.m witha torque wrench.

7. Remove the valve caps of the 2-way valve and the 3-way valve. Position both of the valves to “open” usinga hexagonal wrench (4 mm).

8. Mount the valve caps onto the 2-way and 3-way valves. • Be sure to check for gas leakage.

CautionIf gauge needle does not move from 0 cmHg to -76cmHg in step (3) above, take the following measures:

If the leaks stop when the piping connections aretightened further, continue working from step (3).

If the leaks do not stop when the connections areretightened, repair the location of the leak.

11.1. Evacuation of the Equipment

Procedure:

50

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 51: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11.1.2. Pumping down

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to

the opened position. • Remove the valve stem caps and confirm that the valve

stems are in the opened position. • Be sure to use a hexagonal wrench to operate the valve

stems. 2. Operate the unit for 10 to 15 minutes. 3. Stop operation and wait for 3 minutes, then connect the

charge set to the service port of the 3-way valve. • Connect the charge hose with the push pin to the Gas

service port. 4. Air purging of the charge hose.

• Open the low-pressure valve on the charge set slightlyto purge air from the charge hose.

5. Set the 2-way valve to the closed position.

6. Operate the air conditioner at the cooling cycle andstop it when the gauge indicates 0 MPa (0 kg/cm2G).If the unit cannot be operated at the cooling condition(weather is rather cool), short the Pumping Down pinson the Main Control P.C.B.(Simply press the pumping down button if it isequipped.)So that the unit can be operated.

7. Immediately set the 3-way valve to the closed position. • Do this quickly so that the gauge ends up indicating 0.1

MPa (1 kg/cm2G) to 0.3 MPa (3 kg/cm2G). 8. Use refrigerant reclaiming equipment to collect

refrigerant from indoor unit and pipes. 9. Disconnect the charge set, and mount the 2-way and 3-

way valve’s stem caps and the service port caps. • Use a torque wrench to tighten the service port cap to a

torque of 18 N.m. • Be sure to check for gas leakage.

10. Disconnect pipes from indoor unit and outdoor unit.

51

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 52: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11.1.3. Evacuation of Re-installation

WHEN REINSTALLING AN AIR CONDITIONER, BE SURE TOEVACUATE THE AIR INSIDE THE INDOOR UNIT AND PIPESin the following procedure.

1. Connect a charging hose with a push pin to the Lowside of a charging set and the service port of the 3-wayvalve. • Be sure to connect the end of the charging hose with the

push pin to the service port. 2. Connect the centre hose of the charging set to a

vacuum pump. 3. Turn on the power switch of the vacuum pump and

make sure that the needle in the gauge moves from 0MPa (0 cmHg) to -0.1 MPa (-76 cmHg). Then evacuatethe air for approximately ten minutes.

4. Close the Low side valve of the charging set and turnoff the vacuum pump. Make sure that the needle in thegauge does not move after approximately five minutes.BE SURE TO TAKE THIS PROCEDURE IN ORDER TOAVOID GAS LEAKAGE.

5. Disconnect the charging hose from the vacuum pump. 6. Charge the pipes and indoor unit with gas refrigerant

from 3-way valve service port, and then discharge therefrigerant until low side (gas side) gauge needleindicates 0.3 MPa (3 kg/cm2).

If air remain in the indoor unit and refrigeration pipes, it willaffect the compressor, reduce to cooling capacity, and couldlead to a malfunction.

7. Tighten the service port cap at a torque of 18 N.m witha torque wrench.

8. Remove the valve caps of the 2-way valve and the 3-way valve. Position both of the valves to “open” usinga hexagonal wrench (4 mm).

9. Mount the valve caps onto the 2-way and 3-way valves. • BE SURE TO USE REFRIGERANT RECLAIMING

EQUIPMENT WHILE DISCHARGING THEREFRIGERANT.

• Purge the air from charge set’s centre hose. • Be sure to check for gas leakage.

CautionIf gauge needle does not move from 0 MPA (0 cmHg)to -0.1 MPa (-76 cmHg) in step (3) above, take thefollowing measures:

If the leaks stop when the piping connections aretightened further, continue working from step 3.

If the leaks do not stop when the connections areretightened, repair the location of the leak.

Procedure:

52

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 53: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

(Lack of refrigerant in the refrigeration cycle)

Procedure: 1. Confirm that both the 2-way and 3-way valves are set to

the open position. 2. Connect the charge set to the 3-way valve’s service

port. • Leave the valve on the charge set closed. • Connect the charge hose with the push-pin to the

service port. 3. Connect the charge set’s centre hose to refrigerant

reclaiming equipment. • Purge the air from charge hose.

4. Open the valve (Low side) on the charge set anddischarge the refrigerant until the gauge indicates 0.05MPa (0.5 kg/cm2G) to 0.1 MPa (1 kg/cm2G). • If there is no air in the refrigeration cycle (the pressure

when the air conditioner is not running is higher than 0.1MPa (1 kg/cm2G), discharge the refrigerant until thegauge indicates 0.05 MPa (0.5 km/cm2G) to 0.1 MPa (1kg/cm2G). If this is the case, it will not be necessary toapply a evacuation.

