passive building design and integration with intermittent renewable ... · integration with...

83
Passive Building Design and Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University of Toronto [email protected] 19 April 2012

Upload: others

Post on 19-Jun-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Passive Building Design and

Integration with Intermittent

Renewable Energy Sources

L.D. Danny Harvey

Department of Geography

University of Toronto

[email protected]

19 April 2012

Page 2: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

REDUCING HEATING ENERGY USE

• Reduce the heat load (the amount of heat

that needs to be provided)

• Provide the required heat as efficiently as

possible

Page 3: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Thermal Envelope

• Insulation

• Windows and doors

• Curtainwalls in commercial buildings

• Air leakage

• Double skin façades

Page 4: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.9 Wall and Ceiling Heat Loss

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0 10 20 30 40 50 60

Re

lati

ve

He

at

Lo

ss

R-Value

Walls at R12 (RSI 2.1, U=0.47 W/m2/K)

Walls at R20 (RSI 3.52,U=0.28 W/m2/K)

Roof at R32 (RSI 5.6,U=0.18 W/m2/K)

Walls (R40, RSI 7.0)Roof (R60, RSI 10.6)

Advanced House:

RSI-Value

0 2 4 6 8 10

Page 5: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The heating requirement is the residual (or

difference) between heat loss, useful passive heat

gain, and useful internal heat gain – so a given

percentage reduction in heat loss has a

disproportionately larger effect in reducing the

heating requirement

Page 6: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Greater sensitivity of heating requirement than of

heat loss to changes in the amount of insulation

Source: Danny Harvey

0

20

40

60

80

100

120

100 units

heat loss

Passive Heat

Gain

Internal Heat Gain

80 units

heating

requirement

50 units

heat loss

30 units

heating

requirement

Page 7: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Windows: Benchmark

• A single-glazed, non-coated window has a U-value of about 5 W/m2/K – so the rate of heat loss is 200 W/m2 when the outdoor temperature is -20ºC and the indoor temperature is +20ºC

• The best commercially-available high-performance window will have a centre-of-glazing U-value of 0.5 W/m2/K – so the heat loss will be a factor of 10 smaller!

Page 8: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The normal practice in building design is to place the

heaters or warm-air vents below the window. This is

because normally there is large heat loss from the

window, so heating at the base of the window

• Keeps the window warm, thereby avoiding radiant asymmetry

• Prevents drafts

• Prevents condensation on the window

With high performance windows, the heat loss is

so low that the heaters can be placed on the side

of the room near the core of the building, thereby

reducing costs (and reducing heat loss even further)

Page 9: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.13 Required window U-value at which

perimeter heating can be eliminated as a function

of the coldest designed-for temperature

0

1

2

3

4

-30 -20 -10 0 10

Design Temperature (oC)

Win

do

w U

-valu

e (

W/m

2 /K

)

Perimeter Heating

Not Needed

Perimeter Heating

Needed

Page 10: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Passive Solar Heating

• Direct gain

• Solar collectors

• Air-flow windows

Page 11: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Not all solar gain is usable – some leads to

overheating, requiring the windows to be opened

To maximize the useful solar gain, thermal mass (such

as concrete or stone) is needed and should be

exposed to the indoor air (so minimize interior

finishings) (this is the new look anyway in many

buildings now)

With thermal mass, absorbed solar energy goes into

storing heat with minimal temperature rise (apart from

being uncomfortable, high temperatures result in

greater radiant and convective heat loss, and thus less

heat available for later)

Page 12: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

At night, the heat is slowly released when there is

high thermal mass. This is adequate if the building

is highly insulated with high-performance windows.

If there is too large a glazing fraction (which

typically means > 60%), there will be more solar

gain than can be used, and greater heat loss at

night

Page 13: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Heat Pump, Operating Principles

• Heat pumps transfer of heat from cold to warm (against the macro temperature gradient)

• At each point in the system, heat flow is from warm to cold

• Heat pumps rely on the fact that a gas cools when it expands, and is heated when it is compressed, creating local temperature gradients contrary to the macro-gradient

Page 14: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Components of a heat pump

• Compressor

• Evaporator

• Condenser

Page 15: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.23a Heat pump in heating mode

Indoor air(20 C)

Blower

Heated air (30 C)

High-pressure refrigerant (60 C)

O

O

OExpansion device

Compressor

Reversing valve

Fan

Outdoor air

(0 C)

O

Low-pressurerefrigerant (-10 C)

O

Outdoor coil asevaporator

Reject air

(-5 C)O

Indoor coil as condenser

Page 16: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.23b. Heat pump in cooling mode

Indoor air(25 C)

Blower

Cooled air (15 C)

High-pressure refrigerant (60 C)

O

O

Expansion device

Compressor

Reversing valve

Fan

Outdoor air

(30 C)

O

Low-pressure

refrigerant (-10 C)

O

Outdoor coil ascondenser

Reject air

(35 C)O

Indoor coil as evaporator

O

Page 17: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The Efficiency of a Heat Pump depends not

only on the heat pump itself, but also on the

entire system to which it is connected.

