PCS compact soft startersSoft starting solutions for pumps, conveyors, compressors and fans, while providing integrated motor protection.
Sales 1300 NHP NHP nhp.com.auNHP Electrical Engineering Products Pty Ltd
MOTOR CONTROL AND DRIVES
Now available in a 24 V AC/DC control
variant for easy maintenance and
added safety
PCS Soft Starters—The Compact ChoiceThe PCS provides intelligence and consistent performance in a compact design for controlling your motor. PCS soft starters are suitable for motor starting applications up to 45 kW (3 wire) and 75 kW (6 wire) at 400/415 VAC. It features microprocessor-controlled electronic overload with adjustable trip class, motor and system diagnostics, configurable auxiliary contacts, and multiple start and stop modes. All of these combined features provide a highly accurate, reliable, and efficient soft starter with one of the smallest footprints in the industry.
The PCS AdvantageCompact size with integral bypass
From a slim 45 mm in width, the PCS integrates a bypass to minimise heat generation during run time. The bypass automatically closes when the motor reaches its nominal speed, resulting in a cooler-running component and reduction in enclosure size.
True three phase control
The PCS controls all t hree motor phases for smoother starting and minimal thermal stress on the motor.
3 wire / 6 wire motor connectionWith 3 wire and 6 wire motor connection compatibility as standard, the PCS offers you flexibility. When configured for 6 wire mode the PCS is able to control larger motors without any cost penalty to the user.
Choice of starting & stopping modes PCS soft starters provide the user with a selection of starting and stopping modes as standard. The ability to select and tailor the starting mode ensures the full benefits of soft starting can be achieved in any industrial motor starting application.
Side-by-side stacking at 40 ºC 1)The PCS can be stacked side-by-side thereby saving further panel space and reducing enclosure size.
24 V AC/DC control variantThe standard PCS has a wide control supply range of 100-240 V AC 50/60 Hz for ease of installation. In addition, a 24 V AC/DC control variant is available, maximising your control options.
2
Notes: 1) The PCS can be stacked side-by-side with no space between units. However, frame size one models
(1…37 A) require the optional span-on fan attachment (retains same compact footprint). Frame size two models (43...85 A) include fan as standard.
3
Easy to install, easy to operate
Configurable Auxiliary Contacts
As standard, the PCS provides a configurable (normal or up-to-speed) normally open (N/O) auxiliary contact for motor run status indication. The PCS has a line of side-mount configurable (normal or up-to-speed) auxiliary contacts, allowing you more flexibility.
Potentiometer
A clearly labeled potentiometer is used to adjust motor full load current setting. The lowest minimum Full Load Current (FLC) setting is one third of the soft starters’ current rating. The motor connected must have an FLC within this range. E.g: PCS-009-480 V has an overload range of 3 A to 9 A.
LED status indicationClear indication of all motor and system fault conditions via a ‘flash coded’ LED.
Marking tag holderUsed with marking tags to provide quick and accurate starter identification.
DIP switch set-upQuick, accurate and repeatable settings are assured through a simple to use DIP switch selection panel.
Integral motor overload/fault contactA normally open (N/O) fault contact for indication of motor overload/fault is included on the PCS.
Test / reset buttonThis dual purpose button allows testing of the trip function without motor current flow and fault resetting under normal operating conditions. Optional remote or standard local reset for your convenience.
DIN-rail mounting & screw fixing
Complete with DIN-rail mounting and screw fixing, the PCS is easy to install.
Seamless integration with Sprecher+Schuh switchgear
The PCS fully integrates with Sprecher+Schuh switchgear, forming complete soft starter solutions.
4
PCS modes of operationTimed Voltage Ramp
The timed voltage ramp soft start mode offered by the PCS is for the most general application. User adjustments for initial torque and start ramp time allow the PCS to be configured for a variety of starting conditions. Typical applications include pumps, fans, conveyors and compressors.
The initial torque can be adjustable to 15 %, 25 %, 35 % or 65 % of locked rotor torque. The start ramp time can be adjusted to 2, 5, 10, 15, 20, 25 or 30 seconds.