• Discharge the refrigerant gradually; if it is dischargedtoo suddenly, the refrigeration oil will also bedischarged.

5. Turn on refrigerant reclaiming equipment.

11.1.4. Balance refrigerant of the 2-way, 3-way valves

53

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 54: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

(No refrigerant in the refrigeration cycle)

Procedure: 1. Connect the vacuum pump to the charge set’s centre

hose. 2. Evacuation for approximately one hour.

• Confirm that the gauge needle has moved toward -0.1MPa (-76 cmHg) [vacuum of 4 mmHg or less.]

3. Close the valve (Low side) on the charge set, turn offthe vacuum pump, and confirm that the gauge needledoes not move (approximately 5 minutes after turningoff the vacuum pump).

4. Disconnect the charge hose from the vacuum pump. • Vacuum pump oil

If the vacuum pump oil becomes dirty or depleted,replenish as needed.

11.1.5. Evacuation

54

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 55: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

(After Evacuation)

Procedure: 1. Connect the charge hose to the charging cylinder.

• Connect the charge hose which you disconnected fromthe vacuum pump to the valve at the bottom of thecylinder.

2. Purge the air from the charge hose. • Open the valve at the bottom of the cylinder and press

the check valve on the charge set to purge the air (becareful of the liquid refrigerant).

3. Open the valve (Low side) on the charge set and chargethe system with liquid refrigerant. • If the system cannot be charged with the specified

amount of refrigerant, it can be charged with a little at atime (approximately 150 g each time) while operatingthe air conditioner in the cooling cycle; however, onetime is not sufficient, wait approximately 1 minute andthen repeat the procedure. (pumping down-pin)

This is different from previous procedures. Because you arecharging with liquid refrigerant from the gas side, absolutely dono attempt to charge with large amount of liquid refrigerantwhile operating the air conditioner.

4. Immediately disconnect the charge hose from the 3-way valve’s service port. • Stopping partway will allow the refrigerant to be

discharged. • If the system has been charged with liquid refrigerant

while operating the air conditioner, turn off the airconditioner before disconnecting the hose.

5. Mount the valve stem caps and the service port cap. • Use torque wrench to tighten the service port cap to a

torque of 18 N.m. • Be sure to check for gas leakage.

11.1.6. Gas charging

55

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 56: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Required tools: hexagonal wrench, adjustable wrench, torquewrenches, wrench to hold the joints and gas leak detector.The additional gas for air purging has been charged in theoutdoor unit.However, if the flare connections have not been done correctlyand there gas leaks, a gas cylinder and the charge set will beneeded.

1. Recheck the piping connections. 2. Open the valve stem of the 2-way valve counter-

clockwise approximately 90°, wait 10 seconds, andthen set it to closed position. • Be sure to use a hexagonal wrench to operate the valve

stem. 3. Check for gas leakage.

• Check the flare connection for gas leakage. 4. Purge the air from the system

• Set the 2-way valve to the open position and remove thecap from the 3-way valve’s service port.

• Using the hexagonal wrench to press the valve core pin,discharge for three seconds and then wait for oneminute.Repeat this three times.

5. Use torque wrench to tighten the service port cap to atorque of 1.8 kg.m. (18 N.m).

The air in the indoor unit and in the piping must be purged. If airremains in the refrigeration pipings, it will affect thecompressor, reduce the cooling capacity, and could lead to amalfunction.

6. Set the 3-way valve to the opened position. 7. Mount the valve stem nuts to the 2-way and 3-way

valves. 8. Check for gas leakage.

• At this time, especially check for gas leakage from the 2-way and 3-way’s stem nuts, and from the service portcap.

CautionIf gas leakage is discovered in step (3) above, takethe following measures:

If the leaks stop when the piping connections aretightened further, continue working from step (4).

If the gas leaks do not stop when the connections areretightened, repair the location of the leak, dischargeall of the gas through the service port, and thenrecharge with the specified amount of gas from a gascylinder.

11.2. Air Purging of the Piping and Indoor Unit11.2.1. Air purging (Installation)

Service port capBe sure, using a torque wrench to tighten the service port cap (after using the service port), so that it prevents the gasleakage from the refrigeration cycle.

Procedure:

56

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 57: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

1. Confirm that both the 2-way and 3-way valves are set tothe opened position. • Remove the valve stem caps and confirm that the valve

stems are in the opened position. • Be sure to use a hexagonal wrench to operate the valve

stems.

2. Operate the unit for 10 to 15 minutes.

3. Stop operation and wait for 3 minutes, then connect thecharge set to the service port of the 3-way valve. • Connect the charge hose with the push pin to the Gas

service port.

4. Air purging of the charge hose. • Open the low-pressure valve on the charge set slightly

to purge air from the charge hose.

