parc elise - aermec cover page · 2 aermec – air cooled chillers ch-1, ch-2 plenum condenser fans...

13
344 Harbour Avenue North Vancouver, BC Canada V7J 2E9 SHOP DRAWINGS FOR APPROVAL NOTE: Return of reviewed submittal constitutes a release to production unless otherwise noted. Subsequent changes to the units may delay the equipment production lead time noted. Cancellation or change order costs may apply. January 8, 2016 Olympic International File #: 7056.TN Submitted by: Pablo Gutierrez Project: Parc Elise Contractor: 49 North Mechanical Engineer: Williams Engineering Lead time: 15 Weeks* * from return of approved submittals Qty. Description Tag 2 AERMEC – Air Cooled Chillers CH-1, CH-2 Plenum condenser fans c/w modulating VFD Dual circuit machines, scroll compressors. 575/3/60 electrical BACNET Interface Start Up included

Upload: others

Post on 19-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

344 Harbour AvenueNorth Vancouver, BC

Canada V7J 2E9

SHOP DRAWINGS FOR APPROVAL

NOTE: Return of reviewed submittal constitutes a release to production unless otherwise noted. Subsequent changes to the units may delay the equipment production lead time noted. Cancellation or change order costs may apply.

January 8, 2016

Olympic International File #: 7056.TN Submitted by: Pablo Gutierrez

Project: Parc Elise Contractor: 49 North Mechanical Engineer: Williams Engineering Lead time: 15 Weeks* * from return of approved submittals

Qty. Description Tag

2 AERMEC – Air Cooled Chillers CH-1, CH-2 Plenum condenser fans c/w modulating VFD Dual circuit machines, scroll compressors. 575/3/60 electrical BACNET Interface Start Up included

mdixon
Stamp

�1�/�&���ˆ�˘���$�-

SUBMITTALS

shawn
Text Box
Text

Book Page 2

Magellano v3.26.2 - Aermec S.p.A.

Model: NLC0750°°°A°J°00 Cooling

Capacity ton 55.65Input power kW 50.71Input current A 94.74E.E.R. Btu/W 13.18E.S.E.E.R. W/W 4.27 Available static pressure Pa 120Dry bulb air inlet temperature °F 82.00 Inlet water temperature °F 55.00Temperature difference °F 10.01Outlet water temperature °F 45.00 Ethylene glycol % 0 Water flow rate gph 8,008Pressure drops W.G. in 99.84

Data declared according to UNI EN 14511:2013

Aermec participates in the Eurovent Certification Programme. The certified data of certified models are listed in the Eurovent Directory.

��

Unit NOMENCLATURE

��

3

��

Air to water chiller

Range �6�X�S�S�O�\���D�Q�G���S�O�D�F�H�P�H�Q�W���R�I���W�K�H���O�D�W�H�V�W���J�H�Q�H�U�D�W�L�R�Q���1�/�& series air to water unit;

�U�H�Y�H�U�V�L�E�O�H���R�Q���F�K�L�O�O�H�U���V�L�G�H���E�\���U�H�O�H�Y�D�Q�W���Y�D�O�Y�H�����7�K�H���P�D�F�K�L�Q�H���L�V���V�X�L�W�D�E�O�H���I�R�U���L�Q-

door installation and has an IP24 protection level.

Cooling circuit Two independent cooling circuits that allow to keep the machine running even when the

compressor must be repaired.

Refrigerant �7�K�H���F�K�L�O�O�H�U�V���L�Q���W�K�H���1�/�& series use the almost azeotropic mixture of HFC R410A as refrigerant;

it is characterized by ODP (ozone depletion potential) nil and is classified within the safety

group A1 according to the ASHRAE 34-1997 standard. Thanks to its physical characteristics it

allows to realise up to 10% more efficiency than equivalent models with R407C. Moreover, it

being an “almost azeotropic” mixture it is characterized by a negligible shift in the composition

even in the case of leakage.

Support frame Made in hot galvanized sheet steel with suitable thickness and painted with polyester powders

able to resist atmospheric agents through time.

Composition �8�Q�L�W���F�R�P�S�R�V�H�G���R�I���D���I�U�D�P�H���Z�L�W�K���R�Q�H���P�R�G�X�O�H housing a refrigerant-�Z�D�W�H�U���H�[�F�K�D�Q�J�H�U

Description of the compressors The scroll-type hermetic compressors mounted on the N�/�&�V���D�U�H���R�S�W�L�P�L�]�H�G���W�R���Z�R�U�N���Z�L�W�K���5�������$��refrigerant and are characterized for high efficiency and low power absorption. As standard, it

is also equipped with the sump anti-freeze electrical resistance. This is powered automatically

at every stop, so that the unit is kept live. They are moved by 2-pole electric motors with inter-

nal circuit breaker protection, cooled by intake gas. They are assembled on rubber anti-vibration

mounts positioned at the base. To reduce sound emission to a maximum, the compressors are

enclosed inside an acoustically insulated compartment.

The use of several scroll compressors, used according to plant load requirements, allows effi-

cient “step” adjustment of the power issued by the unit, obtaining a much more efficient func-

tioning of the partial loads. All of this translates into noteworthy seasonal energy efficiency ra-

tios ESEER, calculated according to Eurovent specifications.

4

� ̆

Evaporator

Cooling only: Just one plate type, high efficiency dry expansion water-refrigerant exchanger

braze welded AISI 316 stainless steel with two independent circuits on refrigerant side and one

on the water side, with closed cell external insulation in order to prevent the formation of con-

densation and to reduce heat loss. The anti-freeze electric resistance is mounted as per standard:

its functioning is controlled by a dedicated probe positioned in the heat exchanger itself; activa-

tion is managed by the circuit board and takes place when the temperature of the water is 37.4°F

(default value, which can be modified). Respect the PED standard.