Current Limit
The current limit start mode is used when it is necessary to limit the maximum starting current in order to reduce electrical stress on the motor and supply. The current limit setting can be adjusted to provide 150 %, 250 %, 350 % or 450 % of full load amps during start. The start time is also user adjustable to 2, 5, 10, 15, 20, 25 or 30 seconds.
Note: If the motor is not up to speed after the selected time elapses, the PCS will transition to full voltage.
Kickstart
The Kickstart function is intended for use on machines that present a high frictional starting characteristic. It provides a current pulse of 450 % FLC over a user adjustable period of 0 to 1.5 seconds, allowing the motor to develop the additional starting torque required to get the load moving.
Soft Stop
The soft stop function can be used to extend the stopping time of the motor and load. When enabled the ramp downtime can be set to either once, twice or three times the start ramp time setting.
The motor will stop when the output voltage from the PCS reaches the point where the load torque is greater than the motor torque.
5
Protection featuresElectronic motor overload protection with user selectable trip class
The PCS soft starter provides electronic motor overload protection with adjustable trip class and automatic or manual reset selectivity as standard. Selecting a trip class that closely resembles the driven motor’s thermal withstand capabilities, minimises nuisance tripping and maximizes machine up-time and plant productivity.
The motor full load current is user adjusted via a blue potentiometer located on the front panel. Overload trip class (either OFF, 10, 15 or 20) and automatic or manual reset operation are DIP switch selectable.
Phase imbalance protection
The phase imbalance on a PCS is a measure of the difference in current between the highest and lowest phases. If the percentage of difference is 65 % or greater, the PCS will fault on a phase imbalance.
Shorted SCR
Prior to every start, the PCS checks the integrity of its power assembly (SCRs). If the PCS detects a shorted SCR, the start will be aborted.
Flash coded LED indication
When a fault is detected the PCS will trip and illuminate a flash coded fault LED to protect the motor and assist in the troubleshooting process.
Starter over-temperature protection
The PCS monitors the temperature of its power circuits (SCRs) by means of internal thermistors.
Phase sequence protection
The PCS provides a user selectable (ON or OFF) phase sequence protection function as standard. When selected, the PCS will monitor the incoming phases before application of power to the motor.
Phase loss protection
The PCS provides phase loss protection to both the line and load sides as standard to ensure the motor will not attempt to start when there is a power phase missing. This protects the motor from burnout resulting from single phase starting conditions.
Open circuit output (open load) protection
The PCS monitors the motor circuit to ensure the motor is connected before it commences its ramp. This feature is aimed at those installations which may have a motor isolator fitted between the starter and the motor, thus preventing a start when the isolator is in the ‘open’ position.
LED Description (Number of Flashes)
Solid RUN/ON x 1 Overload x 2 Starter over-temperature x 3 Phase reversal x 4 Phase loss/open load x 5 Phase imbalance x 6 Shorted SCR x 7 Test
6
Typical PCS applications
FANS
COMPRESSORS
CHECK VALVE
DISCHARGE
SUCTION
Note:
The above applications are to be used as an indicative guide only. Consult NHP for further information.
Additional PCS applications: • Bottlewashers
• Debarkers
• Dustcollectors
• Edgers
• Grinders
• Hydraulicpowerpacks
• Planers
• Presses
• Circularsaws
• Slicers
Pumps Conveyors
Fans Filler lines
CrushersCompressors
7
Approx. kW @ 415 V AC
Setting range Amps
100-240 V AC/DC Control Cat. No.
24 V AC/DC Control Cat. No.
AC 53b: INTERNAL BYPASS CONTACTOR
0.55...1.1 1…3 PCS-003-480V PCS-003-480V-024
1.1...4 3…9 PCS-009-480V PCS-009-480V-024
2.2...7.5 5.3…16 PCS-016-480V PCS-016-480V-024
3...9 6.3…19 PCS-019-480V PCS-019-480V-024
4...11 8.3…25 PCS-025-480V PCS-025-480V-024
5.5...15 10…30 PCS-030-480V PCS-030-480V-024
7.5...18.5 12.3…37 PCS-037-480V PCS-037-480V-024
7.5...22 14.3…43 PCS-043-480V PCS-043-480V-024
11...30 20…60 PCS-060-480V PCS-060-480V-024
15...45 28.3…85 PCS-085-480V PCS-085-480V-024
3 wire installation
6 wire installation
Fully enclosed solutions- see page 11
PCS Model Selection The PCS features 3 wire and 6 wire motor connection compatibility as standard, offering you flexibility.