5. Set the 2-way valve to the close position.

6. Operate the air conditioner at the cooling cycle andstop it when the gauge indicates 1 kg/cm2G (0.1 MPa).

7. Immediately set the 3-way valve to the closed position. • Do this quickly so that the gauge ends up indicating 3 to

5 kg/cm2G (0.3 to 0.5 MPa).

8. Disconnect the charge set, and mount the 2-way and 3-way valve’s stem nuts and the service port caps. • Use a torque wrench to tighten the service port cap to a

torque of 1.8 kg.m (18 N.m). • Be sure to check for gas leakage.

11.2.2. Pumping down (Re-installation)

Procedure:

57

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 58: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11.2.3. Re-air purging (Re-installation)

1. Confirm that both the 2-way and 3-way valves are set tothe closed position.

2. Connect the charge set and a charging cylinder to theservice port of the 3-way valve. • Leave the valve on the charging cylinder closed.

3. Air purging. • Open the valves on the charging cylinder and the

charge set. Purge the air by loosening the flare nut onthe 2-way valve approximately 45° for 3 seconds thenclosing it for 1 minute; repeat 3 times.

• After purging the air, use a torque wrench to tighten theflare nut on the 2-way valve.

4. Check for gas leakage. • Check the flare connections for gas leakage.

5. Discharge the refrigerant. • Close the valve on the charging cylinder and discharge

the refrigerant until the gauge indicates 3 to 5 kg/cm2G(0.3 to 0.5 MPa)

6. Disconnect the charge set and the charging cylinder,and set the 2-way and 3-way valves to the openposition. • Be sure to use a hexagonal wrench to operate the valve

stems.

7. Mount the valve stem nuts and the service port cap. • Be sure to use a torque wrench to tighten the service

port cap to a torque 1.8 kg.m (18 N.m). • Be sure to check for gas leakage.

Procedure:

58

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 59: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

(Gas leakage)

1. Confirm that both the 2-way and 3-way valves are set tothe open position.

2. Connect the charge set to the 3-way valve’s serviceport. • Leave the valve on the charge set closed. • Connect the charge hose with the push pin to the

service port.

3. Open the valves (Low side) on the charge set anddischarge the refrigerant until the gauge indicates 0.5to 1 kg/cm2G (0.05 to 0.1 MPa) . • If there is no air in the refrigeration cycle [the pressure

when the air conditioner is not running is higher than 1kg/cm2G (0.1 MPa)], discharge the refrigerant until thegauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1 MPa). Ifthis is the case, it will not be necessary to apply aevacuation.

• Discharge the refrigerant gradually; if it is dischargedtoo suddenly, the refrigeration oil will be discharged.

11.2.4. Balance refrigerant of the 2-way, 3-way valves

Procedure:

59

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 60: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

(No refrigerant in the refrigeration cycle)

1. Connect the vacuum pump to the charge set’s centrehose.

2. Evacuation for approximately one hour. • Confirm that the gauge needle has moved toward -0.1

MPa (-76 cmHg) [vacuum of 4 mmHg or less.]

3. Close the valve (Low side) on the charge set, turn offthe vacuum pump, and confirm that the gauge needledoes not move (approximately 5 minutes after turningoff the vacuum pump).

4. Disconnect the charge hose from the vacuum pump. • Vacuum pump oil

If the vacuum pump oil becomes dirty or depleted,replenish as needed.

11.2.5. Evacuation (Installation)

Procedure:

60

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 61: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

11.2.6. Gas charging(After Evacuation)

1. Connect the charge hose to the charging cylinder. • Connect the charge hose which you disconnected from

the vacuum pump to the valve at the bottom of thecylinder.

2. Purge the air from the charge hose. • Open the valve at the bottom of the cylinder and press

the check valve on the charge set to purge the air (becareful of the liquid refrigerant).

3. Open the valve (Low side) on the charge set and chargethe system with liquid refrigerant. • If the system cannot be charged with the specified

amount of refrigerant, it can be charged with a little at atime (approximately 150 g each time) while operatingthe air conditioner in the cooling cycle; however, onetime is not sufficient, wait approximately 1 minute andthen repeat the procedure. (pumping down-pin)

This is different from previous procedures. Because you arecharging with liquid refrigerant from the gas side, absolutely dono attempt to charge with large amount of liquid refrigerantwhile operating the air conditioner.

4. Immediately disconnect the charge hose from the 3-way valve’s service port. • Stopping partway will allow the refrigerant to be

discharged. • If the system has been charged with liquid refrigerant

while operating the air conditioner, turn off the airconditioner before disconnecting the hose.

5. Mount the valve stem caps and the service port cap. • Use torque wrench to tighten the service port cap to a

torque of 18 N.m. • Be sure to check for gas leakage.

Procedure:

61

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 62: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

• Electronic controller and Display Complete unit can be seenby following the below removal procedures.