• The ratio of heat delivered to energy input is called the coefficient of performance (COP)

• In heating mode, the COP will be larger the warmer the source of heat and the cooler the temperature at which the heat is delivered (e.g, delivering heat at 30 C instead of at 90 C)

• In cooling mode, the COP will be larger the cooler the heat sink (such as the outside air or ground) and the warmer the temperature at which coldness is distributed (e.g, delivering coldness at 18 C rather than at 6 C)

Page 18: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.24a: Heat Pump COP in heating mode

0

2

4

6

8

10

-20 -15 -10 -5 0 5 10 15

Evaporator Temperature (oC)

He

ati

ng

CO

P

30oC

50oC

70oC

90oC

Condenser

Temperature:

nc=0.65

Page 19: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Large wall-mounted radiator in a daycare centre in Frankfurt

– an inexpensive alternative to radiant floor heating

Source: Danny Harvey

Page 20: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.24b: Heat Pump COP in Cooling Mode (or

chiller COP)

0

4

8

12

30 35 40 45 50

Condenser Temperature (oC)

Co

oli

ng

CO

P

10oC

5oC

0oC

Evaporator

Temperature:

nc=0.65

-5oC

-10oC

Page 21: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.48 Chilled Ceiling cooling panels

Source: www.advancedbuildings.org

Page 22: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Sources of heat for a heat pump:

• The outside air (gives an Air-Source Heat Pump)

• The ground (gives a Ground-Source Heat Pump,

now quite incorrectly called “geothermal heating”

by vendors of this equipment)

• The exhaust air (gives an Exhaust-Air Heat

Pump – now standard practice for new houses in

Sweden) (extracts more heat from the outgoing

exhaust air than a simple heat exchanger)

Page 23: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.26a Ground Source Heat Pump, horizontal pipes

Foundation Wall

S upplyR unouts

30 m

R eturnR unouts

84 m

30 m x 84 mavailable surface area

(a)

Source: Caneta Research Inc (1995, Commercial/Institutional Ground-Source Heat Pump Engineering Manual,

American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta)

Page 24: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.26b Ground Source Heat Pump, vertical pipes

15 m

15 m x 46 m

available surface area

46 m

Foundation Wall SupplyRunouts

Return Runouts

(b)

Source: Caneta Research Inc (1995, Commercial/Institutional Ground-Source Heat Pump Engineering Manual,

American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta)

Page 25: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The ground is a better source of heat than the air

because, during the winter, the ground might be at

8-10ºC while the outside air is at -20ºC.

Conversely, during the summer the ground will be

cooler than the air and so it is a good heat sink

Page 26: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

A high-performance envelope saves fossil

fuel energy in 3 ways

• By reducing the heating load (the amount of

heat that needs to be provided)

• By increasing the efficiency of a furnace, boiler

or (especially) of a heat pump in providing the

required heat

• By providing flexibility as to when heat is

provided (this flexibility is amplified if the building

has a high thermal mass)

Page 27: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

REDUCING COOLING

ENERGY USE

• Reduce the amount of heat that a building receives, thereby reducing the cooling load (the amount of the heat that needs to be removed)

• Use passive and low-energy techniques to meet as much of the cooling load as possible

• Use efficient equipment and systems to meet the remaining cooling load

Page 28: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Reducing Cooling Loads

• Building orientation and clustering

• High-reflectivity building materials

• External insulation

• External shading devices

• Windows with low SHGC

• Thermal mass

• Vegetation (provides shading and evaporative cooling)

• Efficient equipment and lighting to reduce internal heat gains

Page 29: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Low-energy Cooling Techniques

• Natural (passive) ventilation

• Hybrid (passive-mechanical) ventilation

• Mechanical ventilation at night (combined with thermal mass and external insulation)

• Evaporative cooling

• Earth-pipe cooling

Page 30: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Natural driving forces for air flow:

• Wind forcing

• Temperature differences (which create

pressure differences)

Page 31: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Wind forcing:

• Cross ventilation

• Wing walls

• Wind catchers

• Wind cowls

Page 32: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Cross-ventilation

Source: Givoni (1998), Passive and Low Energy Cooling of Buildings,

von Nostrand Reinhold, New York

Page 33: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Wing walls:

Source: Givoni (1998), Passive and Low Energy Cooling of Buildings,

von Nostrand Reinhold, New York

Page 34: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Winds catchers in Iran and Doha

Source: Koch-Nielsen (2002), Stay Cool: A Design Guide for the Built Environment

in Hot Climates, James and James, London

Page 35: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Wind catcher at Sir Sanfred Fleming

College, Peterborough, Canada

Source: Loghman Azar, Line Architects, Toronto

Page 36: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Airflow at Sir Sanfred Fleming College,

Peterborough, Canada

Source: Loghman Azar, Line Architects, Toronto

Page 37: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Wind cowl

Source: www.arup.com

Page 38: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Thermally-driven ventilation

• Atria

• Solar chimneys

• Cool towers

Page 39: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.30 Solar chimneys on the Building Research

Establishment (BRE) building in Garston, UK

Source: Copyright by Dennis Gilbert, View Pictures (London)

Page 40: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Earth-pipe cooling

• Ventilation air is first drawn through underground

pipes so as to be cooled by the ground

• COP (cooling over fan energy) of 7-50 obtained

(depending on ground and air temperatures)

• Airflow can also be driven with solar chimneys

Page 41: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.36: Jaer School, Norway – combining

solar chimneys and earth-pipe cooling

Source: Schild and Blom (2002, Pilot Study Report: Jaer School, Nesodden

Municipality, Norway, International Energy Agency, Energy Conservation in

Buildings and Community Systems, Annex 35, hybvent.civil.auc.dk)

Page 42: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Atria and stair wells can also serve

as solar chimneys, driving a natural

ventilation if so-designed

Page 43: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

EnergyBase building, Vienna

Source: Danny Harvey

Page 44: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Adjustable external shading

Source: Danny Harvey

Page 45: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Windows on south facade are slightly overhanging

Source: Ursula Schneider, Pos Architekten, Vienna

Page 46: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Exhaust air is overheated by passing through a

sort of solarium, then passes through a heat

exchanger to heat the incoming fresh air to a

greater extent than would be possible with a

conventional heat exchanger system. And unlike

systems for passive solar preheating of ventilation

air, we still get the benefit of heat recovery on the

exhaust air at night

Page 47: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

EXEMPLARY BUILDINGS

FROM AROUND THE WORLD

Page 48: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The German Passive Standard:

• A heating load of no more than 15 kWh/m2/yr,

irrespective of the climate, and

• A total on-site energy consumption of no more

than 42 kWh/m2/yr

• For cooling-dominated climates, the standard is

a cooling load of no more than 15 kWh/m2/yr

Page 49: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Current average residential

heating energy use:

• 60-100 kWh/m2/yr for new residential buildings

in Switzerland and Germany

• 220 kWh/m2/yr average of existing buildings in

Germany

• 250-400 kWh/m2/yr for existing buildings in

central and eastern Europe

• 150 kWh/m2/yr average of all existing (single-

family and multi-unit) residential buildings in

Canada

Page 50: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Estimated fuel energy use (largely for heating) in

Canadian multi-unit residential buildings

0

50

100

150

200

Hal

ifax

Toronto

Win

nipeg

Reg

ina

Cal

gary

Van

couve

r

White

horse

R-2

000

(Edm

onton)

R-2

000

(Toro

nto)

Fu

el U

se (

kW

h/m

2/y

r)

Passive

House

Standard

Source: Danny Harvey

Page 51: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Climate Comparisons, Heating Season

0

1000

2000

3000

4000

5000

6000

Edm

onton

Win

nipeg

Toronto

Van

couve

r

Ber

lin

Vie

nna

Hel

sinki

Hea

tin

g D

eg

ree

Da

ys

(K

-day

s)

Source: Danny Harvey

Page 52: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

To achieve the Passive House standard on the

heating side requires

• High levels of insulation (U-values of 0.10-0.15 W/m2/K, R35-R60)

• High performance windows (usually TG, double low-e, argon-filled)

• Meticulous attention to avoidance of thermal bridges

• Meticulous attention to air-tightness

• Mechanical ventilation with heat recovery

• Attention to building form (achieving the standard is much easier in multi-unit than single family housing)