Notes: 1) As standard, the PCS is capable of 3 wire and 6 wire motor connection. When using the PCS in 6 wire mode, the
overload current must be set to 58 % of the motor FLC. E.g., a 50 amp motor in 6 wire would use a PCS-030-480 V
and the overload current setting would be set to 29 Amps.
Approx. kW @ 415 V AC
Setting range Amps
100-240 V AC/DC Control Cat. No.
24 V AC/DC Control Cat. No.
AC 53b: INTERNAL BYPASS CONTACTOR
0.55...2.2 1.7…5.1 PCS-003-480V PCS-003-480V-024
2.2...7.5 5.1…16 PCS-009-480V PCS-009-480V-024
4...11 9.1…27.6 PCS-016-480V PCS-016-480V-024
4...15 10.9…32.8 PCS-019-480V PCS-019-480V-024
5.5...22 14.3…43 PCS-025-480V PCS-025-480V-024
7.5...22 17.3…52 PCS-030-480V PCS-030-480V-024
7.5...30 21…64 PCS-037-480V PCS-037-480V-024
11...37 25…74 PCS-043-480V PCS-043-480V-024
15...55 34.6…104 PCS-060-480V PCS-060-480V-024
22...75 50…147 PCS-085-480V PCS-085-480V-024
8
AccessoriesSide-mounted auxiliary contacts 1) Cat. No.
1x N/O contact PCS-PA-10
1x N/C contact PCS-PA-01
2x N/O contacts PCS-PA-20
1x N/O and 1x N/C contact PCS-PA11
Contactor connection modules Cat. No.
Connects PCS-003…019 to CA7-9…23 PCS-23-CI23
Connects PCS-030…037 to CA7-30…37 PCS-23-CI37
Remote reset magnets Cat. No.
24 V AC coil CMR7-24VA
240 V AC coil CMR7-230VA
24 V DC coil CMR7-24VDC
Cooling fans Cat. No.
Frame 1: PCS-003…37 PCV-064
Frame 2: PCS-045…85 PCV-147 2)
Marking tags Cat. No.
Marking tag covers (x 100) CA7-FMP
Transparent cover (x 100) CA7-FMC
Marking tag stickers (x 100) CA7-FMS
Notes: 1) As standard, the PCS includes a configurable (normal or up-to-speed) normally open (N/O) auxiliary contact. 2) Frame size 2 cooling fans come complete as standard.
9
SpecificationsCategory PCS - 3 wire operation PCS - 6 wire operation
Motor rating at 415 V AC 0.55 to 45 kW 0.55 to 75 kW
Current rating 1 to 85 Amps 1.7 to 147 Amps 1)
Motor connection 3 wire (line) 6 wire (inside delta)
Utilisation category to AS 3947-4-2 AC 53b (internal bypass contactor)
No. of controlled phases 3
No. of starts per hour Refer to curves (page 10)
Supply voltage range (3 phase) PCS-xxx-480-xxx V 200 to 480 V AC
Control voltage range (+10 % / -15 %) PCS-xxx-xxx V 100 to 240 V AC PCS-xxx-xxx V-024 24 V AC/DC
Supply frequency range 50/60 Hz, 3 phase supply and control
Soft start modes Timed voltage rampCurrent limitKickstart
Stop modes Soft stopCoast to stop
Selectable start times 2, 5, 10, 15, 20, 25, or 30 s
Selectable initial torque 15 %, 25 %, 35 % and 65 % of locked rotor torque
Selectable current limit 150 %, 250 %, 350 % and 450 % of full load current
Selectable kick start - 450 % FLC OFF, 0.5, 1.0, or 1.5 s
Selectable soft stop OFF, 100 %, 200 %, or 300 % of the start time setting when configured
Protective functions Electronic motor overload with adjustable trip class (OFF, 10, 15 or 20)Starter over-temperaturePhase sequence/reversalPhase lossPhase imbalanceShorted SCROpen load
Enclosure rating IP 2X
Ambient temperature 50º C standard
Altitude 2000 m
Relative humidity 5...95 % (non condensing)
Pollution degree 2
Certification
Notes: 1) As standard, the PCS is capable of 3 wire and 6 wire motor connection. When using the PCS in 6 wire mode, the overload current must be set to 58% of the motor FLC. For complete PCS specifications consult NHP.