Fig. 1

− Remove the 2 caps and 2 screws at the bottom of theFront Grille.(Fig.1)

Fig. 2

− Remove the Front Grille Complete. (Fig.2)

Fig. 3

− Release the taps on top and on the right side of metalplate cover.(Fig.3)

− Then remove the metal plate cover.(Fig.3) − Remove the indicator complete screw, and then remove

the indicator complete.(Fig.3)

12 Servicing Information12.1. Distinction of Lead Free (PbF) Printed Circuit Board • Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.

CAUTION • Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher.

Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C). • Pb free solder will tend to splash when heated too high (about 1100°F/600°C). • If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb

solder. If this is not pratical, be sure to heat the Pb free solder until it melts, before applying Pb solder.

12.2. Indoor Electronic Controller Removal Procedures

62

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 63: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Fig. 4

− To remove the electronic controller. − Remove the particular piece (Fig.4). − Release CN-FM connector (Fig.4) − Release CN-Sonic connector (Fig.4) − Release CN-FB connector (Fig.4) − Release CN-ION connector (Fig.4)

• Remove Control Board cover

Fig. 6

− Remove the screw on the left side of the unit. (Fig.6) − Pull the hook to the left and lift up the evaporator. (Fig.

6) − Pull down the Discharge Grille Complete. (Fig.6)

− Release CN-TH connector (Fig.4) − Release CN-STM connector (Fig.4) − Release CN-REC/DISP connector (Fig.4)

Fig. 5

− Press the hook to the right then take out the PCB (Fig.5) − Remove Ry-Pwr connector (black and brown) and Ac-

Wht connector from the PCB. (Fig.5)

Fig. 7

Fig. 8

− Remove indoor pipe sensor and air intake sensor fromthe evaporator. (Fig.7)

12.3. Indoor Fan Motor and Cross Flow Fan Removal Procedures

63

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 64: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

− Remove the earth wire from the evaporator. (Fig.7) − Release the generator complete wire (green and red).

(Fig.8) − Remove 2 screws on the right and 1 screw at the left

side of the control board. (Fig.7) − Press down the hook on the left side of control board.

(Fig.7) − Then pull out the Control Board Complete from the unit.

(Fig.7)

Fig. 9

− Remove the cross flow fan bushing from the chassis.(Fig.9)

− Loosen the fan boss screw at the cross flow fan. (Fig.9)

Fig. 10

− Push up the evaporator and remove cross flow fan bypulling both cross flow fan and fan motor. (Fig.10)

12.4. Auto OFF/ON Button • The “Auto OFF/ON Button” (behind the front grille) is used to operate the air conditioner if remote control is misplaced or

mulfunctioning. • Forced cooling operation is possible by pressing the “Auto OFF/ON Button” for more than 5s where “beep” sound is heard then

release the button. • User able to select remote control transmission code and toggle remote control signal receiving sound under various setting

mode. • To enter various setting mode:

− Press the “Auto OFF/ON Button” continuously for 5s (“beep” sound is heard) and release. − Within 20s, press the “Auto OFF/ON Button” continuously for 5s again (2 “beep” sound is heard) and release. − Various setting mode has limit up to 20s. Then return to normal operation.

12.4.1. Toggle Remote Control Signal Receiving Sound • Under various setting mode, press the “Auto OFF/ON Button” to toggle the remote control sound.

− Short “beep”: Turn ON remote control signal receiving sound. − Long “beep”: Turn OFF remote control signal receiving sound.

• After “Auto OFF/ON Button” is pressed, the 20s counter for various setting mode is restarted.

64

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 65: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

• When the batteries are inserted for the first time or thebatteries are replaced, you may notice the indications atremote control’s display screen blink continuously and notfunctionable. If this condition happens, try to reset theremote control by pushing the reset terminal with a pointingdevice.

• You may also do the reset to erase the setting at remotecontrol and restore back the default setting.

12.4.2. Remote Control Transmission Code • There are 4 types of remote control transmission code could be selected and stored in EEPROM of indoor unit. The indoor unit

will only operate when received signal with same transmission code from remote control. This could prevent signal interferencewhen there are 2 or more indoor unit installed nearby together.

• To change remote control transmission code, short or open jumpers at the remote control printed circuit board.

• Under various setting mode, after select the transmission code combination of remote control, press any button of remotecontrol to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.

• After signal is received, the various setting mode is cancelled and return to normal operation.

12.5. Remote Control Reset

65

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 66: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

13.1. Refrigeration cycle systemIn order to diagnose malfunctions, make sure that there is noelectrical problem before inspecting the refrigeration cycle.Such problems include insufficient insulation, problem with thepower source, malfunction of compressor or fan motor.The normal outlet air temperature and pressure of therefrigeration cycle depend on various conditions, the standardvalues for them are shown in the table to the right.

13 Troubleshooting Guide

66

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 67: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

13.2. Relationship between the condition of the air conditioner andpressure and electric current

Cooling ModeCondition of the air

conditioner Low Pressure High Pressure Electric current during operation

Insufficient refrigerant (gasleakage)

Clogged capillary tube orStrainer

Short circuit in the indoor unit

Heat radiation deficiency ofthe outdoor unit

Inefficient compression

• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.