Description of the cooling circuit

Realized using copper pipes with welded joints in silver alloy including the following compo-

nents as well as the compressors and exchangers:

For cooling only:

thermostatic valve that modulates the flow of gas depending of the refrigerant load;

mechanical dehydrator filter realized in ceramics and hygroscopic material, able to withhold

impurities and any traces of humidity present in the cooling circuit;

liquid indicator used to check the refrigerant gas load and the eventual presence of humidity

in the cooling circuit;

liquid and pressing line taps that allow to interrupt the refrigerant in the case of extraordinary

maintenance;

solenoid valve on the liquid line that closes when the compressor switches off, blocking the

flow of refrigerant gas to the evaporator.

mdixon
Callout
Supplier to confirm that "welded" joints are in fact brazed, per CSA B52 requirements. [mdixon]

5

� ̌

Electric Control Board

Contains the power section and the management of controls and safety devices. It is in compli-

ance with the LVD 2006/95/CE Directive and the Directives regarding electromagnetic com-

patibility EMC 2004/108/CE. Moreover, all cables are numbers for immediate recognition of all

electric components.

It is always equipped with a door-lock isolating switch: the electric control board can be ac-

cessed by removing the voltage. Act on the opening lever of the control board itself. This lever

can be locked using one or more padlocks during maintenance interventions to prevent the ma-

chine being powered up accidentally. Inside the control board is a control keyboard that allows

complete control of the appliance.

Safety devices and protections

The following devices are always present in the chiller:

High pressure switch with fixed calibration (580 psi) and manual resetting: it is positioned

on the pressing line side of the compressor and stops functioning of the compressor itself in the

case of anomalous working pressures.

High pressure transducer: it is positioned on the pressing line side of the compressor and

stops functioning of the compressor itself in the case of anomalous working pressures.

Low pressure transducer with lower pressure switch function. It is positioned on the com-

pressor intake line. It stops compressor functioning when anomalous working pressures occur.

6

� ̂

Cooling circuit safety valves, the one on the low pressure side is calibrated at 435 psi and

that on the high pressure side at 653 psi: they intervene by discharging the overpressure in the

case of anomalous pressures.

The electric control board is protected by an access door interlock system: This lever can be

locked using one or more padlocks during maintenance interventions to prevent the machine

being powered up accidentally.

Also present:

compressors magnet circuit-breaker protection;

fans magnet circuit-breaker protection;

auxiliary circuit magnet circuit-breaker protection;

exhaust gas temperature control thermostat for every circuit.

Transducers

The unit is supplied complete with: input and output water temperature probe. In this way it is

possible to activate the compressors in order to keep the temperature of the water produced or

the temperature of the plant return water constant. The chiller also has high pressure transducers

(one per circuit): these allow to view the values of the compressor delivery pressure on the mi-

croprocessor board display. Low pressure transducers are also present (one per circuit): these

allow to view the compressor intake values on the board display; these are installed on the low

pressure side of the chiller circuit and stop functioning of the compressor in the case of anoma-

lous working pressures.

Electronic adjustment

The microprocessor has the following functions:

Cooling only:

Complete management of the machine.

Temperature adjustment by means of step thermo stating controlled on the water inlet of the

chiller (with proportional control) or on outlet (with proportional + total control).

Complete compressor management for compressor times (stand-by between peaks, stand-by

between switch off and switch on, minimum functioning time etc.) and rotation of the compres-

sors on the basis of the working hours and minimum stand-by times (favoring machine effi-

ciency and precision regarding water temperature).

Management of any chiller anomalies by: automatic pre-alarms with re-arm, alarms, histori-

cal anomalies to ease diagnosis of the fault.

Display of all main sizes regarding chiller functioning.

Possibility of changing the main functioning parameters.

Cold functioning management with: Desuperheater (accessory) or total recovery (accessory)

and possible hydraulic side flow switch on the recovery circuit.

7

� ̇

Anti-freeze management on the evaporator by means of resistances

Double set-point, both summer and winter pre-set in the menu and can be selected via po-

tential-free contact.

Power reduction function can be inserted via potential-free contact.

Step safety capacity control management for high pressure and anti-freeze.

Daily/weekly timer programmer with 2 time periods (accessory PGS). The board also allows to display all functioning parameters read by the probes, such as tem-

perature of the water, delivery pressure etc.

�˝

����

�+�H�L�J�K�W�������$�������˙�ˇ���˘���L�Q�:�L�G�W�K���������%���������˝���������L�Q�'�H�S�W�K�������&�����������������L�Q

shawn
Text Box
Text
shawn
Text Box
Text

����

��

mdixon
Text Box
Supplier to confirm that all line voltage electrical components are approved or tested by an appropriate Canadian agency (CSA, ULc, ETL etc). [mdixon]
mdixon
Text Box
Supplier to provide complete wiring diagrams, labeled in English, including low voltage control terminals, transformers required, external controllers etc. Diagrams shall be legible (of sufficient resolution). [mdixon]
mdixon
Text Box
Supplier to provide complete electrical data, including unit FLA and RLA data. [mdixon]

�+�\�G�U�D�X�O�L�F���F�R�Q�Q�H�F�W�L�R�Q�V�����L�Q���R�X�W���˛���ˇ�����˘���P�P��

����

TNaughton
Text Box
2.5" Connections
mdixon
Text Box
Supplier to confirm minimum required clearances for installation on all sides of units. [mdixon]
mdixon
Text Box
Supplier to confirm unit weight. [mdixon]