Page 53: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Thermally-

separated

balconies in

Frankfurt

Source: Danny Harvey

Page 54: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Occurrence of buildings meeting the

Passive House Standard:

• Several thousand houses have now been built to

and certified (based on measurements after

construction) to have achieved the PH standard

in Germany, Austria and many other countries in

Europe

• The standard has also been successfully

achieved in schools, daycare centres, nursing

homes, gymnasia and a savings bank

Page 55: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

The PH standard is now the legally

required building standard in many cities

and towns in Germany and Austria

• City of Frankfurt: since 2007, all municipal buildings must meet the standard

• City of Wels, Austria: same thing since 2008

• Vorarlberg, Austria: Passive Standard is mandatory for all new social housing

• Freiberg, Germany: all municipal buildings must meet close to the PH standard

• City of Hanover: since 2005, all new daycare centres to meet the Passive House standard (resolution only – legal status not clear)

Page 56: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Explosive growth in the number of buildings meeting the Passive

House standard in Austria

0

2000

4000

6000

8000

10000

12000

2000 2001 2002 2003 2004 2005 2006 2007 2008 2009 2010

Num

ber

of D

welli

ng U

nits

New during current year

Finished at start of year

Page 57: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Biotop Office Building, Austria

Page 58: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

High school example: Grandschule in

Riedberg, Frankfurt

Page 59: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

South facade

Source: Danny Harvey

Page 60: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Triple-glazing throughout, maximized passive solar heat gain

Source: Danny Harvey

Page 61: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Retractable external shading

Source: Danny Harvey

Page 62: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Passive ventilation and night-time cooling; mechanical

system shut off from ~ early May to end of September

Source: Danny Harvey

Page 63: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Heating required during the winter for only a couple of

hours Monday mornings, using two small biomass-pellet

boilers

Source: Danny Harvey

Page 64: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Commercial Buildings:

The key to achieving savings in new

buildings of 50-75% in overall energy use

compared to recent conventional is in the

design process.

Page 65: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

To achieve ultra-low-energy office

buildings requires

• Attention to building form, glazing fraction, thermal mass (all four facades will not be identical!)

• Attention to insulation levels and glazing properties

• Provision for passive ventilation (even on 50-story office towers), daylighting, heat recovery

• Almost mandatory use of demand-controlled displacement ventilation with radiant slab heating and cooling

• Lots of attention to control systems

Page 66: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

In complex buildings, the usual largely

linear design process needs to be

replaced with the Integrated Design

Process (IDP), in which

• The building is treated as a system

• Architects, engineers of various sorts, and specialists get together at the very beginning of the design process

• Multiple options for achieving deep energy savings are considered, then tested with building computer simulation specialists in order to find the optimal solution

Page 67: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.79a Conventional design process when

client will not occupy the building

Building design process

Level 1:

Client Architect Engineers

Government

Contractors

Source: Hien et al (2000, Building and Environment 35, 709-736, http://www.sciencedirect.com/science/journal/03601323)

Page 68: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.79b Conventional design process when

the client will occupy the building

Building design process

Level 2:

Client Architect Engineers

Government

Contractors

Source: Hien et al (2000, Building and Environment 35, 709-736, http://www.sciencedirect.com/science/journal/03601323)

Page 69: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.79c Integrated Design Process

Client Architect Engineers

Government

Contractors

Simulation team

Dynamic integration in design process

Design Team

Level 3:

Source: Hien et al (2000, Building and Environment 35, 709-736, http://www.sciencedirect.com/science/journal/03601323)

Page 70: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Integrated Design Process: Principles

• Consider building orientation, form, shape, thermal mass and glazing fraction

• Specify a high-performance thermal envelope

• Maximize passive heating, cooling, ventilation and day-lighting

• Install efficient systems to meet remaining loads

• Ensure that individual energy-using devices are as efficient as possible and properly sized

• Ensure that systems and devices are properly commissioned

Page 71: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

My Rating of architects & design teams:

• Can’t deliver 25% savings: totally incompetent, fire them all

• Can deliver 50% savings: competent and knowledgeable team

• Can deliver 75% or greater savings at little or no additional construction cost: truly outstanding

Page 72: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Retrofits of existing buildings

• Insulation

• Windows

• Air sealing

• Mechanical systems

• Lighting

• Solar measures

Page 73: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Renovations to the Passive House

Standard (15 kWh/m2/yr heating load)