13.3. Diagnosis methods of a malfunction of a compressor

Nature of fault Symptom

• Electric current during operation becomes approximately 20% lower than the normal value.

Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).

• The difference between high pressure and low pressure becomes almost zero.

• Electric current reaches a high level abnormally, and the value exceeds the limit of anammeter. In some cases, a breaker turns off.

Locked compressor • The compressor has a humming sound.

67

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 68: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

14 Technical Data14.1. Thermostat characteristics

14.2. Sensible Capacity Chart

CS-C7DKD220V Outdoor Temp.

Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 1.98 1.50 0.54 1.85 1.44 0.58 1.72 1.39 0.62 1.57 1.32 0.6719.0°C 2.00 0.5919.5°C 2.18 1.57 0.55 2.04 1.51 0.59 1.89 1.46 0.63 1.72 1.39 0.6822.0°C 2.37 1.63 0.56 2.22 1.57 0.60 2.06 1.51 0.64 1.88 1.44 0.70

230V Outdoor Temp.Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 2.00 1.52 0.59 1.87 1.46 0.63 1.74 1.40 0.67 1.58 1.33 0.7319.0°C 2.02 0.6419.5°C 2.20 1.59 0.60 2.06 1.53 0.64 1.91 1.47 0.69 1.74 1.40 0.7422.0°C 2.40 1.65 0.61 2.24 1.59 0.65 2.08 1.53 0.70 1.89 1.46 0.75

CS-C9DKD220V Outdoor Temp.

Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 2.58 1.96 0.73 2.41 1.88 0.79 2.24 1.80 0.84 2.04 1.71 0.9119.0°C 2.60 0.8019.5°C 2.83 2.05 0.75 2.65 1.97 0.80 2.46 1.89 0.86 2.24 1.80 0.9322.0°C 3.09 2.12 0.76 2.88 2.04 0.82 2.68 1.97 0.87 2.44 1.88 0.94

230V Outdoor Temp.Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 2.63 1.99 0.76 2.46 1.91 0.81 2.28 1.84 0.87 2.08 1.75 0.9419.0°C 2.65 0.83

68

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 69: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

230V Outdoor Temp.19.5°C 2.89 2.09 0.77 2.70 2.00 0.83 2.51 1.93 0.89 2.28 1.84 0.9622.0°C 3.15 2.16 0.78 2.94 2.08 0.84 2.73 2.01 0.90 2.49 1.91 0.97

CS-C12DKD220V Outdoor Temp.

Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 3.49 2.65 1.02 3.26 2.54 1.09 3.03 2.44 1.17 2.76 2.32 1.2619.0°C 3.52 1.1119.5°C 3.83 2.77 1.04 3.58 2.66 1.11 3.33 2.56 1.19 3.03 2.44 1.2922.0°C 4.18 2.87 1.05 3.90 2.76 1.13 3.63 2.67 1.21 3.30 2.54 1.31

230V Outdoor Temp.Indoor wetbulb temp.

30°C 35°C 40°C 46°CTC SHC IP TC SHC IP TC SHC IP TC SHC IP

17.0°C 3.51 2.66 1.04 3.28 2.55 1.11 3.05 2.45 1.19 2.78 2.33 1.2819.0°C 3.54 1.1319.5°C 3.86 2.79 1.05 3.60 2.68 1.13 3.35 2.58 1.21 3.05 2.45 1.3122.0°C 4.20 2.89 1.07 3.93 2.78 1.15 3.65 2.68 1.24 3.32 2.56 1.33

TC - Total Cooling Capacity (kW) Indoor 27°C/19°CSHC - Sensible Heat Capacity (kW) Outdoor 35°C/24°CIP - Input Power (kW)

14.3. Operation characteristics14.3.1. CS-C7DK CU-C7DK

69

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 70: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

14.3.2. CS-C9DK CU-C9DK

14.3.3. CS-C12DK CU-C12DK

70

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 71: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

15 Exploded View (Indoor Unit)

Note:The above exploded view is for the purpose of parts disassembly and replacement.The non-numbered parts are not kept as standard service parts.

71

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 72: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

16 Replacement Parts List (Indoor Unit)<Model: CS-C7DKD / CS-C9DKD / CS-C12DKD >REF. NO. PART NAME & DESCRIPTION QTY. CS-C7DKD CS-C9DKD CS-C12DKD REMARKS