10
Overload relay trip curves
Starts per hour curves
Dimensions (mm) and weightsA
B
C
F
G
D
E
Cat. No. A B C D E F GMounting hole size
Weight (kg)
PCS-003...037 45 140 100 35 132 46.4 2 4.6 0.86
PCS-043...085 72 206 130 55 198 102 2 5.3 2.25
(3…37 A) (3…37 A)
Trip Class 10 Trip Class 15 Trip Class 20
PCS 3 Starts per hour (3...37 A) 40 º C, 100% Duty Cycle, 10 s, 350 % without fan
PCS 3 Starts per hour (3...37 A) 40 º C, 100% Duty Cycle, 10 s, 350 % with fan
PCS 3 Starts per hour (43...85 A) 40 º C, 100% Duty Cycle, 20 s, 350 % with standard fan
PCS-003...009
PCS-016...019
PCS025...037
Star
ts/H
our
Star
ts/H
our
Star
ts/H
our
Current (Amps)
PCS-003...009
PCS-016...019
PCS025...037
PCS-003...009
PCS-016...019
PCS025...037
Current (Amps) Current (Amps)
11
Enclosed PCS solutions for 3 Wire applicationsThe PCS soft starters are also available in enclosed format and are provided as standard assemblies or manufactured to specifications. The enclosed PCS solutions listed below are suitable for 3 wire applications. Enclosed PCS solutions are also available for 6 wire applications, consult NHP for further information.
Insulated enclosed 0.55 kW to 45 kW•Insulatedpolycarbonateenclosure,IP66protection
Dimensions (mm)
Approx. kW @ 415 V AC
PCS Sof Starter
Line contactor
Setting rangeAmps Height Width Depth Cat. No.
0.55...1.1 PCS-003-480V CA7-9 1…3
280 280 180
SSPC7-1.1-240VAC
1.1...4 PCS-009-480V CA7-9 3…9 SSPC7-4-240VAC
2.2...7.5 PCS-016-480V CA7-16 5.3…16 SSPC7-7.5-240VAC
3...9 PCS-019-480V CA7-23 6.3…19 SSPC7-9-240VAC
4...11 PCS-025-480V CA7-30 8.3…25 SSPC7-11-240VAC
5.5...15 PCS-030-480V CA7-30 10…30 SSPC7-15-240VAC
7.5...18.5 PCS-037-480V CA7-37 12.3…37 280 380 180 SSPC7-18.5-240VAC
7.5...22 PCS-043-480V CA7-43 14.3…43
600 400 210
SSPC7-22-240VAC
11...30 PCS-060-480V CA7-60 20…60 SSPC7-30-240VAC
15...45 PCS-085-480V CA7-85 28.3…85 SSPC7-45-240VAC
Steel enclosed 0.55 kW to 45 kW•Qualitysteelenclosures,IP66protection
Notes: 1) Enclosed PCS soft starters are manufactured to order. Consult NHP for manufacturing lead time. Standard control voltage 240 VAC. 415 VAC available on request. Standard assembly includes line contactor, PCS soft starter with integral bypass contactor and electrical motor protection with adjustable trip class (off, 10, 15, 20), control circuit breaker as well as start, stop and reset pushbuttons.
Dimensions (mm)
Approx. kW @ 415 V AC
PCS Sof Starter
Line contactor
Setting rangeAmps Height Width Depth Cat. No.