• Dozens carried out in old (1950s, 1960s) multi-unit residential buildings in Europe, resulting in 80-90% reduction in heating energy use

• Two examples will be shown here:

-BASF buildings in Ludwigshafen, Germany

- apartment block in Dunaújváros, Hungary

Page 74: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.83 BASF retrofit, before and after

Source: Wolfgang Greifenhagen, BASF

Page 75: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.84 BASF retrofit (a) installation of external insulation, (b)

installation of plaster with micro-encapsulated phase change materials

Source: Wolfgang Greifenhagen, BASF

Page 76: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Figure 4.85 Renovation to the Passive House

Standard in Dunaújváros, Hungary. Before:

Source: Andreas Hermelink, Centre for Environmental Systems Research,

Kassel, Germany

Page 77: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

After:

Source: Andreas Hermelink, Centre for Environmental Systems Research,

Kassel, Germany

Page 78: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Net result:

• 90% reduction in heating energy use – this saves natural gas that can be used to generate electricity at 60% efficiency (or even higher effective efficiency in cogeneration), thereby serving as an alternative to new nuclear power plants

• Problems of summer overheating were greatly reduced

• A grungy, deteriorating building was turned into something attractive and with another 50 years at least of use

Page 79: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

In Toronto and some other North

American cities

• There are opportunities for similarly large

reductions through retrofitted old 1960s and

1970s apartment towers

• Single-family houses will be harder and more

expensive, but are doable

• But what will we do with all the glass

condominiums and office towers being built

now?

Page 80: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Table 4.34 Current and projected energy use (kWh/m2/yr) after various

upgrades of a typical pre-1970 high-rise apartment building in Toronto.

DHW=domestic hot water, IRR=internal rate of return, HRV=heat recovery ventilator.

Natural Gas

Measure Heating DHW

Elec-

tricity

Primary

Energy

Cost

($/m2)

Payback

(years)

IRR

(%/yr)

Current building 203 36 71 443

Roof insulation 184 36 70 420 13 11.4 11.3

Cladding upgrade 167 36 69 398 44 18.1 3.4

Window upgrade 122 36 64 336 73 13.5 9.2

Balcony enclosure 122 36 68 345 121 21 4.3

All of the above 47 36 64 252 199 18.6 5.6

Boiler upgrade 118 36 70 347 23 5.5 23

HRV 136 36 68 362 17 7.8 25.8

Water conservation 203 25 70 430 5 3.4 35.1

Parkade lighting 203 36 70 440 0 4.4 28

All of the above 9.4 25 59 185 257 16.9 6.7

Above with 50% less

tenant electricity 24.1 25 29 128

Page 81: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Getting a Factor-of-50 savings in

heating energy requirements • In some cases, especially for 1970s apartment towers, we can

retrofit them to reduce space heating requirements by 90% (a factor of 10 reduction)

• The low distribution temperatures required for heating would permit premium-quality ground-source heat pumps to operate with a seasonal COP of ~ 4 (equivalent to 400% efficiency)

• If these replace boilers at 80% efficiency, the improvement is a factor of 5

• Thus, the overall reduction in on-site heating energy requirement is a factor of 50!

• The rate of heat loss in such buildings would be so slow (thermal time constants of 5-7 days) that the heat pump could be run when the wind is blowing and turned off when it isn’t – thereby serving as a dispatchable electricity load that would permit larger use of intermittent renewable energy sources than otherwise

Page 82: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Some Final Thoughts on the Role of

Buildings in Renewable Energy

• The rate of heat loss in buildings that meet the Passive House standard is so slow (thermal time constants of 5-7 days) that heat pumps used for heating and powered by wind electricity could be run when the wind is blowing and turned off when it isn’t – thereby serving as a dispatchable electricity load that would permit larger use of intermittent renewable energy sources than otherwise.

• By building several widely-dispersed large wind farms in the regions of the best winds (which tend to be 500-2000 km from major demand centres), and relying on hydro-electric power as additional energy and especially using the reservoirs for energy storage, as well as flexible heat pumps for heating and cooling, and with a strong emphasis on efficient use of electricity, it is conceivable that renewable energy could completely displace fossil fuel and nuclear-generate electricity in Canada over the course of the next 30 years or so.

Page 83: Passive Building Design and Integration with Intermittent Renewable ... · Integration with Intermittent Renewable Energy Sources L.D. Danny Harvey Department of Geography University

Further reading (books published by Earthscan):

2006 March 2010 April 2010