1 CHASSY COMPLETE 1 CWD50C1377 ← ←2 FAN MOTOR 1 CWA921181 ← ← 03 CROSS FLOW FAN COMPLETE 1 CWH02C1031 ← ←4 BEARING ASS’Y 1 CWH64K007 ← ←5 SCREW - CROSS FLOW FAN 1 CWH4580304 ← ←6 EVAPORATOR 1 CWB30C1602 CWB30C1676 CWB30C15527 FLARE NUT 1 CWT25078(1/4”) ← ←8 FLARE NUT 1 CWT25005 (3/8”) ← CWT25007 (1/2”)9 INTAKE AIR SENSOR HOLDER 1 CWH32142 CWH32143 ←10 DISCHARGE GRILLE COMPLETE 1 CWE20C2366 ← ←11 VERTICAL VANE 9 CWE241150 ← ←12 CONNECTING BAR 1 CWE261066 ← ←13 CONNECTING BAR 1 CWE261070 ← ←14 AIR SWING MOTOR 1 CWA98260 ← ← 015 LEAD WIRE - AIR SWING MOTOR 1 CWA67C3977 ← ←16 CAP - DRAIN TRAY 1 CWH521096 ← ←17 HORIZONTAL VANE 1 CWE241173 ← ←18 BACK COVER CHASSIS 1 CWD932454 ← ←19 CONTROL BOARD CASING 1 CWH102259 ← ←20 TERMINAL BOARD COMPLETE 1 CWA28C2073 ← CWA28C2075 021 POWER SUPPLY CORD 1 CWA20C2159 ← ←22 ELECTRONIC CONTROLLER - MAIN 1 CWA743652 CWA743653 CWA743663 023 SENSOR COMPLETE 1 CWA50C2122 ← ← 024 CONTROL BOARD FRONT COVER 1 CWH131207 ← ←25 ELEC CONT - INDICATOR AND RCVR 1 CWE39C1115 ← ← 026 INDICATOR HOLDER 1 CWD932429 ← ←27 INDICATOR HOLDER 1 CWD932430 ← ←28 CONTROL BOARD TOP COVER 1 CWH131195 ← ←29 REMOTE CONTROL COMPLETE 1 CWA75C2600 ← ← 030 FRONT GRILLE COMPLETE 1 CWE11C3125 ← ←31 INTAKE GRILLE COMPLETE 1 CWE22C1154 ← ←32 GRILLE DOOR 1 CWE141073 ← ←33 AIR FILTER 2 CWD001144 ← ←34 SCREW - FRONT GRILLE 2 XTN4+16C ← ←35 CAP - FRONT GRILLE 2 CWH521109 ← ←36 DRAIN HOSE 1 CWH851063 ← ←37 INSTALLATION PLATE 1 CWH361067 ← ←38 BAG COMPLETE - INSTALLATION SCREW 1 CWH82C067 ← ←39 FULCRUM 1 CWH621046 ← ←40 ELECTRONIC CONTROLLER - IONIZER 1 CWA743675 ← ←41 CASING - IONIZER 1 CWD932464 ← ←42 CASING - IONIZER 1 CWD932431 ← ←43 ION GENERATOR 1 CWH94C0001 ← ←44 SUPERSONIC AIR PURIFYING DEVICE 1 CWH91C1013 ← ←45 ELEC. CONTROLLER - SUPERSONIC 1 CWA743874 ← ←46 SUPER ALLERU BUSTER FILTER 1 CWD00C1133 ← ←47 FRAME FR AIR FILTER SUPERSONIC 1 CWD011026 ← ←48 FRAME FR AIR FILTER SUPERSONIC 1 CWD011027 ← ←

(Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061). • “O” marked parts are recommended to be kept in stock.

72

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 73: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

17 Exploded View (Outdoor Unit)CU-C7DKD/CU-C9DKD

Note:The above exploded view is for the purpose of parts disassembly and replacement.The non-numbered parts are not kept as standard service parts.

73

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 74: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

CU-C12DKD

Note:The above exploded view is for the purpose of parts disassembly and replacement.The non-numbered parts are not kept as standard service parts.

74

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 75: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

18 Replacement Parts List (Outdoor Unit)<Model: CU-C7DKD / CU-C9DKD / CU-C12DKD>

REF.NO.

PART NAME & DESCRIPTION QTY. CU-C7DKD CU-C9DKD CU-C12DKD REMARKS

1 CHASSY ASS’Y 1 CWD50K2107 ← CWD50K20882 SOUND PROOF MATERIAL 1 CWG302254 ← CWG3022493 FAN MOTOR BRACKET 1 CWD541069 ← CWD5410304 SCREW - FAN MOTOR BRACKET 2 CWH551060 ← CWH5510595 FAN MOTOR 1 CWA951379 ← CWA951263 06 SCREW - FAN MOTOR MOUNT 3 CWH55406 ← ←7 PROPELLER FAN ASS’Y 1 CWH03K1020 ← CWH03K10068 NUT - PROPELLER FAN 1 CWH56053 ← ←9 COMPRESSOR 1 2RS122D5BC02 2PS156D3BB02 2KS206D5AF04 010 ANTI - VIBRATION BUSHING 3 CWH50077 ← CWH5005511 NUT - COMPRESSOR MOUNT 3 CWH56000 ← CWH458206512 CONDENSER 1 CWB32C1627 CWB32C1626 CWB32C121813 CAPILLARY TUBE ASS’Y 1 CWB15K1140 CWB15K1148 CWB15K109014 STRAINER 1 CWB11025 ← ←15 HOLDER COUPLING ASS’Y 1 CWH351047 ← CWH35102316 2-WAY VALVE (LIQUID) 1 CWB021217 ← CWB021116 017 3-WAY VALVE (GAS) 1 CWB011257 ← CWB011148 018 FLARE NUT 1 CWT25078 (1/4”) ← - 019 FLARE NUT 1 CWT25005 (3/8”) ← - 020 OVERLOAD PROTECTOR 1 CWA121050 CWA121091 - 021 HOLDER - O.L.P. 1 CWH7041200 ← -22 TERMINAL COVER 1 CWH171011 ← CWH17101223 NUT - TERMINAL COVER 1 CWH7080300 ← ←24 SOUND PROOF BOARD 1 CWH151074 ← CWH15102325 CONTROL BOARD 1 - - CWH10220226 TERMINAL BOARD ASS’Y 1 CWA28K1064 ← ←27 CAPACITOR - COMPRESSOR 1 DS371206CPNA