0.55...1.1 PCS-003-480V CA7-9 1…3
300 300 210
MSSPC7-1.1-240VAC
1.1...4 PCS-009-480V CA7-9 3…9 MSSPC7-4-240VAC
2.2...7.5 PCS-016-480V CA7-16 5.3…16 MSSPC7-7.5-240VAC
3...9 PCS-019-480V CA7-23 6.3…19 MSSPC7-9-240VAC
4...11 PCS-025-480V CA7-30 8.3…25 MSSPC7-11-240VAC
5.5...15 PCS-030-480V CA7-30 10…30 MSSPC7-15-240VAC
7.5...18.5 PCS-037-480V CA7-37 12.3…37 400 300 210 MSSPC7-18.5-240VAC
7.5...22 PCS-043-480V CA7-43 14.3…43
500 400 210
MSSPC7-22-240VAC
11...30 PCS-060-480V CA7-60 20…60 MSSPC7-30-240VAC
15...45 PCS-085-480V CA7-85 28.3…85 MSSPC7-45-240VAC
NHP Electrical Engineering Products Pty LtdA.B.N.84004304812
NPCSCSSC 08/12 © Copyright NHP 2012
AUSTRALIAnhp.com.au
SALES 1300 NHP NHP
FAX 1300 NHP FAX
VICToRIAMelbourne 43-67 River Street Richmond VIC 3121 Tel +61 3 9429 2999
Laverton 104-106 William Angliss Drive Laverton North VIC 3026 Tel +61 3 9368 2901
Albury / Wodonga 847 Ramsden Drive Albury NSW 2640 Tel +61 2 6049 0600 Fax +61 3 6025 0592
Dandenong 40-42 Cyber Loop Dandenong South VIC 3175 Tel +61 3 8773 6400 Fax +61 3 8768 8522
TASMANIAHobart Unit 2 65 Albert Street Moonah TAS 7009 Tel +61 3 6228 9575 Fax +61 3 6228 9757
Launceston Unit 3 13-17 Merino Street Kings Meadows TAS 7249 Tel +61 3 6345 2600 Fax +61 3 6344 6324
NEW SoUTH WALESSydney 30-34 Day Street North Silverwater NSW 2128 Tel +61 2 9748 3444
Newcastle 575 Maitland Road Mayfield West NSW 2304 Tel +61 2 4960 2220 Fax +61 2 4960 2203
Wollongong 34 Industrial Road Unanderra NSW 2526 Tel +61 2 4272 5763 Fax +61 2 4272 5957
ACTCanberra Unit1 187GladstoneStreet Fyshwick ACT 2609 Tel +61 2 6280 9888 Fax +61 2 6280 9588
WESTERN AUSTRALIAPerth 38BelmontAve Rivervale WA 6103 Tel +61 8 9277 1777
NoRTHERN TERRIToRyDarwin 3 Steele Street Winnellie NT 0820 Tel +61 8 8947 2666 Fax +61 8 8947 2049
QUEENSLANDBrisbane 16 Riverview Place Murarrie QLD 4172 Tel +61 7 3909 4999
Townsville 5 Leyland Street Garbutt QLD 4814 Tel +61 7 4779 0700 Fax +61 7 4775 1457
Rockhampton 1 Lawson Street Parkhurst QLD 4702 Tel +61 7 4927 2277 Fax +61 7 4922 2947
Toowoomba Cnr Carroll Street and Struan Court QLD 4350 Tel +61 7 4634 4799 Fax +61 7 4633 1796
Cairns Unit 2 1BrampClose Portsmith QLD 4870 Tel +61 7 4035 6888 Fax +61 7 4035 6999
SoUTH AUSTRALIAAdelaide 36-38 Croydon Road Keswick SA 5035 Tel +61 8 8297 9055
NEW ZEALANDnhp-nz.com
SALES 0800 NHP NHP
FAX 0800 FAX NHP
PO Box 62-009 Sylvia Park Auckland 1644 New Zealand
Auckland 118a Carbine Road Mt Wellington 1060 Tel +64 9 276 1967
Hamilton 78 Rostrevor Street Hamilton 3204 Tel +64 7 849 0257 Fax +64 800 329 647
Napier 126 Taradale Road Onekawa 4110 Tel +64 6 843 6928 Fax +64 800 329 647
New Plymouth 2 Dean Place Waiwhakaiho 4312 Tel 0800 NHP NHP Fax +64 800 329 647
Wellington 52 Victoria Street Lower Hutt 5010 Tel +64 4 570 0634 Fax +64 800 329 647
Christchurch 27 Iversen TerraceWaltham 8011 Tel +64 3 377 4407 Fax +64 3 377 4405
Dunedin 30 Fox StreetSouth Dunedin 9012 Tel 0800 NHP NHP Fax +64 800 329 647