1 PARASOL c PARASOL c - m Installation - Commissioning - Maintenance 2014-08-20 2. PARASOL 24" 2. PARASOL 48" 3. 1. Unit Airflow variant A = PARASOL 24" MF Ø 4.92" PARASOL 48" LF Ø 4.92" PARASOL 48" MF Ø 4.92" PARASOL 48" HF Ø 4.92" PARASOL 48" PF Ø 6.3"

Upload: others

Post on 19-Mar-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PARASOL - swegonnorthamerica.comswegonnorthamerica.com/wp-content/uploads/2017/10/PARASOLc-US-m.pdf · 2 PARASOL c - m Swegon reserves the right to alter specifications 2014-08-20

1

PARASOL cPA

RA

SOL c - m

Installation - Commissioning - Maintenance 2014-08-20

2. PARASOL 24" 2. PARASOL 48"

3.

1.

Unit Airflow variant A =

PARASOL 24" MF Ø 4.92"

PARASOL 48" LF Ø 4.92"

PARASOL 48" MF Ø 4.92"

PARASOL 48" HF Ø 4.92"

PARASOL 48" PF Ø 6.3"

Page 2: PARASOL - swegonnorthamerica.comswegonnorthamerica.com/wp-content/uploads/2017/10/PARASOLc-US-m.pdf · 2 PARASOL c - m Swegon reserves the right to alter specifications 2014-08-20

2

PARASOL c - m

Swegon reserves the right to alter specifications 2014-08-20 www.swegon.com

5.

6. 7.

4.

M8

Max. recommended operating pressure: 230 psi

Max. permissible inlet flow temperature: 140°F

The optional damper must always be mounted with the knob to the left viewed in the direction of primary air flow, see figure 6.

Page 3: PARASOL - swegonnorthamerica.comswegonnorthamerica.com/wp-content/uploads/2017/10/PARASOLc-US-m.pdf · 2 PARASOL c - m Swegon reserves the right to alter specifications 2014-08-20

3

PARASOL cInstallation - Commissioning - Maintenance 2014-08-20

PAR

ASO

L c - m

Water

Side 1 2 3 4

Air

Fan-shape

X-shape Nozzle configuration H M C L

H =

M =

C =

5/16T-25

2

3

4

L =

The optional damper must always be mounted with the knob to the left viewed in the direction of primary air flow, see figure 6.

Page 4: PARASOL - swegonnorthamerica.comswegonnorthamerica.com/wp-content/uploads/2017/10/PARASOLc-US-m.pdf · 2 PARASOL c - m Swegon reserves the right to alter specifications 2014-08-20

4

PARASOL c - m

Swegon reserves the right to alter specifications 2014-08-20 www.swegon.com

PARASOL c 48" LF / Double-module unit

Type Nozzle Side k-factor

LF L 1&3 short 4.15

LF L 2&4 long 10.97

LF M 1&3 short 5.89

LF M 2&4 long 15.52

LF H 1&3 short 10.03

LF H 2&4 long 26.49

LF C 1, 2, 3, 4 0.00

PARASOL c 48" MF / Double-module unit

Type Nozzle Side k-factor

MF L 1&3 short 5.89

MF L 2&4 long 15.52

MF M 1&3 short 8.46

MF M 2&4 long 22.31

MF H 1&3 short 14.35

MF H 2&4 long 37.82

MF C 1, 2, 3, 4 0.00

PARASOL c 48" HF / Double-module unit

Type Nozzle Side k-factor

HF L 1&3 short 8.46

HF L 2&4 long 22.31

HF M 1&3 short 14.71

HF M 2&4 long 38.79

HF H 1&3 short 23.17

HF H 2&4 long 61.10

HF C 1, 2, 3, 4 0.00

PARASOL c 24" MF / Single-module unit

Type Nozzle Side k-factor

MF L - 8.46

MF M - 14.71

MF H - 23.17

MF C - 0.00

Example Product Code: PARASOL c 48-A-HF-HLMH

Side 1 = H k=23.2

Side 2 = L k=22.3

Side 3 = M k=14.7

Side 4 = H k=61.1

k-factor HLMH = 23.2+22.3+14.7+61.1=121.3

PARASOL c 48"PF / Double-module unit

Type Nozzle Side k-factor

PF L 1&3 short 28.16

PF L 2&4 long 74.27

PF M 1&3 short 33.14

PF M 2&4 long 87.34

PF H 1&3 short 40.49

PF H 2&4 long 106.74

PF C* 1&3 short 18.59

PF C* 2&4 long 49.05

* Parasol c 1200 PF with nozzle C is not completely closed

1200

Värme retur/Heating return

Kyla tillopp/Cooling supply

Kyla retur/Cooling return

Värme tillopp/Heating supply

1200

Värme retur/Heating return

Kyla tillopp/Cooling supply

Kyla retur/Cooling return

Värme tillopp/Heating supply

PARASOL LF, MF and HF

PARASOL PF

Nozzle L, M and HNozzle C

Nozzle L, M and HNozzle C

Page 5: PARASOL - swegonnorthamerica.comswegonnorthamerica.com/wp-content/uploads/2017/10/PARASOLc-US-m.pdf · 2 PARASOL c - m Swegon reserves the right to alter specifications 2014-08-20

5

PARASOL cInstallation - Commissioning - Maintenance 2014-08-20

PAR

ASO

L c - m

OPEN THIS SIDE

OPEN THIS SIDE

OPEN THIS SIDE

31

2

4

5