(20µF, 370VAC)DS371306CPND

(30µF, 400VAC)DS371356CPNA 0

28 HOLDER CAPACITOR 1 CWH301038 CWH301035 CWH3005729 CAPACITOR - FAN MOTOR 1 DS441205NPQA

(2.0µF, 440VAC)← DS441205NPQA 0

30 CABINET SIDE PLATE (L) 1 CWE041110A ← CWE041031A31 CABINET SIDE PLATE (R) 1 CWE04C1042 ← CWE041037A32 CABINET FRONT PLATE 1 CWE06K1048 ← CWE06K103433 WIRE NET 1 CWD041057A ← CWD04C101134 CABINET TOP PLATE 1 CWE031041A ← CWE031014A35 PLATE - C. B. COVER 1 - - CWH13108836 CONTROL BOARD COVER COMP 1 CWH131193 ← CWH13C106537 HANDLE 1 - - CWE16101038 OPERATION INSTRUCTIONS 1 CWF564402 ← ←39 INSTALLATION INSTRUCTIONS 1 CWF612620CWF612681

CWF612738←←←

←←←

(Note) • All parts are supplied from PHAAM, Malaysia (Vendor Code: 061). • “O” marked parts are recommended to be kept in stock.

75

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 76: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

19 Electronic Circuit Diagram19.1. Indoor Unit

1

2

3

4

C220.01

R5810k

AutoSW

R59 1k

DISPLAY COMPLETE

9

SUPERSONIC COMPLETE

CN-DISP

CN-DISP

8

7

6

5

4

3

2

1

10

2

3

4

5

6

7

8

9

10

1

TIMER/AIR SW(ORG)POWER(GRN)

QUIET(ORG)POWERFUL(ORG)

SUPERSONIC(BLU)

C40147 6.3V

BZ01

BZe

c

b

Q01C143XKTX

R551k

R121k C02

0.01

R885.1k

ELECTRONIC CONTROL UNIT

IC401

3

1

2

+

CN-HA

C230.01

R6010k

C26 0.01

C25 0.01

C24 0.01

D404D403

D401D402

ION(GRN) D405

D406

R401 47

R0710k

R561k

C010.01

R311k

R7810k

C290.1

3

2

1

3

2

1

R6011kR603

1MX601

IC601

R6025.1kC601

0.1

CN-SONICCN-SONIC

1

2

R111k

JP5

SW01

R68100

R13 220

R14 220

R15220

R27 220

R733.3k

R17220

C270.01

C280.01

C350.01

e

c

b

Q09

SCHEMATIC DIAGRAM 1/4

76

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 77: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

3XKTX

R20

R21

R22

R23

R24

R25

D10

D09

D08

D07

D06

D05

R18

R19

D12

D11

P72

P73

P74

P75

P64

P65

P66

P67

P40

P41

P42

P43

P44

P45

P46P47

P50

P51RY-PWR DRIVE SIGNAL

P52

P53

P54

P55

P56

P57

Vss0

VDD0

P30

P31

P32

P33

P34

P35

AN

11

AN

12

AN

13

AN

14

AN

15

AN

16

AN

17

AV

55

VD

D1

P25

P24

P23

SC

K30

S03

0

S13

0

P36

46

41

42

43

44

45

64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49

48

47

40

39

38

37

36

35

34

33

32313029282726252423222120191817

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1P71

TOD

P03

INTP2

INTP1

INTP0

Vss1

X1

X2

IC(VPP)

XT1

XT2

AVref

AN10

RESET

AVDD

1

2

3

4

5

6

7

9

8 16

15

14

13

12

11

10

CN-STM1

12345

12345 (ZH5)

VERTICAL

IC05B1HBGGF00013

IC06B1HBGGF00013

1

2

3

4

5

6

7

9

8 16

15

14

13

12

11

10

R0910k

IC02

5

6

8

3

1RS

DO

DI

R/B

CS

SK 4

VccGND 27

C3EBDG000021

JX2

C050.1 16V

R06 24k

R1010k

AIR TEMP. SENSOR(15k 3950)(20k 3950)

PIPE TEMP. SENSOR

(PH) (RED)CN-TH

4 3 2 1

C040.1 16V

R3020k

C080.1 16V

R3315k

IC01

STEPPINGMOTORDRIVESIGNAL

BUZZER

AUTO OPERATIONTEST RUNREMOTE CONTROLSOUND

TIMER SHORTEN

POWER CLOCK INPUT

REMOTE-CONTROLCOMMAND INPUT

AUTO RESTART GROU ND

POWER

RESET

PIPE TEMP

INTAKE AIR TEMP

DISPLAY

OSC

R77 1k

R74 1k

RY-PWR

JP2

R76 1k

R75 1k

R0443 1/2W

R0543 1/2W

C381000p

C39

SCHEMATIC DIAGRAM 2/4

77

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 78: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

TESTR02 1k

R0110k

R32150k

4.096 MHz(47pF X 2)

R411k

Q03C143XKTX

R441k

C160.01

R3710k

1 2

R38

JX1

C150.01

R43

R7910k

X01

CN-ION

4321

C370.01

Q05C2412KTX

C100.1 16V

JP3 R49 1k

JP4

C173300 35V

C14470 25V

C11100 16V

IC03

G

I 5V12VI

G

IC04

DB01T01

5 8

132

REGULATOR REGULATOR

+~

~

O O

TEMPERATUREFUSE

POWER SUPPLYAC220~240V

50Hz

TO OUTDOOR

RY-PWR

AC-WHT

T 2A L 250V

FUSE P

L

e

c

b

Q08

R6110k

R67

R62

C36

Q07

R646.2k

D01

R636.2k

cb

e

C320.01

C310.01

CN-FM

5

4

3

2

1

CN-FBR361k

3

2

1

FAN MOTOR

C030.047

C-FM

1.5

ZNR01

SS

R01

CR

03

L01125 H

C190.047

C120.1 16V

C2110 50V

cb

e

R66 R48

R291.6k

R03 1.3k

4.7k

10k

R57 12k

C070.1 16V

D16

R47 12k D15

R50100k

C180.1 16V

cb

e

Q06C2412KTXc

b

e R546.2k

R5110k

R5310k

R526.2k

+

Z017.5V

e

c

b

SSR01

Q02C143XKTX

4.7k

10k

e

c

b

1

2

SCHEMATIC DIAGRAM 3/4

78

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 79: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

EH-4P

4321

F1

CH1

VINGNDERR

C2 C1

Q1

Q2

Q4

Q5

R2

c

e

b

4.7k 10k e

b

c

C3 R4

R3

R5

D2 Z01D4

c

e

bC8 D1 D3

R14

R13 R9

R15

R10

R102

-4.2kV

R101 HVCN2

R12

C5

D5

C6

Z02

c

e

b

R6

T1 D101

D102

C101

C7

GNDCN3

HIGH VOLTAGE IONIZER

C12DK

TO INDOOR

1

2

FANMOTOR

CA

PAC

ITO

R

CAPACITOR

COMPRESSOR

GRB

B

B

R

BB

R

Y

SCHEMATIC DIAGRAM 4/4

C7DK/C9DK

TO INDOOR

1

2

FANMOTOR

CA

PAC

ITO

R

CAPACITOROVER LOADPROTECTOR

COMPRESSOR

GR

YB

B

B

R

BB

R

Y

4

1

79

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 80: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

80

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 81: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

How to use electronic circuit diagram

TIMER TABLETest Mode

Name Time (When test point RemarksShort-circuited)

Real Timer 1 hr. 1 min.10 min. 10 sec.1 min. 1 sec.

Time Delay Safety Control 2 min. 58 sec. 0 sec.Forced Operation 60 sec. 0 sec.Time Save Control 7 min. 4.2 sec.Anti-Freezing 4 min. 0 sec.Auto Mode Judgement 20 sec. 0 sec.Soft Dry OFF 6 min. 36 sec.

ON 10 min. 60 sec. Soft Dry: 10 min. operation

Deodorizing Control

Cooling 40 sec. 4 sec.70 sec. 7 sec.20 sec. 2 sec.

180 sec. 18 sec.Soft Dry 40 sec. 4 sec.

360 sec. 36 sec.Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above

2 min. 0 sec.Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.Powerful Mode Operation 15 min. 15 sec.Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.Ion OFF Timer 10 min. 10 sec.

81

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 82: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

19.2. Remote Control

82

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 83: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

19.3. Print PatternIndoor Unit Printed Circuit Board

83

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 84: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

84

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

Page 85: Panasonic Air Conditionerdocshare02.docshare.tips/files/25962/259623507.pdf · Tube material Copper Copper Fin material Aluminium (Pre Coat) Aluminium (Blue Coat) Fin Type Slit Fin

Indicator Printed Circuit Board

85

CS-C7DKD CU-C7DKD / CS-C9DKD CU-C9DKD / CS-C12DKD CU-C12DKD

[PHAAM] Printed in Malaysia